PAGE 1
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
SR489 SETUP
PREFERENCES
Default Message Cycle Time
Default Message Timeout
Parameter Averages Calc. Period
Temperature Display Units
Waveform Trigger Position
Waveform Memory Buffer
2.0 s
300 s
15 min
Celsius
25 %
8 x 28 Cycles
MESSAGE SCRATCHPAD
First Scratchpad Message
Second Scratchpad Message
Third Scratchpad Message
Fourth Scratchpad Message
Fifth Scratchpad Message
COMMUNICATION
Ethernet Subnet Mask
Slave Address
Computer RS485 Baud Rate
Auxiliary RS485 Baud Rate
255.255.252. 0
254
9600 baud
9600 baud
SYSTEM SETUP
CURRENT SENSING
Phase CT Primary
Ground CT
Ground CT Ratio
3200 A
5 A Secondary
3200 :5
VOLTAGE SENSING
VT Connection Type
Transformer Ratio
Neutral Voltage Connection
Wye
4.00 :1
No
GEN. PARAMETERS
Generator Rated MVA
Generator Rated Power Factor
Generator Voltage Phase-Phase
Generator Nominal Frequency
Generator Phase Sequence
1.700 MVA
0.80
480 V
60 Hz
ABC
SERIAL START-STOP
Serial Start/Stop Initiation
Off
DIGITAL INPUTS
BREAKER STATUS
Breaker Status
Breaker Auxiliary a
GENERAL PURPOSE
GENERAL A
Assign Digital Input (A)
Input Name (A)
Asserted Digital Input State (A)
Block Input From Online (A)
General Input A Control
Pulsed Control Relay Dwell Time (A)
Control Relay A
General Input A Control Events
General Input A Alarm
Alarm Relays A
General Input A Alarm Delay
General Input A Alarm Events
General Input A Trip
Trip Relays A
General Input A Trip Delay
Input 1
52CS Trip
Closed
0s
Off
0.0 s
No Relays
Off
Latched
Relays 2-3-4
0.1 s
On
Latched
Relays 1-2-3-4
0.1 s
DUAL SETPOINTS
Active Setpoint Group(Dual Setpoints)
Edit Setpoint Group(Dual Setpoints)
Group 1
Group 1
OUTPUT RELAYS
1 TRIP
PAGE 2
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
1 TRIP (continued from last page)
R1 Trip
All Resets
2 AUXILIARY
R2 Auxiliary
All Resets
3 AUXILIARY
R3 Auxiliary
All Resets
4 AUXILIARY
R4 Auxiliary
All Resets
5 ALARM
R5 Alarm
All Resets
6 SERVICE
R6 Service
All Resets
MONITORING
TRIP COUNTER
Trip Counter Alarm
Trip Counter Alarm Relays
Trip Counter Alarm Level
Trip Counter Alarm Events
Latched
No Relays
200 Trips
On
BREAKER FAILURE
Breaker Failure Alarm
Breaker Failure Alarm Relays
Breaker Failure Level
Breaker Failure Delay
Breaker Failure Alarm Events
Latched
No Relays
0.05 x CT
200 ms
On
CURRENT DEMAND
Current Demand Period
Current Demand Alarm
Current Demand Alarm Relays
Current Demand Limit
Current Demand Alarm Events
10 min
Unlatched
No Relays
1.25 x FLA
On
MW DEMAND
MW Demand Period
MW Demand Alarm
MW Demand Alarm Relays
MW Demand Limit
MW Demand Alarm Events
10 min
Unlatched
No Relays
1.25 x Rated
On
MVAR DEMAND
Mvar Demand Period
Mvar Demand Alarm
Mvar Demand Alarm Relays
Mvar Demand Limit
Mvar Demand Alarm Events
10 min
Unlatched
No Relays
1.25 x Rated
On
MVA DEMAND
MVA Demand Period
MVA Demand Alarm
MVA Demand Alarm Relays
MVA Demand Alarm Level
MVA Demand Alarm Events
10 min
Unlatched
No Relays
1.25 x Rated
On
PULSE OUTPUT
Positive kWh Pulse Output Relays
Positive kWh Pulse Output Interval
Positive kvarh Pulse Output Relays
Positive kvarh Pulse Output Interval
Negative kvarh Pulse Output Relays
Negative kvarh Pulse Output Interval
Pulse Width
No Relays
10 kwh
No Relays
10 kvarh
No Relays
10 kvarh
200 ms
Off
PAGE 3
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
VT FUSE FAILURE
VT Fuse Failure Alarm
VT Fuse Failure Alarm Relays
VT Fuse Failure Alarm Events
Latched
No Relays
On
0h
Off
ANALOG OUTPUTS
Analog Output 1
Analog Output 2
Analog Output 3
Analog Output 4
Average Output Current Minimum
Average Output Current Maximum
Vavg Minimum
Vavg Maximum
Power Factor Minimum
Power Factor Maximum
Real Power Minimum
Real Power Maximum
PROTECTION
CURRENT ELEMENTS[SETPOINT GROUP 1]
OVERCURRENT ALARM[SETPOINT GROUP 1]
Overcurrent Alarm
Overcurrent Alarm Relays
Overcurrent Alarm Level
Overcurrent Alarm Delay
Overcurrent Alarm Events
Unlatched
No Relays
1.05 x FLA
10.0 s
Off
Off
Off
Latched
Relays 1-2-3-4
Yes
0.67 X CT
ANSI Extremely Inv.
2.00
Instantaneous
10 %
Unlatched
No Relays
10 % FLA
5.0 s
On
Latched
Relay 1
25 % FLA
40
1000 s
227.0 s
Unlatched
No Relays
0.10 x CT
9 Cycles
On
Latched
Relays 1-2-3-4
1.00 x CT
PAGE 4
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
GROUND O/C[SETPOINT GROUP 1] (continued from last page)
Ground O/C Curve Shape
Ground O/C Curve Multiplier
Ground O/C Curve Reset
Definite Time
0.05
Instantaneous
Latched
Relays 1-2-3-4
0.10 x CT
10 %
20 %
30 Cycles
0
Off
Off
Latched
Relay 1
4.50 x CT
0.50 s
Unlatched
No Relays
0.90 x Rated
3.0 s
On
Latched
Relays 1-2-3-4
0.80 x Rated
1.0 s
1.4 s
Curve
OVERVOLTAGE[SETPOINT GROUP 1]
Overvoltage Alarm
Overvoltage Alarm Relay
Overvoltage Alarm Pickup
Overvoltage Alarm Delay
Overvoltage Alarm Events
Overvoltage Trip
Overvoltage Trip Relay
Overvoltage Trip Pickup
Overvoltage Trip Delay
Overvoltage Curve Reset Rate
Overvoltage Curve Element
Unlatched
No Relays
1.15 x Rated
3.0 s
On
Latched
Relays 1-2-3-4
1.20 x Rated
1.0 s
1.4 s
Curve
VOLTS/HERTZ[SETPOINT GROUP 1]
Volts/Hertz Alarm
Volts/Hertz Trip
Off
Off
Latched
Relays 1-2-3-4
UNDERFREQUENCY[SETPOINT GROUP 1]
Block Underfrequency from Online
Voltage Level Cutoff
Underfrequency Alarm
Underfrequency Alarm Relay
Underfrequency Alarm Level
Underfrequency Alarm Delay
Underfrequency Alarm Events
Underfrequency Trip
Underfrequency Trip Relay
Underfrequency Trip Level 1
Underfrequency Trip Delay 1
1s
0.50 x Rated
Unlatched
No Relays
59.00 Hz
5.0 s
On
Unlatched
Relay 1
59.50 Hz
60.0 s
PAGE 5
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
UNDERFREQUENCY[SETPOINT GROUP 1] (continued from last page)
Underfrequency Trip Level 2
Underfrequency Trip Delay 2
57.00 Hz
2.0 s
OVERFREQUENCY[SETPOINT GROUP 1]
Block Overfrequency from Online
Voltage Level Cutoff (overfrequency)
Overfrequency Alarm
Overfrequency Alarm Relay
Overfrequency Alarm Level
Overfrequency Alarm Delay
Overfrequency Alarm Events
Overfrequency Trip
Overfrequency Trip Relay
Overfrequency Trip Level 1
Overfrequency Trip Delay1
Overfrequency Trip Level2
Overfrequency Trip Delay2
1s
0.50 x Rated
Unlatched
No Relays
61.00 Hz
5.0 s
On
Unlatched
Relay 1
60.50 Hz
60.0 s
63.00 Hz
2.0 s
Off
Off
Off
Off
Yes
0.70 x Rated
Latched
Relay 1
21.7 Ohm sec
2.5 Ohm sec
0.1 s
Latched
Relay 1
77.4 Ohm sec
2.5 Ohm sec
0.5 s
DISTANCE[SETPOINT GROUP 1]
Fuse Failure Supervision
Zone 1 Trip
Zone 2 Trip
Off
Off
Off
1s
Off
1s
Off
1s
Unlatched
No Relays
0.10 x Rated MW
10.0 s
On
1s
Latched
Relays 1-2-3-4
0.10 x Rated MW
10.0 s
PAGE 6
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
LOW FORWARD POWER ALARM[SETPOINT GROUP 1] (continued from last page)
Block Low Fwd Power From Online
Low Forward Power Alarm
0s
Off
0s
Off
Stator
RTD #1
Off
Off
Stator
RTD #1
Off
Off
Stator
RTD #1
Off
Off
Stator
RTD #1
Off
Off
Stator
RTD #1
Off
Off
Stator
RTD #1
Off
Off
Stator
RTD #1
Off
Off
Bearing
Off
Off
Bearing
Off
Off
Bearing
PAGE 7
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
RTD #10[SETPOINT GROUP 1] (continued from last page)
RTD#10 Name
RTD#10 Alarm
RTD#10 Trip
RTD #11[SETPOINT GROUP 1]
RTD#11 Application
RTD#11 Name
RTD#11 Alarm
RTD#11 Trip
RTD #12[SETPOINT GROUP 1]
RTD#12 Application
RTD#12 Name
RTD#12 Alarm
RTD#12 Trip
Off
Off
Other
Off
Off
Ambient
Off
Off
RTD-ALARMS[SETPOINT GROUP 1]
Open RTD Sensor Alarm
RTD Short/Low Temp Alarm
Off
Off
No
Standard
1
Off
Off
Off
Off
Off
Off
Off
Off
Off
0
Off
Off
Off
Off
Off
OVERVOLTAGE[SETPOINT GROUP 2]
Overvoltage Alarm
Overvoltage Trip
Off
Off
VOLTS/HERTZ[SETPOINT GROUP 2]
PAGE 8
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
VOLTS/HERTZ[SETPOINT GROUP 2] (continued from last page)
Volts/Hertz Alarm
Volts/Hertz Trip
Off
Off
Off
UNDERFREQUENCY[SETPOINT GROUP 2]
Block Underfrequency from Online
Voltage Level Cutoff
Underfrequency Alarm
Underfrequency Trip
1s
0.50 x Rated
Off
Off
OVERFREQUENCY[SETPOINT GROUP 2]
Block Overfrequency from Online
Voltage Level Cutoff (overfrequency)
Overfrequency Alarm
Overfrequency Trip
1s
0.50 x Rated
Off
Off
Off
Off
Off
Off
No
Off
Off
DISTANCE[SETPOINT GROUP 2]
Fuse Failure Supervision
Zone 1 Trip
Zone 2 Trip
Off
Off
Off
1s
Off
1s
Off
1s
Off
1s
Off
0s
Off
0s
Off
Stator
PAGE 9
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
RTD #1[SETPOINT GROUP 2] (continued from last page)
RTD#1 Name
RTD#1 Alarm
RTD#1 Trip
RTD #2[SETPOINT GROUP 2]
RTD#2 Application
RTD#2 Name
RTD#2 Alarm
RTD#2 Trip
RTD #3[SETPOINT GROUP 2]
RTD#3 Application
RTD#3 Name
RTD#3 Alarm
RTD#3 Trip
RTD #4[SETPOINT GROUP 2]
RTD#4 Application
RTD#4 Name
RTD#4 Alarm
RTD#4 Trip
RTD #5[SETPOINT GROUP 2]
RTD#5 Application
RTD#5 Name
RTD#5 Alarm
RTD#5 Trip
RTD #6[SETPOINT GROUP 2]
RTD#6 Application
RTD#6 Name
RTD#6 Alarm
RTD#6 Trip
RTD #7[SETPOINT GROUP 2]
RTD#7 Application
RTD#7 Name
RTD#7 Alarm
RTD#7 Trip
RTD #8[SETPOINT GROUP 2]
RTD#8 Application
RTD#8 Name
RTD#8 Alarm
RTD#8 Trip
RTD #9[SETPOINT GROUP 2]
RTD#9 Application
RTD#9 Name
RTD#9 Alarm
RTD#9 Trip
RTD #10[SETPOINT GROUP 2]
RTD#10 Application
RTD#10 Name
RTD#10 Alarm
RTD#10 Trip
RTD #11[SETPOINT GROUP 2]
RTD#11 Application
RTD#11 Name
RTD#11 Alarm
RTD#11 Trip
RTD #12[SETPOINT GROUP 2]
RTD#12 Application
RTD#12 Name
RTD#12 Alarm
RTD#12 Trip
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Stator
Off
Off
Bearing
Off
Off
Bearing
Off
Off
Bearing
Off
Off
Bearing
Off
Off
Other
Off
Off
Ambient
Off
Off
PAGE 10
AJUSTES.489
C:\USERS\CESAR\DESKTOP\BCP - CHORRILLOS\GEN2 BCP\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3291098
DESCRIPTION: (NONE)
TEXT COLOR
RTD-ALARMS[SETPOINT GROUP 2]
Open RTD Sensor Alarm
RTD Short/Low Temp Alarm
Off
Off
No
Standard
4