3.

4 Design of Base Plate


3.4.1 Design of Base Plate C1

Portion
Considered for
plate design
Mx (-)

X (+)

Z
(+)

Mz (-)

CHECK FOR SIZE OF BASE PLATE C1


Node No.
964
Axial Load P
Factored Moment about X-axis, Mpx
Factored Moment about Z-axis, Mpz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

112
1150 kN
380 kNm
15 kNm
15.6 kN
85 kN

Length of base plate along X-axis, Lbp

1200 mm

Width of base plate along Z- axis, Bpb

1200 mm
800 mm
800 mm
100 mm

Depth of column along X-axis , Dx


Depth of column along Z-axis , Dz
Distance betn. edge of base pl.& cl. of bolt, e d
Ultimate stress of bolt in tension stf

470 N/mm2

Yield stress of bolt fyb

295 N/mm2

Characteristic compressive strength of concrete,fck

25 N/mm2

Permissible stress in conc. in bearing, scc

14.06 N/mm2

No Increase in permissible stress in LSD


Max Bearing Pressure, smax =P/A+6xMx/(Lbp2 x Bbp )+6xMz/(Lbp x Bbp2)

1
2.18 N/mm2

smin =P/A-6xMx/(Lbp2 x Bbp )-6xMz/(Lbp x Bbp2)

-0.58 N/mm2

Min Bearing Pressure,


Remarks

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

Base Plate Size is O.K.

LITL-008-CVE-104-R-0101 Sheet

PART1

#REF!

REV

DESIGN OF BOLT

P
Mx

Bpb
Y1/3

100 mm
Y1

con

T
C

Calculation of bolt along Z- axis


Node No.
964
B
Axial force,AP
Moment about X-axis, Mx
Moment about Z-axis, Mz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

112
1150 kN
380 kNm
15 kNm
15.6 kN
85 kN
2.12 N/mm2

smax =P/A+6xMx/(Lbp x Bbp2 )


Min Bearing Pressure, smin =P/A-6xMx/(Lbp x Bbp2 )
Max Bearing Pressure,

-0.52 N/mm2

Distance Y1 = smax x Bpb/ (smax + smin)

963.64 mm

Distance betn. cl. of base pl. & cg. of comp. Force,


Y 2 = B / 2 - Y1 / 3

278.79 mm

Lever arm, Y3 = Bpb - ed - Y1 / 3

778.79 mm

Tension (Taking moment about Compression line)


T=((Mx+Fzxt - P x Y 2) / Y3
Remarks

78.01 kN
bolt required

Dia of bolt
Gross area provided
Net area provided
Tensile capacity of each bolt based on tensile strength
Tensile capacity of each bolt based on concrete break out failure
So, Effective Tensile capacity
No. of bolt per side

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

40 mm
1257 mm2
1006 mm2
337105 N
10872949 N
337105 N
1.00 nos

REV

LENGTH OF BOLT
Length of bolt provided

2700 mm

DESIGN OF STIFFNER PLATE


The stiffner palte is first checked against local buckling assuming a 25 mm
thick stiffner palte
Fy
325 N/mm2
Ts
Gusset outstand
Outstand length
200 mm
D/Ts
8<
11.93
Average height of the stiffner plate should be less than

298.20 mm

Smaller height
Higher height
So average height

298.20 mm

250 mm
325 mm
287.5 mm

<

25 mm

OK

The stiffner is semi compact section


200 mm
distace between flange to edge of base plate
distance between stiffner plate
288 mm
The shear on the stiffner plate
62784 N
62.78 KN
Shear capacity
1385969 N
1386.0 kN
0.6*Vd
831.58 >
62.78 KN
So the moment capacity will not get reduced by the effect of shear.
Bending moment
0 Nmm
Bending capacity
130030776.515152 Nmm
Hence the size of the stiffenr plate is satisfactory.

OK

0.00 KNm
130.03 KNm

OK

Weld connecting column-gusset-base plate


Load on weld
593.75 KN
Assuming an 6 mm weld
Weld size
10 mm
Length of the weld
5026 mm
Load per mm
0.12 kN/mm
Weld capacity
1519.59
1.52 kN/mm
OK
Thickness of the base plate
Three sides fixed
Thickness of the base plate
40 mm
for stiffner plate connected to flange
Plate dimension (three edge fixed)a
288 b
cofficient from roarks b beta 3
1.01
2
From Roark's chart (Table 11.4) str 55.045 N/mm
a/b
2
Strength of the base plate
354.55 N/mm

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

200
1.44
OK

REV

for stiffner plate connected to web


Plate dimension (three edge fixed)a
169 b
cofficient from roarks b beta 3
0.19 a/b
From Roark's chart (TablStress
19.64868 N/mm2
Strength of the base plate
354.55 N/mm2

275.5
0.61343013
OK

Shear capacity of Bolt 218386.2 N


218.39 KN
when the bolts will be in compression, they will be eefective in shear
Total capacity
218.39 KN
>
85 OK
Bolt subjected to cobined shear and tension
Vsb
Factored shear force acting on the
Vdb
Design shear capacity
Tb
Factored tensile force acting on th
Tdb
Design tension capacity
So, Interaction ratio

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

10.63 kN
218.39 kN
19.50 kN
337.10 kN
0.01 <

LITL-008-CVE-104-R-0101

Sheet
#REF!

1 OK

REV

3.4 Design of Base Plate


3.4.1 Design of Base Plate C1

Portion
Considered for
plate design
Mx (-)

X (+)

Z
(+)

Mz (-)

CHECK FOR SIZE OF BASE PLATE C1


Node No.
990
Axial Load P
Factored Moment about X-axis, Mpx
Factored Moment about Z-axis, Mpz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

129
4503 kN
514 kNm
2430 kNm
600 kN
724 kN

Length of base plate along X-axis, Lbp

1200 mm

Width of base plate along Z- axis, Bpb

1200 mm
800 mm
500 mm
100 mm

Depth of column along X-axis , Dx


Depth of column along Z-axis , Dz
Distance betn. edge of base pl.& cl. of bolt, e d
Ultimate stress of bolt in tension stf

470 N/mm2

Yield stress of bolt fyb

295 N/mm2

Characteristic compressive strength of concrete,fck

25 N/mm2

Permissible stress in conc. in bearing, scc

14.06 N/mm2

No Increase in permissible stress in LSD


Max Bearing Pressure, smax =P/A+6xMx/(Lbp2 x Bbp )+6xMz/(Lbp x Bbp2)

1
13.36 N/mm2

smin =P/A-6xMx/(Lbp2 x Bbp )-6xMz/(Lbp x Bbp2)

-7.11 N/mm2

Min Bearing Pressure,


Remarks

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

Base Plate Size is O.K.

LITL-008-CVE-104-R-0101 Sheet

PART1

#REF!

REV

DESIGN OF BOLT

P
Mz

Bpb
Y1/3

100 mm
Y1

con

T
A

Calculation of bolt along Z- axis


Node No.
990
Axial force, P
Moment about X-axis, Mx
Moment about Z-axis, Mz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

129
4503 kN
514 kNm
2430 kNm
600 kN
724 kN
11.54 N/mm2

smax =P/A+6xMx/(Lbp x Bbp2 )


Min Bearing Pressure, smin =P/A-6xMx/(Lbp x Bbp2 )
Max Bearing Pressure,

-5.28 N/mm2

Distance Y1 = smax x Bpb/ (smax + smin)

823.31 mm

Distance betn. cl. of base pl. & cg. of comp. Force,


Y 2 = B / 2 - Y1 / 3

325.57 mm

Lever arm, Y3 = Bpb - ed - Y1 / 3

825.57 mm

Tension (Taking moment about Compression line)


T=((Mx+Fzxt - P x Y 2) / Y3
Remarks

1179.26 kN
bolt required

Dia of bolt
Gross area provided
Net area provided
Tensile capacity of each bolt based on tensile strength
Tensile capacity of each bolt based on concrete break out failure
So, Effective Tensile capacity

337105 N

No. of bolt per side

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

40 mm
1257 mm2
1006 mm2
337105 N
10872949 N
4.00 nos

LITL-008-CVE-104-R-0101

Sheet
#REF!

REV

DESIGN OF STIFFNER PLATE


The stiffner palte is first checked against local buckling assuming a 25 mm
thick stiffner palte
Fy
325 N/mm2
Ts
Gusset outstand
Outstand length
200 mm
D/Ts
8<
11.93
Average height of the stiffner plate should be less than

298.20 mm

Smaller height
Higher height
So average height

298.20 mm

250 mm
325 mm
287.5 mm

<

25 mm

OK

The stiffner is semi compact section


200 mm
distace between flange to edge of base plate
distance between stiffner plate
263 mm
The shear on the stiffner plate
613009 N
613.01 KN
Shear capacity
1385969 N
1386.0 kN
0.6*Vd
831.58 >
613.01 KN
So the moment capacity will not get reduced by the effect of shear.
Bending moment
64291811.1111111 Nmm
Bending capacity
130030776.515152 Nmm
Hence the size of the stiffenr plate is satisfactory.

OK

64.29 KNm
130.03 KNm

OK

Weld connecting column-gusset-base plate


Load on weld
7111.50 KN
Assuming an 6 mm weld
Weld size
10 mm
Length of the weld
4976 mm
Load per mm
1.43 kN/mm
Weld capacity
1519.59
1.52 kN/mm
OK
Thickness of the base plate
Three sides fixed
Thickness of the base plate

40 mm

for stiffner plate connected to flange


Plate dimension (three edge fixed)a
263 b
cofficient from roarks b beta 3
0.71894
From Roark's chart (Table 11.4) str 240.126 N/mm2
a/b
2
Strength of the base plate
354.55 N/mm

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

200
1.315
OK

REV

for stiffner plate connected to web


Plate dimension (three edge fixed)a
169 b
cofficient from roarks b beta 3
0.213 a/b
From Roark's chart (TablStress
135.2489 N/mm2
Strength of the base plate
354.55 N/mm2

275.5
0.613
OK

Shear capacity of Bolt 218386.2 N


218.39 KN
when the bolts will be in compression, they will be eefective in shear
Total capacity
873.54 KN
>
724 OK
Bolt subjected to cobined shear and tension
Vsb
Factored shear force acting on the
Vdb
Design shear capacity
Tb
Factored tensile force acting on th
Tdb
Design tension capacity
So, Interaction ratio

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

90.50 kN
218.39 kN
294.82 kN
337.10 kN
0.94 <

LITL-008-CVE-104-R-0101

Sheet
#REF!

1 OK

REV

3.4 Design of Base Plate


3.4.1 Design of Base Plate C1

Portion
Considered for
plate design
Mx (-)

X (+)

Z
(+)

Mz (-)

CHECK FOR SIZE OF BASE PLATE C1


Node No.
983
Axial Load P
Factored Moment about X-axis, Mpx
Factored Moment about Z-axis, Mpz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

129
4076 kN
1657 kNm
12 kNm
10 kN
412 kN

Length of base plate along X-axis, Lbp


Width of base plate along Z- axis, Bpb

1200 mm
1200 mm
800 mm
800 mm
100 mm

Depth of column along X-axis , Dx


Depth of column along Z-axis , Dz
Distance betn. edge of base pl.& cl. of bolt, e d
Ultimate stress of bolt in tension stf

470 N/mm2

Yield stress of bolt fyb

295 N/mm2

Characteristic compressive strength of concrete,fck


Permissible stress in conc. in bearing, scc

25 N/mm2
13.125 N/mm2

No Increase in permissible stress in LSD


1
2
2
Max Bearing Pressure, smax =P/A+6xMx/(Lbp x Bbp )+6xMz/(Lbp x Bbp )
8.65 N/mm2
-2.99 N/mm2
Min Bearing Pressure, smin =P/A-6xMx/(Lbp2 x Bbp )-6xMz/(Lbp x Bbp2)
Remarks
Base Plate Size is O.K.

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101 Sheet

PART1

#REF!

REV

DESIGN OF BOLT

P
Mz

Bpb
Y1/3

100 mm
Y1

con

Calculation of bolt along X- axis


Node No.
983
Load Case
Axial force, P
Moment about X-axis, Mx
Moment about Z-axis, Mz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz
Max Bearing Pressure, smax =P/A+6xMx/(Lbp x Bbp2 )
Min Bearing Pressure, smin =P/A-6xMx/(Lbp x Bbp2 )

129
4076 kN
1657 kNm
12 kNm
10 kN
412 kN
8.57 N/mm2
-2.91 N/mm2

Distance Y1 = smax x Bpb/ (smax + smin)

895.82 mm

Distance betn. cl. of base pl. & cg. of comp. Force,


Y 2 = B / 2 - Y1 / 3

301.4 mm

Lever arm, Y3 = Bpb - ed - Y1 / 3

801.4 mm

Tension (Taking moment about Compression line)


T=((Mx+Fzxt - P x Y 2) / Y3
Remarks

542.91 kN
bolt required

Dia of bolt
Gross area provided
Net area provided
Tensile capacity of each bolt based on tensile strength
Tensile capacity of each bolt based on concrete break out failure
So, Effective Tensile capacity
No. of bolt per side

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

40 mm
1257 mm2
1006 mm2
337105 N
3632593 N
337105 N
2.00 nos

REV

DESIGN OF STIFFNER PLATE


The stiffner palte is first checked against local buckling assuming a 25 mm
thick stiffner palte
Fy
325 N/mm2
Ts
Gusset outstand
Outstand length
200 mm
D/Ts
8<
11.93
Average height of the stiffner plate should be less than

298.20 mm

Smaller height
Higher height
So average height

298.20 mm

250 mm
325 mm
287.5 mm

<

25 mm

OK

The stiffner is semi compact section


200 mm
distace between flange to edge of base plate
distance between stiffner plate
138 mm
The shear on the stiffner plate
211968 N
211.97 KN
Shear capacity
1385969 N
1386.0 kN
0.6*Vd
831.58 >
211.97 KN
So the moment capacity will not get reduced by the effect of shear.
Bending moment
22089200 Nmm
Bending capacity
130030776.515152 Nmm
Hence the size of the stiffenr plate is satisfactory.

OK

22.09 KNm
130.03 KNm

OK

Weld connecting column-gusset-base plate


Load on weld
4109.25 KN
Assuming an 6 mm weld
Weld size
10 mm
Length of the weld
4726 mm
Load per mm
0.87 kN/mm
Weld capacity
1519.59
1.52 kN/mm
OK
Thickness of the base plate
Three sides fixed
Thickness of the base plate

30 mm

for stiffner plate connected to flange


Plate dimension (three edge fixed)a
138 b
cofficient from roarks b beta 3
0.1644
From Roark's chart (Table 11.4) str63.20267 N/mm2
a/b
2
Strength of the base plate
354.55 N/mm

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

200
0.69
OK

REV

for stiffner plate connected to web


Plate dimension (three edge fixed)a
188 b
cofficient from roarks b beta 3
0.34 a/b
2
From Roark's chart (TablStress
130.7111 N/mm
Strength of the base plate
354.55 N/mm2

200
0.94
OK

Shear capacity of Bolt 218386.2 N


218.39 KN
when the bolts will be in compression, they will be eefective in shear
Total capacity
436.77 KN
>
412 OK
Bolt subjected to cobined shear and tension
Vsb
Factored shear force acting on the
Vdb
Design shear capacity
Tb
Factored tensile force acting on th
Tdb
Design tension capacity
So, Interaction ratio

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

51.50 kN
218.39 kN
135.73 kN
337.10 kN
0.22 <

LITL-008-CVE-104-R-0101

Sheet
#REF!

1 OK

REV

3.4 Design of Base Plate


3.4.1 Design of Base Plate C1

Portion
Considered for
plate design
Mx (-)

X (+)

Z (+)

Mz (-)

CHECK FOR SIZE OF BASE PLATE C1


Node No.
1956
Axial Load P
Factored Moment about X-axis, Mpx
Factored Moment about Z-axis, Mpz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

129
-3215 kN
-172 kNm
-0.484 kNm
6.633 kN
44.882 kN

Length of base plate along X-axis, Lbp

1200 mm

Width of base plate along Z- axis, Bpb

1200 mm

Depth of column along X-axis , Dx


Depth of column along Z-axis , Dz
Distance betn. edge of base pl.& cl. of bolt, e d

800 mm
400 mm
100 mm

Ultimate stress of bolt in tension stf

470 N/mm2

Yield stress of bolt fyb

295 N/mm2

Characteristic compressive strength of concrete,fck

25 N/mm2

Permissible stress in conc. in bearing, scc

14.0625 N/mm2

No Increase in permissible stress in LSD


Max Bearing Pressure, smax =P/A+6xMx/(Lbp2 x Bbp )+6xMz/(Lbp x Bbp2)

1
-2.83 N/mm2

smin =P/A-6xMx/(Lbp2 x Bbp )-6xMz/(Lbp x Bbp2)

-1.64 N/mm2

Min Bearing Pressure,


Remarks

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

Base Plate Size is O.K.

LITL-008-CVE-104-R-0101 Sheet

PART1

#REF!

REV

DESIGN OF BOLT
Calculation of bolt along X- axis
Node No.
1956

Load Case

129

Axial force, P
Moment about X-axis, Mx
Moment about Z-axis, Mz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz
Max Bearing Pressure, smax =P/A+6xMx/(Lbp x Bbp2 )
Min Bearing Pressure,

-3215 kN
-172 kNm
-0.484 kNm
6.633 kN
44.882 kN
-1.64 N/mm2

smin =P/A-6xMx/(Lbp x Bbp2 )

-2.84 N/mm2

Assume No. of bolt per side

4.00 nos

Tension in one side single bolt due to moment

-43000 N

Tension in single bolt due to Axial tension in column

-267916.7 N

Tension on each bolt

310916.67 N

Dia of bolt
Gross area provided

40 mm
1257 mm2

Net area provided

1006 mm2

Tensile capacity of each bolt based on tensile strength


Tensile capacity of each bolt based on concrete break out failure
So, Effective Tensile capacity of each bolt
Remarks

337105 N
9687500 N
337105 N

Bolt capacity satisfied

DESIGN OF STIFFNER PLATE


The stiffner palte is first checked against local buckling assuming a 25 mm
thick stiffner palte
Fy
Gusset outstand
Outstand length
D/Ts

325 N/mm2

8<

Ts

25 mm

200 mm
11.93

Average height of the stiffner plate should be less than


Smaller height
250 mm
Higher height
325 mm
So average height
287.5 mm
<

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

298.20 mm

298.20 mm

Sheet
#REF!

OK

REV

The stiffner is semi compact section


283.5 mm
distace between flange to edge of base plate
distance between stiffner plate
169 mm
The shear on the stiffner plate
-128855 N
-128.85 KN
Shear capacity
1385969 N
1386.0 kN
0.6*Vd
831.58 >
-128.85 KN
So the moment capacity will not get reduced by the effect of shear.
Bending moment
-18583374 Nmm
Bending capacity
130030777 Nmm
Hence the size of the stiffenr plate is satisfactory.

OK

-18.58 KNm
130.03 KNm

OK

Weld connecting column-gusset-base plate


Load on weld
2037.50 KN
Assuming an 6 mm weld
Weld size
10 mm
Length of the weld
4639 mm
Load per mm
0.44 kN/mm
Weld capacity
1519.59
1.52 kN/mm
OK
Thickness of the base plate
Three sides fixed
Thickness of the base plate
30 mm
for stiffner plate connected to flange
Plate dimension (three edge fixed)a
169 b
cofficient from roarks b beta 3
0.224
2
From Roark's chart (Table 11.4) str
-56.73 N/mm
a/b
2
Strength of the base plate
354.55 N/mm
for stiffner plate connected to web
Plate dimension (three edge fixed)a
169 b
cofficient from roarks b beta 3
0.22448325 a/b
From Roark's chart (TablStress
-56.7328 N/mm2
Strength of the base plate
354.55 N/mm2

283.5
0.596
OK

283.5
0.60
OK

Shear capacity of Bolt 218386.2 N


218.39 KN
when the bolts will be in compression, they will be eefective in shear
Total capacity
873.54 KN
>
44.882 OK
Bolt subjected to cobined shear and tension
Vsb
Factored shear force acting on the
Vdb
Design shear capacity
Tb
Factored tensile force acting on th
Tdb
Design tension capacity
So, Interaction ratio

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

5.61 kN
218.39 kN
310.92 kN
337.10 kN
0.85 <

LITL-008-CVE-104-R-0101

Sheet
#REF!

1 OK

REV

3.4 Design of Base Plate


3.4.1 Design of Base Plate C1

Portion
Considered for
plate design
Mx (-)

X (+)

Z
(+)

Mz (-)

CHECK FOR SIZE OF BASE PLATE C1


Node No.
990
Axial Load P
Factored Moment about X-axis, Mpx
Factored Moment about Z-axis, Mpz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

128
1491.1
-2.4
1196.3
260.5
0.8

Length of base plate along X-axis, Lbp

900

Width of base plate along Z- axis, Bpb

1400
800
500
100

Depth of column along X-axis , Dx


Depth of column along Z-axis , Dz
Distance betn. edge of base pl.& cl. of bolt, e d
Ultimate stress of bolt in tension stf

470

Yield stress of bolt fyb

295

Characteristic compressive strength of concrete,fck

25

Permissible stress in conc. in bearing, scc

15.03

No Increase in permissible stress in LSD


Max Bearing Pressure, smax =P/A+6xMx/(Lbp2 x Bbp )+6xMz/(Lbp x Bbp2)

1
7.49

smin =P/A-6xMx/(Lbp2 x Bbp )-6xMz/(Lbp x Bbp2)

-5.12

Min Bearing Pressure,


Remarks

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

Base Plate Size is O.K.

LITL-008-CVE-104-R-0101 Sheet

PART1

#REF!

REV

DESIGN OF BOLT

P
Mz

Bpb
Y1/3

100 mm
Y1

con

T
A

Calculation of bolt along Z- axis


Node No.
990
Axial force, P
Moment about X-axis, Mx
Moment about Z-axis, Mz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

128
1491.1
-2.4
1196.3
260.5
0.8
5.24

smax =P/A+6xMx/(Lbp x Bbp2 )


Min Bearing Pressure, smin =P/A-6xMx/(Lbp x Bbp2 )
Max Bearing Pressure,

-2.88

Distance Y1 = smax x Bpb/ (smax + smin)

903.45

Distance betn. cl. of base pl. & cg. of comp. Force,


Y 2 = B / 2 - Y1 / 3

398.86

Lever arm, Y3 = Bpb - ed - Y1 / 3

998.86

Tension (Taking moment about Compression line)


T=((Mx+Fzxt - P x Y 2) / Y3
Remarks

606.47
bolt required

Dia of bolt
Gross area provided
Net area provided
Tensile capacity of each bolt based on tensile strength
Tensile capacity of each bolt based on concrete break out failure
So, Effective Tensile capacity
No. of bolt per side

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

40
1257
1006
337105
4059698
337105
2.00

REV

LENGTH OF BOLT
Length of bolt provided

1400

DESIGN OF STIFFNER PLATE


The stiffner palte is first checked against local buckling assuming a 25 mm
thick stiffner palte
Fy
325 N/mm2
Ts
Gusset outstand
Outstand length
200 mm
D/Ts
8<
11.93
Average height of the stiffner plate should be less than

298.20 mm

Smaller height
Higher height
So average height

298.20 mm

250 mm
325 mm
287.5 mm

<

25 mm

The stiffner is semi compact section


300.5 mm
distace between flange to edge of base plate
distance between stiffner plate
188 mm
The shear on the stiffner plate
346685 N
346.69 KN
Shear capacity
1385969 N
1386.0 kN
0.6*Vd
831.58 >
346.69 KN
So the moment capacity will not get reduced by the effect of shear.
Bending moment
55918587 Nmm
Bending capacity
130030777 Nmm
Hence the size of the stiffenr plate is satisfactory.

55.92 KNm
130.03 KNm

Weld connecting column-gusset-base plate


Load on weld
3138.22 KN
Assuming an 6 mm weld
Weld size
10 mm
Length of the weld
5429 mm
Load per mm
0.58 kN/mm
Weld capacity
1519.59
1.52 kN/mm
OK
Thickness of the base plate
Three sides fixed
Thickness of the base plate
30 mm
for stiffner plate connected to flange
Plate dimension (three edge fixed)a
188 b
cofficient from roarks b beta 3
0.20560067
From Roark's chart (Table 11.4) str154.5086 N/mm2
a/b
2
Strength of the base plate
354.55 N/mm

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

300.5
0.62562396
OK

REV

for stiffner plate connected to web


Plate dimension (three edge fixed)a
169 b
cofficient from roarks b beta 3
0.317 a/b
2
From Roark's chart (TablStress
80.75676 N/mm
Strength of the base plate
354.55 N/mm2

175
0.97
OK

Shear capacity of Bolt 218386.2 N


218.39 KN
when the bolts will be in compression, they will be eefective in shear
Total capacity
436.77 KN
>
260.55 OK
Bolt subjected to cobined shear and tension
Vsb
Factored shear force acting on the
Vdb
Design shear capacity
Tb
Factored tensile force acting on th
Tdb
Design tension capacity
So, Interaction ratio

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

0.10 kN
218.39 kN
151.62 kN
337.10 kN
0.20 <

LITL-008-CVE-104-R-0101

Sheet
#REF!

REV

128
kN
kNm
kNm
kN
kN
mm
mm
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2

N/mm2
N/mm2

Size is O.K.

128
kN
kNm
kNm
kN
kN
N/mm2
N/mm2
mm
mm
mm
kN

mm
mm2
mm2
N
N
N
nos

mm

OK

OK

OK

OK

3.4 Design of Base Plate


3.4.1 Design of Base Plate C1

Portion
Considered for
plate design
Mx (-)

X (+)

Z
(+)

Mz (-)

CHECK FOR SIZE OF BASE PLATE C1


Node No.
990
Axial Load P
Factored Moment about X-axis, Mpx
Factored Moment about Z-axis, Mpz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

129
1150.0 kN
380.0 kNm
15.0 kNm
15.0 kN
-85.0 kN

Length of base plate along X-axis, Lbp

900 mm

Width of base plate along Z- axis, Bpb

1400 mm
800 mm
500 mm
100 mm

Depth of column along X-axis , Dx


Depth of column along Z-axis , Dz
Distance betn. edge of base pl.& cl. of bolt, e d
Ultimate stress of bolt in tension stf

470 N/mm2

Yield stress of bolt fyb

295 N/mm2

Characteristic compressive strength of concrete,fck

25 N/mm2

Permissible stress in conc. in bearing, scc

15.03 N/mm2

No Increase in permissible stress in LSD


Max Bearing Pressure, smax =P/A+6xMx/(Lbp2 x Bbp )+6xMz/(Lbp x Bbp2)

1
2.28 N/mm2

smin =P/A-6xMx/(Lbp2 x Bbp )-6xMz/(Lbp x Bbp2)

-0.46 N/mm2

Min Bearing Pressure,


Remarks

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

Base Plate Size is O.K.

LITL-008-CVE-104-R-0101 Sheet

PART1

#REF!

REV

DESIGN OF BOLT

P
Mx

Bpb
Y1/3

100 mm
Y1

con

T
A

Calculation of bolt along Z- axis


Node No.
990
Axial force, P
Moment about X-axis, Mx
Moment about Z-axis, Mz
Horizontal Force along X- axis , Fx
Horizontal Force along Z- axis , Fz

Load Case

128
1150.0 kN
380.0 kNm
15.0 kNm
15.0 kN
-85.0 kN
2.21 N/mm2

smax =P/A+6xMx/(Lbp x Bbp2 )


Min Bearing Pressure, smin =P/A-6xMx/(Lbp x Bbp2 )
Max Bearing Pressure,

-0.39 N/mm2

Distance Y1 = smax x Bpb/ (smax + smin)

765.00 mm

Distance betn. cl. of base pl. & cg. of comp. Force,


Y 2 = B / 2 - Y1 / 3

195 mm

Lever arm, Y3 = Bpb - ed - Y1 / 3

545 mm

Tension (Taking moment about Compression line)


T=((Mx+Fzxt - P x Y 2) / Y3
Remarks

283.29 kN
bolt required

Dia of bolt
Gross area provided
Net area provided
Tensile capacity of each bolt based on tensile strength
Tensile capacity of each bolt based on concrete break out failure
So, Effective Tensile capacity
No. of bolt per side

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

40 mm
1257 mm2
1006 mm2
337105 N
4059698 N
337105 N
1.00 nos

REV

LENGTH OF BOLT
Length of bolt provided

1400 mm

DESIGN OF STIFFNER PLATE


The stiffner palte is first checked against local buckling assuming a 25 mm
thick stiffner palte
Fy
325 N/mm2
Ts
Gusset outstand
Outstand length
200 mm
D/Ts
8<
11.93
Average height of the stiffner plate should be less than

298.20 mm

Smaller height
Higher height
So average height

298.20 mm

250 mm
325 mm
287.5 mm

<

25 mm

OK

The stiffner is semi compact section


distace between web side stiffner to edge of base plate
175 mm
distance between stiffner plate
169 mm
The shear on the stiffner plate
59552.55 N
59.55 KN
Shear capacity
1385969 N
1386.0 kN
0.6*Vd
831.58 >
59.55 KN
So the moment capacity will not get reduced by the effect of shear.
Bending moment
5440636 Nmm
Bending capacity
130030777 Nmm
Hence the size of the stiffenr plate is satisfactory.

OK

5.44 KNm
130.03 KNm

OK

Weld connecting column-gusset-base plate


Load on weld
1335.00 KN
Assuming an 6 mm weld
Weld size
10 mm
Length of the weld
4638 mm
Load per mm
0.29 kN/mm
Weld capacity
1519.59
1.52 kN/mm
OK
Thickness of the base plate
Three sides fixed
Thickness of the base plate
30 mm
for stiffner plate connected to webstiffner
Plate dimension (three edge fixed)a
169 b
cofficient from roarks b beta 3
0.31685714
From Roark's chart (Table 11.4) str24.58283 N/mm2
a/b
2
Strength of the base plate
354.55 N/mm

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

LITL-008-CVE-104-R-0101

Sheet
#REF!

175
0.96571429
OK

REV

for stiffner plate connected to flange


Plate dimension (three edge fixed)a
169 b
cofficient from roarks b beta 3
0.317 a/b
From Roark's chart (TablStress
24.58283 N/mm2
Strength of the base plate
354.55 N/mm2

175
0.97
OK

Shear capacity of Bolt 218386.2 N


218.39 KN
when the bolts will be in compression, they will be eefective in shear
Total capacity
218.39 KN
>
15 OK
Bolt subjected to cobined shear and tension
Vsb
Factored shear force acting on the
Vdb
Design shear capacity
Tb
Factored tensile force acting on th
Tdb
Design tension capacity
So, Interaction ratio

2 X 660MW LANCO VIDARBHA TPP


Design of UCB

10.63 kN
218.39 kN
70.82 kN
337.10 kN
0.05 <

LITL-008-CVE-104-R-0101

Sheet
#REF!

1 OK

REV

Design of Anchor Bolt

Sheet
1

PART1

Design of Anchor Bolt: Rectangular bearing stress

REV

distribution is considered in this


analysis

Calculation of Maximum Anchor Bolt Tension &


Identification of Governing Load Case:

B
Anchor Bolt (AB) Dia. d
=
No. of Anchor Bolt/side N =
Size of Column:
l=
b=
Length of Base Plate L
=
Width of Base Plate B
=
C/C of Anchor Bolt A
=
Grade of concrete: fck
=

25 mm
3 Nos.
600 mm
210 mm
900 mm
500 mm
750 mm

25 Mpa

Max. bearing stress concrete pmax

11.25 N/mm2

Maximum Anchor Bolt Tension Tmax

103.33 kN

L/C
Maximum Effective Shear for Anchor
Fmax
Bolt/ Shear Key Design
kN
L/C
Governing Load Case for Base Plate Design : Load Case
On compression side:
On Bolt Tension Side:
Table 1:
Node

L/C

FX (kN)

Vertical
Load FY
(kN)

1001

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

-35.59
-6.02
11.80
4.75
0.32
0.04
-0.01
-0.03
-32.53
-32.52
32.51
32.52
-1.01
-1.00
0.99

-165.23
-130.88
248.85
118.24
6.03
0.87
-0.18
-0.51
-93.66
-93.64
93.57
93.59
-22.55
-22.53
20.40

Bearing
Moment M Contact
FZ (kN)
Length (Y1
(kNm)
in mm)

0.58
-37.21
2.19
0.66
0.02
0.52
0.10
0.22
0.14
0.14
-0.15
-0.15
-9.40
-9.39
6.16

2.48
-175.10
5.11
1.52
0.05
1.22
0.23
-0.37
0.56
0.56
-0.58
-0.57
-36.20
-36.19
28.92

0.00
0.00
858.92
874.31
883.41
0.33
0.00
0.00
0.00
0.00
900.00
900.00
0.00
0.00
7.92

Refer Table 1 below

Anchor Bolt
Tension T
(kN)

28.64
99.63
0.00
0.00
0.00
0.34
0.13
0.25
15.86
15.86
0.00
0.00
19.85
19.84
8.04

Moment at
Effective
column
face due to Shear
(Fi)
bearing
compressio (kN)
n (kNm)

0.00
0.00
2.65
2.60
2.58
5.06
0.00
0.00
0.00
0.00
2.53
2.53
0.00
0.00
5.04

Design of Anchor Bolt


16
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143

0.99
17.70
25.34
25.29
25.27
0.76
0.77
39.79
39.79
19.68
19.68
20.87
20.87
0.71
0.71
39.74
39.74
19.62
19.63
20.82
20.82
0.69
0.69
39.71
39.72
19.60
19.61
20.80
20.80
-1.45
41.25
16.29
23.52
-1.50
41.20
16.24
23.46
-1.52
41.18
16.21
23.44
-18.77
-18.77
59.27

20.43
373.28
560.59
559.49
559.14
392.45
392.47
504.79
504.81
435.12
435.14
460.89
460.91
391.35
391.37
503.69
503.71
434.02
434.03
459.79
459.81
391.00
391.02
503.34
503.36
433.67
433.69
459.44
459.46
342.28
540.56
362.89
519.95
341.18
539.46
361.79
518.85
340.83
539.11
361.44
518.50
335.81
335.83
560.48

PART1
Rectangular
bearing stress
6.16
28.92
7.92
distribution is considered in this
3.29
7.67
858.93
analysis

4.86
4.42
4.54
4.08
4.08
3.91
3.91
-1.64
-1.64
7.70
7.70
3.64
3.64
3.46
3.46
-2.09
-2.08
7.25
7.25
3.76
3.76
3.59
3.59
-1.96
-1.96
7.37
7.38
4.32
3.63
-18.35
26.30
3.88
3.18
-18.79
25.85
4.00
3.31
-18.67
25.98
3.89
3.90
3.54

11.30
10.26
9.63
9.64
9.64
8.95
8.96
-12.42
-12.42
26.65
26.65
8.59
8.60
7.91
7.92
-13.46
-13.46
25.61
25.61
7.96
7.96
7.28
7.28
-14.10
-14.09
24.97
24.98
10.73
7.75
-95.82
114.30
9.69
6.71
-96.86
113.26
9.05
6.07
-97.49
112.62
9.34
9.34
7.97

859.67
863.32
865.56
850.90
850.89
864.52
864.51
900.00
900.00
784.36
784.36
856.09
856.07
868.58
868.57
900.00
900.00
788.62
788.61
859.28
859.28
871.08
871.07
900.00
900.00
791.29
791.28
837.31
871.33
51.58
69.58
843.21
875.13
51.73
69.24
846.87
877.47
51.84
69.06
844.40
844.38
871.55

Sheet
1

REV

8.04
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
-24.24
-42.85
0.00
0.00
-23.60
-43.13
0.00
0.00
-23.27
-43.35
0.00
0.00
0.00

5.04
2.65
2.64
2.63
2.63
2.67
2.67
2.63
2.63
2.53
2.53
2.86
2.86
2.65
2.65
2.62
2.62
2.53
2.53
2.84
2.84
2.65
2.65
2.61
2.61
2.53
2.53
2.84
2.84
2.71
2.61
4.92
4.87
2.69
2.60
4.92
4.87
2.68
2.59
4.92
4.87
2.69
2.69
2.61

Design of Anchor Bolt


144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187

59.28
19.05
19.06
21.44
21.45
-18.80
-18.80
59.25
59.25
19.03
19.03
21.42
21.42
-18.81
-18.81
59.24
59.24
19.01
19.02
21.40
21.41
-22.82
62.59
12.65
27.11
-22.85
62.56
12.63
27.08
-22.86
62.55
12.62
27.07
-31.09
-31.08
66.47
66.48
16.19
16.20
19.18
19.19
-35.68
71.08
8.67

560.51
421.14
421.17
472.69
472.71
335.25
335.28
559.93
559.95
420.58
420.61
472.13
472.16
335.07
335.10
559.75
559.78
420.41
420.44
471.95
471.98
242.69
639.25
283.91
598.03
242.13
638.69
283.36
597.47
241.96
638.52
283.18
597.30
232.78
232.82
513.63
513.67
339.45
339.49
403.88
403.92
125.43
621.13
176.96

PART1
Rectangular
bearing stress
3.55
7.98
871.53
distribution is considered in this
-7.55
-34.77
900.00
analysis

-7.54
11.12
11.12
3.67
3.67
3.32
3.32
-7.77
-7.77
10.89
10.90
3.73
3.73
3.38
3.39
-7.71
-7.71
10.96
10.96
4.40
3.01
-40.94
48.35
4.17
2.79
-41.17
48.12
4.23
2.85
-41.11
48.19
3.50
3.50
3.06
3.07
-10.80
-10.80
12.53
12.53
4.16
2.43
-52.52

-34.77
43.36
43.37
8.81
8.82
7.45
7.45
-35.30
-35.29
42.84
42.84
8.49
8.50
7.13
7.13
-35.62
-35.61
42.52
42.52
11.58
5.62
-201.51
218.72
11.06
5.10
-202.04
218.19
10.74
4.78
-202.36
217.87
8.51
8.51
6.80
6.81
-46.63
-46.62
51.04
51.05
11.39
3.94
-254.98

900.00
716.53
716.52
847.45
847.42
873.40
873.38
900.00
900.00
718.55
718.53
849.33
849.30
874.53
874.51
900.00
900.00
719.83
719.82
804.54
882.41
69.27
101.73
808.66
884.04
69.35
101.55
811.24
885.03
69.41
101.45
826.92
826.88
873.51
873.48
900.00
900.00
647.26
647.25
718.37
887.31
72.42

Sheet
1

REV

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
35.25
-8.60
0.00
0.00
35.58
-8.75
0.00
0.00
35.75
-8.87
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
76.81

2.61
2.53
2.53
3.05
3.05
2.68
2.68
2.61
2.61
2.53
2.53
3.04
3.04
2.67
2.67
2.60
2.60
2.53
2.53
3.04
3.04
2.80
2.58
4.87
4.78
2.79
2.58
4.87
4.78
2.78
2.57
4.87
4.78
2.74
2.74
2.61
2.61
2.53
2.53
3.24
3.24
3.04
2.57
4.86

Design of Anchor Bolt


188
189
190
191
192
193
194
195
196
197
198
199
200

26.74
-38.17
-38.16
59.39
59.40
9.11
9.12
12.10
12.11
-42.76
64.00
1.59
19.66

569.60
83.47
83.51
364.32
364.35
190.14
190.18
254.57
254.61
-23.88
471.82
27.64
420.29

PART1
Rectangular
bearing stress
59.10
270.31
111.86
distribution is considered in this
2.18
5.44
769.68
analysis

2.19
1.74
1.75
-12.12
-12.11
11.21
11.22
2.84
1.11
-53.83
57.78

5.45
3.74
3.74
-49.70
-49.69
47.97
47.98
8.33
0.88
-258.04
267.24

769.57
879.49
879.45
26.50
26.50
31.51
31.52
0.00
896.29
60.02
97.29

Sheet
1

REV

19.87
0.00
0.00
0.00
0.00
-13.69
-13.70
-25.77
-25.78
7.68
0.00
103.33
42.32

4.75
2.90
2.90
2.59
2.59
4.99
4.99
4.97
4.97
0.00
2.54
4.89
4.79

Design of Anchor Bolt

PART1
Rectangular bearing stress
distribution is considered in this
analysis

Sheet
1

REV

Design of Anchor Bolt

PART1
Rectangular bearing stress
distribution is considered in this
analysis

Sheet
1

REV