GABINETE DE COMUNICACIONES (C1-IN)

N
RU
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

GABINETE DE COMUNICACIONES
(C1-INFORMTICA)

RTULO

POTENC
IA
INSTAL
ADA
(W)

PATCH PANEL PTICO, Cnectores LC

C1-S

PATCH PANEL PTICO, conectores LC

C1-R

PATCH PANEL PTICO, conectores LC

C1-Q

GRANDSTREAM GXW4024
PATCH PANEL PTICO, conectores SC
Panda GateDefender Integra 300
Switch Summit X460-24T
Switch Summit X460-24T

C1-P
C1-O
C1-N
C1-M
C1-L

100
100

C1-K
C1-J

44

66

Ordenador de cables
Patch Panel AMP NetConect XG Cat6A
Switch Summit X440-24T
Ordenador de cables
Patch Panel AMP Cat 6 System

PP-1

20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Switch Summit X440-24T

C1-H

44

C1-G
C1-F
C1-E

44

C1-D
C1-C
C1-B

50

Ordenador de cables
Switch Summit X440-24T
Patch Panel Cat 5 AMP
Patch Panel Cat 6 AMP
Ordenador de cables
Dell Power Conect 5424
Patch Panel
Patch Panel
Patch Panel
Patch Panel

TOTAL CARGA

C1-A

448

GABINETE DE SERVIDORES (S1-IN)

N
RU

GABINETE DE SERVIDORES
(S1-INFORMTICA)

RTULO

POTENCIA
INSTALADA
(W)

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Servidor Power Edge 1950


Servidor Power Edge 1950
PATCH PANEL RJ-45
PATCH PANEL RJ-45

ORDENADOR DE MONITOREO

200

POWER EDGE 860


HP PROLIANT DL360 G5
POWER EDGE 1950

S1-K
S1-J

345
700
300

POWER EDGE 2950

S1-I

750

POWER EDGE 2950

S1-H

750

POWER EDGE 2950

S1-G

750

POWER EDGE 2950

S1-F

750

POWER EDGE RACK CONSOLE


15FP

S1-KMM

100

POWER EDGE 2950

S1-E

POWER EDGE 2950

S1-D

DEL TLL 2000

S1-C

DELL EMC2

S1-B

350

DELL EMC2

S1-A

350

750
750
170

SISTEMA DE BATERAS

TOTAL CARGA
GABINETE DE SERVIDORES (S2-IN)

7,015

N
RU

GABINETE DE SERVIDORES
(S2-INFORMTICA)

1
2
3
4
5
6

PATCH PANEL RJ-45


PATCH PANEL RJ-45

RTULO

POTENCIA
NOMINAL
(W)

7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

DELL POWER EDGE R720

S2-I

750

DELL POWER EDGE R720

S2-H

750

DELL POWER EDGE R720

S2-G

750

DELL POWER EDGE R720

S2-F

750

S2-KMM

100

HP PROLIANT DL 380 G6

S2-E

750

HP PROLIANT DL 380 G6

S2-D

750

HP PROLIANT DL 380 G6

S2-C

750

DELL EMC2

S2-B

350

CLUSTER TYPE 1746 C4A IBM

S2-A

100

SATRA PC + SWITCH

TOTAL CARGA
GABINETE DE SERVIDORES (S1-CC)

5,800

N
RU

GABINETE DE SERVIDORES (S1-CENTRO DE


CONTROL)

POTENCIA
NOMINAL
(W)

1
2
3

GPS Arbite

20

4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Switch AT
Ordenador

20

Servidor de Telefona IP

750

Arreglo de discos

4 Servidores Blade sistema SCADA

2,400

Arreglo de discos

8 Servidores Blade sistema SCADA

TOTAL CARGA

GABINETE DE SERVIDORES (S2-CC)

3,500

6,690

N
RU

Gabinete S2-CC (Servidores Medicin Centro de Control)

Potencia
Instalada
(W)

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Dell Power Edge 2950

Sistema de grabacin de voz analgico NICE

Servidor de Vdeo DELL

GPS Arbiter
Cyberdan
Switch - AT 8824
Gatewat - Fortinet 300 A

750

100

860

20
50
70
160

Router - CISCO 1900 series

70

Switch - AT 8824

70

TOTAL CARGA

GABINETE DE COMUNICACIONES (C1-CC)

2,150

N
RU
1
2
3
4
5
6

Gabinete C1-CC (Comunicaciones 1 - Centro


de Control)
Patch Panel F.O. S.M.
Patch Panel F.O. M.M.
Switch Industrial MOXA EDS 728

Potencia
Instalada
(W)

7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

30

Switch Industrial MOXA CPS 728

30

Switch Microondas
Radioenlace IDU Redline AN 50e

100
50

Switch HP 2920-48G

170

TOTAL CARGA
GABINETE DE COMUNICACIONES (C2-CC)

380

N
RU
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Gabinete C2-CC (Comunicaciones 2 - Centro


de Control)
Patch
Patch
Patch
Patch

Panel
Panel
Panel
Panel

F.O.
F.O.
F.O.
F.O.

Potencia
Instalada
(W)

S.M.
S.M.
M.M.
M.M.

Router CISCO 800 Series (Claro)


Switch DELL 338-B

100
100

Patch Panel RJ-45

Patch Panel RJ-45


Patch Panel RJ-45

Router CISCO 800 Series (Claro)

Router CISCO 800 Series (Claro)


Router CISCO 800 Series (Claro)

TOTAL CARGA

CLCULO DE POTENCIA POR GABINETES

100

100
100

500

N
1
2
3
4
5
6
7
8
9
10
11
12
13

Nombre del Gabinete


Servidores 1 Centro de
Control
Servidores 2 Centro de
Control
Comunicaciones 1 Centro de
Control
Comunicaciones 2 Centro de
Control
Servidores 1 Informtica
Servisores 2 Informtica
Comunicaciones 1
Informtica
Distribucin Elctrica
UPS y Banco de Bateras
Climatizacin 1 LCP
Climatizacin 2 LCP
Climatizacin 3 LCP
Climatizacin 4 LCP

Cdigo

Ancho
(mm)

Potenci
a
Instala
da (W)

S1-CC

800

7,015

S2-CC

800

C1-CC

600

C2-CC
S1-IN
S2-IN

600
800
800

C1-IN
DE1
UPS 1
CL1
CL2
CL3
CL4

600
600
600
300
300
300
300
7400

2,150
380
500
6,815
5,800
450

23,110

Al realizar el clculo de la potencia se ha determinado que se tiene que trabajar con


30KW por efectos del futuro escalamiento del Data Center y por disponibilidad del
UPS.