GENERAL STRUCTURAL NOTES

(PILES) FOUNDATION

1.

1.

MINIMUM REQUIREMENTS

STEEL DECK

UNLESS OTHERWISE NOTED ON DRAWINGS

3.

5.

READ THE STRUCTURAL DRAWINGS IN CONJUNCTION WITH THE SPECIFICATIONS AND OTHER
CONTRACT DOCUMENTS.

6.

CONCRETE CAST-IN PLACE PILES HAVE BEEN DESIGNED ON THE BASIS OF THE FOLLOWING CAPACITIES:

GENERAL CONTRACTOR TO VERIFY AND MARK ALL UNDERGROUND LINES AND RE-ENSURE THAT NEW
FOUNDATIONS DO NOT INTERFERE WITH ANY UNDERGROUND UTILITY LINES.
4.

SITE REVIEW
1.

CONCRETE REINFORCEMENT
MASONRY REINFORCEMENT
STRUCTURAL STEEL
STEEL DECKING

5.

BEFORE EACH POUR


BEFORE EACH GROUT POUR
BEFORE COVERING UP
BEFORE COVERING UP

P.E.C. PROVIDES FIELD REVIEW ONLY FOR THE WORK SHOWN ON THESE STRUCTURAL DRAWINGS. THIS
REVIEW IS NOT A FULL-TIME REVIEW BUT IS A PERIODIC REVIEW AT THE SOLE DISCRETION OF P.E.C. IN
ORDER TO ASCERTAIN THAT THE WORK IS IN GENERAL CONFORMANCE WITH THE PLANS AND SUPPORTING
DOCUMENTS PREPARED BY P.E.C. FIELD REVIEW BY P.E.C. IS NOT CARRIED OUT FOR THE CONTRACTORS
BENEFIT. IT REMAINS THE CONTRACTORS RESPONSIBILITY TO BUILD THE WORK IN CONFORMANCE WITH THE
CONTRACT DOCUMENTS. P.E.C. SHALL NOT BE RESPONSIBLE FOR THE ACTS OR OMISSIONS OF THE
CONTRACTOR, SUB-CONTRACTOR, OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK, OR FOR THE
FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACTOR DOCUMENTS.
P.E.C. WILL REVIEW SHOP DRAWINGS PERTAINING TO WORK SHOWN ON P.E.C.S DRAWINGS. THE EXTENT OF
THIS REVIEW IS AT THE SOLE DISCRETION OF P.E.C.S ENGINEER AND IS FOR THE SOLE PURPOSE OF
ASCERTAINING GENERAL CONFORMANCE WITH THE STRUCTURAL DESIGN CONCEPT. THE REVIEW IS NOT AN
APPROVAL OF THE DESIGN, DETAILS AND DIMENSIONS INHERENT IN THE DESIGNS SUBMITTED BY OTHERS.
SUCH REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITY FOR ERRORS AND OMISSIONS
IN THE SHOP DRAWINGS OR FOR MEETING ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.

DESIGN LOADS

SKIN FRICTION (FACTORED)


0
psf
440 psf
600 psf

CONCRETE CAST IN PLACE END BEARING PILES HAVE BEEN DESIGNED ON THE BASIS OF A FACTORED
END BEARING CAPACITY OF 15,700 psf IN THE BEARING STRATUM RECOMMENDED IN THE
GEOTECHNICAL REPORT.
PRIOR TO PLACING CONCRETE FOR PILE FOUNDATIONS, BEARING STRATA FOR PILES SHALL BE
INSPECTED BY A GEOTECHNICAL CONSULTANT TO CONFIRM THEIR LOAD CARRYING CAPACITY IN
WRITING PRIOR TO COMMENCING WITH WORK. P.E.C. IS NOT RESPONSIBLE FOR CONFIRMING
FOUNDATION CAPACITIES OF SOIL.

NOTIFY THE ENGINEER 48 HOURS IN ADVANCE FOR REVIEW OF THE FOLLOWING:

PILE LENGTHS SHOWN ARE NOT FINAL AND MAY VARY ACCORDING TO SITE CONDITIONS. LENGTH OF
PILE SHALL BE AT THE DISCRETION OF THE GEOTECHNICAL CONSULTANT. EXTEND ALL PILES TO A
BEARING LAYER APPROVED BY THE GEOTECHNICAL ENGINEER. INFORM P.E.C. OF ALL SUCH CASES
PRIOR TO CONSTRUCTION.

7.

TIE ALL DOWELS AND ANCHOR BOLTS IN PLACE BEFORE POURING CONCRETE USE TEMPLATES TO
ENSURE CORRECT PLACEMENT. NO WET SETTING ALLOWED.

8.

PILES SHALL BE PLACED WITH THE FOLLOWING TOLERANCES:


NOT MORE THAN 2% OF ITS LENGTH OUT OF PLUMB VERTICALLY.
NOT MORE THAN 2 (50mm) OFF CENTER AT THE TOP.

9.

PROVIDE CASING AS REQUIRED.

10.

PROVIDE A SEPARATE PRICE FOR FULL CASING OF ALL PILES.

11.

PROVIDE A UNIT RATE FOR CASING OF ALL PILE DIAMETERS SHOWN ON DRAWINGS.

12.

FOR ADDITIONAL NOTES AND REQUIREMENTS SEE SPECIFICATIONS.

13.

VERIFY AND MARK ALL UNDERGROUND LINES AND RE-ENSURE THAT NEW PILE LOCATIONS DO NOT
INTERFERE WITH ANY UNDERGROUND UTILITY LINES.

SHORING OF EXCAVATIONS

1.

1.

SHORING IS NOT UNDER P.E.C.S SCOPE OF WORK AND SHALL BE DESIGNED BY OTHERS.

2.

DESIGN SHALL BE BASED ON THE CRITERIA RECOMMENDED IN THE SOILS REPORT AND SHALL BE TO
CITY STANDARDS OR THE APPLICABLE GOVERNING AUTHORITY.

3.

WHERE REQUIRED, SHORING CONTRACTOR TO OBTAIN ALL NECESSARY APPROVALS FOR


INSTALLATION OF TIE-BACK ANCHORS OUTSIDE THE INDICATED PROPERTY LINE. CONTRACTOR SHALL
ESTABLISH THE LOCATION AND EXTENT TO UNDERGROUND UTILITY LINES WHERE INTERFERENCE
WITH EXCAVATION / SHORING OPERATIONS ARE POSSIBLE TO OCCUR.

6.5 psf
8.8 psf
2.0
1.0

EARTHQUAKE LOADS:
Sa (0.2)
0.12
Sa (0.5)
0.06
Sa (1.0)
0.02
Sa (2.0)
0.01
PGA
0.06
IMPORTANCE FACTOR
1.0
Rd =
3.0
Ro =
1.3
SITE CLASSIFICATION REFER TO GEOTECHNICAL REPORT.
LATERAL LOADS FROM WIND AND EARTHQUAKE ARE RESISTED BY STEEL BRACING.
2.

ROOF LOADS
DEAD LOAD
SNOW LOAD
S
RAIN

25 psf
34 psf + SNOW PILING
3 5/8 (ONE DAY RAIN)

OTHER LOADS:
SNOW PILING LOADS SEE PLAN ON DRAWING S-301.
RAIN PONDING LOADS SEE PLAN ON DRAWING S-303.
WIND UPLIFT LOADS SEE PLAN ON DRAWING S-303.
ROOF JOIST ABOVE MECHANICAL ROOM TO BE DESIGNED FOR AN ADDITIONAL BOTTOM
CHORD LIVE LOAD OF 10 psf (0.5 kPa).
PAVERS 50 psf. REFER TO ARCH. DRAWINGS FOR LOCATIONS.
MISCELLANEOUS LOADS SHOWN DIRECTLY ON THE PLANS.
WATER LINE LOADS = SEE DETAILS ON THIS DRAWING.
3.

TEMPORARY CONSTRUCTION LOADS SHALL NOT EXCEED THE DESIGN PARAMETERS AND SHALL NOT BE
APPLIED BEFORE THE STRUCTURE HAS SUFFICIENT STRENGTH AND STABILITY.

4.

5.

1.

2.

NON STRUCTURAL ELEMENTS OR SECONDARY STRUCTURAL ELEMENTS ARE NOT THE


RESPONSIBILITY OF P.E.C. AND ARE TO BE DESIGNED BY OTHERS. A PROFESSIONAL ENGINEERS SEAL
MAY BE REQUIRED FOR SOME OR ALL SUCH ELEMENTS. NON STRUCTURAL ELEMENTS OR
SECONDARY STRUCTURAL ELEMENTS, IF APPEARING ON P.E.C.S DRAWINGS, ARE FOR INFORMATION
AND / OR COORDINATION ONLY. DESIGN ALL NON STRUCTURAL ELEMENTS OR SECONDARY
STRUCTURAL ELEMENTS IN ACCORDANCE WITH THE LATEST CODES AND STANDARDS.

A.
B.
C.
D.
E.
F.
G.
H.
I.
J.

ARCHITECTURAL COMPONENTS SUCH AS GUARDRAILS, HANDRAILS FLAGPOSTS, AWNINGS,


CEILINGS, MILLWORK ETC.
LANDSCAPE ELEMENTS SUCH AS BENCHES, LIGHT POSTS, PLANTERS, ETC.
CLADDING, GLAZING, WINDOW MULLIONS, PARTITION WALLS.
ARCHITECTURAL PRECAST, PRECAST CLADDING.
SKYLIGHTS.
MECHANICAL AND ELECTRICAL EQUIPMENT, COMPONENTS AND THEIR ATTACHMENT DETAILS.
WINDOW WASHING EQUIPMENT AND THEIR ATTACHMENTS.
ESCALATORS, ELEVATORS AND CONVEYING SYSTEMS.
BRICK OR BLOCK VENEERS AND THEIR ATTACHMENTS.
NON STRUCTURAL CONCRETE TOPPINGS.

SHOP DRAWINGS FOR NON STRUCTURAL ELEMENTS WHICH MAY AFFECT THE PRIMARY STRUCTURAL
SYSTEM SHALL BE SUBMITTED TO P.E.C. THESE DRAWINGS WILL BE REVIEWED ONLY FOR THE EFFECT
OF THE ELEMENT ON THE PRIMARY STRUCTURAL SYSTEM.

CONCRETE TO CONFORM TO THE LATEST CODES AND STANDARDS BEING NORMAL WEIGHT MEETING
THE FOLLOWING REQUIREMENTS / THE REQUIREMENTS IN THE SPECIFICATIONS.

2.

ADMIXTURES CONTAINING CALCIUM CHLORIDE ARE NOT PERMITTED.

3.

SUPERPLASTICIZING ADMIXTURE IS PERMITTED TO ALLOW PUMPING OR IMPROVE SURFACE FINISHING


OF CONCRETE. SUPERPLASTICIZING TO BE IN STRICT ACCORDANCE WITH THE CONCRETE SUPPLIERS
RECOMMENDATIONS.

4.

FOR FLOOR SLABS, DESIGN THE CONCRETE MIXTURE WITH AGGREGATE GRADING AND WATER TO
CEMENTING MATERIALS RATIO THAT MINIMIZES SHRINKAGE.

GEOTECHNICAL NOTES

2.

3.

1.

4.

SUBMIT APPROPRIATE NUMBER OF SHOP DRAWINGS TO P.E.C. FOR ALL METAL STUD WALLS AND THEIR
CONNECTIONS PRIOR TO FABRICATION. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY THE
PROFESSIONAL ENGINEER REGISTERED IN THE PROVINCE OF ALBERTA RESPONSIBLE FOR THE DESIGN
OF THE STEEL STUDS AND THEIR CONNECTIONS.

5.

FOR NON-LOAD BEARING GRAVITY STUDS, PROVIDE DEFLECTION TRACKS TO ALL STEEL STUD WALLS
UNLESS NOTED OTHERWISE.

SLAB THICKNESS

SLABS ON GRADE

REFER TO SPECIFICATIONS FOR MATERIAL GRADE REQUIREMENTS.

3.

DESIGN CONNECTIONS IN ACCORDANCE WITH THE LATEST CODES AND STANDARDS. UNLESS NOTED
OTHERWISE, DESIGN ALL CONNECTIONS FOR NON-COMPOSITE BEAMS FOR 50% OF THE SHEAR
RESISTANCE TABULATED IN THE LATEST EDITION OF THE CISC HANDBOOK OF STEEL CONSTRUCTION.
DESIGN CONNECTIONS DESIGNATED FOR BEAM SIZES AND SPANS SHOWN ON DRAWINGS. USE A
MINIMUM OF 3-3/4" (19mm) BOLTS IN EACH BOLTED CONNECTIONS. LOCALIZE HSS REINFORCEMENT IF
REQUIRED DUE TO CONNECTION. TYPE SHALL BE THE RESPONSIBILITY OF THE STRUCTURAL STEEL
SUPPLIER.

4.

WELDING SHALL CONFORM TO THE LATEST CODES AND STANDARDS AND BE DONE WITH MATCHING
ELECTRODES.

5.

GROUT UNDER COLUMN SHALL BE NON-SHRINK, NON-STAIN AND PLACED IN ACCORDANCE WITH
MANUFACTURES RECOMMENDATIONS. THE MINIMUM COMPRESSIVE STRENGTH OF GROUT SHALL BE
30 MPa AT 7 DAYS.

AIR
FLY ASH
ENTRAINMENT CONTENT (%)

PILES, PILE CAPS, PIERS


AND GRADE BEAMS

MS

4"
30 MPa @
28 DAYS (100mm)

3/4"
(19mm)

0.50

4% - 7%

INTERIOR SLABS ON GRADE

GU

25 MPa @
28 DAYS

3"
(76mm)

3/4"
(19mm)

0.55

NONE
REQUIRED

C-1

STOOPS (STRUCTURAL
OR ON GRADE)

GU

35 MPa @
28 DAYS

3"
(76mm)

3/4"
(19mm)

0.40

5% - 8%

C-1

CONCRETE APRONS

GU

35 MPa @
28 DAYS

3"
(76mm)

3/4"
(19mm)

0.40

5% - 8%

32 MPa @
28 DAYS

3"
(76mm)

3/4"
(19mm)

0.45

5% - 8%

CONCRETE FORMWORK
REFER TO ARCHITECTURAL DRAWINGS FOR CHAMFERS ON CORNERS OF COLUMNS, BEAMS AND
WALLS. USE 3/4 x 3/4 (19mm x 19mm) FORMED CHAMFERS ON EXPOSED CORNERS UNLESS OTHERWISE
SHOWN ON DRAWINGS / ARCHITECTURAL DRAWINGS. REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.

2.

VOID FORM MATERIALS SHALL BE DYNAVOID (40144) OR EQUIVALENT.

3.

REBAR SHALL BE FREE OF RESIDUAL CEMENT PASTE AND FORM OIL.

4.

FOR ADDITIONAL NOTES AND REQUIREMENTS SEE SPECIFICATIONS.

DESIGN, FABRICATE AND ERECT STRUCTURAL STEEL IN ACCORDANCE WITH THE LATEST CODES AND
STANDARDS.

2.

CONCRETE SUPPLIER.

6.

PROVIDE 3/8 (10mm) CAP PLATES ON TOP OF ALL HSS COLUMNS UNLESS NOTED OTHERWISE.

7.

ALL HEADERS TO COME WITH 3/8 (10mm) CAP PLATES AND TO BE WELDED ALL AROUND TO STEEL
SUPPORTS ON EACH END.

8.

FRAME OPENINGS IN STEEL DECK GREATER THAN 18 (450mm) WITH C100x9 ALL AROUND UNLESS
NOTED OTHERWISE ON DRAWINGS. SEE TYPICAL DETAIL.

9.

PROVIDE C200x17 FRAMING UNDER ALL ROOF TOP UNITS UNLESS NOTED OTHERWISE ON DRAWINGS.
SEE TYPICAL DETAIL.

10.

STEEL PRIMER AS PER SPECIFICATIONS.

11.

SUBMIT APPROPRIATE NUMBER OF SHOP DRAWINGS TO P.E.C. PRIOR TO FABRICATION. SHOW ALL
DETAILS, INCLUDING FIELD WELDS, AND MATERIAL SPECIFICATIONS. SHOP DRAWINGS TO BE SIGNED
AND SEALED BY THE PROFESSIONAL ENGINEER REGISTERED IN THE PROVINCE OF ALBERTA
RESPONSIBLE FOR THE DESIGN OF ALL CONNECTIONS.

12.

ALLOW FOR MATERIALS AND WORKMANSHIP TESTING BY AN INDEPENDENT INSPECTION AND TESTING
FIRM AS PER THE SPECIFICATIONS.

13.

FOR ADDITIONAL NOTES AND REQUIREMENTS SEE SPECIFICATIONS.

EXTEND BOTTOM CHORDS TO COLUMN OR BEAM FLANGE WHERE INDICATED ON FRAMING PLAN.
DESIGN CHORD EXTENSIONS FOR 3 Kip (13 kN) FACTORED COMPRESSION.

7.

PROVIDE CROSS BRIDGING IN ACCORDANCE WITH THE LATEST CODES AND STANDARDS.

8.

PRIMER AS PER SPECIFICATIONS.

9.

SUBMIT APPROPRIATE NUMBER OF SHOP DRAWINGS TO P.E.C. PRIOR TO FABRICATION. SHOP


DRAWINGS TO BE SEALED BY THE PROFESSIONAL ENGINEER REGISTERED IN THE PROVINCE OF
ALBERTA RESPONSIBLE FOR THE DESIGN AND FABRICATION OF ALL STEEL JOISTS.

7.

REINFORCED CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF THE LATEST CODES AND
STANDARDS.

8.

CONCRETE COVER TO REINFORCING STEEL SHALL CONFORM TO THE APPLICABLE REQUIREMENTS


LISTED BELOW THAT RESULTS IN THE GREATER AMOUNT OF COVER.

GRADE

UNLESS NOTE OTHERWISE PROVIDE CONTROL JOINTS AT 32-0 (9600mm) MAX. BOND BEAMS, LINTELS
AND HORIZONTAL WALL REINFORCEMENT TO BE CONTINUOUS.

7.

MINIMUM REQUIREMENTS:
UNLESS NOTED OTHERWISE ON DRAWINGS PROVIDE THE FOLLOWING MINIMUM REINFORCEMENT TO
MASONRY WALLS (INCLUDING NON-LOAD BEARING WALLS):
WALL MINIMUM SIZE:
8 (200mm)

BENDING, CUTTING AND PLACING OF REINFORCING STEEL SHALL CONFORM TO THE LATEST CODES
AND STANDARDS.

WALL MIN. VERTICAL


REINFORCEMENT:

15M @ 2- 0 (600mm) VERT.

WALL MIN. BOND BEAMS:

ONE BOND BEAM AT TOP OF WALL


R/W 2-15M CONT

WALL MIN. DOWELS TO


FOUNDATION OR SLAB:

15M @ 2-0 (600mm) x 48 (1200mm) LONG

WALL OPENINGS (U.N.O.):

PROVIDE 8x16 (200x400) LINTEL ABOVE ALL OPENINGS NO


MORE THAN 4-0 (1200mm) WIDE R/W 2-15M TOP & BOTTOM
AND 10M @ 8 (200mm) SINGLE LEG STIRRUPS.
PROVIDE 1-15M VERTICAL REINFORCEMENT TO TOP OF
WALL EACH SIDE OF OPENING. SEE TYPICAL DETAILS FOR
ADDITIONAL INFORMATION.

8.

ALL REINFORCED CORES TO BE SOLID GROUTED.

9.

THE USE OF RUNNING BOND OR STACK BOND TO BE CONFIRMED WITH THE ARCHITECTURAL DRAWINGS.

10.

LATERAL SUPPORT REQUIRED ON TOP OF ALL MASONRY WALLS. SEE DRAWINGS.

11.

NO CONDUIT, ELECTRICAL BOXES, RECESSED FIRE EXTINGUISHERS OR ANY OTHER RECESSED


APPLIANCE ALLOWED IN MASONRY COLUMNS.

12

ADDITIONAL NOTES AND REQUIREMENTS SEE SPECIFICATIONS.

SHORING OF STRUCTURE
1.

SHORING IS NOT UNDER P.E.C.S SCOPE OF WORK AND SHALL BE DESIGNED BY OTHERS.

2.

SUBMIT APPROPRIATE NUMBER OF SHOP DRAWINGS FOR P.E.C.S RECORD ONLY. SHOP DRAWINGS TO
BE STAMPED BY A PROFESSIONAL ENGINEER REGISTERED IN ALBERTA RESPONSIBLE FOR THE DESIGN
AND FABRICATION OF ALL SHORING.

PIPE LOADS 'W' AS SHOWN IN ADDITION TO THE BASIC SPECIFIED DESIGN.

6.

FOR GROUND ELEVATIONS AND DRAINAGE SLOPES, SEE ARCHITECTURAL DRAWINGS.

6.

WELD SEAT CONNECTIONS WITH 1/4 (6mm) WELD MIN CONTINUOUS ALL AROUND.

REBAR SHALL BE FREE OF RESIDUAL CEMENT PASTE AND FORM OIL.

JOINT REINFORCING SHALL BE CONTINUOUS EVERY 16 (400mm) HORIZONTAL. USE STANDARD 9ga. SIDE
RODS AND 9 ga. CROSS TIES MILL GALVANIZED WIRE. LAP JOINT REINFORCEMENT 6 (150mm) AT ALL
SPLICES.

ALL SUPPORTING JOISTS/TRUSSES SHALL BE DESIGNED TO WITHSTAND WATER FILLED PIPES.

5.

6.

5.

REINFORCING STEEL: BILLET-STEEL CONFORMING TO THE LATEST CODES AND STANDARDS. ALL
REINFORCING SHALL BE GRADE 400. USE GRADE 400W WHERE WELDING IS NOTED.

MINIMUM REINFORCEMENT AS PER THE MINIMUM REQUIREMENTS NOTED BELOW.

GROUT TO BE COARSE (20MPa) AND CONFORM TO LATEST CODES AND STANDARDS.

UNLESS NOTED OTHERWISE ON DRAWINGS LIMIT JOIST ROOF TOTAL LOAD DEFLECTION TO L/240 AND
LIVE LOAD DEFLECTION TO L/360.

2.

5.

4.

FOR WATER PIPE AND / OR SPRINKLER LINE LOCATION, SEE MECHANICAL DRAWINGS.

LATERAL SOIL PRESSURE ON WALLS INCLUDING SURCHARGE SHALL BE AS FOLLOWS. UNLESS NOTED
OTHERWISE IN THE GEOTECHNICAL REPORT.

SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DAMP PROOFING OR WATER STOP
REQUIREMENTS.

PORTLAND CEMENT TO CONFORM TO LATEST CODES AND STANDARDS.

UNLESS NOTED OTHERWISE LIMIT JOIST FLOOR TOTAL LOAD DEFLECTION TO L/360 AND LIVE LOAD
DEFLECTION TO L/480.

6.

3.

CAMBER REQUIREMENTS TO LATEST CODES AND STANDARDS UNLESS NOTED ON DRAWINGS. CAMBER
JOISTS FOR DEAD LOAD.

4.

WELDING SHALL CONFORM TO THE LATEST CODES AND STANDARDS.

MORTAR SHALL BE TYPE S.

2.

REINFORCED CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF THE LATEST CODES AND
STANDARDS.

4.

2.

TYPICAL WATER LINE LOADING DETAILS

1.

EXCAVATION REQUIREMENTS SHALL BE REVIEWED AND APPROVED BY A GEOTECHNICAL ENGINEER


PRIOR TO PROCEEDING WITH WORK.

MASONRY UNITS TO BE LIGHTWEIGHT CONCRETE MASONRY CONFORMING TO THE LATEST CODES AND
STANDARDS.

STEEL JOISTS SHALL BE DESIGNED AND FABRICATED BY THE JOIST SUPPLIER IN ACCORDANCE WITH
THE LATEST CODES AND STANDARDS FOR THE LOADS INDICATED UNDER DESIGN LOADS.

REINFORCED CONCRETE

5.

1.

1.

REFER TO FOUNDATION PLAN FOR ADDITIONAL NOTES REGARDING THE APPLICABLE FOUNDATION
SYSTEM.

3.

MASONRY

STEEL JOISTS - OPEN WEB

3.

ALL BACKFILL MATERIALS AND BACKFILL INSTALLATION SHALL BE REVIEWED BY A GEOTECHNICAL


ENGINEER TO ENSURE COMPLIANCE WITH THE RECOMMENDATIONS AS NOTED IN THE GEOTECHNICAL
REPORT.

7.

METAL STUD INSTALLER SHALL CUT HOLES THROUGH WEB AND FLANGES OF METAL STUDS
SUFFICIENT FOR BRACING ROD TO PASS THROUGH. METAL STUD INSTALLER SHALL PROVIDE
STRENGTHENING OF CUT-OUT METAL STUD FLANGES AND WEB BACK TO AT LEAST THE SAME SHEAR
AND MOMENT CAPACITY OF THE ORIGINAL METAL STUDS.

STRUCTURAL STEEL

CONCRETE STRENGTH AND MIX SPECIFICATIONS

10.

FOR TESTING REQUIREMENTS SEE NOTES UNDER STRUCTURAL STEEL SECTION.

11.

FOR ADDITIONAL NOTES AND REQUIREMENTS SEE SPECIFICATIONS.

SMALLER THAN 2" (50mm).......IGNORE


2" (50mm) PIPE......................w = 7.00 lb/ft
3" (76mm) PIPE......................w = 11.00 lb/ft
4" (100mm) PIPE....................w = 16.00 lb/ft
5" (130mm) PIPE....................w = 24.00 lb/ft
6" (150mm) PIPE....................w = 31.00 lb/ft
8" (200mm) PIPE....................w = 50.00 lb/ft
LARGER THAN 8"......................NOT PERMITTED

TOP CHORD

PANEL POINT

BOTTOM CHORD
PIPE LINE PARALLEL TO JOISTS:

EXPOSURE
CONDITION

EXPOSURE CLASS
N

C-XL, C-1, C-3


A-1, A-2, A-3
2 3/8"
(60mm)

C-2, C-4
-

NO

FORMED SURFACES EXPOSED TO EARTH (PILES,


PILE CAPS AND GRADE BEAMS)

1 5/8"
(40mm)

INTERIOR SLAB ON GRADE

3/4"
(20mm)

NO

2 3/8" (60mm)
1 5/8" (40mm)

NO
NO

2 3/8" (60mm)
1 5/8" (40mm)

YES
NO

3/4"
(20mm)

NO

STOOPS (STRUCTURAL OR ON GRADE)

- TOP STEEL
- BOT STEEL

CONCRETE APRONS SUBJECT TO EXTERIOR EXPOSURE


(INCLUDING DOWELS)
- TOP STEEL
- BOT STEEL

0.6 x (125 lbs/ft x H + 250 psf)

F-1, F-2
S-1, S-2
1 5/8"
(40mm)

EXPOXYCOATED
BARS

SIDEWALKS, CURBS AND GUTTERS, SPLASH PADS AND


SUMP PITS

PIPE PERPENDICULAR TO JOISTS:

POINT OF SUPPORT
AT PANEL POINT

CLEAR CONCRETE COVER SCHEDULE

FILL AND COMPACTION AS PER


THE GEOTECHNICAL REPORT

PLUS 100 lbs (45 kg)


AT THE POINT OF HANGING

ALL MECHANICAL PIPES 2" (50mm) OR LARGER SHALL BE HUNG FROM THE TOP CHORD OF JOISTS AT PANEL
POINTS ONLY. DUCT WORK MAY BE HUNG FROM TOP OF JOISTS AT LOCATIONS OTHER THAN PANEL POINTS.

150 psf (7.5 kPa)

4.

GEOTECHNICAL REPORT FOR THIS PROJECT HAS BEEN PREPARED BY SHELBY ENGINEERING. THE
REPORT IS DATED MARCH 2012 AND TITLED "GEOTECHNICAL EVALUATION PROPOSED R&M ENERGY
SYSTEMS DEVELOPMENT LOTS 1 TO 7, BLOCK 14, PLAN 11249011 LEDUC, ALBERTA". GEOTECHNICAL
ENGINEER TO CONFIRM IN WRITING THAT GEOTECHNICAL REPORT PARAMETERS/RECOMMENDATIONS
APPLY FOR THIS BUILDING SITE PRIOR TO COMMENCING WITH WORK.

3.

JOISTS
/TRUSSES

PIPE

2/3 P (TYP.)

1.

STEEL STUDS ERECTED C/W BRACING CHANNEL SPACED AT NO MORE THAN 4-0 (1200mm) O/C
VERTICAL.

TABLE NOTES:
1.
MINIMUM THICKNESS OF SLABS ON GRADE IS 4" (100mm).

FOR ADDITIONAL NOTES AND REQUIREMENTS SEE SPECIFICATIONS.

1.

2.

10M @ 10" (250mm)

FORM WORK TO CONFORM TO THE LATEST CODES AND STANDARDS.


3.

ADDITIONAL NOTES AND REQUIREMENTS SEE SPECIFICATION.

15M @ 10" (250mm) EACH WAY BOTTOM

10M @ 10" (250mm)

GU

11.

< 12" (300mm)

< 12" (300mm)

SIDEWALKS, CURBS AND


GUTTERS, SPLASH PADS
AND SUMP PITS

SUBMIT APPROPRIATE NUMBER OF SHOP DRAWINGS TO P.E.C. PRIOR TO FABRICATION. SHOW ALL
DETAILS, MATERIAL SPECIFICATION AND DESIGN LOADS. SHOP DRAWINGS TO BE SIGNED AND SEALED
BY THE PROFESSIONAL ENGINEER REGISTERED IN THE PROVINCE OF ALBERTA RESPONSIBLE FOR THE
DESIGN OF THE STEEL DECK.

STEEL STUDS SHALL BE DESIGNED AND INSTALLED BY STEEL STUD SUPPLIER IN ACCORDANCE WITH
THE LATEST CODES AND STANDARDS FOR THE LOADS INDICATED UNDER "DESIGN LOADS" AND SHALL
CONFORM TO THE FOLLOWING MINIMUM REQUIREMENTS: 6 (150mm) STUDS, 18ga. MIN, SPACED @ 16
(400mm) O/C. INCREASE GAUGE OR DECREASE SPACING IF NECESSARY TO ACHIEVE CAPACITY UNDER
DESIGN LOADS. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.

< 10" (250mm)

C-2

10.

1.

10M @ 10" (250mm)

1.

EXAMPLES OF NONSTRUCTURAL ELEMENTS INCLUDE, BUT ARE NOT LIMITED TO:

CUT AND FRAME OPENINGS BETWEEN 6 (150mm) AND 18 (450mm) WITH L76x76x6.4 PERPENDICULAR TO
FLUTES. EXTEND MIN. 3 FLUTES PAST THE OPENING EA. SIDE. OPENINGS LARGER THAN 18 (450mm)
FRAMED BY STRUCTURAL STEEL ERECTOR.

15M @ 12" (300mm) EACH WAY BOTTOM

< 9" (225mm)

9.

< 10" (250mm)

10M @ 10" (250mm)

S-3

PAINT ALL WELDS WITH ZINC RICH PAINT.

METAL STUD

< 8" (200mm)

W/C
RATIO

8.

10M @ 7" (175mm) EACH WAY BOTTOM

SOLDIER PILE LOCATIONS TO BE REVIEWED FOR MINIMUM INTERFERENCE TO COLUMNS, WALLS AND
REINFORCEMENT. MAKE PROVISIONS IN ALL EMBEDDED PLATES TO ALLOW FOR THE CONTINUITY OF
WALL REINFORCING.

CEMENT
MIN.
SLUMP MAX. AGG.
TYPE STRENGTH
SIZE

WELD DECK TO SUPPORTING STEEL WITH 3/4 (19mmm) DIA. FUSION WELDS. FASTEN SIDE LAPS BY
BUTTON PUNCHING AT 24 (600mm) MAX. SPACING. WELD EACH SIDE OF SIDE-LAP AT SUPPORTS.
MAXIMUM SPACING OF 6 (150mm) AT PERIMETER AND 12 (300mm) AT INTERIOR SUPPORTS.

< 9" (225mm)

10M @ 11" (275mm)

USE

7.

10M @ 8" (200mm) EACH WAY BOTTOM

10M @ 12" (300mm)

EXPOSURE
CLASS

INSTALL DECKING CONTINUOUS OVER MINIMUM THREE SPANS WHERE POSSIBLE.

< 8" (200mm)

< 7" (175mm)

NON-STRUCTURAL ELEMENTS

6.

MINIMUM SLAB ON GRADE REINFORCEMENT TABLE


U.N.O. ON DRAWINGS

CONCRETE

8.

PROVIDE DRAIN HOLES AT 4-0 (1200mm) O/C. OR AS REQUIRED TO PREVENT RAINWATER


ACCUMULATION DURING INSTALLATION.

10M @ 9" (225mm) EACH WAY BOTTOM

< 6" (150mm)

PROTECT CONCRETE FROM ADVERSE WEATHER CONDITIONS IN ACCORDANCE WITH THE LATEST
CODES AND STANDARDS.

5.

< 7" 175mm)

10M @ 14" (350mm)

7.

DECK COATING AS PER SPECIFICATIONS.

10M @ 12" (300mm) EACH WAY BOTTOM

10M @ 14" (350mm)

DO NOT ADD WATER TO THE CONCRETE ON SITE UNLESS AUTHORIZED BY THE

4.

< 6" (150mm)

< 5" (130mm)

6.

DECK SUPPLIER SHALL COORDINATE METHOD OF ATTACHMENT FOR DUCT, CEILING, AND CONDUIT
HANGERS WITH APPROPRIATE SUBTRADES.

10M @ 12" (300mm) EACH WAY BOTTOM

< 4" (100mm)

REJECT ALL CONCRETE WHEN TIME BETWEEN BATCHING AND PLACING EXCEEDS TWO HOURS.

3.

< 5" (130mm)

EXAMINE THE SITE PLAN FOR EXISTING GRADE ELEVATIONS. CONTRACTOR TO DETERMINE EXTENT OF
SHORING REQUIRED AND SURCHARGE REQUIREMENTS FROM SITE CONDITIONS. DESIGN FOR A
MINIMUM OF 200 psf (9.6 kPa) SURCHARGE.

5.

UNLESS NOTED OTHERWISE ON DRAWINGS LIMIT DECK ROOF TOTAL LOAD DEFLECTION TO L/240 AND
LIVE LOAD DEFLECTION TO L/360.

STRUCTURAL SLABS

TABLE NOTES:
1.
MINIMUM THICKNESS OF STRUCTURAL SLABS IS 5" (125mm)
2.
PROVIDE MINIMUM REINFORCING PERPENDICULAR TO PRINCIPAL REINFORCEMENT IN ONE-WAY SLABS.
PLACE ALTERNATING TOP AND BOTTOM WHERE TOP REINFORCING SPECIFIED.
3.
PROVIDE MINIMUM 2-20M INTEGRITY STEEL BETWEEN COLUMNS IN ALL TWO-WAY STRUCTURAL SLABS,
WITH THE EXCEPTION OF MAIN FLOOR SLABS WITH NO BASEMENT.
4.
FOR ONE WAY SLABS, PROVIDE MINIMUM 0.002 Ag REBAR IN DIRECTION PERPENDICULAR TO PRINCIPAL
REINFORCEMENT U.N.O. ON PLANS.
5.
FOR CANTILEVERS AND SLABS CONTINUOUS OVER WALLS AND BEAMS PROVIDE A MINIMUM 15M @ 12"
(300mm) TOP REINFORCEMENT U.N.O. ON PLANS.

UNLESS NOTED OTHERWISE LOADS NOTED BELOW ARE SPECIFIED LOADS.


LATERAL LOADS FROM WIND
WIND LOADS:
REFERENCE WIND PRESSURE (q 1/10)
REFERENCE WIND PRESSURE (q 1/50)
INTERNAL PRESSURE CATEGORY
IMPORTANCE FACTOR

LAP SPLICE
LENGTH

MINIMUM STRUCTURAL SLAB REINFORCEMENT TABLE U.N.O. ON DRAWINGS


SLAB THICKNESS

6.

EMBEDMENT
LENGTH

10M
16" (400mm)
20" (500mm)
8" (200mm)
12" (300mm)
15M
24" (600mm)
30" (750mm)
12" (300mm)
18" (450mm)
20M
30" (750mm)
40" (1000mm)
16" (400mm)
24" (600mm)
25M
48" (1200mm)
62" (1550mm)
20" (500mm)
30" (750mm)
30M
58" (1450mm)
74" (1850mm)
24" (600mm)
36" (900mm)
35M
60" (1500mm)
86" (2150mm)
28" (700mm)
42" (1050mm)
TABLE NOTES:
1.
BASED ON LATEST CODES AND STANDARDS.
2.
NORMAL DENSITY CONCRETE OF STRENGTH AT LEAST 25 MPa.
3.
ENCLOSED BY MINIMUM STIRRUPS OR TIES.
4.
CLEAR COVER AT LEAST 1.0 X BAR DIAMETER.
5.
CLEAR SPACING AT LEAST 1.4 X BAR DIAMETER.
6.
INCREASE LENGTHS TO 1.31 X LENGTH LISTED FOR EPOXY COATED REINFORCING.

ENSURE THAT THE REQUIREMENTS OUTLINED IN THE GEOTECHNICAL REPORT ARE READ AND
UNDERSTOOD PRIOR TO COMMENCING WITH FOUNDATION WORK.

DEPTH BELOW GRADE


0 TO 5'-0"
5'-0" TO 13'-0"
13-0 +

LAP SPLICE
LENGTH

1.0

1.5

2.0

1.0

RATIO OF COVER TO NOMINAL MAXIMUM AGGREGATE SIZE

1.0

1.5

2.0

1.0

9.

SUBMIT TO P.E.C FOR REVIEW THE LOCATION OF ALL CONSTRUCTION JOINTS NOT SHOWN ON THE DRAWINGS.

10

VERTICAL CONTROL JOINTS IN PERIMETER CONCRETE WALLS SHALL BE SPACED AT NO MORE THAN 18-0
(5400mm) O/C.

11.

HORIZONTAL CONSTRUCTION JOINTS SHALL NOT BE MADE IN BEAMS UNLESS SHOWN ON THE
DRAWINGS.

12.

SUBMIT TO P.E.C FOR REVIEW THE LOCATIONS OF ALL SLEEVES AND OPENINGS NOT SHOWN ON THE
DRAWINGS. P.E.C. WILL PROVIDE STRUCTURAL DETAILS UPON REQUEST.

13.

SLEEVES SHALL NOT BE PLACED HORIZONTALLY ALONG OR VERTICALLY THROUGH BEAMS UNLESS
AUTHORIZED BY P.E.C.

P = wL + 100 lbs (45 kg)


w = SEE ABOVE ( OF PIPE)... lb/ft
L = SPACING OF PIPE SUPPORTS... ft (m)

RATIO OF COVER TO NOMINAL DIAMETER

1/3 P
(TYP.)

JOISTS
/TRUSSES

JOISTS/TRUSSES
L

DO NOT CONSTRUCT FROM THESE DRAWINGS UNLESS MARKED ISSUED FOR CONSTRUCTION.

EMBEDMENT
LENGTH

COMPRESSION

4.

TENSION
BAR SIZE

2.

2.

BAR EMBEDMENT AND LAP SPLICE TABLE

DRAWINGS SHOW COMPLETED STRUCTURE ONLY. TEMPORARY SUPPORT AND BRACING FOR
CONSTRUCTION LOADING CONDITIONS IS THE RESPONSIBILITY OF THE CONTRACTOR.

STEEL DECK TO BE 1 1/2"(38mm) U.N.O. ON DRAWINGS. STEEL DECK SHALL BE DESIGNED AND
INSTALLED BY THE DECK SUPPLIER IN ACCORDANCE WITH THE LATEST CODES, STANDARDS AND FOR
THE LOADS INDICATED UNDER "DESIGN LOADS". MINIMUM THICKNESS=0.91 (20 ga.). INCREASE GAUGE
AS REQUIRED TO MEET LOADING CRITERIA.

CHECK AND VERIFY ALL DIMENSIONS WITH THE ARCHITECTURAL DRAWINGS BEFORE COMMENCING
WITH WORK. NOTIFY PROTOSTATIX ENGINEERING CONSULTANTS (P.E.C.) OF ANY DISCREPANCIES,
ERRORS OR OMISSIONS.

1.

1/3 S

3.

FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL REPORT STATED ABOVE. REFER TO THE
REPORT FOR ANY PARTICULARS AS TO SOIL CONDITION AND FOUNDATION RECOMMENDATIONS.
GEOTECHNICAL ENGINEER TO CONFIRM IN WRITING THAT GEOTECHNICAL REPORT
PARAMETERS/RECOMMENDATIONS APPLY FOR THIS BUILDING SITE PRIOR TO COMMENCING WITH
WORK.

2/3 S

2.

READ STRUCTURAL DRAWINGS IN CONJUNCTION WITH THE ARCHITECTURAL, CIVIL, LANDSCAPE,


MECHANICAL AND ELECTRICAL DRAWINGS.

P = wL + 100 lbs (45 kg)


w = SEE ABOVE ( OF PIPE)... lb/ft
L = SPACING OF PIPE SUPPORTS... ft (m)

PIPES ARE NOT PERMITTED TO BE SUPPORTED OFF BOTTOM CHORD OF JOISTS.

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

SEE ARCH. DWGS. FOR


PLUG-IN DETAILS

SPLICE TOP REBAR


AT MID SPAN IF
REQUIRED.

TENSION LAP
24" MIN.

2"

4"

8" ROUND PIPE FILLED


WITH CONCRETE AND
EMBEDED IN CONC. PILE.

'D2'

EMBED.

SLAB REINF.
SEE PLAN

16" CONCRETE PILE

'D1'

4'-0"

2'-6"

10M @ 8" O/C. E.W.

2X

24" TYP.
SPLICE BOTTOM
REBAR OVER
SUPPORTS IF
REQUIRED.

PROVIDE 4" DYNAVOID


(40144) OR EQUIVALENT
UNDER GRADE BEAM
BETWEEN PILES TYPICAL
L/2

16" MIN.

CONSTRUCTION JOINT
FOR BEAMS TO BE
POSITIONED AT MIDSPAN
BETWEEN PILES

HOOK TOP BARS


AS SHOWN

CHAMFER

X (SEE ARCH. DWGS.)

PROVIDE POCKET AS
REQUIRED. GROUT POCKET
SOLID ONCE COLUMN
INSTALLATION IS COMPLETE.

SIZE AND NUMBER OF BARS


TO MATCH THAT OF THE
GRADE BEAM TOP REINF.

COMPRESSION LAP
24" MIN

TYPICAL DETAILS SHOWN ON THIS


DRAWING ARE TO BE USED UNLESS
NOTED OTHERWISE IN THIS SET OF
DRAWINGS.

CONCRETE PILE R/W.


4-15M VERT. & 10M @
12" O/C.

PILE
SEE PILE
SCHEDULE

'D1' = DEPTH OF SLAB


'D2' = DEPTH OF HOUSE KEEPING PAD
(SEE MECHANICAL DRAWINGS FOR SIZES,
LOCATIONS, AND NUMBERS OF THE
HOUSEKEEPING PADS)

WELD 15M REBAR


ALTERNATING E.F. @ 12"
O/C TO PIPE.

L/2

1'-0"
L

TYPICAL GRADE BEAM SPLICE DETAIL

TYPICAL GRADE BEAM RECESS DETAIL

TYPICAL CAR PLUG-IN SECTION

BOLLARD DETAIL

HOUSE KEEPING PAD DETAIL

-SEE ARCH. DWGS. FOR LOCATION AND QUANTITY.

LAP BAR SAME SIZE


AND SPACING TYP.
ALL HORIZ. REINF.

CLASS 'B' LAP


18" MIN.

'D'

'D'

'D'/4
'D'

T/O MASONRY WALL


SEE ARCH. DWGS.
(9'-4" MAXIMUM)

12"

18" MIN.

ISOLATION JOINT POURED


SEPERATE FROM SLAB ON
GRADE 7 DAYS LATER
TYPICAL

45

TYPICAL LAPPING AT CORNERS

ADD. 2-15M CONT.

'D' = DEPTH OF SLAB

SLAB REINFORCEMENT NOT SHOWN FOR CLARITY

TYPICAL CONCRETE SLAB THICKENING

CONCRETE SIDEWALK
SEE DETAIL ON THIS DWG.
FOR REINFORCEMENT
SEE ARCH. DWGS. FOR
LOCATION AND EXTENT

SLAB REINFORCEMENT NOT SHOWN FOR CLARITY


PROVIDE WATER PROOF SEALER
UNLESS NOTED OTHERWISE, MAXIMUM SPACING OF
SAW CUTS TO BE 12'-0" O/C.
NO SAWCUTS IN STRUCTURAL SLABS TYPICAL.

COLUMN
SEE PLAN

SLAB REINFORCEMENT NOT SHOWN FOR CLARITY


SLAB ON GRADE ONLY

TYPICAL SAWCUT FOR


CONCRETE SLAB ON GRADE

TYPICAL CONCRETE SLAB ON GRADE


POUR BREAK (FLOOR JOINT)

DIAMOND CUT - ISOLATION JOINT


8" MASONRY BLOCK WALL
FULLY GROUTED
R/W 15M @ 24" VERTICAL
TYPICAL U.N.O.

5" CONCRETE SIDEWALK


R/W 10M @ 12" O/C
EACH WAY BOTTOM
10M @ 14" O/C DOWELS
TYPICAL

2'-0"
MIN. LAP

36"

SLAB REINF.
SEE PLAN

TENSION

3/8"

10M @ 12" O/C. x 4'-0" LG.


TOP DOWELS TYP. ALL
SIM. LOCATIONS

1'-0"

SLAB DOWELS
REFER TO PLAN

PROVIDE 2-15M CONT.

'D' = DEPTH OF SLAB

12"

4" 40 Ib/in3 RIGID INSULATION


TYPICAL BELOW SIDEWALK
NEXT TO BUILDING.

'D'

'D'

LAP

45

GRANULAR FILL AS
PER SOILS REPORT

15M @ 24" O/C x 48" LG. DRILLED &


EPOXIED INTO CONC. SLAB WITH
HILTI HIT HY150 MAX. ADHESIVE.
PROVIDE 10" EMBED. TYP.

45

4" DYNAVOID 40144


(OR APPROVED EQUAL)
VOID FORM TYPICAL
UNDER STRUCTURAL SLAB

16" DP. BOND BEAM


R/W 2-15M CONT.
TYP. ALL NON LOAD
BEARING WALLS

SAWCUT JOINT

'D' = DEPTH OF SLAB

14"

STRUCTURAL CONC. SLAB


SEE FOUNDATION PLAN
FOR DEPTH & REINF.
EXTEND REINF. MIN. 24"
INTO SIDEWALK AS SHOWN
TYPICAL

15M @ 16" O/C. x 36" Lg.


WRAP ONE FOR BOND BREAK

'D' = DEPTH OF SLAB

12"

TRANSVERSE REINFORCEMENT
HOOKED AS SHOWN.
PROVIDE A 12" HOOK

12"

1'-0"
-

2-15M CONT. TYP.


'D' = DEPTH OF SLAB
SLAB & GRADE BEAM/WALL REINFORCEMENT NOT SHOWN FOR CLARITY

TYPICAL CONCRETE SIDEWALK DETAIL

TYPICAL RECESSED CONCRETE GRADE


BEAM @ DOOR LOCATIONS

FOR EXTENT AND SLOPE OF SIDEWALK - SEE ARCHITECTURAL DRAWINGS.

TYPICAL REINFORCEMENT LAP IN SLAB


ON GRADE UNLESS NOTED OTHERWISE

SLAB REINFORCEMENT NOT SHOWN FOR CLARITY


SEE ARCHITECTURAL DRAWINGS FOR LOCATION AND
EXTENT OF MASONRY NON-LOAD BEARING WALLS

TYPICAL DETAIL AT MID-HEIGHT NON-LOAD


BEARING MASONRY WALLS ON SLAB ON GRADE

FOR LOCATIONS OF DOOR RECESSES - SEE ARCHITECTURAL DRAWINGS.

CONCRETE SIDEWALK

STRUCTURAL
STOOP

CONCRETE SIDEWALK

TYPICAL S.O.G. SIDEWALK TO STRUCT.


STOOP CONNECTION DETAIL
STEEL GRATING AS MANUFACTURED
BY FISHER & LUDLOW CAPABLE OF
RESISTING A TOTAL LOAD 200 psf AND
18 kips MIN. AXIAL LOAD TYPICAL
VERIFY LOADING WITH OWNER PRIOR
TO COMMENCING WITH WORK

10M @ 12"
DOWELS

45

1'-0"

8"

4-15M CONT. TYP.

10M @ 12" TYP.

PIPE BY OTHERS

8" CONC. WALLS, AND AND


CONC. SLAB FRAMING R/W
10M @ 8" EACH WAY
TYPICAL
2x4 KEY - TYP.

VARIES
'D'

1-15M CONT. TYP.


8"

24" CONCRETE PILE


R/W 10-20M VERT.

1'-0"

10M @ 8" TYP.

T/O CONC. SLAB


ELEV. 100'-0"

SEE MECH. DWGS.

SEE MECH.
DWGS.

12'-0"
BELOW GRADE

TYP.

NOTIFY ENGINEER
ON RECORD IF
EXCEEDS 48"

BELOW
INVERT

2'-0"

SEE MECH. DWGS.

MIN.

NOTIFY ENGINEER
ON RECORD IF
EXCEEDS 48"

18"

1-15M CONT. TYP.

10M @ 16" DWLS.


TYP. ALL AROUND
18"

DEPTH VARIES
TO BE DETERMINED
ON SITE

BASE PLATE, ANCHOR


BOLTS AND GROUT BY
OTHERS

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

1/4" CONT. ANGLE C/W 1/2" DIA. x4" LONG


NELSON STUDS @ 18" O/C. ALL GALVANIZED
CHANGE ANGLE DEPTH AS REQUIRED TO
MATCH DEPTH OF GRATING. NOTIFY
ENGINEER ON RECORD OF ANY REVISIONS

CONFIRM WITH MECH. DWGS.


IF CHECKERED COVER PLATES
ARE REQUIRED.

1/4" CONT. ANGLE C/W 1/2" DIA. x4" LONG


NELSON STUDS @ 18" O/C. ALL GALVANIZED
CHANGE ANGLE DEPTH AS REQUIRED TO
MATCH DEPTH OF GRATING. NOTIFY
ENGINEER ON RECORD OF ANY REVISIONS

1'-0"
10M @ 6" TIES
UPPER 5'-0" OF PILE

STEEL GRATING AS MANUFACTURED


BY FISHER & LUDLOW CAPABLE OF
RESISTING A TOTAL LOAD 200 psf AND
18 kips MIN. AXIAL LOAD TYPICAL
VERIFY LOADING WITH OWNER PRIOR
TO COMMENCING WITH WORK

18"

SEE ARCH.
DWGS.

LIGHT POLE
BY OTHERS

10M @ 12"
FOR REMAINDER OF PILE

CLASS 'B' LAP

PROVIDE KEY BETWEEN


SLAB POURS

1/4"

TYPICAL PILE FOR LIGHT POLE


SUPPORT DETAIL
( FOR LOCATION SEE ARCH. DWGS.)

TYPICAL TRENCH DRAIN DETAIL


(IN A SLAB ON GRADE)

DURAJOINT TYPE 3A
WATERSTOP OR
APPROVED EQUAL
8"

SEE MECH.

8"

DWGS

SEE MECH.
DWGS

REFER TO MECHANICAL / ARCHITECTURAL DRAWINGS


FOR QUANTITY, LOCATION AND EXTENT. TYPICAL.
'D' = DEPTH OF SLAB

DOUBLE SUMP PIT DETAIL


REFER TO MECHANICAL / ARCHITECTURAL DRAWINGS
FOR QUANTITY, LOCATION AND EXTENT. TYPICAL.

8"

O.W.S.J.

PLAN VIEW

PLAN VIEW
PROVIDE SOLID BLOCKING
TO TOP SIDE OF FLUTES
UNDER RTU TYP.

ROUND (D)

SQUARE (S)

RECTANGULAR
L
R

30

15

16 1/2

13 1/2

18

30

24

19 1/2

16

11

23

C100x9
3-3/4 BOLTS MIN.

1'-0"
MIN.

BEAM SPLICE DETAIL

PROVIDE L76x76x6.4 x 1'-0"


LG. PERPENDICULAR
TO STEEL DECK
TYP. EACH SIDE OF COLUMN

TYPICAL STEEL DECK SUPPORT


@ COLUMN LOCATIONS DETAIL

P/2

P/2

TYPICAL ROOF OPENING


FRAMING DETAIL

TYPICAL DETAILS SHOWN ON THIS


DRAWING ARE TO BE USED UNLESS
NOTED OTHERWISE IN THIS SET OF
DRAWINGS.

PROVIDE L76x76x6.4
TYP. EACH SIDE OF COLUMN

O.W.S.J.

REQUIRED DIMENSION OF FREE OPENINGS


FOR VARIOUS JOISTS CONFIGURATIONS

MECH. UNIT
P

STEEL COLUMN

DIRECTION OF STEEL DECK

O.W.S.J.

OPENINGS (in)

SEE PLAN

WEB
JOIST
DEPTH OFFSET
(in)
(in)

E
OP

SEE PLAN

W BEAM

C200x17

C100x9

W BEAM

O.W.S.J.

IT
. UN
ECH

C200x17

C200x17

C200x17

IT
. UN
ECH

C100x9

C200x17
C200x17

C200x17

C200x17

CONNECTION BY
STRUCTURAL STEEL
SUPPLIER

O.W.S.J.

C100x9

O.W.S.J.

CONT. PERIMETER ANGLE


SEE PLAN FOR SIZE

SECTION 1

HANGERS

MECH. UNIT
P

SECTION 1

PROVIDE SOLID BLOCKING


TO TOP SIDE OF FLUTES
UNDER RTU TYP.

1/2" STIFFENER PLATE EACH SIDE


OF WEB MINIMUM.
UNLESS REQUIRED OTHERWISE BY
THE STRUCTURAL STEEL SUPPLIER

1/2" STIFFENER PLATE EACH SIDE


OF WEB. MINIMUM
UNLESS REQUIRED OTHERWISE BY
THE STRUCTURAL STEEL SUPPLIER

MECH. UNIT
P

CONTRACTOR TO PROVIDE SPACING


BETWEEN STEEL COLUMN AND STEEL
BEAM ABOVE FOR STEEL BEAM
DEFLECTION TYP.

SEE PLAN

W BEAM

SEE PLAN

L102x76x4.8 x 3 1/2" LG. CLIP


ANGLES WELDED TO STEEL BEAM
ABOVE WITH 1" SLIP CONNECTION
TO STEEL COLUMN

P/2

P/2

W BEAM

U/S STEEL BEAM

SECTION 2

CONNECTION BY THE
STRUCTURAL STEEL
SUPPLIER.

HANGERS

MECH. UNIT
P

STEEL COLUMN
SEE PLAN FOR SIZE

BOLTED BEAM TO COLUMN


CONNECTION AS REQUIRED
BY STRUCTURAL STEEL
SUPPLIER

3/4" MIN. TOP PLATES WELDED


TO TOP OF COLUMN
STEEL COLUMN
SEE PLAN FOR SIZE

SECTION 2

TYPICAL ROOF TOP UNIT DETAIL

TYPICAL HANGING UNIT DETAIL

( FOR LOCATIONS AND NO. REQUIRED - SEE


MECHANICAL AND ARCHITECTURAL DRAWINGS)

( FOR LOCATIONS AND NO. REQUIRED - SEE


MECHANICAL AND ARCHITECTURAL DRAWINGS)

STEEL BEAM TO HSS COLUMN


CONNECTION DETAIL

TYPICAL SLIP CONNECTION DETAIL

CANTILEVERED STEEL BEAM TO


HSS COLUMN CONNECTION DETAIL

ki
ps

Pf

23

ki
ps

CONNECTION OF BRACE
BY STRUCTURAL STEEL
SUPPLIER TYPICAL

45

HSS BRACE

HSS COLUMN

1/4"

STEEL BEAM

1/4"

HSS BRACE

1/4"

2" - 6"

1/4"

2" - 6"

CONNECTION OF BRACE
BY STRUCTURAL STEEL
SUPPLIER TYPICAL

6"

HSS BRACE

Pf

Pf

HSS COLUMN

STEEL BEAM

HSS COLUMN

Pf

1/4"
1/4"

23

45

ps
ki

ps
ki

EXTEND BOTTOM CHORDS TO


COLUMN OR BEAM FLANGE WHERE
INDICATED ON FRAMING PLANS.
DESIGN CHORD EXTENSIONS FOR
3 kip FACTORED LOAD.

CONNECTION OF BRACE
BY STRUCTURAL STEEL
SUPPLIER TYPICAL
TOP

MID-SPAN

BOTTOM

SCHEMATIC HSS BRACE CONNECTION DETAILS

TYPICAL TIE JOIST DETAIL

TYPICAL STEEL JOIST TO STEEL


BEAM CONNECTION DETAIL

TYPICAL STEEL ANGLE


TO STEEL JOIST DETAIL

TYPICAL STEEL ANGLE


TO STEEL BEAM DETAIL

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

SECTION 03100 CONCRETE FORMWORK

SECTION 03300 CAST-IN-PLACE CONCRETE

SECTION 05100 STRUCTURAL STEEL

SECTION 05215 STEEL JOIST

1.

1.

REFERENCE STANDARDS

REFERENCE STANDARDS

1.

ALL STANDARDS TO BE LATEST AT TIME OF TENDERING

1.

ALL STANDARDS TO BE LATEST AT TIME OF TENDERING

2.

CAN/CSA-G40.20/G40.21-04 "GENERAL REQUIREMENTS FOR ROLLED OR WELDED


STRUCTURAL QUALITY STEEL".

2.

CAN/CSA-G40.20/G40.21-04 "GENERAL REQUIREMENTS FOR ROLLED OR WELDED


STRUCTURAL QUALITY STEEL".

3.

CAN/CSA G164-92 (R2003) "HOT DIPPED GALVANIZING OF IRREGULARLY SHAPED


ARTICLES".

3.

CAN/CSA G164-03 "HOT DIPPED GALVANIZING OF IRREGULARLY SHAPED ARTICLES".

4.

CAN/CSA S16.1-01 "STEEL STRUCTURES FOR BUILDINGS (LIMIT STATES DESIGN)"

4.

CAN/CSA S16.1-01 "STEEL STRUCTURES FOR BUILDINGS (LIMIT STATES DESIGN)"

5.

CSA W47.1-03 "CERTIFICATION OF COMPANIES FOR FUSION WELDING OF STEEL


STRUCTURAL".

1.

DESIGN IN ACCORDANCE TO CAN/CSA-S16-01

6.

CSA W59-03, "WELDED STEEL CONSTRUCTION (METAL ARC WELDING)".

3.

7.

CSA W178.1-03, "QUALIFICATION CODE FOR WELDING INSPECTION ORGANIZATIONS".

UNLESS NOTED OTHERWISE ON DRAWINGS LIMIT JOIST ROOF TOTAL LOAD DEFLECTION
TO L/240 AND LIVE LOAD DEFLECTION TO L/360.

8.

ASTM A307. "LOW CARBON STEEL EXTERNALLY AND INTERNALLY THREADED


FASTENERS".

4.

DESIGN REQUIRED BRIDGING SIZE AND SPACING.

CONCRETE FORMWORK SHALL CONFORM WITH:

ALBERTA BUILDING CODE, 2006.

CSA 23.1-04 AND CSA 269.1-1975 (R2003) "FALSEWORK FOR CONSTRUCTION


PURPOSE".

2.

THE DESIGN OF CONCRETE FORMWORK AND ADEQUATE SHORING SYSTEMS ARE THE
RESPONSIBILITY OF THE CONTRACTOR.

3.

CONSTRUCT FORMWORK TO MAINTAIN THE FOLLOWING MAXIMUM TOLERANCES UNLESS


SPECIFICALLY SHOWN OTHERWISE ON THE DRAWINGS.

DEVIATION FROM HORIZONTAL AND VERTICAL LINES 3/8" (10mm) IN 66 ft (20 m).

DEVIATION OF BUILDING DIMENSIONS NOT MORE THAN 3/16" (5mm).

DEVIATION OF CROSS SECTIONAL DIMENSIONS OF COLUMNS OR BEAMS +/- 1/8"


(+/-3mm).

2.

SECTION 03200 CONCRETE REINFORCEMENT


1.

CONCRETE REINFORCEMENT SHALL CONFORM WITH:

AACI DETAILING MANUAL - A.C.I. 315-74

CSA A23.1-04 AND A23.3-04.

CSA G40.20-M1983 (R2004) GENERAL REINFORCEMENTS FOR ROLLED OR WELDED


STRUCTRUAL QUALITY STEEL

CSA G30.15-M1983 (R1991) WELDED DEFORMED STEEL WIRE BARS

CAN/CSA-G30.18-M92 BILLET STEEL BARS FOR CONCRETE REINFORCEMENT

CSA W186-M1990(R2002) WELDING OF REINFORCING BARS

ASTM A775 EPOXY REINFORCEMENT

2.

SUBMIT SHOP DRAWINGS FOR ALL REINFORCING STEEL

3.

REINFORCING STEEL TO CSA G30.18-M92 400 MPA YIELD GRADE SPECIAL LOW ALLOY
DEFORMED BILLET STEEL FOR WELDING, WITH EQUIVALENT CARBON CONTENT NOT
EXCEEDING 0.5 AND/OR FOR BENDING WHERE BENDING RADIUS IS SMALLER THAN
RECOMMENDED STANDARDS.

3.

4.

5.

4.

SHOP BEND BARS COLD. IDENTIFY STEEL. HOOKS, BENDS, CAPS AND SIMILAR DETAILS TO ACI
DETAILING MANUAL 315-74.

5.

CLEAN REINFORCEMENT TO CSA A23.1-04.

6.

CONCRETE COVER TO BE PROVIDED AS FOLLOWS, UNLESS NOTED OTHERWISE ON THE


DRAWINGS. USE THE GREATER VALUE OF COVER IN THIS SPECIFICATION OR ON THE
DRAWINGS.

CAST-IN-PLACE CONCRETE SHALL CONFORM WITH:

ALBERTA BUILDING CODE 2006

CAN/CSA-A5-93 PORTLAND CEMENTS

CAN/CSA-A8-93 MASONRY CEMENTS

CSA-A23.1-04 AND CSA-A23.2-04

CSA-A23.3-04 DESIGN OF CONCRETE STRUCTURES FOR BUILDINGS

CAN 3-266.2-M78 CHEMICAL ADMIXTURES FOR CONCRETE

CSA A283-1980 QUALIFICATIONS CODE FOR CONCRETE TESTING LABORATORIES

CAN A266.1-M78 AIR ENTRAINMENT ADMIXTURES FOR CONCRETE.


TO ENSURE THAT THE REQUIRED CONCRETE STRENGTHS ARE BEING ACHIEVED, TESTING
SHALL BE PERFORMED BY A RECOGNIZED TESTING LABORATORY AS FOLLOWS:

ONE SET OF THREE (3) STANDARD TEST SPECIMENS, TO BE MADE FOR EACH CLASS
OF CONCRETE IN ANY ONE DAY POUR OF MORE THAN 5 CUBIC METERS. FOR POURS
OF MORE THAN 60 CUBIC METERS, ONE SET PER EACH 60 CUBIC METER.

ONE ADDITIONAL STANDARD TEST SPECIMEN TO BE MADE DURING COLD WEATHER.

CONCRETE TO SAMPLED AT THE POINT OF DEPOSIT OF THE CONCRETE.

FOR EACH SET OF TEST SPECIMENS A SLUMP TEST AND ENTRAINED AIR TEST IS TO BE
INCLUDED.
CONCRETE REQUIREMENTS:

READY MIX CONCRETE TO A.S.T.M. C94 (LATEST VERSION)

REFER TO CONCRETE SCHEDULE FOR MIX REQUIREMENTS.

AGGREGATES TO CSA-A23.1-04 AND ASTM C330-04 MAXIMUM SIZE 3/4" (20mm) COARSE
AGGREGATE.
CONCRETE WORK TO BE WITHIN THE TOLERANCE LISTED BELOW:

VARIATION OF THE LINEAR BUILDING LINES LESS THAN 3/16" (5mm).

VARIATION OF GROSS SECTIONS OF THICKNESS OF SLABS MINUS 6mm OR PLUS 6mm

VARIATION FROM LEVEL OR FROM GRADES INDICATED FOR SURFACES OF SLAB SHALL
NOT EXCEED A 3mm STRAIGHT EDGE IMMEDIATELY AFTER TROWELLING.
CONDUITS, PIPES AND SLEEVES IN CONCRETE

ACCURATELY LOCATE AND SET IN PLACE ITEMS WHICH ARE TO BE CAST DIRECTLY
INTO CONCRETE.

COORDINATE WORK WITH OTHER TRADES.

PLACEMENT OF CONDUITS, SLEEVES, ETC. SHALL NOT IMPAIR THE STRUCTURAL


STRENGTH OF STRUCTURE. CENTER LINE SPACING TO BE NOT LESS THAN 3 CONDUIT
DIAMETERS. CENTER LINE SPACING BETWEEN PARALLEL CONDUITS AND
REINFORCEMENT TO BE 3 CONDUIT DIAMETERS.

SLEEVES OR CONDUITS THROUGH COLUMNS NOT ALLOWED.

SLEEVES THROUGH BEAMS NOT ALLOWED.

DO NOT PLACE SLEEVES NEXT TO COLUMNS. MAINTAIN SLEEVES 4 ft (1200mm)


MINIMUM DISTANCE AWAY FROM FACE OF COLUMN.

SPACING OF SLEEVES THROUGH SLABS TO BE 2 TIMES THE DIAMETERS MINIMUM.

DESIGN

9.

10. ASTM, A490-02, "SPECIFICATION FOR QUENCHED AND TEMPERED STEEL BOLTS AND
STUDS".

EXPOSURE CLASS
N

F-1, F-2
S-1, S-2
1 5/8"
(40mm)

EXPOXYCOATED
BARS

C-XL, C-1, C-3


A-1, A-2, A-3
2 3/8"
(60mm)

C-2, C-4
-

NO

FORMED SURFACES EXPOSED TO EARTH (PILES,


PILE CAPS AND GRADE BEAMS)

1 5/8"
(40mm)

INTERIOR SLAB ON GRADE

3/4"
(20mm)

NO

2 3/8" (60mm)
1 5/8" (40mm)

NO
NO

2 3/8" (60mm)
1 5/8" (40mm)

YES
NO

3/4"
(20mm)

NO

STOOPS (STRUCTURAL OR ON GRADE)

- TOP STEEL
- BOT STEEL

CONCRETE APRONS SUBJECT TO EXTERIOR EXPOSURE


(INCLUDING DOWELS)
- TOP STEEL
- BOT STEEL
SIDEWALKS, CURBS AND GUTTERS, SPLASH PADS AND
SUMP PITS

RATIO OF COVER TO NOMINAL DIAMETER

1.0

1.5

2.0

1.0

RATIO OF COVER TO NOMINAL MAXIMUM AGGREGATE SIZE

1.0

1.5

2.0

1.0

7.

LAP HORIZONTAL STEEL IN ACCORDANCE WITH CSA A23.3-04.

8.

PROVIDE ADDITIONAL REINFORCEMENT TO THAT INDICATED ON DRAWINGS AS FOLLOWS:

2-15M VERTICALS AT ENDS OF WALLS

2-15M HORIZONTALS ABOVE AN OPENINGS IN WALLS. EXTEND REINFORCEMENT 18"


(450mm) BEYOND EDGE OF OPENING ON EACH SIDE.

PROVIDE CORNER BARS TO ALL CORNERS AND INTERSECTIONS.

6.

SUPPORT SLAB BOTTOM REINFORCEMENT ON SLAB BOLSTERS TO MAINTAIN CONCRETE


PROTECTION AS REQUIRED

7.

SLAB POURS SHALL NOT EXCEED 45 ft (14M)

8.

LAYOUT CONSTRUCTION JOINTS PRIOR TO PLACEMENT OF CONCRETE.

9.

HOOKS ON COLUMNS SHALL BEND 135

ABSORPTIVE MAT OR FABRIC KEPT CONTINUOUSLY WET.


DAMP SAND, EARTH, OR SIMILAR MOIST MATERIAL.

SUBMIT SHOP DRAWINGS.

2.

PROVIDE COMPLETE FABRICATION AND ERECTION DRAWINGS OF ALL WORK AND ITEMS.

3.

SHOW FRAMING PLANS AND GRIDLINES, BEARING AND ANCHORAGE DETAILS, FRAMED
OPENINGS, ACCESSORIES, SPECIAL ERECTION PROCEDURES SCHEDULE OF MATERIALS,
CAMBER AND LOADINGS, FASTENERS AND WELDS USING BASIC WELD SYMBOLS TO
AMERICAN WELDING SOCIETY.

4.

PROVIDE SEPARATE LAYOUT PLANS AND SETTING DETAILS FOR ALL BEARING AND
ATTACHMENT DEVICES SUPPLIED UNDER THIS SECTION FOR SETTING AND BUILDING IN
UNDER OTHER SECTIONS.

5.

INCLUDE DETAILS OF ALL TEMPORARY BRACING SYSTEMS REQUIRED FOR STABILITY


DURING CONSTRUCTION AND SHOW THE EXTENT OR PRIOR WORK THAT IS REQUIRED
TO BE IN PLACE FOR THE TEMPORARY BRACING SYSTEMS AS DESIGNED.

6.

THE FABRICATOR IS TO CERTIFY ALL CONNECTIONS, DESIGN AND ERECTION


PROCEDURES, HAVE BEEN SUPERVISED AND CARRIED OUT BY A PROFESSIONAL
ENGINEER, REGISTERED IN THE PROVINCE OF ALBERTA, CERTIFICATION SHALL BE IN
THE FORM OF A LETTER BEARING THE SEAL AND SIGNATURE OF THE PROFESSIONAL
ENGINEER, AND SHOULD BE SUBMITTED WITH THE SHOP DRAWINGS. FAILURE TO
SUBMIT SUCH A LETTER WILL RESULT IN THE SHOP DRAWINGS BEING REJECTED.

7.

SHOP DRAWINGS TO BE CHECKED BY THE CONTRACTOR PRIOR TO SUBMISSION TO THE


ARCHITECT.

8.

REVIEW BY THE ARCHITECT IN NO WAY RELIEVES THE CONTRACTOR OF HIS


RESPONSIBILITY FOR THE ACCURACY OF THE SHOP DRAWINGS.

9.

SPECIFY PRIMER TO BE USED FOR EACH MEMBER AND COMPONENTS HIGHLIGHTING


EXPOSED PAINTED STEEL.

12. CSAG189 1975, "MATERIALS TO BE ZINC METALIZED".

SHOP DRAWINGS
1.

SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH SECTION 01300.

2.

PROVIDE COMPLETE FABRICATION AND ERECTION DRAWINGS OF ALL WORK AND ITEMS.

3.

SHOW FRAMING PLANS AND GRID LINES, BEARING AND ANCHORAGE DETAILS, FRAMED
OPENINGS, ACCESSORIES, SPECIAL ERECTION PROCEDURES SCHEDULE OF MATERIALS,
CAMBER AND LOADINGS, FASTENERS AND WELDS USING BASIC WELD SYMBOLS TO
AMERICAN WELDING SOCIETY.

4.

PROVIDE SEPARATE LAYOUT PLANS AND SETTING DETAILS FOR ALL BEARING AND
ATTACHMENT DEVICES SUPPLIED UNDER THIS SECTION FOR SETTING AND BUILDING IN
UNDER OTHER SECTIONS.

5.

INCLUDE DETAILS OF ALL TEMPORARY BRACING SYSTEMS REQUIRED FOR STABILITY


DURING CONSTRUCTION AND SHOW THE EXTENT OR PRIOR WORK THAT IS REQUIRED
TO BE IN PLACE FOR THE TEMPORARY BRACING SYSTEMS AS DESIGNED.

6.

10. DO NOT REMOVE FORMWORK BEFORE CONCRETE HAS REACHED 75% OF SPECIFIED 28 DAY
STRENGTH.
11. CURING

CONCRETE CURING TO CSA A23.1.

BASIC CURING: KEEP CONCRETE SURFACE CONTINUOUSLY MOIST UNTIL CONCRETE


TEMPERATURE DUE TO HYDRATION HAS PEAKED AND DROPPED SEVERAL DEGREES,
OR FOR THREE DAYS AT A MINIMUM TEMPERATURE OF 10OC.

ADDITIONAL CURING: IMMEDIATELY FOLLOWING BASIC CURING AND BEFORE THE


CONCRETE HAS DRIED, CURE FOR AN ADDITIONAL FOUR DAYS, MAINTAINING THE
TEMPERATURE OF THE AIR IN CONTACT WITH THE CONCRETE ABOVE 10C.

ACCEPTABLE CURING METHODS:


PONDING OR CONTINUOUS SPRINKLING.

1.

11. CISC/CPMA 1-73A "STRUCTURAL STEEL PRIMER".

CLEAR CONCRETE COVER SCHEDULE


EXPOSURE
CONDITION

ASTM A325-00, "HIGH STRENGTH BOLTS FOR STRUCTURAL STEEL JOINTS INCLUDING
SUITABLE NUTS AND PLAIN HARDENED WASHERS".

SHOP DRAWINGS

7.

THE FABRICATOR IS TO CERTIFY ALL CONNECTIONS, DESIGN AND ERECTION


PROCEDURES, HAVE BEEN SUPERVISED AND CARRIED OUT BY A PROFESSIONAL
ENGINEER, REGISTERED IN THE PROVINCE OF ALBERTA, CERTIFICATION SHALL BE IN
THE FORM OF A LETTER BEARING THE SEAL AND SIGNATURE OF THE PROFESSIONAL
ENGINEER, AND SHOULD BE SUBMITTED WITH THE SHOP DRAWINGS. FAILURE TO
SUBMIT SUCH A LETTER WILL RESULT IN THE SHOP DRAWINGS BEING REJECTED.
SHOP DRAWINGS TO BE CHECKED BY THE CONTRACTOR PRIOR TO SUBMISSION TO THE
ARCHITECT.

MATERIALS
1.

CONFORM TO CAN/CSA-G40.20/G40.21-04

2.

WELDING TO CSA W59-03


PRIMER TO CONFORM TO CISC/CPMA-1-73A

8.

REVIEW BY THE ARCHITECT IN NO WAY RELIEVES THE CONTRACTOR OF HIS


RESPONSIBILITY FOR THE ACCURACY OF THE SHOP DRAWINGS.

3.

9.

SPECIFY PRIMER TO BE USED FOR EACH MEMBER AND COMPONENTS HIGHLIGHTING


EXPOSED PAINTED STEEL.

SECTION 05300 METAL DECKING

MATERIALS

REFERENCE STANDARDS

1.

1.

CANADIAN SHEET STEEL BUILDING INSTITUTE CODE OF PRACTICE.

2.

ALBERTA BUILDING CODE 2006

3.

CSA W47.1-03 "CERTIFICATION OF COMPANIES FOR FUSION WELDING OF STEEL


STRUCTURES".

CONTINUOUS STEAM VAPOUR MIST BATH NOT EXCEEDING 70C.


CURING COMPOUND.
WATERPROOF PAPER OR PLASTIC FILM.

STRUCTURAL STEEL TO CONFORM TO CAN/CSA G40.20/G40.21-04 WITH MINIMUM GRADE


AS FOLLOWS:

ROLLED STEEL SECTIONS TO GRADE 350W.

ANGLES AND PLATES TO GRADE 300W.

HSS STEEL SECTIONS TO GRADE 350W.

OTHER MOISTURE_RETAINING METHOD APPROVED BY THE CONSULTANT.

DO NOT USE CURING COMPOUNDS ON CONCRETE SURFACES, WHICH ARE EXPECTED


TO RECEIVE TOPPING, HARDENER, OR OTHER TYPE OF BONDED FINISH UNLESS
APPROVED BY THE CONSULTANT.

2.

ANCHOR BOLTS - ASTM A-307

3.

BOLTS, NUTS AND WASHERS: HIGH STRENGTH TYPE RECOMMENDED FOR STRUCTURAL
STEEL JOINTS, CONFORMING TO REQUIREMENTS OF ASTM A325, MEDIUM-CARBON
STEEL.

PROTECT FRESHLY PLACED AND CONSOLIDATED CONCRETE AGAINST DAMAGE OR


DEFACEMENT FROM ADVERSE WEATHER CONDITIONS.

EXPOSED CONCRETE WALKING SURFACES NOT TO RECEIVE AN INTEGRAL HARDENER:


COAT WITH CURING COMPOUND OR CURING METHOD THAT PROVIDES PERMANENT
SEAL.

4.

WELDING MATERIALS - CSA W59-03

5.

IN AREAS WITH AN EXPOSED CONCRETE FLOOR SURFACE, APPLY THE HARDENER


AND DUST_PROOFING AGENT STRICTLY TO THE MANUFACTURER'S INSTRUCTIONS.

SUBMIT PROPOSED METHODS OF PROTECTION AND CURING WHEN AIR TEMPERATURE


IS AT OR ABOVE 25C OR AT OR BELOW 5C, OR LIKELY TO BE SO WITH 24 HOURS OF
PLACING TIME.

DESIGN
1.

DESIGN IT TO CSA-S136-01

2.

LIMIT DEFLECTION TO L/360 MAXIMUM UNDER SPECIFIED LIVE LOAD AND TO L/240
MAXIMUM UNDER SPECIFIED TOTAL LOADS.

PRIMER, TO CONFORM TO CISC/CPMA 1-73A "STRUCTURAL STEEL PRIMER".

3.

SPAN DECK OVER 3-SPANS.

6.

PRIMERS ARE TO BE DIFFERENT AND DISTINCTIVE COLOR FOR EACH ONE USED.

4.

7.

PRIMER TO CONFORM TO GP 79-005 EPOGARD ACTIVATED ZINC RICH PRIMER TO ALL


STEEL, INTERIOR AND EXTERIOR, EXPOSED TO VIEW IN THE FINAL ASSEMBLY.

LOCATE END JOINTS OVER BEARING SUPPORT AND CAP 2" (50mm) MINIMUM WHERE
APPLICABLE.

5.

BOTTOM PUNCH SIDE LAPS MECHANICALLY, 24" (600mm) MAXIMUM.

WATER FOR CURING SHALL BE CLEAN AND FREE FROM MATERIALS THAT WILL CAUSE
STAINING OR DISCOLORATION OF THE CONCRETE.

8.

SHOP GALVANIZING: HOT DIPPED GALVANIZING WITH A MINIMUM COATING OF 700 G/M2
TO CSA G164.

6.

WELD DECK TO SUPPORTING STEEL WITH 3/4" (20mm) DIAMETER SPOTS AT 12" (300mm)
O.C. AT INTERIOR SUPPORTS, AND 6" (150mm) O.C. AT EXTERIOR SUPPORTS.

FOR HORIZONTAL SURFACES, SPREAD 50 MM OF MOIST SAND OVER THE ENTIRE


SURFACE AND KEEP SATURATED WITH WATER.

9.

7.

FOR VERTICAL SURFACES SUCH AS WALLS, COLUMNS, PIERS, LOOSEN THE FORMS,
LEAVE THEM IN PLACE AND CONTINUOUSLY APPLY WATER BETWEEN THE FORM AND
THE CONCRETE SURFACE. ALTERNATIVELY THE FORMS MAY BE REMOVED AND AN
ABSORPTIVE WOVEN FABRIC APPLIED AND KEPT CONTINUOUSLY MOIST.

SHEAR STUD CONNECTORS: HEADED CONCRETE ANCHORS CONFORMING TO ASTM


A108-73.

FABRICATION AND ERECTION

FOR OPENINGS UP TO 18" (450mm) ACROSS THE FLUTES REINFORCE DECK WITH
L76x76x6.4 STEEL ANGLE PERPENDICULAR TO FLUTES, EXTENDED THREE FLUTES AND
WELD EACH SIDE OF OPENING.

8.

ASTM A653/A653M, STRUCTURAL QUALITY AS REQUIRED, COATING DESIGNATION ZF75.

IF MOIST CURING IS NOT USED, THEN SPRAYED CURING COMPOUNDS ARE TO BE


USED.

CURING COMPOUNDS TO BE OF THE LIQUID MEMBRANE TYPE FOR CURING CONCRETE


AND SHALL BE APPLIED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S
PRINTED INSTRUCTIONS.

CURING COMPOUNDS USED FOR EXPOSED CONCRETE MUST NOT DISCOLOR THE
CONCRETE, NOR BE SUCH AS TO PROHIBIT THE SUBSEQUENT APPLICATION OF PAINT,
TILES, PARGING OR OTHER COATINGS.
FOR HORIZONTAL SURFACES, AFTER THE COMPLETION OF FINISHING OPERATIONS
AND IMMEDIATELY AFTER THE DISAPPEARANCE OF SURFACE MOISTURE, APPLY THE
SPRAYED CURING COMPOUND.

1.

FABRICATORS AND ERECTORS TO SATISFY THE REQUIREMENT OF CAN/CSA W47.1, CSA


W59 AND S16-01

2.

FABRICATION AND ERECTION TO FOLLOW CISC CODE OF STANDARD PRACTICE (R2002)

SECTION 04200

UNIT MASONRY

REVIEW
1.

MATERIAL AND WORKMANSHIP SHALL BE INSPECTED AND APPROVED BY A RECOGNIZED


TESTING FIRM, APPROVED BY THE ARCHITECT OR HIS REPRESENTATIVE AND PAID FOR
BY THE CONTRACTOR.

2.

PROVIDE ACCESS FOR INSPECTION TO ALL PLACES WHERE WORK IS BEING DONE, OR
MATERIAL STOCKPILED PRIOR TO SHIPMENT.

3.

SUBMIT COPIES OF MILL TEST REPORTS PROPERLY CORRELATED TO THE MATERIALS


USED TO THE ARCHITECT UPON REQUEST.

4.

1.

MASONRY WORK SHALL CONFORM TO CSA STANDARD CSA-A371-04, "MASONRY


CONSTRUCTION FOR BUILDING".

2.

MASONRY SHALL BE REINFORCED HORIZONTALLY WITH 3/16" (4.8mm) DIAMETER


GALVANIZED TRUSS OR LADDER TYPE DEFORMED BAR REINFORCEMENT AT 16" (400mm)
O/C, LAPPED 8" (200mm) AT SPLICES.

3.

MASONRY:
MASONRY
MATERIALS

SPECIFICATION

GRADE

INSPECTION TO INCLUDE VISUAL EXAMINATION OF WELDING PROCEDURES, AT THE


PLANT AND IN THE FIELD, PLUS MAGNETIC PARTICAL, X-RAY OR OTHER MEANS DEEMED
NECESSARY BY THE FABRICATOR'S ENGINEER.

MASONRY UNITS

CSA-A165 SERIES 94

H/15/C/M

5.

INSPECTION TO INCLUDE RANDOM CHECKING OF BOLTS.

MORTAR

CSA-A179-04

TYPE S

6.

THE ARCHITECT MAY REQUEST ADDITIONAL TESTING OF WELDS AND BOLTS TO


ASCERTAIN THE FULL AMOUNT OF DEFECTS IF EXCESSIVE DEFICIENCIES ARE NOTED.
ADDITIONAL COSTS FOR EXTRA TESTING TO BE BORN BY THE CONTRACTOR.

GROUT

CSA-A179-04

A179 Sec. 8.0

METAL CONNECTORS

CSA-A370-94

7.

PAY FOR ALL COSTS FOR RE-TESTING AND RE-INSPECTION, AS A RESULT OF DEFECTIVE
WORKMANSHIP.

REINFORCING BARS

CAN/CSA-G30.R(2002)

400 MPa

8.

PAY FOR ALL COSTS OF REPAIRS TO CORRECT DEFECTIVE WORK.

BRICKS

CSA-A165.2-04

400 MPa

9.

INSPECTION FIRM TO SUBMIT TO THE ARCHITECT, A FINAL REPORT CERTIFYING ALL


WELDS AND CONNECTIONS, INCLUDING CONFIRMATION THAT REQUIRED REPAIRS HAVE
BEEN COMPLETED. THIS REPORT MUST BE SUBMITTED UNDER THE SEAL AND
SIGNATURE OF A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE
PROVINCE OF ALBERTA.

4.

ALL GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 20 MPA.

5.

UNLESS SHOWN OTHERWISE, ALL BOND BEAMS SHALL BE CONCRETE FILLED AND
REINFORCED WITH 1-15M BAR TOP AND BOTTOM.

6.

PROVIDE A MINIMUM LENGTH OF 8" (200mm) AND A MINIMUM DEPTH OF 8" (200mm) OF
100% SOLID OR CONCRETE FILLED MASONRY UNITS FOR SUPPORT OF STEEL,
CONCRETE OR REINFORCED MASONRY LINTELS.

7.

UNLESS SHOWN OTHERWISE, PILASTERS AND CELLS ADJACENT TO DOOR FRAMES AND
WINDOW OPENING SHALL BE CONCRETE FILLED AND REINFORCED WITH 1-15M BAR.
PROVIDE VERTICAL DOWELS TO MATCH IN THE ADJACENT REINFORCED CONCRETE
STRUCTURE.

8.

WHERE DOWELS, ANCHOR BOLTS, ETC., ARE SHOWN PROJECTING INTO THE MASONRY,
FILL VOIDS WITH CONCRETE OR CEMENT MORTAR.

10. NOTIFY ARCHITECT 24 HOURS PRIOR TO COMMENCEMENT OF INSPECTION.


11. CONDUCT TESTING TO CSA W59 AND CAN/CSA S16.1 STANDARDS, INCLUDING, BUT NOT
LIMITED TO THE FOLLOWING:

VISUAL EXAMINATION OF ALL WELDS AND WORKMANSHIP THAT ARE READILY


ACCESSIBLE (100%).
RANDOM MAGNETIC PARTICLE TESTING OF SELECTED SHOP WELDS OF ALL
COMPONENTS (20% OF CONNECTIONS).
RANDOM MAGNETIC PARTICLE TESTING OF SELECTED FIELD WELDS OF ALL
COMPONENTS (20% OF CONNECTIONS).
RANDOM CHECKS OF STRUCTURAL STEEL MEMBER SIZES (UP TO 20% OF
COLUMNS AND UP TO 20% OF BEAMS, GIRDERS, BRIDGING AND BRACING, ETC.).
VISUAL EXAMINATION OF MEMBERS FOR CONFORMANCE TO REQUIREMENTS FOR
ARCHITECTURAL FINISHES (LIMITED).
BOLT SPECIFICATIONS, GRADES AND FASTENING VERIFICATION (20% OF ALL
CONNECTIONS).
REVIEW OF DRAWINGS, WELDING PROCEDURES, WELDERS' CERTIFICATIONS, DATA
SHEETS, AND WELDING CONSUMABLES STORAGE (SHOP AND FIELD).
REVIEW OF READILY AVAILABLE MILL CERTIFICATES FOR ALL MATERIAL USED.
EMBED PLATES WILL BE BEND TESTED ON 1% OF RANDOMLY SELECTED STUDS,
AND TESTED TO DESTRUCTION ON (1/3%).
DECKING EXAMINATION OF PROFILE AND GAUGE (20%). INSPECTION OF PUDDLE
WELDS AND SIDE LAP CRIMPING THAT IS ACCESSIBLE (100%).
CONFIRM CORRECT LOADING, UNLOADING, AND SITE STORAGE OF COMPONENTS.
CONFIRM ACCEPTABILITY OF PRIMER COATS.
TRACKING OF ALL NOTED DEFICIENCIES, TIMELY FAXING OF TECHNICAL REPORTS
TO RELEVANT PARTIES, IMMEDIATE CORRESPONDENCE OF IMPORTANT ISSUES TO
THE ENGINEER OF RECORD, AND A FINAL SUMMARY REPORT INCLUDING ALL
RETAINED DOCUMENTATION, THE FINAL PROJECT STATUS.

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

TOP OF PILE = 97'-10"


TO BE COORD. WITH ARCH.
SIDEWALK ELEVATIONS
AND SLOPES. TYPICAL AT
EXTERIOR STOOPS.
240'-0"
40'-0"

40'-0"

40'-0"

40'-0"

40'-0"

40'-0"

16'-0"

12'-0"

12'-0"

16'-0"

12'-0"

'P
4'

'P
4'

'P
4'

12'-0"

12'-0"

16'-0"

12'-0"

12'-0"

16'-0"

10'-5"

1'-7"

'P
1'

1'-4"

'P
1'

1'-4"

'P
1'

1'-7"

'P
2'

1'-4"

'P
1'

1'-4"

'P
1'

1'-7"

'P
2'

1'-4"

'P
1'

1'-4"

'P
1'

1'-7"

'P
2'

1'-4"

'P
1'

1'-4"

'P
1'

1'-7"

'P
2'

1'-4"

'P
1'

1'-4"

'P
1'

1'-7"

'P
2'

1'-4"

'P
1'

1'-4"

F3
S-501

4'-8"

F8

F9

F7

F6

F3

F8

F7

F3

F7

F6

F9

F8

F3

F7

F8

F6

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

SIM.

1'-4"

SIM.

SIM.

SIM.

SIM.

SIM.

SIM.

SIM.

SIM.

SIM.

SIM.

15'-11"

SIM.

15'-11"

8'-0"

'P
4'

'P
1'

'P
1'

6'-11"

1'-7"

12'-0"

4'-8"

16'-0"

4'-8"

12'-0"

4'-8"

12'-0"

1'-7"

16'-0"

4'-8"

10'-5"

1'-7"

4'-8"

'P
4'

'P
4'

3'-8"

F1

SIM.

1'-4"

17'-6"

17'-6"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

F1
S-501

'P
T/ 3'
O
=
95 PI
'-6 LE
"

SIM.
'P
T/ 3'
O
=
95 PI
'-6 LE
"

20'-1"

'P
1'

35'-0"

'P
1'

'P
4'

S-501

SIM.

4'-0"

4'-0"

F4

4'-0"

SIM.

4'-0"

4'-0"

'P
3'

1'-9"
SIM.

F4

'P
3'

4'-0"

SIM.

F5
S-501

SIM.

17'-6"

SIM.

F5
S-501

'P
T/ 3'
O
=
95 PI
'-6 LE
"

F5
S-501

'P
T/ 3'
O
=
95 PI
'-6 LE
"

4'-0"
'P
T/ 3'
O
=
95 PI
'-6 LE
"

4'-0"

SIM.

'P
T/ 3'
O
=
95 PI
'-6 LE
"

F5
S-501

1'-4"
35'-0"

'P
1'

SIM.

SIM.

F2

F2

S-501

S-501

17'-6"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

17'-6"

'P
1'

1'-4"

4'-0"

4'-0"

4'-0"

F4

4'-0"

4'-0"

'P
3'

1'-9"

F4
S-501

F5
S-501

SIM.

S-501

SIM.

1'-4"

'P
1'

1'-4"
SIM.

SIM.

SIM.

F2

F3

F2

F3

F2

F1

S-501

S-501

S-501

S-501

S-501

S-501

S-501

S-501

18'-8"
'P
2'

20'-0"
'P
2'

'P
2'

20'-0"
'P
2'

20'-0"

1'-4"

20'-0"
'P
2'

20'-0"

'P
2'

20'-0"
'P
2'

20'-0"
1'-4"

20'-0"
'P
2'

'P
2'

20'-0"
'P
2'

20'-0"

1'-4"

18'-8"

1'-4"
'P
2'

SIM.

F1

1'-4"

SIM.

F3

'P
2'

1'-4"

SIM.

19'-0"

F1
S-501

19'-0"

F1
S-501

SIM.

'P
2'

9'-8"

'P
3'

F5

'P
T/ 3'
O
=
95 PI
'-6 LE
"

S-501

SIM.

4'-0"

4'-0"

4'-0"

S-501

SIM.

F5

'P
T/ 3'
O
=
95 PI
'-6 LE
"

S-501

SIM.

F5

'P
T/ 3'
O
=
95 PI
'-6 LE
"

'P
1'

F5

'P
T/ 3'
O
=
95 PI
'-6 LE
"

4'-0"

9'-8"

1'-9"

'P
T/ 3'
O
=
95 PI
'-6 LE
"

4'-0"

S-501

30'-0"

1'-4"
'P
4'

4'-8"

'P
4'

'P
4'

'P
4'

4'-8"

4'-8"

CL. OF PILE
4'-8"

CL. OF PILE
1'-4"

THESE BRACES ARE FROM HEADER TO ROOF ONLY


SEE STEEL ELEVATIONS ON DRAWING S-701
FOR MORE INFORMATION.

TOP OF PILE = 97'-10"


TO BE COORD. WITH ARCH.
SIDEWALK ELEVATIONS
AND SLOPES. TYPICAL AT
EXTERIOR STOOPS.

PILE LAYOUT PLAN

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

1/8"=1'-0"
1.

THIS DRAWING SHALL BE READ IN-CONJUCTION WITH THE FOUNDATION PLAN ON DRAWING S-202.

2.

REFER TO DRAWINGS S-101 TO S-103 FOR GENERAL NOTES & TYPICAL DETAILS.

3.

UNLESS NOTED OTHERWISE TOP OF PILE ELEVATION IS AT 97'-6".

4.

T/O PILE ELEVATION IS SHOWN ON PLAN AS THUS: Px (EL. XX'-X")

5.

UNLESS NOTED OTHERWISE PROVIDE A MINIMUM OF 4-15M DOWELS x 48" LONG FROM PILES TO GRADE BEAMS / PIERS ABOVE.

CONCRETE PILE SCHEDULE 'P'


LENGTH

VERTICAL

STIRRUPS

'P1'

16"

42"

85'-0"

4-15M

10M @ 12"

'P2'

16"

48"

85'-0"

4-15M

10M @ 12"

'P3'

20"

60"

85'-0"

8-15M

10M @ 12"

'P4'

16"

4-15M

10M @ 12"

20'-0"

1.

EXTEND PILE REINFORCEMENT FOR FULL LENGTH OF PILE.

2.

INSTALL PILES UNDER THE DIRECT SUPERVISION OF A GEOTECHNICAL ENGINEER


AND PAID FOR BY CONTRACTOR .

3.

PROVIDE A SEPARATE PRICE FOR CASING OF ALL PILES FOR FULL LENGTH.

4.

PROVIDE A UNIT RATE PRICE FOR CASING OF ALL DIFFERENT PILE DIAMETERS.

5.

CONCRETE CAST-IN PLACE PILES HAVE BEEN DESIGNED ON THE BASIS OF THE
FOLLOWING CAPACITIES:
DEPTH BELOW GRADE
0 TO 5'-0"
5'-0" TO 13'-0"
BELOW 13'-0"

SKIN FRICTION (ALLOWABLE)


0
psf
440 psf
600 psf

6.

CONCRETE CAST IN PLACE END BEARING PILES HAVE BEEN DESIGNED ON THE
BASIS OF A FACTORED BEARING CAPACITY OF 15,700 psf IN THE BEARING STRATUM
RECOMMENDED IN THE GEOTECHNICAL REPORT. BOTTOM OF PILE ELEVATION TO
BE VERIFIED IN WRITING BY A GEOTECHNICAL ENGINEER PRIOR TO CONSTRUCTION.

7.

ABOVE BEARING CAPACITIES SHALL BE VERIFIED ON SITE BY A GEOTECHNICAL


ENGINEER IN WRITING AND PAID FOR BY THE CONTRACTOR .GEOTECHNICAL
ENGINEER TO CONFIRM IN WRITING THAT GEOTECHNICAL REPORT
PARAMETERS/RECOMMENDATIONS APPLY FOR THIS BUILDING SITE PRIOR TO
COMMENCING WITH WORK.

8.

PRIOR TO PLACING CONCRETE FOR PILE FOUNDATIONS, BEARING STRATA FOR


PILES SHALL BE INSPECTED BY A GEOTECHNICAL CONSULTANT TO CONFIRM THEIR
LOAD CARRYING CAPACITY IN WRITING PRIOR TO COMMENCING WITH WORK. P.E.C.
IS NOT RESPONSIBLE FOR CONFIRMING FOUNDATION CAPACITIES OF SOIL.

9.

PILE LENGTHS SHOWN ARE NOT FINAL AND MAY VARY ACCORDING TO SITE
CONDITIONS. LENGTH OF PILE SHALL BE AT THE DISCRETION OF THE
GEOTECHNICAL CONSULTANT. EXTEND ALL PILES TO A BEARING LAYER APPROVED
BY THE GEOTECHNICAL ENGINEER. INFORM P.E.C. OF ALL SUCH CASES PRIOR TO
CONSTRUCTION.

ADDITIONAL PILES AT ALLOWED FUTURE MEZZANINE (SEE MEZZANINE PLAN ON DWG. S-302)
1/16"=1'-0"
1.

EACH PILE IS ASSUMED TO C/W 24" x 24" DP. CONCRETE PIER R/W 8-15M VERTICAL & 10M @ 12" TIES (3 TIES MINIMUM). TOP OF PIER = 99'-0".

'P
T/ 2'
= O
97 PI
'-0 LE
"

ELEV. @
BASE U.N.O.

'P
T/ 2'
= O
97 PI
'-0 LE
"

BELL

'P
T/ 2'
= O
97 PI
'-0 LE
"

SHAFT

REINFORCEMENT

'P
T/ 2'
= O
97 PI
'-0 LE
"

SIZE

'P
T/ 2'
= O
97 PI
'-0 LE
"

TYPE

'P
T/ 2'
= O
97 PI
'-0 LE
"

100'-0"

17'-6"

F5
S-501

'P
T/ 3'
O
=
95 PI
'-6 LE
"

1'-9"

4'-0"

S-501

4'-0"

S-501

8" CONCRETE APRON SLAB


R/W 15M @ 10" EACH WAY
TOP AND BOTTOM

CONCRETE APRON
COORD. WITH ARCH. DWGS.

240'-0"

F3

F7

SIM.

S-501

S-501

SIM.

SIM.

F3

F7

F6

S-501

S-501

S-501

SIM.

SIM.

F8
S-501

F9

'GB2'

SIM.

S-501

SIM.

'GB2'

'GB2'

'B
'C .PL
P3 .2
' '

'GB2'

'B
'C .PL
P3 .2
' '

'GB2'

SIM.

F8

F3

F7

S-501

S-501

SIM.

'GB2'

'B
'C .PL
P3 .2
' '

5'-0"

5'-0"

'GB3'

'GB2'

'B
'C .PL
P3 .2
' '

F8

'GB2'

33'-10"

S-501

'B
'C .PL
P2 .3
' '

F6
S-501

'GB3'

'GB2'

S-501

5'-0"

'B
'C .PL
P4 .3
' '

F7
S-501

'GB2'

35'-0"

15M @ 10" TOP x 12'-0" Lg.


TYPICAL AT OVERHEAD DOORS.

5'-0"

5'-0"

'B
'C .PL
P3 .2
' '

F9
S-501

5'-0"

'GB3'

'GB2'

S-501

F6

SIM.

S-501

SIM.

SIM.
SIM.

F1
S-501

'B
'C .PL
P6 .2
' '
'B
'C .PL
P
T
1 .1
= /O ' '
P
99 I
'-0 ER
"

'B
'C .PL
P
T
9 .6
= /O ' '
9 9 PI
'-0 ER
"

F4

'B
'C .PL
P
T
9 .6
= /O ' '
9 9 PI
'-0 ER
"

'B
'C .PL
P5 .4
' '

SIM.

'B
'C .PL
P
T
1 .1
= /O ' '
P
99 I
'-0 ER
"

F1
S-501

'GB2'

CONCRETE SLAB
THICKENING AT U/S OF
MASONRY BLOCK WALL
SEE TYPICAL DETAIL ON
DRAWING S-102.
COORD. LOCATION AND
EXTENT WITH ARCH.
DWGS. TYPICAL

SIM.

'B
'C .PL
P
T
9 .6
= /O ' '
9 9 PI
'-0 ER
"

'B
'C .PL
P6 .2
' '

DOUBLE SUMP PIT


SEE TYPICAL DETAIL
ON DRAWING S-102.
REFER TO MECH.
AND ARCH. DWGS.
FOR ADDITIONAL
INFORMATION
TYPICAL

'GB2'

35'-0"

'GB2'

35'-0"

40'-0"

'GB2'

'GB2'

'GB3'

9'-10"

SIM.

F3

5'-0"

'GB3'

'B
'C .PL
P3 .2
' '

5'-0"
'B
'C .PL
P4 .3
' '

F8
S-501

'GB2'

'B
'C .PL
P3 .2
' '

'GB2'

'B
'C .PL
P3 .2
' '

'B
'C .PL
P2 .3
' '

'B
'C .PL
P3 .2
' '

6'-0"

5'-0"

'GB2'

35'-0"

'B
'C .PL
P1 .7
0' '

CONCRETE FILLED
STEEL BOLLARD
SEE TYPICAL DETAIL
ON DRAWING S-102
TYPICAL AS SHOWN

'GB3'

'GB2'

5'-0"

40'-0"

'B
'C .PL
P3 .2
' '

35'-0"

40'-0"

'B
'C .PL
P1 .7
0' '

5'-0"

41'-2"

40'-0"

'B
'C .PL
P3 .2
' '

40'-0"

'B
'C .PL
P3 .2
' '

40'-0"

'B
'C .PL
P1 .7
0' '

30'-0"

CONCRETE SLAB THICKENING AT


EDGE OF CONCRETE APRON
SEE TYPICAL DETAIL ON DWG. S-102.

SIM.

F4

S-501

S-501

15M @ 10" TOP


x 12'-0" Lg.

15M @ 10" TOP


x 12'-0" Lg.

15M @ 10" TOP


x 12'-0" Lg.

F5

F5

F5

F5

F5

S-501

S-501

S-501

S-501

S-501

T/O CONC. SLAB

SIM.

SIM.

SIM.

'B
'C .PL
P5 .4
' '

15M @ 10" TOP


x 12'-0" Lg.

'GB2'

'GB2'

15M @ 10" TOP


x 12'-0" Lg.

SIM.

SIM.

SIM.

F2

F2

CONCRETE SLAB THICKENING


AT GRIDS 3,4 AND 5
SEE TYPICAL DETAIL ON
DRAWING S-102

'B
'C .PL
P6 .2
' '

S-501

'GB2'
'B
'C .PL
P
T
1 .1
= /O ' '
P
99 I
'-0 ER
"

'B
'C .PL
P
T
9 .6
= /O ' '
9 9 PI
'-0 ER
"

F4

'B
'C .PL
P
T
9 .6
= /O ' '
9 9 PI
'-0 ER
"

'B
'C .PL
P
T
1 .1
= /O ' '
P
99 I
'-0 ER
"

'B
'C .PL
P5 .4
' '

10M @ 10" DOWELS


TYPICAL AT PERIMETER
OF BUILDING U.N.O.
42"
14"

'B
'C .PL
P
T
9 .6
= /O ' '
9 9 PI
'-0 ER
"

'GB2'

84'-2"

S-501

F4
S-501

S-501

15M @ 10" TOP


x 12'-0" Lg.

15M @ 10" TOP


x 12'-0" Lg.

15M @ 10" TOP


x 12'-0" Lg.

'B
'C .PL
P5 .4
' '

15M @ 10" TOP


x 12'-0" Lg.

F5

F5

F5

F5

F5

S-501

S-501

S-501

S-501

S-501

SIM.

SIM.

SIM.

SIM.

SIM.

SIM.

F1

S-501

S-501

'GB3'

73'-2"

62'-2"

7.

8.

9.
10.
11.
12.
13.
14.

3.

4.

'B
'C .PL
P8 .2
' '

5'-0"

EACH LEG SHOWN CAN SUPPORT A MAXIMUM LOAD OF 6,000 Ibs / LEG.
PROVIDE A MINIMUM 4" x 4" BASE PLATE PER LEG.

ALTERNATE SLAB DESIGN (INTERIOR AND


EXTERIOR SLAB EXCLUDING SIDEWALKS)
MINIMUM SLAB THICKNESS

6"

SLAB REINFORCEMENT

10M @ 10" EACH WAY MIDDLE

CONCRETE STRENGTH (MPa)

25 (INTERIOR SLAB)
35 (EXTERIOR SLAB
EXCLUDING SIDEWALKS)

MAXIMUM LEG LOAD

6, 000 Ibs

ALTERNATE SLAB DESIGN WITH FIBER REINFORCING


(INTERIOR AND EXTERIOR SLAB EXCLUDING SIDEWALKS)
MINIMUM SLAB THICKNESS

6"

8"

MIN. STEEL FIBER REINF.


PER CUBIC METER (kg/m3)

20 kg

25 kg

CONCRETE STRENGTH (MPa)

25 (INTERIOR SLAB)
35 (EXTERIOR SLAB
EXCLUDING SIDEWALKS)

25 (INTERIOR SLAB)
35 (EXTERIOR SLAB
EXCLUDING SIDEWALKS)

MAXIMUM LEG LOAD

6, 000 Ibs

12, 000 Ibs

SUBGRADE MODULUS (k)


AS PER GEOTECH. REPORT

27 MPa/m

27 MPa/m

* ABOVE NOTED REINFORCEMENT IS BASED ON 'OPTIMET 11050' STEEL FIBERS.

CONCRETE GRADE BEAM SCHEDULE 'GB'


TYPE

'GB1'

SIZE

10"x30"

10"x30"

8"x24"

2-20M TOP
2-20M BOTTOM
10M @ 12" TIES

2-25M TOP
2-25M BOTTOM
10M @ 10" TIES

2-15M TOP
2-15M BOTTOM
10M @ 12" TIES

REINFORCEMENT

SECTION
SCHEMATIC

'GB3'

'GB2'

10"

10"

8"

(NOT TO SCALE)

4'-0"

4'-0"

5.

1.
2.

2'-6"

2.

CONTROL JOINT LAYOUT PLAN


1/16"=1'-0"
1.

THIS DRAWING SHALL BE READ IN-CONJUCTION WITH FOUNDATION PLAN ON THIS DRAWING..

10'-0"

10'-0"

1.
2.

RACKING LAYOUT (8" SLAB)

3.

1.
2.

4.

EACH LEG SHOWN CAN SUPPORT A MAXIMUM LOAD OF 12,000 Ibs / LEG.
PROVIDE A MINIMUM 4" x 4" BASE PLATE PER LEG.

5'-9"

10'-0"

ALTERNATE RACKING LAYOUT (6" SLAB)

SLOPE SLAB TO DRAINS AS PER ARCHITECTURAL AND MECHANICAL DRAWINGS. MAINTAIN


FULL SLAB THICKNESS THROUGHOUT.
SLAB ON GRADE SHALL BE 8" THICK R/W 15M @ 10" EACH WAY TOP AND BOTTOM ON 10 mil
POLY ON COMPACTED GRANULAR SUBGRADE FILL AS INDICATED IN THE GEOTECHNICAL
REPORT. TYPICAL UNLESS NOTED OTHERWISE ON PLAN. VERIFY ALL SUCH AREAS WITH
P.E.C. PRIOR TO CONSTRUCTION.
FOR FLOOR CURBS, TRENCHES AND OTHER MISCELLANEOUS DETAILS SEE
ARCHITECTURAL AND MECHANICAL DRAWINGS.
FOR LOCATION OF ALL SIDEWALKS AND / OR CONC. STOOPS SEE ARCH. DRAWINGS.
PROVIDE BLOCK-OUT IN GRADE BEAMS AT DOORWAYS TYPICAL SHOWN ON PLAN
AS THUS:
ENSURE ALL GRADE BEAMS ARE TEMPORARILY BRACED AND LATERALLY SUPPORTED.
LEAVE GRADE BEAM FORMS INTACT UNTIL CONCRETE HAS REACHED 70% OF ITS
SPECIFIED STRENGTH.
PROVIDE A FULL TENSION SPLICE AT ALL LAPS IN SLAB REBAR.
REFER TO ARCHITECTURAL DRAWINGS FOR SIZE AND LOCATIONS OF SLAB DEPRESSIONS.
MAINTAIN FULL SLAB THICKNESS THROUGHOUT.
WALL BRACE SHOWN ON PLAN THUS:

PREPARATION / PROTECTION OF SUBGRADE / SUB-BASE IS NOT PART OF P.E.C.S


SCOPE OF WORK AND AS SUCH THE CONTRACTOR SHALL REVIEW AND FOLLOW THE
RECOMMENDATIONS PROVIDED IN THE GEOTECHNICAL REPORT. PREPARATION OF THE
SUB-GRADE / SUB-BASE AND NEW FILL REQUIREMENTS SHALL BE REVIEWED, APPROVED
AND INSPECTED BY A GEOTECHNICAL ENGINEER WITHIN 24 HOURS PRIOR TO POURING
CONCRETE.
REMOVE ALL ORGANIC TOPSOIL, FILL AND OTHER DELETERIOUS MATERIAL FROM THE
BUILDING SLAB AREA.DEPTHS OF TOP SOIL AND FILL MAY VARY THROUGHOUT THE SITE
GEOTECHNICAL ENGINEER TO INSPECT AND ADVISE.
FOLLOWING THE SUBCUTTING OF THE ORGANIC TOPSOIL AND FILL LAYERS, THE GRADE
SHALL BE COMPACTED AND ANY SOFT SOILS BE IDENTIFIED AND ROLL PROOFED PRIOR TO
PLACEMENT OF THE NEW BACKFILL. GEOTECHNICAL ENGINEER TO ADVISE CONTRACTOR
ACCORDINGLY.
NEW ENGINEERED FILL SHALL BE COMPACTED AS PER THE GEOTECHNICAL REPORT.
FILL MATERIAL SHALL BE APPROVED BY A GEOTECHNICAL ENGINEER.
SEE GEOTECHNICAL REPORT FOR ADDITIONAL INFORMATION.

5'-0"

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

10'-0"

1'-0"
MIN.

1.

'GB1'

73'-2"

THIS DRAWING SHALL BE READ IN-CONJUCTION WITH PILE LAYOUT PLAN ON DWG. S-201.
REFER TO ROOF FRAMING PLAN ON DRAWING S-301 FOR COLUMN SIZES AND LOCATIONS.
REFER TO DRAWINGS S-101 TO S-103 FOR GENERAL NOTES & TYPICAL DETAILS.
REFER TO DRAWING S-401 FOR (B.PL.) BASE PLATE AND (CP) CONCRETE PIER DETAILS.
T/O CONC. SLAB ELEV. U.N.O. IS SHOWN ON PLAN AS THUS:
T/O CONC. SLAB
CONFIRM SLAB SLOPES WITH ARCHITECTURAL DRAWINGS.
ELEV. X'-X"
GEODETIC: X.X

SUBGRADE / SUB-BASE PREPARATION FOR


GRADE SUPPORTED FLOOR SLABS

'GB1'

'GB3'

5'-0"

1/8"=1'-0"

6.

'GB1'

6" STRUCTURAL CONCRETE SLAB


R/W 10M @ 10" EACH WAY BOTTOM
TYPICAL AT ALL MAN-DOORS
UNLESS NOTED OTHERWISE.

FOUNDATION PLAN
1.
2.
3.
4.
5.

'B
'C .PL
P8 .2
' '

'GB1'

'GB3'

5'-0"

'B
'C .PL
P8 .2
' '

'B
'C .PL
P8 .2
' '

'GB1'

2'-0"

'GB1'

2'-6"

'GB1'

1'-0"
MIN.

'GB1'

'B
'C .PL
P1 .8
1' '
'B
'C .PL
P1 .8
1' '
'B
'C .PL
P7 .5
' '

F1
S-501

4'-0"

'GB3'

CONCRETE CURB/SIDEWALK
REFER TO ARCHITECTURAL
DRAWINGS. TYPICAL AS SHOWN
FOR SIDEWALK DETAIL REFER
TO DRAWING S-102.

F2
S-501

4'-0"

SLAB THICKENING AT EDGE OF SLAB


TYPICAL AT ALL SIMILAR LOCATIONS.

5'-0"

'GB1'

F3
S-501

5'-0"

'B
'C .PL
P8 .2
' '

'B
'C .PL
P8 .2
' '

'GB1'

F2
S-501

5'-0"

5'-0"

'GB1'

SIM.

'B
'C .PL
P1 .8
1' '
'B
'C .PL
P1 .8
1' '

F3
S-501

THESE BRACES ARE FROM HEADER TO ROOF ONLY


SEE STEEL ELEVATIONS ON DRAWING S-701
FOR MORE INFORMATION.

'B
'C .PL
P8 .2
' '
'B
'C .PL
P1 .8
1' '
'B
'C .PL
P1 .8
1' '

F2
S-501

'B
'C .PL
P8 .2
' '

F1
S-501

'B
'C .PL
P7 .5
' '
'B
'C .PL
P1 .8
1' '
'B
'C .PL
P1 .8
1' '

F3
S-501

'GB1'

5'-9"

SIM.

'B
'C .PL
P8 .2
' '

SIM.

'B
'C .PL
P8 .2
' '

SIM.

'B
'C .PL
P8 .2
' '

SIM.

'GB2'

F1
'GB2'

30'-0"

SIM.

'B
'C .PL
P6 .2
' '

'B
'C .PL
P6 .2
' '

'GB2'

15M @ 10" TOP


x 12'-0" Lg.

'GB2'

'B
'C .PL
P6 .2
' '

35'-0"

100'-0"

ELEV. 100'-0"
GEODETIC: 727.65

UNLESS NOTED OTHERWISE TOP OF GRADE BEAM IS AT ELEVATION 100'-0". COORD. WITH FOUNDATIONS SECTIONS.
SPLICE BOTTOM REINFORCEMENT BARS OVER PILES AND TOP REINFORCEMENT AT MID-LENGTH BETWEEN PILES.
UNLESS NOTED OTHERWISE PROVIDE 24" LAPS.
ENSURE ALL GRADE BEAMS ARE TEMPORARILY BRACED AND LATERALLY SUPPORTED
DURING BACK-FILLING AND COMPACTION.
CONSTRUCTION JOINT SHALL BE HALFWAY BETWEEN PILES.

CL. OF HSS COL.

CL. OF HSS COL.

240'-0"
40'-0"

40'-0"

40'-0"

40'-0"

40'-0"

R10

R11

R12

SIM. R10

SIM. R12

R13

SIM. R10

SIM. R12

SIM. R11

SIM. R12

R13

S-603

S-603

S-603

S-603

S-603

S-603

S-603

S-603

S-603

S-603

S-603

10'-8"

1'-4"

16'-0"

12'-0"

12'-0"

16'-0"

12'-0"

12'-0"

16'-0"

12'-0"

12'-0"

16'-0"

SIM.

12'-0"

40'-0"

SIM. R12

SIM. R13

SIM. R11

SIM. R12

R10

S-603

S-603

S-603

S-603

S-603

12'-0"

16'-0"

12'-0"

12'-0"

16'-0"

10'-8"

1'-4"
3"

23 kips

23 kips

23 kips

23 kips

23 kips

10 kips

10 kips

10 kips

1'-4"

23 kips

3"

10 kips

3"

10 kips

3"

10 kips

3"

10 kips

3"

1'-4"

3"
10 kips

R8
S-602

23 kips
'C
1'

30" DP. O.W.S.J.

DO

DO

DO

DO

DO T.J.

DO

DO

DO

DO

DO

DO T.J.

DO

DO

DO

DO

DO

DO

DO T.J.

DO

DO

DO

DO

DO

DO T.J.

SIM.
16'-2"

129'-6"

129'-6"
DO

DO

DO

DO

DO

DO

DO T.J.

DO

DO

DO

DO

'C
1'

3"

W410x39

23 kips

W410x39

'C
W360x33 129'-6" 4'

129'-6"

'C
1'

W410x39
'C
1'

W410x39
'C
4'

W410x39
'C
1'

129'-6"
'C
1'

W410x39
'C
4'

W410x39
'C
1'

W410x39
'C
1'

W410x39
'C
4'

W410x39
'C
1'

129'-6"

'C
1'

W410x39

JOIST X-BRACING AS REQUIRED BY JOIST SUPPLIER - TYPICAL AS SHOWN

DO

30" DP. O.W.S.J.

W410x39
'C
4'

W410x39
'C
1'

W410x39
'C
1'

W410x39
'C
4'

W410x39
'C
1'

W410x39

L76x76x6.4 COLUMN BRACE


(AT U/S OF STEEL DECK)
TYPICAL AS SHOWN

23 kips

35'-0"

23 kips

SIM. S-602

129'-6"
'C
1'

W360x33 129'-6" 'C


4'

23 kips

3"
16'-2"

R8

W410x39

23 kips

CL. OF HSS COL.

CL. OF HSS COL.

5'-8"

5'-7"

5'-7"

6'-8"

6'-8"

6'-8"

6'-8"

6'-8"

6'-0"

5'-7"

5'-7"

5'-8"

5'-7"

5'-7"

6'-0"

6'-8"

6'-8"

6'-8"

6'-8"

6'-8"

'C
3'
'C
2'

6'-8"

6'-2"

6'-6"

6'-6"

6'-6"

R14

R16

R14

R14

R16

R14

R16

S-604

S-604

S-604

S-604

S-604

S-604

S-604

DO

DO

DO

DO

6'-6"

6'-6"

SIM.

DO T.J.

SIM.

DO

DO

DO

DO

SIM.

DO T.J.

SIM.

DO

DO

DO

DO

DO

DO

DO T.J.

DO

DO

DO

SIM.

DO

DO

DO

DO

DO

DO

DO

DO T.J.

DO

DO

L76x76x6.4 COLUMN BRACE


(AT U/S OF STEEL DECK)
TYPICAL AS SHOWN

129'-6"

R16

SIM.

17'-6"

W360x33
'C
3'

6'-8"

S-604

DO

DO

30" DP. O.W.S.J.

6'-0"

1'-4"

17'-6"

5'-7"

S-603

W360x33

5'-7"

W610x140

129'-6"

6'-0"

W610x113

'C
1'

6'-8"

JOIST X-BRACING AS REQUIRED BY JOIST SUPPLIER - TYPICAL AS SHOWN

'C 129'-6"
1'

17'-6"
35'-0"

6'-8"

W610x82

SIM.

R9

30" DP. O.W.S.J.

6'-8"

DO T.J.

6'-8"

W360x33

6'-8"

129'-6"

5'-4"

1'-4"

'C
3'

S-603

CANT.

DO

W610x113

CANT.

1'-2"

'C
3'

W610x82

5'-6"
12
8'
-1
0"

CANT.

'C
3'

R9

CANT.

5'-6"

'C
3'

W610x140

5'-6"

DO

'C
2'
'C
3'

CANT.

5'-6"

12
8'
-1
0"

12
8'
-1
0"

5'-6"

1'-2"

100'-0"

129'-6"

ROOF ACCESS HATCH


SEE DETAIL ON DWG. S-103
REFER TO ARCH. DWGS. FOR
ADDITIONAL INFORMATION

129'-6"

17'-6"

W360x33

JOIST X-BRACING AS REQUIRED BY JOIST SUPPLIER - TYPICAL AS SHOWN

SIM.

JOIST X-BRACING AS REQUIRED BY JOIST SUPPLIER - TYPICAL AS SHOWN

5'-7"

5'-7"

6'-0"

6'-8"

6'-8"

6'-8"

6'-8"

6'-8"

6'-8"

6'-2"

6'-6"

6'-6"

R15

R16

R15

R16

R15

R16

R15

R16

R15

R16

S-604

S-604

S-604

S-604

S-604

S-604

S-604

S-604

S-604

129'-6"

SIM.

SIM.

SIM.

'C
3'
'C
2'

6'-6"

6'-6"

10 kips

10 kips

10 kips

10 kips

18'-8"

1'-4"

SIM.

20'-0"

23 kips
20'-0"

20'-0"

20'-0"

R2

R3

R1

S-601

S-601

S-601

S-601

S-601

SIM.

SIM.

DO

DO

DO T.J.

DO

DO

DO T.J.

DO

DO

DO T.J.

20'-0"

20'-0"

SIM.

20'-0"

R1
S-601

TYPICAL FACTORED BEAM TO


COLUMN PASS-THROUGH FORCE
UNLESS NOTED OTHERWISE

SIM.

ROOF FRAMING PLAN


1/8"=1'-0"
1.

THIS PLAN SHALL BE READ WITH CRANE FRAMING PLAN AND PROPOSED FUTURE
MEZZANINE FRAMING PLAN ON DRAWING S-302.

2.

REFER TO DRAWINGS S-101 TO S-103 FOR GENERAL NOTES & TYPICAL DETAILS.

3.

REFER TO GENERAL NOTES ON DRAWING S-101 FOR ROOF DESIGN LOADS.

4.

STEEL DECK SLOPES. UNLESS NOTED OTHERWISE U/S STEEL DECK AT PERIMETER AND AT
HIGH POINTS OF BUILDING ARE AT ELEVATION OF 129'-6"; U/S STEEL DECK AT ROOF DRAINS
IS NOTED ON PLAN AS THUS: XX'-X"

NOTE: FOR HEADER AND STEEL GIRT SIZES AND LOCATIONS


REFER TO STEEL ELEVATIONS ON DRAWING S-701.

6.

UNLESS NOTED OTHERWISE ON PLAN, WALL BRACE SHOWN ON PLAN THUS:


SHALL CONSIST OF H.S.S. 127x127x6.4 WELDED ALL AROUND. TYPICAL U.N.O.

7.

HEADERS HAVE BEEN DESIGNED FOR L/240 DEFLECTION. WINDOW SUPPLIER TO BE


ADVISED ACCORDINGLY AND MAKE ALLOWANCE FOR HEADER DEFLECTION.

8.

ROOF DECK SHALL CONSIST OF 1 1/2" STEEL DECK U.N.O ON DRAWINGS. ACTUAL DECK
THICKNESS AND PROFILE TO BE DESIGNED BY THE DECK SUPPLIER. SEE GENERAL NOTES
AND SPECIFICATIONS FOR MORE INFORMATION.

9.

FRAME ROOF ACCESS HATCH WITH C200x17. FOR LOCATION SEE ARCH. DRAWINGS.

10.

PROVIDE 3/4 SAG RODS @ 7-0 O/C. MAX. TYP. ALL HEADERS ABOVE WINDOWS / DOORS.
TYPICAL UNLESS NOTED OTHERWISE ON DRAWINGS.

11.

ALL HEADERS AND COLUMNS TO COME WITH 3/8" CAP PLATES AND TO BE WELDED ALL
AROUND TO STEEL SUPPORTS ON EACH END.

12.

ALLOW FOR ADDITIONAL WEIGHTS DUE TO MECHANICAL UNITS AND ASSOCIATED SNOW
PILING. CONTRACTOR TO VERIFY QUANTITY, LOCATIONS, WEIGHTS AND SIZES OF ALL
MECHANICAL UNITS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS PRIOR TO
FABRICATION.

13.

SLOPE STRUCTURE TO DRAIN. ENSURE DRAINS REMAIN CLEAN FROM DEBRIS AND/OR ICE
WHILE IN USE. PROVIDE ADEQUATE NUMBER OF SCUPPERS. MAINTENANCE OF DRAINS
SHALL BE PERFORMED FOR THE LIFE OF THE STRUCTURE.
15'-0"

EXTEND JOIST BRIDGING TO END BAYS.

COLUMN SCHEDULE 'C'


TYPE

SIZE

REMARK

'C1'

HSS 203x203x8

350W STEEL

'C2'

HSS 203x203x9.5

350W STEEL

'C3'

W360x162

350W STEEL

'C4'

W360x147

350W STEEL

SIM.

R7
S-602

MIRR.

10 kips

20'-0"

10 kips

R2

S-601

S-601

W410x39

10 kips

20'-0"

R3

129'-6"

L76x76x6.4 DECK ANGLE AT


PERIMETER. TYPICAL.
REFER TO ROOF SECTIONS
FOR DECK SUPPORT.

S-602

SIM.

R5
S-602

MIRR.

R4
S-601

CL. OF HSS COL.


10 kips

18'-8"

1'-4"

R1
S-601

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

COORD. ROOF SLOPES WITH ARCH./MECH. DRAWINGS.


5.

23 kips

W410x39

'C
2'

129'-6"
23 kips

20'-0"

THESE BRACES ARE FROM HEADER TO ROOF ONLY


SEE STEEL ELEVATIONS ON DRAWING S-701
FOR MORE INFORMATION.

W410x39

'C
2'

W410x39

'C
2'

W410x39

'C
2'

'C
2'

W410x39

23 kips

R3
SIM.

129'-6"

23 kips

R1
SIM.

W410x39

'C
2'

129'-6"

23 kips

W410x39

'C
2'

W410x39

'C
2'

W410x39

'C
2'

129'-6"

W410x39

'C
2'

129'-6"

'C
2'

W410x39

'C
2'

'C
2'

23 kips

129'-6"

L64x64x6.4 BEAM BOTTOM


FLANGE BRACE
TYPICAL AS SHOWN

1'-4"

R6

DO

DO

DO

DO

DO

DO

DO

SIM.

DO T.J.

SIM.

DO

DO T.J.

DO

DO

SIM.

DO T.J.

DO

DO

DO

DO

DO

DO

DO T.J.

DO

DO

DO T.J.

DO

SIM.

129'-6"

SIM.

6'-6"

9'-8"

5'-8"

19'-0"

5'-7"

1'-4"

5'-7"

23 kips

6'-0"

R9

23 kips

6'-8"

W360x33

6'-8"

12
8'
-1
0"

12
8'
-1
0"

6'-8"

JOIST X-BRACING AS REQUIRED BY JOIST SUPPLIER - TYPICAL AS SHOWN

CL. OF HSS COL.


1'-4"

6'-8"

SIM.

23 kips

19'-0"

W360x33

30" DP. O.W.S.J.

'C
1'

23 kips

30'-0"

R4

6'-8"

S-604

SIM.

S-602

S-601

6'-8"

R16

JOIST X-BRACING AS REQUIRED BY JOIST SUPPLIER - TYPICAL AS SHOWN

S-602

6'-0"

S-602

S-603

W360x33

5'-7"

'C
1'

5'-7"

30" DP. O.W.S.J.

5'-8"

DO

5'-7"

W610x140

DO

5'-7"

'C
3'

6'-0"

W610x113

S-604

R6

R5

6'-8"

W610x82
'C
3'

6'-8"

W610x113
'C
3'

6'-8"

W610x82
'C
3'

6'-8"

'C
3'

6'-8"

W360x33

S-602

W610x140

5'-4"

23 kips

R7

9'-8"

1'-4"

12
8'
-1
0"

1'-2"
'C
2'
'C
3'

1'-2"

17'-6"

W360x33

129'-6"

ROOF PAVERS SHOWN


ARE BASED ON THE
ASSUMED LOCATION
OF ROOF TOP UNITS.
TYPICAL

129'-6"

17'-6"

S-602

W360x33

R8
R8

ROOF TOP UNIT PLAN

70 psf

34 psf

1/16"=1'-0"
1.
2.

ALLOW FOR 1 (1500 Ibs) ROOF TOP UNIT AND ITS ASSOCIATED
SNOW PILING PER EACH BAY IN HATCHED AREAS SHOWN.
JOISTS TO BE PAINTED.

10'-0"

SNOW PILING AROUND RTU


REFER TO MECH. / ARCH. DWGS.
FOR LOCATION AND NUMBER OF
UNITS

R12

R13

S-603

S-603

CENTER OF
HSS BRACE
AT GRID A

R11
S-603

1'-10"

R10
S-603

HSS 152x152x6.4
(BRACE AT CRANE
BEAM LEVEL)
TYPICAL AS SHOWN

HSS 203x203x8 OUTRIGGER AT HSS


COLUMNS FOR BRACE SUPPORT
TYPICAL AT GRID A

CRANE BEAM BY SUPPLIER

R8

FUTURE HSS 254x254x13 CRANE STOP


COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 4. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

FUTURE 10 TON CRANE

FUTURE HSS 254x254x13 CRANE STOP


COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 3. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

SIM. S-602
HSS 203x203x8 OUTRIGGER
FOR BRACE SUPPORT
TYPICAL U.N.O.

FUTURE HSS 254x254x13 CRANE STOP


COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 3. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

2'-2"
CENTER OF
HSS BRACE
AT GRID 1

FUTURE HSS 254x254x13 CRANE STOP


COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 4. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

R8

FUTURE HSS 254x254x13 CRANE STOP


COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 5. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

2'-2"

HSS 152x152x6.4

HSS 203x203x8 OUTRIGGER


FOR BRACE SUPPORT
TYPICAL U.N.O.

FUTURE HSS 254x254x13 CRANE STOP


COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 5. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

SIM.
CRANE BEAM BY SUPPLIER

HSS 152x152x6.4

HSS 152x152x6.4

S-602

CENTER OF
HSS BRACE
AT GRID 7

CRANE BEAM BY SUPPLIER


HSS 152x152x6.4 (BRACE AT CRANE BEAM LEVEL)

SIM.

CRANE BEAM BY SUPPLIER

HSS 152x152x6.4

HSS 152x152x6.4 (BRACE AT CRANE BEAM LEVEL)

R9
S-603

R9
S-603

CRANE BEAM BY SUPPLIER

R16

R14

S-604

S-604

CRANE BEAM BY SUPPLIER

HSS 152x152x6.4
(BRACE AT CRANE
BEAM LEVEL)
TYPICAL AS SHOWN

FUTURE 10 TON CRANE

HSS 152x152x6.4
(BRACE AT CRANE
BEAM LEVEL)
TYPICAL AS SHOWN

HSS 203x203x8 OUTRIGGER


FOR BRACE SUPPORT
TYPICAL U.N.O.
FUTURE HSS 254x254x13 CRANE STOP
COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 3. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

R8
S-602

L76x76x6.4 BRACES
AT COLUMNS
TYPICAL AS SHOWN

HSS 203x203x8 OUTRIGGER


FOR BRACE SUPPORT
TYPICAL U.N.O.
FUTURE HSS 254x254x13 CRANE STOP
COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 4. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

SIM.

R8

FUTURE HSS 254x254x13 CRANE STOP


COLUMN REQUIRED AT END OF CRANE
RUN IF CRANE IS TERMINATED AT
GRIDLINE 5. PROVIDE HSS 254x254x8
TIE-BACK FROM STOP COLUMN TO
(CRANE) SUPPORT COLUMN AT CRANE
BEAM AND BRACE ELEVATION.

S-602

SIM.
CRANE BEAM BY SUPPLIER

CRANE BEAM BY SUPPLIER

R9
S-603

HSS 152x152x6.4 (BRACE AT CRANE BEAM LEVEL)

HSS 152x152x6.4

HSS 152x152x6.4

HSS 152x152x6.4

HSS 152x152x6.4

HSS 152x152x6.4 (BRACE AT CRANE BEAM LEVEL)

R16

R15

S-604

S-604

SIM.

ASSUMED FUTURE CRANE FRAMING PLAN


(CRANE RUN IS FROM GRID 1 TO 7)

IMPORTANT
ALL CRANE RELATED INFORMATION SHOWN HAS BEEN
ASSUMED AND MUST BE CONFIRMED WITH THE CRANE
SUPPLIER PRIOR TO COMMENCING WITH WORK.

1/8"=1'-0"

ALL W-COLUMNS HAVE BEEN DESIGNED FOR FUTURE 10 TON CRANE TO BE ATTACHED WITH A STEEL
CORBEL AT THE ASSUMED ELEVATION SHOWN ON STEEL SECTIONS ON DRAWINGS S-602 TO S-604.
CENTERLINE OF CRANE BEAM TO BE NO MORE THAN 10" FROM FACE OF W-COLUMN.
IF CRANE IS PARTIALLY INSTALLED AND DOESN'T RUN THE WHOLE LENGTH OF BUILDING, HSS
254x254x13 STOP COLUMN MUST BE INSTALLED AT THE END OF THE CRANE RUN (GRID 3, 4 OR 5).
PROVIDE SLIP CONNECTION FOR CRANE STOP COLUMN AT ROOF. TYPICAL.

SIM.

ALLOWED FUTURE MEZZANINE FRAMING PLAN


1/8"=1'-0"
1.

COORD. EXTENT OF MEZZANINE WITH ARCHITECTURAL DRAWINGS.

2.

T/O FUTURE MEZZANINE FLOOR = REFER TO ARCHITECTURAL DRAWINGS.

3.

MEZZANINE HAS BEEN DESIGNED FOR: L.L. = 100 psf

4.

ASSUMED FLOOR TO BE 5" STEEL DECK AND TOPPING.

N
LU
M
C
O
FU
TU
R
E

FUTURE STEEL BEAM


TYPICAL AS SHOWN

FUTURE O.W.S.J.

@ 48" O/C
FUTURE STEEL BEAM
TYPICAL AS SHOWN

N
C
O
FU
TU
R
E

C
O
FU
TU
R
E

REFER TO PILE LAYOUT PLAN


FOR ADDITIONAL PILES AT
FUTURE COLUMNS. TYPICAL.

UNLESS NOTED OTHERWISE


ALL COLUMNS ARE CURRENT
AND PART OF ORIGINAL BASE
BUILDING DESIGN AS SHOWN
ON DRAWING S-301.

LU
M

N
LU
M

N
LU
M
FU
TU
R
E

C
O

LU
M
C
O
FU
TU
R
E

FU
TU
R
E

C
O

LU
M

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

7 psf

7 psf

7 psf

7 psf

7 psf

7 psf
7 psf

7 psf

WATER PONDING PLAN


1/8"=1'-0"
1.
2.

7 psf

7 psf
7 psf

7 psf

TYPICAL

7 psf

sf
p
9

7 psf

7 psf

7 psf

sf
p
9

7 psf

sf
p
9

10'-0"

7 psf

sf
p
9

7 psf

sf
p
9

7 psf

sf
p
9

LOADS SHOWN ARE SERVICE LOADS AND HAVE


INCORPORATED THE IMPORTANCE FACTOR.
SLOPE STRUCTURE TO DRAIN. ENSURE
DRAINS REMAIN CLEAN FROM DEBRIS AND/OR
ICE WHILE IN USE. PROVIDE ADEQUATE
NUMBER OF SCUPPERS. MAINTENANCE OF
DRAINS SHALL BE PERFORMED FOR THE LIFE
OF THE STRUCTURE.

FOR SNOW PILING PLAN


REFER TO ROOF TOP UNIT
PLAN ON DRAWING S-301.

WIND UPLIFT PLAN


1/8"=1'-0"
1.

LOADS SHOWN ARE SERVICE LOADS AND HAVE


INCORPORATED THE IMPORTANCE FACTOR.

10'-0"

10'-0"

TYPICAL

TYPICAL

TYPICAL

10'-0"

-22 psf

-55 psf

-28 psf

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

1'-2"

6"

6"

1'-2"

6"

1'-2"

9"

5"
4"
4 1/2"

2'-0"
11"

3"

VERTICAL CHANNEL
EACH SIDE OF MAN
DOOR BEHIND
PRECAST PANEL WALL
SEE STEEL
ELEVATIONS ON
DRAWING S-701

8"

7"

7"

3"

2" 3"

5"

10"

5"

5"

10"

ANCHOR BOLT DETAILS

('B.PL.1') DETAIL

('B.PL.2') DETAIL

('B.PL.3') DETAIL

('B.PL.4') DETAIL

('B.PL.5') DETAIL

('B.PL.6') DETAIL

16"x16"x3/4" BASE PLATE


C/W 4-3/4" ANCHOR BOLTS
ON 1" NON-SHRINK
EXPANDABLE GROUT

16"x24"x1 1/4" BASE PLATE


C/W 5-1 1/4" ANCHOR BOLTS
ON 1" NON-SHRINK
EXPANDABLE GROUT

16"x24"x1 1/4" BASE PLATE


C/W 9-1 1/4" ANCHOR BOLTS
ON 1" NON-SHRINK
EXPANDABLE GROUT

16"x16"x3/4" BASE PLATE


C/W 4-3/4" ANCHOR BOLTS
ON 1" NON-SHRINK
EXPANDABLE GROUT

40"x28"x1 1/4" BASE PLATE


C/W 8-1 1/4" ANCHOR BOLTS
ON 1" NON-SHRINK
EXPANDABLE GROUT

AT THIS PLATE ANCHOR BOLTS


SHALL BE EMBED. 30" INTO
PIER BELOW.

9"

10"

9"

FUTURE HSS 254x254x13


CRANE STOP COLUMN.
(AS REQUIRED)

('B.PL.7') DETAIL

('B.PL.8') DETAIL

40"x24"x1 1/4" BASE PLATE


C/W 8-1 1/4" ANCHOR BOLTS
ON 1" NON-SHRINK
EXPANDABLE GROUT

9"x6"x3/4" BASE PLATE


C/W 2-3/4" ANCHOR BOLTS
ON 1" NON-SHRINK
EXPANDABLE GROUT

2'-8"

10"

1'-10"

1'-6"
3'-0"

1'-4"

1'-10"

3'-2"

2'-8"

1'-7"

2'-4"

1'-0"

1'-0"

1'-0"

1'-6"

10M @ 6" TIES

10"

2'-8"

CONCRETE PIER
R/W 12-15M VERTICAL
10M @ 12" TIES
(3 TIES MINIMUM)

4'-0"

5'-0"

7-15M TOP AND


7-25M BOTTOM
WITH 24" HOOKS

3'-6"

EXTEND GRADE BEAM


REINF. THROUGH PIER
TYPICAL

1'-4"

1'-7"

MIRRORED

1'-4"

SHADING DENOTES
TOP OF PIER AT MAIN
FLOOR ELEVATION.
TYPICAL AS SHOWN

10"

1'-3"

1'-0"

1'-3"

MIRRORED

10"

CONC. PILE BELOW


PIER - SEE PLAN
ON DWG. S-201
TYPICAL AS SHOWN

THIS PLATE IS AT VERTICAL


CHANNELS EACH SIDE OF
DOORS AT GRIDLINE D

AT THIS PLATE ANCHOR BOLTS


SHALL BE EMBED. 30" INTO
PIER BELOW.

NOTE: AT BRACED BAYS PROVIDE 1 1/4" A.BOLTS WITH 1 1/4" THICK BASE PLATE.

MIRRORED
2'-6"

6"

5"

1 1/4" ANCHOR BOLT

16"x28"x1 1/4" BASE PLATE


C/W 6-1 1/4" ANCHOR BOLTS
ON 1" NON-SHRINK
EXPANDABLE GROUT

6"

2'-0"

3/4" ANCHOR BOLT

6"

3"

1'-0"

3" 2"

5"

1'-0"

5"

3"

5"

U.N.O. U/S OF CONCRETE PIER IS TO MATCH


U/S OF ADJACENT GRADE BEAM.
CORNER BARS NOT SHOWN FOR CLARITY.
SEE TYPICAL DETAILS FOR CORNER BARS.
RECESS TOP OF PIER FOR SLAB THICKNESS
UNLESS NOTED OTHERWISE.
RECESS IN PIER IS SHOWN AS THUS:
GROUT ALL POCKETS (RECESSES) ONCE
COLUMN IS INSTALLED.
EXTEND CONCRETE GRADE BEAM
HORIZONTAL REINF. THROUGH CONC. PIER
U.N.O. ANCHOR BOLTS SHALL BE MIN. 3 1/2"
FROM EDGE OF PIERS AND/OR GRADE BEAMS.
COORD. BOLT LOCATIONS WITH PIER
REINFORCEMENT TO AVOID INTERFERENCE.

3"

1'-4"
3"

3" 3"

3"
5"

8"
11"

6"
3"

5 1/2"
9"

10 1/2"

3"

5 1/2"

3"

1'-2"

3"

4"

10 1/2"

1'-4"

2'-0"
1'-0"

1'-4"

1'-1"

2'-0"

9"

1'-0"

8"

8"
1'-0"

11"

1'-2"

1'-0"

6"

4 1/2"

3"

4"

1'-1"

6"

2"

3"

6"

1'-2"

9"

1'-2"

3'-4"

1'-2"

5"

3"

8"

3'-4"

1'-2"

8"

2'-4"

2'-4"

8"

10 1/2"

1'-4"

11"

1'-2"
2'-4"

B.PL.1
B.PL.6

30"

1'-3"

1'-3"

8"

5 1/2"

8"

1'-4"

TYP.

4"

TYP.

3"

8"

1'-4"

3"

1'-4"

1'-0"

2'-0"
COLUMN BASE PLATE
SEE FOUNDATION PLAN
ON DWG. S-202
FOR BASE PLATE
DETAIL REFER TO
DRAWING S-401
TYPICAL

10"

HATCH DENOTES TOP OF PIER


RECESSED BELOW SLAB.
SEE PLAN AND SECTIONS.
TYPICAL AS SHOWN

2'-4"

1'-4"

'CP3' PIER PLAN DETAIL


3/4"=1'-0"

S-202

3'-2"

10'-0"

1'-4"

1'-9"

CONCRETE PIER
R/W 12-15M VERTICAL
10M @ 12" TIES
(3 TIES MINIMUM)
1'-9"

1'-0"
1'-7"

2'-4"

3'-2"

10M @ 8"
HORIZONTAL
EACH SIDE
(SEE SECTION
FOR ADDITIONAL
INFORMATION)

5'-0"

1'-7"

1'-7"

4'-0"

1'-7"

10"

1'-0"

1'-7"

W-COLUMN
SEE ROOF PLAN
ON DWG. S-301
TYPICAL

1'-2"

1'-0"

T/O CONC. PIER


ELEV. 99'-0"

1'-0"

CONCRETE PIER
R/W 24-15M VERTICAL
(OR 16-20M VERTICAL)
2 SETS OF 10M @ 12" TIES
(3 TIES MINIMUM)

1'-0"

1'-4"

CONCRETE PIER
R/W 16-15M VERTICAL
2 SETS OF
10M @ 12" TIES
(3 TIES MINIMUM)

1'-0"

1'-4"

CONCRETE PIER
R/W 24-15M VERTICAL
(OR 16-20M VERT.)
2 SETS OF
10M @ 12" TIES
(3 TIES MINIMUM)

1'-0"

2'-0"

'CP4' PIER PLAN DETAIL


'CP1' PIER PLAN DETAIL

'CP2' PIER PLAN DETAIL

3/4"=1'-0"

3/4"=1'-0"

S-202

3/4"=1'-0"

S-202

S-202

'CP5' PIER PLAN DETAIL

'CP6' PIER PLAN DETAIL

3/4"=1'-0"

3/4"=1'-0"

S-202

S-202

42" DEEP PIER

1'-0"

MIRRORED

6"

10"

CONC. PILE BELOW


PIER - SEE PLAN
ON DWG. S-201
TYPICAL AS SHOWN

3'-6"
1'-10"

1'-9"

1'-9"

2'-4"
4'-0"

5'-0"

1'-4"

10"

1" MIN.

CONFIRM WITH ARCH. DWGS.


FOR SIZE AND LOCATION

1'-9"

COLUMN BASE PLATE


SEE FOUNDATION PLAN
ON DWG. S-202
FOR BASE PLATE
DETAIL REFER TO
DRAWING S-401
TYPICAL

12"x20" CONCRETE PIER


R/W 4-15M VERTICAL
10M @ 12" TIES
(3 TIES MINIMUM)

1'-9"
3'-6"

10'-0"

1'-4"

1'-0"

1'-7"

W-COLUMN
SEE ROOF PLAN
ON DWG. S-301
TYPICAL

EXTEND GRADE BEAM


REINF. THROUGH PIER
TYPICAL

EXTEND GRADE BEAM


REINF. THROUGH PIER
TYPICAL

'CP7' PIER PLAN DETAIL

'CP8' PIER PLAN DETAIL

3/4"=1'-0"

3/4"=1'-0"

S-202

T/O CONC. PIER


ELEV. 99'-0"

S-202

'CP9' PIER PLAN DETAIL


3/4"=1'-0"
42" DEEP PIER

1'-7"
1'-9"

SIZE AND LOCATION OF MAN DOORS


MUST BE CONFIRMED/COORDINATED
WITH ARCHITECTURAL DRAWINGS
PRIOR TO COMMENCING WITH
FORMING OF THIS PIER

1'-9"

1'-0"

1'-4"

CONCRETE PIER
R/W 20-20M VERTICAL
2 SETS OF
10M @ 12" TIES
(3 TIES MINIMUM)

10M @ 8"
HORIZONTAL
EACH SIDE
(SEE SECTION
FOR ADDITIONAL
INFORMATION)

5'-0"

1'-4"

1'-4"

4'-0"

1'-4"

CONCRETE PIER
R/W 12-15M VERT.
10M @ 12" TIES
(3 TIES MINIMUM)

6"

10"

3'-0" (MAN DOOR)

3'-2"

1'-10"
2'-8"

2'-8"

1'-10"
10"

1'-4"

10-15M TOP AND


10-25M BOTTOM
WITH 24" HOOKS

10M @ 6" TIES

1'-0"

6"

1'-7"

1'-0"

10"

1'-0"

1" MIN.

CONCRETE PIER
R/W 16-15M VERTICAL
10M @ 12" TIES
(3 TIES MINIMUM)

2'-2"

1'-8"

2'-0"
1'-0"

6"

10"

2'-8"

1'-0"

S-202

'CP10' PIER PLAN DETAIL

'CP11' PIER PLAN DETAIL

3/4"=1'-0"

3/4"=1'-0"

S-202

S-202

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

EMBEDED ANGLE/PLATE BY
PRECAST PANEL SUPPLIER
TYPICAL AT ALL SIMILAR
LOCATIONS

REFER TO ARCH. DWGS.


FOR HEIGHT AND EXTENT
OF PRECAST PANELS.
TYPICAL

1'-4"

WINDOW GLAZING
REFER TO ARCH. DWGS.
TYPICAL

T/O PRECAST PANEL


SEE ARCH. DWGS.

1'-4"

C-CHANNEL REFER TO
STEEL ELEVATIONS ON S-701
COORD. WITH PRECAST
PANEL SUPPLIER IF THIS
CHANNEL IS REQUIRED

1'-2"

C-CHANNEL REFER TO
STEEL ELEVATIONS ON S-701
COORD. WITH PRECAST
PANEL SUPPLIER IF THIS
CHANNEL IS REQUIRED

10"

6-15M x 6'-0" LG. DOWELS


TYPICAL AT ALL
8"
PERIMETER PILES

PROVIDE 4" DYNAVOID


(40144) OR EQUIVALENT
UNDER PIERS AROUND
PILES TYPICAL

CONC. PILE
SEE PLAN

CONC. PILE
SEE PLAN

STEEL BASE PLATE


SEE FOUNDATION PLAN
C/W 1" NON-SHRINK
EXPANDABLE GROUT
TYPICAL

2'-6"

SEE

PLAN

CONC. SLAB ON GRADE


SEE PLAN

CONC. SLAB ON GRADE


SEE PLAN

EXTEND GRADE BEAM


TOP AND BOT. REINF.
THROUGH PIER - TYP.

CONC. PIER
SEE PLAN

CONCRETE PIER AT VERTICAL


C-CHANNEL BEYOND
REFER TO FOUNDATION PLAN
TYPICAL AT DOORWAYS

T/O CONC. PILE


ELEV. SEE PLAN

VOID FORM
SEE SECT. F1

SEE PLAN

VOID FORM - SEE SECT. F2

10"

DOWELS
SEE SECT. F2
CONC. PILE
SEE PLAN

6'-0"
1'-9"

1'-4"

SECTION

SECTION

F1

3/4"=1'-0"

3/4"=1'-0"

S-201/S-202

SECTION

F2

3/4"=1'-0"

S-201/S-202

SECTION

F3
S-201/S-202

SEE ARCH. DWGS.

DWGS.

SEE ARCH.

SLOPE AS PER

PRECAST WALL PANEL


BY PRECAST SUPPLIER.
REFER TO ARCH. DWGS.
FOR ADDITIONAL
INFORMATION. TYPICAL.

PRECAST PANEL
CONNECTION
SEE SECT. F1

CONCRETE APRON
SEE FOUNDATION
PLAN - TYPICAL

DOWELS - SEE SECT. F1

SLOPE AS PER

1'-0"

CONC. GRADE BEAM


SEE PLAN

3'-6"

CONC. PIER
SEE PLAN

PANEL CONNECTION
SEE SECT. F1 ON
THIS DRAWING
STEEL BASE PLATE
SEE FOUNDATION PLAN
C/W 1" NON-SHRINK
EXPANDABLE GROUT
TYPICAL

4" 60 Ib/in RIGID INSULATION


TYPICAL AT CONCRETE APRON
FOR 8'-0" NEXT TO BUILDING

VOID FORM
SEE SECT. F1

SEE

PLAN

SEE
CONC. SLAB ON GRADE
SEE PLAN

2'-6"

T/O CONC. PIER


ELEV. 99'-0"

SLAB THICKENING
AT EDGE OF APRON
SEE FOUNDATION PLAN
R/W 2-15M CONT.
TYPICAL

H.S.S. COLUMN
SEE PLAN

ARCH. DWGS.

1'-0"

SEE

PLAN

ARCH. DWGS.

PLAN

SEE

T/O CONC. SLAB


ELEV. 100'-0"

CONCRETE APRON
SEE FOUNDATION
PLAN - TYPICAL

PRECAST WALL PANEL


BY PRECAST SUPPLIER.
REFER TO ARCH. DWGS.
FOR ADDITIONAL
INFORMATION. TYPICAL.

SEE ARCH. DWGS.

SEE FOUNDATION PLAN


COORD. WITH ARCH. DWGS.

CONC. SLAB ON GRADE


SEE PLAN

S-201/S-202

1'-4"

W-COLUMN
SEE PLAN

ADDITIONAL TOP BARS


SEE FOUNDATION PLAN

F4

3/4"=1'-0"

REFER TO ARCH. DWGS.


FOR HEIGHT AND EXTENT
OF PRECAST PANELS.
TYPICAL

STEEL BASE PLATE


SEE FOUNDATION PLAN
C/W 1" NON-SHRINK
EXPANDABLE GROUT
TYPICAL

PLAN

SLOPE AS PER

SEE

4-15M x 48" LG. DOWELS


TYPICAL ALL SIMILAR
LOCATIONS U.N.O.

SEE ARCH. DWGS.

SEE ARCH. DWGS.

DWGS.

14"

CONC. GRADE BEAM


SEE PLAN

T/O CONC. PILE


ELEV. SEE PLAN

PROVIDE 4" DYNAVOID


(40144) OR EQUIVALENT
UNDER GRADE BEAM
BETWEEN PILES TYPICAL

PANEL CONNECTION
SEE SECT. F1 ON
THIS DRAWING

15M @ 10" DOWELS


TYPICAL AT DOORWAYS
42"

W-COLUMN
SEE PLAN

ARCH. DWGS.

PROVIDE 4" DYNAVOID


(40144) OR EQUIVALENT
TYPICAL AT STRUCT.
SLAB LOCATIONS

8"

CONC. PIER
SEE PLAN

HSS COLUMN
SEE PLAN

SEE SECT. F6
FOR CONT.

CONC. SLAB ON GRADE


SEE PLAN
EXTEND GRADE BEAM
TOP AND BOT. REINF.
THROUGH PIER - TYP.

CONC. PIER
SEE PLAN

T/O CONC. PILE


ELEV. SEE PLAN
VOID FORM SEE SECT. F2

10"

PLAN

SLOPE AS PER

2'-0"

2'-6"

EXTEND GRADE BEAM


TOP AND BOT. REINF.
THROUGH PIER - TYP.

EXTERIOR CONC. SLAB


SEE PLAN

PRECAST WALL PANEL


BY PRECAST SUPPLIER.
REFER TO ARCH. DWGS.
FOR ADDITIONAL
INFORMATION. TYPICAL.

ARCH. DWGS.

CONC. SLAB ON GRADE


SEE PLAN

CONC. GRADE BEAM


SEE PLAN

4" 40 Ib/in RIGID INSULATION


TYPICAL BELOW SIDEWALK
NEXT TO BUILDING.

SEE ARCH.

STEEL BASE PLATE


SEE FOUNDATION PLAN
C/W 1" NON-SHRINK
EXPANDABLE GROUT
TYPICAL

CONC. SLAB ON GRADE


SEE PLAN

1'-0"

COORD. WITH ARCH. DWGS.

PANEL CONNECTION
SEE SECT. F1 ON
THIS DRAWING

ARCH. DWGS.

SEE
1'-0"

45

SLAB THICKENING AT
EDGE OF SIDEWALK
SEE TYPICAL DETAIL
ON DRAWING S102
TYPICAL

SEE FOUNDATION PLAN

SEE

ARCH. DWGS.

T/O CONC. SLAB


ELEV. 100'-0"

SLOPE AS PER

14"

VERTICAL C-CHANNEL BEYOND


REFER TO FOUNDATION PLAN
AND STEEL ELEVATIONS
TYPICAL AT DOORWAYS

PLAN

10M @ 10" DOWELS


TYPICAL ALL AROUND
PERIMETER OF BUILDING
42"

H.S.S. COLUMN
SEE PLAN

SEE ARCH. DWGS.

SLOPE AS PER

CANTILEVERED
PRECAST WALL PANEL
BY PRECAST SUPPLIER.
REFER TO ARCH. DWGS.
FOR ADDITIONAL
INFORMATION. TYPICAL.

PLAN

CONCRETE SIDEWALK
SEE TYPICAL DETAIL
ON DRAWING S102
TYPICAL

SEE ARCH. DWGS.

ARCH./CIVIL DWGS.

REFER TO

PRECAST WALL PANEL BEYOND


25M x 24" Lg. AS REQUIRED
BY PRECAST SUPPLIER
PROVIDE MIN. 2 INSERTS
PER PANEL (1 AT EACH END)

CANTILEVERED
PRECAST WALL PANEL
BY PRECAST SUPPLIER.
REFER TO ARCH. DWGS.
FOR ADDITIONAL
INFORMATION. TYPICAL.

DOWELS
SEE SECT. F2
CONC. PILE
SEE PLAN

T/O CONC. PILE


ELEV. 95'-6"

1'-4"

VOID FORM - SEE SECT. F2


6-20M x 60" Lg. DOWELS WITH
8" HOOKS AND 30" EMBED.
INTO PIER ABOVE TYPICAL
AT ALL INTERIOR PILES

CONC. PILE - SEE PLAN


EXTEND PILE VERT. 30"
INTO PIER ABOVE AND
PROVIDE 6" HOOKS.
TYPICAL AT ALL
INTERIOR PILES U.N.O.
1'-0"

4'-0"

SECTION
3/4"=1'-0"

4'-0"

1'-0"

10'-0"

SECTION
3/4"=1'-0"

F5
S-201/S-202

1'-7"

OVERHEAD DOOR BY SUPPLIER


REFER TO ARCH. DWGS. FOR
SIZE AND LOCATION
SLOPE CONCRETE
AS PER ARCH. DWGS.

CONCRETE APRON
SEE FOUNDATION
PLAN - TYPICAL

TOP REINF.
SEE PLAN

SLOPE AS PER

W-COLUMN
SEE PLAN
PANEL CONNECTION
SEE SECT. F1 ON
THIS DRAWING
STEEL BASE PLATE
SEE FOUNDATION PLAN
C/W 1" NON-SHRINK
EXPANDABLE GROUT
TYPICAL

CONC. SLAB ON GRADE


SEE PLAN
CONC. GRADE BEAM
SEE PLAN

CONCRETE APRON
SEE FOUNDATION
PLAN - TYPICAL

VOID FORM
SEE SECT. F1

SEE

SEE

SEE SECT. F6
FOR CONT.

PLAN

ARCH. DWGS.

T/O CONC. SLAB


ELEV. 100'-0"

SEE SECT. F6
FOR CONT.

CONC. SLAB ON GRADE


SEE PLAN
EXTEND GRADE BEAM
TOP AND BOT. REINF.
THROUGH PIER - TYP.

CONC. PIER
SEE PLAN

T/O CONC. PILE


ELEV. SEE PLAN
VOID FORM SEE SECT. F2

10"

DOWELS
SEE SECT. F2
CONC. PILE
SEE PLAN

1'-7"

SECTION
3/4"=1'-0"

F8
S-201/S-202

SECTION
3/4"=1'-0"

F9
S-201/S-202

PLAN

PRECAST WALL PANEL


BY PRECAST SUPPLIER.
REFER TO ARCH. DWGS.
FOR ADDITIONAL
INFORMATION. TYPICAL.

SEE ARCH. DWGS.

REFER TO STEEL SECTIONS


ON DRAWING S-603 FOR
DOOR JAMB DETAILS.
COORD. DETAILS WITH
ARCH. DWGS. TYPICAL

F6
S-201/S-202

SECTION
3/4"=1'-0"

F7
S-201/S-202

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

1
1'-4"

1"

1'-4"
6" STEEL STUD WALL BEHIND
CANTILEVERED INSULATED
PANEL WALL TO BE DESIGNED
AND SUPPLIED BY STEEL
STUD SUPPLIER - TYPICAL

3"

T/O PARAPET
SEE ARCH. DWGS.
CANTILEVERED INSULATED PANEL
PARAPETS TO BE REVIEWED AND
CONFIRMED BY THE INSULATED PANEL
SUPPLIER. ADVISE ENGINEER ON RECORD
IF ADDITIONAL SUPPORTS ARE REQUIRED.
TYPICAL AT ALL SIMILAR LOCATIONS
U/S STEEL DECK
(AT HIGH POINT)
ELEV. 129'-6"

CONT. STEEL ANGLE


SEE PLAN

11 1/2"
1 1/2" STEEL DECK
SEE PLAN

1'-4"

3"

1"

11 1/2"

1'-4"

3"

1"

STEEL STUD PARAPET WALL


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

STEEL STUD PARAPET WALL


SEE SECT. R1

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

11 1/2"

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

1 1/2" STEEL DECK - SEE PLAN

45

CANTILEVER JOIST
TOP CHORD AS
REQUIRED - TYPICAL

CANTILEVER JOIST
TOP CHORD AS
REQUIRED - TYPICAL

STEEL BEAM
SEE PLAN

STEEL BEAM
SEE PLAN

11 1/2"

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1
1 1/2" STEEL DECK - SEE PLAN

C150x12 OUTRIGGERS
AT 5'-0" MAX.
PROVIDE MOMENT
CONNECTION FOR
Mf = 6 kN.m
TYPICAL ALL SIMILAR
LOCATIONS

BEAM BOTTOM
FLANGE BRACE
SEE PLAN

STEEL BEAM
SEE PLAN

STEEL BEAM
SEE PLAN

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

3"

STEEL STUD PARAPET WALL


SEE SECT. R1

1 1/2" STEEL DECK - SEE PLAN

CONT. BLOCKING WITHIN


DECK FLUTES AT
PLYWOOD STRIP.
TYPICAL.
CANTILEVER JOIST
TOP CHORD AS
REQUIRED - TYPICAL

1"

5/8" x 12" WIDE T&G D.FIR CONT. PLYWOOD


STRIP AT U/S OF PARAPET WALL
TYPICAL UNLESS NOTED OTHERWISE (U.N.O.)
Ps = 1 kip
TYPICAL
U.N.O.

COORD. EDGE OF DECK LOCATION


WITH ARCH. DWGS. TYPICAL

STEEL JOIST
SEE PLAN
BEAM BOTTOM
FLANGE BRACE
SEE PLAN

STEEL TIE-JOIST
SEE PLAN
INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

Ps = 1 kip
TYPICAL
U.N.O.

STEEL JOIST - SEE PLAN

STEEL JOIST
SEE PLAN
INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

HSS COLUMN
SEE PLAN

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

HSS COLUMN
SEE PLAN

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS AT CHANNEL


OUTRIGGERS AT DECK
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

HSS COLUMN BEYOND


SEE PLAN

HSS COLUMN BEYOND


SEE PLAN
STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

CLIP ANGLE AT COLUMN BEYOND


AS REQUIRED BY STRUCTURAL
STEEL SUPPLIER - TYPICAL

CLIP HEADER
ANGLE AT COLUMN BEYOND
HSS
AS REQUIRED
BY STRUCTURAL
SEE
STEEL ELEVATIONS
STEEL
SUPPLIER
- TYPICAL
ON
DRAWING
S-701
HEADER C/W MATCHING
OUTRIGGERS AT EACH COLUMN.
WELD HEADER TO OUTRIGGER
AND OUTRIGGER TO COLUMN
ALL AROUND. TYPICAL

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

WINDOW GLAZING
REFER TO ARCH. DWGS.
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

WINDOW GLAZING
REFER TO ARCH. DWGS.
TYPICAL

U/S HSS HEADER


U/S STEEL GIRT
SEE ARCH. DWGS.

REFER TO STEEL ELEVATIONS ON


DRAWING S-701 FOR HEADER/GIRT
SIZES AND LOCATIONS. TYPICAL.
HSS VERTICAL AT EDGE OF
WINDOW GLAZING BEYOND
SEE STEEL ELEVATIONS ON
DRAWING S-701.
T/O HSS
SEE ARCH. DWGS.

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
HEADER C/W MATCHING
OUTRIGGERS AT EACH COLUMN.
WELD HEADER TO OUTRIGGER
AND OUTRIGGER TO COLUMN
ALL AROUND. TYPICAL

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
HEADER C/W MATCHING
OUTRIGGERS AT EACH COLUMN.
WELD HEADER TO OUTRIGGER
AND OUTRIGGER TO COLUMN
ALL AROUND. TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

U/S HSS HEADER


U/S STEEL GIRT
SEE ARCH. DWGS.
HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SECTION
3/4"=1'-0"

WINDOW GLAZING
REFER TO ARCH. DWGS.
TYPICAL

R1
S-301

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

CLIP ANGLE AT COLUMN BEYOND


AS REQUIRED BY STRUCTURAL
STEEL SUPPLIER - TYPICAL

SECTION
3/4"=1'-0"

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

WINDOW GLAZING
REFER TO ARCH. DWGS.
TYPICAL

R2
S-301

REFER TO ROOF PLAN FOR DECK SLOPES.


COORD. WITH ARCH. DRAWINGS. TYPICAL.

CLIP ANGLE AT COLUMN BEYOND


AS REQUIRED BY STRUCTURAL
STEEL SUPPLIER - TYPICAL

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SECTION

SECTION

3/4"=1'-0"

R3
S-301

3/4"=1'-0"

R4
S-301

1'-4"

1"

6" STEEL STUD WALL BEHIND


CANTILEVERED INSULATED
PANEL WALL TO BE DESIGNED
AND SUPPLIED BY STEEL
STUD SUPPLIER - TYPICAL

3"

T/O PARAPET
SEE ARCH. DWGS.
CANTILEVERED INSULATED PANEL
PARAPETS TO BE REVIEWED AND
CONFIRMED BY THE INSULATED PANEL
SUPPLIER. ADVISE ENGINEER ON RECORD
IF ADDITIONAL SUPPORTS ARE REQUIRED.
TYPICAL AT ALL SIMILAR LOCATIONS
U/S STEEL DECK
(AT HIGH POINT)

1'-4"

1"

1'-4"

3"

1"

3"

1"

STEEL STUD PARAPET WALL


SEE SECT. R1

11 1/2"

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

1 1/2" STEEL DECK - SEE PLAN

11 1/2"

1'-4"

3"

STEEL STUD PARAPET WALL


SEE SECT. R1

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

1 1/2" STEEL DECK - SEE PLAN

11 1/2"

STEEL STUD PARAPET WALL


SEE SECT. R1

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

11 1/2"

1 1/2" STEEL DECK - SEE PLAN

1 1/2" STEEL DECK - SEE PLAN

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

COLUMN BRACE
SEE PLAN

STEEL BEAM
SEE PLAN

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

CHANNEL OUTRIGGERS
SEE SECT. R4
STEEL BEAM
SEE PLAN

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

CHANNEL OUTRIGGERS
SEE SECT. R4
STEEL BEAM
SEE PLAN

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

SAG RODS AT CHANNEL


OUTRIGGERS AT DECK
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS AT CHANNEL


OUTRIGGERS AT DECK
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS AT CHANNEL


OUTRIGGERS AT DECK
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

HSS COLUMN BEYOND


SEE PLAN

HSS COLUMN
SEE PLAN

HSS COLUMN BEYOND


SEE PLAN

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

HSS COLUMN BEYOND


SEE PLAN

SAG RODS AT CHANNEL


OUTRIGGERS AT DECK
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

U/S HSS HEADER


U/S STEEL GIRT
SEE ARCH. DWGS.

STEEL JOIST - SEE PLAN

STEEL BEAM
SEE PLAN

C150x12 OUTRIGGER
PROVIDE MOMENT
CONNECTION FOR
Mf = 6 kN.m
TYPICAL ALL SIMILAR
LOCATIONS

STEEL JOIST - SEE PLAN

STEEL JOIST - SEE PLAN

CHANNEL OUTRIGGERS
SEE SECT. R4

STEEL JOIST - SEE PLAN

ELEV. 129'-6"

FUTURE HSS CRANE BRACE


SEE PLAN ON DWG. S-302
TO BE INSTALLED AT SAME
TIME AS CRANE BEAM

2'-2"

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
HEADER C/W MATCHING
OUTRIGGERS AT EACH COLUMN.
WELD HEADER TO OUTRIGGER
AND OUTRIGGER TO COLUMN
ALL AROUND. TYPICAL

CLIP ANGLE AT COLUMN BEYOND


AS REQUIRED BY STRUCTURAL
STEEL SUPPLIER - TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

ASSUMED
U/S CRANE BEAM
ELEV. 121'-9"
TO BE CONFIRMED
WITH SUPPLIER

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL
10"

HSS OUTRIGGER AT
COLUMN BEYOND
SEE PLAN ON DWG. S-302

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

REFER TO STEEL ELEVATIONS ON


DRAWING S-701 FOR HEADER/GIRT
SIZES AND LOCATIONS. TYPICAL.

CLIP ANGLE AT COLUMN BEYOND


AS REQUIRED BY STRUCTURAL
STEEL SUPPLIER - TYPICAL
T/O HSS
SEE ARCH. DWGS.

T/O STEEL GIRT


SEE STEEL
ELEVATIONS
ON DWG. S-701
HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
HEADER C/W MATCHING
OUTRIGGERS AT EACH COLUMN.
WELD HEADER TO OUTRIGGER
AND OUTRIGGER TO COLUMN
ALL AROUND. TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

CONT. C-CHANNEL
SEE STEEL ELEVATIONS
ON DWG. S-701 FOR SIZE

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SECTION
3/4"=1'-0"

WINDOW GLAZING
REFER TO ARCH. DWGS.
TYPICAL

R5
S-301

HSS HEADER
SEE STEEL ELEVATIONS
ON DRAWING S-701
HEADER C/W MATCHING
OUTRIGGERS AT EACH COLUMN.
WELD HEADER TO OUTRIGGER
AND OUTRIGGER TO COLUMN
ALL AROUND. TYPICAL

SECTION
3/4"=1'-0"

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

CONT. C-CHANNEL
SEE SECT. R7

U/S HSS HEADER


T/O PRECAST WALL
SEE ARCH. DWGS.
WINDOW GLAZING
REFER TO ARCH. DWGS.
TYPICAL

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

U/S C-CHANNEL
T/O PRECAST WALL
ELEV. 110'-0"
COORD. WITH
ARCH. DWGS.
10" INSULATED PRECAST
PANEL WALL BY SUPPLIER.
REFER TO ARCH. DWGS.
FOR LOCATION AND EXTENT.
TYPICAL

R6
S-301

REFER TO ROOF PLAN FOR DECK SLOPES.


COORD. WITH ARCH. DRAWINGS. TYPICAL.

EMBEDED ANGLE/PLATE
BY PRECAST SUPPLIER
TYPICAL ALL SIMILAR
LOCATIONS

SECTION
3/4"=1'-0"

10" INSULATED PRECAST


PANEL WALL BY SUPPLIER.
REFER TO ARCH. DWGS.
FOR LOCATION AND EXTENT.
TYPICAL

R7
S-301

SECTION
3/4"=1'-0"

R8
S-301

1
7

A
1'-4"

1"

1'-2"

1'-4"

3"

1"

1'-4"

3"

1"

1'-4"

3"

1"

1'-7"

3"

1"

3"

T/O PARAPET
SEE ARCH. DWGS.
STEEL STUD PARAPET WALL
SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

11 1/2"

U/S STEEL DECK


(AT HIGH POINT)

STEEL STUD PARAPET WALL


SEE SECT. R1

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

11 1/2"

1 1/2" STEEL DECK - SEE PLAN

STEEL STUD PARAPET WALL


SEE SECT. R1

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

11 1/2"

1 1/2" STEEL DECK - SEE PLAN

STEEL STUD PARAPET WALL


SEE SECT. R1

CONT. STEEL ANGLE


SEE PLAN

STEEL STUD PARAPET WALL


SEE SECT. R1

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

11 1/2"

1 1/2" STEEL DECK - SEE PLAN

CONT. STEEL ANGLE


SEE PLAN

PLYWOOD STRIP AND BLOCKING


SEE SECT. R1

11 1/2"

1 1/2" STEEL DECK - SEE PLAN

1 1/2" STEEL DECK - SEE PLAN

ELEV. 129'-6"

STEEL BEAM
SEE PLAN

CANTILEVER JOIST
TOP CHORD AS
REQUIRED - TYPICAL

CANTILEVER JOIST
TOP CHORD AS
REQUIRED - TYPICAL

STEEL BEAM
SEE PLAN

STEEL BEAM
SEE PLAN

PROVIDE SLIP
CONNECTION
TYPICAL

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

SAG RODS AT CHANNEL


OUTRIGGERS AT DECK
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

W-COLUMN
SEE PLAN

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

HSS COLUMN BEYOND


SEE PLAN

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

FUTURE CRANE BEAM BY


THE CRANE SUPPLIER
TYPICAL
STEEL GIRT
SEE STEEL ELEV.
ON DWG. S-701
TYPICAL

U/S STEEL GIRT


SEE STEEL ELEVATIONS
ON DWG. S-701

2'-2"

ASSUMED
U/S CRANE BEAM
ELEV. 121'-9"
TO BE CONFIRMED
WITH SUPPLIER

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

ASSUMED
U/S CRANE BEAM
ELEV. 121'-9"
TO BE CONFIRMED
WITH SUPPLIER

FUTURE HSS CRANE BRACE


SEE PLAN ON DWG. S-302
TO BE INSTALLED AT SAME
TIME AS CRANE BEAM

FUTURE HSS CRANE BRACE


SEE PLAN ON DWG. S-302
TO BE INSTALLED AT SAME
TIME AS CRANE BEAM

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

FUTURE HSS CRANE BRACE


SEE PLAN ON DWG. S-302
TO BE INSTALLED AT SAME
TIME AS CRANE BEAM

6"

HSS OUTRIGGER AT
COLUMN BEYOND
SEE PLAN ON DWG. S-302

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

HSS OUTRIGGER AT
COLUMN BEYOND
SEE PLAN ON DWG. S-302

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

T/O STEEL GIRT


SEE STEEL
ELEVATIONS
ON DWG. S-701

VERTICAL CHANNEL AT
DOOR JAMB BEYOND
SEE STEEL ELEVATIONS
ON DRAWING S-701

STEEL JOIST
SEE PLAN

STEEL TIE-JOIST
SEE PLAN
INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

C-CHANNEL AS REQUIRED FOR


O/H DOOR SPRING SUPPORT

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL
10"

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

MAX.
FUTURE CRANE BEAM BY
THE CRANE SUPPLIER
TYPICAL

FUTURE CRANE BEAM BY


THE CRANE SUPPLIER
TYPICAL

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

STEEL GIRT
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

SAG RODS BEYOND


NOT SHOWN FOR CLARITY
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

FUTURE HSS
CRANE BRACE
SEE PLAN ON
DWG. S-302
TO BE INSTALLED
AT SAME TIME AS
CRANE BEAM

ASSUMED
U/S CRANE BEAM
ELEV. 121'-9"
TO BE CONFIRMED
WITH SUPPLIER
3"

FUTURE STEEL CORBEL


FOR CRANE SUPPORT
BY CRANE SUPPLIER.
TYPICAL.

FUTURE HSS CRANE BRACE


SEE PLAN ON DWG. S-302
TO BE INSTALLED AT SAME
TIME AS CRANE BEAM

WINDOW GLAZING
REFER TO ARCH. DWGS.
TYPICAL

ADDITIONAL GIRT
FRAMING AROUND
WINDOWS SEE STEEL
ELEVATIONS ON DWG.
S-701

U/S CHANNEL
SEE STEEL
ELEVATIONS
ON DWG. S-701

W-COLUMN
SEE PLAN

NOTE: ANGLE BRACES AT COLUMNS


NOT SHOWN FOR CLARITY. TYP.

REFER TO STEEL ELEVATIONS ON


DRAWING S-701 FOR HEADER/GIRT
SIZES AND LOCATIONS. TYPICAL.

CLIP ANGLE AT COLUMN


AS REQUIRED BY
STRUCTURAL STEEL
SUPPLIER - TYPICAL

3"

STEEL BEAM
SEE PLAN

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

STEEL GIRT
SEE STEEL ELEV.
ON DWG. S-701
TYPICAL

STEEL BEAM
SEE PLAN

HSS COLUMN
SEE PLAN

FUTURE CRANE BEAM BY


THE CRANE SUPPLIER
TYPICAL

HSS COLUMN
SEE PLAN

U/S STEEL GIRT


SEE STEEL
ELEVATIONS
ON DWG. S-701

STEEL TIE-JOIST
SEE PLAN

CANTILEVER JOIST
TOP CHORD AS
REQUIRED - TYPICAL

1'-4"

C200x17 OUTRIGGER
TYPICAL AT ALL
SIMIILAR LOCATIONS
STEEL JOIST
SEE PLAN

INSULATED
METAL PANEL
BY SUPPLIER
SEE ARCH. DWGS.
TYPICAL

PROVIDE A BEAM
BOTTOM FLANGE BRACE
AT OUTRIGGER
LOCATION TYPICAL

45

STEEL BEAM
SEE PLAN

STEEL JOIST
SEE PLAN

CHANNEL OUTRIGGERS
SEE SECT. R6

C-CHANNEL
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

C-CHANNEL
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

CLIP ANGLE AT COLUMN BEYOND


AS REQUIRED BY STRUCTURAL
STEEL SUPPLIER - TYPICAL

CLIP ANGLE AT COLUMN


AS REQUIRED BY STRUCTURAL
STEEL SUPPLIER - TYPICAL

SAG RODS
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

VERTICAL CHANNEL AT
DOOR JAMB BEYOND
SEE STEEL ELEVATIONS
ON DRAWING S-701

C-CHANNEL
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

BENT PLATE AT O/H DOORS


REFER TO ARCH. DWGS.
TYPICAL

C-CHANNEL
SEE STEEL ELEVATIONS
ON DRAWING S-701
TYPICAL

O/H DOORS BY SUPPLIER


REFER TO ARCH. DWGS.
TYPICAL

CONT. C-CHANNEL
SEE SECT. R7

CONT. C-CHANNEL
SEE SECT. R7

CONT. C-CHANNEL
SEE SECT. R7

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

CONT. C-CHANNEL
SEE SECT. R7

U/S C-CHANNEL
T/O PRECAST WALL
ELEV. 110'-0"
COORD. WITH
ARCH. DWGS.

U/S C-CHANNEL
T/O PRECAST WALL
ELEV. 110'-0"
COORD. WITH
ARCH. DWGS.

SECTION
3/4"=1'-0"

10" INSULATED PRECAST


PANEL WALL BY SUPPLIER.
REFER TO ARCH. DWGS.
FOR LOCATION AND EXTENT.
TYPICAL

R9
S-301

10" INSULATED PRECAST


PANEL WALL BY SUPPLIER.
REFER TO ARCH. DWGS.
FOR LOCATION AND EXTENT.
TYPICAL

10" INSULATED PRECAST


PANEL WALL BY SUPPLIER.
REFER TO ARCH. DWGS.
FOR LOCATION AND EXTENT.
TYPICAL

SECTION

R10

SECTION

R11

SECTION

R12

SECTION

R13

3/4"=1'-0"

S-301

3/4"=1'-0"

S-301

3/4"=1'-0"

S-301

3/4"=1'-0"

S-301

INSULATED PRECAST
PANEL BY SUPPLIER
TYPICAL

2"

INSULATED METAL
PANEL BY SUPPLIER
TYPICAL

2"

A
CRANE BEAM SUPPORT AND FRAMING HAS
BEEN ASSUMED. ALL SIZES, ELEVATIONS
AND DIMENSIONS TO BE CONFIRMED WITH
CRANE SUPPLIER PRIOR TO COMMENCING
WITH WORK. TYPICAL.

REFER TO ROOF PLAN FOR DECK SLOPES.


COORD. WITH ARCH. DRAWINGS. TYPICAL.

10"

10" INSULATED PRECAST


PANEL WALL BY SUPPLIER.
REFER TO ARCH. DWGS.
FOR LOCATION AND EXTENT.
TYPICAL

1"

EMBEDED ANGLE/PLATE
BY PRECAST SUPPLIER
TYPICAL ALL SIMILAR
LOCATIONS

1/4" BENT PLATE


REFER TO ARCH.
DWGS.

VERTICAL C-CHANNEL
REFER TO STEEL
ELEVATIONS ON
DWG. S-701

1/4" BENT PLATE


REFER TO ARCH.
DWGS.

EMBEDED STEEL PLATES


AS REQUIRED BY
PRECAST SUPPLIER

AT PRECAST WALLS

AT INSULATED PANEL WALLS

PLAN DETAILS AT OVERHEAD DOORS


1 1/2"=1'-0"

THESE DETAILS NEED TO BE COORDINATED WITH ARCHITECTURAL AND DOOR SUPPLIER'S DRAWINGS.
ADDITIONAL INFORMATION MAY BE REQUIRED. COORD. WITH PRECAST PANEL AND INSULATED PANEL SUPPLIERS.

B
B

STEEL BEAM
SEE PLAN

STEEL BEAM
SEE PLAN

1 1/2" STEEL DECK - SEE PLAN

U/S STEEL DECK


ELEV. VARIES
SEE ROOF PLAN

1 1/2" STEEL DECK - SEE PLAN

1 1/2" STEEL DECK - SEE PLAN

STEEL TIE-JOIST
SEE PLAN

STEEL TIE-JOIST
SEE PLAN

STEEL TIE-JOIST
SEE PLAN

STEEL TIE-JOIST
SEE PLAN

STEEL JOIST - SEE PLAN

STEEL JOIST - SEE PLAN


STEEL BEAM - SEE PLAN

W-COLUMN
SEE PLAN

W-COLUMN
SEE PLAN

FUTURE CRANE BEAM BY


THE CRANE SUPPLIER
TYPICAL

FUTURE CRANE BEAM BY


THE CRANE SUPPLIER
TYPICAL

10"

10"

10"

MAX.

MAX.

MAX.

SECTION

R16

3/4"=1'-0"

S-301

FUTURE STEEL CORBEL


FOR CRANE SUPPORT
BY CRANE SUPPLIER.
TYPICAL.
ASSUMED
U/S CRANE BEAM
ELEV. 121'-9"
TO BE CONFIRMED
WITH SUPPLIER

FUTURE STEEL CORBEL


FOR CRANE SUPPORT
BY CRANE SUPPLIER.
TYPICAL.

FUTURE HSS CRANE BRACE


SEE PLAN ON DWG. S-302
TO BE INSTALLED AT SAME
TIME AS CRANE BEAM

FUTURE HSS CRANE BRACE


SEE PLAN ON DWG. S-302
TO BE INSTALLED AT SAME
TIME AS CRANE BEAM

NOTE: ANGLE BRACES AT COLUMNS


NOT SHOWN FOR CLARITY. TYP.

NOTE: ANGLE BRACES AT COLUMNS


NOT SHOWN FOR CLARITY. TYP.

SECTION

R14

SECTION

R15

3/4"=1'-0"

S-301

3/4"=1'-0"

S-301

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com

CRANE BEAM SUPPORT AND FRAMING HAS


BEEN ASSUMED. ALL SIZES, ELEVATIONS
AND DIMENSIONS TO BE CONFIRMED WITH
CRANE SUPPLIER PRIOR TO COMMENCING
WITH WORK. TYPICAL.

REFER TO ROOF PLAN FOR DECK SLOPES.


COORD. WITH ARCH. DRAWINGS. TYPICAL.

SAG RODS. SEE NOTES ON THIS DWG.


TYPICAL AS SHOWN
SIM.

FOR ELEVATION OF BRACES BEYOND


SEE SEPARATE ELEVATION ON THIS
DRAWING.

SIM.

SIM.

SIM.

SIM.

SIM.

SIM.

R1

R3

R2

R3

R1

R2

R1

R3

R2

R1

S-601

S-601

S-601

S-601

S-601

S-601

S-601

S-601

S-601

S-601

SHADING DENOTES LOCATION


OF PRECAST PANEL WALL
TYPICAL AS SHOWN

SIM.

R4

R5

R6

R7

R9

R8

S-601

S-602

S-602

S-602

S-603

S-602

SIM.
5'-0"

SIM.

R9

R8

R8

S-603

S-602

S-602

HSS 152x152x9.5

STEEL BEAM

203S70-290M GIRT

203S70-290M GIRT

203S70-290M GIRT

203S70-290M GIRT

203S70-290M GIRT

HSS 152x152x9.5

C200x17

C200x17

C200x17

C200x17

C200x17
W-COLUMN

C200x17

HSS COLUMN

203S70-290M GIRT

HSS COLUMN

HSS 152x152x6.4

HSS COLUMN

HSS 152x152x6.4

HSS COLUMN

U/S HSS HEADER


SEE ARCH. DWGS.

STEEL BEAM

203S70-290M GIRT

HSS COLUMN

T/O HSS
SEE ARCH. DWGS.

203S70-290M GIRT

203S70-290M GIRT

HSS COLUMN

HSS 152x152x6.4

U/S HSS HEADER


SEE ARCH. DWGS.

STEEL BEAM

STEEL BEAM

C200x17

203S70-290M GIRT

C200x17

HSS COLUMN

HSS 152x152x6.4

HSS 152x152x6.4

HSS 152x152x9.5

C200x17

C200x17

203S70-290M GIRT

C200x17

R9

R8

R7

R6

R5

R4

S-603

S-602

S-602

S-602

S-602

S-601

MAX.
U/S STL. DECK
ELEV. 129'-6"

U/S STL. DECK


ELEV. 129'-6"

U/S STEEL GIRT


ELEV. 122'-0"

U/S STEEL GIRT


ELEV. 122'-0"

T/O STEEL GIRT


ELEV. 116'-3"

T/O STEEL GIRT


ELEV. 116'-3"

U/S CHANNEL
T/O PRECAST PANEL
ELEV. 110'-0"

U/S CHANNEL
T/O PRECAST PANEL
ELEV. 110'-0"

STEEL BEAM

STEEL BEAM

203S70-290M GIRT

STEEL BEAM

203S70-290M GIRT

STEEL BEAM

STEEL BEAM

203S70-290M GIRT

203S70-290M GIRT

U/S STL. DECK


ELEV. 129'-6"

STEEL BEAM

HSS 152x152x9.5

203S70-290M GIRT

203S70-290M GIRT

203S70-290M GIRT

203S70-290M GIRT

203S70-290M GIRT

HSS 152x152x6.4

HSS 152x152x6.4

C200x17

C200x17

C200x17

C200x17

C200x17

HSS 152x152x9.5

HSS COLUMN

STEEL BEAM

C200x17

5'-0"

W-COLUMN

STEEL BEAM

203S70-290M GIRT

HSS 152x152x6.4

SIM.

MAX.
U/S STL. DECK
ELEV. 129'-6"

HSS 152x152x6.4

U/S HSS HEADER


SEE ARCH. DWGS.

T/O HSS
SEE ARCH. DWGS.

HSS COLUMN

SIM.

SIM.

HSS 152x152x6.4

HSS 152x152x6.4

MIRR.

C200x17

HSS 152x152x6.4

HSS 152x152x9.5

HSS COLUMN

SIM.

C200x17

203S70-290M GIRT

C200x17 VERTICAL EACH SIDE OF DOOR


AT EDGE OF PRECAST PANEL. REFER
TO DRAWING S-401 FOR BASE PLATE
AND PIER DETAILS. COORD. LOCATION
OF CHANNELS WITH ARCHITECTURAL
DOOR DETAILS. TYPICAL AS SHOWN ON
THIS GRIDLINE/BUILDING FACE

1/8"=1'-0"

MIRR.

C200x17

203S70-290M GIRT

HSS COLUMN

(WEST) STEEL ELEVATION ALONG GRID D

C200x17

HSS 152x152x9.5

203S70-290M GIRT

C200x17

C200x17

203S70-290M GIRT

STEEL BEAM

HSS COLUMN

C200x17

203S70-290M GIRT

STEEL BEAM

HSS COLUMN

C200x17

HSS 152x152x9.5

HSS 152x152x6.4

STEEL BEAM

HSS COLUMN

C200x17

203S70-290M GIRT

HSS 152x152x6.4

STEEL BEAM

HSS COLUMN

C200x17

203S70-290M GIRT

HSS 152x152x6.4

HSS 152x152x9.5

HSS COLUMN

203S70-290M GIRT

HSS 152x152x6.4

203S70-290M GIRT

C200x17

HSS 152x152x6.4

203S70-290M GIRT

HSS 152x152x6.4

HSS 152x152x6.4

STEEL BEAM

HSS COLUMN

HSS 152x152x6.4

HSS 152x152x9.5

STEEL BEAM

HSS COLUMN

203S70-290M GIRT

HSS COLUMN

203S70-290M GIRT

STEEL BEAM

C200x17

T/O MAIN FLOOR


ELEV. 100'-0"

C200x17

C200x17

C200x17

C200x17

HSS 152x152x9.5

203S70-290M GIRT

STEEL BEAM

HSS 152x152x6.4

U/S HSS HEADER


U/S STEEL GIRT
SEE ARCH. DWGS.

HSS 152x152x6.4

STEEL BEAM

HSS 152x152x6.4

T/O HSS
SEE ARCH. DWGS.

HSS COLUMN

HSS COLUMN

HSS 152x152x6.4

HSS 152x152x9.5

STEEL BEAM

HSS COLUMN

U/S HSS HEADER


U/S STEEL GIRT
SEE ARCH. DWGS.

STEEL BEAM

HSS COLUMN

STEEL BEAM

HSS COLUMN

U/S STL. DECK


ELEV. 129'-6"

HSS 152x152x6.4

HSS COLUMN

HSS 152x152x6.4

C200x17

U/S HSS HEADER


SEE ARCH. DWGS.

T/O MAIN FLOOR


ELEV. 100'-0"

T/O MAIN FLOOR


ELEV. 100'-0"
FOR ELEVATION OF BRACES BEYOND
SEE SEPARATE ELEVATION ON THIS
DRAWING.

(SOUTH) STEEL ELEVATION ALONG GRID 7

SHADING DENOTES LOCATION


OF PRECAST PANEL WALL
TYPICAL AS SHOWN

(NORTH) STEEL ELEVATION ALONG GRID 1

203S70-290M GIRT

T/O MAIN FLOOR


ELEV. 100'-0"

(EAST) STEEL ELEVATION ALONG GRID A

C200x17

C200x17

C200x17

C200x17

C200x17

STEEL PLATE

OVERHEAD DOOR
REFER TO ARCH.
DWGS. FOR SIZE
AND LOCATION

C200x17

MAN DOOR

C200x17

C200x17

OVERHEAD DOOR
REFER TO ARCH.
DWGS. FOR SIZE
AND LOCATION

R12

R11

R10

S-603

S-603

S-603

STEEL BEAM

203S70-290M GIRT

STEEL BEAM

203S70-290M GIRT

203S70-290M GIRT

STEEL BEAM

STEEL BEAM

STEEL BEAM

203S70-290M GIRT

203S70-290M GIRT

203S70-290M GIRT

WINDOW

C200x17

C200x17

C200x17

C200x17

FOR ELEVATION OF BRACES BEYOND


SEE SEPARATE ELEVATION ON THIS
DRAWING.

C200x17

OVERHEAD DOOR
REFER TO ARCH.
DWGS. FOR SIZE
AND LOCATION

STEEL BEAM

203S70-290M GIRT

WINDOW

C200x17

C200x17

C200x17

C200x17

FOR ELEVATION OF BRACES BEYOND


SEE SEPARATE ELEVATION ON THIS
DRAWING.

C200x17

OVERHEAD DOOR
REFER TO ARCH.
DWGS. FOR SIZE
AND LOCATION

STEEL BEAM

STEEL BEAM

203S70-290M GIRT

203S70-290M GIRT

WINDOW

C200x17

C200x17

C200x17

C200x17

C200x17

OVERHEAD DOOR
REFER TO ARCH.
DWGS. FOR SIZE
AND LOCATION

C200x17

203S70-290M GIRT

R10
S-603

C200x17

C200x17

STEEL PLATE

203S70-290M GIRT

STEEL BEAM

WINDOW

C200x17

C200x17

C200x17

C200x17

STEEL PLATE

OVERHEAD DOOR
REFER TO ARCH.
DWGS. FOR SIZE
AND LOCATION

C200x17

MAN DOOR

STEEL PLATE

C200x17

C200x17

C200x17

C200x17

STEEL BEAM

WINDOW

STEEL PLATE

U/S CHANNEL
ELEV. 116'-1"
COORD. WITH
ARCH. DWGS.
U/S CHANNEL
T/O PRECAST PANEL
ELEV. 110'-0"

C200x17

WINDOW

203S70-290M GIRT

STEEL BEAM

R12
S-603

C200x17

203S70-290M GIRT

STEEL BEAM

R13
S-603

STEEL PLATE

203S70-290M GIRT

STEEL BEAM

R10
S-603

MAN DOOR

203S70-290M GIRT

STEEL BEAM

R11
S-603

C200x17

203S70-290M GIRT

STEEL BEAM

R12

STEEL PLATE

STEEL BEAM

SIM.

S-603

C200x17

STEEL BEAM

R10
S-603

SIM.

STEEL PLATE

STEEL BEAM

R13
S-603

SIM.

MAN DOOR

R13
S-603

SIM.

C200x17

R10
S-603

SIM.
C200x17 VERT. FOR DOOR TRACK SUPPORT.
PROVIDE SLOTTED CONNECTION AT BEAM.
SEE SECTION R12 ON DRAWING S-603.

STEEL PLATE

R11
S-603

SIM.

C200x17

R12
S-603

PROVIDE ADDITIONAL 203S70-290M GIRTS


AT WINDOW OPENING AS REQUIRED.
REFER TO ARCH. DWGS. FOR SIZE AND
LOCATION OF WINDOW. TYPICAL.

STEEL PLATE

R10
S-603

203S70-290M GIRT

SIM.

SIM.

MAN DOOR

SIM.

C200x17

SIM.

STEEL PLATE

SIM.

STEEL PLATE

SIM.

U/S STEEL GIRT


ELEV. 122'-8"
COORD. WITH
ARCH. DWGS.

SHADING DENOTES LOCATION


OF PRECAST PANEL WALL
TYPICAL AS SHOWN

1/8"=1'-0"

1/8"=1'-0"

U/S STL. DECK


ELEV. 129'-6"

FOR ELEVATION OF BRACES BEYOND


SEE SEPARATE ELEVATION ON THIS
DRAWING.

FOR ELEVATION OF BRACES BEYOND


SEE SEPARATE ELEVATION ON THIS
DRAWING.

1/8"=1'-0"

U/S STL. DECK


ELEV. 129'-6"

STEEL BEAM

U/S STL. DECK


ELEV. 129'-6"

STEEL BEAM

STEEL BEAM

U/S STL. DECK


ELEV. 129'-6"

STEEL BEAM

STEEL BEAM

6"

6"

6"

6"

T/O MAIN FLOOR


ELEV. 100'-0"

BRACES AT GRID D

BRACES AT GRIDS 1 AND 7

BRACES AT GRID A

1/8"=1'-0"

1/8"=1'-0"

1/8"=1'-0"

ALL DIMENSIONS SHOWN ARE WORKING POINT DIMENSIONS.


ALL BRACE HORIZONTAL AND DIAGONAL MEMBERS ARE
H.S.S. 127x127x6.4 TYPICAL UNLESS NOTED OTHERWISE.
FOUNDATIONS ARE NOT SHOWN FOR CLARITY.
COORD. LENGTH OF COLUMNS WITH CONC. PIER DETAILS.

HSS COLUMN

EQUAL

HSS COLUMN

HSS COLUMN

HSS COLUMN

T/O MAIN FLOOR


ELEV. 100'-0"

W-COLUMN

U/S HSS HEADER


SEE ARCH. DWGS.

T/O MAIN FLOOR


ELEV. 100'-0"

HSS COLUMN

HSS COLUMN

HSS COLUMN

6"

6"

EQUAL

ALL DIMENSIONS SHOWN ARE WORKING POINT DIMENSIONS.


ALL BRACE HORIZONTAL AND DIAGONAL MEMBERS ARE
H.S.S. 127x127x6.4 TYPICAL UNLESS NOTED OTHERWISE.
FOUNDATIONS ARE NOT SHOWN FOR CLARITY.
COORD. LENGTH OF COLUMNS WITH CONC. PIER DETAILS.

ALL DIMENSIONS SHOWN ARE WORKING POINT DIMENSIONS.


ALL BRACE HORIZONTAL AND DIAGONAL MEMBERS ARE
H.S.S. 127x127x6.4 TYPICAL UNLESS NOTED OTHERWISE.
FOUNDATIONS ARE NOT SHOWN FOR CLARITY.
COORD. LENGTH OF COLUMNS WITH CONC. PIER DETAILS.

ELEVATIONS SHOWN ON THIS DRAWING SHALL


BE READ WITH THE ROOF FRAMING PLAN ON
DRAWING S-301.
COORDINATE ALL ELEVATIONS AND
DIMENSIONS WITH ARCHITECTURAL DRAWINGS
PRIOR TO COMMENCING WITH WORK.
ASSUMED JOIST SHOE DEPTH = 4". TO BE
VERIFIED WITH JOIST SUPPLIER.
U.N.O. SAG RODS TO BE 3/4" @ 7'-0" O/C MAX.
WELD ALL H.S.S. HEADERS ALL AROUND AT
EACH END TYPICAL
OPENINGS NOTED ON THESE ELEVATIONS MAY
BE DUE TO DOOR, WINDOW OR GLAZING AND
ARE FOR REFERENCE ONLY. VERIFY LOCATIONS
AND SIZE OF EACH OPENING WITH
ARCHITECTURAL DRAWINGS PRIOR TO
COMMENCING WITH WORK.
REFER TO ARCHITECTURAL DRAWINGS FOR
PARAPET ELEVATIONS.
STEEL GIRT MAXIMUM SPACING = 7'-6"

SUITE 1100-10117 JASPER AVENUE,


EDMONTON, ALBERTA T5J 1W8
FAX: (780) 425-7227 PHONE: (780) 423-5855
E-MAIL: protostatix@caisnet.com