Also, similar messages appeared when I configured Q21 with AD06B & Q22 with

AD08B

Bay unit allocation like this:

For bus section (Q11, Q12, CB, Q21, Q22, CT3, CT4) there are 2 bay units
(BU@8, BU@9).

I assign Q11, Q12, CB, CT3 for one bay unit & Q21, Q22, CT4 for the other bay unit
but this message appears. Is this assignment not correct?

For bus section: which one is coorect: to insert 2 bay names (AD7A , AD7B &
assign components connected in BU@8 to AD7A & assign components
connected in BU@9 to AD7B as in figure 1 below) or to insert one bay name
(AD7) & assign all components in both BU@8 & BU@9 to AD7 as in figure
2 ???

Figure 1

Figure 2

Is the same for 2 bus couplers AD6 & AD8?


For fiber communication between CU, BU:

I configured LED in BU for fiber communication fail. I tested by removing 1


one time & another time by removing 2. But LED operate in one case &
doesnt operate in the other case. Is this normal?

If CB is closed & 2 busbar isolators are open, does end fault protection operate or
no?