PROJECT

LOCATION
CLIENT
CONSULTANT

G+5 BUILDING HEAT LOAD


Laxmi nagar , New delhi.
XYZ
ABC
Area or

Item

Sun Gain or
Factor

Btu/Hour

Temp. Diff.
ROOM HEAT
Quantity
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N
SqFt x
F
x
0.00
Glass - NE
SqFt x
F
x
0.00
Glass - E
SqFt x
F
x
0.00
Glass - SE
SqFt x
F
x
0.00
Glass - S
SqFt x
F
x
0.00
Glass - SW
SqFt x
F
x
0.00
Glass - W
164.00 SqFt x 40.00
F
x
0.65
4,264.00
Glass - NW
SqFt x
F
x
0.00
Skylight
SqFt x
F
x
0.00
Solar & Transmission Gain - Walls & Roof
Wall - N
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NE
SqFt x
F
x
0.00
Wall - E
SqFt x
F
x
0.00
Wall - SE
SqFt x
F
x
0.00
Wall - S
SqFt x
F
x
0.00
Wall - SW
SqFt x
F
x
0.00
Wall - W
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NW
SqFt x
F
x
0.00
Roof
0.00 SqFt x 0.00
F
x
0.00
0.00
Transmission Gain - Except Walls & Roof
All Glass
40.00 SqFt x 35.00
F
x
0.65
910.00
Partition
300.80 SqFt x 30.00
F
x
0.32
2,887.68
Ceiling
160.96 SqFt x 30.00
F
x
0.16
772.61
Floor
160.96 SqFt x 30.00
F
x
0.16
772.61
INFILTRATION AND BY PASSED AIR
Infiltration
76.00 CFM x 35.00 T.Diff
x
1.08
2,872.80
Outside Air
180.00 CFM x 35.00 T.Diff
x 0.3x 1.08 2,041.20
Internal Heat
People
6.00 Nos. x 245.00 Btu/Hour Per Person
1,470.00
Lighting
160.97 SqFt x 0.75 W/SqFt
x
3.41
409.14
Equipments
160.97 SqFt x 2.48 W/SqFt
x
3.41
1,363.94
Power
0.00 kW/H x
0.00
0.00
Sub Total
17,763.98
Factor
5-10%
1,776.40
Effective Room Sensible Heat
19,540.38
ROOM LATENT HEAT
Infiltration
76.00 CFM x 9.00 Gr/Lb
x
0.68
465.12
Outside Air
180.00 CFM x 9.00 Gr/Lb
x BFx0.68
330.48
People
6.00 Nos. x 205.00 Btu/Hour Per Person
1,230.00
Sub Total
2,025.60
Factor
2.5 - 5%
101.28
Effective Room Latent Heat
2,126.88

FLOOR
SPACE REFERENCE
AREA ( SqFt)
Height (Ft)
Volume (CuFt)
Estimate for
Design Conditions
Ambient
Room
Difference

1st

DB (F)
110.00
75.00
35.00

By Pass Factor (BF)


Contact Factor (CF = 1 - BF)
CFM Ventilat
CFM Per Person
30.00 No
CFM Per SqFt
0.33 Sqft
Air Change Per Hour (CFM)
CFM
Cu.ft 1,609.65 x
CFM Infiltrat
window
x
Revolving Doors (People)
x
Open Doors
x
Crack
(feet)
x

Supply CFM from


Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room
Apparatus Dew Po
Indicated ADP (F)
Selected ADP (F)

Dehumidified
(Room DB - ADP) x CF
DEHUMIDIFIED Cfm (AIR QUANTITY)
Effective Room Sensible Heat
Dehumidified Rise x 1.08

TOTAL HEAT CAPACITY


3.01

1.00 SENSIBLE HEAT CAPACITY


Grand Sensible Heat
12,000.00

2.00

TR =
CFM =

EFFECTIVE ROOM TOTAL HEAT


OUTSIDE AIR HEAT
Sensible
180.00 CFM x 35.00 F(TD)
Latent
180.00 CFM x 9.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
TONS=GRAND TOTAL HEAT/12000

21,667.26
x
x

CF x 1.08
CF x 0.68

1 - 3%

4,762.80
771.12
5,533.92
27,201.18
816.04
28,017.21
2.33

3.00
4.00
Notes:

1st floor Right side


HALL
160.97
10.00
1,609.65
Summer
WB (F)
RH (%)
75.00
20.00
63.00
50.00
-

SH Gr/Lb
75.00
66.00
9.00

=
=
CFM Ventilation
=
x
=
1.00
CFM Infiltration

6.00
160.97
1.00
x1/60
cfm/window
cfm/door
cfm/door
cfm/ft

Supply CFM from Machine


Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat
Apparatus Dew Point (ADP)

0.30
0.70

= 180.00
= 53.12
= 26.83
=
=
=
=

0.00
0.00
0.00
0.00
0.00

=
=
=

53.50

15.05

Dehumidified Rise
DEHUMIDIFIED Cfm (AIR QUANTITY)
=

1,202.19

CFM

565.03

L/s

2.33
933.91

TR
cfm

TR = 3.01
CFM =1202.19

PROJECT
LOCATION
CLIENT
CONSULTANT

G+5 BUILDING HEAT LOAD


Laxmi nagar , New delhi.
XYZ
ABC
Area or

Item

Sun Gain or
Factor

Temp. Diff.
ROOM HEAT
Quantity
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N
0.00 SqFt x 0.00
F
x
0.00
Glass - NE
SqFt x
F
x
Glass - E
SqFt x
F
x
Glass - SE
SqFt x
F
x
Glass - S
SqFt x
F
x
Glass - SW
SqFt x
F
x
Glass - W
SqFt x
F
x
Glass - NW
SqFt x
F
x
Skylight
SqFt x
F
x
Solar & Transmission Gain - Walls & Roof
Wall - N
0.00 SqFt x 0.00
F
x
0.00
Wall - NE
SqFt x
F
x
Wall - E
SqFt x
F
x
Wall - SE
SqFt x
F
x
Wall - S
SqFt x
F
x
Wall - SW
SqFt x
F
x
Wall - W
0.00 SqFt x 0.00
F
x
0.00
Wall - NW
SqFt x
F
x
Roof
0.00 SqFt x 0.00
F
x
0.00
Transmission Gain - Except Walls & Roof
All Glass
0.00 SqFt x 35.00
F
x
0.65
Partition
147.40 SqFt x 30.00
F
x
0.32
Ceiling
54.31 SqFt x 30.00
F
x
0.16
Floor
54.31 SqFt x 30.00
F
x
0.16
INFILTRATION AND BY PASSED AIR
Infiltration
20.00 CFM x 35.00 T.Diff
x
1.08
Outside Air
180.00 CFM x 35.00 T.Diff
x 0.3x 1.08
Internal Heat
People
6.00 Nos. x 245.00 Btu/Hour Per Person
Lighting
54.32 SqFt x 2.20 W/SqFt
x
3.41
Equipments
54.32 SqFt x 11.04 W/SqFt
x
3.41
Power
0.00 kW/H x
0.00
Sub Total
Factor
5-10%

Btu/Hour

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1,415.04
260.69
260.69
756.00
2,041.20
1,470.00
407.47
2,044.78
0.00
8,655.86
865.59

FLOOR
SPACE REFERENCE
AREA ( SqFt)
Height (Ft)
Volume (CuFt)
Estimate for
Design Conditions
Ambient
Room
Difference

By Pass Factor (BF)


Contact Factor (CF = 1 - BF)
CFM Ve
CFM Per Person
CFM Per SqFt
Air Change Per Hour (CFM)
CFM
Cu.ft
CFM Inf
window
Revolving Doors (People)
Open Doors
Crack
(feet)

Supply CFM f
Effective Room Sensible Heat Fact
Effective Room Sensible Heat/Eff R
Apparatus De
Indicated ADP (F)
Selected ADP (F)
Dehumid
(Room DB - ADP) x CF
DEHUMIDIFIED Cfm (AIR QUANT
Effective Room Sensible Heat
Dehumidified Rise x 1.08

TOTAL HEAT CAPACITY


1.37

Effective Room Sensible Heat


9,521.45
ROOM LATENT HEAT
Infiltration
20.00 CFM x 9.00 Gr/Lb
x
0.68
122.40
Outside Air
180.00 CFM x 9.00 Gr/Lb
x BFx0.68
330.48
People
6.00 Nos. x 205.00 Btu/Hour Per Person
1,230.00
Sub Total
1,682.88
Factor
2.5 - 5%
84.14
Effective Room Latent Heat
1,767.02
EFFECTIVE ROOM TOTAL HEAT
11,288.48
OUTSIDE AIR HEAT
Sensible
180.00 CFM x 35.00 F(TD)
x CF x 1.08 4,762.80
Latent
180.00 CFM x 9.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
TONS=GRAND TOTAL HEAT/12000

CF x 0.68

1 - 3%

771.12
5,533.92
16,822.40
504.67
17,327.07
1.44

1.00 SENSIBLE HEAT CAPACITY


Grand Sensible Heat
12,000.00

2.00
3.00
4.00
Notes:

DB (F)
110.00
75.00
35.00

1st floor Right side


DINING
54.32
10.00
543.15
Summer
WB (F)
RH (%)
75.00
20.00
63.00
50.00
-

DIMENSION
7.41
7.33
Area
54.3153

INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ON

SH Gr/Lb
75.00
66.00
9.00

=
=

ctor (CF = 1 - BF)


CFM Ventilation
30.00 No
=
0.33 Sqft
x
Per Hour (CFM)
=
543.15 x 1.00
CFM Infiltration
x
Doors (People)
x
x
x

6.00
54.32
1.00
x1/60
cfm/window
cfm/door
cfm/door
cfm/ft

Supply CFM from Machine


oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat
Apparatus Dew Point (ADP)

0.30
0.70

= 180.00
= 17.92
=

9.05

=
=
=
=

0.00
0.00
0.00
0.00
0.00

=
=
=

52.00

16.10

Dehumidified Rise
- ADP) x CF
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08
=

547.59

CFM

257.37

L/s

AT CAPACITY
TR = 1.37
CFM =547.59

HEAT CAPACITY
=

1.44
577.57

TR
cfm

ACCEPT THIS TR
ACCEPT THIS CFM

EN IN BLUE COLOR BOXES ONLY

PROJECT
LOCATION
CLIENT
CONSULTANT

G+5 BUILDING HEAT LOAD


Laxmi nagar , New delhi.
XYZ
ABC
Area or

Item

Sun Gain or
Factor

Btu/Hour

Temp. Diff.
ROOM HEAT
Quantity
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N
SqFt x
F
x
0.00
Glass - NE
SqFt x
F
x
0.00
Glass - E
SqFt x
F
x
0.00
Glass - SE
SqFt x
F
x
0.00
Glass - S
SqFt x
F
x
0.00
Glass - SW
SqFt x
F
x
0.00
Glass - W
164.00 SqFt x 40.00
F
x
0.65
4,264.00
Glass - NW
SqFt x
F
x
0.00
Skylight
SqFt x
F
x
0.00
Solar & Transmission Gain - Walls & Roof
Wall - N
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NE
SqFt x
F
x
0.00
Wall - E
SqFt x
F
x
0.00
Wall - SE
SqFt x
F
x
0.00
Wall - S
59.10 SqFt x 43.00
F
x
0.48
1,219.82
Wall - SW
SqFt x
F
x
0.00
Wall - W
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NW
SqFt x
F
x
0.00
Roof
0.00 SqFt x 0.00
F
x
0.00
0.00
Transmission Gain - Except Walls & Roof
All Glass
40.00 SqFt x 35.00
F
x
0.65
910.00
Partition
101.60 SqFt x 30.00
F
x
0.32
975.36
Ceiling
148.68 SqFt x 30.00
F
x
0.16
713.66
Floor
148.68 SqFt x 30.00
F
x
0.16
713.66
INFILTRATION AND BY PASSED AIR
Infiltration
76.00 CFM x 35.00 T.Diff
x
1.08
2,872.80
Outside Air
60.00 CFM x 35.00 T.Diff
x 0.3x 1.08
680.40
Internal Heat
People
2.00 Nos. x 245.00 Btu/Hour Per Person
490.00
Lighting
148.68 SqFt x 0.40 W/SqFt
x
3.41
204.57
Equipments
148.68 SqFt x 2.35 W/SqFt
x
3.41
1,193.48
Power
0.00 kW/H x
0.00
0.00
Sub Total
14,237.76
Factor
5-10%
1,423.78

FLOOR
SPACE REFERENCE
AREA ( SqFt)
Height (Ft)
Volume (CuFt)
Estimate for
Design Conditions
Ambient
Room
Difference

By Pass Factor (BF)


Contact Factor (CF = 1 - BF)
CFM Ve
CFM Per Person
CFM Per SqFt
Air Change Per Hour (CFM)
CFM
Cu.ft
CFM Inf
window
Revolving Doors (People)
Open Doors
Crack
(feet)

Supply CFM f
Effective Room Sensible Heat Fact
Effective Room Sensible Heat/Eff R
Apparatus De
Indicated ADP (F)
Selected ADP (F)
Dehumid
(Room DB - ADP) x CF
DEHUMIDIFIED Cfm (AIR QUANT
Effective Room Sensible Heat
Dehumidified Rise x 1.08

TOTAL HEAT CAPACITY


2.48

Effective Room Sensible Heat


15,661.54
ROOM LATENT HEAT
Infiltration
76.00 CFM x 9.00 Gr/Lb
x
0.68
465.12
Outside Air
60.00 CFM x 9.00 Gr/Lb
x BFx0.68
110.16
People
2.00 Nos. x 205.00 Btu/Hour Per Person
410.00
Sub Total
985.28
Factor
2.5 - 5%
49.26
Effective Room Latent Heat
1,034.54
EFFECTIVE ROOM TOTAL HEAT
16,696.08
OUTSIDE AIR HEAT
Sensible
60.00 CFM x 35.00 F(TD)
x CF x 1.08 1,587.60
Latent
60.00 CFM x 9.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
TONS=GRAND TOTAL HEAT/12000

CF x 0.68

1 - 3%

257.04
1,844.64
18,540.72
556.22
19,096.94
1.59

1.00 SENSIBLE HEAT CAPACITY


Grand Sensible Heat
12,000.00

2.00
3.00
4.00
Notes:

DB (F)
110.00
75.00
35.00

1st floor Right side


BEDROOM
148.68
10.00
1,486.80
Summer
WB (F)
RH (%)
75.00
20.00
63.00
50.00
-

DIMENSION
10.5
14.16
Area
148.68

INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BO

SH Gr/Lb
75.00
66.00
9.00

=
=

ctor (CF = 1 - BF)


CFM Ventilation
30.00 No
=
0.33 Sqft
x
Per Hour (CFM)
=
1,486.80 x 1.00
CFM Infiltration
x
Doors (People)
x
x
x

2.00
148.68
1.00
x1/60
cfm/window
cfm/door
cfm/door
cfm/ft

Supply CFM from Machine


oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat
Apparatus Dew Point (ADP)

0.30
0.70

= 60.00
= 49.06
= 24.78
=
=
=
=

0.00
0.00
0.00
0.00
0.00

=
=
=

54.15

14.60

Dehumidified Rise
- ADP) x CF
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08
=

993.59

CFM

466.99

L/s

AT CAPACITY
TR = 2.48
CFM =993.59

ACCEPT THIS TR

HEAT CAPACITY
=

1.59
636.56

TR
cfm

ACCEPT THIS CFM

EN IN BLUE COLOR BOXES ONLY

PROJECT
LOCATION
CLIENT
CONSULTANT

G+5 BUILDING HEAT LOAD


Laxmi nagar , New delhi.
XYZ
ABC
Area or

Item

Sun Gain or
Factor

Btu/Hour

Temp. Diff.
ROOM HEAT
Quantity
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N
SqFt x
F
x
0.00
Glass - NE
SqFt x
F
x
0.00
Glass - E
40.00 SqFt x 12.00
F
x
0.65
312.00
Glass - SE
SqFt x
F
x
0.00
Glass - S
SqFt x
F
x
0.00
Glass - SW
SqFt x
F
x
0.00
Glass - W
SqFt x
F
x
0.00
Glass - NW
SqFt x
F
x
0.00
Skylight
SqFt x
F
x
0.00
Solar & Transmission Gain - Walls & Roof
Wall - N
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NE
SqFt x
F
x
0.00
Wall - E
101.60 SqFt x 29.00
F
x
0.48
1,414.27
Wall - SE
SqFt x
F
x
0.00
Wall - S
SqFt x
F
x
0.00
Wall - SW
SqFt x
F
x
0.00
Wall - W
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NW
SqFt x
F
x
0.00
Roof
0.00 SqFt x 0.00
F
x
0.00
0.00
Transmission Gain - Except Walls & Roof
All Glass
40.00 SqFt x 35.00
F
x
0.65
910.00
Partition
161.60 SqFt x 30.00
F
x
0.32
1,551.36
Ceiling
172.19 SqFt x 30.00
F
x
0.16
826.49
Floor
172.19 SqFt x 30.00
F
x
0.16
826.49
INFILTRATION AND BY PASSED AIR
Infiltration
56.00 CFM x 35.00 T.Diff
x
1.08
2,116.80
Outside Air
120.00 CFM x 35.00 T.Diff
x 0.3x 1.08 1,360.80
Internal Heat
People
4.00 Nos. x 245.00 Btu/Hour Per Person
980.00
Lighting
172.19 SqFt x 0.58 W/SqFt
x
3.41
340.99
Equipments
172.19 SqFt x 2.61 W/SqFt
x
3.41
1,534.41
Power
0.00 kW/H x
0.00
0.00
Sub Total
12,173.61
Factor
5-10%
1,217.36

FLOOR
SPACE REFERENCE
AREA ( SqFt)
Height (Ft)
Volume (CuFt)
Estimate for
Design Conditions
Ambient
Room
Difference

By Pass Factor (BF)


Contact Factor (CF = 1 - BF)
CFM Ve
CFM Per Person
CFM Per SqFt
Air Change Per Hour (CFM)
CFM
Cu.ft
CFM Inf
window
Revolving Doors (People)
Open Doors
Crack
(feet)

Supply CFM f
Effective Room Sensible Heat Fact
Effective Room Sensible Heat/Eff R
Apparatus De
Indicated ADP (F)
Selected ADP (F)
Dehumid
(Room DB - ADP) x CF
DEHUMIDIFIED Cfm (AIR QUANT
Effective Room Sensible Heat
Dehumidified Rise x 1.08

TOTAL HEAT CAPACITY


2.06

Effective Room Sensible Heat


13,390.97
ROOM LATENT HEAT
Infiltration
56.00 CFM x 9.00 Gr/Lb
x
0.68
342.72
Outside Air
120.00 CFM x 9.00 Gr/Lb
x BFx0.68
220.32
People
4.00 Nos. x 205.00 Btu/Hour Per Person
820.00
Sub Total
1,383.04
Factor
2.5 - 5%
69.15
Effective Room Latent Heat
1,452.19
EFFECTIVE ROOM TOTAL HEAT
14,843.16
OUTSIDE AIR HEAT
Sensible
120.00 CFM x 35.00 F(TD)
x CF x 1.08 3,175.20
Latent
120.00 CFM x 9.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
TONS=GRAND TOTAL HEAT/12000

CF x 0.68

1 - 3%

514.08
3,689.28
18,532.44
555.97
19,088.42
1.59

1.00 SENSIBLE HEAT CAPACITY


Grand Sensible Heat
12,000.00

2.00
3.00
4.00
Notes:

DB (F)
110.00
75.00
35.00

1st floor Right side


MASTER BEDROOM
172.19
10.00
1,721.86
Summer
WB (F)
RH (%)
SH Gr/Lb
75.00
20.00
75.00
63.00
50.00
66.00
9.00

=
=

ctor (CF = 1 - BF)


CFM Ventilation
30.00 No
=
0.33 Sqft
x
Per Hour (CFM)
=
1,721.86 x 1.00
CFM Infiltration
x
Doors (People)
x
x
x

4.00
172.19
1.00
x1/60
cfm/window
cfm/door
cfm/door
cfm/ft

Supply CFM from Machine


oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat
Apparatus Dew Point (ADP)

DIMENSION
12.16
14.16
Area
172.1856

INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BO

0.30
0.70

= 120.00
= 56.82
= 28.70
=
=
=
=

0.00
0.00
0.00
0.00
0.00

=
=
=

53.50

15.05

Dehumidified Rise
- ADP) x CF
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08
=

823.86

CFM

387.21

L/s

AT CAPACITY
TR = 2.06
CFM =823.86

ACCEPT THIS TR

HEAT CAPACITY
=

1.59
636.28

TR
cfm

ACCEPT THIS CFM

EN IN BLUE COLOR BOXES ONLY

PROJECT
LOCATION
CLIENT
CONSULTANT

G+5 BUILDING HEAT LOAD


Laxmi nagar , New delhi.
XYZ
ABC
Area or

Item

Sun Gain or
Factor

Btu/Hour

Temp. Diff.
ROOM HEAT
Quantity
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N
SqFt x
F
x
0.00
Glass - NE
SqFt x
F
x
0.00
Glass - E
SqFt x
F
x
0.00
Glass - SE
SqFt x
F
x
0.00
Glass - S
SqFt x
F
x
0.00
Glass - SW
SqFt x
F
x
0.00
Glass - W
164.00 SqFt x 40.00
F
x
0.65
4,264.00
Glass - NW
SqFt x
F
x
0.00
Skylight
SqFt x
F
x
0.00
Solar & Transmission Gain - Walls & Roof
Wall - N
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NE
SqFt x
F
x
0.00
Wall - E
SqFt x
F
x
0.00
Wall - SE
SqFt x
F
x
0.00
Wall - S
SqFt x
F
x
0.00
Wall - SW
SqFt x
F
x
0.00
Wall - W
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NW
SqFt x
F
x
0.00
Roof
0.00 SqFt x 0.00
F
x
0.00
0.00
Transmission Gain - Except Walls & Roof
All Glass
40.00 SqFt x 35.00
F
x
0.65
910.00
Partition
218.30 SqFt x 30.00
F
x
0.32
2,095.68
Ceiling
160.97 SqFt x 30.00
F
x
0.16
772.63
Floor
160.97 SqFt x 30.00
F
x
0.16
772.63
INFILTRATION AND BY PASSED AIR
Infiltration
76.00 CFM x 35.00 T.Diff
x
1.08
2,872.80
Outside Air
180.00 CFM x 35.00 T.Diff
x 0.3x 1.08 2,041.20
Internal Heat
People
6.00 Nos. x 245.00 Btu/Hour Per Person
1,470.00
Lighting
160.97 SqFt x 0.75 W/SqFt
x
3.41
409.14
Equipments
160.97 SqFt x 2.48 W/SqFt
x
3.41
1,363.94
Power
0.00 kW/H x
0.00
0.00
Sub Total
16,972.03
Factor
5-10%
1,697.20
Effective Room Sensible Heat
18,669.23
ROOM LATENT HEAT
Infiltration
76.00 CFM x 9.00 Gr/Lb
x
0.68
465.12
Outside Air
180.00 CFM x 9.00 Gr/Lb
x BFx0.68
330.48
People
6.00 Nos. x 205.00 Btu/Hour Per Person
1,230.00
Sub Total
2,025.60
Factor
2.5 - 5%
101.28
Effective Room Latent Heat
2,126.88

FLOOR
SPACE REFERENCE
AREA ( SqFt)
Height (Ft)
Volume (CuFt)
Estimate for
Design Conditions
Ambient
Room
Difference

1st

DB (F)
110.00
75.00
35.00

By Pass Factor (BF)


Contact Factor (CF = 1 - BF)
CFM Ventilat
CFM Per Person
30.00 No
CFM Per SqFt
0.33 Sqft
Air Change Per Hour (CFM)
CFM
Cu.ft 1,609.65 x
CFM Infiltrat
window
x
Revolving Doors (People)
x
Open Doors
x
Crack
(feet)
x

Supply CFM from


Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room
Apparatus Dew Po
Indicated ADP (F)
Selected ADP (F)

Dehumidified
(Room DB - ADP) x CF
DEHUMIDIFIED Cfm (AIR QUANTITY)
Effective Room Sensible Heat
Dehumidified Rise x 1.08

TOTAL HEAT CAPACITY


2.84

1.00 SENSIBLE HEAT CAPACITY


Grand Sensible Heat
12,000.00

2.00

TR =
CFM =

EFFECTIVE ROOM TOTAL HEAT


OUTSIDE AIR HEAT
Sensible
180.00 CFM x 35.00 F(TD)
Latent
180.00 CFM x 9.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
TONS=GRAND TOTAL HEAT/12000

20,796.11
x
x

CF x 1.08
CF x 0.68

1 - 3%

4,762.80
771.12
5,533.92
26,330.03
789.90
27,119.93
2.26

3.00
4.00
Notes:

1st floor Right side


HALL
160.97
10.00
1,609.65
Summer
WB (F)
RH (%)
75.00
20.00
63.00
50.00
-

SH Gr/Lb
75.00
66.00
9.00

=
=
CFM Ventilation
=
x
=
1.00
CFM Infiltration

6.00
160.97
1.00
x1/60
cfm/window
cfm/door
cfm/door
cfm/ft

Supply CFM from Machine


Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat
Apparatus Dew Point (ADP)

0.30
0.70

= 180.00
= 53.12
= 26.83
=
=
=
=

0.00
0.00
0.00
0.00
0.00

=
=
=

53.25

15.23

Dehumidified Rise
DEHUMIDIFIED Cfm (AIR QUANTITY)
=

1,135.39

CFM

533.63

L/s

2.26
904.00

TR
cfm

TR = 2.84
CFM =1135.39

PROJECT
LOCATION
CLIENT
CONSULTANT

G+5 BUILDING HEAT LOAD


Laxmi nagar , New delhi.
XYZ
ABC
Area or

Item

Sun Gain or
Factor

Temp. Diff.
ROOM HEAT
Quantity
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N
0.00 SqFt x 0.00
F
x
0.00
Glass - NE
SqFt x
F
x
Glass - E
SqFt x
F
x
Glass - SE
SqFt x
F
x
Glass - S
SqFt x
F
x
Glass - SW
SqFt x
F
x
Glass - W
SqFt x
F
x
Glass - NW
SqFt x
F
x
Skylight
SqFt x
F
x
Solar & Transmission Gain - Walls & Roof
Wall - N
0.00 SqFt x 0.00
F
x
0.00
Wall - NE
SqFt x
F
x
Wall - E
SqFt x
F
x
Wall - SE
SqFt x
F
x
Wall - S
SqFt x
F
x
Wall - SW
SqFt x
F
x
Wall - W
0.00 SqFt x 0.00
F
x
0.00
Wall - NW
SqFt x
F
x
Roof
0.00 SqFt x 0.00
F
x
0.00
Transmission Gain - Except Walls & Roof
All Glass
0.00 SqFt x 35.00
F
x
0.65
Partition
156.60 SqFt x 30.00
F
x
0.32
Ceiling
61.20 SqFt x 30.00
F
x
0.16
Floor
61.20 SqFt x 30.00
F
x
0.16
INFILTRATION AND BY PASSED AIR
Infiltration
20.00 CFM x 35.00 T.Diff
x
1.08
Outside Air
180.00 CFM x 35.00 T.Diff
x 0.3x 1.08
Internal Heat
People
6.00 Nos. x 245.00 Btu/Hour Per Person
Lighting
61.20 SqFt x 1.96 W/SqFt
x
3.41
Equipments
61.20 SqFt x 9.80 W/SqFt
x
3.41
Power
0.00 kW/H x
0.00
Sub Total
Factor
5-10%

Btu/Hour

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1,503.36
293.76
293.76
756.00
2,041.20
1,470.00
409.04
2,046.00
0.00
8,813.12
881.31

FLOOR
SPACE REFERENCE
AREA ( SqFt)
Height (Ft)
Volume (CuFt)
Estimate for
Design Conditions
Ambient
Room
Difference

By Pass Factor (BF)


Contact Factor (CF = 1 - BF)
CFM Ve
CFM Per Person
CFM Per SqFt
Air Change Per Hour (CFM)
CFM
Cu.ft
CFM Inf
window
Revolving Doors (People)
Open Doors
Crack
(feet)

Supply CFM f
Effective Room Sensible Heat Fact
Effective Room Sensible Heat/Eff R
Apparatus De
Indicated ADP (F)
Selected ADP (F)
Dehumid
(Room DB - ADP) x CF
DEHUMIDIFIED Cfm (AIR QUANT
Effective Room Sensible Heat
Dehumidified Rise x 1.08

TOTAL HEAT CAPACITY


1.39

Effective Room Sensible Heat


9,694.43
ROOM LATENT HEAT
Infiltration
20.00 CFM x 9.00 Gr/Lb
x
0.68
122.40
Outside Air
180.00 CFM x 9.00 Gr/Lb
x BFx0.68
330.48
People
6.00 Nos. x 205.00 Btu/Hour Per Person
1,230.00
Sub Total
1,682.88
Factor
2.5 - 5%
84.14
Effective Room Latent Heat
1,767.02
EFFECTIVE ROOM TOTAL HEAT
11,461.45
OUTSIDE AIR HEAT
Sensible
180.00 CFM x 35.00 F(TD)
x CF x 1.08 4,762.80
Latent
180.00 CFM x 9.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
TONS=GRAND TOTAL HEAT/12000

CF x 0.68

1 - 3%

771.12
5,533.92
16,995.37
509.86
17,505.23
1.46

1.00 SENSIBLE HEAT CAPACITY


Grand Sensible Heat
12,000.00

2.00
3.00
4.00
Notes:

DB (F)
110.00
75.00
35.00

1st floor Right side


DINING
61.20
10.00
612.00
Summer
WB (F)
RH (%)
75.00
20.00
63.00
50.00
-

DIMENSION
7.5
8.16
Area
61.2

INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ON

SH Gr/Lb
75.00
66.00
9.00

=
=

ctor (CF = 1 - BF)


CFM Ventilation
30.00 No
=
0.33 Sqft
x
Per Hour (CFM)
=
612.00 x 1.00
CFM Infiltration
x
Doors (People)
x
x
x

6.00
61.20
1.00
x1/60
cfm/window
cfm/door
cfm/door
cfm/ft

Supply CFM from Machine


oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat
Apparatus Dew Point (ADP)

0.30
0.70

= 180.00
= 20.20
= 10.20
=
=
=
=

0.00
0.00
0.00
0.00
0.00

=
=
=

52.00

16.10

Dehumidified Rise
- ADP) x CF
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08
=

557.54

CFM

262.04

L/s

AT CAPACITY
TR = 1.39
CFM =557.54

HEAT CAPACITY
=

1.46
583.51

TR
cfm

ACCEPT THIS TR
ACCEPT THIS CFM

EN IN BLUE COLOR BOXES ONLY

PROJECT
LOCATION
CLIENT
CONSULTANT

G+5 BUILDING HEAT LOAD


Laxmi nagar , New delhi.
XYZ
ABC
Area or

Item

Sun Gain or
Factor

Btu/Hour

Temp. Diff.
ROOM HEAT
Quantity
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N
SqFt x
F
x
0.00
Glass - NE
SqFt x
F
x
0.00
Glass - E
SqFt x
F
x
0.00
Glass - SE
SqFt x
F
x
0.00
Glass - S
SqFt x
F
x
0.00
Glass - SW
12.00 SqFt x
F
x
0.00
Glass - W
164.00 SqFt x 20.00
F
x
0.65
2,132.00
Glass - NW
SqFt x
F
x
0.00
Skylight
SqFt x
F
x
0.00
Solar & Transmission Gain - Walls & Roof
Wall - N
105.00 SqFt x 27.00
F
x
0.48
1,360.80
Wall - NE
SqFt x
F
x
0.00
Wall - E
SqFt x
F
x
0.00
Wall - SE
SqFt x
F
x
0.00
Wall - S
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - SW
SqFt x
F
x
0.00
Wall - W
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NW
SqFt x
F
x
0.00
Roof
0.00 SqFt x 0.00
F
x
0.00
0.00
Transmission Gain - Except Walls & Roof
All Glass
20.00 SqFt x 35.00
F
x
0.65
455.00
Partition
181.60 SqFt x 30.00
F
x
0.32
1,743.36
Ceiling
148.68 SqFt x 30.00
F
x
0.16
713.66
Floor
148.68 SqFt x 30.00
F
x
0.16
713.66
INFILTRATION AND BY PASSED AIR
Infiltration
38.00 CFM x 35.00 T.Diff
x
1.08
1,436.40
Outside Air
60.00 CFM x 35.00 T.Diff
x 0.3x 1.08
680.40
Internal Heat
People
2.00 Nos. x 245.00 Btu/Hour Per Person
490.00
Lighting
148.68 SqFt x 0.40 W/SqFt
x
3.41
204.57
Equipments
148.68 SqFt x 2.35 W/SqFt
x
3.41
1,193.48
Power
0.00 kW/H x
0.00
0.00
Sub Total
11,123.34
Factor
5-10%
1,112.33

FLOOR
SPACE REFERENCE
AREA ( SqFt)
Height (Ft)
Volume (CuFt)
Estimate for
Design Conditions
Ambient
Room
Difference

By Pass Factor (BF)


Contact Factor (CF = 1 - BF)
CFM Ve
CFM Per Person
CFM Per SqFt
Air Change Per Hour (CFM)
CFM
Cu.ft
CFM Inf
window
Revolving Doors (People)
Open Doors
Crack
(feet)

Supply CFM f
Effective Room Sensible Heat Fact
Effective Room Sensible Heat/Eff R
Apparatus De
Indicated ADP (F)
Selected ADP (F)
Dehumid
(Room DB - ADP) x CF
DEHUMIDIFIED Cfm (AIR QUANT
Effective Room Sensible Heat
Dehumidified Rise x 1.08

TOTAL HEAT CAPACITY


1.95

Effective Room Sensible Heat


12,235.67
ROOM LATENT HEAT
Infiltration
38.00 CFM x 9.00 Gr/Lb
x
0.68
232.56
Outside Air
60.00 CFM x 9.00 Gr/Lb
x BFx0.68
110.16
People
2.00 Nos. x 205.00 Btu/Hour Per Person
410.00
Sub Total
752.72
Factor
2.5 - 5%
37.64
Effective Room Latent Heat
790.36
EFFECTIVE ROOM TOTAL HEAT
13,026.03
OUTSIDE AIR HEAT
Sensible
60.00 CFM x 35.00 F(TD)
x CF x 1.08 1,587.60
Latent
60.00 CFM x 9.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
TONS=GRAND TOTAL HEAT/12000

CF x 0.68

1 - 3%

257.04
1,844.64
14,870.67
446.12
15,316.79
1.28

1.00 SENSIBLE HEAT CAPACITY


Grand Sensible Heat
12,000.00

2.00
3.00
4.00
Notes:

DB (F)
110.00
75.00
35.00

1st floor Right side


BEDROOM
148.68
10.00
1,486.80
Summer
WB (F)
RH (%)
75.00
20.00
63.00
50.00
-

DIMENSION
10.5
14.16
Area
148.68

INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BO

SH Gr/Lb
75.00
66.00
9.00

=
=

ctor (CF = 1 - BF)


CFM Ventilation
30.00 No
=
0.33 Sqft
x
Per Hour (CFM)
=
1,486.80 x 1.00
CFM Infiltration
x
Doors (People)
x
x
x

2.00
148.68
1.00
x1/60
cfm/window
cfm/door
cfm/door
cfm/ft

Supply CFM from Machine


oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat
Apparatus Dew Point (ADP)

0.30
0.70

= 60.00
= 49.06
= 24.78
=
=
=
=

0.00
0.00
0.00
0.00
0.00

=
=
=

54.30

14.49

Dehumidified Rise
- ADP) x CF
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08
=

781.87

CFM

367.48

L/s

AT CAPACITY
TR = 1.95
CFM =781.87

ACCEPT THIS TR

HEAT CAPACITY
=

1.28
510.56

TR
cfm

ACCEPT THIS CFM

EN IN BLUE COLOR BOXES ONLY

PROJECT
LOCATION
CLIENT
CONSULTANT

G+5 BUILDING HEAT LOAD


Laxmi nagar , New delhi.
XYZ
ABC
Area or

Item

Sun Gain or
Factor

Btu/Hour

Temp. Diff.
ROOM HEAT
Quantity
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N
SqFt x
F
x
0.00
Glass - NE
SqFt x
F
x
0.00
Glass - E
20.00 SqFt x 12.00
F
x
0.65
156.00
Glass - SE
SqFt x
F
x
0.00
Glass - S
SqFt x
F
x
0.00
Glass - SW
SqFt x
F
x
0.00
Glass - W
SqFt x
F
x
0.00
Glass - NW
SqFt x
F
x
0.00
Skylight
SqFt x
F
x
0.00
Solar & Transmission Gain - Walls & Roof
Wall - N
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NE
SqFt x
F
x
0.00
Wall - E
86.60 SqFt x 29.00
F
x
0.48
1,205.47
Wall - SE
SqFt x
F
x
0.00
Wall - S
SqFt x
F
x
0.00
Wall - SW
SqFt x
F
x
0.00
Wall - W
0.00 SqFt x 0.00
F
x
0.00
0.00
Wall - NW
SqFt x
F
x
0.00
Roof
0.00 SqFt x 0.00
F
x
0.00
0.00
Transmission Gain - Except Walls & Roof
All Glass
20.00 SqFt x 35.00
F
x
0.65
455.00
Partition
201.60 SqFt x 30.00
F
x
0.32
1,935.36
Ceiling
129.63 SqFt x 30.00
F
x
0.16
622.20
Floor
129.63 SqFt x 30.00
F
x
0.16
622.20
INFILTRATION AND BY PASSED AIR
Infiltration
38.00 CFM x 35.00 T.Diff
x
1.08
1,436.40
Outside Air
120.00 CFM x 35.00 T.Diff
x 0.3x 1.08 1,360.80
Internal Heat
People
4.00 Nos. x 245.00 Btu/Hour Per Person
980.00
Lighting
129.63 SqFt x 0.77 W/SqFt
x
3.41
340.99
Equipments
129.63 SqFt x 3.47 W/SqFt
x
3.41
1,534.44
Power
0.00 kW/H x
0.00
0.00
Sub Total
10,648.86
Factor
5-10%
1,064.89

FLOOR
SPACE REFERENCE
AREA ( SqFt)
Height (Ft)
Volume (CuFt)
Estimate for
Design Conditions
Ambient
Room
Difference

By Pass Factor (BF)


Contact Factor (CF = 1 - BF)
CFM Ve
CFM Per Person
CFM Per SqFt
Air Change Per Hour (CFM)
CFM
Cu.ft
CFM Inf
window
Revolving Doors (People)
Open Doors
Crack
(feet)

Supply CFM f
Effective Room Sensible Heat Fact
Effective Room Sensible Heat/Eff R
Apparatus De
Indicated ADP (F)
Selected ADP (F)
Dehumid
(Room DB - ADP) x CF
DEHUMIDIFIED Cfm (AIR QUANT
Effective Room Sensible Heat
Dehumidified Rise x 1.08

TOTAL HEAT CAPACITY


1.78

Effective Room Sensible Heat


11,713.75
ROOM LATENT HEAT
Infiltration
38.00 CFM x 9.00 Gr/Lb
x
0.68
232.56
Outside Air
120.00 CFM x 9.00 Gr/Lb
x BFx0.68
220.32
People
4.00 Nos. x 205.00 Btu/Hour Per Person
820.00
Sub Total
1,272.88
Factor
2.5 - 5%
63.64
Effective Room Latent Heat
1,336.52
EFFECTIVE ROOM TOTAL HEAT
13,050.27
OUTSIDE AIR HEAT
Sensible
120.00 CFM x 35.00 F(TD)
x CF x 1.08 3,175.20
Latent
120.00 CFM x 9.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
TONS=GRAND TOTAL HEAT/12000

CF x 0.68

1 - 3%

514.08
3,689.28
16,739.55
502.19
17,241.74
1.44

1.00 SENSIBLE HEAT CAPACITY


Grand Sensible Heat
12,000.00

2.00
3.00
4.00
Notes:

DB (F)
110.00
75.00
35.00

1st floor Right side


MASTER BEDROOM
129.63
10.00
1,296.26
Summer
WB (F)
RH (%)
SH Gr/Lb
75.00
20.00
75.00
63.00
50.00
66.00
9.00

=
=

ctor (CF = 1 - BF)


CFM Ventilation
30.00 No
=
0.33 Sqft
x
Per Hour (CFM)
=
1,296.26 x 1.00
CFM Infiltration
x
Doors (People)
x
x
x

4.00
129.63
1.00
x1/60
cfm/window
cfm/door
cfm/door
cfm/ft

Supply CFM from Machine


oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat
Apparatus Dew Point (ADP)

DIMENSION
12.16
10.66
Area
129.6256

INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BO

0.30
0.70

= 120.00
= 42.78
= 21.60
=
=
=
=

0.00
0.00
0.00
0.00
0.00

=
=
=

53.25

15.23

Dehumidified Rise
- ADP) x CF
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08
=

712.39

CFM

334.82

L/s

AT CAPACITY
TR = 1.78
CFM =712.39

ACCEPT THIS TR

HEAT CAPACITY
=

1.44
574.72

TR
cfm

ACCEPT THIS CFM

EN IN BLUE COLOR BOXES ONLY

G+5 BUILDING HEAT LOAD 1ST FLO


LEFT TOP FLAT IN 1ST FLOOR (3)
ROOMS
BEDROOM
DINING
HALL
MASTER BEDROOM

TOTAL TR
TOTAL CFM

CALCULATED
TR
CFM
1.25
501.85
1.42
571.71
1.81
727.12
1.33
533.15

DEHUMIDIFIED
TR
1.92
1.408
2.22
1.75

7.31 TR
2333.83 CFM

G+5 BUILDING HEAT LOAD 5th FLO


LEFT TOP
ROOMS
BEDROOM
DINING
HALL
MASTER BEDROOM

CALCULATED
TR
CFM
1.43
572
1.6
640
2.39
956
1.44
576

DEHUMIDIFIED
TR
2.25
1.63
3.16
1.78

RIGHT TOP
ROOMS
BEDROOM
DINING
HALL
MASTER BEDROOM

CALCULATED
TR
CFM
1.18
472
1.6
640
1.4
560
1.43
572

DEHUMIDIFIED
TR
1.78
1.64
1.95
1.81

TOTAL TR IN RHS IN 1ST FLOOR


TOTAL CFM IN RHS IN 1ST FLOOR

TOTAL TR IN 1ST FLOOR


TOTAL CFM IN 1ST FLOOR
TOTAL TR UPTO 4TH FLOOR
TOTAL CFM UPTO 4TH FLOOR

32.215896 TR
10056.331 CFM
128.86359 TR
40225.323 CFM

TOTAL TR 1-5th floor


total cfm 1-5th floor

160.66359 TR
50189.323 CFM

5 BUILDING HEAT LOAD 1ST FLOOR

T FLOOR (3)
DEHUMIDIFIED
CFM
771.95
563.5
890.07
703.57

LEFT BOTTOM FLAT IN 1ST FLOOR (4)


ROOMS
BEDROOM
DINING
HALL
MASTER BEDROOM

TOTAL TR
TOTAL CFM

CALCULATED
TR
CFM
1.7
680.8
1.45
582.7
1.36
547.8
1.385
554.09

DEHUMIDIFIED
TR
CFM
1024.25
2.56
574.54
1.43
858.87
2.14
694.63
1.73

7.88 TR
2365.39 CFM

5 BUILDING HEAT LOAD 5th FLOOR


LEFT BOTTOM
DEHUMIDIFIED
CFM
900
655.44
1267.87
712

ROOMS
HALL
DINING
BEDROOM
MASTER BEDROOM

CALCULATED
TR
CFM
2.5
1000
1.45
580
1.53
612
1.37
548

DEHUMIDIFIED
TR
CFM
3.37
348.02
1.44
577.92
2.41
966.29
1.67
671.46

RIGHT BOTTOM
DEHUMIDIFIED
CFM
713.39
656
782
726

17.025896
5357.1108

ROOMS
BEDROOM
DINING
HALL
MASTER BEDROOM

CALCULATED
TR
CFM
1.2
480
1.47
588
1.32
528
1.6
640

TOTAL TR IN 5TH FLOOR


TOTAL CFM IN 5TH FLOOR

31.8
9964

DEHUMIDIFIED
TR
CFM
1.74
696.53
1.41
565.62
1.59
639.14
2.1
840