LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)

33/11kV S/S IN AL AIN AREA


INDEX
CT / VT PARAMETER CALCULATION
Description
A.

B.

CT Parameter Calculation

Sheets
3 TO 27

1 33kV Cable Feeder -Directional Over Current & Earth Fault Protection (67,67N)

3 TO 4

2 33kV Cable Feeder -Pilot Wire Protection- (85)

5 TO 5

3 33kV Cable Feeder -Metering

6 TO 7

4 33kV Bus Bar Differential Protection Line Feeder (87B)

8 TO 9

5 33kV Bus Bar Differential Protection Transformer Feeder (87B)

10 TO 10

6 33kV Transformer Feeder -Metering

11 TO 12

7 33/11kV Transformer Differential Protection Calculation (87T)

13 TO 16

8 33kV Transformer Feeder -Directional Over Current Protection (51-51N)

17 TO 18

9 33/11kV Transformer Feeder -Restricted Earth Fault Protection- (64R)

19 TO 21

10 33/11kV Transformer Feeder -Stand By Earth Fault Protection (SBEF)

22 TO 23

11 11kV Cable/Capacitor Bank Feeder -Directional Over Current Protection (51-51N)

24 TO 25

12 11kV Transformer Feeder -Directional Over Current Protection (51-51N)

26 TO 27

VT Parameter Calculation

28 TO 35

1 33kV LINE VT - METERING

28 TO 29

2 33kV LINE VT- PROTECTION

30 TO 31

3 33kV BUS VT

32 TO 33

4 11kV BUS VT

34 TO 35

C.

Summary Sheet

36 TO 37

D.

List of catalogue References

38 TO 38

2 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

1
1.1

1.2

1.3

1.4

1.5

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

33kV Cable Feeder -Directional Over Current & Earth Fault Protection (67,67N)
The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap

=
=
=
=
=
=

CT-F1, CORE-1
600-400/1A
1
A
5
P 20
2
Ohms at
400
A

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus

31.5 kA

Relays Proposed
a Make
b Directional Over Current Relay
c Directional Earth Fault Relay
d Rated Relay secondary current

=
=
=
=

ABB
SPAS 348 C
REJ 527
1
A

=
=
=
=
=
=
=
=

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.166 Ohms
0.33 Ohms
(1x1) x 0.33
VA
0.33
VA

Ipn
Isn
Rct

Ir

Calculation of Lead Burden RL


Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead

Burden of Relay
Directional Over Current Relay (SPAS 348 C)
Directional Earth Fault Relay (REJ 527)
VA Burden of Over Current Relay (SPAS 348 C)
VA Burden of Over Current Relay (REJ 527)

3 of 43

=
=
=
=
=
=

100 mohm
100 mohm
(1x1) x 100.00 / 1000
0.10 VA
(1x1) x 100.00 / 1000
0.10 VA

400

A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

1.6

1.7

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD

Burden Details
S.No.
Device
a.
Directional Over Current Relay
b.
Directional Earth Fault Relay
c.
Lead Burden
Total Burden
Accuracy Limit Factor of the CT
ABB's Requirement
Ikmax =
In
=

RAJIV

SKA / AKS

Burden
0.10
0.10
0.33
0.53

Make
SPAS 348 C, ABB
REJ 527, ABB

n'

>

Ikmax/In

Highest Fault Current


Nominal Primary Current of the CT

400 A

Hence as Per ABB (n') must be greater than

Real accuracy Limit Factor

n'

>
>

31500 / 400
79

nx

KRJ

(PN + PE)
(PB + PE)

n
PN

CT rated Accuracy Limit Factor

20

15

VA Chosen Value

Rated CT Power
CT Internal Losses In2 x Rct

PE

Watts

PB

Burden at Rated Current

=
=
=

0.53
20 x (15.0 + 2.0) / (0.53 + 2.0)
134

n'

n' =
1.8

134

>

79 , so the current transformer satisfies the requirement.

Conclusion
CT Ratio Selected
Selected Tap
CT Secondary Resistance
Rated VA of the CT core Selected for Directional=
Accuracy Class
Rated Continuous Thermal Current
Rated Short Time Thermal Current

4 of 43

=
=
=
=
=
=

600-400/1A
400 A
2 Ohms
15 VA
5
P 20
150 %
31.5 kA for 3 Sec

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

2
2.1

2.2

2.3

2.4

2.5

2.6

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

33kV Cable Feeder -Pilot Wire Protection- (85)


The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Accuracy Class
Secondary Winding Resistance
Selected Tap

=
=
=
=
=
=

CT-F1 CORE-2
600-400/1A
1
A
X
2
Ohms at
400
A

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus

31.5 kA

Relay Proposed
a Make
b Type
d Rated Relay secondary current Ir

=
=
=

M/S Vatech Reyrolle Ltd.


Solkar Rf
1
A

Calculation of Lead Burden RL


Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL

=
=
=
=
=
=

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.166
Ohms
0.33
Ohms

>=

(50/In) + (If/N) x (Rct+2RL)

=
=

Rated current of SOLKAR Rf Relay


Primary current under maximum steady
state through fault conditions
Current Transformer Ratio
CT Secondary Winding Resistance
Single Lead Resistance from CT to Relay

Ipn
Isn
Rct

Knee Point Voltage Requirement


As per Manufactureres Requirement
Vk
Where
In
If

400

A tap

Volts

N
Rct
RL

=
=
=

Vk

>=

50/1 + 31500 / 400 x (2 + 2x0.166)


234 V

Conclusion
CT Ratio Selected
Selected Tap
CT Secondary Resistance
Class of Accuracy
Knee Point Voltage Selected
Magnetising Current at Vk/2
Rated Continuous Thermal Current

=
=
=
=
>=
<=
=

600-400/1A
400 A
2 Ohms
X
400 V
30 mA
150 %

5 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Rated Short Time Thermal Current

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV
=

6 of 43

31.5

SKA / AKS

KRJ

kA for 3 Sec

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

33kV Cable Feeder -Metering

3.1

The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap

3.2

3.3

3.4

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

Ipn
Isn
Rct

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus
Calculation of Lead Burden RL
Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead

=
=
=
=
=
=

CT-F1 CORE-3
600-400/1A
1
A
0.5 S
2
Ohms at
400
A

31.5 kA

=
=
=
=
=
=
=
=

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.166
Ohms
0.33
Ohms
(1x1) x 0.33
VA
0.33
VA

Burden Details
S.No.
Device
a.
Bay Control Unit
b.
Multifunction Meter
c.
Ammeter Transducer
d.
Lead Burden

Burden
0.10
0.60
2.20
0.33
3.23

Total Burden

3.5

Conclusion
CT Ratio Selected
Selected Tap
CT Secondary Resistance
Rated VA of the CT core Selected for Metering
Accuracy Class
Instrument Security Factor
Rated Continuous Thermal Current
Rated Short Time Thermal Current

SKA / AKS

=
=
=
=
=
<=
=
=

7 of 43

KRJ

400

Make
ABB, REF 542
CIRCUTOR, CVMK
CELSA, CRI

600-400/1A
400 A
2 Ohms
10 VA
0.5 S
5 at all Taps
150 %
31.5
kA for 3 Sec

DATE
7.04.2004

A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

Note :
1.
Instrument security factor (ISF) shall be less than 5 at all taps and shall be ensured by the CT
manufacturer.
2.
Whenever the actual Burden is less than the noted Burden of the CT, protection Panel Manufacturer
shall ensure the Metering and connected Instruments are not stressed beyond its Short time
withstand capacity by providing means like Dummy Resistor etc.

8 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

4
4.1

4.2

4.3

4.4

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

33kV Bus Bar Differential Protection Line Feeder (87B)


The CT details
Current Transformer
Rated Primary Current for CT
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap

Ipn

=
=
Isn =
=
Rct =
=

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus
System X/R Ratio
System L/R ratio

Calculation of Lead Burden RL


Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead

Burden Details
S.No.
a.
Relay Burden
b.
Lead Burden

Device

Total Burden

CT-F1 CORE-4
1200 / 1A
1
A
5
P 20
6
Ohms at
1200
A

=
=
=
=
=

31.5 kA
20
20 / (2x3.14x50)
0.064 sec
64 msec

=
=
=
=
=
=
=
=

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.166
Ohms
0.33
Ohms
(1x1) x 0.33
VA
0.33
VA

Burden
0.02
0.33
0.35

Make
ABB, REB 500

4.5 Current Transformer Requirement


a. Condition -1 (With out Taking DC Time constant in to Consideration)
As per Relay manufacturers Catalogue
1xIkmax
n'
>=
5xI1N

9 of 43

1200 A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

b. Condition -2 (Taking DC Time constant in to Consideration)


n'
>=
10 for TN<= 120ms, or
20 for 120ms<=TN<= 300ms

n'
>=
Where
n'
=
Ikmax
=
I1N
=

Effective accuracy limit Factor

TN

DC Time constant

Maximum Primary through fault current=

31.5 kA

Rated Primary CT current

As per Condition-1
n'
>=
(1x31500) / (5 x 1200)
>=
5.25
As per Condition-2
n'
>=
10
For the time constant of
64
msec
Hence the maximum value of the n' form the condition 1 and condition 2 is selected for comparison.
n'
>=
10
(PN + PE)
Rated accuracy Limit Factor
n' = n x
(PB + PE)

(to be provided by the CT manufacturer)


Where
n
= CT Rated Accuracy Limit Factor
PN
= Rated VA

20

10 VA

PE

CT Internal Losses In2 x Rct

PB

Burden at Rated Current


n'

n'=

50 >

=
=
=

Chosen Value

6 Watts
0.35
20 x (10.0 + 6.0) / (0.35 + 6.0)
50

10 , so the current transformer satisfies the requirement.

4.6 Conclusion
CT Ratio Selected Line Feeder
CT Secondary Resistance
Rated VA of the CT
Accuracy Class
Rated Continuous Thermal Current
Rated Short Time Thermal Current

=
=
=
=
=
=

10 of 43

1200 / 1A
6 Ohms
10 VA
5
P 20
150 %
31.5
kA for

Sec

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

33kV Bus Bar Differential Protection Transformer Feeder (87B)


The CT details
Current Transformer
Rated Primary Current for CT
Rated Secondary Current
Rated VA of the CT
CT Class
Secondary Winding Resistance
Rated Continuous Thermal Current
Rated Short Time Thermal Current

=
=
=
=
=
=
=
=

Note : For Detailed calculation refer clause 4 .

11 of 43

CT-T1-1 CORE-1
1200/1 A
1
A
10
VA
5
P 20
6
Ohms at
150 %
31.5
kA for 3

1200 A tap
Sec

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

12 of 43

SKA / AKS

KRJ

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

6
6.1

6.2

6.3

6.4

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

KRJ

7.04.2004

33kV Transformer Feeder -Metering


The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap

=
=
=
=
=
=

Ipn
Isn
Rct

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus
Transformer MVA Rating
Transformer kV Rating
Load Current on 33kV Side
Load Current on 11.55kV Side

=
=
=
=
=

Calculation of Lead Burden RL


Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead

=
=
=
=
=
=
=
=

Burden Details
S.No.
Device
a.
Bay Control Unit
b.
Multifunction Meter
c.
Ammeter Transducer
d.
Lead Burden

Conclusion
CT Ratio Selected
Selected Tap
CT Secondary Resistance
Rated VA of the CT core Selected for Metering
Accuracy Class
Instrument Security Factor
Rated Continuous Thermal Current

CT-T1-1 CORE-2
600-300/1 A
1
A
0.5 S
1.5
Ohms at
300
A

31.5
15
33 /
262.4
749.8

=
=
=
=
=
<=
=

13 of 43

300

kA
MVA
11.55 kV
A
A

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.166
Ohms
0.33
Ohms
(1x1) x 0.33
VA
0.33
VA

Burden
0.10
0.60
2.20
0.33
3.23

Total Burden

6.5

SKA / AKS

DATE

Make
ABB, REF 542
CIRCUTOR, CVMK
CELSA, CRI

600-300/1 A
300 A
1.5 Ohms
10 VA
0.5 S
5 at all Taps
150 %

A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Rated Short Time Thermal Current

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV
=

14 of 43

31.5

SKA / AKS

KRJ

kA for 3 Sec

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

Note :
1.
Instrument security factor (ISF) shall be less than 5 at all taps and shall be assured by the
manufacturer.
2.
Whenever the actual Burden is less than the noted Burden of the CT, protection Panel Manufacturer
shall ensure the Metering and connected Instruments are not stressed beyond its Short time
withstand capacity by providing means like Dummy Resistor etc.

15 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

7
7.1

7.2

7.3

7.4

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

KRJ

7.04.2004

33/11kV Transformer Differential Protection Calculation (87T)


The CT details
Current Transformer
=
Rated Primary Current for CT on 33kV side
=
Rated Primary Current for CT on 11kV side
=
Rated Secondary Current
Isn =
CT Class
=
Secondary Winding Resistance on 33kV Side
Rct =
Secondary Winding Resistance on 11kV Side
Rct =
Selected Tap for 33kV Side
Selected Tap for 11kV Side
Assumptions :
The Max.3Ph.S.C Current of 33kV Bus
System X/R Ratio
System L/R ratio

Calculation of Lead Burden RL


Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead

Burden Details
S.No.
a.
Relay Burden
b.
Lead Burden

Device

Total Burden
7.5

SKA / AKS

DATE

System Short Circuit Calculation


Short Circuit Level on
33 kV Side
Short Circuit Level on
11.55 kV Side
System Impedance on 33 kV Side
System Impedance on

CT-T1-1 CORE-3 / CT-T1-2 CORE-1


600-300/1 A
1000-800/1 A
1
A
X
1.5
Ohms at
300 A tap
4
Ohms at
800 A tap
300
A
800
A

=
=
=
=
=

31.5 kA
20
20 / (2x3.14x50)
0.064 sec
64 msec

=
=
=
=
=
=
=
=

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.17
Ohms
0.33
Ohms
(1x1) x 0.33
VA
0.33
VA

Burden
0.10
0.33
0.43

Make
ABB, RET 316*4

= 31.5 kA
= 31.5 kA
= 33 / sqrt(3) / 31.5
= 0.60 ohms
= 11.55 / sqrt(3) / 31.5
= 0.21 ohms

11.55 kV Side

16 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

kV Rating of the Transformer


MVA Rating of the Transformer
Per Unit Impedance
Impedance of the Transformer on

=
=
=
33 kV Side =
=
Impedance of the Transformer on 11.55 kV Side
=
=
Thus through fault current on 33kV Side
=
=
Thus through fault current on 11.55kV Side
=
=

SKA / AKS

KRJ

33
/ 11.55 kV
15 MVA
10 %
0.10x(33 x 33) / 15
7.26 ohms
0.10x(11.55 x 11.55) / 15
0.89 ohms
33 / sqrt(3) / (0.60+7.26)
2.42 kA
11.55 / sqrt(3) / (0.21+0.89)
6.06 kA

7.6 Current Transformer Requirement


a 33kV Side
As per Relay manufacturers Catalogue
n'
<= n x (PN + PE)x IN of CT
(PB + PE)xIN
Where
n'
=
IN
=

Effective accuracy limit Factor


Nominal current Related to Protected Object =
15000 / sqrt(3) / 33
=

IN of CT
n
PN

=
=

Nominal current of CT =
CT rated Accuracy Limit Factor

PE
PB

262 A

300
45

10

Rated CT Power
CT Internal Losses In2 x Rct

Burden at Rated Current

(Calculated Below)
VA (Selected Value)

1.5 Watts
0.43

Ikmax

=
Maximum Primary through fault current= 2.42 kA
For a class X Current Transformer, equivalent value of CT rated accuracy class factor (n)
n
= Uk x Insec x 1.3
PN + P E
Where
Uk
=
n
=
n
=
=
Hence,
n'
=

CT Knee point Voltage


CT rated Accuracy Limit Factor
(400 x 1x1.3) / (10 + 2)
45

45 x (10 + 2) x 300
(0.43 + 2) x 262
n'
=
308
For the system under consideration
Ikmax = Highest through Fault Current

17 of 43

=
=

400
45.2

V (Selected Value)
(Calculated Below)

Ikmax/In

=
=

2422 / 262
9.23

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

For Ikmax/In calculated above


n' =

308

>

n'

SKA / AKS

KRJ

DATE
7.04.2004

(from ABB's Relay Catalogue)


(Figure-1 Page 3/3)
9 , so the current transformer satisfies the requirement.

a 11kV Side
As per Relay manufacturers Catalogue
n'
<= n x (PN + PE)x IN of CT
(PB + PE)xIN
Where
n'
=
IN
=
IN of CT
n
PN

Effective accuracy limit Factor


Nominal current Related to Protected Object =
15000 / sqrt(3) / 11.55
=

=
=

Nominal current of CT =
CT rated Accuracy Limit Factor

PE

Rated CT Power
CT Internal Losses In2 x Rct

PB

Burden at Rated Current

750 A

800
37

10

0.43

(Calculated Below)
VA (Selected Value)
Watts

Ikmax
=
Maximum Primary through fault current= 6.06 kA
For a class X Current Transformer, equivalent value of CT rated accuracy class factor (n)
n
= Uk x Insec x 1.3
PN + P E
Where
Uk
=
n
=
n
=
=
Hence,
n'
=

CT Knee point Voltage


CT rated Accuracy Limit Factor
(400 x 1x1.3) / (10 + 4)
37

37 x (10 + 4) x 800
(0.43 + 4) x 750
n'
=
125
For the system under consideration

=
=

400
37.1

V (Selected Value)
(Calculated Below)

=
=
=
=

Ikmax/In
6056 / 750
8.08
8.5 (from ABB's Relay Catalogue)
(Figure-1 Page 3/3)

For Ikmax/In calculated above


n'
Where
Ikmax = Highest through Fault Current
n' =
125 > 8.5 , so the current transformer satisfies the requirement.

18 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

7.7

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

Conclusion
CT Ratio Selected for 33kV Side
CT Ratio Selected for 11kV Side
Rated VA of the CT on 33kV Side
Rated VA of the CT on 11kV Side
Selected Tap on 33kV Side
Selected Tap on 11kV Side
CT Secondary Resistance on 33kV side
CT Secondary Resistance on 11kV side
Accuracy Class
I magnetising
Knee point Voltage on 33kV Side
Knee point Voltage on 11kV Side
Rated Continuous Thermal Current
Rated Short Time Thermal Current

=
=
=
=
=
=
=
=
=
=
=
=
=
=

19 of 43

SKA / AKS

600-300/1 A
1000-800/1 A
10
VA
10
VA
300 A
800 A
1.5 Ohms
4
Ohms
X
30 mA @ Vk/2
400
400
150 %
31.5
kA for 3

KRJ

Sec

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

33kV Transformer Feeder -Directional Over Current Protection (51-51N)

8.1

The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap

8.2

8.3

8.4

8.5

8.6

Ipn
Isn
Rct

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus
Transformer MVA Rating
Transformer kV Rating
Load Current on 33kV Side
Load Current on 11.55kV Side

=
=
=
=
=
=

CT-T1-1,CORE-4
600-300/1A
1
A
5
P 20
1.5
Ohms at
300
A

=
=
=
=
=

31.5 kA
15
33 /
262.4
749.8

Relays Proposed
a Make
=
b Directional Over Current and Earth fault Relay =
c Rated Relay secondary current Ir
=
Calculation of Lead Burden RL
Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead

=
=
=
=
=
=
=
=

Burden Details
S.No.
Device
a.
Directional Over Current Relay
c.
Lead Burden
Total Burden
Accuracy Limit Factor of the CT
ABB's Requirement

n'

Hence as Per ABB (n') must be greater than

20 of 43

MVA
11.55 kV
A
A

ABB
SPAJ 140C
1
A

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.17
Ohms
0.33
Ohms
(1x1) x 0.33
VA
0.33
VA
Burden
0.10
0.33
0.43

Make
SPAJ 140C

>= Ikmax/In
>= 31500 / 300
>= 105

KRJ

300

DATE
7.04.2004

A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

For the System under Consideration


Real accuracy Limit Factor

n'

nx

(PN + PE)
(PB + PE)

Where
n
=
PN
=
PE
=
PB

CT rated Accuracy Limit Factor

20

Rated CT Power
CT Internal Losses In2 x Rct

10

VA (Selected Value)

1.5

Watts

Burden at Rated Current

0.43
=
20 x (10 + 1.5) / (0.43 + 1.5)
=
119

n'

n' =
8.7

119 > 105 , so the current transformer satisfies the requirement.

Conclusion
CT Ratio Selected
Selected Tap
CT Secondary Resistance
Rated VA of the CT core
Accuracy Class
Rated Continuous Thermal Current
Rated Short Time Thermal Current

=
=
=
=
=
=
=

21 of 43

600-300/1A
300 A
1.5 Ohms
10 VA
5
P 20
150 %
31.5 kA for 3 Sec

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

33/11kV Transformer Feeder -Restricted Earth Fault Protection- (64R)

9.1

The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap
I magnetising

9.2

9.3

9.4

=
=
=
=
=
=
=

CT-T1-N CORE-1
1000-800/1A
1
A
X
4
Ohms at
800
A
30 mA @ Vk/2

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus

31.5 kA

Relays Proposed
a Make
b Restricted Earth Fault Relay
d Rated Relay secondary current Ir

=
=
=

ABB
SPAJ 115C
1
A

Calculation of Lead Burden RL


Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL

=
=
=
=
=
=

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.17
Ohms
0.33
Ohms

Ipn
Isn
Rct

9.5 Through fault current calculation


KV Rating of the Transformer
MVA rating of the transformer
Transformer Per unit impedance
Short Circuit MVA
Hence Maximum through fault current on
the secondary side
Ikmax
9.6 Knee point voltage calculation
The Knee Point Voltage

The setting Voltage

800

=
33 / 11.55 kV
=
15 MVA
=
10 p.u
=
15 / 0.10
=
150 MVA
=
150000 / (sqrt(3) x 11.55)
=
7498.06 A
= 7.5 kA

Vk
=
2 Us
Where Us is the Voltage setting of the Relay
Us

KRJ

Ikmax/n x ( Rct + 2 RL)

22 of 43

DATE
7.04.2004

A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

9.7 Sensitivity Check


The Primary operating Current

RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

Ikmax

n
Rct
RL
Us
Us

=
=
=
=
=
=
>=
>=
>=
>=

Maximum through fault current for which relay


must not operate
Current Transformer turns ratio
Secondary Resitance ( Ohms)
Total resistance of the longest measuring circuit
7498.1 / 800(4 + 0.33)
40.6
50
2Us
2 x 50
100
100

400

Set value of Us
Hence Knee point voltage

Knee point Voltage selected


approx.
Adopted Value of Uk

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD

Uk

n x ( Ir + m * Ie + Iu)
CT transformation ratio
800
Ir
Relay Operating Current >= m*Ie
30
mA
Ie
Current Transformer Mag. Current at
setting voltage
=
(30x50) / (400/2)
=
7.5
mA
m
=
Number of CT's in the differential current circuit
=
4
Nos
Iu
=
Current through varistor at Us
=
10
mA (As per Relay Catalogue for SPAJ 115C)
(Figure-4, Operating Characterstic of the voltage dependant Resistor)
( Voltage Dependant Resistor Type 5248 831-C)
Hence, the primary operating Current
=
800 ( 0.030 + 4x0.008 + 0.010)
=
56

9.8 Value of stabilising Resistor (Rs)


Maximum Possible value of Us
Minimum value of start Current Ir
Value of stabilising Resistor (Rs)

Iop
n

=
=
=
=
=
=

=
=

50 V
30 mA

=
=

Us/Ir
1666.7

23 of 43

(It is m x Ie as recommended in
the catalogue for SPAJ 115C)
Ohms Type - (5248 831-C)

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

The input Impedance of the SPAJ115C relay


=
0.1 Ohms
Since the input impedance of the relay is negligible in comparison to the value of stabilising resistor,
the same is not substracted from the calculated value of Rs above.
9.9

Conclusion
CT Ratio Selected
Selected Tap
CT Secondary Resistance
Rated VA of the CT core Selected for Restricted=
Earth fault protection
Minimum Knee point Voltage Requirement
Accuracy Class
I magnetising
Rated Continuous Thermal Current
Rated Short Time Thermal Current

=
=
=

1000-800/1A
800 A
4 Ohms
10 VA

=
=
=
=
=

400 V
X
30 mA @ Vk/2
150 %
31.5
kA for 3 Sec

24 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

10

33/11kV Transformer Feeder -Stand By Earth Fault Protection (SBEF)

10.1

The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap

10.2

10.3

10.4

10.5

Ipn
Isn
Rct

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus
Calculation of Lead Burden RL
Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead

=
=
=
=
=
=

CT-T1-N CORE-2
1000-800/1A
1
A
5
P 20
4
Ohms at
800
A

31.5 kA

=
=
=
=
=
=
=
=

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.17
Ohms
0.33
Ohms
(1x1) x 0.33
VA
0.33
VA

Burden Details
S.No.
Device
a.
Stand By Earth Fault Relay
B.
Lead Burden
Total Burden
Accuracy Limit Factor of the CT
ABB's Requirement
Ikmax =
In
=

Burden
0.10
0.33
0.43

>

Ikmax/In

Highest Fault Current


Nominal Primary Current of the CT

800 A

>
>

31500 / 800
39

nx

Real accuracy Limit Factor

n'

(PN + PE)
(PB + PE)

n
PN

CT rated Accuracy Limit Factor

20

15

VA Chosen Value

Rated CT Power
CT Internal Losses In2 x Rct

PE

Watts

25 of 43

800

Make
ABB, REJ 521

n'

Hence as Per ABB (n') must be greater than

KRJ

DATE
7.04.2004

A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Burden at Rated Current

PB

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV
=

26 of 43

0.43

SKA / AKS

KRJ

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV
n'

10.6

=
=

SKA / AKS

KRJ

20 x (15.0 + 4.0) / (0.43 + 4.0)


86

n' =
86
> 39 , so the current transformer satisfies the requirement.
Conclusion
CT Ratio Selected
= 1000-800/1A
Selected Tap
=
800 A
CT Secondary Resistance
=
4 Ohms
Rated VA of the CT core Selected for Metering
=
10 VA
Accuracy Class
=
5 P 20
Rated Continuous Thermal Current
= 150 %
Rated Short Time Thermal Current
= 31.5
kA for 3 Sec

27 of 43

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

11

11kV Cable/Capacitor Bank Feeder -Directional Over Current Protection (51-51N)

11.1

The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap

11.2

11.3

11.4

11.5

11.6

=
=
=
=
=
=

CT-2, 4 CORE-1
600-300/1A
1
A
5
P 20
1.5
Ohms at
300
A

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus

31.5 kA @

Relays Proposed
a Make
b Directional Over Current Relay
c Directional Earth Fault Relay
d Rated Relay secondary current

=
=
=
=

ABB
REF 542 Plus
REF 542 Plus
1
A

=
=
=
=
=
=
=
=

4 sq.mm Cu
5.52
Ohms/km
30
Mtrs
0.030 x 5.52
0.17
Ohms
0.33
Ohms
(1x1) x 0.33
VA
0.33
VA

Ipn
Isn
Rct

Ir

Calculation of Lead Burden RL


Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead
Burden Details
S.No.
Device
a.
Directional Over Current Relay
c.
Lead Burden
Total Burden
Accuracy Limit Factor of the CT
ABB's Requirement
Hence as Per ABB (n') must be greater than

28 of 43

Burden
0.10
0.33
0.43

33

300

kV

Make
REF 542 Plus

>= Ikmax/In
>= 31500 / 300
>= 105

DATE
7.04.2004

A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

For the System under Consideration


Real accuracy Limit Factor

n'

nx

(PN + PE)
(PB + PE)

Where
n
=
PN
=
PE
=
PB

CT rated Accuracy Limit Factor

20

Rated CT Power
CT Internal Losses In2 x Rct

10

VA (Selected Value)

1.5

Watts

Burden at Rated Current

0.43
=
20 x (10.0 + 1.5) / (0.43 + 1.5)
=
119

n'

n' =
11.7

119 > 105 , so the current transformer satisfies the requirement.

Conclusion
CT Ratio Selected
Selected Tap
CT Secondary Resistance
Rated VA of the CT core Selected for Directional=
Overcurrent Earth fault protection
Accuracy Class
Rated Short Time Thermal Current

29 of 43

=
=
=

=
=

600-300/1A
300 A
1.5 Ohms
10 VA
5
P 20
31.5 kA for 3 Sec

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

12

11kV Transformer Feeder -Directional Over Current Protection (51-51N)

12.1

The CT details
Current Transformer
Rated Primary Current
Rated Secondary Current
CT Class
Secondary Winding Resistance
Selected Tap

12.2

12.3

12.4

12.5

12.6

Ipn
Isn
Rct

Assumptions :
The Max.3Ph.S.C Current of 33kV Bus
Transformer MVA Rating
Transformer kV Rating
Load Current on 33kV Side
Load Current on 11.55kV Side

=
=
=
=
=
=

CT-T1-2, CORE-4
1000-800/1A
1
A
5
P 20
4
Ohms at
800
A

=
=
=
=
=

31.5 kA @
33 kV
15
MVA
33 / 11.55 kV
262.4
A
749.8
A

Relays Proposed
a Make
=
b Directional Over Current and Earth fault Relay =
c Rated Relay secondary current Ir
=
Calculation of Lead Burden RL
Cable considered for CT connection
AC Resistance of the cable @ 70deg C
Length between CT and the Relay
Single Lead Resistance from CT to
Relay
RL
2RL
VA Burden of the Lead

=
=
=
=
=
=
=
=

Burden Details
S.No.
Device
a.
Directional Over Current Relay
c.
Lead Burden
Total Burden
Accuracy Limit Factor of the CT
ABB's Requirement
Hence as Per ABB (n') must be greater than

30 of 43

KRJ

ABB
SPAJ 140C
1
A

4 sq.mm Cu
5.52
Ohms/km
10
Mtrs
0.010 x 5.52
0.06
Ohms
0.11
Ohms
(1x1) x 0.11
VA
0.11
VA
Burden
0.10
0.11
0.21

Make
SPAJ 140C

>= Ikmax/In
>= 31500 / 800
>=
39

800

DATE
7.04.2004

A tap

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

CT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

For the System under Consideration


Real accuracy Limit Factor

n'

nx

(PN + PE)
(PB + PE)

Where
n
=
PN
=
PE
=
PB

CT rated Accuracy Limit Factor

20

Rated CT Power
CT Internal Losses In2 x Rct

10

VA (Selected Value)

Watts

Burden at Rated Current

0.21
=
20 x (10 + 4.0) / (0.21 + 4.0)
=
67

n'

n' =
12.7

67

>

39 , so the current transformer satisfies the requirement.

Conclusion
CT Ratio Selected
Selected Tap
CT Secondary Resistance
Rated VA of the CT core Selected for Directional=
Overcurrent Earth fault protection
Accuracy Class
Rated Continuous Thermal Current
Rated Short Time Thermal Current

31 of 43

=
=
=

1000-800/1A
800 A
4 Ohms
10 VA

=
=
=

5
P 20
150 %
31.5 kA for 3 Sec

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

VT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

DATE

KRJ

7.04.2004

1 33kV LINE VT - METERING


1.1 VT Details
VT
Voltage Rating
VA Rating
Core-1

=
=
=
=

PT-F1, CORE-1

VA
Cl :1

1.2 VT Burden Calculation


Burden on Core-1
Voltage Rating of the VT
=
VA Rating of the VT
=
Current Supplied by VT at maximum VA Rating =
IVT
(a) Lead Burden on Core-1
Cable

S.
No

110
V
100
VA
(100 x sqrt(3) ) / (110)
1.575

Cable Size
in (Sq.mm)

From

To

VT

Synchronising Circuit

4C

2.5

A
Cable
2 Way
Resistance Cable
Total Lead
(R) in
Length Loss (VA)=
(Ohms/km) (L) in (m) (IVT2xRxL/1000)
8.87

Cu. Conductor
(b) Other Burdens on Core-1
S.No.
Device
1
Tarrif Metering
Not Applicable
2
Backup Metering
Voltmeter
3
Protection Relays
Not Applicable
4
Synchronisation
a.
Check Synchronisation Relay
b.
Synchroscope
c.
Double Frequency Meter
d.
Double Volt Meter
e.
No Voltage Relay
5
Lead Burden
a.
Lead Burden under S.No-1 above
Total Burden

2 x 30

1.320

60

Burden (VA)

Make

Type

0.25
6
1.2
5
1.2

ABB
ABB
ABB
ABB
ABB

SPAU140 C

1.32
19.97

32 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

VT Parameter Calculations

1.3 Conclusion
Actual Burden of the Line-1 VT Core-1
Selected Parameters
VA rating Selected
Accuracy Class of Core-1

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

19.97

VA

:
:

100.0
Cl :1

VA

33 of 43

KRJ

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

VT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

2 33kV LINE VT- PROTECTION


2.1 VT Details
VT
Voltage Rating
VA Rating
Core-2

=
=
=
=

PT-F1, CORE-2

VA
Cl :3P

2.2 VT Burden Calculation


Burden on Core-2
Voltage Rating of The VT
=
VA Rating of the VT
=
Current Supplied by VT at maximum VA Rating =
IVT
(a) Lead Burden on Core-1
Cable

S.
No

110
V
50
VA
(50 x sqrt(3) ) / (110)
0.787

Cable Size
in (Sq.mm)

From

To

VT

SPAS 348C Relay

4C

2.5

A
Cable
2 Way
Resistance Cable
Total Lead
(R) in
Length Loss (VA)=
(Ohms/km) (L) in (m) (IVT2xRxL/1000)
8.87

Cu. Conductor
(b) Other Burdens on Core-2
S.No.
Device
1
Tarrif Metering
Not Applicable
2
Backup Metering
Not Applicable
3
Protection Relays
Directional O/C and Earth Fault Relay
4
Synchronisation
Not Applicable
5
Lead Burden
a.
Lead Burden under S.No-1 above
Total Burden

2 x 30

0.330

60

Burden (VA)

Make

Type

0.5

ABB

SPAS 348 C

0.33
0.83

34 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

VT Parameter Calculations

2.3 Conclusion
Actual Burden of the Line-1 VT Core-2
Selected Parameters
VA rating Selected
Accuracy Class of Core-2

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV
:
:
:

35 of 43

0.83

SKA / AKS
VA

50.0 VA
Cl :3P

KRJ

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

VT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

KRJ

DATE
7.04.2004

3 33kV BUS VT
3.1 VT Details
VT
Voltage Rating
VA Rating
Core-1

=
=
=
=

PT-BUS-1, CORE-1

VA
Cl :1

3.2 VT Burden Calculation


Burden on Core-1
Voltage Rating of The VT
=
VA Rating of the VT
=
Current Supplied by VT at maximum VA Rating =
IVT
(a) Lead Burden on Core-1
Cable

S.
No

110
V
100
VA
(100 x sqrt(3) ) / (110)
1.575

Cable Size
in (Sq.mm)

From

To

VT

Synchronising Circuit

4C

2.5

A
Cable
2 Way
Resistance Cable
Total Lead
(R) in
Length Loss (VA)=
(Ohms/km) (L) in (m) (IVT2xRxL/1000)
8.87

Cu. Conductor
(b) Other Burdens on Core-1
S.No.
Device
1
Tarrif Metering
Not Applicable
2
Backup Metering
Not Applicable
3
Protection Relays
Not Applicable
4
Synchronisation
a.
Check Synchronisation Relay
b.
Synchroscope
c.
Double Frequency Meter
d.
Double Volt Meter
e.
No Voltage Relay
5
Lead Burden
a.
Lead Burden under S.No-1 above
Total Burden

2 x 30

1.320

60

Burden (VA)

Make

Type

0.25
6
1.2
5
1.2

ABB
ABB
ABB
ABB
ABB

SPAU140 C

1.32
14.97

36 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

VT Parameter Calculations

3.3 Conclusion
Actual Burden of the Line-1 VT Core-1
Selected Parameters
VA rating Selected
Accuracy Class of Core-1

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

14.97

VA

:
:

100.0
Cl :1

VA

37 of 43

KRJ

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

VT Parameter Calculations

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

DATE

KRJ

7.04.2004

4 11kV BUS VT
4.1 VT Details
Voltage Rating
VA Rating
Core-1

VA
Cl :1

=
=
=

4.2 VT Burden Calculation


Burden on Core-1
Voltage Rating of The VT
=
VA Rating of the VT
=
Current Supplied by VT at maximum VA Rating =
IVT

110
V
100
VA
(100 x sqrt(3) ) / (110)
1.575

(a) Lead Burden on Core-1


Cable

S.
No

Cable Size
in (Sq.mm)

From

To

VT

Synchronising Circuit

4C

2.5

Cable
2 Way
Resistance Cable
Total Lead
(R) in
Length Loss (VA)=
(Ohms/km) (L) in (m) (IVT2xRxL/1000)
8.87

Cu. Conductor
(b) Other Burdens on Core-1
S.No.
Device
1
Tarrif Metering
Not Applicable
2
Backup Metering
Not Applicable
3
Protection Relays
Voltmeter
4
Synchronisation
a.
Check Synchronisation Relay
b.
Synchroscope
c.
Double Frequency Meter
d.
Double Volt Meter
e.
No Voltage Relay
5
Lead Burden
a.
Lead Burden under S.No-1 above
Total Burden

2 x 30

1.320

60

Burden (VA)

Make

Type

0.25
6
1.2
5
1.2

ABB
ABB
ABB
ABB
ABB

SPAU140 C

1.32
19.97

38 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
PROJECT

33/11kV S/S IN AL AIN AREA

TITLE

VT Parameter Calculations

4.3 Conclusion
Actual Burden of the 11kV Feeder VT Core-1
Selected Parameters
VA rating Selected
Accuracy Class of Core-1

Ref : G1409--RL7440J353 A
PREP
CHKD
APPRD
RAJIV

SKA / AKS

19.97

VA

:
:

100.0
Cl :1

VA

39 of 43

KRJ

DATE
7.04.2004

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
Revision : A
S.No.

Description

CT No.

Ratio
(A/A)

Class

Burden
(VA)

Date : 7.04.2004

Ukp
(V)

Rct
(Ohm)

Relay

1.

33kV Cable Feeder -Directional


Over Current & Earth Fault
Protection (67,67N)

CT-F1, CORE-1

600-400/1A

5 P 20

15

SPAS 348 C

2.

33kV Cable Feeder -Pilot Wire


Protection- (85)

CT-F1 CORE-2

600-400/1A

400

Solkar Rf

CT-F1 CORE-3

600-400/1A

0.5 S

10

CT-F1 CORE-4

1200 / 1A

5 P 20

10

ABB, REB 500

CT-T1-1 CORE-1

1200/1 A

5 P 20

10

ABB, REB 500

CT-T1-1 CORE-2

600-300/1 A

0.5 S

10

1.5

10

400

1.5

3.
4.
5.
6.

7.

33kV Cable Feeder -Metering


33kV Bus Bar Differential
Protection Line Feeder (87B)
33kV Bus Bar Differential
Protection Transformer Feeder
(87B)
33kV Transformer Feeder
-Metering
33/11kV Transformer Differential
Protection Calculation (87T)

CT-T1-1 CORE-3 / CTT1-2 CORE-1

600-300/1 A
X
1000-800/1 A

ABB, RET 316*4


10

400

8.

33kV Transformer Feeder


-Directional Over Current
Protection (51-51N)

CT-T1-1,CORE-4

600-300/1A

5 P 20

10

1.5

SPAJ 140C

9.

33/11kV Transformer Feeder


-Restricted Earth Fault Protection(64R)

CT-T1-N CORE-1

1000-800/1A

10

400

SPAJ 115C

10.

33/11kV Transformer Feeder


-Stand By Earth Fault Protection
(SBEF)

CT-T1-N CORE-2

1000-800/1A

5 P 20

10

ABB, REJ 521

11.

33kV Bus Bar Differential


Protection - Bus Section Feeder
(87B)

CT-BC1-1 CORE-3 / CTBC1-2 CORE-1

1200/1A

5 P 20

10

ABB, REB 500

40 of 43

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
Revision : A
S.No.

Description

CT No.

Ratio
(A/A)

Class

Burden
(VA)

Date : 7.04.2004

Ukp
(V)

Rct
(Ohm)

Relay

12.

33kV Bus Section Feeder Metering

CT-BC1-1 CORE-2

1200/1A

0.5 S

10

13.

33kV Bus Section Feeder Directional Overcurrent Protection


(51-51N)

CT-BC1-1 CORE-1

1200/1A

5 P 20

10

SPAJ 140C

14.

11kV Transformer Feeder


-Directional Over Current
Protection (51-51N)

CT-T1-2, CORE-4

1000-800/1A

5 P 20

10

SPAJ 140C

15.

11kV Transformer Feeder


-Metering

CT-T1-2, CORE-3

1000-800/1A

0.5 S

10

16.

11kV Cable/Capacitor Bank


Feeder -Directional Over Current
Protection (51-51N)

CT-2, 4 CORE-1

600-300/1A

5 P 20

10

1.5

REF 542 Plus

17.

11kV Cable/Capacitor Bank


Feeder - Metering

CT-2, 4 CORE-2

600-300/1A

0.5 S

10

1.5

18.

11kV Aux. Transformer FeederOver Current Protection

CT-3 CORE-1

30/1A

5 P 20

10

REF 542 Plus

19.

11kV Aux. Transformer FeederMetering

CT-3 CORE-2

30/1A

0.5 S

10

20.

11kV Bus Section Feeder- Over


Current Protection

CT-1 CORE-1

1600/1A

5 P 20

10

41 of 43

REF 542 Plus

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)
Revision : A
S.No.

21.

S.No.
1.
2.
3.
4.

1.
2.
3.
4.
5.

Description

11kV Bus Section FeederMetering

VT Data
33kV LINE VT - METERING
33kV LINE VT- PROTECTION
33kV BUS VT
11kV BUS VT
Technical Data: 33kV Side
Rated Voltage
Service Voltage
Frequency
Continuous Thermal Current
Short time Current (3 sec.)

CT No.

CT-1 CORE-2

VT No.
PT-F1, CORE-1
PT-F1, CORE-2
PT-BUS-1, CORE-1
Core-1

Additional CTs
requirements
36 kV
33 kV
50 Hz
150 %
31.5 kA

Ratio
(A/A)

Class

1600/1A

Ratio
(V/V)

0.5 S

Burden
(VA)
19.97
0.83
14.97
19.97

Technical Data: 11kV Side


Rated Voltage
Service Voltage
Frequency
Continuous Thermal Current
Short time Current (3 sec.)

42 of 43

Burden
(VA)

Date : 7.04.2004

Ukp
(V)

10

Rct
(Ohm)

Selected Class
(VA)
100
Cl :1
50
Cl :3P
100
Cl :1
100
Cl :1

12 kV
11 kV
50 Hz
150 %
31.5 kA

Relay

LARSEN & TOUBRO LIMITED


ECC Division - EDRC (Electrical)

REFERENCES
CT / VT PARAMETER CALCULATION
S.No.
a.

Description
ABB's Application guide to Overcurrent Modules and functions of SPACOM and
RE_ Series

b.

SPAS 348C Relay Catalogue for Relay Burden Information

c.

REJ 527 Relay Catalogue for Relay Burden Information

d.

Solkar Rf Relay Catalogue for Current Transformer Requirement

e.

Circuitor CVKm Multifunction Meter Catalogue

f.

CELSA CRI Ammeter Transducer

e.

REB 500 Relay Catalogue for Burden Information

g.

ABB's Requirement on Current Transformers for REB 500

h.

RET 316*4 Relay Catalogue for Burden Information

I.

ABB's Requirement on Current Transformers for RET 316 / RET 316*4

j.

SPAJ 140 C Relay Catalogue for Burden Information

k.

SPAJ 115 C Relay Catalogue

l.

ABB's Requirement on Current Transformers for SPAJ 115C

m.

REJ 521 Relay Catalogue for Burden Information

n.

REF 542 Plus Relay Catalogue for Burden Information

43 of 43