You are on page 1of 3

GE Power Management

BC-bfhtmcc.aut (MAIN)

Model:F650***F1G1***6
Version:5.41
Part:21.12.9.0
Project Name: buscopler
Path:
D:\EXECUTION\TOTAL BACKUP OF RELAY CONFIGURATION& SETTING\RSP_F650Backup_03032015\BLAST

650
PLC
LOGIC
1

EnerVista 650 Setup

GE Power Management

BC-bfhtmcc.aut (MAIN)

EnerVista 650 Setup

IC-HEALTHY_IC-2 UV OPTD

11
CONT IP_F_CC14(CC14)
85
CONT IP_G_CC3(CC3)
4
70

ACO ENABLED
IC-1 CB CLOSE
IC-1 CB SERVICE

BPT-2 UV OPTD

CONT IP_G_CC7(CC7)
76
PHASE UV1 OP
10

BPT-1 HEALTHY
LPT-2 UV OPTD

CONT IP_F_CC16(CC16)
71
CONT IP_F_CC10(CC10)

IC-2 86 NOT OPTD

AND8

OutAND1

InAND2

CONT IP_F_CC5(CC5)
84
CONT IP_F_CC9(CC9)
83
86

IC-2 CB SERVICE

13
VIRTUAL OUTPUT 003

0
InAND1

InAND3
InAND4

77
NOT

InAND5
InAND6
InAND7
InAND8

72
NOT

IC-2 HEALTHY_IC-1 UV OPTD


22
CONT IP_F_CC14(CC14)
89
CONT IP_G_CC5(CC5)
87
CONT IP_F_CC5(CC5)
88
CONT IP_F_CC9(CC9)
61
PHASE UV1 OP
90
89
CONT IP_G_CC7(CC7)

ACO ENABLED
IC-2 CB CLOSE
IC-1 CB SERVICE
IC-2 CB SERVICE
BPT-1 UV OPTD
BPT-2 HEALTHY

24
CONT IP_F_CC15(CC15)

LPT-1 UV OPTD

74
CONT IP_F_CC6(CC6)

IC-1 86 NOT OPTD

25
VIRTUAL OUTPUT 004

14
AND8

InAND1

OutAND1

InAND2
InAND3
InAND4

90
NOT

InAND5
InAND6
InAND7

73
NOT

InAND8

BC CB READY FOR CLOSE


28
CONT IP_F_CC2(CC2)
30
CONT IP_F_CC7(CC7)
31
CONT IP_F_CC13(CC13)

BC CB SERVICE
BC CB OPEN
BC 86 NOT OPTD

BC TCH HEALTHY

34
CONT IP_F_CC8(CC8)

BC CU HEALTHY

35
CONT IP_F_CC4(CC4)

BC CB CLOSE

40
CONT IP_F_CC1(CC1)

BC CB SERVICE

41
CONT IP_F_CC2(CC2)

38

33
NOT

AND5

InAND1

OutAND1

39
VIRTUAL OUTPUT 005

InAND2
InAND3
InAND4
InAND5

44
AND

45
VIRTUAL OUTPUT 000

BC AUTO CHANGE OVER CLOSE COMMAND

IC-1 CB OPEN

76
91
CONT IP_G_CC4(CC4)
47
VIRTUAL OUTPUT 004
48
VIRTUAL OUTPUT 005

IC-2 CB OPEN

92
CONT IP_G_CC6(CC6)
50
VIRTUAL OUTPUT 003

54
VIRTUAL OUTPUT 001

51
AND3

InAND1

OutAND1

InAND2

79
VIRTUAL OUTPUT 001

53
OR

78

InAND3

80
52
InAND1

AND3

T_Pickup

81

OutAND1

InAND2

49
VIRTUAL OUTPUT 005

T_Input

2000

InAND3

T_Dropout

Timer(Pkp-Dpt)

T_Output

82
VIRTUAL OUTPUT 002

GE Power Management

BC-bfhtmcc.aut (MAIN)
BC,IC-1,IC-2 TRIP COMMAND

56
PHASE UV1 OP
93
CONT IP_G_CC7(CC7)
94
CONT IP_G_CC4(CC4)
95
CONT IP_G_CC6(CC6)
83
CONT IP_F_CC1(CC1)

62
VIRTUAL OUTPUT 004
IC-1 CB CLOSE

AND5

97
CONT IP_G_CC5(CC5)

OutAND1

58
VIRTUAL OUTPUT 010

InAND2
InAND3
InAND4
InAND5

64
AND

96
CONT IP_G_CC3(CC3)
63
VIRTUAL OUTPUT 003

IC-2 CB CLOSE

57
InAND1

65
AND

66
VIRTUAL OUTPUT 006

67
VIRTUAL OUTPUT 007

EnerVista 650 Setup