AIR COOLED CONDENSING UNITS

SERIE UMC/E
Cooling and heating split systems
for comfort and process application

50 - 400 KW

UMC/E AIR COOLED CONDENSING UNITS

Range overview
UMC/E = cooling only
UMC/E-HP = heat pump
The Bini Clima air cooled compact condensing units offer cooling capacities from 50-400 kW.
The UMC/E range is designed to be quiet, energy efficient and easy to install. Its at the forefront of market technology and specially developed for split system applications. Modular construction and improved range of options
ensure there is a unit for every application. The UMC/E range is ideally applicable to a variety of environments, from
large retail outlets to high tech environments and from process to comfort applications. All models offer the benefits
and reliability of multiple scroll compressor technology, in an efficient dual refrigeration circuit system providing two
or four stages of cooling for improved energy efficiency during part load conditions. The range includes the UMC/E
& UMC/E-HP models which are reversible for heat pump operation. The complete range is available with low noise,
super low noise, low ambient temperature and many other options, making the UMC/E series the most flexible on
the market.
Integrated Intelligent Controls allows efficient operating which can be integrated into a wide range of BMS systems
by using interface cards or gateways. Combine all this with modulating head pressure control and high efficiency
heat exchangers ensures the lowest possible life cycle costs.
Key features
50 to 400 kW Cooling capacity
18 unit sizes, wide range of options
Scroll compressor technology
R407C refrigerant as standard
R410A & R134a upon request

Key benefits
Energy Efficient split system
Suitable for most of AC applications
High quality and reliability
Easy to install and maintain
Quiet operation

Typical applications

Office buildings

Commercial centers

Airports

Data centers

Pharma industry

Food & Beverages

UMC/E AIR COOLED CONDENSING UNITS

Certifications

The UMC/E units are designed, manufactured and tested


in compliance with the ISO 9001 quality management and
according to CE (89/392) regulations.
UMC/E and UMC/E-HP units also meet the following European directives:
EN 12055 (Chiller performances)
PED (Devices under pressure)
IEC 204-1 CEI 44-5 (Electric regulations)
CEI - EN 60204-1 (General safety regulations )
73/23/EEC (Low voltage directive)
98/37/EC (Machines directive)
89/336/EEC (Electro-magnetic compatibility)
All units are delivered with factory test certificate and CE
marking of conformity to the European safety rules.
For hazardous areas, the UMC/E units can be designed
and manufacture to meet ATEX requirements. For more
information, please contact your local representative.

ATEX

Typical installation

UMC/E AIR COOLED CONDENSING UNITS

Standard features

Housing
The units are designed for outdoor installation. The unit housing is made from galvanized steel protected against
corrosion with an epoxy paint, color RAL 9010.
Upon request, the structure can be reinforced with anodized aluminum profiles, tightly secured to a strong base
frame to allow an easy lifting of the unit with hooks. The distribution of weight is uniform for an easy positioning on
site.
All electric and control devices are fitted into the electric panel fixed on the unit side and provided with a main switch.
Compressors
UMC/E & UMC/E-HP units are equipped with orbiting, rotary Scroll compressors. Thanks to the reduced quantity of
parts in motion and to the absence of suction/delivery valves, these compressors are extremely silent and are fit for
applications with low/average capacity.

Air Exchangers
Highly efficient condensing coils are made of copper tubes and mechanically expanded into aluminum fins.

Fans
Low noise and water proof axial type fans, protected with safety grid are used on the condensing coil side. Fan motors are directly coupled thus reducing vibrations and transmission failures. Motors are IP 54 and class F insulated
and are protected from voltage peaks with magneto-thermic switches installed into the electric panel placed on
machine side.
Unit Controller
Advanced digital controller allows intelligent control of compressors and fan as well as full communication to BMS
systems.

UMC/E AIR COOLED CONDENSING UNITS

Standard options

1 Pressure transducer (only HP versions)


detect the unit operating pressure, manages defrost and
fan speed control functions

2 Thermostatic expansion valve (optional)


modulates the condensed refrigerant (provided disassembled)
3 Electronic expansion valve (optional)
modulates the condensed refrigerant (provided disassembled)

4 Liquid receiver (standard HP versions)


works like a storage tank on the refrigerant circuit
5 Liquid separator (standard HP versions)
separates the vapour from the condensed, it is collocated at the compressor aspiration.

4
5

6 Fans speed control (optional)


controls the condensation (or evaporation in heat pump),
it reduces the active power absorbed and the noise
7 Compressor faucet valves (optional)
isolate the compressor from the refrigerant circuit

8 Rubber anti-vibration isolators (optional)


reduce the vibrations transmission to the building structure
9 Condenser guard wire grids (optional)
it protects the operators near the finned coil
10 Heat recovery plate heat exchanger (optional)
allows energy recovery from the condensers to hot water
11 Low noise version (optional)
sandwich panel with additional acoustic isolation
12 Super low noise version (optional)
sandwich panel enhanced acoustic isolation on the compressor
Operating kit up to -25C external air temperature (optional only for HP versions)
allows to the chiller to operate with external temperatures
up to -25C.

9
10
11
12

UMC/E AIR COOLED CONDENSING UNITS COOLING ONLY


Performances - UMC/E 50 to 120 KW

Unit size
Cooling capacity
Power absorbed
E.E.R.

kW
kW
kW

50
49,6
14,6
3,4

60
57,3
16,4
3,5

65
65
18,8
3,4

Refrigerant
Compressors

Fans

120

97,6
27,8
3,5

123
35,1
3,5

2
2
2
2

2
2
2

2
2
2

2
2
2

2
2
2

2
2
2

2
2
2
2

kW

1,8

1,8

3,6

3,6

3,6

3,6

3,6

mm
rpm
m/s
C

800
900
4,2

800
900
4,84

800
900
5,48

800
900
8,29

800
900
10,43

dB(A)

67

67,5

67,5

71,5

71,5

71,5

72

2x12
2x22

2x12
2x22

2x16
2x28

2x16
2x28
+15 C
+45 C

2x16
2x28

2x22
2x35

2x22
2x35

Liquid Lime
Suction Lime
Min ambient temperature
Max ambient temperature

800
800
900
900
6,33
7,21
35
Turbolenced fins - Pipes striped inside

Out of standard unit sizes and


conditions on request available!

100

nr
nr
%
nr

Condensing coils
Sound pressure level at 1 m distance
in free field (ref. 2x 10-5)

85
85
24,4
3,5

Scroll

Type
Quantity
Cooling circuits
Partializing steps
Axial type
Nominal absorbed
power
Diameter
Revs
Total air flow
Ambient temperature

75
74,8
21,4
3,5
R407C

UMC/E AIR COOLED CONDENSING UNITS COOLING ONLY


Performances - UMC/E 135 to 400 KW

135
137,2
39,2
3,5

145
147,4
42,2
3,5

2
1
2
3

2
1
2

170

195

220

245

275

295

340

370

400

170
48,6
3,5

195
55,7
3,5

220
63,4
3,5

246
70,3
3,5
R407C

274,4
78,4
3,5

298,8
84,2
3,5

340
97
3,5

370
105,7
3,5

400
115
3,5

Scroll

2
2
2
3

2
2
2
4

2 Tandem
2
4
4

2 Tandem 2 Tandem 2 Tandem 2 Tandem 2 Tandem 2 Tandem


2
2
2
2
2
2
4
4
4
4
4
4
4
6
6
6
8
8

5,4

5,4

5,4

7,2

7,2

800
900
11,65

800
900
12,52

800
900
16,13

800
900
16,59

800
900
18,73

72

73

73

75

75

75

75

2x22
2x35

2x22
2x35

2x28
2x42

2x28
2x42

2x28
2x42

2x28
2x54
+15 C
+45 C

2x35
2x54

7,2

10,8

10,8

10,8

14,4

14,4

800
800
800
900
900
900
20,87
23,29
25,05
35
Turbolenced fins - Pipes striped inside

800
900
32,26

800
900
36,26

800
900
42,5

75

77

77

80

2x35
2x54

2x35
2x64

2x35
2x64

2x42
2x64

UMC/E-HP AIR COOLED CONDENSING UNITS WITH HEAT PUMP

Performances - UMC/E-HP 50 to 120 KW


Unit size

Heating pump

Electric data

50

60

65

75

85

100

120

Heating capacity

kW

66

73,7

83,8

96,2

109,4

125,4

158,1

Absorbed power

kW

14,6

16,4

16,8

21,4

24,4

22,8

35,1

Ambient temperature

Voltage 1

3ph/400V/50Hz

Nominal current 2

3,47

39,7

48,4

52,2

60,8

69,4

81,4

Current absorbed by compressors

36,4

41,6

46,8

53,2

62,4

72,8

88,6

Current absorbed by fans

3,7

3,7

7,4

7,4

7,4

7,4

7,4

Current absorbed by the unit 3

40,1

45,3

54,2

60,6

69,8

80,2

96

Starting current 4

149,2

194,2

202,9

204,8

294,1

298,4

339,4

Current for cable sizing

61,7

67,7

77,4

77,4

87,4

123,4

127,4

Starting current: LRA (Locked Rotor Ampere)


Current with full operation of motos: FLA (Full Load Ampere)
1
2

Voltage tolerance allowed: +/-10%. Phases imbalance allowed: +/-3%


Nominal current values are based on inlet/outlet temperature to the evaporator of 25/13 C and
ambient temperature of 35 C.
Starting current of bigget compressor + nominal current absorbed by t he other compressors +
current absorbed by fans
FLA of compressors + current absorbed by fans

Out of standard unit sizes and


conditions on request available!

UMC/E-HP AIR COOLED CONDENSING UNITS WITH HEAT PUMP


Performances UMC/E-HP 135 to 400 KW
135

145

170

195

220

245

275

295

340

370

400

176,4

189,8

218,6

250,9

284

316,3

352,8

379

437

425,7

515

39,2

42,2

48,5

55,7

63,4

70,3

76,4

84,2

97

105,7

115

7,0
3ph/400V/50Hz
94,3

100,5

135,9

160,4

162,8

192

219,8

234,6

221,8

320,8

345,8

98,8

106,2

124,8

145,6

148

177,2

197,6

212,4

249,6

220

293,6

11,1

11,1

11,1

14,8

14,8

14,8

22,2

22,2

22,2

29,6

29,6

109,9

117,3

135,9

160,4

162,8

192

219,8

234,6

274,8

299,6

323,2

402,7

405,8

351,2

367,8

414,8

420,8

497

506,3

580

630

695

151,1

151,1

171,1

246,8

210,8

254,8

302,2

302,2

350

350

420

UMC/E AIR COOLED CONDENSING UNITS

Installation considerations - Dimensions

Foundations
No special foundations are required, provided the supporting surface is flat and level, and can withstand the weight
or the unit. Installation of anti-vibration rubber pads is recommended to avoid transmission of vibrations to the building.
Clearances
For an optimal operation of the UMC/E condensing units, it is essential to respect the specified clearance around
the unit to ensure the proper air flow distribution through the condensers and allow an easy maintenance. Reduced
spaces may cause decrease of cooling capacity and loss of performances.
The space around the unit must be accurately respected to avoid air short circuits that may cause condensing
temperature raising.
The UMC/E condensing units must be easily accessible for periodic maintenance. Minimum suggested distance for
service from unit side is 1.000 mm.
If two or more units should be installed on the same site, a distance of 2.600 mm (minimum distance between two
condensing coils) must be respected to prevent recirculation of warm air.
The distance between the units and side walls must not be less than 2.100 mm. If the walls around the unit would
be higher than the unit sides, it s mandatory to respect a minimum distance of 2.600 mm.

1000

1000

10

1000

2,6 m between 2 condensers


2,1 m between condenser & walls

Unit
size

L
W
H
mm mm mm

50
60
65
75
85
100
120
135
145
170
195
220
245
276
295
340
370
400

1570
1570
2540
2540
2540
2540
2540
3510
3510
3510
2540
2540
2540
3510
3510
3510
4150
4150

1270
1270
1270
1270
1270
1270
1270
1270
1270
1270
2240
2240
2240
2240
2240
2240
2240
2240

2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350

Shipping
weight
(kg)

Operating
weight
(kg)

680
715
1005
1040
1075
1110
1145
1435
1470
1505
1795
1875
1955
2245
2325
2320
2490
2570

705
740
1030
1065
1125
1160
1195
1485
1520
1555
1845
1925
2005
2295
2375
2415
2550
2690

UMC/E AIR COOLED CONDENSING UNITS

Product Specifications

Air-cooled condensing unit


Unit shall operate with HFC based refrigerant like R407C, R410A or R134A.
Unit should be wired and tested in simulation at the factory. All units shall be furnished with hermetic scrolls compressors, air-cooled condenser and microprocessor control panel.
Unit shall be able to operate at ambient down to +10 C as standard feature or -10 C with a 2-speed fan low ambient kit. Unit shall be able to operate up to +43 C or up to 50 C (R134a). The airflow through the
condenser shall be handled by multiple direct-driven fans. Entire fan assembly shall be statically and dynamically
balanced. Fan motors shall be with permanently lubricated ball bearings, protected by circuit breaker, class F and
IP 55.
Total unit shall comply with EC requirement for machinery, Electromagnetic and Pressure Equipment Directives (directive 98/37/CE), as amended, and its national implementing legislation.
Unit shall be designed and manufactured in accordance with the quality insurance ISO 9001/BS EN ISO9001.
Unit construction
Unit shall be designed for outdoor application and corrosion protected with epoxy powder paint.
Condenser coils
Coils shall be made with smooth copper tubes mechanically bonded to configured aluminum plate fins as standard.
Coils shall be factory tested to 28/31 bar.
Refrigerant circuit
All units shall have 1 or 2 refrigeration circuits with 1, 2 or 3 manifold compressors maximum on each circuit. Provide
for each refrigerant circuit: high and low pressostat and 2 manual shut valves on each refrigerant circuits.
Electrical
Electrical panels shall be fully mounted and wired in factory, IP55 (weatherproof) and with full opening access panel.
Provide lockable though the door disconnect operating handle switch external to panel and clearly visible from outside of unit indicated if the power is on or off.
Controls
Units shall be completely factory wired with microprocessor based control and contactor pressure lugs or terminal
block for power wiring. Control wiring shall be 230V or 24V control circuit which includes fusing and control transformer. Units shall include a fused disconnect device. Microprocessor shall control leaving and entering air temperature, operating parameters and anti-short cycling. The liquid crystal display shall indicate leaving air temperature.
Free contacts shall be available for remote signaling of operating modes and general faults.

11