December 2012
Sheet 14 014
General Description
VPI/VPE Dry-Type
Transformers
Application Description
Eatons VPI and VPE transformers
are custom-designed dry-type power
transformers, which give environmental protection, for both indoor and
outdoor applications. The transformers are explosion-resistant, fireresistant, non-polluting to the
environment, and ideally suitable for
use in coordinated unit substations.
Typical applications of VPI/VPE
transformers are:
Ventilation
Louvers
Fan Control/
Winding
Temperature
Indicator
Core-Coil
Assembly
Removable
Panel
Benefits
Ratings
14
112.53750 kVA
Primary voltages: 600V35 kV
Primary BIL: up to 150 kV
Secondary voltages: 120V15 kV
Secondary BIL: up to 75 kV
Temperature rise: 80/115/150C
CA08104001E
December 2012
Sheet 14 015
General Description
VPI/VPE Dry-Type
Transformers (Continued)
Optional Features
Accessories
Jacking pads
Ground pad
Diagrammatic nameplate
Provisions for rolling
Ventilation grilles
Core ground strap
Primary reconnectable taps
Future fan provisions on units
over 500 kVA
Core ground strap
ANSI 61 paint finish
Step-lap mitered core
NEMA 1 enclosure
Copper windings/bussing
(aluminum is standard)
VPE silicone resin vacuum pressure
impregnation and encapsulation
Fan cooling package, complete with
digital winding temperature
80C or 115C rise (150C rise is
standard)
Non-standard ambient temperature
(30C average/24-hour 40C
maximum is standard)
Non-standard altitude (up to
3300 ft (1006m) is standard)
Non-standard BIL level
NEMA 3R enclosure
Aluminum or copper ground bus
Lightning arresters
Low loss design (loss evaluation)
Special sound level
Wye-wye connected windings
UL label
Tests
The following tests are standard:
Induced potential
Applied potential
Resistance measurement
Ratio test
Polarity and phase relationship test
No load loss at rated voltage
Exciting current at rated voltage
Impedance and load loss
Quality control impulse
Special Tests
The following tests can be provided at
additional cost:
Temperature rise
ANSI impulse
Sound level
Witness
14
CA08104001E
15 kV 95 kV BIL Copper 80
Height
Width
Depth
Weight
Inches (mm)
Inches (mm)
Inches (mm)
Lbs. (kg)
113
90 (2286)
78 (1981)
60 (1524)
2250 (1022)
225
300
500
90 (2286)
90 (2286)
90 (2286)
78 (1981)
60 (1524)
78 (1981)
78 (1981)
60 (1524)
60 (1524)
2850 (1294)
3200 (1453)
750
1000
90 (2286)
90 (2286)
84 (2134)
84 (2134)
1500
90 (2286)
2000
2500
3000
Height
Width
Depth
Weight
Inches (mm)
Inches (mm)
Inches (mm)
Lbs. (kg)
113
90 (2286)
78 (1981)
60 (1524)
90 (2286)
90 (2286)
90 (2286)
90 (2286)
60 (1524)
90 (2286)
60 (1524)
2950 (1339)
4250 (1930)
4650 (2111)
4350 (1975)
225
300
500
96 (2438)
60 (1524)
66 (1676)
5450 (2474)
6250 (2838)
750
1000
90 (2286)
90 (2286)
102 (2591)
102 (2591)
66 (1676)
66 (1676)
6350 (2883)
8150 (3700)
66 (1676)
9200 (4177)
84 (2134)
66 (1676)
8150 (3700)
1500
102 (2591)
108 (2743)
66 (1676)
12,050 (5471)
90 (2286)
90 (2286)
96 (2438)
102 (2591)
66 (1676)
66 (1676)
9350 (4245)
11,050 (5017)
2000
2500
102 (2591)
112 (2845)
114 (2896)
126 (3200)
66 (1676)
66 (1676)
14,850 (6742)
18,550 (8422)
102 (2591)
108 (2743)
66 (1676)
112 (2845)
144 (3658)
66 (1676)
20,850 (9466)
kVA
kVA
Values listed are typical and should not be used for construction purposes.
Peak Load
in Hours
90%
(1)
70%
(1)
50%
(1)
1/2
1
2
3
1.56
1.37
(210)
(196)
1.64
1.42
(217)
(203)
1.71
1.45
(220)
(206)
1.27
1.19
(181)
(165)
1.29
1.21
(185)
(169)
1.30
1.21
(186)
(169)
1.14
(155)
1.14
(156)
1.15
(158)
Quality Assurance
Optional Tests:
UL
LISTED
93DO
DISTRIBUTION
TRANSFORMER
5. Temperature Test
Optional tests which are
routinely performed:
9. Seismic Qualification.
UL
LISTED
93DO
DISTRIBUTION
TRANSFORMER
given rating.
NUCLEAR 1E
CERTIFICATION
IEEE 323QUALIFIED
IEEE 344SEISMIC
LIFE
CERTIFICATION
Specifications
Self-Cooled
Power Rating
kVA
Primary
Voltage
kV
Primary BIL
kV
Secondary
Voltage
kV
Secondary BIL
kV
Temperature
Rise
C
112.5-10,000
Up through 35
Up to 150
Up through 15
Up to 75
80/115/150
1.
____ UL listing
2.
3.
Nuclear 1E certification:
rise
4.
5.
above 601 V
7.
8.
enclosure
6.
dry powder
9.
temperature monitor
Temperature Rise
Temperature
Rise
150C
115C
80C
Base
Rated
kVA
150C
Rise
kVA
Fan
Cooled
kVA
1000
1000
1000
1000
1150
1350
1333
1530
1800
ANSI C57.12.01
ANSI C57.12.91
ANSI N45.2-1977
UL
NRC 10CFR50 Appendix B
ISO 9001
NEMA ST20
CSA Z 299.3
When ordered with 115C rise, the VPE transformer (if specified)
will have a 115% continuous overload capability (153% with
fans). AA/FA/FA
MIL-I-45208A
Qualified for manufacture of Nuvlear Class 1-E, Safety Related
Transformers including IEEE 344 Certification.
Secondary Voltage
kVA 3-Phase
112 1/2
FanCooled
Ventilated
Dry
150
225
300
500
400
667
750
SelfCooled
Fan-Cooled
208Y/120 480Y/277
Weather
480
240
Resistant
Delta
Delta
Ventilated
X
X
X
X
X
400
X
X
kVA Correction
2400 Delta
4160Y /
2400
4160 Delta
Altitude
(FT)
Forced Air
(FA)
1.00
.994
.985
1.00
.989
.974
1.00
.975
.966
.959
.944
.92
7000
8000
.957
.929
.86
3300
4000
5000
BIL
Correction
VPE
(AA)
6000
.98
.95
.89
X
X
1000
667
1000
X
X
1000
1000
1500
2000
2500
3750
1333
1333
9000
.948
.914
.83
1333
2000
1333
2000
X
X
X
X
X
X
.939
.930
.898
.883
2666
3333
4687
2666
3333
4687
.921
.912
.903
.868
.853
.838
6250
9375
12,500
6250
9375
X
X
X
X
X
.80
.77
.75
.72
.70
5000
7500
X
X
10,000
11,000
12,000
13,000
14,000
15,000
.894
.823
.67
12,500
10,000
Self-Cooled
Equivalent
Two-Winding
(kVA)
0-9
Ventilated
(Class AA
Rating)
kVA
Class FA
and AFA
Rating
40
0-1167
67
10-50
51-150
45
50
1168-1667
1668-2000
68
69
151-300
301-500
501-700
701-1000
1001-1500
1501-2000
2001-3000
3001-4000
4001-5000
55
60
62
64
65
66
68
70
71
2001-3333
3334-5000
5001-6667
6668-8333
71
73
74
75
5001-6000
6001-7500
72
75
1
S
8.7
1
1
S
1
1
S
15.0
25.0
34.5
1
1
S
1
1
2
1
2
1
S
NOTES:
S = Standard value.
1 = Optional higher levels where exposure to overvoltage occurs
and improved protective margins are required.
2 = Lower levels where protective characteristics of applied surge
arresters have been evaluated and found to provide appropriate
surge protection.
Impedance Chart
kVA
ANSI Std.
112.5-500
None Specified
501 & Larger *
5.75%
* For Units with 60 kV Primaries and below.
8
ABB
5.75%
5.75%