DO NOT CAULK
BETWEEN FLASHING
& “ee |
WALL
"AULK GAP BETWEEN SLEEVE AND
ADJACENT FLASHINGIWALL ON TOP.
AND SIDES.
_~-CAULK GAP BETWEEN LOUVER AND
‘SLEEVE ON TOP AND SIDES. DO NOT
CAULK AT BOTTOM,
HEAD FLASHING—
WALL SLEEVE
BIRD SCREEN ON
EXTERIOR OF LOUVER——_
LOUVER
MANA AAAS AAT
DRIP SILL—_
24" MIN.
‘Access DOOR
24X24 OR AS
LARGE AS POSSIBLE
\\30° MIN,
t
SILL FLASHING—
GENERAL NOTES .
1, DO NOT ATTACH DUCT TO TOP OF LOWER,
LOUVER BLADE AS TYPICAL. THIS CREATES
SEALING PROBLEMS AT MULLIONS AND
OTHER VERTICAL MEMBERS.
CONSTRUCT SLEEVE AND DUCTWORK TO
SUPPORT WEIGHT OF SERVICE
TECHNICIAN.
3. SEAL JOINT BETWEEN DUCT AND SLEEVE
WATER TIGHT ALL AROUND.
INSULATE DUCT AND SLEEVE AS SPECIFIED.
MAINTAIN 1/8" GAP BETWEEN
SLEEVE AND BOTTOM OF LOUVER
FOR FREE DRAINAGE, PROVIDE
ALUMINUM SHIMS AS REQUIRED.
DO NOT CAULK THIS GAP.
NOTE TO AVE:
INDICATE WORK TO BE DONE BY GENERAL
CONTRACTOR AND VENT CONTRACTOR,
OUTSIDE AIR PLENUM IS PREFERRED. SEE
OUTSIDE AIR PLENUM CONSTRUCTION
DETAIL.
(4)\WALL LOUVER DETAIL
(@101/ SCALE: NO SCALE
WALL LOUVER DETAIL
Facies Planning & Construction
ws Standard Detail