You are on page 1of 1

Date of issue:

17.11.2011

Serial No.:

3GP11023272

Order No.:
Type:
Product Code:

596095-50 / 30164862-1
M3BP 315MLA 4 B3
3GBP312410-ADG

Type Test Report


Customer:

Customer ref.:
Rating:
V
400

3~Motor
Insul.cl.F
IP55

Resistance
Line

Ambient:
0,01001
0,01001
0,01003

U1 - V1
U1 - W 1
V1 - W 1

Hz
50

21,0 C

kW
185

r/min
1487

Insulation resistance at
4100 M

35,5

Torque
[Nm]

Line
U[V]
400,0
67,3

1188,0

891,8
592,5
295,5

No load test
Locked rotor test
Thermal test (100% load)

Duty
S1

Overload

1000 V
Torque

High-voltage test winding

Test

cos
0,85

A
328

1900 V

D
D

f[Hz]
50
50

Input
I[A]
111,4
328,0

P1 [kW]
2,99
11,25

400,1

50

327,2

193,1

185,0

400,1
400,1
400,2

D
D
D

50
50
50

255,1
189,9
137,0

144,6
96,7
49,6

138,8
92,5
46,3

[oC]

[K]
59,9
35,4
46,8

Method
1
2
2

160 %

60 s

Output
P2 [kW] n[r/min]
1500
0

cos
0,04
0,29

[%]

1489

0,85

95,8

1492
1495
1498

0,82
0,74
0,52

96,0
95,6
93,3

Partial load points:


~75% load
~50% load
~25% load
Temperature rise at rated load.
Stator winding :
Frame :
Bearing D-end :
Ambient Temperature :

25,0

Measurement method
1 Resistance
2 Thermometer
3 Thermocouples

Starting current (IS / IN) :


Locked rotor torque (Tl / TN) :
Breakdown torque (Tb / TN) :
Pull-up torque (Tu / TN) :

Manufactured and tested in accordance with rules of IEC 60034-1 and IEC 60034-2-1.
PLL determined from residual loss.
On behalf of customer
On behalf of manufacturer

Date of test

31.10.2011
Telephone

Tested by ABB Oy, Motors and Generators, Vaasa, Finland


Computer print-out valid without signature.

ABB, Motors and Generators


www abb.com/motors&generators

Telefax

+358 10 2211
+358 10 22 47372

7,14
2,35
2,95
2,02

15s

You might also like