SHEET NO.
SHEET TITLE
S-00
COVER SHEET
S-01
GENERAL NOTES
S-02
S-03
S-04
S-05
S-06
S-07
S-08
S-09
S-10
S-11
S-12
S-13
S-14
S-15
S-16
S-17
S-18
S-19
S-20
S-21
S-22
S-23
S-24
S-25
S-26
S-27
S-28
S-29
S-30
S-31
S-32
S-33
S-34
S-35
S-36
S-37
S-38
S-39
S-40
WALL LAYOUT
S-41
S-42
S-43
S-44
S-45
S-46
S-47
S-48
BEAM HEIGHT
ZONE B
TYPICAL LAP
(SEE NOTE 5)
ZONE C
G
ZONE A
L2
D
F
ZONE B
DRAWING
GENERAL NOTES - 1
H
ZONE C
ZONE B
STRUCTURE
ZONE A
SENIOR
PROJECT
Lc2
L1
D
BEAM HEIGHT
H
ZONE B
ZONE A
ZONE A
ZONE B
CLIENT
L2
B
L2
NOTES:
1. SEE BEAM SCHEDULE FOR STIRRUP TYPE AND SPACING.
2. ZONE A LENGTH SHALL BE TWICE THE BEAM HEIGHT, h.
3. THE FIRST STIRRUP IN ZONE A SHALL BE LOCATED 50.8mm MAXIMUM FROM THE FACE OF THE SUPPORT.
4. LAP SPLICES SHALL NOT BE LOCATED WITHIN THE BEAM/COLUMN JOINT, NOR WITHIN A DISTANCE OF 2H.
5. LAP SPLICES SHALL BE ENCLOSED BY HOOP STIRRUPS AT A MAXIMUM SPACING OF D/4 OR 101.6mm, WHICHEVER IS SMALLER.
Typical Concrete Beam Elevation 2S
2/20/2015
G
ZONE A
DATE
NOTES:
1. SEE BEAM SCHEDULE FOR STIRRUP TYPE AND SPACING.
2. ZONE A LENGTH SHALL BE TWICE THE BEAM HEIGHT, h.
3. THE FIRST STIRRUP IN ZONE A SHALL BE LOCATED 50.8mm MAXIMUM FROM THE FACE OF THE SUPPORT.
4. LAP SPLICES SHALL NOT BE LOCATED WITHIN THE BEAM/COLUMN JOINT, NOR WITHIN A DISTANCE OF 2H.
5. LAP SPLICES SHALL BE ENCLOSED BY HOOP STIRRUPS AT A MAXIMUM SPACING OF D/4 OR 101.6mm, WHICHEVER IS SMALLER.
BEAM HEIGHT
DESCRIPTION
Lc
L1
B
Lc1
L1
B
NO
TYPICAL LAP
(SEE NOTE 5)
ZONE C
G
ZONE B
CONSULTANT
ZONE A
TOSHIBA
PROJECT NUMBER
DATE
DESIGNED BY
CHECKED BY
SCALE
S-01