Reference Manual

Section 6: Troubleshooting

00809-0100-4100, Rev AA

March 2013

Device Status

Description

LO Alarm

The primary variable has surpassed


the user defined limit.

LO LO Alarm

Button Stuck

Simulation Active

86

The primary variable has surpassed


the user defined limit.

A buttons on the Electronics Board


is detected as stuck in the active
position.

The device is in simulation mode


and may not be reporting actual
information.

Recommended Action
1.

Verify that the process variable is within user


specified limits

2.

Reconfirm the user defined alarm limit

3.

If not needed, disable this alert

1.

Verify that the process variable is within user


specified limits

2.

Reconfirm the user defined alarm limit

3.

If not needed, disable this alert

1.

Check the buttons for obstructions

2.

Reset the device

3.

If the condition persists, replace the electronics

1.

Verify that simulation is no longer required

2.

Disable Simulation mode in Service Tools

3.

Reset the device