Professional Documents
Culture Documents
1. Ifitis necessary to start a boiler from dead ship conditions with neither shore power nor shore
steam available, diesel oil may be used until steam has been raised enough to heat the bunker
fuel.
2. Fill the boiler with deaerated water from a deaerator if at all possible. The feed tanks should
be filled with condensate before securing the boilers to provide the water necessary for
restarting, It is advisable to fill the boiler S0~80 mm above the normal water level to provide
an additional storage until the feed pump can be started
3. Start the emergency diesel generator, and blow out the gas remaining in the furnace using the
forced draft fan at low speed before lighting up the burner.
4. Prepare the boiler for service as outlined under the normal starting procedure
Line up the emergency fuel oil pump to take suction from the diesel oil tank and to discharge
to the burner manifold.
6. Start pumping diesel oil, bleed off enough through the recirculating line, or through the
‘bumer oil lead into a bucket to remove all heavy oil from the piping
7. The diesel fuel oil must to supplied to the bumers at designated oil pressure in order to obtain
proper atomization
8. Open the following valves before lighting up.
(1) Drum air vent valve (49B, SOB)
(2) Superheater header drain valves (72B, 76B, 77B, 78B)
(3) Starting valves (73B, 74B)
(4) Control desuperheater drain valves (135B, 136B, 137B, 138B)
9. Light on a burner with air atomizing, Fuel oil pressure is 3.0 kg/cm? (Combustion rate is 250
kg/h),
10, When steam pressure is up to, 1.0 kg/cm? close drum air vent valve. In case the steam
severely spurt, crack open the superheater header and control desuperheater drain valve The
superheater outlet header vent valve must be left open until the boiler is put on the line.
11, If completely drain, close the superheater header drain valves and control desuperheater drain
valves.
12, After a drum pressure 2.0 kg/cm? has been reached, start warming up the auxiliary steam lines.
Line up steam to the settling tank coils. Line up feed pump and have it ready for service when
needed. The starting valve must be left open until the boiler has been cut in on the load
13. As soon as the fuel oil in the settling tank is warm enough to pump, prepare to change from
diesel fuel to bunker fuel. Line up steam on the fuel oil heaters.
14, Secure the bumer, Circulate bunker fuel through the fuel oil heaters and piping until oil at the
MIs BISHI HEAVY INDUSTRIES, LTD.15.
16
17.
18,
19,
20.
2
22,
Note)
ae
proper temperature is available in the manifold, Relight the burner, normal conditions, and
continue raising pressure as outlined under normal condition.
When steam pressure is up to 10~15 kg/cm? start warming up the feed water pump, main
‘generator and other machineries
After a drum pressure 15 kg/em? has been reached, change atomizing fluid from air to steam
1g pressure at 4.5 kg/cm? of fuel oil pressure as outlined under normal
condition.
Start the feed pump, as early as possible. After starting the feed pump, close starting valve.
Start the main generator.
When the generator is up to speed and capable of carrying a load, switch over to generator
and secure the diesel generator
Drain and warm up connecting piping to the main and auxiliary steam lines. It is essential that
the connecting steam piping is clear of all water and warmed up to approximately operating
temperature before cutting the boiler in on the load
‘When the steam pressure is about 3~4 kg/cm? below normal operating pressure, check the
safety valves with the easing gear. Lift the disc well off the seat to give a strong blow and
release the lifting lever quickly to reseat the valves sharply.
Set up the burners with the proper sprayer plates for the service required, lighting up as
necessary.
1. Combustion rate should be used as a guide for start-up and should be controlled
appropriately so as to follow the pressure raising curve. To prevent damage to
supetheater tubes, combustion rate should not be increased excessively.
2. When it takes time to raise pressure, the starting valve should be operated (throttled) so
that the combustion rate will follow the pressure raising curve
MIs BISHI HEAVY INDUSTRIES, LTD.|
|
3|
3
Bi
Z|
gi
a
SI
zy
s
a
sI
Cold Start
(In case the other boiler is not used.)
Note: 1. Combustion rate should be used as a guide for
|
yowwouoT we oMp LEIS,
Sunseys ot
Kp 950] puw ourqimy dund soe poay om) HEI
Sp ‘ssid “Q'y aster pur
9/84, >
Du OF JasaIp Woy Ho Jon} dsuyD)
‘ayvoy [0 fony 0} weais