You are on page 1of 17

CDC APPROVAL STAMP

IGT-MYANMAR GSM ROLLOUT PROJECT


UNION REPUBLIC OF MYANMAR

DETAILED DESIGN DRAWINGS FOR (SITE ID: YN0878_YAT20212)

OUTDOOR GREENFIELD SITE


GENERAL NOTES

NO.

DRAWING NO.

DESCRIPTION

IGT_C2_TABLE OF CONTENTS_REV_01

TABLE OF CONTENTS

IGT_C2_LOCATION MAP_REV_01

LOCATION / VICINITY PLAN & GOOGLE MAP WITH COORDINATES

IGT_C2_SITE LAYOUT_REV_01

SITE LAYOUT (INCLUDING DUCTING FOR ELECTRICAL CABLES)

IGT_C2_TOWER ELEVATION_REV_01

TOWER ELEVATION LAYOUT

IGT_C2_SITE_EARTHING_REV_01

SITE EARTHING LAYOUT

IGT_C2_TOWER EARTHING_REV_01

TOWER EARTHING LAYOUT

IGT_STD_TOWER FOUNDATION_REV_01

TOWER FOUNDATION DESIGN DRAWING

IGT_STD_OUTDOOR BTS PAD_REV_01

OUTDOOR BTS PAD

IGT_STD_GENSET PAD_REV_01

GENSET PAD

10

IGT_STD_CABLE LADDER/TRAY_REV_01

CABLE TRAY AND CABLE LADDER DETAIL DRAWING

11

IGT_STD_FENCE DETAIL_REV_01

FENCE DETAILED DRAWING

12

IGT_STD_EARTHING TEST PIT_REV_01

EARTHING TEST PIT

13

IGT_STD_SINGLE LINE DIAGRAM_REV_01

SINGLE LINE DIAGRAM

2. ALL HEALTH & SAFETY POLICIES AND PROCEDURES SHALL


BE STRICTLY IMPLEMENTED DURING CONSTRUCTION.
3. CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES
FOR THE USE OF TOOLS AND EQUIPMENTS ON SITE, WHICH
MAY AFFECT THE STRUCTURAL SOUNDNESS OF ANY
ADJACENT STRUCTURES.

14

IGT_STD_TOWER TEMPLATE

EKI_37m_150KPA_195KMPH_Access

4. ALL REFERENCES FOR AZIMUTH READING AND ANGULAR


POSITIONS SHALL BE FROM TRUE GEOGRAPHICAL NOTH.

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS


OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.
3. CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER IN
ADVANCE OF ANY CHANGES ON SITE THAT DO NOT
CONFORM TO THE DESIGN SPECIFICATIONS AND
REQUIREMENTS IN THE DETAILED DETAIL DESIGN DWGS.
4. ANY CHANGES ON THE EXECUTION OF WORK AND SITE
METHODOLOGY SHALL BE CARRIED OUT ONLY UPON
WRITTEN APPROVAL FROM AN ENGINEER.
5. NO WORKS SHALL BE EXECUTED UNLESS ALL NECESSARY
CONSTRUCTION PERMITS ARE OBTAINED AND APPROVED
BY THE CUSTOMER.

CONSTRUCTION NOTES
1. CONTRACTOR SHALL ENSURE THAT ALL EXISTING UNDER
GROUND & ABOVEGROUND SERVICES & UTILITIES FOUND
WITHIN THE SITE PERIMETER AND NOT INDICATED IN THE
DETAILED DESIGN DRAWING SHALL BE REPORTED TO THE
PROPER MANAGEMENT AND PROTECTED FROM ANY
FURTHER DAMAGES DURING CONSTRUCTION.

5. ALL EXCESS MATERIAL ON SITE SHALL BE DISPOSED OFF


TO PROPER LOCATIONS AFTER CONSTRUCTIONS.

LEGEND

C2

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

CONSULTANT APPROVAL STAMP

SITE INFORMATION

NAME

ADDRESS

CONTACT NO.

SITE ID: YN0878_YAT20212

IGT APPROVAL

NAME

SIGNATURE

DATE

SHEET CONTENTS:

SHEET NO.

SITE NAME:
LAND OWNER

U Zaw Win

447, Ywar Street, Lat KhoteKone,


KunChanKone Tsp.

09-420017477

YAT20212_KunChanKone

DISTRICT

KunChanKone
_
:

REGION

TOWN
LONGITUDE
COORDINATES
LATTITUDE

APPROVED
CANIDATE
C2

DRAWN

MYINT MYAT

13 Oct 2015

KRISHAN TANEJA

APPROVED

KRISHAN TANEJA

DWG. NO.

Yangon

TABLE OF CONTENTS

CHECKED

RELEASED
FOR

IGT_C2_TABLE OF CONTENTS_REV_01
PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

14

CDC APPROVAL STAMP

GENERAL NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.
3. CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER IN
ADVANCE OF ANY CHANGES ON SITE THAT DO NOT
CONFORM TO THE DESIGN SPECIFICATIONS AND
REQUIREMENTS IN THE DETAILED DETAIL DESIGN DWGS.
4. ANY CHANGES ON THE EXECUTION OF WORK AND SITE
METHODOLOGY SHALL BE CARRIED OUT ONLY UPON
WRITTEN APPROVAL FROM AN ENGINEER.
5. NO WORKS SHALL BE EXECUTED UNLESS ALL NECESSARY
CONSTRUCTION PERMITS ARE OBTAINED AND APPROVED
BY THE CUSTOMER.

CONSTRUCTION NOTES
1. CONTRACTOR SHALL ENSURE THAT ALL EXISTING UNDER
GROUND & ABOVEGROUND SERVICES & UTILITIES FOUND
WITHIN THE SITE PERIMETER AND NOT INDICATED IN THE
DETAILED DESIGN DRAWING SHALL BE REPORTED TO THE
PROPER MANAGEMENT AND PROTECTED FROM ANY
FURTHER DAMAGES DURING CONSTRUCTION.
2. ALL HEALTH & SAFETY POLICIES AND PROCEDURES SHALL
BE STRICTLY IMPLEMENTED DURING CONSTRUCTION.
3. CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES
FOR THE USE OF TOOLS AND EQUIPMENTS ON SITE, WHICH
MAY AFFECT THE STRUCTURAL SOUNDNESS OF ANY
ADJACENT STRUCTURES.
4. ALL REFERENCES FOR AZIMUTH READING AND ANGULAR
POSITIONS SHALL BE FROM TRUE GEOGRAPHICAL NOTH.
5. ALL EXCESS MATERIAL ON SITE SHALL BE DISPOSED OFF
TO PROPER LOCATIONS AFTER CONSTRUCTIONS.

LEGEND

C2

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

CONSULTANT APPROVAL STAMP

SITE INFORMATION

NAME

ADDRESS

CONTACT NO.

SITE ID: YN0878_YAT20212

IGT APPROVAL

NAME

SIGNATURE

DATE

SHEET CONTENTS:

SHEET NO.

SITE NAME:
LAND OWNER

U Zaw Win

447, Ywar Street, Lat KhoteKone,


KunChanKone Tsp.

09-420017477

YAT20212_KunChanKone

DISTRICT

KunChanKone
_
:

REGION

TOWN
LONGITUDE
COORDINATES
LATTITUDE

APPROVED
CANIDATE
C2

DRAWN

MYINT MYAT

13 Oct 2015

KRISHAN TANEJA

APPROVED

KRISHAN TANEJA

DWG. NO.

Yangon

2A

LOCATION PLAN

CHECKED

RELEASED
FOR

IGT_C2_LOCATION PLAN_REV_00
PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

14

CDC APPROVAL STAMP

GENERAL NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.
3. CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER IN
ADVANCE OF ANY CHANGES ON SITE THAT DO NOT
CONFORM TO THE DESIGN SPECIFICATIONS AND
REQUIREMENTS IN THE DETAILED DETAIL DESIGN DWGS.
4. ANY CHANGES ON THE EXECUTION OF WORK AND SITE
METHODOLOGY SHALL BE CARRIED OUT ONLY UPON
WRITTEN APPROVAL FROM AN ENGINEER.
5. NO WORKS SHALL BE EXECUTED UNLESS ALL NECESSARY
CONSTRUCTION PERMITS ARE OBTAINED AND APPROVED
BY THE CUSTOMER.

CONSTRUCTION NOTES
1. CONTRACTOR SHALL ENSURE THAT ALL EXISTING UNDER
GROUND & ABOVEGROUND SERVICES & UTILITIES FOUND
WITHIN THE SITE PERIMETER AND NOT INDICATED IN THE
DETAILED DESIGN DRAWING SHALL BE REPORTED TO THE
PROPER MANAGEMENT AND PROTECTED FROM ANY
FURTHER DAMAGES DURING CONSTRUCTION.
2. ALL HEALTH & SAFETY POLICIES AND PROCEDURES SHALL
BE STRICTLY IMPLEMENTED DURING CONSTRUCTION.
3. CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES
FOR THE USE OF TOOLS AND EQUIPMENTS ON SITE, WHICH
MAY AFFECT THE STRUCTURAL SOUNDNESS OF ANY
ADJACENT STRUCTURES.
4. ALL REFERENCES FOR AZIMUTH READING AND ANGULAR
POSITIONS SHALL BE FROM TRUE GEOGRAPHICAL NOTH.
5. ALL EXCESS MATERIAL ON SITE SHALL BE DISPOSED OFF
TO PROPER LOCATIONS AFTER CONSTRUCTIONS.

LEGEND

C2

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

CONSULTANT APPROVAL STAMP

SITE INFORMATION

NAME

ADDRESS

CONTACT NO.

SITE ID: YN0878_YAT20212

IGT APPROVAL

NAME

SIGNATURE

DATE

SHEET CONTENTS:

SHEET NO.

SITE NAME:
LAND OWNER

U Zaw Win

447, Ywar Street, Lat KhoteKone,


KunChanKone Tsp.

09-420017477

YAT20212_KunChanKone

DISTRICT

KunChanKone
_
:

REGION

TOWN
LONGITUDE
COORDINATES
LATTITUDE

APPROVED
CANIDATE
C2

DRAWN

MYINT MYAT

CHECKED

KRISHAN TANEJA

APPROVED

KRISHAN TANEJA

13 Oct 2015

GOOGLE MAP WITH COORDINATES 2B


DWG. NO.

Yangon

RELEASED
FOR

IGT_C2_GOOGLE MAP_REV_00
PRELIMINARY

TENDER

INFORMATION

APPROVAL

14
CONSTRUCTION

CDC APPROVAL STAMP

CONSTRUCTION NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS


OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.
3. MAGNETIC NORTH TO BE VERIFIED ON THE SITE BY THE
CONTRACTOR PRIOR TO INSTALLATION OF ANTENNA
MOUNTS.
4. HIGH CARE TO BE TAKEN TO AVOID ANY DAMAGE DURING
EXCAVATION BY PROVIDING PROPER SHORING.
5. CABLE TRAY/LADDER SHALL BE HOT DIP GALVANIZED.
6. HOT WORKS LIKE WELDING ON TOWER FOUNDATIONS
IS NOT ALLOWED ON SITE UNLESS OTHERWISE APPROVED
BY ENGINEERING DEPARTMENT.

LEGEND

C2

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

CONSULTANT APPROVAL STAMP

SITE INFORMATION

NAME

ADDRESS

CONTACT NO.

SITE ID: YN0838_YAT20212

IGT APPROVAL

NAME

SIGNATURE

DATE

SHEET CONTENTS:

SHEET NO.

SITE NAME:
LAND OWNER

U Zaw Win

447, Ywar Street, Lat KhoteKone,


KunChanKone Tsp.

09-420017477

YAT20212_KunChanGone
TOWN

LONGITUDE
COORDINATES
LATTITUDE

APPROVED
CANIDATE
C2

DISTRICT
REGION

Kun Chan Kone


:
:
YANGON
:

DRAWN

MYINT MYAT

CHECKED

KRISHAN TANEJA

APPROVED

KRISHAN TANEJA

13-Oct-2015

SITE LAYOUT

EKI TYPE TOWER


(37m,195Kmph,150Kpa)Access
DWG. NO.
RELEASED
FOR

IGT_C2_SITELAYOUT_REV_01
PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

14

CDC APPROVAL STAMP

CONSTRUCTION NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.
3. MAGNETIC NORTH TO BE VERIFIED ON THE SITE BY THE
CONTRACTOR PRIOR TO INSTALLATION OF ANTENNA
MOUNTS.
4. ANTENNA ELEVATIONS SHOULD BE MEASURED FROM
TOWER BASE PLATE.
5. HIGH CARE TO BE TAKEN TO AVOID ANY DAMAGE DURING
EXCAVATION BY PROVIDING PROPER SHORING.
6. USE IMPORTED BACKFILLING MATERIALS OR ANY OTHER
SUITABLE MATERIALS SUBJECT FOR APPROVAL FROM
IGT-ENGINEERING DEPARTMENT.
7. BACKFILL MATERIALS TO BE PLACED IN 150MM LAYERS
AND COMPACTED TO 95% OF THE MAX. DRY DENSITY IN
ACCORDANCE WITH ASTM D1556.
8. CABLE TRAY/LADDER SHALL BE HOT DIP GALVANIZED.
9. HOT WORKS LIKE WELDING ON TOWER FOUNDATIONS
IS NOT ALLOWED ON SITE UNLESS OTHERWISE APPROVED
BY ENGINEERING DEPARTMENT.

LEGEND

C2

- APPROVED CANDIDATE NUMBER

AZ

- AZIMUTH

EL

- ELEVEATION

MW

- MW ANTENNA

FGL

- FINISHED GRADE LINE

CONSULTANT APPROVAL STAMP

SITE INFORMATION

NAME

ADDRESS

CONTACT NO.

SITE ID: YN0838_YAT20212

IGT APPROVAL

NAME

SIGNATURE

DATE

SHEET CONTENTS:

SITE NAME:
LAND OWNER

U Zaw Win

LONGITUDE

447, Ywar Street, Lat KhoteKone,


KunChanKone Tsp.

09-420017477

APPROVED
CANIDATE

COORDINATES
LATTITUDE

C2

YAT20212_KunChanGone
TOWN

DISTRICT

REGION

Kun Chan Kone


YANGON

DRAWN

MYINT MYAT

CHECKED

KRISHAN TANEJA

APPROVED

KRISHAN TANEJA

SHEET NO.

ELEVATION LAYOUT

13-Oct-2015

4B

EKI TYPE TOWER


(37m,195Kmph,150 kpa)Access
DWG. NO.
RELEASED
FOR

IGT_C2_ELEVATION_REV_01
PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

14

CDC APPROVAL STAMP

CONSTRUCTION NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.
3. MAGNETIC NORTH TO BE VERIFIED ON THE SITE BY THE
CONTRACTOR PRIOR TO INSTALLATION OF ANTENNA
MOUNTS.
4. ANTENNA ELEVATIONS SHOULD BE MEASURED FROM
TOWER BASE PLATE.
5. HIGH CARE TO BE TAKEN TO AVOID ANY DAMAGE DURING
EXCAVATION BY PROVIDING PROPER SHORING.
6. USE IMPORTED BACKFILLING MATERIALS OR ANY OTHER
SUITABLE MATERIALS SUBJECT FOR APPROVAL FROM
IGT-ENGINEERING DEPARTMENT.
7. BACKFILL MATERIALS TO BE PLACED IN 150MM LAYERS
AND COMPACTED TO 95% OF THE MAX. DRY DENSITY IN
ACCORDANCE WITH ASTM D1556.
8. CABLE TRAY/LADDER SHALL BE HOT DIP GALVANIZED.
9. HOT WORKS LIKE WELDING ON TOWER FOUNDATIONS
IS NOT ALLOWED ON SITE UNLESS OTHERWISE APPROVED
BY ENGINEERING DEPARTMENT.

LEGEND

C2

- APPROVED CANDIDATE NUMBER

AZ

- AZIMUTH

EL

- ELEVEATION

MW

- MW ANTENNA

FGL

- FINISHED GRADE LINE

CONSULTANT APPROVAL STAMP

SITE INFORMATION

NAME

ADDRESS

CONTACT NO.

SITE ID: YN0838_YAT20212

IGT APPROVAL

NAME

SIGNATURE

DATE

SHEET CONTENTS:

SITE NAME:
LAND OWNER

U Zaw Win

447, Ywar Street, Lat KhoteKone,


KunChanKone Tsp.

09-420017477

YAT20212_KunChanGone
TOWN

LONGITUDE
COORDINATES
LATITUDE

APPROVED
CANDIDATE
C2

DISTRICT
REGION

Kun Chan Kone


:
: YANGON
:

DRAWN

MYINT MYAT

CHECKED

KRISHAN TANEJA

APPROVED

KRISHAN TANEJA

SHEET NO.

ELEVATION LAYOUT

13-Oct-2015

4B

EKI TYPE TOWER


(37m,195Kmph,150Kpa)Access
DWG. NO.
RELEASED
FOR

IGT_C2_ELEVATION_REV_01
PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

14

CDC APPROVAL STAMP

CONSTRUCTION NOTES

1.

ALL DIMENSIONS SHALL BE IN MILLIMETERS UNLESS


OTHERWISE NOTED.

2.

CABLE GANTRY SHALL BE EARTHED/BOUNDED AT THE


EQUIPMENT AND AT THE TOWER.

3.

AFTER THE INSTALLATION OF THE EARTHING SYSTEM


THE RESISTANCE TO EARTH SHALL BE TESTED IN
ACCORDANCE WITH EARTHING TEST PROCEDURE FOR
GSM SITES.

4.

ANTI-CORROSION COMPOUND SHALL BE APPLIED AFTER


TERMINATION AND MECHANICAL WELD CONNECTION.

5.
OF PROTECTION TO THE ANTENNA OF THE TOWER.
6.

GROUNDING TEST RESISTANCE SHOULD BE


< OR = TO 5 OHMS.
LEGEND

- EARTHING INSPECTION PIT WITH EARTH ROD


- BOLTED CONNECTION
- MECHANICAL WELD CONNECTION
- 25mmX3mm COPPER TAPE
- EARTHING BUS BAR
- EARTH ROD, 2400mm LONG x 3/4' DIA.

- EARTH ROD 1200/1500mm LONG

CONSULTANT APPROVAL STAMP

SITE INFORMATION

NAME

ADDRESS

CONTACT NO.

SITE ID: YN0838_YAT20212

IGT APPROVAL

NAME

SIGNATURE

DATE

SHEET CONTENTS:

SITE NAME:
LAND OWNER

U Zaw Win

LONGITUDE
COORDINATES
LATITUDE

447, Ywar Street, Lat KhoteKone,


KunChanKone Tsp.

09-420017477

APPROVED
CANDIDATE
C2

YAT20212_KunChanGone

DRAWN

MYINT MYAT

TOWN

Kun Chan Kone

CHECKED

KRISHAN TANEJA

DISTRICT

REGION

YANGON

APPROVED

KRISHAN TANEJA

SHEET NO.

SITE EARTHING LAYOUT

13-Oct-2015

EKI TYPE TOWER


(37m,195Kmph,150Kpa)Access
DWG. NO.
RELEASED
FOR

IGT_C2_TOWER EARTHING_REV_01
PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

14

CDC APPROVAL STAMP

CONSTRUCTION NOTES

1.

ALL DIMENSIONS SHALL BE IN MILLIMETERS UNLESS


OTHERWISE NOTED.

2.

CABLE GANTRY SHALL BE EARTHED/BOUNDED AT THE


EQUIPMENT AND AT THE TOWER.

3.

AFTER THE INSTALLATION OF THE EARTHING SYSTEM


THE RESISTANCE TO EARTH SHALL BE TESTED IN
ACCORDANCE WITH EARTHING TEST PROCEDURE FOR
GSM SITES.

4.

ANTI-CORROSION COMPOUND SHALL BE APPLIED AFTER


TERMINATION AND MECHANICAL WELD CONNECTION.

5.
OF PROTECTION TO THE ANTENNA OF THE TOWER.
6.

GROUNDING TEST RESISTANCE SHOULD BE


< OR = TO 5 OHMS.

LEGEND

- EARTHING INSPECTION PIT WITH EARTH ROD


- BOLTED CONNECTION
- MECHANICAL WELD CONNECTION
- 25mmX3mm COPPER TAPE
- EARTHING BUS BAR
- EARTH ROD, 2400mm LONG x 3/4' DIA.
- 25mm Y/G GROUNDING WIRE

CONSULTANT APPROVAL STAMP

SITE INFORMATION

NAME

ADDRESS

CONTACT NO.

SITE ID: YN0838_YAT20212

IGT APPROVAL

NAME

SIGNATURE

DATE

SHEET CONTENTS:

SITE NAME:
LAND OWNER

U Zaw Win

LONGITUDE
COORDINATES
LATITUDE

447, Ywar Street, Lat KhoteKone,


KunChanKone Tsp.

09-420017477

APPROVED
CANDIDATE
C2

YAT20212_KunChanGone
TOWN

DISTRICT

REGION

Kun Chan Kone


YANGON

DRAWN

MYINT MYAT

CHECKED

KRISHAN TANEJA

APPROVED

KRISHAN TANEJA

SHEET NO.

TOWER EARTHING LAYOUT

13-Oct-2015

EKI TYPE TOWER


(37m,195Kmph,150Kpa)Access
DWG. NO.
RELEASED
FOR

IGT_C2_ELEVATION_REV_01
PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

6
14

CDC APPROVAL STAMP

3500
M12x25

12mmx75mm Long
Anchor fastener 2Nos

12mm HOLE GROUNDING

FGL

Angle Cleat
( 50x50x5mm , 100mm Long)

25

100

450
700
800

M12 bolts

1650

3. ANY CHANGES ON THE EXECUTION OF WORK AND SITE


METHODOLOGY SHALL BE CARRIED OUT ONLY UPON
WRITTEN APPROVAL FROM AN ENGINEER.

25

100

FRONT VIEW

B
RCC
Pedestal

RCC Pedestal

GENERAL NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER IN
ADVANCE OF ANY CHANGES ON SITE THAT DO NOT
CONFORM TO THE DESIGN SPECIFICATIONS AND
REQUIREMENTS IN THE DETAILED DETAIL DESIGN DWGS.

TO
GROUNDING
RING

50

250

350

300

400

FGL

300

EQUIPMENT PLATFORM
AS PER DRAWING

100

1500

200

45

4. NO WORKS SHALL BE EXECUTED UNLESS ALL NECESSARY


CONSTRUCTION PERMITS ARE OBTAINED AND APPROVED
BY THE CUSTOMER.

SIDE VIEW
700

CONSTRUCTION NOTES

45x45x4

TOP VIEW

70x70x4, 45mm LONG

45

4. ALL REFERENCES FOR AZIMUTH READING AND ANGULAR


POSITIONS SHALL BE FROM TRUE GEOGRAPHICAL NOTH.
5. ALL EXCESS MATERIAL ON SITE SHALL BE DISPOSED OFF
TO PROPER LOCATIONS AFTER CONSTRUCTIONS.

350

Detail B

450

25

25

LEGEND

HORIZONTAL CABLE TRAY


FLAT 40mm x 4mm

400

C1

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

Detail A
45x45x4

500

45

CONSULTANT APPROVAL STAMP

450

300

100

25

SIDE VIEW

500

1. CONTRACTOR SHALL ENSURE THAT ALL EXISTING UNDER


GROUND & ABOVEGROUND SERVICES & UTILITIES FOUND
WITHIN THE SITE PERIMETER AND NOT INDICATED IN THE
DETAILED DESIGN DRAWING SHALL BE REPORTED TO THE
PROPER MANAGEMENT AND PROTECTED FROM ANY
FURTHER DAMAGES DURING CONSTRUCTION.
2. ALL HEALTH & SAFETY POLICIES AND PROCEDURES SHALL
BE STRICTLY IMPLEMENTED DURING CONSTRUCTION.
3. CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES
FOR THE USE OF TOOLS AND EQUIPMENTS ON SITE, WHICH
MAY AFFECT THE STRUCTURAL SOUNDNESS OF ANY
ADJACENT STRUCTURES.

650

400
TO TOWER

45x45x4

M12 BOLTS

RCC
Pedestal

45

8
80 0

450

2200MAX

FLAT40mm x 4mm

40
25
150

500

GENERIC HORIZONTAL CABLE TRAY LAYING PLAN


(CABLE TRAY WIDTH - 450mm)

500
3000
PLAN VIEW

HORIZONTAL CABLE TRAY

IGT APPROVAL
DRAWN

STANDARD DRAWING

NAME
YAN NAING

SIGNATURE

DATE

DRAWING NUMBER

SHEET CONTENTS:

IGT_STD_HORIZONTAL CABLE TRAY-GBT_REV_01

CHECKED

APPROVED

KRISHAN TANEJA

RELEASED FOR

PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

HORIZONTAL CABLE TRAY


DETAIL DRAWING

SHEET NO.

1
1

BARREL BOLT
250

150

70

150

12mm HOLE

158

WEEP HOLE

80

CDC APPROVAL STAMP

400
WELDED
60-13 IN LINE
DE1/16

PCC ( 1 : 2 : 4 )

150

40x40x5 IS ANGLE

25mm CHAMFER

75mm
50mm GRAVEL LAYER

DETAIL C

DETAIL A

150

40x40x5 IS ANGLE

100mm COMPACTED EARTH


BACKFILL(EXTRA)

25

23

50mm PVC PIPE


1425

1375

50

GENERAL NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.

200

50

50

450

500

17

150mm HINGE
3Nos EACH SIDE

150

50

400

DETAIL (M)

3. CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER IN


ADVANCE OF ANY CHANGES ON SITE THAT DO NOT
CONFORM TO THE DESIGN SPECIFICATIONS AND
REQUIREMENTS IN THE DETAILED DETAIL DESIGN DWGS.
4. ANY CHANGES ON THE EXECUTION OF WORK AND SITE
METHODOLOGY SHALL BE CARRIED OUT ONLY UPON
WRITTEN APPROVAL FROM AN ENGINEER.
5. NO WORKS SHALL BE EXECUTED UNLESS ALL NECESSARY
CONSTRUCTION PERMITS ARE OBTAINED AND APPROVED
BY THE CUSTOMER.

DETAIL A
DETAIL C
45x45x5 IS ANGLE

1400

1800

150

3000

CONSTRUCTION NOTES
1. CONTRACTOR SHALL ENSURE THAT ALL EXISTING UNDER
GROUND & ABOVEGROUND SERVICES & UTILITIES FOUND
WITHIN THE SITE PERIMETER AND NOT INDICATED IN THE
DETAILED DESIGN DRAWING SHALL BE REPORTED TO THE
PROPER MANAGEMENT AND PROTECTED FROM ANY
FURTHER DAMAGES DURING CONSTRUCTION.

STIRRUPS(BS1)

PCC ( 1 : 2 : 4 )

100

30
150

150

GRAVEL LAYER
75mm
50mm THICKNESS

SITE RING BEAM

25mm CHAMFER

30

200

150

100

FGL
12mm DROP BOLT

FENCE POLE
FOUNDATION

BS1
500

450

50

5. ALL EXCESS MATERIAL ON SITE SHALL BE DISPOSED OFF


TO PROPER LOCATIONS AFTER CONSTRUCTIONS.

50

SECTION B - B

3000

4. ALL REFERENCES FOR AZIMUTH READING AND ANGULAR


POSITIONS SHALL BE FROM TRUE GEOGRAPHICAL NOTH.

COMPACTED
BACKFILL 100mm
below gravel bed

@ c/c 250 mm

GATE RAMP

2. ALL HEALTH & SAFETY POLICIES AND PROCEDURES SHALL


BE STRICTLY IMPLEMENTED DURING CONSTRUCTION.
3. CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES
FOR THE USE OF TOOLS AND EQUIPMENTS ON SITE, WHICH
MAY AFFECT THE STRUCTURAL SOUNDNESS OF ANY
ADJACENT STRUCTURES.

150
400

LEGEND

DETAIL D

SECTION A - A
25x3 GI FLAT BOLTED(M10x80)@EVERY 300mm c/c
TO HOLD WIRE MESH
15m

9 Gauge Tension Wire,


Knit Through the Fence at
Top & Middle with Strainer
at Each End

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

CONSULTANT APPROVAL STAMP

50

1.5m

1.5m

1.5m

1.5m

1.5m

1.5m

1.5m

ENTRY GATE 3m

PCC(1:5:10)

INCLINED SUPPORT MEMBER(M)


IS ANGLE 40x40x5

230mm thickness BRICKWORK


IN CM 1:5

IGT APPROVAL
DRAWN

NAME

1.5m

WELD WIRE MESH 3.5mm THICK WITH


APPERTURE 65mm x 65mm

WIRE MESH GROUTED 25mm


IN CONCRETE BEAM

NOTE : ONLY GALVANIZED IRON TO BE USED FOR FENCE MATERIAL

STANDARD DRAWING

DETAIL C

50

50

450

NGL
GATE RAMP

150

150

3000

1800

50

450

C1

SIGNATURE

DATE

DRAWING NUMBER

YAN NAING

SHEET CONTENTS:

IGT_STD_FENCING_REV_01

FENCING
DETAIL DRAWING

CHECKED

APPROVED

KRISHAN TANEJA

RELEASED FOR

PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

SHEET NO.

1
1

CDC APPROVAL STAMP

GENERAL NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.
3. CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER IN
ADVANCE OF ANY CHANGES ON SITE THAT DO NOT
CONFORM TO THE DESIGN SPECIFICATIONS AND
REQUIREMENTS IN THE DETAILED DETAIL DESIGN DWGS.
4. ANY CHANGES ON THE EXECUTION OF WORK AND SITE
METHODOLOGY SHALL BE CARRIED OUT ONLY UPON
WRITTEN APPROVAL FROM AN ENGINEER.
5. NO WORKS SHALL BE EXECUTED UNLESS ALL NECESSARY
CONSTRUCTION PERMITS ARE OBTAINED AND APPROVED
BY THE CUSTOMER.

CONSTRUCTION NOTES
1. CONTRACTOR SHALL ENSURE THAT ALL EXISTING UNDER
GROUND & ABOVEGROUND SERVICES & UTILITIES FOUND
WITHIN THE SITE PERIMETER AND NOT INDICATED IN THE
DETAILED DESIGN DRAWING SHALL BE REPORTED TO THE
PROPER MANAGEMENT AND PROTECTED FROM ANY
FURTHER DAMAGES DURING CONSTRUCTION.
2. ALL HEALTH & SAFETY POLICIES AND PROCEDURES SHALL
BE STRICTLY IMPLEMENTED DURING CONSTRUCTION.
3. CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES
FOR THE USE OF TOOLS AND EQUIPMENTS ON SITE, WHICH
MAY AFFECT THE STRUCTURAL SOUNDNESS OF ANY
ADJACENT STRUCTURES.
4. ALL REFERENCES FOR AZIMUTH READING AND ANGULAR
POSITIONS SHALL BE FROM TRUE GEOGRAPHICAL NOTH.
5. ALL EXCESS MATERIAL ON SITE SHALL BE DISPOSED OFF
TO PROPER LOCATIONS AFTER CONSTRUCTIONS.

LEGEND

C1

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

CONSULTANT APPROVAL STAMP

IGT APPROVAL
DRAWN

STANDARD DRAWING

NAME
May Thu Aung

SIGNATURE

DATE

DRAWING NUMBER

SHEET CONTENTS:

IGT_STD_EARTHING TEST PIT_REV_01


EARTHING /GROUNDING
TEST PIT

CHECKED

APPROVED

KRISHAN TANEJA

RELEASED FOR

PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

SHEET NO.

1
1

CDC APPROVAL STAMP

GSM Antenna

Battery pack
Enersys
4x12 Volt
AGM 4x190 Ah

Eltek Power and


Battery Cabinet

GENERAL NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.

AC Socket
with RCB
16A/30mA

3. CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER IN


ADVANCE OF ANY CHANGES ON SITE THAT DO NOT
CONFORM TO THE DESIGN SPECIFICATIONS AND
REQUIREMENTS IN THE DETAILED DETAIL DESIGN DWGS.
4. ANY CHANGES ON THE EXECUTION OF WORK AND SITE
METHODOLOGY SHALL BE CARRIED OUT ONLY UPON
WRITTEN APPROVAL FROM AN ENGINEER.

FCU

5. NO WORKS SHALL BE EXECUTED UNLESS ALL NECESSARY


CONSTRUCTION PERMITS ARE OBTAINED AND APPROVED
BY THE CUSTOMER.
Rectifier

CONSTRUCTION NOTES
Customer 1 PDU
BTS
Load
Low Prio

2x1,5mm
2x1,5mm
2x25mm

5x6mm
(Rectifier
Configuration see
page 2)

Genset Control

AC Socket
with RCB
16A/30mA

2x16mm

BTS
Load
High Prio

Emergency Stop
MCB
4x25A

ATS

Subsystem #3

2. ALL HEALTH & SAFETY POLICIES AND PROCEDURES SHALL


BE STRICTLY IMPLEMENTED DURING CONSTRUCTION.
3. CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES
FOR THE USE OF TOOLS AND EQUIPMENTS ON SITE, WHICH
MAY AFFECT THE STRUCTURAL SOUNDNESS OF ANY
ADJACENT STRUCTURES.
4. ALL REFERENCES FOR AZIMUTH READING AND ANGULAR
POSITIONS SHALL BE FROM TRUE GEOGRAPHICAL NOTH.

MCB
4x25A
Fueltank

1. CONTRACTOR SHALL ENSURE THAT ALL EXISTING UNDER


GROUND & ABOVEGROUND SERVICES & UTILITIES FOUND
WITHIN THE SITE PERIMETER AND NOT INDICATED IN THE
DETAILED DESIGN DRAWING SHALL BE REPORTED TO THE
PROPER MANAGEMENT AND PROTECTED FROM ANY
FURTHER DAMAGES DURING CONSTRUCTION.

5. ALL EXCESS MATERIAL ON SITE SHALL BE DISPOSED OFF


TO PROPER LOCATIONS AFTER CONSTRUCTIONS.

2x1,5mm

L1

Customer 2 PDU

L2
L3

Integrated in
Genset

BTS
Load
Low Prio

2x25mm

2x1,5mm
Genset
subsystem #2

GEKO 20kVA

Heliocentris
Energymanager

BTS
Load
High Prio

AC Socket
with RCB
16A/30mA

2x1,5mm

4xSPD, Type 2
20kA/40kA(8/20 s)

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

CONSULTANT APPROVAL STAMP

IGT APPROVAL
DRAWN

STANDARD DRAWING

LEGEND

C1

NAME

SIGNATURE

DATE

DRAWING NUMBER

YAN NAING

SHEET CONTENTS:

IGT_STD_SINGLE LINE DIAGRAM_=REV_01

CHECKED

APPROVED

KRISHAN TANEJA

RELEASED FOR

PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

SINGLE LINE DIAGRAM


DETAIL DRAWING

SHEET NO.

1
2

CDC APPROVAL STAMP

Overview of the
Rectifier Configuration

-48V

MCCB
100A

GND

Batt 1

MCCB
100A

Batt 2

MCCB
100A

Batt 3

Customer 1 PDU

LVBD

3x3kW
Rectifier

MCCB
100A

L1

GENERAL NOTES

Batt 4

MCB
32A

TeleNor HP 2

MCB
32A

TeleNor HP 2

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS


OTHERWISE NOTED.
2. ALL ELEVATIONS ARE IN METERS.
3. CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER IN
ADVANCE OF ANY CHANGES ON SITE THAT DO NOT
CONFORM TO THE DESIGN SPECIFICATIONS AND
REQUIREMENTS IN THE DETAILED DETAIL DESIGN DWGS.
4. ANY CHANGES ON THE EXECUTION OF WORK AND SITE
METHODOLOGY SHALL BE CARRIED OUT ONLY UPON
WRITTEN APPROVAL FROM AN ENGINEER.

1xSPD, Type
15kA/30kA(8/20 s)
GND Bus
MCB
4A

L2

MCB
2A

L3

~
=
N

GND Bus

5. NO WORKS SHALL BE EXECUTED UNLESS ALL NECESSARY


CONSTRUCTION PERMITS ARE OBTAINED AND APPROVED
BY THE CUSTOMER.

FCU
MCB
63A

TeleNor LP 1

MCB
63A

TeleNor LP 2

Cabinet light

MCB
2A

Smoke detector

MCB
6A

AWL

MCB
6A

Outdoor light

MCB
6A

EM

MCB
2A

LAN switch

CONSTRUCTION NOTES
1. CONTRACTOR SHALL ENSURE THAT ALL EXISTING UNDER
GROUND & ABOVEGROUND SERVICES & UTILITIES FOUND
WITHIN THE SITE PERIMETER AND NOT INDICATED IN THE
DETAILED DESIGN DRAWING SHALL BE REPORTED TO THE
PROPER MANAGEMENT AND PROTECTED FROM ANY
FURTHER DAMAGES DURING CONSTRUCTION.

1xSPD, Type
15kA/30kA(8/20 s)
AC Socket
with RCB
16A/30A

2. ALL HEALTH & SAFETY POLICIES AND PROCEDURES SHALL


BE STRICTLY IMPLEMENTED DURING CONSTRUCTION.
3. CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES
FOR THE USE OF TOOLS AND EQUIPMENTS ON SITE, WHICH
MAY AFFECT THE STRUCTURAL SOUNDNESS OF ANY
ADJACENT STRUCTURES.

Customer 2 PDU
MCB
32A

1xSPD, Type
15kA/30kA(8/20 s)

MCB
32A

Customer2
HP 1

4. ALL REFERENCES FOR AZIMUTH READING AND ANGULAR


POSITIONS SHALL BE FROM TRUE GEOGRAPHICAL NOTH.

Customer2
HP 2

5. ALL EXCESS MATERIAL ON SITE SHALL BE DISPOSED OFF


TO PROPER LOCATIONS AFTER CONSTRUCTIONS.

1xSPD, Type
15kA/30kA(8/20 s)

GND Bus
LEGEND
MCB
63A

LVLD

MCB
63A

Customer2
LP 1
Customer2
LP 2

C1

- APPROVED CANDIDATE NUMBER

REV

- REVISION NO.

IGT

- IRRAWADDY GREEN TOWERS

STD

- STANDARD DRAWING

1xSPD, Type
15kA/30kA(8/20 s)

GND Bus
AC Socket
with RCB
16A/30A

IGT APPROVAL
DRAWN

STANDARD DRAWING

NAME

SIGNATURE

DATE

CONSULTANT APPROVAL STAMP

DRAWING NUMBER

YAN NAING

SHEET CONTENTS:

IGT_STD_SINGLE LINE DIAGRAM_=REV_01

CHECKED

APPROVED

KRISHAN TANEJA

RELEASED FOR

PRELIMINARY

TENDER

INFORMATION

APPROVAL

CONSTRUCTION

SINGLE LINE DIAGRAM


DETAIL DRAWING

SHEET NO.

1
2