You are on page 1of 6

see Item Code: LKASXJ4140SE2N

TRANSMISSION MATERIALS STANDARD SPECIFICATION

ll-TMSS-02, Rev.01

7.0 DATA SCHEDULE


1 x 2500 mm2
132kV, XLPEPOWERCABLE
Date:

SEC Enquiry No.

SECPurchase Order
Date:

No.
or Contract No.
PTS10W0306

SECPTSNo./Project Title with J.O. No.


REFERENCE

DESCRIPTION

SECTION NO.

3.0

'B'

'A'

'C'

APPLICABLECODESAND STANDARDS
IEC60840 and
ll-TMSS-02
Reference Manufacturing Standard

4.0

DESIGNAND CONSTRUCTIONREQUIREMENTS

4.2

Design Criteria/Rating

AEIC/IEC 60840

Rev.1

Tech. Specs.
wnere applicaDle.

a. Cable Nominal Voltage, (kV)


b. System Short Circuit Current, kA
c. Maximum Conductor short circuit current

132
40

132
40

temperature. .C
d. Maximum permissible continuous

2S0

-250

conductor temperature. .C
e. Emergency Loading
Maximum emergency conductor

90

-90

105

105

for one second

.
.

loading temperature. .C
Permissible Load in Amps, A

72

During any 12 months


During the life of the cable

1500

-72
1500

Materials Details:
Conductor:
Material

Copper

'A' 'B' 'C' -

TBU SPECIFIEDDATA/PARAMETER.
BIDDER/SUPPLIER/VENDOR/CONTRACTORPROPOSEDDATA/PARAMETERS.
REMARKSSUPPORTINGTHE PROPOSEDDEVIATION IN COLUMN 'B'.

DATA/PARAMETERTO BE PROVIDED/PROPOSEDBYTHE BIDDER/SUPPLIER/


VENDOR/CONTRACTORIN COLUMN 'B'

(*)

Pleaserefer to Page22 of 35

Allowable loading duration; hrs


i)
ii)

4.3
4.3.1

* Production

IlT~SS02R01/FAZ

Sampling Tests will be according to ICEAS-108-720

Date of Approval:

December

12,2011

Copper

TRANSMISSION MATERIALSSTANDARD SPECIFICATION

ll-TMSS-02,

Rev.O!

7.0 DATASCHEDULE
132kV, XLPEPOWERCABLE
REFERENCE
SECTION NO.

Conductor for stranding

(Non-segm enta 1/segm enta I)

No. of strands

Dia. of strand prior to compaction, mm


Cross-sectional area, mm2
(400,630,800,

1000, 1200, 1600 or 2000)

No. of segments: 5
No.of strands:91( per segment)
19 ( for central conductor)

appx. 2.78 mm in segments


(before compaction)
2500
appx. 63.0

Resistance at 25. C, O/km

(without tapes)
max. 0.00734

Conductor AC resistance at 20.C

max. 0.011 ohm/km

Conductor DC resistance at 20.C

Temp. coeff at 20.C/"C


Skin effect loss factor (k,)

'C'

::.egmentallea
stranded compacted

Diameter, mm

max.O.0072ohm/km

0.00393

k, =0.66

Proximity effect loss factor (kp)

DC Resistance at 90. C, O/km


Short circuit capability of conductor in kA
for 1 second staryting with 90. C conductor
temperature up to max. short circuit current
temperature

40

Water blocking material between strands

4.3.2

'6'

'A'

DESCRIPTION

max. 0.0092

40

Yes (Swelling tapes shall be applied


inside the segments)

Conductor shield:
SEMICON

Material

Same

Average thickness, mm
400 mm2

0.64

800 to 2000 mm2

0.76

apprx. 1.6

Minimum thickness, mm
400 mm2

0.512

800 to 2000 mm2

0.608

11TM5502R01/FAZ

Date of Approval:

December

12, 2011

0.608 at any point

35

TRANSMISSION MATERIALSSTANDARD SPECIFICATION

.F
ll-TMSS-02,

Rev.01

7.0 DATA SCHEDULE

132kV, XLPEPOWERCABLE
REFERENCE
SECTIONNO.

*
*

Dia.Overconductor shield, mm
Thermal resistivity, K.m/W
Conductor Moisture Impervious layer
Material
4.3.3

SUPER
CLEANXLPE

21.6
19.44
*

Average thickness, mm
Minimum thickness, mm
Dia. Over insulation, mm
Thermal resistivity, K.m/W
Relative permittivity
or dielectric constant (E)

*
*

Loss factor (0)


Specific Resistance, MO-km
(Actual Test Value)

Insulation shield:
Material

SEMICON
1.75
1.40
*

Average thickness, mm
Minimum thickness, mm

Dia.OverInsulationshield, mm

Thermal resistivity,K.m/W
4.3.5

Semi Conducting
Tape

'C'

apprx. 68
3.5

Same

Insulation:
Material

4.3.4

'B'

'A'

DESCRIPTION

Metallic shield:
Material

21.6
19.44 (at any point)
apprx. 111
3.5
2.3 (at 20.C )
Max. 10x10-4
Min. 781 (at 20.C )

Same
1.75
1.4 (at any point)
apprx. 115
3.5
Plain annealed copper wires +

Total effective cross-sectional area, mm2


Diameter over metallic shield, mm
Temp. coefficient at 20.C/"C
DCresistance at 20. C,O/km
AC resistance at 20. C, O/km
Self inductance, mH/km
ACresistance at 90. C, O/km
DCresistance at 90. C, O/km

*
*
*
*
*
*
*
*
*

Resistivityat 20. C, O.m


Short circuit capability in kAfor 1 second
of the metallic shield starting with 90. C
conductor temperature

11 TMSS02ROl/FAZ

Super clean XLPE

40

Date of Approval: December 12, 2011

copper tape contact h';!ix


nom. 305 (geomertical)
apprx. 121
0.00393
0.07 apprx.
0.07 apprx.
0.158
0.08
0.08
Typical1.7241x10.s

40

apprx.
apprx.

TRANSMISSION MATERIALSSTANDARD SPECIFICATION

ll-TMSS-02,

Rev.Ol

7.0 DATA SCHEDULE

132kV, XLPE POWER CABLE


REFERENCE
SECTIONNO.

4.3.6

'A'

DESCRIPTION

Moisture impervious layer (first layer) :


Material

SE~I-CONDUCTIVE

'B'

SCSwellable tapes

'C'

(under metallic screen)

SWELLABLE
TAPE
0.12

Thickness, mm
Diameter over the layer, mm

Moisture impervious layer (second layer) :


Material

SE~ICONDUCTIVE

apprx. 0.4 apprx. (orig. thickness)


apprx. 117

Same

(over metallic screen)

SWELLABLE TAPE

0.12

Thickness, mm

Diameter over the layer, mm

YES/No

Third Moisture impervious layer

4.3.7

Jacket:
Material

(LlDPE, lMDPE or HDPE)


Average thickness, mm
Minimum thicknes, mm

4.3.8

Conductive layer:
Material

5.3

Special Thermal Short Circuit Test

6.0

PACKING
a. Total quantity required, m
b. Are matched sets of cable reel length
required?
c.
If "YES",how many reels
are reuired per set?
d. Tolerancein cable length of
matched reel sets
e. Conductorweight, kg/km
f.
Cableweight, kg/km
g.
Reeland cable weight, kg
h. Cablelength per reel. M
i.
Cablereel diameter, mm
j.
Cablereel width, mm

llT~SS02R01/FAZ

3.55

3.55 (at any point)


apprx. 130

YES/No

Date of Approval:

lMDPE
3.95

*
*

Thickness, mm

Yes - PE laminated AI. Tape

3.95

Overall cable diameter,mm

apprx. 0.4 (original thick.)


apprx. 122

Graphite
apprx. 0.01
Yes (during Type Test only)

Dependingupon
project
requirement

*
*
*
*

*
*

December

12, 2011

-2%
apprx. 22500
apprx. 34700
apprx. 19850
-498 m
apprx. 4040
apprx. 2250

TRANSMISSION MATERIALSSTANDARD SPECIFICATION

ll-TMSS-02,Rev.Ol

7.0 DATASCHEDULE
132kV, XLPE POWER CABLE
REFERENCE

DESCRIPTION

SECTION NO.

'A'

'e'

'B'

OTHERREQUIREDINFORMATION

a.

Lifeexpectancyof cable, years

b.

3-phase inductance in trefoil/Fiat


formation, mH/km

c.

3-phase capacitance in trefoil/Flat


formation,

IlF/km

Over 30

~30 years (designed life)


based on operation conditions

0.335 (trefoil)

0.261 + 8%

1 cable

d. Maximum permissible overload in %


Il-hour / 12-hours

of 3 cables in underground cable duct


trefoil/Flat formation at 40. C soil

temperature, for 1/2/3 ( Il-hour

13-hours

/ IHours

ICable

( 13-hours)
hours starting with a prior loading
of

12-hours

13-hours

A*

(cables laid in trench, direct buried)


*

50%
75%
100%

= 1358

Il-hour

250/250/250
250/250/230
217/180/167

e.

Maximum pulling Tension (kN)

125

f.

Maximum sidewall pressure, kN/m

5.0

g.

Minimum bending radius, mm

2600

at conductor

* Cables laid in flat formation with 0.5 m axial spacing between phases and assumed Native Soil
Thermal Resistivity of 1.2 K.m/W

IlT~SS02ROI/FAZ

Date of Approval:December 12, 2011

TRANSMISSION MATERIALS STANDARD SPECIFICATION

ll-TMSS-02,Rev.Ol

7.0 DATA SCHEDULE


132kV, XLPE POWER CABLE

A.

ADDITIONAL TECHNICALINFORMATION OR FEATURESTO BE FURNISHEDBY SEC:

B.

ADDITIONAL

SUPPLEMENTARY DATA

OR

FEATURES PROPOSED BY

BIDDER/VENDOR/SUPPLIER/CONTRACTOR:

C.

OTHER PARTICULARSTO BE FILLEDUP BY BIDDER/VENDOR/SUPPLIER/CONTRACTOR:

Actual Manufacturer
of Equipment/Material

Name of the Company


Location and address

Vendor/Supplier/
Contractor

Saudi Cable Company


Jeddah

Name and Signature of


authorized rpresentative
and Date

Official Seal/Stamp
of the Company & Date

IlT~SS02ROI/FAZ

Date of Approval: December 12, 2011

Page NO. 23 OF 3S