TRANSFORMADORES

FEDERICO
MILANO

DEPARTAMENTO DE INGENIERA ELCTRICA, ELECTRNICA, AUTOMTICA Y COMUNICACIONES


ESCUELA TCNICA SUPERIOR DE INGENIEROS INDUSTRIALES
UNIVERSIDAD DE CASTILLA - LA MANCHA

CAMPUS UNIVERSITARIO S/N


E-13071 CIUDAD REAL
ESPAA

CURSO 2008/09

MQUINAS ELCTRICAS

TRANSFORMADORES

CONTENIDOS
1. INTRODUCCIN
2. CARACTERSTICAS CONSTRUCTIVAS
3. FUNCIONAMIENTO DE UN TRANSFORMADOR MONOFSICO REAL
4. TRANSFORMADORES TRIFSICOS EN RGIMEN EQUILIBRADO
5. TRANSFORMADORES EN PARALELO
6. AUTOTRANSFORMADOR
7. TRANSFORMADORES CON TOMAS
8. TRANSFORMADORES DE MEDIDA (TENSIN, INTENSIDAD)

MQUINAS ELCTRICAS

TRANSFORMADORES

INTRODUCCIN

MQUINAS ELCTRICAS

TRANSFORMADORES

INTRODUCCIN

MQUINAS ELCTRICAS

TRANSFORMADORES

INTRODUCCIN

MQUINAS ELCTRICAS

TRANSFORMADORES

INTRODUCCIN

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS


A) NCLEO

CHAPAS DE ACERO AL SILICIO

LAMINADAS EN FRO (GRANO ORIENTADO)

CAPA AISLANTE (0,01 mm) CARLITE

COLUMNAS, CULATAS, VENTANAS DEL NCLEO, JUNTAS

SEGN LA POSICIN RELATIVA NCLEO - DEVANADO

ACORAZADAS (NCLEO ABRAZA DEVANADO)

DE COLUMNAS (DEVANADO ABRAZA NCLEO)

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

SECCIN TRANSVERSAL

PEQUEA POTENCIA: SECCIN CUADRADA

GRAN POTENCIA: POLGONO ESCALONADO (CRUCIFORME)

CANALES DE VENTILACIN
8

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

FIJACIN MECNICA DE CHAPA (VIBRACIONES)

B) DEVANADOS

HILOS DE COBRE (BARNIZ)

PLETINA DE COBRE (FIBRA DE ALGODN O CINTA DE PAPEL)

SEGN LA DISPOSICIN DE LOS ARROLLAMIENTOS:

CONCNTRICOS

ALTERNADOS (DISMINUCIN FLUJO DISPERSO)

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

B.T.
A.T.
B.T.
A.T.
B.T.
A.T.

B.T.

C) SISTEMAS DE REFRIGERACIN

PRDIDAS CALOR TEMPERATURA MQUINA

PEQUEAS POTENCIAS: TRANSFORMADORES EN SECO

10

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

POTENCIAS ELEVADAS:
TRANSFORMADORES EN BAO DE ACEITE

MAYOR CONDUCTIVIDAD TRMICA QUE EL AIRE

MAYOR RIGIDEZ DIELCTRICA QUE EL AIRE

ENVEJECIMIENTO
INHIBIDORES
DEPSITO DE EXPANSIN ( 8%)

ACEITE MINERAL: INFLAMABLE Y VAPORES MEZCLAS EXPLOSIVAS

11

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

ACEITE SINTTICO (ASKAREL) IMPACTO ECOLGICO

ACEITES DE SILICONA

ALETAS, VENTILADORES, INTERCAMBIADORES DE CALOR (MVA)


D) AISLADORES PASANTES Y OTROS ELEMENTOS

PASATAPAS

12

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

REL DE BUCHHOLTZ (GAS)

SOBRECARGAS, FALLOS DE AISLAMIENTO, ETC.

CALENTAMIENTO ANMALO VAPOR DE ACEITE

SISTEMA DE DOS FLOTADORES: ALARMA Y DESCONEXIN

13

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS


E) PLACA DE CARACTERSTICAS DEL TRANSFORMADOR

POTENCIA NOMINAL

TENSIONES NOMINALES

FRECUENCIA

IMPEDANCIA EQUIVALENTE (%)

14

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL

1 = + d1
SENTIDO

HORARIO
2 = d2

e1 = N1

d1
dt

= N1

15

d
dt

+ N1

dd1
dt

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL


e2 = N2

d 2
dt

= N2

d
dt

N2

v1 = R1i1 + e1 = R1i1 + N1
e2 = R2i2 + v 2 = N2

d
dt

dt

d d 2
dt

+ N1

N2

dd1
dt

d d 2
dt

SI SE DEFINEN LAS INDUCTANCIAS DE DISPERSIN:


L d1 = N1

d d1
di1

X1 = Ld1

L d 2 = N2

d d 2
di 2

X2 = Ld2

16

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL

v1 = e1 + R1i1 + L d1

di1
dt

e1 = N1

d
dt

e2 = v2 + R2i2 + L d2

di 2
dt

e 2 = N2

d
dt

E1 = 4,44fN1m
E1 N1

=
=m

E
N
2
2
E 2 = 4,44fN2 m
17

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL


V1 = E1 + R1I1 + jX1I1
E2 = V2 + R2I2 + jX2I2

CADA TENSIN TRAFO INDUSTRIAL A PLENA CARGA: 1 - 10% UNOM

V1 E1
V1

V2
V2 E 2

(APROXIMADAMENTE)

18

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL


INTERRUPTOR S ABIERTO
V1 = E1 + R1I0+ jX1I0
E2 = V2
I0: CORRIENTE DEL PRIMARIO EN VACO
I0: 0.6 8 % I1 NOMINAL
V1 = E1
V1

=m

V
2
V2 = E2

19

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL


INTERRUPTOR S CERRADO (EN CARGA)
V1 EN VACO = V1 EN CARGA
COMO

,
m EN VACO m EN CARGA
F.M.M. EN VACO F.M.M. EN CARGA
N1 I0 = N1 I1 N2 I2

20

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
REDUCCIN AL PRIMARIO:
VALORES INSTANTNEOS:

N1i1 N2i2 =

RGIMEN SENOIDAL:

N1I1 N2I2 = ef
V1 = (R1 + jX1 )I1 + E 2

V1 = (R1 + jX1 )I1 + R 2I2

I1

N1
N2

N1
N
N
+ V2 1 + jX 2I2 1
N2
N2
N2

N2
I2 = ef
N1
N1

21

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
N2
I2 = I' 2 I2 REFERIDA AL PRIMARIO
N1

ef
= I0 CORRIENTE DE VACO O DE EXCITACIN
N1

POR LO TANTO:
V1 = (R1 + jX1 )I1 + (R 2 + jX 2 )I2

N1
N
+ V2 1
N2
N2

N12 N2
N
V1 = (R1 + jX1 )I1 + (R 2 + jX 2 ) 2 I2
+ V2 1
N2 N1
N2

22

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
V1 = (R1 + jX1 )I1 + (R' 2 + jX' 2 )I' 2 + V ' 2

N1
V2 = V ' 2 V2 REFERIDA AL PRIMARIO
N2
2

N1
R 2 = R' 2 R 2 REFERIDA AL PRIMARIO
N2
2

N1
X 2 = X' 2 X 2 REFERIDA AL PRIMARIO
N2

23

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
TRANSFORMADOR REAL PRDIDAS MAGNTICAS RFE
IFE PRDIDAS EN EL HIERRO

I0
I CORRIENTE DE MAGNETIZACIN

I1

R1

X1

X2

V1

R2
+

I0
IFE

I2

RFE

V2

24

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
EN LA PRCTICA, DEBIDO A QUE I0 <<< I1, I2 SE SUELE TRABAJAR CON UN
CIRCUITO APROXIMADO
R1

I1
+

X2

I2

R2

RFE

Rcc

I1
+

I0
IFE

V1

X1

V2

V1

Rcc = R1 + R2 RESISTENCIA DE CORTOCIRCUITO


Xcc = X1 + X2 REACTANCIA DE CORTOCIRCUITO

25

RFE

I2
+

I0
IFE

Xcc

I
X

V2

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE VACO: TRANSFORMADOR MONOFSICO


P0
~

i2 = 0

I0

V10

V20

TRANSFORMADOR

MEDIDAS: V10, V20, P0, I0

IFE
0

I0

+
V10

RFE
IFE

I0

X
I

26

V10 = E10

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE VACO: TRANSFORMADOR MONOFSICO

P0 =

IFE =

V102

RFE

RFE

V10

2
I = I02 IFE

RFE

V10

X =

Cos 0 =

m=

P0
V10I0

V10
V20

27

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE CORTOCIRCUITO
Pcc

CORTOCIRCUITO

I1cc

TENSIN VARIABLE
V1cc
DE C.A.

TRANSFORMADOR

MEDIDAS: V1cc, Pcc, I1cc

28

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE CORTOCIRCUITO

29

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADOR MONOFSICO EN CARGA


I2 0
NDICE DE CARGA C =

I2
I'
I
= 2 1
I2N I' 2N I1N

C = 1 PLENA CARGA
C > 1 SOBRECALENTAMIENTO (ADMITIDO NORMA UNE POCO TIEMPO)
MAGNITUDES DE INTERS:

CADA DE TENSIN

RENDIMIENTO

30

MQUINAS ELCTRICAS

TRANSFORMADORES

CADA DE TENSIN
CADA DE TENSIN INTERNA V2 = |V20| |V2|
CADA DE TENSIN RELATIVA O REGULACIN c =
REFERIDA AL PRIMARIO:
c =

V1N V '2

c =

V1 V '2

V1N

100 %

EN CARGA:

V1

31

100 %

V20 V2
V20

100 %

MQUINAS ELCTRICAS

TRANSFORMADORES

CADA DE TENSIN. APROXIMACIN DE KAPP


CIRCUITO EQUIVALENTE APROXIMADO. FACTOR DE POTENCIA INDUCTIVO
Rcc
+

Xcc

I2

V1N

XccI2 2

V1N

V2

ZL

V2

I2

P 2
RccI2

R
M

V1N = V2 + (Rcc + jXcc)I2


|V1N| |V'2|= |OS| |OP| = |PS|
|V1N| |V'2| = |PS| |PR|
32

MQUINAS ELCTRICAS

TRANSFORMADORES

CADA DE TENSIN. APROXIMACIN DE KAPP


|PR| = |PQ| + |QR| = |PQ| + |MN|
|PR| = RccI2Cos(2) + XccI2Sen(2)
|V1N| |V'2| = RccI2Cos(2) + XccI2Sen(2)
|V1N| |V'2| = CRccI2NCos(2) + CXccI2NSen(2)

APROXIMACIN DE KAPP:
c = C Rcc Cos(2) + C XccSen(2)
33

MQUINAS ELCTRICAS

TRANSFORMADORES

CADA DE TENSIN
cc =

Z ccI1N
100
V1N

Rcc =

R I'
R ccI1N
100 cc 2N 100
V1N
V1N

Xcc =

X I'
X ccI1N
100 cc 2N 100
V1N
V1N

EFECTO FERRANTI:
CON F.D.P. CAPACITIVO c PUEDE SER NEGATIVA
c = C Rcc Cos(2) C XccSen(2)

34

MQUINAS ELCTRICAS

TRANSFORMADORES

PRDIDAS Y RENDIMIENTO
PRDIDAS
1)

HIERRO:

PFE = P0

2)

COBRE:

PCU = I' 22 Rcc = C2I' 22N Rcc = C2Pcc

RENDIMIENTO
=

P2
P
PPERD
= 1 PERD = 1
P1
P1
P2 + PPERD
P0 + C 2Pcc
= 1
P2 + P0 + C 2Pcc

35

MQUINAS ELCTRICAS

TRANSFORMADORES

PRDIDAS Y RENDIMIENTO
POTENCIA DEL SECUNDARIO ( P2)
P2 = V2I2Cos(2) = CV2I2NCos(2)
POR LO TANTO:
P0 + C 2Pcc
CV2I2NCos( 2 )
=
= 1
CV2I2NCos( 2 ) + P0 + C 2Pcc CV2I2NCos( 2 ) + P0 + C 2Pcc

RENDIMIENTO MXIMO:
2
P0 = C OPT
Pcc

C OPT =

36

P0
Pcc

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
BANCOS TRIFSICOS
A
A

iA

ia

ib

ic

B
B

iB

C
C

iC

37

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
CONDICIONES EQUILIBRADAS:

LAS TRES MQUINAS IDNTICAS

TRABAJANDO EN IDNTICAS CONDICIONES

DESFASE ENTRE MAGNITUDES DE 120

38

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
PROPIEDADES EN RGIMEN EQUILIBRADO:
1)

TRAFOS TRIFSICOS UNIN DE 3 MQUINAS

2)

A + B + C = 0 AHORRO DE MATERIAL

TRANSFORMADOR DE 3 COLUMNAS (CORE - TYPE)


FASES LATERALES (a, c) MAYOR LONGITUD FASE CENTRAL (b)
DESEQUILIBRIOS INTENSIDADES MAGNETIZANTES
POCA IMPORTANCIA FORMA CONSTRUCTIVA MUY EXTENDIDA

39

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
OTRAS FORMAS CONSTRUCTIVAS:
1)

TRANSFORMADORES DE 5 COLUMNAS

2)

ARROLLAMIENTOS EN LAS COLUMNAS CENTRALES


EL FLUJO SE CIERRA POR LAS LATERALES MENOR SECCIN CULATA
(MENOR ALTURA TOTAL)
TRANSFORMADORES ACORAZADOS (SHELL - TYPE)

40

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
CLASIFICACIN SEGN EL TIPO DE CIRCUITO MAGNTICO
A) FLUJOS LIBRES
HAY MALLAS DONDE SLO ACTA DE UNA FASE
B) FLUJOS LIGADOS
EN CADA MALLA ACTAN DE VARIAS FASES
BANCO TRIFSICO
TRES COLUMNAS
CINCO COLUMNAS
ACORAZADOS

41

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
COMPARACIN
TRIFSICOS

BANCOS

TRIFSICOS

COMPORTAMIENTO ELCTRICO IDNTICO

TRANSFORMADORES TRIFSICOS:

VS.

MENOR PESO
MENORES PRDIDAS
MENOR VOLUMEN DE MQUINA Y PARQUE
AVERA: OTRO TRANSFORMADOR TRIFSICO

42

TRANSFORMADORES

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS

BANCOS TRIFSICOS:

AVERA: RESERVA DEL 33%


MEJORES CONDICIONES DE TRANSPORTE

UTILIZACIN TPICA:

TRANSFORMADORES
TRIFSICOS
SALVO
TRANSFORMACIN DE GRANDES POTENCIAS

43

CENTROS

DE

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
MAGNITUDES NOMINALES Y PARMETROS
POTENCIA NOMINAL, SN (kVA), TRIFSICA
TENSIN NOMINAL PRIMARIA (VN1) (TENSIN COMPUESTA)
TENSIN NOMINAL SECUNDARIA (VN2) (TENSIN COMPUESTA)
INTENSIDAD NOMINAL:
IN =

SN
3 UN

44

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
RELACIN DE TRANSFORMACIN (k) RELACIN NMERO DE ESPIRAS
GRUPO DE CONEXIN

RELACIN DE TRANSFORMACIN (k)

Dd, Yy
Dy
3

Yd
Dz
Yz

45

N1
N2

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
DISTINTOS TIPOS DE CONEXIN ORIGINAN DIFERENCIAS DE FASE ENTRE
TENSIONES COMPUESTAS DE PRIMARIO Y SECUNDARIO
NDICE HORARIO RETRASO DEL LADO DE MENOR TENSIN (R)
RESPECTO AL DE TENSIN MS ELEVADA (R) MEDIDO
EN MLTIPLOS DE 30
AGUJA GRANDE (ALTA TENSIN) 12
AGUJA PEQUEA (BAJA TENSIN) HORA CORRESPONDIENTE
R

R
R

YNd1

R
R

YNd11

46

YNyn0

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-ESTRELLA
R

R
+

UU

U'U

S
+

UV

U' V

T
+

UW

U' W

47

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-ESTRELLA

UU

U'U

UV

U'V

UW

U' W

HIPTESIS: SISTEMA EQUILIBRADO, SECUENCIA DIRECTA

U u = U0

U v = U-120

U w = U120

U u = U0

U v = U-120

U w = U120

48

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-ESTRELLA
TRANSFORMADOR IDEAL:

URS
U(10 1 120 ) U
N

=
= 0 = 0
N'
U'RS U' (10 1 120 ) U'

49

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-ESTRELLA
DESFASE 0 CONEXIN YNyn0

U W = UT

U' W = U' T

U'U = U'R

U' V = U'S

U V = US
50

UU = UR

UU = UR

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-TRINGULO
R

R
+

UU

U'U

S
+

UV

U'V

N
T

T
+

UW

U' W

51

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-TRINGULO

U'U

UU
R

UV

U'V
N

U' W

UW

HIPTESIS: TRANSFORMADOR IDEAL, SISTEMA EQUILIBRADO, SECUENCIA


DIRECTA

52

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO. CONEXIN ESTRELLA-TRINGULO

URS = UU UV

U'RS = U' V

URS
U(10 1 120 )
3U30
N

=
=
= 3 30
N'
U'RS U' (1 120 + 180 ) U' 60

UW = UT

U' W = U'TS

U'T

CONEXIN YNd11

U'R
N

U' V = U'SR

U'S

UV = US

53

30

U'U = U'RT

UU = UR

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-TRINGULO

U'U

UU
R

UV

U'V
N

U' W

UW

HIPTESIS: TRANSFORMADOR IDEAL, SISTEMA EQUILIBRADO, SECUENCIA


DIRECTA

54

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO. CONEXIN ESTRELLA-TRINGULO

URS = UU UV

CONEXIN YNd1

55

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN TRINGULO-ESTRELLA

UU

U'U

UV

U'V
N

U'W

UW
T

HIPTESIS: TRANSFORMADOR IDEAL, SISTEMA EQUILIBRADO, SECUENCIA


DIRECTA

56

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO. CONEXIN TRINGULO-ESTRELLA

URS = UU

UW = UTR

UT

U' W = U'T

UU = URS

U'U = U'R

CONEXIN Dyn11

US

U' V = U'S

UV = UST

57

30

UR

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN TRINGULO-TRINGULO

UU

U'U

UV

U'V

U'W

UW
T

HIPTESIS: SECUENCIA DIRECTA,


EQUILIBRADO

TRANSFORMADOR

58

IDEAL,

SISTEMA

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN TRINGULO-TRINGULO

URS = UU

U'RS = U'U

URS
U0 N

=
= 0
U'RS U' 0 N'

U V = UST
CONEXIN Dd0

U W = UTR

UU = URS

59

U' V = U' ST

U' W = U' TR

R
S U
'U = U'RS

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN TRINGULO-TRINGULO

UU

U'U

UV

U'V

U'W

UW
T

HIPTESIS: SECUENCIA DIRECTA,


EQUILIBRADO

TRANSFORMADOR

60

IDEAL,

SISTEMA

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN TRINGULO-TRINGULO

URS = UU

U' RS = U' V

URS
U0
N

=
= 60
U' RS U' 180 120 N'

U V = UST
CONEXIN Dd10

U W = UTR

UU = URS R
61

30

U'U = U'RT

U' W = U'TS

30

U'V = U'SR

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-ZIGZAG

U'U
2

UU

U'U
2

U' V
2

UV
S

U' V
2
N

U' W
2

UW

U'W
2

HIPTESIS: SECUENCIA DIRECTA,


EQUILIBRADO

TRANSFORMADOR

62

IDEAL,

SISTEMA

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-ZIGZAG

URS = UU U V

U' U U' V U' W U' V 3


U' RS =
+

+
= U' V
2
2
2
2
2

URS U(10 1 120)


3U30
2 N

=
=
=
150
3
3
3 N'
U'RS
U' 120
U' 120
2
2

CONEXIN YNzn5

63

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
CONEXIN ESTRELLA-ZIGZAG

U' V

UW = UT

U'S

U'U

U' W
2

U'R

U' W

U' V

U'U

UU = UR

150

UV = US

64

U'T

MQUINAS ELCTRICAS

TRANSFORMADORES

ESQUEMA EQUIVALENTE
ESQUEMA EQUIVALENTE POR FASE REFERIDO A UN LADO
TRANSFORMADOR TRIFSICO: ESTRELLA DE IMPEDANCIAS

I1

Z'2

Z1

V1


V1 , V' 2

I '2

Z0

I0

TENSIONES SIMPLES


I1, I '2 , I0 INTENSIDADES SIMPLES

65

V '2

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE VACO
CONEXIN:

TENSIN NOMINAL DEVANADO DE MAYOR TENSIN

ABIERTO DEVANADO DE MENOR TENSIN

LECTURAS:

POTENCIA TOTAL ABSORBIDA (TRIFSICA) P0

INTENSIDAD DE FASE I0A, I0B, I0C

POR DESEQUILIBRIO EN EL CIRCUITO MAGNTICO:


I0 =

1
(I0 A + I0B + I0C )
3
66

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE VACO: TRANSFORMADOR TRIFSICO


P0 = 3R I

2
FE FE

IFE =

V10
RFE

3 V102
RFE

RFE

2
I = I02 IFE
X =

67

V10
I

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE CORTOCIRCUITO
CONEXIN:

INTENSIDADES NOMINALES

TENSIN REDUCIDA DEVANADO DE MAYOR TENSIN

CORTOCIRCUITO DEVANADO DE MENOR TENSIN

LECTURAS:

TENSIN DE CORTOCIRCUITO, Vcc, COMPUESTA

POTENCIA TOTAL ABSORBIDA, Pcc, TRIFSICA

68

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE CORTOCIRCUITO
Pcc = 3RccI12cc Rcc

Vcc VSIMPLE

VLNEA

= 3
V
LNEA

CONEXIN EN ESTRELLA
CONEXIN EN TRINGULO

69

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO MONOFSICO EQUIVALENTE


ESTRELLA-ESTRELLA

I1

Z' 2

Z1

I '2 = I 'L
+

V1

Z'L

Z0

V '2

I0

70

Z'

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO MONOFSICO EQUIVALENTE


ESTRELLA-TRINGULO
ZL

b'

a
T

c'
a

Z' 2

Z1

3Z'L

I '2 = I 'ab
+

V1

I1

IL

Z0

V '2

I0

71

Z'

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO MONOFSICO EQUIVALENTE


TRINGULO-ESTRELLA / ESTRELLA-TRINGULO
RECOMENDACIN: CONVERTIR LA CARGA A LA CONEXIN DEL DEVANADO
DEL TRANSFORMADOR
DOS POSIBILIDADES:
CONVERSIN DEL TRINGULO A ESTRELLA
CONVERSIN DE LA ESTRELLA A TRINGULO

72

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO
SITUACIONES PRCTICAS:
1)

AMPLIACIN DE INSTALACIONES (SOLUCIN MS ECONMICA)

2)

FLEXIBILIDAD DE OPERACIN

3)

1 NICO TRANSFORMADOR PRDIDA DE SUMINISTRO EN AVERA O


REVISIN
2 TRANSFORMADORES LIMITACIN DE POTENCIA
POTENCIAS ELEVADAS

FIABILIDAD (SALIDA DE GENERADORES)

TAMAO (TRANSPORTE)

73

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO
CONDICIONES DE FUNCIONAMIENTO

CONDICIONES CONVENIENTES:

IGUAL RELACIN DE TRANSFORMACIN


CORRECTO FUNCIONAMIENTO EN VACO

IGUAL TENSIN DE CORTOCIRCUITO EN p.u.


Vcc
VN

ZccIN
VN

= cc

EQUILIBRIO DE LA CARGA (CI = CII)

IGUAL POTENCIA DE CORTOCIRCUITO EN p.u.


SI ccI = ccII Zcc CON IGUAL ARGUMENTO

74

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO

CONDICIONES OBLIGATORIAS

TRAFOS MONOFSICOS: CONEXIN BORNAS HOMLOGAS ENTRE S

TRAFOS TRIFSICOS:
CONEXIN BORNAS HOMLOGAS ENTRE S
IGUAL NDICE HORARIO

IGUAL SECUENCIA DE FASES


INCONVENIENTES:

AUMENTA LA INTENSIDAD DE CORTOCIRCUITO

AUMENTA COSTE DEL APARELLAJE ELCTRICO

75

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO
INCUMPLIMIENTO DE CONDICIONES

CONDICIONES
PTIMO)

CONVENIENTES:

FUNCIONAMIENTO

POSIBLE

(NO

CONDICIONES OBLIGATORIAS: IMPOSIBILIDAD DE FUNCIONAMIENTO


(CORTOCIRCUITO)
+

TRANSFORMADOR
I

V1

A'II

A'I

TRANSFORMADOR
II

AII

AI

II

III

ZccI

ZccII

aI
V'2

a'II
a'I

I
CARGA

76

aII

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO
ZccIII = ZccIIIII
II Z ccIIIN
I Z I

100 = II ccII IIN 100


IIN V1N
IIIN V1N

CIccI = CIIccII
CI ccII
=
CII ccI
R
S
T

C B A
c b a

II

77

C B A
c b a

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

DIVISOR DE TENSIN

NICO ARROLLAMIENTO

PRIMARIO Y SECUNDARIO UNIDOS GALVNICAMENTE

78

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

ARROLLAMIENTO SERIE: CIRCULA I1 (MENOS LONGITUD POR TRAFO)

ARROLLAMIENTO COMN: CIRCULA I2 - I1 (MENOS SECCIN POR TRAFO)

MENOR CANTIDAD DE COBRE

RELACIN DE TRANSFORMACIN:
k=

N1 Ns + Nc U1
=
=
N2
Nc
U2

HIPTESIS
IDEAL
DESPRECIANDO m LA ECUACIN MAGNTICA:
NsI1 - Nc(I2 - I1) = 0
79

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

COMPORTAMIENTO COMO EL DEL TRANSFORMADOR


ARROLLAMIENTOS DE FORMA INDIVIDUALIZADA:

EL AUTOTRANSFORMADOR PUEDE ENTENDERSE COMO UNA FORMA


ESPECIAL DE CONECTAR UN TRANSFORMADOR
COINCIDE CON SUS CARACTERSTICAS CONSTRUCTIVAS

80

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
COMPARACIN ENTRE TRANSFORMADOR Y AUTOTRANSFORMADOR
BASES: DOS MQUINAS CON:
1)

IGUALES CARACTERSTICAS NOMINALES (TENSIN, POTENCIA)

2)

IGUALES PRDIDAS POR UNIDAD DE PESO (Bmax)

3)

IGUAL DENSIDAD DE CORRIENTE

PARMETROS DE CORTOCIRCUITO:
TRAFO
AUTOTRAFO

81

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

82

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

(BASE 3)

BASE 1 MISMA POTENCIA NOMINAL

83

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

MENOR NECESIDAD DE COBRE

REACTANCIA DE DISPERSIN
EN GENERAL:

84

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
PARMETROS DE VACO
IGUAL B (BASE 2)

MISMO

FLUJO

MISMA

SECCIN

CIRCUITO

MAGNTICO

AL SER

AUNQUE TRABAJEN CON


MENOR SECCIN LA VENTANA:

85

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
MENOR LONGITUD MAGNTICA INTENSIDAD MAGNETIZANTE
MENOR PESO PRDIDAS TOTALES
NECESARIO CONOCER LAS DIMENSIONES DEL CIRCUITO
EN GENERAL:
i0 % A < i0 % T
p 0 % A < p 0 %T

PESO DE COBRE
IGUAL DENSIDAD CORRIENTE (BASE 3) IGUALES PRDIDAS POR UNIDAD
DE PESO

86

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
FACTOR DE REDUCCIN DE PRDIDAS EN EL COBRE

SE PUEDE APLICAR AL PESO DE COBRE

VENTAJAS DE LOS AUTOTRANSFORMADORES

MENORES PRDIDAS (COBRE, HIERRO)

MEJOR RENDIMIENTO

87

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

MENORES CADAS DE TENSIN

MENOR INTENSIDAD DE VACO

MENOR COSTE: COBRE, HIERRO

MENOR TAMAO (ESPACIO EN SUBESTACIONES)

INCONVENIENTES DE LOS AUTOTRANSFORMADORES

MAYOR INTENSIDAD DE CORTOCIRCUITO COSTE APARELLAJE


NO EXISTE AISLAMIENTO GALVNICO ENTRE PRIMARIO Y SECUNDARIO
APARICIN DE TENSIONES PRIMARIAS EN EL SECUNDARIO

88

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
AVERA:

89

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
CORTOCIRCUITO A TIERRA EN ALTA TENSIN:

90

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
AVERA:

BORNA COMN: CONEXIN RGIDA A TIERRA

91

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

REGLAMENTACIN: k < 1,25


CON POTENCIALES POR DEBAJO DE 250 V, NO REGULADO
ACONSEJABLE (GENERAL) 1 < k < 2

92

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
POTENCIA EN LOS AUTOTRANSFORMADORES
POTENCIA NOMINAL:

POTENCIA MXIMA QUE PUEDE TRANSFERIR DEL


PRIMARIO AL SECUNDARIO

POTENCIA CEDIDA AL SECUNDARIO:


S2 = V2I2 = V2I1 + V2(I2 - I1)

Sc POTENCIA DE CIRCULACIN
Si POTENCIA INTERNA (TRANSFERENCIA ELECTROMAGNTICA)

93

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

Si = V2(I2 - I1) = V2I2

= Sp

Sp POTENCIA DE PASO
AUTOTRAFO SOLO TRANSFORMA EL

100 % DE LA POTENCIA TOTAL

TRANSFERIDA AL SECUNDARIO
EJEMPLO:
TRAFO 100 kVA, k = 2, TRANSF. ELECTROMAGNTICA = 100 kVA
AUTOTRAFO 100 kVA, k = 2, TRANSF. ELECTROMAGNTICA = 50 kVA

94

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES CON TOMAS


CONTROL DE LA TENSIN

REGULAR TENSIN SERVIDA DENTRO LMITES LEGALES

CONTROLAR FLUJOS DE P Y Q EN LA RED

AJUSTE TENSIN FRENTE A INCREMENTO EN LA CARGA


MONOFSICO

TRIFSICO

95

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES CON TOMAS


CONMUTACIN A ALTA TENSIN

ECONMICO: EN BAJA TENSIN CONMUTADORES DE ALTA INTENSIDAD


TCNICO: EN ALTA TENSIN MAYOR NMERO DE ESPIRAS MAYOR
CAPACIDAD DE REGULACIN
SI AMBOS ARROLLAMIENTOS ESTN A ALTA TENSIN LA REGULACIN
EN EL ARROLLAMIENTO QUE VAYA A TENER TENSIN VARIABLE (B
CTE.)

TRANSFORMACIN A I CTE. VERSUS TRANSFORMACIN A P CTE.


CONMUTACIN EN VACO VERSUS CONMUTACIN EN CARGA

96

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
TRANSFORMADOR DE TENSIN

FUNCIONA CASI EN VACO

CADA DE TENSIN INTERNA MUY PEQUEA

BORNE DE SECUNDARIO A TIERRA PELIGRO CONTACTO PRIMARIO Y


SECUNDARIO

97

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
V1 - V2 = RccI2Cos(cc) + XccI2Sen(cc)
IDEALMENTE:
V1 = V2
ERROR DE RELACIN O DE TENSIN

98

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
ERROR DE FASE O DE NGULO DIFERENCIA DE FASE ENTRE V1 Y V2 (MIN)
CLASES DE PRECISIN: 0,1, 0,2, 0,5, 1, 3 VALOR MXIMO DE V A
POTENCIA NOMINAL Y
F.D.P. 0,8 INDUCTIVO
APARATO
VOLTMETROS
BOBINA VOLTIMTRICA VATMETRO
BOBINA VOLTIMTRICA CONTADOR
FASMETROS
SINCRONOSCOPIOS
RELS

99

CONSUMO (VA)
2-8
1-8
2-6
2-12
5-15
5-50

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
TRANSFORMADOR DE CORRIENTE

FUNCIONA CASI EN CORTOCIRCUITO


EN A.T. BORNE DE SECUNDARIO A TIERRA PELIGRO CONTACTO
PRIMARIO
Y
SECUNDARIO

100

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
I1 = I2 + I0
IDEALMENTE:
I1 = I2 = KiI2
B.T. TRANSFORMADOR DE TENAZA O PINZAS (NO SE CORTA LA LNEA)

101

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
SI SE DEJA EN CIRCUITO ABIERTO EL SECUNDARIO I1 = I0

I1 ES CTE. (RED) Y MUY ELEVADA FLUJO CRECE PELIGROSAMENTE


PFE Y V2 PELIGRO EN LA VIDA DE LOS AISLANTES Y LA SEGURIDAD
DEL PERSONAL

SOLUCIONES:

INTERRUMPIR EL SERVICIO DE LA LNEA

CORTOCIRCUITAR PREVIAMENTE EL SECUNDARIO

102

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
ERROR DE RELACIN O DE INTENSIDAD
I2
i =

I1
Ki

I1
Ki

100

ERROR DE FASE DIFERENCIA DE FASE ENTRE I1 E I2 (MIN)


CLASES DE PRECISIN: IGUAL QUE LOS TRANSFORMADORES DE TENSIN
APARATO
AMPERMETRO
BOBINA AMPERIMTRICA VATMETRO
BOBINA AMPERIMTRICA CONTADOR
FASMETROS
RELS

103

CONSUMO (VA)
1-4
1-8
1-2
2-12
5-20