You are on page 1of 12

HMD 2326 A.H.

U FAN MOTOR
CONCEPT FOR CONTROL

HIAIR AIRCONDITIONING
ENGINEERING Dept.
Assistant Manager

HIAIR AIRCONDITIONING
ENGINEERING Dept.
Assistant Manager

CONTENTS
1. CONCEPT
1) EXISTING
2) REQUEST
3) CONCEPT

2. PRESSURE SENSOR(QBM66.203)
1) CONNECTION TERMINALS
2) WIRING DRAWING

3. FREQUENCY CONTROL(KX4N)
1) CONNECTION TERMINALS
2) WIRING DRAWING
3) VALUE SETTING

4. INVERTER(SV550iP5A)
1) CONNECTION TERMINALS
2) WIRING DRAWING
3) MANUAL SETTING
4) SETTING VALUE

1. CONCEPT (SAME TO DSME 5389)


1) EXISTING : FAN ON/OFF according to AHU MOTOR SIGNAL (not SPEED control )
2) REQUEST : MOTOR SPEED is controlled according to the internal temperature of DUCT
and FAN SPEED is controlled according to MOTOR SPEED.
3) CONCEPT
(1) the detection of refrigerant pressure inside the DUCT sends output(0~10V)
-. PRESURE SENSOR : QBM66.203
(2)TEMPERTURE SENSOR changes from INPUT(0~10V) to OUTPUT(4~20mA)
-. TEMPERTURE SENSOR : KX4(HANYOUNG)
(3) INVERTER controls MOTOR SPEED in accordance to input signal(4~20mA)
-. INVERTER : SV550iP5A(LS)
(4) FAN SPEED is controlled according to MOTOR SPEED.

2. PRESSURE SENSOR(QBM66.203)
1) CONNECTION TERMINALS

-> HI AIR KOREA determines PRESSURE SENSOR

2) WIRING DRAWING

3. FREQUENCY CONTROL(KX4N)
1) CONNECTION TERMINALS

3) SETTING VALUE
KX4N SETTING VALUE
System Mode Settings
CODE
SL1

DESCRIPTION
Select input type
Output mode (fixed)
Decimal Point Selection

SL2

Tempreture Unit Selection


Indicator / Controller Selection
Standby Function of Alarm Selection
Transmission Output (Optional)

SL3

Alarm Mode Selection


Deviation alarm / Absolute Alarm

SL4
SL5
SL6

Decimal Point Position Selection


Input Correction value
High Alarm(ALH)
Hysteresis Setting

SL7
SL8

Max. Temperature Setting Value


Min. Temperature Setting Value

SL9

Control direction

SL10
SL11
SL12
SL13
SL14
SL15
SL16

Low Alarm(ALL)
Hysteresis Setting
Input filter
Max. Input scale
Min. Input scale
High Alarm (ALH)
Delay time setting
Low Alarm (ALL)
Delay time setting
Output hysteresis

2) WIRING DRAWING

KX4N SETTING VALUE


System Mode Settings
SETTING VALUE
0~10Vdc
0: Current output
1: Relay or Voltage Pulse output
0: With decimal ponit
1: Without decimal ponit
0: None
1:
0: Indicator
1: Controller
0: With Standby function
1: Without Standby function
0: With transmission output
1: Without transmission output
0: Alarm within range
1: High and Low alarm
0: Deviation alarm
1: Absolute alarm
0~3
100% of F.S
0~10% of F.S

CODE
1111
SV1
P
A

0011

1111

2
0.00
0.01

I
d

Comon Set Mode


DESCRIPTION
Set-value 1
Proportional
Anti-reset
Wind-up
Integral time
Derivative time

Within Input range


SL7>SL8
0: Reverse action (Heating Operation)
1: Forward action (Cooling Operation)
0~10% of F.S

10.00
0.00
0
0.01

0~100SEC
9999
-1999

3
10.00
0.00

0~100SEC

0~100SEC

0: hysteresis
1: hysteresisX2

omon Set Mode


SETTING VALUE
2.0~3.5
3.5~11.0
3.5~11.0
2~7
0

4. INVERTER(SV550iP5A)
1) CONNECTION TERMINALS

2) WIRING DRAWING

3) SETTING VALUE
CODE
01
02
DRV
03
04
23

FU1

FU2

I/O

VFD SETTING VALUE


Description
Acceleration Time
Deceleration Time
Drive Mode
Frequency Mode
Stop Mode

Setting value
30
30
Fx/Rx-1
I
FREE RUN

Unit
SEC
SEC
TERMINAL
TERMINAL
STOP

29
30
31
49
50
66
67
68

Power Source Freq


Maximum Frequency
Base Frequency
Input voltage adjustment
Motor Rated Voltage
Overload Trip Selection
Overload Trip Level
Overload Trip Delay Time

60
60
60
100
440
YES
110
5

Hz
Hz
Hz
%, 440V
Volt
Trip
%
SEC

40
41
43
06
07
09

Rated Motor Selection for inverter


Number of Motor Poles
Rated Motor Current (RMS)
Filtering Time Constant for I Signal Input
I Input Minimum Current
Filtering Time Constant for I Signal Input
Frequency Corresponding to

45
4
78.1
100
4
20

kW
P
A
mSEC
mA
mA

60

Hz

10

I Input Maximum Current