You are on page 1of 35

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Brief Introduction for Automated Relay Testing


Kamin Dave
Application Engineer (Protective Relaying)

DOBLE ENGINEERING COMPANY

Protection Relay Testing:

Testing of Differential Protection


Relay type P632

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Details: P632


Two/Three Winding Differential Protection
relays
Inbuilt IDMTL & Inst. O/C function for backup
Protection
Low Impedance Restricted Earth Fault
Protection
Automatic calculation for TAP values based on
CTR
Settings for Transformer & CT vector group
compensations
2nd Harmonic content setting during inrush
period due to point on wave switching
DFT (Independent or Cross Blocking)

5th Harmonic content setting for Over excitation


phenomena
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Details: P632


MAKE
MODEL

: AREVA
: P632
Relay Settings:
Differential Element:
MVA = 20
VWDG1 = 132KV
VWDG2 = 66KV
TRCON = YY0.
CTCON = YY
ID> = 0.2
Turn Point2 = 2.0PU
ID>> = 5.0PU
SLP1 = 30%
SLP2 = 70%
PCT2 = 20.0%
PCT5 = 20%
In = 1A

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Details: P632


MAKE
MODEL

: AREVA
: P632

Relay Settings:
Differential Element:
CTR1 = 150
CTR2 = 300
Kam1 = 1.715
KCT2 = 1.715

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Details: P632


FLC on TR Primary side:
IFLC = (20*1000) / (1.7325*132)
= 87.45 Ampere
FLC on TR Secondary side:
IFLC = (20*1000) / (1.7325*66)
= 174.90 Ampere
CF1 = (1*87.45) / (150*1) = 0.58303
Kam1 = (1 / CF1) = (1/0.58303) = 1.715
CF2 = (1*174.90) / (300*1) = 0.58303
Kam2 = (1/CF2) = (1/0.58303) = 1.715

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Characteristic: Dual Slope

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Characteristic on Settings:

HS
SLP2=70%
SLP1=30%

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Characteristic: Dual Slope

Idiff@SLP1 = (ID)*(1-SLP1/2) + SLP1*(Ibias)


Idiff@SLP2 = (ID)*(1-SLP1/2) + SLP2*Ibias + (SLP1-SLP2)*Turn Point1

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Test Equipment

Make

: DOBLE

Model : F6150

Software

F6TesT Version 2.18-1026

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Test Circuit:
Source Configurations:
Six current sources
Winding 1 currents
Winding 2 currents

I1

IA
IB
IC

P632

I2
I3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Tests conducted:

Pickup test for Winding1

Pickup test for winding2

Slope Characteristic test

2nd Harmonic test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Winding Pickup Test


Use RAMP Module

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Winding Pickup Test:


Pickup Test for Winding1 (WDG1):Ipickup = (ID)*CF1
= (0.2)*0.58303

= 0.116A
Pickup Test for Winding2 (WDG2):Ipickup = (ID)*CF2
= (0.2)*0.58303

= 0.116A
Not need to enter correction factor for CTR matching. Relay will
Automatically adjust TAP value based on CTR
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Pickup Test: WDG1

WDG1 current sources

Expected value = 0.115A


Actual Test value = 0.114A
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Pickup Test: WDG2

WDG2 current sources

Expected value = 0.115A


Actual Test value
= 0.116AIs Power
Knowledge

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Slope Characteristic Test


Use DiffChar Module

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Slope Characteristic Test:


Star conn.

Star conn.

IP

Is

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Software
Configuration
Star conn.

YD1

YD1

Star conn.

YY0

Enter YD1 & YY0

Amplitude Compensation

GRT100
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

How to Adjust
Slope?

SLP2=70%
SLP1=30%

Enter Slope 30% & 70% based on relay setting


Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Bias current Formula:

Ibias = (IP+IS) / 2

Select Bias current (Ibias) formula from list


Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Select test points for test & click on Add Point to List
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Test results
Blue line shows
Expected curve

White line shows


Actual results on
Selected points

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Second Harmonics Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

%2nd Harmonics are


more during TR
Energization

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

2nd Harmonic Test : Test Method


50Hz +100Hz
Combine signal

I1

IA
IB
IC

P632

I2
I3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

2nd Harmonic Test : Trip/Block


2nd Harmonic content
35% of fundamental
Component &
Fundamental current
(0.1A) is less than
Idiff> (0.115A)

Relay blocked Trip


Command

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Harmonic Analysis bar


Shows Fundamental
Current is 0.1A
Harmonic Analysis bar
Shows % of 2nd Harmonic
is 0.035A

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Harmonic Analysis bar


Shows Fundamental
Component is 100%
Harmonic Analysis bar
Shows % of 2nd Harmonic
is 35%

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

2nd Harmonic Test : Trip/Block


2nd Harmonic content
35% of fundamental
Component &
Fundamental current
(0.125A) is more than
Idiff> (0.115A)

Relay issued Trip


Command

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Harmonic Analysis bar


Shows Fundamental
Current is 0.125A
Harmonic Analysis bar
Shows % of 2nd Harmonic
is 0.0437A

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

2nd Harmonic Test : Trip/Block


2nd Harmonic content
18.5% of fundamental
Component &
Fundamental current
(0.1A) is less than
Idiff> (0.115A)

Relay issued Trip


Command

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Harmonic Analysis bar


Shows Fundamental
Current is 0.1A
Harmonic Analysis bar
Shows % of 2nd Harmonic
is 0.0185A

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Harmonic Analysis bar


Shows Fundamental
Component is 100%
Harmonic Analysis bar
Shows % of 2nd Harmonic
is 18.5%

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery