You are on page 1of 1

Base kVA

Base Voltage
p.u. generator reactance

500
415
X'd x base kVA
DG Capacity in kVA

Where X'd is the transient reactance


Considering the transient reactance of DG to be 20% i:e
a) p.u. generator reactance
b) Rated current of Motor
Rating
pf
eff

0.2
9.661432
5
0.8
0.9

Starting current= Rated Currentx6

Motor p.u. impedence at starting

57.96859

12 p.u.

c) Cable impedence from DG to 415V PCC


Cable selected is
No of runs
No of cores
Conductor size
R
X

6
3.5
300
0.123
0.085

Impedence of 300Sqmm Cable=

0.149513 Ohm/km

Impedence for n runs

0.024919

Cable impedence

0.2

You might also like