You are on page 1of 1

LOCATION MAP

ELP-1
m

LP-1

e
d

j
a

c
k
m

m
g
f

f
g
h

f
h

g
h

LIGHTING LAYOUT
SCALE

GENERAL NOTES

1:50

ALL WORKS SHALL COMPLY WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, WITH THE RULES
AND REGULATIONS OF THE NATIONAL AND LOCAL AUTHORITIES CONCERNED WITH ENFORCEMENT OF THE ELECTRICAL LAWS AND
ORDINANCES AND WITH THE RULES AND REGULATION OF THE UTILITY COMPANIES CONCERNED.

LP-7

1. SERVICE SHALL BE 230 VOLTS, 1-PHASE, 3-WIRES.

LP-6
S

2. SERVICE ENTRANCE SHALL BE IN RIGID STEEL CONDUIT (RSC) "MATSUSHITA" OR APPROVED EQUAL.
3. BRANCH CIRCUIT WIRING SHALL BE DONE IN SCHEDULE RIGID STEEL CONDUIT WHERE TYPE THHN WIRES AREA
USED. ALL BRANCH CIRCUIT SHALL BE PROVIDED WITH GREEN INSULATED GROUND WIRES.

LP
MTS
ELP

THAN 3.5mm INSULATED FOR 600 VOLTS.


5. DUPLEX RECEPTACLE OUTLETS SHALL BE RATED 10A, 250 VOLTS, GROUNDING TYPE "NATIONAL". SPECIAL PURPOSE OUTLETS
SHALL BE OF TYPE AND RATING SUITABLE FOR THE EQUIPMENT SERVED.

LP-3
ABOVE
CEILING

LP-5

6. LIGHT CONTROL SWITCHES SHALL BE RATED 15A, 300 VOLTS, "PANASONIC"


7. OUTLET BOXES SHALL BE GAUGE#1.55mm(MINIMUM) PRESSED-STEEL, GALVANIZED, 55mm DEEP.

LP-4

8. ALL MATERIALS TO BE USED SHALL BE NEW AND OF APPROVED TYPE FOR THE LOCALTION AND PURPOSED

9. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:

b. WALL RECEPTACLE, TEL. AND TV ANTENNA OUTLETS.

=
=

1.37m ABOVE FLOOR AT CENTER


0.30 ABOVE FLOOR AT CENTER

c. RANGE OUTLET

0.60 ABOVE FLOOR AT CENTER

d. SPECIAL PURPOSE OUTLET

=
=

AS REQUIRED BY EQUIPMENTER SERVED, VERIFY

a. LIGHTING CONTROL SWITCHES & PUSH BUTTON

e. PANELBOARDS AND CABINET

POWER LAYOUT

1.37M ABOVE FLOOR AT CENTER UNLESS OTHERWISE


REQUIRED BY FIELD CONDITIONS

SCALE

1:50

ALL MOUNTING HEIGHTS SHALL BE SUBJECT TO PRIOR APPROVAL BY THE ARCHITECT.

LEGEND
ELECTRICAL PANELBOARD
11 WATTS PINLIGHT

ONE - SINGLE POLE SWITCH IN A GANG

20-WATT T5 ELECTRONIC LAMP

TWO - SINGLE POLE SWITCH IN A GANG

25 WATTS PILOT LIGHT

THREE - SINGLE POLE SWITCH IN A GANG

11 WATTS EMERGENCY PINLIGHT

CIRCUIT HOMERUN TO PANEL

AT ELECTRICAL ROOM\
NORMAL POWER (VERIFY)
EXACT LOCATION)

EMERGENCY POWER
AT ELECTRICAL

20-WATT T5 EMERGENCY ELECTRONIC LAMP

505

2.19

1000

4.35

1000

4.35

1000

4.35

1000

4.35

1000

4.35

1000

4.35

1000

4.35

DO

IT = 2.19AMPERES
USE: 2-5.5mm 2THHN, 1-2.0mm 2
MAIN: 20AT, 50AF,2PCB,240V,10KAIC, B.O.

DUPLEX CONVENIENCE OUTLET


CT

COUNTERTOP OUTLET

LP
(50/44.00A)

ELP

LOAD COMPUTATION
SCALE

MTS

N.T.S.

MTS; 2-20AT, 50AF,2PCB,240V,


10 KAIC, B.O. WITH
MECHANICAL INTERLOCK IN
NEMA-I ENCLOSURE
IT = 47.36 AMPERES
USE: 2-8.0mm 2THHN, 1-5.5mm 2
MAIN: 60AT, 60AF,2PCB,240V,10KAIC, B.O.

47.36 AMPS)

SINGLE LINE DIAGRAM


SCALE

REPUBLIC ACT 545

23 Flr Unit 03 World Trade Exchange Building


215 Juan Luna Street Binondo, Manila

CONSULTANT
Mobile No. 0917-8282013
Tel. No. 242-0933

PRC NO.
PTR NO.
DATE ISSUED

08071979

TIN NO.

8744552 PLACE
06-09-10

PROJECT

REVISIONS:

DESIGNED

LOCATION

ARCHITECT
PRESIDENTIAL DECREE NO. 49

ARCHITECT ENGINEERING

Section 25 (4)

SHEET CONTENTS:

DRAWN

ANDREW CHENG

CA ARCHITECT

N.T.S.

187-299-017
MANILA

J.J.DUFF

UNIT 222 SECOND FLR.SM CITY GEN. SAN., GENERAL SANTOS, PHILIPPINES

OWNER

CHECKED

APPROVAL
DATE

VICINITY MAP
LOCATION MAP
GENERAL NOTES
LEGEND
SINGLE LINE DIAGRAM
LOAD COMPUTATION
ELECTRICAL LAYOUTS

SHEET NO.

E
1