Corona discharge in air produces optical signal in the ultra violet region,ultra sonic
waves, thermal signatures and radio waves in the range of 0.2 to 10 MHz. Optical
signals generated by discharge will be analysed with the help of spectrometer. Thermal signatures will be alnalysed using thermal imaging camera, audio signatures by
using fibre optic interferrometer and radio waves by using antenna reciver.
1.1
For production of corona discharge point and plane electrode geometry is used. AC
voltage of 100 KV is apllied between the electrodes. The elctric field field produced
between the electrodes is non uniform in nature.
1.2
Optical signal generated by corona discharge is focused into the anti solarization
fibre with the help of quartz collamator. Then the collected light is guided to the
spectrometer for analysis.
1.2.1
Collamator
Ultra violet light is easily absorbed by glass material hence to prevent absorption
quartz material is used.
1.2.2
Normal glass fibre has higher attenuation in ultra violet region as compared to anti
solarization fibre as shown in Fig.1.1
Figure 1.1: Attenuation charactrestic of glass fibre and anti solarization fibre
1.2.3
Spectrometers
Most of them spectrometer gets saturated in ultra violet region. The block diagram
Table 1.1: Spectrometers
Spectrometer
Manufacturer
Range
USB 4000
Ocean Optics
190 to 890 nm
USB 4000
Ocean Optics
210 to 445 nm
HR 2000+
Ocean Optics
190 to 1090 nm
Auaspec 2048L
Aventes
200 to 1100 nm