You are on page 1of 2

Contract No.

SCL 1108
Kai Tak Site
ICEs comments dated 17-09-2015

2015-09-17 Design Calculations of External Stone


Cladding
ITEM
NO.

REVIEWER

Atkins
(ICE)

DOCUMENT /
DRAWING
REFERENCE

Calculation

ICES COMMENT

CONTRACTORS RESPONSE

1. Please justify the thermal effect is negligible.


2. The coefficient of wind load (Cp) has to consider.
3. Please justify the load factor: 1.25.

1. Thermal effect is only considered


when a temperature difference of 32
degrees C occurred according to MTR
specification Section ES 24. Therefore it
is considered to be negligible.
2.Wind pressure coefficient of 1.4 is
adopted.
3.The load factor is revised to 1.6 for all
loading for conservative design.

Atkins
(ICE)

Calculation

Stone
report
is
poor
Comments on 17-09-2015:

quality

for

information.

Atkins
(ICE)

Calculation

Please highlight the capacity of stone in the test report for easy
reference.
Additional comments may be provided after the revised calculation.

Atkins
(ICE)

Drawing

Comments on the drawings refer to attachment.

Comments on 17-09-2015:
Comments refer to attachment.

Comments on 17-09-2015:
Comments refer to attachment.

-1-

Noted and revised


Response on 25-09-2015:
Revised as attached Report
Noted
Response on 25-09-2015:
Revised as attached Report
Revied as attached Drawings.
Response on 25-09-2015:
Revised as attached Drawings

Contract No. SCL 1108


Kai Tak Site
ICEs comments dated 17-09-2015

2015-09-17 Design Calculations of External Stone


Cladding
ITEM
NO.

REVIEWER

DOCUMENT /
DRAWING
REFERENCE

Atkins
(ICE)

Drawing

Atkins
(ICE)

Drawing

Atkins
(ICE)

Drawing

Atkins
(ICE)

Drawing

ICES COMMENT

CONTRACTORS RESPONSE

Many items in the drawings are not for ICE approval.


Please review.
Comments on 17-09-2015:
Many sections, elevations, items or information are NOT related
to ICE approval. Please double before submission.
Many Sections are not match and miss the dimension.
Please review.
Comments on 17-09-2015:
Comments refer to attachment.

Items not for ICE approval is half-tone,


please refer to Drawings.
Response on 25-09-2015:
Revised as attached Drawings
Noted
and
revised
as
attached
Drawings.
Response on 25-09-2015:
Revised as attached Drawings

Comments on 17-09-2015:
Revised as per Drawing No.
Typical section/plan have to provide to show the frame 1108_C_KAT_KCJ_A65_721A
with brackets from bottom level to top level. Please
refer to the marking in attachment.
Comments on 17-09-2015:
Noted and revised.
Many drawings are not relate to the submission. Please double
check.