You are on page 1of 15

APPR'D CERT

SAUDI Electricity Company

DESCRIPTION

CHK'D

Western Region Branch

01-02-08
2

DATE

24/11/2007

BY

Indoor Lighting Calculations

REVISION
DRAWN
TNZ

BY:

DATE:

24/10/07

CHECKED
ROD

BY:
DATE:-

OPRG. DEPT
BY
DATE:-

ENG'G. DEPT.
BY:DATE:-

CERTIFIED.
BY:-

ROD

DATE:THIS DRAWING IS NOT


TO BE USED FOR
CONSTRUCTION OF
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND
DATED

AS BUILT BY

COGELEX (AREVA T & D)


DRAWING TITLE

INDEX

KAU 110/13.8kV DRAWING CONTROL SHEET


WESTERN AREA 110kV INTEGRATION
THUWAL

PLANT

J215

SAUDI ARABIA JOB ORDER NO.

01-01-08

DATE
DRAWING NO.

WE-027979
3-073205002

SHEET NO.

01

DWG. CONT. SHT.

REV NO.

02
WE-027698

CONTENTS:

Page

1- References

2- Design Basis

3- Design Parameter

4- Illumination Levels for Normal Lighting

5- Lamps & Fixtures Technical Data

6- Summary of normal & emergency lighting system

7- Summary Calculation sheets


8- Technical data sheets of Lighting Fixures and lamps.

Annexe1

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

1 - References:
12345678910-

KING ABDULLAH UNIVERSITY JEDDAH (PTS - 06WT131 )


"WOA Specification" Clause no. (5.1 B.5.3)
"Lighting and Receptacles for Substation yard and Building"
"Site Grading & Development Plan"
"Basement Plan"
"Ground Plan"
Building Elevations."
"Building Sections."
"Finishing Schedule."
"General Equipment Layout and Section."

( TES-P-119.25)
( WA - 027996 )
( WA - 028000 )
( WA - 028001 )
( WA - 028003 )
( WA - 028004 )
( WA - 028006 )
( WA - 027730 )

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

2 - Design Basis
Lighting calculation for indoor area is designed using Easy Plan Ver.2.4.1. of
Saudi Lighting company for all Indoor / Outdoor areas.
3 Design Parameter
3.1 Reference to SCECO standard no [TES.P.119.25], Rev(0), Clause [4.1.4],
Page no. 7, The reflectance factor for control building & 110kV GIS building and
13.8kV SWGR building.
3.1.1 Reflectance Factors
-Ceiling
0.3
-Wall
0.3
-Floor
0.2
3.1.2 Maintenance Factor
-Maintenance Factor will be 0.7 & 0.6 as per consultant requirement by
comments letter no.
(SCJ/SEC/20731025/D10595 DATED 29.03.08).
3.2 Work Plane height for normal indoor lighting system shall be considered
at zero level from finished level except Office as per consultant requirement by
comments letter no.
(SCJ/SEC/20731025/D10595 DATED 29.03.08).
3.3 Work Plane height for normal indoor lighting system shall be considered
at zero level from finished level except Office as per consultant requirement by

3.4 Work Plane height for emergency lighting system shall be at zero level
from finished floor level as per SCECO standard (TES-P-119.25), Rev(0),
Clause (5.4), and Page (12)
3.5 Recessed type fixture are considered for areas with false ceiling
Suspended type/surface type fixture are considered for areas without false ceiling.

Type of fixture considered for various rooms are as below


a) 4x40w

- recessed

Control room,Aux room ,office

b) 2x40w

Suspended/ceiling type and wall

GIS room,basement,corridor

c) 2x36

Explosion proof

Battery room

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

d) 400w
e) 2x36w
f) 2x36

- reMetal hallide high bay


Bracket type
Explosion proof

GIS and MV swgr room


GIS room,basement,corridor
GIS building

Mounting Heights
a) Battery room
b) Basement
c) Area with false ceiling
d) other areas in control building
e) GIS room
f) MVSWGR room

3.6

Portable type self contained emergency light fixture are proposed near the
main entrance. These will be connected to sockets outlet

3.7

8W wall mounted "EXIT" light fixtures with 3hrs emergency battery back up are
proposed at the exit.

3.8

DC emergency light
DC emergency lights with 60W incandescent lamps are proposed. These lights will be powered
by 125VDC substation batteries. Recessed down light type fixture propsed for false ceiling and
surface type is proposed for other areas.
A switch is also provide d in the rrom to control the lights.

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

4 illumination levels for normal lighting


4.1 Reference to SCECO standard no (TES-P-119.25), Clause 5.2, Page
(12). The minimum maintained illumination level for indoor fluorescent system
shall be provide as per below table.
Location

S.N.

Lux Level

Control Room

400

13.8kV Switchgear Room

300

110kV GIS Room

300

AC/DC Room

300

Battery Room

200

Office

500

Kitchen

100

Toilet

100

Corridor

100

10 Basement - 1

100

11 Basement - 2 (Control Room Basement)

100

12 Basement - 3 (110kV GIS Room Basement)

100

13 Basement - 4 (Cable Tunnel)

100

14 FM 200 Room

200

4.1 Reference to SCECO standard no (TES-P-119.25), Clause 5.4, Page (12),


The average maintained illumination level for the emergency lighting 10 Lux at
the floor level.

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

5 Lamps & Fixtures Technical data


5.1 As per Saudi Lighting Catalog. The ordering no. format will be as the following:
7266

P /

40

Product no.
Mounting System
No. of Lighting
Watt. Of Lighting
Voltage &
Ballast Type
P
S
B
B

:
:
:
:

Pendant Mounting
Surface Mounting
220VAC or 127VAC/60Hz
Switch Start Ballast

5.2 Luminaries description


A 7266P/240.XB.CL
Pendent mounted luminaries suspended by rods. Wires or chain. Body & end pieces are
made of stamped welded cold rolled steel sheet. Contain 2 x 40 w Lamps (T5) (high
efficacy) fluorescent lamp with bi-pin caps and having min. efficacy of 100 lumens/W
shall be used. Operate at 124V 60HZ With switch start & clear prismatic sheet diffuser.
B 7266S/240.XB.CL
Surface mounted luminaries suspended by rods, wires or chain, Body & end pieces are
made of stamped welded cold rolled steel sheet. Contain 2 x 40 W Lamps (T5) (high
efficacy) fluorescent lamp with bi-pin caps and having min. efficacy of 100 lumens / W
shall be used. Operate at 127 V.60HZ With switch start & clear prismatic sheet diffuser.
C 7266W/240.XB.CL
Wall mounted luminaries suspended by rods, wires or chain, Body & end pieces are
made of stamped welded cold rolled steel sheet. Contain 2 x 40 W Lamps (T5) (high
efficacy) fluorescent lamp with bi-pin caps and having min. efficacy of 100 lumens/W
shall be used. Operate at 127V, 60HZ with switch start & clear prismatic sheet diffuser.
E 5712A/440.XB.2
Reseed mounted luminaries used for false ceiling system, Body is made of steel sheet,
Contain 4 x 40W Lamps (T-5) (high efficacy) fluorescent lamp with bi-pin caps and
having min. efficacy of 100 lumens / W shall be used, Operate at 127V, 60HZ With
switch start & Clear prismatic sheet diffuser.
F 5712A/240.XB.2
Reseed mounted luminaries used for false ceiling system, Body is made of steel sheet,
Contain 4 x 40W Lamps (T-5) (high efficacy) fluorescent lamp with bi-pin caps and
having min. efficacy of 100 lumens / W shall be used, Operate at 127V, 60HZ With
switch start & Clear prismatic sheet diffuser.
THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

G Ellk 92/236.ADAF.PC
Pendant mounted luminaries suspended by rods, wires or chains, Body is made of
molded glass reinforce polyester in gray color & height resistance to chemical and
explosion protect Contain 2 x 36 W Lamps. Operate at 127 V, 60HZ. Clear translucent
molded, Polycarbonate below diffuser.
H 5313ZP / 1-400AP.GL
Pendant mounted low bay indoor luminaire, 1 x 400-watt Mercury Vapor lamp,
127VAC/60Hz reactor type high power factor control gear, frame made of stamped
clear plain pattern flat tempered glass in frame body is made of spun aluminum,
brackets and glass frame are made of stamped galvanized steel sheet.
I 5771 / 11-60KB.GF
Reseed mounted luminaries used for false ceiling system. Contain 60 W incandescent
Lamps, Operate 125V dc, the lamp shall have efficacy more than 13 lum/W as per
specification (TES-P.119.25,Ro) clause no (4.3.2)
J 8513W/11-60K.GL
Base and frame are made from die casted aluminum wall mounted luminaries,, contain
60 W incandescent lamps. Operate at 125V dc. The lamp shall have efficacy more than
13 lum/W, as per specification (TES-P-119.25.R0) clause no (4.3.2).
K 8513S/11-60K.GL
Base and frame are made from die casted aluminum wall mounted luminaries,, contain
60 W incandescent lamps. Operate at 125V dc. The lamp shall have efficacy more than
13 lum/W, as per specification (TES-P-119.25.R0) clause no (4.3.2).
L AB50IXM/11-60K.GB.C110
Pendant mounted luminaries indirect entry. Contain 60W, incandescent lamp operate
125V dc.

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

Saudi Electricity Company


6. Summary of Normal & Emergency Lighting System
Table (1)
Location

Control Room
Normal
"SLC"

13.8kV SGWR Room

5313ZP/
1-400AP.GL

Recessed/Pendant
Switch Start

Emergency
"SLC"
5771/1160KB.GF
Recessed
-

Lighting Source

Fluores. 4x40W

Incandesce.1x60W

HPMV.1x400W

Supply

127VAC, 60Hz

125Vdc

2.9

2.9

Quantity

24

13

10

Required

400

10

300

10

403

14.9

349

13

Lighting Sys.
Manufacturer

5712A/440XB.2

Order No.
Mounting
Ballast Type

MH

Actual Lux

Room
Dimension(m)

Normal
"SLC"
72665/
240.XB.CL
Surface

Pendant

8513W/11-60K.GL
Wall
-

Switch Start
Fluores.2x40W

125Vdc
2

20

18

L = 14

L = 5.5
W = 49.6

H=3
21

Incandes.1x60W

127Vac. 60Hz

W = 20
43

IP Class no.

Emergency
"SLC"

54

H = 5.1
43

65

MH : Mounting Height

SAUDI ARABIA

THUWAL
JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

Saudi Electricity Company


Table (2)
Location

110kV GIS Room


Normal
"SLC"

Lighting Sys.
Manufacturer
Order No.
Mounting
Ballast Type

Fluores.2x40W

**

Indes.1x60W

127 Vac, 60Hz

5712A/440XB.2

5771/11.60SGC

Pendant
Switch Start

Recessed
-

Fluores 4x40W

Incandes. 1x60W

127 Vac. 60Hz

125Vdc

2.5

2.5

2.9

2.9

Quantity
Required Lux.
Actual lux

**

300

10

300

10

349

12.9

320

10

Room
Dimension (m)
Class of
protection (IP)

Emergency
"SLC"

6.5

Supply
MH

Normal
"SLC"

Emergency
"SLC"

5313ZP/
7266S/
1.400AP.GL
240XB.CL
Pendant
Surface
Switch Start

Lighting Source HPMV.1x400W

AC/DC Room

L=10

L = 5.4

W=20.1

W=6

H=8

H = 2.9

54

43

65

Order No

8513W/
11-60K.GL

85135/
11-60K.GL

Mounting

Wall

Surface

Quantity

43

21

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

Saudi Electricity Company


Table (3)
Location

Battery Room
Normal
"SLC"

Office

127 Vac, 60Hz

Emergency
"SLC"
AB501XM/
11-60K.GB
Pendant
Incandes.
1x60W
125Vdc

MH

2.9

Quantity

Required Lux.

200

10

500

10

Actual lux.

312

10

708

Lighting Sys.
Manufacturer

eLLK92/23ADAF.PC

Order No.

Pendant
Switch Start

Mounting
Ballast Type
Lighting Source

Fluores. 2X36W

Aux. Supply

Room
Dimension (m)
Class of
Protection (IP)

Normal
"SLC"

Emergency
"SLC"

5712/440XB.2

5771/11-60KB.GF

Pendant
Switch Start

Recessed
-

Fluores. 4x40W

Incandes. 1x60W

127 Vac, 60 Hz

125Vdc
2.9

14.9

L = 5.5

L = 5.4

W=4

W=4

H = 4.9

H = 2.9

66

66

43

21

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

Saudi Electricity Company


Table (4)
Location

Kitchen
Normal
"SLC"

Lighting Sys.
Manufacturer

Toilet
Emergency
"SLC"
5771/1160KB.GF
Recessed
-

Normal
"SLC"

Emergency
"SLC"

5712A/440XB.2

5771/11-60KB.GF

Pendant

Order No.

5712A/440XB.2

Mounting
Ballast Type
Lighting Source

Pendant
Switch Start
Fluores. 4x40W

Incandes. 1x60W

Fluores. 4x40W

Recessed
Incandes.1x60W

127Vac. 60Hz

125Vdc

127 Vac. 60Hz

125Vdc

2.9

2.9

2.9

2.9

Aux. Supply
MH
Quantity

Switch Start

Required Lux.

100

10

100

10

Actual lux.

202

18.9

138

14.2

Room
Dimension (m)
Class of
Protection (IP)

L = 5.4

L = 5.4

W=3

W = 1.5

H = 2.9

H=3

43

21

21

43

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

Saudi Electricity Company


Table (5)
Location

Corridor
Normal
"SLC"

Lighting Sys.
Manufacturer

Basement - 1MVSWGR
Emergency
"SLC"

Emergency
"SLC"
8513W/
11-60K.GL
Wall
-

Normal
"SLC"
72665/240XB.CL

Incandex. 1x60W

Fluores. 2x40W

Incandes. 1x60W
125Vdc

Order No.

5712A/440XB.2

Mounting
Ballast Type
Lighting Source

Pendant
Switch Start
Fluores. 4x40W

Aux. Supply

127 Vac, 60Hz

125Vdc

127 Vac, 60Hz

MH

Quantity

11

22

Required Lux.

100

10

100

10

204

10

176

11.4

Actual lux.
Room
Dimension (m)

**

Surface
Switch Start

**

L = 18.6

Area (1) = (L,W,H) = (5.6, 54,3)

W = 23.3

Area (2) = (L,W,H) = (5.3, 10,3)

H=3

Class of
Protection (IP)

43

21

Order No

8513W/
11-60K.GL

85135/
11-60K.GL

Mounting

Wall

Surface

Mounting Height

2.2

Quantity

18

43

65

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

Saudi Electricity Company


Table (5)
Location

Basement 2-Cntrl ROOM

Basement -3GIS

Order No.

5712A/440XB.2

Mounting
Ballast Type
Lighting Source

Pendant
Switch Start
Fluores. 4x40W

Incandex. 1x60W

Fluores. 2x40W

Emergency
"SLC"
85135/
11-60K.GL
Surface
Incandes. 1x60W

Aux. Supply

127 Vac, 60Hz

125Vdc

127 Vac, 60Hz

125Vdc

MH

Quantity

14

18

Normal
"SLC"

Lighting Sys.
Manufacturer

Required Lux.
Actual lux.

Emergency
"SLC"
5770/1160KB.GF
Recessed
-

Normal
"SLC"
72665/240XB.CL
Surface
Switch Start

100

10

100

10

188

17.6

179

14

43

21

43

65

Room
Dimension (m)
Class of
Protection (IP)

Order No

8513W/
11-60K.GL

85135/
11-60K.GL

Mounting

Wall

Surface

Mounting Height

2.2

Quantity

18

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02

Saudi Electricity Company


Table (5)
Location

Basement 4-Tunnel

Lighting Sys.
Manufacturer

Normal
"SLC"

Emergency
"SLC"

Order No.

5712A/440XB.2

8513w

Mounting
Ballast Type
Lighting Source

Pendant
Switch Start
Fluores. 4x40W

Wall
Incandex. 1x60W

Aux. Supply

127 Vac, 60Hz

125Vdc

MH

2.2

Quantity

14

Required Lux.
Actual lux.

100

10

100

10.8

43

65

Room
Dimension (m)
Class of
Protection (IP)

THUWAL

SAUDI ARABIA

JOB ORDER NO.

INDEX

PLANT NO.

DRAWING NUMBER

3-073205002

J215

WE-027979

SHEET NO.

of

REV. NO

02