DEFLECTION CALCULATION / SUPPORT SPAN CALCULATION FOR ABOVE GROUND PIP

S.No

Description
1 Line Size (ID)

2 Internal Working Pressure

3 Allowable Stress Value


4 Minimum Calculated Thickness
5 Selected Thickness

Calculated OD of Pipe

Dead Load of the Pipe / Mtr


Dead Load of the Pipe / Mtr
Water Load of the Pipe
Water Load of the Pipe
Total Uniform Distributed Load on Pipe
Concentrated weight on pipe
Moment of Inertia
Modulus of Elasticity

Assumed Pipe Span support


Actual Deflection
Allowable Deflection as per AWWA M11
Deflection accepted/not accepted

MOMENT OF INERTIA

BENDING STRESS

PORT SPAN CALCULATION FOR ABOVE GROUND PIPES


Individual Pump Discharge Line
1828.8 mm
1.8288 mtrs

3.5 Kg/cm2
49.77 PSI
18000 PSI
2.528316 mm
2.52 mm
0.00252 mm

Author:
This should be the
minimum thickness
selected as per IS3589.

1833.84 mm
1.83384 mtrs
113.7533208336 Kg/m
1115.9200773776 N/m
2625.4399104 Kg/m
25755.565521024 N/m
26871.4855984016 N/m
0N
0.0060794677 m^4
30000000 PSI
2.07E+11 N/m2
10 m

ACCEPTED

0.0027824 m

0.09144 m

0.0001036947

100129799
7769517757
0.0128875179
12.887517878
16.195