You are on page 1of 3

2/3/2016

PMU

PMU
Thepowermonitoringunit11A(PMU11A)providesthefollowingfunctions:powersystemmanagement,
batterymanagement,powermonitoring,andalarmreporting.

Exterior
Figure1showstheexteriorofaPMU11A.
Figure1ExteriorofaPMU11A

Functions
ThePMU11Aperformsthefollowingfunctions:
CommunicateswiththeupperleveldevicethroughanRS485serialport.
Managesthepowersystemandchargesanddischargesstoragebatteries.
Reportsalarmsrelatedtothedoorstatus,standbyBooleanvalues,andbatterytemperature.
Monitorspowerdistributionandreportsalarms.
CommunicateswiththebatterycabinetthroughanRS485serialport.

Ports
Figure2showstheportsonthefrontpanelofthePMU11A.
Figure2PortsonthefrontpanelofthePMU11A

Table1describestheportsonthefrontpanelofthePMU11A.
Table1PortsonthefrontpanelofthePMU11A
No.

Silkscreen

Connector

Remarks

GATE

2pinconnector

Connectstoadoor
statussensor

http://127.0.0.1:52199/hedex/hdx.do?lib=31185699&v=07&id=31185699_07_11475&tocURL=resources%252fhert%252fbts3900al%252fbts3900al%252dhard%25

1/3

2/3/2016

PMU

TEM_BAT

2pinconnector

Monitorsthebattery
temperaturesensor

COM_IN

RJ45connector

BBUcommunicationport
whichisconnectedto
theBBUor
communicateswiththe
upperlevelmonitoring
board

COM_OUT

RJ45connector

Lowerlevelmonitoring
board

COM_485

RJ45connector

Connectstothe
monitoringboardinthe
batterycabinet,and
receivesalarmsignals
fromthebatterycabinet.

Indicators
Table2describestheindicatorsonthePMU11A.
Table2IndicatorsonthePMU11A
Silkscreen Color

Meaning

Status

Meaning

RUN

Runningindicator

Steadyon

ThePMU11Aisperformingstartup,
selfcheck,loading,andactivation.

Blinking(onfor1s
andofffor1s)

ThePMU11Aisfunctionaland
communicatingwiththemaincontrol
boardintheBBUproperly.(Thisstatus
doesnotnecessarilymeanthatthe
PMU11Ahasbeenconfigured.)

Blinking(onfor
0.125sandofffor
0.125s)

ThePMU11Aisfunctionalbutunable
tocommunicateproperly.

Steadyoff

ThePMU11Aisfaultyorthereisno
DCpowersupply.

Steadyon

Alarmsaregenerated,andthemodule
mustbereplaced.

Steadyoff

Noalarmisgenerated.

Blinking(onfor1s
andofffor1s)

Analarmisgeneratedandyouneedto
locatethefaultbeforedetermining
whethertoreplacethePMU11A.

ALM

Green

Red

Alarmindicator

DIPSwitch
ThereisaDIPswitchontheleftpanelofthePMU11A.TheDIPswitchhaseightbits,wherethefourleast
significantbits(1,2,3,and4)definethemonitoringaddressofthePMU11A,andthefourmostsignificant
bits(5,6,7,and8)arenotdefinedbutreservedforfutureuse.
ONisindicatedby1,andOFFisindicatedby0.ThemonitoringaddressofthePMU11Aissetto3by
defaultbeforedelivery,asshowninFigure3.
http://127.0.0.1:52199/hedex/hdx.do?lib=31185699&v=07&id=31185699_07_11475&tocURL=resources%252fhert%252fbts3900al%252fbts3900al%252dhard%25

2/3

2/3/2016

PMU

Figure3DIPswitchontheleftpanelofthePMU11A

NOTE:
WhentwoPMU11AssharethesameRS485businthecasethattwoormoreAPM30Hsareconfiguredina
basestation,themonitoringaddressofthesecondPMU11Aissetto4.