Professional Documents
Culture Documents
1.0
0.01216 u I u
tc
50000.00 Amperes
1.00 Sec
608.00 Square mm
A=
I=
tc =
A=
0.01216 u I u
tc
50000.00 Amperes
1.00 Sec
608.00 Square mm
A=
I=
tc =
A=
0.01216 u I u
tc
50000.00 Amperes
1.00 Sec
608.00 Square mm
ABOVE 90 KW
A= 0.01216 u I u t c
I=
50000.00 Amperes
tc =
1.00 Sec
A=
608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate
ABOVE 30 KW UPTO 90 KW
A= 0.01216 u I u t c
I=
3000.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc =
0.20 Sec
A=
16.31 Square mm
Hence the Size chosen 25 x 3 mm is adequate
ABOVE 5 KW UPTO 30 KW
A= 0.01216 u I u t c
I=
2000.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc =
0.20 Sec
A=
10.88 Square mm
Hence the Size selected 8 SWG GI wire is adequate
Upto 5 KW
A= 0.01216 u I u t c
I=
600.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc =
0.20 Sec
A=
3.26 Square mm
Hence the Size selected 8 SWG GI wire is adequate
1.06 SYSTEM NEUTRAL
The maximum system neutral fault current is 50 kA of the 415 system, so that
will be considered for calculations.
A= 0.01216 u I u t c
I=
50000.00 Amperes
tc =
1.00 Sec
A=
608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate