You are on page 1of 24

Learning Module 6:

101 Basic Series

Medium Voltage Power Circuit Breakers

Medium Voltage Power Circuit Breakers


What You Will Learn

Well step through each of these topics in detail:


Introduction

Components
Frame
Operating Mechanism
Trip Unit
Trip Intelligence
Arc Extinguisher

4
5
5
5
6
7

Arc Extinguishing Technologies


Vacuum Interrupter Technology
Spiral Contacts
SF6 Gas Technology
Puffer-Type SF6 Gas Technology
Rotary Arc-Type SF6 Gas Technology

7
7
9
9
10
11

Review 1

12

Ratings
Ratings and Standards Vary
Maximum Voltage
Continuous Current

13
13
14
14

Enclosure and Mounting


Enclosure
Mounting
Fixed Mount
Drawout Mount

14
14
15
15
16

Standards

18

Helping the Customer


Circuit Breaker Details
Configuration and Accessory Details

19
19
19

Review 2

20

Glossary

21

Review 1 Answers

24

Review 2 Answers

24

Page 2

Medium Voltage Power Circuit Breakers


Welcome

Welcome to Module 6, which is about Medium Voltage Power Circuit Breakers.


By medium voltage, we mean a voltage range of 1000 volts to 38 kV. (Some consider 72.5 kV as the upper end of medium voltage, but we will work with 38 kV for
the purpose of this training module.)
Figure 1. Family of Medium Voltage Vacuum Circuit Breakers (ANSI and IEC Types)

Like the other modules in this series, this one presents small, manageable sections of new material followed by a series of questions about that material. Study
the material carefully, then answer the questions without referring back to what
youve just read.
You are the best judge of how well you grasp the material. Review the material as
often as you think necessary. The most important thing is establishing a solid
foundation to build on as you move from topic to topic and module to module.
A Note on Font Styles

Key points are in bold.


Glossary items are italicized and underlined the first time they appear.

Viewing the Glossary

Printed versions have the glossary at the end of the module. You may also browse
the Glossary by clicking on the Glossary bookmark in the left-hand margin.

Page 3

Medium Voltage Power Circuit Breakers


Introduction

To understand where the medium voltage power circuit breaker fits into the
scheme of things, you need to understand the basics of power distribution in an
industrial environment.
An industrial distribution system consists of:

metering devices to measure power consumption

main and branch disconnects

protective devices

switching devices to start and stop power flow

conductors

transformers

Power may be distributed through various Switchgear and Switchboards, transformers and Panelboards. The medium voltage power circuit breaker is found in
switchgear assembly. A switchgear assembly controls electric power circuits.
Figure 2. Typical Industrial Power Distribution

The Circuit Breaker is the main device the heart of the switchgear. It provides centralized control and protection of medium voltage power equipment and
circuits. Its operation covers load switching, control and fault protection for generators, motors, transformers, capacitors and all types of feeder circuits.
This type of power equipment is normally found in industrial, commercial
and electric utility installations. Typical applications include electric utility systems, industrial distribution systems, commercial buildings, municipal pumping
stations, and transportation systems.

Components

There are four main parts to a medium voltage power circuit breaker. These are:
Frame
Operating Mechanism
Trip Unit
Arc Extinguisher

Page 4

Medium Voltage Power Circuit Breakers


Figure 3. Typical Medium Voltage Vacuum Circuit Breaker
with Front Cover Removed, Exposing Operating Mechanism

Frame

A medium voltage power circuit breaker is essentially an assembly of parts on a


rugged metal Frame. Depending upon factors such as ratings and interrupting
method, they come in a variety of shapes, sizes and configurations.

Operating Mechanism

The medium voltage power circuit breaker uses a stored-energy Operating Mechanism to open the circuit breaker. It has a motor-charged, spring-type, storedenergy closing mechanism. Closing the breaker charges the accelerating springs.
Protective relays on the control switch energize a shunt trip coil to release the
accelerating springs and open the breaker.
This is a trip-free design truly mechanically and electrically trip free. Breaker
contacts will not touch or close onto a fault, even when a mechanical or electrical
close command is issued.
The manual controls are usually accessed from the front of the circuit breaker.
Although medium voltage power circuit breakers are electrically operated, the
closing springs can be charged manually.
For more on operating mechanisms, see Module 5, Fundamentals of Circuit
Breakers.

Trip Unit

A Trip Unit is typically integral to a circuit breaker. But, the medium voltage
power circuit breaker uses externally mounted trip units to provide the operational intelligence. These devices are called Protective Relays.
The protective relays are normally wired to the circuit breaker and Current Transformers. They are mounted on a panel or door of the switchgear assembly. They
function to detect a defective line or apparatus, as well as dangerous or undesirable system conditions. The relay energizes the trip coil of the circuit breaker to
clear a fault.

Page 5

Medium Voltage Power Circuit Breakers


Figure 4. Typical Medium Voltage Switchgear Assembly with Protective Relays and
Other Devices Shown Mounted on Compartment Doors

Trip Intelligence

The protective relay intelligence devices fall into two broad categories. These are:
ElectromagneticThe electromagnetic protective relay has been used widely in
the industry for many years, with a high degree of success. It functions to tell
the circuit breaker when to operate, based on the specific relay type selected.
Many different types of electromagnetic protective relays are available, and each
type performs rather specific functions.
Common relay types include: instantaneous overcurrent, time overcurrent
and overvoltage. Because these devices are limited in scope, a number of different relays (each with different protective capabilities) must be used to provide a
comprehensive protective package.
Microprocessor-BasedThe microprocessor-based protective relay is a
multi-function device. It can provide all the features of several electromagnetic
relays in one box. It is also easier to mount and wire. Overall, it is a smaller investment than an electromagnetic protective relay solution.
Figure 5. Typical Medium Voltage Switchgear Assembly with
Microprocessor-Based Devices Shown Mounted

In most cases, only one device is required for each three-phase circuit, not
one device for each phase. One of the more sophisticated microprocessorbased protective relays is capable of replacing the normal complement of three or
four electromagnetic relays, as well as a number of associated meters and
switches (Figure 6).

Page 6

Medium Voltage Power Circuit Breakers


Figure 6. Typical Sophisticated Microprocessor-Based Protective Relay

Because these are individual devices, apart from the medium voltage circuit
breaker itself, there will be no further discussion of the tripping intelligence in this
module.
Arc Extinguisher

The Arc Extinguisher extinguishes the Arc produced when the contacts are
pulled apart to interrupt current flow. The higher the voltage, the harder it is to
interrupt the flow of current.
There are a number of arc extinguishing technologies in use today. We will look at
the most prominent types in the next section.

Arc Extinguishing
Technologies

In a low voltage circuit breaker, using air or Arc Chutes is sufficient to extinguish
an arc. In the medium voltage range, a different technology needs to be used. The
main technology used today is the Vacuum Interrupter.

Vacuum Interrupter
Technology

The vacuum interrupter (VI) was briefly discussed in Module 5, Fundamentals of


Circuit Breakers.
Figure 7. Schematic for a Typical Vacuum Interrupter

Basically, the vacuum interrupter is a pair of separable contacts (called primary contacts) enclosed in a vacuum-tight envelope. The Envelope itself is a
ceramic material, with a metal end plate brazed to each end. The metal plates
seal the ends and provide support for the parts inside.
Of the two contacts (also called electrodes) inside, one is fixed. The other is
movable, through a bellows-type connection. Various shields inside the envelope
provide different types of protection to interrupter parts.

Page 7

Medium Voltage Power Circuit Breakers


Figure 8 depicts the important arcing and interruption phenomena within a vacuum.
Figure 8. Interruption in a Vacuum

When the circuit breaker is closed, the contacts within the interrupter touch, allowing current to flow.
When a fault occurs and interruption is required, the contacts are quickly
separated and an arc forms. An arc is formed because the voltage tries to keep
the current moving.
Figure 9. Enclosing Contacts in a Vacuum

The arc burns in the metal vapor evaporated from hot spots on the contact surfaces. This metal vapor continuously leaves the contact region and recondenses
on the contact surfaces and surrounding metal shield, which protects the ceramic
envelope.
At Current Zero, the arc extinguishes, contact vapor production stops, and the
original vacuum condition is restored. Current zero is a point in the AC current
sine wave where the value is zero.
Figure 10. Current Zero Points in an AC Cycle

The vacuum in the envelope is considered a Dielectric. The Dielectric Strength is


the maximum voltage the dielectric can withstand without breaking down. The
Transient Recovery Voltage (TRV) is the most severe waveform the interrupter will

Page 8

Medium Voltage Power Circuit Breakers


have to withstand. This is why the speed of the dielectric recovery and the
strength of the dielectric inside the interrupter are critical issues for successful circuit interruption. If the dielectric does not reach sufficient strength fast
enough, the arc will re-ignite.
Vacuum interrupters for circuit breaker duty must be capable of interrupting currents of 12 to 50 kA (and up), at voltages up to 38 kV (Figure 11).
Figure 11. Rear View of Circuit Breaker with
Vacuum Interrupters Installed (One Per Phase)

Spiral Contacts

A newer technology is now being used in the vacuum interrupter. It involves


using spiral-shaped copper-chrome contacts inside the vacuum tube. They
provide a self-induced magnetic effect that moves the arc root around the contact
periphery. This very efficient arc control method prevents hot spots, minimizing
contact erosion.
Figure 12. Spiral Contacts

SF6 Gas Technology

Another arc extinguishing technology is SF6 (sulfur hexafluoride) technology. It is


popular outside the United States. It is specifically associated with European manufacturers of medium and higher voltage circuit breakers.
SF6 technology was briefly discussed in Module 5, Fundamentals of Circuit
Breakers. The main contacts are enclosed in a chamber of SF6 gas, which happens to be a very good dielectric (Figure 13).

Page 9

Medium Voltage Power Circuit Breakers


Figure 13. Enclosing Contacts in SF6 Gas

In short, this arc interruption technology results the in arc energy being used and
absorbed, while the arc is simultaneously cooled.
There are several SF6 interrupter designs, but only two types will be covered
here:

Puffer-Type SF6 Gas


Technology

Puffer

Rotary Arc

The puffer-type of SF6 interrupter is the older of the two SF6 technologies. It is
more capable but more complicated than the rotary arc-type.
The interrupter is shown below in the closed position, and in the opening
sequence.
Figure 14. Typical SF6 Puffer Interrupter in Closed Position

Figure 15. Typical SF6 Puffer Interrupter During Opening Sequence


High Current Arc on Left and Near Current Zero on Right

Page 10

Medium Voltage Power Circuit Breakers


During current interruption, a piston compresses the SF6 gas in a cylinder, all of
which is enclosed in an epoxy-type enclosure. After the main current-carrying
contacts part, the current transfers to the arcing contacts. Once the arcing contacts part, the SF6 gas in the compression chamber blasts the arc through
the nozzle. The heat created by the arc breaks the SF6 molecules into fluorine
and sulfur. Arc energy is absorbed and the arc is cooled.
As current zero is approached, the heat energy subsides as more SF6 gas enters
the system. At current zero, the high-pressure SF6 gas flows through the nozzle
and extinguishes the arc.
Compressing the SF6 gas requires significant mechanical energy. A circuit
breaker equipped with this type of technology requires a higher-energy operating
mechanism than is required by an equivalent vacuum circuit breaker. In addition,
this interrupter type has a large number of parts.
Rotary Arc-Type SF6 Gas
Technology

Rotary arc SF6 technology is less complicated in design than the puffer
type. It has fewer parts and does not require such a high-energy operating mechanism. However, it is not effective over as wide a range of short circuit currents
and voltages as the SF6 puffer or vacuum. Suitable applications are somewhat
limited.
Figure 16 shows a typical SF6 rotary arc interrupter.
Figure 16. Cross-Sectional View of Typical SF6 Rotary Arc Interrupter

As the contacts part, the arc transfers from the main contacts to an annular contact. This causes the current to switch into the coil behind it. The coils magnetic
field, produced by the load current itself, causes the arc to rotate rapidly.
The arc is cooled by moving through the SF6 gas.
The SF6 gas is normally at rest inside this interrupter. The arcs movement acts
like a mixer, mixing hotter and cooler gas. This helps cool the arc. Contact erosion is also reduced due to this rapid arc movement.
As current zero is approached, the dwindling arc must sustain enough speed to
be lost in the SF6 environment in order to withstand the transient recovery voltage.
(This is mentioned because the magnetic field produced by the load current
causes the all important arc rotation. As the current decreases, the magnetic field
decreases, and the arc rotation slows.)
At current zero, the arc is cooled and extinguished.

Page 11

Medium Voltage Power Circuit Breakers


Review 1

Answer the following questions without referring to the material just presented.
Begin the next section when you are confident that you understand what youve
already read.
1. The ________ ________ is the heart of the switchgear.
2. There are four main parts to a medium voltage power circuit breaker. These
are:
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
3. A microprocessor-based trip intelligence is superior to an electromagneticbased trip intelligence. In your own words, explain why.
_____________________________________________________________
_____________________________________________________________
_____________________________________________________________
4. Vacuum interrupters for circuit breaker duty must be capable of interrupting
currents of ___ to ___ kA (and up), at voltages up to ___ kV.
5. SF6 arc extinguishing technology is popular outside the United States. The
two mostly commonly used types are __________ and __________
__________.

Page 12

Medium Voltage Power Circuit Breakers


Ratings
Ratings and Standards
Vary

Medium voltage power circuit breaker ratings vary in different parts of the
world. As a matter of fact, medium voltage is not uniformly defined around the
world. Although the standard we are using in this training module defines medium
voltage as 1000 volts to 72.5 kV (a commonly accepted medium voltage range in
the United States, as well as other parts of the world), one foreign country considers 1000 volts and above to be high voltage.
Medium voltage power circuit breaker ratings charts specify many different
types of ratings. Usually, a chart indicates the ratings required by the governing
standards where the circuit breaker is applied.
ANSI or IEC is normally the governing standard for medium voltage power circuit
breakers. ANSI is associated with U.S. standards, and IEC is associated with
international standards. However, neither the standards nor the ratings charts are
identical. Charts also vary from manufacturer to manufacturer (Figures 17 and
18). To give an idea of the differences, consider the following example.
Figure 17. Partial Sample of a Medium Voltage ANSI Ratings Chart

Breaker Type

Medium Voltage
(kA rms)

270VCP-W750

27

270VCP-W1000

27

270VCP-W1250

27

Continuous
Current (Amps)
600
1200
2000
600
1200
2000
600
1200
2000

Short Circuit
Current (kA rms)
16

22

25

Figure 18. Partial Sample of a Medium Voltage IEC Ratings Chart

Voltage Class
(kA rms)

Breaker Type
240VCP-W16

24

240VCP-W20

24

240VCP-W25

24

Normal Current
(Amps)
630
1250
2000
630
1250
2000
630
1250
2000

Short Circuit
Current (kA rms)
16

20

25

All of the indicated ratings are important. A number of them are merely calculations. For the sake of this discussion, we will cover only three of them.
These are:

Maximum Voltage

Continuous Current

Page 13

Medium Voltage Power Circuit Breakers

Short Circuit Current

These three ratings are common to both ANSI- and IEC-rated circuit breakers. In
most instances, a grasp of these three ratings will allow you to assist a customer
with a medium voltage power circuit breaker selection.
Maximum Voltage

This is the maximum voltage at which the breaker can operate. It is termed
Maximum Voltage on ANSI charts and Voltage Class on IEC charts. The operating
voltage where the circuit breaker is applied should not exceed the circuit breakers
rated maximum voltage.
Typical maximum voltage ratings encountered with ANSI applications are: 4.76,
8.25, 15, 27 and 38 kV. Typical voltage classes encountered with IEC applications
are: 3.6, 7.2, 12, 17.5 and 24 kV.

Continuous Current

This is the amount of current the breaker can carry continuously at 60


cycles without exceeding the temperature rise limit. It is termed Continuous
Current on ANSI charts and Normal Current on IEC charts. This maximum rating
should always be in excess of the utilization equipment rating to provide for a
short-time overload capability.
Typical continuous current currents encountered with ANSI applications are: 600,
1200, 2000 and 3000 amps. Typical normal currents encountered with IEC applications are: 630, 1250 and 2000 amps.

Short Circuit Current

This is the level of three-phase short circuit current that the circuit breaker
can safely interrupt. The Short Circuit Current is a rating at the circuit breakers
maximum voltage (ANSI) or voltage class (IEC).
Typical short circuit currents encountered with ANSI applications are: 16, 29, 33,
37 and 63 kA. Typical short circuit currents encountered with IEC applications are:
16, 25, 31.5, and 40 kA.

Enclosure and
Mounting
Enclosure

The medium voltage power circuit breaker is always placed in a switchgear


assembly. The switchgear assembly is usually referred to as a Metal-Enclosed
Assembly. The phrase metal-clad means that compartments within the switchgear assembly are separated by metal barriers (Figure 19).
Figure 19. Typical Medium Voltage Metal-Clad Assembly Structure with
Two Vacuum Circuit Breakers (Side View)

Page 14

Medium Voltage Power Circuit Breakers


This is different from a metal enclosed assembly, where the equipment is
enclosed, but not necessarily separated by barriers. The metal enclosed assembly is typically associated with low voltage equipment.
Figure 20. Typical Vacuum Switchgear Assembly with One Circuit Breaker in
Upper Compartment and One Below with Door Closed

Mounting

Fixed Mount

There are two methods for mounting a circuit breaker in the switchgear. These
are:

Fixed Mount

Drawout Mount

Fixed Mount circuit breakers are usually found in outdoor applications. When
installed outdoors, a special type of housing must be provided to protect the
equipment from the elements. This outdoor protection is provided in a number of
ways.
Fixed medium voltage power circuit breaker designs exist for a limited range of
applications and voltages.

Page 15

Medium Voltage Power Circuit Breakers


In the Workplace
This outdoor substation utilizes fixed medium voltage power circuit breakers to
perform a series of capacitor switching functions.
Fixed Medium Voltage Power Circuit Breaker
Installed in Outdoor Enclosure

Each breaker must be housed in a weatherproof enclosure to protect it from the


elements.
Drawout Mount

The Drawout Mount (or removable) type is by far the most common medium
voltage power circuit breaker in use. It is used almost exclusively through 38 kV.
Prior to the introduction of vacuum designs, medium voltage power circuit breakers were much larger (Figure 21). For example, one vertical structure could
accommodate one Magnetic Air Type Circuit Breaker. The circuit breaker was
removable, typically rolled out of the structure on wheels.
Figure 21. Typical Medium Voltage Magnetic Air Circuit Breaker (Front Barrier Removed)

Today, medium voltage power circuit breakers are frequently small enough to be
stacked two units high in one vertical compartment.
The circuit breaker has three positions: DISCONNECT, TEST and CONNECT.
Normally, the circuit breaker is manually pushed to the TEST position, then
mechanically levered between the TEST and CONNECT positions (Figure 22).

Page 16

Medium Voltage Power Circuit Breakers


The secondary and primary electrical connections are automatically connected or
disconnected as the circuit breaker is levered from one position to another.
Figure 22. Medium Voltage Vacuum Circuit Breaker
Being Mechanically Levered Into Its Structure

Most drawout medium voltage power circuit breakers can be completely


removed from their compartments onto integral extension rails (Figure 23).
This feature makes the task of inspecting the circuit breaker and the compartment
much simpler.
Figure 23. Medium Voltage Vacuum Circuit Breaker
Shown Removed From Compartment on Extension Rails

If the circuit breaker must be lifted from the extension rails onto the floor, integral
wheels permit it to be rolled around outside of its structure.

Page 17

Medium Voltage Power Circuit Breakers


Standards

The testing required and the standards that must be met by a medium voltage power circuit breaker depend on the area of the world where the circuit
breaker is applied.
A medium voltage power circuit breaker must meet the requirements of ANSI,
IEC, IEEE and NEMA to be considered world-class (Figure 24).
Figure 24. Dominant Worldwide Standards

In addition, UL is an important consideration in certain local areas.


Standards and testing to prove compliance are rather stringent. This is
because of the voltage and current levels associated with medium voltage equipment under abnormal (and even normal) operating conditions.
The testing goes beyond just testing the circuit breaker itself. Because a
medium voltage power circuit breaker must function properly with a compatible
housing, it is tested separately and in combination with the structural assembly.
For this reason, most circuit breaker manufacturers are also switchgear assembly
manufacturers.

Page 18

Medium Voltage Power Circuit Breakers


Helping the
Customer

Circuit Breaker Details

Now you should be ready to assist a customer in matching a product to an application. When you meet with the customer, conduct a short interview to obtain
information in these two areas:

Circuit Breaker Details

Configuration and Accessory Details

Before you can select a specific circuit breaker, get the following information from
the customer:

Which set of standards (ANSI or IEC) apply to the circuit breaker?

What maximum voltage (ANSI) or voltage class (IEC) is required?

What continuous current (ANSI) or normal current (IEC) is required?

What short circuit current is required?

This information alone should be enough to allow you to select an appropriate circuit breaker. However, the more information you have, the better.
Configuration and
Accessory Details

It is also important to know how the circuit breaker is to be configured. Ask the
customer these three questions:

Will the circuit breaker be drawout or fix mounted?

Will the circuit breaker be used indoors or outdoors?

Will circuit breakers be stacked two to a vertical structure, or mounted one per
structure?

Medium voltage circuit breakers do not normally have a large number of accessory items. However, you should make yourself aware of anything additional the
customer expects.

Page 19

Medium Voltage Power Circuit Breakers


Review 2

Answer the following questions without referring to the material just presented.
1. For each rating type, identify it as being ANSI, IEC, or both.
Normal Current __________
Short Circuit Current __________
Maximum Voltage __________
2. In your own words, explain the difference between a metal-clad assembly and
a metal enclosed assembly.
_____________________________________________________________
_____________________________________________________________
_____________________________________________________________
3. There are two methods for mounting a circuit breaker in the switchgear.
These are:
____________________________________________________________
____________________________________________________________
4. A medium voltage power circuit breaker must meet the requirements of
______, ______, ______ and ______ in order to be considered world-class.
5. There are seven main questions to ask a customer when attempting to match
a product to an application. Name three of them.
____________________________________________________________
____________________________________________________________
____________________________________________________________

Page 20

Medium Voltage Power Circuit Breakers


Glossary
ANSI

American National Standards Institute. It was organized


to simplify and standardize production and construction.

Arc

The effect generated when current is forced to be


interrupted between two contacts.

Arc Chute

A component of the arc extinguisher in a low voltage


circuit breaker. It elongates and cools an arc.

Arc Extinguisher

A component of a circuit breaker. It actually interrupts


the flow of current.

Circuit Breaker

A reusable overcurrent protection device. After tripping


to break the circuit, it can be reset to protect the circuit
again.

Continuous Current

The amount of current the breaker can carry


continuously at 60 cycles without exceeding the
temperature rise limit, according to ANSI charts.

Current Transformer

A step-down transformer that steps down supplied


current to a current usable by control components such
as relays and meters.

Current Zero

Also Zero Point. A point in the AC current sine wave


where the value is zero.

Dielectric

The insulating medium between two contacts. Typical


dielectrics are air, gas, ceramic or gas and ceramic. A
vacuum is the only perfect dielectric.

Dielectric Strength

The maximum voltage a dielectric can withstand without


breaking down.

Drawout Mount

A mounting type for medium voltage power circuit


breakers in which the breaker can be completely
removed from its compartment onto integral extension
rails.

Envelope

Main component of a vacuum interrupter. A sealed,


evacuated ceramic enclosure, with a metal end plate
brazed to each end.

Fixed Mount

A mounting type for medium voltage power circuit


breakers in which the breakers are fixed in place.
Usually found in outdoor applications.

Frame

A component of a medium voltage power circuit breaker.


Its primary function is to provide a rigid, mechanically
strong, insulated housing in which the other components
are mounted.

IEC

Abbreviation for International Electro-technical


Commission. This organization is associated with
equipment used internationally.

IEEE

Institute of Electrical and Electronic Engineers. A


professional organization of scientists and engineers
whose purpose is the advancement of engineering.

Magnetic Air Type


Circuit Breaker

A type of medium voltage power circuit breaker no


longer in common use.

Page 21

Medium Voltage Power Circuit Breakers


Maximum Voltage

The highest voltage at which the breaker can operate,


according to ANSI charts. The operating voltage where
the circuit breaker is applied should not exceed the
circuit breakers rated maximum voltage.

Medium Voltage
A specific type of circuit breaker, used in a switchgear
Power Circuit Breaker assembly, with a voltage range of 1000 volts to 38 kV.
Metal-Clad Assembly Equipment in the assembly is enclosed, and separated
by metal barriers into individual compartments. Typically
associated with medium voltage equipment.
Metal-Enclosed
Assembly

Equipment in the assembly is enclosed, but not


necessarily separated by barriers. Typically associated
with low voltage equipment.

NEMA

Abbreviation for National Electrical Manufacturers


Association. An organization of manufacturers of
electrical products.

Normal Current

The amount of current the breaker can carry


continuously at 60 cycles without exceeding the
temperature rise limit, according to IEC charts.

Operating
Mechanism

Opens and closes the contacts of a circuit breaker.

Panelboard

A wall-mounted electrical power distribution device for


use in commercial and industrial applications. It
provides circuit control and overcurrent protection for
light, heat or power circuits.

Protective Relay

The specific trip unit used with a medium voltage power


circuit breaker. Functions to detect a defective line or
apparatus, as well as dangerous or undesirable system
conditions.

SF6

An arc extinguishing technology involving the use of


sulfur hexafluoride gas.

Short Circuit Current A rating of the level of three-phase short circuit current
that the circuit breaker can safely interrupt. The short
circuit current is a rating at the circuit breakers
maximum voltage (ANSI) or voltage class (IEC).
Switchboard

A floor-standing electrical power distribution device for


use in commercial and industrial applications. It divides
large blocks of electrical current into smaller blocks of
current used by electrical equipment.

Switchgear

An assembly of switching and interrupting devices,


along with control, metering, protective and regulating
equipment.

Transient Recovery
Voltage

The most severe waveform the vacuum interrupter will


have to withstand.

Trip Unit

brain of a circuit breaker.

UL

Underwriters Laboratory. An independent laboratory that


tests equipment to determine whether it meets certain
safety standards when properly used.

Page 22

Medium Voltage Power Circuit Breakers


Vacuum Interrupter

An arc extinguishing technology. Features a pair of


separable contacts enclosed in a vacuum-tight
envelope. Because the environment inside the
interrupter envelope is a vacuum, an arc cannot be
sustained easily.

Voltage Class

The highest voltage at which the breaker can operate,


according to IEC charts. The operating voltage where
the circuit breaker is applied should not exceed the
circuit breakers rated voltage class.

Page 23

Medium Voltage Power Circuit Breakers


Review 1 Answers

1. Circuit breaker
2. Frame
Operating Mechanism
Trip Unit
Arc Extinguisher
3. Answer should basically say: The microprocessor-based protective relay is a
multi-function device. It can provide all the features of several electromagnetic
relays in one box. It is also easier to mount and wire. Overall, it is a smaller
investment than an electromagnetic protective relay solution.
4. 12, 50, 38
5. Puffer, Rotary Arc

Review 2 Answers

1. IEC
Both
ANSI
2. Answer should basically say: A metal-clad assembly has internal compartments which are separated by metal barriers. A metal enclosed assembly
does not necessarily have internal separation barriers
3. Fixed mount, Drawout mount
4. ANSI, IEC, IEEE and NEMA
5. Any three of the following:
Which set of standards (ANSI or IEC) apply to the circuit breaker?
What maximum voltage (ANSI) or voltage class (IEC) is required?
What continuous current (ANSI) or normal current (IEC) is required?
What short circuit current is required?
Will the circuit breaker be drawout or fix mounted?
Will the circuit breaker be used indoors or outdoors?
Will circuit breakers be stacked two to a vertical structure, or mounted one per
structure?

Page 24