DO NOT CAULK BETWEEN FLASHING & “ee | WALL "AULK GAP BETWEEN SLEEVE AND ADJACENT FLASHINGIWALL ON TOP. AND SIDES. _~-CAULK GAP BETWEEN LOUVER AND ‘SLEEVE ON TOP AND SIDES. DO NOT CAULK AT BOTTOM, HEAD FLASHING— WALL SLEEVE BIRD SCREEN ON EXTERIOR OF LOUVER——_ LOUVER MANA AAAS AAT DRIP SILL—_ 24" MIN. ‘Access DOOR 24X24 OR AS LARGE AS POSSIBLE \\30° MIN, t SILL FLASHING— GENERAL NOTES . 1, DO NOT ATTACH DUCT TO TOP OF LOWER, LOUVER BLADE AS TYPICAL. THIS CREATES SEALING PROBLEMS AT MULLIONS AND OTHER VERTICAL MEMBERS. CONSTRUCT SLEEVE AND DUCTWORK TO SUPPORT WEIGHT OF SERVICE TECHNICIAN. 3. SEAL JOINT BETWEEN DUCT AND SLEEVE WATER TIGHT ALL AROUND. INSULATE DUCT AND SLEEVE AS SPECIFIED. MAINTAIN 1/8" GAP BETWEEN SLEEVE AND BOTTOM OF LOUVER FOR FREE DRAINAGE, PROVIDE ALUMINUM SHIMS AS REQUIRED. DO NOT CAULK THIS GAP. NOTE TO AVE: INDICATE WORK TO BE DONE BY GENERAL CONTRACTOR AND VENT CONTRACTOR, OUTSIDE AIR PLENUM IS PREFERRED. SEE OUTSIDE AIR PLENUM CONSTRUCTION DETAIL. (4)\WALL LOUVER DETAIL (@101/ SCALE: NO SCALE WALL LOUVER DETAIL Facies Planning & Construction ws Standard Detail