MICOM P143 Logic Scheme

BUS COUPLER - SWGR BLDG GDZ-B


Logic Inputs

Logic Inputs
INFORMATIONS FROM INCOMING 1 & 2
MV CB CLOSED

SR User Alarm 1
DDB #168
Input L2
DDB #033

MV CB OPEN
CB Aux 3ph(52-B)
DDB #229

SR User Alarm 2
DDB #169

Input L3
DDB #034

SR User Alarm 3
DDB #170

Input L4
DDB #035

SR User Alarm 4
DDB #171

Input L5
DDB #036

MOVING PART PLUGGED-IN & MV CB CLOSED & VOLTAGE PRESENCE


& NO ELECTRIC FAULT

Input L13
DDB #044

CB Aux 3ph(52-A)
DDB #228

Input L1
DDB #032

MOVING PART PLUGGED-IN

SPRING LOADED

SR User Alarm 5
DDB #172

INPUT L16 ON TRIP COMMAND IN (DDB #536)

MANUAL RETURN PUSH BUTTON

INFORMATIONS FROM INCOMING 1


Input L6
DDB #037

SR User Alarm 6
DDB #173

SELECTOR SWITCH LOCAL


Input L17
DDB #048

Input L7
DDB #038

SR User Alarm 7
DDB #174

SELECTOR SWITCH REMOTE

Input L8
DDB #039

SR User Alarm 8
DDB #175

MANUAL RETURN PLC ORDER

Input L9
DDB #040

Input L10
DDB #041

Input L11
DDB #042

Input L12
DDB #043

SR User Alarm 9
DDB #176

SELECTOR SWITCH ON LOCAL & NO ELECTRIC FAULT

Input L18
DDB #049

SELECTOR SWITCH ON REMOTE & NO ELECTRIC FAULT

Input L19
DDB #050

MOVING PART TEST OR MV CB OPEN

Input L20
DDB #051

MOVING PART PLUGGED-IN & MV CB CLOSED

TRANSFER SELECTOR SWITCH ON AUTO

SR User Alarm 10
DDB #177

TRANSFER SELECTOR SWITCH ON MANU


VOLUNTARY TRANSFER SELECTOR
SWITCH
INCOMING 1 TO INCOMING 2

SR User Alarm 11
DDB #178

INFORMATIONS FROM INCOMING 2

VOLUNTARY TRANSFER SELECTOR


SWITCH
INCOMING 2 TO INCOMING 1

SR User Alarm 12
DDB #179

Input L21
DDB #052

SELECTOR SWITCH ON LOCAL & NO ELECTRIC FAULT

Input L22
DDB #053

SELECTOR SWITCH ON REMOTE & NO ELECTRIC FAULT

Input L23
DDB #054

MOVING PART TEST OR MV CB OPEN

Input L24
DDB #055

MOVING PART PLUGGED-IN & MV CB CLOSED

Faults recorder
200
Trip Command Out
DDB #537

Fault REC TRIG


DDB #144

Dwell
0

Rep:B - 01/02/2010

Sheet: 1

Order Nr S010766

Output Relays

Sheet: 2

Rep:B - 01/02/2010

Output Relays

TO PLC
0

Trip Command Out


DDB #537

Output R22
DDB #021

Straight

MOVING PART PLUGGED-IN

TRIPPING ORDER

&

MV CB CLOSED

Output R3
DDB #002

Latching
0

TO INCOMING 2 P143 INPUT

MV CB OPEN

Input L2
DDB #033

CLOSING FORBIDDEN

SPRING LOADED

INCOMING 1

MOVING PART PLUGGED-IN & MV CB CLOSED


Input L20
DDB #051

SELECTOR SWITCH REMOTE

TRANSFER SELECTOR SWITCH ON AUTO

Output R4
DDB #003

Straight

Input L4
DDB #035

Output R11
DDB #010

Straight

Input L7
DDB #038

Output R8
DDB #007

Straight

Input L1
DDB #032

Input L3
DDB #034

TO INCOMING 1 P143 INPUT

Input L3
DDB #034

MOVING PART PLUGGED-IN

Rep:B - 01/02/2

TO INCOMING 1 P143 INPUT


0

&

MOVING PART TEST OR MV CB OPEN

Input L9
DDB #040

&

INCOMING 2

Output R6
DDB #005

Straight

Input L23
DDB #054

NO PARALLEL OPERATING CLOSING AUTHORIZATION

&

TO INCOMING 2 P143 INPUT

MOVING PART PLUGGED-IN

Input L3
DDB #034

INCOMING 1

Output R9
DDB #008

Straight

Output R12
DDB #011

Straight
0

MOVING PART TEST OR MV CB OPEN

Input L19
DDB #050

MV CB CLOSED
Input L1
DDB #032

&

INCOMING 2
MOVING PART PLUGGED-IN & MV CB CLOSED

TRANSFER SELECTOR SWITCH ON MANU

Input L24
DDB #055

Input L10
DDB #041

Output R14
DDB #013

SELECTOR SWITCH LOCAL


Input L6
DDB #037

TO INCOMING 1 P143 INPUT

MANUAL RETURN PUSH BUTTON


Input L5
DDB #036

&

SELECTOR SWITCH REMOTE


Input L7
DDB #038

0
Output R7
DDB #006

Straight

SELECTOR SWITCH LOCAL

READY TO TRANSFER

Input L6
DDB #037

TRANSFER SELECTOR SWITCH ON MANU

Input L17
DDB #048

&

&

Output R13
DDB #012

Straight
0

Input L21
DDB #052

Output R10
DDB #009

Straight

Output R14
DDB #013

SELECTOR SWITCH REMOTE


Input L7
DDB #038

INCOMING 1 & INCOMING 2

MANUAL RETURN PLC ORDER

Input L10
DDB #041

TO INCOMING 2 P143 INPUT

MOVING PART PLUGGED-IN & MV CB CLOSED & VOLTAGE


PRESENCE
& NO ELECTRIC FAULT

Input L8
DDB #039

Input L13
DDB #044
Input L18
DDB #049

&
Input L22
DDB #053

2010

Sheet: 3

Rep:B - 01/02/2010

Sheet: 4
Output R19
DDB #018

&

Rep:B - 01/02/2010

Output Relays
TO INDICATING LIGHT
0
Trip Command Out
DDB #537

Output R14
DDB #013

Latching
0

TO F60 RELAY INPUT


0
Output R15
DDB #014

Straight
0
ISEF>1 Trip
DDB #269

51-51N TO F60 RELAY INPUT

I>1 Trip
DDB #243

I>3 Trip
DDB #251

Output R16
DDB #015

Straight
0

IN1>3 Trip
DDB #263

25 TO F60 RELAY INPUT


0
Check Sync 1 OK
DDB #447

Output R17
DDB #016

Straight
0

27 TO F60 RELAY INPUT


0
Output R18
DDB #017

Straight

V<2 Trip
DDB #282

SPARE
0
Output R5
DDB #004

Straight
0

Check Sync 1 OK
DDB #447

Output R21
DDB #020

Straight
0

SPARE
0
Output R1
DDB #000

Straight
0

Sheet: 5

Trip output mapping


I>1 Trip
DDB #243
SR User Alarm 13
DDB #180
I>3 Trip
DDB #251
SR User Alarm 14
DDB #181

Automatic transfer
Note: DDB SignalsTrip
Command In and Trip Command
Out are joined
together in the fixed scheme
logic

VOLUNTARY TRANSFER INCOMING 1 TO INCOMING 2


INCOMING 1
SELECTOR SWITCH ON REMOTE & NO ELECTRIC FAULT
Input L18
DDB #049

INCOMING 2
SELECTOR SWITCH ON REMOTE & NO ELECTRIC FAULT
Input L22
DDB #053

&

SELECTOR SWITCH ON REMOTE

Broken Line Trip


DDB #260

Input L7
DDB #038

VOLUNTARY TRANSFER INC.1 TO INC.2 PLC ORDER


Input L14
DDB #045

IN1>3 Trip
DDB #263

INCOMING 1
SELECTOR SWITCH ON LOCAL & NO ELECTRIC FAULT
Input L17
DDB #048

SR User Alarm 15
DDB #182

INCOMING 2
SELECTOR SWITCH ON LOCAL & NO ELECTRIC FAULT
Input L21
DDB #052

Trip Command In
DDB #536

&

SELECTOR SWITCH LOCAL


Input L6
DDB #037

SR User Alarm 17
DDB #184

Trip LED Trigger


DDB #518

VOLUNTARY TRANSFER SELECTOR


SWITCH
MV CB OPEN
INCOMING 1 TO INCOMING 2
Input L11
DDB #042

V>1 Trip
DDB #286

INCOMING 1 CB OPENING

SR User Alarm 16
DDB #183

&
TRANSFER SELECTOR SWITCH ON MANU

0
Output R19
DDB #018

Straight
0

Input L10
DDB #041

ISEF>1 Trip
DDB #269
MR User Alarm 18
DDB #185

Output R14
DDB #013
YN> Trip
DDB #436
GN> Trip
DDB #437
BN> Trip
DDB #438

Input L13
DDB #044

AR Trip Test
DDB #372

TRIP BY P746 PROTECTION


Input L16
DDB #047

Rep:B - 01/02/2010

Order Nr S010766

Sheet: 6

Rep:B - 01/02/2010

Order Nr S010766

Sheet: 7

Rep:B - 01/02/20

Check Sync 1 OK
DDB #447

Automatic transfer

Input L3
DDB #034

Input L2
DDB #033

Input L4
DDB #035

Input L18
DDB #049

&
Input L22
DDB #053

Input L24
DDB #055

&

Input L7
DDB #038

Input L19
DDB #050
Check Sync 1 OK
DDB #447

Input L15
DDB #046

Output R19
DDB #018

S
RD

Input L17
DDB #048

BUS COUPLER CB CLOSING

Input L1
DDB #032
Output R20
DDB #019

Input L21
DDB #052

&

Check Sync 1 OK
DDB #447

Input L6
DDB #037

0
Output R2
DDB #001

Straight
0

&

Input L3
DDB #034

Input L2
DDB #033

Input L12
DDB #043

&

0
Output R20
DDB #019

Straight

Input L4
DDB #035

&

Input L10
DDB #041
Input L20
DDB #051
Output R14
DDB #013
Input L23
DDB #054
Check Sync 1 OK
DDB #447

Input L13
DDB #044

VOLUNTARY TRANSFER INC.2 TO INC.1 PLC ORDER

Output R20
DDB #019

S
Input L1
DDB #032

RD

Input L15
DDB #046

VOLUNTARY TRANSFER INC.1 TO INC.2 PLC ORDER


Input L14
DDB #045

Order Nr S010766

010

Sheet: 8

READY TO TRANSFER
Output R13
DDB #012

Check Sync 1 OK
DDB #447

Non Latching

LED 1
DDB #064

Non Latching

LED 2
DDB #065

Sheet: 9