You are on page 1of 1452

Relion 670 series

Generator protection REG670 2.1 ANSI and


Injection equipment REX060, REX061, REX062
Technical manual

Document ID: 1MRK 502 066-UUS


Issued: February 2016
Revision: A
Product version: 2.1

Copyright 2016 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license and
may be used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the OpenSSL
Toolkit. (http://www.openssl.org/) This product includes cryptographic software written/
developed by: Eric Young (eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com).

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product
names mentioned in this document may be trademarks or registered trademarks of their
respective holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties. All
persons responsible for applying the equipment addressed in this manual must satisfy
themselves that each intended application is suitable and acceptable, including that any
applicable safety or other operational requirements are complied with. In particular, any
risks in applications where a system failure and/or product failure would create a risk for
harm to property or persons (including but not limited to personal injuries or death) shall
be the sole responsibility of the person or entity applying the equipment, and those so
responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the
manufacturer. Other than under explicit contractual commitments, in no event shall ABB
be responsible or liable for any loss or damage resulting from the use of this manual or the
application of the equipment.

Conformity
This product complies with the directive of the Council of the European Communities on
the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use
within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is
the result of tests conducted by ABB in accordance with the product standard EN
60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN
60255-27 for the low voltage directive. The product is designed in accordance with the
international standards of the IEC 60255 series and ANSI C37.90.

Table of contents

Table of contents
Section 1

Introduction..........................................................................43
This manual............................................................................................ 43
Intended audience.................................................................................. 43
Product documentation...........................................................................44
Product documentation set................................................................44
Document revision history................................................................. 45
Related documents............................................................................46
Document symbols and conventions...................................................... 46
Symbols.............................................................................................46
Document conventions...................................................................... 47
IEC61850 edition 1 / edition 2 mapping..................................................48

Section 2

Available functions.............................................................. 57
Main protection functions........................................................................57
Back-up protection functions.................................................................. 58
Control and monitoring functions............................................................ 59
Communication.......................................................................................63
Basic IED functions.................................................................................65

Section 3

Analog inputs.......................................................................67
Introduction............................................................................................. 67
Function block.........................................................................................67
Signals.................................................................................................... 68
Settings...................................................................................................70
Monitored data........................................................................................78
Operation principle..................................................................................79
Technical data........................................................................................ 80

Section 4

Binary input and output modules.........................................83


Binary input.............................................................................................83
Binary input debounce filter............................................................... 83
Oscillation filter.................................................................................. 83
Settings..............................................................................................83
Setting parameters for binary input modules................................84
Setting parameters for binary input/output module.......................84

Section 5

Local Human-Machine-Interface LHMI ...............................85

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Local HMI screen behaviour................................................................... 85


Identification...................................................................................... 85
Settings..............................................................................................85
Local HMI signals................................................................................... 85
Identification...................................................................................... 85
Function block................................................................................... 86
Signals...............................................................................................86
Basic part for LED indication module......................................................87
Identification...................................................................................... 87
Function block................................................................................... 87
Signals...............................................................................................87
Settings..............................................................................................88
LCD part for HMI function keys control module...................................... 89
Identification...................................................................................... 89
Function block................................................................................... 89
Signals...............................................................................................89
Settings..............................................................................................89
Operation principle..................................................................................91
Local HMI...........................................................................................91
Keypad......................................................................................... 92
Display..........................................................................................94
LEDs.............................................................................................98
LED configuration alternatives...........................................................98
Functionality ................................................................................ 98
Status LEDs..................................................................................99
Indication LEDs............................................................................ 99
Function keys.................................................................................. 109
Functionality .............................................................................. 109
Operation principle..................................................................... 109

Section 6

Differential protection........................................................ 113


Transformer differential protection T2WPDIF and T3WPDIF (87T)......113
Identification.................................................................................... 113
Functionality ................................................................................... 113
Function block................................................................................. 117
Signals.............................................................................................118
Settings............................................................................................122
Monitored data.................................................................................127
Operation principle.......................................................................... 128
Function calculation principles....................................................129

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Logic diagram............................................................................. 153


Technical data................................................................................. 158
1Ph High impedance differential protection HZPDIF (87).....................159
Identification.................................................................................... 159
Functionality.................................................................................... 159
Function block................................................................................. 160
Signals.............................................................................................160
Settings............................................................................................161
Monitored data.................................................................................161
Operation principle.......................................................................... 161
Logic diagram............................................................................. 163
Technical data................................................................................. 164
Generator differential protection GENPDIF (87G)................................ 165
Identification.................................................................................... 165
Functionality.................................................................................... 165
Function block................................................................................. 166
Signals.............................................................................................166
Settings............................................................................................167
Monitored data.................................................................................169
Operation principle.......................................................................... 169
Function calculation principles....................................................170
Fundamental frequency differential currents.............................. 170
Supplementary criteria................................................................175
Harmonic restrain....................................................................... 178
Open CT detection feature......................................................... 178
Cross-block logic scheme...........................................................180
Technical data................................................................................. 183
Low impedance restricted earth fault protection REFPDIF (87N).........184
Identification.................................................................................... 184
Functionality.................................................................................... 184
Function block................................................................................. 185
Signals.............................................................................................185
Settings............................................................................................186
Monitored data.................................................................................187
Operation principle.......................................................................... 187
Fundamental principles of the restricted ground fault protection187
Restricted ground fault protection, low impedance differential
protection....................................................................................190
Calculation of differential current and bias current..................... 191
Detection of external ground faults.............................................192
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Algorithm of the restricted ground fault protection......................194


Technical data................................................................................. 195

Section 7

Impedance protection........................................................197
Full-scheme distance measuring, Mho characteristic ZMHPDIS (21).. 197
Identification.................................................................................... 197
Functionality.................................................................................... 197
Function block................................................................................. 198
Signals.............................................................................................198
Settings............................................................................................199
Operation principle.......................................................................... 201
Full scheme measurement......................................................... 201
Impedance characteristic............................................................201
Basic operation characteristics...................................................202
Theory of operation.................................................................... 205
Simplified logic diagrams............................................................215
Technical data................................................................................. 219
Directional impedance element for mho characteristic ZDMRDIR
(21D).....................................................................................................219
Identification.................................................................................... 219
Functionality.................................................................................... 220
Function block................................................................................. 220
Signals.............................................................................................220
Settings............................................................................................221
Monitored data.................................................................................222
Operation principle.......................................................................... 223
Directional impedance element for mho characteristic
ZDMRDIR (21D)......................................................................... 223
Distance protection zone, quadrilateral characteristic, separate
settings ZMRPDIS (21), ZMRAPDIS (21) and ZDRDIR (21D)............. 225
Identification.................................................................................... 226
Functionality.................................................................................... 226
Function block................................................................................. 227
Signals.............................................................................................227
Settings............................................................................................229
Operation principle.......................................................................... 232
Full scheme measurement......................................................... 232
Impedance characteristic............................................................232
Minimum operating current.........................................................236
Measuring principles...................................................................236
Directional impedance element for quadrilateral characteristics 239

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Simplified logic diagrams............................................................242


Phase selection, quadrilateral characteristic with settable angle
FRPSPDIS (21).................................................................................... 246
Identification.................................................................................... 246
Functionality.................................................................................... 247
Function block................................................................................. 247
Signals.............................................................................................248
Settings............................................................................................249
Operation principle.......................................................................... 250
Phase-to-ground fault................................................................. 252
Phase-to-phase fault.................................................................. 254
Three-phase faults......................................................................255
Load encroachment....................................................................256
Minimum operate currents..........................................................261
Simplified logic diagrams............................................................262
Technical data................................................................................. 267
High speed distance protection ZMFPDIS (21).................................... 267
Identification.................................................................................... 267
Functionality.................................................................................... 267
Function block................................................................................. 269
Signals.............................................................................................270
Settings............................................................................................272
Monitored data.................................................................................278
Operation principle.......................................................................... 279
Filtering.......................................................................................279
Distance measuring zones......................................................... 279
Phase-selection element............................................................ 280
Directional element.....................................................................281
Fuse failure.................................................................................282
Power swings............................................................................. 282
Measuring principles...................................................................283
Load encroachment....................................................................295
Simplified logic schemes............................................................ 297
Measurement..............................................................................303
Technical data................................................................................. 308
High speed distance protection for series compensated lines
ZMFCPDIS (21).................................................................................... 308
Identification.................................................................................... 309
Functionality.................................................................................... 309
Function block................................................................................. 311
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Signals.............................................................................................312
Settings............................................................................................314
Monitored data.................................................................................322
Operation principle.......................................................................... 323
Filtering.......................................................................................323
Distance measuring zones......................................................... 323
Phase-selection element............................................................ 324
Directional element.....................................................................325
Fuse failure.................................................................................326
Power swings............................................................................. 327
Measurement principles............................................................. 327
Load encroachment....................................................................340
Simplified logic schemes............................................................ 341
Measurement..............................................................................346
Technical data................................................................................. 352
Pole slip protection PSPPPAM (78)......................................................352
Identification.................................................................................... 352
Functionality.................................................................................... 352
Function block................................................................................. 354
Signals.............................................................................................354
Settings............................................................................................355
Monitored data.................................................................................356
Operation principle.......................................................................... 356
Technical data................................................................................. 360
Out-of-step protection OOSPPAM (78)................................................ 361
Identification.................................................................................... 361
Functionality.................................................................................... 361
Function block................................................................................. 362
Signals.............................................................................................362
Settings............................................................................................363
Monitored data.................................................................................364
Operation principle.......................................................................... 364
Lens characteristic......................................................................367
Detecting an out-of-step condition..............................................369
Maximum slip frequency.............................................................370
Taking care of the circuit breaker .............................................. 371
Design........................................................................................ 373
Technical data................................................................................. 374
Loss of excitation LEXPDIS(40)........................................................... 374
Identification.................................................................................... 375
6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Functionality.................................................................................... 375
Function block................................................................................. 375
Signals.............................................................................................376
Settings............................................................................................376
Monitored data.................................................................................377
Operation principle.......................................................................... 378
Technical data................................................................................. 382
Sensitive rotor earth fault protection, injection based ROTIPHIZ (64R)383
Identification.................................................................................... 383
Functionality.................................................................................... 383
Description of input signals..............................................................383
Description of output signals........................................................... 384
Function block................................................................................. 386
Signals.............................................................................................386
Settings............................................................................................387
Monitored data.................................................................................388
Operation principle.......................................................................... 389
The injection unit REX060.......................................................... 390
Rotor Earth Fault Protection function......................................... 391
General measurement of ground fault impedance..................... 392
Simplified logic diagram..............................................................394
Technical data................................................................................. 396
100% stator earth fault protection, injection based STTIPHIZ (64S).... 397
Identification.................................................................................... 397
Functionality.................................................................................... 397
Description of input signals..............................................................398
Description of output signals........................................................... 398
Function block................................................................................. 400
Signals.............................................................................................401
Settings............................................................................................401
Monitored data.................................................................................403
Operation principle.......................................................................... 403
Configuration principle................................................................403
Generator system grounding methods....................................... 406
100% Stator earth fault protection function................................ 411
General measurement of ground fault impedance..................... 415
Measuring reference impedance................................................ 417
Simplified logic diagram..............................................................421
Technical data................................................................................. 422

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Under impedance protection for generators and transformers


ZGVPDIS.............................................................................................. 423
Identification.................................................................................... 423
Functionality.................................................................................... 423
Function block................................................................................. 424
Signals.............................................................................................424
Settings............................................................................................425
Monitored data.................................................................................426
Operation principle.......................................................................... 426
Operation principle of zone 1......................................................428
Operation principle of zone 2......................................................431
Operation principle of zone 3......................................................434
Load encroachment....................................................................435
Under voltage seal-in..................................................................436
Technical data................................................................................. 437

Section 8

Current protection..............................................................439
Instantaneous phase overcurrent protection PHPIOC (50).................. 439
Identification.................................................................................... 439
Functionality.................................................................................... 439
Function block................................................................................. 439
Signals.............................................................................................439
Settings............................................................................................440
Monitored data.................................................................................441
Operation principle.......................................................................... 441
Technical data................................................................................. 442
Four step phase overcurrent protection OC4PTOC(51/67).................. 442
Identification.................................................................................... 442
Functionality.................................................................................... 442
Function block................................................................................. 443
Signals.............................................................................................444
Settings............................................................................................446
Monitored data.................................................................................452
Operation principle.......................................................................... 452
Technical data................................................................................. 460
Instantaneous residual overcurrent protection EFPIOC (50N)............. 461
Identification.................................................................................... 461
Functionality.................................................................................... 461
Function block................................................................................. 461
Signals.............................................................................................462

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Settings............................................................................................462
Monitored data.................................................................................462
Operation principle.......................................................................... 463
Technical data................................................................................. 463
Four step residual overcurrent protection, (Zero sequence or
negative sequence directionality) EF4PTOC (51N/67N)...................... 464
Identification.................................................................................... 464
Functionality.................................................................................... 464
Function block................................................................................. 465
Signals.............................................................................................465
Settings............................................................................................466
Monitored data.................................................................................474
Operation principle.......................................................................... 474
Operating quantity within the function........................................ 475
Internal polarizing....................................................................... 476
External polarizing for ground-fault function............................... 478
Directional detection for ground fault function............................ 478
Base quantities within the protection.......................................... 478
Internal ground-fault protection structure....................................479
Four residual overcurrent steps..................................................479
Directional supervision element with integrated directional
comparison function................................................................... 480
Second harmonic blocking element............................................483
Switch on to fault feature............................................................ 485
Technical data................................................................................. 487
Four step directional negative phase sequence overcurrent
protection NS4PTOC (46I2)..................................................................488
Identification.................................................................................... 488
Functionality.................................................................................... 489
Function block................................................................................. 489
Signals.............................................................................................490
Settings............................................................................................491
Monitored data.................................................................................496
Operation principle.......................................................................... 496
Operating quantity within the function........................................ 496
Internal polarizing facility of the function.....................................497
External polarizing for negative sequence function.................... 498
Internal negative sequence protection structure.........................498
Four negative sequence overcurrent stages.............................. 498

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Directional supervision element with integrated directional


comparison function................................................................... 500
Technical data................................................................................. 502
Sensitive directional residual overcurrent and power protection
SDEPSDE (67N)...................................................................................503
Identification.................................................................................... 503
Functionality.................................................................................... 503
Function block................................................................................. 505
Signals.............................................................................................505
Settings............................................................................................506
Monitored data.................................................................................508
Operation principle.......................................................................... 508
Function inputs........................................................................... 508
Technical data................................................................................. 516
Thermal overload protection, two time constants TRPTTR (49)...........517
Identification.................................................................................... 517
Functionality.................................................................................... 517
Function block................................................................................. 517
Signals.............................................................................................518
Settings............................................................................................518
Monitored data.................................................................................519
Operation principle.......................................................................... 520
Technical data................................................................................. 524
Breaker failure protection CCRBRF(50BF)...........................................524
Identification.................................................................................... 524
Functionality.................................................................................... 524
Function block................................................................................. 525
Signals.............................................................................................525
Settings............................................................................................526
Monitored data.................................................................................527
Operation principle.......................................................................... 527
Technical data................................................................................. 530
Pole discrepancy protection CCPDSC(52PD)...................................... 530
Identification.................................................................................... 530
Functionality.................................................................................... 531
Function block................................................................................. 531
Signals.............................................................................................531
Settings............................................................................................532
Monitored data.................................................................................533
Operation principle.......................................................................... 533
10

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Pole discrepancy signaling from circuit breaker......................... 536


Unsymmetrical current detection................................................ 536
Technical data................................................................................. 536
Directional underpower protection GUPPDUP (37)..............................536
Identification.................................................................................... 537
Functionality.................................................................................... 537
Function block................................................................................. 538
Signals.............................................................................................538
Settings............................................................................................539
Monitored data.................................................................................541
Operation principle.......................................................................... 541
Low pass filtering........................................................................543
Calibration of analog inputs........................................................ 544
Technical data................................................................................. 545
Directional overpower protection GOPPDOP (32)................................545
Identification.................................................................................... 545
Functionality.................................................................................... 545
Function block................................................................................. 546
Signals.............................................................................................547
Settings............................................................................................547
Monitored data.................................................................................549
Operation principle.......................................................................... 549
Low pass filtering........................................................................552
Calibration of analog inputs........................................................ 552
Technical data................................................................................. 554
Negativ sequence time overcurrent protection for machines
NS2PTOC (46I2).................................................................................. 554
Identification.................................................................................... 554
Functionality.................................................................................... 554
Function block................................................................................. 556
Signals.............................................................................................556
Settings............................................................................................557
Monitored data.................................................................................558
Operation principle.......................................................................... 558
Pickup sensitivity........................................................................ 560
Alarm function.............................................................................560
Logic diagram............................................................................. 561
Technical data................................................................................. 561
Accidental energizing protection for synchronous generator
AEGPVOC (50AE)................................................................................562
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

11

Table of contents

Identification.................................................................................... 562
Functionality .............................................................................. 562
Function block............................................................................ 563
Signals........................................................................................563
Settings.......................................................................................563
Monitored data............................................................................564
Operation principle..................................................................... 564
Technical data............................................................................ 565
Voltage-restrained time overcurrent protection VRPVOC (51V)...........566
Identification.................................................................................... 566
Functionality.................................................................................... 566
Function block................................................................................. 567
Signals.............................................................................................567
Settings............................................................................................568
Monitored data.................................................................................569
Operation principle.......................................................................... 569
Measured quantities................................................................... 569
Base quantities........................................................................... 569
Overcurrent protection................................................................569
Logic diagram............................................................................. 571
Undervoltage protection............................................................. 572
Technical data................................................................................. 572
Generator stator overload protection, GSPTTR (49S)..........................573
Identification.................................................................................... 573
Functionality.................................................................................... 574
Function block................................................................................. 574
Signals.............................................................................................574
Settings............................................................................................575
Monitored data.................................................................................576
Operation principle.......................................................................... 576
Technical data................................................................................. 583
Generator rotor overload protection, GRPTTR (49R)...........................583
Identification.................................................................................... 583
Functionality.................................................................................... 583
Function block................................................................................. 584
Signals.............................................................................................584
Settings............................................................................................585
Monitored data.................................................................................586
Operation principle.......................................................................... 586
Technical data................................................................................. 596
12

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Section 9

Voltage protection............................................................. 597


Two step undervoltage protection UV2PTUV (27)................................597
Identification.................................................................................... 597
Functionality.................................................................................... 597
Function block................................................................................. 598
Signals.............................................................................................598
Settings............................................................................................599
Monitored data.................................................................................601
Operation principle.......................................................................... 602
Measurement principle............................................................... 602
Time delay.................................................................................. 603
Blocking...................................................................................... 608
Design........................................................................................ 609
Technical data................................................................................. 611
Two step overvoltage protection OV2PTOV (59)................................. 611
Identification.................................................................................... 611
Functionality OV2PTOV.................................................................. 612
Function block................................................................................. 612
Signals.............................................................................................612
Settings............................................................................................613
Monitored data.................................................................................615
Operation principle.......................................................................... 615
Measurement principle............................................................... 616
Time delay.................................................................................. 617
Blocking...................................................................................... 622
Design........................................................................................ 622
Technical data................................................................................. 624
Two step residual overvoltage protection ROV2PTOV (59N)...............624
Identification.................................................................................... 624
Functionality.................................................................................... 625
Function block................................................................................. 625
Signals.............................................................................................625
Settings............................................................................................626
Monitored data.................................................................................628
Operation principle.......................................................................... 628
Measurement principle............................................................... 628
Time delay.................................................................................. 628
Blocking...................................................................................... 634
Design........................................................................................ 634

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

13

Table of contents

Technical data................................................................................. 635


Overexcitation protection OEXPVPH (24)............................................ 636
Identification.................................................................................... 636
Functionality.................................................................................... 636
Function block................................................................................. 637
Signals.............................................................................................637
Settings............................................................................................637
Monitored data.................................................................................639
Operation principle.......................................................................... 639
Measured voltage....................................................................... 642
Operate time of the overexcitation protection.............................642
Cooling....................................................................................... 646
Overexcitation protection function measurands......................... 646
Overexcitation alarm...................................................................647
Logic diagram............................................................................. 648
Technical data................................................................................. 648
Voltage differential protection VDCPTOV (60)..................................... 649
Identification.................................................................................... 649
Functionality.................................................................................... 649
Function block................................................................................. 649
Signals.............................................................................................650
Settings............................................................................................650
Monitored data.................................................................................651
Operation principle.......................................................................... 651
Technical data................................................................................. 653
100% Stator ground fault protection, 3rd harmonic based STEFPHIZ
(59THD)................................................................................................ 653
Identification.................................................................................... 653
Functionality.................................................................................... 653
Function block................................................................................. 655
Signals.............................................................................................655
Settings............................................................................................656
Monitored data.................................................................................657
Operation principle.......................................................................... 657
Technical data................................................................................. 662

Section 10 Frequency protection.........................................................665


Underfrequency protection SAPTUF (81).............................................665
Identification.................................................................................... 665
Functionality.................................................................................... 665
14

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Function block................................................................................. 665


Signals.............................................................................................666
Settings............................................................................................666
Monitored data.................................................................................667
Operation principle.......................................................................... 667
Measurement principle............................................................... 667
Time delay.................................................................................. 668
Voltage dependent time delay.................................................... 668
Blocking...................................................................................... 670
Design........................................................................................ 670
Overfrequency protection SAPTOF (81)...............................................671
Identification.................................................................................... 671
Functionality.................................................................................... 672
Function block................................................................................. 672
Signals.............................................................................................672
Settings............................................................................................673
Monitored data.................................................................................673
Operation principle.......................................................................... 673
Measurement principle............................................................... 674
Time delay.................................................................................. 674
Blocking...................................................................................... 674
Design........................................................................................ 675
Technical data................................................................................. 675
Rate-of-change frequency protection SAPFRC (81)............................ 676
Identification.................................................................................... 676
Functionality.................................................................................... 676
Function block................................................................................. 677
Signals.............................................................................................677
Settings............................................................................................677
Monitored data.................................................................................678
Operation principle.......................................................................... 678
Measurement principle............................................................... 678
Time delay.................................................................................. 678
Blocking...................................................................................... 679
Design........................................................................................ 679
Technical data................................................................................. 680
Frequency time accumulation protection function FTAQFVR (81A).....681
Identification.................................................................................... 681
Functionality ................................................................................... 681
Function block ................................................................................ 681
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

15

Table of contents

Signals.............................................................................................682
Settings............................................................................................683
Monitored data.................................................................................683
Operation principle.......................................................................... 683

Section 11 Multipurpose protection..................................................... 689


General current and voltage protection CVGAPC................................ 689
Identification.................................................................................... 689
Functionality.................................................................................... 689
Inadvertent generator energization.............................................690
Function block................................................................................. 690
Signals.............................................................................................691
Settings............................................................................................693
Monitored data.................................................................................700
Operation principle.......................................................................... 701
Measured quantities within CVGAPC.........................................701
Base quantities for CVGAPC function........................................ 703
Built-in overcurrent protection steps........................................... 704
Built-in undercurrent protection steps.........................................709
Built-in overvoltage protection steps...........................................710
Built-in undervoltage protection steps........................................ 710
Inadvertent generator energizing................................................710
Logic diagram............................................................................. 712
Technical data................................................................................. 717

Section 12 System protection and control...........................................721


Multipurpose filter SMAIHPAC..............................................................721
Identification.................................................................................... 721
Functionality.................................................................................... 721
Function block................................................................................. 721
Signals.............................................................................................721
Settings............................................................................................722
Operation principle.......................................................................... 722
Filter calculation example................................................................ 726

Section 13 Secondary system supervision..........................................729


Current circuit supervision (87).............................................................729
Identification.................................................................................... 729
Functionality.................................................................................... 729
Function block................................................................................. 729
Signals.............................................................................................730
16

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Settings............................................................................................730
Operation principle.......................................................................... 731
Technical data................................................................................. 732
Fuse failure supervision FUFSPVC...................................................... 732
Identification.................................................................................... 733
Functionality.................................................................................... 733
Function block................................................................................. 733
Signals.............................................................................................734
Settings............................................................................................735
Monitored data.................................................................................736
Operation principle.......................................................................... 736
Zero and negative sequence detection...................................... 736
Delta current and delta voltage detection................................... 738
Dead line detection.....................................................................741
Main logic................................................................................... 742
Technical data................................................................................. 745
Fuse failure supervision VDSPVC (60).................................................745
Identification.................................................................................... 745
Functionality.................................................................................... 745
Function block................................................................................. 746
Signals.............................................................................................746
Settings............................................................................................747
Monitored data.................................................................................748
Operation principle.......................................................................... 748
Technical data................................................................................. 749

Section 14 Control...............................................................................751
Synchronism check, energizing check, and synchronizing
SESRSYN (25)..................................................................................... 751
Identification.................................................................................... 751
Functionality.................................................................................... 751
Function block................................................................................. 752
Signals.............................................................................................752
Settings............................................................................................755
Monitored data.................................................................................757
Operation principle.......................................................................... 758
Basic functionality.......................................................................758
Logic diagrams........................................................................... 758
Technical data................................................................................. 770
Interlocking (3)...................................................................................... 771
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

17

Table of contents

Functionality.................................................................................... 771
Operation principle.......................................................................... 771
Logical node for interlocking SCILO (3)...........................................774
Identification............................................................................... 774
Functionality............................................................................... 774
Function block............................................................................ 775
Signals........................................................................................775
Logic diagram............................................................................. 775
Interlocking for busbar grounding switch BB_ES (3)....................... 776
Identification............................................................................... 776
Functionality............................................................................... 776
Function block............................................................................ 777
Logic diagram............................................................................. 777
Signals........................................................................................777
Interlocking for bus-section breaker A1A2_BS (3)...........................778
Identification............................................................................... 778
Functionality............................................................................... 778
Function block............................................................................ 779
Logic diagram............................................................................. 780
Signals........................................................................................781
Interlocking for bus-section disconnector A1A2_DC (3).................. 783
Identification............................................................................... 783
Functionality............................................................................... 783
Function block............................................................................ 784
Logic diagram............................................................................. 784
Signals........................................................................................785
Interlocking for bus-coupler bay ABC_BC (3).................................. 786
Identification............................................................................... 786
Functionality............................................................................... 786
Function block............................................................................ 787
Logic diagram............................................................................. 788
Signals........................................................................................790
Interlocking for breaker-and-a-half diameter BH (3)........................ 793
Identification............................................................................... 793
Functionality............................................................................... 793
Function blocks...........................................................................795
Logic diagrams........................................................................... 797
Signals........................................................................................802
Interlocking for double CB bay DB (3)............................................. 806
Identification............................................................................... 807
18

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Functionality............................................................................... 807
Logic diagrams........................................................................... 808
Function block............................................................................ 812
Signals........................................................................................813
Interlocking for line bay ABC_LINE (3)............................................ 816
Identification............................................................................... 817
Functionality............................................................................... 817
Function block............................................................................ 818
Logic diagram............................................................................. 819
Signals........................................................................................824
Interlocking for transformer bay AB_TRAFO (3)..............................827
Identification............................................................................... 827
Functionality............................................................................... 827
Function block............................................................................ 828
Logic diagram............................................................................. 829
Signals........................................................................................831
Position evaluation POS_EVAL.......................................................833
Identification............................................................................... 833
Functionality............................................................................... 833
Function block............................................................................ 833
Logic diagram............................................................................. 833
Signals........................................................................................834
Apparatus control APC......................................................................... 834
Functionality.................................................................................... 834
Operation principle.......................................................................... 835
Error handling.................................................................................. 836
Bay control QCBAY......................................................................... 839
Functionality............................................................................... 839
Function block............................................................................ 839
Signals........................................................................................839
Settings.......................................................................................840
Operation principle..................................................................... 840
Local/Remote switch LOCREM, LOCREMCTRL............................ 842
Function block............................................................................ 842
Signals........................................................................................843
Settings.......................................................................................844
Operation principle..................................................................... 844
Switch controller SCSWI..................................................................846
Functionality .............................................................................. 846
Function block............................................................................ 846
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

19

Table of contents

Signals........................................................................................846
Settings.......................................................................................848
Operation principle..................................................................... 848
Circuit breaker SXCBR....................................................................855
Functionality .............................................................................. 855
Function block............................................................................ 856
Signals........................................................................................856
Settings.......................................................................................857
Operation principle..................................................................... 857
Circuit switch SXSWI....................................................................... 862
Functionality .............................................................................. 862
Function block............................................................................ 863
Signals........................................................................................863
Settings.......................................................................................864
Operation principle..................................................................... 864
Bay reserve QCRSV........................................................................869
Functionality............................................................................... 869
Function block............................................................................ 869
Signals........................................................................................870
Settings.......................................................................................871
Operation principle..................................................................... 871
Reservation input RESIN.................................................................873
Functionality............................................................................... 873
Function block............................................................................ 874
Signals........................................................................................874
Settings.......................................................................................875
Operation principle..................................................................... 875
Voltage control......................................................................................877
Identification.................................................................................... 877
Functionality.................................................................................... 877
Tap changer control and supervision, 6 binary inputs TCMYLTC
(84) and TCLYLTC (84)...................................................................878
Operation principle..................................................................... 878
Function block................................................................................. 882
Signals.............................................................................................883
Settings............................................................................................887
Monitored data.................................................................................888
Operation principle.......................................................................... 889
Technical data................................................................................. 889

20

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Logic rotating switch for function selection and LHMI presentation


SLGAPC............................................................................................... 890
Identification.................................................................................... 890
Functionality.................................................................................... 891
Function block................................................................................. 891
Signals.............................................................................................892
Settings............................................................................................893
Monitored data.................................................................................893
Operation principle.......................................................................... 893
Graphical display........................................................................ 894
Selector mini switch VSGAPC.............................................................. 895
Identification.................................................................................... 895
Functionality.................................................................................... 896
Function block................................................................................. 896
Signals.............................................................................................896
Settings............................................................................................897
Operation principle.......................................................................... 897
Generic communication function for Double Point indication DPGAPC898
Identification.................................................................................... 898
Functionality.................................................................................... 898
Function block................................................................................. 898
Signals.............................................................................................899
Settings............................................................................................899
Operation principle.......................................................................... 899
Single point generic control 8 signals SPC8GAPC...............................899
Identification.................................................................................... 899
Functionality.................................................................................... 899
Function block................................................................................. 900
Signals.............................................................................................900
Settings............................................................................................901
Operation principle.......................................................................... 901
AutomationBits, command function for DNP3.0 AUTOBITS................ 902
Identification.................................................................................... 902
Functionality.................................................................................... 902
Function block................................................................................. 903
Signals.............................................................................................903
Settings............................................................................................904
Operation principle.......................................................................... 920
Single command, 16 signals SINGLECMD.......................................... 920
Identification.................................................................................... 920
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

21

Table of contents

Functionality.................................................................................... 920
Function block................................................................................. 921
Signals.............................................................................................921
Settings............................................................................................922
Operation principle.......................................................................... 922

Section 15 Logic..................................................................................923
Tripping logic SMPPTRC (94).............................................................. 923
Identification.................................................................................... 923
Functionality.................................................................................... 923
Function block................................................................................. 924
Signals.............................................................................................924
Settings............................................................................................925
Operation principle.......................................................................... 925
Logic diagram............................................................................. 927
Technical data................................................................................. 931
Trip matrix logic TMAGAPC..................................................................932
Identification.................................................................................... 932
Functionality.................................................................................... 932
Function block................................................................................. 933
Signals.............................................................................................933
Settings............................................................................................935
Operation principle.......................................................................... 935
Technical data................................................................................. 936
Logic for group alarm ALMCALH..........................................................937
Identification.................................................................................... 937
Functionality.................................................................................... 937
Function block................................................................................. 937
Signals.............................................................................................937
Settings............................................................................................938
Operation principle.......................................................................... 938
Technical data................................................................................. 939
Logic for group warning WRNCALH..................................................... 939
Identification.................................................................................... 939
Functionality.................................................................................... 939
Function block................................................................................. 940
Signals.............................................................................................940
Settings............................................................................................941
Operation principle.......................................................................... 941
Technical data................................................................................. 941
22

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Logic for group indication INDCALH.....................................................942


Identification.................................................................................... 942
Functionality.................................................................................... 942
Function block................................................................................. 942
Signals.............................................................................................942
Settings............................................................................................943
Operation principle.......................................................................... 943
Technical data................................................................................. 944
Basic configurable logic blocks.............................................................944
AND function block AND................................................................. 945
Function block............................................................................ 945
Signals........................................................................................946
Technical data............................................................................ 946
Controllable gate function block GATE............................................946
Function block............................................................................ 946
Signals........................................................................................946
Settings.......................................................................................947
Technical data............................................................................ 947
Inverter function block INV.............................................................. 947
Function block............................................................................ 947
Signals........................................................................................947
Technical data............................................................................ 948
Loop delay function block LLD........................................................ 948
Function block............................................................................ 948
Signals........................................................................................948
Technical data............................................................................ 948
OR function block OR......................................................................949
Function block............................................................................ 949
Signals........................................................................................949
Technical data............................................................................ 949
Pulse timer function block PULSETIMER........................................950
Function block............................................................................ 950
Signals........................................................................................950
Settings.......................................................................................950
Technical data............................................................................ 950
Reset-set with memory function block RSMEMORY.......................951
Function block............................................................................ 951
Signals........................................................................................951
Settings.......................................................................................952
Technical data............................................................................ 952
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

23

Table of contents

Set-reset with memory function block SRMEMORY....................... 952


Function block............................................................................ 952
Signals........................................................................................953
Settings.......................................................................................953
Technical data............................................................................ 953
Settable timer function block TIMERSET........................................ 953
Function block............................................................................ 954
Signals........................................................................................954
Settings.......................................................................................955
Technical data............................................................................ 955
Exclusive OR function block XOR................................................... 955
Function block............................................................................ 955
Signals........................................................................................956
Technical data............................................................................ 956
Configurable logic blocks Q/T...............................................................956
ANDQT function block..................................................................... 958
Function block............................................................................ 958
Signals........................................................................................958
Technical data............................................................................ 958
Single point indication related signals combining function block
INDCOMBSPQT.............................................................................. 959
Function block............................................................................ 959
Signals........................................................................................959
Technical data............................................................................ 960
Single point input signal attributes converting function block
INDEXTSPQT..................................................................................960
Function block............................................................................ 960
Signals........................................................................................960
Technical data............................................................................ 961
Invalid logic function block INVALIDQT........................................... 961
Function block............................................................................ 962
Signals........................................................................................962
Technical data............................................................................ 963
Inverter function block INVERTERQT............................................. 963
Function block............................................................................ 963
Signals........................................................................................964
Technical data............................................................................ 964
ORQT function block....................................................................... 964
Function block............................................................................ 964
Signals........................................................................................964
24

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Technical data............................................................................ 965


Pulse timer function block PULSETIMERQT...................................965
Function block............................................................................ 966
Signals........................................................................................966
Settings.......................................................................................966
Technical data............................................................................ 966
Reset/Set function block RSMEMORYQT.......................................966
Function block............................................................................ 967
Signals........................................................................................967
Settings.......................................................................................968
Technical data............................................................................ 968
Set/Reset function block SRMEMORYQT.......................................968
Function block............................................................................ 969
Signals........................................................................................969
Settings.......................................................................................969
Technical data............................................................................ 969
Settable timer function block TIMERSETQT................................... 969
Function block............................................................................ 970
Signals........................................................................................970
Settings.......................................................................................970
Technical data............................................................................ 971
Exclusive OR function block XORQT.............................................. 971
Function block............................................................................ 971
Signals........................................................................................971
Technical data............................................................................ 972
Extension logic package....................................................................... 972
Fixed signals FXDSIGN........................................................................973
Identification.................................................................................... 973
Functionality.................................................................................... 973
Function block................................................................................. 973
Signals.............................................................................................973
Settings............................................................................................974
Operation principle.......................................................................... 974
Boolean 16 to Integer conversion B16I.................................................974
Identification.................................................................................... 974
Function block................................................................................. 975
Signals.............................................................................................975
Monitored data.................................................................................976
Settings............................................................................................976
Operation principle.......................................................................... 976
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

25

Table of contents

Technical data................................................................................. 977


Boolean 16 to Integer conversion with logic node representation
BTIGAPC.............................................................................................. 977
Identification.................................................................................... 977
Functionality.................................................................................... 978
Function block................................................................................. 978
Signals.............................................................................................978
Settings............................................................................................979
Monitored data.................................................................................979
Operation principle.......................................................................... 979
Technical data................................................................................. 980
Integer to boolean 16 conversion IB16................................................. 981
Identification.................................................................................... 981
Functionality.................................................................................... 981
Function block................................................................................. 981
Signals.............................................................................................981
Setting parameters.......................................................................... 982
Operation principle.......................................................................... 982
Technical data................................................................................. 984
Integer to Boolean 16 conversion with logic node representation IT
BGAPC................................................................................................. 984
Identification.................................................................................... 984
Functionality.................................................................................... 984
Function block................................................................................. 985
Signals.............................................................................................985
Settings............................................................................................986
Operation principle.......................................................................... 986
Technical data................................................................................. 987
Pulse integrator TIGAPC...................................................................... 987
Identification.................................................................................... 988
Functionality.................................................................................... 988
Function block................................................................................. 988
Signals.............................................................................................988
Settings............................................................................................988
Operation principle.......................................................................... 989
Elapsed time integrator with limit transgression and overflow
supervision TEIGAPC...........................................................................991
Identification.................................................................................... 991
Functionality.................................................................................... 991
Function block................................................................................. 992
26

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Signals.............................................................................................993
Settings............................................................................................993
Operation principle.......................................................................... 993
Operation accuracy.................................................................... 995
Memory storage..........................................................................995
Technical data................................................................................. 995
Comparator for integer inputs INTCOMP............................................. 996
Identification.................................................................................... 996
Functionality.................................................................................... 996
Function block................................................................................. 996
Signals.............................................................................................996
Settings............................................................................................997
Operation principle.......................................................................... 997
Technical data................................................................................. 998
Comparator for real inputs - REALCOMP.............................................998
Identification.................................................................................... 998
Functionality.................................................................................... 998
Function block................................................................................. 999
Signals.............................................................................................999
Settings............................................................................................999
Operation principle........................................................................ 1000
Technical data............................................................................... 1001

Section 16 Monitoring........................................................................1003
Measurements.................................................................................... 1003
Identification.................................................................................. 1003
Functionality.................................................................................. 1004
Function block............................................................................... 1005
Signals...........................................................................................1007
Settings..........................................................................................1010
Monitored data...............................................................................1023
Operation principle........................................................................ 1025
Measurement supervision........................................................ 1025
Measurements CVMMXN.........................................................1030
Phase current measurement CMMXU......................................1035
Phase-phase and phase-neutral voltage measurements
VMMXU, VNMMXU.................................................................. 1036
Voltage and current sequence measurements VMSQI, CMSQI1036
Technical data............................................................................... 1036
Gas medium supervision SSIMG (63)................................................ 1038
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

27

Table of contents

Identification.................................................................................. 1038
Functionality.................................................................................. 1039
Function block............................................................................... 1039
Signals...........................................................................................1039
Settings..........................................................................................1040
Operation principle........................................................................ 1040
Technical data............................................................................... 1041
Liquid medium supervision SSIML (71).............................................. 1042
Identification.................................................................................. 1042
Functionality.................................................................................. 1042
Function block............................................................................... 1042
Signals...........................................................................................1042
Settings..........................................................................................1043
Operation principle........................................................................ 1043
Technical data............................................................................... 1044
Breaker monitoring SSCBR................................................................ 1045
Identification.................................................................................. 1045
Functionality.................................................................................. 1045
Function block............................................................................... 1046
Signals...........................................................................................1046
Settings..........................................................................................1047
Monitored data...............................................................................1049
Operation principle........................................................................ 1049
Circuit breaker contact travel time............................................ 1051
Circuit breaker status................................................................1053
Remaining life of circuit breaker............................................... 1053
Accumulated energy.................................................................1054
Circuit breaker operation cycles............................................... 1056
Circuit breaker operation monitoring........................................ 1057
Circuit breaker spring charge monitoring..................................1058
Circuit breaker gas pressure indication.................................... 1058
Technical data............................................................................... 1059
Event function EVENT........................................................................ 1060
Identification.................................................................................. 1060
Functionality.................................................................................. 1060
Function block............................................................................... 1060
Signals...........................................................................................1061
Settings..........................................................................................1062
Operation principle........................................................................ 1064
Disturbance report DRPRDRE........................................................... 1065
28

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Identification.................................................................................. 1065
Functionality.................................................................................. 1066
Function block............................................................................... 1066
Signals...........................................................................................1068
Settings..........................................................................................1070
Monitored data...............................................................................1079
Operation principle........................................................................ 1083
Technical data............................................................................... 1091
Logical signal status report BINSTATREP......................................... 1091
Identification.................................................................................. 1091
Functionality.................................................................................. 1091
Function block............................................................................... 1092
Signals...........................................................................................1092
Settings..........................................................................................1093
Operation principle........................................................................ 1093
Measured value expander block RANGE_XP.................................... 1094
Identification.................................................................................. 1094
Functionality.................................................................................. 1094
Function block............................................................................... 1095
Signals...........................................................................................1095
Operation principle........................................................................ 1095
Limit counter L4UFCNT...................................................................... 1096
Identification.................................................................................. 1096
Identification............................................................................. 1096
Functionality.................................................................................. 1096
Operation principle........................................................................ 1096
Design...................................................................................... 1096
Reporting.................................................................................. 1098
Function block............................................................................... 1098
Signals...........................................................................................1098
Settings..........................................................................................1099
Monitored data...............................................................................1099
Technical data............................................................................... 1100
Running hour-meter TEILGAPC ........................................................ 1100
Identification.................................................................................. 1100
Functionality.................................................................................. 1100
Function block............................................................................... 1101
Signals...........................................................................................1101
Settings..........................................................................................1102
Operation principle........................................................................ 1102
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

29

Table of contents

Operation accuracy.................................................................. 1103


Memory storage........................................................................1104
Technical data............................................................................... 1104

Section 17 Metering.......................................................................... 1105


Pulse-counter logic PCFCNT..............................................................1105
Identification.................................................................................. 1105
Functionality.................................................................................. 1105
Function block............................................................................... 1105
Signals...........................................................................................1106
Settings..........................................................................................1106
Monitored data...............................................................................1107
Operation principle........................................................................ 1107
Technical data............................................................................... 1109
Function for energy calculation and demand handling ETPMMTR.... 1109
Identification.................................................................................. 1109
Functionality.................................................................................. 1109
Function block............................................................................... 1110
Signals...........................................................................................1111
Settings..........................................................................................1112
Monitored data...............................................................................1113
Operation principle........................................................................ 1113
Technical data............................................................................... 1117
Technical data.......................................................................... 1117

Section 18 Station communication.................................................... 1119


Communication protocols................................................................... 1119
Communication protocol diagnostics.................................................. 1119
DNP3 protocol.................................................................................... 1120
IEC 61850-8-1 communication protocol............................................. 1121
Communication interfaces and protocols...................................... 1121
Settings..........................................................................................1121
Technical data............................................................................... 1122
Generic communication function for Single Point indication
SPGAPC, SP16GAPC...................................................................1122
Functionality............................................................................. 1122
Function block.......................................................................... 1122
Signals......................................................................................1123
Settings.....................................................................................1124
Monitored data..........................................................................1124
Operation principle................................................................... 1125
30

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Generic communication function for Measured Value MVGAPC.. 1125


Functionality............................................................................. 1125
Function block.......................................................................... 1125
Signals......................................................................................1126
Settings.....................................................................................1126
Monitored data..........................................................................1127
Operation principle................................................................... 1127
IEC 61850-8-1 redundant station bus communication.................. 1127
Functionality............................................................................. 1127
Function block.......................................................................... 1127
Signals......................................................................................1128
Settings.....................................................................................1128
Monitored data..........................................................................1128
Principle of operation................................................................1129
LON communication protocol............................................................. 1131
Functionality.................................................................................. 1131
Settings..........................................................................................1131
Operation principle........................................................................ 1132
Technical data............................................................................... 1151
SPA communication protocol..............................................................1151
Functionality.................................................................................. 1151
Design........................................................................................... 1151
Settings..........................................................................................1152
Operation principle........................................................................ 1152
Communication ports................................................................1160
Technical data............................................................................... 1161
IEC 60870-5-103 communication protocol......................................... 1161
Introduction....................................................................................1161
Measurands for IEC 60870-5-103 I103MEAS............................... 1161
Functionality............................................................................. 1161
Identification............................................................................. 1162
Function block.......................................................................... 1162
Signals......................................................................................1162
Settings.....................................................................................1163
Measurands user defined signals for IEC 60870-5-103
I103MEASUSR..............................................................................1163
Functionality............................................................................. 1163
Identification............................................................................. 1163
Function block.......................................................................... 1164
Signals......................................................................................1164
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

31

Table of contents

Settings.....................................................................................1164
Function status auto-recloser for IEC 60870-5-103 I103AR..........1165
Functionality............................................................................. 1165
Identification............................................................................. 1165
Function block.......................................................................... 1165
Signals......................................................................................1166
Settings.....................................................................................1166
Function status ground-fault for IEC 60870-5-103 I103EF............1166
Functionality............................................................................. 1166
Identification............................................................................. 1166
Function block.......................................................................... 1166
Signals......................................................................................1167
Settings.....................................................................................1167
Function status fault protection for IEC 60870-5-103
I103FLTPROT............................................................................... 1167
Functionality............................................................................. 1167
Identification............................................................................. 1167
Function block.......................................................................... 1168
Signals......................................................................................1168
Settings.....................................................................................1169
IED status for IEC 60870-5-103 I103IED...................................... 1169
Functionality............................................................................. 1169
Identification............................................................................. 1170
Function block.......................................................................... 1170
Signals......................................................................................1170
Settings.....................................................................................1170
Supervison status for IEC 60870-5-103 I103SUPERV..................1171
Functionality............................................................................. 1171
Identification............................................................................. 1171
Function block.......................................................................... 1171
Signals......................................................................................1171
Settings.....................................................................................1172
Status for user defined signals for IEC 60870-5-103 I103USRDEF1172
Functionality............................................................................. 1172
Identification............................................................................. 1172
Function block.......................................................................... 1172
Signals......................................................................................1173
Settings.....................................................................................1173
Function commands for IEC 60870-5-103 I103CMD.................... 1175
Functionality............................................................................. 1175
32

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Identification............................................................................. 1175
Function block.......................................................................... 1175
Signals......................................................................................1175
Settings.....................................................................................1175
IED commands for IEC 60870-5-103 I103IEDCMD...................... 1176
Functionality............................................................................. 1176
Identification............................................................................. 1176
Function block.......................................................................... 1176
Signals......................................................................................1176
Settings.....................................................................................1177
Function commands user defined for IEC 60870-5-103
I103USRCMD................................................................................1177
Functionality............................................................................. 1177
Identification............................................................................. 1177
Function block.......................................................................... 1177
Signals......................................................................................1177
Settings.....................................................................................1178
Function commands generic for IEC 60870-5-103 I103GENCMD 1178
Functionality............................................................................. 1178
Identification............................................................................. 1179
Function block.......................................................................... 1179
Signals......................................................................................1179
Settings.....................................................................................1180
IED commands with position and select for IEC 60870-5-103
I103POSCMD................................................................................1180
Functionality............................................................................. 1180
Identification............................................................................. 1180
Function block.......................................................................... 1181
Signals......................................................................................1181
Settings.....................................................................................1181
Operation principle ....................................................................... 1181
General.....................................................................................1181
Communication ports................................................................1193
Technical data............................................................................... 1193
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV.............................................................................1193
Functionality.................................................................................. 1193
Function block............................................................................... 1194
Signals...........................................................................................1195
Settings..........................................................................................1196
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

33

Table of contents

Goose binary receive GOOSEBINRCV.............................................. 1197


Function block............................................................................... 1197
Signals...........................................................................................1197
Settings..........................................................................................1199
GOOSE function block to receive a double point value
GOOSEDPRCV.................................................................................. 1199
Identification.................................................................................. 1199
Functionality.................................................................................. 1199
Function block............................................................................... 1199
Signals...........................................................................................1199
Settings..........................................................................................1200
Operation principle ....................................................................... 1200
GOOSE function block to receive an integer value GOOSEINTRCV.1201
Identification.................................................................................. 1201
Functionality.................................................................................. 1201
Function block............................................................................... 1201
Signals...........................................................................................1201
Settings..........................................................................................1202
Operation principle ....................................................................... 1202
GOOSE function block to receive a measurand value GOOSEMVRCV1202
Identification.................................................................................. 1202
Functionality.................................................................................. 1203
Function block............................................................................... 1203
Signals...........................................................................................1203
Settings..........................................................................................1203
Operation principle ....................................................................... 1203
GOOSE function block to receive a single point value GOOSESPRCV1204
Identification.................................................................................. 1204
Functionality.................................................................................. 1204
Function block............................................................................... 1204
Signals...........................................................................................1205
Settings..........................................................................................1205
Operation principle ....................................................................... 1205
MULTICMDRCV and MULTICMDSND...............................................1206
Functionality.................................................................................. 1206
Design........................................................................................... 1206
General.....................................................................................1206
Function block............................................................................... 1207
Signals...........................................................................................1207
Settings..........................................................................................1209
34

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Operation principle........................................................................ 1209


Security events on protocols SECALARM..........................................1210
Security alarm SECALARM........................................................... 1210
Signals......................................................................................1210
Settings.....................................................................................1210
Activity logging parameters ACTIVLOG............................................. 1210
Activity logging ACTIVLOG........................................................... 1210
Settings..........................................................................................1211

Section 19 Remote communication...................................................1213


Binary signal transfer.......................................................................... 1213
Identification.................................................................................. 1213
Functionality.................................................................................. 1213
Function block............................................................................... 1214
Signals...........................................................................................1215
Settings..........................................................................................1216
Monitored data...............................................................................1219
Operation principle........................................................................ 1220
Transmission of analog data from LDCM LDCMTransmit.................. 1221
Function block............................................................................... 1221
Signals...........................................................................................1221

Section 20 Basic IED functions......................................................... 1223


Authority check ATHCHCK.................................................................1223
Identification.................................................................................. 1223
Functionality.................................................................................. 1223
Operation principle ....................................................................... 1224
Authorization with Central Account Management enabled IED1226
Authority management AUTHMAN.....................................................1229
Identification.................................................................................. 1229
AUTHMAN.....................................................................................1229
Settings..........................................................................................1229
FTP access with password FTPACCS............................................... 1230
Identification.................................................................................. 1230
FTP access with TLS, FTPACCS.................................................. 1230
Settings..........................................................................................1230
Authority status ATHSTAT..................................................................1231
Identification.................................................................................. 1231
Functionality.................................................................................. 1231
Function block............................................................................... 1231
Signals...........................................................................................1231
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

35

Table of contents

Settings..........................................................................................1231
Operation principle ....................................................................... 1232
Self supervision with internal event list INTERRSIG.......................... 1232
Functionality.................................................................................. 1232
Function block............................................................................... 1232
Signals...........................................................................................1233
Settings..........................................................................................1233
Operation principle........................................................................ 1233
Internal signals......................................................................... 1235
Supervision of analog inputs.................................................... 1237
Technical data............................................................................... 1237
Time synchronization..........................................................................1238
Functionality.................................................................................. 1238
Settings..........................................................................................1238
Operation principle ....................................................................... 1243
General concepts..................................................................... 1243
Real-time clock (RTC) operation.............................................. 1245
Synchronization alternatives.....................................................1246
Technical data............................................................................... 1250
Parameter setting groups................................................................... 1250
Functionality.................................................................................. 1250
Function block............................................................................... 1250
Signals...........................................................................................1251
Settings..........................................................................................1251
Operation principle........................................................................ 1251
ChangeLock function CHNGLCK....................................................... 1253
Functionality.................................................................................. 1253
Function block............................................................................... 1254
Signals...........................................................................................1254
Operation principle ....................................................................... 1254
Test mode functionality TEST.............................................................1255
Functionality.................................................................................. 1255
Function block............................................................................... 1255
Signals...........................................................................................1256
Settings..........................................................................................1256
Operation principle ....................................................................... 1256
IED identifiers..................................................................................... 1257
Functionality.................................................................................. 1257
Settings .........................................................................................1258
Product information.............................................................................1258
36

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Functionality.................................................................................. 1258
Settings .........................................................................................1259
Factory defined settings................................................................ 1259
Signal matrix for binary inputs SMBI...................................................1260
Functionality.................................................................................. 1260
Function block............................................................................... 1260
Signals...........................................................................................1260
Operation principle........................................................................ 1261
Signal matrix for binary outputs SMBO ..............................................1261
Functionality.................................................................................. 1261
Function block............................................................................... 1262
Signals...........................................................................................1262
Operation principle........................................................................ 1262
Signal matrix for mA inputs SMMI...................................................... 1262
Functionality.................................................................................. 1263
Function block............................................................................... 1263
Signals...........................................................................................1263
Operation principle........................................................................ 1264
Signal matrix for analog inputs SMAI..................................................1264
Functionality.................................................................................. 1264
Function block............................................................................... 1264
Signals...........................................................................................1265
Settings..........................................................................................1266
Operation principle ....................................................................... 1268
Frequency values..................................................................... 1269
Summation block 3 phase 3PHSUM.................................................. 1270
Functionality.................................................................................. 1270
Function block............................................................................... 1270
Signals...........................................................................................1271
Settings..........................................................................................1271
Operation principle ....................................................................... 1272
Global base values GBASVAL........................................................... 1272
Identification.................................................................................. 1272
Functionality.................................................................................. 1272
Settings..........................................................................................1273
Primary system values PRIMVAL.......................................................1273
Identification.................................................................................. 1273
Functionality.................................................................................. 1273
Settings..........................................................................................1273
Denial of service DOS........................................................................ 1274
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

37

Table of contents

Functionality ................................................................................. 1274


Function blocks..............................................................................1274
Signals...........................................................................................1274
Settings..........................................................................................1275
Monitored data...............................................................................1275
Operation principle........................................................................ 1276

Section 21 IED hardware.................................................................. 1277


Overview.............................................................................................1277
Variants of case size with local HMI display.................................. 1277
Case from the rear side................................................................. 1279
Hardware modules..............................................................................1284
Overview........................................................................................1284
Numeric processing module (NUM).............................................. 1285
Introduction...............................................................................1285
Functionality............................................................................. 1285
Block diagram...........................................................................1286
Power supply module (PSM)......................................................... 1286
Introduction...............................................................................1286
Design...................................................................................... 1287
Technical data.......................................................................... 1287
Local human-machine interface (Local HMI)................................. 1287
Transformer input module (TRM).................................................. 1287
Introduction...............................................................................1287
Design...................................................................................... 1288
Technical data.......................................................................... 1289
Analog digital conversion module, with time synchronization
(ADM) ........................................................................................... 1290
Introduction...............................................................................1290
Design...................................................................................... 1291
Binary input module (BIM)............................................................. 1293
Introduction...............................................................................1293
Design...................................................................................... 1293
Signals......................................................................................1296
Settings.....................................................................................1297
Monitored data..........................................................................1297
Technical data.......................................................................... 1298
Binary output modules (BOM)....................................................... 1299
Introduction...............................................................................1299
Design...................................................................................... 1299
38

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Signals......................................................................................1300
Settings.....................................................................................1301
Monitored data..........................................................................1301
Technical data.......................................................................... 1305
Static binary output module (SOM)............................................... 1306
Introduction...............................................................................1306
Design...................................................................................... 1306
Signals......................................................................................1307
Settings.....................................................................................1308
Monitored data..........................................................................1308
Technical data.......................................................................... 1310
Binary input/output module (IOM)..................................................1311
Introduction...............................................................................1311
Design...................................................................................... 1312
Signals......................................................................................1314
Settings.....................................................................................1315
Monitored data..........................................................................1315
Technical data.......................................................................... 1317
mA input module (MIM)................................................................. 1320
Introduction...............................................................................1320
Design...................................................................................... 1320
Signals......................................................................................1322
Settings.....................................................................................1322
Monitored data..........................................................................1324
Technical data.......................................................................... 1324
Serial and LON communication module (SLM) ............................ 1324
Introduction...............................................................................1324
Design...................................................................................... 1325
Technical data.......................................................................... 1326
Galvanic RS485 communication module.......................................1326
Introduction...............................................................................1326
Design...................................................................................... 1326
Technical data.......................................................................... 1328
Optical ethernet module (OEM).....................................................1328
Introduction...............................................................................1328
Functionality............................................................................. 1328
Design...................................................................................... 1328
Technical data.......................................................................... 1329
Line data communication module (LDCM).................................... 1329
Introduction...............................................................................1329
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

39

Table of contents

Design...................................................................................... 1330
Technical data.......................................................................... 1331
Galvanic X.21 line data communication (X.21-LDCM).................. 1332
Introduction...............................................................................1332
Design...................................................................................... 1332
Functionality............................................................................. 1335
Technical data.......................................................................... 1335
GPS time synchronization module (GTM)..................................... 1336
Introduction...............................................................................1336
Design...................................................................................... 1336
Monitored data..........................................................................1336
Technical data.......................................................................... 1336
GPS antenna................................................................................. 1337
Introduction...............................................................................1337
Design...................................................................................... 1337
Technical data.......................................................................... 1338
IRIG-B time synchronization module IRIG-B................................. 1338
Introduction...............................................................................1338
Design...................................................................................... 1338
Settings.....................................................................................1339
Technical data.......................................................................... 1339
Dimensions......................................................................................... 1341
Case without rear cover.................................................................1341
Case with rear cover......................................................................1343
Flush mounting dimensions...........................................................1345
Side-by-side flush mounting dimensions....................................... 1346
Wall mounting dimensions.............................................................1348
External resistor unit for high impedance differential protection.... 1348
External current transformer unit................................................... 1350
Mounting alternatives..........................................................................1350
Flush mounting.............................................................................. 1350
Overview...................................................................................1350
Mounting procedure for flush mounting.................................... 1351
19 panel rack mounting................................................................ 1352
Overview...................................................................................1352
Mounting procedure for 19 panel rack mounting.....................1353
Wall mounting................................................................................1354
Overview...................................................................................1354
Mounting procedure for wall mounting..................................... 1355
How to reach the rear side of the IED...................................... 1355
40

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Table of contents

Side-by-side 19 rack mounting.....................................................1356


Overview...................................................................................1356
Mounting procedure for side-by-side rack mounting................ 1357
IED mounted with a RHGS6 case............................................ 1357
Side-by-side flush mounting.......................................................... 1358
Overview...................................................................................1358
Mounting procedure for side-by-side flush mounting................1359
Technical data.................................................................................... 1359
Enclosure.......................................................................................1359
Electrical safety............................................................................. 1360
Connection system........................................................................ 1360
Influencing factors......................................................................... 1361
Type tests according to standard.................................................. 1362

Section 22 Injection equipment hardware......................................... 1365


Overview.............................................................................................1365
Front view of injection unit, coupling capacitor and shunt resitor unit1365
Injection unit REX060............................................................... 1365
REX060 Front panel controls................................................... 1366
Coupling capacitor unit REX061...............................................1368
Shunt resistor unit REX062...................................................... 1369
Injection unit REX060 from rear side.............................................1371
Injection unit REX060............................................................... 1371
Injection unit REX060......................................................................... 1371
Introduction....................................................................................1371
Design........................................................................................... 1371
Coupling capacitor unit REX061.........................................................1375
Introduction....................................................................................1375
Design........................................................................................... 1375
Shunt resistor unit REX062................................................................ 1376
Introduction....................................................................................1376
Design........................................................................................... 1376
Technical data.................................................................................... 1378
Hardware....................................................................................... 1378
Type tests according to standards.................................................1380
Influencing factors......................................................................... 1382

Section 23 Labels..............................................................................1385
Labels on IED..................................................................................... 1385
Labels on injection equipment............................................................ 1388
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

41

Table of contents

Section 24 Connection diagrams...................................................... 1393


Section 25 Inverse time characteristics.............................................1395
Application.......................................................................................... 1395
Principle of operation.......................................................................... 1398
Mode of operation..........................................................................1398
Inverse characteristics........................................................................ 1404

Section 26 Glossary.......................................................................... 1435


Glossary..............................................................................................1435

42

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 1
Introduction

1MRK 502 066-UUS A

Section 1

Introduction

1.1

This manual
The technical manual contains operation principle descriptions, and lists function blocks,
logic diagrams, input and output signals, setting parameters and technical data, sorted per
function. The manual can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

1.2

Intended audience
This manual addresses system engineers and installation and commissioning personnel,
who use technical data during engineering, installation and commissioning, and in normal
service.
The system engineer must have a thorough knowledge of protection systems, protection
equipment, protection functions and the configured functional logic in the IEDs. The
installation and commissioning personnel must have a basic knowledge in handling
electronic equipment.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

43

Section 1
Introduction

Decommissioning
Deinstalling & disposal

Maintenance

Operation

Product documentation set

Commissioning

1.3.1

Engineering

Product documentation

Planning & purchase

1.3

Installing

1MRK 502 066-UUS A

Engineering manual
Installation manual
Commissioning manual
Operation manual
Application manual
Technical manual
Communication
protocol manual
Cyber security
deployment guideline
IEC07000220-4-en.vsd
IEC07000220 V4 EN

Figure 1:

The intended use of manuals throughout the product lifecycle

The engineering manual contains instructions on how to engineer the IEDs using the
various tools available within the PCM600 software. The manual provides instructions on
how to set up a PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for the engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 60870-5-103, IEC 61850, DNP3,
LON and SPA.
The installation manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are organized
in the chronological order in which the IED should be installed.

44

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 1
Introduction

1MRK 502 066-UUS A

The commissioning manual contains instructions on how to commission the IED. The
manual can also be used by system engineers and maintenance personnel for assistance
during the testing phase. The manual provides procedures for the checking of external
circuitry and energizing the IED, parameter setting and configuration as well as verifying
settings by secondary injection. The manual describes the process of testing an IED in a
substation which is not in service. The chapters are organized in the chronological order
in which the IED should be commissioned. The relevant procedures may be followed also
during the service and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and
setting of the IED. The manual also describes how to identify disturbances and how to
view calculated and measured power grid data to determine the cause of a fault.
The application manual contains application descriptions and setting guidelines sorted per
function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also provide assistance for calculating
settings.
The technical manual contains operation principle descriptions, and lists function blocks,
logic diagrams, input and output signals, setting parameters and technical data, sorted per
function. The manual can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.
The communication protocol manual describes the communication protocols supported
by the IED. The manual concentrates on the vendor-specific implementations.
The point list manual describes the outlook and properties of the data points specific to the
IED. The manual should be used in conjunction with the corresponding communication
protocol manual.
The cyber security deployment guideline describes the process for handling cyber security
when communicating with the IED. Certification, Authorization with role based access
control, and product engineering for cyber security related events are described and sorted
by function. The guideline can be used as a technical reference during the engineering
phase, installation and commissioning phase, and during normal service.

1.3.2

Document revision history


Document revision/date

History

December 2015

First release

A/February 2016

Minor updates

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

45

Section 1
Introduction
1.3.3

1MRK 502 066-UUS A

Related documents
Documents related to REG670

Document numbers

Application manual

1MRK 502 065-UUS

Commissioning manual

1MRK 502 067-UUS

Product guide

1MRK 502 068-BEN

Technical manual

1MRK 502 066-UUS

Type test certificate

1MRK 502 068-TUS

670 series manuals

Document numbers

Operation manual

1MRK 500 123-UUS

Engineering manual

1MRK 511 355-UUS

Installation manual

1MRK 514 024-UUS

Communication protocol manual, DNP3

1MRK 511 348-UUS

Communication protocol manual, IEC 61850 Edition


2

1MRK 511 350-UEN

Point list manual, DNP3

1MRK 511 354-UUS

Accessories guide

1MRK 514 012-BUS

Connection and Installation components

1MRK 513 003-BEN

Test system, COMBITEST

1MRK 512 001-BEN

1.4

Document symbols and conventions

1.4.1

Symbols
The electrical warning icon indicates the presence of a hazard which could
result in electrical shock.

The warning icon indicates the presence of a hazard which could result in
personal injury.

The caution hot surface icon indicates important information or warning


about the temperature of product surfaces.

46

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 1
Introduction

1MRK 502 066-UUS A

Class 1 Laser product. Take adequate measures to protect the eyes and do
not view directly with optical instruments.

The caution icon indicates important information or warning related to the


concept discussed in the text. It might indicate the presence of a hazard
which could result in corruption of software or damage to equipment or
property.

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project
or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand that
under certain operational conditions, operation of damaged equipment may result in
degraded process performance leading to personal injury or death. It is important that the
user fully complies with all warning and cautionary notices.

1.4.2

Document conventions

Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
Push button navigation in the LHMI menu structure is presented by using the push
button icons.
For example, to navigate between the options, use
and
.
HMI menu paths are presented in bold.
For example, select Main menu/Settings.
LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press
.
Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
Each function block symbol shows the available input/output signal.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

47

Section 1
Introduction

1MRK 502 066-UUS A

Logic diagrams describe the signal logic inside the function block and are bordered
by dashed lines.

1.5

the character ^ in front of an input/output signal name indicates that the signal
name may be customized using the PCM600 software.
the character * after an input signal name indicates that the signal must be
connected to another function block in the application configuration to achieve
a valid application configuration.

Signals in frames with a shaded area on their right hand side represent setting
parameter signals that are only settable via the PST or LHMI.
If an internal signal path cannot be drawn with a continuous line, the suffix -int
is added to the signal name to indicate where the signal starts and continues.
Signal paths that extend beyond the logic diagram and continue in another
diagram have the suffix -cont.

Dimensions are provided both in inches and mm. If it is not specifically mentioned
then the dimension is in mm.

IEC61850 edition 1 / edition 2 mapping


Table 1:

IEC61850 edition 1 / edition 2 mapping

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

AEGPVOC

AEGGAPC

AEGPVOC

AGSAL

AGSAL
SECLLN0

AGSAL

ALMCALH

ALMCALH

ALMCALH

ALTIM

ALTIM

ALTMS

ALTMS

ALTRK

ALTRK

BCZSPDIF

BCZSPDIF

BCZSPDIF

BCZTPDIF

BCZTPDIF

BCZTPDIF

BDCGAPC

SWSGGIO

BBCSWI
BDCGAPC

BRCPTOC

BRCPTOC

BRCPTOC

BRPTOC

BRPTOC

BRPTOC

BTIGAPC

B16IFCVI

BTIGAPC

BUSPTRC_B1

BUSPTRC
BBSPLLN0

BUSPTRC

BUSPTRC_B2

BUSPTRC

BUSPTRC

BUSPTRC_B3

BUSPTRC

BUSPTRC

Table continues on next page

48

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 1
Introduction

1MRK 502 066-UUS A

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

BUSPTRC_B4

BUSPTRC

BUSPTRC

BUSPTRC_B5

BUSPTRC

BUSPTRC

BUSPTRC_B6

BUSPTRC

BUSPTRC

BUSPTRC_B7

BUSPTRC

BUSPTRC

BUSPTRC_B8

BUSPTRC

BUSPTRC

BUSPTRC_B9

BUSPTRC

BUSPTRC

BUSPTRC_B10

BUSPTRC

BUSPTRC

BUSPTRC_B11

BUSPTRC

BUSPTRC

BUSPTRC_B12

BUSPTRC

BUSPTRC

BUSPTRC_B13

BUSPTRC

BUSPTRC

BUSPTRC_B14

BUSPTRC

BUSPTRC

BUSPTRC_B15

BUSPTRC

BUSPTRC

BUSPTRC_B16

BUSPTRC

BUSPTRC

BUSPTRC_B17

BUSPTRC

BUSPTRC

BUSPTRC_B18

BUSPTRC

BUSPTRC

BUSPTRC_B19

BUSPTRC

BUSPTRC

BUSPTRC_B20

BUSPTRC

BUSPTRC

BUSPTRC_B21

BUSPTRC

BUSPTRC

BUSPTRC_B22

BUSPTRC

BUSPTRC

BUSPTRC_B23

BUSPTRC

BUSPTRC

BUSPTRC_B24

BUSPTRC

BUSPTRC

BUTPTRC_B1

BUTPTRC
BBTPLLN0

BUTPTRC

BUTPTRC_B2

BUTPTRC

BUTPTRC

BUTPTRC_B3

BUTPTRC

BUTPTRC

BUTPTRC_B4

BUTPTRC

BUTPTRC

BUTPTRC_B5

BUTPTRC

BUTPTRC

BUTPTRC_B6

BUTPTRC

BUTPTRC

BUTPTRC_B7

BUTPTRC

BUTPTRC

BUTPTRC_B8

BUTPTRC

BUTPTRC

BZISGGIO

BZISGGIO

BZISGAPC

BZITGGIO

BZITGGIO

BZITGAPC

BZNSPDIF_A

BZNSPDIF

BZASGAPC
BZASPDIF
BZNSGAPC
BZNSPDIF

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

49

Section 1
Introduction

1MRK 502 066-UUS A

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

BZNSPDIF_B

BZNSPDIF

BZBSGAPC
BZBSPDIF
BZNSGAPC
BZNSPDIF

BZNTPDIF_A

BZNTPDIF

BZATGAPC
BZATPDIF
BZNTGAPC
BZNTPDIF

BZNTPDIF_B

BZNTPDIF

BZBTGAPC
BZBTPDIF
BZNTGAPC
BZNTPDIF

CBPGAPC

CBPLLN0
CBPMMXU
CBPPTRC
HOLPTOV
HPH1PTOV
PH3PTUC
PH3PTOC
RP3PDOP

CBPMMXU
CBPPTRC
HOLPTOV
HPH1PTOV
PH3PTOC
PH3PTUC
RP3PDOP

CCPDSC

CCRPLD

CCPDSC

CCRBRF

CCRBRF

CCRBRF

CCRWRBRF

CCRWRBRF

CCRWRBRF

CCSRBRF

CCSRBRF

CCSRBRF

CCSSPVC

CCSRDIF

CCSSPVC

CMMXU

CMMXU

CMMXU

CMSQI

CMSQI

CMSQI

COUVGAPC

COUVLLN0
COUVPTOV
COUVPTUV

COUVPTOV
COUVPTUV

CVGAPC

GF2LLN0
GF2MMXN
GF2PHAR
GF2PTOV
GF2PTUC
GF2PTUV
GF2PVOC
PH1PTRC

GF2MMXN
GF2PHAR
GF2PTOV
GF2PTUC
GF2PTUV
GF2PVOC
PH1PTRC

CVMMXN

CVMMXN

CVMMXN

D2PTOC

D2LLN0
D2PTOC
PH1PTRC

D2PTOC
PH1PTRC

DPGAPC

DPGGIO

DPGAPC

DRPRDRE

DRPRDRE

DRPRDRE

ECPSCH

ECPSCH

ECPSCH

ECRWPSCH

ECRWPSCH

ECRWPSCH

Table continues on next page

50

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 1
Introduction

1MRK 502 066-UUS A

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

EF2PTOC

EF2LLN0
EF2PTRC
EF2RDIR
GEN2PHAR
PH1PTOC

EF2PTRC
EF2RDIR
GEN2PHAR
PH1PTOC

EF4PTOC

EF4LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC

EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC

EFPIOC

EFPIOC

EFPIOC

EFRWPIOC

EFRWPIOC

EFRWPIOC

ETPMMTR

ETPMMTR

ETPMMTR

FDPSPDIS

FDPSPDIS

FDPSPDIS

FMPSPDIS

FMPSPDIS

FMPSPDIS

FRPSPDIS

FPSRPDIS

FPSRPDIS

FTAQFVR

FTAQFVR

FTAQFVR

FUFSPVC

SDDRFUF

FUFSPVC
SDDSPVC

GENPDIF

GENPDIF

GENGAPC
GENPDIF
GENPHAR
GENPTRC

GOOSEBINRCV

BINGREC

GOOSEDPRCV

DPGREC

GOOSEINTLKRCV

INTGREC

GOOSEINTRCV

INTSGREC

GOOSEMVRCV

MVGREC

GOOSESPRCV

BINSGREC

GOOSEVCTRRCV

VCTRGREC

GOPPDOP

GOPPDOP

GOPPDOP
PH1PTRC

GRPTTR

GRPTTR

GRPTTR

GSPTTR

GSPTTR

GSPTTR

GUPPDUP

GUPPDUP

GUPPDUP
PH1PTRC

HZPDIF

HZPDIF

HZPDIF

INDCALCH

INDCALH

INDCALH

ITBGAPC

IB16FCVB

ITBGAPC

L3CPDIF

L3CPDIF

L3CGAPC
L3CPDIF
L3CPHAR
L3CPTRC

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

51

Section 1
Introduction

1MRK 502 066-UUS A

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

L4UFCNT

L4UFCNT

L4UFCNT

L6CPDIF

L6CPDIF

L6CGAPC
L6CPDIF
L6CPHAR
L6CPTRC

LAPPGAPC

LAPPLLN0
LAPPPDUP
LAPPPUPF

LAPPPDUP
LAPPPUPF

LCCRPTRC

LCCRPTRC

LCCRPTRC

LCNSPTOC

LCNSPTOC

LCNSPTOC

LCNSPTOV

LCNSPTOV

LCNSPTOV

LCP3PTOC

LCP3PTOC

LCP3PTOC

LCP3PTUC

LCP3PTUC

LCP3PTUC

LCPTTR

LCPTTR

LCPTTR

LCZSPTOC

LCZSPTOC

LCZSPTOC

LCZSPTOV

LCZSPTOV

LCZSPTOV

LD0LLN0

LLN0

LDLPSCH

LDLPDIF

LDLPSCH

LDRGFC

STSGGIO

LDRGFC

LEXPDIS

LEXPDIS

LEXPDIS
LEXPTRC

LFPTTR

LFPTTR

LFPTTR

LMBRFLO

LMBRFLO

LMBRFLO

LOVPTUV

LOVPTUV

LOVPTUV

LPHD

LPHD

LPTTR

LPTTR

LPTTR

LT3CPDIF

LT3CPDIF

LT3CGAPC
LT3CPDIF
LT3CPHAR
LT3CPTRC

LT6CPDIF

LT6CPDIF

LT6CGAPC
LT6CPDIF
LT6CPHAR
LT6CPTRC

MVGAPC

MVGGIO

MVGAPC

NS2PTOC

NS2LLN0
NS2PTOC
NS2PTRC

NS2PTOC
NS2PTRC

NS4PTOC

EF4LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC

EF4PTRC
EF4RDIR
PH1PTOC

Table continues on next page

52

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 1
Introduction

1MRK 502 066-UUS A

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

O2RWPTOV

GEN2LLN0
O2RWPTOV
PH1PTRC

O2RWPTOV
PH1PTRC

OC4PTOC

OC4LLN0
GEN4PHAR
PH3PTOC
PH3PTRC

GEN4PHAR
PH3PTOC
PH3PTRC

OEXPVPH

OEXPVPH

OEXPVPH

OOSPPAM

OOSPPAM

OOSPPAM
OOSPTRC

OV2PTOV

GEN2LLN0
OV2PTOV
PH1PTRC

OV2PTOV
PH1PTRC

PAPGAPC

PAPGAPC

PAPGAPC

PCFCNT

PCGGIO

PCFCNT

PH4SPTOC

GEN4PHAR
OCNDLLN0
PH1BPTOC
PH1PTRC

GEN4PHAR
PH1BPTOC
PH1PTRC

PHPIOC

PHPIOC

PHPIOC

PRPSTATUS

RCHLCCH

RCHLCCH
SCHLCCH

PSLPSCH

ZMRPSL

PSLPSCH

PSPPPAM

PSPPPAM

PSPPPAM
PSPPTRC

QCBAY

QCBAY

QCRSV

QCRSV

QCRSV

REFPDIF

REFPDIF

REFPDIF

ROTIPHIZ

ROTIPHIZ

ROTIPHIZ
ROTIPTRC

ROV2PTOV

GEN2LLN0
PH1PTRC
ROV2PTOV

PH1PTRC
ROV2PTOV

SAPFRC

SAPFRC

SAPFRC

SAPTOF

SAPTOF

SAPTOF

SAPTUF

SAPTUF

SAPTUF

SCCVPTOC

SCCVPTOC

SCCVPTOC

SCILO

SCILO

SCILO

SCSWI

SCSWI

SCSWI

SDEPSDE

SDEPSDE

SDEPSDE
SDEPTOC
SDEPTOV
SDEPTRC

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

53

Section 1
Introduction

1MRK 502 066-UUS A

Function block name


SESRSYN

Edition 1 logical nodes


RSY1LLN0
AUT1RSYN
MAN1RSYN
SYNRSYN

SINGLELCCH

Edition 2 logical nodes


AUT1RSYN
MAN1RSYN
SYNRSYN
SCHLCCH

SLGAPC

SLGGIO

SLGAPC

SMBRREC

SMBRREC

SMBRREC

SMPPTRC

SMPPTRC

SMPPTRC

SP16GAPC

SP16GGIO

SP16GAPC

SPC8GAPC

SPC8GGIO

SPC8GAPC

SPGAPC

SPGGIO

SPGAPC

SSCBR

SSCBR

SSCBR

SSIMG

SSIMG

SSIMG

SSIML

SSIML

SSIML

STBPTOC

STBPTOC

BBPMSS
STBPTOC

STEFPHIZ

STEFPHIZ

STEFPHIZ

STTIPHIZ

STTIPHIZ

STTIPHIZ

SXCBR

SXCBR

SXCBR

SXSWI

SXSWI

SXSWI

T2WPDIF

T2WPDIF

T2WGAPC
T2WPDIF
T2WPHAR
T2WPTRC

T3WPDIF

T3WPDIF

T3WGAPC
T3WPDIF
T3WPHAR
T3WPTRC

TCLYLTC

TCLYLTC

TCLYLTC
TCSLTC

TCMYLTC

TCMYLTC

TCMYLTC

TEIGAPC

TEIGGIO

TEIGAPC
TEIGGIO

TEILGAPC

TEILGGIO

TEILGAPC

TMAGAPC

TMAGGIO

TMAGAPC

TPPIOC

TPPIOC

TPPIOC

TR1ATCC

TR1ATCC

TR1ATCC

TR8ATCC

TR8ATCC

TR8ATCC

TRPTTR

TRPTTR

TRPTTR

U2RWPTUV

GEN2LLN0
PH1PTRC
U2RWPTUV

PH1PTRC
U2RWPTUV

Table continues on next page


54

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 1
Introduction

1MRK 502 066-UUS A

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

UV2PTUV

GEN2LLN0
PH1PTRC
UV2PTUV

PH1PTRC
UV2PTUV

VDCPTOV

VDCPTOV

VDCPTOV

VDSPVC

VDRFUF

VDSPVC

VMMXU

VMMXU

VMMXU

VMSQI

VMSQI

VMSQI

VNMMXU

VNMMXU

VNMMXU

VRPVOC

VRLLN0
PH1PTRC
PH1PTUV
VRPVOC

PH1PTRC
PH1PTUV
VRPVOC

VSGAPC

VSGGIO

VSGAPC

WRNCALH

WRNCALH

WRNCALH

ZC1PPSCH

ZPCPSCH

ZPCPSCH

ZC1WPSCH

ZPCWPSCH

ZPCWPSCH

ZCLCPSCH

ZCLCPLAL

ZCLCPSCH

ZCPSCH

ZCPSCH

ZCPSCH

ZCRWPSCH

ZCRWPSCH

ZCRWPSCH

ZCVPSOF

ZCVPSOF

ZCVPSOF

ZGVPDIS

ZGVLLN0
PH1PTRC
ZGVPDIS
ZGVPTUV

PH1PTRC
ZGVPDIS
ZGVPTUV

ZMCAPDIS

ZMCAPDIS

ZMCAPDIS

ZMCPDIS

ZMCPDIS

ZMCPDIS

ZMFCPDIS

ZMFCLLN0
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU

PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU

ZMFPDIS

ZMFLLN0
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU

PSFPDIS
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU

ZMHPDIS

ZMHPDIS

ZMHPDIS

ZMMAPDIS

ZMMAPDIS

ZMMAPDIS

ZMMPDIS

ZMMPDIS

ZMMPDIS

ZMQAPDIS

ZMQAPDIS

ZMQAPDIS

ZMQPDIS

ZMQPDIS

ZMQPDIS

ZMRAPDIS

ZMRAPDIS

ZMRAPDIS

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

55

Section 1
Introduction

1MRK 502 066-UUS A

Function block name

56

Edition 1 logical nodes

Edition 2 logical nodes

ZMRPDIS

ZMRPDIS

ZMRPDIS

ZMRPSB

ZMRPSB

ZMRPSB

ZSMGAPC

ZSMGAPC

ZSMGAPC

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 2
Available functions

1MRK 502 066-UUS A

Section 2

Available functions

2.1

Main protection functions


Table 2:

IEC 61850

ANSI

Example of quantities

= number of basic instances

0-3

= option quantities

3-A03

= optional function included in packages A03 (refer to ordering details)

Function description

Generator
REG670 (Customized)

Differential protection
T2WPDIF

87T

Transformer differential protection, two winding

0-2

T3WPDIF

87T

Transformer differential protection, three winding

0-2

HZPDIF

87

1Ph high impedance differential protection

0-6

GENPDIF

87G

Generator differential protection

0-2

REFPDIF

87N

Restricted earth fault protection, low impedance

0-3

Impedance protection
ZMHPDIS

21

Fullscheme distance protection, mho characteristic

0-4

ZDMRDIR

21D

Directional impedance element for mho characteristic

0-2

ZMFPDIS

21

High speed distance protection

01

ZMFCPDIS

21

High speed distance protection for series compensated


lines

01

PSPPPAM

78

Pole slip/out-of-step protection

0-1

OOSPPAM

78

Out-of-step protection

0-1

LEXPDIS

40

Loss of excitation

0-2

ROTIPHIZ

64R

Sensitive rotor ground fault protection, injection based

0-1

STTIPHIZ

64S

100% stator ground fault protection, injection based

0-1

ZGVPDIS

21

Underimpedance protection for generators and


transformers

01

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

57

Section 2
Available functions

2.2
IEC 61850

1MRK 502 066-UUS A

Back-up protection functions


ANSI

Function description

REG670 (Customized)

Current protection
PHPIOC

50

Instantaneous phase overcurrent protection

0-4

OC4PTOC

51_671)

Four step phase overcurrent protection

0-6

EFPIOC

50N

Instantaneous residual overcurrent protection

0-2

EF4PTOC

51N
67N2)

Four step residual overcurrent protection

0-6

NS4PTOC

46I2

Four step directional negative phase sequence


overcurrent protection

0-2

SDEPSDE

67N

Sensitive directional residual overcurrent and power


protection

0-2

TRPTTR

49

Thermal overload protection, two time constant

0-3

CCRBRF

50BF

Breaker failure protection

0-4

CCPDSC

52PD

Pole discordance protection

0-4

GUPPDUP

37

Directional underpower protection

0-4

GOPPDOP

32

Directional overpower protection

0-4

NS2PTOC

46I2

Negative sequence time overcurrent protection for


machines

0-2

AEGPVOC

50AE

Accidental energizing protection for synchronous


generator

0-2

VRPVOC

51V

Voltage restrained overcurrent protection

0-3

GSPTTR

49S

Stator overload protection

0-1

GRPTTR

49R

Rotor overload protection

01

UV2PTUV

27

Two step undervoltage protection

0-2

OV2PTOV

59

Two step overvoltage protection

0-2

ROV2PTOV

59N

Two step residual overvoltage protection

0-3

OEXPVPH

24

Overexcitation protection

0-2

VDCPTOV

60

Voltage differential protection

0-2

STEFPHIZ

59THD

100% stator earth fault protection, 3rd harmonic based

0-1

Voltage protection

Frequency protection
SAPTUF

81

Underfrequency protection

0-6

SAPTOF

81

Overfrequency protection

0-6

SAPFRC

81

Rate-of-change frequency protection

0-3

Table continues on next page

58

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 2
Available functions

1MRK 502 066-UUS A

IEC 61850

ANSI

FTAQFVR

81A

Function description

REG670 (Customized)

Frequency time accumulation protection

0-12

General current and voltage protection

1-12

Multipurpose filter

0-6

Multipurpose protection
CVGAPC
General calculation
SMAIHPAC
1) 67 requires voltage
2) 67N requires voltage

2.3
IEC 61850

Control and monitoring functions


ANSI

Function description

Generator
REG670

Control
SESRSYN

25

Synchrocheck, energizing check and


synchronizing

0-2

APC30

Apparatus control for up to 6 bays, max 30


apparatuses (6CBs) incl. interlocking

0-1

QCBAY

Apparatus control

1+5/APC30

LOCREM

Handling of LRswitch positions

1+5/APC30

LOCREMCTRL

LHMI control of PSTO

1+5/APC30

TR8ATCC

90

Automatic voltage control for tap changer, parallel


control

TCMYLTC

84

Tap changer control and supervision, 6 binary


inputs

0-4

TCLYLTC

84

Tap changer control and supervision, 32 binary


inputs

0-4

SLGAPC

Logic rotating switch for function selection and


LHMI presentation

15

VSGAPC

Selector mini switch

20

DPGAPC

Generic communication function for Double Point


indication

16

SPC8GAPC

Single point generic control 8 signals

AUTOBITS

AutomationBits, command function for DNP3.0

SINGLECMD

Single command, 16 signals

I103CMD

Function commands for IEC 60870-5-103

I103GENCMD

Function commands generic for IEC 60870-5-103

50

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

59

Section 2
Available functions

IEC 61850

ANSI

1MRK 502 066-UUS A

Function description

Generator
REG670

I103POSCMD

IED commands with position and select for IEC


60870-5-103

50

I103POSCMDV

IED direct commands with position for IEC


60870-5-103

10

I103IEDCMD

IED commands for IEC 60870-5-103

I103USRCMD

Function commands user defined for IEC


60870-5-103

Secondary system
supervision
CCSSPVC

87

Current circuit supervision

0-5

Fuse failure supervision

0-3

60

Fuse failure supervision based on voltage


difference

0-3

94

Tripping logic

12

TMAGAPC

Trip matrix logic

12

ALMCALH

Logic for group alarm

WRNCALH

Logic for group warning

INDCALH

Logic for group indication

AND, GATE, INV,


LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR

Basic configurable logic blocks (see Table 3)

40-280

ANDQT,
INDCOMBSPQT,
INDEXTSPQT,
INVALIDQT,
INVERTERQT,
ORQT,
PULSETIMERQT,
RSMEMORYQT,
SRMEMORYQT,
TIMERSETQT,
XORQT

Configurable logic blocks Q/T (see Table 4)

01

AND, GATE, INV,


LLD, OR,
PULSETIMER,
SLGAPC,
SRMEMORY,
TIMERSET,
VSGAPC, XOR

Extension logic package (see Table 5)

01

FXDSIGN

Fixed signal function block

B16I

Boolean 16 to Integer conversion

18

FUFSPVC
VDSPVC
Logic
SMPPTRC

Table continues on next page

60

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 2
Available functions

1MRK 502 066-UUS A

IEC 61850

ANSI

Function description

Generator
REG670

BTIGAPC

Boolean 16 to Integer conversion with Logic Node


representation

16

IB16

Integer to Boolean 16 conversion

18

ITBGAPC

Integer to Boolean 16 conversion with Logic Node


representation

16

TIGAPC

Delay on timer with input signal integration

30

TEIGAPC

Elapsed time integrator with limit transgression


and overflow supervision

12

INTCOMP

Comparator for integer inputs

12

REALCOMP

Comparator for real inputs

12

CVMMXN,
VMMXU, CMSQI,
VMSQI, VNMMXU

Measurements

CMMXU

Measurements

10

AISVBAS

Function block for service value presentation of


secondary analog inputs

EVENT

Event function

20

DRPRDRE,
A1RADRA4RADR,
B1RBDRB8RBDR

Disturbance report

SPGAPC

Generic communication function for Single Point


indication

64

SP16GAPC

Generic communication function for Single Point


indication 16 inputs

16

MVGAPC

Generic communication function for Measured


Value

24

BINSTATREP

Logical signal status report

RANGE_XP

Measured value expander block

66

Gas medium supervision

21

Monitoring

SSIMG

63

SSIML

71

Liquid medium supervision

SSCBR

Circuit breaker monitoring

0-12

I103MEAS

Measurands for IEC 60870-5-103

I103MEASUSR

Measurands user defined signals for IEC


60870-5-103

I103AR

Function status auto-recloser for IEC 60870-5-103

I103EF

Function status earth-fault for IEC 60870-5-103

I103FLTPROT

Function status fault protection for IEC


60870-5-103

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

61

Section 2
Available functions

IEC 61850

ANSI

1MRK 502 066-UUS A

Function description

Generator
REG670

I103IED

IED status for IEC 60870-5-103

I103SUPERV

Supervison status for IEC 60870-5-103

I103USRDEF

Status for user defined signals for IEC


60870-5-103

20

L4UFCNT

Event counter with limit supervision

30

TEILGAPC

Running hour-meter

PCFCNT

Pulse-counter logic

16

ETPMMTR

Function for energy calculation and demand


handling

Metering

Table 3:

Total number of instances for basic configurable logic blocks

Basic configurable logic block

Total number of instances

AND

280

GATE

40

INV

420

LLD

40

OR

280

PULSETIMER

40

RSMEMORY

40

SRMEMORY

40

TIMERSET

60

XOR

40

Table 4:

Total number of instances for configurable logic blocks Q/T

Configurable logic blocks Q/T

Total number of instances

ANDQT

120

INDCOMBSPQT

20

INDEXTSPQT

20

INVALIDQT

22

INVERTERQT

120

ORQT

120

PULSETIMERQT

40

RSMEMORYQT

40

Table continues on next page

62

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 2
Available functions

1MRK 502 066-UUS A

Configurable logic blocks Q/T

Total number of instances

SRMEMORYQT

40

TIMERSETQT

40

XORQT

40

Table 5:

Total number of instances for extended logic package

Extended configurable logic block

Total number of instances

AND

180

GATE

49

INV

180

LLD

49

OR

180

PULSETIMER

59

SLGAPC

74

SRMEMORY

110

TIMERSET

49

VSGAPC

130

XOR

49

2.4
IEC 61850

Communication
ANSI

Function description

Generator
REG670
(Customized)

Station communication
LONSPA, SPA

SPA communication protocol

ADE

LON communication protocol

HORZCOMM

Network variables via LON

PROTOCOL

Operation selection between SPA and IEC 60870-5-103 for


SLM

RS485PROT

Operation selection for RS485

RS485GEN

RS485

DNPGEN

DNP3.0 communication general protocol

DNPGENTCP

DNP3.0 communication general TCP protocol

CHSERRS485

DNP3.0 for EIA-485 communication protocol

CH1TCP, CH2TCP,
CH3TCP, CH4TCP

DNP3.0 for TCP/IP communication protocol

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

63

Section 2
Available functions

IEC 61850

ANSI

1MRK 502 066-UUS A

Function description

Generator
REG670
(Customized)

CHSEROPT

DNP3.0 for TCP/IP and EIA-485 communication protocol

MST1TCP,
MST2TCP,
MST3TCP,
MST4TCP

DNP3.0 for serial communication protocol

DNPFREC

DNP3.0 fault records for TCP/IP and EIA-485 communication


protocol

IEC 61850-8-1

Parameter setting function for IEC 61850

GOOSEINTLKRCV

Horizontal communication via GOOSE for interlocking

59

GOOSEBINRCV

GOOSE binary receive

16

GOOSEDPRCV

GOOSE function block to receive a double point value

64

GOOSEINTRCV

GOOSE function block to receive an integer value

32

GOOSEMVRCV

GOOSE function block to receive a measurand value

60

GOOSESPRCV

GOOSE function block to receive a single point value

64

MULTICMDRCV,
MULTICMDSND

Multiple command and transmit

FRONT, LANABI,
LANAB, LANCDI,
LANCD

Ethernet configuration of links

GATEWAY

Ethernet configuration of link one

OPTICAL103

IEC 60870-5-103 Optical serial communication

RS485103

IEC 60870-5-103 serial communication for RS485

AGSAL

Generic security application component

LD0LLN0

IEC 61850 LD0 LLN0

SYSLLN0

IEC 61850 SYS LLN0

LPHD

Physical device information

PCMACCS

IED Configuration Protocol

SECALARM

Component for mapping security events on protocols such as


DNP3 and IEC103

FSTACCS
FSTACCSNA

Field service tool access via SPA protocol over ethernet


communication

ACTIVLOG

Activity logging parameters

ALTRK

Service Tracking

SINGLELCCH

Single ethernet port link status

PRPSTATUS

Dual ethernet port link status

60/10

Process bus communication IEC 61850-9-2 1)


PRP

IEC 62439-3 parallel redundancy protocol

0-1

Remote communication
Table continues on next page

64

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 2
Available functions

1MRK 502 066-UUS A

IEC 61850

ANSI

Function description

Binary signal transfer receive/transmit

Generator
REG670
(Customized)
6/36

Transmission of analog data from LDCM

Receive binary status from remote LDCM

6/3/3

1) Only included for 9-2LE products

2.5
Table 6:

Basic IED functions


Basic IED functions

IEC 61850 or function


name

Description

INTERRSIG
SELFSUPEVLST

Self supervision with internal event list

TIMESYNCHGEN

Time synchronization module

BININPUT,
SYNCHCAN,
SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
SYNCHSPA

Time synchronization

TIMEZONE

Time synchronization

DSTBEGIN,
DSTENABLE, DSTEND

GPS time synchronization module

IRIG-B

Time synchronization

SETGRPS

Number of setting groups

ACTVGRP

Parameter setting groups

TESTMODE

Test mode functionality

CHNGLCK

Change lock function

SMBI

Signal matrix for binary inputs

SMBO

Signal matrix for binary outputs

SMMI

Signal matrix for mA inputs

SMAI1 - SMAI12

Signal matrix for analog inputs

ATHSTAT

Authority status

ATHCHCK

Authority check

AUTHMAN

Authority management

FTPACCS

FTP access with password

SPACOMMMAP

SPA communication mapping

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

65

Section 2
Available functions

IEC 61850 or function


name

1MRK 502 066-UUS A

Description

SPATD

Date and time via SPA protocol

DOSFRNT

Denial of service, frame rate control for front port

DOSLANAB

Denial of service, frame rate control for OEM port AB

DOSLANCD

Denial of service, frame rate control for OEM port CD

DOSSCKT

Denial of service, socket flow control

GBASVAL

Global base values for settings

PRIMVAL

Primary system values

ALTMS

Time master supervision

ALTIM

Time management

MSTSER

DNP3.0 for serial communication protocol

PRODINF

Product information

RUNTIME

IED Runtime Comp

CAMCONFIG

Central account management configuration

CAMSTATUS

Central account management status

TOOLINF

Tools Information component

SAFEFILECOPY

Safe file copy function

Table 7:

Local HMI functions

IEC 61850 or function


name

ANSI

Description

LHMICTRL

Local HMI signals

LANGUAGE

Local human machine language

SCREEN

Local HMI Local human machine screen behavior

FNKEYTY1FNKEYTY5
FNKEYMD1
FNKEYMD5

Parameter setting function for HMI in PCM600

LEDGEN

General LED indication part for LHMI

OPENCLOSE_LED

LHMI LEDs for open and close keys

GRP1_LED1
GRP1_LED15
GRP2_LED1
GRP2_LED15
GRP3_LED1
GRP3_LED15

Basic part for CP HW LED indication module

66

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 3
Analog inputs

1MRK 502 066-UUS A

Section 3

Analog inputs

3.1

Introduction
Analog input channels must be configured and set properly in order to get correct
measurement results and correct protection operations. For power measuring and all
directional and differential functions the directions of the input currents must be defined
in order to reflect the way the current transformers are installed/connected in the field
( primary and secondary connections ). Measuring and protection algorithms in the IED
use primary system quantities. Setting values are in primary quantities as well and it is
important to set the data about the connected current and voltage transformers properly.
A reference PhaseAngleRef can be defined to facilitate service values reading. This analog
channels phase angle will always be fixed to zero degrees and all other angle information
will be shown in relation to this analog input. During testing and commissioning of the
IED the reference channel can be changed to facilitate testing and service values reading.
The availability of VT inputs depends on the ordered transformer input
module (TRM) type.

3.2

Function block
The hardware channels appear in the signal matrix tool (SMT) and in ACT
when a TRM is included in the configuration with the hardware
configuration tool. In the SMT or the ACT they can be mapped to the
desired virtual input (SMAI) of the IED and used internally in the
configuration.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

67

Section 3
Analog inputs

3.3

1MRK 502 066-UUS A

Signals
Table 8:
Name

Type

Description

STATUS

BOOLEAN

Analog input module status

CH1(I)

STRING

Analogue current input 1

CH2(I)

STRING

Analog current input 2

CH3(I)

STRING

Analog current input 3

CH4(I)

STRING

Analog current input 4

CH5(I)

STRING

Analog current input 5

CH6(I)

STRING

Analog current input 6

CH7(I)

STRING

Analog current input 7

CH8(I)

STRING

Analog current input 8

CH9(I)

STRING

Analog current input 9

CH10(I)

STRING

Analog current input 10

CH11(I)

STRING

Analog current input 11

CH12(I)

STRING

Analog current input 12

Table 9:
Name

68

TRM_12I Output signals

TRM_6I_6U Output signals


Type

Description

STATUS

BOOLEAN

Analog input module status

CH1(I)

STRING

Analogue current input 1

CH2(I)

STRING

Analog current input 2

CH3(I)

STRING

Analog current input 3

CH4(I)

STRING

Analog current input 4

CH5(I)

STRING

Analog current input 5

CH6(I)

STRING

Analog current input 6

CH7(V)

STRING

Analog voltage input 7

CH8(V)

STRING

Analog voltage input 8

CH9(V)

STRING

Analog voltage input 9

CH10(V)

STRING

Analog voltage input 10

CH 11(V)

STRING

Analog voltage input 11

CH12(V)

STRING

Analog voltage input 12

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 3
Analog inputs

1MRK 502 066-UUS A

Table 10:
Name

TRM_6I Output signals


Type

Description

STATUS

BOOLEAN

Analog input module status

CH1(I)

STRING

Analogue current input 1

CH2(I)

STRING

Analog current input 2

CH3(I)

STRING

Analog current input 3

CH4(I)

STRING

Analog current input 4

CH5(I)

STRING

Analog current input 5

CH6(I)

STRING

Analog current input 6

Table 11:
Name

TRM_7I_5U Output signals


Type

Description

STATUS

BOOLEAN

Analog input module status

CH1(I)

STRING

Analogue current input 1

CH2(I)

STRING

Analog current input 2

CH3(I)

STRING

Analog current input 3

CH4(I)

STRING

Analog current input 4

CH5(I)

STRING

Analog current input 5

CH6(I)

STRING

Analog current input 6

CH7(I)

STRING

Analog current input 7

CH8(V)

STRING

Analog voltage input 8

CH9(V)

STRING

Analog voltage input 9

CH10(V)

STRING

Analog voltage input 10

CH 11(V)

STRING

Analog voltage input 11

CH12(V)

STRING

Analog voltage input 12

Table 12:
Name

TRM_9I_3U Output signals


Type

Description

STATUS

BOOLEAN

Analog input module status

CH1(I)

STRING

Analogue current input 1

CH2(I)

STRING

Analog current input 2

CH3(I)

STRING

Analog current input 3

CH4(I)

STRING

Analog current input 4

CH5(I)

STRING

Analog current input 5

CH6(I)

STRING

Analog current input 6

CH7(I)

STRING

Analog current input 7

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

69

Section 3
Analog inputs

1MRK 502 066-UUS A

Name

Type
STRING

Analog current input 8

CH9(I)

STRING

Analog current input 9

CH10(V)

STRING

Analog voltage input 10

CH 11(V)

STRING

Analog voltage input 11

CH12(V)

STRING

Analog voltage input 12

Table 13:

TRM_10I_2U Output signals

Name

3.4

Description

CH8(I)

Type

Description

STATUS

BOOLEAN

Analog input module status

CH1(I)

STRING

Analogue current input 1

CH2(I)

STRING

Analog current input 2

CH3(I)

STRING

Analog current input 3

CH4(I)

STRING

Analog current input 4

CH5(I)

STRING

Analog current input 5

CH6(I)

STRING

Analog current input 6

CH7(I)

STRING

Analog current input 7

CH8(I)

STRING

Analog current input 8

CH9(I)

STRING

Analog current input 9

CH10(I)

STRING

Analog current input 10

CH 11(V)

STRING

Analog voltage input 11

CH12(V)

STRING

Analog voltage input 12

Settings
Dependent on ordered IED type.

70

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 3
Analog inputs

1MRK 502 066-UUS A

Table 14:
Name
PhaseAngleRef

Table 15:
Name

AISVBAS Non group settings (basic)


Values (Range)
TRM40-Ch1 - Ch12
TRM41-Ch1 - Ch12
MU1-IA
MU1-IB
MU1-IC
MU1-I0
MU1- VA
MU1- VB
MU1-VC
MU1-V0
MU2-IA
MU2-IB
MU2-IC
MU2-I0
MU2-VA
MU2-VB
MU2-VC
MU2-V0
MU3-IA
MU3-IB
MU3-IC
MU3-I0
MU3-VB
MU2-VB
MU3-VC
MU3-V0
MU4-L1I - L4I
MU4-L1U - L4U
MU5-L1I - L4I
MU5-L1U - L4U
MU6-L1I - L4I
MU6-L1U - L4U

Unit

Step

Default
TRM40-Ch1

Description
Reference channel
for phase angle
presentation

TRM_12I Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

CT_WyePoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CT_WyePoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

CT_WyePoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

71

Section 3
Analog inputs

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

CT_WyePoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CT_WyePoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CT_WyePoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

CT_WyePoint7

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec7

1 - 10

Rated CT secondary current

CTprim7

1 - 99999

3000

Rated CT primary current

CT_WyePoint8

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec8

1 - 10

Rated CT secondary current

CTprim8

1 - 99999

3000

Rated CT primary current

CT_WyePoint9

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec9

1 - 10

Rated CT secondary current

CTprim9

1 - 99999

3000

Rated CT primary current

CT_WyePoint10

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec10

1 - 10

Rated CT secondary current

CTprim10

1 - 99999

3000

Rated CT primary current

CT_WyePoint11

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec11

1 - 10

Rated CT secondary current

CTprim11

1 - 99999

3000

Rated CT primary current

CT_WyePoint12

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec12

1 - 10

Rated CT secondary current

CTprim12

1 - 99999

3000

Rated CT primary current

72

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 3
Analog inputs

1MRK 502 066-UUS A

Table 16:
Name

TRM_6I_6U Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

CT_WyePoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CT_WyePoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

CT_WyePoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CT_WyePoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CT_WyePoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CT_WyePoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

VTsec7

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim7

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec8

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim8

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec9

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim9

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec10

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim10

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec11

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim11

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec12

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim12

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

73

Section 3
Analog inputs

1MRK 502 066-UUS A

Table 17:

TRM_6I Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

CT_WyePoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CT_WyePoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

CT_WyePoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CT_WyePoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CT_WyePoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CT_WyePoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

Table 18:
Name

TRM_7I_5U Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

CT_WyePoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CT_WyePoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

CT_WyePoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

Table continues on next page


74

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 3
Analog inputs

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

CTprim3

1 - 99999

3000

Rated CT primary current

CT_WyePoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CT_WyePoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CT_WyePoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

CT_WyePoint7

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec7

1 - 10

Rated CT secondary current

CTprim7

1 - 99999

3000

Rated CT primary current

VTsec8

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim8

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec9

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim9

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec10

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim10

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec11

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim11

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec12

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim12

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

Step

Default

Table 19:
Name

TRM_9I_3U Non group settings (basic)


Values (Range)

Unit

Description

CT_WyePoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CT_WyePoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

75

Section 3
Analog inputs

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

CT_WyePoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CT_WyePoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CT_WyePoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CT_WyePoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

CT_WyePoint7

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec7

1 - 10

Rated CT secondary current

CTprim7

1 - 99999

3000

Rated CT primary current

CT_WyePoint8

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec8

1 - 10

Rated CT secondary current

CTprim8

1 - 99999

3000

Rated CT primary current

CT_WyePoint9

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec9

1 - 10

Rated CT secondary current

CTprim9

1 - 99999

3000

Rated CT primary current

VTsec10

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim10

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec11

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim11

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec12

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim12

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

76

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 3
Analog inputs

1MRK 502 066-UUS A

Table 20:
Name

TRM_10I_2U Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

CT_WyePoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CT_WyePoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

CT_WyePoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CT_WyePoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CT_WyePoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CT_WyePoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

CT_WyePoint7

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec7

1 - 10

Rated CT secondary current

CTprim7

1 - 99999

3000

Rated CT primary current

CT_WyePoint8

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec8

1 - 10

Rated CT secondary current

CTprim8

1 - 99999

3000

Rated CT primary current

CT_WyePoint9

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec9

1 - 10

Rated CT secondary current

CTprim9

1 - 99999

3000

Rated CT primary current

CT_WyePoint10

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec10

1 - 10

Rated CT secondary current

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

77

Section 3
Analog inputs

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

CTprim10

1 - 99999

3000

Rated CT primary current

VTsec11

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim11

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec12

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim12

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

3.5

Monitored data
Table 21:
Name
Status

Table 22:
Name
STATUS

Table 23:
Name
STATUS

Table 24:
Name
STATUS

Table 25:
Name
STATUS

78

AISVBAS Monitored data


Type
INTEGER

Values (Range)
0=Ok
1=Error
2=AngRefLow
3=Uncorrelated

Unit
-

Description
Service value status

TRM_12I Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=Error

Unit
-

Description
Analog input module status

TRM_6I_6U Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=Error

Unit
-

Description
Analog input module status

TRM_6I Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=Error

Unit
-

Description
Analog input module status

TRM_7I_5U Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=Error

Unit
-

Description
Analog input module status

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 3
Analog inputs

1MRK 502 066-UUS A

Table 26:
Name
STATUS

Table 27:
Name
STATUS

3.6

TRM_9I_3U Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=Error

Unit
-

Description
Analog input module status

TRM_10I_2U Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=Error

Unit
-

Description
Analog input module status

Operation principle
The direction of a current depends on the connection of the CT. The main CTs are typically
star (WYE) connected and can be connected with the Star (WYE) point towards the object
or away from the object. This information must be set in the IED.
The convention of the directionality is defined as follows:

Positive value of current or power means that the quantity has the direction into the
object.
Negative value of current or power means that the quantity has the direction out from
the object.

For directional functions the directional conventions are defined as follows (see figure 2)

Forward means the direction is into the object.


Reverse means the direction is out from the object.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

79

Section 3
Analog inputs

1MRK 502 066-UUS A

Definition of direction
for directional functions

Definition of direction
for directional functions

Reverse

Forward

Forward

Reverse

Protected Object
Line, transformer, etc
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object

e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"

Set parameter
CTStarPoint
Correct Setting is
"FromObject"

en05000456-2.vsd
ANSI05000456 V2 EN

Figure 2:

Internal convention of the directionality in the IED

If the settings of the primary CT is correct, that is CTStarPoint set as FromObject or


ToObject according to the plant condition, then a positive quantity always flows towards
the protected object, and a Forward direction always looks towards the protected object.
The settings of the IED is performed in primary values. The ratios of the main CTs and
VTs are therefore basic data for the IED. The user has to set the rated secondary and
primary currents and voltages of the CTs and VTs to provide the IED with their rated
ratios.
The CT and VT ratio and the name on respective channel is done under Main menu/
Hardware/Analog modules in the Parameter Settings tool or on the HMI.

3.7

Technical data
Table 28:

TRM - Energizing quantities, rated values and limits for protection transformer modules

Quantity

Rated value

Current

In = 1 or 5 A

Operative range

(0-100) x In

Permissive overload

4 In cont.
100 In for 1 s *)

Burden

< 150 mVA at In = 5 A


< 20 mVA at In = 1 A

Ac voltage

Vn = 120 V

Operative range

(0340) V

Nominal range
(0.2-40) In

0.5288 V

Table continues on next page

80

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 3
Analog inputs

1MRK 502 066-UUS A

Quantity

Rated value

Permissive overload

420 V cont.
450 V 10 s

Burden

< 20 mVA at 110 V

Frequency

fn = 60/50 Hz

*)

Nominal range

5%

max. 350 A for 1 s when COMBITEST test switch is included.

Table 29:

TRM - Energizing quantities, rated values and limits for measuring transformer modules

Quantity

Rated value

Current

In = 1 or 5 A

Permissive overload

1.1 In cont.
1.8 In for 30 min at In = 1 A
1.6 In for 30 min at In = 5 A

Burden

< 350 mVA at In = 5 A


< 200 mVA at In = 1 A

Ac voltage

Vn = 120 V

Operative range

(0340) V

Permissive overload

420 V cont.
450 V 10 s

Burden

< 20 mVA at 110 V

Frequency

fn = 60/50 Hz

Table 30:

Nominal range
(0-1.8) In at In = 1 A
(0-1.6) In at In = 5 A

0.5288 V

5%

CT and VT circuit connectors

Connector type

Rated voltage and current

Maximum conductor area

Screw compression type

250 V AC, 20 A

4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)

Terminal blocks suitable for ring


lug terminals

250 V AC, 20 A

4 mm2 (AWG12)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

81

82

Section 4
Binary input and output modules

1MRK 502 066-UUS A

Section 4

Binary input and output modules

4.1

Binary input

4.1.1

Binary input debounce filter


The debounce filter eliminates bounces and short disturbances on a binary input.
A time counter is used for filtering. The time counter is increased once in a millisecond
when a binary input is high, or decreased when a binary input is low. A new debounced
binary input signal is forwarded when the time counter reaches the set DebounceTime
value and the debounced input value is high or when the time counter reaches 0 and the
debounced input value is low. The default setting of DebounceTime is 1 ms.
The binary input ON-event gets the time stamp of the first rising edge, after which the
counter does not reach 0 again. The same happens when the signal goes down to 0 again.

4.1.2

Oscillation filter
Binary input wiring can be very long in substations and there are electromagnetic fields
from for example nearby breakers. An oscillation filter is used to reduce the disturbance
from the system when a binary input starts oscillating.
An oscillation counter counts the debounced signal state changes during 1 s. If the counter
value is greater than the set value OscBlock, the input signal is blocked. The input signal
is ignored until the oscillation counter value during 1 s is below the set value OscRelease.

4.1.3

Settings
OscBlock must always be set to a value greater than OscRelease. If this is
not done, oscillation detection will not function correctly, and the
resulting behaviour will be undefined.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

83

Section 4
Binary input and output modules
4.1.3.1
Table 31:
Name

1MRK 502 066-UUS A

Setting parameters for binary input modules


BIM Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Enabled

Operation Disabled/Enabled

DebounceTime

0.001 - 0.020

0.001

0.001

Debounce time for binary inputs

OscBlock

1 - 40

Hz

40

Oscillation block limit

OscRelease

1 - 30

Hz

30

Oscillation release limit

4.1.3.2

Setting parameters for binary input/output module

Table 32:

IOMIN Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Enabled

Binary input/output module in operation (On) or


not (Off)

DebounceTime

0.001 - 0.020

0.001

0.001

Debounce time for binary inputs

OscBlock

1 - 40

Hz

40

Oscillation block limit

OscRelease

1 - 30

Hz

30

Oscillation release limit

84

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Section 5

Local Human-Machine-Interface LHMI

5.1

Local HMI screen behaviour

5.1.1

Identification
Function description

IEC 61850
identification

Local HMI screen behaviour

5.1.2
Table 33:

SCREEN

IEC 60617
identification

ANSI/IEEE C37.2
device number

Settings
SCREEN Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

DisplayTimeout

1 - 120

Min

10

Local HMI display timeout

ContrastLevel

-100 - 100

10

Contrast level for display

Default screen

DefaultScreen

EvListSrtOrder

Latest on top
Oldest on top

Latest on top

Sort order of event list

AutoIndicationDRP

Disabled
Enabled

Disabled

Automatic indication of disturbance report

SubstIndSLD

No
Yes

No

Substitute indication on single line diagram

InterlockIndSLD

No
Yes

No

Interlock indication on single line diagram

BypassCommands

No
Yes

No

Enable bypass of commands

5.2

Local HMI signals

5.2.1

Identification
Function description

IEC 61850
identification

Local HMI signals

LHMICTRL

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

85

Section 5
Local Human-Machine-Interface LHMI
5.2.2

1MRK 502 066-UUS A

Function block
LHMICTRL
CLRLEDS

HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD
IEC09000320-1-en.vsd

IEC09000320 V1 EN

Figure 3:

5.2.3

Signals
Table 34:
Name
RSTLEDS

Table 35:
Name

86

LHMICTRL function block

LHMICTRL Input signals


Type
BOOLEAN

Default
0

Description
Input to reset the LCD-HMI LEDs

LHMICTRL Output signals


Type

Description

HMI-ON

BOOLEAN

Backlight of the LCD display is active

RED-S

BOOLEAN

Red LED on the LCD-HMI is steady

YELLOW-S

BOOLEAN

Yellow LED on the LCD-HMI is steady

YELLOW-F

BOOLEAN

Yellow LED on the LCD-HMI is flashing

RSTPULSE

BOOLEAN

A reset pulse is provided when the LEDs on the LCDHMI are cleared

LEDSRST

BOOLEAN

Active when the LEDs on the LCD-HMI are not ON

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

5.3

Basic part for LED indication module

5.3.1

Identification
Function description

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Basic part for LED indication module

LEDGEN

Basic part for LED indication HW


module

GRP1_LED1 GRP1_LED15

GRP2_LED1 GRP2_LED15
GRP3_LED1 GRP3_LED15

5.3.2

Function block
LEDGEN
BLOCK
RESET

NEWIND
ACK
IEC09000321-1-en.vsd

IEC09000321 V1 EN

Figure 4:

LEDGEN function block

GRP1_LED1
^HM1L01R
^HM1L01Y
^HM1L01G
IEC09000322 V1 EN

Figure 5:

GRP1_LED1 function block

The GRP1_LED1 function block is an example. The 15 LEDs in each of the three groups
have a similar function block.

5.3.3

Signals
Table 36:
Name

LEDGEN Input signals


Type

Default

Description

BLOCK

BOOLEAN

Input to block the operation of the LEDs

RESET

BOOLEAN

Input to acknowledge/reset the indication LEDs

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

87

Section 5
Local Human-Machine-Interface LHMI

Table 37:

LEDGEN Output signals

Name

Type
BOOLEAN

New indication signal if any LED indication input is set

ACK

BOOLEAN

A pulse is provided when the LEDs are acknowledged

GRP1_LED1 Input signals

Name

Table 39:
Name

Description

NEWIND

Table 38:

5.3.4

1MRK 502 066-UUS A

Type

Default

Description

HM1L01R

BOOLEAN

Red indication of LED1, local HMI alarm group 1

HM1L01Y

BOOLEAN

Yellow indication of LED1, local HMI alarm group 1

HM1L01G

BOOLEAN

Green indication of LED1, local HMI alarm group 1

Settings
LEDGEN Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Enabled

Operation Disabled/Enabled

tRestart

0.0 - 100.0

0.1

0.0

Defines the disturbance length

t_MaxTripDelay

0.1 - 100.0

0.1

1.0

Maximum time for the definition of a


disturbance

Table 40:
Name

GRP1_LED1 Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

SequenceType

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 1, local HMI alarm


group 1

LabelOff

0 - 18

G1L01_OFF

Label string shown when LED 1, alarm group 1


is off

LabelRed

0 - 18

G1L01_RED

Label string shown when LED 1, alarm group 1


is red

LabelYellow

0 - 18

G1L01_YELLOW

Label string shown when LED 1, alarm group 1


is yellow

LabelGreen

0 - 18

G1L01_GREEN

Label string shown when LED 1, alarm group 1


is green

88

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

5.4

LCD part for HMI function keys control module

5.4.1

Identification
Function description

IEC 61850
identification

LCD part for HMI Function Keys Control


module

5.4.2

IEC 60617
identification

FNKEYMD1 FNKEYMD5

ANSI/IEEE C37.2
device number
-

Function block
FNKEYMD1
^LEDCTL1
^FKEYOUT1
IEC09000327 V1 EN

Figure 6:

FNKEYMD1 function block

Only the function block for the first button is shown above. There is a similar block for
every function key button.

5.4.3

Signals
Table 41:

FNKEYMD1 Input signals

Name

Type

LEDCTL1

BOOLEAN

Table 42:

Type

FKEYOUT1

Table 43:
Name

Description
LED control input for function key

FNKEYMD1 Output signals

Name

5.4.4

Default

Description

BOOLEAN

Output controlled by function key

Settings
FNKEYMD1 Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Mode

Disabled
Toggle
Pulsed

Disabled

Output operation mode

PulseTime

0.001 - 60.000

0.001

0.200

Pulse time for output controlled by LCDFn1

LabelOn

0 - 18

LCD_FN1_ON

Label for LED on state

LabelOff

0 - 18

LCD_FN1_OFF

Label for LED off state

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

89

Section 5
Local Human-Machine-Interface LHMI

Table 44:

FNKEYTY1 Non group settings (basic)

Name

Values (Range)

Type

Disabled
Menu shortcut
Control

MenuShortcut

1MRK 502 066-UUS A

Unit
-

Step
-

Default

Description

Disabled

Function key type

Menu shortcut for function key

MenuShortcut values are product dependent and created dynamically depending on the
product main menu.

90

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

5.5

Operation principle

5.5.1

Local HMI

ANSI13000239-2-en.vsd

ANSI13000239 V2 EN

Figure 7:

Local human-machine interface

The LHMI of the IED contains the following elements:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

91

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Keypad
Display (LCD)
LED indicators
Communication port for PCM600

The LHMI is used for setting, monitoring and controlling.

5.5.1.1

Keypad
The LHMI keypad contains push-buttons which are used to navigate in different views or
menus. The push-buttons are also used to acknowledge alarms, reset indications, provide
help and switch between local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either as
menu shortcut or control buttons.

92

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

24

1
23

2
18

3
19

4
5
6

20
21

22

10

11

12

13

14

15

16

17

ANSI15000157-1-en.vsdx
ANSI15000157 V1 EN

Figure 8:

LHMI keypad with object control, navigation and command push-buttons


and RJ-45 communication port

1...5 Function button


6

Close

Open

Escape

Left

10

Down

11

Up

12

Right

13

Key

14

Enter

15

Remote/Local

16

Uplink LED

17

Not in use

18

Multipage

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

93

Section 5
Local Human-Machine-Interface LHMI

5.5.1.2

19

Menu

20

Clear

21

Help

22

Communication port

23

Programmable indication LEDs

24

IED status LEDs

1MRK 502 066-UUS A

Display
The LHMI includes a graphical monochrome liquid crystal display (LCD) with a
resolution of 320 x 240 pixels. The character size can vary.
The display view is divided into four basic areas.

94

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

IEC15000270-1-en.vsdx

IEC15000270 V1 EN

Figure 9:

Display layout

1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)

The path shows the current location in the menu structure. If the path is too long to be
shown, it is truncated from the beginning, and the truncation is indicated with three
dots.
The content area shows the menu content.
The status area shows the current IED time, the user that is currently logged in and the
object identification string which is settable via the LHMI or with PCM600.
If text, pictures or other items do not fit in the display, a vertical scroll bar appears on
the right. The text in content area is truncated from the beginning if it does not fit in
the display horizontally. Truncation is indicated with three dots.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

95

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

IEC15000138-1-en.vsdx

IEC15000138 V1 EN

Figure 10:

Truncated path

The number after : (colon sign) at the end of the function instance, for example, 1 in
SMAI1:1, indicates the number of that function instance.
The function key button panel shows on request what actions are possible with the
function buttons. Each function button has a LED indication that can be used as a feedback
signal for the function button control action. The LED is connected to the required signal
with PCM600.

96

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

IEC13000281-1-en.vsd
GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN

Figure 11:

Function button panel

The indication LED panel shows on request the alarm text labels for the indication LEDs.
Three indication LED pages are available.

IEC13000240-1-en.vsd
GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN

Figure 12:

Indication LED panel

The function button and indication LED panels are not visible at the same time. Each panel
is shown by pressing one of the function buttons or the Multipage button. Pressing the
ESC button clears the panel from the display. Both panels have a dynamic width that
depends on the label string length.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

97

Section 5
Local Human-Machine-Interface LHMI
5.5.1.3

1MRK 502 066-UUS A

LEDs
The LHMI includes three protection status LEDs above the display: Normal, Pickup and
Trip.
There are 15 programmable indication LEDs on the front of the LHMI. Each LED can
indicate three states with the colors: green, yellow and red. The texts related to each threecolor LED are divided into three panels.
There are 3 separate panels of LEDs available. The 15 physical three-color LEDs in one
LED group can indicate 45 different signals. Altogether, 135 signals can be indicated
since there are three LED groups. The LEDs are lit according to priority, with red being
the highest and green the lowest priority. For example, if on one panel there is an
indication that requires the green LED to be lit, and on another panel there is an indication
that requires the red LED to be lit, the red LED takes priority and is lit. The LEDs can be
configured with PCM600 and the operation mode can be selected with the LHMI or
PCM600.
Information panels for the indication LEDs are shown by pressing the Multipage button.
Pressing that button cycles through the three pages. A lit or un-acknowledged LED is
indicated with a highlight. Such lines can be selected by using the Up/Down arrow
buttons. Pressing the Enter key shows details about the selected LED. Pressing the ESC
button exits from information pop-ups as well as from the LED panel as such.
The Multipage button has a LED. This LED is lit whenever any LED on any panel is lit.
If there are un-acknowledged indication LEDs, then the Multipage LED blinks. To
acknowledge LEDs, press the Clear button to enter the Reset menu (refer to description of
this menu for details).
There are two additional LEDs which are next to the control buttons
and
. They
can, for example, represent the status of a circuit breaker. The LEDs are controlled by the
function block OPENCLOSE_LED which must be configured to show the status of the
breaker.

5.5.2

LED configuration alternatives

5.5.2.1

Functionality
The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx
(x=1-15) controls and supplies information about the status of the indication LEDs. The
input and output signals of the function blocks are configured with PCM600. The input
signal for each LED is selected individually using SMT or ACT. Each LED is controlled
by the GRPn_LEDx (n=1-3) function block that controls the color and the operating
mode.

98

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Each indication LED on local HMI can be set individually to operate in 6 different
sequences; two as follow type and four as latch type. Two of the latching sequence types
are intended to be used as a protection indication system, either in collecting or restarting
mode, with reset functionality. The other two are intended to be used as signalling system
in collecting mode with acknowledgment functionality.

5.5.2.2

Status LEDs
There are three status LEDs above the LCD in front of the IED: green, yellow and red.
The green LED has a fixed function that presents the healthy status of the IED. The yellow
and red LEDs are user configured. The yellow LED can be used to indicate that a
disturbance report is triggered (steady) or that the IED is in test mode (flashing). The red
LED can be used to indicate a trip command.
Here is a typical configuration of the status LEDs:

Green LED: unlit > no power; blinking > startup or abnormal situation (IED is not in
service); steady > IED is in service
Yellow LED: unlit > no attention required; blinking > IED is in Testmode (IED is not
in normal service); steady > at least one of the signals configured to turn the yellow
LED on has been active
Red LED: unlit > no attention required; blinking > user performs a common write
from PCM600; steady > at least one of the signals configured to turn the red LED on
has been active

The yellow and red status LEDs are configured in the disturbance recorder function,
DRPRDRE, by connecting a pickup or trip signal from the actual function to a BxRBDR
binary input function block using the PCM600, and configuring the setting to Off,Pickup
or Trip for that particular signal.

5.5.2.3

Indication LEDs
Operating modes
Collecting mode

LEDs that are used in the collecting mode of operation are accumulated continuously
until the unit is acknowledged manually. This mode is suitable when the LEDs are
used as a simplified alarm system. When all three inputs (red, yellow and green) are
connected to different sources of events for the same function block, collecting mode
shows the highest priority LED color that was activated since the latest
acknowledgment was made. If a number of different indications were made since the
latest acknowledgment, it is not possible to get a clear view of what triggered the
latest event without looking at the sequence of events list. A condition for getting the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

99

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

sequence of events is that the signals have been engineered in the disturbance
recorder.
Re-starting mode

In the re-starting mode of operation each new pickup resets all previous active LEDs
and activates only those which appear during one disturbance. Only LEDs defined for
re-starting mode with the latched sequence type 6 (LatchedReset-S) will initiate a
reset and a restart at a new disturbance. A disturbance is defined to end a settable time
after the reset of the activated input signals or when the maximum time limit has
elapsed. In sequence 6, the restarting or reset mode means that upon occurrence of
any new event, all previous indications will be reset. This facilitates that only the LED
indications related to the latest event is shown.

Acknowledgment/reset

From local HMI

The active LED indications can be acknowledged/reset manually. Manual


acknowledgment and manual reset have the same meaning and is a common
signal for all the operating sequences and LEDs. The function is positive edge
triggered, not level triggered. The acknowledgment/reset is performed via the
button and menus on the LHMI.

From function input

The active LED indications can also be acknowledged/reset via an input,


CLRLEDS, to the function block LHMICTRL. This input can for example be
configured to a binary input operated from an external push button or a function
button. The function is positive edge triggered, not level triggered. This means
that even if the button is continuously pressed, the acknowledgment/reset only
affects indications active at the moment when the button is first pressed.

Automatic reset

The automatic reset can only be performed for LED indications defined for restarting mode with the latched sequence type 6 (LatchedReset-S). When the
automatic reset of the LEDs has been performed, still persisting indications will
be indicated with a steady light.

Operating sequence
The sequences can be of type Follow or Latched. For the Follow type, the LED follows the
input signal completely. For the Latched type, each LED latches to the corresponding
input signal until it is reset.
100

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

The figures below show the function of available sequences selectable for each LED
separately. The following 6 sequences are available:

Sequence 1: Follow-S
Sequence 2: Follow-F
Sequence 3: LatchedAck-F-S
Sequence 4: LatchedAck-S-F
Sequence 5: LatchedColl-S
Sequence 6: LatchedReset-S

For sequence 1 and 2, which are of the Follow type, the acknowledgment (Ack ) /reset
function is not applicable because the indication shown by the LED follows its input
signal. Sequence 3 and 4, which are of the Latched type with acknowledgement, are only
working in collecting (Coll) mode. Sequence 5 is working according to Latched type and
collecting mode while Sequence 6 is working according to Latched type and re-starting
(Reset) mode. The letters S and F in the sequence names have the meaning S = Steady and
F = Flash.
At the activation of the input signal to any LED, the indication on the corresponding LED
obtains a color that corresponds to the activated input, and operates according to the
selected sequence diagrams shown below.
In the sequence diagrams the different statuses of the LEDs are shown using the following
symbols:
= No indication
G=

Green

= Steady light
Y=

Yellow

= Flash
R=

Red

IEC09000311.vsd
IEC09000311 V1 EN

Figure 13:

Symbols used in the sequence diagrams

Sequence 1 (Follow-S)
This sequence follows the corresponding input signals all the time with a steady light. It
does not react on acknowledgment or reset. Every LED is independent of the other LEDs
in its operation.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

101

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Activating
signal

LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN

Figure 14:

Operating Sequence 1 (Follow-S)

If inputs for two or more colors are active at the same time to the same LED, the priority
color it shows is in accordance with the color described above. An example of the
operation when two colors are activated in parallel to the same LED is shown in Figure
15.
Activating
signal GREEN
Activating
signal RED

LED

IEC09000312_1_en.vsd
IEC09000312 V1 EN

Figure 15:

Operating sequence 1, two colors

Sequence 2 (Follow-F)
This sequence is the same as Sequence 1, Follow-S, but the LEDs are flashing instead of
showing steady light.
Sequence 3 LatchedAck-F-S
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal, the
indication starts flashing. After acknowledgment the indication disappears if the signal is
not present any more. If the signal is still present after acknowledgment it gets a steady
light.

102

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Activating
signal

LED

Acknow.
en01000231.vsd
IEC01000231 V1 EN

Figure 16:

Operating Sequence 3 LatchedAck-F-S

The sequence described below is valid only if the same function block is
used for all three colour LEDs.
When an acknowledgment is performed, all indications that appear before the indication
with higher priority has been reset, will be acknowledged, independent of if the low
priority indication appeared before or after acknowledgment. In Figure 17 it is shown the
sequence when a signal of lower priority becomes activated after acknowledgment has
been performed on a higher priority signal. The low priority signal will be shown as
acknowledged when the high priority signal resets.
Activating
signal GREEN
Activating
signal RED

LED

Acknow
IEC09000313_1_en.vsd
IEC09000313 V1 EN

Figure 17:

Operating Sequence 3 (LatchedAck-F-S), 2 colors involved

If all three signals are activated the order of priority is still maintained. Acknowledgment
of indications with higher priority will acknowledge also low priority indications, which
are not visible according to Figure 18.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

103

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Activating
signal GREEN
Activating
signal YELLOW
Activating
signal RED

LED

Acknow.
IEC09000314-1-en.vsd
IEC09000314 V1 EN

Figure 18:

Operating sequence 3, three colors involved, alternative 1

If an indication with higher priority appears after acknowledgment of a lower priority


indication the high priority indication will be shown as not acknowledged according to
Figure 19.
Activating
signal GREEN
Activating
signal YELLOW
Activating
signal RED

LED

Acknow.
IEC09000315-1-en.vsd
IEC09000315 V1 EN

Figure 19:

Operating sequence 3, three colors involved, alternative 2

Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing light have
been alternated.

Sequence 5 LatchedColl-S
This sequence has a latched function and works in collecting mode. At the activation of
the input signal, the indication will light up with a steady light. The difference to sequence
104

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

3 and 4 is that indications that are still activated will not be affected by the reset that is,
immediately after the positive edge of the reset has been executed a new reading and
storing of active signals is performed. Every LED is independent of the other LEDs in its
operation.
Activating
signal

LED

Reset
IEC01000235_2_en.vsd
IEC01000235 V2 EN

Figure 20:

Operating Sequence 5 LatchedColl-S

That means if an indication with higher priority has reset while an indication with lower
priority still is active at the time of reset, the LED will change color according to Figure
21.
Activating
signal GREEN
Activating
signal RED

LED

Reset
IEC09000316_1_en.vsd
IEC09000316 V1 EN

Figure 21:

Operating sequence 5, two colors

Sequence 6 LatchedReset-S
In this mode all activated LEDs, which are set to Sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other LEDs
set to Sequence 6 LatchedReset-S. Also in this case indications that are still activated will
not be affected by manual reset, that is, immediately after the positive edge of that the
manual reset has been executed a new reading and storing of active signals is performed.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

105

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

LEDs set for sequence 6 are completely independent in its operation of LEDs set for other
sequences.
Timing diagram for sequence 6
Figure 22 shows the timing diagram for two indications within one disturbance.
Disturbance
tRestart

Activating
signal 1
Activating
signal 2

LED 1

LED 2
Automatic
reset
Manual
reset

IEC01000239_2-en.vsd

IEC01000239 V2 EN

Figure 22:

Operating sequence 6 (LatchedReset-S), two indications within same


disturbance

Figure 23 shows the timing diagram for a new indication after tRestart time has elapsed.

106

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Disturbance
tRestart

Disturbance
tRestart

Activating
signal 1
Activating
signal 2

LED 1

LED 2
Automatic
reset
Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN

Figure 23:

Operating sequence 6 (LatchedReset-S), two different disturbances

Figure 24 shows the timing diagram when a new indication appears after the first one has
reset but before tRestart has elapsed.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

107

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Disturbance
tRestart
Activating
signal 1
Activating
signal 2

LED 1

LED 2
Automatic
reset
Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN

Figure 24:

Operating sequence 6 (LatchedReset-S), two indications within same


disturbance but with reset of activating signal between

Figure 25 shows the timing diagram for manual reset.

108

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Disturbance
tRestart
Activating
signal 1
Activating
signal 2

LED 1

LED 2
Automatic
reset
Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN

Figure 25:

Operating sequence 6 (LatchedReset-S), manual reset

5.5.3

Function keys

5.5.3.1

Functionality
Local Human-Machine-Interface (LHMI) has five function buttons, directly to the left of
the LCD, that can be configured either as menu shortcut or control buttons. Each button
has an indication LED that can be configured in the application configuration.
When used as a menu shortcut, a function button provides a fast way to navigate between
default nodes in the menu tree. When used as a control, the button can control a binary
signal.

5.5.3.2

Operation principle
Each output on the FNKEYMD1 - FNKEYMD5 function blocks can be controlled from
the LHMI function keys. By pressing a function button on the LHMI, the output status of
the actual function block will change. These binary outputs can in turn be used to control
other function blocks, for example, switch control blocks, binary I/O outputs etc.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

109

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

FNKEYMD1 - FNKEYMD5 function block also has a number of settings and parameters
that control the behavior of the function block. These settings and parameters are normally
set using the PST.

Operating sequence
The operation mode is set individually for each output, either OFF, TOGGLE or
PULSED.
Setting OFF
This mode always sets the outputs to a low value (0).

Input value

Output value
IEC09000330-2-en.vsd

IEC09000330 V2 EN

Figure 26:

Sequence diagram for setting OFF

Setting TOGGLE
In this mode the output toggles each time the function key has been pressed for more than
500ms. Note that the input attribute is reset each time the function block executes. The
function block execution is marked with a dotted line below.

Input value

500ms

500ms

500ms

Output value
IEC09000331_1_en.vsd

IEC09000331 V2 EN

Figure 27:

Sequence diagram for setting TOGGLE

Setting PULSED
In this mode the output sets high (1) when the function key has been pressed for more than
500ms and remains high according to set pulse time. After this time the output will go back
to 0. The input attribute is reset when the function block detects it being high and there is
no output pulse.

110

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 5
Local Human-Machine-Interface LHMI

1MRK 502 066-UUS A

Note that the third positive edge on the input attribute does not cause a pulse, since the
edge was applied during pulse output. A new pulse can only begin when the output is zero;
else the trigger edge is lost.

Input value

500ms

500ms

pulse time

Output value

500ms

500ms

pulse time

pulse time
IEC09000332_2_en.vsd

IEC09000332 V2 EN

Figure 28:

Sequence diagram for setting PULSED

Input function
All function keys work the same way: When the LHMI is configured so that a certain
function button is of type CONTROL, then the corresponding input on this function block
becomes active, and will light the yellow function button LED when high. This
functionality is active even if the function block operation setting is set to off. It has been
implemented this way for safety reasons; the idea is that the function key LEDs should
always reflect the actual status of any primary equipment monitored by these LEDs.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

111

112

Section 6
Differential protection

1MRK 502 066-UUS A

Section 6

Differential protection

6.1

Transformer differential protection T2WPDIF and


T3WPDIF (87T)

6.1.1

Identification
Function description
Transformer differential protection, twowinding

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
87T

T2WPDIF

3Id/I
SYMBOL-BB V1 EN

Transformer differential protection,


three-winding

87T

T3WPDIF

3Id/I
SYMBOL-BB V1 EN

6.1.2

Functionality
The Transformer differential protection is provided with internal CT ratio matching,
phase shift compensation and settable zero sequence current elimination.
The function can be provided with up to six three-phase sets of current inputs if enough
HW is available. All current inputs are provided with percentage bias restraint features,
making the IED suitable for two- or three-winding transformer in multi-breaker station
arrangements.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

113

Section 6
Differential protection

1MRK 502 066-UUS A

Two-winding applications

352

152

xx05000048_ansi.vsd
ANSI05000048 V1 EN

two-winding power transformer

352

152

xx05000049_ansi.vsd
ANSI05000049 V1 EN

two-winding power transformer with unconnected


delta tertiary winding

152

352

252

xx05000050_ansi.vsd
ANSI05000050 V1 EN

twowinding power transformer with two circuit


breakers on one side

152

352

252

452

xx05000051_ansi.vsd
ANSI05000051 V1 EN

Table continues on next page


114

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

twowinding power transformer with two circuit


breakers and two CT-sets on both sides
Three-winding applications

452

152

352

xx05000052_ansi.vsd
ANSI05000052 V1 EN

threewinding power transformer with all three


windings connected

452

152

352

252

xx05000053_ansi.vsd
ANSI05000053 V1 EN

threewinding power transformer with two circuit


breakers and two CT-sets on one side
Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

115

Section 6
Differential protection

1MRK 502 066-UUS A

152

252

552

352

452

xx05000057_ansi.vsd
ANSI05000057 V1 EN

Autotransformer with two circuit breakers and two


CT-sets on two out of three sides

Figure 29:

CT group arrangement
for differential
protection

The setting facilities cover the application of the differential protection to all types of
power transformers and auto-transformers with or without load tap changer as well as
shunt reactors and local feeders within the station. An adaptive stabilizing feature is
included for heavy through-fault currents.By introducing the load tap changer position,
the differential protection pick-up can be set to optimum sensitivity thus covering internal
faults with low fault current level.
Harmonic restraint is included for inrush and overexcitation currents respectively, crossblocking is also available. Adaptive stabilization is also included for system recovery
inrush and CT saturation during external faults. A high set unrestrained differential
current protection element is included for a very high speed tripping at high internal fault
currents.
Included is an sensitive differential protection element based on the theory of negative
sequence current component. This element offers the best possible coverage of power
transformer windings turn to turn faults.

116

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

6.1.3

Function block
T2WPDIF (87T)
I3PW1CT1*
TRIP
I3PW1CT2*
TRIPRES
I3PW2CT1*
TRIPUNRE
I3PW2CT2*
TRNSUNR
TAPOLTC1
TRNSSENS
OLTC1AL
PICKUP
BLOCK
PU_A
BLKRES
PU_B
BLKUNRES
PU_C
BLKNSUNR
BLK2H
BLKNSSEN
BLK2H_A
BLK2H_B
BLK2H_C
BLK5H
BLK5H_A
BLK5H_B
BLK5H_C
BLKWAV
BLKWAV_A
BLKWAV_B
BLKWAV_C
IDALARM
OPENCT
OPENCTAL
ID_A
ID_B
ID_C
IDMAG_A
IDMAG_B
IDMAG_C
IBIAS
IDMAG_NS
ANSI06000249-2-en.vsd
ANSI06000249 V2 EN

Figure 30:

T2WPDIF (87T) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

117

Section 6
Differential protection

1MRK 502 066-UUS A

T3WPDIF (87T)
I3PW1CT1*
TRIP
I3PW1CT2*
TRIPRES
I3PW2CT1*
TRIPUNRE
I3PW2CT2*
TRNSUNR
I3PW3CT1*
TRNSSENS
I3PW3CT2*
PICKUP
TAPOLTC1
PU_A
TAPOLTC2
PU_B
OLTC1AL
PU_C
OLTC2AL
BLK2H
BLOCK
BLK2H_A
BLKRES
BLK2H_B
BLKUNRES
BLK2H_C
BLKNSUNR
BLK5H
BLKNSSEN
BLK5H_A
BLK5H_B
BLK5H_C
BLKWAV
BLKWAV_A
BLKWAV_B
BLKWAV_C
IDALARM
OPENCT
OPENCTAL
ID_A
ID_B
ID_C
IDMAG_A
IDMAG_B
IDMAG_C
IBIAS
IDMAG_NS
ANSI06000250-2-en.vsd
ANSI06000250 V2 EN

Figure 31:

6.1.4

T3WPDIF (87T) function block

Signals
Table 45:
Name

T2WPDIF (87T) Input signals


Type

Default

Description

I3PW1CT1

GROUP
SIGNAL

Three phase winding primary CT1

I3PW1CT2

GROUP
SIGNAL

Three phase winding primary CT2

I3PW2CT1

GROUP
SIGNAL

Three phase winding secondary CT1

I3PW2CT2

GROUP
SIGNAL

Three phase winding secondary CT2

TAPOLTC1

INTEGER

Most recent tap position reading on OLTC 1

OLTC1AL

BOOLEAN

OLTC1 alarm

BLOCK

BOOLEAN

Block of function

BLKRES

BOOLEAN

Block of trip for restrained differential feature

Table continues on next page

118

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Name

Type

Default

Description

BLKUNRES

BOOLEAN

Block of trip for unrestrained differential feature

BLKNSUNR

BOOLEAN

Block of trip for unrestrained negative sequence


differential protection

BLKNSSEN

BOOLEAN

Block of trip for sensitive negative sequence differential


protection

Table 46:
Name

T2WPDIF (87T) Output signals


Type

Description

TRIP

BOOLEAN

General, common trip signal

TRIPRES

BOOLEAN

Trip signal from restrained differential protection

TRIPUNRE

BOOLEAN

Trip signal from unrestrained differential protection

TRNSUNR

BOOLEAN

Trip signal from unrestrained negative sequence


differential protection

TRNSSENS

BOOLEAN

Trip signal from sensitive negative sequence differential


protection

PICKUP

BOOLEAN

Common pickup signal from any phase

PU_A

BOOLEAN

Pickup signal from phase A

PU_B

BOOLEAN

Pickup signal from phase B

PU_C

BOOLEAN

Pickup signal from phase C

BLK2H

BOOLEAN

Common second harmonic block signal from any phase

BLK2H_A

BOOLEAN

Second harmonic block signal, phase A

BLK2H_B

BOOLEAN

Second harmonic block signal, phase B

BLK2H_C

BOOLEAN

Second harmonic block signal, phase C

BLK5H

BOOLEAN

Common fifth harmonic block signal from any phase

BLK5H_A

BOOLEAN

Fifth harmonic block signal, phase A

BLK5H_B

BOOLEAN

Fifth harmonic block signal, phase B

BLK5H_C

BOOLEAN

Fifth harmonic block signal, phase C

BLKWAV

BOOLEAN

Common block signal, waveform criterion, from any


phase

BLKWAV_A

BOOLEAN

Block signal, waveform criterion, phase A

BLKWAV_B

BOOLEAN

Block signal, waveform criterion, phase B

BLKWAV_C

BOOLEAN

Block signal, waveform criterion, phase C

IDALARM

BOOLEAN

Alarm for sustained diff currents in all three phases

OPENCT

BOOLEAN

An open CT was detected

OPENCTAL

BOOLEAN

Open CT Alarm output signal. Issued after a delay ...

ID_A

REAL

Value of the instantaneous differential current, phase A

ID_B

REAL

Value of the instantaneous differential current, phase B

ID_C

REAL

Value of the instantaneous differential current, phase C

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

119

Section 6
Differential protection

1MRK 502 066-UUS A

Name

Description

REAL

Magnitude of fundamental frequency differential


current, phase A

IDMAG_B

REAL

Magnitude of fundamental frequency differential


current, phase B

IDMAG_C

REAL

Magnitude of fundamental frequency differential


current, phase C

IBIAS

REAL

Magnitude of the bias current, which is common to all


phases

IDMAG_NS

REAL

Magnitude of the negative sequence differential current

Table 47:
Name

120

Type

IDMAG_A

T3WPDIF (87T) Input signals


Type

Default

Description

I3PW1CT1

GROUP
SIGNAL

Three phase winding primary CT1

I3PW1CT2

GROUP
SIGNAL

Three phase winding primary CT2

I3PW2CT1

GROUP
SIGNAL

Three phase winding secondary CT1

I3PW2CT2

GROUP
SIGNAL

Three phase winding secondary CT2

I3PW3CT1

GROUP
SIGNAL

Three phase winding tertiary CT1

I3PW3CT2

GROUP
SIGNAL

Three phase winding tertiary CT2

TAPOLTC1

INTEGER

Most recent tap position reading on OLTC 1

TAPOLTC2

INTEGER

Most recent tap position reading on OLTC 2

OLTC1AL

BOOLEAN

OLTC1 alarm

OLTC2AL

BOOLEAN

OLTC2 alarm

BLOCK

BOOLEAN

Block of function

BLKRES

BOOLEAN

Block of trip for restrained differential feature

BLKUNRES

BOOLEAN

Block of trip for unrestrained differential feature

BLKNSUNR

BOOLEAN

Block of trip for unrestrained negative sequence


differential protection

BLKNSSEN

BOOLEAN

Block of trip for sensitive negative sequence differential


protection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Table 48:
Name

T3WPDIF (87T) Output signals


Type

Description

TRIP

BOOLEAN

General, common trip signal

TRIPRES

BOOLEAN

Trip signal from restrained differential protection

TRIPUNRE

BOOLEAN

Trip signal from unrestrained differential protection

TRNSUNR

BOOLEAN

Trip signal from unrestrained negative sequence


differential protection

TRNSSENS

BOOLEAN

Trip signal from sensitive negative sequence differential


protection

PICKUP

BOOLEAN

Common pickup signal from any phase

PU_A

BOOLEAN

Pickup signal from phase A

PU_B

BOOLEAN

Pickup signal from phase B

PU_C

BOOLEAN

Pickup signal from phase C

BLK2H

BOOLEAN

Common second harmonic block signal from any phase

BLK2H_A

BOOLEAN

Second harmonic block signal, phase A

BLK2H_B

BOOLEAN

Second harmonic block signal, phase B

BLK2H_C

BOOLEAN

Second harmonic block signal, phase C

BLK5H

BOOLEAN

Common fifth harmonic block signal from any phase

BLK5H_A

BOOLEAN

Fifth harmonic block signal, phase A

BLK5H_B

BOOLEAN

Fifth harmonic block signal, phase B

BLK5H_C

BOOLEAN

Fifth harmonic block signal, phase C

BLKWAV

BOOLEAN

Common block signal, waveform criterion, from any


phase

BLKWAV_A

BOOLEAN

Block signal, waveform criterion, phase A

BLKWAV_B

BOOLEAN

Block signal, waveform criterion, phase B

BLKWAV_C

BOOLEAN

Block signal, waveform criterion, phase C

IDALARM

BOOLEAN

Alarm for sustained diff currents in all three phases

OPENCT

BOOLEAN

An open CT was detected

OPENCTAL

BOOLEAN

Open CT Alarm output signal. Issued after a delay ...

ID_A

REAL

Value of the instantaneous differential current, phase A

ID_B

REAL

Value of the instantaneous differential current, phase B

ID_C

REAL

Value of the instantaneous differential current, phase C

IDMAG_A

REAL

Magnitude of fundamental frequency differential


current, phase A

IDMAG_B

REAL

Magnitude of fundamental frequency differential


current, phase B

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

121

Section 6
Differential protection

1MRK 502 066-UUS A

Name

6.1.5
Table 49:
Name

Type

Description

IDMAG_C

REAL

Magnitude of fundamental frequency differential


current, phase C

IBIAS

REAL

Magnitude of the bias current, which is common to all


phases

IDMAG_NS

REAL

Magnitude of the negative sequence differential current

Settings
T2WPDIF (87T) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

SOTFMode

Disabled
Enabled

Enabled

Operation mode for switch onto fault

tAlarmDelay

0.000 - 60.000

0.001

10.000

Time delay for diff currents alarm level

IDiffAlarm

0.05 - 1.00

IB

0.01

0.20

Dif. cur. alarm, multiple of base curr, usually


W1 curr.

IdMin

0.05 - 0.60

IB

0.01

0.30

Section1 sensitivity, multi. of base curr, usually


W1 curr.

IdUnre

1.00 - 100.00

IB

0.01

10.00

Unrestrained protection limit, multiple of


Winding 1 rated current

CrossBlockEn

Disabled
Enabled

Enabled

Operation Off/On for cross-block logic between


phases

NegSeqDiffEn

Disabled
Enabled

Enabled

Operation Off/On for neg. seq. differential


protections

IMinNegSeq

0.02 - 0.20

IB

0.01

0.04

Negative sequence current must be higher


than this level to be used

NegSeqROA

30.0 - 120.0

Deg

0.1

60.0

Operate Angle for internal / external negative


sequence fault discriminator

Unit

Step

Default

Table 50:
Name

T2WPDIF (87T) Group settings (advanced)


Values (Range)

Description

EndSection1

0.20 - 1.50

IB

0.01

1.25

End of section 1, multiple of Winding 1 rated


current

EndSection2

1.00 - 10.00

IB

0.01

3.00

End of section 2, multiple of Winding 1 rated


current

SlopeSection2

10.0 - 50.0

0.1

40.0

Slope in section 2 of operate-restrain


characteristic, in %

SlopeSection3

30.0 - 100.0

0.1

80.0

Slope in section 3 of operate-restrain


characteristic, in %

I2/I1Ratio

5.0 - 100.0

0.1

15.0

Max. ratio of second harmonic to fundamental


harm dif. curr. in %

Table continues on next page


122

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Name

Unit

Step

Default

I5/I1Ratio

5.0 - 100.0

0.1

25.0

Max. ratio of fifth harmonic to fundamental


harm dif. curr. in %

OpenCTEnable

Disabled
Enabled

Disabled

Open CT detection feature. Open CTEnable


Off/On

tOCTAlarmDelay

0.100 - 10.000

0.001

3.000

Open CT: time in s to alarm after an open CT is


detected

tOCTResetDelay

0.100 - 10.000

0.001

0.250

Reset delay in s. After delay, diff. function is


activated

tOCTUnrstDelay

0.10 - 6000.00

0.01

10.00

Unrestrained diff. protection blocked after this


delay, in s

Step

Default

Table 51:

Values (Range)

Description

T2WPDIF (87T) Non group settings (basic)

Name

Values (Range)

Unit

Description

GlobalBaseSelW1

1 - 12

Global base selector for winding 1

GlobalBaseSelW2

1 - 12

Global base selector for winding 2

ConnectTypeW1

WYE (Y)
Delta (D)

WYE (Y)

Connection type of winding 1: Y-wye or D-delta

ConnectTypeW2

WYE (Y)
Delta (D)

WYE (Y)

Connection type of winding 2: Y-wye or D-delta

ClockNumberW2

0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]

0 [0 deg]

Phase displacement between W2 & W1=HV


winding, hour notation

ZSCurrSubtrW1

Disabled
Enabled

Enabled

Enable zer. seq. current subtraction for W1


side, On / Off

ZSCurrSubtrW2

Disabled
Enabled

Enabled

Enable zer. seq. current subtraction for W2


side, On / Off

TconfigForW1

No
Yes

No

Two CT inputs (T-config.) for winding 1, YES /


NO

CT1RatingW1

1 - 99999

3000

CT primary rating in A, T-branch 1, on transf.


W1 side

CT2RatingW1

1 - 99999

3000

CT primary in A, T-branch 2, on transf. W1 side

TconfigForW2

No
Yes

No

Two CT inputs (T-config.) for winding 2, YES /


NO

CT1RatingW2

1 - 99999

3000

CT primary rating in A, T-branch 1, on transf.


W2 side

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

123

Section 6
Differential protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

CT2RatingW2

1 - 99999

3000

CT primary rating in A, T-branch 2, on transf.


W2 side

LocationOLTC1

Not Used
Winding 1 (W1)
Winding 2 (W2)

Not Used

Transformer winding where OLTC1 is located

LowTapPosOLTC1

0 - 10

OLTC1 lowest tap position designation (e.g. 1)

RatedTapOLTC1

1 - 100

OLTC1 rated tap/mid-tap position designation


(e.g. 6)

HighTapPsOLTC1

1 - 100

11

OLTC1 highest tap position designation (e.g.


11)

TapHighVoltTC1

1 - 100

OLTC1 end-tap position with winding highest


no-load voltage

StepSizeOLTC1

0.01 - 30.00

0.01

1.00

Voltage change per OLTC1 step in percent of


rated voltage

Step

Default

Table 52:
Name

T3WPDIF (87T) Group settings (basic)


Values (Range)

Unit

tAlarmDelay

0.000 - 60.000

0.001

10.000

Time delay for diff currents alarm level

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

IDiffAlarm

0.05 - 1.00

IB

0.01

0.20

Dif. cur. alarm, multiple of base curr, usually


W1 curr.

SOTFMode

Disabled
Enabled

Enabled

Operation mode for switch onto fault feature

IdMin

0.05 - 0.60

IB

0.01

0.30

Section1 sensitivity, multi. of base curr, usually


W1 curr.

IdUnre

1.00 - 100.00

IB

0.01

10.00

Unrestr. prot. limit, multi. of base curr. usually


W1 curr.

CrossBlockEn

Disabled
Enabled

Enabled

Operation Off/On for cross-block logic between


phases

NegSeqDiffEn

Disabled
Enabled

Enabled

Operation Off/On for neg. seq. differential


protections

IMinNegSeq

0.02 - 0.20

IB

0.01

0.04

Neg. seq. curr. limit, mult. of base curr, usually


W1 curr.

NegSeqROA

30.0 - 120.0

Deg

0.1

60.0

Operate Angle for internal / external negative


sequence fault discriminator

124

Description

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Table 53:

T3WPDIF (87T) Group settings (advanced)

Name

Unit

Step

Default

EndSection1

0.20 - 1.50

IB

0.01

1.25

End of section 1, multi. of base current, usually


W1 curr.

EndSection2

1.00 - 10.00

IB

0.01

3.00

End of section 2, multi. of base current, usually


W1 curr.

SlopeSection2

10.0 - 50.0

0.1

40.0

Slope in section 2 of operate-restrain


characteristic, in %

SlopeSection3

30.0 - 100.0

0.1

80.0

Slope in section 3 of operate-restrain


characteristic, in %

I2/I1Ratio

5.0 - 100.0

0.1

15.0

Max. ratio of second harmonic to fundamental


harm dif. curr. in %

I5/I1Ratio

5.0 - 100.0

0.1

25.0

Max. ratio of fifth harmonic to fundamental


harm dif. curr. in %

OpenCTEnable

Disabled
Enabled

Disabled

Open CT detection feature. Open CTEnable


Off/On

tOCTAlarmDelay

0.100 - 10.000

0.001

3.000

Open CT: time in s to alarm after an open CT is


detected

tOCTResetDelay

0.100 - 10.000

0.001

0.250

Reset delay in s. After delay, diff. function is


activated

tOCTUnrstDelay

0.10 - 6000.00

0.01

10.00

Unrestrained diff. protection blocked after this


delay, in s

Step

Default

Table 54:

Values (Range)

Description

T3WPDIF (87T) Non group settings (basic)

Name

Values (Range)

Unit

Description

GlobalBaseSelW1

1 - 12

Global base selector for winding 1

GlobalBaseSelW2

1 - 12

Global base selector for winding 2

GlobalBaseSelW3

1 - 12

Global base selector for winding 3

ConnectTypeW1

WYE (Y)
Delta (D)

WYE (Y)

Connection type of winding 1: Y-wye or D-delta

ConnectTypeW2

WYE (Y)
Delta (D)

WYE (Y)

Connection type of winding 2: Y-wye or D-delta

ConnectTypeW3

WYE (Y)
Delta (D)

Delta (D)

Connection type of winding 3: Y-wye or D-delta

ClockNumberW2

0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]

0 [0 deg]

Phase displacement between W2 & W1=HV


winding, hour notation

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

125

Section 6
Differential protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

ClockNumberW3

0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]

5 [150 deg lag]

Phase displacement between W3 & W1=HV


winding, hour notation

ZSCurrSubtrW1

Disabled
Enabled

Enabled

Enable zer. seq. current subtraction for W1


side, On / Off

ZSCurrSubtrW2

Disabled
Enabled

Enabled

Enable zer. seq. current subtraction for W2


side, On / Off

ZSCurrSubtrW3

Disabled
Enabled

Enabled

Enable zer. seq. current subtraction for W3


side, On / Off

TconfigForW1

No
Yes

No

Two CT inputs (T-config.) for winding 1, YES /


NO

CT1RatingW1

1 - 99999

3000

CT primary rating in A, T-branch 1, on transf.


W1 side

CT2RatingW1

1 - 99999

3000

CT primary in A, T-branch 2, on transf. W1 side

TconfigForW2

No
Yes

No

Two CT inputs (T-config.) for winding 2, YES /


NO

CT1RatingW2

1 - 99999

3000

CT primary rating in A, T-branch 1, on transf.


W2 side

CT2RatingW2

1 - 99999

3000

CT primary rating in A, T-branch 2, on transf.


W2 side

TconfigForW3

No
Yes

No

Two CT inputs (T-config.) for winding 3, YES /


NO

CT1RatingW3

1 - 99999

3000

CT primary rating in A, T-branch 1, on transf.


W3 side

CT2RatingW3

1 - 99999

3000

CT primary rating in A, T-branch 2, on transf.


W3 side

LocationOLTC1

Not Used
Winding 1 (W1)
Winding 2 (W2)
Winding 3 (W3)

Not Used

Transformer winding where OLTC1 is located

LowTapPosOLTC1

0 - 10

OLTC1 lowest tap position designation (e.g. 1)

RatedTapOLTC1

1 - 100

OLTC1 rated tap/mid-tap position designation


(e.g. 6)

HighTapPsOLTC1

1 - 100

11

OLTC1 highest tap position designation (e.g.


11)

TapHighVoltTC1

1 - 100

OLTC1 end-tap position with winding highest


no-load voltage

Table continues on next page

126

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Name

Unit

Step

Default

StepSizeOLTC1

0.01 - 30.00

0.01

1.00

Voltage change per OLTC1 step in percent of


rated voltage

LocationOLTC2

Not Used
Winding 1 (W1)
Winding 2 (W2)
Winding 3 (W3)

Not Used

Transformer winding where OLTC2 is located

LowTapPosOLTC2

0 - 10

OLTC2 lowest tap position designation (e.g. 1)

RatedTapOLTC2

1 - 100

OLTC2 rated tap/mid-tap position designation


(e.g. 6)

HighTapPsOLTC2

1 - 100

11

OLTC2 highest tap position designation (e.g.


11)

TapHighVoltTC2

1 - 100

OLTC2 end-tap position with winding highest


no-load voltage

StepSizeOLTC2

0.01 - 30.00

0.01

1.00

Voltage change per OLTC2 step in percent of


rated voltage

6.1.6

Values (Range)

Description

Monitored data
Table 55:
Name

T2WPDIF (87T) Monitored data


Type

Values (Range)

Unit

Description

OCTSIDE

INTEGER

Open CT side : 1 -> W 1 (pri), 2


-> W 2 (sec)

OPENCTIN

INTEGER

Open CT on Input : 1 for input


1, 2 for input 2

OPENCTPH

INTEGER

Open CT in Phase : 1 for A, 2


for B, 3 for C

IDMAG_A

REAL

Magnitude of fundamental
frequency differential current,
phase A

IDMAG_B

REAL

Magnitude of fundamental
frequency differential current,
phase B

IDMAG_C

REAL

Magnitude of fundamental
frequency differential current,
phase C

IBIAS

REAL

Magnitude of the bias current,


which is common to all phases

IDMAG_NS

REAL

Magnitude of the negative


sequence differential current

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

127

Section 6
Differential protection

1MRK 502 066-UUS A

Table 56:

T3WPDIF (87T) Monitored data

Name

6.1.7

Type

Values (Range)

Unit

Description

IDMAG_A

REAL

Magnitude of fundamental
frequency differential current,
phase A

IDMAG_B

REAL

Magnitude of fundamental
frequency differential current,
phase B

IDMAG_C

REAL

Magnitude of fundamental
frequency differential current,
phase C

IBIAS

REAL

Magnitude of the bias current,


which is common to all phases

IDMAG_NS

REAL

Magnitude of the negative


sequence differential current

Operation principle
The task of the power transformer differential protection is to determine whether a fault
is within the protected zone, or outside of the protected zone. The protected zone is limited
by the position of current transformers (see Figure 32), and in principle can include more
objects than just a transformer. If the fault is found to be internal, the faulty power
transformer must be quickly disconnected from the system.
The main CTs are normally supposed to be Wye connected. The main CTs can be
grounded in anyway (that is, either "ToObject" or "FromObject"). However internally the
differential function will always use reference directions towards the protected
transformer as shown in Figure 32. Thus the IED will always internally measure the
currents on all sides of the power transformer with the same reference direction towards
the power transformer windings as shown in Figure 32. For more information see the
Application manual.
IW1

E1S1

IW2

Z1S1

Z1S2

IW1

IW2

E1S2

IED

en05000186_ansi.vsd
ANSI05000186 V1 EN

Figure 32:
128

Typical CT location and definition of positive current direction


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Even in a healthy power transformer, the currents are generally not equal when they flow
through it. This is due to the ratio of the number of turns of the windings and the
connection group of the protected transformer. Therefore the differential protection must
first correlate all currents to each other before any calculation can be performed.
First, compensation for the protected transformer transformation ratio and connection
group is made, and only then are the currents compared phase-wise. This makes external
auxiliary (interposing) current transformers unnecessary. Conversion of all currents to the
common reference side of the power transformer is performed by pre-programmed
coefficient matrices, which depends on the protected power transformer transformation
ratio and connection group. Once the power transformer phase shift, rated currents and
voltages have been entered by the user, the differential protection is capable to calculate
off-line matrix coefficients required in order to perform the on-line current comparison by
means of a fixed equation.
The negative-sequence-current-based internal-external fault discriminator, is used with
advantage in order to determine whether a fault is internal or external. It not only
positively discriminates between internal and external faults, but can also independently
detect minor faults which may not be sensed by the "usual" differential protection based
on operate-restrain characteristic.
For all differential functions it is the common trip that is used to initiate a
trip of a breaker. The separate trip signals from the different parts lacks the
safety against maloperation. This will in some cases result in a 6 ms time
difference between, for example restrained trip is issued and common trip
is issued. The separate trip signals are only used for information purpose
of which part that has caused the trip.

6.1.7.1

Function calculation principles


To make a differential IED as sensitive and stable as possible, restrained differential
characteristics have been developed and is now adopted as the general practice in the
protection of power transformers. The protection should be provided with a proportional
bias, which makes the protection operate for a certain percentage differential current
related to the current through the transformer. This stabilizes the protection under through
fault conditions while still permitting the system to have good basic sensitivity. The
following chapters explain how these quantities are derived.

Fundamental frequency differential currents


The fundamental frequency differential current is a vectorial sum (sum of fundamental
frequency phasors) of the individual phase currents from the different sides of the
protected power transformer.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

129

Section 6
Differential protection

1MRK 502 066-UUS A

Before any differential current can be calculated, the power transformer phase shift, and
its transformation ratio, must be accounted for. Conversion of all currents to a common
reference is performed in two steps:

all current phasors are phase-shifted to (referred to) the phase-reference side,
(whenever possible the first winding with wye connection)
all currents magnitudes are always referred to the first winding of the power
transformer (typically transformer high-voltage side)

The two steps of conversion are made simultaneously on-line by the pre-programmed
coefficient matrices, as shown in equation 1 for a two-winding power transformer, and in
equation 2 for a three-winding power transformer.
These are the internal compensation within the differential function. The
protected power transformer data is always entered per its nameplate. The
Differential function will correlate nameplate data and select proper
reference windings.

IDA
I _ A _ W 1
I _ A _ W 2
IDB = A I _ B _ W 1 + Vn _ W 2 B I _ B _ W 2

Vn _ W 1

IDC
I _ C _ W 1
I _ C _ W 2
1

(Equation 1)

EQUATION1879 V1 EN

where:

130

1.

is the resulting Differential Currents

2.

is the current contribution from the W1 side

3.

is the current contribution from the W2 side

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

IDA
I _ A _ W 1
I _ A _ W 2
IL _ A _ W 3
IDB = A I _ B _ W 1 + Vn _ W 2 B I _ B _ W 2 + Vn _ W 3 C IL _ B _ W 3

Vn _ W 1

Vn _ W 1

IDC
I _ C _ W 1
I _ C _ W 2
IL _ C _ W 3
1

(Equation 2)

EQUATION1882-ANSI V1 EN

where:
1.

is the resulting Differential Currents

2.

is the current contribution from the W1 side

3.

is the current contribution from the W2 side

4.

is the current contribution from the W3 side

and where, for equation 1 and equation 2:


ID_A

is the fundamental frequency differential current in phaseA (in W1 side primary amperes)

ID_B

is the fundamental frequency differential current in phase B (in W1 side primary amperes)

ID_C

is the fundamental frequency differential current in phaseC (in W1 side primary amperes)

I_A_W1

is the fundamental frequency phase current in phaseA on the W1 side

I_B_W1

is the fundamental frequency phase current in phaseB on the W1 side

I_C_W1

is the fundamental frequency phase current in phaseC on the W1 side

I_A_W2

is the fundamental frequency phase current in phaseA on the W2 side

I_B_W2

is the fundamental frequency phase current in phase B on the W2 side

I_C_W2

is the fundamental frequency phase current in phase C on the W2 side

I_A_W3

is the fundamental frequency phase current in phase A on the W3 side

I_B_W3

is the fundamental frequency phase current in phaseB on the W3 side

I_C_W3

is the fundamental frequency phase current in phaseC on the W3 side

Vn_W1

is transformer rated phase-to-phase voltage on the W1 side (setting parameter)

Vn_W2

is transformer rated phase-to-phase voltage on the W2 side (setting parameter)

Vn_W3

is transformer rated phase-to-phase voltage on the W3 side (setting parameter)

A, B and C

are three by three matrices with numerical coefficients

Values of the matrix A, B and C coefficients depend on:


1.

The Power transformer winding connection type, such as wye (Y/y) or delta (D/d)

Note! The capitalized letter Y or D is used to represent the high voltage (HV)
side of the transformer and the smaller letter y or d to represent lower
voltage(LV) level. When neutral bushing of a wye winding is brought out, the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

131

Section 6
Differential protection

1MRK 502 066-UUS A

same may be represented as YN or yn depending on whether the winding is HV


or LV.
2.

3.

The Transformer phase shift such as Yd1, Dy11, YNautod5, Yy0d5 and so on, which
introduce phase displacement between individual windings currents in multiples of
30. Since the HV and LV winding voltages are in phase for wye/wye or Delta/Delta
transformers, the same is represented in IEC as represented as Dd0, Yy0. Polarity
reversal in one of the windings would give 180 degree phase displacement which can
be represented by clock position 6. Such transformers can thus be represented as Dd6
or Yy6. It is also possible to rename the phases ABC to CAB or BCA, giving 120 or
240 degree displacements, represented by clock positions 4 & 8 . Polarity reversals in
one of the windings would provide clock positions 10 & 2. These can all be
represented for example: Yy0, Yy2, Yy4, Dd0, Dd6. ANSI wye/Delta or Delta/wye
transformers have the HV winding leading the LV winding by 30degrees. This can be
represented by Yd1 or Dy1. Again considering polarity reversals and renaming of
phases gives rise to other clock positions 4,7,5,11
The Settings for elimination of zero sequence currents for the individual windings.

When the end user enters all these parameters, transformer differential function
automatically calculates the matrix coefficients. During this calculations the following
rules are used:
For the phase reference, the first winding with set wye (Y) connection is always used. For
example, if the power transformer is a Yd1 power transformer, the HV winding (Y) is
taken as the phase reference winding. If the power transformer is a Dy1, then the LV
winding (y) is taken for the phase reference. If there is no wye connected winding, such
as in Dd0 type of power transformers, then the HV delta winding (D) is automatically
chosen as the phase reference winding.
The fundamental frequency differential currents are in general composed of currents of all
sequences, that is, the positive-, the negative-, and the zero-sequence currents. If the zerosequence currents are eliminated (see section "Optional Elimination of zero sequence
currents"), then the differential currents can consist only of the positive-, and the negativesequence currents. When the zero-sequence current is subtracted on one side of the power
transformer, then it is subtracted from each individual phase current.
As it can be seen from equation 1 and equation 2 the first entered winding (W1) is always
taken for ampere level reference (current magnitudes from all other sides are always
transferred to W1 side). In other words, within the differential protection function, all
differential currents and bias current are always expressed in HV side primary Amperes.
It can be shown that the values of the matrix A, B & C coefficients (see equation 1 and
equation 2) can be pre-calculated in advance depending on the relative phase shift between
the reference winding and other power transformer windings.

132

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Table 57 summarizes the values of the matrices for all standard phase shifts between
windings.
Table 57:

Matrices for differential current calculation


Matrix with Zero Sequence
Reduction set to On

Matrix for Reference Winding

2 -1 -1
1
-1 2 -1

3
-1 -1 2

Matrix for winding with 30


lagging

1 -1 0
1
0 1 -1

3
-1 0 1
1
1
1
3
-2

-2

-2

(Equation 6)

0 -1 1
1 0 -1

3
-1 1 0

-1 -1 2
1
2 -1 -1

3
-1 2 -1

-1 0 1
1 -1 0

3
0 1 -1

-2
1
1
3
1

(Equation 7)

EQUATION1234 V1 EN

(Equation 10)

Not applicable. Matrix on the left


used.

(Equation 11)

EQUATION1235 V1 EN

Matrix for winding which is in


opposite phase

EQUATION1231 V1 EN

Not applicable. Matrix on the left


used.

0 0 1
1 0 0

0 1 0
(Equation 9)

EQUATION1233 V1 EN

Matrix for winding with 150


lagging

Not applicable. Matrix on the left


used.

(Equation 8)

EQUATION1232 V1 EN

Matrix for winding with 120


lagging

(Equation 4)

0 -1 0
0 0 -1

-1 0 0

EQUATION1230 V1 EN

Matrix for winding with 90


lagging

EQUATION1228 V1 EN

(Equation 5)

EQUATION1229 V1 EN

Matrix for winding with 60


lagging

1 0 0
0 1 0

0 0 1
(Equation 3)

EQUATION1227 V1 EN

Matrix with Zero Sequence


Reduction set to Off

-2 1

1 -2

EQUATION1236 V1 EN

(Equation 12)

-1 0 0
0 -1 0

0 0 -1
EQUATION1237 V1 EN

(Equation 13)

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

133

Section 6
Differential protection

1MRK 502 066-UUS A

Matrix with Zero Sequence


Reduction set to On
Matrix for winding with 150
leading

-1 1 0
1
0 -1 1

3
1 0 -1
EQUATION1238 V1 EN

Matrix for winding with 120


leading

Matrix for winding with 90


leading

Matrix for winding with 60


leading

0 1 -1
-1 0 1

3
1 -1 0

1
1
-2
3
1

1
1
-2

EQUATION1242 V1 EN

Matrix for winding with 30


leading

(Equation 15)

EQUATION1241 V1 EN

0 1 0
0 0 1

1 0 0
EQUATION1240 V1 EN

(Equation 16)

Not applicable. Matrix on the left


used.

(Equation 17)

-2
1

1
(Equation 18)

1 0 -1
1
-1 1 0

3
0 -1 1
EQUATION1244 V1 EN

Not applicable. Matrix on the left


used.

(Equation 14)

-1 2 -1
1
-1 -1 2

3
2 -1 -1
EQUATION1239 V1 EN

Matrix with Zero Sequence


Reduction set to Off

0 0 -1
-1 0 0

0 -1 0
EQUATION1243 V1 EN

(Equation 19)

Not applicable. Matrix on the left


used.

(Equation 20)

By using this table complete equation for calculation of fundamental frequency


differential currents for two winding power transformer with YNd5 phase shift and
enabled zero sequence current reduction on HV side will be derived. From the given
power transformer phase shift the following is possible to be concluded:
1.
2.

The HV wye (Y) connected winding will be used as the reference winding and zero
sequence currents shall be subtracted on that side
The LV winding is lagging for 150

With the help of table 57, the following matrix equation can be written for this power
transformer:

134

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

ID _ A
2 -1 -1 I _ A _ W 1
-1 0 1 I _ A _ W 2
ID _ B = 1 -1 2 -1 I _ B _ W 1 + Vr _ W 2 1 1 -1 0 I _ B _ W 2

3

Vr _ W 1 3

ID _ C
-1 -1 2 I _ C _ W 1
0 1 -1 I _ C _ W 2
EQUATION1810-ANSI V1 EN

(Equation 21)

where:
ID_A

is the fundamental frequency differential current in phase A (in W1 side primary amperes)

ID_B

is the fundamental frequency differential current in phase B (in W1 side primary amperes)

ID_C

is the fundamental frequency differential current in phase C (in W1 side primary amperes)

I_A_W1

is the fundamental frequency phase current in phase A on the W1 side

I_B_W1

is the fundamental frequency phase current in phase B on the W1 side

I_C_W1

is the fundamental frequency phase current in phaseC on the W1 side

I_A_W2

is the fundamental frequency phase current in phase A on the W2 side

I_B_W2

is the fundamental frequency phase current in phase B on the W2 side

I_C_W2

is the fundamental frequency phase current in phaseC on the W2 side

Vn_W1

is transformer rated phase-to-phase voltage on the W1 side (setting parameter)

Vn_W2

is transformer rated phase-to-phase voltage on the W2 side (setting parameter)

As marked in equation 1 and equation 2, the first term on the right hand side of the
equation, represents the total contribution from the individual phase currents from the W1
side to the fundamental frequency differential currents, compensated for eventual power
transformer phase shift. The second term on the right hand side of the equation, represents
the total contribution from the individual phase currents from the W2 side to the
fundamental frequency differential currents, compensated for eventual power transformer
phase shift and transferred to the power transformer W1 side. The third term on the right
hand side of the equation, represents the total contribution from the individual phase
currents from the W3 side to the fundamental frequency differential currents,
compensated for eventual power transformer phase shift and transferred to the power
transformer W1 side. These current contributions are important, because they are used for
calculation of common bias current.
The fundamental frequency differential currents are the "usual" differential currents, the
magnitudes which are applied in a phase-wise manner to the operate - restrain
characteristic of the differential protection. The magnitudes of the differential currents
can be read as service values from the function and they are available as outputs
IDMAG_A, IDMAG_B, IDMAG_C from the differential protection function block. Thus
they can be connected to the disturbance recorder and automatically recorded during any
external or internal fault condition.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

135

Section 6
Differential protection

1MRK 502 066-UUS A

On-line compensation for load tap changer movement


A load tap changer is a mechanical device, which is used to step-wise change number of
turns within one power transformer winding. Consequently the power transformer overall
turns ratio is changed. Typically the load tap changer is located within the HV winding
(that is, winding 1, W1) of the power transformer. By operating load tap changer, it is
possible to step-wise regulate voltage on the LV side of the power transformer. However
at the same time the differential protection for power transformer becomes unbalanced.
Differential function in the IED has built-in feature to continuously monitor the load tap
changer position and dynamically compensate on-line for changes in power transformer
turns ratio.
Differential currents are calculated as shown in equation 1 and equation 2. By setting
parameters, the winding location of the OLTC is defined. Also, the voltage change of each
step. Thus, if for example the load tap changer is located within winding 1 the no-load
voltage Un_W1 will be treated as a function of the actual load tap changer position in
equation 1 and equation 2. Thus for every load tap changer position a corresponding value
for Vn_W1 will be calculated and used in the above mentioned equations. By doing this,
complete on-line compensation for load tap changer movement is achieved. Differential
protection will be ideally balanced for every load tap changer position and no false
differential current will appear irrespective of actual load tap changer position.
Typically the minimum differential protection pickup for power transformer with load tap
changer is set between 30% to 40%. However with this load tap changer compensation
feature it is possible to set the differential protection in the IED more sensitive with a
pickup value of 15% to 20%.
Load tap changer position is measured within the IED by Tap changer control and
supervision, (TCLYLTC ,84). Within this function block, the load tap changer position
value is continuously monitored to insure its integrity.
When any error in the load tap changer position is detected an alarm is given. This signal
shall be connected to the OLTCxAL input of the differential function block. While
OLTCxAL input has a logical value of one the differential protection minimum pickup,
originally defined by setting parameter IdMin, will be increased by the set range of the
load tap changer. Alternatively the differential current alarm feature can be used to alarm
for any problems in the whole load tap changer compensation chain.
It shall be noted that:

136

two-winding differential protection in the IED can on-line compensate for one load
tap changer within the protected power transformer
three-winding differential protection in the IED can on-line compensate for up to two
load tap changers within the protected power transformer

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Differential current alarm


Fundamental frequency differential current level is monitored all the time within the
differential function. As soon as all three fundamental frequency differential currents are
above the set threshold defined by setting parameter IDiffAlarm a delay on pickup timer
is started. When the pre-set time, defined by setting parameter tAlarmDelay, has expired
the differential current alarm is generated and output signal IDALARM is set to logical
value one. This feature can be effectively used to provide alarm when load tap changer
position compensation is used and something in the whole compensation chain goes
wrong. This alarm can be as well used with some additional IED configuration logic to
desensitize the differential function.

Bias current
The bias current is calculated as the highest current amongst all individual winding current
contributions to the total fundamental frequency differential currents, as shown in
equation 1 and equation 2. All individual winding current contributions are already
referred to the power transformer winding one side (power transformer HV winding) and
therefore they can be compared regarding their magnitudes. There are six (or nine in the
case of a three-winding transformer) contributions to the total fundamental differential
currents, which are the candidates for the common bias current. The highest individual
current contribution is taken as a common bias (restrain) current for all three phases. This
"maximum principle" makes the differential protection more secure, with less risk to
operate for external faults and in the same time brings more meaning to the breakpoint
settings of the operate - restrain characteristic.
It shall be noted that if the zero-sequence currents are subtracted from the separate
contributions to the total differential current, then the zero-sequence component is
automatically eliminated from the bias current as well. This ensures that for secondary
injection from just one power transformer side the bias current is always equal to the
highest differential current regardless of the fault type. During normal through-load
operation of the power transformer, the bias current is equal to the maximum load current
from two (three) -power transformer windings.
The magnitudes of the common bias (restrain) current expressed in HV side amperes can
be read as service value from the function. At the same time it is available as an output
IBIAS from the differential protection function block. It can be connected to the
disturbance recorder and automatically recorded during any external or internal fault
condition.
For application with so called "T" configuration, that is, two restraint CT inputs from one
side of the protected power transformer, such as in the case of breaker-and-a-half schemes
the primary CT ratings can be much higher than the rating of the protected power
transformer. In order to determine the bias current for such T configuration, the two
separate currents flowing in the T-side are scaled down to the protected power transform
level by means of additional settings. This is done in order to prevent unwanted desensitizing of the overall differential protection. In addition to that, the resultant currents
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

137

Section 6
Differential protection

1MRK 502 066-UUS A

(the sum of two currents) into the protected power transformer winding, which is not
directly measured is calculated, and included in the common bias calculation. The rest of
the bias calculation procedure is the same as in protection schemes without breaker-anda-half arrangements.

Optional Elimination of zero sequence currents


To avoid unwanted trips for external ground-faults, the zero sequence currents should be
subtracted on the side of the protected power transformer, where the zero sequence
currents can flow at external ground-faults.
The zero sequence currents can be explicitly eliminated from the differential currents and
common bias current calculation by special, dedicated parameter settings, which are
available for every individual winding.
Elimination of the zero sequence component of current is necessary whenever:

the protected power transformer cannot transform the zero sequence currents to the
other side.
the zero sequence currents can only flow on one side of the protected power
transformer.

In most cases, power transformers do not properly transform the zero sequence current to
the other side. A typical example is a power transformer of the wye-delta type, for example
YNd1. Transformers of this type do not transform the zero sequence quantities, but zero
sequence currents can flow in the grounded wye connected winding. In such cases, an
external ground-fault on the wye-side causes zero sequence current to flow on the wyeside of the power transformer, but not on the other side. This results in false differential
currents - consisting exclusively of the zero sequence currents. If high enough, these false
differential currents can cause an unwanted disconnection of the healthy power
transformer. They must therefore be subtracted from the fundamental frequency
differential currents if an unwanted trip is to be avoided.
For delta windings this feature shall be enabled only if a grounding transformer exists
within the differential zone on the delta side of the protected power transformer.
Removing the zero sequence current from the differential currents decreases to some
extent the sensitivity of the differential protection for internal ground-faults. In order to
counteract this effect to some degree, the zero sequence current is subtracted not only from
the three fundamental frequency differential currents, but from the bias current as well.

Restrained and unrestrained limits of the differential protection


The power transformer differential protection function uses two limits, to which actual
magnitudes of the three fundamental frequency differential currents are compared at each
execution of the function.

138

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

The unrestrained (that is, non-stabilized, "instantaneous") part of the differential


protection is used for very high differential currents, where it should be beyond any doubt,
that the fault is internal. This settable limit is constant and not proportional to the bias
current. Neither harmonic, nor any other restrain is applied to this limit, which is therefore
allowed to trip the power transformer instantaneously.
The restrained (stabilized) part of the differential protection compares the calculated
fundamental differential (operating) currents and the bias (restrain) current, by applying
them to the operate - restrain characteristic. Practically, the magnitudes of the individual
fundamental frequency differential currents are compared with an adaptive limit. This
limit is adaptive because it is dependent on the bias (that is, restrain) current magnitude.
This limit is called the operate - restrain characteristic. It is represented by a double-slope,
double-breakpoint characteristic, as shown in figure 33. The restrained characteristic is
determined by the following 5 settings:
1.
2.
3.
4.
5.

IdMin (Sensitivity in section 1, multiple of trans. HV side rated current set under the
parameter RatedCurrentW1)
EndSection1 (End of section 1, as multiple of transformer HV side rated current set
under the parameter RatedCurrentW1)
EndSection2 (End of section 2, as multiple of transformer HV side rated current set
under the parameter RatedCurrentW1)
SlopeSection2 (Slope in section 2, as multiple of transformer HV side rated current
set under the parameter RatedCurrentW1)
SlopeSection3 (Slope in section 2, as multiple of transformer HV side rated current
set under the parameter RatedCurrentW1)

The restrained characteristic in figure 33 is defined by the settings:


1.
2.
3.
4.
5.

IdMin
EndSection1
EndSection2
SlopeSection2
SlopeSection3

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

139

Section 6
Differential protection

1MRK 502 066-UUS A

operate current
[ times IBase ]

Operate

unconditionally
UnrestrainedLimit

Operate

conditionally

2
Section 1

Section 2

Section 3
SlopeSection3

1
IdMin
SlopeSection2

Restrain

0
0

EndSection1
EndSection2

restrain current
[ times IBase ]

en05000187-2.vsd
IEC05000187 V2 EN

Figure 33:

Description of the restrained, and the unrestrained operate


characteristics

where:

slope = D Ioperate 100%


D Irestrain
EQUATION1246 V1 EN

The operate - restrain characteristic is tailor-made and can be designed freely by the user
after his needs. The default characteristic is recommended to be used. It gives good results
in a majority of applications. The operate - restrain characteristic has in principle three
sections with a section-wise proportionality of the operate value to the bias (restrain)
current. The reset ratio is in all parts of the characteristic equal to 0.95.
Section 1: This is the most sensitive part on the characteristic. In section 1, normal
currents flow through the protected circuit and its current transformers, and risk for higher
false differential currents is relatively low. An un-compensated on-load tap-changer is a
140

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

typical reason for existence of the false differential currents in this section. The slope in
section 1 is always zero percent.
Section 2: In section 2, a certain minor slope is introduced which is supposed to cope with
false differential currents proportional to higher than normal currents through the current
transformers.
Section 3: The more pronounced slope in section 3 is designed to result in a higher
tolerance to substantial current transformer saturation at high through-fault currents,
which may be expected in this section.
The operate - restrain characteristic should be designed so that it can be expected that:

for internal faults, the operate (differential) currents are always with a good margin
above the operate - restrain characteristic
for external faults, the false (spurious) operate currents are with a good margin below
the operate - restrain characteristic

Fundamental frequency negative sequence differential currents


Existence of relatively high negative sequence currents is in itself a proof of a disturbance
on the power system, possibly a fault in the protected power transformer. The negativesequence currents are a measurable indication of an abnormal condition, similar to the
zero sequence current. One of the several advantages of the negative sequence currents
compared to the zero sequence currents is that they provide coverage for phase-to-phase
and power transformer turn-to-turn faults. Theoretically, the negative sequence currents
do not exist during symmetrical three-phase faults, however they do appear during initial
stage of such faults for a long enough time (in most cases) for the IED to make the proper
decision. Further, the negative sequence currents are not stopped at a power transformer
by the Yd, or Dy connection type. The negative sequence currents are always properly
transformed to the other side of any power transformer for any external disturbance.
Finally, the negative sequence currents are not affected by symmetrical through-load
currents.
For power transformer differential protection applications, the negative sequence based
differential currents are calculated by using exactly the same matrix equations, which are
used to calculate the traditional phase-wise fundamental frequency differential currents.
The same equation shall be fed by the negative sequence currents from the two power
transformer sides instead of individual phase currents, as shown in matrix equation 23 for
a case of two-winding, YNd5 power transformer.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

141

Section 6
Differential protection

1MRK 502 066-UUS A

IDNS _ A
2 -1 -1 INS _ W 1
-1 0 1 INS _ W 2
IDNS _ B = 1 -1 2 -1 a INS _ W 1 + Vn _ W 2 1 1 -1 0 a INS _ W 2
Vn _ W 1

3


3
IDNS _ C
-1 -1 2 a 2 INS _ W 1
0 1 -1 a 2 INS _ W 2
1

3
(Equation 23)

EQUATION1560 V1 EN

where:
1.

is the Negative Sequence Differential Currents

2.

is the Negative Sequence current contribution from the W1 side

3.

is the Negative Sequence current contribution from the W2 side

and where:
IDNS_A

is the negative sequence differential current in phase A (in


W1 side primary amperes)

IDNS_B

is the negative sequence differential current in phase B (in


W1 side primary amperes)

IDNS_C

is the negative sequence differential current in phase C (in


W1 side primary amperes)

INS_W1

is the negative sequence current on the W1 side in primary


amperes (phase A reference)

INS_W2

is the negative sequence current on the W2 side in primary


amperes (phase A reference)

Vn_W1

is the transformer rated phase-to-phase voltage on the W1


side (setting parameter)

Vn_W2

is the transformer rated phase-to-phase voltage on W2 side


(setting parameter)

is the complex operator for sequence quantities,

a=e

j 120

=-

EQUATION1248 V1 EN

1
2

+ j

3
2
(Equation 24)

Because the negative sequence currents always form the symmetrical three phase current
system on each transformer side (that is, negative sequence currents in every phase will
always have the same magnitude and be phase displaced for 120 electrical degrees from
each other), it is only necessary to calculate the first negative sequence differential current
that is, IDNS_A.

142

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

As marked in equation 23, the first term on the right hand side of the equation, represents
the total contribution of the negative sequence current from the W1 side compensated for
eventual power transformer phase shift. The second term on the right hand side of the
equation, represents the total contribution of the negative sequence current from the W2
side compensated for eventual power transformer phase shift and transferred to the power
transformer W1 side. These negative sequence current contributions are phasors, which
are further used in directional comparisons, to characterize a fault as internal or external.
See section "Internal/external fault discriminator" for more information.
The magnitudes of the negative sequence differential current expressed in the HV side A
can be read as service values from the function. In the same time it is available as outputs
IDMAG_NS from the differential protection function block. Thus, it can be connected to
the disturbance recorder and automatically recorded during any external or internal fault
condition.

Internal/external fault discriminator


The internal/external fault discriminator is a very powerful and reliable supplementary
criterion to the traditional differential protection. It is recommended that this feature shall
be always used (that is, enabled) when protecting three-phase power transformers. The
internal/external fault discriminator detects even minor faults, with a high sensitivity and
at high speed, and at the same time discriminates with a high degree of dependability
between internal and external faults.
The internal/external fault discriminator responds to the magnitudes and the relative phase
angles of the negative-sequence fault currents at the different windings of the protected
power transformer. The negative sequence fault currents must first be referred to the same
phase reference side, and put to the same magnitude reference. This is done by the matrix
expression (see equation 23).
Operation of the internal/external fault discriminator is based on the relative position of
the two phasors representing the winding one (W1) and winding two (W2) negative
sequence current contributions, respectively, defined by expression shown in
equation 23. It performs a directional comparison between these two phasors. First, the
LV side phasor is referred to the HV side (W1 side): both the magnitude, and the phase
position are referred to the HV (W1 side). Then the relative phase displacement between
the two negative sequence current phasors is calculated. In case of three-winding power
transformers, a little more complex algorithm is applied, with two directional tests. The
overall directional characteristic of the internal/external fault discriminator is shown in
figure 34, where the directional characteristic is defined by two setting parameters:
1.
2.

IMinNegSeq
NegSeqROA

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

143

Section 6
Differential protection

1MRK 502 066-UUS A

90 deg
120 deg
If one or the
other of
currents is too
low, then no
measurement
is done, and
120 degrees
is mapped

Internal/external
fault boundary

NegSeqROA
(Relay
Operate
Angle)

180 deg

0 deg

IMinNegSeq

Internal
fault
region

External
fault
region

270 deg

en05000188-3-en.vsd

IEC05000188 V3 EN

Figure 34:

Operating characteristic of the internal/external fault discriminator

In order to perform directional comparison of the two phasors their magnitudes must be
high enough so that one can be sure that they are due to a fault. On the other hand, in order
to guarantee a good sensitivity of the internal/external fault discriminator, the value of this
minimum limit must not be too high. Therefore this limit value, called IminNegSeq, is
settable in the range of 0.02 to 0.20 times the IBase of the power transformer winding one.
The default value is 0.04. Note that, in order to enhance stability at higher fault currents,
the relatively very low threshold value IminNegSeq is dynamically increased at currents
higher than normal currents: if the bias current is higher than 110% of IBase ,then 10% of
the bias current is added to the IminNegSeq. Only if the magnitudes of both negative
sequence current contributions are above the actual limit, the relative position between
these two phasors is checked. If either of the negative sequence current contributions,
which should be compared, is too small (less than the set value for IminNegSeq), no
directional comparison is made in order to avoid the possibility to produce a wrong
decision. This magnitude check guarantees stability of the algorithm, when the power
transformer is energized. The setting NegSeqROA represents the Relay Operate Angle,
which determines the boundary between the internal and external fault regions. It can be
selected in a range from 30 degrees to 90 degrees, with a step of 0.1 degree. The default
value is 60 degrees. The default setting 60 degree favours security in comparison to
dependability.

144

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

If the above condition concerning magnitudes is fulfilled, the internal/external fault


discriminator compares the relative phase angle between the negative sequence current
contributions from W1 and W2 sides of the power transformer using the following two
rules:

If the negative sequence current contributions from the W1 and the W2 sides are in
phase, the fault is internal (that is, both phasors are within protected zone)
If the negative sequence currents contributions from W1 and W2 sides are 180
degrees out of phase, the fault is external (that is, W1 phasors is outside protected
zone)

For example, for any unsymmetrical external fault, ideally the respective negative
sequence current contributions from the W1 and W2 power transformer sides will be
exactly 180 degrees apart and equal in magnitude, regardless the power transformer turns
ratio and phase displacement. An example is shown in figure 35, which shows trajectories
of the two separate phasors representing the negative sequence current contributions from
the HV and LV sides of an Yd5 power transformer (after compensation of the transformer
turns ratio and phase displacement) by using equation 23) for an unsymmetrical external
fault. Observe that the relative phase angle between these two phasors is 180 electrical
degrees at any point in time. No current transformer saturation was assumed for this case.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

145

Section 6
Differential protection

1MRK 502 066-UUS A

"steady state"
for HV side
neg. seq. phasor

90
60

150

30
10
ms

180

0
0.1 kA
10
ms

0.2 kA

0.3 kA

0.4 kA

330

210

240
270

"steady state"
for LV side
neg. seq. phasor

Contribution to neg. seq. differential current from HV side


Contribution to neg. seq. differential current from LV side

en05000189.vsd
IEC05000189 V1 EN

Figure 35:

Trajectories of Negative Sequence Current Contributions from HV and


LV sides of Yd5 power transformer during external fault

Under external fault conditions, the relative angle is theoretically equal to 180 degrees.
During internal faults, the angle shall ideally be 0 degrees, but due to possible different
negative sequence source impedance angles on the W1 and W2 sides of the protected
power transformer, it may differ somewhat from the ideal zero value. However, during
heavy faults, CT saturation might cause the measured phase angle to differ from 180
degrees for an external, and from 0 degrees for an internal fault. See figure 36 for an
example of a heavy internal fault with transient CT saturation.

146

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Dire ctiona l Compa ris on Crite rion: Inte rna l fa ult a s s e e n from the HV s ide
90
e xcurs ion
from 0 de gre e s
due to CT
s a tura tion

60

120
35 ms

150

30
de finite ly
a n inte rna l
fa ult

180
e xte rna l
fa ult
re gion

0.5 kA

330

210

trip c o mmand
in 12 ms
Inte rna l fa ult
de cla re d 7 ms
a fte r inte rna l
fa ult occure d

1.0 kA

240

300
270

1.5 kA

HV s ide contribution to the tota l ne ga tive s e que nce diffe re ntia l curre nt in kA
Dire ctiona l limit (within the re gion de limite d by 60 de gre e s is inte rna l fa ult)

en05000190.vsd
IEC05000190 V1 EN

Figure 36:

Operation of the internal/external fault discriminator for internal fault with


CT saturation

It shall be noted that additional security measures are implemented in the internal/external
fault discriminator algorithm in order to guarantee proper operation with heavily saturated
current transformers. The trustworthy information on whether a fault is internal or
external is typically obtained in about 10ms after the fault inception, depending on the
setting IminNegSeq, and the magnitudes of the fault currents. During heavy faults,
approximately 5ms time to full saturation of the main CT is sufficient in order to produce
a correct discrimination between internal and external faults.

Unrestrained, and sensitive negative sequence protections


Two sub functions, which are based on the internal/external fault discriminator with the
ability to trip a faulty power transformer, are parts of the traditional power transformer
differential protection.
The unrestrained negative sequence differential protection
The unrestrained negative sequence protection is activated if one or more pickup signals
have been set by the traditional differential protection algorithm. This happens because
one or more of the fundamental frequency differential currents entered the operate region
on the operate - restrain characteristic. So, this protection is not independent of the
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

147

Section 6
Differential protection

1MRK 502 066-UUS A

traditional restrained differential protection - it is activated after the first start signal has
been placed.
If the same fault has been positively recognized as internal, then the unrestrained negative
sequence differential protection places its own trip request.
Any block signals by the harmonic and/or waveform criteria, which can block the
traditional differential protection are overridden, and the differential protection operates
quickly without any further delay.
This logic guarantees a fast disconnection of a faulty power transformer for any internal
fault.
If the same fault has been classified as external, then generally, but not unconditionally,
a trip command is prevented. If a fault is classified as external, the further analysis of the
fault conditions is initiated. If all the instantaneous differential currents in phases where
pickup signals have been issued are free of harmonic pollution, then a (minor) internal
fault, simultaneous with a predominant external fault can be suspected. This conclusion
can be drawn because at external faults, major false differential currents can only exist
when one or more current transformers saturate. In this case, the false instantaneous
differential currents are polluted by higher harmonic components, the 2nd, the 5th etc.
Sensitive negative sequence based turn-to-turn fault protection
The sensitive, negative sequence current based turn-to-turn fault protection detects the
low level faults, which are not detected by the traditional differential protection until they
develop into more severe faults, including power transformer iron core. The sensitive
protection is independent from the traditional differential protection and is a very good
complement to it. The essential part of this sensitive protection is the internal/external
fault discriminator. In order to be activated, the sensitive protection requires no pickup
signal from the traditional power transformer biased differential protection. If magnitudes
of HV and LV negative sequence current contributions are above the set limit for
IminNegSeq, then their relative positions are determined. If the disturbance is
characterized as an internal fault, then a separate trip request will be placed. Any decision
on the way to the final trip request must be confirmed several times in succession in order
to cope with eventual CT transients. This causes a short additional operating time delay
due to this security count. For very low level turn-to-turn faults the overall response time
of this protection is about 30ms.

Instantaneous differential currents


The instantaneous differential currents are calculated from the instantaneous values of the
input currents in order to perform the harmonic analysis and waveform analysis upon each
one of them (see section "Harmonic and waveform block criteria" for more information).
The instantaneous differential currents are calculated using the same matrix expression as
shown in equation 1 and equation 2. The same matrices A, B and C are used for these

148

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

calculations. The only difference is that the matrix algorithm is fed by instantaneous
values of currents, that is, samples.

Harmonic and waveform block criteria


The two block criteria are the harmonic restrain and the waveform restrain. These two
criteria have the power to block a trip command by the traditional differential protection,
which produces pickup signals by applying the differential currents, and the bias current,
to the operate - restrain characteristic.
Harmonic restrain
The harmonic restrain is the classical restrain method traditionally used with power
transformer differential protections. The goal is to prevent an unwanted trip command due
to magnetizing inrush currents at switching operations, or due to magnetizing currents at
over-voltages.
The magnetizing currents of a power transformer flow only on one side of the power
transformer and are therefore always the cause of false differential currents. The harmonic
analysis (the 2nd and the 5th harmonic) is applied to the instantaneous differential currents.
Typical instantaneous differential currents during power transformer energizing are
shown in figure 37. The harmonic analysis is only applied in those phases, where pickup
signals have been set. For example, if the content of the 2nd harmonic in the instantaneous
differential current of phase A is above the setting I2/I1Ratio, then a block signal is set for
that phase, which can be read as BLK2H_A output of the differential protection.
Waveform restrain
The waveform restrain criterion is a good complement to the harmonic analysis. The
waveform restrain is a pattern recognition algorithm, which looks for intervals within each
fundamental power system cycle with low instantaneous differential current. This interval
is often called current gap in protection literature. However, within differential function
this criterion actually searches for long-lasting intervals with low rate-of-change in
instantaneous differential current, which are typical for the power transformer inrush
currents. Block signals BLKWAV_A(B,C) are set in those phases where such behavior is
detected. The algorithm does not require any end user settings. The waveform algorithm
is automatically adapted dependent only on the power transformer rated data.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

149

Section 6
Differential protection

1MRK 502 066-UUS A

Current [%]

400kV Currents

I_A
I_B
I_C

Time [cycles]
en05000343_ansi.vsd
ANSI05000343 V1 EN

Figure 37:

Inrush currents to a transformer as seen by a protective IED. Typical is a


high amount of the 2nd harmonic, and intervals of low current, and low
rate-of-change of current within each period.

Cross-blocking between phases


The basic definition of the cross-blocking is that one of the three phases can block
operation (that is, tripping) of the other two phases due to the harmonic pollution of the
differential current in that phase (that is, waveform, 2nd or 5th harmonic content). In
differential algorithm the user can control the cross-blocking between the phases via the
setting parameter CrossBlockEn=Enabled.
When parameter CrossBlockEn=Enabled cross blocking between phases is introduced.
There is no time settings involved, but the phase with the operating point above the set bias
characteristic (in the operate region) will be able to cross-block the other two phases if it
is itself blocked by any of the previously explained restrained criteria. As soon as the
operating point for this phase is below the set bias characteristic (that is, in the restrain
region) cross blocking from that phase will be inhibited. In this way cross-blocking of the
temporary nature is achieved. It should be noted that this is the default setting value for this
parameter.
When parameter CrossBlockEn=Disabled, any cross blocking between phases will be
disabled. It is recommended to use the value Disabled with caution in order to avoid the
unwanted tripping during initial energizing of the power transformer.

Switch onto fault feature


The transformer differential function has a built-in, advanced switch onto fault feature.
This feature can be enabled or disabled by a setting parameter SOTFMode. When enabled
this feature ensures quick differential protection tripping in cases where a transformer is
150

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

energized with an internal fault (for example, forgotten grounding on transformer LV


side). Operation of this feature is based on the fact that a current gap (term current gap is
explained under waveblock feature above) will exist within the first power system cycle
when healthy power transformer is energized. If this is not the case the waveblock
criterion will reset quickly. This quick reset of the waveblock criterion will temporarily
disable the second harmonic blocking feature of the differential protection function. This
consequently ensures fast operation of the transformer differential function for a switch
onto a fault condition. It shall be noted that this feature is only active during initial power
transformer energizing, under the first 50 ms. When the switch onto fault feature is
disabled by the setting parameter SOTFMode, the waveblock and second harmonic
blocking features work in parallel and are completely independent from each other.

Open CT detection feature


Transformer differential protection has a built-in, advanced open CT detection feature.
A sudden inadvertently opened CT circuit may cause an unexpected and unwanted
operation of the Transformer differential protection under normal load conditions.
Damage of secondary equipment may occur due to high voltage from open CT circuit
outputs. It is always an advantage, from the point of view of security and reliability, to
have the open CT detection function to block the transformer differential protection
function in case of an open CT condition, and produce an alarm signal to the operational
personnel to quickly correct the open CT condition.
The built-in open CT feature can be enabled or disabled by the setting parameter
OpenCTEnable (Disabled/Enabled). When enabled, this feature tries to prevent maloperation when a loaded main CT connected to Transformer differential protection is by
mistake open circuited on the secondary side. Note that this feature can only detect
interruption of one CT phase current at a time. If two or even all three-phase currents of
one set of CTs are accidentally interrupted at precisely the same time, this feature cannot
operate. Transformer differential protection generates a trip signal if the false differential
current is sufficiently high. An open CT circuit is typically detected in 1214 ms, and if
the load in the protected circuit is relatively high, about the nominal load, the unwanted
trip cannot always be prevented. Still, the information about what was the cause of the
open CT secondary circuit, is vital.
The principle applied to detect an open CT is a simple pattern recognition method, similar
to the waveform check used by the Power transformer differential protection in order to
detect the magnetizing inrush condition. The open CT detection principle is based on the
fact that for an open CT, the current in the phase with the open CT suddenly drops to zero
(that is, as seen by the protection), while the currents of the other two phases continue as
before.
The open CT function is supposed to detect an open CT under normal conditions, that is,
with the protected multi-terminal circuit under normal load (10...110% of the rated load).
If the load currents are very low or zero, the open CT condition cannot be detected. In
addition to load condition requirement, Open CT function also checks the differential
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

151

Section 6
Differential protection

1MRK 502 066-UUS A

current on faulty phase. If the differential current is lower than 50% of IdMin, the open CT
condition cannot be detected. Therefore, the Open CT algorithm only detects an open CT
if the load on the power transformer is 10...110% of rated load and the differential current
is higher than 50% of IdMin on that phase. The search for an open CT starts 60 seconds
(50 seconds in 60 Hz systems) after the transformer is energized. The Open CT detection
feature can also be explicitly deactivated by setting: OpenCTEnable = 0 (Disabled ).
If an open CT is detected and the output OPENCT set to 1, then all the differential
functions are blocked, except the unrestrained (instantaneous) differential. An alarm
signal is also produced after a settable delay (tOCTAlarmDelay) to report to operational
personnel for quick remedy actions once the open CT is detected. When the open CT
condition is removed (that is, the previously open CT is reconnected), the functions
remain blocked for a specified interval of time, which is also defined by a setting
(tOCTResetDelay). This is to prevent an eventual mal-operation after the reconnection of
the previously open CT secondary circuit.
The open CT algorithm provides detailed information about the location of the defective
CT secondary circuit. The algorithm clearly indicates the IED side, CT input and phase in
which an open CT condition has been detected. These indications are provided via the
following outputs from the Transformer differential protection function:
1.
2.
3.
4.

Output OPENCT provides instant information to indicate that an open CT circuit has
been detected.
Output OPENCTAL provides a time-delayed alarm that the open CT circuit has been
detected. Time delay is defined by the parameter tOCTAlarmDelay.
Integer output OPENCTIN provides information on the local HMI regarding which
open CT circuit has been detected (1=CT input No 1; 2=CT input No 2).
Integer output OPENCTPH provides information on the local HMI regarding in
which phase an open CT circuit has been detected (1=Phase A; 2= Phase B; 3= Phase
C).

Once the open CT condition is declared, the algorithm stops to search for further open CT
circuits. It waits until the first open CT circuit has been corrected. Note that once the open
CT condition has been detected, it can be reset automatically within the differential
function. It is not possible to externally reset an open CT condition. To reset the open CT
circuit alarm automatically, the following conditions must be fulfilled:

Bias current is for at least one minute smaller than 110%


The open CT condition in the defective CT circuit has been corrected (for example,
current asymmetry disappears)
The above two conditions are fulfilled for a longer time than defined by the setting
parameter tOCTResetDelay

If an open CT has been detected in a separate group of three CTs, the algorithm is reset
either when the missing current returns to the normal value, or when all three currents
152

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

become zero. After the reset, the open CT detection algorithm starts again to search for
open CT circuits within the protected zone.

6.1.7.2

Logic diagram
The simplified internal logics, for transformer differential protection are shown in the
following figures.
IED
Differential function

Derive equation to calculate differential currents

Phasors &
samples
Phasors &
samples

Phasor calculation of
individual phase current

Trafo
Data

Phasor calculation of
individual phase current

152

A/D conversion scaling with


CT ratio

52

A/D conversion scaling with


CT ratio

ADM

Instantaneous (sample based)


Differential current, phase A

ID_A

Instantaneous (sample based)


Differential current, phase B

ID_B

Instantaneous (sample based)


Differential current, phase C

ID_C

IDMAG_NS

Negative sequence diff current


& NS current contribution from
individual windings

IDMAG_A

Fundamental frequency (phasor


based) Diff current, phase A &
phase current contributions from
individual windings

IDMAG_B

Fundamental frequency (phasor


based) Diff current, phase B &
phase current contributions from
individual windings

IDMAG_C

Fundamental frequency (phasor


based) Diff current, phase C &
phase current contributions from
individual windings

MAX

IBIAS

Settings for Zer. Seq.


Current Reduction
ANSI05000166_2_en.vsd
ANSI05000166 V2 EN

Figure 38:

Treatment of measured currents within IED for transformer differential function

Figure 38 shows how internal treatment of measured currents is done in case of a twowinding transformer.
The following currents are inputs used in the power transformer differential protection
function. They must all be expressed in power system (primary) A.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

153

Section 6
Differential protection

1.
2.
3.

1MRK 502 066-UUS A

Instantaneous values of currents (samples) from the HV, and LV sides for twowinding power transformers, and from the HV, the first LV, and the second LV side
for three-winding power transformers.
Currents from all power transformer sides expressed as fundamental frequency
phasors with their real and imaginary parts. These currents are calculated within the
protection function by the fundamental frequency Fourier filters.
Negative sequence currents from all power transformer sides expressed as phasors.
These currents are calculated within the protection function by the symmetrical
components module.

The power transformer differential protection:


1.

2.
3.

154

Calculates three fundamental frequency differential currents and one common bias
current. The zero-sequence component can optionally be eliminated from each of the
three fundamental frequency differential currents and at the same time from the
common bias current.
Calculates three instantaneous differential currents. They are used for harmonic, and
waveform analysis. Instantaneous differential currents are useful for post-fault
analysis using disturbance recording
Calculates negative-sequence differential current. Contributions to it from both (all
three) power transformer sides are used by the internal/external fault discriminator to
detect and classify a fault as internal or external.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

BLKUNRES
a

IdUnre

AND

b>a

TRIPUNRE_A

IDMAG_A
IBIAS

PU_A

AND

BLOCK
BLKRES

AND
OR
IDA

NOT

2nd
Harmonic

BLK2H_A

5th
Harmonic

BLK5H_A
BLKWAV_A

Wave
block
Cross Block
from B or C phases
CrossBlockEn=Enabled

TRIPRES_A

AND

OR

AND

Cross Block
to B or C phases

ANSI05000168_2_en.vsd
ANSI05000168 V2 EN

Figure 39:

Transformer differential protection simplified logic diagram for Phase A

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

155

Section 6
Differential protection

1MRK 502 066-UUS A

Internal/
External
Fault
discrimin
ator

Neg.Seq. Diff
Current
Contributions

EXTFAULT
INTFAULT

TRNSSENS

AND

TRNSUNR

AND

OpNegSeqDiff=On
IBIAS

t
0

b>a

Constant
BLKNSSEN
BLKNSUNR
BLOCK
PU_A
PU_B

OR

PU_C

en05000167_ansi.vsd
ANSI05000167 V1 EN

Figure 40:

Transformer differential protection simplified logic diagram for external/


internal fault discriminator

TRIPRES_A
TRIPRES_B
TRIPRES_C

OR

TRIPRES

OR

TRIPUNRE

TRIPUNRE_A
TRIPUNRE_B
TRIPUNRE_C

TRNSSENS

OR

TRIP

TRNSUNR

en05000278_ansi.vsd
ANSI05000278 V1 EN

Figure 41:

156

Transformer differential protection internal grouping of tripping signals

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

PU_A
PU_B
PU_C

OR

PICKUP

OR

BLK2H

OR

BLK5H

OR

BLKWAV

BLK2H_A
BLK2H_B
BLK2H_C
BLK5H_A
BLK5H_B
BLK5H_C
BLKWAV_A
BLKWAV_B
BLKWAV_C

en05000279_ansi.vsd
ANSI05000279 V1 EN

Figure 42:

Transformer differential protection internal grouping of logical signals

Logic in figures 39, 40, 41 and 42 can be summarized as follows:


1.

2.

3.

4.

The three fundamental frequency differential currents are applied in a phase-wise


manner to two limits. The first limit is the operate-restrain characteristic, while the
other is the high-set unrestrained limit. If the first limit is exceeded, a pickup signal
PICKUP is set. If the unrestrained limit is exceeded, an immediate unrestrained trip
TRIPUNRE and common trip TRIP are issued.
If a pickup signal is issued in a phase the harmonic and the waveform block signals
are checked. Only a pickup signal, which is free of all of its block signals can result
in a trip command. If the cross-block logic scheme is applied, then only if all phases
with set pickup signal are free of their respective block signals, a restrained trip
TRIPRES and common trip TRIP are issued
If a pickup signal is issued in a phase, and the fault has been classified as internal, then
any eventual block signals are overridden and unrestrained negative-sequence trip
TRNSUNR and common trip TRIP are issued without any further delay. This feature
is called the unrestrained negative-sequence protection 110% bias.
The sensitive negative sequence differential protection is independent of any pickup
signals. It is meant to detect smaller internal faults such as turn-to-turn faults, which
are often not detected by the traditional differential protection. The sensitive negative
sequence differential protection pickup whenever both contributions to the total
negative sequence differential current (that must be compared by the internal/
external fault discriminator) are higher than the value of the setting IMinNegSeq. If a
fault is positively recognized as internal, and the condition is stable with no
interruption for at least one fundamental frequency cycle the sensitive negative

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

157

Section 6
Differential protection

1MRK 502 066-UUS A

5.

6.

sequence differential protection TRNSSENS and common trip TRIP are issued. This
feature is called the sensitive negative sequence differential protection.
If a pickup signal is issued in a phase (see signal PU_A), even if the fault has been
classified as an external fault, then the instantaneous differential current of that phase
(see signal ID_A) is analyzed for the 2nd and the 5th harmonic contents (see the blocks
with the text inside: 2nd Harmonic; Wave block and 5th Harmonic). If there is less
harmonic pollution than allowed by the settings I2/I1Ratio, and I5/I1Ratio, (then the
outputs from the blocks 2nd harmonic and 5th harmonic is 0) then it is assumed that
a minor simultaneous internal fault must have occurred. Only under these conditions
a trip command is allowed (the signal TRIPRES_A is = 1). The cross-block logic
scheme is automatically applied under such circumstances. (This means that the cross
block signals from the other two phases B and C is not activated to obtain a trip on the
TRIPRES_A output signal in figure 39)
All pickup and blocking conditions are available as phase segregated as well as
common (that is three-phase) signals.

IDMAG_A Diff

a
a>b
b

IDiffAlarm

IDMAG_B Diff

a
a>b

&

IDiffAlarm
IDMAG_C Diff

0-tAlarmDelay
0

IDALARM

a
a>b
b

IDiffAlarm

ANSI06000546-2-en.vsd
ANSI06000546 V2 EN

Figure 43:

6.1.8

Differential current alarm logic

Technical data
Table 58:

T2WPDIF, T3WPDIF (87T) technical data

Function

Range or value

Accuracy

Operating characteristic

Adaptable

1.0% of In at I In
1.0% of I at I > In

Reset ratio

> 90%

Unrestrained differential current limit

(100-5000)% ofIBase on high voltage


winding

1.0% of set value

Table continues on next page


158

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Minimum pickup

(5-60)% of IBase

1.0% of In

Second harmonic blocking

(5.0-100.0)% of fundamental
differential current

1.0% of In
Note: Fundamental
magnitude = 100% of In

Fifth harmonic blocking

(5.0-100.0)% of fundamental
differential current

5.0% of In
Note: Fundamental
magnitude = 100% of In

Connection type for each of the


windings

Wye or delta

Phase displacement between high


voltage winding, W1 and each of the
windings, W2 and W3. Hour notation

011

Trip time at 0 to 2 x Id, restrained


function

Min. = 20 ms
Max. = 30 ms

Reset time at 2 to 0 x Id, restrained


function

Min. = 10 ms
Max. = 25 ms

Trip time at 0 to 5 x Id, unrestrained


function

Min. = 10 ms
Max. = 20 ms

Reset time at 5 to 0 x Id, unrestrained


function

Min. = 15 ms
Max. = 30 ms

Critical impulse time

2 ms typically at 0 to 5 x Id

6.2

1Ph High impedance differential protection HZPDIF


(87)

6.2.1

Identification
Function description

1Ph High impedance differential


protection

IEC 61850
identification

HZPDIF

IEC 60617
identification

Id

ANSI/IEEE C37.2
device number

87

SYMBOL-CC V2 EN

6.2.2

Functionality
The 1Ph High impedance differential protection HZPDIF (87) functions can be used when
the involved CTs have the same turns ratio and similar magnetizing characteristics. It
utilizes an external CT secondary current summation by wiring. Actually all CT

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

159

Section 6
Differential protection

1MRK 502 066-UUS A

secondary circuits which are involved in the differential scheme are connected in parallel.
External series resistor, and a voltage dependent resistor which are both mounted
externally to the IED, are also required.
The external resistor unit shall be ordered under IED accessories in the Product Guide.
HZPDIF (87) can be used to protect generator stator windings, tee-feeders or busbars,
reactors, motors, auto-transformers, capacitor banks and so on. One such function block
is used for a high-impedance restricted earth fault protection. Three such function blocks
are used to form three-phase, phase-segregated differential protection. Several function
block instances (for example, six) can be available in a single IED.

6.2.3

Function block
HZPDIF (87)
ISI*
BLOCK
BLKTR

TRIP
ALARM
MEASVOLT
ANSI05000363-2-en.vsd

ANSI05000363 V2 EN

Figure 44:

6.2.4

Signals
Table 59:
Name

HZPDIF (87) Input signals


Type

Default

Description

ISI

GROUP
SIGNAL

Single phase current input

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block of trip

Table 60:
Name

160

HZPDIF (87) function block

HZPDIF (87) Output signals


Type

Description

TRIP

BOOLEAN

Trip signal

ALARM

BOOLEAN

Alarm signal

MEASVOLT

REAL

Measured RMS voltage on CT secondary side

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

6.2.5
Table 61:
Name

Settings
HZPDIF (87) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

AlarmPickup

5 - 500

10

Alarm voltage level on CT secondary

tAlarm

0.000 - 60.000

0.001

5.000

Time delay to activate alarm

TripPickup

10 - 900

100

Pickup voltage level in volts on CT secondary


side

R series

50 - 20000

Ohm

250

Value of series resistor in Ohms

6.2.6

Monitored data
Table 62:
Name
MEASVOLT

6.2.7

HZPDIF (87) Monitored data


Type
REAL

Values (Range)
-

Unit
kV

Description
Measured RMS voltage on CT
secondary side

Operation principle
High impedance protection system is a simple technique which requires that all CTs, used
in the protection scheme, have relatively high knee point voltage, similar magnetizing
characteristic and the same ratio. These CTs are installed in all ends of the protected
object. In order to make a scheme all CT secondary circuits belonging to one phase are
connected in parallel. From the CT junction points a measuring branch is connected. The
measuring branch is a series connection of one variable setting resistor (or series resistor)
RS with high ohmic value and an over-current element. Thus, the high impedance
differential protection responds to the current flowing through the measuring branch.
However, this current is result of a differential voltage caused by this parallel CT
connection across the measuring branch. Non-linear resistor (that is, metrosil) is used in
order to protect entire scheme from high peak voltages which may appear during internal
faults. Typical high impedance differential scheme is shown in Figure 45. Note that only
one phase is shown in this figure.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

161

Section 6
Differential protection

1MRK 502 066-UUS A

RS

1
I> (50)

2
GUID-C7509DA3-F6AA-4BA0-9D08-EAA376663AFA V1 EN

Figure 45:

HZPDIF scheme

Where in the Figure:


1.
2.

shows one main CT secondary winding connected in parallel with all other CTs, from
the same phase, connected to this scheme.
shows the scheme earthing point.
It is of utmost importance to insure that only one earthing point exists
in such protection scheme.

3.
4.

shows the setting (stabilizing) resistor RS.


shows the over-current measuring element.
The series connection of stabilizing resistor and over-current element
is designated as measuring branch.

5.
6.
7.

shows the non-linear resistor (that is, metrosil).


V is the voltage across the CT paralleling point (for example, across the measuring
branch).
I is the current flowing through the measuring branch.
V and I are interrelated in accordance with the following formula
V=RS I.

162

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Due to the parallel CT connections the high impedance differential relay can only measure
one current and that is the relay operating quantity. That means that there is no any
stabilizing quantity (that is, bias) in high-impedance differential protection schemes.
Therefore in order to guaranty the stability of the differential relay during external faults
the operating quantity must not exceed the set pickup value. Thus, for external faults, even
with severe saturation of some of the current transformers, the voltage across the
measuring branch shall not rise above the relay set pickup value. To achieve that a suitable
value for setting resistor RS is selected in such a way that the saturated CT secondary
winding provides a much lower impedance path for the false differential current than the
measuring branch. In case of an external fault causing current transformer saturation, the
non-saturated current transformers drive most of the spill differential current through the
secondary winding of the saturated current transformer and not through the measuring
brunch of the relay. The voltage drop across the saturated current transformer secondary
winding appears also across the measuring brunch, however it will typically be relatively
small. Therefore, the pick-up value of the relay has to be set above this false operating
voltage.
See the application manual for operating voltage and sensitivity calculation.

6.2.7.1

Logic diagram
The logic diagram shows the operation principles for the 1Ph High impedance differential
protection function HZPDIF (87), see Figure 46.
The function utilizes the raw samples from the single phase current input connected to it.
Thus the twenty samples per fundamental power system cycle are available to the
HZPDIF function. These current samples are first multiplied with the set value for the
used stabilizing resistor in order to get voltage waveform across the measuring branch.
The voltage waveform is then filtered in order to get its RMS value. Note that used
filtering is designed in such a way that it ensures complete removal of the DC current
component which may be present in the primary fault current. The voltage RMS value is
then compared with set Alarm and Trip thresholds. Note that the TRIP signal is
intentionally delayed on drop off for 30 ms within the function. The measured RMS
voltage is available as a service value from the function. The function has block and trip
block inputs available as well.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

163

Section 6
Differential protection

1MRK 502 066-UUS A

AlarmPickup
0-tAlarm
0

AlarmPickup
0.03s
0

en05000301_ansi.vsd
ANSI05000301 V1 EN

Figure 46:

6.2.8

Logic diagram for 1Ph High impedance differential protection HZPDIF


(87)

Technical data
Table 63:

HZPDIF (87)technical data

Function

164

Range or value

Accuracy

Trip voltage

(10-900) V
I=V/R

1.0% of In at I < In
1.0% of I at I > In

Reset ratio

>95% at (30-900) V

Maximum continuous
power

V>Pickup2/SeriesResistor 200 W

Trip time at 0 to 10 x Vd

Min. = 5 ms
Max. = 15 ms

Reset time at 10 to 0 x
Vd

Min. = 75 ms
Max. = 95 ms

Critical impulse time

2 ms typically at 0 to 10 x Vd

Trip time at 0 to 2 x Vd

Min. = 25 ms
Max. = 35 ms

Reset time at 2 to 0 x
Vd

Min. = 50 ms
Max. = 70 ms

Critical impulse time

15 ms typically at 0 to 2 x Vd

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

6.3

Generator differential protection GENPDIF (87G)

6.3.1

Identification
Function description
Generator differential protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
87G

GENPDIF

Id>
SYMBOL-NN V1 EN

6.3.2

Functionality
Short circuit between the phases of the stator windings causes normally very large fault
currents. The short circuit gives risk of damages on insulation, windings and stator iron
core. The large short circuit currents cause large forces, which can cause damage even to
other components in the power plant, such as turbine and generator-turbine shaft.
To limit the damage due to stator winding short circuits, the fault clearance must be as fast
as possible (instantaneous). If the generator block is connected to the power system close
to other generating blocks, the fast fault clearance is essential to maintain the transient
stability of the non-faulted generators.
Normally, the short circuit fault current is very large, that is, significantly larger than the
generator rated current. There is a risk that a short circuit can occur between phases close
to the neutral point of the generator, thus causing a relatively small fault current. The fault
current can also be limited due to low excitation of the generator. Therefore, it is desired
that the detection of generator phase-to-phase short circuits shall be relatively sensitive,
detecting small fault currents.
It is also of great importance that the generator differential protection does not trip for
external faults, with large fault currents flowing from the generator.
To combine fast fault clearance, as well as sensitivity and selectivity, the generator
differential protection is normally the best choice for phase-to-phase generator short
circuits.
Generator differential protection GENPDIF (87G) is also well suited for protection of
shunt reactors or small busduct.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

165

Section 6
Differential protection
6.3.3

1MRK 502 066-UUS A

Function block
GENPDIF (87G)
I3PNCT1*
TRIP
I3PNCT2*
TRIPRES
I3PTCT1*
TRIPUNRE
I3PTCT2*
TRNSUNR
BLOCK
TRNSSENS
BLKRES
PICKUP
BLKUNRES
PU_A
BLKNSUNR
BFI_B
BLKNSSEN
BFI_C
DESENSIT
BLKH
OPENCT
OPENCTAL
ID_A
ID_B
ID_C
IDMAG_NS
IBIAS
ANSI11000212-1-en.vsd
ANSI11000212 V1 EN

Figure 47:

6.3.4

Signals
Table 64:
Name

166

GENPDIF (87G) function block

GENPDIF (87G) Input signals


Type

Default

Description

I3PNCT1

GROUP
SIGNAL

Neutral side input1

I3PNCT2

GROUP
SIGNAL

Neutral side input2

I3PTCT1

GROUP
SIGNAL

Terminal side input1

I3PTCT2

GROUP
SIGNAL

Terminal side input2

BLOCK

BOOLEAN

Block of function

BLKRES

BOOLEAN

Block of trip command by the restrained diff. protection

BLKUNRES

BOOLEAN

Block of trip by unrestrained "instantaneous" diff. prot.

BLKNSUNR

BOOLEAN

Block of trip for unrestrained negative sequence


differential protection

BLKNSSEN

BOOLEAN

Block of trip for sensitive negative sequence differential


protection

DESENSIT

BOOLEAN

Raise pick up: function temporarily desensitized

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Table 65:

GENPDIF (87G) Output signals

Name

6.3.5
Table 66:
Name

Type

Description

TRIP

BOOLEAN

General, common trip signal

TRIPRES

BOOLEAN

Trip signal from restrained differential protection

TRIPUNRE

BOOLEAN

Trip signal from unrestrained differential protection

TRNSUNR

BOOLEAN

Trip signal from unrestrained negative sequence


differential protection

TRNSSENS

BOOLEAN

Trip signal from sensitive negative sequence differential


protection

PICKUP

BOOLEAN

Common pickup signal from any phase

PU_A

BOOLEAN

Pickup signal from phase A

BFI_B

BOOLEAN

Pickup signal from phase B

BFI_C

BOOLEAN

Pickup signal from phase C

BLKH

BOOLEAN

Common harmonic block signal

OPENCT

BOOLEAN

An open CT was detected

OPENCTAL

BOOLEAN

Open CT Alarm output signal. Issued after a delay ...

ID_A

REAL

Instantaneous differential current A; in primary Amperes

ID_B

REAL

Instantaneous differential current B; in primary Amperes

ID_C

REAL

Instantaneous differential current C; in primary Amperes

IDMAG_NS

REAL

Negative Sequence Differential current; in primary


Amperes

IBIAS

REAL

Magnitude of the common Bias current; in primary


Amperes

Settings
GENPDIF (87G) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

IdMin

0.05 - 1.00

IB

0.01

0.25

Section 1 sensitivity, multiple of generator


rated current

IdUnre

1.00 - 50.00

IB

0.01

10.00

Unrestr. prot. limit, multiple of generator rated


current

OpNegSeqDiff

Disabled
Enabled

Enabled

Negative Sequence Differential Enable Off/On

IMinNegSeq

0.02 - 0.20

IB

0.01

0.04

Neg. sequence curr. limit, as multiple of gen.


rated curr.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

167

Section 6
Differential protection

Table 67:
Name

1MRK 502 066-UUS A

GENPDIF (87G) Group settings (advanced)


Unit

Step

Default

EndSection1

0.20 - 1.50

IB

0.01

1.25

End of section 1, multiple of generator rated


current

EndSection2

1.00 - 10.00

IB

0.01

3.00

End of section 2, multiple of generator rated


current

SlopeSection2

10.0 - 50.0

0.1

40.0

Slope in section 2 of operate-restrain


characteristic, in %

SlopeSection3

30.0 - 100.0

0.1

80.0

Slope in section 3 of operate-restrain


characteristic, in %

OpCrossBlock

Disabled
Enabled

Enabled

Operation Enable/ Disable for cross-block logic


between phases

NegSeqROA

30.0 - 120.0

Deg

0.1

60.0

Operate Angle of int/ext neg. seq. fault


discriminator, deg

HarmDistLimit

5.0 - 100.0

0.1

10.0

(Total) relative harmonic distorsion limit,


percent

TempIdMin

1.0 - 5.0

IdMin

0.1

2.0

Temp. Id pickup when input raisePickUp=1,


multiple of IdMin

AddTripDelay

0.000 - 60.000

0.001

0.100

Additional trip delay, when input


raisePickUp=1

OperDCBiasing

Disabled
Enabled

Disabled

Operation DC biasing On / Off

OpenCTEnable

Disabled
Enabled

Disabled

Enable/Disable open CT detection

tOCTAlarmDelay

0.100 - 10.000

0.001

1.000

Open CT: time to alarm if an open CT is


detected, in sec

tOCTResetDelay

0.100 - 10.000

0.001

0.250

Reset delay in s. After delay, diff. function is


activated

tOCTUnrstDelay

0.100 - 100.000

0.001

10.000

Unrestrained diff. protection blocked after this


delay, in s

Table 68:
Name

Values (Range)

Description

GENPDIF (87G) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

InvertCT2Curr

No
Yes

No

Invert CT 2 curr., yes (1) or no (0). Default is no


(0).

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

168

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

6.3.6

Monitored data
Table 69:
Name

6.3.7

GENPDIF (87G) Monitored data


Type

Values (Range)

Unit

Description

IDMAG_A

REAL

Fund. freq. differential current,


phase A; in primary A

IDMAG_B

REAL

Fund. freq. differential current,


phase B; in primary A

IDMAG_C

REAL

Fund. freq. differential current,


phase C; in primary A

IDMAG_NS

REAL

Negative Sequence
Differential current; in primary
Amperes

IBIAS

REAL

Magnitude of the common


Bias current; in primary
Amperes

Operation principle
The task of Generator differential protection GENPDIF (87G) is to determine whether a
fault is within the protected zone, or outside the protected zone. The protected zone is
delimited by the position of current transformers, as shown in figure 48.

IEC06000430-2-en.vsd

IEC06000430 V2 EN

Figure 48:

Position of current transformers; the recommended (default) orientation

If the fault is internal, the faulty generator must be quickly tripped, that is, disconnected
from the network, the field breaker tripped and the agent to the prime mover interrupted.
GENPDIF (87G) function always uses reference (default) directions of CTs towards the
protected generator as shown in figure 48. Thus, it always measures the currents on the
two sides of the generator with the same reference direction towards the generator
windings. With the orientation of CTs as in figure 48, the difference of currents flowing
in, and out, of a separate stator winding phase is simply obtained by summation of the two
currents fed to the differential protection function.
Numerical IEDs have brought a large number of advantages and new functionality to the
protective relaying. One of the benefits is the simplicity and accuracy of calculating
symmetrical components from individual phase quantities. Within the firmware of a
numerical IED, it is no more difficult to calculate negative-sequence components than it
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

169

Section 6
Differential protection

1MRK 502 066-UUS A

is to calculate zero-sequence components. Diversity of operation principles integrated in


the same protection function enhances the overall performance without a significant
increase in cost.
A novelty in GENPDIF (87G), namely the negative-sequence-current-based internalexternal fault discriminator, is used advantageously in order to determine whether a fault
is internal or external. Indeed, the internal-external fault discriminator not only positively
discriminates between internal and external faults, but can independently detect minor
faults which may not be ascertained (until they develop into more serious faults) by the
"usual" differential protection based only on operate-restrain characteristic.
GENPDIF (87G) is using fundamental frequency phase current phasors and negative
sequence current phasors. These quantities are derived outside the differential protection
function block, in the general pre-processing blocks. GENPDIF (87G) is also using with
advantage the DC component of the instantaneous differential current and the 2nd and 5th
harmonic components of the instantaneous differential currents. The instantaneous
differential currents are calculated from the input samples of the instantaneous values of
the currents measured at both ends of the stator winding. The DC and the 2nd and 5th
harmonic components of each separate instantaneous differential current are extracted
inside the differential protection.

6.3.7.1

Function calculation principles


To make a differential protection as sensitive and stable as possible, the restrained
differential characteristic is used. The protection must be provided with a proportional
bias, which makes the protection operate for a certain percentage differential current
related to the current through the generator stator winding. This stabilizes the protection
under through fault conditions while still permitting the system to have good basic
sensitivity. The following chapters explain how these quantities are calculated.
The fundamental frequency phasors of the phase currents from both sides of the generator
(the neutral side and the terminal side) are delivered to the differential protection function
by the pre-processing module of the IED.

6.3.7.2

Fundamental frequency differential currents


The fundamental frequency RMS differential current is a vectorial sum (that is, sum of
fundamental frequency phasors) of the individual phase currents from the two sides of the
protected generator. The magnitude of the fundamental frequency RMS differential
current, in phase A, is as calculated in equation 25:
Idiff _ A = [(Re( IAn + IAt )) 2 + (Im( IAn + IAt )) 2 ]
ANSIEQUATION2316 V2 EN

170

(Equation 25)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

One common fundamental frequency bias current is used. The bias current is the
magnitude of the highest measured current in the protected circuit. The bias current is not
allowed to drop instantaneously, instead, it decays exponentially with a predefined time
constant. These principles make the differential IED more secure, with less risk to operate
for external faults. The maximum principle brings as well more meaning to the
breakpoint settings of the operate-restrain characteristic.

Ibias = max( IAn, IBn, ICn, IAt , IBt , ICt )


(Equation 26)

EQUATION2049-ANSI V2 EN

IAn

IAt

Idiff

IAt

IAn
ANSI0700018_3_en.vsd
ANSI07000018 V3 EN

Figure 49:

Internal fault

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

171

Section 6
Differential protection

1MRK 502 066-UUS A

IAn

IAt

External fault: IAn = - IAt

IAt

IAn
Idiff = 0

en07000019-2_ansi.vsd

ANSI07000019 V2 EN

Figure 50:

External fault

Generator differential protection GENPDIF (87G) function uses two mutually


independent characteristics to which magnitudes of the three fundamental frequency
RMS differential currents are compared at each execution of the differential protection
function. These two characteristics divide, each of them independently, the operate
current restrain current plane into two regions: the operate (trip) region and the restrain
(block) region, as shown in figure 52. Two kinds of protection are obtained:

the non-stabilized (instantaneous unrestrained) differential protection


the stabilized differential protection

The non-stabilized (instantaneous) differential protection is used for very high differential
currents, where it must be beyond any doubt, that the fault is internal. This limit, (defined
by the setting UnrestrainedLimit), is a constant, not proportional dependent on the bias
(restrain) current. No harmonic or any other restrain is applied to this limit, which is,
therefore, called the unrestrained limit. The reset ratio of the unrestrained characteristic is
equal to 0.95.
The stabilized differential protection applies a differential (operate) current, and the
common bias (restrain) current, on the operate-restrain characteristic, as shown in
figure 52. Here, the actual limit, where the protection can operate, is dependent on the bias
(restrain) current. The operate value, is stabilized by the bias current. This operate
restrain characteristic is represented by a double-slope, double-breakpoint characteristic.
The restrained characteristic is determined by the following 5 settings:

172

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

IdMin (Sensitivity in section 1, set as multiple of generator rated current)


EndSection1 (End of section 1, set as multiple of generator rated current)
EndSection2 (End of section 2, set as multiple of generator rated current)
SlopeSection2 (Slope in section 2 of the characteristic, set in percent)
SlopeSection3 (Slope in section 3 of the characteristic, set in percent)

slope = D Ioperate 100%


D Irestrain
(Equation 27)

EQUATION1246 V1 EN

Note that both slopes are calculated from the characteristics break points.

The operate-restrain characteristic is tailor-made, in other words, it can be constructed by


the user. A default operate-restrain characteristic is suggested which gives acceptably
good results in a majority of applications. The operate-restrain characteristic has in
principle three sections with a section-wise proportional dependence of the operate value
to the common restrain (bias) current. The reset ratio is in all parts of the characteristic
equal to 0.95.
Section 1 is the most sensitive part on the characteristic. In section 1, normal currents flow
through the protected circuit and its current transformers, and risk for higher false
differential currents is low. With generators, the only cause of small false differential
currents in this section can be tolerances of the current transformers used on both sides of
the protected generator. Slope in section 1 is always zero percent. Normally, with the
protected machine at rated load, the restrain, bias current will be around 1 p.u., that is,
equal to the machine rated current.
In section 2, a certain minor slope is introduced which is supposed to cope with false
differential currents proportional to higher than normal currents through the current
transformers.
The more pronounced slope in section 3 is designed to result in a higher tolerance to
substantial current transformer saturation at high through-fault currents, which can be
expected in this section.
Temporarily decreased sensitivity of differential protection is activated if the binary input
DESENSIT is (temporarily) set to 1 (TRUE). In this case, a new, separate limit is
superposed to the otherwise unchanged operate-bias characteristic. This limit is called
TempIdMin and it is available as a setting. The value of the setting TempIdMin must be
given as a multiple of the setting IdMin. In this case no trip command can be issued if all
fundamental frequency differential currents are below the value of the setting
TempIdMin.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

173

Section 6
Differential protection

1MRK 502 066-UUS A

AddTripDelay: If the input DESENSIT is activated also the operation time of the
protection function can be increased by using the setting AddTripDelay.
operate current
[ times IBase ]

Operate

unconditionally
UnrestrainedLimit

Operate

conditionally

2
Section 1

TempIdMin
IdMin

Section 2

Section 3
SlopeSection3

1
SlopeSection2

Restrain

0
0

EndSection1
EndSection2

restrain current
[ times IBase ]

en06000637.vsd
IEC06000637 V2 EN

Figure 52:

Operate-restrain characteristic

GENPDIF (87G) can also be temporarily desensitized if the Boolean setting


OperDCBiasing is set to 1 (TRUE). In this case, the DC component is extracted on-line
from the instantaneous differential currents. The highest DC component is taken as a kind
of bias in the sense that the highest sensitivity of the differential protection is inversely
proportional to the ratio of this DC component to the maximum fundamental frequency
differential current. Similar to the desensitization described above, a separate
(temporary) additional limit is activated. The value of this limit is bounded to either the
generator rated current, or 3 times IdMin, whichever is smaller. This temporary extra limit
decays exponentially from its maximum value with a time constant equal to T = 1 second.
This feature must be used when unmatched CTs are used on the generator or shunt reactor,
especially where a long DC time constant can be expected. The new limit is superposed
on the otherwise unchanged operate-bias characteristic, and temporarily determines the
highest sensitivity of the differential protection. This temporary sensitivity must be lower
than the sensitivity in section 1 of the operate-bias characteristic.

174

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

This DC desensitization is not active, if a disturbance has been detected


and characterized as internal fault.

6.3.7.3

Supplementary criteria
To relieve the burden of constructing an exact optimal operate-restrain characteristic, two
special features supplement the basic stabilized differential protection function, making
Generator differential protection GENPDIF (87G) a very reliable one.
The supplementary criteria are:

Internal/external fault discriminator (enhances, or blocks, the trip command)


Harmonic restrain (blocks only)

The internal/external fault discriminator is a very reliable supplementary criterion. It


discriminates with a high speed between internal and external faults. The discriminator is
the main part of what is here called the negative-sequence-current-based differential
protections. It is recommended that this feature is always used (that is, enabled,
OpNegSeqDiff = On).
If a fault is classified as internal, then any eventual block signals by the harmonic criterion
are ignored, and the differential protection can operate very quickly without any further
delay.
If a fault (disturbance) is classified as external, then generally, but not unconditionally, a
trip command is prevented. If a fault is classified as external, harmonic analysis of the fault
conditions is initiated.
If all the differential currents which caused their respective pickup signals to be set, are
free of harmonic pollution, that is, if no harmonic block signal has been set, then a (minor)
internal fault, simultaneous with a predominant external fault, can be suspected. This
conclusion can be drawn because at external faults, major false differential currents can
only exist when one or more current transformers saturate transiently. In this case, the
false instantaneous differential currents are highly polluted by higher harmonic
components, the 2nd, and the 5th.
The existence of relatively high negative-sequence currents is in itself an indication of a
disturbance, as the negative-sequence currents are superimposed, pure-fault quantities.
The negative-sequence currents are measurable indications of abnormal conditions. The
negative sequence currents are particularly suitable for directional tests. The negative
sequence internal or external fault discriminator works satisfactorily even in case of threephase faults. Because of the fundamental frequency components (50/60 Hz) of the
decaying DC offset of the fault currents, the system is not fully symmetrical immediately

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

175

Section 6
Differential protection

1MRK 502 066-UUS A

after the fault. Due to the transient existence of the negative sequence system, faults can
be distinguished as internal or external, even for three-phase faults.
The internal or external fault discriminator responds to the relative phase angles of the
negative sequence fault currents at both ends of the stator winding. Observe that the source
of the negative sequence currents at unsymmetrical faults is at the fault point.

If the two negative sequence currents, as seen by the differential relay, flow in the
same direction (that is with the CTs oriented as in figure 48), the fault is internal. If
the two negative sequence currents flow in opposite directions, the fault is external.
Under external fault condition, the relative angle is theoretically equal to 180. Under
internal fault condition, the angle is ideally 0, but due to possible different negativesequence impedance angles on both sides of the internal fault, it may differ somewhat
from 0.

The setting NegSeqROA, as shown in figure 53, represents the so called Relay Operate
Angle, which determines the boundary between the internal and external fault regions. It
can be selected in the range 30 to 90, with a step of 1. The default value is 60. The
default setting, 60, favors somewhat security in comparison to dependability.
Magnitudes of both negative-sequence currents which are to be compared as to their phase
positions in the complex plane must be high enough so that one can be sure that they are
due to a fault. The limit value IMinNegSeq is settable in the range [0.02 0.20] of the
protected generator rated current. Adaptability is introduced if the bias current is higher
than 150 % rated current. Adaptability is introduced 10 ms after this limit of 150 % rated
current has been crossed so that the internal/external discriminator is given the time to
detect correctly a fault before an eventual CT saturation sets in. The threshold
IMinNegSeq is dynamically increased by 4 % of the bias current, in case of internal faults,
and by 8 % of the bias current in case of external faults. Only if magnitudes of both
currents are above the limit IMinNegSeq, the angle between the two currents is calculated.
If any of the two currents is too small, no decision is taken regarding the relative position
of the fault, and this feature then remains inactive rather than to produce a wrong decision.
The relative angle is then assigned the value of 120 (2.094 radians). If this value persists,
then this is an indication that no directional comparison has been made. Neither internal,
nor external fault (disturbance) is declared in this case.

176

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

90 deg
120 deg
NegSeqROA
(Relay Operate Angle)

Angle could not be


measured. One or both
currents too small

Internal fault
region

180 deg

0 deg

IminNegSeq

External fault
region

Internal /
external fault
boundary.
Default 60 deg

The characteristic is defined by the


settings:
IMinNegSeq and NegSeqROA
270 deg

en06000433-2.vsd
IEC06000433 V2 EN

Figure 53:

NegSeqROA determines the boundary between the internal and external


fault regions

Unrestrained negative sequence differential protection


If one or more pickup signals have been set by the restrained differential protection
algorithm, because one or more of the fundamental frequency differential currents entered
the operate region of the restrained differential protection, then the internal/external
fault discriminator can enhance the final, common, trip command by the differential
protection. If a fault is classified as internal, then any eventual block signals by the
harmonic criterion are ignored, and the differential protection operates immediately
without any further delay. This makes the overall generator differential protection very
fast. Operation of this protection is signaled on the output of GENPDIF (87G) as
TRNSUNRE.

Sensitive negative sequence differential protection


The difference from the unrestrained negative sequence differential protection, described
above, is that the sensitive one does not require any pickup signal to be set. It is enough that
both of the negative sequence currents, contributions to the total negative sequence
differential current, which should be compared, are above the setting IMinNegSeq. Thus,
this protection can be made very sensitive. Further, an intentional delay of one cycle is
added in order not to inadvertently operate for some eventual transients. Further, the
sensitive negative sequence differential protection is automatically disabled when the bias

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

177

Section 6
Differential protection

1MRK 502 066-UUS A

current exceeds 1.5 times the rated current of the protected generator. Operation of this
protection is signaled on the output of the function as TRNSENS.

6.3.7.4

Harmonic restrain
Harmonic restrain is the classical restrain method traditionally used with power
transformer differential protections. The goal there was to prevent an unwanted trip
command due to magnetizing inrush currents at switching operations, due to magnetizing
currents at over-voltages, or external faults. Harmonic restrain is just as useful with
Generator differential protection GENPDIF (87G). The harmonic analysis is only
executed in those phases, where pickup signals have been set.
There is no magnetizing inrush to a generator, but there may be some in case of shunt
reactors. The false initial differential currents of a shunt reactor have an appreciable
amount of higher harmonic currents.
At external faults dangerous false differential currents can arise for different reasons,
mainly due to saturation of one or more current transformers. The false differential
currents display in this case a considerable amount of higher harmonics, which can,
therefore, be used to prevent an unwanted trip of a healthy generator or shunt reactor.
If a fault is recognized as external by the internal/external fault discriminator, but
nevertheless one or more pickup signals have been set, the harmonic analysis is initiated
in the phases with pickup signal, as previously described. If all of the instantaneous
differential currents, where trip signals have been set, are free of higher harmonics (that
is the cross-block principle is imposed temporarily), a (minor) internal fault is assumed to
have happened simultaneously with a predominant external one. A trip command is then
allowed.

6.3.7.5

Open CT detection feature


Transformer differential protection has a built-in, advanced open CT detection feature.
A sudden inadvertently opened CT circuit may cause an unexpected and unwanted
operation of the Transformer differential protection under normal load conditions.
Damage of secondary equipment may occur due to high voltage from open CT circuit
outputs. It is always an advantage, from the point of view of security and reliability, to
have the open CT detection function to block the transformer differential protection
function in case of an open CT condition, and produce an alarm signal to the operational
personnel to quickly correct the open CT condition.
The built-in open CT feature can be enabled or disabled by the setting parameter
OpenCTEnable (Disabled/Enabled). When enabled, this feature tries to prevent maloperation when a loaded main CT connected to Transformer differential protection is by
mistake open circuited on the secondary side. Note that this feature can only detect

178

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

interruption of one CT phase current at a time. If two or even all three-phase currents of
one set of CTs are accidentally interrupted at precisely the same time, this feature cannot
operate. Transformer differential protection generates a trip signal if the false differential
current is sufficiently high. An open CT circuit is typically detected in 1214 ms, and if
the load in the protected circuit is relatively high, about the nominal load, the unwanted
trip cannot always be prevented. Still, the information about what was the cause of the
open CT secondary circuit, is vital.
The principle applied to detect an open CT is a simple pattern recognition method, similar
to the waveform check used by the Power transformer differential protection in order to
detect the magnetizing inrush condition. The open CT detection principle is based on the
fact that for an open CT, the current in the phase with the open CT suddenly drops to zero
(that is, as seen by the protection), while the currents of the other two phases continue as
before.
The open CT function is supposed to detect an open CT under normal conditions, that is,
with the protected multi-terminal circuit under normal load (10...110% of the rated load).
If the load currents are very low or zero, the open CT condition cannot be detected. In
addition to load condition requirement, Open CT function also checks the differential
current on faulty phase. If the differential current is lower than 50% of IdMin, the open CT
condition cannot be detected. Therefore, the Open CT algorithm only detects an open CT
if the load on the power transformer is 10...110% of rated load and the differential current
is higher than 50% of IdMin on that phase. The search for an open CT starts 60 seconds
(50 seconds in 60 Hz systems) after the transformer is energized. The Open CT detection
feature can also be explicitly deactivated by setting: OpenCTEnable = 0 (Disabled ).
If an open CT is detected and the output OPENCT set to 1, then all the differential
functions are blocked, except the unrestrained (instantaneous) differential. An alarm
signal is also produced after a settable delay (tOCTAlarmDelay) to report to operational
personnel for quick remedy actions once the open CT is detected. When the open CT
condition is removed (that is, the previously open CT is reconnected), the functions
remain blocked for a specified interval of time, which is also defined by a setting
(tOCTResetDelay). This is to prevent an eventual mal-operation after the reconnection of
the previously open CT secondary circuit.
The open CT algorithm provides detailed information about the location of the defective
CT secondary circuit. The algorithm clearly indicates the IED side, CT input and phase in
which an open CT condition has been detected. These indications are provided via the
following outputs from the Transformer differential protection function:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

179

Section 6
Differential protection

1.
2.
3.
4.

1MRK 502 066-UUS A

Output OPENCT provides instant information to indicate that an open CT circuit has
been detected.
Output OPENCTAL provides a time-delayed alarm that the open CT circuit has been
detected. Time delay is defined by the parameter tOCTAlarmDelay.
Integer output OPENCTIN provides information on the local HMI regarding which
open CT circuit has been detected (1=CT input No 1; 2=CT input No 2).
Integer output OPENCTPH provides information on the local HMI regarding in
which phase an open CT circuit has been detected (1=Phase A; 2= Phase B; 3= Phase
C).

Once the open CT condition is declared, the algorithm stops to search for further open CT
circuits. It waits until the first open CT circuit has been corrected. Note that once the open
CT condition has been detected, it can be reset automatically within the differential
function. It is not possible to externally reset an open CT condition. To reset the open CT
circuit alarm automatically, the following conditions must be fulfilled:

Bias current is for at least one minute smaller than 110%


The open CT condition in the defective CT circuit has been corrected (for example,
current asymmetry disappears)
The above two conditions are fulfilled for a longer time than defined by the setting
parameter tOCTResetDelay

If an open CT has been detected in a separate group of three CTs, the algorithm is reset
either when the missing current returns to the normal value, or when all three currents
become zero. After the reset, the open CT detection algorithm starts again to search for
open CT circuits within the protected zone.

6.3.7.6

Cross-block logic scheme


According to the cross-block logic, to issue a common trip command, the harmonic
contents in all phases with a pickup signal set (pickup = TRUE) must be below the limit
defined with the setting HarmDistLimit. In the opposite case, no trip command is issued.
The cross-block logic is active if the setting OpCrossBlock = Yes. By always using the
cross-block logic, the false trips can be prevented for external faults in cases where the
internal or external fault discriminator should for some reason fail to declare an external
fault. For internal faults, the higher frequency components of an instantaneous differential
current are most often relatively low, compared to the fundamental frequency component.
While for an external (heavy) fault, they can be relatively high. For external faults with
moderate fault currents, there can be little or no current transformer saturation and only
small false differential currents.
The principle design of the Generator differential protection GENPDIF (87G) is shown in
figure 54.

180

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Phasors IAN, IBN,ICN

Phasors IAT, IBT,ICT

Calculation
Idiff and Ibias

Magnitude
Idiff and Ibias

Diff.prot.
characteristic

TRIP
Signals

Pickup
phase
selective

PICKUP
Signals

BLOCK
Signals
Samples IAN, IBN,ICN

Samples IAT, IBT,ICT

Calculation
instantaneous
Idiff

Samples Idiff

Hamonic
analysis: DC,
2nd and 5th

Harm.
Block

Pickup
and trip
logic

INTFAULT
EXTFAULT
OPENCT
OPENCTAL

The sensitive protection is deactivated


above bias current > 150 % rated
current.
Phasor IAN (neg.seq.)

Phasor IAT (neg.seq.)

Calculation
negative
sequence
Idiff

Internal/
External Fault
Discriminator
and Sensitive
differential
protection

Analog
Outputs

Intern/
extern
Fault

en06000434-2_ansi.vsd
ANSI06000434 V2 EN

Figure 54:

Simplified principle design of the Generator differential protection GENPDIF (87G)

Simplified logic diagrams of the function are shown in figures 55, 56, 57 and 58.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

181

Section 6
Differential protection

1MRK 502 066-UUS A

BLKUNRES
a

IdUnre

AND

b>a

TRIPUNRE_A

IDMAG_A
IBIAS

PU_A

AND

BLOCK
BLKRES

AND
OR
ID_A

TRIPRES_A

NOT

2nd and
5th
Harmonic

BLKH

Cross Block
from B or C

AND

Cross Block
To B or C

AND

OpCrossBlock=Yes

ANSI07000020-3-en.vsd
ANSI07000020 V3 EN

Figure 55:

Generator differential logic diagram 1

Internal/
External
Fault
discrimin
ator

Neg.Seq. Diff
Current
Contributions

Constant

INTFAULT

TRNSSENS

AND

OpNegSeqDiff=On
IBIAS

EXTFAULT

b>a

BLKNSSEN
BLKNSUNR
BLOCK

AND

PU_A
PU_B
PU_C

TRNSUNR

OR

en07000021_ansi.vsd
ANSI07000021 V2 EN

Figure 56:

182

Generator differential logic diagram 2

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

PU_A
PU_B
PU_C

OR

PICKUP

OR

BLKH

BLKH_A
BLKH_B
BLKH_C

en07000022_ansi.vsd
ANSI07000022 V1 EN

Figure 57:

Generator differential logic diagram 3

TRIPRES_A
TRIPRES_B
TRIPRES_C

OR

TRIPRES

OR

TRIPUNRE

TRIPUNRE_A
TRIPUNRE_B
TRIPUNRE_C

TRIP

OR

TRNSSENS
TRNSUNR

en07000023_ansi.vsd
ANSI07000023 V1 EN

Figure 58:

6.3.8

Generator differential logic diagram 4

Technical data
Table 70:

GENPDIF (87G) technical data

Function

Range or value

Accuracy

Unrestrained differential current limit

(1-50)p.u. of IBase

1.0% of set value

Reset ratio

> 95%

Minimum pickup

(0.051.00)p.u. of

1.0% of In

Negative sequence current level

(0.020.20)p.u. of

1.0% of In

Trip time at 0 to 2 x IdMin


restrained function

Min. = 25 ms
Max. = 35 ms

Reset time at 2 to 0 x IdMin


restrained function

Min. = 10 ms
Max. = 25 ms

IBase
IBase

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

183

Section 6
Differential protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Trip time at 0 to 5 x IdUnre


unrestrained function

Min. = 5 ms
Max. = 15 ms

Reset time at 5 to 0 x IdUnre


unrestrained function

Min. = 15 ms
Max. = 30 ms

Critical impulse time, unrestrained function

2 ms typically at 0 to 5 x
IdUnre

Impulse margin time unrestrained function

10 ms typically

Trip time at 0 to 5 x IMinNegSeq


Negative sequence unrestrained function

Min. = 25 ms
Max. = 35 ms

Reset time at 5 to 0 x IMinNegSeq


Negative sequence unrestrained function

Min. = 30 ms
Max. = 45 ms

6.4

Low impedance restricted earth fault protection


REFPDIF (87N)

6.4.1

Identification
Function description
Restricted earth-fault protection, low
impedance

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
87N

REFPDIF

IdN/I
SYMBOL-AA V1 EN

6.4.2

Functionality
Restricted fault protection, low-impedance function REFPDIF (87N) can be used on all
solidly or low-impedance grounded windings. The REFPDIF (87N) function provides
high sensitivity and high speed tripping as it protects each winding separately and thus
does not need inrush stabilization.
The REFPDIF function is a percentage biased function with an additional zero sequence
current directional comparison criterion. This gives excellent sensitivity and stability
during through faults.
REFPDIF can also protect autotransformers. Five currents are measured at the most
complicated configuration as shown in Figure 59.

184

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

152

252

352

452

xx05000058_ansi.vsd
ANSI05000058 V1 EN

Figure 59:

6.4.3

Examples of applications of the REFPDIF (87N)

Function block
REFPDIF (87N)
I3P*
TRIP
I3PW1CT1*
PICKUP
I3PW1CT2*
DIR_INT
I3PW2CT1*
BLK2H
I3PW2CT2*
IRES
BLOCK
IN
IBIAS
IDIFF
ANGLE
2NDHARM
ANSI14000059-1-en.vsd
ANSI06000251 V3 EN

Figure 60:

6.4.4

REFPDIF (87N) function block

Signals
Table 71:
Name

REFPDIF (87N) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for ground current input

I3PW1CT1

GROUP
SIGNAL

Group signal for primary CT1 current input

I3PW1CT2

GROUP
SIGNAL

Group signal for primary CT2 current input

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

185

Section 6
Differential protection

1MRK 502 066-UUS A

Name

Type

Group signal for secondary CT1 current input

I3PW2CT2

GROUP
SIGNAL

Group signal for secondary CT2 current input

BLOCK

BOOLEAN

Block of function

REFPDIF (87N) Output signals

Name

Table 73:
Name

Description

GROUP
SIGNAL

Table 72:

6.4.5

Default

I3PW2CT1

Type

Description

TRIP

BOOLEAN

Trip by restricted earth fault protection function

PICKUP

BOOLEAN

Pickup by restricted earth fault protection function

DIR_INT

BOOLEAN

Directional Criteria satisfied for internal fault

BLK2H

BOOLEAN

Block due to 2-nd harmonic

IRES

REAL

Magnitude of fundamental frequency residual current

IN

REAL

Magnitude of fundamental frequency ground current

IBIAS

REAL

Magnitude of the bias current

IDIFF

REAL

Magnitude of fundamental frequency differential current

ANGLE

REAL

Direction angle from zero sequence feature

2NDHARM

REAL

Second harmonic ratio

Settings
REFPDIF (87N) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

IdMin

4.0 - 100.0

%IB

0.1

10.0

Maximum sensitivity in % of IBase

CTFactorPri1

1.0 - 10.0

0.1

1.0

CT factor for HV side CT1 (CT1rated/ HVrated


current)

CTFactorPri2

1.0 - 10.0

0.1

1.0

CT factor for HV side CT2 (CT2rated/ HVrated


current)

CTFactorSec1

1.0 - 10.0

0.1

1.0

CT factor for MV side CT1 (CT1rated/ MVrated


current)

CTFactorSec2

1.0 - 10.0

0.1

1.0

CT factor for MV side CT2 (CT2rated/ MVrated


current)

Table 74:
Name
ROA

186

REFPDIF (87N) Group settings (advanced)


Values (Range)
60 - 90

Unit
Deg

Step
1

Default
60

Description
Relay operate angle for zero sequence
directional feature

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Table 75:
Name
GlobalBaseSel

6.4.6

REFPDIF (87N) Non group settings (basic)


Values (Range)
1 - 12

Unit

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 76:
Name

REFPDIF (87N) Monitored data


Type

Values (Range)

Unit

Description

IRES

REAL

Magnitude of fundamental
frequency residual current

IN

REAL

Magnitude of fundamental
frequency ground current

IBIAS

REAL

Magnitude of the bias current

IDIFF

REAL

Magnitude of fundamental
frequency differential current

ANGLE

REAL

deg

Direction angle from zero


sequence feature

2NDHARM

REAL

Second harmonic ratio

6.4.7

Operation principle

6.4.7.1

Fundamental principles of the restricted ground fault protection


Restricted fault protection, low impedance function (REFPDIF, 87N) detects ground
faults on grounded power transformer windings, most often an grounded wye winding.
REFPDIF (87N) is a unit protection of the differential type. Since REFPDIF (87N) is
based on the zero sequence current, which theoretically only exists in case of a ground
fault, REFPDIF (87N) can be made very sensitive regardless of normal load currents. It is
the fastest protection a power transformer winding can have. The high sensitivity and the
high speed tend to make such a protection unstable. Special measures must be taken to
make it insensitive to conditions for which it should not operate, for example, heavy
through faults of phase-to-phase type or heavy external ground faults.
REFPDIF (87N) is a differential protection of the low impedance type. All three-phase
currents, and the neutral point current, must be fed separately to REFPDIF(87N). The
fundamental frequency components of all currents are extracted from all input currents,
while other eventual zero sequence components, such as the 3rd harmonic currents, are
fully suppressed. Then the residual current phasor is calculated from the three line current
phasors. This zero sequence current phasor is added to the neutral current vectorially, in
order to obtain differential current.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

187

Section 6
Differential protection

1MRK 502 066-UUS A

The following facts may be observed from Figure 61 and Figure 62, where the three line
CTs are shown as connected together in order to measure the residual 3Io current, for the
sake of simplicity.

ROA (Relay Operate Angle)


ROA = 60 deg
IN

REFPDIF never operates for any faults


external to the protected zone.
Currents 3Io and IN are theoretically
180o out of phase for any external
ground-fault.

ANSI05000724 V3 EN

Figure 61:

188

Zero sequence currents at an external ground fault

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

Uzs

Uzs

IN

ANSI05000725 V3 EN

Figure 62:

1.

2.

Zero sequence currents at an internal ground fault

For an external ground fault (Figure 61), the residual current 3Io and the neutral
current IN have equal magnitude, but they are seen within the IED as 180 degrees outof-phase if the current transformers are connected as in Figure 61, which is the ABB
recommended connection. The differential current becomes zero as both CTs ideally
measure exactly the same component of the ground fault current.
For an internal fault, the total ground fault current is composed generally of two zero
sequence currents. One zero sequence current (3IZS1) flows towards the power
transformer neutral point and into the ground, while the other zero sequence current
(3IZS2) flows into the connected power system. These two primary currents can be
expected to have approximately opposite directions (about the same zero sequence
impedance angle is assumed on both sides of the ground fault). However, on the
secondary CT sides of the current transformers, they will be approximately in phase
if the current transformers are oriented as in Figure 59, which is the orientation
recommended by ABB. The magnitudes of the two currents may be different,
dependent on the magnitudes of zero sequence impedances of both sides. No current
can flow towards the power system, if the only point where the system is grounded,
is at the protected power transformer. Likewise, no current can flow into the power

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

189

Section 6
Differential protection

1MRK 502 066-UUS A

3.

4.

system, if the winding is not connected to the power system (circuit breaker open and
power transformer energized from the other side).
For both internal and external ground faults, the current in the neutral connection IN
always has the same direction, which is towards the ground (except in case of
autotransformers where the direction can vary).
The two internally processed zero sequence currents are 3Io and IN. The vectorial sum
is the REFPDIF (87N) differential current, which is equal to Idiff = IN +3Io .

The line zero sequence (residual) current is calculated from 3 line (terminal) currents. A
bias quantity must give stability against false operations due to high through fault currents.
To stabilize REFPDIF at external faults, a fixed bias characteristic is implemented.
REFPDIF (87N) should also be stable against heavy phase-to-phase internal faults, not
including ground. These faults may also give false zero sequence currents due to saturated
line CTs. Such faults, however are without neutral current, and can thus be eliminated as
a source of danger.
As an additional measure against unwanted operation, a directional check is made in
agreement with the above points 1 and 2. Operation is only allowed if the currents 3Io and
IN (as shown in Figure 61 and Figure 62) are both within the operating region. By taking
a smaller ROA, REFPDIF (87N) can be made more stable under heavy external fault
conditions, as well as under the complex conditions, when external faults are cleared by
other protections.

6.4.7.2

Restricted ground fault protection, low impedance differential protection


Restricted earth-fault protection, low impedance (REFPDIF, 87N) is a protection of
differential type, a unit protection, whose settings are independent of any other protection.
It has some advantages compared to the transformer differential protection. It is less
complicated, as no current phase correction or magnitude correction are needed, not even
in the case of an eventual on-load tap changer (OLTC). REFPDIF (87N) is not sensitive
to inrush and overexcitation currents. The only danger is an eventual current transformer
saturation.
REFPDIF (87N) has only one operate-bias characteristic, which is described in the table
77 and shown in Figure 63.
Table 77:

Data of the operate-bias characteristic of REFPDIF(87N)

Default sensitivity Idmin Max. base


(zone 1)
sensitivity Idmin
(zone 1)
% IBase
% IBase
30

190

Min. base sensitivity End of zone First slope


Idmin (zone 1)
1

Second
slope

% IBase

100

% IBase
125

%
70

100

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

The differential protection REFPDIF (87N) calculates a differential current and a bias
current. In case of internal ground faults, the differential current is theoretically equal to
the total ground fault current. The bias current is supposed to give stability to
REFPDIF(87N). The bias current is a measure of how high the currents are and how
difficult the conditions are under which the CTs operate. With a high bias, difficult
conditions can be suspected, and it will be more likely that the calculated differential
current has a component of a false current, primarily due to CT saturation. This law is
formulated by the operate-bias characteristic. This characteristic divides the Idiff - Ibias
plane in two areas. The area above the operate-bias characteristic is the operate area, while
the one below is the block area, see Figure 63.
Figure 63:

6.4.7.3

Operate - bias characteristic of the Restricted earth-fault protection, low


impedance REFPDIF (87N)

Calculation of differential current and bias current


The differential current (operate current), as a fundamental frequency phasor, is
calculated as (with designations as in Figure 61 and Figure 62):

Idiff = IN + 3 Io
EQUATION1533 V1 EN

(Equation 29)

where:
IN is current in the power transformer neutral as a fundamental frequency phasor.
3Io is residual current of the power transformer terminal currents as a phasor.
If there are two three-phase CT inputs, as in breaker-and-a-half configurations, see figure
10, then their respective residual currents are added within the REFPDIF (87N) function
so that:
I3PW1 = I3PW1CT1 + I3PW1CT2
where the signals are defined in the input and output signal tables for REFPDIF (87N).
The bias current is a measure (expressed internally as a true fundamental frequency
current in Amperes) of how difficult the conditions are under which the instrument current
transformers operate. Dependent on the magnitude of the bias current, the corresponding
zone (section) of the operate-bias characteristic is applied, when deciding whether to trip,
or not to trip. In general, the higher the bias current, the higher the differential current
required to produce a trip.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

191

Section 6
Differential protection

1MRK 502 066-UUS A

The bias current is the highest current of all separate input currents to REFPDIF (87N),
that is, of current in phase A, phase B, phase C, and the current in the neutral point
(designated as IN in Figure 61 and in Figure 62).
If there are two feeders included in the zone of protection of REFPDIF (87N), as in case
of an auto-transformer with two feeders included on both sides, then the respective bias
current is found as the relatively highest of the following currents:
current[1] = max (I3PW1CT1)

1
CTFactorPri1
(Equation 30)

EQUATION1526 V1 EN

current[2] = max (I3PW1CT2)

1
CTFactorPri2
(Equation 31)

EQUATION1527 V1 EN

current[3] = max (I3PW2CT1)

1
CTFactorSec1
(Equation 32)

EQUATION1528 V1 EN

current[4] = max (I3PW2CT2)

1
CTFactorSec2
(Equation 33)

EQUATION1529 V1 EN

current[5] = IN
(Equation 34)

EQUATION1530 V1 EN

The bias current is thus generally equal to none of the input currents. If all primary ratings
of the CTs were equal to IBase, then the bias current would be equal to the highest current
in Amperes. IBase shall be set equal to the rated current of the protected winding where
REFPDIF (87N) function is applied.

6.4.7.4

Detection of external ground faults


External faults are more common than internal ground faults for which the restricted
ground fault protection should operate. It is important that the restrictedground fault
protection remains stable during heavy external ground and phase-to-phase faults, and
also when such a heavy external fault is cleared by some other protection such as
overcurrent, or ground fault protection. The conditions during a heavy external fault, and
particularly immediately after the clearing of such a fault may be complex. The circuit
breakers poles may not open exactly at the same moment, some of the CTs may still be
highly saturated, and so on.

192

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

The detection of external ground faults is based on the fact that for such a fault a high
neutral current appears first, while a false differential current only appears if one or more
current transformers saturate.
An external fault is thus assumed to have occurred when a high neutral current suddenly
appears, while at the same time the differential current Idiff remains low, at least for a
while. This condition must be detected before a trip request is placed within REFPDIF.
Any search for external fault is aborted if a trip request has been placed. A condition for
a successful detection is that it takes not less than 4ms for the first CT to saturate.
For an internal fault, a true differential current develops immediately, while for an external
fault it only develops if a CT saturates. If a trip request comes first, before an external fault
could be positively detected, then it must be an internal fault.
If an external fault has been detected, then the REFPDIF is temporarily desensitized.

Directional criterion
The directional criterion is applied in order to positively distinguish between internal and
external ground faults. This check is an additional criterion, which should prevent
malfunctions at heavy external ground faults, and during the disconnection of such faults
by other protections. Ground faults on lines connecting the power transformer occur much
more often than ground faults on a power transformer winding. It is important therefore
that the Restricted ground fault protection, low impedance (REFPDIF87N) must remain
stable during an external fault, and immediately after the fault has been cleared by some
other protection.
For an external ground faults with no CT saturation, the residual current in the lines (3Io)
and the neutral current (IN in Figure 61) are theoretically equal in magnitude and are 180
degrees out-of-phase. The current in the neutral (IN) serves as a directional reference
because it has the same direction for both internal and external ground faults. The
directional criterion in REFPDIF (87N) protection makes it a current-polarized
protection.
However, if one or more CTs saturate under external fault conditions, then the measured
currents 3Io and IN may no longer be equal, nor will their positions in the complex plane
be exactly 180 degrees apart. There is a risk that the resulting false differential current Idiff
enters the operate area of the operate-restrain characteristic under external fault
conditions. If this happens, a directional test may prevent a malfunction.
A directional check is only executed if:
1.
2.

a trip request signal has been issued (REFPDIF (87N) function PICKUP signal set to
1)
the residual current in lines (3Io) is at least 3% of the IBase current.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

193

Section 6
Differential protection

1MRK 502 066-UUS A

If a directional check is either unreliable or not possible to do, due to too small currents,
then the direction is cancelled as a condition for an eventual trip.
If a directional check is executed, the REFPDIF (87N) protection operation is only
allowed if currents 3Io and IN (as seen in Figure 61 and Figure 62) are both within the
operating region determined by the set value of ROA, in degrees.
ROA = 60 to 90 degrees; where ROA stands for Relay Operate Angle.

Second harmonic analysis


When energizing a transformer a false differential current may appear in ground fault
protection, low impedance function (REFPDIF 87N). The phase CTs may saturate due to
a high DC component with a long duration, but the current through the neutral CT does not
have either the same DC component or the same magnitude and the risk for saturation of
this CT is not as high. As a result the differential current due to the saturation may be so
high that it reaches the operate characteristic. A calculation of the content of 2nd harmonic
in the neutral current is made when the neutral current, residual current and bias current
are within some windows and some timing criteria are fulfilled. If the ratio between
second and fundamental harmonic exceeds 40%, REFPDIF (87N) is blocked.

6.4.7.5

Algorithm of the restricted ground fault protection


1.
2.
3.
4.
5.

6.
7.

194

Check if current in the neutral Ineutral (IN) is less than 50% of the base sensitivity
Idmin. If yes, only service values are calculated, then REFPDIF (87N) algorithm is
not used.
If current in the Ineutral (IN) is more than 50% of Idmin, then determine the bias
current Ibias.
Determine the differential (operate) current Idiff as a phasor, and calculate its
magnitude.
Check if the point P(Ibias, Idiff) is above the operate-bias characteristic. If yes,
increment the trip request counter by 1. If the point P(Ibias, Idiff) is found to be below
the operate-bias characteristic, then the trip request counter is reset to zero.
If the trip request counter is still zero, search for an eventual heavy external ground
fault. The search is only made if the neutral current is at least 50% of the Idmin
current. If an external ground fault has been detected, a flag is set which remains set
until the external fault has been cleared. The external fault flag is reset to zero when
Ineutral falls below 50% of the base sensitivity Idmin. Any search for an external fault
is aborted if trip request counter is more than zero.
As long as the external fault persists, an additional temporary trip condition is
introduced. This means that REFPDIF (87N) is temporarily desensitized.
If point P(Ibias, Idiff) is found to be above the operate-bias characteristic), so that trip
request counter is more than zero, a directional check can be made. The directional
check is made only if Iresidual (3Io) is more than 3% of the IBase current. If the result

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 6
Differential protection

1MRK 502 066-UUS A

8.

9.

6.4.8

of the check means external fault, then the internal trip request is reset. If the
directional check cannot be executed, then direction is no longer a condition for a trip.
When neutral current, residual current and bias current are within some windows and
some timing criteria are fulfilled, the ratio of 2nd to fundamental harmonic is
calculated. If it is found to be above 60% the trip request counter is reset and TRIP
remains zero.
Finally, a check is made if the trip request counter is equal to, or higher than 2. If yes,
and at the same instance of time tREFtrip, the actual bias current at this instance of time
tREFtrip is at least 50% of the highest bias current Ibiasmax (Ibiasmax is the highest
recording of any of the three phase currents measured during the disturbance), then
REFPDIF (87N) sets output TRIP to 1. If the counter is less than 2, the TRIP signal
remains zero.

Technical data
Table 78:

REFPDIF (87N) technical data

Function

Range or value

Accuracy

Trip characteristic

Adaptable

1.0% of In at I In
1.0% of I at I > In

Reset ratio

>95%

Minimum pickup, IdMin

(4.0-100.0)% of IBase

1.0% of In

Directional characteristic

Fixed 180 degrees or 60 to 90


degrees

2.0 degrees

Trip time, trip at 0 to 10 x IdMin

Min. = 15 ms
Max. = 30 ms

Reset time, trip at 10 to 0 x IdMin

Min. = 15 ms
Max. = 30 ms

Second harmonic blocking

60.0% of fundamental (hidden


setting)

1.0% of In

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

195

196

Section 7
Impedance protection

1MRK 502 066-UUS A

Section 7

Impedance protection

7.1

Full-scheme distance measuring, Mho characteristic


ZMHPDIS (21)

7.1.1

Identification
Function description

Full-scheme distance protection, mho


characteristic

IEC 61850
identification

IEC 60617 identification

ZMHPDIS

ANSI/IEEE
C37.2 device
number
21

S00346 V1 EN

7.1.2

Functionality
The numerical mho line distance protection is a, up to four zone full scheme protection for
detection of short circuit and earth faults. The numerical mho line distance protection is a
four zone full scheme protection for detection of short circuit and earth faults.
The full scheme technique provides back-up protection of power lines with high
sensitivity and low requirement on remote end communication.
The four zones have fully independent measuring and settings, which gives high
flexibility for all types of lines.
Built-in selectable zone timer logic is also provided in the function.
The function can be used as under impedance back-up protection for transformers and
generators.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

197

Section 7
Impedance protection
7.1.3

1MRK 502 066-UUS A

Function block
ZMHPDIS (21)
I3P*
TRIP
V3P*
TR_A
CURR_INP*
TR_B
VOLT_INP*
TR_C
POL_VOLT*
TRPG
BLOCK
TRPP
BLKZ
PICKUP
BLKZMTD
PU_A
BLKHSIR
PU_B
BLKTRIP
PU_C
BLKPG
PHG_FLT
BLKPP
PHPH_FLT
EXTNST
PU_TIMER
INTRNST
DIRCND
PHSEL*
LDCND
ANSI06000423-2-en.vsd
ANSI06000423 V2 EN

Figure 64:

7.1.4

ZMHPDIS (21) function block

Signals
Table 79:
Name

ZMHPDIS (21) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Connection for current sample signals

V3P

GROUP
SIGNAL

Connection for voltage sample signals

CURR_INP

GROUP
SIGNAL

Connection for current signals

VOLT_INP

GROUP
SIGNAL

Connection for voltage signals

POL_VOLT

GROUP
SIGNAL

Connection for polarizing voltage

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Block due to fuse failure

BLKZMTD

BOOLEAN

Block signal for blocking of time domaine function

BLKHSIR

BOOLEAN

Blocks time domain function at high SIR

BLKTRIP

BOOLEAN

Blocks all operate output signals

BLKPG

BOOLEAN

Blocks phase-to-ground operation

BLKPP

BOOLEAN

Blocks phase-to-phase operation

EXTNST

BOOLEAN

External start

INTRNST

BOOLEAN

Internal start

Table continues on next page

198

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Type

External directional condition

PHSEL

INTEGER

Faulted phase loop selection enable from phase


selector

LDCND

INTEGER

External load condition (loop enabler)

ZMHPDIS (21) Output signals

Name

Table 81:
Name

Description

INTEGER

Table 80:

7.1.5

Default

DIRCND

Type

Description

TRIP

BOOLEAN

Trip General

TR_A

BOOLEAN

Trip phase A

TR_B

BOOLEAN

Trip phase B

TR_C

BOOLEAN

Trip phase C

TRPG

BOOLEAN

Trip phase-to-ground

TRPP

BOOLEAN

Trip phase-to-phase

PICKUP

BOOLEAN

Pickup General

PU_A

BOOLEAN

Pickup phase A

PU_B

BOOLEAN

Pickup phase B

PU_C

BOOLEAN

Pickup phase C

PHG_FLT

BOOLEAN

Pickup phase-to-ground

PHPH_FLT

BOOLEAN

Pickup phase-to-phase

PU_TIMER

BOOLEAN

Pick up timer

Settings
ZMHPDIS (21) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

DirMode

Disabled
Offset
Forward
Reverse

Forward

Direction mode

LoadEncMode

Disabled
Enabled

Disabled

Load encroachment mode Off/On

ReachMode

Overreach
Underreach

Overreach

Reach mode Over/Underreach

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

199

Section 7
Impedance protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

ZnTimerSel

Timers seperated
Timers linked
Internal start
Start from PhSel
External start

Timers seperated

Zone timer selection

OpModePG

Disabled
Enabled

Enabled

Operation mode Disable/Enable of PhaseGround loops

ZPG

0.005 - 3000.000

Ohm/p

0.001

30.000

Positive sequence impedance setting for


Phase-Ground loop

ZAngPG

10 - 90

Deg

85

Angle for positive sequence line impedance for


Phase-Ground loop

KN

0.00 - 3.00

0.01

0.80

Magnitude of earth return compensation factor


KN

KNAng

-180 - 180

Deg

-15

Angle for ground return compensation factor


KN

ZRevPG

0.005 - 3000.000

Ohm/p

0.001

30.000

Reverse reach of the phase to ground


loop(magnitude)

tPG

0.000 - 60.000

0.001

0.000

Delay time for operation of phase to ground


elements

IMinPUPG

10 - 30

%IB

20

Minimum operation phase to ground current

OpModePP

Disabled
Enabled

Enabled

Operation mode Disable/Enable of PhasePhase loops

ZPP

0.005 - 3000.000

Ohm/p

0.001

30.000

Impedance setting reach for phase to phase


elements

ZAngPP

10 - 90

Deg

85

Angle for positive sequence line impedance for


Phase-Phase elements

ZRevPP

0.005 - 3000.000

Ohm/p

0.001

30.000

Reverse reach of the phase to phase


loop(magnitude)

tPP

0.000 - 60.000

0.001

0.000

Delay time for operation of phase to phase

IMinPUPP

10 - 30

%IB

20

Minimum operation phase to phase current

Table 82:
Name

ZMHPDIS (21) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

OffsetMhoDir

Non-directional
Forward
Reverse

Non-directional

Direction mode for offset mho

OpModetPG

Disabled
Enabled

Enabled

Operation mode Disable/ Enable of Zone timer,


Ph-G

OpModetPP

Disabled
Enabled

Enabled

Operation mode Off / On of Zone timer, Ph-ph

200

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 83:
Name
GlobalBaseSel

ZMHPDIS (21) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step

Default

7.1.6

Operation principle

7.1.6.1

Full scheme measurement

Description
Selection of one of the Global Base Value
groups

The execution of the different fault loops within the IED are of full scheme type, which
means that each fault loop for phase-to-ground faults and phase-to-phase faults are
executed in parallel for all zones.
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a phase selector element to select correct voltages and current
depending on fault type. So each distance protection zone performs like one independent
distance protection function with six measuring elements.

7.1.6.2

Impedance characteristic
The Mho distance function ZMHPDIS is present with four instances so that four separate
zones could be designed. Each instance can be selected to be either forward or reverse with
positive sequence polarized mho characteristic; alternatively self polarized offset mho
characteristics is also available. One example of the operating characteristic is shown in
Figure 65 A) where zone 5 is selected offset mho.
The directional mho characteristic of Figure 65 has a dynamic expansion due to the source
impedance. Instead of crossing the origin as for the mho to the left of Figure 65, which is
only valid where the source impedance is zero, the crossing point is moved to the
coordinates of the negative source impedance giving an expansion of the circle of Figure
65 D) .

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

201

Section 7
Impedance protection

1MRK 502 066-UUS A

D
jx

Mho, zone4
Zs=0

Mho, zone3
Mho, zone2

Mho, zone1
Zs=Z1
Zs=2Z1
R

IEC11000223-2-en.vsd
IEC11000223 V2 EN

Figure 65:

Mho characteristic and the source impedance influence on the mho characteristic

The polarization quantities used for the mho circle are 100% memorized positive
sequence voltages. This will give a somewhat less dynamic expansion of the mho circle
during faults than a plain cross polarized characteristic. However, if the source impedance
is high, the dynamic expansion of the mho circle might lower the security of the function
too much with high loading and mild power swing conditions.
The mho distance element has a load encroachment function which cuts off a section of
the characteristic when enabled. The function is enabled by setting the setting parameter
LoadEnchMode to Enabled. Enabling of the load encroachment function increases the
possibility to detect high resistive faults without interfering with the load impedance. The
algorithm for the load encroachment is located in the Faulty phase identification with load
encroachment for mho function FMPSPDIS (21), where also the relevant settings can be
found. Information about the load encroachment from FMPSPDIS (21) to the zone
measurement is given in binary format to the input signal LDCND.

7.1.6.3

Basic operation characteristics


Each impedance zone can be switched OnEnabled and OffDisabled by the setting
parameter Operation.

202

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Each zone can be set to Non-directional, Forward or Reverse by setting the parameter
DirModeSel.
The mho characteristics can be classified into - Offset or Directional. The directional mho
characteristics can be set to Offset, Forward or Reverse by the setting parameter
DirMode. The offset mho characteristic can be set to Forward or Reverse or NonDirectional by the setting parameter OffsetMhoDir.
The operation for phase-to-ground and phase-to-phase fault can be individually switched
Enabled and Disabled by the setting parameter OpModePG and OpModePP.
For critical applications such as for lines with high SIRs as well as CVTs, it is possible to
improve the security by setting the parameter ReachMode to Underreach. In this mode the
reach for faults close to the zone reach is reduced by 20% and the filtering is also
introduced to increase the accuracy in the measuring. If the ReachMode is set to
Overreach no reduction of the reach is introduced and no extra filtering introduced. The
latter setting is recommended for overreaching pilot zone, zone 2 or zone 3 elements and
reverse zone where overreaching on transients is not a major issue either because of less
likelihood of overreach with higher settings or the fact that these elements do not initiate
tripping unconditionally.
The offset Mho characteristic can be set in Non-directional, Forward or Reverse by the
setting parameter OffsetMhoDir. When Forward or Reverse is selected a directional line
is introduced. Information about the directional line is given from the directional element
and given to the measuring element as binary coded signal to the input DIRCND.
When DirMode is set to offset and offsetMhoDir is set as Non-Directional, ZDMRDIR
does not have any effect on the measurement loop and operation of the function. When
DirMode is selected as Forward or Reverse, a directional line is introduced. Information
about the directional line is given from the directional element (ZDMRDIR) and given to
the measuring element as binary coded signal to the input DIRCND.
The zone reach for phase-to-ground fault and phase-to-phase fault is set individually in
polar coordinates.
The impedance is set by the parameters ZPG and ZPP and the corresponding angles by the
parameters ZAngPG and ZAngPP.
Compensation for ground-return path for faults involving ground is done by setting the
parameter KN and KNAng where KN is the magnitude of the ground-return path and
KNAng is the angle of the ground-return path.

KN =

Z 0 - Z1
3 Z1

IECEQUATION14023 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

(Equation 35)

203

Section 7
Impedance protection

1MRK 502 066-UUS A

KNAng = ang

Z 0 - Z1
3 Z1

)
(Equation 36)

EQUATION1807-ANSI V1 EN

where
Z0

is the complex zero sequence impedance of the line in /phase

Z1

is the complex positive sequence impedance of the line in /phase

The phase-to-ground and phase-to-phase measuring loops can be time delayed


individually by setting the parameter tPG and tPP respectively. To release the time delay,
the operation mode for the timers, OpModetPG and OpModetPP, has to be set to On. This
is also the case for instantaneous operation. In instantaneous case, the timers tPG and tPP
need to be set as zero.
The operate timers triggering input depends on the parameter ZnTimerSel setting. The
parameter ZnTimerSel can be set to:

Timers separated: Phase-to-ground and phase-to-phase timers are triggered by the


respective measuring loop pickup signals.
Timers linked: Start of any of the phase-to-ground or phase-to-phase loops will
trigger both the phase-to-ground or phase-to-phase timers.
Internal start: Phase-to-ground and phase-to-phase timers are triggered by the
INTRNST input.
Start from PhSel: The phase-to-ground and phase-to-phase timers are triggered by the
STCND and LDCND inputs. Each of the two inputs consist binary status information
related to the six measuring loops. Hence if any of the measuring loop status is high
in both two inputs STCND and LDCND, then the timers will be triggered. In case when
LoadEnchMode is off then only STCND enables the timer.
It is not recommended to use this timer setting for the Zone instance
where LoadEnchMode is off.

External start: Phase-to-ground and phase-to-phase timers are triggered by the


EXTNST input.

The function can be blocked in the following ways:

204

activating of input BLOCK blocks the whole function


activating of the input BLKZ (fuse failure) blocks all output signals
activating of the input BLKZMTD blocks the delta based time domain algorithm
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

activating of the input BLKHSIR blocks the high speed part of the algorithm for high
SIR values
activating of the input BLKTRIP blocks all output signals
activating the input BLKPG blocks the phase-to-ground fault loop outputs
activating the input BLKPP blocks the phase-to-phase fault loop outputs

The activation of input signal BLKZ can be made by external fuse failure function or from
the loss of voltage check in the Mho supervision logic (ZSMGAPC). In both cases the
output BLKZ in the Mho supervision logic shall be connected to the input BLKZ in the
Mho distance function block (ZMHPDIS, 21)
The input signal BLKZMTD is activated during some ms after fault has been detected by
ZSMGAPC to avoid unwanted operations due to transients. It shall be connected to the
BLKZMTD output signal of ZSMGAPC function.
At SIR values >10, the use of electronic CVT might cause overreach due to the built-in
resonance circuit in the CVT, which reduce the secondary voltage for a while. The input
BLKHSIR is connected to the output signal HSIR on ZSMGAPC for increasing of the
filtering and high SIR values. This is valid only when permissive underreach scheme is
selected by setting ReachMode=Underreach.

7.1.6.4

Theory of operation
The mho algorithm is based on the phase comparison of an operating phasor and a
polarizing phasor. When the operating phasor leads the reference polarizing phasor by 90
degrees or more, the function operates and gives a trip output.

Phase-to-phase fault
Mho
The plain Mho circle has the characteristic as in Figure 66. The condition for deriving the
angle is according to equation 37.

b = ang (V AB - I AB ZPP ) - ang (V pol )


EQUATION1789-ANSI V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

(Equation 37)

205

Section 7
Impedance protection

1MRK 502 066-UUS A

where

V AB

is the voltage vector difference between phases A and B

EQUATION1790-ANSI
V1 EN

I AB

is the current vector difference between phases A and B

EQUATION1791-ANSI
V1 EN

ZPP

is the positive sequence impedance setting for phase-to-phase fault

Vpol

is the polarizing voltage

The polarized voltage consists of 100% memorized positive sequence voltage (VAB for
phase A to B fault). The memorized voltage will prevent collapse of the Mho circle for
close in faults.
Operation occurs if 90270
IABX

Vcomp=VAB - IAB ZPP

I AB ZPP

V pol
V AB

IABR

en07000109_ansi.vsd
ANSI07000109 V1 EN

Figure 66:

206

Simplified mho characteristic and vector diagram for phase A-to-B fault

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Offset Mho
The characteristic for offset mho is a circle where two points on the circle are the setting
parameters ZPP and ZRevPP. The vector ZPP in the impedance plane has the settable
angle AngZPP and the angle for ZRevPP is AngZPP+180.
The condition for operation at phase-to-phase fault is that the angle between the two
compensated voltages Vcomp1 and Vcomp2 is greater than or equal to 90 (figure 67).
The angle will be 90 for fault location on the boundary of the circle.
The angle for A-to-B fault can be defined according to equation 38.

V -(-IAB ZRevPP)

b = arg

V -IAB ZPP

(Equation 38)

EQUATION1792-ANSI V1 EN

where

is the VAB voltage

EQUATION1801 V1 EN

ZRevPP

is the positive sequence impedance setting for phase-to-phase fault in reverse direction

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

207

Section 7
Impedance protection

1MRK 502 066-UUS A

IABjX

V comp1 = VAB - IAB ZPP

I AB ZPP

Vcomp2 = V =IFZF =VAB


IABR

- I AB

Z Re vPP
en07000110_ansi.vsd

ANSI07000110 V1 EN

Figure 67:

Simplified offset mho characteristic and voltage vectors for phase A-to-B
fault.

Operation occurs if 90270.


Offset mho, forward direction
When forward direction has been selected for the offset mho, an extra criteria beside the
one for offset mho (90<<270) is introduced, that is the angle between the voltage and
the current must lie between the blinders in second quadrant and fourth quadrant. See
figure 68. Operation occurs if 90270 and ArgDirArgNegRes.
where

ArgDir

is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR (21D).

ArgNegRes

is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR (21D).

is calculated according to equation 38

The directional information is brought to the mho distance measurement from the mho
directional element as binary coded information to the input DIRCND. See Directional
impedance element for mho characteristic (ZDMRDIR ,21D) for information about the
mho directional element.
208

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

IABjX

ZPP

VAB

ArgNegRes

IAB
ArgDir

en07000111_ansi
ANSI07000111 V1 EN

Figure 68:

Simplified offset mho characteristic in forward direction for phase A-to-B


fault

Offset mho, reverse direction


The operation area for offset mho in reverse direction is according to figure 69. The
operation area in second quadrant is ArgNegRes+180.
Operation occurs if 90270 and 180 - ArgDir ArgNegRes + 180
The is derived according to equation 38 for the mho circle and is the angle between the
voltage and current.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

209

Section 7
Impedance protection

1MRK 502 066-UUS A

X
ZPP

ArgNegRes

IAB

ArgDir

VAB

ZRevPP
en06000469_ansi.ep
ANSI06000469 V1 EN

Figure 69:

Operation characteristic for reverse phase A-to-B fault

Phase-to-ground fault
Mho
The measuring of ground faults uses ground-return compensation applied in a
conventional way. The compensation voltage is derived by considering the influence from
the ground-return path.
For a ground fault in phase A, the compensation voltage Vcomp can be derived, as shown
in Figure 70.

210

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Vcomp = V

pol

- I A Z loop
(Equation 39)

EQUATION1793-ANSI V1 EN

where
Vpol

is the polarizing voltage (memorized VA for Phase A-to- ground fault)

Zloop

is the loop impedance, which in general terms can be expressed as

Z1+ZN = Z 1 1 + KN

where
Z1

is the positive sequence impedance of the line (Ohm/phase)

KN

is the zero-sequence compensator factor

The angle between the Vcomp and the polarize voltage Vpol for a A-to-ground fault is

b = arg V A - I A + IN KN ZPE - arg(Vpol)

(Equation 40)

EQUATION1592 V1 EN

where
VA

is the phase voltage in faulty phase A

IA

is the phase current in faulty phase A

IN

is the zero-sequence current in faulty phase A (3I0)

KN

Z0-Z1
3 Z1
the setting parameter for the zero sequence
compensation consisting of the magnitude KN and the
angle KNAng.

Vpol

is the 100% of positive sequence memorized voltage VA

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

211

Section 7
Impedance protection

1MRK 502 066-UUS A

IAX
IAZN

V comp

I A Z loop
IAZPE
Vpol
f
IA (Ref)

IAR

en06000472_ansi.vsd
ANSI06000472 V1 EN

Figure 70:

Simplified offset mho characteristic and vector diagram for phase A-toground fault

Operation occurs if 90270.


Offset mho
The characteristic for offset mho at ground fault is a circle containing the two vectors from
the origin ZPE and ZRevPE where ZPE and ZrevPE are the setting reach for the positive
sequence impedance in forward respective reverse direction. The vector ZPE in the
impedance plane has the settable angle AngZPE and the angle for ZRevPP is AngZPE
+180.
The condition for operation at phase-to-ground fault is that the angle between the two
compensated voltages Vcomp1 and Vcomp2 is greater or equal to 90 see figure 71. The
angle will be 90 for fault location on the boundary of the circle.
The angle for A-to-ground fault can be defined as

Table continues on next page

212

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

IABjX

V comp1 = VA - IA ZPE

IA ZPE

VA

V comp2 = VA - (-IA ZRevPE)


I AB R

- IA Z RevPe
en 06000465_ansi. vsd
ANSI06000465 V1 EN

Figure 71:

Simplified offset mho characteristic and voltage vector for phase A-toground fault

Operation occurs if 90270.


Offset mho, forward direction
In the same way as for phase-to-phase fault, selection of forward direction of offset mho
will introduce an extra criterion for operation. Beside the basic criteria for offset mho
according to equation 41 and 90270, also the criteria that the angle between the
voltage and the current must lie between the blinders in second and fourth quadrant. See
figure 72. Operation occurs if 90270 and ArgDirArgNegRes.
where

ArgDir

is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR (21D).

ArgNegRes

is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR (21D).

is calculated according to equation 41

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

213

Section 7
Impedance protection

1MRK 502 066-UUS A

IA jX

VA

ArgNegRes

IAR

IA
ArgDir

en 06000466_ansi.vsd
ANSI06000466 V1 EN

Figure 72:

Simplified characteristic for offset mho in forward direction for A-toground fault

Offset mho, reverse direction


In the same way as for offset in forward direction, the selection of offset mho in reverse
direction will introduce an extra criterion for operation compare to the normal offset mho.
The extra is that the angle between the fault voltage and the fault current shall lie between
the blinders in second and fourth quadrant. The operation area in second quadrant is
limited by the blinder defined as 180 -ArgDir and in fourth quadrant ArgNegRes+180,
see figure 73.
The conditions for operation of offset mho in reverse direction for A-to-ground fault is
90270 and 180-ArgdirArgNegRes+180.
The is derived according to equation 41 for the offset mho circle and is the angle
between the voltage and current.

214

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

X
ZPE

ArgNegRes

IA
ArgDir

VA
ZRevPE

en06000470_ansi.ep
ANSI06000470 V1 EN

Figure 73:

7.1.6.5

Simplified characteristic for offset mho in reverse direction for A-toground fault

Simplified logic diagrams


Distance protection zones
The design of the distance protection zones are presented for all measuring loops: phaseto-ground as well as phase-to-phase.
Phase-to-ground related signals are designated by AG, BG and CG. The phase-to-phase
signals are designated by AB, BC and CA.
Fulfillment of two different measuring conditions is necessary to obtain the one logical
signal for each separate measuring loop:

Zone measuring condition, which follows the operating equations described above.
Group functional input signal (PHSEL), as presented in figure 74.

The ZMHPDIS (21) function block is used in the IED for each zone.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

215

Section 7
Impedance protection

1MRK 502 066-UUS A

The PHSEL input signal represents a connection of six different integer values from Phase
selection with load encroachment function FMPSPDIS (21) within the IED, which are
converted within the zone measuring function into corresponding boolean expressions for
each condition separately. Input signal PHSEL is connected from FMPSPDIS (21)
function output signal PHSCND.
The input signal DIRCND is used to give condition for directionality for the distance
measuring zones. The signal contains binary coded information for both forward and
reverse direction. The zone measurement function filters out the relevant signals
depending on the setting of the parameter DirMode. Input signal DIRCND must be
configured to the STDIRCND output signal on ZDMRDIR (21D) function.

OffsetMhoDir=
Non-directional

AND

AND

DirMode=Offset
PHSEL

T
F

AND

AND
LoadEnchMode=
On/Off
LDCND

T
F

True

AND

Release

DIRCND
OffsetMhoDir=
Forward/Reverse
DirMode=
Forward/Reverse

AND

BLKZ
BLOCK

OR

ANSI11000216-1-en.vsd
ANSI11000216 V1 EN

Figure 74:

Simplified logic for release start signal

When load encroachment mode is switched on (LoadEnchMode=On), start signal PHSEL


is also checked against LDCND signal.
Results of the directional measurement enter the logic circuits when the zone operates in
directional (forward or reverse) mode, as shown in figure 74.

216

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Composition of the phase pickup signals is presented in figure 75.

Release

PU_AG
PU_BG
PU_CG

PHG_FLT

OR

AND

PU_A

OR
AND
AND

PU_B

OR
PU_AB
PU_BC

AND
AND
PU_C

OR
PU_CA

AND

OR

OR

PICKUP
PHPH_FLT

ANSI11000217-1-en.vsd
ANSI11000217 V1 EN

Figure 75:

Composition of pickup signals

Tripping conditions for the distance protection zone one are symbolically presented in
figure 76.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

217

Section 7
Impedance protection

1MRK 502 066-UUS A

Timer tPP=On

0-tPP
0

AND

PHPH_FLT

OR

Timer tPG=On

AND

PHG_FLT

0-tPG
0

PU_A

AND

PU_B

AND

PU_C

AND

TRIP

0
15 ms

AND

BLKTRIP

TR_A
TR_B
TR_C

ANSI11000218-2-en.vsd
ANSI11000218 V2 EN

Figure 76:

Tripping logic for the distance protection zone

Zone timer logic for the distance protection is symbolically presented in figure 77.
STPE
BLOCK
&
&
a
a=b
b

Internal
start

Internal
start

a
b

TRPE

tON
t

STTIMER

&

a<b

&

tON
t

&&

TRPP
STPP

ZnTimerSel
FALSE

1
internalCommonStart

1 timers seperated
2 timers linked
3 internal start

phSelStart

4 start from phSel

externalCommonStart

5 external start

IEC12000463-3-en.vsd

IEC12000463 V2 EN

Figure 77:

218

Zone timer logic

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.1.7

Technical data
Table 84:

ZMHPDIS (21) technical data

Function

Range or value

Accuracy

Number of zones, phase-toground

Max 4 with selectable direction

Minimum trip current

(1030)% of IBase

Positive sequence impedance,


phase-to-ground loop

(0.0053000.000) W/phase

Positive sequence impedance


angle, phase-to-ground loop

(1090) degrees

Reverse reach, phase-to-ground


loop (Magnitude)

(0.0053000.000) /phase

2.0% static accuracy


Conditions:
Voltage range: (0.1-1.1) x Vn
Current range: (0.5-30) x In
Angle: 85 degrees

Magnitude of ground return


compensation factor KN

(0.003.00)

Angle for ground compensation


factor KN

(-180180) degrees

Dynamic overreach

<5% at 85 degrees measured


with CVTs and 0.5<SIR<30

Definite time delay phase-phase


and phase-ground operation

(0.000-60.000) s

0.2% or 60 ms whichever is
greater

Trip time

22 ms typically

IEC 60255-121

Reset ratio

105% typically

Reset time at 0.5 to 1.5 x Zreach

Min. = 30 ms
Max. = 45 ms

7.2

Directional impedance element for mho characteristic


ZDMRDIR (21D)

7.2.1

Identification
Function description
Directional impedance element for mho
characteristic

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
21D

ZDMRDIR

S00346 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

219

Section 7
Impedance protection
7.2.2

1MRK 502 066-UUS A

Functionality
The phase-to-ground impedance elements can be supervised by a phase unselective
directional function based on symmetrical components (option).

7.2.3

Function block
I3P*
V3P*

ZDMRDIR (21D)
DIR_CURR
DIR_VOLT
DIR_POL
PUFW
PUREV
STDIRCND
ANSI06000422-2-en.vsd

ANSI06000422 V2 EN

Figure 78:

7.2.4

Signals
Table 85:
Name

ZDMRDIR (21D) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

Table 86:
Name

220

ZDMRDIR (21D) function block

ZDMRDIR (21D) Output signals


Type

Description

CURR

GROUP SIGNAL

Group signal for current signals to Mho function

VOLT

GROUP SIGNAL

Group signal for voltage signals to Mho function

POL

GROUP SIGNAL

Group signal for polarization voltage signals to Mho


function

PUFW

BOOLEAN

Pickup in forward direction

PUREV

BOOLEAN

Pickup in reverse direction

STDIRCND

INTEGER

Binary coded directional information per measuring loop

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 87:

ZDARDIR Input signals

Name

Type

Current signals

V3P

GROUP
SIGNAL

Voltage signals

I3PPOL

GROUP
SIGNAL

Polarisation current signals

DIRCND

INTEGER

Binary coded directional signal

ZDARDIR Output signals

Name

Table 89:
Name

Description

GROUP
SIGNAL

Table 88:

7.2.5

Default

I3P

Type

Description

FWD_G

BOOLEAN

Forward start signal from phase-to-ground directional


element

REV_G

BOOLEAN

Reverse start signal from phase-to-ground directional


element

DIREFCND

INTEGER

Pickuo direction Binary coded

Settings
ZDMRDIR (21D) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

DirEvalType

Impedance
Comparator
Imp/Comp

Comparator

Directional evaluation mode Impedance /


Comparator

AngNegRes

90 - 175

Deg

115

Angle of blinder in second quadrant for forward


direction

AngDir

5 - 45

Deg

15

Angle of blinder in fourth quadrant for forward


direction

IMinPUPG

5 - 30

%IB

Minimum pickup phase current for Phase-toground loops

IMinPUPP

5 - 30

%IB

10

Minimum pickup phase-phase current for


Phase-Phase loops

Table 90:
Name
GlobalBaseSel

ZDMRDIR (21D) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description
Selection of one of the Global Base Value
groups

221

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 91:

ZDARDIR Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

PolMode

-3U0
-V2
IPol
Dual
-3U0Comp
-V2comp

-3U0

Polarization quantity for opt dir function for P-G


faults

AngleRCA

-90 - 90

Deg

75

Characteristic relay angle (= MTA or base


angle)

IPickup

5 - 200

%IB

Minimum operation current in % of IBase

VPolPU

4 - 100

%VB

Minimum polarizing voltage in % of VBase

IPolPU

5 - 100

%IB

10

Minimum polarizing current in % of IBase

Table 92:
Name

ZDARDIR Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

AngleOp

90 - 180

Deg

160

Operation sector angle

Kmag

0.50 - 3000.00

Ohm

0.01

40.00

Boost-factor in -V0comp and -V2comp


polarization

Step

Default

Table 93:
Name
GlobalBaseSel

7.2.6

ZDARDIR Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 94:
Name

ZDMRDIR (21D) Monitored data


Type

Values (Range)

Unit

Description

A_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase A

B_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase B

C_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase C

Aph_R

REAL

Ohm

Resistance in phase A

Aph_X

REAL

Ohm

Reactance in phase A

Bph_R

REAL

Ohm

Resistance in phase B

Table continues on next page

222

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

Bph_X

REAL

Ohm

Reactance in phase B

Cph_R

REAL

Ohm

Resistance in phase C

Cph_X

REAL

Ohm

Reactance in phase C

7.2.7

Operation principle

7.2.7.1

Directional impedance element for mho characteristic ZDMRDIR (21D)


The evaluation of the directionality takes place in Directional impedance element for mho
characteristic (ZDMRDIR ,21D). Equation 42 and equation 43 are used to classify that the
fault is in the forward direction for phase-to-ground fault and phase-to-phase fault
respectively.
- AngDir < Ang

0.85 V 1A + 0.15 V 1 AM
IA

< AngNeg Re s
(Equation 42)

EQUATION1618 V1 EN

- AngDir < Ang

0.85 V 1 AB + 0.15 V 1 ABM


IAB

< AngNeg Re s
(Equation 43)

EQUATION1620 V1 EN

Where:
AngDir

Setting for the lower boundary of the forward directional characteristic, by default set to 15
(= -15 degrees)

AngNegRes

Setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 79 for mho characteristics.

V1A

Positive sequence phase voltage in phase A

V1AM

Positive sequence memorized phase voltage in phase A

IA

Phase current in phase A

V1AB

Voltage difference between phase A and B (B lagging A)

V1ABM

Memorized voltage difference between phase A and B (B lagging A)

IAB

Current difference between phase A and B (B lagging A)

The default settings for AngDir and AngNegRes are 15 (= -15) and 115 degrees
respectively (see figure 79) and they should not be changed unless system studies show
the necessity.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

223

Section 7
Impedance protection

1MRK 502 066-UUS A

If one sets DirEvalType to Comparator (which is recommended when using the mho
characteristic) then the directional lines are computed by means of a comparator-type
calculation, meaning that the directional lines are based on mho-circles (of infinite
radius). The default setting value Impedance otherwise means that the directional lines are
implemented based on an impedance calculation equivalent to the one used for the
quadrilateral impedance characteristics.
When Directional impedance element for mho characteristic
(ZDMRDIR) is used together with Fullscheme distance protection, mho
characteristic (ZMHPDIS) the following settings for parameter
DirEvalType is vital:

alternative Comparator is strongly recommended


alternative Imp/Comp should generally not be used
alternative Impedance should not be used. This altenative is intended
for use together with Distance protection zone, quadrilateral
characteristic (ZMQPDIS)

X
Zset reach point

AngNegRes

-AngDir

-Zs
en06000416_ansi.vsd
ANSI06000416 V1 EN

Figure 79:

Setting angles for discrimination of forward fault

The reverse directional characteristic is equal to the forward characteristic rotated by 180
degrees.
The code built up for release of the measuring fault loops is as follows: STDIRCND =
AN*1 + BN*2 + CN*4 + AB*8 + BC*16 + CA*32
Example: If only ANpickup, the value is 1, if pickup in AN and CN are detected, the value
is 1+4=5.
224

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

The polarizing voltage is available as long as the positive-sequence voltage exceeds 5%


of the set base voltage VBase, thus the directional element can use it for all unsymmetrical
faults including close-in faults.
For close-in three-phase faults, the V1AM memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100ms or until the positive sequence voltage is restored.
After 100ms, the following occurs:

If the current is still above the set value of the minimum operating current the
condition seals in.

If the fault has caused tripping, the trip continues.


If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.

If the current decreases below the minimum operate value, no directional indications
will be given until the positive sequence voltage exceeds 10% of its rated value.

The Directional impedance element for mho characteristic (ZDMRDIR ,21D) function
has the following output signals:
The STDIRCND output provides an integer signal that depends on the evaluation and is
derived from a binary coded signal as follows:
bit 11
(2048)

bit 10
(1024)

bit 9
(512)

bit 8
(256)

bit 7
(128)

bit 6
(64)

REV_CA1=1

REV_BC=1

REV_AB=1

REV_C=1

REV_B=1

REV_A=1

bit 5
(32)

bit 4
(16)

bit 3
(8)

bit 2
(4)

bit 1
(2)

bit 0
(1)

FWD_CA=1

FWD_BC=1

FWD_AB=1

FWD_C=1

FWD_B=1

FWD_A=1

The PUFW output is a logical signal with value 1 or 0. It is made up as an OR-function of


all the forward starting conditions, that is, FWD_A, FWD_B, FWD_C, FWD_AB,
FWD_BC and RWD_CA. The PUREV output is similar to the PUFW output, the only
difference being that it is made up as an OR-function of all the reverse starting conditions,
that is, REV_A, REV_B, REV_C. REV_AB, REV_BC and REV_CA.

7.3

Distance protection zone, quadrilateral characteristic,


separate settings ZMRPDIS (21), ZMRAPDIS (21) and
ZDRDIR (21D)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

225

Section 7
Impedance protection
7.3.1

1MRK 502 066-UUS A

Identification
Function description
Distance protection zone, quadrilateral
characteristic, separate settings (zone
1)

IEC 61850
identification

IEC 60617
identification

ZMRPDIS

ANSI/IEEE C37.2
device number
21

S00346 V1 EN

Distance protection zone, quadrilateral


characteristic, separate settings (zone
2-5)

ZMRAPDIS

21

S00346 V1 EN

Function description
Directional impedance quadrilateral

7.3.2

IEC 61850
identification
ZDRDIR

IEC 60617
identification
Z<->

ANSI/IEEE C37.2
device number
21D

Functionality
The line distance protection is up to five zone full scheme protection with three fault loops
for phase-to-phase faults and three fault loops for phase-to-ground fault for each of the
independent zones. Individual settings for each zone in resistive and reactive reach gives
flexibility for use as back-up protection for transformer connected to overhead lines and
cables of different types and lengths.
Mho alternative quadrilateral characteristic is available.
ZMRPDIS (21) together with Phase selection, quadrilateral characteristic with settable
angle FRPSPDIS (21) has functionality for load encroachment, which increases the
possibility to detect high resistive faults on heavily loaded lines.
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode.

226

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.3.3

Function block
ZMRPDIS (21)
I3P*
V3P*
BLOCK
BLKZ
BLKTR
PHSEL
DIRCND

TRIP
TR_A
TR_B
TR_C
RI
BFI_A
BFI_B
PU_C
PHPUND
ANSI08000248-1-en.vsd

ANSI08000248 V1 EN

Figure 80:

ZMRPDIS (21) function block

ZMRAPDIS (21)
I3P*
V3P*
BLOCK
BLKZ
BLKTR
PHSEL
DIRCND

TRIP
TR_A
TR_B
TR_C
BFI
PU_A
BFI_B
PU_C
PHPUND
ANSI08000290_1_en.vsd

ANSI08000290 V1 EN

Figure 81:

ZMRAPDIS (21) function block

ZDRDI R (21D)
I3P*
V3P*

STDI RCND

ANSI10000007-1-en.vsdx

ANSI10000007 V1 EN

7.3.4

Signals
Table 95:
Name

ZMRPDIS (21) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Blocks all output for LOV (or fuse failure) condition

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

227

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Type

Default

Description

BLKTR

BOOLEAN

Blocks all trip outputs

PHSEL

INTEGER

Faulted phase loop selection enable from phase


selector

DIRCND

INTEGER

External directional condition

Table 96:
Name

ZMRPDIS (21) Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TR_A

BOOLEAN

Trip signal from phase A

TR_B

BOOLEAN

Trip signal from phase B

TR_C

BOOLEAN

Trip signal from phase C

RI

BOOLEAN

General Pickup, issued from any phase or loop

BFI_A

BOOLEAN

Pickup signal from phase A

BFI_B

BOOLEAN

Pickup signal from phase B

PU_C

BOOLEAN

Pickup signal from phase C

PHPUND

BOOLEAN

Non-directional pickup, issued from any selected phase


or loop

Table 97:
Name

ZMRAPDIS (21) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Blocks all output for LOV (or fuse failure) condition

BLKTR

BOOLEAN

Blocks all trip outputs

PHSEL

INTEGER

Faulted phase loop selection enable from phase


selector

DIRCND

INTEGER

External directional condition

Table 98:
Name

ZMRAPDIS (21) Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TR_A

BOOLEAN

Trip signal from phase A

TR_B

BOOLEAN

Trip signal from phase B

Table continues on next page

228

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Type
BOOLEAN

Trip signal from phase C

BFI

BOOLEAN

General Pickup, issued from any phase or loop

PU_A

BOOLEAN

Pickup signal from phase A

BFI_B

BOOLEAN

Pickup signal from phase B

PU_C

BOOLEAN

Pickup signal from phase C

PHPUND

BOOLEAN

Non-directional pickup, issued from any selected phase


or loop

Table 99:

ZDRDIR (21D) Input signals

Name

Type

group connection for current abs 2

V3P

GROUP
SIGNAL

group connection for voltage abs 2

ZDRDIR (21D) Output signals


Type

STDIRCND

Name

Description

GROUP
SIGNAL

Name

Table 101:

Default

I3P

Table 100:

7.3.5

Description

TR_C

Description

INTEGER

Binary coded directional information per measuring loop

Settings
ZMRPDIS (21) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OperationDir

Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

X1PP

0.10 - 3000.00

Ohm/p

0.01

30.00

Positive sequence reactance reach Ph-Ph

R1PP

0.01 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-Ph

X1PG

0.10 - 3000.00

Ohm/p

0.01

30.00

Positive sequence reactance reach Ph-G

R1PG

0.01 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-G

RFPP

0.10 - 3000.00

Ohm/l

0.01

30.00

Fault resistance reach in ohm/loop, Ph-Ph

X0PG

0.10 - 9000.00

Ohm/p

0.01

100.00

Zero sequence reactance reach, Ph-G

RFPG

0.10 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach in ohm/loop, Ph-G

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

229

Section 7
Impedance protection

Name

Step

Default

R0PG

0.01 - 3000.00

Ohm/p

0.01

15.00

Zero seq. resistance for zone characteristic


angle, Ph-G

OperationPP

Disabled
Enabled

Enabled

Operation mode Disable/Enable of PhasePhase loops

OpModetPP

Disabled
Enabled

Enabled

Operation mode Disable/Enable of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-Ph

OperationPG

Disabled
Enabled

Enabled

Operation mode Disable/Enable of PhaseGround loops

OpModetPG

Disabled
Enabled

Enabled

Operation mode Disable/ Enable of Zone timer,


Ph-G

tPG

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-G

IMinPUPP

10 - 1000

%IB

20

Minimum operate delta current for PhasePhase loops

IMinPUPG

10 - 1000

%IB

20

Minimum pickup phase current for Phase-toground loops

IMinOpIR

5 - 1000

%IB

Minimum operate residual current for PhaseGround loops

Table 102:
Name
GlobalBaseSel

Table 103:
Name

Values (Range)

1MRK 502 066-UUS A

Unit

Description

ZMRPDIS (21) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Description
Selection of one of the Global Base Value
groups

ZMRAPDIS (21) Group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OperationDir

Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

X1PP

0.10 - 3000.00

Ohm/p

0.01

30.00

Positive sequence reactance reach Ph-Ph

R1PP

0.01 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-Ph

X1PG

0.10 - 3000.00

Ohm/p

0.01

30.00

Positive sequence reactance reach Ph-G

R1PG

0.01 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-G

RFPP

0.10 - 3000.00

Ohm/l

0.01

30.00

Fault resistance reach in ohm/loop, Ph-Ph

X0PG

0.10 - 9000.00

Ohm/p

0.01

100.00

Zero sequence reactance reach, Ph-G

RFPG

0.10 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach in ohm/loop, Ph-G

Table continues on next page

230

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Step

Default

R0PG

0.01 - 3000.00

Ohm/p

0.01

15.00

Zero seq. resistance for zone characteristic


angle, Ph-G

OperationPP

Disabled
Enabled

Enabled

Operation mode Disable/Enable of PhasePhase loops

OpModetPP

Disabled
Enabled

Enabled

Operation mode Disable/Enable of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-Ph

OperationPG

Disabled
Enabled

Enabled

Operation mode Disable/Enable of PhaseGround loops

OpModetPG

Disabled
Enabled

Enabled

Operation mode Disable/ Enable of Zone timer,


Ph-G

tPG

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-G

IMinPUPP

10 - 1000

%IB

20

Minimum operate delta current for PhasePhase loops

IMinPUPG

10 - 1000

%IB

20

Minimum pickup phase current for Phase-toground loops

Table 104:
Name
GlobalBaseSel

Table 105:
Name

Values (Range)

Unit

Description

ZMRAPDIS (21) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Description
Selection of one of the Global Base Value
groups

ZDRDIR (21D) Group settings (basic)


Values (Range)

Unit

Step

Default

Description

IMinPUPP

5 - 30

%IB

10

Minimum pickup phase-phase current for


Phase-Phase loops

IMinPUPG

5 - 30

%IB

Minimum pickup phase current for Phase-toground loops

AngNegRes

90 - 175

Deg

115

Angle of blinder in second quadrant for forward


direction

AngDir

5 - 45

Deg

15

Angle of blinder in fourth quadrant for forward


direction

Table 106:
Name
GlobalBaseSel

ZDRDIR (21D) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description
Selection of one of the Global Base Value
groups

231

Section 7
Impedance protection

1MRK 502 066-UUS A

7.3.6

Operation principle

7.3.6.1

Full scheme measurement


The execution of the different fault loops within the IED are of full scheme type, which
means that each fault loop for phase-to-ground faults and phase-to-phase faults for
forward and reverse faults are executed in parallel.
Figure 82 presents an outline of the different measuring loops for up to five, impedancemeasuring zones. There are 3 to 5 zones depending on product type and variant.
A-G

B-G

C-G

A- B

B-C

C-A

Zone 1

A-G

B-G

C-G

A- B

B-C

C-A

Zone 2

A-G

B-G

C-G

A- B

B-C

C-A

Zone 3

A-G

B-G

C-G

A- B

B-C

C-A

Zone 4

A-G

B-G

C-G

A- B

B-C

C-A

Zone 5

A-G

B-G

C-G

A- B

B-C

C-A

Zone 6

ANSI05000458-2-en.vsd
ANSI05000458 V2 EN

Figure 82:

The different measuring loops at phase-to-ground fault and phase-tophase fault.

The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a pickup of an overreaching element to select correct voltages
and current depending on fault type. Each distance protection zone performs like one
independent distance protection IED with six measuring elements.

7.3.6.2

Impedance characteristic
The distance measuring zone includes six impedance measuring loops; three intended for
phase-to-ground faults, and three intended for phase-to-phase as well as, three-phase
faults.
The distance measuring zone will essentially operate according to the non-directional
impedance characteristics presented in figure 83 and figure 84. The phase-to-ground
characteristic is illustrated with the full loop reach while the phase-to-phase characteristic
presents the per phase reach.

232

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

X (Ohm/loop)
RFPG

R1+Rn

RFPG

Xn =

X1+Xn

Rn =

jn
RFPG

jn

X0-X1
3
R0-R1
3

R (Ohm/loop)

RFPG

X1+Xn

RFPG

R1+Rn

RFPG
ANSI05000661-3-en.vsd

ANSI05000661 V3 EN

Figure 83:

Characteristic for phase-to-ground measuring , ohm/loop domain

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

233

Section 7
Impedance protection

1MRK 502 066-UUS A

RFPP

(Ohm/phase)

R1PP

RFPP

X 0 PE - X 1RVPE
XNRV =XX00PE
PG- 1RVPG
X3
1XRVPE
XNRV
=
XNRV =
3
3
PE
--1X
11FWPE
XX
00
PE
-X
X
0
PG
XFWPE
FWPG
XNFW
=
XNFW
XNFW==
3 33

X1PP

R (Ohm/phase)
RFPP

RFPP

X1PP

RFPP
2

R1PP

RFPP
2

en07000062.vsd

IEC07000062 V2 EN

Figure 84:

Characteristic for phase-to-phase measuring

The fault loop reach with respect to each fault type may also be presented as in figure 85.
Note in particular the difference in definition regarding the (fault) resistive reach for
phase-to-phase faults and three-phase faults.

234

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

VA

Ip

R1 + j X1

Phase-to-ground
fault in phase A

Phase-to-ground
element

RFPG
(Arc + tower
resistance)
0

VA
Phase-to-phase
fault in phase A-B

IN

(R0-R1)/3 +
j (X0-X1)/3 )

IA

R1 + j X1

Phase-to-phase
element A-B
RFPP

IB

(Arc resistance)

VB
R1 + j X1

VA
Three-phase
fault

IA

R1 + j X1

0.5RFPP

R1 + j X1

0.5RFPP

Phase-to-phase
element A-C

IC
VC
ANSI05000181_2_en.vsd

ANSI05000181 V2 EN

Figure 85:

Fault loop model

The R1 and jX1 in figure 85 represents the positive sequence impedance from the
measuring point to the fault location. The settings RFPG and RFPP are the eventual fault
resistances in the faulty place.
Regarding the illustration of three-phase fault in figure 85, there is of course fault current
flowing also in the third phase during a three-phase fault. The illustration merely reflects
the loop measurement, which is made phase-to-phase.
The zone can be set to operate in Non-directional, Forward or Reverse direction through
the setting OperationDir. The result from respective set value is illustrated in figure 86.
The impedance reach is symmetric, in the sense that it conforms for forward and reverse
direction. Therefore, all reach settings apply to both directions.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

235

Section 7
Impedance protection

1MRK 502 066-UUS A

Non-directional

Forward

Reverse
IEC05000182-2-en.vsdx

IEC05000182 V2 EN

Figure 86:

7.3.6.3

Directional operating modes of the distance measuring zones

Minimum operating current


The operation of Distance measuring zones, quadrilateral characteristic (ZMRPDIS, 21)
is blocked if the magnitude of input currents fall below certain threshold values.
The phase-to-ground loop AG (BG or CG) is blocked if IA (IB or IC) < IMinPUPG.
For zone 1 with load compensation feature the additional criterion applies, that all phaseto-ground loops can be blocked when IN < IMinOpIR, regardless of the phase currents.
IA (IB or IC) is the RMS value of the current in phase IA (IB or IC). IN is the RMS value
of the vector sum of the three-phase currents, that is residual current 3I0.
The phase-to-phase loop AB (BC or CA) is blocked if IAB (BC or CA)< IMinPUPP.
All three current limits IMinPUPG, IMinOpIR and IMinPUPP are
automatically reduced to 75% of regular set values if the zone is set to
operate in reverse direction, that is OperationDir=Reverse

7.3.6.4

Measuring principles
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The

236

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

apparent impedances at phase-to-phase faults follow equation 44 (example for a phase A


to phase B fault).
VA - VB

Zapp =

IA - IB
(Equation 44)

EQUATION1545 V1 EN

Here V and I represent the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3)
The ground return compensation applies in a conventional manner to phase-to-ground
faults (example for a phase A to ground fault) according to equation 45.
V_A

Z app =

I _ A + IN KN

EQUATION1546 V1 EN

(Equation 45)

Where:
V_A, I_A and IN are the phase voltage, phase current and residual current present to the IED

KN
is defined as:

KN =

Z 0 - Z1
3 Z1

EQUATION-2105 V2 EN

Z 0 = R 0 + jX 0
EQUATION2106 V2 EN

Z 1 = R1 + jX 1
EQUATION2107 V2 EN

Where
R0

is setting of the resistive zero sequence reach

X0

is setting of the reactive zero sequence reach

R1

is setting of the resistive positive sequence reach

X1

is setting of the reactive positive sequence reach

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

237

Section 7
Impedance protection

1MRK 502 066-UUS A

Here IN is a phasor of the residual current in IED point. This results in the same reach
along the line for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and
reactance X.
The formula given in equation 45 is only valid for radial feeder application without load.
When load is considered in the case of single phase-to-ground fault, conventional distance
protection might overreach at exporting end and underreach at importing end. The IED
has an adaptive load compensation which increases the security in such applications.
Measuring elements receive current and voltage information from the A/D converter. The
check sums are calculated and compared, and the information is distributed into memory
locations. For each of the six supervised fault loops, sampled values of voltage (V), current
(I), and changes in current between samples (DI) are brought from the input memory and
fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related to the
loop impedance according to equation 46,
V =R i +

Di

w0 Dt
(Equation 46)

EQUATION1547 V1 EN

in complex notation, or:


Re (V ) = R Re (I ) +

X
w0

D Re (I )
Dt
(Equation 47)

EQUATION1548 V1 EN

Im (V ) = R Im (I ) +
EQUATION1549 V1 EN

X
w0

D Im (I )
Dt
(Equation 48)

with

238

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

w0 = 2 p f 0
(Equation 49)

EQUATION356 V1 EN

where:
Re

designates the real component of current and voltage,

Im

designates the imaginary component of current and voltage and

f0

designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real value of
the voltage and substitutes it in the equation for the imaginary part. The equation for the
Xm measured reactance can then be solved. The final result is equal to:
Rm =

Im (V) D Re (I) - Re (V) Dlm(I)


D Re (I) lm(I) - Dlm(I) Re (I)
(Equation 50)

EQUATION1550 V1 EN

X m = w0 D t

Re (V) lm(I) - lm(V ) Re (I)


D Re (I) lm(I) - Dlm(I) Re (I)
(Equation 51)

EQUATION1551 V1 EN

The calculated Rm and Xm values are updated each sample and compared with the set zone
reach. The adaptive tripping counter counts the number of permissive tripping results.
This effectively removes any influence of errors introduced by the capacitive voltage
transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and reverse
directions, and in all six fault loops. Positive sequence voltage and a phase locked positive
sequence memory voltage are used as a reference. This ensures unlimited directional
sensitivity for faults close to the IED point.

7.3.6.5

Directional impedance element for quadrilateral characteristics


The evaluation of the directionality takes place in Directional impedance quadrilateral
function ZDRDIR (21D). Equation 52 and equation 53 are used to classify that the fault
is in forward direction for phase-to-ground fault and phase-to-phase fault.
- ArgDir < arg

0.8 V 1L1 + 0.2 V 1L1 M


I L1

< ArgNeg Re s

EQUATION1552 V2 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

(Equation 52)

239

Section 7
Impedance protection

1MRK 502 066-UUS A

For the AB element, the equation in forward direction is according to.


- ArgDir < arg

0.8 V 1L1 L 2 + 0.2 V 1L1 L 2 M


I L1 L 2

< ArgNeg Re s
(Equation 53)

EQUATION1553 V2 EN

where:
AngDir

is the setting for the lower boundary of the forward directional characteristic, by default set to 15
(= -15 degrees) and

AngNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 87.
V1A

is positive sequence phase voltage in phase A

V1AM

is positive sequence memorized phase voltage in phase A

IA

is phase current in phase A

V1AB

is voltage difference between phase A and B (B lagging A)

V1ABM

is memorized voltage difference between phase A and B (B lagging A)

IAB

is current difference between phase A and B (B lagging A)

The setting of AngDir and AngNegRes is by default set to 15 (= -15) and 115 degrees
respectively (as shown in figure 87). It should not be changed unless system studies have
shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the output
STDIRCND.
STDIR=

240

FWD_A*1+FWD_B*2+FWD_C*4+FWD_AB*8+
+FWD_BC*16+FWD_CA*32+REV_A*64+REV_B*128+REV_C*256+
+REV_AB*512+REV_BC*1024+REV_CA*2048

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

AngNegRes

AngDir

en05000722_ansi.vsd
ANSI05000722 V1 EN

Figure 87:

Setting angles for discrimination of forward and reverse fault in


Directional impedance quadrilateral function ZDRDIR (21D)

The reverse directional characteristic is equal to the forward characteristic rotated by 180
degrees.
The polarizing voltage is available as long as the positive sequence voltage exceeds 5% of
the set base voltage VBase. So the directional element can use it for all unsymmetrical
faults including close-in faults.
For close-in three-phase faults, the V1AM memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
After 100 ms the following occurs:

If the current is still above the set value of the minimum operating current (between
10 and 30% of the set IED rated current IBase), the condition seals in.

If the fault has caused tripping, the trip endures.


If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.

If the current decreases below the minimum operating value, the memory resets until
the positive sequence voltage exceeds 10% of its rated value.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

241

Section 7
Impedance protection
7.3.6.6

1MRK 502 066-UUS A

Simplified logic diagrams


Distance protection zones
The design of the distance protection zones are presented for all measuring loops: phaseto-ground as well as phase-to-phase.
Phase-to-ground related signals are designated by AG, BG and CG.. The phase-to-phase
signals are designated by AB, BC and CA.
Fulfillment of two different measuring conditions is necessary to obtain the one logical
signal for each separate measuring loop:

Zone measuring condition, which follows the operating equations described above.
Group functional input signal (PHSEL), as presented in figure 88.

The PHSEL input signal represents a connection of six different integer values from Phase
selection with load encroachment, quadrilateral characteristic function FRPSPDIS (21)
within the IED, which are converted within the zone measuring function into
corresponding boolean expressions for each condition separately. Input signal PHSEL is
connected to FRPSPDIS (21) function output STCNDZ.
The input signal DIRCND is used to give condition for directionality for the distance
measuring zones. The signal contains binary coded information for both forward and
reverse direction. The zone measurement function filter out the relevant signals
depending on the setting of the parameter OperationDir. It must be configured to the
STDIRCND output on directional function ZDRDIR (21D) function.

242

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

PUZMPP

OR

PHSEL

NDIR_AB

AB

AND

BC

AND

CA

AND

NDIR_CA

AG

AND

NDIR_A

BG

AND

NDIR_B

CG

AND

NDIR_BC

NDIR_C
STNDPE

OR

OR
LOVBZ
BLOCK

AND

OR
BLOCFUNC

PHPUND
BLK
ANSI99000557-1-en.vsd

ANSI99000557 V2 EN

Figure 88:

Conditioning by a group functional input signal PHSEL, external start


condition

Composition of the phase pickup signals for a case, when the zone operates in a nondirectional mode, is presented in figure 75.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

243

Section 7
Impedance protection

1MRK 502 066-UUS A

NDIR_A

OR

NDIR_B
NIDR_C
NDIR_AB

OR

AND

0
15ms

AND

0
15ms

AND

0
15ms

AND

0
15ms

NDIR_BC
NDIR_CA

OR
OR

PU_A
PU_B
PU_C
PICKUP

BLK
ANSI09000889-1-en.vsd
ANSI09000889 V1 EN

Figure 89:

Composition of pickup signals in non-directional operating mode

Results of the directional measurement enter the logic circuits, when the zone operates in
directional (forward or reverse) mode, as shown in figure 90.

244

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

NDIR_A
DIR_A

AND

AND

NDIR_C
DIR_C

AND

NDIR_AB
DIR_AB

AND

NDIR_BC
DIR_BC

AND

NDIR_CA
DIR_CA

PU_ZMPG

OR

NDIR_B
DIR_B

OR

OR

OR

AND

0
15 ms

AND

0
15 ms

AND

0
15 ms

AND

PU_A

PU_B

PU_C

PU_ZMPP

OR
BLK

OR

AND

PICKUP

0
15 ms

ANSI09000888-2-en.vsd
ANSI09000888 V2 EN

Figure 90:

Composition of pickup signals in directional operating mode

Tripping conditions for the distance protection zone one are symbolically presented in
figure 76.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

245

Section 7
Impedance protection

1MRK 502 066-UUS A

Timer tPP=enable
PUZMPP

tPP

AND

AND

0-tPP
0

BLOCFUNC

OR

OR
tPG

Timer tPG=enable
PUZMPG

0-tPG
0

AND

AND

AND

BLKTR
BLK

OR

TRIP

0
15 ms

PU_A

AND

TR_A

PU_B

AND

TR_B

PU_C

AND

TR_C

ANSI09000887-3-en.vsdx

ANSI09000887 V3 EN

Figure 91:

Tripping logic for the distance protection zone

7.4

Phase selection, quadrilateral characteristic with


settable angle FRPSPDIS (21)

7.4.1

Identification
Function description
Phase selection, quadrilateral
characteristic with settable angle

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
21

FRPSPDIS

Z<phs
SYMBOL-DD V1 EN

246

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.4.2

Functionality
The ability to accurately and reliably classify the different types of fault, so that single pole
tripping and autoreclosing can be used plays an important role in today's power systems.
Phase selection, quadrilateral characteristic with settable angle FRPSPDIS (21) is
designed to accurately select the proper fault loop in the distance function dependent on
the fault type.
The heavy load transfer that is common in many transmission networks may make fault
resistance coverage difficult to achieve. Therefore, FRPSPDIS (21) has a built-in
algorithm for load encroachment, which gives the possibility to enlarge the resistive
setting of both the phase selection and the measuring zones without interfering with the
load.
The extensive output signals from the phase selection gives also important information
about faulty phase(s) which can be used for fault analysis.
A current-based phase selection is also included. The measuring elements continuously
measure three phase currents and the residual current and, compare them with the set
values.

7.4.3

Function block
FRPSPDIS (21)
I3P*
V3P*
BLOCK
DIRCND

TRIP
BFI
FWD_A
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
REV_G
NDIR_A
NDIR_B
NDIR_C
NDIR_G
FWD_1PH
FWD_2PH
FWD_3PH
PHG_FLT
PHPH_FLT
PHSELZ
DLECND
ANSI08000430-2-en.vsd

ANSI08000430 V2 EN

Figure 92:

FRPSPDIS (21) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

247

Section 7
Impedance protection
7.4.4

1MRK 502 066-UUS A

Signals
Table 107:
Name

Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

DIRCND

INTEGER

External directional condition

Table 108:
Name

248

FRPSPDIS (21) Input signals

FRPSPDIS (21) Output signals


Type

Description

TRIP

BOOLEAN

Trip by pilot communication scheme logic

BFI

BOOLEAN

Start in any phase or loop

FWD_A

BOOLEAN

Fault detected in phaseA - forward direction

FWD_B

BOOLEAN

Fault detected in phase B - forward direction

FWD_C

BOOLEAN

Fault detected in phase C - forward direction

FWD_G

BOOLEAN

Ground fault detected in forward direction

REV_A

BOOLEAN

Fault detected in phase A- reverse direction

REV_B

BOOLEAN

Fault detected in phase B - reverse direction

REV_C

BOOLEAN

Fault detected in phase C - reverse direction

REV_G

BOOLEAN

Ground fault detected in reverse direction

NDIR_A

BOOLEAN

Non directional fault detected in Phase A

NDIR_B

BOOLEAN

Non directional fault detected in Phase B

NDIR_C

BOOLEAN

Non directional fault detected in Phase C

NDIR_G

BOOLEAN

Non directional phase-to-ground fault detected

FWD_1PH

BOOLEAN

Single phase-to-ground fault in forward direction

FWD_2PH

BOOLEAN

Phase-to-phase fault in forward direction

FWD_3PH

BOOLEAN

Three phase fault in forward direction

PHG_FLT

BOOLEAN

Release condition to enable phase-ground measuring


elements

PHPH_FLT

BOOLEAN

Release condition to enable phase-phase measuring


elements

PHSELZ

INTEGER

21 pickup with load encroachment and 3I0

DLECND

INTEGER

Pickup for load encroachment and 3I0

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.4.5
Table 109:
Name

Settings
FRPSPDIS (21) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

3I0BLK_PP

10 - 100

%IPh

40

3I0 limit for disabling phase-to-phase


measuring loops

3I0Enable_PG

10 - 100

%IPh

20

3I0 pickup for releasing phase-to-ground


measuring loops

RLdFwd

1.00 - 3000.00

Ohm/p

0.01

80.00

Forward resistive reach for the load impedance


area

RldRev

1.00 - 3000.00

Ohm/p

0.01

80.00

Reverse resistive reach for the load impedance


area

LdAngle

5 - 70

Deg

30

Load angle determining the load impedance


area

X1

0.50 - 3000.00

Ohm/p

0.01

40.00

Positive sequence reactance reach

R1PP

0.10 - 1000.00

Ohm/p

0.01

15.00

Positive seq. resistance for characteristic


angle, Ph-Ph

R1PG

0.10 - 1000.00

Ohm/p

0.01

1.50

Positive seq. resistance for characteristic


angle, Ph-G

X0

0.50 - 9000.00

Ohm/p

0.01

120.00

Zero sequence reactance reach

R0PG

0.50 - 3000.00

Ohm/p

0.01

5.00

Zero seq. resistance for zone characteristic


angle, Ph-G

RFltFwdPP

0.50 - 3000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, forward

RFltRevPP

0.50 - 3000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, reverse

RFltFwdPG

1.00 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, forward

RFltRevPG

1.00 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, reverse

IMinPUPP

5 - 500

%IB

10

Minimum operate delta current for PhasePhase loops

IMinPUPG

5 - 500

%IB

Minimum pickup phase current for Phase-toground loops

Table 110:
Name

FRPSPDIS (21) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

TimerPP

Disabled
Enabled

Disabled

Operation mode Disable/Enable of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

3.000

Time delay to trip, Ph-Ph

TimerPE

Disabled
Enabled

Disabled

Operation mode Disable/ Enable of Zone timer,


Ph-G

tPG

0.000 - 60.000

0.001

3.000

Time delay to trip, Ph-E

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

249

Section 7
Impedance protection

Table 111:
Name
GlobalBaseSel

7.4.6

1MRK 502 066-UUS A

FRPSPDIS (21) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Description
Selection of one of the Global Base Value
groups

Operation principle
Phase selection, quadrilateral characteristic with settable angle (FRPSPDIS, 21) includes
six impedance measuring loops; three intended for phase-to-ground faults, and three
intended for phase-to-phase as well as for three-phase faults.
The difference, compared to the distance zone measuring function, is in the combination
of the measuring quantities (currents and voltages) for different types of faults.
The characteristic is basically non-directional, but FRPSPDIS (21) uses information from
the directional function ZDRDIR to discriminate whether the fault is in forward or reverse
direction.
The pickup condition PHSELZ is essentially based on the following criteria:

Residual current criteria, that is, separation of faults with and without ground
connection
Regular quadrilateral impedance characteristic
Load encroachment characteristics is always active but can be switched off by
selecting a high setting.

The current pickup condition PHSELI is based on the following criteria:

Residual current criteria


No quadrilateral impedance characteristic. The impedance reach outside the load area
is theoretically infinite. The practical reach, however, will be determined by the
minimum operating current limits.
Load encroachment characteristic is always active, but can be switched off by
selecting a high setting.

The PHSELI output is non-directional. The directionality is determined by the distance


zones directional function ZDRDIR.
There are output from FRPSPDIS (21) that indicate whether a pickup is in forward or
reverse direction or non-directional, for example FWD_A, REV_A and NDIR_A.
These directional indications are based on the sector boundaries of the directional function
and the impedance setting of FRPSPDIS (21) function. Their operating characteristics are
illustrated in figure 93.
250

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

60

60

R
60

R
60

Non-directional (ND)

Forward (FWD)

Reverse (REV)
en05000668_ansi.vsd

ANSI05000668 V1 EN

Figure 93:

Characteristics for non-directional, forward and reverse operation of


Phase selection, quadrilateral characteristic with settable angle
(FRPSPDIS, 21)

The setting of the load encroachment function may influence the total operating
characteristic, for more information, refer to section "Load encroachment".
The input DIRCND contains binary coded information about the directional coming from
the directional function ZDRDIR (21D). It shall be connected to the STDIR output on
ZDRDIR (21D). This information is also transferred to the input DIRCND on the distance
measuring zones, that is, the ZMRPDIS (21) block.
The code built up for the directionality is as follows:
STDIR=

FWD_A*1+FWD_B*4+FWD_C*16+FWD_AB*64+
+FWD_BC*256+FWD_CA*1024+REV_A*2+REV_B*8+REV_C*32+
+REV_AB*128+REV_BC*512+REV_CA*2048

If the binary information is 1 then it will be considered that we have pickup in forward
direction in phase A. If the binary code is 3 then we have pickup in forward direction in
phase A and B etc.
The or PHSEL output contains, in a similar way as DIRCND, binary coded information,
in this case information about the condition for opening correct fault loop in the distance
measuring element. It shall be connected to the PHSEL input on the ZMRPDIS distance
measuring zones (21) block.
The code built up for release of the measuring fault loops is as follows:
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

251

Section 7
Impedance protection

1MRK 502 066-UUS A

PHSEL = AG*1+BG*2+CG*4+AB*8+BC*16+CA*32

7.4.6.1

Phase-to-ground fault
Index PHS in images and equations reference settings for Phase selection,
quadrilateral characteristic with settable angle (FRPSPDIS, 21).

ZPHSn =

VA( B , C )
IA( B , C )

(Equation 54)

EQUATION1554 V1 EN

where:
n

corresponds to the particular phase (n=1, 2 or 3)

The characteristic for FRPSPDIS (21) function at phase-to-ground fault is according to


figure 94. The characteristic has a settable angle for the resistive boundary in the first
quadrant of 70.
The resistance RN and reactance XN are the impedance in the ground-return path defined
according to equation 57 and equation 58.
RN =

R 0 PE - R1PE
3

EQUATION-2125 V1 EN

XN =

X 0 - X1
3

EQUATION1257 V1 EN

252

(Equation 55)

(Equation 56)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

X (ohm/loop)
R1PE+RN
RFRvPE

RFFwPE

X1+XN
RFFwPE
R (Ohm/loop)

RFRvPE

X1+XN

RFFwPE

RFRvPE
R1PE+RN

IEC09000633-1-en.vsd
IEC09000633 V1 EN

Figure 94:

Characteristic of FRPSPDIS (21) for phase to fault (directional lines are


drawn as "line-dot-dot-line")

Besides this, the 3I0 residual current must fulfil the conditions according to equation 57
and equation 58.
3 I0 0.5 IMinOpPE
(Equation 57)

EQUATION2108 V1 EN

3 I0

3I 0 Enable _ PG
100

Iph max
(Equation 58)

EQUATION1812-ANSI V1 EN

where:

IMinOpPE

is the minimum operation current for forward zones

3I0Enable_PG is the setting for the minimum residual current needed to enable operation in the phase-toground fault loops (in %).
Iphmax

is the maximum phase current in any of three phases.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

253

Section 7
Impedance protection
7.4.6.2

1MRK 502 066-UUS A

Phase-to-phase fault
For a phase-to-phase fault, the measured impedance by FRPSPDIS (21) is according to
equation 59.
ZPHS =

Vm - Vn
-2 In
(Equation 59)

EQUATION1813-ANSI V1 EN

Vm is the leading phase voltage, Vn the lagging phase voltage and In the phase current in
the lagging phase n.
The operation characteristic is shown in figure 95.
X (ohm/phase)
0.5FRvPP

R1PP 0.5RFFwPP

X1

0.5RFFwPP

R (ohm/phase)
0.5RFRvPP

0.5RFRvPP

R1PP

X1

0.5RFFwPP

IEC09000634-1-en.vsd

IEC09000634 V1 EN

Figure 95:

254

The operation characteristic for FRPSPDIS (21) at phase-to-phase fault


(directional lines are drawn as "line-dot-dot-line")

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

In the same way as the condition for phase-to-ground fault, there are current conditions
that have to be fulfilled in order to release the phase-to-phase loop. Those are according
to equation 60 or equation 61.
3I 0 < 3I 0Enable _ PG

(Equation 60)

EQUATION1814-ANSI V1 EN

3I 0 < 3I 0BLK _ PP
(Equation 61)

EQUATION1815-ANSI V1 EN

where:

3I0Enable_PG is the minimum operation current for forward ground measuring loops,

7.4.6.3

3I0BLK_PP

is 3I0 limit for blocking phase-to-phase measuring loop and

Iphmax

is maximal magnitude of the phase currents.

Three-phase faults
The operation conditions for three-phase faults are the same as for phase-to-phase fault,
that is equation 59, equation 60 and equation 61 are used to release the operation of the
function.
However, the reach is expanded by a factor 2/3 (approximately 1.1547) in all directions.
At the same time the characteristic is rotated 30 degrees, counter-clockwise. The
characteristic is shown in figure 96.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

255

Section 7
Impedance protection

1MRK 502 066-UUS A

X (ohm/phase)
4 X1PP
3

0.5RFFwPPK3
X1K3

30 deg

RFwPP

2
3

R (ohm/phase)
0.5RFRvPPK3
K3 = 2 / sqrt(3)

30 deg

IEC09000635-1-en.vsd
IEC09000635 V2 EN

Figure 96:

7.4.6.4

The characteristic of FRPSPDIS (21) for three-phase fault (set angle 70)

Load encroachment
Each of the six measuring loops has its own load encroachment characteristic based on the
corresponding loop impedance. The load encroachment functionality is always active, but
can be switched off by selecting a high setting.
The outline of the characteristic is presented in figure 98. As illustrated, the resistive
blinders are set individually in forward and reverse direction while the angle of the sector
is the same in all four quadrants.

256

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

RLdFwd
LdAngle

LdAngle

LdAngle

LdAngle

RLdRev

en05000196_ansi.vsd
ANSI05000196 V1 EN

Figure 97:

Characteristic of load encroachment function

The influence of load encroachment function on the operation characteristic is dependent


on the chosen operation mode of FRPSPDIS (21) function. When output signal PHSELZ
is selected, the characteristic for FRPSPDIS (21) (and also zone measurement depending
on settings) will be reduced by the load encroachment characteristic, see figure 99.
When output signal PHSELI is selected, the operation characteristic will be as in
figure 98. The reach will in this case be limit by the minimum operation current and the
distance measuring zones.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

257

Section 7
Impedance protection

1MRK 502 066-UUS A

PHSELZ

DLECND
ANSI10000099-1-en.vsd

ANSI10000099 V1 EN

Figure 98:

Difference in operating characteristic depending on operation mode


when load encroachment is activated

When FRPSPDIS (21) is set to operate together with a distance measuring zone the
resultant operate characteristic could look like in figure 99. The figure shows a distance
measuring zone operating in forward direction. Thus, the operating area of the zone
together with the load encroachment is highlighted in black.

258

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

X
"Phase selection"
"quadrilateral" zone
Distance measuring zone

Load encroachment
characteristic
R
Directional line

en05000673.vsd
IEC05000673 V1 EN

Figure 99:

Operating characteristic in forward direction when load encroachment is


activated

Figure 99 is valid for phase-to-ground. During a three-phase fault, or load, when the
quadrilateral phase-to-phase characteristic is subject to enlargement and rotation the
operate area is transformed according to figure 100. Notice in particular what happens
with the resistive blinders of the "phase selection" "quadrilateral" zone. Due to the 30degree rotation, the angle of the blinder in quadrant one is now 100 degrees instead of the
original 70 degrees (if the angle setting is 70 degrees). The blinder that is nominally
located to quadrant four will at the same time tilt outwards and increase the resistive reach
around the R-axis. Consequently, it will be more or less necessary to use the load
encroachment characteristic in order to secure a margin to the load impedance.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

259

Section 7
Impedance protection

1MRK 502 066-UUS A

X (W /

phase)

Phase selection
Quadrilateral zone

Distance measuring zone

R (W /

phase)

IEC09000049-1-en.vsd
IEC09000049 V1 EN

Figure 100:

Operating characteristic for FRPSPDIS (21) in forward direction for


three-phase fault, ohm/phase domain

The result from rotation of the load characteristic at a fault between two phases is
presented in fig 101. Since the load characteristic is based on the same measurement as the
quadrilateral characteristic, it will rotate with the quadrilateral characteristic clockwise by
30 degrees when subject to a pure phase-to-phase fault. At the same time the characteristic
will "shrink" by 2/3, from the full RLdFw and RLdRv reach, which is valid at load or
three-phase fault.

260

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

IEC08000437.vsd
IEC08000437 V1 EN

Figure 101:

Rotation of load characteristic for a fault between two phases

There is a gain in selectivity by using the same measurement as for the quadrilateral
characteristic since not all phase-to-phase loops will be fully affected by a fault between
two phases. It should also provide better fault resistive coverage in quadrant one. The
relative loss of fault resistive coverage in quadrant four should not be a problem even for
applications on series compensated lines.

7.4.6.5

Minimum operate currents


The operation of Phase selection, quadrilateral characteristic with settable angle
(FRPSPDIS, 21) is blocked if the magnitude of input currents falls below certain threshold
values.
The phase-to-ground loop n is blocked if In<IMinPUPG, where In is the RMS value of the
current in phase n (A or B or C).
The phase-to-phase loop mn is blocked if (2In<IMinOpPPIMinPUPP).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

261

Section 7
Impedance protection
7.4.6.6

1MRK 502 066-UUS A

Simplified logic diagrams


Figure 102 presents schematically the creation of the phase-to-phase and phase-to-ground
operating conditions. Consider only the corresponding part of measuring and logic
circuits, when only a phase-to-ground or phase-to-phase measurement is available within
the IED.
LDEblock

3 I 0 0.5 IMinPUPG

3I 0

3 I 0 Enable _ PG
100

IRELPG

Iphmax

0
15ms

AND

Bool to
integer

BLOCK

3I 0 < IMinPUPG
AND

3I 0 <

3I 0 BLK _ PP
100

STPG

10ms
0

IRELPG
0
20ms

AND

0
15ms

AND

DLECND

STPP
IRELPP

Iph max
ANSI09000149-3-en.vsd

ANSI09000149 V3 EN

Figure 102:

Phase-to-phase and phase-to-ground operating conditions (residual


current criteria)

A special attention is paid to correct phase selection at evolving faults. A PHSEL output
signal is created as a combination of the load encroachment characteristic and current
criteria, refer to figure 102. This signal can be configured to STCND functional input
signals of the distance protection zone and this way influence the operation of the phaseto-phase and phase-to-ground zone measuring elements and their phase related pickup
and tripping signals.
Figure 103 presents schematically the composition of non-directional phase selective
signals NDIR_A (B or C). Internal signals ZMn and ZMmn (m and n change between A,
B and C according to the phase) represent the fulfilled operating criteria for each separate
loop measuring element, that is within the characteristic.

262

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

INDIR_A
INDIR_B
INDIR_C

IRELPG
LDEblockA
ZMA
LDEblockB
ZMB
LDEblockC
ZMC
LDEblockAB
ZMAB
LDEblockBC
ZMBC
LDEblockCA
ZMCA

AND

OR

0
15 ms

OR

0
15 ms

OR

0
15 ms

OR

0
15 ms

AND
AND
AND
AND
AND

PHSEL_G

PHSEL_A

PHSEL_B

PHSEL_C

INDIR_AB
INDIR_BC
INDIR_CA

IRELPP
OR

0
15 ms

PHSEL_PP

ANSI00000545-4-en.vsd
ANSI00000545 V4 EN

Figure 103:

Composition on non-directional phase selection signals

Composition of the directional (forward and reverse) phase selective signals is presented
schematically in figure 104 and figure 105. The directional criteria appears as a condition
for the correct phase selection in order to secure a high phase selectivity for simultaneous
and evolving faults on lines within the complex network configurations. Internal signals
DFWLn and DFWLnLm present the corresponding directional signals for measuring
loops with phases Ln and Lm. Designation FW (figure 105) represents the forward
direction as well as the designation RV (figure 104) represents the reverse direction. All
directional signals are derived within the corresponding digital signal processor.
Figure 104 presents additionally a composition of a PHSELZ output signal, which is
created on the basis of impedance measuring conditions. This signal can be configured to
PHSEL functional input signals of the distance protection zone and this way influence the
operation of the phase-to-phase and phase-to-ground zone measuring elements and their
phase related pickup and tripping signals.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

263

Section 7
Impedance protection

1MRK 502 066-UUS A

INDIR_A
AND

DRV_A
INDIR_AB

AND

DRV_AB

OR

0
15 ms

OR

0
15 ms

OR

0
15 ms

REV_A

INDIR_CA
AND

DRV_CA
INDIR_B

AND

DRV_B

REV_G

INDIR_AB
AND
INDIR_BC

INDIR_A
INDIR_B
INDIR_C
INDIR_AB
INDIR_BC
INDIR_CA

AND

DRV_BC
INDIR_C

AND

DRV_C

REV_B

Bool to
integer

PHSELZ

INDIR_BC
AND

OR

0
15 ms

OR

0
15 ms

REV_C

INDIR_CA
AND

REV_PP

ANSI00000546-3-en.vsd
ANSI00000546 V3 EN

Figure 104:

264

Composition of phase selection signals for reverse direction

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

AND
INDIR_A
DFW_A

AND

AND

OR

INDIR_AB
DFW_AB

AND

OR

INDIR_CA
DFW_CA

OR
AND

FWD_IPH

0
15 ms

FWD_A

0
15 ms

FWD_G

0
15 ms

FWD_B

0
15 ms

FWD_2PH

0
15 ms

FWD_C

0
15 ms

FWD_3PH

AND

INDIR_AB
AND

OR

INDIR_BC
DFW_BC

0
15 ms

AND

AND

INDIR_B
DFW_B

15 ms
0

AND
AND

OR

15 ms
0

INDIR_C
DFW_C

AND

AND

INDIR_BC
AND

OR

INDIR_CA

AND
AND

OR

FWD_PP

0
15 ms

ANSI05000201-3-en.vsd

ANSI05000201 V3 EN

Figure 105:

Composition of phase selection signals for forward direction

Figure106 presents the composition of output signals TRIP and START, where internal
signals STNDPP, STFWPP and STRVPP are the equivalent to internal signals STNDPE,
STFWPE and STRVPE, but for the phase-to-phase loops.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

265

Section 7
Impedance protection

1MRK 502 066-UUS A

TimerPP=Disabled

tPP
t

AND
OR

TimerPE=Disabled

tPE
t

AND

AND
OR

TRIP

AND

STNDPP
STFWPP

OR

STRVPP
OR

STNDPE
STFWPE

RI

OR

STRVPE

ANSI08000441 1-1-en.vsd
ANSI08000441-1 V1 EN

Figure 106:

266

TRIP and START signal logic

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.4.7

Technical data
Table 112:

FRPSPDIS (21) technical data

Function

Range or value

Accuracy

(5-500)% of IBase

1.0% of In at I In
1.0% of I at I > In

Reactive reach, positive


sequence

(0.503000.00) /phase

Resistive reach, positive


sequence

(0.101000.00) /phase

Reactive reach, zero sequence

(0.509000.00) /phase

Resistive reach, zero sequence

(0.503000.00) /phase

2.0% static accuracy


2.0 degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x Vn
Current range: (0.5-30) x In
Angle: at 0 degrees and 85
degrees

Fault resistance, phase-toground faults, forward and


reverse

(1.009000.00) /loop

Fault resistance, Ph-Ph faults,


forward and reverse

(0.503000.00) /loop

Load encroachment criteria:


Load resistance, forward and
reverse
Safety load impedance angle

(1.003000.00) /phase
(5-70) degrees

Reset ratio

105% typically

7.5

High speed distance protection ZMFPDIS (21)

7.5.1

Identification
Function description
High speed distance protection zone

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
21

ZMFPDIS

S00346 V1 EN

7.5.2

Functionality
The ZMFPDIS function is a six zone full scheme protection with three fault loops for
phase-to-phase faults and three fault loops for phase-to-ground faults for each of the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

267

Section 7
Impedance protection

1MRK 502 066-UUS A

independent zones, which makes the function suitable in applications with single-phase
autoreclosing.
In each measurement zone, ZMFPDIS function is designed with the flexibility to operate
in either quadrilateral or mho characteristic mode for separate phase-to-earth or phase-tophase loops.
The zones can operate independently of each other. Zones 3 to 5 in directional (forward
or reverse) or non-directional mode. Zone1 and zone2 are designed to measure in forward
direction only, while one zone (ZRV) is designed to measure in the reverse direction. This
makes them suitable, together with a communication scheme, for protection of power
lines and cables in complex network configurations, such as parallel lines, multi-terminal
lines, and so on.
A built-in adaptive load compensation algorithm prevents overreaching of the distance
zones in the load exporting end during phase-to-ground faults on heavily loaded power
lines. It also reduces underreach in the importing end.
The ZMFPDIS function block itself incorporates a phase-selection element and a
directional element, contrary to previous designs in the 600-series, where these elements
were represented with separate function-blocks.
The operation of the phase-selection element is primarily based on current change criteria
(i.e. delta quantities), with significantly increased dependability. Naturally, there is also a
phase selection criterion operating in parallel which bases its operation only on voltage
and current phasors.
The directional element utilizes a set of well-established quantities to provide fast and
correct directional decision during various power system operating conditions, including
close-in three-phase faults, simultaneous faults and faults with only zero-sequence infeed.

268

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.5.3

Function block

ZMFPDIS (21)
I3P*
V3P*
BLOCK
LOVBZ
BLKZ1
BLKZ2
BLKZ3
BLKZ4
BLKZ5
BLKZRV
BLKTRZ1
BLKTRZ2
BLKTRZ3
BLKTRZ4
BLKTRZ5
BLKTRZRV

TRIP
TRZ1
TR_A_Z1
TR_B_Z1
TR_C_Z1
TRZ2
TR_A_Z2
TR_B_Z2
TR_C_Z2
TRZ3
TRZ4
TRZ5
TRZRV
BFI_3P
PU_Z1
PU_ND_Z1
PU_Z2
PU_A_Z2
PU_B_Z2
PU_C_Z2
PU_ND_Z2
PU_Z3
PU_ND_Z3
PU_Z4
PU_ND_Z4
PU_Z5
STND_Z5
PU_ZRV
PU_A_RV
PU_B_RV
PU_C_RV
STNDRV
PHPUN D
NDIR_A
NDIR_B
NDIR_C
FWD_A
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
REV_G
FWD_1PH
FWD_2PH
FWD_3PH
PHG_FLT
PHPH_FLT
ANSI11000433-3-en.vsdx

ANSI11000433 V3 EN

Figure 107:

ZMFPDIS (21) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

269

Section 7
Impedance protection
7.5.4

1MRK 502 066-UUS A

Signals
Table 113:
Name

ZMFPDIS (21) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Blocks and resets timers and outputs of entire function

LOVBZ

BOOLEAN

Blocks and resets timers and outputs of entire function

BLKZ1

BOOLEAN

Blocks and resets zone 1 timers and outputs

BLKZ2

BOOLEAN

Blocks and resets zone 2 timers and outputs

BLKZ3

BOOLEAN

Blocks and resets zone 3 timers and outputs

BLKZ4

BOOLEAN

Blocks and resets zone 4 timers and outputs

BLKZ5

BOOLEAN

Blocks and resets zone 5 timers and outputs

BLKZRV

BOOLEAN

Blocks and resets reverse zone timers and outputs

BLKTRZ1

BOOLEAN

Blocks and resets zone 1 timers and trip outputs

BLKTRZ2

BOOLEAN

Blocks and resets zone 2 timers and trip outputs

BLKTRZ3

BOOLEAN

Blocks and resets zone 3 timers and trip outputs

BLKTRZ4

BOOLEAN

Blocks and resets zone 4 timers and trip outputs

BLKTRZ5

BOOLEAN

Blocks and resets zone 5 timers and trip outputs

BLKTRZRV

BOOLEAN

Blocks and resets reverse zone timers and trip outputs

Table 114:
Name

ZMFPDIS (21) Output signals


Type

Description

TRIP

BOOLEAN

Trip in any phase or phases from any zone or zones

TRZ1

BOOLEAN

Trip in any phase or phases from zone 1 - forward


direction

TR_A_Z1

BOOLEAN

Trip in phase A from zone 1 foward direction

TR_B_Z1

BOOLEAN

Trip in phase B from zone 1 forward direction

TR_C_Z1

BOOLEAN

Trip in phase C from zone 1 forward direction

TRZ2

BOOLEAN

Trip in any phase or phases from zone 2 - forward


direction

TR_A_Z2

BOOLEAN

Trip in phase A from a zone 2 forward direction

TR_B_Z2

BOOLEAN

Trip in phase B from zone 2 forward direction

TR_C_Z2

BOOLEAN

Trip in phase C from zone 2 forward direction

TRZ3

BOOLEAN

Trip in any phase or phases from zone 3 - zone direction

TRZ4

BOOLEAN

Trip in any phase or phases from zone 4 - zone direction

Table continues on next page

270

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Type

Description

TRZ5

BOOLEAN

Trip in any phase or phases from zone 5 - zone direction

TRZRV

BOOLEAN

Trip in any phase or phases from zone RV - reverse dir.

BFI_3P

BOOLEAN

Pickup in any phase or phases from any zone or zones

PU_Z1

BOOLEAN

Pick up of any phase or phases from a Zone 1 fault in the


forward direction

PU_ND_Z1

BOOLEAN

Pick up any phase or phases from zone 1 - any direction

PU_Z2

BOOLEAN

Pick up of any phase or phases from a Zone 2 fault in the


forward direction

PU_A_Z2

BOOLEAN

Pick up of phase A for a zone 2 fault in forward direction

PU_B_Z2

BOOLEAN

Pick up for phase B fault in forward direction

PU_C_Z2

BOOLEAN

Pick up in phase C for a zone 2 fault in the forward


direction

PU_ND_Z2

BOOLEAN

Pick uo in any phase or phases for a zone 2 fault in any


direction

PU_Z3

BOOLEAN

Pick up of any phase or phases from a Zone 3 fault in the


forward direction

PU_ND_Z3

BOOLEAN

Pick up any phase or phases from zone 3- any direction

PU_Z4

BOOLEAN

Pick up in any pjase or phases for a zone 4 fault - zone


direction

PU_ND_Z4

BOOLEAN

Pick up any phase or phases from zone -4 any direction

PU_Z5

BOOLEAN

Pick up in any phase or phase for Zone 5 - Zone


direction

STND_Z5

BOOLEAN

Pick up in any phase or phases from a zone 5 fault in any


direction

PU_ZRV

BOOLEAN

Pick up in any phase or phase for a reverse fault

PU_A_RV

BOOLEAN

Pick up for a phase A reverse fault

PU_B_RV

BOOLEAN

Pick up for a phase B revers fault

PU_C_RV

BOOLEAN

Pick up for a phase C reverse fault

STNDRV

BOOLEAN

Pick up for a reverse zone for a fauult in nay direction

PHPUND

BOOLEAN

Fault detected in any phase or phases - any direction

NDIR_A

BOOLEAN

Fault detected in phase A - any direction

NDIR_B

BOOLEAN

Fault detected in phase B - any direction

NDIR_C

BOOLEAN

Fault detected in phase C - any direction

FWD_A

BOOLEAN

Fault detected in phaseA - forward direction

FWD_B

BOOLEAN

Fault detected in phase B - forward direction

FWD_C

BOOLEAN

Fault detected in phase C - forward direction

FWD_G

BOOLEAN

forward fault involving ground

REV_A

BOOLEAN

Fault detected in phase A- reverse direction

REV_B

BOOLEAN

Fault detected in phase B - reverse direction

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

271

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

7.5.5
Table 115:
Name

Type

Description

REV_C

BOOLEAN

Fault detected in phase C - reverse direction

REV_G

BOOLEAN

Fault in reverse direction involving ground

FWD_1PH

BOOLEAN

Single-phase fault detected - forward direction

FWD_2PH

BOOLEAN

Two-phase fault detected - forward direction

FWD_3PH

BOOLEAN

Three-phase fault detected - forward direction

PHG_FLT

BOOLEAN

Ph-G zone measurement enabled - any direction

PHPH_FLT

BOOLEAN

Ph-Ph zone measurement enabled - any direction

Settings
ZMFPDIS (21) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Disable/Enable operation of the function

RLdFwd

0.01 - 5000.00

Ohm/p

0.01

60.00

Resistance determining the load impedance


area - forward

RLdRvFactor

1 - 1000

%RLdF
w

100

Resistance factor determining the load


impedance area - reverse

XLd

0.01 - 10000.00

Ohm/p

0.01

400.00

Resistance determining the load impedance


area - forward

LdAngle

5 - 70

Deg

30

Angle determining the load impedance area

CVTType

Any
Passive type
None (Magnetic)

Passive type

CVT selection determining filtering of the


function

OpModePPZ1

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 1

OpModePGZ1

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 1

X1PPZ1

0.01 - 3000.00

Ohm/p

0.01

30.00

Positive sequence reactance reach, Ph-Ph,


zone 1

R1PPZ1

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive sequence resistive reach, Ph-Ph,


zone 1

X1PGZ1

0.01 - 3000.00

Ohm/p

0.01

30.00

positive sequence reactance reach, Ph-G,


zone 1

R1PZG1

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive sequence resistive reach, Ph-G, zone


1

X0Z1

0.01 - 9000.00

Ohm/p

0.01

100.00

Zero sequence reactance reach, zone 1

R0Z1

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero sequence resistive reach, zone 1

Table continues on next page

272

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Step

Default

RFPPZ1

Values (Range)
0.01 - 9000.00

Unit
Ohm/l

0.01

30.00

Description
Fault resistance reach, Ph-Ph, zone 1

RFPGZ1

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 1

tPPZ1

0.000 - 60.000

0.001

0.000

Time delay to trip, Phase-Phase, zone 1

tPGZ1

0.000 - 60.000

0.001

0.000

Time delay to trip, Ground-Earth, zone 1

IMinOpPPZ1

10 - 6000

%IB

10

Minimum operate ph-ph current for PhasePhase loops, zone 1

IMinOpPGZ1

5 - 6000

%IB

10

minimum operate phase current for phaseground loops. zone 1

OpModePPZ2

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 2

OpModePGZ2

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 2

X1Z2

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive sequence reactance reach, zone 2

R1Z2

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive sequence reactance reach, zone 2

X0Z2

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero sequence reactance reach, zone 2

R0Z2

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero sequence reactance reach, zone 2

RFPPZ2

0.01 - 9000.00

Ohm/l

0.01

30.00

Zero sequence reactance reach, zone 2

RFPGZ2

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-g, Zone 2

tPPZ2

0.000 - 60.000

0.001

0.400

Time delay to trip, Phase-Phase, zone 2

tPGZ2

0.000 - 60.000

0.001

0.400

Time delay to trip, Phase-Ground, zone 2

IMinOpPPZ2

10 - 6000

%IB

10

Time delay to trip, Phase-Phase, zone 2

IMinOpPGZ2

5 - 6000

%IB

10

Minimum operate phase current for phase ground loops, zone 2

OpModePPZ3

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 3

OpModePGZ3

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 3

DirModeZ3

Non-directional
Forward
Reverse

Forward

Time delay to trip, Phase-Phase, zone 2

X1Z3

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive sequence reactance reach, zone 3

R1Z3

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive sequence resistive reach, zone 3

X0Z3

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero sequence reactance reach, zone 3

R0Z3

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero sequence resistive reach, zone 3

RFPPZ3

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone 3

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

273

Section 7
Impedance protection

Name

Values (Range)

1MRK 502 066-UUS A

Step

Default

RFPGZ3

0.01 - 9000.00

Unit
Ohm/l

0.01

100.00

Description
Fault resistance reach, Ph-G, zone 3

tPPZ3

0.000 - 60.000

0.001

0.800

Time delay to trip, Phase-Phase, zone 3

tPGZ3

0.000 - 60.000

0.001

0.800

Time delay to trip, Phase-Ground, zone 3

IMinOpPPZ3

10 - 6000

%IB

10

Minimum operate ph-ph current for PhasePhase loops, zone 3

IMinOpPGZ3

5 - 6000

%IB

10

Minimum operate phase current for phaseground loops, zone 3

OpModePPZ4

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 4

OpModePGZ4

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 4

DirModeZ4

Non-directional
Forward
Reverse

Forward

Direction of zone 4 (which will be the Fw


direction of zone 4)

X1Z4

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive sequence reactance reach, zone 4

R1Z4

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive sequence resistive reach, zone 4

X0Z4

0.01 - 9000.00

Ohm/p

0.01

120.00

Positive sequence resistive reach, zone 4

R0Z4

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero sequence resistive reach, zone 4

RFPPZ4

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone 4

RFPEZ4

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 4

tPPZ4

0.000 - 60.000

0.001

1.200

Time delay to trip, Phase-Phase, zone 4

tPGZ4

0.000 - 60.000

0.001

1.200

Time delay to trip, Phase-ground, zone 4

IMinOpPPZ4

10 - 6000

%IB

10

How start of trip delay timers should be linked


for zone 4

IMinOpPGZ4

5 - 6000

%IB

10

Minimum operate phase current for phaseground loops, zone 4

OpModePPZ5

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 5

OpModePGZ5

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 5

DirModeZ5

Non-directional
Forward
Reverse

Forward

Direction of zone 5 (which will be the Fw


direction of zone 5)

X1Z5

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive sequence reactance reach, zone 5

R1Z5

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive sequence resistive reach, zone 5

X0Z5

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero sequence reactance reach, zone 5

Table continues on next page


274

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Values (Range)

Step

Default

R0Z5

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero sequence resistive reach, zone 5

RFPPZ5

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone 5

RFPEZ5

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 5

tPPZ5

0.000 - 60.000

0.001

1.600

Time delay to trip, Phase-Phase, zone 5

tPGZ5

0.000 - 60.000

0.001

1.600

Time delay to trip, Phase-ground, zone 5

IMinOpPPZ5

10 - 6000

%IB

10

Minimum operate ph-ph current for PhasePhase loops, zone 5

IMinOpPGZ5

5 - 6000

%IB

10

Minimum operate phase current for phaseground loops, zone 5

OpModePPZRV

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone RV

OpModePGZRV

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone RV

tPPZRV

0.000 - 60.000

0.001

0.000

Time delay to trip, Phase-Phase, zone RV

tPEZRV

0.000 - 60.000

0.001

0.000

Time delay to trip, Phase -Ground, zone RV

IMinOpPPZRV

10 - 6000

%IB

10

Minimum operate ph-ph current for PhasePhase loops, zone RV

IMinOpPGZRV

5 - 6000

%IB

10

Minimum operate phase current for phaseground loops, zone RV

X1ZRV

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive sequence reactance reach, zone RV

R1ZRV

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive sequence resistive reach, zone RV

X0ZRV

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero sequence reactance reach, zone RV

R0ZRV

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero sequence resistive reach, zone RV

RFPPZRV

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone RV

RFPGZRV

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach Ph-G. zone RV

Step

Default

Table 116:
Name

Unit

Description

ZMFPDIS (21) Group settings (advanced)


Values (Range)

Unit

Description

ZoneLinkPU

Phase Selection
1st starting zone

Phase Selection

Select. of start source for all ZoneLinked trip


delay timers

3I0Enable_PG

5 - 400

%MaxIP
h

400

3I0 limit for releasing Phase-to-Ground


measuring loops

TimerModeZ1

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/Off setting for Ph-Ph and Ph-G trip output,


zone 1

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

275

Section 7
Impedance protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

TimerLinksZ1

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 1

TimerModeZ2

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip output,


zone 2

TimerLinksZ2

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 2

TimerModeZ3

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip output,


Zone 3

TimerLinksZ3

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 3

TimerLinksZ4

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip output


Zone 4

TimerLinksZ4

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 4

TimerModeZ5

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip output,


zone 5

TimerLinksZ5

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 5

TimerModeZRV

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip outout,


zone RV

TimerLinksZRV

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone RV

276

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 117:
Name

ZMFPDIS (21) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

ZDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

ZMax

0.0 - 5000.0

Ohm

0.1

1500.0

Maximum value in ohm

ZRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

ZAngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Table 118:
Name

ZMFPDIS (21) Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ZZeroDb

0 - 100000

m%

100

Zero point clamping

ZHiHiLim

0.0 - 5000.0

Ohm

0.1

1350.0

High High limit in ohm

ZHiLim

0.0 - 5000.0

Ohm

0.1

1200.0

High limit in ohm

ZLowLim

0.0 - 5000.0

Ohm

0.1

300.0

Low limit in ohm

ZLowLowLim

0.0 - 5000.0

Ohm

0.1

150.0

Low Low limit in ohm

ZMin

0.000 - 5000.000

Ohm

0.001

0.005

Minimum value in ohm

ZLimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

ArgLdMinEd2

5 - 70

Deg

Minimum settable angle determining the load


impedance area, for 61850 Ed.2 settings

ArgLdMaxEd2

5 - 70

Deg

70

Maximum settable angle determining the load


impedance area, for 61850 Ed.2 settings

RLdFwMinEd2

0.01 - 5000.00

Ohm/p

0.01

0.01

Minimum settable resistance determining the


load impedance area, for 61850 Ed.2 settings

RLdFwMaxEd2

0.01 - 5000.00

Ohm/p

0.01

5000.00

Maximum settable resistance determining the


load impedance area, for 61850 Ed.2 settings

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

277

Section 7
Impedance protection
7.5.6

1MRK 502 066-UUS A

Monitored data
Table 119:
Name

278

ZMFPDIS (21) Monitored data


Type

Values (Range)

Unit

Description

A_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase A

B_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase B

C_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase C

ABDir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in loop AB

BCDIR

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in looop BC

CADir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in loop CA

Aph_R

REAL

Ohm

Resistance in phase A

Aph_X

REAL

Ohm

Reactance in phase A

Bph_R

REAL

Ohm

Resistance in phase B

Bph_X

REAL

Ohm

Reactance in phase B

Cph_R

REAL

Ohm

Resistance in phase C

Cph_X

REAL

Ohm

Reactance in phase C

ZAIMAG

REAL

Ohm

ZA Amplitude, magnitude of
instantaneous value

ZAANGIM

REAL

deg

ZA Angle, magnitude of
instantaneous value

ZBIMAG

REAL

Ohm

ZB Amplitude, magnitude of
instantaneous value

ZBANGIM

REAL

deg

ZB Angle, magnitude of
instantaneous value

ZCIMAG

REAL

Ohm

ZC Amplitude, magnitude of
instantaneous value

ZCANGIM

REAL

deg

ZC Angle, magnitude of
instantaneous value

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.5.7

Operation principle
Settings, input and output names are sometimes mentioned in the following text without
its zone suffix (i.e. BLKZx instead of BLKZ3) when the description is equally valid for
all zones.

7.5.7.1

Filtering
Practically all voltage, current and impedance quantities used within the ZMFPDIS
function are derived from fundamental frequency phasors filtered by a half cycle filter.
The phasor filter is frequency adaptive in the sense that its coefficients are changed based
on the estimated power system frequency.
A half cycle filter will not be able to reject both even and odd harmonics. So, while odd
harmonics will be completely attenuated, accuracy will be affected by even harmonics.
Even harmonics will not cause the distance zones to overreach however; instead there will
be a slightly variable underreach, on average in the same order as the magnitude ratio
between the harmonic and fundamental component.

7.5.7.2

Distance measuring zones


The execution of the different fault loops within the IED are of full scheme type, which
means that ground fault loop for phase-to-ground faults and phase-to-phase faults for
forward and reverse faults are executed in parallel.
Figure 108 presents an outline of the different measuring loops for the six distance zones.
A-G

B-G

C-G

A- B

B-C

C-A

Zone 1

A-G

B-G

C-G

A- B

B-C

C-A

Zone 2

A-G

B-G

C-G

A- B

B-C

C-A

Zone 3

A-G

B-G

C-G

A- B

B-C

C-A

Zone 4

A-G

B-G

C-G

A- B

B-C

C-A

Zone 5

A-G

B-G

C-G

A- B

B-C

C-A

Zone 6

ANSI05000458-2-en.vsd
ANSI05000458 V2 EN

Figure 108:

The different measuring loops at phase-to-ground fault and phase-tophase fault

Each distance protection zone performs like one independent distance protection function
with six measuring elements.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

279

Section 7
Impedance protection

1MRK 502 066-UUS A

Transients from CVTs may have a significant impact on the transient overreach of a
distance protection. At the same time these transients can be very diverse in nature from
one type to the other; in fact, more diverse than can be distinguished by the algorithm itself
in the course of a few milliseconds. So, a setting (CVTtype) is introduced in order to inform
the algorithm about the type of CVT applied and thus providing the advantage of knowing
how performance should be optimized, even during the first turbulent milliseconds of the
fault period.
There are two types of CVTs from the function point of view, the passive and the active
type, which refers to the type of ferro-resonance suppression device that is employed. The
active type requires more rigorous filtering which will have a negative impact on operate
times. However, this will be evident primarily at higher source impedance ratios (SIRs),
SIR 5 and above, or close to the reach limit.
The IEC 60044-5 transient classification is of little or no use in relation to this. It is not
primarily the damping of transients that is important; it is the frequency content of the
transients that is decisive, i.e. how difficult it is to filter out the specific frequency. So,
even if two CVTs, one passive and the other active type, comply with the same transient
class, the active type requires more extensive filtering in order to avoid transient
overreach.
To avoid overreach and at the same time achieve fast operate times, a supplementary
circular characteristic is implemented. A circular characteristic exists for every measuring
loop and quadrilateral/mho characteristic. There are no specific reach settings for this
circular zone. It uses the normal quadrilateral/mho zone settings to determine a reach that
will be appropriate. This implies that the circular characteristic will always have
somewhat shorter reach than the quadrilateral/mho zone.

7.5.7.3

Phase-selection element
The operation of the phase-selection element is primarily based on current change criteria
(i.e. delta quantities) with significantly increased dependability. Naturally, there is also a
phase selection criterion operating in parallel which bases its operation only on voltage
and current phasors.
This continuous criteria will, in the vast majority of cases, operate in parallel and carry on
the fault indication after the current change phase has ended. Only in some particularly
difficult faults on heavily loaded lines, the continuous criteria might not be sufficient, for
example, when the estimated fault impedance resides within the load area defined by the
load encroachment characteristic. In this case, the indication will be restricted to a pulse
lasting for one or two power system cycles.
The phase-selection element can, owing to the current change criteria, distinguish faults
with minimum influence from load and fault impedance. In other words, it is not restricted
by a load encroachment characteristic during the current change phase. This significantly

280

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

improves performance for remote phase-to-ground faults on heavily loaded lines. One
exception, however, are three-phase faults to which the load encroachment characteristic
always has to be applied in order to distinguish fault from load.
Phase-to-phase-ground faults (also called double ground faults) will practically always
activate phase-to-phase zone measurements. This is a substantial difference compared to
the previous phase selection function (FDPSPDIS). Measurement in two phase-to-ground
loops at the same time is associated with so-called simultaneous faults: two ground faults
at the same time, one each on the two circuits of a double line, or when the zero sequence
current is relatively high due to a source with low Z0/Z1 ratio. In fact, in these situations
zone measurement will be released both for the related phase-to-ground loops and the
phase-to-phase loop simultaneously. On the other hand, simultaneous faults closer to the
remote bus will gradually take on the properties of a phase-to-phase-ground fault and the
function will eventually use phase-to-phase zone measurements also here.
In cases where the fault current infeed is more or less completely of zero sequence nature
(all phase currents in phase), the measurement will be performed in the phase-to-ground
loops only for a phase-to-phase-ground fault.
However, should it be desirable to use phase-to-ground (and only phase-to-ground) zone
measurement for phase-to-phase-ground faults, there is a setting 3I0Enable_PG that can
be lowered from its excessive default value to the level above which phase-to-ground
measurement should be activated.

7.5.7.4

Directional element
Several criteria are employed when making the directional decision. The basis is provided
by comparing a positive sequence based polarizing voltage with phase currents. For extra
security, especially in making a very fast decision, this method is complemented with an
equivalent comparison where, instead of the phase current, the change in phase current is
used. Moreover, a basic negative sequence directional evaluation is taken into account as
a reliable reference during high load condition. Finally, zero sequence directional
evaluation is used whenever there is more or less exclusive zero sequence in-feed.
Fundamentally, the directional sectors that represent forward direction, one per measuring
loop, are defined by the following equations.
-15<arg

PolA

< 120

(Equation 62)

ANSIEQUATION15059 V1 EN

-15<arg

PolAB

< 120

AB

ANSIEQUATION15060 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

(Equation 63)

281

Section 7
Impedance protection

1MRK 502 066-UUS A

Where:
VPolA

is the polarizing voltage for phase A.

IA

is the phase current in phase A.

VPolAB

is the polarizing voltage difference between phase A and B (B lagging A).

IAB

is the current difference between phase A and B (B lagging A).

The corresponding reverse directional sectors range from 165 to -60 degrees.
Since the polarizing voltage is also used for the Mho distance characteristics, the
magnitude of the voltage is just as interesting as the phase. If there are symmetrical
conditions and the measured per phase positive sequence voltage magnitude is above 75%
of the base voltage before the fault, the pre-fault magnitude will be memorized and used
as long as there is a fault. The phase angle however will only be memorized (locked) for
75 ms at a time, not to lose synchronism with the real system voltage.
Should the positive sequence voltage drop below 2% of the base voltage, it will be
considered invalid. In this situation, directional signals and pickups from Mho elements
will be sealed-in and kept static as long as there is a fault.
For ZMFCPDIS, when option SeriesComp is chosen for OperationSC, the voltages of
faulty phases will be discarded in order not to affect the polarizing voltage with voltage
reversal.

7.5.7.5

Fuse failure
The ZMFPDIS function has to be blocked by an additional function like the Fuse failure
supervision (FUFSPVC) or an equivalent external device. Typically, the binary input
VTSZ is used for this purpose.
A built-in supervision feature within high-speed distance protection itself, based on phase
current change, will ensure that the FUFSPVC blocking signal is received in time.
Namely, an intentional time delay will be introduced if no current magnitude change
greater than 5% of IBase has been detected for any of the three phase currents.

7.5.7.6

Power swings
There is need for external blocking of the ZMFPDIS function during power swings, either
from the Power Swing Blocking function (ZMRPSB) or an external device.

282

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.5.7.7

Measuring principles
Quadrilateral characteristic
ZMFPDIS implements quadrilateral and mho characteristic in all the six zones separately.
Set OpModePEZx or OpModePPZx to Quadrilateral, to choose particular measuring loop
in a zone to work as quadrilateral distance protection.
All ZMFPDIS zones operate according to the non-directional impedance characteristics
presented in figure 110 and figure 109. The phase-to-ground characteristic is given in
ohms-per-loop domain while the phase-to-phase characteristic is given in ohms-perphase domain.

RFPP

(Ohm/phase)

R1PP

RFPP

X 0 PE - X 1RVPE
XNRV =XX00PE
PG- 1RVPG
X3
1XRVPE
XNRV
=
XNRV =
33
11FWPE
XX
-X-1X
X00PE
0PE
PG
XFWPE
FWPG
XNFW
XNFW
XNFW===
3
3 3

X1PP

j
R (Ohm/phase)

RFPP

RFPP

X1PP

RFPP
2

R1PP

RFPP
2

IEC11000416-1-en.vsd

IEC11000416 V1 EN

Figure 109:

ZMFPDIS Characteristic for phase-to-phase measuring

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

283

Section 7
Impedance protection

1MRK 502 066-UUS A

X (Ohm/loop)

(Ohm/loop)

ANSI11000415-1-en.vsd

ANSI11000415 V1 EN

Figure 110:

ZMFPDIS Characteristic for phase-to-ground measuring, ohm/loop


domain

The faulty loop in relation to the fault type can be presented as in figure 111. The main
intention with this illustration is to make clear how the fault resistive reach should be
interpreted and set. Note in particular that the setting RFPP always represents the total
fault resistance of the loop, regardless the fact that the fault resistance (arc) may be divided
into parts like for three-phase or phase-to-phase faults. The R1 + jX1 represent the positive
sequence impedance from the measuring point to the fault location.

284

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

IA

R1 + j X1

Phase-to-ground
element

VA

Phase-to-ground
fault in phase A

RFPG

(Arc + tower
resistance)
N
IG

(R0-R1)/3 +
j (X0-X1)/3 )

IA

R1 + j X1

Phase-to-phase
element A-B

VA
Phase-to-phase
fault in phase
A-B

RFPP
IB

(Arc resistance)

VB
R1 + j X1

IA
Three-phase
fault or Phase-tophase-ground fault

R1 + j X1

0.5RFPP

R1 + j X1

0.5RFPP

VA

Phase-to-phase
element A-C

IC
VC

ANSI11000419-3-en.vsd
ANSI11000419 V3 EN

Figure 111:

Fault loop model

Mho characteristic
ZMFPDIS implements quadrilateral and mho characteristic in all the six zones separately.
Set OpModePEZx or OpModePPZx setting to Mho or Offset, to choose a particular
measuring loop in a zone to work as mho (or Offset Mho) distance protection.
Zones 3 to 5 can be selected to be either forward or reverse with positive sequence
polarized mho characteristic; alternatively self polarized offset mho characteristics. The
operating characteristic is in accordance to figure 65 where zone 5 is selected offset mho.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

285

Section 7
Impedance protection

1MRK 502 066-UUS A

X
Z4

Z3
ZS=0

Z2
Z1
Z5

R
R
ZS=Z1

ZRV

ZS=2Z1

IEC15000056-1-en.vsdx

IEC15000056 V1 EN

Figure 112:

Mho, offset mho characteristics and the source impedance influence on


the mho characteristic

The mho characteristic has a dynamic expansion due to the source impedance. Instead of
crossing the origin, as for the mho to the left of figure 65, which is only valid where the
source impedance (Zs) is zero, the crossing point is moved to the coordinates of the
negative source impedance given an expansion of the circle shown to the right of figure
65. Z1 denotes the complex positive sequence impedance.
The magnitude of the polarizing voltage is determined completely by the positive
sequence voltage magnitude from before the fault. This will give a somewhat less
dynamic expansion of the mho circle during faults. However, if the source impedance is
high, the dynamic expansion of the mho circle might lower the security of the function too
much with high loading and mild power swing conditions.

Basic operation characteristics


In ZMFPDIS, each zone measurement loop characteristic can be set to mho characteristic
or offset mho characteristic by setting zxOpModePE or zxOpModePP (where x is 1-5
depending on selected zone).
ZMFPDIS fixes zone 1 and 2 in Forward mode and zone RV in Reverse mode. Zone 3-5
can be set to Non-directional, Forward or Reverse by setting the parameter DirModeZx
(where x is 3-5 depending on selected zone).
If DirModeZx (where x is 3-5 depending on selected zone) is selected as Non-directional,
the directional element will not have any effect on the measurement loop and operation of
the function. When DirModeZx (where x is 3-5 depending on selected zone) is selected as
Forward or Reverse, directional lines are introduced. Information about the directional

286

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

lines is given from the directional element. Basic Mho characteristics with different mode
settings are indicated in figure 113.

OpModePP/PEZx = Mho
Zone 1, Zone 2 and
DirModeZ3-5 = Forward

OpModePP/PEZx = Mho
Zone RV and
DirModeZ3-5 = Reverse

OpModePP/PEZx = Offset
Zone 1, Zone 2 and
DirModeZ3-5 = Forward

OpModePP/PEZx = Mho
Only Zone 3-5
DirModeZ3-5 = Non-directional

OpModePP/PEZx = Offset
Zone RV and
DirModeZ3-5 = Reverse

OpModePP/PEZx = Offset
Only Zone 3-5
DirModeZ3-5 = Non-directional
IEC15000055-1-en.vsdx

IEC15000055 V1 EN

Figure 113:

Mho characteristics

For each zone, the impedance is set in cartesian coordinates (resistance and reactance)
which is the same as for quadrilateral characteristic.
The ZMFPDIS function has only one set of reach setting so the reverse will be the same
as for the forward reach, meaning that the non-directional offset mho characteristic will
always be centered around the origin. In detail, for Zone 1, the resistive and reactance
reaches for phase-to-earth fault and phase-to-phase fault are set individually using the
settings R1PPZ1, X1PPZ1, R1PEZ1, X1PEZ1, X0Z1 and R0Z1. In Zone 2-5 and Zone RV,

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

287

Section 7
Impedance protection

1MRK 502 066-UUS A

the same zone reach settings are used for phase-to-earth fault and phase-to-phase (R1Zx,
X1Zx, X0Zx and R0Zx, x=2-5 or RV).

Theory of operation
The mho algorithm is based on the phase comparison of an operating phasor and a
polarizing phasor. When the operating phasor leads the reference polarizing phasor by 90
degrees or more, the function operates and gives a trip output.
Phase-to-phase fault
Mho
The plain Mho circle has the characteristic as in figure 66. The condition for deriving the
angle is according to equation 64.

( )

b = arg VAB - I AB Z 1set - arg V pol

(Equation 64)

ANSIEQUATION15027 V1 EN

where

V AB

is the voltage vector difference between phases A and B

EQUATION1790ANSI V1 EN

I AB

is the current vector difference between phases A and B

EQUATION1791ANSI V1 EN

Z 1set

is the positive sequence impedance setting for phase-to-phase fault in zone direction

For Zone 1,

Z 1set = R1PPZ 1 + j X 1PPZ 1


(Equation 65)

IECEQUATION15011 V1 EN

where

R1PPZ1

is the positive sequence resistive reach for phase-to-phase fault for zone 1

X1PPZ1

is the positive sequence reactance reach for phase-to-phase fault for zone 1

For Zone 2-5 and RV

Z 1set = R1Zx + j X 1Zx


IECEQUATION15012 V1 EN

288

(Equation 66)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

where

R1Zx

is the positive sequence resistive reach for zone x (x=2-5 and RV)

X1Zx

is the positive sequence reactance reach for zone x (x=2-5 and RV)

Vpol

is the polarizing voltage

Operation occurs if 90270

I AB jX

I L1L 2 Z1set

Vcomp VAB I AB Z1set

VAB
V pol

I AB R
ANSI15000060-1-en.vsdx
ANSI15000060 V1 EN

Figure 114:

Simplified mho characteristic and vector diagram for phase A-to-B fault

Offset Mho
The characteristic for offset mho is a circle where two points on the circle are given by the
two vectors Z 1set and Z 1RVset where Z 1set and Z 1RVset are settable through the
resistance and reactance settings in forward and reverse directions.
The condition for operation at phase-to-phase fault is that the angle between the two
compensated voltages is greater than or equal to 90 (figure 115). The angle will be 90
for fault location on the boundary of the circle.
The angle for A to B fault can be defined according to equation below.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

289

Section 7
Impedance protection

1MRK 502 066-UUS A

V I Z1
AB
AB
set
= arg
VAB I AB Z 1RVset

(Equation 67)

ANSIEQUATION15008 V1 EN

where

Z 1RVset

is the positive sequence impedance setting for phase-to-phase fault opposite to zone direction and is
defined as

For Zone 1,

Z 1RVset = R1PPZ 1 + j X 1PPZ 1


IECEQUATION15015 V1 EN

For Zone 2-5 and RV,

Z 1RVset = R1Zx + j X 1Zx


IECEQUATION15016 V1 EN

290

(Equation 68)

(Equation 69)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

I AB jX
Vcomp1 VAB I AB Z 1set

I AB Z 1set

VAB
Vcomp 2 VAB ( I AB Z 1RVset )

I AB Z 1RVset

I AB R
ANSI15000058-1-en.vsdx

ANSI15000058 V1 EN

Figure 115:

Simplified offset mho characteristic and voltage vector for phase A to B


fault

Operation occurs if 90270 .


Phase-to-ground fault
The measuring of earth faults uses earth return compensation applied in a conventional
way. The compensation voltage is derived by considering the influence from the earth
return path.
Compensation for earth return path for faults involving earth is done by setting the positive
and zero sequence impedance of the line. It is known that the ground compensation factor
KN is,

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

291

Section 7
Impedance protection

1MRK 502 066-UUS A

KN =

Z 0set Z 1set
3 Z 1set

IECEQUATION15017 V1 EN

Z 0set = R 0Zx + j X 0 Zx
IECEQUATION15018 V1 EN

For Zone 1,

Z 1set = R1PEZ 1 + j X 1PEZ 1


IECEQUATION15019 V1 EN

For Zone 2-5 and RV,

Z 1set = R1Zx + j X 1Zx


IECEQUATION15020 V1 EN

(Equation 70)

where
is the complex zero sequence impedance of the line in /phase

Z 0set

is the complex positive sequence impedance of the line in /phase

Z 1set
R1PEZ1

is the positive sequence resistive reach of the line in /phase for


phase-to-ground fault for zone 1

X1PEZ1

is the positive sequence reactance reach of the line in /phase for


phase-to-ground fault for zone 1

R0Zx

is the zero sequence resistive reach of the line in /phase for zone x
(x=2-5, or RV)

X0Zx

is the zero sequence reactance reach of the line in /phase for zone
x (x=2-5, or RV)

For an earth fault in phase A, the angle between the compensation voltage and the
polarizing voltage Vpol is,

292

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

= arg [VA ( I A + 3I 0 K N ) Z 1set ] arg(V pol )


(Equation 71)

ANSIEQUATION15021 V1 EN

where

VA
IA

is the phase voltage in faulty phase A


is the phase current in faulty phase A

3I0

is the zero-sequence current in faulty phase A

Z 1set

is the complex positive sequence impedance of the line in /phase for


phase-to-ground fault in zone direction

Vpol

is the polarizing voltage for phase A

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

293

Section 7
Impedance protection

1MRK 502 066-UUS A

IAjX

Vcomp VA ( I A 3I 0 K N ) Z1set

3I 0 K N Z1set

VA

I A Z1set

V pol

IAR
ANSI15000059-1-en.vsdx

ANSI15000059 V1 EN

Figure 116:

Simplified offset mho characteristic and vector diagram for phase A-toground fault

Operation occurs if 90270.


Offset mho
The condition for operation of offset mho at phase-to-earth fault is that the angle
between the two compensated voltages is equal to or greater than 90, see figure 71. The
angle will be 90 for fault location on the boundary of the circle.

= arg VA ( I A + 3I 0 K N ) Z 1set arg VA ( I A + 3I 0 K N Z 1RVset ]

(Equation 72)

ANSIEQUATION15022 V1 EN

where

Z 1RVset

294

is the complex positive sequence impedance of the line in /phase for


phase-to-ground fault opposite to zone direction and is defined as,

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

For Zone 1,

Z 1RVset = R1PEZ 1 + j X 1PEZ 1


(Equation 73)

IECEQUATION15025 V1 EN

For Zone 2-5 and


RV,

Z 1RVset = R1Zx + j X 1Zx


(Equation 74)

IECEQUATION15026 V1 EN

IA jX

Vcomp1 VA ( I A 3I 0 K N ) Z1set

( I A 3I 0 K N ) Z1set
VA

Vcomp 2 VA ( I A 3I 0 K N ) Z1RVset )

( I A 3I 0 K N ) Z1RVset

IA R

ANSI15000057-1-en.vsdx

ANSI15000057 V1 EN

Figure 117:

Simplified offset mho characteristic and voltage vector for phase A-toground fault

Operation occurs if 90 270 .

7.5.7.8

Load encroachment
In some cases the measured load impedance might enter the set zone characteristic
without any fault on the protected line. This phenomenon is called load encroachment and
it might occur when an external fault is cleared and high emergency load is transferred
onto the protected line. The effect of load encroachment is illustrated on the left in

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

295

Section 7
Impedance protection

1MRK 502 066-UUS A

figure118. The entrance of the load impedance inside the characteristic is of course not
desirable and the way to handle this with conventional distance protection is to consider
this with the resistive reach settings, that is, to have a security margin between the distance
zone characteristic and the minimum load impedance. Such a solution has the drawback
that it will reduce the sensitivity of the distance protection, that is, the ability to detect
resistive faults.
The IED has a built in feature which shapes the characteristic according to the
characteristic shown in figure118. The load encroachment algorithm will increase the
possibility to detect high fault resistances, especially for phase-to-ground faults at remote
line end. For example, for a given setting of the load angle LdAngle, the resistive blinder
for the zone measurement can be set according to figure118 affording higher fault
resistance coverage without risk for unwanted operation due to load encroachment.
Separate resistive blinder settings are available in forward and reverse direction.
The use of the load encroachment feature is essential for long heavily loaded lines, where
there might be a conflict between the necessary emergency load transfer and necessary
sensitivity of the distance protection. The function can also preferably be used on heavy
loaded, medium long lines. For short lines, the major concern is to get sufficient fault
resistance coverage. Load encroachment is not a major problem. See section "".
X
Zm

Zm
ZL
Load impedance area in
forward direction
R

LdAngle
LdAngle
R
LdAngle

LdAngle
RldRev

RLdFwd

ANSI05000495_2_en.vsd
ANSI05000495 V2 EN

Figure 118:

Load encroachment phenomena and shaped load encroachment


characteristic

[1]

[1] RLdRv=RLdRvFactor*RLdFw
296

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.5.7.9

Simplified logic schemes


PHSA, PHSB,...PHSCA are internal binary logical signals from the Phase-selection
element. They correspond directly to the six loops of the distance zones and determine
which loops should be released to possibly issue a pickup or a trip.
FWA, FWB,...FWCA and RVA, RVB,...RVCA are the internal binary signals from the
Directional element. An FW signal is activated if the criteria for a forward fault or load is
fulfilled for its particular loop. The equivalent applies to the reverse (RV) signals.
The internal input 'IN present' is activated if the residual current (3I0) exceeds 10% of the
maximum phase current magnitude and at the same time is above 5% of IBase. However,
if current transformer saturation is detected, this criterion is changed to residual voltage
(3V0) exceeding 5% of VBase/sqrt(3) instead.
FWD(n & mn)

DIR(n & mn)Z1

FWD(n & mn)

DIR(n & mn)Z2

REV(n & mn)

DIR(n & mn)ZRV


DirModeZ3-5

TRUE (1)
FWD(n & mn)
REV(n & mn)

Non-directional
Forward
Reverse

DIR(n & mn)Z3-5

ANSI12000137-1-en.vsd
ANSI12000137 V1 EN

Figure 119:

Connection of directional signals to Zones

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

297

Section 7
Impedance protection

1MRK 502 066-UUS A

PGZx

OR

ZMAZx
PHSA
DIRAZx
ZMBZx
PHSB
DIRBZx
ZMCZx
PHSC
DIRCZx

AND
AND
AND
AND

AZx

OR

AND
AND

ZMABZx
PHSAB
DIRABZx
ZMLBCZx
PHSBC
DIRBCZx
ZMCAZx
PHSCA
DIRCAZx

BZx

OR

AND
AND

OR

AND

CZx

AND
AND
AND
OR

OR

PPZx
NDZx

ANSI12000140-1-en.vsd
ANSI12000140 V1 EN

Figure 120:

298

Intermediate logic

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

TimerModeZx =
Enable Ph-Ph,
Ph-G

AND

PPZx

AND

PGZx

BLOCK
LOVBZ
BLKZx
BLKTRZx

OR

AND

AND

TZx

OR
OR

AND

tPPZx
0

AND

OR

TimerLinksZx

OR

ZoneLinkStart

PUPHS

tPPZx
0

OR

Phase Selection
1st pickup zone

LNKZ1
LNKZ2
LNKZRV
OR
LNKZ3
LNKZ4
LNKZ5

LoopLink (tPP-tPG)
LoopLink & ZoneLink
no links

FALSE (0)
AND

LNKZx

TimerLinksZx =
LoopLink & ZoneLink

ANSI12000139-2-en.vsdx

ANSI12000139 V2 EN

Figure 121:

Logic for linking of timers

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

299

Section 7
Impedance protection

1MRK 502 066-UUS A

TZx

0
15 ms

BLKTRZx
BLOCK
LOVBZ
BLKZx

TRIPZx

AND

OR

AND

OR

AND
AND

AZx
BZx
CZx
PPZx
PGZx

OR

NDZx

0
15 ms

AND

0
15 ms

AND

0
15 ms

AND

0
15 ms

AND

0
15 ms

AND

TR_A_Zx
TR_B_Zx
TR_B_Zx
PU_A_Zx
PU_B_Zx
PU_C_Zx
PU_Zx
PU_ND_Zx

ANSI12000138-1-en.vsd
ANSI12000138 V1 EN

Figure 122:

300

Pickup and trip outputs

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

0
15 ms

AND

OR

0
15 ms

AND

OR

0
15 ms

AND

OR

0
15 ms

AND

0
15 ms

AND

OR

PHSA
PHSB

PHG_FLT

PHSC
PHSAB
PHSBC
PHSCA
OR

BLOCK
LOVBZ

PHPH_FLT

OR

OR

PU_ND
PU_PHS
ANSI12000133-1-en.vsd

ANSI12000133 V1 EN

Figure 123:

Additional pickup outputs 1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

301

Section 7
Impedance protection

1MRK 502 066-UUS A

PHSA
FWA
PHSB
FWB
PHSC
FWC

AND
AND

OR

0
15 ms

AND

OR

0
15 ms

AND

OR

0
15 ms

AND

FWD_A

AND

PHSAB
FWAB
PHSBC
FWBC
PHSCA
FWCA

AND
AND

FWD_B

FWD_C

AND
OR

IN present

BLOCK
LOVBZ

AND

=1

FWD_G
FWD_1PH

OR
=2

=3

FWD_2PH

FWD_3PH

ANSI12000134-1-en.vsd
ANSI12000134 V1 EN

Figure 124:

302

Additional pickup outputs 2

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

PHSA
RVA
PHSB
RVB
PHSC
RVC

AND
AND

OR

0
15 ms

AND

OR

0
15 ms

AND

OR

0
15 ms

AND

REV_A

AND

PHSAB
RVAB
PHSBC
RVBC
PHSCA
RVCA

AND
AND

REV_B

REV_C

AND
OR

IN present
BLOCK
LOVBZ

AND

REV_G

OR
ANSI12000141-1-en.vsd

ANSI12000141 V1 EN

Figure 125:

7.5.7.10

Additional pickup outputs 3

Measurement
Measurement supervision
The protection, control, and monitoring IEDs have functionality to measure and further
process information for currents and voltages obtained from the pre-processing blocks.
The number of processed alternate measuring quantities depends on the type of IED and
built-in options.
The information on measured quantities is available for the user at different locations:

Locally by means of the local HMI


Remotely using the monitoring tool within PCM600 or over the station bus
Internally by connecting the analog output signals to the Disturbance Report function

Zero point clamping


Measured value below zero point clamping limit is forced to zero. This allows the noise
in the input signal to be ignored. The zero point clamping limit is a setting (XZeroDb
where X equals Z).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

303

Section 7
Impedance protection

1MRK 502 066-UUS A

Continuous monitoring of the measured quantity


Users can continuously monitor the measured quantity available in the function block by
means of four defined operating thresholds, see figure 126. The monitoring has two
different modes of operating:

Overfunction, when the measured current exceeds the High limit (XHiLim) or Highhigh limit (XHiHiLim) pre-set values
Underfunction, when the measured current decreases under the Low limit (XLowLim)
or Low-low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 126.

Y
X_RANGE = 3
High-high limit

X_RANGE= 1

Hysteresis

High limit
X_RANGE=0

X_RANGE=0
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4

IEC05000657-2-en.vsdx

IEC05000657 V2 EN

Figure 126:

Presentation of operating limits

Each analog output has one corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: Highhigh limit exceeded, 2: below Low limit and 4: below Low-low limit). The output may be
connected to a measurement expander block (XP (RANGE_XP)) to get measurement
supervision as binary signals.
The logical value of the functional output signals changes according to figure 126.
The user can set the hysteresis (XLimHyst), which determines the difference between the
operating and reset value at each operating point, in wide range for each measuring
channel separately. The hysteresis is common for all operating values within one channel.

304

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Actual value of the measured quantity


The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting of the
value to the higher levels depends on the selected reporting mode. The following basic
reporting modes are available:

Cyclic reporting (Cyclic)


Magnitude dead-band supervision (Dead band)
Integral dead-band supervision (Int deadband)

Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of magnitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.

Value Reported
(1st)

Value Reported

Value Reported

Value Reported

Value Reported

Y3
Y2

Y4

Y1

Y5

(*)Set value for t: XDbRepInt

t (*)

Value 5

Value 4

t (*)

Value 3

t (*)

Value 2

Value 1

t (*)

IEC05000500-2-en.vsdx

IEC05000500 V2 EN

Figure 127:

Periodic reporting

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

305

Section 7
Impedance protection

1MRK 502 066-UUS A

Magnitude dead-band supervision


If a measuring value is changed, compared to the last reported value, and the change is
larger than the Y pre-defined limits that are set by user (UDbRepIn), then the measuring
channel reports the new value to a higher level. This limits the information flow to a
minimum necessary. Figure 128 shows an example with the magnitude dead-band
supervision. The picture is simplified: the process is not continuous but the values are
evaluated with a time interval of one execution cycle from each other.

Value Reported

Y
Value Reported
(1st)

Value Reported
Y3
Y2

Y1

Value Reported
Y
Y

Y
Y

Y
Y

t
IEC99000529-2-en.vsdx

IEC99000529 V2 EN

Figure 128:

Magnitude dead-band supervision reporting

After the new value is reported, the Y limits for dead-band are automatically set around
it. The new value is reported only if the measured quantity changes more than defined by
the Y set limits.
Integral dead-band reporting
The measured value is reported if the time integral of all changes exceeds the pre-set limit
(XDbRepInt), figure 129, where an example of reporting with integral dead-band
supervision is shown. The picture is simplified: the process is not continuous but the
values are evaluated with a time interval of one execution cycle from each other.

306

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

The last value reported, Y1 in figure 129 serves as a basic value for further measurement.
A difference is calculated between the last reported and the newly measured value and is
multiplied by the time increment (discrete integral). The absolute values of these integral
values are added until the pre-set value is exceeded. This occurs with the value Y2 that is
reported and set as a new base for the following measurements (as well as for the values
Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals with
small variations that can last for relatively long periods.

A1 >=
pre-set value

Y
A >=
pre-set value

A2 >=
pre-set value
Y3

Y2
Value Reported
(1st)

A1

Value
Reported

A2
Value
Reported

Y4

A3 + A4 + A5 + A6 + A7 >=
pre-set value
A4
A3

Value
Reported

Y1

A5

A6

A7

Y5
Value
Reported
t
IEC99000530-2-en.vsdx

IEC99000530 V2 EN

Figure 129:

Reporting with integral dead-band supervision

Measurement ZMMXU
The magnitude and angle of the impedance for each phase are available on the outputs
(ZLxMAG and ZLxANGL (x=1,2,3)). Each analogue output has a corresponding
supervision level output (ZLxRANG, ZLxANGR). The supervision output signal is an
integer in the interval 0-4, see section Measurement supervision.
Impedance measurement is calculated based on VA / IA , VB / IB , VC / IC , where VX and

IX are phase-to-ground voltage and phase-to-ground current.


When the operating current is too low, the impedance measurement can be erroneous. In
order to avoid such error, minimum operating current will be checked. For phase currents

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

307

Section 7
Impedance protection

1MRK 502 066-UUS A

lower than 3% of IBase, the magnitude of impedance is force to 9999999 and the angle is
forced to 0 degree.
Inside the function, to ensure the readability of the output for the users, ZLxMAG and
ZLxANGL (x=1,2,3) will not change more often than a certain time period, for example,
every 100 ms.

7.5.8

Technical data
Table 120:

ZMFPDIS, ZMFCPDIS (21) technical data

Function

7.6

308

Range or value

Accuracy

Number of zones

3 selectable
directions, 3 fixed
directions

Minimum operate current, phaseto-phase and phase-to-ground

(5-6000)% of IBase

1.0% of In at I In
1.0% of I at I > In

Positive sequence reactance


reach, phase-to-ground and
phase-to-phase loop

(0.01 - 3000.00) ohm/


phase

Positive sequence resistance


reach, phase-to-ground and
phase-to-phase loop

(0.00 - 1000.00) ohm/


phase

Zero sequence reactance reach

(0.01 - 9000.00) ohm/p

Zero sequence resistive reach

(0.00 - 3000.00) ohm/p

Fault resistance reach, phase-toground and phase-to-phase

(0.01 -9000.00) ohm/l

Dynamic overreach

< 5% at 85 degrees
measured with CVTs
and 0.5 < SIR < 30

Definite time delay to trip, phaseto-ground and phase-to-phase


operation

(0.000-60.000) s

2.0% or 35 ms whichever is greater

Operate time

16 ms typically

IEC 60255-121

Reset time at 0.1 to 2 x Zreach

Min. = 20 ms
Max. = 35 ms

Reset ratio

105% typically

2.0% of static accuracy


2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Vn
Current range: (0.5-30) x In
Angle: At 0 degrees and 85 degrees

High speed distance protection for series compensated


lines ZMFCPDIS (21)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.6.1

Identification
Function description
High speed distance protection zone
(zone 1-6)

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
21

ZMFCPDIS

S00346 V1 EN

7.6.2

Functionality
High speed distance protection (ZMFCPDIS, 21) provides sub-cycle, down towards halfcycle, operate time for basic faults within 60% of the line length and up to around SIR 5.
At the same time, it is specifically designed for extra care during difficult conditions in
high voltage transmission networks, like faults on long heavily loaded lines and faults
generating heavily distorted signals. These faults are handled with utmost security and
dependability, although sometimes with reduced operating speed.
High speed distance protection ZMFCPDIS is fundamentally the same function as
ZMFPDIS but provides more flexibility in zone settings to suit more complex
applications, such as series compensated lines. In operation for series compensated
networks, the parameters of the directional function are altered to handle voltage reversal.
The ZMFCPDIS function is a six-zone full scheme protection with three fault loops for
phase-to-phase faults and three fault loops for phase-to-ground faults for each of the
independent zones, which makes the function suitable in applications with single-phase
autoreclosing.
In each measurement zone, ZMFCPDIS function is designed with the flexibility to operate
in either quadrilateral or mho characteristic mode for separate phase-to-earth or phase-tophase loops.
The zones can operate independently of each other. Zones 3 to 5 in directional (forward
or reverse) or non-directional mode. Zone1 and zone2 are designed to measure in forward
direction only, while one zone (ZRV) is designed to measure in the reverse direction. This
makes them suitable, together with a communication scheme, for protection of power
lines and cables in complex network configurations, such as parallel lines, multi-terminal
lines, and so on.
A new built-in adaptive load compensation algorithm prevents overreaching of the
distance zones in the load exporting end during phase-to-ground faults on heavily loaded
power lines. It also reduces underreach in the importing end.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

309

Section 7
Impedance protection

1MRK 502 066-UUS A

The ZMFCPDIS function block incorporates a phase-selection element and a directional


element, contrary to previous designs in the IED series, where these elements were
represented with separate function blocks.
The operation of the phase-selection element is primarily based on current change criteria,
with significant increased dependability. Naturally, there is also a part operating with
continuous criteria that operates in parallel
The directional element utilizes a set of well-established quantities to provide fast and
correct directional evaluation during various conditions, including close-in three-phase
faults, simultaneous faults and faults with only zero-sequence in-feed.

310

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.6.3

Function block

ZMFCPDIS (21)
I3P*
V3P*
BLOCK
LOVBZ
BLKZ1
BLKZ2
BLKZ3
BLKZ4
BLKZ5
BLKZRV
BLKTRZ1
BLKTRZ2
BLKTRZ3
BLKTRZ4
BLKTRZ5
BLKTRZRV

TRIP
TRZ1
TR_A_Z1
TR_B_Z1
TR_C_Z1
TRZ2
TR_A_Z2
TR_B_Z2
TR_C_Z2
TRZ3
TRZ4
TRZ5
TRZRV
BFI_3P
PU_Z1
PU_ND_Z1
PU_Z2
PU_A_Z2
PU_B_Z2
PU_C_Z2
PU_ND_Z2
PU_Z3
PU_ND_Z3
PU_Z4
PU_ND_Z4
PU_Z5
STND_Z5
PU_ZRV
PU_A_RV
PU_B_RV
PU_C_RV
STNDRV
PHPUN D
NDIR_A
NDIR_B
NDIR_C
FWD_A
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
REV_G
FWD_1PH
FWD_2PH
FWD_3PH
PHG_FLT
PHPH_FLT
ANSI11000422-2-en.vsdx

ANSI11000422 V2 EN

Figure 130:

ZMFCPDIS (40) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

311

Section 7
Impedance protection
7.6.4

1MRK 502 066-UUS A

Signals
Table 121:
Name

ZMFCPDIS (21) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Blocks and resets timers and outputs of entire function

LOVBZ

BOOLEAN

Blocks and resets timers and outputs of entire function

BLKZ1

BOOLEAN

Blocks and resets zone 1 timers and outputs

BLKZ2

BOOLEAN

Blocks and resets zone 2 timers and outputs

BLKZ3

BOOLEAN

Blocks and resets zone 3 timers and outputs

BLKZ4

BOOLEAN

Blocks and resets zone 4 timers and outputs

BLKZ5

BOOLEAN

Blocks and resets zone 5 timers and outputs

BLKZRV

BOOLEAN

Blocks and resets reverse zone timers and outputs

BLKTRZ1

BOOLEAN

Blocks and resets zone 1 timers and trip outputs

BLKTRZ2

BOOLEAN

Blocks and resets zone 2 timers and trip outputs

BLKTRZ3

BOOLEAN

Blocks and resets zone 3 timers and trip outputs

BLKTRZ4

BOOLEAN

Blocks and resets zone 4 timers and trip outputs

BLKTRZ5

BOOLEAN

Blocks and resets zone 5 timers and trip outputs

BLKTRZRV

BOOLEAN

Blocks and resets reverse zone timers and trip outputs

Table 122:
Name

ZMFCPDIS (21) Output signals


Type

Description

TRIP

BOOLEAN

Trip in any phase or phases from any zone or zones

TRZ1

BOOLEAN

Trip in any phase or phases from zone 1 - forward


direction

TR_A_Z1

BOOLEAN

Trip in phase A from zone 1 foward direction

TR_B_Z1

BOOLEAN

Trip in phase B from zone 1 forward direction

TR_C_Z1

BOOLEAN

Trip in phase C from zone 1 forward direction

TRZ2

BOOLEAN

Trip in any phase or phases from zone 2 - forward


direction

TR_A_Z2

BOOLEAN

Trip in phase A from a zone 2 forward direction

TR_B_Z2

BOOLEAN

Trip in phase B from zone 2 forward direction

TR_C_Z2

BOOLEAN

Trip in phase C from zone 2 forward direction

TRZ3

BOOLEAN

Trip in any phase or phases from zone 3 - zone direction

TRZ4

BOOLEAN

Trip in any phase or phases from zone 4 - zone direction

Table continues on next page

312

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Type

Description

TRZ5

BOOLEAN

Trip in any phase or phases from zone 5 - zone direction

TRZRV

BOOLEAN

Trip in any phase or phases from zone RV - reverse dir.

BFI_3P

BOOLEAN

Pickup in any phase or phases from any zone or zones

PU_Z1

BOOLEAN

Pick up of any phase or phases from a Zone 1 fault in the


forward direction

PU_ND_Z1

BOOLEAN

Pick up any phase or phases from zone 1 - any direction

PU_Z2

BOOLEAN

Pick up of any phase or phases from a Zone 2 fault in the


forward direction

PU_A_Z2

BOOLEAN

Pick up of phase A for a zone 2 fault in forward direction

PU_B_Z2

BOOLEAN

Pick up for phase B fault in forward direction

PU_C_Z2

BOOLEAN

Pick up in phase C for a zone 2 fault in the forward


direction

PU_ND_Z2

BOOLEAN

Pick uo in any phase or phases for a zone 2 fault in any


direction

PU_Z3

BOOLEAN

Pick up of any phase or phases from a Zone 3 fault in the


forward direction

PU_ND_Z3

BOOLEAN

Pick up any phase or phases from zone 3- any direction

PU_Z4

BOOLEAN

Pick up in any pjase or phases for a zone 4 fault - zone


direction

PU_ND_Z4

BOOLEAN

Pick up any phase or phases from zone -4 any direction

PU_Z5

BOOLEAN

Pick up in any phase or phase for Zone 5 - Zone


direction

STND_Z5

BOOLEAN

Pick up in any phase or phases from a zone 5 fault in any


direction

PU_ZRV

BOOLEAN

Pick up in any phase or phase for a reverse fault

PU_A_RV

BOOLEAN

Pick up for a phase A reverse fault

PU_B_RV

BOOLEAN

Pick up for a phase B revers fault

PU_C_RV

BOOLEAN

Pick up for a phase C reverse fault

STNDRV

BOOLEAN

Pick up for a reverse zone for a fauult in nay direction

PHPUND

BOOLEAN

Fault detected in any phase or phases - any direction

NDIR_A

BOOLEAN

Fault detected in phase A - any direction

NDIR_B

BOOLEAN

Fault detected in phase B - any direction

NDIR_C

BOOLEAN

Fault detected in phase C - any direction

FWD_A

BOOLEAN

Fault detected in phaseA - forward direction

FWD_B

BOOLEAN

Fault detected in phase B - forward direction

FWD_C

BOOLEAN

Fault detected in phase C - forward direction

FWD_G

BOOLEAN

forward fault involving ground

REV_A

BOOLEAN

Fault detected in phase A- reverse direction

REV_B

BOOLEAN

Fault detected in phase B - reverse direction

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

313

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

7.6.5
Table 123:
Name

Type

Description

REV_C

BOOLEAN

Fault detected in phase C - reverse direction

REV_G

BOOLEAN

Fault in reverse direction involving ground

FWD_1PH

BOOLEAN

Single-phase fault detected - forward direction

FWD_2PH

BOOLEAN

Two-phase fault detected - forward direction

FWD_3PH

BOOLEAN

Three-phase fault detected - forward direction

PHG_FLT

BOOLEAN

Ph-G zone measurement enabled - any direction

PHPH_FLT

BOOLEAN

Ph-Ph zone measurement enabled - any direction

Settings
ZMFCPDIS (21) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Disable/Enable operation of the function

OperationSC

NoSeriesComp
SeriesComp

NoSeriesComp

Selection of series compensation operation


Off / On

RLdFwd

0.01 - 5000.00

Ohm/p

0.01

60.00

Resistance determining the load impedance


area - forward

RLdRvFactor

1 - 1000

%RLdF
w

100

Resistance factor determining the load


impedance area - reverse

XLd

0.01 - 10000.00

Ohm/p

0.01

400.00

Resistance determining the load impedance


area - forward

LdAngle

5 - 70

Deg

30

Angle determining the load impedance area

CVTType

Any
Passive type
None (Magnetic)

Passive type

CVT selection determining the filtering of the


function

OpModePPZ1

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 1

OpModePGZ1

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 1

X1FwPPZ1

0.01 - 3000.00

Ohm/p

0.01

30.00

Positive seq. reactance reach, Ph-Ph, zone 1,


forward dir.

R1FwPPZ1

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-Ph, zone 1,


forward dir.

X1RvPPZ1

0.01 - 3000.00

Ohm/p

0.01

30.00

Pos. seq. react. reach, Ph-Ph, zone 1, reverse


direction

X1FwPGZ1

0.01 - 3000.00

Ohm/p

0.01

30.00

Positive seq. reactance reach, Ph-G, zone 1,


forward dir.

Table continues on next page

314

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Step

Default

R1FwPGZ1

Values (Range)
0.00 - 1000.00

Unit
Ohm/p

0.01

5.00

Description
Positive seq. resistive reach, Ph-G, zone 1,
forward dir.

X0FwPGZ1

0.01 - 9000.00

Ohm/p

0.01

100.00

Zero seq. reactance reach, Ph-G, zone 1,


forward direction

R0FwPGZ1

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero seq. resistive reach, Ph-G, zone 1,


forward direction

X1RvPgZ1

0.01 - 3000.00

Ohm/p

0.01

30.00

Pos. seq. react. reach, Ph-G, zone 1, reverse


direction

RFPPZ1

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone 1

RFPGZ1

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 1

tPPZ1

0.000 - 60.000

0.001

0.000

Time delay to trip, Phase-Phase, zone 1

tPGZ1

0.000 - 60.000

0.001

0.000

Time delay to trip, Ground-Earth, zone 1

IMinOpPPZ1

10 - 6000

%IB

10

Minimum operate ph-ph current for PhasePhase loops, zone 1

IMinOpPGZ1

5 - 6000

%IB

10

minimum operate phase current for phaseground loops. zone 1

OpModePPZ2

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 2

OpModePGZ2

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 2

X1FwPPZ2

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. reactance reach, Ph-Ph, zone 2,


forward dir.

R1FwPPZ2

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-Ph, zone 2,


forward dir.

X1RvPPZ2

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-Ph, zone 2, reverse


direction

X1FwPGZ2

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. reactance reach, Ph-G, zone 2,


forward dir.

R1FwPGZ2

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-G, zone 2,


forward dir.

X0FwPGZ2

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero seq. reactance reach, Ph-G, zone 2,


forward direction

R0FwPGZ2

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero seq. resistive reach, Ph-G, zone 2,


forward direction

X1RvPGZ2

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-G, zone 2, reverse


direction

RFPPZ2

0.01 - 9000.00

Ohm/l

0.01

30.00

Zero sequence reactance reach, zone 2

RFPGZ2

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-g, Zone 2

tPPZ2

0.000 - 60.000

0.001

0.400

Time delay to trip, Phase-Phase, zone 2

tPGZ2

0.000 - 60.000

0.001

0.400

Time delay to trip, Phase-Ground, zone 2

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

315

Section 7
Impedance protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

IMinOpPPZ2

10 - 6000

%IB

10

Time delay to trip, Phase-Phase, zone 2

IMinOpPGZ2

5 - 6000

%IB

10

Minimum operate phase current for phase ground loops, zone 2

OpModePPZ3

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 3

OpModePGZ3

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 3

DirModeZ3

Non-directional
Forward
Reverse

Forward

Time delay to trip, Phase-Phase, zone 2

X1FwPPZ3

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. reactance reach, Ph-Ph, zone 3,


zone direction

R1FwPPZ3

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-Ph, zone 3,


zone direction

RFFwPPZ3

0.01 - 9000.00

Ohm/l

0.01

30.00

Positive seq. resistive reach, Ph-Ph, zone 3,


zone direction

X1RvPPZ3

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-Ph, zone 3, opposite


to zone dir

RFRvPPZ3

0.01 - 9000.00

Ohm/l

0.01

30.00

Positive seq. resistive reach, Ph-Ph, zone 3,


zone direction

X1FwPGZ3

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. resistive reach, Ph-G, zone 3,


zone direction

R1FwPGZ3

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-G, zone 3,


zone direction

X0FwPGZ3

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero seq. reactance reach, Ph-G, zone 3, zone


direction

R0FwPGZ3

0.01 - 3000.00

Ohm/p

0.01

15.00

Zero seq. resistive reach, Ph-G, zone 3, zone


direction

RFFwPGZ3

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 3, zone


direction

X1RvPGZ3

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-G, zone 3, opposite


to zone dir

RFRvPGZ3

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 3, opposite


to zone dir.

tPPZ3

0.000 - 60.000

0.001

0.800

Time delay to trip, Phase-Phase, zone 3

tPGZ3

0.000 - 60.000

0.001

0.800

Time delay to trip, Phase-Ground, zone 3

IMinOpPPZ3

10 - 6000

%IB

10

Minimum operate ph-ph current for PhasePhase loops, zone 3

IMinOpPGZ3

5 - 6000

%IB

10

Minimum operate phase current for phaseground loops, zone 3

Table continues on next page

316

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

OpModePPZ4

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 4

OpModePGZ4

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 4

DirModeZ4

Non-directional
Forward
Reverse

Forward

Direction of zone 4 (which will be the Fw


direction of zone 4)

X1FwPPZ4

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. reactance reach, Ph-Ph, zone 4,


zone direction

R1FwPPZ4

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-Ph, zone 4,


zone direction

RFFwPPZ4

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone 4, zone


direction

X1RvPPZ4

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-Ph, zone 4, opposite


to zone dir

RFRvPPZ4

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone 4,


opposite to zone dir.

X1FwPGZ4

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. reactance reach, Ph-G, zone 4,


zone direction

R1FwPGZ4

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-G, zone 4,


zone direction

X0FwPGZ4

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero seq. reactance reach, Ph-G, zone 4, zone


direction

R0FwPGZ4

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero seq. resistive reach, Ph-G, zone 4, zone


direction

RFFwPGZ4

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 4, zone


direction

X1RvPGZ4

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-G, zone 4, opposite


to zone dir

RFRvPGZ4

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 4, opposite


to zone dir.

tPPZ4

0.000 - 60.000

0.001

1.200

Time delay to trip, Phase-Phase, zone 4

tPGZ4

0.000 - 60.000

0.001

1.200

Time delay to trip, Phase-ground, zone 4

IMinOpPPZ4

10 - 6000

%IB

10

How start of trip delay timers should be linked


for zone 4

IMinOpPGZ4

5 - 6000

%IB

10

Minimum operate phase current for phaseground loops, zone 4

OpModePPZ5

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone 5

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

317

Section 7
Impedance protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

OpModePGZ5

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone 5

DirModeZ5

Non-directional
Forward
Reverse

Forward

Direction of zone 5 (which will be the Fw


direction of zone 5)

X1FwPPZ5

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. reactance reach, Ph-Ph, zone 5,


zone direction

R1FwPPZ5

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-Ph, zone 5,


zone direction

RFFwPPZ5

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone 5, zone


direction

X1RvPPZ5

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-Ph, zone 5, opposite


to zone dir

RFRvPPZ5

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone 5,


opposite to zone dir.

X1FwPGZ5

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. reactance reach, Ph-G, zone 5,


zone direction

R1FwPGZ5

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-G, zone 5,


zone direction

X0FwPGZ5

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero seq. reactance reach, Ph-G, zone 5, zone


direction

R0FwPGZ5

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero seq. resistive reach, Ph-G, zone 5, zone


direction

RFFwPGZ5

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 5, zone


direction

X1RvPGZ5

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-G, zone 5, opposite


to zone dir

RFRvPGZ5

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach, Ph-G, zone 5, opposite


to zone dir.

tPPZ5

0.000 - 60.000

0.001

1.600

Time delay to trip, Phase-Phase, zone 5

tPGZ5

0.000 - 60.000

0.001

1.600

Time delay to trip, Phase-ground, zone 5

IMinOpPPZ5

10 - 6000

%IB

10

Minimum operate ph-ph current for PhasePhase loops, zone 5

IMinOpPGZ5

5 - 6000

%IB

10

Minimum operate phase current for phaseground loops, zone 5

OpModePPZRV

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-Ph loops, zone RV

OpModePGZRV

Disabled
Quadrilateral
Mho
MhoOffset

Quadrilateral

Enabled/Disabled and characteristic setting for


Ph-G loops, zone RV

Table continues on next page

318

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Step

Default

X1FwPPZRV

0.01 - 3000.00

Ohm/p

0.01

40.00

Positive seq. reactance reach, Ph-Ph, zone


RV, reverse dir.

R1FwPPZRV

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-Ph, zone RV,


reverse dir.

X1RvPPZRV

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react, reach, Ph-Ph, zone RV,


forward direction

X1FwPGZRV

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react, reach, Ph-G, zone RV, reverse


direction

R1FwPGZRV

0.00 - 1000.00

Ohm/p

0.01

5.00

Positive seq. resistive reach, Ph-G, zone RV,


reverse dir.

X0FwPGZRV

0.01 - 9000.00

Ohm/p

0.01

120.00

Zero seq. reactance reach, Ph-G, zone RV,


reverse direction

R0FwPGZRV

0.00 - 3000.00

Ohm/p

0.01

15.00

Zero seq. resistive reach, Ph-G, zone RV,


reverse direction

X1RvPGZRV

0.01 - 3000.00

Ohm/p

0.01

40.00

Pos. seq. react. reach, Ph-G, zone RV, forward


direction

tPPZRV

0.000 - 60.000

0.001

0.000

Time delay to trip, Phase-Phase, zone RV

tPEZRV

0.000 - 60.000

0.001

0.000

Time delay to trip, Phase -Ground, zone RV

IMinOpPPZRV

10 - 6000

%IB

10

Minimum operate ph-ph current for PhasePhase loops, zone RV

IMinOpPGZRV

5 - 6000

%IB

10

Minimum operate phase current for phaseground loops, zone RV

RFPPZRV

0.01 - 9000.00

Ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, zone RV

RFPGZRV

0.01 - 9000.00

Ohm/l

0.01

100.00

Fault resistance reach Ph-G. zone RV

Step

Default

Table 124:
Name

Values (Range)

Unit

Description

ZMFCPDIS (21) Group settings (advanced)


Values (Range)

Unit

Description

ZoneLinkPU

Phase Selection
1st starting zone

Phase Selection

Select. of start source for all ZoneLinked trip


delay timers

3I0Enable_PG

5 - 400

%MaxIP
h

400

3I0 limit for releasing Phase-to-Ground


measuring loops

TimerModeZ1

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/Off setting for Ph-Ph and Ph-G trip output,


zone 1

TimerLinksZ1

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 1

TimerModeZ2

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip output,


zone 2

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

319

Section 7
Impedance protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

TimerLinksZ2

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 2

TimerModeZ3

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip output,


Zone 3

TimerLinksZ3

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 3

TimerLinksZ4

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip output


Zone 4

TimerLinksZ4

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 4

TimerModeZ5

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip output,


zone 5

TimerLinksZ5

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone 5

TimerModeZRV

Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH

Enable Ph-G
PhPH

On/off setting for Ph-Ph and Ph-G trip outout,


zone RV

TimerLinksZRV

LoopLink (tPP &


tPG)
LoopLink &
ZoneLink
no links

LoopLink (tPP &


tPG)

How start of trip delay timers should be linked


for zone RV

320

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 125:
Name

ZMFCPDIS (21) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

ZDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

ZMax

0.0 - 5000.0

Ohm

0.1

1500.0

Maximum value in ohm

ZRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

ZAngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Table 126:
Name

ZMFCPDIS (21) Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ZZeroDb

0 - 100000

m%

100

Zero point clamping

ZHiHiLim

0.0 - 5000.0

Ohm

0.1

1350.0

High High limit in ohm

ZHiLim

0.0 - 5000.0

Ohm

0.1

1200.0

High limit in ohm

ZLowLim

0.0 - 5000.0

Ohm

0.1

300.0

Low limit in ohm

ZLowLowLim

0.0 - 5000.0

Ohm

0.1

150.0

Low Low limit in ohm

ZMin

0.000 - 5000.000

Ohm

0.001

0.005

Minimum value in ohm

ZLimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

ArgLdMinEd2

5 - 70

Deg

Minimum settable angle determining the load


impedance area, for 61850 Ed.2 settings

ArgLdMaxEd2

5 - 70

Deg

70

Maximum settable angle determining the load


impedance area, for 61850 Ed.2 settings

RLdFwMinEd2

0.01 - 5000.00

Ohm/p

0.01

0.01

Minimum settable resistance determining the


load impedance area, for 61850 Ed.2 settings

RLdFwMaxEd2

0.01 - 5000.00

Ohm/p

0.01

5000.00

Maximum settable resistance determining the


load impedance area, for 61850 Ed.2 settings

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

321

Section 7
Impedance protection
7.6.6

1MRK 502 066-UUS A

Monitored data
Table 127:
Name

322

ZMFCPDIS (21) Monitored data


Type

Values (Range)

Unit

Description

A_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase A

B_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase B

C_Dir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in phase C

ABDir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in loop AB

BCDIR

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in looop BC

CADir

INTEGER

1=Forward
2=Reverse
0=No direction

Direction in loop CA

Aph_R

REAL

Ohm

Resistance in phase A

Aph_X

REAL

Ohm

Reactance in phase A

Bph_R

REAL

Ohm

Resistance in phase B

Bph_X

REAL

Ohm

Reactance in phase B

Cph_R

REAL

Ohm

Resistance in phase C

Cph_X

REAL

Ohm

Reactance in phase C

ZAIMAG

REAL

Ohm

ZA Amplitude, magnitude of
instantaneous value

ZAANGIM

REAL

deg

ZA Angle, magnitude of
instantaneous value

ZBIMAG

REAL

Ohm

ZB Amplitude, magnitude of
instantaneous value

ZBANGIM

REAL

deg

ZB Angle, magnitude of
instantaneous value

ZCIMAG

REAL

Ohm

ZC Amplitude, magnitude of
instantaneous value

ZCANGIM

REAL

deg

ZC Angle, magnitude of
instantaneous value

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.6.7

Operation principle
Settings, input and output names are sometimes mentioned in the following text without
its zone suffix (i.e. BLKZx instead of BLKZ3) when the description is equally valid for
all zones.

7.6.7.1

Filtering
Practically all voltage, current and impedance quantities used within the ZMFCPDIS
function are derived from fundamental frequency phasors filtered by a half-cycle filter.
The phasor filter is frequency adaptive in the sense that its coefficients are changed based
on the estimated power system frequency.
A half-cycle filter will not be able to reject both even and odd harmonics. So, while odd
harmonics will be completely attenuated, accuracy will be affected by even harmonics.
Even harmonics will not cause the distance zones to overreach; instead there will be a
slightly variable underreach, on average in the same order as the magnitude ratio between
the harmonic and the fundamental component.

7.6.7.2

Distance measuring zones


The execution of the different fault loops within the IED are of full scheme type, which
means that ground fault loop for phase-to-ground faults and phase-to-phase faults for
forward and reverse faults are executed in parallel.
Figure 108 presents an outline of the different measuring loops for the six distance zones.
A-G

B-G

C-G

A- B

B-C

C-A

Zone 1

A-G

B-G

C-G

A- B

B-C

C-A

Zone 2

A-G

B-G

C-G

A- B

B-C

C-A

Zone 3

A-G

B-G

C-G

A- B

B-C

C-A

Zone 4

A-G

B-G

C-G

A- B

B-C

C-A

Zone 5

A-G

B-G

C-G

A- B

B-C

C-A

Zone 6

ANSI05000458-2-en.vsd
ANSI05000458 V2 EN

Figure 131:

The different measuring loops at phase-to-ground fault and phase-tophase fault

The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a pickup of an overreaching element to select correct voltages
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

323

Section 7
Impedance protection

1MRK 502 066-UUS A

and current depending on fault type. Each distance protection zone performs like one
independent distance protection function with six measuring elements.
Transients from CVTs may have a significant impact on the transient overreach of a
distance protection. At the same time these transients can be very diverse in nature from
one type to the other; in fact, more diverse than can be distinguished by the algorithm itself
in the course of a few milliseconds. So, a setting is introduced in order to inform the
algorithm about the type of CVT applied and thus providing the advantage of knowing
how performance should be optimized, even during the first turbulent milliseconds of the
fault period.
There are two types of CVTs from the function point of view, the passive and the active
type, which refers to the type of ferro-resonance suppression device that is employed. The
active type requires more rigorous filtering which will have a negative impact on operate
times. However, this will be evident primarily at higher source impedance ratios (SIRs),
SIR 5 and above, or close to the reach limit.
The IEC 60044-5 transient classification is of little or no use in relation to this. It is not
primarily the damping of transients that is important; it is the frequency content of the
transients that is decisive, i.e. how difficult it is to filter out the specific frequency. So,
even if two CVTs, one passive and the other active type, comply with the same transient
class, the active type requires more extensive filtering in order to avoid transient
overreach.
To avoid overreach and at the same time achieve fast operate times, a supplementary
circular characteristic that includes some alternative processing (retained from REL 531)
is implemented. One such circular characteristic exists for every measuring loop and
quadrilateral/mho characteristic. There are no specific reach settings for this circular zone.
It uses the normal quadrilateral/mho zone settings to determine a reach that will be
appropriate. This implies that the circular characteristic will always have somewhat
shorter reach than the quadrilateral/mho zone.

7.6.7.3

Phase-selection element
The operation of the phase-selection element is primarily based on current change criteria.
The current change criteria itself can however only be relied on for a short period
following the fault inception (during what we will call the current change phase).
Subsequent switching in the network may render the change in current invalid. So,
naturally, the phase-selection element also operates on continuous criteria.
The phase-selection element can, owing to the current change criteria, distinguish faults
with minimum influence from load and fault impedance. In other words, it is not restricted
by a load encroachment characteristic during the current change phase. This significantly
improves performance for remote phase-to-ground faults on heavily loaded lines. One

324

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

exception, however, is three-phase faults, for which the load encroachment characteristic
always has to be applied, in order to distinguish fault from load.
The continuous criteria will in the vast majority of cases operate in parallel and carry on
the fault indication after the current change phase has ended. Only in some particularly
difficult faults on heavily loaded lines the continuous criteria might not be sufficient, for
example, when the estimated fault impedance resides within the load area defined by the
load encroachment characteristic. In this case, the indication will be restricted to a pulse
lasting for one or two power system cycles.
Phase-to-phase-ground faults (also called double ground faults) will practically always
activate phase-to-phase zone measurements. This is a substantial difference compared to
the previous phase selection function in the 500- and 600-series (that is, FDPSPDIS).
Measurement in two phase-to-ground loops at the same time is associated with so-called
simultaneous faults: two ground faults at the same time, one each on the two circuits of a
double line, or when the zero sequence current is relatively high due to a source with low
Z0/Z1 ratio.In fact, in these situations zone measurement will be released both for the
related phase-to-ground loops and the phase-to-phase loop simultaneously. On the other
hand, simultaneous faults closer to the remote bus will gradually take on the properties of
a phase-to-phase-ground fault and the function will eventually use phase-to-phase zone
measurements also here.
In cases where the fault current infeed is more or less completely lack of zero sequence
nature (all phase currents in phase), the measurement will be performed in the phase-toground loops only for a phase-to-phase-ground fault.
However, should it be desirable to use phase-to-ground (and only phase-to-ground) zone
measurement for phase-to-phase-ground faults, the setting INReleasePE can be lowered
from its excessive default value to the level above which phase-to-ground measurement
should be activated.

7.6.7.4

Directional element
Several criteria are employed when making the directional decision. The basis is provided
by comparing a positive sequence based polarizing voltage with phase currents. For extra
security, especially in making a very fast decision, this method is complemented with an
equivalent comparison where, instead of the phase current, the change in phase current is
used. Moreover, a basic negative sequence directional evaluation is taken into account as
a reliable reference during high load condition. Finally, zero sequence directional
evaluation is used whenever there is more or less exclusive zero sequence in-feed.
Fundamentally, the directional sectors that represent forward direction, one per measuring
loop, are defined by the following equations.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

325

Section 7
Impedance protection

-15<arg

1MRK 502 066-UUS A

PolA

< 120

(Equation 75)

ANSIEQUATION15059 V1 EN

-15<arg

PolAB

< 120

AB

(Equation 76)

ANSIEQUATION15060 V1 EN

Where:
VPolA

is the polarizing voltage for phase A.

IA

is the phase current in phase A.

VPolAB

is the polarizing voltage difference between phase A and B (B lagging A).

IAB

is the current difference between phase A and B (B lagging A).

The corresponding reverse directional sectors range from 165 to -60 degrees.
Since the polarizing voltage is also used for the Mho distance characteristics, the
magnitude of the voltage is just as interesting as the phase. If there are symmetrical
conditions and the measured per phase positive sequence voltage magnitude is above 75%
of the base voltage before the fault, the pre-fault magnitude will be memorized and used
as long as there is a fault. The phase angle however will only be memorized (locked) for
75 ms at a time, not to lose synchronism with the real system voltage.
Should the positive sequence voltage drop below 2% of the base voltage, it will be
considered invalid. In this situation, directional signals and pickups from Mho elements
will be sealed-in and kept static as long as there is a fault.
For ZMFCPDIS, when option SeriesComp is chosen for OperationSC, the voltages of
faulty phases will be discarded in order not to affect the polarizing voltage with voltage
reversal.

7.6.7.5

Fuse failure
The ZMFCPDIS function has to be blocked by an additional function like the Fuse failure
supervision (FUFSPVC) or an equivalent external device. Typically, the binary input
VTSZ is used for this purpose.
However, to guarantee that also very fast operation is blocked in a fuse failure situation,
there is a built-in supervision based on change in current that will delay operation before
the FUFSPVC blocking signal is received. The delay will be introduced if no (vector)
magnitude change greater than 5% of IBase has been detected in any of the phase currents.

326

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.6.7.6

Power swings
There is need for external blocking of the ZMFCPDIS function during power swings,
either from the Power Swing Blocking function (ZMRPSB) or an external device.

7.6.7.7

Measurement principles
Quadrilateral characteristic
ZMFCPDIS implements quadrilateral and mho characteristic in all the six zones
separately. Set OpModePEZx or OpModePPZx to Quadrilateral, to choose particular
measuring loop in a zone to work as quadrilateral distance protection.
All ZMFCPDIS zones operate according to the non-directional impedance characteristics
presented in figure 132 and figure 133. The phase-to-ground characteristic is illustrated
with the full loop reach while the phase-to-phase characteristic presents the per-phase
reach.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

327

Section 7
Impedance protection

1MRK 502 066-UUS A

X (Ohm/loop)

R1PG+RNFw
RFRvPG

RFFwPG

X 0 PG X 1FwPG
3
PG
1RVPGX 1RvPG
XX00PE
X 1XRVPE
XNRV
XNRv
= XNFw

XNRV
==
3
3
X 1FwPG
XNFw =

XX0 PE
X1X
FWPE
0 PG
1FWPG
XNFW
XNFW==
3 3

X1FwPG+XNFw

RNFw =

R0 PG R1PG
3

R (Ohm/loop)
RFRvPG

RFFwPG

X1RvPG+XNRv

N
RFRvPG

RFFwPG

R1PG+RNRv

ANSI11000417-1-en.vsd

ANSI11000417 V1 EN

Figure 132:

328

ZMFCPDIS Characteristic for phase-to-ground measuring loops, ohm/


loop domain

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

RFRvPP

(Ohm/phase)

R1PP

RFFwPP

X 0 PE - X 1RVPE
XNRV =XX00PE
PG- 1RVPG
X3
1XRVPE
XNRV
=
XNRV =
33
XX00PE
PE
11FWPE
X
X-1X
0
PG
XFWPE
FWPG
XNFW
XNFW
XNFW===
3
3 3

X1FwPP

j
jN
RFRvPP

RFFwPP

j
R (Ohm/phase)

X1RvPP

jN
RFRvPP

RFFwPP

IEC11000418-1-en.vsd

IEC11000418 V1 EN

Figure 133:

ZMFCPDIS Characteristic for the phase-to-phase measuring loops

Note that for ZMFCPDIS, the reverse zone ZRV, as well as any of zones
3-5, that are set to DirMode=Reverse will get their operating impedances
inverted (rotated 180 degrees) internally in order to make use of the main
settings, which are the settings designated Fw. Therefore, a reverse zone
will have its Fw-settings (RFFwPPZRV, X1FwPGZ3, and so on) applied
in the third quadrant, that is, towards the busbar instead of the line.
The fault loop reach in relation to each fault type may also be presented as in figure 111.
The main intension with this illustration is to make clear how the fault resistive reach
should be interpreted. Note in particular that the setting RFPP always represents the total
fault resistance of the loop, even while the fault resistance (arc) may be divided into parts
like for three-phase or phase-to-phase-to-ground faults. The R1 and jX1 represent the
positive sequence impedance from the measuring point to the fault location.
Figure 134:

Fault loop model

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

329

Section 7
Impedance protection

1MRK 502 066-UUS A

IA

R1 + j X1

Phase-to-ground
element

VA

Phase-to-ground
fault in phase A

RFPG

(Arc + tower
resistance)
N
IG

(R0-R1)/3 +
j (X0-X1)/3 )

IA

R1 + j X1

Phase-to-phase
element A-B

VA
Phase-to-phase
fault in phase
A-B

RFPP
IB

(Arc resistance)

VB
R1 + j X1

IA
Three-phase
fault or Phase-tophase-ground fault

R1 + j X1

0.5RFPP

R1 + j X1

0.5RFPP

VA

Phase-to-phase
element A-C

IC
VC

ANSI11000419-3-en.vsd

Mho characteristic
ZMFCPDIS implements quadrilateral and mho characteristic in all the six zones
separately. Set OpModePEZx or OpModePPZx setting to Mho or Offset, to choose a
particular measuring loop in a zone to work as mho (or Offset Mho) distance protection.
Zones 3 to 5 can be selected to be either forward or reverse with positive sequence
polarized mho characteristic; alternatively self polarized offset mho characteristics. The
operating characteristic is in accordance to figure 65 where zone 5 is selected offset mho.

330

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

X
Z4

Z3
ZS=0

Z2
Z1
Z5

R
R
ZS=Z1

ZRV

ZS=2Z1

IEC15000056-1-en.vsdx

IEC15000056 V1 EN

Figure 135:

Mho, offset mho characteristics and the source impedance influence on


the mho characteristic

The mho characteristic has a dynamic expansion due to the source impedance. Instead of
crossing the origin, as for the mho to the left of figure 65, which is only valid where the
source impedance (Zs) is zero, the crossing point is moved to the coordinates of the
negative source impedance given an expansion of the circle shown to the right of figure
65. Z1 denotes the complex positive sequence impedance.
The magnitude of the polarized voltage is determined completely by the positive sequence
voltage magnitude from before the fault. This will give a somewhat less dynamic
expansion of the mho circle during faults. However, if the source impedance is high, the
dynamic expansion of the mho circle might lower the security of the function too much
with high loading and mild power swing conditions.
Basic operation characteristics
In ZMFPDIS, each zone measurement loop characteristic can be set to mho characteristic
or offset mho characteristic by setting zxOpModePE or zxOpModePP (where x is 1-5
depending on selected zone).
ZMFPDIS fixes zone 1 and 2 in Forward mode and zone RV in Reverse mode. Zone 3-5
can be set to Non-directional, Forward or Reverse by setting the parameter DirModeZx
(where x is 3-5 depending on selected zone).
If DirModeZx (where x is 3-5 depending on selected zone) is selected as Non-directional,
the directional element will not have any effect on the measurement loop and operation of
the function. When DirModeZx (where x is 3-5 depending on selected zone) is selected as
Forward or Reverse, directional lines are introduced. Information about the directional

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

331

Section 7
Impedance protection

1MRK 502 066-UUS A

lines is given from the directional element. Basic Mho characteristics with different mode
settings are indicated in figure 136.

OpModePP/PEZx = Mho
Zone 1, Zone 2 and
DirModeZ3-5 = Forward

OpModePP/PEZx = Mho
Zone RV and
DirModeZ3-5 = Reverse

OpModePP/PEZx = Offset
Zone 1, Zone 2 and
DirModeZ3-5 = Forward

OpModePP/PEZx = Mho
Only Zone 3-5
DirModeZ3-5 = Non-directional
X

OpModePP/PEZx = Offset
Zone RV and
DirModeZ3-5 = Reverse

OpModePP/PEZx = Offset
Only Zone 3-5
DirModeZ3-5 = Non-directional
IEC15000065.vsdx

IEC15000065 V1 EN

Figure 136:

Mho characteristics

For each zone, the impedance is set in cartesian coordinates (resistance and reactance)
which is the same as for quadrilateral characteristic.
ZMFCPDIS function uses separate sets of reach settings in forward and reverse directions
for phase-to-earth fault and phase-to-phase fault. These settings are R1FwPPZx,
X1FwPPZx, X1RvPPZx, R1FwPEZx, X1FwPEZx, X1RvPEZx, R0FWPEZx, X0FwPPZx
(x=1-5 or RV). Thus, the center of the Non-directional offset mho circle can be arbitrary
located in the circle (figure 136).

332

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Note that the reverse ZoneRV, as well as any of zones 3-5, that are set to
DirModeZx=Reverse will get their operating impedances inverted (rotated 180 degrees)
internally in order to make use of the main settings, which are the settings designated Fw.
Therefore, a reverse zone will have its Fw-settings (R1FwPPZRV, X1FwPEZ3, and so on)
applied in the third quadrant, that is, towards the busbar instead of the line.
In Non-directional mode, for both Mho and Quad, the reach settings are equal to Forward
mode in this respect. The Fw settings apply in the first quadrant and the Rv settings
apply in the third quadrant.
Theory of operation
The mho algorithm is based on the phase comparison of an operating phasor and a
polarizing phasor. When the operating phasor leads the reference polarizing phasor by 90
degrees or more, the function operates and gives a trip output.
Phase-to-phase fault
The plain Mho circle has the characteristic as in figure 66. The condition for deriving the
angle is according to equation 64.

( )

b = arg VAB - I AB Z 1set - arg V pol


ANSIEQUATION15027 V1 EN

(Equation 77)

where

V AB

is the voltage vector difference between phases A and B

EQUATION1790ANSI V1 EN

I AB

is the current vector difference between phases A and B

EQUATION1791ANSI V1 EN

Z 1set
Vpol

is the positive sequence impedance setting for phase-to-phase fault in zone direction
is the polarizing voltage

Z 1set = R1FwPPZx + j X 1FwPPZx


(Equation 78)

IECEQUATION15010 V1 EN

where

R1FwPP
Zx

is the positive sequence resistive reach for phase-to-phase fault in zone direction for zone x (x=1-5
and RV)

X1FwPP
Zx

is the positive sequence reactance reach for phase-to-phase fault in zone direction for zone x (x=1-5
and RV)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

333

Section 7
Impedance protection

1MRK 502 066-UUS A

The polarized voltage consists of 100% memorized positive sequence voltage (VAB for
phase A to B fault). The memorized voltage will prevent collapse of the mho circle for
close in faults.
Operation occurs if 90270.

I AB jX

I L1L 2 Z1set

Vcomp VAB I AB Z1set

VAB
V pol

I AB R
ANSI15000060-1-en.vsdx
ANSI15000060 V1 EN

Figure 137:

Simplified mho characteristic and vector diagram for phase A-to-B fault

Offset Mho
The characteristic for offset mho is a circle where two points on the circle are given by the
two vectors Z 1set and Z 1RVset where Z 1set and Z 1RVset are settable through the
resistance and reactance settings in forward and reverse directions.
The condition for operation at phase-to-phase fault is that the angle between the two
compensated voltages is greater than or equal to 90 (figure 115). The angle will be 90
for fault location on the boundary of the circle.
The angle for A to B fault can be defined according to equation 67.

334

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

V I Z1
AB
AB
set
= arg
VAB I AB Z 1RVset

(Equation 80)

ANSIEQUATION15008 V1 EN

where

Z 1RVset

is the positive sequence impedance setting for phase-to-phase fault


opposite to zone direction and is defined as

Z 1RVset = R1RvPPZx + j X 1RvPPZx


(Equation 81)

IECEQUATION15013 V1 EN

where

X1RvPPZx

is the positive sequence reactance reach for phase-to-phase fault


opposite to zone direction for zone x (x=1-5 and RV)

R1RvPPZx

is the positive sequence resistive reach for phase-to-phase fault


opposite to zone direction for zone x (x=1-5 and RV) and is internally
calculated according to the equation below,

R1FwPPZx
R1RvPPZx = X 1RvPPZx

X 1FwPPZx
IECEQUATION15014 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

(Equation 82)

335

Section 7
Impedance protection

1MRK 502 066-UUS A

I AB jX
Vcomp1 VAB I AB Z 1set

I AB Z 1set

VAB
Vcomp 2 VAB ( I AB Z 1RVset )

I AB Z 1RVset

I AB R
ANSI15000058-1-en.vsdx

ANSI15000058 V1 EN

Figure 138:

Simplified offset mho characteristic and voltage vector for phase A to B


fault

Operation occurs if 90270 .


Phase-to-ground fault
The measuring of earth faults uses earth return compensation applied in a conventional
way. The compensation voltage is derived by considering the influence from the earth
return path.
Compensation for earth return path for faults involving earth is done by setting the positive
and zero sequence impedance of the line. It is known that the ground compensation factor
KN is,

KN =

Z 0set Z 1set
3 Z 1set

IECEQUATION15017 V1 EN

336

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Z 0set = R 0 FwPEZx + j X 0 FwPEZx


IECEQUATION15028 V1 EN

Z 1set = R1FwPEZx + j X 1FwPEZx


(Equation 83)

IECEQUATION15029 V1 EN

where
is the complex zero sequence impedance of the line in /phase

Z 0set

is the complex positive sequence impedance of the line in /phase

Z 1set
R0FwPEZx

is the zero sequence resistive reach of the line in /phase for phaseto-ground fault in zone direction for zone x (x=1-5, or RV)

X0FwPEZx

is the zero sequence reactance reach of the line in /phase for phaseto-ground fault in zone direction for zone x (x=1-5, or RV)

R1FwPEZx

is the positive sequence resistive reach of the line in /phase for


phase-to-ground fault in zone direction for zone x (x=1-5, or RV)

X1FwPEZx

is the positive sequence reactance reach of the line in /phase for


phase-to-ground fault in zone direction for zone x (x=1-5, or RV)

For an earth fault in phase A, the angle between the compensation voltage and the
polarizing voltage Vpol is,

= arg [VA ( I A + 3I 0 K N ) Z 1set ] arg(V pol )


(Equation 84)

ANSIEQUATION15021 V1 EN

where

VA
IA

is the phase voltage in faulty phase A


is the phase current in faulty phase A

3I0

is the zero-sequence current in faulty phase A

Z 1set

is the complex positive sequence impedance of the line in /phase for


phase-to-ground fault in zone direction

Vpol

is the polarizing voltage in phase A

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

337

Section 7
Impedance protection

1MRK 502 066-UUS A

IAjX

Vcomp VA ( I A 3I 0 K N ) Z1set

3I 0 K N Z1set

VA

I A Z1set

V pol

IAR
ANSI15000059-1-en.vsdx

ANSI15000059 V1 EN

Figure 139:

Simplified offset mho characteristic and vector diagram for phase A-toground fault

Operation occurs if 90 270 .


Offset mho
The condition for operation of offset mho at phase-to-earth fault is that the angle
between the two compensated voltages is equal to or greater than 90, see figure 71. The
angle will be 90 for fault location on the boundary of the circle.

= arg VA ( I A + 3I 0 K N ) Z 1set arg VA ( I A + 3I 0 K N Z 1RVset ]

(Equation 85)

ANSIEQUATION15022 V1 EN

where

Z 1RVset

338

is the complex positive sequence impedance of the line in /phase for


phase-to-ground fault opposite to zone direction and is defined as,

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Z 1RVset = R1RvPEZx + j X 1RvPEZx


(Equation 86)

IECEQUATION15023 V1 EN

where
X1RvPEZx

is the positive sequence reactance reach for phase-to-ground fault


opposite to zone direction for zone x (x=1-5 and RV)

R1RvPEZx

is the positive sequence resistive reach for phase-to-ground fault


opposite to zone direction for zone x (x=1-5 and RV) and expressed
by,

R1FwPEZx
R1RvPEZx = X 1RvPEZx

X 1FwPEZx
(Equation 87)

IECEQUATION15024 V1 EN

IA jX

Vcomp1 VA ( I A 3I 0 K N ) Z1set

( I A 3I 0 K N ) Z1set
VA

Vcomp 2 VA ( I A 3I 0 K N ) Z1RVset )

( I A 3I 0 K N ) Z1RVset

IA R

ANSI15000057-1-en.vsdx

ANSI15000057 V1 EN

Figure 140:

Simplified offset mho characteristic and voltage vector for phase A-toground fault

Operation occurs if 90 270 .


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

339

Section 7
Impedance protection
7.6.7.8

1MRK 502 066-UUS A

Load encroachment
In some cases the load impedance might enter the zone characteristic without any fault on
the protected line. The phenomenon is called load encroachment and it might occur when
an external fault is cleared and high emergency load is transferred on the protected line.
The effect of load encroachment is illustrated in the left part of figure 141. The entrance
of the load impedance inside the characteristic is not allowed and the previous way of
handling this was to consider it with the settings, that is, with a security margin between
the distance zone and the minimum load impedance. This has the drawback that it will
reduce the sensitivity of the protection, that is, the ability to detect resistive faults.
The IED has a built-in function which shapes the characteristic according to the right part
of figure 141. The load encroachment algorithm will increase the possibility to detect high
fault resistances, especially for phase-to-ground faults at remote line end.For example, for
a given setting of the load angle LdAngle the resistive blinder for the zone measurement
can be expanded according to the right part of the figure 141, given higher fault resistance
coverage without risk for unwanted operation due to load encroachment. This is valid in
both directions.
The use of the load encroachment feature is essential for long heavily loaded lines, where
there might be a conflict between the necessary emergency load transfer and necessary
sensitivity of the distance protection. The function can also preferably be used on heavy
loaded medium long lines. For short lines, the major concern is to get sufficient fault
resistance coverage. Load encroachment is not a major problem. Nevertheless, always set
RLdFwd, RldRev and LdAngleaccording to the expected maximum load since these
settings are used internally in the function as reference points to improve the performance
of the phase selection.
X
Zm

Zm
ZL
Load impedance area in
forward direction
R

LdAngle
LdAngle
R
LdAngle

LdAngle
RldRev

RLdFwd

ANSI05000495_2_en.vsd
ANSI05000495 V2 EN

Figure 141:

340

Load encroachment phenomena and shaped load encroachment


characteristic

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.6.7.9

Simplified logic schemes


PHSA, PHSB,...PHSCA are internal binary logical signals from the Phase-selection
element. They correspond directly to the six loops of the distance zones and determine
which loops should be released to possibly issue a pickup or a trip.
FWA, FWB,...FWCA and RVA, RVB,...RVCA are the internal binary signals from the
Directional element. An FW signal is set true if the criteria for a forward fault or load is
fulfilled for its particular loop. The equivalent applies to the reverse (RV) signals.
The internal input 'IN present' is true if the residual current (3I0) exceeds 7% of IBase.
However, if current transformer saturation is detected, this criterion is changed to residual
voltage (3V0) exceeding 5% of VBase/sqrt(3) instead.

0
15 ms

AND

OR

0
15 ms

AND

OR

0
15 ms

AND

OR

0
15 ms

AND

0
15 ms

AND

OR

PHSA
PHSB

PHG_FLT

PHSC
PHSAB
PHSBC
PHSCA
OR

BLOCK
LOVBZ

PHPH_FLT

OR

OR

PU_ND
PU_PHS
ANSI12000133-1-en.vsd

ANSI12000133 V1 EN

Figure 142:

Additional pickup outputs 1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

341

Section 7
Impedance protection

1MRK 502 066-UUS A

PHSA
FWA
PHSB
FWB
PHSC
FWC

AND
AND

OR

0
15 ms

AND

OR

0
15 ms

AND

OR

0
15 ms

AND

FWD_A

AND

PHSAB
FWAB
PHSBC
FWBC
PHSCA
FWCA

AND
AND

FWD_B

FWD_C

AND
OR

IN present

BLOCK
LOVBZ

AND

=1

FWD_G
FWD_1PH

OR
=2

=3

FWD_2PH

FWD_3PH

ANSI12000134-1-en.vsd
ANSI12000134 V1 EN

Figure 143:

Additional pickup outputs 2

FWD(n & mn)

DIR(n & mn)Z1

FWD(n & mn)

DIR(n & mn)Z2

REV(n & mn)

DIR(n & mn)ZRV


DirModeZ3-5

TRUE (1)
FWD(n & mn)
REV(n & mn)

Non-directional
Forward
Reverse

DIR(n & mn)Z3-5

ANSI12000137-1-en.vsd
ANSI12000137 V1 EN

Figure 144:

342

Connection of directional signals to zones

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

TZx

0
15 ms

BLKTRZx
BLOCK
LOVBZ
BLKZx

TRIPZx

AND

OR

AND

OR

AND
AND

AZx
BZx
CZx
PPZx
PGZx

OR

NDZx

0
15 ms

AND

0
15 ms

AND

0
15 ms

AND

0
15 ms

AND

0
15 ms

AND

TR_A_Zx
TR_B_Zx
TR_B_Zx
PU_A_Zx
PU_B_Zx
PU_C_Zx
PU_Zx
PU_ND_Zx

ANSI12000138-1-en.vsd
ANSI12000138 V1 EN

Figure 145:

Pickup and trip outputs

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

343

Section 7
Impedance protection

1MRK 502 066-UUS A

TimerModeZx =
Enable Ph-Ph,
Ph-G

AND

PPZx

AND

PGZx

BLOCK
LOVBZ
BLKZx
BLKTRZx

OR

AND

tPPZx
0

AND

TZx

OR
OR

AND

tPPZx
0

AND

OR

TimerLinksZx

OR

ZoneLinkStart

PUPHS

OR

Phase Selection
1st pickup zone

LNKZ1
LNKZ2
LNKZRV
OR
LNKZ3
LNKZ4
LNKZ5

LoopLink (tPP-tPG)
LoopLink & ZoneLink
no links

FALSE (0)
AND

LNKZx

TimerLinksZx =
LoopLink & ZoneLink

ANSI12000139-2-en.vsdx

ANSI12000139 V2 EN

Figure 146:

344

Logic for linking of timers

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

PHSA
RVA
PHSB
RVB
PHSC
RVC

AND
AND

OR

0
15 ms

AND

OR

0
15 ms

AND

OR

0
15 ms

AND

REV_A

AND

PHSAB
RVAB
PHSBC
RVBC
PHSCA
RVCA

AND
AND

REV_B

REV_C

AND
OR

IN present
BLOCK
LOVBZ

AND

REV_G

OR
ANSI12000141-1-en.vsd

ANSI12000141 V1 EN

Figure 147:

Additional pickup outputs 3

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

345

Section 7
Impedance protection

1MRK 502 066-UUS A

PGZx

OR

ZMAZx
PHSA
DIRAZx
ZMBZx
PHSB
DIRBZx
ZMCZx
PHSC
DIRCZx

AND
AND
AND
AND

AZx

OR

AND
AND

ZMABZx
PHSAB
DIRABZx
ZMLBCZx
PHSBC
DIRBCZx
ZMCAZx
PHSCA
DIRCAZx

BZx

OR

AND
AND

OR

AND

CZx

AND
AND
AND
OR

OR

PPZx
NDZx

ANSI12000140-1-en.vsd
ANSI12000140 V1 EN

Figure 148:

7.6.7.10

Intermediate logic

Measurement
Measurement supervision
The protection, control, and monitoring IEDs have functionality to measure and further
process information for currents and voltages obtained from the pre-processing blocks.
The number of processed alternate measuring quantities depends on the type of IED and
built-in options.
The information on measured quantities is available for the user at different locations:

346

Locally by means of the local HMI


Remotely using the monitoring tool within PCM600 or over the station bus
Internally by connecting the analog output signals to the Disturbance Report function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Zero point clamping


Measured value below zero point clamping limit is forced to zero. This allows the noise
in the input signal to be ignored. The zero point clamping limit is a setting (XZeroDb
where X equals Z).
Continuous monitoring of the measured quantity
Users can continuously monitor the measured quantity available in the function block by
means of four defined operating thresholds, see figure 126. The monitoring has two
different modes of operating:

Overfunction, when the measured current exceeds the High limit (XHiLim) or Highhigh limit (XHiHiLim) pre-set values
Underfunction, when the measured current decreases under the Low limit (XLowLim)
or Low-low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 126.

Y
X_RANGE = 3
High-high limit

X_RANGE= 1

Hysteresis

High limit
X_RANGE=0

X_RANGE=0
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4

IEC05000657-2-en.vsdx

IEC05000657 V2 EN

Figure 149:

Presentation of operating limits

Each analog output has one corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: Highhigh limit exceeded, 2: below Low limit and 4: below Low-low limit). The output may be
connected to a measurement expander block (XP (RANGE_XP)) to get measurement
supervision as binary signals.
The logical value of the functional output signals changes according to figure 126.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

347

Section 7
Impedance protection

1MRK 502 066-UUS A

The user can set the hysteresis (XLimHyst), which determines the difference between the
operating and reset value at each operating point, in wide range for each measuring
channel separately. The hysteresis is common for all operating values within one channel.
Actual value of the measured quantity
The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting of the
value to the higher levels depends on the selected reporting mode. The following basic
reporting modes are available:

Cyclic reporting (Cyclic)


Magnitude dead-band supervision (Dead band)
Integral dead-band supervision (Int deadband)

Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of magnitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.

348

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Value Reported
(1st)

Value Reported

Value Reported

Value Reported

Value Reported

Y3
Y2

Y4

Y1

Y5

(*)Set value for t: XDbRepInt

t (*)

Value 5

Value 4

t (*)

Value 3

t (*)

Value 2

Value 1

t (*)

IEC05000500-2-en.vsdx

IEC05000500 V2 EN

Figure 150:

Periodic reporting

Magnitude dead-band supervision


If a measuring value is changed, compared to the last reported value, and the change is
larger than the Y pre-defined limits that are set by user (UDbRepIn), then the measuring
channel reports the new value to a higher level. This limits the information flow to a
minimum necessary. Figure 128 shows an example with the magnitude dead-band
supervision. The picture is simplified: the process is not continuous but the values are
evaluated with a time interval of one execution cycle from each other.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

349

Section 7
Impedance protection

1MRK 502 066-UUS A

Value Reported

Y
Value Reported
(1st)

Value Reported
Y3
Y2

Y1

Value Reported
Y
Y

Y
Y

Y
Y

t
IEC99000529-2-en.vsdx

IEC99000529 V2 EN

Figure 151:

Magnitude dead-band supervision reporting

After the new value is reported, the Y limits for dead-band are automatically set around
it. The new value is reported only if the measured quantity changes more than defined by
the Y set limits.
Integral dead-band reporting
The measured value is reported if the time integral of all changes exceeds the pre-set limit
(XDbRepInt), figure 129, where an example of reporting with integral dead-band
supervision is shown. The picture is simplified: the process is not continuous but the
values are evaluated with a time interval of one execution cycle from each other.
The last value reported, Y1 in figure 129 serves as a basic value for further measurement.
A difference is calculated between the last reported and the newly measured value and is
multiplied by the time increment (discrete integral). The absolute values of these integral
values are added until the pre-set value is exceeded. This occurs with the value Y2 that is
reported and set as a new base for the following measurements (as well as for the values
Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals with
small variations that can last for relatively long periods.
350

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

A1 >=
pre-set value

Y
A >=
pre-set value

A2 >=
pre-set value
Y3

Y2
Value Reported
(1st)

A1

Value
Reported

A2
Value
Reported

Y4

A3 + A4 + A5 + A6 + A7 >=
pre-set value
A4
A3

Value
Reported

Y1

A5

A6

A7

Y5
Value
Reported
t
IEC99000530-2-en.vsdx

IEC99000530 V2 EN

Figure 152:

Reporting with integral dead-band supervision

Measurement ZMMXU
The magnitude and angle of the impedance for each phase are available on the outputs
(ZLxMAG and ZLxANGL (x=1,2,3)). Each analogue output has a corresponding
supervision level output (ZLxRANG, ZLxANGR). The supervision output signal is an
integer in the interval 0-4, see section Measurement supervision.
Impedance measurement is calculated based on VA / IA , VB / IB , VC / IC , where VX and

IX are phase-to-ground voltage and phase-to-ground current.


When the operating current is too low, the impedance measurement can be erroneous. In
order to avoid such error, minimum operating current will be checked. For phase currents
lower than 3% of IBase, the magnitude of impedance is force to 9999999 and the angle is
forced to 0 degree.
Inside the function, to ensure the readability of the output for the users, ZLxMAG and
ZLxANGL (x=1,2,3) will not change more often than a certain time period, for example,
every 100 ms.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

351

Section 7
Impedance protection
7.6.8

1MRK 502 066-UUS A

Technical data
Table 128:

ZMFCPDIS (21) technical data

Function

Range or value

Accuracy

Number of zones

3 selectable
directions, 3 fixed
directions

Minimum operate current, Ph-Ph


and Ph-E

(5 - 6000)% of IBase

1.0% of Ir

Positive sequence reactance


reach, Ph-E and Ph-Ph loop

(30 - 3000) /phase

Positive sequence resistance


reach, Ph-E and Ph-Ph loop

(30 - 3000) /phase

Zero sequence reactance reach

(100.00 - 9000.00) /p

Zero sequence resistive reach

(15.00 - 3000.00) /p

Fault resistance reach, Ph-E and


Ph-Ph

(1.00 - 9000.00) /l

Dynamic overreach

< 5% at 85 deg
measured with CVT's
and 0.5 < SIR <30

Definite time delay to trip, Ph-E


and Ph-Ph operation

(0.000 - 60.000) s

Operate time

16 ms typically

Reset time at 0.1 to 2 x Zreach

Min = 20 ms
Max = 35 ms

Reset ratio

105% typically

" +- 2.0% static accuracy +- 2.0 deg static


angular accuracy Conditions: Voltage range:
(0.1 - 1.1) x Ur Current range: (0.5 - 30) x Ir
Angle: At 0 deg and 85 deg"

0.2% or 35 ms whichever is greater


IEC 60255-121
-

7.7

Pole slip protection PSPPPAM (78)

7.7.1

Identification

7.7.2

Function description

IEC 61850
identification

Pole slip protection

PSPPPAM

IEC 60617
identification
Ucos

ANSI/IEEE C37.2
device number
78

Functionality
The phenomenon pole slip, also named out of step conditions, occurs when there is phase
opposition between different parts of a power system. This is often shown in a simplified

352

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

way as two equivalent generators connected to each other via an equivalent transmission
line and the phase difference between the equivalent generators is 180.
Angle = 90

Angle = -90

Centre of Pole Slip


en07000003.vsd
IEC07000003 V1 EN

Figure 153:

The centre of pole slip

The centre of the pole slip can occur in the generator itself or somewhere in the power
system. When a pole slip occurs within the generator it is essential to trip the generator. If
the centre of pole slip occurs outside any generator the power system should be split into
two different parts that could have the ability to get stable operating conditions.
Pole slip protection (PSPPPAM ,78) function in the IED can be used both for generator
protection application as well as, line protection applications.
The situation with pole slip of a generator can be caused by different reasons.
A short circuit may occur in the external power grid, close to the generator. If the fault
clearing time is too long, the generator will accelerate so much, that the synchronism
cannot be maintained.
Undamped oscillations occur in the power system, where generator groups at different
locations, oscillate against each other. If the connection between the generators is too
weak the magnitude of the oscillations will increase until the angular stability is lost.
The operation of a generator having pole slip will give risk of damages to the generator,
shaft and turbine.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

353

Section 7
Impedance protection

1MRK 502 066-UUS A

At each pole slip there will be significant torque impact on the generator-turbine
shaft.
In asynchronous operation there will be induction of currents in parts of the generator
normally not carrying current, thus resulting in increased heating. The consequence
can be damages on insulation and stator/rotor iron.

The Pole slip protection (PSPPPAM ,78) function shall detect pole slip conditions and trip
the generator as fast as possible if the locus of the measured impedance is inside the
generator-transformer block. If the centre of pole slip is outside in the power grid, the first
action should be to split the network into two parts, after line protection action. If this fails
there should be operation of the generator PSPPPAM (78) in zone 2, to prevent further
damages to the generator, shaft and turbine.

7.7.3

Function block
PSPPPAM (78)
I3P*
TRIP
V3P*
TRIP1
BLOCK
TRIP2
BLKGEN
PICKUP
BLKMOTOR
ZONE1
EXTZONE1
ZONE2
GEN
MOTOR
SFREQ
SLIPZOHM
SLIPZPER
VCOS
VCOSPER
ANSI10000045-1-en.vsd
ANSI10000045 V1 EN

Figure 154:

7.7.4

Signals
Table 129:
Name

354

PSPPPAM (78) function block

PSPPPAM (78) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Current group connection

V3P

GROUP
SIGNAL

Voltage group connection

BLOCK

BOOLEAN

Block of function

BLKGEN

BOOLEAN

Block operation in generating direction

BLKMOTOR

BOOLEAN

Block operation in motor direction

EXTZONE1

BOOLEAN

Extension of zone1 with zone2 region

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 130:

PSPPPAM (78) Output signals

Name

7.7.5
Table 131:
Name

Type

Description

TRIP

BOOLEAN

Common trip signal

TRIP1

BOOLEAN

Trip1 after the N1Limit slip in zone1

TRIP2

BOOLEAN

Trip2 after the N2Limit slip in zone2

PICKUP

BOOLEAN

Common start signal

ZONE1

BOOLEAN

First slip in zone1 region

ZONE2

BOOLEAN

First slip in zone2 region

GEN

BOOLEAN

Generator is faster than the system

MOTOR

BOOLEAN

Generator is slower than the system

SFREQ

REAL

Slip frequency

SLIPZOHM

REAL

Slip impedance in ohms

SLIPZPER

REAL

Slip impedance in percent of ZBase

VCOS

REAL

UCosPhi voltage

VCOSPER

REAL

VCosPhi voltage in percent of VBase

Settings
PSPPPAM (78) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Enable / Disable

OperationZ1

Disabled
Enabled

Enabled

Operation Enable/Disable zone Z1

OperationZ2

Disabled
Enabled

Enabled

Operation Enable/Disable zone Z2

ImpedanceZA

0.00 - 1000.00

0.01

10.00

Forward impedance in % of Zbase

ImpedanceZB

0.00 - 1000.00

0.01

10.00

Reverse impedance in % of Zbase

ImpedanceZC

0.00 - 1000.00

0.01

10.00

Impedance of zone1 limit in % of Zbase

AnglePhi

72.00 - 90.00

Deg

0.01

85.00

Angle of the slip impedance line

pick up Angle

0.0 - 180.0

Deg

0.1

110.0

Rotor angle for the pickup signal

TripAngle

0.0 - 180.0

Deg

0.1

90.0

Rotor angle for the trip1 and trip2 signals

N1Limit

1 - 20

Count limit for the trip1 signal

N2Limit

1 - 20

Count limit for the trip2 signal

Table 132:
Name
ResetTime

PSPPPAM (78) Group settings (advanced)


Values (Range)

Unit

0.000 - 60.000

Step
0.001

Default
5.000

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description
Time without slip to reset all signals

355

Section 7
Impedance protection

Table 133:
Name

1MRK 502 066-UUS A

PSPPPAM (78) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

MeasureMode

PosSeq
AB
BC
CA

PosSeq

Measuring mode (PosSeq, AB, BC, CA)

InvertCTcurr

No
Yes

No

Invert current direction

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

7.7.6

Monitored data
Table 134:
Name

7.7.7

PSPPPAM (78) Monitored data


Type

Values (Range)

Unit

Description

SFREQ

REAL

Hz

Slip frequency

SLIPZOHM

REAL

Ohm

Slip impedance in ohms

SLIPZPER

REAL

Slip impedance in percent of


ZBase

VCOS

REAL

kV

UCosPhi voltage

VCOSPER

REAL

VCosPhi voltage in percent of


VBase

Operation principle
If the generator is faster than the power system, the rotor movement in the impedance and
voltage diagram is from right to left and generating is signaled. If the generator is slower
than the power system, the rotor movement is from left to right and motoring is signaled
(the power system drives the generator as if it were a motor).
The movements in the impedance plane can be seen in Figure 155. The transient behavior
is described by the transient EMF's EA and EB, and by X'd, XT and the transient system
impedance ZS.

356

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Zone 1
EB

Zone 2

Xd

XT

XS

IED

EA

jX

A
XS

Pole slip
impedance
movement

XT

Apparent generator
impedance

Xd
B

IEC06000437_2_en.vsd
IEC06000437 V2 EN

Figure 155:

Movements in the impedance plain

where:
X'd

= transient reactance of the generator

XT

= short-circuit reactance of the step-up transformer

ZS

= impedance of the power system A

The detection of rotor angle is enabled when:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

357

Section 7
Impedance protection

1MRK 502 066-UUS A

the minimum current exceeds 0.10 IN (IN is IBase parameter set under general
setting).
the maximum voltage falls below 0.92 VBase
the voltage Ucos (the voltage in phase with the generator current) has an angular
velocity of 0.2...8 Hz and
the corresponding direction is not blocked.

en07000004.vsd
IEC07000004 V1 EN

Figure 156:

Different generator quantities as function of the angle between the


equivalent generators

An alarm is given when movement of the rotor is detected and the rotor angle exceeds the
angle set for 'WarnAngle'.
Slipping is detected when:

a change of rotor angle of min. 50 ms is recognized


the slip line is crossed between ZA and ZB.

When the impedance crosses the slip line between ZB and ZC it counts as being in zone 1
and between ZC and ZA in zone 2. The entire distance ZA-ZB becomes zone 1 when signal
EXTZONE1 is high (external device detects the direction of the centre of slipping).

358

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

After the first slip, the signals ZONE1 or ZONE2 and depending on the direction of slip
- either GEN or MOTOR are issued.
Every time pole slipping is detected, the impedance of the point where the slip line is
crossed and the instantaneous slip frequency are displayed as measurements.
Further slips are only detected, if they are in the same direction and if the rate of rotor
movement has reduced in relation to the preceding slip or the slip line is crossed in the
opposite direction outside ZA-ZB. A further slip in the opposite direction within ZA-ZB
resets all the signals and is then signalled itself as a first slip.
The TRIP1 tripping command and signal are generated after N1 slips in zone 1, providing
the rotor angle is less than TripAngle. The TRIP2 signal is generated after N2 slips in zone
2, providing the rotor angle is less than TripAngle.
All signals are reset if:

the direction of movement reverses


the rotor angle detector resets without a slip being counted or
no rotor relative movement was detected during the time ResetTime.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

359

Section 7
Impedance protection

1MRK 502 066-UUS A

Imin > 0.10 IBase

AND

Vcos< 0.92 VBase

PICKUP

AND
0.2 Slip.Freq. 8 Hz

startAngle
ZONE1

AND

Z cross line ZC - ZB

ZONE2

AND

Z cross line ZA - ZC

Counter
a
b

N1Limit

ab

TRIP1

AND

tripAngle

OR

TRIP

Counter
a
ab
b

N2Limit

TRIP2

AND

ANSI07000005.vsd

ANSI07000005 V2 EN

Figure 157:

7.7.8

Simplified logic diagram for pole slip protection PSPPPAM (78)

Technical data
Table 135:

PSPPPAM (78) technical data

Function

360

Range or value

Accuracy

Impedance reach

(0.00 - 1000.00)% of Zbase

2.0% of Vn/In

Zone 1 and Zone 2 trip counters

(1 - 20)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.8

Out-of-step protection OOSPPAM (78)

7.8.1

Identification
Function description
Out-of-step protection

IEC 61850
identification

IEC 60617
identification

OOSPPAM

ANSI/IEEE C37.2
device number
78

<

7.8.2

Functionality
The out-of-step protection OOSPPAM (78) function in the IED can be used for both
generator protection and as well for line protection applications.
The main purpose of the OOSPPAM (78) function is to detect, evaluate, and take the
required action during pole slipping occurrences in the power system.
The OOSPPAM (78) function detects pole slip conditions and trips the generator as fast
as possible, after the first pole-slip if the center of oscillation is found to be in zone 1,
which normally includes the generator and its step-up power transformer. If the center of
oscillation is found to be further out in the power system, in zone 2, more than one poleslip is usually allowed before the generator-transformer unit is disconnected. A parameter
setting is available to take into account the circuit breaker opening time. If there are several
out-of-step relays in the power system, then the one which finds the center of oscillation
in its zone 1 should operate first.
Two current channels I3P1 and I3P2 are available in OOSPPAM function to allow the
direct connection of two groups of three-phase currents; that may be needed for very
powerful generators, with stator windings split into two groups per phase, when each
group is equipped with current transformers. The protection function performs a simple
summation of the currents of the two channels I3P1 and I3P2.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

361

Section 7
Impedance protection
7.8.3

1MRK 502 066-UUS A

Function block
OOSPPAM (78)
I3P1*
TRIP
I3P2*
TRIPZ1
V3P*
TRIPZ2
BLOCK
PICKUP
BLKGEN
GENMODE
BLKMOT
MOTMODE
EXTZ1
R
X
SLIPFREQ
ROTORANG
VCOSPHI
ANSI14000055-1-en.vsd
ANSI12000188 V2 EN

Figure 158:

7.8.4

OOSPPAM (78) function block

Signals
Table 136:
Name

OOSPPAM (78) Input signals


Type

Default

Description

I3P1

GROUP
SIGNAL

Group connection for three-phase current input 1

I3P2

GROUP
SIGNAL

Group connection for three-phase current input 2

V3P

GROUP
SIGNAL

Group connection for three-phase voltage input

BLOCK

BOOLEAN

Block of function

BLKGEN

BOOLEAN

Block operation in generating direction

BLKMOT

BOOLEAN

Block operation in motor direction

EXTZ1

BOOLEAN

Extension of zone1 reach to zone2 settings

Table 137:
Name

OOSPPAM (78) Output signals


Type

Description

TRIP

BOOLEAN

Common trip, issued when either zone 1 or zone 2 trip

TRIPZ1

BOOLEAN

Zone 1 trip

TRIPZ2

BOOLEAN

Zone 2 trip

PICKUP

BOOLEAN

Set when measured impedance enters lens


characteristic

GENMODE

BOOLEAN

Generator rotates faster than the system during pole slip

MOTMODE

BOOLEAN

Generator rotates slower than the system during pole


slip

REAL

Real part of measured positive-sequence impedance %


of VBase/(sqrt(3)*IBase)

Table continues on next page


362

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

7.8.5
Table 138:
Name

Type

Description

REAL

Imaginary part of measured positive-seq impedance %


of VBase/(sqrt(3)*IBase)

SLIPFREQ

REAL

Slip frequency in Hz

ROTORANG

REAL

Rotor angle as estimated by the out-of-step function

VCOSPHI

REAL

Estimated Ucos(Phi) voltage during pole slip, in V

Settings
OOSPPAM (78) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OperationZ1

Disabled
Enabled

Enabled

Operation Zone1 Enable/Disable

ReachZ1

1.00 - 100.00

% ZFw

0.01

50.00

Percentage part of total forward impedance;


defines Z1 reach

OperationZ2

Disabled
Enabled

Enabled

Operation Z2 Enable/Disable

tBreaker

0.000 - 1.000

0.001

0.040

Breaker opening time; use default 0s value if it


is unknown

Table 139:
Name

OOSPPAM (78) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

NoOfSlipsZ1

1 - 20

Number of pole-slips in zone 1 required for


zone 1 trip

NoOfSlipsZ2

1 - 60

Number of pole-slips in zone 2 required for


zone 2 trip

tReset

1.000 - 60.000

0.001

6.000

Time without any slip required to completely


reset function

Table 140:
Name

OOSPPAM (78) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

ForwardR

0.00 - 1000.00

%ZB

0.01

1.00

Real part of total forward impedance for Z2, in


% of VBase/(sqrt(3)*IBase)

ForwardX

0.00 - 1000.00

%ZB

0.01

10.00

Imag. part of total forward impedance for Z2, in


% of VBase/(sqrt(3)*IBase)

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

363

Section 7
Impedance protection

Name

1MRK 502 066-UUS A

Step

Default

ReverseR

0.00 - 1000.00

%ZB

0.01

1.00

Real part of source impedance behind relay, in


% of VBase/(sqrt(3)*IBase)

ReverseX

0.00 - 1000.00

%ZB

0.01

10.00

Imag. part of source impedance behind relay,


in % of VBase/(sqrt(3)*IBase)

InvertCTCurr

No
Yes

No

Invert current direction

Table 141:
Name

Values (Range)

Unit

Description

OOSPPAM (78) Non group settings (advanced)


Step

Default

pick up Angle

90.0 - 130.0

Deg

0.1

110.0

Angle between two rotors to get the pick up


signal, in deg

TripAngle

15.0 - 90.0

Deg

0.1

60.0

Maximum rotor angle to allow trip signals, in


deg

7.8.6

Values (Range)

Description

Monitored data
Table 142:
Name

7.8.7

Unit

OOSPPAM (78) Monitored data


Type

Values (Range)

Unit

Description

CURRENT

REAL

Magnitude of the measured


positive-sequence current, in
A

VOLTAGE

REAL

kV

Magnitude of the measured


positive-sequence voltage, in
V

REAL

Real part of measured


positive-sequence impedance
% of VBase/(sqrt(3)*IBase)

REAL

Imaginary part of measured


positive-seq impedance % of
VBase/(sqrt(3)*IBase)

SLIPFREQ

REAL

Hz

Slip frequency in Hz

ROTORANG

REAL

deg

Rotor angle as estimated by


the out-of-step function

VCOSPHI

REAL

kV

Estimated Ucos(Phi) voltage


during pole slip, in V

Operation principle
General
Under balanced and stable conditions, a generator operates with a constant rotor angle
(power angle), delivering active electrical power to the power system, which is

364

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

approximately equal to the input mechanical power on the generator axis.The currents and
voltages are constant and stable. An out-of-step condition is characterized by periodic
changes in the rotor angle, that leads to a wild flow of the synchronizing power; so there
are also periodic changes of rotational speed, currents and voltages. When displayed in the
complex impedance plane, these changes are characterized by a cyclic change in the
complex load impedance Z(R, X) as measured at the terminals of the generator, or at the
location of the instrument transformers of a power line connecting two power subsystems.
This is shown in Figure 159.
trajectory

1.5

of Z(R, X)
The 2nd
pole slip
occurred

Imaginary part (X) of Z in Ohms

The 1st
pole slip
occurred

Pre-disturbance
RE
normal load
- - -------- - - Z(R, X)
- - 3 ------ ------ - - Zone 2
--- 2 1 --0
---^ --^ ^ ^ ^ ---^ ^ ^ ^ ^ ^ ^ ---^ -^- ^ ^ ^ --^
-Zone 1
------ relay
-R in Ohms
-limit of reach -----lens determined
- - ---- -----0- - pre-disturbance Z(R, X)
- by the setting - - - - -------- - - - - 1 Z(R, X) under 3-phase fault
Pickup Angle = 120 SE
2 Z(R, X) when fault cleared

0.5

-0.5

-1

to the 3rd
pole-slip

X in Ohms

-1.5

-1

-0.5

Z when pole-slip declared

0
0.5
Real part (R) of Z in Ohms

1.5

ANSI10000109-1-en.vsd

ANSI10000109 V1 EN

Figure 159:

Loci of the complex impedance Z(R, X) for a typical case of generator


losing step after a short circuit that was not cleared fast enough

Under typical, normal load conditions, when the protected generator supplies the active
and the reactive power to the power system, the complex impedance Z(R, X) is in the 1st
quadrant, point 0 in Figure 159. One can see that under a three-phase fault conditions, the
centre of oscillation is at the point of fault, point 1, which is logical, as all three voltages
are zero or near zero at that point. Under the fault conditions the generator accelerated and
when the fault was finally cleared, the complex impedance Z(R, X) jumped to the point 2.
By that time, the generator has already lost its step, Z(R, X) continues its way from the
right-hand side to the left-hand side, and the 1st pole-slip cannot be avoided. If the
generator is not immediately disconnected, it will continue pole-slipping see Figure
159, where two pole-slips (two pole-slip cycles) are shown. Under out-of-step conditions,
the centre of oscillation is where the locus of the complex impedance Z(R, X) crosses the
(impedance) line connecting the points SE (Sending End), and RE (Receiving End). The
point on the SE RE line where the trajectory of Z(R, X) crosses the impedance line can
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

365

Section 7
Impedance protection

1MRK 502 066-UUS A

change with time and is mainly a function of the internal induced voltages at both ends of
the equivalent two-machine system, that is, at points SE and RE.
Measurement of the magnitude, direction and rate-of-change of load impedance relative
to a generators terminals provides a convenient and generally reliable means of detecting
whether machines are out-of-step and pole-slipping is taking place. Measurement of the
rotor (power) angle is important as well.
Rotor (power) angle can be thought of as the angle between the two lines, connecting
point 0 in Figure 159, that is, Z(R, X) under normal load, with the points SE and RE,
respectively. These two lines are not shown in Figure 159. Normal values of the power
angle, that is, under stable, steady-state, load conditions, are from 30 to 60 electrical
degrees. It can be observed in Figure 160 that the angle reaches 180 degrees when the
complex impedance Z(R, X) crosses the impedance line SE RE. It then changes the sign,
and continues from -180 degrees to 0 degrees, and so on. Figure 160 shows the rotor
(power) angle and the magnitude of Z(R, X) against time for the case from Figure 159.

Impe dance Z in Ohm and rotor a ngle in radian

4
3

|Z| in Ohms
angle in rad

normal
load

rotor (power)
angle

Z(R, X) unde r fa ult lies


on the impe dance line
or nea r (for 3-ph faults )

|Z|

0
0
fault 500 ms
fa ult
occ urrs

-1

Unde r 3-pha s e fa ult


condition rotor a ngle
of a pp. 180 de gre e s
is m e a s ure d ...

-2

3
2

-3

1
-4

200

400

Z(R,X) cros s e d
the im pe da nce line , Z-line ,
conne cting points S E - RE

600
800
1000
Time in millis econds

1200

1400

IEC10000110-2-en.vsd
IEC10000110 V2 EN

Figure 160:

Rotor (power) angle and magnitude of the complex impedance Z(R, X)


against the time

In order to be able to fully understand the principles of OOSPPAM (78), a stable case, that
is, a case where the disturbance does not make a generator to go out-of-step, must be
shown.
366

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

SE

Imaginary part (X) of Z in Ohms

0.8

RE

G
relay

0.4
0.2
0
-0.2
-0.4
-0.6

this circle forms


the right-hand side
edge of the lens

-0.8
-1

Z(R,X) 20 ms
after line out

fault

- - - - - RE
- ----- ----- 4 - ---zone 2 - ------ 2
---1
------ fault
-3
X-line ^ -^ ^ ^ ^ ---^ ^
^
^
^ ^ ^ ^ ^-- ^ ^ ^ -^
----- Z-line
--------limit of
-- relay
lens -reach
-110 -----zone 1- ------------ ------- ---- - -- - - -- - SE

0.6

-1

X [Ohm]

-0.5

pre-fault
Z(R,X)
5
0

0 pre-fault Z(R, X)
3 Z(R, X) under fault
5 Z 20 ms after line out
6 pow er line reclosed

0
0.5
Real part (R) of Z in Ohms

1.5

ANSI10000111-1-en.vsd

ANSI10000111 V1 EN

Figure 161:

A stable case where the disturbance does not make the generator to go
out-of-step

It shall be observed that for a stable case, as shown in Figure 161, where the disturbance
does not cause the generator to lose step, the complex impedance Z(R, X) exits the lens
characteristic on the same side (point 4) it entered it (point 2), and never re-enters the lens.
In a stable case, where the protected generator remains in synchronism, the complex
impedance returns to quadrant 1, and, after the oscillations fade, it returns to the initial
normal load position (point 0), or near.

7.8.7.1

Lens characteristic
A precondition in order to be able to construct a suitable lens characteristic is that the
power system in which OOSPPAM (78) is installed, is modeled as a two-machine
equivalent system, or as a single machine infinite bus equivalent power system. Then the
impedances from the position of OOSPPAM (78) in the direction of the normal load flow
(that is from the measurement point to the remote system) can be taken as forward. The
lens characteristic, as shown in Figure159 and Figure161, is obtained so that two equal in
size but differently offset Mho characteristics are set to overlap. The resultant lens
characteristic is the loci of complex impedance Z(R, X) for which the rotor (power) angle
is constant, for example 110 degrees or 120 degrees; if the rotor (power) angle approaches
this value, then there is a high risk to have an out of step condition. The limit-of- reach
circle is constructed automatically by the algorithm; it is about 10% wider than the the
circle that has the line SE-RE as diameter (that is the out-of-step characteristic which

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

367

Section 7
Impedance protection

1MRK 502 066-UUS A

corresponds to the rotor (power) angle of 90 degrees). Figure 162 illustrates construction
of the lens characteristic for a power system.
X
Position of the OOS
- RE
- - relay is the origin of
--- the R - X plane
-- -------- Ze
-- Zone 2
--X-line
--determined
-- Zline
--by the ^ ^- ^
--^ ^ ^- ^
-^ ^ ^ ^
setting
^ ^ ^ --- ^
--^ ^ ^ReachZ1 --Ztr
R
---- Zone 1 -relay
-120 -- Z(R,X) ---- Z-line --Zgen
----limit-of-reach -- Lens is -the locus
--circle depends on-of constant
rotor (power)
----the position of the -- - angle,
e.g.
120.
- points SE and RE
- - -- - - - - - - Lens' width determined
SE
by the setting Pickup Angle

0.6

Imaginary part (X) of Z in Ohms

0.4
0.2
0
-0.2
-0.4
-0.6

-0.8

-0.6

-0.4

-0.2
0
0.2
0.4
Real part (R) of Z in Ohms

0.6

0.8

ANSI10000112-1-en.vsd

ANSI10000112 V1 EN

Figure 162:

Construction of the lens characteristic for a power system

ReverseZ(ReverseR, ReverseX)
Zgen(Rgen, Xgen)

ForwardZ(ForwardR, ForwardX)

Ztr(Rtr, Xtr)

Zline(Rline, Xline)

Transformer
13.8 / 220 kV

Generator
13.8 kV
13.8 kV

Zeq(Req, Xeq)

Infinite power
system
Power line
220 kV

System
equivalent

SE

REG

RE
Out-Of-Step
protection
OOSPPAM

ReverseR = Rg
ReverseX = Xd

ForwardR = Rtr + Rline + Req


For wardX = Xtr + Xline + Xeq

All impedances must be referred to the generator voltage 13.8 kV


ANSI10000113-1-en.vsd

ANSI10000113 V1 EN

Figure 163:

368

Example of an actual power system

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

To be able to automatically construct the lens characteristic for a system shown in Figure
163, the actual power system must be modeled as a two-machine equivalent system, or as
a single machine infinite bus equivalent system, the following information is necessary:
Zgen(Rgen, Xgen), Ztr(Rtr, Xtr), Zline(Rline, Xline), Zeq(Req, Xeq), and the setting
PickupAngle, for example 120 degrees. All impedances must be referred to the voltage
level where the out-of-step protection relay is placed; in the case shown in Figure 163 the
relay is connected to the terminals of the generator and, therefore, the previous quantities
shall be referred to the generator nominal voltage and nominal current. The impedances
from the position of the out-of-step protection in the direction of the normal load flow can
be taken as forward.
The out-of-step relay, as in Figure 163 looks into the system and the impedances in that
direction are forward impedances:

ForwardX = Xtr + Xline + Xeq (All values referred to generator voltage)


ForwardR = Rtr + Rline + Req (All values referred to generator voltage)

The impedances that can be measured in the reverse direction are:

ReverseX = Xd' (Generator transient reactance suitable for this protection)


ReverseR = Rg (Relatively very small, can often be neglected)

Resistances are much smaller than reactances, but in general can not be neglected. The
ratio (ForwardX + ReverseX) / (ForwardR + ReverseR) determines the inclination of the
Z-line, connecting the point SE (Sending End) and RE (Receiving End), and is typically
approximately 85 degrees. While the length of the Z-line depends on the values of
ForwardX, ReverseX, ForwardR, and ReverseR, the width of the lens is a function of the
setting PickupAngle.The lens is broader for smaller values of the PickupAngle, and
becomes a circle for PickupAngle = 90 degrees.
When the complex impedance Z(R, X) enters the lens, pole slipping is imminent, and a
pickup signal is issued. The angle recommended to form the lens is 110 or 120 degrees,
because it is this rotor (power) angle where problems with dynamic stability usually begin.
Rotor (power) angle 120 degrees is sometimes called the angle of no return because if
this angle is reached under generator power swings, the generator is most likely to lose
step.

7.8.7.2

Detecting an out-of-step condition


An out-of-step condition is characterized by periodic changes of the rotor angle, that leads
to a wild flow of the synchronizing power; so there are also periodic changes of rotational
speed, currents and voltages. When displayed in the complex impedance plane, these
changes are characterized by a cyclic change in the complex load impedance Z(R, X) as
measured at the terminals of the generator, or at the location of the instrument
transformers of a power line connecting two power sub-systems. This was shown in

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

369

Section 7
Impedance protection

1MRK 502 066-UUS A

Figure 159. When a synchronous machine is out-of-step, pole-slips occur. To recognize a


pole-slip, the complex impedance Z(R,X) must traverse the lens from right to left in case
of a generator and in the opposite direction in case of a motor. Another requirement is that
the travel across the lens takes no less than a specific minimum traverse time, typically
40...60 milliseconds. The above timing is used to discriminate a fault from an out-of-step
condition. In Figure 159, some important points on the trajectory of Z(R, X) are
designated. Point 0: the pre-fault, normal load Z(R, X). Point 1: impedance Z under a
three-phase fault with low fault resistance: Z lies practically on, or very near, the Z-line.
Transition of the measured Z from point 0 to point 1 takes app. 20 ms, due to Fourier
filters. Point 2: Z immediately after the fault has been cleared. Transition of the measured
Z from point 1 to point 2 takes approximately 20 ms, due to Fourier filters. The complex
impedance then travels in the direction from the right to the left, and exits the lens on the
opposite side. When the complex impedance exits the lens on the side opposite to its
entrance, the 1st pole-slip has already occurred and more pole-slips can be expected if the
generator is not disconnected. Figure 159 shows two pole-slips. Figures like Figure 159
and Figure 161 are always possible to draw by means of the analog output data from the
pole-slip function, and are of great help with eventual investigations of the performance
of the out-of-step function.

7.8.7.3

Maximum slip frequency


A pole-slip may be detected if it has a slip frequency lower than a maximum value fsMax.
The specific value of fsMax depends on the setting (parameter) PickupAngle (which
determines the width of the lens characteristic). A parameter in this calculation routine is
the value of the minimum traverse time, traverseTimeMin. The minimum traverse time is
the minimum time that the travel of the complex impedance Z(R, X) through the lens, from
one side to the other, must last in order to recognize that a pole-slip has occurred. The value
of the internal constant traverseTimeMin is a function of the set PickupAngle.For values of
PickupAngle <= 110, traverseTimeMin = 50 ms. For values PickupAngle > 110,
traverseTimeMin = 40 ms. The expression which relates the maximum slip frequency
fsMax and the traverseTimeMin is as follows:
fsMax [ Hz ]

PickupAngle []
1000
1.000

traverseTimeMin [ ms ]
180 []

(Equation 88)

ANSIEQUATION2319 V1 EN

The maximum slip frequency fsMax for traverseTimeMin = 50 ms is:


PickupAngle = 90 fsMax = 20 0.500 = 10.000 Hz
PickupAngle = 100 fsMax = 20 0.444 = 8.888 Hz
PickupAngle = 110 fsMax = 20 0.388 = 7.777 Hz

(default 110)

The maximum slip frequency fsMax for traverseTimeMin = 40 ms is:


370

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

PickupAngle = 120 fsMax = 25 0.333 = 8.333 Hz


PickupAngle = 130 fsMax = 25 0.277 = 6.944 Hz

The minimum value of fsMax is 6.994 Hz. When PickupAngle = 110 degrees, fsMax =
7.777 Hz. This implies, that the default PickupAngle = 110 degrees covers 90% of cases
as, the typical final slip frequency is between 2 - 5Hz. In practice, however, before the slip
frequency, for example 7.777 Hz, is reached, at least three pole-slips have occurred. In
other words, if we consider a linear increase of frequency from 50 Hz to 57.777 Hz, at least
three pole-slips will occur (in fact: (57.777 - 50) / 2 = 3.889). The exact instantaneous slipfrequency expressed in Hz (corresponding to number of pole slips per second) is difficult
to calculate. The easiest and most exact method is to measure time between two successive
pole slips. This means that, the instantaneous slip-frequency is measured only after the
second pole-slip, if the protected machine is not already disconnected after the first poleslip. The measured value of slipsPerSecond (SLIPFREQ) is equal to the average slipfrequency of the machine between the last two successive pole-slips.

7.8.7.4

Taking care of the circuit breaker


Although out-of-step events are relatively rare, the out-of-step protection should take care
of the circuit breaker health. The electromechanical stress to which the breaker is exposed
shall be minimized. The maximum currents flowing under out-of-step conditions can be
even greater that those for a three-phase short circuit on generator terminals; see Figure
165. The currents flowing are highest at rotor angle 180 degrees, and smallest at 0 degrees,
where relatively small currents flow. To open the circuit breaker at 180 degrees, when not
only the currents are highest, but the two internal (that is, induced) voltages at both ends
are in opposition, could be fatal for the circuit breaker. There are two methods available
in order to minimize the stress; the second method is more advanced than the first one.

The first method


The circuit breaker is only allowed to break the current when the rotor angle has become
less than the set value TripAngle, on its way to 0 electrical degrees. A recommended value
for the setting TripAngle is 90 degrees or less, for example 60 degrees. Figure 164
illustrates the case with TripAngle = 90 degrees. The offset Mho circle represents loci of
the complex impedance Z(R, X) for which the rotor (power) angle is 90 degrees. If the
circuit breaker must not open before the rotor angle has reached 90 degrees on its way
towards 0 degrees, then it is clear that the circle delimits the R X plane into a no trip
and a trip region. For TripAngle = 90 degrees, the trip command will be issued at point
3 when the complex impedance Z(R, X) exits the circle. By that time the relay logic had
already ascertained the loss of step, and the general decision to trip the generator has
already been taken.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

371

Section 7
Impedance protection

1MRK 502 066-UUS A

The second method


This method is more exact. If the break-time of the circuit breaker is known, (and specified
as the setting tBreaker) than it is possible to initiate a trip (break) command almost exactly
tBreaker milliseconds before the rotor (power) angle reaches 0 degrees, where the
currents are at their minimum possible values. The breaker contacts open at almost exactly
0 degrees, as illustrated in Figure 165 for tBreaker = 0.060 s. The point in time when the
breaker opening process must be initiated is estimated by solving on-line the so called
synchronizer differential equation. Note that if tBreaker is left on the initial (default)
value, which is zero (0), then the alternative setting TripAngle decides when the trip
command is given. If specified tBreaker > 0, for example tBreaker = 0.040 second, then
automatically, the TripAngle is ignored and the second, more exact method applied.

Imaginary part (X) of Z in Ohms

0.6

trip
region

0.4

0.2

3
here rotor
angle
is -90

no trip
region
inside
circle

-0.2

-0.4

outside the
circle is the trip
region for
TripAngle <= 90
-0.6

-0.4

X[Ohm]

RE - Receiving End (infinite bus)


loci of Z(R, X)

no trip
region

1
2

no trip
region

rotor angle
= 180

relay

here
rotor angle
is +90

R[Ohm]

Z - line connects
points SE & RE

this circle

is loci of
the rotor
angle = 90

SE - Sending End (generator)


-0.2
0
0.2
0.4
Real part (R) of Z in Ohms

0.6

0.8

IEC10000114-1-en.vsd
IEC10000114 V1 EN

Figure 164:

372

The imaginary offset Mho circle represents loci of the impedance Z(R, X)
for which the rotor angle is 90 degrees

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Current in kA, trip command to CB, rotor angle in rad

35

very high currents due


to out-of-step condition

pos. seq. current in kA


trip command to CB

30

rotor angle in radian


fault cleared

25

2nd

20

current increases under


fault conditions
current decreases

15
fault
occurs

10
5

trip command
issued here
normal load current

min. current
tBreaker = 60 ms

rotor angle

0
-5

after 1st
pole slip

angle towards 0
0

200

400
600
800
Time in milliseconds

1000

1200

IEC10000115-1-en.vsd
IEC10000115 V1 EN

Figure 165:

7.8.7.5

Trip initiation when the break-time of the circuit breaker is known

Design
At every execution of the function the following is calculated: active power P, reactive
power Q, rotor angle ROTORANG, quantity UCOSPHI, the positive-sequence current
CURRENT and voltage VOLTAGE. All other quantities, that can as well be read as outputs,
are only calculated if the Z(R, X) enters the limit of reach zone, which is a circle in the
complex (R X) plane. When the complex impedance Z(R, X) enters the limit-of-reach
region, the algorithm:

determines in which direction the impedance Z moves, that is, the direction the lens
is traversed
measures the time taken to traverse the lens from one side to the other one

If the traverse time is more than the limit 40 or 50 ms, a pole-slip is declared. If the
complex impedance Z(R, X) exits the lens on the same side it entered, then it is a stable
case and the protected machine is still in synchronism. If a pole-slip has been detected,
then it is determined in which zone the centre of oscillation is located. If the number of
actual pole-slips exceeds the maximum number of allowed pole-slips in either of the
zones, a trip command is issued taking care of the circuit breaker safety.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

373

Section 7
Impedance protection

1MRK 502 066-UUS A

UPSRE
UPSIM
UPSMAG
IPSRE
IPSIM

R
X

Calculation of
R and X parts
of the complex
positivesequence
impedance
Z(R, X)

R
X

Z(R,X)
Z(R,X)
within limit of
reach?

NO

Return

YES

UCOSPHI

Z(R,X)
within lens
characteristic?

NO

ROTORANG
Function alert
SLIPFREQ

YES
LEFT
Motor losing
step ?

Calculation of
positive- sequence
active power P,
reactive power Q,
rotor angle
ROTORANG
and
UCOSPHI

Z(R,X)
entered lens
from?

GENMODE
Z(R,X)
exited lens
on the left- hand
side?
Generator losing
step ?
YES
RIGHT

Was
traverse time
more than
50 ms?
P

MOTMODE

NO

NO

YES (pole- slip!)

UCOSPHI

ZONE 2

>= 1

Number
of pole- slips
exceeded in
a zone?

ROTORANG

TRIP

NO
TRIPZ1

Open
circuit
breaker
safely

ZONE 1

TRIPZ2

IEC10000116-3-en.vsd
IEC10000116 V3 EN

Figure 166:

7.8.8

OOSPPAM (78) Simplified function block

Technical data
Table 143:

OOSPPAM (78) technical data

Function

7.9

374

Range or value

Accuracy

Impedance reach

(0.00 - 1000.00)% of Zbase

2.0% of Vn/(3 In)

Rotor pickup angle

(90.0 - 130.0) degrees

5.0 degrees

Rotor trip angle

(15.0 - 90.0) degrees

5.0 degrees

Zone 1 and Zone 2 trip counters

(1 - 20)

Loss of excitation LEXPDIS(40)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.9.1

Identification
Function description
Loss of excitation

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
40

LEXPDIS

<
SYMBOL-MM V1 EN

7.9.2

Functionality
There are limits for the under-excited operation of a synchronous machine. A reduction of
the excitation current weakens the coupling between the rotor and the stator. The machine
may lose the synchronism and start to operate like an induction machine. Then, the
reactive power consumption will increase. Even if the machine does not loose
synchronism it may not be acceptable to operate in this state for a long time. Reduction of
excitation increases the generation of heat in the end region of the synchronous machine.
The local heating may damage the insulation of the stator winding and the iron core.
To prevent damages to the generator it should be tripped when excitation is lost.

7.9.3

Function block
LEXPDIS (40)
I3P*
V3P*
BLOCK
BLKTRZ1
BLKTRZ2

TRIP
TRZ1
TRZ2
PICKUP
PU_Z1
PU_Z2
XOHM
XPERCENT
ROHM
RPERCENT
ANSI0700031-1-en.vsd

ANSI0700031 V1 EN

Figure 167:

LEXPDIS (40) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

375

Section 7
Impedance protection
7.9.4

1MRK 502 066-UUS A

Signals
Table 144:

LEXPDIS (40) Input signals

Name

Type

Current group connection

V3P

GROUP
SIGNAL

Voltage group connection

BLOCK

BOOLEAN

Block of function

BLKTRZ1

BOOLEAN

Block trip of zone Z1

BLKTRZ2

BOOLEAN

Block trip of zone Z2

LEXPDIS (40) Output signals

Name

Table 146:
Name

Description

GROUP
SIGNAL

Table 145:

7.9.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Common trip signal

TRZ1

BOOLEAN

Trip signal from impedance zone Z1

TRZ2

BOOLEAN

Trip signal from impedance zone Z2

PICKUP

BOOLEAN

Common start signal

PU_Z1

BOOLEAN

Pickup signal from impedance zone Z1

PU_Z2

BOOLEAN

Pickup signal from impedance zone Z2

XOHM

REAL

Reactance in Primary Ohms

XPERCENT

REAL

Reactance in percent of Zbase

ROHM

REAL

Resistance in Primary Ohms

RPERCENT

REAL

Resistance in percent of Zbase

Settings
LEXPDIS (40) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OperationZ1

Disabled
Enabled

Enabled

Operation Disable/Enable zone Z1

XoffsetZ1

-1000.00 - 1000.00

0.01

-10.00

Offset of Z1 circle top point along X axis in % of


Zbase

Z1diameter

0.01 - 3000.00

0.01

100.00

Diameter of impedance circle for Z1 in % of


Zbase

tZ1

0.00 - 6000.00

0.01

0.01

Trip time delay for Z1

Table continues on next page

376

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

OperationZ2

Disabled
Enabled

Enabled

Operation Disable/Enable zone Z2

XoffsetZ2

-1000.00 - 1000.00

0.01

-10.00

Offset of Z2 circle top point along X axis in % of


Zbase

Z2diameter

0.01 - 3000.00

0.01

200.00

Diameter of impedance circle for Z2 in % of


Zbase

tZ2

0.00 - 6000.00

0.01

1.00

Trip time delay for Z2

Step

Default

Table 147:
Name

LEXPDIS (40) Group settings (advanced)


Values (Range)

Unit

Description

DirSuperv

Disabled
Enabled

Disabled

Operation Off/On for additional directional


criterion

XoffsetDirLine

-1000.00 - 3000.00

0.01

0.00

Offset of directional line along X axis in % of


Zbase

DirAngle

-180.0 - 180.0

Deg

0.1

-13.0

Angle between directional line and R-axis in


degrees

Step

Default

Table 148:
Name

LEXPDIS (40) Non group settings (basic)


Values (Range)

Unit

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

MeasureMode

PosSeq
AB
BC
CA

PosSeq

Measuring mode (PosSeq, AB, BC, CA)

Table 149:
Name
InvertCTcurr

7.9.6

LEXPDIS (40) Non group settings (advanced)


Values (Range)
No
Yes

Unit

Step

Default
No

Description
Invert CT current

Monitored data
Table 150:
Name

LEXPDIS (40) Monitored data


Type

Values (Range)

Unit

Description

XOHM

REAL

Ohm

Reactance in Primary Ohms

XPERCENT

REAL

Reactance in percent of Zbase

ROHM

REAL

Ohm

Resistance in Primary Ohms

RPERCENT

REAL

Resistance in percent of
Zbase

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

377

Section 7
Impedance protection
7.9.7

1MRK 502 066-UUS A

Operation principle
The Loss of excitation (LEXPDIS ,40) protection in the IED measures the apparent
impedance seen out from the generator.The measurement loop of apparent impedance can
be chosen as the positive sequence loop or any one of the three phase-to-phase loops
depending on the available current and voltage signals. It is recommended to use positive
sequence quantities for function operation.
Measured mode

Zposseq

Measured apparent impedance

Vposseq
I posseq

EQUATION2051-ANSI V1 EN

ZAB

VA - VB
IA - IB

EQUATION2052-ANSI V1 EN

ZBC

(Equation 90)

VB - VC
IB - IC

EQUATION2053-ANSI V1 EN

ZCA

(Equation 89)

(Equation 91)

VC - VA
IC - IA

EQUATION2054-ANSI V1 EN

(Equation 92)

There are three characteristics in LEXPDIS (40) protection as shown in figure 168.
Naimly:

378

Offset mho circle for Z1


Offset mho circle for Z2
Directional blinder

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

UnderexitationProtection
protection
Underexcitation
Restrainarea
area
Restrain
R

R
Directional
blinder

Z1, Fast zone


Z2, Slow zone
IEC06000455-2-en.vsd
IEC06000455 V2 EN

Figure 168:

Three characteristics in LEXPDIS (40) protection

When the apparent impedance reaches the zone Z1 this zone will operate, normally with
a short delay. The zone is related to the dynamic stability of the generator.
When the apparent impedance reaches the zone Z2 this zone will operate, normally with
a longer delay. The zone is related to the static stability of the generator.
LEXPDIS (40) protection also has a directional blinder (supervision). See figure 168.
In LEXPDIS (40) function the zone measurement is done as shown in figure 169.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

379

Section 7
Impedance protection

1MRK 502 066-UUS A

Offset

R
XoffsetZ1

Z1diameter

Z (apparent impedance)

Z1 = Z - (XoffsetZ1 +
Z1diameter/2)

Z1 or Z2

en06000456-2.vsd
IEC06000456 V2 EN

Figure 169:

Zone measurement in LEXPDIS (40) protection function

The impedance Z1 is constructed from the measured apparent impedance Z and the
impedance corresponding to the centre point of the impedance characteristic (Z1 or Z2).
If the magnitude of this impedance is less than the radius (diameter/2) of the characteristic,
this part of the protection will operate.
If the directional restrain is set Disabled the impedance zone operation will start the
appropriate timer and LEXPDIS (40) will trip after the set delay (tZ1 or tZ2).
If the directional restrain is set Enabled the directional release function must also operate
to enable operation. A new impedance is constructed from the measured apparent
impedance Z and the XoffsetDirLine point on the y-axis. If the phase angle of this
impedance is less than the set DirAngle LEXPDIS (40) function will be released, see
figure 170.

380

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Underexcitation Protection
Restrain area

XoffsetDirLine
DirAngle

Z (apparent impedance)

en06000457.vsd
IEC06000457 V1 EN

Figure 170:

Impedance constructed as XoffsetDirLine in LEXPDIS (40) protection

LEXPDIS (40) function is schematically described in figure 171.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

381

Section 7
Impedance protection

1MRK 502 066-UUS A

Positive
sequence
current
phasor
Positive
sequence
voltage
phasor

Apparent
impedance
calculation

Z in
Z1 char.

AND

Z in
Z2 char.

AND

pickupZ1

tZ1
0

TripZ1

pickupZ2

tZ2
0

TripZ2

Dir.
Restrain
OR

Dir.Restrain Enabled

en060004582_ansi.vsd
ANSI06000458 V2 EN

Figure 171:

7.9.8

Simplified logic diagram of LEXPDIS (40) protection

Technical data
Table 151:

LEXPDIS (40) technical data

Function

382

Range or value

Accuracy

X offset of Mho top point for Zone


1 and Zone 2

(1000.001000.00)% of ZBase

5.0% of Vn/In

Diameter of Mho circle for Zone 1


and Zone 2

(0.03000.00)% of ZBase

5.0% of Vn/In

Independent time delay for Zone


1 when impedance jumps from
the outside the set circle to the
center of the set circle

(0.00-6000.00) s

0.2% or 60 ms whichever is
greater

Independent time delay for Zone


2 when impedance jumps from
the outside the set circle to the
center of the set circle

(0.00-6000.00) s

0.2% or 60 ms whichever is
greater

Trip time, pickup when


impedance jumps from the
outside the set circle to the center
of the set circle

Min. = 35 ms
Max. = 50 ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.10

Sensitive rotor earth fault protection, injection based


ROTIPHIZ (64R)

7.10.1

Identification
Function description

IEC 61850
identification

Sensitive rotor earth fault protection,


injection based

7.10.2

ROTIPHIZ

IEC 60617
identification
Rre<

ANSI/IEEE C37.2
device number
64R

Functionality
The sensitive rotor earth fault protection (ROTIPHIZ, 64R) is used to detect ground faults
in the rotor windings of generators. ROTIPHIZ (64R) is applicable for all types of
synchronous generators.
To implement the above concept, a separate injection box is required. The injection box
generates a square wave voltage signal at a certain preset frequency which is fed into the
rotor winding.
The magnitude of the injected voltage signal and the resulting injected current is measured
through a resistive shunt located within the injection box. These two measured values are
fed to the IED. Based on these two measured quantities, the protection IED determines the
rotor winding resistance to ground. The resistance value is then compared with the preset
fault resistance alarm and trip levels.
The protection function can detect ground faults in the entire rotor winding and associated
connections.
Requires injection unit REX060 and a coupling capacitor unit REX061 for correct
operation.

7.10.3

Description of input signals


The inputs to the sensitive rotor earth-fault protection function block are as shown in table
152.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

383

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 152:
Input signal

7.10.4

Description of various inputs


Description

USV

The measured injection voltage. This signal is taken from a pre-processor block, the AI output.
The analog voltage input AI1 is linked to the phase A in the pre-processor block in the Signal
Matrix tool.

USI

The measured injection current. This signal is taken from a pre-processor block, the AI output.
In the pre-configured version, the analog voltage input AI2 is linked to the phase B in the preprocessor block in the Signal Matrix tool.

BLOCK

Input to block the function

ZREFSEL

The selection of any of the predefined reference impedances. There is a possibility to change
from one set reference impedance to another. Two different reference impedances are
available.

Description of output signals


The outputs of the sensitive rotor earth-fault protection function block are as shown in
table 153.
Table 153:
Output signal

Description of various outputs


Description

TRIP

Common trip command signal

TRIPDC

is the trip command signal at DC-side ground fault

TRIPAC

is the trip command signal at AC-side ground fault

BFI

is a common signal for both AC and DC side of exciter

PU_DC

is the start signal at DC-side ground fault

PU_DC

is the start signal at AC-side ground fault

ALARM

Signal activated after a set time delay, if the calculated fault resistance gets lower than the
set alarm level

ERROR

Error signal which is boolean with values 0 and 1

ERRSTAT

Status coded signal giving type of error. See table 154

RAVE

Measured resistance to ground in at an injected frequency (real part of the complex


impedance)

XAVE

Measured reactance to ground in at the injected frequency (imaginary part of the


complex impedance)

FREQV

Measured frequency of the injected voltage

RFAULT

Estimated fault resistance in

ZREF

Selected reference impedance number

Table continues on next page

384

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Output signal

Description

ZREFRE

The real part (resistance) of the used reference impedance

ZREFIM

The imaginary part (reactance) of the used reference impedance

VRMSSTAT

This signal is set true, if the measured RMS voltage is larger than the set limit VLimRMS

ERRSTAT output signal


Convert the integer output signal to binary and see table below for interpretation of
individual bits:
Table 154:
Priority 3
Bit 7
Interference
detected

Definition of errors

Bit 6
Undercurrent

ERRSTAT output integer


Priority 2
Bit 5
Bit 4
Bit 3
Undervoltage

Overcurrent

Overvoltage

Priority 3
Bit 2
Frequency
difference

Bit 1

Priority 1

No current

Bit 0

No voltage

The ERRSTAT description will be shown in clear text in ICT.


The priority of the signals is set that the group priority 1 overrides the group priority 2 and
3, and priority 2 overrides priority 3. Note that the ERRSTAT signal can enable several
error cases at the same time.
Following errors is detected and derived in the Error block:

B0 = Injected voltage signal not found


B1 = Injected current signal not found
B2 = Voltage and current signal frequency differs
B3 = Measured total RMS voltage too high
B4 = Measured total RMS current too high
B5 = Injected voltage signal too low
B6 = Injected current signal too low
B7 = External interference voltage detected

ERRSTAT = BitToInt[B7,,B1,B0] The priority of the error conditions that will be


flagged out:

Prio1 = B0, B1
Prio2 = B3, B4, B5, B6
Prio3 = B2, B7

RFAULT output signal

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

385

Section 7
Impedance protection

1MRK 502 066-UUS A

The injection equipment provides calculation of the fault resistance:

7.10.5

If the fault resistance is equal or below 10 k, RFAULT is displayed in


If the fault resistance is above 10 k, RFAULT is initially displayed as -1000 until
the fault resistance has reached a stable value and then displayed in
RFAULT displayed as -2000 means error

Function block
ROTIPHIZ (64R)
USV*
TRIP
USI*
TRIPDC
BLOCK
TRIPAC
ZREFSEL
BFI
PU_DC
PU_DC
ALARM
ERROR
ERRSTAT
RAVE
XAVE
FREQV
RFAULT
ZREF
ZREFRE
ZREFIM
VRMSSTAT
ANSI10000297-1-en.vsd
ANSI10000297 V1 EN

Figure 172:

7.10.6

Signals
Table 155:
Name

386

ROTIPHIZ (64R) function block

ROTIPHIZ (64R) Input signals


Type

Default

Description

USV

GROUP
SIGNAL

Injected voltage signal

USI

GROUP
SIGNAL

Injected current signal (voltage over shunt)

BLOCK

BOOLEAN

Block of function

ZREFSEL

INTEGER

Reference impedance selection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 156:

ROTIPHIZ (64R) Output signals

Name

7.10.7
Table 157:
Name

Type

Description

TRIP

BOOLEAN

Trip (common AC and DC side of exciter)

TRIPDC

BOOLEAN

Trip for DC side of exciter

TRIPAC

BOOLEAN

Trip for AC side of exciter

BFI

BOOLEAN

Initiate (common AC and DC side of exciter)

PU_DC

BOOLEAN

Pick up for DC side of exciter

PU_AC

BOOLEAN

Pick up for AC side of exciter

ALARM

BOOLEAN

Alarm

ERROR

BOOLEAN

Error

ERRSTAT

INTEGER

Error indication

RAVE

REAL

Measured resistance to earth in Ohm at inj freq

XAVE

REAL

Measured reactance to earth in Ohm at inj freq

FREQV

REAL

Measured frequency of injected voltage into rotor

RFAULT

REAL

Estimated fault resistance in Ohm

ZREF

INTEGER

Selected reference impedance number

ZREFRE

REAL

Used reference impedance real part in Ohm

ZREFIM

REAL

Used reference impedance imaginary part in Ohm

VRMSSTAT

BOOLEAN

RMS voltage status, TRUE when > VLimRMS

Settings
ROTIPHIZ (64R) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Enable/Disable

RTrip

100 - 100000

Ohm

1000

Trip limit of fault resistance in Ohm

RAlarm

100 - 1000000

Ohm

10000

Alarm limit of fault resistance in Ohm

tAlarm

0.00 - 600.00

1.00

30.00

Alarm time delay

FactACLim

0.01 - 2.00

0.01

0.25

Scale factor for rotor earth fault on AC side of


exciter

tTripAC

0.000 - 60.000

1.000

10.000

Time delay for trip on AC side of exciter

VLimRMS

1 - 1000

100

RMS voltage level

Table 158:
Name
FreqInjected

ROTIPHIZ (64R) Group settings (advanced)


Values (Range)
75.000 - 250.000

Unit
Hz

Step
0.001

Default
113.000

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description
Injected frequency

387

Section 7
Impedance protection

Table 159:
Name

1MRK 502 066-UUS A

ROTIPHIZ (64R) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

k1Real

-10000000000.000
- 10000000000.000

0.001

10000.000

Multiplication factor k1 for calibration, real part

k1Imag

-10000000000.000
- 10000000000.000

0.001

0.000

Multiplication factor k1 for calibration,


imaginary part

k2Real

-10000000000.000
- 10000000000.000

Ohm

0.001

0.000

Addition factor k2 for calibration, real part in


Ohm

k2Imag

-10000000000.000
- 10000000000.000

Ohm

0.001

0.000

Addition factor k2 for calibration, imaginary part


in Ohm

RefR1

0.001 1000000000.000

Ohm

0.001

1000000.000

Reference resistance R1 in ohm

RefX1

-1000000.000 1000000.000

Ohm

0.001

2000.000

Reference reactance X1 in ohm

RefR2

0.001 1000000000.000

Ohm

0.001

1000000.000

Reference resistance R2 in ohm

RefX2

-1000000.000 1000000.000

Ohm

0.001

2000.000

Reference reactance X2 in ohm

Table 160:
Name
FilterLength

7.10.8

ROTIPHIZ (64R) Non group settings (advanced)


Values (Range)
1s
2s

Step

Default
1s

Description
Length of filter buffer

Monitored data
Table 161:
Name

388

Unit

ROTIPHIZ (64R) Monitored data


Type

Values (Range)

Unit

Description

RAVE

REAL

Ohm

Measured resistance to earth


in Ohm at inj freq

XAVE

REAL

Ohm

Measured reactance to earth


in Ohm at inj freq

FREQV

REAL

Hz

Measured frequency of
injected voltage into rotor

RFAULT

REAL

Ohm

Estimated fault resistance in


Ohm

ZREF

INTEGER

Selected reference
impedance number

ZREFRE

REAL

Ohm

Used reference impedance


real part in Ohm

ZREFIM

REAL

Ohm

Used reference impedance


imaginary part in Ohm

VRMSSTAT

BOOLEAN

RMS voltage status, TRUE


when > VLimRMS

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.10.9

Operation principle
The protection principle is based on injection of voltage to the exciter point of the field
circuit.
8

Step
-up
Transformer

U>

Vinj
Rshunt

GEN

ROTOR EF

5
6

REX061

I
RN

REX060/ RIM module

REG670
Generator Protection Panel

ANSI11000014_1_en.vsd

ANSI11000014 V1 EN

Figure 173:

Example installation for rotor injection

Generator unit consisting of a synchronous generator and a step-up transformer

Generator field winding

Capacitor coupling unit which is used to provide insulation barrier between rotor circuit and injection
equipment

Cable used to inject the square-wave signal into the rotor circuit

Connection for measurement of injected current. This signal is amplified in REX060 before it is passed
on to IED for evaluation.

Connection for measurement of injected voltage. This signal is amplified in REX060 before it is passed
on to IED for evaluation.

Two VT inputs into IED which are used to measure injected current and voltage

Protection for excessive over-voltages posed by generator. REX060 can withstand without damage
maximum voltage of 120V and when used together with REX062 up to 240V.

The injection signals are generated in a separate unit, REX060. The signals have square
wave form and are injected to the generator via the coupling capacitor unit REX061 to the
excitation circuit.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

389

Section 7
Impedance protection

1MRK 502 066-UUS A

In the REX060 unit the injection voltage and current signals are amplified to a level
adapted to the analogue voltage inputs of IED. In IED the measured signals evaluated to
detect rotor ground faults.

7.10.9.1

The injection unit REX060


IED and
Injection
connectors

Top view

Back view

Power
connector

Front view
Keylock
LED

X11

X61

X81

18

Front-plate

X82

Rotor

Stator

Power

Backplane
HMI with logic

18

X62

PSM

Injection Stator

Injection Rotor

Injection LED

Injection switch

IEC11000015-1-en.vsd
IEC11000015 V1 EN

Figure 174:

Injection unit REX060

The REX060 unit is a common unit that can be configured for either rotor or stator ground
fault protection, or for both. The REX060 have separate modules for rotor and stator
protection. The REX060 generate square wave signals, where one is used for injection to
the stator neutral point and the other to the field winding circuit (rotor circuit), if
configured for both stator and rotor protection. The injected voltage and currents are
measured by the unit and amplified, resulting in voltage signals both for the injected
voltage and current, and adapted to the analogue inputs of IED. The injection unit REX060
shall be located close to the IED, preferably in the same cubicle.
For the Sensitive rotor earth fault protection, there are some settings necessary for
REX060:

System frequency: 50/60 Hz


Injected frequency for rotor circuit injection is settable in 1 Hz steps 75 250 Hz.
Gain factor in four steps

REX060 will also continuously check the measured signal for detection of saturation
which could cause error in the evaluation in IED. If saturation level is reached a binary
signal, connected to IED, is activated. Also other errors in the injection circuit will initiate
a binary signal to IED for blocking of the function.

390

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Rotor injection output is protected against high voltages by a relay blocking the injection
circuit. This blocking remains blocked by stored status in non-volatile memory.
The output is also protected by a fuse. If this fuse is blown, it is caused by external voltage
source, since the injection unit cannot provide enough energy to blow this fuse.
Refer to the Hardware section in this manual for a detailed description of REX060.

7.10.9.2

Rotor Earth Fault Protection function


The injection to the rotor is schematically shown in figure 175.
Iinj
Crot

DC
Rf

Crot

Vinj

AC
REX061
Rf

Iinj
+
Vinj

Rotor Reference
Impedance

ANSI11000065_1_en.vsd

ANSI11000065 V1 EN

Figure 175:

Equivalent diagram for Sensitive rotor earth fault protection principle

The impedance ZMeasured is equal to the capacitive reactance between the rotor winding
and ground (1/Crot) and the ground fault resistance (Rf). The series resistance in the
injection circuit is eliminated. Rf is very large in the non-faulted case and the measured
impedance, called the rotor reference impedance and can be calculated as :

Z ref = - j

1
wCrot

EQUATION2510 V1 EN

alternative

1
= jwCrot
Z ref
EQUATION2511 V1 EN

Where

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

391

Section 7
Impedance protection

1MRK 502 066-UUS A

w = 2p finj
EQUATION2512 V1 EN

The injected frequency finj of the square wave, is a set value, deviating from the
fundamental frequency (50 or 60 Hz). The injected frequency can be set within the range
75 250 Hz with the recommended value 113 Hz in 50 Hz systems and 137 Hz in 60 Hz
systems.
Rseries is a resistance in the REX061 unit used to protect against overvoltage to the
injection unit. Such overvoltages can occur if the unit is fed from static excitation system.
The injection unit REX060 is connected to the generator and to IED as shown in figure
173.

7.10.9.3

General measurement of ground fault impedance


From the REX060 the injected voltage and current are delivered as AC voltages to IED.
The injected voltage and current is measured and analyzed in the protection function
software within IED. The measured injected voltage and current are first processed by
means of special filtering so that the signals are referred to the injected frequency only.
The bare complex impedance is, see fig 176:
Z bare =

V Inj
I Inj

EQUATION2500-ANSI V1 EN

An equivalent circuit for the measured impedance is shown in figure 176.

ZMeasured

Zbare
Z series

Iinj
+

Rf

Z shunt

Vinj
-

ANSI11000003_1_en.vsd
ANSI11000003 V1 EN

Figure 176:
392

Equivalent of the impedance measurement


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

In non-faulted operation Rf is very large. A healthy impedance is calculated as:

Z Measured = k1 Z bare + k 2
EQUATION2501 V1 EN

For definition of k1 and k2, see figure 177


The factors k1 and k2 [] are derived from measurements during commissioning, where
calibration to known fault resistance will be used to convert the measurement to true
primary impedance. The factor k1 will compensate for transformer ratio and other factors
to achieve impedance values related to the primary system. The factor k2 [] will
compensate for the series impedance Zseries
The healthy impedance measured at non-faulted conditions is referred to as the reference
impedance in further text.
In IED the measured impedance is compared to the reference impedance. In case of a
ground fault, the fault impedance is estimated and compared to the set values RAlarm and
RTrip.
The measured values are transferred to the primary impedance values by taking the actual
impedance value through the complex transformation given by the equation.
Ztrue = k1 Z measured + k2
GUID-20ADF3F6-6A89-4B5F-B0DA-9740C4FD5482 V1 EN

The factors k1 and k2 [] are derived during the calibration measurements under
commissioning. As support for the calibration, the Injection Commissioning tool must be
used. This tool is an integrated part of the PCM600 tool.
In connection to this calibration, the reference impedance is also derived. In case of a rotor
ground fault with fault impedance Zf, the measured admittance is:
1
1
1
=
+
Z Z ref Z f
=
1
1
1
= Zf
Z Z ref
EQUATION2405 V1 EN

The real part gives the fault conductance.


1
1
1
= Re
Rf
Z Z ref

EQUATION2421 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

393

Section 7
Impedance protection

1MRK 502 066-UUS A

RAlarm and RTrip are the two resistance levels given in the settings. The values of RAlarm
and RTrip are given in .
An alarm signal ALARM is given after a set delay tAlarm if Rf < RAlarm
A initiate signal BFI is given if Rf < RTrip
See figure 179

7.10.9.4

Simplified logic diagram


ROTIPHIZ (64R)

Vinj
Rshunt

2
6

Rf

Z Measured
Compare &
Evaluate

Z bare
S

K2

I Inj

v_i_ref

V Inj

v_v_ref

K1

ZRef1
ZRef2

REX060

REG670
ANSI10000327_1_en.vsd

ANSI10000327 V1 EN

Figure 177:

394

Simplified logic diagram for sensitive rotor earth fault protection, injection
based ROTIPHIZ (64R)

The sensitive rotor earth fault protection function receives amplified injected voltage and current
via the REX060 unit as two voltages signals. (Voltage inputs in the IED)

The phasor of injected voltage VInj and phasor of injected current IInj is calculated by using special
filter from raw samples. Observe that phasors are calculated for the injected frequency.

The complex bare impedance is calculated from Vinj / Iinj.

4, 5

The complex measured impedance is derived as ZMeasured = Zbare*k1 + k2 [].

The fault resistance (Rf) is calculated from the complex measured impedance and a selected
complex reference.

Selection of one (out of maximum 2) ZRef.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Rf
OR

Alarm

Adaptive
TripDelay

Trip

IEC10000326-3.vsd
IEC10000326 V2 EN

Figure 178:

ROTIPHIZ (64R) Alarm and trip logic

If the fault resistance Rf is smaller than RAlarm and longer than alarm delay (using delayon), output ALARM is set. If the fault resistance Rf is smaller than RTrip, using internal trip
time characteristic, output signal TRIP is set after the calculated time. For trip time delay,
see fig 179
When 1s filter length is used and the fault resistance is equal to the set value RTrip, the trip
time is about 10 s. If the fault resistance is estimated to be 0 , the trip delay is 2 s. For
values in between, the delay follows the linear interpolation describing the fault resistance
time characteristic.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

395

Section 7
Impedance protection

1MRK 502 066-UUS A

Trip time

10 FilterLength

2 FilterLength

Fault resistance

RTrip

RAlarm
IEC11000002-1-en.vsd

IEC11000002 V1 EN

Figure 179:

Trip time characteristic as function of fault resistance

A third high level step for the detection of excitation system ground faults on the AC side
of the excitation rectifier is available. This step uses the network frequency (50 or 60 Hz)
for the evaluation. If a ground fault occurs at the AC side of the excitation system rectifier,
there is a fundamental frequency component at the measured voltage and current injection
points.
The third high level step is not applicable if mixed signals are used, that is when the
REX060 is used for both rotor and stator ground fault protection and only two, instead of
four, analog inputs on the IED are used.

7.10.10

Technical data
Table 162:

ROTIPHIZ (64R) technical data

Function

Range or value

Fault resistance sensitivity

Injection frequency

Accuracy

Can be reached at
steady state operating
condition of the machine

500 k

Typically

20 - 50 k

(75.000 - 250.000) Hz

0.1 Hz

Table continues on next page


396

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Trip limit of fault resistance

(100 - 100000)

5% of 1 k at Rf 1 k
5% of set value at 1 k < Rf 20 k
10% of set value at Rf > 20 k

Alarm limit of fault resistance

(100 - 1000000)

5% of 1 k at Rf 1 k
5% of 10 k at 1 k < Rf 20 k
10% of set value at 20 k < Rf 200 k

Operate time, start at Rf ~ 0 and


filter length = 1 s

1.00 s typically

Operate time, trip at Rf ~ 0 and


filter length = 1 s

3.00 s typically

Alarm time delay at Rf ~ 0 and


filter length = 1 s

(0.00 - 600.00) s

0.2% or 2.00 s whichever is greater

7.11

100% stator earth fault protection, injection based


STTIPHIZ (64S)

7.11.1

Identification
Function description
100% stator earth fault protection,
injection based

7.11.2

IEC 61850
identification
STTIPHIZ

IEC 60617
identification
Rse<

ANSI/IEEE C37.2
device number
64S

Functionality
The 100% stator earth-fault protection STTIPHIZ (64S) is used to detect ground faults in
the stator windings of generators and motors. STTIPHIZ (64S) is applicable for generators
connected to the power system through a unit transformer in a block connection. An
independent signal with a certain frequency different from the generator rated frequency
is injected into the stator circuit. The responce of this injected signal is used to detect stator
ground faults.
To implement the above concept, a separate injection box is required. The injection box
generates a square wave voltage signal which for example can be fed into the secondary
winding of the generator neutral point voltage transformer or grounding transformer. This
signal propagates through this transformer into the stator circuit.
The magnitude of the injected voltage signal is measured on the secondary side of the
neutral point voltage transformer or grounding transformer. In addition, the resulting
injected current is measured through a resistive shunt located within the injection box.
These two measured values are fed to the IED. Based on these two measured quantities,

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

397

Section 7
Impedance protection

1MRK 502 066-UUS A

the IED determines the stator winding resistance to ground. The resistance value is then
compared with the preset fault resistance alarm and trip levels.
The protection function can not only detect the ground fault at the generator star point, but
also along the stator windings and at the generator terminals, including the connected
components such as voltage transformers, circuit breakers, excitation transformer and so
on. The measuring principle used is not influenced by the generator operating mode and
is fully functional even with the generator at standstill. It is still required to have a standard
95% stator earth-fault protection, based on the neutral point fundamental frequency
displacement voltage, operating in parallel with the 100% stator earth-fault protection
function.
Requires injection unit REX060 and optional shunt resistor unit REX062 for correct
operation.

7.11.3

Description of input signals


The inputs to the 100% stator earth fault protection function block are as shown in the
table.
Table 163:
Input signal

7.11.4

Description of various inputs


Description

USV

The measured injection voltage. This signal is taken from a pre-processor block, the AI output.
The analog voltage input AI1 is linked to the phase A in the pre-processor block in the Signal
Matrix tool.

USI

The measured injection current. This signal is taken from a pre-processor block, the AI output.
In the pre-configured version, the analog voltage input AI2 is linked to the phase B in the preprocessor block in the Signal Matrix tool.

BLOCK

Input to block the function

ZREFSEL

The selection of any of the pre-defined reference impedances. The reference impedance can
differ, for example, with the generator breaker open or closed. Therefore, there is a possibility
to change from one set reference impedance to another. Five different reference impedances
are available.

Description of output signals


The outputs of the 100% stator earth fault protection function block are as shown in the
table.

398

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Table 164:
Output signal

Description of various outputs


Description

TRIP

Trip command signal

BFI

Signal activated, if the calculated fault resistance gets lower than the set level

ALARM

Signal activated after a set time delay, if the calculated fault resistance gets lower than the
set alarm level

OPCIRC

Signal indicating open stator injection circuit (interruption)

ERROR

Error signal which is boolean with values 0 and 1

ERRSTAT

Status coded signal giving type of error. See below table

RAVE

Measured stator resistance to earth in at an injected frequency (real part of the complex
impedance)

XAVE

Measured stator reactance to earth in at the injected frequency (imaginary part of the
complex impedance)

FREQV

Measured frequency of the injected voltage

RFAULT

Estimated fault resistance in

ZREF

Selected reference impedance number

ZREFRE

The real part (resistance) of the used reference impedance

ZREFIM

The imaginary part (reactance) of the used reference impedance

VRMSSTAT

This signal is set true, if the measured RMS voltage is larger than the set limit ULimRMS

IRMSSTAT

This signal is set true, if the measured RMS current is larger than the set limit ILimRMS

ERRSTAT output signal


Convert the integer output signal to binary and see table below for interpretation of
individual bits:
Table 165:
Priority 3
Bit 7
Interference
detected

Definition of errors

Bit 6
Undercurrent

ERRSTAT output integer


Priority 2
Bit 5
Bit 4
Bit 3
Undervoltage

Overcurrent

Overvoltage

Priority 3
Bit 2
Frequency
difference

Bit 1

Priority 1

No current

Bit 0

No voltage

The ERRSTAT description will be shown in clear text in ICT.


The priority of the signals is set that the group priority 1 overrides the group priority 2 and
3, and priority 2 overrides priority 3. Note that the ERRSTAT signal can enable several
error cases at the same time.
Following errors is detected and derived in the Error block:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

399

Section 7
Impedance protection

1MRK 502 066-UUS A

B0 = Injected voltage signal not found


B1 = Injected current signal not found
B2 = Voltage and current signal frequency differs
B3 = Measured total RMS voltage too high
B4 = Measured total RMS current too high
B5 = Injected voltage signal too low
B6 = Injected current signal too low
B7 = External interference voltage detected

ERRSTAT = BitToInt[B7,,B1,B0] The priority of the error conditions that will be


flagged out:

Prio1 = B0, B1
Prio2 = B3, B4, B5, B6
Prio3 = B2, B7

RFAULT output signal


The injection equipment provides calculation of the fault resistance:

7.11.5

If the fault resistance is equal or below 10 k, RFAULT is displayed in


If the fault resistance is above 10 k, RFAULT is initially displayed as -1000 until
the fault resistance has reached a stable value and then displayed in
RFAULT displayed as -2000 means error

Function block
STTIPHIZ (64S)
USV*
TRIP
USI*
BFI
BLOCK
ALARM
ZREFSEL
OPCIRC
ERROR
ERRSTAT
RAVE
XAVE
FREQV
RFAULT
ZREF
ZREFRE
ZREFIM
VRMSSTAT
ANSI10000298-1-en.vsd
ANSI10000298 V1 EN

Figure 180:

400

STTIPHIZ (64S) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.11.6

Signals
Table 166:

STTIPHIZ (64S) Input signals

Name

Type

Injected voltage signal

USI

GROUP
SIGNAL

Injected current signal (voltage over shunt)

BLOCK

BOOLEAN

Block of function

ZREFSEL

INTEGER

Reference impedance selection

STTIPHIZ (64S) Output signals

Name

Table 168:
Name

Description

GROUP
SIGNAL

Table 167:

7.11.7

Default

USV

Type

Description

TRIP

BOOLEAN

Trip

BFI

BOOLEAN

Initiate

ALARM

BOOLEAN

Alarm

OPCIRC

BOOLEAN

Injection circuit open

ERROR

BOOLEAN

Error

ERRSTAT

INTEGER

Error indication

RAVE

REAL

Measured resistance to earth in Ohm at inj freq

XAVE

REAL

Measured reactance to earth in Ohm at inj freq

FREQV

REAL

Measured frequency of injected voltage into stator

RFAULT

REAL

Estimated fault resistance in Ohm

ZREF

INTEGER

Selected reference impedance number

ZREFRE

REAL

Used reference impedance real part in Ohm

ZREFIM

REAL

Used reference impedance imaginary part in Ohm

VRMSSTAT

BOOLEAN

RMS voltage status, TRUE when > VLimRMS

Settings
STTIPHIZ (64S) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Enable/Disable

RTrip

100 - 10000

Ohm

1000

Trip limit of fault resistance in Ohm

RAlarm

100 - 100000

Ohm

5000

Alarm limit of fault resistance in Ohm

tAlarm

0.00 - 600.00

1.00

30.00

Alarm time delay

OpenCircLim

100 - 10000000

Ohm

10000000

Open circuit limit in Ohm

VLimRMS

1 - 1000

100

RMS voltage level

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

401

Section 7
Impedance protection

Table 169:
Name
FreqInjected

Table 170:
Name

1MRK 502 066-UUS A

STTIPHIZ (64S) Group settings (advanced)


Values (Range)
50.000 - 250.000

Unit
Hz

Step
0.001

Default
87.000

Description
Injected frequency

STTIPHIZ (64S) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

k1Real

-10000000000.000
- 10000000000.000

0.001

10000.000

Multiplication factor k1 for calibration, real part

k1Imag

-10000000000.000
- 10000000000.000

0.001

0.000

Multiplication factor k1 for calibration,


imaginary part

k2Real

-10000000000.000
- 10000000000.000

Ohm

0.001

0.000

Addition factor k2 for calibration, real part in


Ohm

k2Imag

-10000000000.000
- 10000000000.000

Ohm

0.001

0.000

Addition factor k2 for calibration, imaginary part


in Ohm

RefR1

0.001 1000000000.000

Ohm

0.001

1000.000

Reference resistance R1 in ohm

RefX1

-1000000.000 1000000.000

Ohm

0.001

2000.000

Reference reactance X1 in ohm

RefR2

0.001 1000000000.000

Ohm

0.001

1000.000

Reference resistance R2 in ohm

RefX2

-1000000.000 1000000.000

Ohm

0.001

2000.000

Reference reactance X2 in ohm

RefR3

0.001 1000000000.000

Ohm

0.001

1000.000

Reference resistance R3 in ohm

RefX3

-1000000.000 1000000.000

Ohm

0.001

2000.000

Reference reactance X3 in ohm

RefR4

0.001 1000000000.000

Ohm

0.001

1000.000

Reference resistance R4 in ohm

RefX4

-1000000.000 1000000.000

Ohm

0.001

2000.000

Reference reactance X4 in ohm

RefR5

0.001 1000000000.000

Ohm

0.001

1000.000

Reference resistance R5 in ohm

RefX5

-1000000.000 1000000.000

Ohm

0.001

2000.000

Reference reactance X5 in ohm

Table 171:
Name
FilterLength

402

STTIPHIZ (64S) Non group settings (advanced)


Values (Range)
1s
2s

Unit
-

Step
-

Default
1s

Description
Length of filter buffer

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.11.8

Monitored data
Table 172:
Name

7.11.9

STTIPHIZ (64S) Monitored data


Type

Values (Range)

Unit

Description

RAVE

REAL

Ohm

Measured resistance to earth


in Ohm at inj freq

XAVE

REAL

Ohm

Measured reactance to earth


in Ohm at inj freq

FREQV

REAL

Hz

Measured frequency of
injected voltage into stator

RFAULT

REAL

Ohm

Estimated fault resistance in


Ohm

ZREF

INTEGER

Selected reference
impedance number

ZREFRE

REAL

Ohm

Used reference impedance


real part in Ohm

ZREFIM

REAL

Ohm

Used reference impedance


imaginary part in Ohm

VRMSSTAT

BOOLEAN

RMS voltage status, TRUE


when > VLimRMS

Operation principle
The protection function is based on signal injection into a stator winding. These square
wave signals are generated in a separate injection unit REX060.
The injection signals are connected to the stator winding via:

secondary winding of a voltage transformer (VT) located at the stator neutral point
open delta winding of a three-phase VT set located at generator terminals
secondary winding of a distribution transformer (DT) located at the stator neutral
point; note that REX062 is typically required for such arrangement
open delta winding of a three-phase grounding transformer (GT) located at generator
terminals; note that REX062 is typically required for such arrangement

In the REX060 unit the injection voltage and current signals are amplified to a level
adapted to the analogue voltage inputs of IED. In IED the measured signals are processed
and evaluation will give detection of stator faults.

7.11.9.1

Configuration principle
Figure 181 shows a typical installation for stator injection.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

403

Section 7
Impedance protection

1MRK 502 066-UUS A

10
Step-up
Transformer

U>

Vinj

1
Rshunt

GEN

Generator

100% SEF

I
RN

REX060/SIM module

8
3

95 % SEF

REG670

Generator Protection Panel

ANSI11000067-1-en.vsd

ANSI11000067 V1 EN

Figure 181:

404

Example installation for stator injection

Generator unit consisting of a synchronous generator and a step-up transformer

Grounding resistor for the stator winding

Neutral point VT which is used as injection point and also to provide galvanic separation between
primary circuit and injection equipment

Cable used to inject the square-wave signal into the stator circuit

Connection for measurement of injected current. This signal is amplified in REX060 before it is given to
REG670 for evaluation.

Cable for measurement of injected voltage at the injection point. This signal is amplified in REX060
before it is given to REG670 for evaluation.

Two VT inputs into REG670 which are used to measure injected current and voltage

Cable for 95% stator earth-fault protection

Separate VT input in REG670 used for 95% stator earth-fault protection

10

Protection for excessive over-voltages posed by generator. REX060 can withstand without damage
maximum voltage of 120V and when used together with REX062 up to 240V.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

The injection unit REX060


IED and
Injection
connectors

Top view

Back view

Power
connector

Front view
Keylock
LED

X11

X61

X81

18

Front-plate

X82

Rotor

Stator

Power

Backplane
HMI with logic

18

X62

PSM

Injection Stator

Injection Rotor

Injection LED

Injection switch

IEC11000015-1-en.vsd
IEC11000015 V1 EN

Figure 182:

Injection unit REX060

The REX060 unit is a common unit with it's own built-in Power Supply Module (PSM) of
the same type as used in the IED that can be equipped for either rotor or stator ground fault
protection, or for both. The REX060 has specific injection modules for rotor and stator
protection. The REX060 generates square wave signals, where one is used for injection to
the stator neutral point and the other to the field winding circuit (rotor circuit), if
configured for both stator and rotor protection. The injected voltages and currents are
measured by the unit and amplified, giving voltage signals both for the injected voltage
and current, and adapted to the analogue inputs of IED. The injection unit REX060 shall
be located close to the IED.
For the stator ground fault protection, there are some settings necessary for REX060:

System frequency: 50/60 Hz


Injected frequency for stator neutral point is settable in 1 Hz steps 50 250 Hz.
VT/DT maximum fundamental frequency voltage during ground fault in the stator
winding

REX060 will also continuously check the measured signal for detection of saturation
which could cause error in the evaluation in IED. If saturation level is reached, a binary
output contact is activated, which is connected to IED. Also other errors in injection will
activate another output contact to IED for blocking the function.
Stator injection output is protected against voltages exceeding maximum operating range
(10% of rated VT/DT) by a relay blocking the injection circuit. This blocking remains
blocked by stored status in non-volatile memory. Note REX060 is designed to cope with
such voltages of up to 120V. When optional REX062 resistor unit is used, REX060 can
cope with voltages of up to 240V at injection point.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

405

Section 7
Impedance protection

1MRK 502 066-UUS A

The output is also protected by a fuse. If this fuse is blown, it is caused by external voltage
source, since the injection unit cannot provide enough energy to blow this fuse.
Refer to the Hardware section in this manual for a detailed description of REX060.

7.11.9.2

Generator system grounding methods


There are several principles for system grounding of synchronous generators. The choice
of grounding method depends on different factors:

Limitation of earth fault current at stator ground fault


Damping of transient overvoltages in the generator system
Required insulation level to withstand overvoltage in healthy phases at single
phase ground fault
or Y coupled stator windings
Connection of a single generator via a step up transformer or connection of more than
one generator via a common step up transformer

Normally the generator system has some kind of high resistance grounding, giving ground
fault current within the range 5 20 A, thus preventing serious damages in case of stator
ground faults. Direct grounding will give too high ground fault current level. Isolated
generator system will give risk of transient overvoltages.
Below some alternatives for generator system grounding are shown;

406

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

C
IEC110000066-1-en.vsd

IEC11000066 V1 EN

Figure 183:

Generator grounding alternatives

High-resistance grounding with a neutral point resistor

Effective high-resistance grounding via a distribution transformer

High-resistance grounding via a delta, grounded-wye transformer

These earthing alternatives are characterized by the following properties:


A: High-resistance grounding with a neutral point resistor
This grounding method utilizes a high resistance in the primary circuit by inserting
resistor RN between the generator neutral and the ground. The actual resistance value of
RN is generally in order of k. Such high resistance is required in order to limit the primary
ground fault current to a quite small value (i.e. always < 20A and quite often < 10A
primary). Actual primary ground fault current can be calculated as follows:

EF_Max

G _ Ph - Ph

3 RN

EQUATION2515 V1 EN

where:

RN

is the ohmic value of the primary resistor

UG_Ph-Ph

is the protected generator rated phase-to-phase voltage

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

407

Section 7
Impedance protection

1MRK 502 066-UUS A

Typically a VT is connected in parallel with this resistor in order to measure voltage in the
stator neutral point.
The VT must have a rating of at least 100VA and a rated secondary
winding voltage of up to 120V. It must adhere to IEC 61869-3:2011
section 5.5.301 Rated Output Values and the standard values specified
according to burden range II.
The maximum voltage on the secondary side of the VT for an ground fault at generator
terminals can be calculated as:

U EF_Max =

U G _ Ph - Ph
3

U2
U1

EQUATION2516 V1 EN

where:

U2/U1

is the turn (i.e. rated voltage) ratio of the VT

UG_Ph-Ph

is the protected generator rated phase to phase voltage

B: Effective high-resistance grounding via a distribution transformer


This earthing method utilizes a distribution transformer that provides high resistance in
the primary circuit by utilizing a small resistor RN connected to the secondary winding of
the distribution transformer. The primary winding of the distribution transformer is
connected between the generator neutral and ground. The actual resistance value RN is
generally extremely small (i.e. typically < 1); however, the imposed ohmic value to the
primary circuit becomes quite high (i.e. in the order of k). The equivalent resistance in
the primary circuit can be calculated as follows:
2

U1
REq =
RN
U2
EQUATION2517 V1 EN

where:

408

U1/U2

is the turn (i.e. rated voltage) ratio of the distribution transformer

RN

is the ohmic value of the resistor connected to the secondary winding

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

The distribution transformer typically has rating of several kVA (e.g. 33kVA) and rated
secondary winding voltage of up to 240V. Note that maximum voltage on the secondary
side of the distribution transformer for an ground fault at generator terminals can be
calculated as follows:

U EF_Max =

U G _ Ph - Ph
3

U2
U1

EQUATION2516 V1 EN

where:

U2/U1

is the turn (i.e. rated voltage) ratio of the distribution transformer

UG_Ph-Ph

is the protected generator rated phase to phase voltage

Note that in case of an ground fault in the stator, the secondary current through the RN
resistor will be often in order of couple of hundred amperes. This maximum secondary
current can be calculated as follows:

I EF _ Sec =

U EF _ Max
RN

EQUATION2518 V1 EN

C: High-resistance grounding via a delta, grounded-wye transformer


This grounding method utilizes a specially constructed three-phase, five-limb power
transformer that provides high resistance in the primary circuit by utilizing a relatively
small resistor RN connected to the secondary open-delta connected windings. The primary
windings of this transformer is star (i.e. wye) connected and this neutral point is directly
connected to ground. The actual resistance value RN is relatively small (i.e. typically <
5); however, the imposed ohmic value to the primary circuit becomes quite high (i.e. in
the order of k). The equivalent resistance in the primary circuit can be calculated as
follows:
2

U1
REq =
RN
3 U 2
EQUATION2519 V1 EN

where:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

409

Section 7
Impedance protection

U1/U2

1MRK 502 066-UUS A

is the turn (i.e. rated voltage) ratio of one phase of the power transformer, e.g.
8 kV
3

500V
3

EQUATION2521 V1 EN

RN

is the ohmic value of a resistor connected to the secondary open-delta windings

The three-phase power transformer typically has rating of several tens of kVA (e.g.
129kVA) and rated secondary winding voltage of up to 550V. Note that maximum voltage
across secondary resistor RN for an ground fault at generator terminals can be calculated
as follows:

U EF_Max =

3 U G _ Ph - Ph

U2
U1

EQUATION2520 V1 EN

where:

U2/U1

is the turn (i.e. rated voltage) ratio of one phase of the power transformer, e.g.
500V
3

8 kV
3

EQUATION2522 V1 EN

UG_Ph-Ph

is the protected generator rated phase to phase voltage

Note that in case of an ground fault in the stator, the secondary current through the RN
resistor will be often in order of couple of hundred amperes. This maximum secondary
current can be calculated as follows:

I EF _ Sec =

U EF _ Max
RN

EQUATION2518 V1 EN

For all the alternatives the 100% stator earth fault protection can be applied.

410

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.11.9.3

100% Stator earth fault protection function


The injection to the stator is schematically shown in figure 184. It should be observed that
in this figure injection equivalent circuit is also shown with all impedances and injection
generator related to the primary side of the neutral point voltage transformer. Points a &
b indicate connection terminals for the injection equipment. Similar equivalent circuit can
be drawn for all other types of generator stator grounding shown in latter figures.

Z Bare
Z Measured
Z series
Cstat

R fault

Iinj

a
VN

Rf

Cstat

RN

ZmT

+
Vinj
-

b
Iinj
+
RN

Stator Reference
Impedance ZRef

Vinj
-

b
ANSI11000008_1_en.vsd

ANSI11000008 V1 EN

Figure 184:

High-resistance generator grounding with a neutral point resistor

There are some alternatives for connection of the neutral point resistor as shown in figure
185 (low voltage neutral point resistor connected via a DT).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

411

Section 7
Impedance protection

1MRK 502 066-UUS A

Cstat

Iinj

a
+

RN

Vinj
b

ANSI11000009_1_en.vsd
ANSI11000009 V1 EN

Figure 185:

Effective high-resistance generator grounding via a distribution


transformer

Another alternative is shown in figure 186 (High-resistance grounding via a delta,


grounded-wye transformer). In this case the transformer must withstand the large
secondary current caused by primary ground fault. The resistor typically has to be divided
as shown in figure 186 to limit the voltage to the injection equipment in case of ground
fault at the generator terminal. This voltage is often in the range 400 500 V. As the open
delta connection gives three times the zero sequence phase voltage this gives too high
voltage at the injection point if the resistance is not divided as shown in the figure 186 . By
dividing the resistor in two parts it shall be ensured that maximum voltage imposed back
on injection equipment is equal to or less than 240V.

412

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

I inj
RN
C stat

Vinj
b

ANSI11000010_1_en.vsd
ANSI11000010 V1 EN

Figure 186:

High-resistance generator grounding via a delta, grounded-wye


transformer

It is also possible to make the injection via VT open delta connection, as shown in figure
187.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

413

Section 7
Impedance protection

1MRK 502 066-UUS A

V1 / V2
Y

I inj
+
Rd

Vinj
-

stat

V
R d >> 1 RN
V2

RN

ANSI11000011_1_en.vsd
ANSI11000011 V1 EN

Figure 187:

Injection via open delta VT connection

It must be observed that the resistor Rd is normally applied for ferro-resonance damping.
The resistance Rd is will have very little contribution to the ground fault current as it has
high resistance. This injection principle can be used for applications with various
generator system grounding methods. It is therefore recommended to make the injection
via the open delta VT on the terminal side in most applications.
Accuracy for STTIPHIZ (64S) is installation dependent and it mainly depends on the
characteristic of grounding or voltage transformer used to inject signal into the stator.
Note that large variation of the ambient temperature and variation of stator capacitance
414

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

and conductance to ground between standstill and fully loaded machine will also limit the
possible setting level for the alarm stage. As a consequence 10 k sensitivity can be
typically reached without problem. Depending on particular installation alarm sensitivity
of up to 50 k may be reached at steady state operating condition of the machine.
Note that it is possible to connect two REG670 in parallel to the REX060 injection unit in
order to obtain redundant measurement in two separate IEDs. However, at commissioning
both REG670 IEDs must be connected during calibration procedure.

7.11.9.4

General measurement of ground fault impedance


From the REX060 the injected voltage and current are delivered as AC voltages to IED.
The injected voltage and current is measured and analyzed in the protection function
software within IED. The measured injected voltage and current are first processed by
means of special filtering so that the signals are referred to the injected frequency only.
The bare complex impedance is, see fig 184:

Z bare =

U Inj
I Inj

EQUATION2500 V1 EN

An equivalent circuit for the measured impedance is shown in figure 176.

ZMeasured

ZBare
Z series

Iinj
+

Rf

Z shunt

Uinj
-

IEC11000003-2-en.vsd
IEC11000003 V1 EN

Figure 188:

Equivalent of the impedance measurement

In non-faulted operation Rf is very large. A healthy impedance is calculated as:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

415

Section 7
Impedance protection

1MRK 502 066-UUS A

Z Measured = k1 Z bare + k 2
EQUATION2501 V1 EN

For definition of k1 and k2, see figure 177


The factors k1 and k2 [] are derived from measurements during commissioning, where
calibration to known fault resistance will be used to convert the measurement to true
primary impedance. The factor k1 will compensate for transformer ratio and other factors
to achieve impedance values related to the primary system. The factor k2 [] will
compensate for the series impedance Zseries
The healthy impedance measured at non-faulted conditions is referred to as the reference
impedance in further text.
In IED the measured impedance is compared to the reference impedance. In case of an
ground fault, the fault impedance is estimated and compared to the set values RAlarm and
RTrip.
If the measured impedance is larger than the setting openCircuitLimit, the output OPCIRC
is set TRUE. If OPCIRC is set, it means there is a strong likelihood that the generator
neutral resistor is not anymore connected to ground, since only the capacitive part in the
circuit is left. The open circuit is only applied on the stator winding protection. To make
the open circuit limit more stable a hysteresis is added. If OPCIRC is TRUE, the measured
fault impedance must drop below open circuit limit * (1 - OpenCircLim) to reset. The
hysteresis is hidden and set to a default value of 10% of open Circuit limit for the stator.
Open- circuit
characteristics
no open- circuit

open- circuit

Open Circuit
Hysteresis

{Z

Measured

} re

openCircuitLimit
IEC11000073-1-en.vsd
IEC11000073 V1 EN

Figure 189:

Open circuit characteristics

Blocking: The output OPCIRC is blocked during an error occurring and during
initialization of function.
Detailed Set: If the total measured real part of the impedance is greater than the setting
OpenCircLim the output OPCIRC is TRUE, see figure 176.
416

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.11.9.5

Measuring reference impedance


The healthy impedance is equal to the parallel connection of the neutral point resistor
(RN), the capacitive reactance between the stator windings and ground (1/Cstat), the
transformer magnetization impedance (ZmT) and the ground fault resistance (Rf). The
series resistance in the injection circuit is eliminated by k2. Rf is very large in the nonfaulted case and the measured impedance is equal to the stator reference impedance:

1
Z ref

1
RN

+ jw C stat +

1
Z mT

EQUATION2502 V1 EN

Where

w = 2p finj
EQUATION2503 V1 EN

The injected frequency finj of the square wave, is a set value, deviating from the
fundamental frequency (50 or 60 Hz). The injected frequency can be set within the range
50 250 Hz with recommend value 87 Hz in 50 Hz systems and 103 Hz in 60 Hz systems.
The reference impedance can vary depending on the operational state. The reason for this
can be the following:

The influence from the impedance ZmT will be different when the generator is standstill and when it is in operation
The capacitance to ground will vary if the generator breaker is open or closed
The capacitance will vary if the generator is energized or not depending on stator end
winding corona protection
Non-linearity of used injection transformer, different properties at low and high total
voltage and temperature changes
Impedance to ground is affected by auxiliary loads connected between generator and
unit transformer. If these loads vary, the estimated ground fault resistance will be
affected.

The difference from the first reference impedance is identified by monitoring impedance
(RAVE + jXRAVE) during different operation modes. This impedance is available as a
service value from the stator function both on built-in HMI and in ICT tool. If the
difference is significant more than one reference impedance is required. In the ICT up to
five different sets of reference impedances can be derived during commissioning for
different states of operation and downloaded to the protection function as different values

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

417

Section 7
Impedance protection

1MRK 502 066-UUS A

of the reference impedance; RefRn and RefXn where n = 1, 2, and up to 5. Switching of


reference impedance can be made automatically.
During commissioning ICT also makes cross-calculations between acquired
references, giving basically the calculated fault resistance between each existing
reference combination. This would be the fault resistance measured by the function when
the reference change occurs from one reference to another if the real generator impedance
stays the same, in other words a worst case scenario.
RMS voltage (rmsVolt) value at the injection point can be used for detecting when a
reference needs to be changed and logical outputs can be set to reflect whether the RMS
voltage is higher or lower than a prescribed value. There is one such output for the voltage
signal and one for the current signal. It is advantageous to use RMS to determine a change
of machine condition because the RMS makes a distinction between the measured values
and the total amplitude of the signal. The standstill condition only contains the injected
frequency, while the full load condition and full speed condition contains other
frequencies, which amplitudes may change under varying machine conditions.
In case of a stator ground fault with fault impedance Zf the measured admittance will be:

1
Z

1
Z ref

1
Zf

EQUATION2513 V1 EN

and this gives:

1
Zf

1
Z

1
Z ref

EQUATION2514 V1 EN

and the real part gives the fault conductance:


1
1
1
= Re Z Z ref
Rf

EQUATION2421 V1 EN

In the settings there are given two resistance levels:

RAlarm given in . If

R f < RAlarm
EQUATION2524 V1 EN

418

an alarm signal ALARM is given after a set delay tAlarm.


RTrip given in . If
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

R f < RTrip
EQUATION2523 V1 EN

a start signal BFI is given.


If the fault resistance is slightly below the set value RTrip the trip time will be about 10 s
with default filter length of 1 s. If the fault resistance is estimated to 0 the trip delay will
be 2 s with default filter length of 1 s. For values in between the delay will follow linear
interpolation describing the fault resistance time relation, as shown in figure 190.
Note that actual tripping time is dependent on the set parameter FilterLength which has
default value of 1s.
Trip time

10 FilterLength

2 FilterLength

Fault resistance

RTrip

RAlarm
IEC11000002-1-en.vsd

IEC11000002 V1 EN

Figure 190:

Trip time characteristic as function of fault resistance

During run-up and shut down of the generator, i.e. when the rotational speed of the
generator changes, there will occur harmonic voltages with varying frequency at the
injection equipment connection point (for example see voltage generator Vn in Figure
184). If such frequencies interfere with the injected frequency this might create an error in
the fault resistance estimation. Such situations are identified in the function and the
function is automatically stabilized to prevent unwanted operation of the protection.
In connection with this calibration the reference impedance is also derived.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

419

Section 7
Impedance protection

1MRK 502 066-UUS A

It is possible to have up to five different reference impedances. The need to change


reference impedance is due to different operating conditions for the generator, for
instance:
1.
2.
3.

Generator stand still


Generator running, not synchronized to the power network
Generator in normal operation, synchronized to the power network

The following automatic choice for the actual reference impedance can for example be
made:

Generator voltage < set value and generator circuit breaker open: Reference
impedance 1
Generator voltage > set value and generator circuit breaker open: Reference
impedance 2
Generator voltage > set value and generator circuit breaker closed: Reference
impedance 3

The monitoring, enabled in ICT, will give indication if several reference impedance
values are needed.
From the measured impedance the stator ground fault resistance can be estimated since the
reference impedance is known. An alarm level () is set at a higher value and the ALARM
signal is activated after a set alarm delay time. A trip level () is also set at a lower value.
When the trip level is reached a TRIP signal is activated as shown in figure 190.

420

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.11.9.6

Simplified logic diagram


STTIPHIZ

Uinj
Rshunt

2
6

Rf

Z Measured
Compare &
Evaluate

I Inj

u_i_sef

U Inj

u_u_sef

Z Bare
X

K2

K1

ZRef1

ZRef2

REX060

ZRef3
ZRef4

SELECT REFERENCE

ZRef5

95% Trip

tON=0.5s
t

a
a>b
b

UN

UN> = 5%

un

95% Stator earth fault protection

REG670

IEC10000325-2-en.vsd

IEC10000325 V1 EN

Figure 191:

Simplified logic diagram for 100% stator earth fault protection STTIPHIZ

The 100% stator earth fault protection function receives amplified injected voltage and current via
the REX060 unit as two voltage signals. (Voltage inputs in the REG670).

The phasor of injected voltage UInj and phasor of injected current IInj is calculated by using special
filter from raw samples. Observe that phasors are calculated for the injected frequency.

The complex bare impedance is calculated from Uinj / Iinj.

4, 5

The complex measured impedance is derived as ZMeasured = Zbare*k1 + k2.

The fault resistance (RFault) is calculated from the complex measured impedance and a selected
complex reference.

Selection of one (out of maximum 5) ZRef.

Fourier filter to derive the phasor of zero sequence voltage at fundamental frequency

The 95% stator earth fault zero sequence over voltage function must operate in parallel with
STTIPHIZ.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

421

Section 7
Impedance protection

1MRK 502 066-UUS A

Rf
OR

Alarm

Adaptive
TripDelay

Trip

IEC10000326-3.vsd
IEC10000326 V2 EN

Figure 192:

STTIPHIZ alarm and trip logic

If the fault resistance Rf is smaller than RAlarm and last longer than set alarm delay, output
ALARM is set. If the fault resistance Rf is smaller than RTrip, output signal TRIP is set after
the calculated time. For trip time delay, see fig 190

7.11.10

Technical data
Table 173:

STTIPHIZ technical data

Function

Range or value

Accuracy

Can be reached at
steady state operating
condition of the machine

50 k

Typically

10 k

Injection frequency

(50.000 - 250.000) Hz

0.1 Hz

Injection voltage

240 V

Trip limit of fault resistance

(100 - 10000)

5% of 1 k at Rf 1 k
10% of set value at Rf > 1 k

Alarm limit of fault resistance

(100 - 100000)

5% of 1 k at Rf 1 k
10% of 10 k at 1 k < Rf 10 k
50% of set value at Rf > 10 k

Fault resistance sensitivity

Table continues on next page

422

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Trip time, start at Rf ~ 0 and filter


length = 1 s

1.00 s typically

Trip time, trip at Rf ~ 0 and filter


length = 1 s

3.00 s typically

Alarm time delay at Rf ~ 0 and


filter length = 1 s

(0.00 - 600.00) s

0.2% or 2.00 s whichever is greater

7.12

Under impedance protection for generators and


transformers ZGVPDIS

7.12.1

Identification
Function description
Under impedance function for
generators and transformers

IEC 61850
identification

IEC 60617
identification

ZGVPDIS

ANSI/
IEEEidentification
21G

S00346 V1 EN

7.12.2

Functionality
The under impedance protection is a three zone full scheme impedance protection using
offset mho characteristics for detecting faults in the generator, generator-transformer and
transmission system. The three zones have fully independent measuring loops and
settings. The functionality also comprises an under voltage seal-in feature to ensure
issuing of a trip even if the current transformer goes into saturation and, in addition, the
positive-sequence-based load encroachment feature for the second and the third
impedance zone. Built-in compensation for the step-up transformer vector group
connection is available.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

423

Section 7
Impedance protection
7.12.3

1MRK 502 066-UUS A

Function block
ZGVPDIS (21)
I3P*
V3P*
BLOCK
BLKZ
BLKUV

TRIP
TRZ1
TRZ2
TRZ3
27 Trip
PICKUP
PU_Z1
PU_Z2
PU_Z3
27 PU
ANSI14000063-1-en.vsd

ANSI14000063 V1 EN

Figure 193:

7.12.4

Signals
Table 174:
Name

ZGVPDIS (21) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Connection for current sample signals

V3P

GROUP
SIGNAL

Connection for voltage sample signals

BLOCK

BOOLEAN

Block of the function

BLKZ

BOOLEAN

Block due to fuse failure

BLKUV

BOOLEAN

Block of the under voltage seal in

Table 175:
Name

424

ZGVPDIS (21) function block

ZGVPDIS (21) Output signals


Type

Description

TRIP

BOOLEAN

General Trip

TRZ1

BOOLEAN

Trip signal Zone 1

TRZ2

BOOLEAN

Trip signal Zone 2

TRZ3

BOOLEAN

Trip signal Zone 3

27 Trip

BOOLEAN

Trip from Under voltage seal in

PICKUP

BOOLEAN

Pickup

PU_Z1

BOOLEAN

Pick up Zone 1

PU_Z2

BOOLEAN

Pick up Zone 2

PU_Z3

BOOLEAN

Pick up zone 3

27 PU

BOOLEAN

Pick up under voltage seal in

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.12.5
Table 176:
Name

Settings
ZGVPDIS (21) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
On

Disabled

Operation Disabled/Enabled

ImpedanceAng

5 - 90

Deg

80

Impedance angle in degrees, common for all


zones

IMinOp

5 - 80

%IB

10

Minimum operate phase current

OpModeZ1

Disabled
PP Loops

PP Loops

Operation mode of Zone 1: Off/Ph-Ph loops

Z1Fwd

3.0 - 100.0

% Zb

0.1

8.0

Zone 1 forward reach in % of rated impedance,


100%=full load

Z1Rev

3.0 - 100.0

% Zb

0.1

8.0

Zone 1 reverse reach in % of rated impedance,


100%=full load

tZ1

0.000 - 60.000

0.001

0.000

Time delay to operate for Zone 1

OpModeZ2

Disabled
PP Loops
EnhancedReach

EnhancedReach

Operation mode of Zone 2: Off/Ph-Ph/


EnhancedReach

Z2Fwd

3.0 - 200.0

% Zb

0.1

15.0

Zone 2 forward reach in % of rated impedance,


100%=full load

Z2Rev

3.0 - 200.0

% Zb

0.1

8.0

Zone 2 reverse reach in % of rated impedance,


100%=full load

tZ2

0.000 - 60.000

0.001

0.500

Time delay to operate for Zone 2

OpModeZ3

Disabled
PP Loops
EnhancedReach

EnhancedReach

Operation mode of Zone 3: Disable/Ph-Ph/


EnhancedReach

Z3Fwd

3.0 - 200.0

% Zb

0.1

75.0

Zone 3 forward reach in % of rated impedance,


100%=full load

Z3Rev

3.0 - 200.0

% Zb

0.1

8.0

Zone 3 reverse reach in % of rated impedance,


100%=full load

tZ3

0.000 - 60.000

0.001

1.500

Time delay to operate for Zone 3

OpMode27pickup

Disabled
Z2pick up
Z3pick up

Disabled

Enable under voltage seal in (Disable/Z2Start/


Z3Start)

27_COMP

5 - 90

%VB

70

Pickup value of under voltage seal in

timeDelay27

0.000 - 60.000

0.001

5.000

Time delay to operate for under voltage seal in

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

425

Section 7
Impedance protection

Table 177:
Name

1MRK 502 066-UUS A

ZGVPDIS (21) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

RLd

5 - 120

% Zb

50

Resistive reach in % for load encroachment


charateristics

LdAngle

5 - 85

Deg

38

Load encroachment inclination of load angular


sector

LoadEnchModZ2

Disabled
Enabled

Disabled

Enable load encroachement for Zone 2 enable/


disable

LoadEnchModZ3

Disabled
Enabled

Enabled

Enable load encroachement for Zone 3 enable/


disable

Table 178:
Name
GlobalBaseSel

7.12.6

ZGVPDIS (21) Non group settings (basic)


Values (Range)

Unit

1 - 12

Step

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 179:

ZGVPDIS (21) Monitored data

Name

7.12.7

Default

Type

Values (Range)

Unit

Description

VA

REAL

kV

Voltage in phase A

VB

REAL

kV

Voltage in phase B

VC

REAL

kV

Voltage in phase C

IA

REAL

Current in phase A

IB

REAL

Current in phase B

IC

REAL

Current in phase C

Operation principle
The reach values for all the zones are set in percentage of impedance base value. The
impedance base value is calculated using the generator current and voltage ratings.
The base value of impedance can be calculated according to equation 93.
ZBase =

VBase
3 IBase
(Equation 93)

ANSIEQUATION1400024 V1 EN

Where,

ZBase
426

is the base value of impedance

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

VBase

is the line-to-line voltage rating at the generator terminal

IBase

is the line current rating at the generator terminal

The minimum trip current is provided using the setting IMinOp.


All the outputs will be blocked by activation of the BLOCK or BLKZ input.

Offset mho characteristic


ZGVPDIS consists of three distance elements operated for three zones separately. Each
zone consists of measuring loops which uses self-polarized offset mho characteristics
with both forward and reverse reach settings for the detection of the fault in the respective
zone. The operating characteristics of all the three zones are shown in Figure 194. The
ImpedanceAngle setting is common to all three zones.
jX

Offset Mho, Zone3

Offset Mho, Zone2


Offset Mho, Zone1
ImpedanceAng
R

IEC11000294-2-en.vsd
IEC11000294 V2 EN

Figure 194:

Offset mho characteristics of three zones

The complete functionality is shown in figure 195.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

427

Section 7
Impedance protection

1MRK 502 066-UUS A

V3P
I3P
BLKZ
BLOCK

PU_Z1

ZONE 1

TRZ1
OpModetZ1
Z1Fw
Z1Rev
tZ1

PICKUP

OR

PU_Z2

ZONE 2
OpModetZ2
Z2Fw
Z2Rev
tZ2
LoadEnchModZ2

TRZ2

TRIP

OR
OR

ZONE 3

PU_Z3

OpModetZ3
Z3Fw
Z3Rev
tZ3
LoadEnchModZ3

TRZ3

LoadEnch
RLd
LdAngle

UVSealIn

27 Trip

OpMode27pickup
27_COMP
timeDelay27

27 PU

BLOCKUV
ANSI11000295_2_en.vsd
ANSI11000295 V2 EN

Figure 195:

7.12.7.1

Block diagram of ZGVPDIS

Operation principle of zone 1


In general, the zone 1 must cover the generator winding, the cables or busbars and step up
transformer.
Under impedance functionality is provided as selective protection for the phase-to-phase
faults in zone 1. Hence the functionality of zone 1 includes only phase-to-phase measuring
loops.
Zone 1 functionality can be set to PP Loops or Disabled using the setting OpModeZ1.

428

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

Figure 196 shows the functionality of zone 1.


BLOCK
BLKZ

V3P
I3P

Comparator
ZAB <
EnableZone1
Z1Fw
Z1Rev

pickupZone1

Timer Logic

Comparator
ZBC

<

EnableZone1
Z1Fw
Z1Rev

OR

tripZone1

tOpDelayZ1
opModetZ1

Comparator
ZCA <
EnableZone1
Z1Fw
Z1Rev

ANSI11000297_1.en.vsd

ANSI11000297 V1 EN

Figure 196:

Block diagram of zone 1

The functionality included in zone 1:

Comparator to detect, if the operating impedance has entered inside zone 1 offset mho
characteristic.
All three phase-to-phase loops are implemented separately.
Forward and reverse reach values are provided in percentage of impedance base value
at generator.
Trip time delay is provided.

Comparator characteristics
The comparator consists of offset mho characteristics. Three individual comparators are
provided in the three phase-to-phase loops. The offset mho characteristic is as shown in
figure 197.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

429

Section 7
Impedance protection

1MRK 502 066-UUS A

I AB jX
I A B Z1FW
Vcomp1= VAB - I AB Z1FW

Vcomp 2 = VA B + IABZ1REV
I A B jX

- I AB Z 1REV
ANSI11000296_1_en.vsd
ANSI11000296 V1 EN

Figure 197:

Simplified offset mho characteristics for A-B fault in zone 1

Criteria: Operation occurs if 90 270.


In the above characteristics, Z1Fwd and Z1Rev are the forward and reverse reach
percentage values and ImpedanceAng is the characteristic angle provided for the zone 1
operation region.
Z 1Fwd

Z 1Fwd ImpedanceAng
(Equation 94)

IECEQUATION14000025 V2 EN

Z 1Rev = Z 1rev ImpedanceAng


(Equation 95)

IECEQUATION14000026 V2 EN

Voltage and current phasors selected for phase-to-phase loops are:


Sl.No

Phase-to-phase loop
1

A-B

B-C

C-A

Voltage phasor

Current phasor

VAB

IAB

VBC

IBC

VCA

ICA

Trip time
The operate time delay for zone 1 can be provided using the setting tZ1.

430

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.12.7.2

Operation principle of zone 2


Figure 198 shows the function block diagram describing the functionality of zone 2.
EnableZone2 = Max Curr PhG

V3P

Zero
sequence
Voltage
Compensation

I3P
BLOCK
BLKZ

Max Curr
Loop logic

Measuring Loop
phase-to-ground
(ZA<,ZB<,ZC<)

T
F

EnableZone2
Z2Fwd
Z2Rev
LineAngle

PU_Z2

OR

AND
Measuring Loop
phase-to-phase

(ZAB<,ZBC<,ZCA<)

EnableZone2
Z2Fwd
Z2Rev
LineAngle

AND

LoadEnchMod2

Timer
T

TRZ2

tZ2

OpModeZ2

Load
Encroachment
RLd
LdAngle

ANSI11000298_2_en.vsd

ANSI11000298 V2 EN

Figure 198:

Block diagram of zone 2

Zone 2 can be used to cover up to the HV side of the transformer and the HV bus bar. It
also covers to some degree, the stator winding. The time to trip is provided in order to
coordinate with the zone 1 element on the shortest outgoing line from the bus.
Zone 2 coverage provides backup for the phase-to-phase and three-phase faults in
generator. It also protects LV winding of generator transformer and phase-to-ground,
phase-to-phase and three-phase faults in the HV side of transformer and bus. A separate
maximum current feature is provided in phase-to-ground loop selection which gives
correct reach measurement for phase-to-phase fault on HV side. Zero sequence
compensation for the phase voltages is given in phase-to-ground measuring loops in order
to prevent operation for the stator ground faults.
Zone 2 can be selected for different measuring loops using the setting OpModeZ2. The
OpModeZ2 can be selected as Disabled or PP Loops or EnhancedReach. If the OpModeZ2
is selected as EnhancedReach, the loop used for measurements is the phase-to-earth
measuring loop (AG, BG and CG) which is with maximum phase current of all the three
phase currents.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

431

Section 7
Impedance protection

1MRK 502 066-UUS A

Figure 199 shows the logic to detect the phase to ground loop with maximum phase
current.
a

i1Mag

pickupPh1

NOT

i2Mag

a
b

pickupPh2

AND

AND

OR

pickup

B
a==b

pickupPh3

OR
i3Mag

AND

a==b

NOT

AND

AND

C
a==b

MAX

ANSI11000307_1_en.vsd

ANSI11000307 V1 EN

Figure 199:

Logic diagram for the selection of the maximum current loop

The phase-to-ground voltage is compensated with zero sequence voltage in order to avoid
the function operating for ground faults in zone 1, that is, complete generator stator
winding and LV winding of the power transformer.
The reach settings for zone 2 can be provided using the Z2Fwd, Z2Rev and ImpedanceAng
settings. The Z2Fwd is forward reach setting and Z2Rev is reverse reach setting. The offset
mho characteristic for phase-to-ground loop is shown in Figure 200. The offset mho
characteristics for phase-to-phase loop is shown in Figure 201.

432

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

I A jX
I A Z 2 FW

Vcomp1 = V AG - V 0 - I A Z 2 FW

Vcomp 2 = V AG - V 0 + I A Z 2 REV

I A jX
- I A Z 2 REV

ANSI11000299_1_en.vsd
ANSI11000299 V1 EN

Figure 200:

Simplified offset mho characteristics for A-to-G fault in zone 2


IAB jX

IAB Z 2 FW

Vcomp1 = VAB - IAB Z 2 FW

Vcomp 2 = VAB + IAB Z 2 REV

IAB jX
- IAB Z 2 REV

ANSI11000300_1_en.vsd
ANSI11000300 V1 EN

Figure 201:

Simplified offset mho characteristics for A-to-B fault in zone 2

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

433

Section 7
Impedance protection

1MRK 502 066-UUS A

Operation occurs if 90 270.


Impedance defined in the Figure 200 and 201 is described in equation 96.
Z 2 Fwd

Z 2 Fwd ImpedanceAng

Z 2 Rev

Z 2 Rev ImpedanceAng
(Equation 96)

GUID-007D6357-B7CF-4C21-B772-2245F06C83A2 V2 EN

Voltage and current phasors selected for different measuring loops:


Phase Phase:
Sl.No

Measuring Loop

A-B

B-C

C-A

Voltage Phasor

Current Phasor

VAB

IAB

VBC

IBC

VCA

ICA

Enhanced Reach:
Sl.No

Measuring Loop

IA

IB

IC

Voltage Phasor

Current Phasor

VAG - V 0

IA

VBG - V 0

IB

VCG - V 0

IC

Trip time
The operate time delay for zone 2 can be provided using the setting tZ2.
Zone 2 is provided load encroachment detection feature based on positive sequence
components measurements.. This feature avoids the function from operating due to load
encroachment. The load encroachment feature for zone 2 can be set using
LoadEnchModZ2 to Enabled or Disabled.

7.12.7.3

Operation principle of zone 3


Zone 3 is used to cover up to the HV side of the transformer, interconnecting bus network
and outgoing lines. The time to trip should be provided in order to coordinate with the
transmission line protection.

434

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

The Zone3 functionality is same as zone2, hence the explanation of zone 2 applies for zone
3, except the zone 3 has separate reach (Z3Fw, Z3Rev), operate timer (tZ3) and load
encroachment enable (LoadEnchModZ3) settings.

7.12.7.4

Load encroachment
The load encroachment characteristics can be set for zone2 and zone3. Load
encroachment can be enabled for zone 2 by setting LoadEnchModZ2 to Enabled.
Similarly the load encroachment for zone 3 can be enabled by setting LoadEnchModZ3 to
Enabled.
The load encroachment characteristic is based on positive sequence quantities and can be
set using the settings RLd and LdAngle.
RLd is the positive sequence resistive reach value in percentage. LdAngle is angle in
degrees from the origin to the resistive axis as shown in Figure 202.

ANSI11000304-1-en.vsd
ANSI11000304 V1 EN

Figure 202:

Load encroachment characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

435

Section 7
Impedance protection
7.12.7.5

1MRK 502 066-UUS A

Under voltage seal-in


The under voltage seal-in logic ensures the trip under fault condition, where as under
impedance function will reset due to CT saturation. The pickup signal of zone 2 and zone
3 elements trigger the under voltage seal-in. This can be selected using the setting
OpMode27pickup. The setting OpMode27pickup can be selected as Disabled or Z2pick up
or Z3pick up. Select Z2Start to choose zone 2 for triggering the seal-in logic. Similarly,
select Z2pick up to choose zone 3 for triggering the seal-in logic.
Under voltage seal-in is activated from the criterion based on line-to-line voltage
magnitude. The voltage criteria checks by comparing all three line-to-line voltage levels
with the level given by the setting parameter 27_COMP. If any loop detects lower voltage,
the under voltage seal-in logic gets triggered, provided the respective selected zone start
is also high. Once the under voltage seal-in logic is triggered, the pick-up signal 27 PU
becomes high. If it is constantly high for a time longer than the setting timeDelay27, the
tripping signal 27 Trip is issued as a pulse signal with a duration of one second.
Figure 203 shows the functionality of under voltage seal-in for zone 2 and zone 3.
q-1

BLOCK
BLKUV

OR

AND

Zone 2 picukp
AND

EnableUV =
0 = UV OFF
1 =Z2 pickup
2 =Z3 pickup

int

b0

uP1P2

OR

b1

Zone 3 pickup

27_COMP

27 PU

Drop-Off
timer
0
10 ms

OR

timeDelay27
0

27 Trip
tPulse = 1sec

q1

AND

a<b

Comparator
with
hysterisis relative as 5%

uP2P3

27_COMP

a<b

OR

Comparator
with
hysterisis relative as 5%

uP3P1
27_COMP

a
a<b
b
Comparator
with
hysterisis relative as 5%
ANSI11000306_2_en.vsd

ANSI11000306 V3 EN

Figure 203:
436

Under voltage seal-in for zone 2 and zone 3


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 7
Impedance protection

1MRK 502 066-UUS A

7.12.8

Technical data
Table 180:

ZGVPDIS (21) Technical data

Function

Range or value

Accuracy

Number of zones

Forward reach

(3.0 - 200.0)% of Zn
where Zn=VBase/3IBase

5.0% of set impedance


Conditions:
Voltage range: (0.1 - 1.1) x Vn
Current range: (0.5 - 30) x In

Reverse reach

(3.0 - 200.0)% of Zn
where Zn=VBase/3IBase

5.0% of set impedance


Conditions:
Voltage range: (0.1 - 1.1) x Vn
Current range: (0.5 - 30) x In

Impedance angle

(5 - 90) degrees

Reset ratio

105% typically

Pickup time at 1.2 to 0.8 x set


impedance

Min. = 15 ms

Independent time delay to operate


at 1.2 to 0.8 x set impedance

Max. = 35 ms
(0.000 60.000) s

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

0.2% or 40 ms whichever is
greater

437

438

Section 8
Current protection

1MRK 502 066-UUS A

Section 8

Current protection

8.1

Instantaneous phase overcurrent protection PHPIOC


(50)

8.1.1

Identification
Function description

IEC 61850
identification

Instantaneous phase overcurrent


protection 3-phase output

IEC 60617
identification

ANSI/IEEE C37.2
device number
50

PHPIOC

3I>>
SYMBOL-Z V1 EN

8.1.2

Functionality
The instantaneous three phase overcurrent function has a low transient overreach and
short tripping time to allow use as a high set short-circuit protection function.

8.1.3

Function block
PHPIOC (50)
I3P*
BLOCK
MULTPU

TRIP
TR_A
TR_B
TR_C
ANSI04000391-2-en.vsd

ANSI04000391 V2 EN

Figure 204:

8.1.4

PHPIOC (50) function block

Signals

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

439

Section 8
Current protection

1MRK 502 066-UUS A

Table 181:

PHPIOC (50) Input signals

Name

Type

Three phase current

BLOCK

BOOLEAN

Block of function

MULTPU

BOOLEAN

Enable current pickup value multiplier

PHPIOC (50) Output signals

Name

Table 183:
Name

Description

GROUP
SIGNAL

Table 182:

8.1.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Trip signal from any phase

TR_A

BOOLEAN

Trip signal from phase A

TR_B

BOOLEAN

Trip signal from phase B

TR_C

BOOLEAN

Trip signal from phase C

Settings
PHPIOC (50) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OpModeSel

2 out of 3
1 out of 3

1 out of 3

Select operation mode (2 of 3 / 1 of 3)

Pickup

5 - 2500

%IB

200

Phase current pickup in % of IBase

Table 184:
Name
MultPU

Table 185:
Name
GlobalBaseSel

440

PHPIOC (50) Group settings (advanced)


Values (Range)
0.5 - 5.0

Unit
-

Step
0.1

Default
1.0

Description
Multiplier for operate current level

PHPIOC (50) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Description
Selection of one of the Global Base Value
groups

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 186:
Name

PHPIOC (50) Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

PU_MinEd2Set

5 - 2500

%IB

Minimum settable operate phase current level


in % of IBase, for 61850 Ed.2 settings

PU_MaxEd2Set

5 - 2500

%IB

2500

Maximum settable operate phase current level


in % of IBase, for 61850 Ed.2 settings

8.1.6

Monitored data
Table 187:
Name

8.1.7

PHPIOC (50) Monitored data


Type

Values (Range)

Unit

Description

IA

REAL

Current in phase A

IB

REAL

Current in phase B

IC

REAL

Current in phase C

Operation principle
The sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT)
block. The RMS value of each phase current is derived from the fundamental frequency
components, as well as sampled values of each phase current. These phase current values
are fed to the instantaneous phase overcurrent protection 3-phase output function
PHPIOC (50). In a comparator the RMS values are compared to the set operation current
value of the function Pickup. If a phase current is larger than the set operation current a
signal from the comparator for this phase is set to true. This signal will, without delay,
activate the output signal TR_x(x=A, B or C) for this phase and the TRIP signal that is
common for all three phases.
There is an operation mode (OpModeSel) setting: 1 out of 3 or 2 out of 3. If the parameter
is set to 1 out of 3 any phase trip signal will be activated. If the parameter is set to 2 out of 3
at least two phase signals must be activated for trip.
There is also a possibility to activate a preset change of the set operation current (MultPU)
via a binary input (MULTPU). In some applications the operation value needs to be
changed, for example due to transformer inrush currents.
PHPIOC (50) can be blocked from the binary input BLOCK.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

441

Section 8
Current protection
8.1.8

1MRK 502 066-UUS A

Technical data
Table 188:

PHPIOC (50) technical data

Function

Range or value

Accuracy

Trip current

(5-2500)% of lBase

1.0% of In at I In
1.0% of I at I > In

Reset ratio

> 95% at (502500)% of IBase

Trip time at 0 to 2 x Iset

Min. = 15 ms
Max. = 25 ms

Reset time at 2 to 0 x Iset

Min. = 15 ms
Max. = 25 ms

Critical impulse time

10 ms typically at 0 to 2 x Iset

Trip time at 0 to 10 x Iset

Min. = 5ms
Max. = 15ms

Reset time at 10 to 0 x Iset

Min. = 25ms
Max. = 40 ms

Critical impulse time

2 ms typically at 0 to 10 x Iset

Dynamic overreach

< 5% at t = 100 ms

8.2

Four step phase overcurrent protection


OC4PTOC(51/67)

8.2.1

Identification
Function description
Four step phase overcurrent protection
3-phase output

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
51_67

OC4PTOC

TOC-REVA V2 EN

8.2.2

Functionality
The four step three-phase overcurrent protection function OC4PTOC (51/67) has
independent inverse time delay settings for steps 1 to 4.
All IEC and ANSI inverse time characteristics are available together with an optional user
defined time characteristic.

442

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

The directional function needs voltage as it is voltage polarized with memory. The
function can be set to be directional or non-directional independently for each of the steps.
A second harmonic blocking level can be set for the function and can be used to block each
step individually.

8.2.3

Function block
OC4PTOC (51_67)
I3P*
TRIP
V3P*
TRST1
BLOCK
TRST2
BLKTR
TRST3
BLK1
TRST4
BLK2
TR_A
BLK3
TR_B
BLK4
TR_C
MULTPU1
TRST1_A
MULTPU2
TRST1_B
MULTPU3
TRST1_C
MULTPU4
TRST2_A
TRST2_B
TRST2_C
TRST3_A
TRST3_B
TRST3_C
TRST4_A
TRST4_B
TRST4_C
PICKUP
PU_ST1
PU_ST2
PU_ST3
PU_ST4
PU_A
PU_B
PU_C
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2_A
PU_ST2_B
PU_ST2_C
PU_ST3_A
PU_ST3_B
PU_ST3_C
PU_ST4_A
PU_ST4_B
PU_ST4_C
2NDHARM
DIR_A
DIR_B
DIR_C
ANSI06000187-2-en.vsd
ANSI06000187 V2 EN

Figure 205:

OC4PTOC (51_67) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

443

Section 8
Current protection
8.2.4

1MRK 502 066-UUS A

Signals
Table 189:
Name

OC4PTOC (51_67) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block of trip

BLK1

BOOLEAN

Block of Step1

BLK2

BOOLEAN

Block of Step2

BLK3

BOOLEAN

Block of Step3

BLK4

BOOLEAN

Block of Step4

MULTPU1

BOOLEAN

When activated, the pickup multiplier is in use for step1

MULTPU2

BOOLEAN

When activated, the pickup multiplier is in use for step2

MULTPU3

BOOLEAN

When activated, the pickup multiplier is in use for step3

MULTPU4

BOOLEAN

When activated, the pickup multiplier is in use for step4

Table 190:
Name

OC4PTOC (51_67) Output signals


Type

Description

TRIP

BOOLEAN

Trip

TRST1

BOOLEAN

Common trip signal from step1

TRST2

BOOLEAN

Common trip signal from step2

TRST3

BOOLEAN

Common trip signal from step3

TRST4

BOOLEAN

Common trip signal from step4

TR_A

BOOLEAN

Trip signal from phase A

TR_B

BOOLEAN

Trip signal from phase B

TR_C

BOOLEAN

Trip signal from phase C

TRST1_A

BOOLEAN

Trip signal from step1 phase A

TRST1_B

BOOLEAN

Trip signal from step1 phase B

TRST1_C

BOOLEAN

Trip signal from step1 phase C

TRST2_A

BOOLEAN

Trip signal from step2 phase A

TRST2_B

BOOLEAN

Trip signal from step2 phase B

TRST2_C

BOOLEAN

Trip signal from step2 phase C

TRST3_A

BOOLEAN

Trip signal from step3 phase A

TRST3_B

BOOLEAN

Trip signal from step3 phase B

Table continues on next page

444

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Type

Description

TRST3_C

BOOLEAN

Trip signal from step3 phase C

TRST4_A

BOOLEAN

Trip signal from step4 phase A

TRST4_B

BOOLEAN

Trip signal from step4 phase B

TRST4_C

BOOLEAN

Trip signal from step4 phase C

PICKUP

BOOLEAN

Common pickup signal

PU_ST1

BOOLEAN

Common pickup signal from step1

PU_ST2

BOOLEAN

Common pickup signal from step2

PU_ST3

BOOLEAN

Common pickup signal from step3

PU_ST4

BOOLEAN

Common pickup signal from step4

PU_A

BOOLEAN

Pickup signal from phase A

PU_B

BOOLEAN

Pickup signal from phase B

PU_C

BOOLEAN

Pickup signal from phase C

PU_ST1_A

BOOLEAN

Pickup signal from step1 phase A

PU_ST1_B

BOOLEAN

Pickup signal from step1 phase B

PU_ST1_C

BOOLEAN

Pickup signal from step1 phase C

PU_ST2_A

BOOLEAN

Pickup signal from step2 phase A

PU_ST2_B

BOOLEAN

Pickup signal from step2 phase B

PU_ST2_C

BOOLEAN

Pickup signal from step2 phase C

PU_ST3_A

BOOLEAN

Pickup signal from step3 phase A

PU_ST3_B

BOOLEAN

Pickup signal from step3 phase B

PU_ST3_C

BOOLEAN

Pickup signal from step3 phase C

PU_ST4_A

BOOLEAN

Pickup signal from step4 phase A

PU_ST4_B

BOOLEAN

Pickup signal from step4 phase B

PU_ST4_C

BOOLEAN

Pickup signal from step4 phase C

PU2NDHARM

BOOLEAN

Second harmonic detected

DIR_A

INTEGER

Direction for phase A

DIR_B

INTEGER

Direction for phase B

DIR_C

INTEGER

Direction for phase C

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

445

Section 8
Current protection
8.2.5
Table 191:
Name

1MRK 502 066-UUS A

Settings
OC4PTOC (51_67) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

AngleRCA

40 - 65

Deg

55

Relay characteristic angle (RCA)

AngleROA

40 - 89

Deg

80

Relay operation angle (ROA)

NumPhSel

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for phase selection


(1 of 3, 2 of 3, 3 of 3)

DirModeSel1

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 1 (Disabled, Nondir,


Forward, Reverse)

Characterist1

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for step 1

Pickup1

5 - 2500

%IB

1000

Operating phase current level for step 1 in % of


IBase

t1

0.000 - 60.000

0.001

0.000

Def time delay or add time delay for inverse


char of step 1

TD1

0.05 - 999.00

0.01

0.05

Time dial multiplier for the inverse time delay


for step 1

IMin1

1 - 10000

%IB

100

Minimum operate current for step1 in % of


IBase

t1Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves for


step 1

MultPU1

1.0 - 10.0

0.1

2.0

Multiplier for current operate level for step 1

DirModeSel2

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 2 (Disabled, Nondir,


Forward, Reverse)

Table continues on next page

446

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Characterist2

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for step 2

Pickup2

5 - 2500

%IB

500

Operating phase current level for step 2 in % of


IBase

t2

0.000 - 60.000

0.001

0.400

Def time delay or add time delay for inverse


char of step 2

TD2

0.05 - 999.00

0.01

0.05

Time multiplier for the inverse time delay for


step 2

IMin2

1 - 10000

%IB

50

Minimum operate current for step2 in % of


IBase

t2Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves for


step 2

MultPU2

1.0 - 10.0

0.1

2.0

Multiplier for current operate level for step 2

DirModeSel3

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 3 (Disabled, Nondir,


Forward, Reverse)

Characterist3

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for step 3

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

447

Section 8
Current protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

Pickup3

5 - 2500

%IB

250

Operating phase current level for step 3 in % of


IBase

t3

0.000 - 60.000

0.001

0.800

Def time delay or add time delay for inverse


char of step 3

TD3

0.05 - 999.00

0.01

0.05

Time multiplier for the inverse time delay for


step 3

IMin3

1 - 10000

%IB

33

Minimum operate current for step3 in % of


IBase

t3Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves for


step 3

MultPU3

1.0 - 10.0

0.1

2.0

Multiplier for current operate level for step 3

DirModeSel4

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 4 (Disabled, Nondir,


Forward, Reverse)

Characterist4

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for step 4

Pickup4

5 - 2500

%IB

175

Operating phase current level for step 4 in % of


IBase

t4

0.000 - 60.000

0.001

2.000

Def time delay or add time delay for inverse


char of step 4

TD4

0.05 - 999.00

0.01

0.05

Time dial multiplier for the inverse time delay


for step 4

IMin4

1 - 10000

%IB

17

Minimum operate current for step4 in % of


IBase

t4Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves for


step 4

MultPU4

1.0 - 10.0

0.1

2.0

Multiplier for current operate level for step 4

448

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 192:
Name

OC4PTOC (51_67) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

PUMinOpPhSel

1 - 100

%IB

Minimum current for phase selection in % of


IBase

2ndHarmStab

5 - 100

%IB

20

Operate level of 2nd harmonic curr in % of


fundamental curr

ResetTypeCrv1

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for step 1

tReset1

0.000 - 60.000

0.001

0.020

Constant reset time for step 1

tPCrv1

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

tACrv1

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 1

tBCrv1

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 1

tCCrv1

0.1 - 10.0

0.1

1.0

Parameter C for customer programmable


curve for step 1

tPRCrv1

0.005 - 3.000

0.001

0.500

Parameter PR for customer programmable


curve for step 1

tTRCrv1

0.005 - 100.000

0.001

13.500

Parameter TR for customer programmable


curve for step 1

tCRCrv1

0.1 - 10.0

0.1

1.0

Parameter CR for customer programmable


curve for step 1

HarmBlock1

Disabled
Enabled

Disabled

Enable block of step 1 for harmonic restraint

ResetTypeCrv2

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for step 2

tReset2

0.000 - 60.000

0.001

0.020

Constant reset time for step 2

tPCrv2

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

tACrv2

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 2

tBCrv2

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 2

tCCrv2

0.1 - 10.0

0.1

1.0

Parameter C for customer programmable


curve for step 2

tPRCrv2

0.005 - 3.000

0.001

0.500

Parameter PR for customer programmable


curve for step 2

tTRCrv2

0.005 - 100.000

0.001

13.500

Parameter TR for customer programmable


curve for step 2

tCRCrv2

0.1 - 10.0

0.1

1.0

Parameter CR for customer programmable


curve for step 2

HarmBlock2

Disabled
Enabled

Disabled

Enable block of step 2 for harmonic restraint

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

449

Section 8
Current protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

ResetTypeCrv3

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for step 3

tReset3

0.000 - 60.000

0.001

0.020

Constant reset time for step 3

tPCrv3

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 3

tACrv3

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 3

tBCrv3

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 3

tCCrv3

0.1 - 10.0

0.1

1.0

Parameter C for customer programmable


curve for step 3

tPRCrv3

0.005 - 3.000

0.001

0.500

Parameter PR for customer programmable


curve for step 3

tTRCrv3

0.005 - 100.000

0.001

13.500

Parameter TR for customer programmable


curve for step 3

tCRCrv3

0.1 - 10.0

0.1

1.0

Parameter CR for customer programmable


curve for step 3

HarmBlock3

Disabled
Enabled

Disabled

Enable block of step 3 for harmonic restraint

ResetTypeCrv4

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for step 4

tReset4

0.000 - 60.000

0.001

0.020

Constant reset time for step 4

tPCrv4

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 4

tACrv4

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 4

tBCrv4

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 4

tCCrv4

0.1 - 10.0

0.1

1.0

Parameter C for customer programmable


curve for step 4

tPRCrv4

0.005 - 3.000

0.001

0.500

Parameter PR for customer programmable


curve for step 4

tTRCrv4

0.005 - 100.000

0.001

13.500

Parameter TR for customer programmable


curve for step 4

tCRCrv4

0.1 - 10.0

0.1

1.0

Parameter CR for customer programmable


curve for step 4

HarmBlock4

Disabled
Enabled

Disabled

Enable block of step 4 from harmonic restrain

450

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 193:
Name

OC4PTOC (51_67) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

MeasType

DFT
RMS

DFT

Selection between DFT and RMS


measurement

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

Table 194:
Name

OC4PTOC (51_67) Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

PU1_MinEd2Set

5 - 2500

%IB

Minimum settable operating phase current


level for step 1 in % of IBase, for 61850 Ed.2
settings

PU1_MaxEd2Set

5 - 2500

%IB

2500

Maximum settable operating phase current


level for step 1 in % of IBase, for 61850 Ed.2
settings

PU2_MinEd2Set

5 - 2500

%IB

Minimum settable operating phase current


level for step 2 in % of IBase, for 61850 Ed.2
settings

PU2_MaxEd2Set

5 - 2500

%IB

2500

Maximum settable operating phase current


level for step 2 in % of IBase, for 61850 Ed.2
settings

PU3_MinEd2Set

5 - 2500

%IB

Minimum settable operating phase current


level for step 3 in % of IBase, for 61850 Ed.2
settings

PU3_MaxEd2Set

5 - 2500

%IB

2500

Maximum settable operating phase current


level for step 3 in % of IBase, for 61850 Ed.2
settings

PU4_MinEd2Set

5 - 2500

%IB

Minimum settable operating phase current


level for step 4 in % of IBase, for 61850 Ed.2
settings

PU4_MaxEd2Set

5 - 2500

%IB

2500

Maximum settable operating phase current


level for step 4 in % of IBase, for 61850 Ed.2
settings

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

451

Section 8
Current protection
8.2.6

1MRK 502 066-UUS A

Monitored data
Table 195:
Name

8.2.7

OC4PTOC (51_67) Monitored data


Type

Values (Range)

Unit

Description

DIR_A

INTEGER

1=Forward
2=Reverse
0=No direction

Direction for phase A

DIR_B

INTEGER

1=Forward
2=Reverse
0=No direction

Direction for phase B

DIR_C

INTEGER

1=Forward
2=Reverse
0=No direction

Direction for phase C

IA

REAL

Current in phase A

IB

REAL

Current in phase B

IC

REAL

Current in phase C

Operation principle
The Four step phase overcurrent protection OC4PTOC (51_67) is divided into four
different sub-functions, one for each step. For each step x , where x is step 1, 2, 3 and 4,
an operation mode is set by DirModeSelx: Disable/Non-directional/Forward/Reverse.
The protection design can be divided into four parts:

The direction element


The harmonic restraint blocking function
The four step over current function
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModeSelx shall be left to default value, Non-directional.

452

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

faultState

Direction
Element

I3P

dirPhAFlt
dirPhBFlt
dirPhCFlt

4 step over current


element
One element for each
step

faultState

PICKUP

V3P

TRIP

Harmonic
Restraint
Element

harmRestrBlock

enableDir
Mode Selection

enableStep1-4
DirectionalMode1-4

ANSI05000740-2-en.vsd
ANSI05000740 V2 EN

Figure 206:

Functional overview of OC4PTOC (51/67)

A common setting for all steps, NumPhSel, is used to specify the number of phase currents
to be high to enable operation. The settings can be chosen: 1 out of 3, 2 out of 3 or 3 out
of 3.
The sampled analog phase currents are processed in a pre-processing function block.
Using a parameter setting MeasType within the general settings for the four step phase
overcurrent protection 1 and 3-phase output function OC4PTOC (51/67), it is possible to
select the type of the measurement used for all overcurrent stages. It is possible to select
either discrete Fourier filter (DFT) or true RMS filter (RMS).
If DFT option is selected then only the RMS value of the fundamental frequency
components of each phase current is derived. Influence of DC current component and
higher harmonic current components are almost completely suppressed. If RMS option is
selected then the true RMS values is used. The true RMS value in addition to the
fundamental frequency component includes the contribution from the current DC
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

453

Section 8
Current protection

1MRK 502 066-UUS A

component as well as from higher current harmonic. The selected current values are fed
to OC4PTOC (51/67).
In a comparator, the DFT or RMS values are compared to the set operation current value
of the function (Pickup1, Pickup2, Pickup3, Pickup4) for each phase current. If a phase
current is larger than the set operation current, outputs PICKUP, PU_STx, PU_A, PU_B
and PU_C are activated without delay. Output signals PU_A, PU_B and PU_C are
common for all steps. This means that the lowest set step will initiate the activation. The
PICKUP signal is common for all three phases and all steps. It shall be noted that the
selection of measured value (DFT or RMS) do not influence the operation of directional
part of OC4PTOC (51/67) .
Service value for individually measured phase currents are also available on the local HMI
for OC4PTOC (51/67) function, which simplifies testing, commissioning and in service
operational checking of the function.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in relation
to the fundamental current is used. The 2nd harmonic current is taken from the preprocessing of the phase currents and the relation is compared to a set restrain current level.
The function can be directional. The direction of the fault current is given as current angle
in relation to the voltage angle. The fault current and fault voltage for the directional
function is dependent of the fault type. To enable directional measurement at close in
faults, causing low measured voltage, the polarization voltage is a combination of the
apparent voltage (85%) and a memory voltage (15%). The following combinations are
used.
Phase-phase short circuit:

Vref _ AB = VA - VB

I dir _ AB = I A - I B
(Equation 97)

GUID-4F361BC7-6D91-47B5-8119-A27009C0AD6A V1 EN

Vref _ BC = VB - VC

I dir _ BC = I B - I C
(Equation 98)

ANSIEQUATION1450 V1 EN

Vref _ CA = VC - VA
ANSIEQUATION1451 V1 EN

I dir _ CA = IC - I A
(Equation 99)

Phase-ground short circuit:


Table continues on next page

454

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Vref _ A = VA

I dir _ A = I A
(Equation 100)

ANSIEQUATION1452 V1 EN

Vref _ B = VB

I dir _ B = I B
(Equation 101)

ANSIEQUATION1453 V1 EN

Vref _ C = VC

I dir _ C = I C

ANSIEQUATION1454 V1 EN

(Equation 102)

The polarizing voltage is available as long as the positive-sequence voltage exceeds 4%


of the set base voltage VBase. So the directional element can use it for all unsymmetrical
faults including close-in faults.
For close-in three-phase faults, the V1AM memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
After 100 ms, the following occurs:

If the current is still above the set value of the minimum operating current (between
10 and 30% of the set terminal rated current IBase), the condition seals in.

If the fault has caused tripping, the trip endures.


If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.

If the current decreases below the minimum operating value, the memory resets until
the positive sequence voltage exceeds 10% of its rated value.

The directional setting is given as a characteristic angle AngleRCA for the function and an
angle window ROADir.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

455

Section 8
Current protection

1MRK 502 066-UUS A

Reverse

Uref
RCA

ROA

ROA

Forward

Idir

en05000745.vsd
IEC05000745 V1 EN

456

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Reverse

Vref
RCA

ROA

ROA

Forward

Idir

en05000745_ansi.vsd
ANSI05000745 V1 EN

Figure 207:

Directional characteristic of the phase overcurrent protection

The default value of AngleRCA is 65. The parameters AngleROA gives the angle sector
from AngleRCA for directional borders.
A minimum current for directional phase pickup current signal can be set.
PUMinOpPhSel is the pickup level for directional evaluation of IA, IB and IC. The
directional signals release the overcurrent measurement in respective phases if their
current amplitudes are higher than the pickup level (PUMinOpPhSel) and the direction of
the current is according to the set direction of the step.
If no blockings are given, the pickup signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or inverse time
characteristic. A wide range of standardized inverse time characteristics is available.It is
also possible to create a tailor made time characteristic.
The possibilities for inverse time characteristics are described in section "Inverse
characteristics".
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

457

Section 8
Current protection

1MRK 502 066-UUS A

All four steps in OC4PTOC (51/67) can be blocked from the binary input BLOCK. The
binary input BLKx (x=1, 2, 3 or 4) blocks the operation of respective step.

|IOP|
Pickupx

Characteristx=DefTime
a

AND

OR

a>b

0-tx
0
PUx
STx

AND

0-txMin
0

AND

Inve rse
Characteristx=Inve rse
DirModeSelx=Disa bled

OR

STAGE x_DIR_Int

DirModeSelx=Non-dire ctional

DirModeSelx=Forward
DirModeSelx=Reverse

FORWARD_Int

REVERSE_Int

AND

OR

AND

ANSI12000008-3-en.vsd
ANSI12000008-3-en.vsd

ANSI12000008 V3 EN

Figure 208:

458

Simplified logic diagram for OC4PTOC

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

I3P

DFWDLx
DFWDLxx

V3P

Directional
Element

AngleRCA

DREVLx
DREVLxx

FORWARD_int

Directional
Release
Block

AngleROA

REVERSE_int

STLx

PUminOpPhSel

Greater
Comparator

x- means three phases 1,2 and 3


xx means phase to phase 12,23,31

ANSI15000266-1-en.vsdx

ANSI15000266 V1 EN

Figure 209:

OC4 directional release block diagram

Different types of reset time can be selected as described in section "Inverse


characteristics".
There is a possibility to activate a preset change (MultiPUx, x= 1, 2, 3 or 4) of the set
operation current via a binary input (enable multiplier). In some applications the operation
value needs to be changed, for example due to changed network switching state.
The function can be blocked from the binary input BLOCK. The pickup signals from the
function can be blocked from the binary input BLK.The trip signals from the function can
be blocked from the binary input BLKTR.
A harmonic restrain of the Four step overcurrent protection function OC4PTOC 51_67
can be chosen. If the ratio of the 2nd harmonic component in relation to the fundamental
frequency component in the residual current exceeds the preset level defined by parameter
2ndHarmStab setting, any of the four overcurrent stages can be selectively blocked by
parameter HarmRestrainx setting. When the 2nd harmonic restraint feature is active, the
OC4PTOC 51_67 function output signal ST2NDHRM will be set to logical value one.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

459

Section 8
Current protection

1MRK 502 066-UUS A

BLOCK
a
0.07*IBase

a>b

b
a

a>b

IOP

Extract second
harmonic current
component
Extract
fundamental
current component

AND
a

a>b

2ndH_BLOCK_Int

2ndHarmStab

IEC13000014-2-en.vsd
IEC13000014 V2 EN

Figure 210:

8.2.8

Second harmonic blocking

Technical data
Table 196:

OC4PTOC (51/67) technical data

Function

Setting range

Accuracy

Trip current, step 1 - 4

(5-2500)% of lBase

1.0% of In at I In
1.0% of I at I > In

Reset ratio

> 95% at (502500)% of


lBase

Minimum operate current, step 1 - 4

(1-10000)% of lBase

1.0% of In at I In
1.0% of I at I > In

Relay characteristic angle (RCA)

(40.065.0) degrees

2.0 degrees

Relay operating angle (ROA)

(40.089.0) degrees

2.0 degrees

Second harmonic blocking

(5100)% of fundamental

2.0% of In

Independent time delay at 0 to 2 x


Iset, step 1 - 4

(0.000-60.000) s

0.2 % or 35 ms whichever is greater

Minimum trip time for inverse


curves , step 1 - 4

(0.000-60.000) s

0.2 % or 35 ms whichever is
greater

Inverse time characteristics, see


table 977, table 978 and table 979

16 curve types

See table 977, table 978 and table


979

Trip time, pickup non-directional at


0 to 2 x Iset

Min. = 15 ms

Reset time, pickup non-directional


at 2 to 0 x Iset

Min. = 15 ms

Max. = 30 ms
-

Max. = 30 ms

Table continues on next page


460

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Function

Setting range

Accuracy

Operate time, start non-directional


at 0 to 10 x Iset

Min. = 5 ms
Max. = 20 ms

Reset time, start non-directional at


10 to 0 x Iset

Min. = 20 ms
Max. = 35 ms

Critical impulse time

10 ms typically at 0 to 2 x Iset

Impulse margin time

15 ms typically

8.3

Instantaneous residual overcurrent protection EFPIOC


(50N)

8.3.1

Identification
Function description

IEC 61850
identification

Instantaneous residual overcurrent


protection

IEC 60617
identification

ANSI/IEEE C37.2
device number
50N

EFPIOC

IN>>
IEF V1 EN

8.3.2

Functionality
The Instantaneous residual overcurrent protection EFPIOC (50N) has a low transient
overreach and short tripping times to allow the use for instantaneous ground-fault
protection, with the reach limited to less than the typical eighty percent of the line at
minimum source impedance. EFPIOC (50N) is configured to measure the residual current
from the three-phase current inputs and can be configured to measure the current from a
separate current input.

8.3.3

Function block
EFPIOC (50N)
I3P*
BLOCK
BLKAR
MULTPU

TRIP

ANSI06000269-2-en.vsd
ANSI06000269 V2 EN

Figure 211:

EFPIOC (50N) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

461

Section 8
Current protection
8.3.4

1MRK 502 066-UUS A

Signals
Table 197:

EFPIOC (50N) Input signals

Name

Type

Three phase currents

BLOCK

BOOLEAN

Block of function

BLKAR

BOOLEAN

Block from auto recloser

MULTPU

BOOLEAN

Enable current multiplier

EFPIOC (50N) Output signals

Name

Type

TRIP

Table 199:
Name

Description

GROUP
SIGNAL

Table 198:

8.3.5

Default

I3P

Description

BOOLEAN

Trip signal

Settings
EFPIOC (50N) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

Pickup

5 - 2500

%IB

200

Operate residual current level in % of IBase

Table 200:
Name
MultPU

Table 201:
Name
GlobalBaseSel

8.3.6

EFPIOC (50N) Group settings (advanced)


Values (Range)
0.5 - 5.0

Step

0.1

Default
1.0

Description
Multiplier for operate current level

EFPIOC (50N) Non group settings (basic)


Values (Range)
1 - 12

Unit

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 202:
Name
IN

462

Unit

EFPIOC (50N) Monitored data


Type
REAL

Values (Range)
-

Unit
A

Description
Residual current

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.3.7

Operation principle
The sampled analog residual currents are pre-processed in a discrete Fourier filter (DFT)
block. From the fundamental frequency components of the residual current, as well as
from the sample values the equivalent RMS value is derived. This current value is fed to
the Instantaneous residual overcurrent protection (EFPIOC,50N). In a comparator the
RMS value is compared to the set operation current value of the function (Pickup). If the
residual current is larger than the set operation current a signal from the comparator is set
to true. This signal will, without delay, activate the output signal TRIP.
There is also a possibility to activate a preset change of the set operation current via a
binary input (enable multiplier MULTPU). In some applications the operation value
needs to be changed, for example due to transformer inrush currents.
EFPIOC (50N) function can be blocked from the binary input BLOCK. The trip signals
from the function can be blocked from the binary input BLKAR, that can be activated
during single pole trip and autoreclosing sequences.

8.3.8

Technical data
Table 203:

EFPIOC (50N) technical data

Function

Range or value

Accuracy

Trip current

(5-2500)% of lBase

1.0% of In at I In
1.0% of In at I > In

Reset ratio

> 95% at (502500)% of lBase

Trip time at 0 to 2 x Iset

Min. = 15 ms
Max. = 25 ms

Reset time at 2 to 0 x Iset

Min. = 15 ms
Max. = 25 ms

Critical impulse time

10 ms typically at 0 to 2 x Iset

Trip time at 0 to 10 x Iset

Min. = 5 ms
Max. = 15 ms

Reset time at 10 to 0 x Iset

Min. = 25 ms
Max. = 35 ms

Critical impulse time

2 ms typically at 0 to 10 x Iset

Dynamic overreach

< 5% at t = 100 ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

463

Section 8
Current protection

1MRK 502 066-UUS A

8.4

Four step residual overcurrent protection, (Zero


sequence or negative sequence directionality)
EF4PTOC (51N/67N)

8.4.1

Identification
Function description
Four step residual overcurrent
protection

IEC 61850
identification

IEC 60617
identification

EF4PTOC

4(IN>)
4
4

ANSI/IEEE C37.2
device number
51N_67N

alt

TEF-REVA V2 EN

8.4.2

Functionality
The four step residual overcurrent protection EF4PTOC (51N/67N) has an inverse or
definite time delay independent for each step.
All IEC and ANSI time-delayed characteristics are available together with an optional
user defined characteristic.
EF4PTOC (51N/67N) can be set directional or non-directional independently for each of
the steps.
IDir, VPol and IPol can be independently selected to be either zero sequence or negative
sequence.
Second harmonic blocking can be set individually for each step.
EF4PTOC (51N/67N) can be used as main protection for phase-to-ground faults.
EF4PTOC (51N/67N) can also be used to provide a system back-up for example, in the
case of the primary protection being out of service due to communication or voltage
transformer circuit failure.
Directional operation can be combined together with corresponding communication logic
in permissive or blocking teleprotection scheme. Current reversal and weak-end infeed
functionality are available as well.
Residual current can be calculated by summing the three phase currents or taking the input
from neutral CT

464

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.4.3

Function block

EF4PTOC (51N_67N)
I3P*
TRIP
V3P*
TRST1
I3PPOL*
TRST2
I3PDIR*
TRST3
BLOCK
TRST4
BLKTR
TRSOTF
BLK1
PICK UP
BLK2
PUST1
BLK3
PUST2
BLK4
PUST3
MULTPU1
PUST4
MULTPU2
PUSOTF
MULTPU3
PUFW
MULTPU4
PUREV
52A
2NDHARMD
CLOSECMD
OPENCMD
ANSI06000424-4-en.vsd

ANSI06000424 V4 EN

Figure 212:

8.4.4

EF4PTOC (51N/67N) function block

Signals
Table 204:
Name

EF4PTOC (51N_67N) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group connection for operate current

V3P

GROUP
SIGNAL

Group connection for polarizing voltage

I3PPOL

GROUP
SIGNAL

Group connection for polarizing current

I3PDIR

GROUP
SIGNAL

Group connection for directional current

BLOCK

BOOLEAN

General block

BLKTR

BOOLEAN

Block of trip

BLK1

BOOLEAN

Block of step 1 (Pickup and trip)

BLK2

BOOLEAN

Block of step 2 (Pickup and trip)

BLK3

BOOLEAN

Block of step 3 (Pickup and trip)

BLK4

BOOLEAN

Block of step 4 (Pickup and trip)

MULTPU1

BOOLEAN

When activated, the pickup multiplier is in use for step1

MULTPU2

BOOLEAN

When activated, the pickup multiplier is in use for step2

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

465

Section 8
Current protection

1MRK 502 066-UUS A

Name

Type

When activated, the pickup multiplier is in use for step3

MULTPU4

BOOLEAN

When activated, the pickup multiplier is in use for step4

52a

BOOLEAN

Breaker position

CLOSECMD

BOOLEAN

Breaker close command

OPENCMD

BOOLEAN

Breaker open command

EF4PTOC (51N_67N) Output signals

Name

Table 206:
Name

Description

BOOLEAN

Table 205:

8.4.5

Default

MULTPU3

Type

Description

TRIP

BOOLEAN

General trip signal

TRST1

BOOLEAN

Trip signal from step 1

TRST2

BOOLEAN

Trip signal from step 2

TRST3

BOOLEAN

Trip signal from step 3

TRST4

BOOLEAN

Trip signal from step 4

TRSOTF

BOOLEAN

Trip signal from switch onto fault function

PICKUP

BOOLEAN

Common pickup signal

PUST1

BOOLEAN

Pickup signal step 1

PUST2

BOOLEAN

Pickup signal step 2

PUST3

BOOLEAN

Pickup signal step 3

PUST4

BOOLEAN

Pickup signal step 4

PUSOTF

BOOLEAN

Pickup signal from switch onto fault function

PUFW

BOOLEAN

Pick up foward direction

PUREV

BOOLEAN

Pick up reverse direction

2NDHARMD

BOOLEAN

2nd harmonic block signal

Settings
EF4PTOC (51N_67N) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

EnDir

Disable
Enable

Enable

Enabling the Directional calculation

AngleRCA

-180 - 180

Deg

65

Relay Characteristic Angle (RCA)

polMethod

Voltage
Current
Dual

Voltage

Type of polarization

Table continues on next page

466

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

VPolMin

1 - 100

%VB

Minimum voltage level for polarization in % of


VBase

IPolMin

2 - 100

%IB

Minimum current level for polarization in % of


IBase

RNPol

0.50 - 1000.00

Ohm

0.01

5.00

Real part of source impedance used for current


polarisation

XNPol

0.50 - 3000.00

Ohm

0.01

40.00

Imaginary part of source imp. used for current


polarisation

INDirPU

1 - 100

%IB

10

Residual current level in % of IBase for


Direction release

2ndHarmStab

5 - 100

20

Operate level of 2nd harmonic curr in % of


fundamental curr

BlkParTransf

Disabled
Enabled

Disabled

Enable blocking at energizing of parallel


transformers

Use_PUValue

ST1
ST2
ST3
ST4

ST4

Current pickup blocking at parallel transf


(step1, 2, 3 or 4)

SOTF

Disabled
SOTF
UnderTime
SOTF&UnderTime

Disabled

SOTF operation mode (Off/SOTF/Undertime/


SOTF&Undertime)

SOTFSel

Open
Closed
CloseCommand

Open

Select signal to activate SOTF: CB-Open/ Closed/ -Close cmd

StepForSOTF

Step 2
Step 3

Step 2

Select start from step 2 or 3 to start SOTF

HarmBlkSOTF

Disabled
Enabled

Disabled

Enable harmonic restrain function in SOTF

tSOTF

0.000 - 60.000

0.001

0.200

Time delay for SOTF

t4U

0.000 - 60.000

0.001

1.000

Switch-onto-fault active time

ActUndrTimeSel

CB position
CB command

CB position

Select signal to activate under time (CB Pos /


CB Command)

tUnderTime

0.000 - 60.000

0.001

0.300

Time delay for under time

DirModeSel1

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 1 (Off, Non-dir,


Forward, Reverse)

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

467

Section 8
Current protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

Characterist1

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay characteristic for step 1

Pickup1

1 - 2500

%IB

100

Residual current operate level for step 1 in % of


IBase

t1

0.000 - 60.000

0.001

0.000

Def time delay or add time delay for inverse


char of step 1

TD1

0.05 - 999.00

0.01

0.05

Time multiplier for the step 1 selected time


characteristic

IMin1

1.00 - 10000.00

%IB

1.00

100.00

Minimum operate residual current for step 1 in


% of IBase

t1Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse time


characteristic step 1

MultPU1

1.0 - 10.0

0.1

2.0

Multiplier for the residual current setting value


for step 1

HarmBlock1

Disabled
Enabled

Enabled

Enable block of step 1 for harmonic restraint

DirModeSel2

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 2 (Off, Non-dir,


Forward, Reverse)

Table continues on next page

468

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Characterist2

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay characteristic for step 2

Pickup2

1 - 2500

%IB

50

Residual current operate level for step 2 in % of


IBase

t2

0.000 - 60.000

0.001

0.400

Def time delay or add time delay for inverse


char of step 2

TD2

0.05 - 999.00

0.01

0.05

Time multiplier for the step 2 selected time


characteristic

IMin2

1.00 - 10000.00

%IB

1.00

50

Minimum operate residual current for step 2 in


% of IBase

t2Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse time


characteristic step 2

MultPU2

1.0 - 10.0

0.1

2.0

Multiplier for the residual current setting value


for step 2

HarmBlock2

Disabled
Enabled

Enabled

Enable block of step 2 for harmonic restraint

DirModeSel3

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 3 (Off, Non-dir,


Forward, Reverse)

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

469

Section 8
Current protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

Characterist3

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay characteristic for step 3

Pickup3

1 - 2500

%IB

33

Residual current operate level for step 3 in % of


IBase

t3

0.000 - 60.000

0.001

0.800

Def time delay or add time delay for inverse


char of step 3

TD3

0.05 - 999.00

0.01

0.05

Time multiplier for the step 3 selected time


characteristic

IMin3

1.00 - 10000.00

%IB

1.00

33

Minimum operate residual current for step 3 in


% of IBase

t3Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse time


characteristic step 3

MultPU3

1.0 - 10.0

0.1

2.0

Multiplier for the residual current setting value


for step 3

HarmBlock3

Disabled
Enabled

Enabled

Enable block of step 3 for harmonic restraint

DirModeSel4

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 4 (Off, Non-dir,


Forward, Reverse)

Table continues on next page

470

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Characterist4

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay characteristic for step 4

Pickup4

1 - 2500

%IB

17

Residual current operate level for step 4 in % of


IBase

t4

0.000 - 60.000

0.001

1.200

Def time delay or add time delay for inverse


char of step 4

TD4

0.05 - 999.00

0.01

0.05

Time multiplier for the step 4 selected time


characteristic

IMin4

1.00 - 10000.00

%IB

1.00

17

Minimum operate residual current for step 4 in


% of IBase

t4Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse time


characteristic step 4

MultPU4

1.0 - 10.0

0.1

2.0

Multiplier for the residual current setting value


for step 4

HarmBlock4

Disabled
Enabled

Enabled

Enable block of step 4 for harmonic restraint

Table 207:
Name

EF4PTOC (51N_67N) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ResetTypeCrv1

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step1 (Instantaneous /


IEC / ANSI)

tReset1

0.000 - 60.000

0.001

0.020

Reset time delay for step 1

tPCrv1

0.005 - 3.000

0.001

1.000

Param P for customized inverse trip time curve


for step 1

tACrv1

0.005 - 200.000

0.001

13.500

Param A for customized inverse trip time curve


for step 1

tBCrv1

0.00 - 20.00

0.01

0.00

Param B for customized inverse trip time curve


for step 1

tCCrv1

0.1 - 10.0

0.1

1.0

Param C for customized inverse trip time curve


for step 1

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

471

Section 8
Current protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

tPRCrv1

0.005 - 3.000

0.001

0.500

Param PR for customized inverse reset time


curve for step 1

tTRCrv1

0.005 - 100.000

0.001

13.500

Param TR for customized inverse reset time


curve for step 1

tCRCrv1

0.1 - 10.0

0.1

1.0

Param CR for customized inverse reset time


curve for step 1

ResetTypeCrv2

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step2 (Instantaneous /


IEC / ANSI)

tReset2

0.000 - 60.000

0.001

0.020

Reset time delay for step 2

tPCrv2

0.005 - 3.000

0.001

1.000

Param P for customized inverse trip time curve


for step 2

tACrv2

0.005 - 200.000

0.001

13.500

Param A for customized inverse trip time curve


for step 2

tBCrv2

0.00 - 20.00

0.01

0.00

Param B for customized inverse trip time curve


for step 2

tCCrv2

0.1 - 10.0

0.1

1.0

Param C for customized inverse trip time curve


for step 2

tPRCrv2

0.005 - 3.000

0.001

0.500

Param PR for customized inverse reset time


curve for step 2

tTRCrv2

0.005 - 100.000

0.001

13.500

Param TR for customized inverse reset time


curve for step 2

tCRCrv2

0.1 - 10.0

0.1

1.0

Param CR for customized inverse reset time


curve for step 2

ResetTypeCrv3

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step3 (Instantaneous /


IEC / ANSI)

tReset3

0.000 - 60.000

0.001

0.020

Reset time delay for step 3

tPCrv3

0.005 - 3.000

0.001

1.000

Param P for customized inverse trip time curve


for step 3

tACrv3

0.005 - 200.000

0.001

13.500

Param A for customized inverse trip time curve


for step 3

tBCrv3

0.00 - 20.00

0.01

0.00

Param B for customized inverse trip time curve


for step 3

tCCrv3

0.1 - 10.0

0.1

1.0

Param C for customized inverse trip time curve


for step 3

tPRCrv3

0.005 - 3.000

0.001

0.500

Param PR for customized inverse reset time


curve for step 3

tTRCrv3

0.005 - 100.000

0.001

13.500

Param TR for customized inverse reset time


curve for step 3

tCRCrv3

0.1 - 10.0

0.1

1.0

Param CR for customized inverse reset time


curve for step 3

ResetTypeCrv4

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step4 (Instantaneous /


IEC / ANSI)

Table continues on next page

472

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

tReset4

0.000 - 60.000

0.001

0.020

Reset time delay for step 4

tPCrv4

0.005 - 3.000

0.001

1.000

Param P for customized inverse trip time curve


for step 4

tACrv4

0.005 - 200.000

0.001

13.500

Param A for customized inverse trip time curve


for step 4

tBCrv4

0.00 - 20.00

0.01

0.00

Param B for customized inverse trip time curve


for step 4

tCCrv4

0.1 - 10.0

0.1

1.0

Param C for customized inverse trip time curve


for step 4

tPRCrv4

0.005 - 3.000

0.001

0.500

Param PR for customized inverse reset time


curve for step 4

tTRCrv4

0.005 - 100.000

0.001

13.500

Param TR for customized inverse reset time


curve for step 4

tCRCrv4

0.1 - 10.0

0.1

1.0

Param CR for customized inverse reset time


curve for step 4

Table 208:
Name

Step

Default

Description

EF4PTOC (51N_67N) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

SeqTypeIDir

Zero seq
Neg seq

Zero seq

Choice of measurand for directional current

SeqTypeIPol

Zero seq
Neg seq

Zero seq

Choice of measurand for polarizing current

SeqTypeVPol

Zero seq
Neg seq

Zero seq

Choice of measurand for polarizing voltage

Table 209:
Name

EF4PTOC (51N_67N) Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

PU1_MinEd2Set

1 - 2500

%IB

Minimum settable operate residual current


level for step 1 in % of IBase, for 61850 Ed.2
settings

PU1_MaxEd2Set

1 - 2500

%IB

2500

Maximum settable operate residual current


level for step 1 in % of IBase, for 61850 Ed.2
settings

PU2_MinEd2Set

1 - 2500

%IB

Minimum settable operate residual current


level for step 2 in % of IBase, for 61850 Ed.2
settings

PU2_MaxEd2Set

1 - 2500

%IB

2500

Maximum settable operate residual current


level for step 2 in % of IBase, for 61850 Ed.2
settings

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

473

Section 8
Current protection

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

PU3_MinEd2Set

1 - 2500

%IB

Minimum settable operate residual current


level for step 3 in % of IBase, for 61850 Ed.2
settings

PU3_MaxEd2Set

1 - 2500

%IB

2500

Maximum settable operate residual current


level for step 3 in % of IBase, for 61850 Ed.2
settings

PU4_MinEd2Set

1 - 2500

%IB

Minimum settable operate residual current


level for step 4 in % of IBase, for 61850 Ed.2
settings

PU4_MaxEd2Set

1 - 2500

%IB

2500

Maximum settable operate residual current


level for step 4 in % of IBase, for 61850 Ed.2
settings

8.4.6

Monitored data
Table 210:
Name

8.4.7

EF4PTOC (51N_67N) Monitored data


Type

Values (Range)

Unit

Description

IOp

REAL

Operating current level

VPol

REAL

kV

Polarizing voltage level

IPol

REAL

Polarizing current level

VPOLIANG

REAL

deg

Polarizing angle between


voltage and current

IPOLIANG

REAL

deg

Polarizing current angle

Operation principle
This function has the following three Analog Inputs on its function block in the
configuration tool:
1.
2.
3.
4.

I3P, input used for Operating Quantity. Supply the zero-sequence magnitude
measuring functionality.
V3P, input used for Voltage Polarizing Quantity. Supply either zero or negative
sequence voltage to the directional functionality
I3PPOL, input used for Current Polarizing Quantity. Provide polarizing current to
the directional functionality. This current is normally taken from the grounding of a
power transformer.
I3PDIR, input used for Directional detection. Supply either zero or negative
sequence current to the directional functionality.

These inputs are connected from the corresponding pre-processing function blocks in the
Configuration Tool within PCM600.

474

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.4.7.1

Operating quantity within the function


The function always uses Residual Current (3I0) for its operating quantity. The residual
current can be:
1.

directly measured (when a dedicated CT input of the IED is connected in PCM600 to


the fourth analog input of the pre-processing block connected to EF4PTOC (51N/
67N) function input I3P). This dedicated IED CT input can be for example, connected
to:

2.

parallel connection of current instrument transformers in all three phases


(Holm-Green connection).
one single core balance, current instrument transformer (cable CT).
one single current instrument transformer located between power system WYE
point and ground (that is, current transformer located in the neutral grounding
of a WYE connected transformer winding).
one single current instrument transformer located between two parts of a
protected object (that is, current transformer located between two WYE points
of double WYE shunt capacitor bank).

calculated from three-phase current input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC (51N/67N) function
Analog Input I3P is not connected to a dedicated CT input of the IED in PCM600).
In such case the pre-processing block will calculate 3I0 from the first three inputs into
the pre-processing block by using the following formula (will take I2 from SMAI
AI3P connected to I3PDIR input which was connected to I3P input also):

If zero sequence current is selected,


I op = 3 Io = IA + IB + IC
(Equation 103)

EQUATION2011-ANSI V1 EN

where:
IA, IB, IC

are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of the
fundamental frequency component of the residual current is derived. The phasor
magnitude is used within the EF4PTOC (51N/67N) protection to compare it with the set
operation current value of the four steps (Pickup1, Pickup2, Pickup3 or Pickup4). If the
residual current is larger than the set operation current and the step is used in nondirectional mode a signal from the comparator for this step is set to true. This signal will,
without delay, activate the output signal PUSTx (x=step 1-4) for this step and a common
PICKUP signal.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

475

Section 8
Current protection
8.4.7.2

1MRK 502 066-UUS A

Internal polarizing
A polarizing quantity is used within the protection in order to determine the direction to
the ground fault (Forward/Reverse).
The function can be set to use voltage polarizing, current polarizing or dual polarizing.

Voltage polarizing
When voltage polarizing is selected the protection will use the residual voltage -3V0 as
polarizing quantity V3P.
This voltage can be:
1.

2.

directly measured (when a dedicated VT input of the IED is connected in PCM600 to


the fourth analog input of the pre-processing block connected to EF4PTOC (51N/
67N) function input V3P). This dedicated IED VT input shall be then connected to
open delta winding of a three phase main VT.
calculated from three phase voltage input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC (51N/67N) analog
function input V3P is NOT connected to a dedicated VT input of the IED in
PCM600). In such case the pre-processing block will calculate -3V2 from the first
three inputs into the pre-processing block by using the following formula:

VPol=3V0=(VA +VB +VC)


EQUATION2012 V1 EN

(Equation 105)

where:
VA, VB, VC

are fundamental frequency phasors of three individual phase voltages.


In order to use this, all three phase-to-ground voltages must be connected to three IED VT
inputs.

The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor of the
fundamental frequency component of the residual voltage is derived.
This phasor is used together with the phasor of the operating directional current, in order
to determine the direction to the ground fault (Forward/Reverse). In order to enable
voltage polarizing the magnitude of polarizing voltage shall be bigger than a minimum
level defined by setting parameter VpolMin.

476

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

It shall be noted that residual voltage (-3V0) or negative sequence voltage (-3V2) is used
to determine the location of the ground fault. This insures the required inversion of the
polarizing voltage within the ground-fault function.

Current polarizing
When current polarizing is selected the function will use an external residual current (3I0)
as polarizing quantity IPol. This current can be:
1.

directly measured (when a dedicated CT input of the IED is connected in PCM600 to


the fourth analog input of the pre-processing block connected to EF4PTOC (51N/
67N) function input I3PPOL). This dedicated IED CT input is then typically
connected to one single current transformer located between power system WYE
point and ground (current transformer located in the WYE point of a WYE connected
transformer winding).

2.

For some special line protection applications this dedicated IED CT input can
be connected to parallel connection of current transformers in all three phases
(Holm-Green connection).

calculated from three phase current input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC (51N/67N) function
analog input I3PPOL is NOT connected to a dedicated CT input of the IED in
PCM600). In such case the pre-processing block will calculate 3I0 from the first three
inputs into the pre-processing block by using the following formula:

I Pol = 3 Io = IA + IB + IC
EQUATION2019-ANSI V1 EN

(Equation 107)

where:
IA, IB and IC are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete fourier filter. Thus the phasor of the
fundamental frequency component of the polarizing current is derived. This phasor is then
multiplied with pre-set equivalent zero-sequence source Impedance in order to calculate
equivalent polarizing voltage VIPol in accordance with the following formula:
VIPol = Zo S I Pol = ( RNPol + j XNPOL ) I Pol
EQUATION2013-ANSI V1 EN

(Equation 108)

which will be then used, together with the phasor of the operating current, in order to
determine the direction to the ground fault (Forward/Reverse).
In order to enable current polarizing the magnitude of polarizing current shall be bigger
than a minimum level defined by setting parameter IPolMin.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

477

Section 8
Current protection

1MRK 502 066-UUS A

Dual polarizing
When dual polarizing is selected the function will use the vectorial sum of the voltage
based and current based polarizing in accordance with the following formula:
VTotPol = VVPol + VIPol = -3V0 + Z 0 s IPol = -3V0 + ( RNPol + jXNPol ) IPol
(Equation 109)

ANSIEQUATION1878 V1 EN

Vpol and Ipol can be either zero sequence component or negative sequence component
depending upon the user selection.
Then the phasor of the total polarizing voltage VTotPol will be used, together with the
phasor of the operating current, to determine the direction of the ground fault (Forward/
Reverse).

8.4.7.3

External polarizing for ground-fault function


The individual steps within the protection can be set as non-directional. When this setting
is selected it is then possible via function binary input BLKx to provide external
directional control (that is, torque control) by for example using one of the following
functions if available in the IED:
1.
2.

8.4.7.4

Distance protection directional function.


Negative sequence polarized General current and voltage multi purpose protection
function.

Directional detection for ground fault function


Zero sequence components will be used for detecting directionality for ground fault
function. In some cases zero sequence quantities might detect directionality wrong.
Negative sequence quantities will be used in such scenario. The user can select either zero
sequence components or negative sequence components for detecting directionality with
the parameter SeqTypeIPol. I3PDIR input always connected to the same source as I3P
input.

8.4.7.5

Base quantities within the protection


The base quantities are entered as global settings for all functions in the IED. Base current
(IBase) shall be entered as rated phase current of the protected object in primary amperes.
Base voltage (VBase) shall be entered as rated phase-to-phase voltage of the protected
object in primary kV.

478

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.4.7.6

Internal ground-fault protection structure


The protection is internally divided into the following parts:
1.
2.
3.
4.

8.4.7.7

Four residual overcurrent steps.


Directional supervision element for residual overcurrent steps with integrated
directional comparison step for communication based ground-fault protection
schemes (permissive or blocking).
Second harmonic blocking element with additional feature for sealed-in blocking
during switching of parallel transformers.
Switch on to fault feature with integrated Under-Time logic for detection of breaker
problems during breaker opening or closing sequence.

Four residual overcurrent steps


Each overcurrent step uses operating quantity Iop (residual current) as measuring
quantity. Each of the four residual overcurrent steps has the following built-in facilities:

Directional mode can be set to Disabled/Non-directional/Forward/Reverse. By this


parameter setting the directional mode of the step is selected. It shall be noted that the
directional decision (Forward/Reverse) is not made within the residual overcurrent
step itself. The direction of the fault is determined in common directional
supervision element.
Residual current pickup value.
Type of operating characteristic (inverse or definite time). By this parameter setting
it is possible to select inverse or definite time delay for the ground-fault protection.
Most of the standard IEC and ANSI inverse characteristics are available. For the
complete list of available inverse curves please refer to section "Inverse
characteristics".
Type of reset characteristic (Instantaneous / IEC Reset / ANSI Reset). By this
parameter setting it is possible to select the reset characteristic of the step. For the
complete list of available reset curves please refer to section "".
Time delay related settings. By these parameter settings the properties like definite
time delay, minimum operating time for inverse curves, reset time delay and
parameters to define user programmable inverse curve are defined.
Supervision by second harmonic blocking feature (Enabled/Disabled). By this
parameter setting it is possible to prevent operation of the step if the second harmonic
content in the residual current exceeds the preset level.
Multiplier for scaling of the set residual current pickup value by external binary
signal. By this parameter setting it is possible to increase residual current pickup
value when function binary input MULTPUx has logical value 1.

Simplified logic diagram for one residual overcurrent step is shown in figure 213.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

479

Section 8
Current protection

1MRK 502 066-UUS A

BLKTR
EMULTX
IMinx

Characteristx=DefTime

a>b

tx

|IOP|

AND

TRSTx

OR

a>b

MultPUx

PUSTx

AND

T
F

Pickupx

AND

Inverse

tMin

BLKx
BLOCK

Characteristx=Inverse
2ndHarm_BLOCK_Int

OR

HarmRestrainx=Disabled
DirModex=Off

OR

STEPx_DIR_Int

DirModex=Non-directional
DirModex=Forward
DirModex=Reverse

FORWARD_Int

REVERSE_Int

AND

OR

AND

ANSI10000008-4-en.vsd
ANSI10000008 V3 EN

Figure 213:

Simplified logic diagram for residual overcurrent step x, where x = step 1, 2, 3 or 4

The protection can be completely blocked from the binary input BLOCK. Output signals
for respective step, and PUSTx and TRSTx, can be blocked from the binary input BLKx.
The trip signals from the function can be blocked from the binary input BLKTR.

8.4.7.8

Directional supervision element with integrated directional comparison


function
It shall be noted that at least one of the four residual overcurrent steps shall
be set as directional in order to enable execution of the directional
supervision element and the integrated directional comparison function.
The protection has integrated directional feature. As the operating quantity current lop is
always used. The polarizing method is determined by the parameter setting polMethod.
The polarizing quantity will be selected by the function in one of the following three ways:

480

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

1.
2.
3.

When polMethod = Voltage, VPol will be used as polarizing quantity.


When polMethod = Current, IPol will be used as polarizing quantity.
WhenpolMethod = Dual, VPol + IPol ZNPol will be used as polarizing quantity.

The operating and polarizing quantity are then used inside the directional element, as
shown in figure 214, in order to determine the direction of the ground fault.

Operating area

PUREV
0.6 * INDirPU

Characteristic for reverse


release of measuring steps
-RCA -85 deg

Characteristic
for PUREV

40% of
INDirPU

RCA +85 deg

RCA
65

VPol = -3V0

-RCA +85 deg

RCA -85 deg

Characteristic for forward


release of measuring steps

INDirPU

PUFW
I op = 3I0
Operating area
Characteristic
for PUFW

ANSI11000243-1-en.ai

ANSI11000243 V1 EN

Figure 214:

Operating characteristic for ground-fault directional element using the


zero sequence components

Two relevant setting parameters for directional supervision element are:

Directional element will be internally enabled to trip as soon as Iop is bigger than 40%
of IDirPU and directional condition is fulfilled in set direction.
Relay characteristic angle AngleRCA, which defines the position of forward and
reverse areas in the operating characteristic.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

481

Section 8
Current protection

1MRK 502 066-UUS A

Directional comparison step, built-in within directional supervision element, will set
EF4PTOC (51N/67N) function output binary signals:
1.
2.

PUFW=1 when operating quantity magnitude Iop x cos( - AngleRCA) is bigger than
setting parameter IDirPU and directional supervision element detects fault in
forward direction.
PUREV=1 when operating quantity magnitude Iop x cos( - AngleRCA) is bigger
than 60% of setting parameter IDirPU and directional supervision element detects
fault in reverse direction.

These signals shall be used for communication based ground-fault teleprotection


communication schemes (permissive or blocking).
Simplified logic diagram for directional supervision element with integrated directional
comparison step is shown in figure 215:

482

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

|IopDir|

a
a>b
b

0.6

PUREV

AND

REVERSE_Int

X
a
a>b

IDirPU

0.4

FORWARD_Int

PUFW

AND

FWD
polMethod=Voltage

OR

polMethod=Dual

VPolMin
VPol

polMethod=Current

OR
IPol
0.0
RNPol
XNPol

T
0.0 F

IPolMin
I3PDIR

AND

FORWARD_Int

AND

REVERSE_Int

Directional
Characteristic

AngleRCA

VTPol
RVS

T
F

Complex
Number

VIPol
0.0

T
F

STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int
STAGE4_DIR_Int

OR
AND

BLOCK

ANSI07000067-4-en.vsd

ANSI07000067 V4 EN

Figure 215:

8.4.7.9

Simplified logic diagram for directional supervision element with integrated directional comparison step

Second harmonic blocking element


A harmonic restrain of four step residual overcurrent protection function EF4PTOC can
be chosen for each step by a parameter setting HarmRestrainx. If the ratio of the 2nd
harmonic component in relation to the fundamental frequency component in the residual
current exceeds the preset level (defined by parameter 2ndHarmStab) then ST2NDHRM
function output signal is set to logical value one and harmonic restraining feature to the
function block will be applicable.
Blocking from 2nd harmonic element activates if all three criteria are satisfied:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

483

Section 8
Current protection

1MRK 502 066-UUS A

1.
2.
3.

Current fundamental frequency component > IMinOpHarmBlk


Current second harmonic component > IMinOpHarmBlk
Ratio of the 2nd harmoinc component in relation to the fundamental frequency
component in the residual current exceeds the preset level defined parameter
2ndHarmStab setting

If all the above three conditions are fulfilled then ST2NDHRM function output signal is
set to logical value one and harmonic restraining feature to the function block is
applicable.
In addition to the basic functionality explained above the 2nd harmonic blocking can be set
in such way to seal-in until residual current disappears. This feature might be required to
stabilize EF4PTOC (51N67N) during switching of parallel transformers in the station. In
case of parallel transformers there is a risk of sympathetic inrush current. If one of the
transformers is in operation, and the parallel transformer is switched in, the asymmetric
inrush current of the switched in transformer will cause partial saturation of the
transformer already in service. This is called transferred saturation. The 2nd harmonic of
the inrush currents of the two transformers is in phase opposition. The summation of the
two currents thus gives a small 2nd harmonic current. The residual fundamental current is
however significant. The inrush current of the transformer in service before the parallel
transformer energizing, is a little delayed compared to the first transformer. Therefore we
have high 2nd harmonic current component initially. After a short period this current is
however small and the normal 2nd harmonic blocking resets. If the BlkParTransf function
is activated the 2nd harmonic restrain signal is latched as long as the residual current
measured by the relay is larger than a selected step current level by using setting
UseStartValue.
This feature has been called Block for Parallel Transformers. This 2nd harmonic seal-in
feature is activated when all of the following three conditions are simultaneously fulfilled:
1.
2.
3.

Feature is enabled by entering setting parameter BlkParTransf = On.


Basic 2nd harmonic restraint feature has been active for at least 70ms.
Residual current magnitude is higher than the set pickup value for one of the four
residual overcurrent stages. By a parameter setting Use_PUValue it is possible to
select which one of the four pickup values that will be used (Pickup1 or Pickup2 or
Pickup3 or Pickup4).

Once Block for Parallel Transformers is activated the basic 2nd harmonic blocking signal
is sealed-in until the residual current magnitude falls below a value defined by parameter
setting Use_PUValue (see condition 3 above).
Simplified logic diagram for 2nd harmonic blocking feature is shown in figure 216.

484

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

BLOCK
a
0.07*IBase

IOP

a>b

Extract second
harmonic current
component
Extract
fundamental
current component

a>b

2NDHARMD

AND
a>b

2ndHarmStab

q-1

0-70ms
0

OR
AND

OR

2ndH_BLOCK_Int

BlkParTransf=On
|IOP|

a>b

Use_PUValue
Pickup1>
Pickup2>
Pickup3>
Pickup4>

ANSI13000015-1-en.vsd
ANSI13000015 V1 EN

Figure 216:

8.4.7.10

Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers feature

Switch on to fault feature


Integrated in the four step residual overcurrent protection are Switch on to fault logic
(SOTF) and Under-Time logic. The setting parameter SOTF is set to activate either SOTF
or Under-Time logic or both. When the circuit breaker is closing there is a risk to close it
onto a permanent fault, for example during an autoreclosing sequence. The SOTF logic
will enable fast fault clearance during such situations. The time during which SOTF and
Under-Time logics will be active after activation is defined by the setting parameter t4U.
The SOTF logic uses the pickup signal from step 2 or step 3 for its operation, selected by
setting parameter StepForSOTF. The SOTF logic can be activated either from change in
circuit breaker position or from circuit breaker close command pulse. The setting

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

485

Section 8
Current protection

1MRK 502 066-UUS A

parameter SOTFSel can be set for activation of CB position open change, CB position
closed change or CB close command. In case of a residual current pickup from step 2 or
3 (dependent on setting) the function will give a trip after a set delay tSOTF. This delay is
normally set to a short time (default 200 ms).
The Under-Time logic always uses the pickup signal from the step 4. The Under-Time
logic will normally be set to operate for a lower current level than the SOTF function. The
Under-Time logic can also be blocked by the 2nd harmonic restraint feature. This enables
high sensitivity even if power transformer inrush currents can occur at breaker closing.
This logic is typically used to detect asymmetry of CB poles immediately after switching
of the circuit breaker. The Under-Time logic is activated either from change in circuit
breaker position or from circuit breaker close and open command pulses. This selection is
done by setting parameter ActUnderTime. In case of a pickup from step 4 this logic will
give a trip after a set delay tUnderTime. This delay is normally set to a relatively short time
(default 300 ms). Practically the Under-Time logic acts as circuit breaker polediscrepancy protection, but it is only active immediately after breaker switching. The
Under-Time logic can only be used in solidly or low impedance grounded systems.
SOTF

Open

t4U
Closed

SOTFSel

Close command

tSOTF
AND

AND

PUST2
StepForSOTF

PUST3

OperationMode
BLOCK

Disabled
SOTF

UNDERTIME

TRIP

Undertime
tUnderTime

2nd Harmonic

EnHarmRestSOTF

AND

Undertime

OR

Open
OR

Close

t4U
Close command

ActUndrTimeSel

AND

PUST4

ANSI06000643-4-en.vsd
ANSI06000643 V4 EN

Figure 217:

486

Simplified logic diagram for SOTF and Under-Time features

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

EF4PTOC (51N/67N) Logic Diagram Simplified logic diagram for the complete
EF4PTOC (51N/67N) function is shown in figure 218:
signal to
communication
scheme

Directional Check
Element

INPol
3V0

Direction
Element

4
operatingCurrent
ground FaultDirection

3I0

step over current


element
One element for each
step

TRIP

angleValid

DirModeSel
enableDir

3I0

Harmonic
Restraint
Element

harmRestrBlock

or

pickup step 2 , 3 and 4


Blocking at parallel
transformers
SwitchOnToFault

DirModeSel
Mode
Selection

enableDir

TRIP

CB
pos
or cmd

enableStep1-4
DirectionalMode1-4

en 06000376_ ansi. vsd


ANSI06000376 V1 EN

Figure 218:

8.4.8

Functional overview of EF4PTOC (51N/67N)

Technical data
Table 211:

EF4PTOC (51N/67N) technical data

Function

Range or value

Accuracy

Trip current, step 1 - 4

(1-2500)% of lBase

1.0% of In at I In
1.0% of I at I > In

Reset ratio

> 95% at (10-2500)% of lBase

Relay characteristic angle


(RCA)

(-180 to 180) degrees

2.0 degrees

Trip current for directional release

(1100)% of lBase

For RCA 60 degrees:


2.5% of In at I In
2.5% of I at I > In

Independent time delay at 0 to 2 x


Iset, step 1 - 4

(0.000-60.000) s

0.2% or 35 ms whichever is
greater

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

487

Section 8
Current protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Minimum operate time for inverse


curves, step 1 - 4

(0.000 - 60.000) s

0.2% or 35 ms whichever is
greater

Inverse time characteristics, see


Table 977, Table 978 and Table
979

16 curve types

See Table 977, Table 978 and


Table 979

Second harmonic blocking

(5100)% of fundamental

2.0% of In

Minimum polarizing voltage

(1100)% of VBase

0.5% of Vn

Minimum polarizing current

(2-100)% of IBase

1.0% of In

Real part of source Z used for


current polarization

(0.50-1000.00) W/phase

Imaginary part of source Z used


for current polarization

(0.503000.00) W/phase

Trip time, pickup non-directional


at 0 to 2 x Iset

Min. = 15 ms
Max. = 30 ms

Reset time, pickup nondirectional at 2 to 0 x Iset

Min. = 15 ms
Max. = 30 ms

Trip time, pickup non-directional


at 0 to 10 x Iset

Min. = 5 ms
Max. = 20 ms

Reset time, pickup nondirectional at 10 to 0 x Iset

Min. = 20 ms
Max. = 35 ms

Critical impulse time

10 ms typically at 0 to 2 x Iset

Impulse margin time

15 ms typically

8.5

Four step directional negative phase sequence


overcurrent protection NS4PTOC (46I2)

8.5.1

Identification
Function description
Four step negative sequence
overcurrent protection

IEC 61850
identification

IEC 60617 identification ANSI/IEEE C37.2


device number

NS4PTOC

I2

46I2

4
4

alt

IEC10000053 V1 EN

488

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.5.2

Functionality
Four step negative sequence overcurrent protection (NS4PTOC, (4612) ) has an inverse or
definite time delay independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an optional user
defined characteristic.
The directional function is voltage polarized.
NS4PTOC (4612) can be set directional or non-directional independently for each of the
steps.
NS4PTOC (4612) can be used as main protection for unsymmetrical fault; phase-phase
short circuits, phase-phase-ground short circuits and single phase ground faults.
NS4PTOC (4612) can also be used to provide a system backup for example, in the case of
the primary protection being out of service due to communication or voltage transformer
circuit failure.
Directional operation can be combined together with corresponding communication logic
in permissive or blocking teleprotection scheme. The same logic as for directional zero
sequence current can be used. Current reversal and weak-end infeed functionality are
available.

8.5.3

Function block

NS4PTOC (46I2)
I3P*
I3PDIR*
V3P*
BLOCK
BLKTR
BLK1
BLK2
BLK3
BLK4
MULTPU1
MULTPU2
MULTPU3
MULTPU4

TRIP
TRST1
TRST2
TRST3
TRST4
PICK UP
PU_ST1
PU_ST2
PU_ST3
PU_ST4
PUFW
PUREV

ANSI10000054-1-en.vsd

ANSI10000054 V1 EN

Figure 219:

NS4PTOC (4612) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

489

Section 8
Current protection
8.5.4

1MRK 502 066-UUS A

Signals
Table 212:
Name

Type

Default

Description

I3P

GROUP
SIGNAL

Group connection for operate current

I3PDIR

GROUP
SIGNAL

Group connection for directional current

V3P

GROUP
SIGNAL

Group connection for polarizing voltage

BLOCK

BOOLEAN

General block

BLKTR

BOOLEAN

Block of trip

BLK1

BOOLEAN

Block of step 1 (Pickup and trip)

BLK2

BOOLEAN

Block of step 2 (Pickup and trip)

BLK3

BOOLEAN

Block of step 3 (Pickup and trip)

BLK4

BOOLEAN

Block of step 4 (Pickup and trip)

MULTPU1

BOOLEAN

When activated, the pickup multiplier is in use for step1

MULTPU2

BOOLEAN

When activated, the pickup multiplier is in use for step2

MULTPU3

BOOLEAN

When activated, the pickup multiplier is in use for step3

MULTPU4

BOOLEAN

When activated, the pickup multiplier is in use for step4

Table 213:
Name

490

NS4PTOC (46I2) Input signals

NS4PTOC (46I2) Output signals


Type

Description

TRIP

BOOLEAN

General trip signal

TRST1

BOOLEAN

Trip signal from step 1

TRST2

BOOLEAN

Trip signal from step 2

TRST3

BOOLEAN

Trip signal from step 3

TRST4

BOOLEAN

Trip signal from step 4

PICKUP

BOOLEAN

Common pickup signal

PU_ST1

BOOLEAN

Pickup signal step 1

PU_ST2

BOOLEAN

Pickup signal step 2

PU_ST3

BOOLEAN

Pickup signal step 3

PU_ST4

BOOLEAN

Pickup signal step 4

PUFW

BOOLEAN

Forward directional pickup signal

PUREV

BOOLEAN

Reverse directional pickup signal

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.5.5
Table 214:
Name

Settings
NS4PTOC (46I2) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

EnDir

Disable
Enable

Enable

Enabling the Directional calculation

AngleRCA

-180 - 180

Deg

65

Relay characteristic angle (RCA)

VPolMin

1 - 100

%VB

Minimum voltage level for polarization in % of


VBase

I2>Dir

1 - 100

%IB

10

Residual current level in % of IBase for


Direction release

DirModeSel1

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 1 (Disabled, Nondir,


Forward, Reverse)

Characterist1

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay characteristic for step 1

I2-1>

1 - 2500

%IB

100

Negative sequence current op level for step 1


in % of IBase

t1

0.000 - 60.000

0.001

0.000

Time delay of step 1 when definite time char. is


selected

TD1

0.05 - 999.00

0.01

0.05

Time multiplier for the step 1 selected time


characteristic

IMin1

1.00 - 10000.00

%IB

1.00

100.00

Minimum current for step 1

t1Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse time


characteristic step 1

MultPU1

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting value


for step 1

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

491

Section 8
Current protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

DirModeSel2

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 2 (Disabled, Nondir,


Forward, Reverse)

Characterist2

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay characteristic for step 2

I2-2>

1 - 2500

%IB

50

Negative sequence current op level for step 2


in % of IBase

t2

0.000 - 60.000

0.001

0.400

Time delay of step 2 when definite time char. is


selected

TD2

0.05 - 999.00

0.01

0.05

Time multiplier for the step 2 selected time


characteristic

IMin2

1.00 - 10000.00

%IB

1.00

50

Minimum current for step 2

t2Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse time


characteristic step 2

MultPU2

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting value


for step 2

DirModeSel3

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 3 (Disabled, Nondir,


Forward, Reverse)

Table continues on next page

492

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Characterist3

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay characteristic for step 3

I2-3>

1 - 2500

%IB

33

Negative sequence current op level for step 3


in % of IBase

t3

0.000 - 60.000

0.001

0.800

Time delay of step 3 when definite time char. is


selected

TD3

0.05 - 999.00

0.01

0.05

Time multiplier for the step 3 selected time


characteristic

IMin3

1.00 - 10000.00

%IB

1.00

33

Minimum current for step 3

t3Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse time


characteristic step 3

MultPU3

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting value


for step 3

DirModeSel4

Disabled
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 4 (Disabled, Nondir,


Forward, Reverse)

Characterist4

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay characteristic for step 4

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

493

Section 8
Current protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

I2-4>

1 - 2500

%IB

17

Negative sequence current op level for step 4


in % of IBase

t4

0.000 - 60.000

0.001

1.200

Time delay of step 4 when definite time char. is


selected

TD4

0.05 - 999.00

0.01

0.05

Time multiplier for the step 4 selected time


characteristic

IMin4

1.00 - 10000.00

%IB

1.00

17

Minimum current for step 4

t4Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse time


characteristic step 4

MultPU4

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting value


for step 4

Table 215:
Name

NS4PTOC (46I2) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ResetTypeCrv1

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step1 (Instantaneous /


IEC / ANSI)

tReset1

0.000 - 60.000

0.001

0.020

Reset time delay for step 1

tPCrv1

0.005 - 3.000

0.001

1.000

Param P for customized inverse trip time curve


for step 1

tACrv1

0.005 - 200.000

0.001

13.500

Param A for customized inverse trip time curve


for step 1

tBCrv1

0.00 - 20.00

0.01

0.00

Param B for customized inverse trip time curve


for step 1

tCCrv1

0.1 - 10.0

0.1

1.0

Param C for customized inverse trip time curve


for step 1

tPRCrv1

0.005 - 3.000

0.001

0.500

Param PR for customized inverse reset time


curve for step 1

tTRCrv1

0.005 - 100.000

0.001

13.500

Param TR for customized inverse reset time


curve for step

tCRCrv1

0.1 - 10.0

0.1

1.0

Param CR for customized inverse reset time


curve for step 1

ResetTypeCrv2

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step2 (Instantaneous /


IEC / ANSI)

tReset2

0.000 - 60.000

0.001

0.020

Reset time delay for step 2

tPCrv2

0.005 - 3.000

0.001

1.000

Param P for customized inverse trip time curve


for step 2

tACrv2

0.005 - 200.000

0.001

13.500

Param A for customized inverse trip time curve


for step 2

tBCrv2

0.00 - 20.00

0.01

0.00

Param B for customized inverse trip time curve


for step 2

Table continues on next page

494

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

tCCrv2

0.1 - 10.0

0.1

1.0

Param C for customized inverse trip time curve


for step 2

tPRCrv2

0.005 - 3.000

0.001

0.500

Param PR for customized inverse reset time


curve for step 2

tTRCrv2

0.005 - 100.000

0.001

13.500

Param TR for customized inverse reset time


curve for step 2

tCRCrv2

0.1 - 10.0

0.1

1.0

Param C for customized inverse reset time


curve for step 2

ResetTypeCrv3

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step3 (Instantaneous /


IEC / ANSI)

tReset3

0.000 - 60.000

0.001

0.020

Reset time delay for step 3

tPCrv3

0.005 - 3.000

0.001

1.000

Param P for customized inverse trip time curve


for step 3

tACrv3

0.005 - 200.000

0.001

13.500

Param A for customized inverse trip time curve


for step 3

tBCrv3

0.00 - 20.00

0.01

0.00

Param B for customized inverse trip time curve


for step 3

tCCrv3

0.1 - 10.0

0.1

1.0

Param C for customized inverse trip time curve


for step 3

tPRCrv3

0.005 - 3.000

0.001

0.500

Param PR for customized inverse reset time


curve for step 3

tTRCrv3

0.005 - 100.000

0.001

13.500

Param TR for customized inverse reset time


curve for step 3

tCRCrv3

0.1 - 10.0

0.1

1.0

Param CR for customized inverse reset time


curve for step 3

ResetTypeCrv4

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step4 (Instantaneous /


IEC / ANSI)

tReset4

0.000 - 60.000

0.001

0.020

Reset time delay for step 4

tPCrv4

0.005 - 3.000

0.001

1.000

Param P for customized inverse trip time curve


for step 4

tACrv4

0.005 - 200.000

0.001

13.500

Param A for customized inverse trip time curve


for step 4

tBCrv4

0.00 - 20.00

0.01

0.00

Param B for customized inverse trip time curve


for step 4

tCCrv4

0.1 - 10.0

0.1

1.0

Param C for customized inverse trip time curve


for step 4

tPRCrv4

0.005 - 3.000

0.001

0.500

Param PR for customized inverse reset time


curve for step 4

tTRCrv4

0.005 - 100.000

0.001

13.500

Param TR for customized inverse reset time


curve for step 4

tCRCrv4

0.1 - 10.0

0.1

1.0

Param CR for customized inverse reset time


curve for step 4

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

495

Section 8
Current protection

Table 216:
Name
GlobalBaseSel

8.5.6

1MRK 502 066-UUS A

NS4PTOC (46I2) Non group settings (basic)


Values (Range)

Unit

1 - 12

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 217:

NS4PTOC (46I2) Monitored data

Name

8.5.7

Step

Type

Values (Range)

Unit

Description

IOp

REAL

Operating current level

VPol

REAL

kV

Polarizing voltage level

VPOLIANG

REAL

deg

Polarizing angle between


voltage and current

Operation principle
Four step negative sequence overcurrent protection NS4PTOC (4612) function has the
following three Analog Inputs on its function block in the configuration tool:
1.
2.
3.

I3P, input used for Operating Quantity.


V3P, input used for Polarizing Quantity.
I3PDIR, input used for "Directional finding"

These inputs are connected from the corresponding pre-processing function blocks in the
Configuration Tool within PCM600.

8.5.7.1

Operating quantity within the function


Four step negative sequence overcurrent protection NS4PTOC (46I2) function always
uses negative sequence current (I2) for its operating quantity. The negative sequence
current is calculated from three-phase current input within the IED. The pre-processing
block calculates I2 from the first three inputs into the pre-processing block by using the
following formula:
I2 =

1
3

IA + a IB + a IC

ANSIEQUATION2266 V1 EN

496

)
(Equation 110)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

where:
IA, IB, IC

are fundamental frequency phasors of three individual phase currents.

is so called operator which gives a phase shift of 120 deg, that is, a = 1120 deg

a2

similarly gives a phase shift of 240 deg, that is, a2 = 1240 deg

The phasor magnitude is used within the NS4PTOC (4612) protection to compare it with
the set operation current value of the four steps (Pickup1, Pickup2, Pickup3 or Pickup4).
If the negative sequence current is larger than the set operation current and the step is used
in non-directional mode a signal from the comparator for this step is set to true. This
signal, without delay, activates the output signal PU_STx (x=1 - 4) for this step and a
common PICKUP signal.

8.5.7.2

Internal polarizing facility of the function


A polarizing quantity is used within the protection to determine the direction to the fault
(Forward/Reverse).
Four step negative sequence overcurrent protection NS4PTOC (4612) function uses the
voltage polarizing method.
NS4PTOC (4612) uses the negative sequence voltage -V2 as polarizing quantity V3P.
This voltage is calculated from three phase voltage input within the IED. The preprocessing block calculates -V2 from the first three inputs into the pre-processing block
by using the following formula:
V2 =

1
3

VA + a VB + a VC
2

ANSIEQUATION00024 V1 EN

where:
VA, VB, VC

are fundamental frequency phasors of three individual phase voltages.


To use this all three phase-to-ground voltages must be connected to three IED VT inputs.

This phasor is used together with the phasor of the operating current, in order to determine
the direction to the fault (Forward/Reverse).To enable voltage polarizing the magnitude
of polarizing voltage must be bigger than a minimum level defined by setting VpolMin.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

497

Section 8
Current protection

1MRK 502 066-UUS A

Note that V2 is used to determine the location of the fault. This ensures the required
inversion of the polarizing voltage within the function.

8.5.7.3

External polarizing for negative sequence function


The individual steps within the protection can be set as non-directional. When this setting
is selected it is then possible via function binary input BLKx (where x indicates the
relevant step within the protection) to provide external directional control (that is, torque
control) by for example using one of the following functions if available in the IED:

8.5.7.4

Distance protection directional function


Negative sequence polarized general current and voltage multi purpose protection
function

Internal negative sequence protection structure


The protection is internally divided into the following parts:

Four negative sequence overcurrent steps


Directional supervision element for negative sequence overcurrent steps with
integrated directional comparison step for communication based negative sequence
protection schemes (permissive or blocking)

Each part is described separately in the following sections.

8.5.7.5

Four negative sequence overcurrent stages


Each overcurrent stage uses Operating Quantity I2 (negative sequence current) as
measuring quantity. Every of the four overcurrent stage has the following built-in
facilities:

498

Operating mode (Disabled/ Non-directional /Forward / Reverse). By this parameter


setting the operating mode of the stage is selected. Note that the directional decision
(Forward/Reverse) is not made within the overcurrent stage itself. The direction of
the fault is determined in common Directional Supervision Element described in
the next paragraph.
Negative sequence current pickup value.
Type of operating characteristic (Inverse or Definite Time). By this parameter setting
it is possible to select Inverse or definite time delay for negative sequence overcurrent
function. Most of the standard IEC and ANSI inverse characteristics are available.
For the complete list of available inverse curves, refer to Chapter ""

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Type of reset characteristic (Instantaneous / IEC Reset /ANSI reset).By this


parameter setting it is possible to select the reset characteristic of the stage. For the
complete list of available reset curves, refer to Chapter ""
Time delay related settings. By these parameter settings the properties like definite
time delay, minimum operating time for inverse curves, reset time delay and
parameters to define user programmable inverse curve are defined.
Multiplier for scaling of the set negative sequence current pickup value by external
binary signal. By this parameter setting it is possible to increase negative sequence
current pickup value when function binary input MULTPUx has logical value 1.

Simplified logic diagram for one negative sequence overcurrent stage is shown in the
following figure:

ANSI09000684 V1 EN

Figure 220:

Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4

NS4PTOC (4612) can be completely blocked from the binary input BLOCK. The pickup
signals from NS4PTOC (4612) for each stage can be blocked from the binary input
BLKx. The trip signals from NS4PTOC (4612) can be blocked from the binary input
BLKTR.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

499

Section 8
Current protection
8.5.7.6

1MRK 502 066-UUS A

Directional supervision element with integrated directional comparison


function
At least one of the four negative sequence overcurrent steps must be set as
directional in order to enable execution of the directional supervision
element and the integrated directional comparison function.
The operating and polarizing quantity are then used inside the directional element, as
shown in figure 214, to determine the direction of the fault.

Reverse
Area

Vpol=-V2

AngleRCA

Forward
Area
Iop = I2

ANSI10000031-1-en.vsd
ANSI10000031 V1 EN

Figure 221:

Operating characteristic for fault directional element

Two relevant setting parameters for directional supervision element are:

500

Directional element is internally enable to trip as soon as Iop is bigger than 40% of
INDirPU and the directional condition is fulfilled in set direction.
Relay characteristic angle AngleRCA which defines the position of forward and
reverse areas in the operating characteristic.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Directional comparison step, built-in within directional supervision element, set


NS4PTOC (4612) output binary signals:
1.
2.

PUFW=1 when tip of I2 phasor (operating quantity magnitude) is in forward area, see
fig 214 (Operating quantity magnitude is bigger than setting INDirPU)
PUREV=1 when tip of I2 phasor (operating quantity magnitude) is in the reverse
area, see fig 214. (Operating quantity magnitude is bigger than 60% of setting
INDirPU)

These signals must be used for communication based fault teleprotection communication
schemes (permissive or blocking).
Simplified logic diagram for directional supervision element with integrated directional
comparison step is shown in figure 215:
|IopDir|

a
a>b
b

0.6

PUREV

AND

REVERSE_Int

X
a
a>b

IDirPU

0.4

FORWARD_Int

PUFW

AND

FWD
polMethod=Voltage

OR

polMethod=Dual

VPolMin
VPol

polMethod=Current

OR
IPol
0.0
RNPol
XNPol

T
0.0 F

IPolMin
I3PDIR

AND

FORWARD_Int

AND

REVERSE_Int

Directional
Characteristic

AngleRCA

VTPol
RVS

T
F

Complex
Number

VIPol
0.0

T
F

STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int
STAGE4_DIR_Int

OR
AND

BLOCK

ANSI07000067-4-en.vsd

ANSI07000067 V4 EN

Figure 222:

Simplified logic diagram for directional supervision element with integrated directional comparison step

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

501

Section 8
Current protection
8.5.8

1MRK 502 066-UUS A

Technical data
Table 218:

NS4PTOC (46I2) technical data

Function

502

Range or value

Accuracy

Trip value, step 1 - 4

(1-2500)% of lBase

1.0% of In at I In
1.0% of I at I > In

Reset ratio

> 95% at (10-2500)% of IBase

Independent time delay at 0 to 2


x Iset, step 1 - 4

(0.000-60.000) s

0.2% or 35 ms whichever is
greater

Minimum operate time for


inverse curves, step 1 - 4

(0.000 - 60.000) s

0.2% or 35 ms whichever is
greater

Inverse time characteristics,


see table 977, table 978 and
table 979

16 curve types

See table 977, table 978 and table


979

Minimum trip current, step 1 - 4

(1.00 - 10000.00)% of IBase

1.0% of In at I In
1.0% of I at I > In

Relay characteristic angle


(RCA)

(-180 to 180) degrees

2.0 degrees

Trip current for directional


release

(1100)% of IBase

For RCA 60 degrees:


2.5% of In at I In
2.5% of I at I > In

Minimum polarizing voltage

(1100)% of VBase

0.5% of Vn

Minimum polarizing current

(2-100)% of IBase

1.0% of In

Real part of negative sequence


source impedance used for
current polarization

(0.50-1000.00) W/phase

Imaginary part of negative


sequence source impedance
used for current polarization

(0.503000.00) W/phase

Trip time, pickup nondirectional at 0 to 2 x Iset

Min. = 15 ms
Max. = 30 ms

Reset time, pickup nondirectional at 2 to 0 x Iset

Min. = 15 ms
Max. = 30 ms

Trip time, pickup nondirectional at 0 to 10 x Iset

Min. = 5 ms
Max. = 20 ms

Reset time, pickup nondirectional at 10 to 0 x Iset

Min. = 20 ms
Max. = 35 ms

Critical impulse time

10 ms typically at 0 to 2 x Iset

Impulse margin time

15 ms typically

Transient overreach

<10% at = 100 ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.6

Sensitive directional residual overcurrent and power


protection SDEPSDE (67N)

8.6.1

Identification
Function description
Sensitive directional residual over
current and power protection

8.6.2

IEC 61850
identification
SDEPSDE

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
67N

Functionality
In networks with high impedance grounding, the phase-to-ground fault current is
significantly smaller than the short circuit currents. Another difficulty for ground fault
protection is that the magnitude of the phase-to-ground fault current is almost independent
of the fault location in the network.
Directional residual current can be used to detect and give selective trip of phase-toground faults in high impedance grounded networks. The protection uses the residual
current component 3I0 cos , where is the angle between the residual current and the
residual voltage (-3V0), compensated with a characteristic angle. Alternatively, the
function can be set to strict 3I0 level with a check of angle .
Directional residual power can also be used to detect and give selective trip of phase-toground faults in high impedance grounded networks. The protection uses the residual
power component 3I0 3V0 cos , where is the angle between the residual current and
the reference residual voltage, compensated with a characteristic angle.
A normal non-directional residual current function can also be used with definite or
inverse time delay.
A backup neutral point voltage function is also available for non-directional residual
overvoltage protection.
In an isolated network, that is, the network is only coupled to ground via the capacitances
between the phase conductors and ground, the residual current always has -90 phase shift
compared to the residual voltage (3V0). The characteristic angle is chosen to -90 in such
a network.
In resistance grounded networks or in Petersen coil grounded, with a parallel resistor, the
active residual current component (in phase with the residual voltage) should be used for
the ground fault detection. In such networks, the characteristic angle is chosen to 0.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

503

Section 8
Current protection

1MRK 502 066-UUS A

As the magnitude of the residual current is independent of the fault location, the selectivity
of the ground fault protection is achieved by time selectivity.
When should the sensitive directional residual overcurrent protection be used and when
should the sensitive directional residual power protection be used? Consider the
following:

Sensitive directional residual overcurrent protection gives possibility for better


sensitivity. The setting possibilities of this function are down to 0.25 % of IBase, 1 A
or 5 A. This sensitivity is in most cases sufficient in high impedance network
applications, if the measuring CT ratio is not too high.
Sensitive directional residual power protection gives possibility to use inverse time
characteristics. This is applicable in large high impedance grounded networks, with
large capacitive ground fault currents. In such networks, the active fault current
would be small and by using sensitive directional residual power protection, the
operating quantity is elevated. Therefore, better possibility to detect ground faults. In
addition, in low impedance grounded networks, the inverse time characteristic gives
better time-selectivity in case of high zero-resistive fault currents.

Phase
currents

IN

Phase
ground
voltages
VN
ANSI13000013-1-en.vsd

ANSI13000013 V1 EN

Figure 223:

Connection of SDEPSDE to analog preprocessing function block

Overcurrent functionality uses true 3I0, i.e. sum of GRPxA, GRPxB and GRPxC. For 3I0
to be calculated, connection is needed to all three phase inputs.
Directional and power functionality uses IN and VN. If a connection is made to GRPxN
this signal is used, else if connection is made to all inputs GRPxA, GRPxB and GRPxC the
internally calculated sum of these inputs (3I0 and 3V0) will be used.
504

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.6.3

Function block
SDEPSDE (67N)
I3P*
TRIP
V3P*
TRDIRIN
BLOCK
TRNDIN
BLKTR
TRVN
BLKTRDIR
PICKUP
BLKNDN
PUDIRIN
BLKVN
PUNDIN
PUVN
PUFW
PUREV
CND
VNREL
ANSI07000032-2-en.vsd
ANSI07000032 V2 EN

Figure 224:

8.6.4

SDEPSDE (67N) function block

Signals
Table 219:
Name

SDEPSDE (67N) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current

V3P

GROUP
SIGNAL

Group signal for voltage

BLOCK

BOOLEAN

Blocks all the outputs of the function

BLKTR

BOOLEAN

Blocks the trip outputs of the function

BLKTRDIR

BOOLEAN

Blocks the directional operate outputs of the function

BLKNDN

BOOLEAN

Blocks the Non directional current residual outputs

BLKVN

BOOLEAN

Blocks the Non directional voltage residual outputs

Table 220:
Name

SDEPSDE (67N) Output signals


Type

Description

TRIP

BOOLEAN

General trip of the function

TRDIRIN

BOOLEAN

Trip of the directional residual over current function

TRNDIN

BOOLEAN

Trip of non directional residual over current

TRVN

BOOLEAN

Trip of non directional residual over voltage

PICKUP

BOOLEAN

General pickup of the function

PUDIRIN

BOOLEAN

Pickup of the directional residual over current function

PUNDIN

BOOLEAN

Pickup of non directional residual over current

PUVN

BOOLEAN

Pickup of non directional residual over voltage

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

505

Section 8
Current protection

1MRK 502 066-UUS A

Name

8.6.5
Table 221:
Name

Type

Description

PUFW

BOOLEAN

Pickup of directional function for a fault in forward


direction

PUREV

BOOLEAN

Pickup of directional function for a fault in reverse


direction

CND

INTEGER

Direction of fault. A general signal common to all three


mode of residual over current protection

VNREL

BOOLEAN

Residual voltage release of operation of all directional


modes

Settings
SDEPSDE (67N) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OpModeSel

3I0Cosfi
3I03V0Cosfi
3I0 and fi

3I0Cosfi

Selection of operation mode for protection

DirMode

Forward
Reverse

Forward

Direction of operation forward or reverse

RCADir

-179 - 180

Deg

-90

Relay characteristic angle RCA, in deg

RCAComp

-10.0 - 10.0

Deg

0.1

0.0

Relay characteristic angle compensation

ROADir

0 - 90

Deg

90

Relay open angle ROA used as release in


phase mode, in deg

INCosPhiPU

0.25 - 200.00

%IB

0.01

1.00

Set level for 3I0cosFi, directional res over


current in % of IBase

SN_PU

0.25 - 200.00

%SB

0.01

10.00

Set level for 3I03U0cosFi, starting inv time


count in % of SBase

INDirPU

0.25 - 200.00

%IB

0.01

5.00

Set level for directional residual over current


prot in % of IBase

tDef

0.000 - 60.000

0.001

0.100

Definite time delay directional residual


overcurrent, in sec

SRef

0.03 - 200.00

%SB

0.01

10.00

Reference value of res power for inverse time


count in % of SBase

TDSN

0.00 - 2.00

0.01

0.10

Time multiplier setting for directional residual


power mode

OpINNonDir

Disabled
Enabled

Disabled

Operation of non-directional residual


overcurrent protection

INNonDirPU

1.00 - 400.00

%IB

0.01

10.00

Set level for non directional residual over


current in % of IBase

tINNonDir

0.000 - 60.000

0.001

1.000

Time delay for non-directional residual over


current, in sec

Table continues on next page

506

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

TimeChar

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

IEC Norm. inv.

Operation curve selection for IDMT operation

t_MinTripDelay

0.000 - 60.000

0.001

0.040

Minimum operate time for IEC IDMT curves, in


sec

TDIN

0.05 - 2.00

0.01

1.00

IDMT time mult for non-dir res over current


protection

OpVN

Disabled
Enabled

Disabled

Operation of non-directional residual


overvoltage protection

VN_PU

1.00 - 200.00

%VB

0.01

20.00

Set level for non-directional residual over


voltage in % of VBase

tVN

0.000 - 60.000

0.001

0.100

Time delay for non-directional residual over


voltage, in sec

INRelPU

0.25 - 200.00

%IB

0.01

1.00

Residual release current for all directional


modes in % of IBase

VNRelPU

1.00 - 300.00

%VB

0.01

3.00

Residual release voltage for all direction


modes in % of UBase

Step

Default

Table 222:
Name

SDEPSDE (67N) Group settings (advanced)


Values (Range)

Unit

tReset

0.000 - 60.000

0.001

0.040

Time delay used for reset of definite timers, in


sec

tPCrv

0.005 - 3.000

0.001

1.000

Setting P for customer programmable curve

tACrv

0.005 - 200.000

0.001

13.500

Setting A for customer programmable curve

tBCrv

0.00 - 20.00

0.01

0.00

Setting B for customer programmable curve

tCCrv

0.1 - 10.0

0.1

1.0

Setting C for customer programmable curve

ResetTypeCrv

Immediate
IEC Reset
ANSI reset

IEC Reset

Reset mode when current drops off.

tPRCrv

0.005 - 3.000

0.001

0.500

Setting PR for customer programmable curve

tTRCrv

0.005 - 100.000

0.001

13.500

Setting TR for customer programmable curve

tCRCrv

0.1 - 10.0

0.1

1.0

Setting CR for customer programmable curve

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description

507

Section 8
Current protection

Table 223:
Name
GlobalBaseSel

Table 224:
Name
RotResV

8.6.6

1MRK 502 066-UUS A

SDEPSDE (67N) Non group settings (basic)


Values (Range)
1 - 12

Unit

Step

Default
1

Description
Global base selection for function groups

SDEPSDE (67N) Non group settings (advanced)


Values (Range)
0 deg
180 deg

Unit

Step

Default
180 deg

Description
Setting for rotating polarizing quantity if
necessary

Monitored data
Table 225:

SDEPSDE (67N) Monitored data

Name

Type

Values (Range)

Unit

Description

INCOSPHI

REAL

Magnitude of residual current


along the polarizing quantity
3I0cos(Fi-RCA)

IN

REAL

Measured magnitude of the


residual current 3I0

VN

REAL

kV

Measured magnitude of the


residual voltage 3V0

SN

REAL

MVA

Measured magnitude of
residual power 3I03V0cos(FiRCA)

ANG FI-RCA

REAL

deg

Angle between 3V0 and 3I0


minus RCA (Fi-RCA)

8.6.7

Operation principle

8.6.7.1

Function inputs
The function is using phasors of the residual current and voltage. Group signals I3P and
V3P containing phasors of residual current and voltage are taken from pre-processor
blocks.
The sensitive directional ground fault protection has the following sub-functions
included:

Directional residual current protection measuring 3I0cos


is defined as the angle between the residual current 3I0 and the reference voltage (|
=ang(3I0)-ang(Vref)|). The reference voltage (Vref) is the polarizing quantity which is
used for directionality and is defined as Vref = -3V0 ejRCADir, that is -3V0 inversely
508

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

rotated by the set characteristic angle RCADir. RCADir is normally set equal to 0 in a high
impedance grounded network with a neutral point resistor as the active current component
is appearing out on the faulted feeder only. RCADir is set equal to -90 in an isolated
network as all currents are mainly capacitive. The function operates when 3I0cos gets
larger than the set value.
Vref

RCA = 0, ROA = 90

3I0

= ang(3I0) - ang(3Vref)
-3V0=Vref

3I0 cos

en06000648_ansi.vsd
ANSI06000648 V1 EN

Figure 225:

RCADir set to 0

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

509

Section 8
Current protection

1MRK 502 066-UUS A

Vref

RCA = -90, ROA = 90

3I0
3I0 cos
= ang(3I0) ang(Vref)
-3V0

en06000649_ansi.vsd
ANSI06000649 V1 EN

Figure 226:

RCADir set to -90

For trip, the operating quantity 3I0 cos , the residual current 3I0, and the residual voltage
3V0 must be larger than the set levels : INCosPhiPU, INRelPU and VNRelPU. Refer to the
simplified logical diagram in Figure 230.
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals PICKUP and PUDIRIN are activated.
If the output signals PICKUP and PUDIRIN remain active for the set delay tDef the binary
output signals TRIP and TRDIRIN get activated. The trip from this sub-function has
definite time delay.
ROADir is Relay Operating Angle. ROADir is identifying a window around the reference
direction in order to detect directionality. Figure 227 shows the restrictions made by the
ROADir.

510

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

RCADir 0

3I0

Trip area

3V0 Vref

3I0 cos
ROADir

ANSI06000650-3-en.vsd

ANSI06000650 V3 EN

Figure 227:

Characteristic with ROADir restriction

The function indicates forward/reverse direction to the fault. Reverse direction is defined
as 3I0cos ( + 180) the set value.
It is also possible to tilt the characteristic to compensate for current transformer angle error
with a setting RCAComp as shown in the Figure 228:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

511

Section 8
Current protection

1MRK 502 066-UUS A

RCADir = 0

Trip area

-3V0 =Vref

Instrument
transformer
angle error

RCAcomp

Characteristic after
angle compensation

3I0 (prim)

3I0 (to prot)

ANSI06000651-2-en.vsd

ANSI06000651 V2 EN

Figure 228:

Explanation of RCAComp

Directional residual power protection measuring 3I0 3V0 cos


is defined as the angle between the residual current 3I0 and the reference voltage (Vref =
-3V0 e-jRCA) compensated with the set characteristic angle RCADir (|=ang(3I0)
ang(Vref)|). The function operates when 3I0 3V0 cos gets larger than the set value
SN>. Refer to the simplified logical diagram in Figure 230.
For trip, the residual power 3I0 3V0 cos , the residual current 3I0 and the release
voltage 3V0, shall be larger than the set levels (SN_PU, INRelPU and VNRelPU).
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals PICKUP and PUDIRIN are activated.
If the output signals PICKUP and PUDIRIN remain active for the set delay tDef or after

512

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

the inverse time delay (setting TDSN) the binary output signals TRIP and TRDIRIN get
activated.
The function shall indicate forward/reverse direction to the fault. Reverse direction is
defined as 3I0 3V0cos ( + 180) the set value.
This variant has the possibility of choice between definite time delay and inverse time
delay.
The inverse time delay is defined as:
tinv =

TDSN (3I 0 3V0 cos (reference))


3I 0 3V0 cos (measured )
(Equation 111)

EQUATION2032-ANSI V2 EN

Directional residual current protection measuring 3I0 and


The function will operate if the residual current is larger than the set value and the angle |
= ang(3I0)-ang(Vref)| is within the sector RCADir ROADir
RCA = 0
ROA = 80

Operate area
3I0
Vref=-3V0

ANSI06000652-2-en.vsd
ANSI06000652 V2 EN

Figure 229:

Example of characteristic

For trip, Residual current 3I0 shall be larger than both INRelPU and INDirPU, and residual
voltage 3V0 shall be larger than the VNRelPU. In addition, the angle shall be in the set
area defined by ROADir and RCADir. Refer to the simplified logical diagram in Figure
230.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

513

Section 8
Current protection

1MRK 502 066-UUS A

Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals PICKUP and PUDIRIN are activated.
If the output signals PICKUP and PUDIRIN remain active for the set delay tDef the binary
output signals TRIP and TRDIRIN get activated.
The function indicates forward/reverse direction to the fault. Reverse direction is defined
as is within the angle sector: RCADir + 180 ROADir
This variant has definite time delay.

Directional functions
For all the directional functions there are directional pickup signals PUFW: fault in the
forward direction, and PUREV: fault in the reverse direction. Even if the directional
function is set to operate for faults in the forward direction, a fault in the reverse direction
will give the pickup signal PUREV. Also if the directional function is set to operate for
faults in the reverse direction, a fault in the forward direction will give the pickup signal
PUFW.

Non-directional ground fault current protection


This function will measure the residual current without checking the phase angle. The
function will be used to detect cross-country faults. This function can serve as alternative
or backup to distance protection with phase preference logic. To assure selectivity the
distance protection can block the non-directional ground fault current function via the
input BLKNDN.
The non-directional function is using the calculated residual current, derived as sum of the
phase currents. This will give a better ability to detect cross-country faults with high
residual current, also when dedicated core balance CT for the sensitive ground fault
protection will saturate.
This variant has the possibility of choice between definite time delay and inverse time
delay (TimeChar parameter). The inverse time delay shall be according to IEC 60255-3.
For trip, the residual current 3I0 shall be larger than the set level (INNonDirPU).
Trip from this function can be blocked from the binary input BLKNDN.
When the function picks up, binary output signal PUNDIN is activated. If the output signal
PUNDIN remains active for the set delay tINNonDir or after the inverse time delay the
binary output signals TRIP and TRNDIN get activated.

Residual overvoltage release and protection


All the directional functions shall be released when the residual voltage gets higher than
a set level VNRelPU.

514

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

In addition, there is also a separate non-directional residual over voltage protection, with
its own definite time delay tVN and set level VN_PU.
For trip, the residual voltage 3V0 shall be larger than the set level (VN_PU).
Trip from this function can be blocked from the binary input BLKVN.
When the function picks up, binary output signal PUVN is activated. If the output signal
PUVN is active for the set delay tVNNonDir, the binary output signals TRIP and TRUN
get activated. A simplified logical diagram of the total function is shown in Figure 230.
PUNDIN

INNonDirPU
UN_PU

0-t
0

TRNDIN

0-t
0

TRVN

PUVN

OpMODE=INcosPhi

Pickup_N

AND

INCosPhiPU
OpMODE=INVNCosPhi

AND

OR

PUDIRIN

AND

INVNCosPhiPU

SN

Phi in RCA +- ROA

AND

TRDIRIN

TimeChar = InvTime

AND

OpMODE=IN and Phi

TimeChar = DefTime

DirMode = Forw

AND

AND

OR
PUFW

Forw
DirMode = Rev

AND

PUREV

Rev

en06000653_ansi.vsd
ANSI06000653 V1 EN

Figure 230:

Simplified logical diagram of the sensitive ground fault current protection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

515

Section 8
Current protection
8.6.8

1MRK 502 066-UUS A

Technical data
Table 226:

SDEPSDE (67N) technical data

Function

516

Range or value

Accuracy

Trip level for 3I0cosj


directional residual
overcurrent

(0.25-200.00)% of lBase

1.0% of In at I In
1.0% of I at I > In

Trip level for 3I03V0cosj


directional residual power

(0.25-200.00)% of SBase

1.0% of Sn at S Sn
1.0% of S at S > Sn

Trip level for 3I0 and j residual


overcurrent

(0.25-200.00)% of lBase

1.0% of In at In
1.0% of I at I > In

Trip level for non-directional


overcurrent

(1.00-400.00)% of lBase

1.0% of In at I In
1.0% of I at I > In

Trip level for non-directional


residual overvoltage

(1.00-200.00)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Residual release current for all


directional modes

(0.25-200.00)% of lBase

1.0% of In at I In
1.0% of I at I > In

Residual release voltage for


all directional modes

(1.00-300.00)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Trip time for non-directional


residual overcurrent at 0 to 2 x
Iset

Min. = 40 ms

Reset time for non-directional


residual overcurrent at 2 to 0 x
Iset

Min. = 40 ms

Trip time for directional


residual overcurrent at 0 to 2 x
Iset

Min. = 110 ms

Reset time for directional


residual overcurrent at 2 to 0 x
Iset

Min. = 20 ms

Independent time delay for


non-directional residual
overvoltage at 0.8 to 1.2 x Vset

(0.000 60.000) s

0.2% or 75 ms whichever is greater

Independent time delay for


non-directional residual
overcurrent at 0 to 2 x Iset

(0.000 60.000) s

0.2% or 75 ms whichever is greater

Independent time delay for


directional residual
overcurrent at 0 to 2 x Iset

(0.000 60.000) s

0.2% or 170 ms whichever is


greater

Inverse characteristics, see


table 983, table 984 and table
985

16 curve types

See table 983, table 984 and table


985

Relay characteristic angle


(RCADir)

(-179 to 180) degrees

2.0 degrees

Relay operate angle (ROADir)

(0 to 90) degrees

2.0 degrees

Max. = 65 ms

Max. = 65 ms

Max. = 160 ms

Max. = 60 ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.7

Thermal overload protection, two time constants


TRPTTR (49)

8.7.1

Identification
Function description
Thermal overload protection, two time
constants

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
49

TRPTTR

SYMBOL-A V1 EN

8.7.2

Functionality
If a power transformer reaches very high temperatures the equipment might be damaged.
The insulation within the transformer will experience forced ageing. As a consequence of
this the risk of internal phase-to-phase or phase-to-ground faults will increase.
The thermal overload protection estimates the internal heat content of the transformer
(temperature) continuously. This estimation is made by using a thermal model of the
transformer with two time constants, which is based on current measurement.
Two warning pickup levels are available. This enables actions in the power system to be
done before dangerous temperatures are reached. If the temperature continues to increase
to the trip value, the protection initiates a trip of the protected transformer.
The estimated time to trip before operation is presented.

8.7.3

Function block
TRPTTR (49)
I3P*
TRIP
BLOCK
PICKUP
COOLING
ALARM1
MULTPU
ALARM2
RESET
LOCKOUT
WARNING
ANSI06000272-2-en.vsd
ANSI06000272 V2 EN

Figure 231:

TRPTTR (49) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

517

Section 8
Current protection
8.7.4

1MRK 502 066-UUS A

Signals
Table 227:

TRPTTR (49) Input signals

Name

Type

Group signal for current input

BLOCK

BOOLEAN

Block of function

COOLING

BOOLEAN

Cooling input Disabled/ Enabled. Changes Ib setting


and time constant

MULTPU

BOOLEAN

Enable Multiplier for currentReference setting

RESET

BOOLEAN

Reset of function

TRPTTR (49) Output signals

Name

Table 229:
Name

Description

GROUP
SIGNAL

Table 228:

8.7.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Trip Signal

PICKUP

BOOLEAN

Pickup signal

ALARM1

BOOLEAN

First level alarm signal

ALARM2

BOOLEAN

Second level alarm signal

LOCKOUT

BOOLEAN

Lockout signal

WARNING

BOOLEAN

Warning signal: Trip within set warning time

Settings
TRPTTR (49) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

IRef

10.0 - 1000.0

%IB

1.0

100.0

Reference current in % of IBase

IRefMult

0.01 - 10.00

0.01

1.00

Multiplication Factor for reference current

IBase1

30.0 - 250.0

%IB

1.0

100.0

Base current,IBase1 without Cooling input in %


of IBase

IBase2

30.0 - 250.0

%IB

1.0

100.0

Base Current,IBase2, with Cooling input ON in


% of IBase

Tau1

1.0 - 500.0

Min

1.0

60.0

Time constant without cooling input in min, with


IBase1

Tau2

1.0 - 500.0

Min

1.0

60.0

Time constant with cooling input in min, with


IBase2

IHighTau1

30.0 - 250.0

%IB1

1.0

100.0

Current Sett, in % of IBase1 for rescaling TC1


by TC1-IHIGH

Table continues on next page

518

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Tau1High

5 - 2000

%tC1

100

Multiplier in % to TC1 when current is > IHIGHTC1

ILowTau1

30.0 - 250.0

%IB1

1.0

100.0

Current Set, in % of IBase1 for rescaling TC1


by TC1-ILOW

Tau1Low

5 - 2000

%tC1

100

Multiplier in % to TC1 when current is < ILOWTC1

IHighTau2

30.0 - 250.0

%IB2

1.0

100.0

Current Set, in % of IBase2 for rescaling TC2


by TC2-IHIGH

Tau2High

5 - 2000

%tC2

100

Multiplier in % to TC2 when current is >IHIGHTC2

ILowTau2

30.0 - 250.0

%IB2

1.0

100.0

Current Set, in % of IBase2 for rescaling TC2


by TC2-ILOW

Tau2Low

5 - 2000

%tC2

100

Multiplier in % to TC2 when current is < ILOWTC2

ITrip

50.0 - 250.0

%IBx

1.0

110.0

Steady state operate current level in % of


IBasex

Alarm1

50.0 - 99.0

%Itr

1.0

80.0

First alarm level in % of heat content trip value

Alarm2

50.0 - 99.0

%Itr

1.0

90.0

Second alarm level in % of heat content trip


value

LockoutReset

10.0 - 95.0

%Itr

1.0

60.0

Lockout reset level in % of heat content trip


value

ThetaInit

0.0 - 95.0

1.0

50.0

Initial Heat content, in % of heat content trip


value

Warning

1.0 - 500.0

Min

0.1

30.0

Time setting, below which warning would be


set (in min)

tPulse

0.01 - 0.30

0.01

0.10

Length of the pulse for trip signal (in sec).

Step

Default

Table 230:
Name
GlobalBaseSel

8.7.6

TRPTTR (49) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 231:
Name

TRPTTR (49) Monitored data


Type

Values (Range)

Unit

Description

HEATCONT

REAL

Percentage of the heat


content of the transformer

I-MEASUR

REAL

Current measured by the


function in % of the rated
current

TTRIP

INTEGER

Estimated time to trip (in min)

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

519

Section 8
Current protection

1MRK 502 066-UUS A

Name

8.7.7

Type

Values (Range)

Unit

Description

TRESLO

INTEGER

Estimated time to reset of the


function (in min)

TTRIPCAL

INTEGER

0=Not Active
1=Long Time
2=Active

Calculated time status to trip:


not active/long time/active

TRESCAL

INTEGER

0=Not Active
1=Long Time
2=Active

Calculated time status to


reset: not active/long time/
active

Operation principle
The sampled analog phase currents are pre-processed and for each phase current the true
RMS value of each phase current is derived. These phase current values are fed to the
protection function.
From the largest of the three phase currents a relative final temperature (heat content) is
calculated according to the expression:

Q final

I
=
I ref

(Equation 112)

EQUATION1171 V1 EN

where:
I

is the largest phase current

Iref

is a given reference current

If this calculated relative temperature is larger than the relative temperature level
corresponding to the set operate (trip) current, then the pickup output signal PICKUP will
be activated.
The actual temperature at the actual execution cycle is calculated as:

520

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Q final > Q n

If

(Equation 113)

EQUATION1172 V1 EN

Qn = Qn -1 + ( Q final

Dt

- Q n-1 ) 1 - e t

(Equation 114)

EQUATION1173 V1 EN

Q final < Qn

If

(Equation 115)

EQUATION1174 V1 EN

Qn = Q final - ( Q final - Qn -1 ) e

Dt

(Equation 116)

EQUATION1175 V1 EN

where:
Qn

is the calculated present temperature

Qn-1

is the calculated temperature at the previous time step

Qfinal

is the calculated final (steady state) temperature with the actual current

Dt

is the time step between calculation of the actual and final temperature

is the thermal time constant of the protected circuit given in minutes. There are different time
constants depending on the cooling used. Please refer to manufacturer's manuals for details

The calculated transformer relative temperature can be monitored and it is exported from
the function as a real figure HEATCONT.
When the transformer temperature reaches any of the set alarm levels Alarm1 or Alarm2
the corresponding output signal ALARM1 or ALARM2 is activated. When the
temperature of the object reaches the set trip level which corresponds to continuous
current equal to ITrip the output signal TRIP is activated.
There is also a calculation of the time to trip with the present current. This calculation is
only performed if the final temperature is calculated to be above the operation
temperature:

final trip
ttrip ln


final n
ANSIEQUATION1176 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

(Equation 117)
521

Section 8
Current protection

1MRK 502 066-UUS A

The calculated time to trip can be monitored and it is exported from the function as an
integer output TTRIP.
After a trip there can be a lockout to inhibit reconnecting the tripped circuit. The output
lockout signal LOCKOUT is activated when the temperature of the object is above the set
lockout release temperature setting ResLo.
The time to lockout release is calculated by the following cooling time calculation.

Q
- Qlockout _ release
tlockout _ release = -t ln final

Q final - Q n

(Equation 118)

EQUATION1177 V1 EN

In the above equation, the final temperature is calculated according to equation 112. The
calculated component temperature can be monitored as it is exported from the function as
a real figure, TRESLO.
When the current is so high that it has given a pickup signal PICKUP, the estimated time
to trip is continuously calculated and given as analog output TTRIP. If this calculated time
get less than the setting time Warning, set in minutes, the output WARNING is activated.
In case of trip a pulse with a set duration tPulse is activated.

522

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Final Temp
> TripTemp

RESET

PICKUP

HEATCONT

Calculation
of heat
content

I3P
ENMULT

Calculation
of final
temperature

ALARM1

Actual Temp >


Alarm1,Alarm2
Temp

ALARM2

Current base used


TRIP
Actual Temp
> TripTemp

COOLING

Management of
setting
parameters: Tau,
IBase

S
R

Tau used

LOCKOUT

Actual Temp
< Recl
Temp

Calculation
of time to
trip

Calculation
of time to
reset of
lockout

TTRIP
WARNING

TRESCAL

ANSI05000833-2-en.vsd
ANSI05000833 V2 EN

Figure 232:

Functional overview of TRPTTR (49)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

523

Section 8
Current protection
8.7.8

1MRK 502 066-UUS A

Technical data
Table 232:

TRPTTR (49) technical data

Function

Range or value

Accuracy

Base current 1 and 2

(30250)% of IBase

1.0% of In

Trip time:

Ip = load current before overload


occurs
Time constant = (0.10500.00)
minutes

5.0% or 200 ms whichever is


greater

Alarm pickup 1 and 2

(5099)% of heat content trip


value

2.0% of heat content trip

Trip current

(50250)% of IBase

1.0% of In

Reset level temperature

(1095)% of heat content trip

2.0% of heat content trip

I 2 - I p2

t = t ln
I 2 - I ref 2

EQUATION1356 V2 EN

(Equation 119)

I = actual measured current


Ip = load current before overload
occurs
Iref = reference load current

8.8

Breaker failure protection CCRBRF(50BF)

8.8.1

Identification
Function description
Breaker failure protection, 3-phase
activation and output

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
50BF

CCRBRF

3I>BF
SYMBOL-U V1 EN

8.8.2

Functionality
Breaker failure protection (CCRBRF) ensures a fast backup tripping of the surrounding
breakers in case the own breaker fails to open. CCRBRF (50BF) can be current-based,
contact-based or an adaptive combination of these two conditions.
A current check with extremely short reset time is used as check criterion to achieve high
security against inadvertent operation.

524

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Contact check criteria can be used where the fault current through the breaker is small.
CCRBRF (50BF) can be single- or three-phase initiated to allow use with single pole
tripping applications. For the three-phase version of CCRBRF (50BF) the current criteria
can be set to trip only if two out of four for example, two phases or one phase plus the
residual current pickups. This gives a higher security to the back-up trip command.
CCRBRF (50BF) function can be programmed to give a single- or three-phase re-trip of
its own breaker to avoid unnecessary tripping of surrounding breakers at an incorrect
initiation due to mistakes during testing.

8.8.3

Function block
CCRBRF (50BF)
I3P*
BLOCK
BFI_3P
BFI_A
BFI_B
BFI_C
52A_A
52A_B
52A_C
52FAIL

TRBU
TRBU2
TRRET
TRRET_A
TRRET_B
TRRET_C
CBALARM

ANSI06000188-2-en.vsd
ANSI06000188 V2 EN

Figure 233:

8.8.4

CCRBRF (50BF) function block

Signals
Table 233:
Name

CCRBRF (50BF) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three phase group signal for current inputs

BLOCK

BOOLEAN

Block of function

BFI_3P

BOOLEAN

Three phase breaker failure initiation

BFI_A

BOOLEAN

Phase A breaker failure initiation

BFI_B

BOOLEAN

Phase B breaker failure initiation

BFI_C

BOOLEAN

Phase C breaker failure initiation

52a_A

BOOLEAN

Circuit breaker closed in phase A

52a_B

BOOLEAN

Circuit breaker closed in phase B

52a_C

BOOLEAN

Circuit breaker closed in phase C

52FAIL

BOOLEAN

CB faulty, unable to trip. Back-up trip instantaneously

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

525

Section 8
Current protection

1MRK 502 066-UUS A

Table 234:

CCRBRF (50BF) Output signals

Name

8.8.5
Table 235:
Name

Type

Description

TRBU

BOOLEAN

Back-up trip by breaker failure protection function

TRBU2

BOOLEAN

Second back-up trip by breaker failure protection


function

TRRET

BOOLEAN

Retrip by breaker failure protection function

TRRET_A

BOOLEAN

Retrip by breaker failure protection function phase A

TRRET_B

BOOLEAN

Retrip by breaker failure protection function phase B

TRRET_C

BOOLEAN

Retrip by breaker failure protection function phase C

CBALARM

BOOLEAN

Alarm for faulty circuit breaker

Settings
CCRBRF (50BF) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

FunctionMode

Current
Contact
Current/Contact

Current

Detection for trip based on Current/Contact/


Current&Contact

BuTripMode

2 out of 4
1 out of 3
1 out of 4

1 out of 3

Back-up trip modes: 2 out of 4 or 1 out of 3 or 1


out of 4

RetripMode

Retrip Off
CB Pos Check
No CBPos Check

Retrip Off

Oper mode of re-trip logic: OFF/CB Pos Check/


No CB Pos Check

Pickup_PH

5 - 200

%IB

10

Phase current pickup in % of IBase

Pickup_N

2 - 200

%IB

10

Operate residual current level in % of IBase

t1

0.000 - 60.000

0.001

0.000

Time delay of re-trip

t2

0.000 - 60.000

0.001

0.150

Time delay of back-up trip

t2MPh

0.000 - 60.000

0.001

0.150

Time delay of back-up trip at multi-phase


pickup

tPulse

0.000 - 60.000

0.001

0.200

Trip pulse duration

Table 236:
Name

CCRBRF (50BF) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

Pickup_BlkCont

5 - 200

%IB

20

I> in % of IBase block operation using Function


Mode Contact

t3

0.000 - 60.000

0.001

0.030

Additional time delay to 27P2TDLY for a


second back-up trip

tCBAlarm

0.000 - 60.000

0.001

5.000

Time delay for alarm when faulty circuit breaker


indicated

526

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 237:
Name
GlobalBaseSel

8.8.6

CCRBRF (50BF) Non group settings (basic)


Values (Range)
1 - 12

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 238:
Name

8.8.7

Unit

CCRBRF (50BF) Monitored data


Type

Values (Range)

Unit

Description

IA

REAL

Measured current in phase A

IB

REAL

Measured current in phase B

IC

REAL

Measured current in phase C

IN

REAL

Measured residual current

Operation principle
Breaker failure protection CCRBRF (50BF) is initiated from the protection trip command,
either from protection functions within the IED or from external protection devices.
The initiate signal can be phase selective or general (for all three phases). Phase selective
initiate signals enable single pole re-trip function. The re-trip attempt is made after a set
time delay t1. The re-trip function can be done with or without current check. With the
current check, the re-trip is only performed if the current through the circuit breaker is
larger than the operate current level.
The initiate signal can be an internal or external protection trip signal. This signal will
initiate the back-up trip timer. The function detects the successful breaker opening, either
by detection of low current through RMS evaluation and a special adapted current
algorithm or by open contact indication. The special algorithm enables a very fast
detection of successful breaker opening, that is, fast resetting of the current measurement.
If the current and/or contact detection has not detected breaker opening before the backup timer has run its time a back-up trip is initiated.
Further the following possibilities are available:

The minimum length of the re-trip pulse, the back-up trip pulse and the back-up trip
pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the back-up trip pulse
2 will however sustain as long as there is an indication of closed breaker.
In the current detection it is possible to use three different options: 1 out of 3 where
it is sufficient to detect failure to open (high current) in one pole, 1 out of 4 where it
is sufficient to detect failure to open (high current) in one pole or high residual current

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

527

Section 8
Current protection

1MRK 502 066-UUS A

and 2 out of 4 where at least two current (phase current and/or residual current) shall
be high for breaker failure detection.
The current detection level for the residual current can be set different from the setting
of phase current detection.
It is possible to have different back-up time delays for single-phase faults and for
multi-phase faults.
The back-up trip can be made without current check. It is possible to have this option
activated for small load currents only.
It is possible to have instantaneous back-up trip function if a signal is high if the
circuit breaker is incapable to clear faults, for example at low gas pressure.
30 ms

BFI_3P
BFI_A

BFP Started A

OR

AND

S
R

BLOCK

SR

150ms

Time out A

AND

OR

Reset A

Retrip Time Out A


BackupTrip A

OR

ANSI09000976-2-en.vsd
ANSI09000976 V2 EN

Figure 234:

Simplified logic scheme of the CCRBRF (50BF) starting logic

Pickup_PH
a
b

FunctionMode

a>b

Current

OR

AND

OR

Time out A
OR

Current and Contact

I_A

AND

Current High A
CB Closed A

AND

OR

BFP Started A
a

Pickup_BlkCont
52a_A

Reset A

Contact

a>b

AND

OR

AND

AND

AND

Contact Closed A

ANSI09000977-1-en.vsd
ANSI09000977 V1 EN

Figure 235:

528

Simplified logic scheme of the CCRBRF (50BF), CB position evaluation

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

BFP Started A
RetripMode

OR

TRRET

OR

TRRET_A

OR

OR

AND

CB Pos Check
CB Closed A

52FAIL

TRRET_B

tPulse

AND

No CBPos Check
1

TRRET_C

From other
phases

Retrip Time Out A

t1
0

AND

ANSI09000978-4-en.vsd

ANSI09000978 V4 EN

Figure 236:

Simplified logic scheme of the retrip logic function

BFP Started A
BFP Started B

AND

BFP Started C

AND

IN

Pickup_N

BUTripMode
1

From other
phases

a>b

Contact Closed A

2 out of 4
1 out of 4
1 out of 3
Current High B
Current High C

OR
OR

Current High A
52FAIL

AND

AND

BFP Started A

t2
OR

0
AND

OR

From other
phases

BFP Started B

AND

AND

Backup Trip A

t2MPh
0

OR

tPulse

From other Backup Trip B


phases
Backup Trip C

OR

2 of 3

OR

TRBU

tPulse

BFP Started C
S
AND

SR

t3

OR

TRBU2

ANSI09000979-4-en.vsd

ANSI09000979 V4 EN

Figure 237:

Simplified logic scheme of the back-up trip logic function

The internal logical signals PU_A, PU_B, PU_C have logical value 1 when the current in
the respective phase has the magnitude larger than the setting parameter Pickup_PH.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

529

Section 8
Current protection
8.8.8

1MRK 502 066-UUS A

Technical data
Table 239:

CCRBRF (50BF) technical data

Function

Range or value

Accuracy

Trip phase current

(5-200)% of lBase

1.0% of In at I In
1.0% of I at I > In

Reset ratio, phase current

> 95%

Trip residual current

(2-200)% of lBase

1.0% of In at I In
1.0% of I at I > In

Reset ratio, residual


current

> 95%

Phase current pickup for


blocking of contact
function

(5-200)% of lBase

1.0% of In at I In
1.0% of I at I > In

Reset ratio

> 95%

Trip time for current


detection

10 ms typically

Reset time for current


detection

15 ms maximum

Time delay for re-trip at 0


to 2 x Iset

(0.000-60.000) s

0.2% or 15 ms whichever is
greater

Time delay for back-up trip


at 0 to 2 x Iset

(0.000-60.000) s

0.2% or 15 ms whichever is
greater

Time delay for back-up trip


at multi-phase pickup at 0
to 2 x Iset

(0.000-60.000) s

0.2% or 20 ms whichever is
greater

Additional time delay for a


second back-up trip at 0 to
2 x Iset

(0.000-60.000) s

0.2% or 20 ms whichever is
greater

Time delay for alarm for


faulty circuit breaker

(0.000-60.000) s

0.2% or 15 ms whichever is
greater

8.9

Pole discrepancy protection CCPDSC(52PD)

8.9.1

Identification
Function description
Pole discrepancy protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
52PD

CCPDSC

PD
SYMBOL-S V1 EN

530

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.9.2

Functionality
An open phase can cause negative and zero sequence currents which cause thermal stress
on rotating machines and can cause unwanted operation of zero sequence or negative
sequence current functions.
Normally the own breaker is tripped to correct such a situation. If the situation warrants
the surrounding breakers should be tripped to clear the unsymmetrical load situation.
The Pole discrepancy protection function CCPDSC (52PD) operates based on
information from auxiliary contacts of the circuit breaker for the three phases with
additional criteria from unsymmetrical phase currents when required.

8.9.3

Function block

CCPDSC (52PD)
I3P*
BLOCK
BLKDBYAR
CLOSECMD
OPENCMD
EXTPDIND
52B_A
52A_A
52B_B
52A_B
52B_C
52A_C

TRIP
PICK UP

ANSI13000305-2-en.vsdx

ANSI13000305 V2 EN

Figure 238:

8.9.4

CCPDSC (52PD) function block

Signals
Table 240:
Name

CCPDSC (52PD) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three phase currents

BLOCK

BOOLEAN

Block of function

BLKDBYAR

BOOLEAN

Block of function at CB single phase auto re-closing


cycle

CLOSECMD

BOOLEAN

Close command to CB

OPENCMD

BOOLEAN

Open command to CB

EXTPDIND

BOOLEAN

Pole discrepancy signal from CB logic

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

531

Section 8
Current protection

1MRK 502 066-UUS A

Name

Type

Phase A Pole opened indication from CB

52a_A

BOOLEAN

Phase A Pole closed indication from CB

52b_B

BOOLEAN

Phase B Pole opened indication from CB

52a_B

BOOLEAN

Phase B Pole closed indication from CB

52b_C

BOOLEAN

Phase C Pole opened indication from CB

52a_C

BOOLEAN

Phase C Pole closed indication from CB

CCPDSC (52PD) Output signals

Name

Table 242:
Name

Description

BOOLEAN

Table 241:

8.9.5

Default

52b_A

Type

Description

TRIP

BOOLEAN

Trip signal to CB

PICKUP

BOOLEAN

Trip condition TRUE, waiting for time delay

Settings
CCPDSC (52PD) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

tTrip

0.000 - 60.000

0.001

0.300

Time delay between trip condition and trip


signal

ContactSel

Disabled
PD signal from CB
Pole pos aux cont.

Disabled

Contact function selection

CurrentSel

Disabled
CB oper monitor
Continuous monitor

Disabled

Current function selection

CurrUnsymPU

0 - 100

80

Unsym magn of lowest phase current


compared to the highest.

CurrRelPU

0 - 100

%IB

10

Current magnitude for release of the function in


% of IBase

Table 243:
Name
GlobalBaseSel

532

CCPDSC (52PD) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Description
Selection of one of the Global Base Value
groups

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.9.6

Monitored data
Table 244:

CCPDSC (52PD) Monitored data

Name

8.9.7

Type

Values (Range)

Unit

Description

IMin

REAL

Lowest phase current

IMax

REAL

Highest phase current

Operation principle
The detection of pole discrepancy can be made in two different ways. If the contact based
function is used an external logic can be made by connecting the auxiliary contacts of the
circuit breaker so that a pole discrepancy is indicated, see figure 239.
C.B.

52a
52a
52a

52b

poleDiscrepancy Signal from C.B.

52b
52b

ANSI_en05000287.vsd

ANSI05000287 V1 EN

Figure 239:

Pole discrepancy external detection logic

This binary signal is connected to a binary input of the IED. The appearance of this signal
will pickup a timer that will give a trip signal after the set time delay.
There is also a possibility to connect all phase selective auxiliary contacts (phase contact
open and phase contact closed) to binary inputs of the IED, see figure 240.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

533

Section 8
Current protection

1MRK 502 066-UUS A

C.B.

52a

poleOneClosed from C.B.


52a

poleTwoClosed from C.B.


52a

52b

poleThreeClosed from C.B.


poleOneOpened from C.B.

52b

poleTwoOpened from C.B.


52b

poleThreeOpened from C.B.


en05000288_ansi.vsd

ANSI05000288 V1 EN

Figure 240:

Pole discrepancy signals for internal logic

In this case the logic is realized within the function. If the inputs are indicating pole
discrepancy the trip timer is started. This timer will give a trip signal after the set delay.
Pole discrepancy can also be detected by means of phase selective current measurement.
The sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT)
block. From the fundamental frequency components of each phase current the RMS value
of each phase current is derived. The smallest and the largest phase current are derived. If
the smallest phase current is lower than the setting CurrUnsymPU times the largest phase
current the settable trip timer (tTrip) is started. The tTrip timer gives a trip signal after the
set delay. The TRIP signal is a pulse 150 ms long. The current based pole discrepancy
function can be set to be active either continuously or only directly in connection to
breaker open or close command.
The function also has a binary input that can be configured from the autoreclosing
function, so that the pole discrepancy function can be blocked during sequences with a
single pole open if single pole autoreclosing is used.

534

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

BLOCK
OR

BLKDBYAR

PolPosAuxCont
AND

52b_A
52a_A
52b_B
52a_B
52b_C
52a_C

Pole
Disc repancy
detection
150 ms
AND
OR

0- t
0

TRIP

PD signal from CB
AND

EXTPDIND
CLOSECMD
OPENCMD

t+ 200 ms
OR
AND
Unsymmetry current
detection
en 05000747_ansi.vsd

ANSI05000747 V1 EN

Figure 241:

Simplified block diagram of pole discrepancy function CCPDSC (52PD) contact and current based

CCPDSC (52PD) is disabled if:

The IED is in TEST mode and CCPDSC (52PD) has been blocked from the local HMI
The input signal BLOCK is high
The input signal BLKDBYAR is high

The BLOCK signal is a general purpose blocking signal of the pole discrepancy
protection. It can be connected to a binary input in the IED in order to receive a block
command from external devices or can be software connected to other internal functions
in the IED itself in order to receive a block command from internal functions. Through OR
gate it can be connected to both binary inputs and internal function outputs.
The BLKDBYAR signal blocks the pole discrepancy operation when a single phase
autoreclosing cycle is in progress. It can be connected to the output signal 1PT1 on
SMBRREC (79) function block. If the autoreclosing function is an external device, then
BLKDBYAR has to be connected to a binary input in the IED and this binary input is
connected to a signalization 1phase autoreclosing in progress from the external
autoreclosing device.
If the pole discrepancy protection is enabled, then two different criteria can generate a trip
signal TRIP:

Pole discrepancy signaling from the circuit breaker.


Unsymmetrical current detection.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

535

Section 8
Current protection
8.9.7.1

1MRK 502 066-UUS A

Pole discrepancy signaling from circuit breaker


If one or two poles of the circuit breaker have failed to open or to close the pole
discrepancy status, then the function input EXTPDIND is activated from the pole
discrepancy signal derived from the circuit breaker auxiliary contacts (one NO contact for
each phase connected in parallel, and in series with one NC contact for each phase
connected in parallel) and, after a settable time interval tTrip (0-60 s), a 150 ms trip pulse
command TRIP is generated by the Polediscrepancy function (52PD).

8.9.7.2

Unsymmetrical current detection


Unsymmetrical current indicated if:

any phase current is lower than CurrUnsymPU of the highest current in the three
phases.
the highest phase current is greater than CurrRelPU of IBase.

If these conditions are true, an unsymmetrical condition is detected and the internal signal
INPS is turned high. This detection is enabled to generate a trip after a set time delay tTrip
if the detection occurs in the next 200 ms after the circuit breaker has received a command
to open trip or close and if the unbalance persists. The 200 ms limitation is for avoiding
unwanted operation during unsymmetrical load conditions.
The pole discrepancy protection is informed that a trip or close command has been given
to the circuit breaker through the inputs CLOSECMD (for closing command information)
and OPENCMD (for opening command information). These inputs can be connected to
terminal binary inputs if the information are generated from the field (that is from
auxiliary contacts of the close and open push buttons) or may be software connected to the
outputs of other integrated functions (that is close command from a control function or a
general trip from integrated protections).

8.9.8

Technical data
Table 245:

CCPDSC (52PD) technical data

Function

8.10

536

Range or value

Accuracy

Trip current

(0100)% of IBase

1.0% of In

Independent time delay between


trip condition and trip signal

(0.000-60.000) s

0.2% or 25 ms whichever is
greater

Directional underpower protection GUPPDUP (37)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.10.1

Identification
Function description
Directional underpower protection

IEC 61850
identification

IEC 60617
identification

GUPPDUP

P<

ANSI/IEEE C37.2
device number
37

2
SYMBOL-LL V2 EN

8.10.2

Functionality
The task of a generator in a power plant is to convert mechanical energy available as a
torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that it does
not cover bearing losses and ventilation losses. Then, the synchronous generator becomes
a synchronous motor and starts to take electric power from the rest of the power system.
This operating state, where individual synchronous machines operate as motors, implies
no risk for the machine itself. If the generator under consideration is very large and if it
consumes lots of electric power, it may be desirable to disconnect it to ease the task for the
rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state. The
task of the low forward power protection is to protect the turbine and not to protect the
generator itself.
Figure 242 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a higher
margin and should provide better dependability. On the other hand, the risk for unwanted
operation immediately after synchronization may be higher. One should set the
underpower IED to trip if the active power from the generator is less than about 2%. One
should set the overpower IED to trip if the power flow from the network to the generator
is higher than 1% depending on the type of turbine.
When IED with a metering class input CTs is used pickup can be set to more sensitive
value (e.g.0,5% or even to 0,2%).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

537

Section 8
Current protection

1MRK 502 066-UUS A

Underpower IED

Overpower IED

Trip
Line

Trip
Line

Margin

Margin

Tripping point
without
turbine torque

Tripping point
without
turbine torque

ANSI06000315-1-en.vsd

ANSI06000315 V1 EN

Figure 242:

8.10.3

Protection with underpower IED and overpower IED

Function block
GUPPDUP (37)
I3P*
V3P*
BLOCK
BLOCK1
BLOCK2

TRIP
TRIP1
TRIP2
PICKUP
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI07000027-2-en.vsd

ANSI07000027 V2 EN

Figure 243:

8.10.4

Signals
Table 246:
Name

538

GUPPDUP (37) function block

GUPPDUP (37) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Current group connection

V3P

GROUP
SIGNAL

Voltage group connection

BLOCK

BOOLEAN

Block of function

BLOCK1

BOOLEAN

Block of stage 1

BLOCK2

BOOLEAN

Block of stage 2

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 247:

GUPPDUP (37) Output signals

Name

8.10.5
Table 248:
Name

Type

Description

TRIP

BOOLEAN

Common trip signal

TRIP1

BOOLEAN

Trip of stage 1

TRIP2

BOOLEAN

Trip of stage 2

PICKUP

BOOLEAN

Common pickup

PICKUP1

BOOLEAN

Pickup of stage 1

PICKUP2

BOOLEAN

Pickup of stage 2

REAL

Active Power in MW

PPERCENT

REAL

Active power in % of SBase

REAL

Reactive power in MVAr

QPERCENT

REAL

Reactive power in % of SBase

Settings
GUPPDUP (37) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OpMode1

Disabled
UnderPower

UnderPower

Operation mode for stage 1 Off / On

Power1

0.0 - 500.0

%SB

0.1

1.0

Stage 1 underpower setting in Angle1 direction


in % of SBase

Angle1

-180.0 - 180.0

Deg

0.1

0.0

Characteristic angle for max power senistivity


stage 1

TripDelay1

0.01 - 6000.00

0.01

1.00

Trip delay for stage 1

DropDelay1

0.01 - 6000.00

0.01

0.06

Drop-off delay for stage 1

OpMode2

Disabled
UnderPower

UnderPower

Operation mode for stage 2 Off / On

Power2

0.0 - 500.0

%SB

0.1

1.0

Power setting for stage 2 in % of SBase

Angle2

-180.0 - 180.0

Deg

0.1

0.0

Characteristic angle for max power senistivity


stage 2

TripDelay2

0.01 - 6000.00

0.01

1.00

Trip delay for stage 2

DropDelay2

0.01 - 6000.00

0.01

0.06

Drop-off delay for stage 2

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

539

Section 8
Current protection

Table 249:
Name

1MRK 502 066-UUS A

GUPPDUP (37) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

TD

0.000 - 0.999

0.001

0.000

Low pass filter coefficient for power


measurement, P and Q

Hysteresis1

0.2 - 5.0

%SB

0.1

0.5

Absolute hysteresis of stage 1 in % SBase

Hysteresis2

0.2 - 5.0

%SB

0.1

0.5

Absolute hysteresis of stage 2 in % SBase

IMagComp5

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates current


error at 5% of Ir

IMagComp30

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates current


error at 30% of Ir

IMagComp100

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates current


error at 100% of Ir

VMagComp5

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates voltage


error at 5% of Ur

VMagComp30

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates voltage


error at 30% of Ur

VMagComp100

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates voltage


error at 100% of Ur

IAngComp5

-10.000 - 10.000

Deg

0.001

0.000

Corr of error betw current and voltage angles at


5% of Ir

IAngComp30

-10.000 - 10.000

Deg

0.001

0.000

Corr of error betw current and voltage angles at


30% of Ir

IAngComp100

-10.000 - 10.000

Deg

0.001

0.000

Corr of error betw current and voltage angles at


100% of Ir

Table 250:
Name

GUPPDUP (37) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

Mode

A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C

Pos Seq

Selection of measured current and voltage

540

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.10.6

Monitored data
Table 251:
Name

8.10.7

GUPPDUP (37) Monitored data


Type

Values (Range)

Unit

Description

REAL

MW

Active Power in MW

PPERCENT

REAL

Active power in % of SBase

REAL

MVAr

Reactive power in MVAr

QPERCENT

REAL

Reactive power in % of SBase

Operation principle
A simplified scheme showing the principle of the power protection function is shown in
figure 244. The function has two stages with individual settings.

Chosen current
phasors

Chosen voltage
phasors

P
Complex
power
calculation

Derivation of
S( composant)
in Char angle

S( angle)

S( angle ) <
Power1

t
0

TRIP1
PICKUP1

S( angle ) <
Power2

t
0

TRIP2
PICKUP2

P = POWRE
Q = POWIM

ANSI06000438-2-en.vsd
ANSI06000438 V2 EN

Figure 244:

Simplified logic diagram of the power protection function

The function will use voltage and current phasors calculated in the pre-processing blocks.
The apparent complex power is calculated according to chosen formula as shown in
table 252.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

541

Section 8
Current protection

1MRK 502 066-UUS A

Table 252:

Complex power calculation

Set value: Mode


A, B, C

Formula used for complex power calculation

S = V A I A* + VB I B* + VC I C *
EQUATION2055-ANSI V1 EN

Arone

S = V AB I A* - VBC IC *
EQUATION2056-ANSI V1 EN

PosSeq

(Equation 126)

S = 3 VB I B*
EQUATION2062-ANSI V1 EN

(Equation 125)

S = 3 VA I A*
EQUATION2061-ANSI V1 EN

(Equation 124)

S = VCA ( I C * - I A* )
EQUATION2060-ANSI V1 EN

(Equation 123)

S = VBC ( I B* - IC * )
EQUATION2059-ANSI V1 EN

CA

(Equation 122)

S = VAB ( I A* - I B* )
EQUATION2058-ANSI V1 EN

BC

(Equation 121)

S = 3 VPosSeq I PosSeq*
EQUATION2057-ANSI V1 EN

AB

(Equation 120)

(Equation 127)

S = 3 VC I C *
EQUATION2063-ANSI V1 EN

(Equation 128)

The active and reactive power is available from the function and can be used for
monitoring and fault recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is calculated.
If this angle is 0 the active power component P is calculated. If this angle is 90 the
reactive power component Q is calculated.
The calculated power component is compared to the power pick up setting Power1(2). For
directional underpower protection, a pickup signal PICKUP1(2) is activated if the
calculated power component is smaller than the pick up value. For directional overpower
protection, a pickup signal PICKUP1(2) is activated if the calculated power component is
542

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

larger than the pick up value. After a set time delay TripDelay1(2) a trip TRIP1(2) signal
is activated if the pickup signal is still active. At activation of any of the two stages a
common signal PICKUP will be activated. At trip from any of the two stages also a
common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The absolute
hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) + drop-power1(2)). For
generator low forward power protection the power setting is very low, normally down to
0.02 p.u. of rated generator power. The hysteresis should therefore be set to a smaller
value. The drop-power value of stage1 can be calculated with the Power1(2),
Hysteresis1(2): drop-power1(2) = Power1(2) + Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the drop-power1(2)
would be too small. In such cases, the hysteresis1 greater than (0.5 Power1(2)) is
corrected to the minimal value.
If the measured power drops under the drop-power1(2) value, the function will reset after
a set time DropDelay1(2). The reset means that the pickup signal will drop out and that the
timer of the stage will reset.

8.10.7.1

Low pass filtering


In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for S (P, Q). This will
make slower measurement response to the step changes in the measured quantity.
Filtering is performed in accordance with the following recursive formula:

S = TD SOld + (1 TD ) SCalculated
EQUATION1959-ANSI V1 EN

(Equation 129)

Where
S

is a new measured value to be used for the protection function

Sold

is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle


TD

is settable parameter by the end user which influence the filter properties

Default value for parameter TD is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay). When
TD is set to value bigger than 0, the filtering is enabled. A typical value for TD=0.92 in
case of slow operating functions.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

543

Section 8
Current protection
8.10.7.2

1MRK 502 066-UUS A

Calibration of analog inputs


Measured currents and voltages used in the Power function can be calibrated to get class
0.5 measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30
and 100% of rated current and voltage. The compensation below 5% and above 100% is
constant and linear in between, see example in figure 245.
% of In

Magnitude
compensation

+10
IMagComp5

Measured
current

IMagComp30
IMagComp100

30

-10

Degrees

100

% of In

0-5%:
Constant
5-30-100%: Linear
>100%:
Constant

Angle
compensation

+10
Measured
current

IAngComp30
IAngComp5
IAngComp100

30

100

% of In

-10

ANSI05000652_3_en.vsd
ANSI05000652 V3 EN

Figure 245:

Calibration curves

The first current and voltage phase in the group signals will be used as reference and the
amplitude and angle compensation will be used for related input signals.
Analog outputs (Monitored data) from the function can be used for service values or in the
disturbance report. The active power is provided as MW value: P, or in percent of base
power: PPERCENT. The reactive power is provided as Mvar value: Q, or in percent of
base power: QPERCENT.

544

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.10.8

Technical data
Table 253:

GUPPDUP (37) technical data

Function

Range or value

Accuracy

Power level
for Step 1 and Step 2

(0.0500.0)% of SBase

1.0% of Sn at S Sn
1.0% of S at S > Sn
where
Sr= 1,732*Vn*In

Characteristic angle
for Step 1 and Step 2

(-180.0180.0) degrees

2.0 degrees

Independent time delay to trip for


Step 1 and Step 2 at 2 to 0.5 x Sn
and k=0.000

(0.01-6000.00) s

0.2% or 40 ms whichever is
greater

8.11

Directional overpower protection GOPPDOP (32)

8.11.1

Identification
Function description
Directional overpower protection

IEC 61850
identification

IEC 60617
identification

GOPPDOP

P>

ANSI/IEEE C37.2
device number
32

2
DOCUMENT172362-IMG158942
V2 EN

8.11.2

Functionality
The task of a generator in a power plant is to convert mechanical energy available as a
torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that it does
not cover bearing losses and ventilation losses. Then, the synchronous generator becomes
a synchronous motor and starts to take electric power from the rest of the power system.
This operating state, where individual synchronous machines operate as motors, implies
no risk for the machine itself. If the generator under consideration is very large and if it
consumes lots of electric power, it may be desirable to disconnect it to ease the task for the
rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state. The
task of the reverse power protection is to protect the turbine and not to protect the
generator itself.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

545

Section 8
Current protection

1MRK 502 066-UUS A

Figure 246 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a higher
margin and should provide better dependability. On the other hand, the risk for unwanted
operation immediately after synchronization may be higher. One should set the
underpower IED to trip if the active power from the generator is less than about 2%. One
should set the overpower IED to trip if the power flow from the network to the generator
is higher than 1%.
When IED with a metering class input CTs is used pickup can be set to more sensitive
value (e.g.0,5% or even to 0,2%).

Underpower IED

Overpower IED

Trip
Line

Trip
Line

Margin

Margin

Tripping point
without
turbine torque

Tripping point
without
turbine torque

ANSI06000315-1-en.vsd

ANSI06000315 V1 EN

Figure 246:

8.11.3

Reverse power protection with underpower IED and overpower IED

Function block
GOPPDOP (32)
I3P*
V3P*
BLOCK
BLOCK1
BLOCK2

TRIP
TRIP1
TRIP2
PICKUP
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI07000028-2-en.vsd

ANSI07000028 V2 EN

Figure 247:

546

GOPPDOP (32) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.11.4

Signals
Table 254:

GOPPDOP (32) Input signals

Name

Type

Current group connection

V3P

GROUP
SIGNAL

Voltage group connection

BLOCK

BOOLEAN

Block of function

BLOCK1

BOOLEAN

Block of stage 1

BLOCK2

BOOLEAN

Block of stage 2

GOPPDOP (32) Output signals

Name

Table 256:
Name

Description

GROUP
SIGNAL

Table 255:

8.11.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Common trip signal

TRIP1

BOOLEAN

Trip of stage 1

TRIP2

BOOLEAN

Trip of stage 2

PICKUP

BOOLEAN

Common pickup

PICKUP1

BOOLEAN

Pickup of stage 1

PICKUP2

BOOLEAN

Pickup of stage 2

REAL

Active power P in MW

PPERCENT

REAL

Active power P in % of SBase

REAL

Reactive power Q in MVAr

QPERCENT

REAL

Reactive power Q in % of SBase

Settings
GOPPDOP (32) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OpMode1

Disabled
OverPower

OverPower

Operation mode for stage 1 Off / On

Power1

0.0 - 500.0

%SB

0.1

120.0

Stage 1 overpower setting in Angle1 direction


in % of SBase

Angle1

-180.0 - 180.0

Deg

0.1

0.0

Characteristic angle for max power senistivity


stage 1

TripDelay1

0.01 - 6000.00

0.01

1.00

Trip delay for stage 1

DropDelay1

0.01 - 6000.00

0.01

0.06

Drop-off delay for stage 1

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

547

Section 8
Current protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

OpMode2

Disabled
OverPower

OverPower

Operation mode for stage 2 Off / On

Power2

0.0 - 500.0

%SB

0.1

120.0

Stage 2 overpower setting in Angle2 direction


in % of SBase

Angle2

-180.0 - 180.0

Deg

0.1

0.0

Characteristic angle for max power senistivity


stage 2

TripDelay2

0.01 - 6000.00

0.01

1.00

Trip delay for stage 2

DropDelay2

0.01 - 6000.00

0.01

0.06

Drop-off delay for stage 2

Step

Default

Table 257:
Name

GOPPDOP (32) Group settings (advanced)


Values (Range)

Unit

Description

0.000 - 0.999

0.001

0.000

Low pass filter coefficient for power


measurement, P and Q

Hysteresis1

0.2 - 5.0

%SB

0.1

0.5

Absolute hysteresis of stage 1 in % of SBase

Hysteresis2

0.2 - 5.0

%SB

0.1

0.5

Absolute hysteresis of stage 2 in % of SBase

IMagComp5

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates current


error at 5% of Ir

IMagComp30

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates current


error at 30% of Ir

IMagComp100

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates current


error at 100% of Ir

VMagComp5

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates voltage


error at 5% of Ur

VMagComp30

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates voltage


error at 30% of Ur

VMagComp100

-10.000 - 10.000

0.001

0.000

Amplitude correction compensates voltage


error at 100% of Ur

IAngComp5

-10.000 - 10.000

Deg

0.001

0.000

Corr of error betw current and voltage angles at


5% of Ir

IAngComp30

-10.000 - 10.000

Deg

0.001

0.000

Corr of error betw current and voltage angles at


30% of Ir

IAngComp100

-10.000 - 10.000

Deg

0.001

0.000

Corr of error betw current and voltage angles at


100% of Ir

548

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 258:
Name

GOPPDOP (32) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

Mode

A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C

Pos Seq

Selection of measured current and voltage

8.11.6

Monitored data
Table 259:
Name

8.11.7

GOPPDOP (32) Monitored data


Type

Values (Range)

Unit

Description

REAL

MW

Active power P in MW

PPERCENT

REAL

Active power P in % of SBase

REAL

MVAr

Reactive power Q in MVAr

QPERCENT

REAL

Reactive power Q in % of
SBase

Operation principle
A simplified scheme showing the principle of the power protection function is shown in
figure 248. The function has two stages with individual settings.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

549

Section 8
Current protection

1MRK 502 066-UUS A

Chosen current
phasors

Chosen voltage
phasors

P
Complex
power
calculation

Derivation of
S(composant)
in Char angle

S(angle)

S(angle) >
Power1

TRIP1
PICKUP1

S(angle) >
Power2

TRIP2
PICKUP2

P = POWRE
Q = POWIM

ANSI06000567-2-en.vsd
ANSI06000567 V2 EN

Figure 248:

Simplified logic diagram of the power protection function

The function will use voltage and current phasors calculated in the pre-processing blocks.
The apparent complex power is calculated according to chosen formula as shown in
table 260.
Table 260:

Complex power calculation

Set value: Mode


A,B,C

Formula used for complex power calculation


*

S = V A I A + V B I B + V C IC

(Equation 130)

EQUATION2038 V1 EN

Arone

S = V AB I A - V BC I C
S = 3 V PosSeq I PosSeq

(Equation 132)

EQUATION2040 V1 EN

A,B

(Equation 131)

EQUATION2039 V1 EN

PosSeq

S = V AB (I A - I B )
(Equation 133)

EQUATION2041 V1 EN

B,C

S = V BC (I B - I C )
EQUATION2042 V1 EN

(Equation 134)

Table continues on next page

550

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Set value: Mode


C,A

Formula used for complex power calculation


*

S = V CA (I C - I A )
(Equation 135)

EQUATION2043 V1 EN

S = 3 V A IA

(Equation 136)

EQUATION2044 V1 EN

S = 3 V B IB

(Equation 137)

EQUATION2045 V1 EN

S = 3 V C IC
EQUATION2046 V1 EN

(Equation 138)

The active and reactive power is available from the function and can be used for
monitoring and fault recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is calculated.
If this angle is 0 the active power component P is calculated. If this angle is 90 the
reactive power component Q is calculated.
The calculated power component is compared to the power pick up setting Power1(2). A
pickup signal PICKUP1(2) is activated if the calculated power component is larger than
the pick up value. After a set time delay TripDelay1(2) a trip TRIP1(2) signal is activated
if the pickup signal is still active. At activation of any of the two stages a common signal
PICKUP will be activated. At trip from any of the two stages also a common signal TRIP
will be activated.
To avoid instability there is a settable hysteresis in the power function. The absolute
hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) drop-power1(2)). For
generator reverse power protection the power setting is very low, normally down to 0.02
p.u. of rated generator power. The hysteresis should therefore be set to a smaller value.
The drop-power value of stage1 can be calculated with the Power1(2), Hysteresis1(2):
drop-power1(2) = Power1(2) Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the drop-power1(2)
would be too small. In such cases, the hysteresis1 greater than (0.5 Power1(2)) is
corrected to the minimal value.
If the measured power drops under the drop-power1(2) value the function will reset after
a set time DropDelay1(2). The reset means that the pickup signal will drop out ant that the
timer of the stage will reset.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

551

Section 8
Current protection
8.11.7.1

1MRK 502 066-UUS A

Low pass filtering


In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for S (P, Q). This will
make slower measurement response to the step changes in the measured quantity.
Filtering is performed in accordance with the following recursive formula:
S = k SOld + (1 - k ) SCalculated
(Equation 139)

EQUATION1959 V1 EN

Where
S

is a new measured value to be used for the protection function

Sold

is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle


k

is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay). When k
is set to value bigger than 0, the filtering is enabled. A typical value for k = 0.92 in case
of slow operating functions.

8.11.7.2

Calibration of analog inputs


Measured currents and voltages used in the Power function can be calibrated to get class
0.5 measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30
and 100% of rated current and voltage. The compensation below 5% and above 100% is
constant and linear in between, see example in figure 249.

552

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

% of In

Magnitude
compensation

+10
IMagComp5

Measured
current

IMagComp30
IMagComp100

30

-10

Degrees

100

% of In

0-5%:
Constant
5-30-100%: Linear
>100%:
Constant

Angle
compensation

+10
Measured
current

IAngComp30
IAngComp5
IAngComp100

30

100

% of In

-10

ANSI05000652_3_en.vsd
ANSI05000652 V3 EN

Figure 249:

Calibration curves

The first current and voltage phase in the group signals will be used as reference and the
amplitude and angle compensation will be used for related input signals.
Analog outputs from the function can be used for service values or in the disturbance
report. The active power is provided as MW value: P, or in percent of base power:
PPERCENT. The reactive power is provided as Mvar value: Q, or in percent of base
power: QPERCENT.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

553

Section 8
Current protection
8.11.8

1MRK 502 066-UUS A

Technical data
Table 261:

GOPPDOP (32) technical data

Function

Range or value

Power level
for Step 1 and Step 2

Accuracy

(0.0500.0)% of SBase
When measuring transformer
inputs are used, the following
accuracy can be obtained for low
pickup settings which are typical
for reverse power protection
application:

Characteristic angle
for Step 1 and Step 2

(-180.0180.0) degrees

Trip time, pickup at 0.5 to 2 x Sr


and k=0.000

Min. =10 ms

Reset time, pickup at 2 to 0.5 x Sr


and k=0.000

Min. = 35 ms

Independent time delay to trip for


Step 1 and Step 2 at 0.5 to 2 x Sn
and k=0.000

(0.01-6000.00) s

1.0% of Sn at S Sn
1.0% of S at S > Sn
Pickup value=0.5% of Sn
Pickup accuracy of 0.20% of Sn*)
Pickup value=0.2% of Sn
Pickup accuracy of 0.15% of Sn*)
whereSn= 1,732*Vn*In
2.0 degrees

Max. = 25 ms

Max. = 55 ms
0.2% or 40 ms whichever is
greater

*) To achieve this accuracy for reverse power protection it is also recommended to apply settings k=0.990 and
Mode=PosSeq. These settings will help to minimize the overall measurement error ensuring the best
accuracy for this application.

8.12

Negativ sequence time overcurrent protection for


machines NS2PTOC (46I2)

8.12.1

Identification
Function description
Negative sequence time overcurrent
protection for machines

8.12.2

IEC 61850
identification
NS2PTOC

IEC 60617
identification
2I2>

ANSI/IEEE C37.2
device number
46I2

Functionality
Negative-sequence time overcurrent protection for machines NS2PTOC (46I2) is
intended primarily for the protection of generators against possible overheating of the
rotor caused by negative sequence current in the stator current.

554

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

The negative sequence currents in a generator may, among others, be caused by:

Unbalanced loads
Line to line faults
Line to ground faults
Broken conductors
Malfunction of one or more poles of a circuit breaker or a disconnector

NS2PTOC (46I2) can also be used as a backup protection, that is, to protect the generator
in case line protections or circuit breakers fail to clear unbalanced system faults.
To provide an effective protection for the generator for external unbalanced conditions,
NS2PTOC (46I2) is able to directly measure the negative sequence current. NS2PTOC
(46I2) also has a time delay characteristic which matches the heating characteristic of the
2
generator I 2 t = K as defined in standard IEEE C50.13.
where:
I2

is negative sequence current expressed in per unit of the rated generator


current

is operating time in seconds

is a constant which depends of the generators size and design

NS2PTOC (46I2) has a wide range of K settings and the sensitivity and capability of
detecting and tripping for negative sequence currents down to the continuous capability of
a generator.
In order to match the heating characteristics of the generator a reset time parameter can be
set.
A separate definite time delayed output is available as an alarm feature to warn the
operator of a potentially dangerous situation.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

555

Section 8
Current protection
8.12.3

1MRK 502 066-UUS A

Function block

NS2PTOC (46I2)
I3P*
BLOCK
BLKST1
BLKST2
BLKTR

TRIP
TR1
TR2
START
ST1
ST2
ALARM
NSCURR
ANSI08000359.vsdx

ANSI08000359 V3 EN

Figure 250:

8.12.4

Signals
Table 262:
Name

NS2PTOC (46I2) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group connection for neg seq.

BLOCK

BOOLEAN

Block of function

BLK1

BOOLEAN

Block of step 1

BLK2

BOOLEAN

Block of step 2

BLKTR

BOOLEAN

Block of trip signals

Table 263:
Name

556

NS2PTOC (46I2) function block

NS2PTOC (46I2) Output signals


Type

Description

TRIP

BOOLEAN

Common trip signal

TRST1

BOOLEAN

Trip signal from step 1

TRST2

BOOLEAN

Trip signal from step 2

PICKUP

BOOLEAN

Common start signal

PU_ST1

BOOLEAN

Pick up signal from step 1

PU_ST2

BOOLEAN

Pick up signal from step 2

ALARM

BOOLEAN

Alarm signal

NSCURR

REAL

Negative sequence current in primary amps

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.12.5
Table 264:
Name

Settings
NS2PTOC (46I2) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

tAlarm

0.00 - 6000.00

0.01

3.00

Time delay for alarm ( operated by pick up


signal) in seconds

OpStep1

Disabled
Enabled

Enabled

Enable execution of step 1

I2-1>

3 - 500

%IB

10

Negative sequence current level for step 1 in %


of IBase

CurveType1

Definite
Inverse

Definite

Selection of definite or inverse time-characteri.


for step 1

t1

0.00 - 6000.00

0.01

10.00

Definite time delay for trip of step 1, in sec

tResetDef1

0.000 - 60.000

0.001

0.000

Time delay for reset of definite timer of step 1,


in sec

K1

1.0 - 99.0

0.1

10.0

Neg. seq. capability value of generator for step


1, in sec

t1Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves for


step 1

t1Max

0.00 - 6000.00

0.01

1000.00

Maximum trip delay for step 1, in sec

ResetMultip1

0.01 - 20.00

0.01

1.00

Reset multiplier for K1, defines reset time of


inverse curve

OpStep2

Disabled
Enabled

Enabled

Enable execution of step 2

I2-2>

3 - 500

%IB

10

Negative sequence current level for step 2 in %


of IBase

CurveType2

Definite
Inverse

Definite

Selection of definite or inverse time-characteri.


for step 2

t2

0.00 - 6000.00

0.01

10.00

Definite time delay for trip of step 2, in sec

tResetDef2

0.000 - 60.000

0.001

0.000

Time delay for reset of definite timer of step 2,


in sec

K2

1.0 - 99.0

0.1

10.0

Neg. seq. capability value of generator for step


2, in sec

t2Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves for


step 2

t2Max

0.00 - 6000.00

0.01

1000.00

Maximum trip delay for step 2, in sec

ResetMultip2

0.01 - 20.00

0.01

1.00

Reset multiplier for K2, defines reset time of


inverse curve

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

557

Section 8
Current protection

Table 265:
Name
GlobalBaseSel

8.12.6

1MRK 502 066-UUS A

NS2PTOC (46I2) Non group settings (basic)


Values (Range)
1 - 12

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 266:
Name
NSCURR

8.12.7

Unit

NS2PTOC (46I2) Monitored data


Type
REAL

Values (Range)
-

Unit
A

Description
Negative sequence current in
primary amps

Operation principle
The negative sequence time overcurrent protection for machines (NS2PTOC, 46I2)
function directly measures the amplitude of the negative phase sequence component of the
measured current. NS2PTOC (46I2) sets the PICKUP, PU_ST1 or PU_ST2 outputs active
and starts to count trip time only when the measured negative sequence current value rises
above the set value of parameters I2-1> or I2-2> respectively.
To avoid oscillation in the output signals, a certain hysteresis has been included. For both
steps, the reset ratio is 0.97.
Step 1 of NS2PTOC (46I2) can operate in the Definite Time (DT) or Inverse Time (IDMT)
mode depending on the selected value for the CurveType1 parameter. If CurveType1=
Definite, NS2PTOC (46I2) operates with a Definite Time Delay characteristic and if
CurveType1 = Inverse, NS2PTOC (46I2) operates with an Inverse Time Delay
characteristic. Step 2 is operating in an analogous way as Step 1.
Definite time delay is not dependent on the magnitude of measured negative sequence
current. Once the measured negative sequence current exceeds the set level, the settable
definite timer t1 or t2 respectively, starts to count and the corresponding trip signal gets
activated after the pre-set definite time delay has elapsed. Reset time in definite time mode
is determined by the setting parameters tResetDef1 or tResetDef2 respectively. If
NS2PTOC (46I2) has already picked up but not tripped and measured negative sequence
current goes below the pickup value, the pickup outputs remains active for the time
defined by the resetting parameters.
A BLOCK input signal resets NS2PTOC (46I2) momentarily.
When the parameter CurveType1 is set to Inverse, an inverse curve is selected according
to selected value for parameter K1. The minimum trip time setting of parameter t1Min and
reset time parameter ResetMultip1 also influence step operation. However, to match the

558

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

heating characteristics of the generator, the reset time is depending on the setting of
parameter K1, which must be set according to the generators negative sequence current
capacity.

K = I 2 2t
EQUATION2112 V1 EN

Where:
I2

is negative sequence current expressed in per unit of the rated generator current

is operating time in seconds

is a constant [s], which depends on generator size and design

Operate
time

t1Max
(Default= 1000 s)

t1Min
(Default= 5 s)

K1

Current I2-1>
IEC09000691-2-en.vsd
IEC09000691 V2 EN

Figure 251:

Inverse time characteristic with t1Min and t1Max

For a detailed description of inverse time characteristic, see chapter "Inverse


characteristics".
The reset time is exponential and is given by the following expression:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

559

Section 8
Current protection

1MRK 502 066-UUS A

ResetMultip
ResetTime [ s ] =
2

K1

I
NS

1
I Pickup

(Equation 140)

ANSIEQUATION2111 V1 EN

Where

8.12.7.1

INS

is the measured negative sequence current

IPickup

is the desired pickup level in pu of rated generator current

ResetMultip

is multiplier of the generator capability constant K equal to setting K1 and thus defines reset
time of inverse time characteristic

Pickup sensitivity
The trip pickup levels Current I2-1> and I2-2> of NS2PTOC (46I2) are freely settable
over a range of 3 to 500 % of rated generator current IBase. The wide range of pickup
setting is required in order to be able to protect generators of different types and sizes.
After pickup, a certain hysteresis is used before resetting pickup levels. For both steps the
reset ratio is 0.97.

8.12.7.2

Alarm function
The alarm function is operated by PICKUP signal and used to warn the operator for an
abnormal situation, for example, when generator continuous negative sequence current
capability is exceeded, thereby allowing corrective action to be taken before removing the
generator from service. A settable time delay tAlarm is provided for the alarm function to
avoid false alarms during short-time unbalanced conditions.

560

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.12.7.3

Logic diagram

0-t1
0

CurveType1=Definite

Negative sequence current

a
b

TRST1

OR

a>b

I2-1>

PU_ST1

AND
Inverse

Operation=Enabled

0-txMin
0

AND

BLK1
BLOCK
CurveType1=Inverse
ANSI08000466-4-en.vsd
ANSI08000466 V4 EN

Figure 252:

Simplified logic diagram for step 1 of Negative sequence time overcurrent


protection for machines (NS2PTOC, 46I2)

Step 2 for Negative sequence time overcurrent protection for machines (NS2PTOC, 46I2)
is similar to step 1.

PU_ST1
PU_ST2

PICKUP

OR

ALARM

0-tAlarm
0

TRST1
TRST2

TRIP

OR

ANSI09000690-3-en.vsd
ANSI09000690 V3 EN

Figure 253:

8.12.8

Simplified logic diagram for the PICKUP, ALARM and TRIP signals for
NS2PTOC (46I2)

Technical data
Table 267:

NS2PTOC (46I2) technical data

Function

Range or value

Accuracy

Trip current, step 1 - 2

(3-500)% of IBase

1.0% of In at I In
1.0% of I at I > In

Reset ratio

>95%

Trip time, pickup at 0 to 2 x Iset

Min. = 15 ms
Max. = 30 ms

Reset time, pickup at 2 to 0 x Iset

Min. = 15 ms
Max. = 30 ms

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

561

Section 8
Current protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Trip time, pickup at 0 to 10 x Iset

Min. = 5 ms
Max. = 20 ms

Reset time, pickup at 10 to 0 x Iset

Min. = 20 ms
Max. = 35 ms

Time characteristics

Definite or Inverse

Inverse time characteristic, step 1 - 2

K=1.0-99.0

2.0% or 40 ms whichever is
greater

Reset Multiplier = 0.01-20.00

5.0% or 40 ms whichever is
greater

Minimum trip time for inverse time


characteristic, step 1 - 2

(0.000-60.000) s

0.2% or 35 ms whichever is
greater

Maximum trip delay at 0.5 to 2 x Iset,


step 1 - 2

(0.00-6000.00) s

0.2% or 35 ms whichever is
greater

Independent time delay at 0.5 to 2 x


Iset, step 1 - 2

(0.00-6000.00) s

0.2% or 35 ms whichever is
greater

Independent time delay for Alarm at


0.5 to 2 x Iset

(0.00-6000.00) s

0.2% or 35 ms whichever is
greater

I2 t = K
Reset time, inverse characteristic,
step 1 - 2

I 22t = K

8.13

Accidental energizing protection for synchronous


generator AEGPVOC (50AE)

8.13.1

Identification
Function description
Accidental energizing protection for
synchronous generator

8.13.1.1

IEC 61850
identification
AEGPVOC

IEC 60617
identification
U<I>

ANSI/IEEE C37.2
device number
50AE

Functionality
Inadvertent or accidental energizing of off-line generators has occurred often enough due
to operating errors, breaker head flashovers, control circuit malfunctions, or a
combination of these causes. Inadvertently energized generator operates as induction
motor drawing a large current from the system. The voltage supervised overcurrent
protection is used to detect the inadvertently energized generator.
Accidental energizing protection for synchronous generator (AEGPVOC, 50AE) takes
the maximum phase current input and maximum phase to phase voltage inputs from the

562

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

terminal side. AEGPVOC (50AE) is enabled when the terminal voltage drops below the
specified voltage level for the preset time.

8.13.1.2

Function block
AEGPVOC (50AE)
I3P*
TRIP
U3P*
START
BLOCK
ARMED
BLKTR
ANSI13000302-1-en.vsd
ANSI13000302 V1 EN

Figure 254:

8.13.1.3

AEGPVOC (50AE) Function block

Signals
Table 268:

AEGPVOC (50AE) Input signals

Name

Type

Three Phase Current input

V3P

GROUP
SIGNAL

Three Phase Voltage input

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block of trip

AEGPVOC (50AE) Output signals

Name

Table 270:
Name

Description

GROUP
SIGNAL

Table 269:

8.13.1.4

Default

I3P

Type

Description

TRIP

BOOLEAN

Trip signal from accidental energizing of generator


protection

RI

BOOLEAN

Start signal from accidental energizing of generator


protection

ENABLED

BOOLEAN

True when accidental energizing of generator protection


is armed

Settings
AEGPVOC (50AE) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

IPickup

5 - 900

%IB

120

Phase current pickup in % of IBase

tOC

0.000 - 60.000

0.001

0.030

Trip time daly for overcurrent level

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

563

Section 8
Current protection

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

27_pick_up

2 - 150

%VB

50

Undervoltage level to arm protection in % of


Vbase

tArm

0.000 - 60.000

0.001

5.000

Time delay to arm protection with undervoltage


pickup

59_Drop_out

2 - 200

%VB

80

Over voltage level to disarm protection in % of


Vbase

tDisarm

0.000 - 60.000

0.001

0.500

Time delay to disarm protection when voltage


greater than drop out level

Table 271:
Name
GlobalBaseSel

8.13.1.5

AEGPVOC (50AE) Non group settings (basic)


Values (Range)
1 - 12

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 272:
Name

8.13.1.6

Unit

AEGPVOC (50AE) Monitored data


Type

Values (Range)

Unit

Description

IMAX

REAL

Maximum value of current

VMAX

REAL

kV

Maximum value of phase to


phase voltage

Operation principle
Accidental energizing protection for synchronous generator AEGPVOC (50AE) function
is connected to three phase current input either from the generator terminal side or from
generator neutral point side and three phase voltage from the generator terminals. The
maximum of the three phase-to-phase voltages and maximum of the three phase currents
are measured.
When the maximum phase-to-phase voltage is less than the 27_pick_up for the period
tArm, it is ensured that the generator is off-line. The Enabled signal will initiate the
overcurrent function. If the calculated maximum current of the three phases is larger than
IPickup for the period tOC then the TRIP signal becomes activated. Also PICKUP signal
becomes activated when overcurrent is detected.
When the maximum phase-to-phase voltage is larger than 59_Drop_out for a period
longer than tDisarm, it is ensured generator is on line. During this state, undervoltage
operation is disarmed, blocking the overcurrent operation and thus the function becomes
inoperative.

564

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

BLOCK input can be used to block AEGPVOC (50AE). In addition, the BLKTR input
that blocks the TRIP signal is also present. The input BLKTR can be used if AEGPVOC
(50AE) is to be used only for monitoring purposes.

Imax_DFT

a
a>b
b

IPickup

AND

Operation = Enabled
BLOCK

TRIP

0-tOC
0

RI

Enabled

Uph-ph_max_DFT
a
a<b
b

27_pick_up

0-tArm
0

AND

ON - Delay

a
a>b
b

59_Drop_out

0-tDisarm
0

OUT

NOUT

OR

ON - Delay
ANSI09000784-2-en.vsd
ANSI09000784 V2 EN

Figure 255:

8.13.1.7

AEGPVOC (50AE) logic diagram

Technical data
Table 273:

AEGPVOC (50AE) technical data

Function

Range or value

Accuracy

Trip value, overcurrent

(5-900)% of IBase

1.0% of In at IIn
1.0% of I at I>In

Reset ratio, overcurrent

>95% at (20900)% of IBase

Transient overreach,
overcurrent function

<10% at = 100 ms

Critical impulse time,


overcurrent

10 ms typically at 0 to 2 x Iset

Impulse margin time,


overcurrent

15 ms typically

Trip value, undervoltage

(2-150)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Critical impulse time,


undervoltage

10 ms typically at 2 to 0 x Vset

Impulse margin time,


undervoltage

15 ms typically

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

565

Section 8
Current protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Trip value, overvoltage

(2-200)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Definite time delay,


overcurrent, at 0 to 2 x Iset

(0.000-60.000) s

0.2% or 35 ms whichever is
greater

Definite time delay,


undervoltage, at 1.2 x Vset to
0.8 x Vset

(0.000-60.000) s

Less than 35 ms (0.2% or 35


ms, whichever is greater) at 1.2
x Vset to 0.8 x Vset

Definite time delay,


overvoltage, at 0.8 x Vset to
1.2 x Vset

(0.000-60.000) s

Less than 35 ms (0.2% or 35


ms, whichever is greater) at 0.8
x Vset to 1.2 x Vset

8.14

Voltage-restrained time overcurrent protection


VRPVOC (51V)

8.14.1

Identification
Function description
Voltage-restrained time overcurrent
protection

8.14.2

IEC 61850
identification
VRPVOC

IEC 60617
identification
I>/U<

ANSI/IEEE C37.2
device number
51V

Functionality
Voltage-restrained time overcurrent protection (VRPVOC, 51V) function can be used as
generator backup protection against short-circuits.
The overcurrent protection feature has a settable current level that can be used either with
definite time or inverse time characteristic. Additionally, it can be voltage controlled/
restrained.
One undervoltage step with definite time characteristic is also available within the
function in order to provide functionality for overcurrent protection with undervoltage
seal-in.

566

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.14.3

Function block
VRPVOC (51V)
I3P*
V3P*
BLOCK
BLKOC
BLKUV

TRIP
TROC
27 Trip
PICKUP
PU_OC
27 PU
ANSI14000056-1-en.vsd

ANSI12000184 V2 EN

Figure 256:

8.14.4

VRPVOC (51V) function block

Signals
Table 274:
Name

VRPVOC (51V) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three phase group signal for current inputs

V3P

GROUP
SIGNAL

Three phase group signal for voltage inputs

BLOCK

BOOLEAN

Block of function both stages

BLKOC

BOOLEAN

Block of voltage restraint overcurrent stage (ANSI 51V)

BLKUV

BOOLEAN

Block of under voltage function

Table 275:
Name

VRPVOC (51V) Output signals


Type

Description

TRIP

BOOLEAN

Common trip signal

TROC

BOOLEAN

Trip signal from voltage restrained overcurrent stage

27 Trip

BOOLEAN

Trip signal from undervoltage function

PICKUP

BOOLEAN

Common pickup signal

PU_OC

BOOLEAN

Pickup signal from voltage restrained overcurrent stage

27 PU

BOOLEAN

Pick up signal from undervoltage function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

567

Section 8
Current protection
8.14.5
Table 276:
Name

1MRK 502 066-UUS A

Settings
VRPVOC (51V) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

Pickup_Curr

2.0 - 5000.0

%IB

1.0

120.0

Pick up current level in % of IBase

Characterist

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time

IEC Norm. inv.

Time delay curve type for 51V Voltage


restrained overcurrent

tDef_OC

0.00 - 6000.00

0.01

0.50

Definite time delay for Over Current

0.05 - 999.00

0.01

1.00

Time multiplier for Inverse Definite Minimum


Time curves

t_MinTripDelay

0.00 - 60.00

0.01

0.05

Minimum operate time for Inverse Definite


Minimum Time curve

Operation_UV

Disabled
Enabled

Disabled

Operation of under-voltage stage (ANSI 27)


Off / On

PickUp_Volt

2.0 - 100.0

%VB

0.1

50.0

Voltage for pickup of under-voltage stage in %


of UBase

tDef_UV

0.00 - 6000.00

0.01

1.00

Definite time time delay when used for UnderVoltage

EnBlkLowV

Disabled
Enabled

Disabled

Enable internal low voltage level blocking for


Under-Voltage

BlkLowVolt

0.0 - 5.0

%VB

0.1

3.0

Internal low voltage level for blocking of UV in


% of VBase

Table 277:
Name

VRPVOC (51V) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

VDepMode

Step
Slope

Slope

Voltage dependent mode OC (step, slope)

VDepFact

5.0 - 100.0

0.1

25.0

Pick up current level in % of pickup when V<


25% of VBase

VHighLimit

30.0 - 100.0

%VB

0.1

100.0

Voltage high limit setting in % of VBase

568

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 278:
Name
GlobalBaseSel

8.14.6

VRPVOC (51V) Non group settings (basic)


Values (Range)
1 - 12

Unit

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 279:

VRPVOC (51V) Monitored data

Name

Type

Values (Range)

Unit

Description

IMAX

REAL

Maximum phase current


magnitude

VUMIN

REAL

kV

Minimum ph-to-ph voltage


magnitude

8.14.7

Operation principle

8.14.7.1

Measured quantities
The voltage-restrained time overcurrent protection VRPVOC (51V) function is always
connected to three-phase current and three-phase voltage input in the configuration tool
(ACT), but it will always measure the maximum of the three-phase currents and the
minimum of the three phase-to-phase voltages. If frequency tracking mode for
preprocessing blocks is used, then the function operates properly in wide frequency range
(e.g. 10-90 Hz).

8.14.7.2

Base quantities
GlobalBaseSel defines the particular Global Base Values Group where the base quantities
of the function are set. In that Global Base Values Group:
IBase shall be entered as rated phase current of the protected object in primary amperes.
VBase shall be entered as rated phase-to-phase voltage of the protected object in primary
kV.

8.14.7.3

Overcurrent protection
The overcurrent step simply compares the magnitude of the measured current quantity
with the set pickup level. The overcurrent step picks up if the magnitude of the measured
current quantity is higher than the set level.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

569

Section 8
Current protection

1MRK 502 066-UUS A

Voltage restraint/control feature


The overcurrent protection operation is made dependent of a measured voltage quantity.
This means that the pickup level of the overcurrent step is not constant but decreases with
the decrease in magnitude of the measured voltage quantity. This feature affects the
pickup current value of both definite time and inverse time IDMT overcurrent protection;
in particular the overcurrent with IDMT curve operates faster during low voltage
conditions. Two different types of dependencies are available:

Voltage restrained overcurrent (when setting parameter VDepMode = Slope); the


pickup level of the overcurrent stage changes according to the Figure 257. The
voltage restrained characteristic is defined by the two points: (0.25*VBase ;
VDepFact *Pickup_Curr/100*IBase) and (VHighLimit/100*VBase; Pickup_Curr/
100*IBase). In the first point the factor 0.25 that multiply VBase cannot be changed.
Pickup level of the current

PickupCurr

VDepFact * PickupCurr

0,25

VHighLimit

VBase

ANSI10000123-2-en.vsd
ANSI10000123 V2 EN

Figure 257:

570

Example for pickup level of the current variation as function of measured


voltage magnitude in Slope mode of operation

Voltage controlled overcurrent (when setting parameter VDepMode = Step); the


pickup level of the overcurrent stage changes according to the Figure 258.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Pickup level of the current

PickupCurr

VDepFact * PickupCurr

VHighLimit

VBase
ANSI10000124-2-en.vsd

ANSI10000124 V2 EN

Figure 258:

8.14.7.4

Example for pickup level of the current variation as function of measured


voltage magnitude in Step mode of operation

Logic diagram
DEF time
selected

MaxPhCurr

0-tDef_OC
0

OR

TROC

PU_OC

a>b

PickupCurr

Voltage
control or
restraint
feature

Inverse
Inverse
time
selected

MinPh-Ph Voltage

ANSI10000214-2-en.vsd
ANSI10000214 V2 EN

Figure 259:

Simplified internal logic diagram for overcurrent function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

571

Section 8
Current protection

1MRK 502 066-UUS A

DEF time
selected
MinPh-PhVoltage

0-tDef_UV
0

TRUV

b>a

PickupVolt

PU_UV

AND

Operation_UV=Disabled
BLKUV
ANSI10000213-2-en.vsd
ANSI10000213 V2 EN

Figure 260:

8.14.7.5

Simplified internal logic diagram for undervoltage function

Undervoltage protection
The undervoltage step simply compares the magnitude of the measured voltage quantity
with the set pickup level. The undervoltage step picks up if the magnitude of the measured
voltage quantity is lower than the set level.
The pickup signal starts a definite time delay. If the value of the pickup signal is one for
longer than the set time delay, the undervoltage step sets its trip signal to one.
This undervoltage functionality together with additional ACT logic can be used to provide
functionality for overcurrent protection with undervoltage seal-in.

8.14.8

Technical data
Table 280:

VRPVOC (51V) technical data

Function

Range or value

Accuracy

Pickup overcurrent

(2.0 - 5000.0)% of IBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio, overcurrent

> 95%

Trip time, pickup


overcurrent at 0 to 2 x Iset

Min. = 15 ms

Reset time, pickup


overcurrent at 2 to 0 x Iset

Min. = 15 ms

Trip time, pickup


overcurrent at 0 to 10 x Iset

Min. = 5 ms
Max. = 20 ms

Reset time, pickup


overcurrent at 10 to 0 x Iset

Min. = 20 ms
Max. = 35 ms

Max. = 30 ms
-

Max. = 30 ms

Table continues on next page


572

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Independent time delay to


trip at 0 to 2 x Iset

(0.00 - 6000.00) s

0.2% or 35 ms whichever is
greater

Inverse time
characteristics,
see tables 977 and 978

13 curve types

See tables 977 and 978

Minimum trip time for


inverse time characteristics

(0.00 - 60.00) s

0.2% or 35 ms whichever is
greater

High voltage limit, voltage


dependent operation

(30.0 - 100.0)% of VBase

1.0% of Vr

Pickup undervoltage

(2.0 - 100.0)% of VBase

0.5% of Vr

Reset ratio, undervoltage

< 105%

Trip time pickup


undervoltage at 2 to 0 x Vset

Min. = 15 ms

Reset time pickup


undervoltage at 0 to 2 x Vset

Min. = 15 ms

Max. = 30 ms
-

Max. = 30 ms

Independent time delay to


trip, undervoltage at 2 to 0 x
Vset

(0.00 - 6000.00) s

0.2% or 35 ms whichever is
greater

Internal low voltage


blocking

(0.0 - 5.0)% of VBase

0.25% of Vn

Overcurrent:
Critical impulse time
Impulse margin time

10 ms typically at 0 to 2 x Iset
15 ms typically

Undervoltage:
Critical impulse time
Impulse margin time

10ms typically at 2 to 0 x Vset


15 ms typically

8.15

Generator stator overload protection, GSPTTR (49S)

8.15.1

Identification
Function description
Generator stator overload protection

IEC 61850
identification
GSPTTR

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

IEC 60617
identification

ANSI/IEEE C37.2
device number
49S

573

Section 8
Current protection
8.15.2

1MRK 502 066-UUS A

Functionality
The generator overload function, GSPTTR (49S) is used to protect the stator winding
against excessive temperature as a result of overcurrents. The functions operating
characteristic is designed in accordance with the American standard IEEE-C50.13.
If internal generator components exceed its design temperature limit, damage can be the
result. Damage to generator insulation can range from minor loss of life to complete
failure, depending on the severity and duration of the temperature excursion. Excess
temperature can also cause mechanical damage due to thermal expansion. Since
temperature increases with current, it is logical to apply overcurrent elements with inverse
time characteristics.
For its operation the function either measures the true RMS current of the stator winding
or waited sum of the positive and negative sequence components in the stator winding.
The function is designed to work on 50/60 Hz systems.

8.15.3

Function block
GSPTTR (49S)
I3P*
TRIP
BLOCK
PICKUP
SETLKOUT
LOCKOUT
RSTLKOUT
79M BLOCK
ANSI14000051-1-en.vsd
ANSI12000027 V2 EN

Figure 261:

8.15.4

Signals
Table 281:
Name

574

GSPTTR (49S) function block

GSPTTR (49S) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Current Group Connection

BLOCK

BOOLEAN

Block of function

SETLKOUT

BOOLEAN

Input for forcing the output LOCKOUT

RSTLKOUT

BOOLEAN

Reset of the output LOCKOUT and theta to 0%

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 282:

GSPTTR (49S) Output signals

Name

8.15.5
Table 283:
Name

Type

Description

TRIP

BOOLEAN

General trip signal from the function

PICKUP

BOOLEAN

General pickup signal from the function

LOCKOUT

BOOLEAN

Trip lockout output (latched)

79M BLOCK

BOOLEAN

Block machine closing command

Settings
GSPTTR (49S) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

IPickup

105.0 - 900.0

0.1

110.0

Current pickup value for overload protection

ReclsLevTheta

1.0 - 100.0

0.1

70.0

Level for theta in percent below which the


generator can be reconnected to grid

TD1

1.00 - 200.00

0.01

37.50

Time multiplier for thermal charact. operate


time delay

AutoLockout

Disabled
Enabled

Disabled

Auto lockout enables activation of LOCKOUT


when TRIP is set

tPulse

0.5 - 10.0

0.1

1.0

Minimum pulse length of the trip signal

t_MinTripDelay

1.0 - 120.0

0.1

10.0

Minimum time, used in operate characteristic

t_MaxTripDelay

100.0 - 2000.0

0.1

300.0

Maximum time, used in operate characteristic

tCutOff

10.0 - 2000.0

0.1

120.0

Cut-off time, used in operate characteristic

tReset

10.0 - 2000.0

0.1

120.0

Time required for Theta to reset from 100% to


0%

Step

Default

Table 284:
Name

GSPTTR (49S) Group settings (advanced)


Values (Range)

Unit

Description

PosSeqFactor

0.0 - 10.0

0.1

1.0

Weighting factor for the positive sequence


current

NegSeqFactor

0.0 - 10.0

0.1

6.0

Weighting factor for the negative sequence


current

Table 285:
Name

GSPTTR (49S) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

MeasurCurrent

RMS
PosSeqNegSeq

RMS

Measured current quantity (RMS or weighted


sum of positive and negative sequence)

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

575

Section 8
Current protection
8.15.6

1MRK 502 066-UUS A

Monitored data
Table 286:

GSPTTR (49S) Monitored data

Name

8.15.7

Type

Values (Range)

Unit

Description

IMEAS

REAL

Measured current, used for


calculation of operate time

THETA

REAL

Overload in percent of set trip


level (i.e. Trip=100%)

Operation principle
The stator overload protection can be illustrated in three separate sub-blocks, see
Figure262.
block
Overload
characteristic

Current
measurement

Trip logic

IEC12000013-1-en.vsd
IEC12000013 V1 EN

Figure 262:

Representation of the stator overload protection

Current measurement
Three phase currents are measured either on the high voltage (HV) side of the generator
or on the neutral side of the stator winding, see Figure

576

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Step-up
transformer

HV- side
IA I B I C
Excitation
transformer

Two
alternative
measurement
points
for the stator
overload
function

Field breaker
Neutral side
ANSI12000012-2-en.vsd
ANSI12000012 V2 EN

Figure 263:

Measurement of stator current

The selection of current measurement is done by using the parameter MeasurCurrent::

When MeasurCurrent = RMS (default); the maximum true RMS current value from
the three-phase input currents is used as the measured quantity for the stator overload
protection.
When MeasurCurrent = PosSeqNegSeq; the weighted sum of positive and negative
sequence stator currents in primary amperes is used as the measured quantity for the
stator overload protection. This current value is calculated from the connected threephase input currents, see Figure.

The weighted sum of positive and negative sequence stator currents is calculated as per the
following equation.

I = PosSeqFactor I12 + NegSeqFactor I 22


GUID-8768BBBF-3EF7-4D4A-9FF6-DF4A07272812 V1 EN

(Equation 141)

Where:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

577

Section 8
Current protection

1MRK 502 066-UUS A

I is current value in primary amperes used by the overload function


I1 is stator positive sequence current in primary amperes
I2 is stator negative sequence current in primary amperes

PosSeqFactor is a setting factor to multiply the positive sequence current and its default value is 1.0
NegSeqFactor is a setting factor to multiply the negative sequence current and its default value is 6.0

The measured current used by the function is available as a service value.

Overload characteristics
Stator winding temperature increases with the current. Thus, it is logical to apply over
current elements with inverse time-current characteristics for overload protection. The
function operating characteristic is designed in accordance with the American standard
IEEE-C50.13. This standard specifies the following operating points:
Table 287:

Operate time in accordance with IEEE-C50.13 standard

Current (% of IBase)

Trip time (s)

116

120

130

60

154

30

226

10

In order to obtain such operating characteristic the stator overload function utilizes the
following formula in order to calculate the operate time:
ttr =

TD1
2

1
IBase

GUID-7CF0FE5A-F5CE-44EC-A2D7-F1E05849171C V1 EN

(Equation 142)

Where:
ttr is trip time in seconds
TD1 is a multiplier (it shall have default value of 41.4 in order to get the operating points as prescribed by the
standard, see Table287)
I is measured current by the function
IBase is base current (stator winding rated current)

578

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

In addition to this equation based operating characteristic, the stator overload function has
some additional cut-off features. The actual overall operating characteristic of the stator
overload function is shown in Figure264
t (s)

t_MaxTripDelay

tCutOff
t tr

TD1
I
IBase

t_MinTripDelay

I (A)
IBase IPickup

ANSI12000009-1-en.vsd

ANSI12000009 V1 EN

Figure 264:

Operating characteristic for overload function

As shown in Figure 264 it is possible to define the maximum (t_MaxTripDelay) and


minimum (t_MinTripDelay) operate time for the function regardless of the level of the
measured current. In addition to this it is also possible to specify the cut-off time below
which the IDMT curve defined by the above equation will be used. Note that tCutOff shall
be always set to the smaller value than t_MaxTripDelay.
The trip time of the stator overload function is calculated by using the integration principle
(see Chapter Inverse time characteristics in the Technical Manual for more
information). As a service value from the stator overload function regarding this
integration process the Theta parameter, proportional to the stator heating content, is
provided. This parameter has value of 100% when function gives the trip signal. Thus, in
simple words, it represent a percentage of the function trip level. As soon as the measured
current is above the pick-up level IPickup and no block signal is present, the output signal
PICKUP is activated and the Theta parameter is incremented following the inverse
characteristic given in Figure264. When Theta has reached value 100%, the output signal
TRIP is set. The minimum trip signal duration is defined by the parameter tPulse. Note
also that the 79M BLOCK signal will remain one as long as Theta > ReclsLevTheta. Thus

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

579

Section 8
Current protection

1MRK 502 066-UUS A

the parameter ReclsLevTheta represents the Theta value below which is safe again to reconnect the tripped generator to the network.
The output signal PICKUP will reset if the measured current falls below reset level or if
BLOCK signal is set to one. However the Theta value is stored in the IED memory and it
starts to decay slowly following a linear reset characteristic defined by the parameter
tReset. The parameter tReset actually defines the rest time for Theta from value 100 to
zero. Note that if an overload condition happens again, the last Theta value is used as a
starting point for the calculation. Thus the stator winding will be properly protected
against varying current levels.

580

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Imeasured

IBase * IPickup

Pickup hysteresis

t
THETA

100
ReclsLevTheta

TRIP

PICKUP
t
tReset

ANSI12000014-1-en.vsd
ANSI12000014 V1 EN

Figure 265:

Operating principles of the stator overload function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

581

Section 8
Current protection

1MRK 502 066-UUS A

Tripping logic
This tripping logic provides some additional features regarding blocking and tripping
options available within the function. The list below describes functionality of every
binary input and output from the function which influence the trip logic.
Available binary inputs:
BLOCK prevents operation of overload feature, at the same time all binary outputs are
forced to zero.
SETLKOUT forces lockout operation (output LOCKOUT) by external signal
RESET resets lockout and forces Theta value to zero
Available binary outputs:
TRIP, operation of the overload feature
PICKUP, current bigger than IPickup level
LOCKOUT, sealed-in TRIP output signal from the function. Note that lockout feature is
only enabled by setting AutoLockout = Enabled
79M BLOCK, output signal active as long as Theta > ReclsLevTheta, which can be used
to block closing of the generator CB
Simplified logic diagram for lockout functionality is shown in Figure266.

AutoLockout

TRIP

AND

OR

AND

AND

LOCKOUT

SETLKOUT
RESET

NOT

BLOCK
IEC12000010-1-en.vsd
IEC12000010 V1 EN

Figure 266:

582

Trip Lockout logic

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

8.15.8

Technical data
Table 288:

GSPTTR (49S) technical data

Function

Range or value

Current start level for overload


protection

(105.0900.0)% of IBase

Reset ratio

>95%

Start time at 0 to 2 x Iset

Min. = 50 ms

Accuracy
1.0% of Ir at I Ir
1.0% of I at I > Ir

Max. = 170 ms
Thermal time characteristic

According to
IEEE Std C50.132005

1.5% or 200 ms whichever is


greater

Minimum operate time for thermal


characteristic

(1.0120.0) s

1.5% or 200 ms whichever is


greater

Maximum operate time for


thermal characteristic

(100.02000.0) s

1.5% or 200 ms whichever is


greater

8.16

Generator rotor overload protection, GRPTTR (49R)

8.16.1

Identification
Function description
Generator rotor overload protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
49R

GRPTTR

<
SYMBOL-MM V1 EN

8.16.2

Functionality
The generator overload function, GRPTTR (49R) is used to protect the rotor winding
against excessive temperature as a result of overcurrents. The functions operating
characteristic is designed in accordance with the American standard IEEE-C50.13.
If internal generator components exceed its design temperature limit, damage can be the
result. Damage to generator insulation can range from minor loss of life to complete
failure, depending on the severity and duration of the temperature excursion. Excess
temperature can also cause mechanical damage due to thermal expansion. Rotor
components such as bars and end rings are vulnerable to this damage. Since temperature

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

583

Section 8
Current protection

1MRK 502 066-UUS A

increases with current, it is logical to apply overcurrent elements with inverse time
characteristics.
For its operation the function either measures the true RMS current of the excitation
transformer or calculates the DC current in the rotor winding. The rotor winding DC
current can be calculated from the AC currents measured on either high voltage side (HV)
or low voltage side (LV) side of the excitation transformer. For the HV side measurement
ratings of the excitation transformer shall be given. The use of the DC current is default
(i.e. recommended) measurement for generators with static excitation system. When the
DC current is used, the function can provide a DC current ripple alarm, due to possible
problem with the static excitation equipment. The rotor DC current can be also sent to the
plant supervisory system via communication channel or displayed on the IED built-in
HMI.
The function can also detect undercurrent condition in the rotor winding which indicates
either under-excitation or loss of excitation condition of the generator.
The function is designed to work on 50/60 Hz systems.

8.16.3

Function block
GRPTTR (49R)
I3P*
TRIP
BLOCK
37 TRIP
BLOCK37
PICKUP
SETLKOUT
37 PICKUP
RSTLKOUT
LOCKOUT
79M BLOCK
ALRIPPLE
IMEAS
ANSI14000050-1-en.vsd
ANSI12000028 V2 EN

Figure 267:

8.16.4

Signals
Table 289:
Name

584

GRPTTR (49R) function block

GRPTTR (49R) Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Current Group Connection

BLOCK

BOOLEAN

Block of function

BLOCK37

BOOLEAN

Block under-current protection feature

SETLKOUT

BOOLEAN

Input for forcing the output LOCKOUT

RSTLKOUT

BOOLEAN

Reset of the output LOCKOUT and theta to 0%

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Table 290:

GRPTTR (49R) Output signals

Name

8.16.5
Table 291:
Name

Type

Description

TRIP

BOOLEAN

General trip signal from the function

37 TRIP

BOOLEAN

Trip signal from under-current feature

PICKUP

BOOLEAN

General pickup signal from the function

37 PICKUP

BOOLEAN

Pickup from under-current feature

LOCKOUT

BOOLEAN

Trip lockout output (latched)

79M BLOCK

BOOLEAN

Block machine closing command

ALRIPPLE

BOOLEAN

Ripple alarm, is set (with delay-on 20ms) if


instRippleAlarm is active longer than tAlarmRipple

IMEAS

REAL

Measured current, used for calculation of operate time

Settings
GRPTTR (49R) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

IPickup

105.0 - 900.0

0.1

110.0

Current pickup value for overload protection

ReclsLevTheta

1.0 - 100.0

0.1

70.0

Level for theta in percent below which the


generator can be reconnected to grid

TD1

1.00 - 200.00

0.01

33.75

Time multiplier for thermal charact. operate


time delay

AutoLockout

Disabled
Enabled

Disabled

Auto lockout enables activation of LOCKOUT


when TRIP is set

tPulse

0.5 - 10.0

0.1

1.0

Minimum pulse length of the trip signal

t_MinTripDelay

1.0 - 120.0

0.1

10.0

Minimum time, used in operate characteristic

t_MaxTripDelay

100.0 - 2000.0

0.1

300.0

Maximum time, used in operate characteristic

tCutOff

10.0 - 2000.0

0.1

120.0

Cut-off time, used in operate characteristic

tReset

10.0 - 2000.0

0.1

120.0

Time required for Theta to reset from 100% to


0%

OpAlarmRipple

On
Disabled

Disabled

Operation Off / On of alarmRipple feature

AlmRippleLev

10.0 - 100.0

0.1

25.0

Alarm ripple level in percent

tAlarmRipple

0.1 - 600.0

0.1

5.0

Alarm ripple time, the alarm ripple has to be


active longer than the specified time to set
output al

37 Enable

Disabled
On

Disabled

Operation Off / On for under-current protection


feature

37 PICKUP

5.0 - 500.0

0.1

10.0

Under-current feature pickup level

37 trip delay

0.0 - 600.0

0.1

1.0

Under-current feature trip delay

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

585

Section 8
Current protection

Table 292:
Name

1MRK 502 066-UUS A

GRPTTR (49R) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

MeasurCurrent

RMS
DC

DC

Measured current quantity (RMS or Calculated


DC)

CT_Location

LV_winding
HV_winding

LV_winding

Excitation transformer winding where used CT


is located

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

VrLV

10.0 - 3000.0

0.1

400.0

Excitation transformer LV winding rated Ph-Ph


voltage in V

VrHV

0.10 - 100.00

kV

0.01

11.00

Excitation transformer HV winding rated Ph-Ph


voltage in kV

PhAngleShift

-180 - 180

Deg

30

30

Phase angle shift across excitation transformer


(degrees)

8.16.6

Monitored data
Table 293:
Name

8.16.7

GRPTTR (49R) Monitored data


Type

Values (Range)

Unit

Description

IMEAS

REAL

Measured current, used for


calculation of operate time

IDC

REAL

Average DC current value,


used for alarm and trip logic

THETA

REAL

Overload in percent of set trip


level (i.e. Trip=100%)

RIPPLVAL

REAL

DC ripple as percent of
measured DC current

Operation principle
The rotor overload protection GRPTTR (49R) can be illustrated in five separate subblocks, see Figure262.

586

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

block
Overload
characteristic

Current
measurement

Trip logic

block
Undercurrent
protection for rotor
winding

block
Alarm Ripple
Detection

IEC12000016-1-en.vsd
IEC12000016 V1 EN

Figure 268:

Representation of the rotor overload protection

Each of these five sub-blocks will be described in the following sections of this document.

Current measurement
Three phase currents are measured either on the high voltage side (HV) or on the low
voltage side (LV) of the excitation transformer, see Figure269.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

587

Section 8
Current protection

1MRK 502 066-UUS A

Step- up
transformer

Pri- side (HV)


IA IB IC
Excitation
transformer

VA

Va

Two alternative
measurement points
for the rotor overload
function

Sec- side(LV)
I a Ib I c

Field breaker
ANSI12000019-2-en.vsd
ANSI12000019 V2 EN

Figure 269:

Measurement of rotor currents

The selection of current measurement is done by using the parameter MeasurCurrent:

When MeasurCurrent = RMS; The maximum true RMS current value from the threephase input currents is used as the measured quantity for the rotor overload
protection.
MeasurCurrent = DC (default); The calculated rotor winding DC current in primary
amperes is used as the measured quantity for the rotor overload protection. The DC
current is calculated from the connected three-phase input currents, see Figure269.
This DC current calculation is valid for any type of three phase rectifier bridge (i.e.
either diode or thyristor based).

In order to properly calculate the rotor winding DC current the physical location of the
used CT is defined by the parameter CT_Location

588

When CT_Location = LV_winding (default) is selected, it means that the used CT is


located on the secondary, low-voltage side (LV) of the excitation transformer which
directly feeds into the rectifier bridge, see Figure269. In that case the rotor winding
instantaneous DC current iDC is calculated as per the following equation

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

iDC =

ia + ib + ic
2

GUID-8C279C3B-3CDE-47FA-ADD3-1E5CFD4F7536 V2 EN

(Equation 143)

where ia, ib and ic are instantaneous sampled values of the three-phase currents from LV
side of the excitation transformer. Note that this calculation is done twenty times per
power system cycle. After that the average DC current value IDC is calculated over one
power system cycle by using the following formula:
20

I DC =

DC

20

GUID-5D825381-66DE-404D-B3E9-471B13A394A5 V1 EN

(Equation 144)

The average DC current value IDC is used further within the rotor overload function for the
operating characteristic calculations and for the service value.

When CT_Location = HV_winding is selected, it means that the used CT is located


on the primary, high-voltage side (HV) of the excitation transformer, see Figure269.
In that case the measured HV side three-phase currents (IA, IB, IC) are first transferred
to the LV side currents (ia, ib, ic) by using the rating data of the excitation transformer.
The excitation transformer ratings are specified by the following three setting
parameters:
VrLV: LV winding rated ph-ph voltage in Volts.
VrHV: HV winding rated ph-ph voltage in kV.
PhAngleShift: HV side to LV side phase angle shift in degrees (it has value of +30 for Dy1 excitation
transformer and -30 for Dy11 excitation transformer)

Once the measured currents are transferred from the HV side to the LV side of the
excitation transformer the same calculations are performed as in case when CT is located
on the LV side.
The measured current used by the function is available as a service value.

Overload characteristics
Rotor winding temperature increases with the current. Thus, it is logical to apply over
current elements with inverse time-current characteristics for overload protection. The
function operating characteristic is designed in accordance with the American standard
IEEE-C50.13. This standard specifies the following operating points:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

589

Section 8
Current protection

1MRK 502 066-UUS A

Table 294:

Operate time in accordance with IEEE-C50.13 standard

Current (% of IBase)

Trip time (s)

113

120

125

60

146

30

209

10

In order to obtain such operating characteristic the rotor overload function utilizes the
following formula in order to calculate the operate time:
ttr =

TD1
2

1
IBase

GUID-7CF0FE5A-F5CE-44EC-A2D7-F1E05849171C V1 EN

(Equation 145)

Where:
ttr is triptime in seconds
TD1 is a multiplier (it shall have default value of 33.8 in order to get the operating points as prescribed by the
standard, see Table287)
I is measured current by the function
IBase is base current (rotor winding rated current when DC current is used as measured current)

In addition to this equation based operating characteristic, the rotor overload function has
some additional cut-off features. The actual overall operating characteristic of the rotor
overload function is shown in Figure270.

590

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

t (s)

t_MaxTripDelay

tCutOff
t tr

TD1
I
IBase

t_MinTripDelay

I (A)
IBase IPickup

ANSI12000011-1-en.vsd

ANSI12000011 V1 EN

Figure 270:

Operating characteristic for the overload function

As shown in Figure 270 it is possible to define the maximum (t_MaxTripDelay) and


minimum (t_MinTripDelay) trip time for the function regardless of the level of the
measured current. In addition to this it is also possible to specify the cut-off time below
which the IDMT curve defined by the above equation will be used. Note that tCutOff shall
be always set to the smaller value than t_MaxTripDelay.
The trip time of the rotor overload function is calculated by using the integration principle
(see Chapter Inverse time characteristics in the Technical Manual for more
information). As a service value from the rotor overload function regarding this
integration process the Theta parameter, proportional to the rotor heating content, is
provided. This parameter has value of 100% when function issues the trip signal. Thus, in
simple words, it represent a percentage of the function trip level. As soon as the measured
current is above the pick-up level IPickup and no block signal is present, the output signal
PICKUP is activated and the Theta parameter is incremented following the inverse
characteristic given in Figure 271. When theta has reached value 100%, the output signal
TRIP is set. The minimum trip signal duration is defined by the parameter tPulse. Note
also that the BLKRECL signal will remain one as long as Theta > ReclsLevTheta. Thus the
parameter ReclsLevTheta represents the Theta value below which is safe again to reconnect the tripped generator to the network.
The output signal PICKUP will reset if the measured current falls below reset level or if
BLOCK signal is set to one. However the Theta value is stored in the IED memory and it
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

591

Section 8
Current protection

1MRK 502 066-UUS A

starts to decay slowly following a linear reset characteristic defined by the parameter
tReset. The parameter tReset actually defines the rest time for Theta from value 100% to
zero. Note that if an overload condition happens again, the last theta value is used as a
starting point for the calculation. Thus the rotor winding will be properly protected against
varying current levels.

592

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Imeasured

IBase * IPickup

Pickup hysteresis

t
THETA

100
ReclsLevTheta

TRIP

PICKUP
t
tReset

ANSI12000015-1-en.vsd
ANSI12000015 V1 EN

Figure 271:

Operating principles of the rotor overload function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

593

Section 8
Current protection

1MRK 502 066-UUS A

Under current protection of rotor winding


One undercurrent protection level with definite time delay is available within the function.
It can be used to either alarm or trip for low-excitation/loss-of-excitation condition of the
machine. This built-in feature monitors the level of the measured current. As soon as it is
lower than the pre-set value (i.e. parameter 37 PICKUP) it will start a timer (i.e defined by
parameter 37 trip delay). Once this timer has expired the signal 37 TRIP will be given. In
order to avoid unwanted tripping of this undercurrent feature when machine is
disconnected from the network it shall be supervised by appropriate signal (e.g. blocked
when generator CB is open). Simplified logic diagram of this feature is given in
Figure272.

37 Enable
MeasurCurrent

<

37 PICKUP

37 trip delay
AND

37 TRIP

IBase

BLOCK37

NOT

BLOCK

NOT

ANSI12000021-1-en.vsd
ANSI12000021 V1 EN

Figure 272:

Undercurrent protection feature

Tripping logic
This tripping logic provides some additional features regarding blocking and tripping
options available within the function. The list below describes functionality of every
binary input and output from the function which influence the trip logic.
Available binary inputs:
BLOCK prevents operation of overload and undercurrent features, at the same time all
binary outputs are forced to zero.
BLOCK37 prevents operation of undercurrent feature only
SETLKOUT forces lockout operation (output LOCKOUT) by external signal
RESET resets lockout and forces Theta value to zero

594

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 8
Current protection

1MRK 502 066-UUS A

Available binary outputs:


TRIP, operation of the overload feature
37 TRIP, operation of the undercurrent feature
PICKUP, current bigger than IPickup level
37 PICKUP, current smaller than 37 PICKUP level
LOCKOUT, sealed-in TRIP output signal from the function. Note that lockout feature is
only enabled by setting AutoLockout = On
79M BLOCK, output signal active as long as Theta > ReclsLevTheta, which can be used
to block closing of the generator CB
Simplified logic diagram for lockout functionality is shown in Figure273.

AutoLockout

TRIP

AND

OR

AND

AND

LOCKOUT

SETLKOUT
RESET

NOT

BLOCK
IEC12000020-1-en.vsd
IEC12000020 V1 EN

Figure 273:

Trip Lockout logic

Alarm ripple detection


The rotor winding is provided with DC excitation current through the rectifier bridge and
the excitation transformer. In case a fault happens in the rectifier circuit, for example a
short circuit or broken diode/thyristor, the rotor system is endangered, due to asymmetry
in the three phase currents. This asymmetry will cause a ripple in the rotor DC current.
This alarm method estimates the ripple of the rotor DC current and if it exceed the preset
level (parameter AlmRippleLev) it will start a timer (defined by parameter tAlarmRipple).
Once this timer has expired the signal ALRIPPLE will be given.
The service value for the ripple level is provided. It is recommended to check the natural
ripple of the rotor DC current at site before the level for parameter AlmRippleLev is set.
Note that this ripple supervision shall only be used if the rotor DC current is used as
measured quantity.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

595

Section 8
Current protection
8.16.8

1MRK 502 066-UUS A

Technical data
Table 295:

GRPTTR (49R) technical data

Function

596

Range or value

Accuracy

Overcurrent start level for


overload protection

(105.0900.0)% of IBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio, overcurrent

>95%

Start time, overcurrent at 0 to 2 x


Iset

Min = 50 ms

Thermal time characteristic

According to
IEEE Std C50.132005

1.5% or 200 ms whichever is


greater

Minimum operate time for thermal


characteristic

(1.0120.0) s

1.5% or 200 ms whichever is


greater

Maximum operate time for


thermal characteristic

(100.02000.0) s

1.5% or 200 ms whichever is


greater

Undercurrent start level

(5.0500.0)% of IBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Start time, undercurrent at 2 to 0 x


Iset

Min = 15 ms

Independent time delay for


undercurrent function at 2 to 0 x
Iset

(0.0600.0) s

Max = 170 ms

Max = 30 ms
0.2% or 45 ms whichever is
greater

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Section 9

Voltage protection

9.1

Two step undervoltage protection UV2PTUV (27)

9.1.1

Identification
Function description
Two step undervoltage protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
27

UV2PTUV

3U<
SYMBOL-R-2U-GREATER-THAN
V2 EN

9.1.2

Functionality
Undervoltages can occur in the power system during faults or abnormal conditions. Two
step undervoltage protection (UV2PTUV, 27) function can be used to open circuit
breakers to prepare for system restoration at power outages or as long-time delayed backup to primary protection.
UV2PTUV (27) has two voltage steps, each with inverse or definite time delay.
UV2PTUV (27) has a high reset ratio to allow settings close to system service voltage.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

597

Section 9
Voltage protection
9.1.3

1MRK 502 066-UUS A

Function block
UV2PTUV (27)
V3P*
BLOCK
BLKTR1
BLK1
BLKTR2
BLK2

TRIP
TRST1
TRST1_A
TRST1_B
TRST1_C
TRST2
TRST2_A
TRST2_B
TRST2_C
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
PU_ST2_A
PU_ST2_B
PU_ST2_C
ANSI06000276-2-en.vsd

ANSI06000276 V2 EN

Figure 274:

9.1.4

UV2PTUV (27) function block

Signals
Table 296:
Name

UV2PTUV (27) Input signals


Type

Default

Description

V3P

GROUP
SIGNAL

Three phase voltages

BLOCK

BOOLEAN

Block of function

BLKTR1

BOOLEAN

Block of trip signal, step 1

BLK1

BOOLEAN

Block of step 1

BLKTR2

BOOLEAN

Block of trip signal, step 2

BLK2

BOOLEAN

Block of step 2

Table 297:
Name

UV2PTUV (27) Output signals


Type

Description

TRIP

BOOLEAN

Trip

TRST1

BOOLEAN

Common trip signal from step1

TRST1_A

BOOLEAN

Trip signal from step1 phase A

TRST1_B

BOOLEAN

Trip signal from step1 phase B

TRST1_C

BOOLEAN

Trip signal from step1 phase C

TRST2

BOOLEAN

Common trip signal from step2

TRST2_A

BOOLEAN

Trip signal from step2 phase A

Table continues on next page


598

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Name

9.1.5
Table 298:
Name

Type

Description

TRST2_B

BOOLEAN

Trip signal from step2 phase B

TRST2_C

BOOLEAN

Trip signal from step2 phase C

PICKUP

BOOLEAN

Common pickup signal

PU_ST1

BOOLEAN

Common pickup signal from step1

PU_ST1_A

BOOLEAN

Pickup signal from step1 phase A

PU_ST1_B

BOOLEAN

Pickup signal from step1 phase B

PU_ST1_C

BOOLEAN

Pickup signal from step1 phase C

PU_ST2

BOOLEAN

Common pickup signal from step2

PU_ST2_A

BOOLEAN

Pickup signal from step2 phase A

PU_ST2_B

BOOLEAN

Pickup signal from step2 phase B

PU_ST2_C

BOOLEAN

Pickup signal from step2 phase C

Settings
UV2PTUV (27) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OperationStep1

Disabled
Enabled

Enabled

Enable execution of step 1

Characterist1

Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve

Definite time

Selection of time delay curve type for step 1

OpMode1

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of 3, 2 of


3, 3 of 3) from step 1

Pickup1

1.0 - 100.0

%VB

0.1

70.0

Voltage pickup value (Definite-Time & InverseTime curve) in % of VBase, step 1

t1

0.00 - 6000.00

0.01

5.00

Definitive time delay of step 1

t1Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves for


step 1

TD1

0.05 - 1.10

0.01

0.05

Time dial multiplier for the inverse time delay


for step 1

IntBlkSel1

Disabled
Block of trip
Block all

Disabled

Internal (low level) blocking mode, step 1

IntBlkStVal1

1 - 50

%VB

20

Voltage setting for internal blocking in % of


VBase, step 1

tBlkUV1

0.000 - 60.000

0.001

0.000

Time delay of internal (low level) blocking for


step 1

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

599

Section 9
Voltage protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

HystAbs1

0.0 - 50.0

%VB

0.1

0.5

Absolute hysteresis in % of VBase, step 1

OperationStep2

Disabled
Enabled

Enabled

Enable execution of step 2

Characterist2

Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve

Definite time

Selection of time delay curve type for step 2

OpMode2

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of 3, 2 of


3, 3 of 3) from step 2

Pickup2

1.0 - 100.0

%VB

0.1

50.0

Voltage pickup value (Definite-Time & InverseTime curve) in % of VBase, step 2

t2

0.000 - 60.000

0.001

5.000

Definitive time delay of step 2

t2Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves for


step 2

TD2

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay for


step 2

IntBlkSel2

Disabled
Block of trip
Block all

Disabled

Internal (low level) blocking mode, step 2

IntBlkStVal2

1 - 50

%VB

20

Voltage setting for internal blocking in % of


VBase, step 2

tBlkUV2

0.000 - 60.000

0.001

0.000

Time delay of internal (low level) blocking for


step 2

HystAbs2

0.0 - 50.0

%VB

0.1

0.5

Absolute hysteresis in % of VBase, step 2

Table 299:
Name

UV2PTUV (27) Group settings (advanced)


Values (Range)

Unit

tReset1

0.000 - 60.000

Step
0.001

Default
0.025

Description
Reset time delay used in IEC Definite Time
curve step 1

ResetTypeCrv1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type for


step 1

tIReset1

0.000 - 60.000

0.001

0.025

Time delay in Inverse-Time reset (s), step 1

ACrv1

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 1

BCrv1

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 1

CCrv1

0.0 - 1.0

0.1

0.0

Parameter C for customer programmable


curve for step 1

DCrv1

0.000 - 60.000

0.001

0.000

Parameter D for customer programmable


curve for step 1

PCrv1

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

Table continues on next page


600

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

CrvSat1

0 - 100

Tuning param for prog. under voltage InverseTime curve, step 1

tReset2

0.000 - 60.000

0.001

0.025

Reset time delay used in IEC Definite Time


curve step 2

ResetTypeCrv2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of Time Delay reset curve for step 2

tIReset2

0.000 - 60.000

0.001

0.025

Time delay in Inverse-Time reset (s), step 2

ACrv2

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 2

BCrv2

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 2

CCrv2

0.0 - 1.0

0.1

0.0

Parameter C for customer programmable


curve for step 2

DCrv2

0.000 - 60.000

0.001

0.000

Parameter D for customer programmable


curve for step 2

PCrv2

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

CrvSat2

0 - 100

Tuning param for prog. under voltage InverseTime curve, step 2

Table 300:
Name

UV2PTUV (27) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ConnType

PhN DFT
PhPh RMS
PhN RMS
PhPh DFT

PhN DFT

Group selector for connection type

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

9.1.6

Monitored data
Table 301:
Name

UV2PTUV (27) Monitored data


Type

Values (Range)

Unit

Description

VA

REAL

kV

Voltage in phase A

VB

REAL

kV

Voltage in phase B

VC

REAL

kV

Voltage in phase C

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

601

Section 9
Voltage protection
9.1.7

1MRK 502 066-UUS A

Operation principle
Two-step undervoltage protection (UV2PTUV ,27) is used to detect low power system
voltage. UV2PTUV (27) has two voltage measuring steps with separate time delays. If
one, two or three phase voltages decrease below the set value, a corresponding PICKUP
signal is generated. UV2PTUV (27) can be set to PICKUP/TRIP based on 1 out of 3, 2 out
of 3 or 3 out of 3 of the measured voltages, being below the set point. If the voltage remains
below the set value for a time period corresponding to the chosen time delay, the
corresponding trip signal is issued. To avoid an unwanted trip due to disconnection of the
related high voltage equipment, a voltage controlled blocking of the function is available,
that is, if the voltage is lower than the set blocking level the function is blocked and no
PICKUP or TRIP signal is generated.The time delay characteristic is individually chosen
for each step and can be either definite time delay or inverse time delay.
UV2PTUV (27) can be set to measure phase-to-ground fundamental value, phase-tophase fundamental value, phase-to-ground true RMS value or phase-to-phase true RMS
value. The choice of the measuring is done by the parameter ConnType. The voltage
related settings are made in percent of base voltage which is set in kV phase-to-phase
voltage. This means operation for phase-to-ground voltage under:
Vpickup < (%) VBase(kV )
3
(Equation 146)

EQUATION1606 V1 EN

and operation for phase-to-phase voltage under:


Vpickup < (%) VBase(kV)
(Equation 147)

EQUATION1991-ANSI V1 EN

When phase-to-ground voltage measurement is selected the function


automatically introduces division of the base value by the square root of
three.

9.1.7.1

Measurement principle
Depending on the set ConnType value, UV2PTUV (27) measures phase-to-ground or
phase-to-phase voltages and compare against set values, Pickup1 and Pickup2. The
parameters OpMode1 and OpMode2 influence the requirements to activate the PICKUP
outputs. Either 1 out of 3, 2 out of 3, or 3 out of 3 measured voltages have to be lower than
the corresponding set point to issue the corresponding PICKUP signal.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.

602

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.1.7.2

Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse time
undervoltage (TUV). For the inverse time delay three different modes are available:

inverse curve A
inverse curve B
customer programmable inverse curve

The type A curve is described as:


t=

TD
Vpickup < -V
Vpickup <
(Equation 148)

ANSIEQUATION1431 V1 EN

where:
Vpickup
<

Set value for step 1 and step 2

Measured voltage

The type B curve is described as:


t=

TD 480

Vpickup < -V

- 0.5
32
Vpickup <

2.0

+ 0.055

EQUATION1608 V1 EN

(Equation 149)

The customer programmable curve can be created as:

TD A
+D
t=
P
Vpickup < -V

-C
B
Vpickup

EQUATION1609 V1 EN

(Equation 150)

When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to
compensate for this phenomenon. In the voltage interval Vpickup< down to Vpickup<

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

603

Section 9
Voltage protection

1MRK 502 066-UUS A

(1.0 CrvSatn/100) the used voltage will be: Vpickup< (1.0 CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:

CrvSatn
-C > 0
100
(Equation 151)

EQUATION1435 V1 EN

The lowest voltage is always used for the inverse time delay integration. The details of the
different inverse time characteristics are shown in section 25.3 "Inverse characteristics".
Figure 275:

Voltage used for the inverse time characteristic integration

Voltage

VA
VB
VC

IDMT Voltage

Time
ANSI12000186-1-en.vsd

Trip signal issuing requires that the undervoltage condition continues for at least the user
set time delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT)
and by some special voltage level dependent time curves for the inverse time mode
(TUV). If the pickup condition, with respect to the measured voltage ceases during the
delay time, and is not fulfilled again within a user defined reset time (tReset1 and tReset2
for the definite time and tIReset1 and tIReset2pickup for the inverse time) the
corresponding pickup output is reset. Here it should be noted that after leaving the
hysteresis area, the pickup condition must be fulfilled again and it is not sufficient for the
signal to only return back to the hysteresis area. Note that for the undervoltage function the
TUV reset time is constant and does not depend on the voltage fluctuations during the
drop-off period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer value is
linearly decreased during the reset time. See figure 276 and figure 277.

604

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

tIReset1
Voltage

tIReset1
PICKUP
HystAbs1

Measured
Voltage

TRIP

PICKUP1

Time
t

PICKUP
TRIP

Time
Integrator

Frozen Timer

Instantaneous

Linearly
decreased

Time
ANSI05000010-3-en.vsd

ANSI05000010 V3 EN

Figure 276:

Voltage profile not causing a reset of the pickup signal for step 1, and inverse time delay at different
reset types

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

605

Section 9
Voltage protection

1MRK 502 066-UUS A

tIReset1

Voltage
PICKUP

PICKUP

tIReset1
HystAbs1

Measured Voltage
TRIP

PICKUP 1

Time
t

PICKUP

TRIP

Time
Integrator

Frozen Timer

Time
Instantaneous

Linearly
decreased

ANSI05000011-2-en.vsd

ANSI05000011 V2 EN

Figure 277:

Voltage profile causing a reset of the pickup signal for step 1, and inverse time delay at different reset
types

Definite timer delay

606

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

When definite time delay is selected the function will trip as shown in figure 278. Detailed
information about individual stage reset/operation behavior is shown in figure 279 and
figure 280 respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the
definite time delayed stage is ensured.
PU_ST1
V
Pickup1

a
a<b

R tReset1

TRST1

t1
0

AND

ANSI09000785-3-en.vsd
ANSI09000785 V3 EN

Figure 278:

Detailed logic diagram for step 1, DT operation

Pickup1

PU_ST1

TRST1
tReset1

t1

ANSI10000039-3-en.vsd
ANSI10000039 V3 EN

Figure 279:

Example for Definite Time Delay stage1 reset

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

607

Section 9
Voltage protection

1MRK 502 066-UUS A

Pickup1

PU_ST1

TRST1

tReset1

t1

ANSI10000040-3-en.vsd
ANSI10000040 V3 EN

Figure 280:

9.1.7.3

Example for Definite Time Delay stage1 operation

Blocking
It is possible to block Two step undervoltage protection UV2PTUV (27) partially or
completely, by binary input signals or by parameter settings, where:
BLOCK:

blocks all outputs

BLKTR1:

blocks all trip outputs of step 1

BLK1:

blocks all pickup and trip outputs related to step 1

BLKTR2:

blocks all trip outputs of step 2

BLK2:

blocks all pickup and trip outputs related to step 2

If the measured voltage level decreases below the setting of IntBlkStVal1, either the trip
output of step 1, or both the trip and the PICKUP outputs of step 1, are blocked. The
characteristic of the blocking is set by the IntBlkSel1 parameter. This internal blocking can
also be set to Disabled resulting in no voltage based blocking. Corresponding settings and
functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will get very
low. The event will PICKUP both the under voltage function and the blocking function,
as seen in figure 281. The delay of the blocking function must be set less than the time
delay of under voltage function.

608

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Disconnection

Normal voltage
Pickup1
Pickup2

tBlkUV1 <
t1,t1Min
IntBlkStVal1

tBlkUV2 <
t2,t2Min

IntBlkStVal2
Time
Block step 1
Block step 2
en05000466_ansi.vsd
ANSI05000466 V1 EN

Figure 281:

9.1.7.4

Blocking function

Design
The voltage measuring elements continuously measure the three phase-to-neutral
voltages or the three phase-to-phase voltages. Recursive fourier filters or true RMS filters
of input voltage signals are used. The voltages are individually compared to the set value,
and the lowest voltage is used for the inverse time characteristic integration. A special
logic is included to achieve the 1 out of 3, 2 out of 3 and 3 out of 3 criteria to fulfill the
PICKUP condition. The design of Two step undervoltage protection UV2PTUV (27) is
schematically shown in Figure 282.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

609

Section 9
Voltage protection

1MRK 502 066-UUS A

VA

VB

VC

Comparator
VA < V1<
Comparator
VB < V1<
Comparator
VC < V1<

PU_ST1_A

Voltage Phase
Selector
OpMode1
1 out of 3
2 out of 3
3 out of 3

Phase 1

PU_ST1_B
Phase 2

Phase 3

IntBlkStVal1
PICKUP

MinVoltSelector

Time integrator
tIReset1
ResetTypeCrv1

Pickup
t1
t1Reset
&
Trip
Output
Logic

PU_ST1_C
PU_ST1

OR

TRST1_A

Step 1

TRST1_B

TRIP
TRST1_C
TRST1

OR

Comparator
VA < V2<
Comparator
VB < V2<
Comparator
VC < V2<

PU_ST2_A

Voltage Phase
Selector
OpMode2
1 out of 3
2 out of 3
3 out of 3
IntBlkStVal2

PICKUP

Phase 1

PU_ST2_B
Phase 2

Pickup
t2
Phase 3 t2Reset
&
Trip
Output
Logic

PU_ST2_C
PU_ST2

OR

TRST2_A

Step 2
MinVoltSelector

Time integrator
tIReset2
ResetTypeCrv2

TRST2_B
TRIP
TRST2_C
TRST2

OR

PICKUP
OR

OR

TRIP

ANSI05000012-3-en.vsd
ANSI05000012 V3 EN

Figure 282:

610

Schematic design of Two step undervoltage protection UV2PTUV (27)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.1.8

Technical data
Table 302:

UV2PTUV (27) technical data

Function

Range or value

Accuracy

Trip voltage, low and high


step

(1.0100.0)% of VBase

0.5% of Vn

Absolute hysteresis

(0.050.0)% of VBase

0.5% of Vn

Internal blocking level,


step 1 and step 2

(1.050.0)% of VBase

0.5% of Vn

Inverse time
characteristics for step 1
and step 2, see table 989

See table 989

Definite time delay, step 1


at 1.2 to 0 x Vset

(0.00-6000.00) s

less than 40 ms

Definite time delay, step 2


at 1.2 to 0 x Vset

(0.000-60.000) s

less than 40 ms

Minimum trip time, inverse


characteristics

(0.00060.000) s

0.5% or 40ms whichever is


greater

Trip time, pickup at 2 to 0 x


Vset

Min. = 15 ms
Max. = 30 ms

Reset time, pickup at 0 to 2


x Vset

Min. = 15 ms
Max. = 30 ms

Trip time, pickup at 1.2 to 0


x Vset

Min. = 5 ms
Max. = 25 ms

Reset time, pickup at 0 to


1.2 x Vset

Min. = 15 ms
Max. = 35 ms

Critical impulse time

5 ms typically at 1.2 to 0 x Vset

Impulse margin time

15 ms typically

9.2

Two step overvoltage protection OV2PTOV (59)

9.2.1

Identification
Function description
Two step overvoltage protection

IEC 61850
identification

IEC 60617 identification

ANSI/IEEE C37.2
device number
59

OV2PTOV

3U>
SYMBOL-C-2U-SMALLER-THAN V2 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

611

Section 9
Voltage protection
9.2.2

1MRK 502 066-UUS A

Functionality OV2PTOV
Overvoltages may occur in the power system during abnormal conditions such as sudden
power loss, tap changer regulating failures, and open line ends on long lines.
OV2PTOV (59) has two voltage steps, each of them with inverse or definite time delayed.
OV2PTOV (59) has a high reset ratio to allow settings close to system service voltage.

9.2.3

Function block
OV2PTOV (59)
V3P*
BLOCK
BLKTR1
BLK1
BLKTR2
BLK2

TRIP
TRST1
TRST1_A
TRST1_B
TRST1_C
TRST2
TRST2_A
TRST2_B
TRST2_C
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
PU_ST2_A
PU_ST2_B
PU_ST2_C
ANSI06000277-2-en.vsd

ANSI06000277 V2 EN

Figure 283:

9.2.4

Signals
Table 303:
Name

612

OV2PTOV (59) function block

OV2PTOV (59) Input signals


Type

Default

Description

V3P

GROUP
SIGNAL

Group signal for three phase voltage input

BLOCK

BOOLEAN

Block of function

BLKTR1

BOOLEAN

Block of trip signal, step 1

BLK1

BOOLEAN

Block of step 1

BLKTR2

BOOLEAN

Block of trip signal, step 2

BLK2

BOOLEAN

Block of step 2

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Table 304:

OV2PTOV (59) Output signals

Name

9.2.5
Table 305:
Name

Type

Description

TRIP

BOOLEAN

Trip

TRST1

BOOLEAN

Common trip signal from step1

TRST1_A

BOOLEAN

Trip signal from step1 phase A

TRST1_B

BOOLEAN

Trip signal from step1 phase B

TRST1_C

BOOLEAN

Trip signal from step1 phase C

TRST2

BOOLEAN

Common trip signal from step2

TRST2_A

BOOLEAN

Trip signal from step2 phase A

TRST2_B

BOOLEAN

Trip signal from step2 phase B

TRST2_C

BOOLEAN

Trip signal from step2 phase C

PICKUP

BOOLEAN

Common pickup signal

PU_ST1

BOOLEAN

Common pickup signal from step1

PU_ST1_A

BOOLEAN

Pickup signal from step1 phase A

PU_ST1_B

BOOLEAN

Pickup signal from step1 phase B

PU_ST1_C

BOOLEAN

Pickup signal from step1 phase C

PU_ST2

BOOLEAN

Common pickup signal from step2

PU_ST2_A

BOOLEAN

Pickup signal from step2 phase A

PU_ST2_B

BOOLEAN

Pickup signal from step2 phase B

PU_ST2_C

BOOLEAN

Pickup signal from step2 phase C

Settings
OV2PTOV (59) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OperationStep1

Disabled
Enabled

Enabled

Enable execution of step 1

Characterist1

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for step 1

OpMode1

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of 3, 2 of


3, 3 of 3) from step 1

Pickup1

1.0 - 200.0

%VB

0.1

120.0

Voltage pickup value (Definite-Time & InverseTime curve) in % of VBase, step 1

t1

0.00 - 6000.00

0.01

5.00

Definitive time delay of step 1

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

613

Section 9
Voltage protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

t1Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves for


step 1

TD1

0.05 - 1.10

0.01

0.05

Time dial multiplier for the inverse time delay


for step 1

HystAbs1

0.0 - 50.0

%VB

0.1

0.5

Absolute hysteresis in % of VBase, step 1

OperationStep2

Disabled
Enabled

Enabled

Enable execution of step 2

Characterist2

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for step 2

OpMode2

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of 3, 2 of


3, 3 of 3) from step 2

Pickup2

1.0 - 200.0

%VB

0.1

150.0

Voltage pickup value (Definite-Time & InverseTime curve) in % of VBase, step 2

t2

0.000 - 60.000

0.001

5.000

Definitive time delay of step 2

t2Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves for


step 2

TD2

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay for


step 2

HystAbs2

0.0 - 50.0

%VB

0.1

0.5

Absolute hysteresis in % of VBase, step 2

Table 306:
Name

Step

Default

Description

OV2PTOV (59) Group settings (advanced)


Values (Range)

Unit

tReset1

0.000 - 60.000

Step
0.001

Default
0.025

Description
Reset time delay used in IEC Definite Time
curve step 1

ResetTypeCrv1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type for


step 1

tIReset1

0.000 - 60.000

0.001

0.025

Time delay in Inverse-Time reset (s), step 1

ACrv1

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 1

BCrv1

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 1

CCrv1

0.0 - 1.0

0.1

0.0

Parameter C for customer programmable


curve for step 1

DCrv1

0.000 - 60.000

0.001

0.000

Parameter D for customer programmable


curve for step 1

PCrv1

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

CrvSat1

0 - 100

Tuning param for programmable over voltage


TOV curve, step 1

Table continues on next page


614

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

tReset2

0.000 - 60.000

0.001

0.025

Reset time delay used in IEC Definite Time


curve step 2

ResetTypeCrv2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of Time Delay reset curve for step 2

tIReset2

0.000 - 60.000

0.001

0.025

Time delay in Inverse-Time reset (s), step 2

ACrv2

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 2

BCrv2

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 2

CCrv2

0.0 - 1.0

0.1

0.0

Parameter C for customer programmable


curve for step 2

DCrv2

0.000 - 60.000

0.001

0.000

Parameter D for customer programmable


curve for step 2

PCrv2

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

CrvSat2

0 - 100

Tuning param for programmable over voltage


TOV curve, step 2

Table 307:
Name

Step

Default

Description

OV2PTOV (59) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ConnType

PhN DFT
PhPh DFT
PhN RMS
PhPh RMS

PhN DFT

Group selector for connection type

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

9.2.6

Monitored data
Table 308:
Name

9.2.7

OV2PTOV (59) Monitored data


Type

Values (Range)

Unit

Description

VA

REAL

kV

Voltage in phase A

VB

REAL

kV

Voltage in phase B

VC

REAL

kV

Voltage in phase C

Operation principle
Two step overvoltage protection OV2PTOV (59) is used to detect high power system
voltage. OV2PTOV (59) has two steps with separate time delays. If one-, two- or threephase voltages increase above the set value, a corresponding PICKUP signal is issued.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

615

Section 9
Voltage protection

1MRK 502 066-UUS A

OV2PTOV (59) can be set to PICKUP/TRIP, based on 1 out of 3, 2 out of 3 or 3 out of 3 of


the measured voltages, being above the set point. If the voltage remains above the set value
for a time period corresponding to the chosen time delay, the corresponding trip signal is
issued.
The time delay characteristic is individually chosen for the two steps and can be either,
definite time delay or inverse time delay.
The voltage related settings are made in percent of the global set base voltage VBase,
which is set in kV, phase-to-phase.
OV2PTOV (59) can be set to measure phase-to-ground fundamental value, phase-tophase fundamental value, phase-to-ground RMS value or phase-to-phase RMS value. The
choice of measuring is done by the parameter ConnType.
The setting of the analog inputs are given as primary phase-to-ground or phase-to-phase
voltage. OV2PTOV (59) will trip if the voltage gets higher than the set percentage of the
set base voltage VBase. This means operation for phase-to-ground voltage over:
Vpickup > (%) VBase(kV ) / 3
(Equation 152)

EQUATION1610 V2 EN

and operation for phase-to-phase voltage over:


Vpickup > (%) VBase(kV)
(Equation 153)

EQUATION1992 V1 EN

When phase-to-ground voltage measurement is selected the function


automatically introduces division of the base value by the square root of
three.

9.2.7.1

Measurement principle
All the three voltages are measured continuously, and compared with the set values,
Pickup1 for Step 1 and Pickup2 for Step 2. The parameters OpMode1 and OpMode2
influence the requirements to activate the PICKUP outputs. Either 1 out of 3, 2 out of 3 or
3 out of 3 measured voltages have to be higher than the corresponding set point to issue the
corresponding PICKUP signal.
To avoid oscillations of the output PICKUP signal, a hysteresis is included.

616

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.2.7.2

Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse time
delay (TOV). For the inverse time delay four different modes are available:

inverse curve A
inverse curve B
inverse curve C
customer programmable inverse curve

The type A curve is described as:


TD
V Vpickup >
Vpickup >

t=

(Equation 154)

EQUATION1625 V2 EN

where:
Vpickup
>

Set value for step 1 and step 2

Measured voltage

The type B curve is described as:


t=

TD 480
+ 0.035
V Vpickup >
0.5
32
Vpickup >
(Equation 155)

ANSIEQUATION2287 V3 EN

The type C curve is described as:


t=

TD 480
+ 0.035
V Vpickup >
32
0.5
Vpickup >
(Equation 156)

ANSIEQUATION2288 V2 EN

The customer programmable curve is defined by the below equation, where A, B, C, D, k


and p are settings:
t=

TD A

V - Vpickup

-C
B
Vpickup

+D

EQUATION1616 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

(Equation 157)

617

Section 9
Voltage protection

1MRK 502 066-UUS A

When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore, a tuning parameter CrvSatn is set to
compensate for this phenomenon. In the voltage interval Vpickup up to Vpickup (1.0 +
CrvSatn/100) the used voltage will be: Vpickup (1.0 + CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:

CrvSatn
-C > 0
100
(Equation 158)

EQUATION1435 V1 EN

The highest phase (or phase-to-phase) voltage is always used for the inverse time delay
integration, see figure 284. The details of the different inverse time characteristics are
shown in section "Inverse characteristics".
Voltage
IDMT Voltage

VA
VB
VC

Time
ANSI05000016-2-en.vsd
ANSI05000016 V2 EN

Figure 284:

Voltage used for the inverse time characteristic integration

Operation of the trip signal requires that the overvoltage condition continues for at least
the user set time delay. This time delay is set by the parameter t1 and t2 for definite time
mode (DT) and by selected voltage level dependent time curves for the inverse time mode
(TOV). If the PICKUP condition, with respect to the measured voltage ceases during the
delay time, and is not fulfilled again within a user defined reset time (tReset1 and tReset2
for the definite time and tIReset1 and tIReset2 for the inverse time) the corresponding
PICKUP output is reset, after that the defined reset time has elapsed. Here it should be
noted that after leaving the hysteresis area, the PICKUP condition must be fulfilled again
and it is not sufficient for the signal to only return back to the hysteresis area. The
hysteresis value for each step is settable HystAbsn (where n means either 1 or 2
respectively) to allow a high and accurate reset of the function. For OV2PTOV (59) the

618

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

TOV reset time is constant and does not depend on the voltage fluctuations during the
drop-off period. However, there are three ways to reset the timer: either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer value is
linearly decreased during the reset time.
tIReset1
tIReset1

Voltage
PICKUP

TRIP

PU_Overvolt1

HystAbs1

Measured
Voltage

Time
PICKUP

TRIP

Time
Integrator
Frozen Timer

Linearly
decreased

Instantaneous

Time
ANSI05000019-3-en.vsd

ANSI05000019 V3 EN

Figure 285:

Voltage profile not causing a reset of the PICKUP signal for step 1, and inverse time delay at different
reset types

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

619

Section 9
Voltage protection

1MRK 502 066-UUS A

tIReset1

Voltage
PICKUP

PICKUP

tIReset1
HystAbs1

TRIP

Pickup1
Measured Voltage

Time
t

PICKUP

TRIP

Time
Integrator

Frozen Timer

Time
Instantaneous

Linearly decreased

ANSI05000020-2-en.vsd

ANSI05000020 V2 EN

Figure 286:

Voltage profile causing a reset of the PICKUP signal for step 1, and inverse time delay at different reset
types

Definite time delay


When definite time delay is selected, the function will trip as shown in figure 287. Detailed
information about individual stage reset/operation behavior is shown in figure 279 and
figure 280 respectively. Note that by setting tResetn = 0.0s (where n means either 1 or 2
respectively), instantaneous reset of the definite time delayed stage is ensured.
620

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

PU_ST1

tReset1

a
a>b

Vpickup>

t1
t

TRST1
AND

b
OFF
Delay

ON
Delay

ANSI10000100-2-en.vsd
ANSI10000100 V2 EN

Figure 287:

Detailed logic diagram for step 1, definite time delay, DT operation

Pickup1

PICKUP

TRIP
tReset1

t1

ANSI10000037-2-en.vsd
ANSI10000037 V2 EN

Figure 288:

Example for step 1, Definite Time Delay stage 1 reset

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

621

Section 9
Voltage protection

1MRK 502 066-UUS A

Pickup1

PICKUP

TRIP

tReset1

t1

ANSI10000038-2-en.vsd
ANSI10000038 V2 EN

Figure 289:

9.2.7.3

Example for Definite Time Delay stage 1 operation

Blocking
It is possible to block Two step overvoltage protection OV2PTOV, (59) partially or
completely, by binary input signals where:

9.2.7.4

BLOCK:

blocks all outputs

BLKTR1:

blocks all trip outputs of step 1

BLK1:

blocks all pickup and trip outputs related to step 1

BLKTR2:

blocks all trip outputs of step 2

BLK2:

blocks all pickup and trip outputs related to step 2

Design
The voltage measuring elements continuously measure the three phase-to-ground
voltages or the three phase-to-phase voltages. Recursive Fourier filters or true RMS filters
of input voltage signals are used. The phase voltages are individually compared to the set
value, and the highest voltage is used for the inverse time characteristic integration. A
special logic is included to achieve the 1 out of 3, 2 out of 3 or 3 out of 3 criteria to fulfill the
PICKUP condition. The design of Two step overvoltage protection (OV2PTOV, 59) is
schematically described in figure 290.

622

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

VA

VB

VC

Comparator
VA >
Pickup 1
Comparator
VB >
Pickup 1
Comparator
VC >
Pickup 1

Voltage Phase
Selector
OpMode1
1 out of 3
2 out of 3
3 out of 3

PU_ST1_A

Phase A

PU_ST1_B
Phase B
Phase C

Phase C

PICKUP

Pickup
t1
t1Reset
&
Trip
Output
Logic

PU_ ST1_C
PU_ST1

OR

TRST1-A

Step1
MaxVoltSelect

Time integrator
tIReset1
ResetTypeCrv1

TRST1_B

TRIP

TRST1_C
TRST1

OR
Comparator
VA >
Pickup 2
Comparator
VB >
Pickup 2
Comparator
VC >
Pickup 2

Voltage Phase
Selector

Phase A

OpMode2
1 out of 3
2 out of 3
3 out of 3

Phase B
Phase C

PICKUP

MaxVoltSelect

Time integrator
tIReset2
ResetTypeCrv2

TRIP

PU_ST2_A
PU_ST2_B

Pickup
t2
t2Reset
&
Trip
Output
Logic

PU_ST2_C
PU_ST2

OR

TRST2-A

Step 2

TRST2-B
TRST2-C
TRST2

OR

OR PICKUP

OR

TRIP

ANSI05000013-2-en.vsd
_
.
ANSI05000013 V2 EN

Figure 290:

Schematic design of Two step overvoltage protection OV2PTOV (59)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

623

Section 9
Voltage protection
9.2.8

1MRK 502 066-UUS A

Technical data
Table 309:

OV2PTOV (59) technical data

Function

Range or value

Accuracy

Trip voltage, step 1


and 2

(1.0-200.0)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Absolute hysteresis

(0.050.0)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Inverse time
characteristics for
steps 1 and 2, see
table 988

See table 988

Definite time delay,


low step (step 1) at 0
to 1.2 x Vset

(0.00 - 6000.00) s

0.2% or 45 ms whichever is
greater

Definite time delay,


high step (step 2) at 0
to 1.2 x Vset

(0.000-60.000) s

0.2% or 45 ms whichever is
greater

Minimum trip time,


Inverse
characteristics

(0.000-60.000) s

0.2% or 45 ms whichever is greater

Trip time, pickup at 0


to 2 x Vset

Min. = 15 ms
Max. = 30 ms

Reset time, pickup at


2 to 0 x Vset

Min. = 15 ms
Max. = 30 ms

Trip time, pickup at 0


to 1.2 x Vset

Min. = 20 ms
Max. = 35 ms

Reset time, , pickup


at 1.2 to 0 x Vset

Min. = 5 ms
Max. = 25 ms

Critical impulse time

10 ms typically at 0 to 2 x Vset

Impulse margin time

15 ms typically

9.3

Two step residual overvoltage protection ROV2PTOV


(59N)

9.3.1

Identification
Function description
Two step residual overvoltage
protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
59N

ROV2PTOV

3U0
TRV V1 EN

624

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.3.2

Functionality
Residual voltages may occur in the power system during ground faults.
Two step residual overvoltage protection ROV2PTOV (59N) function calculates the
residual voltage from the three-phase voltage input transformers or measures it from a
single voltage input transformer fed from a broken delta or neutral point voltage
transformer.
ROV2PTOV (59N) has two voltage steps, each with inverse or definite time delay.
Reset delay ensures operation for intermittent ground faults.

9.3.3

Function block
ROV2PTOV (59N)
V3P*
TRIP
BLOCK
TRST1
BLKTR1
TRST2
BLK1
PICKUP
BLKTR2
PU_ST1
BLK2
PU_ST2
ANSI06000278-2-en.vsd
ANSI06000278 V2 EN

Figure 291:

9.3.4

ROV2PTOV (59N) function block

Signals
Table 310:
Name

ROV2PTOV (59N) Input signals


Type

Default

Description

V3P

GROUP
SIGNAL

Three phase voltages

BLOCK

BOOLEAN

Block of function

BLKTR1

BOOLEAN

Block of trip signal, step 1

BLK1

BOOLEAN

Block of step 1

BLKTR2

BOOLEAN

Block of trip signal, step 2

BLK2

BOOLEAN

Block of step 2

Table 311:
Name

ROV2PTOV (59N) Output signals


Type

Description

TRIP

BOOLEAN

Trip

TRST1

BOOLEAN

Common trip signal from step1

TRST2

BOOLEAN

Common trip signal from step2

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

625

Section 9
Voltage protection

1MRK 502 066-UUS A

Name

9.3.5
Table 312:
Name

Type

Description

PICKUP

BOOLEAN

Common pickup signal

PU_ST1

BOOLEAN

Common pickup signal from step1

PU_ST2

BOOLEAN

Common pickup signal from step2

Settings
ROV2PTOV (59N) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OperationStep1

Disabled
Enabled

Enabled

Enable execution of step 1

Characterist1

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for step 1

Pickup1

1.0 - 200.0

%VB

0.1

30.0

Voltage setting/pickup value (DT & TOV), step


1 in % of VBase

t1

0.00 - 6000.00

0.01

5.00

Definitive time delay of step 1

t1Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves for


step 1

TD1

0.05 - 1.10

0.01

0.05

Time dial multiplier for the inverse time delay


for step 1

HystAbs1

0.0 - 50.0

%VB

0.1

0.5

Absolute hysteresis in % of VBase, step 1

OperationStep2

Disabled
Enabled

Enabled

Enable execution of step 2

Characterist2

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for step 2

Pickup2

1.0 - 100.0

%VB

0.1

45.0

Voltage setting/pickup value (DT & TOV), step


2 in % of VBase

t2

0.000 - 60.000

0.001

5.000

Definitive time delay of step 2

t2Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves for


step 2

TD2

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay for


step 2

HystAbs2

0.0 - 50.0

%VB

0.1

0.5

Absolute hysteresis in % of VBase, step 2

626

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Table 313:
Name

ROV2PTOV (59N) Group settings (advanced)


Values (Range)

Unit

tReset1

0.000 - 60.000

0.001

0.025

Reset time delay used in IEC Definite Time


curve step 1

ResetTypeCrv1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type for


step 1

tIReset1

0.000 - 60.000

0.001

0.025

Time delay in Inverse-Time reset (s), step 1

ACrv1

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 1

BCrv1

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 1

CCrv1

0.0 - 1.0

0.1

0.0

Parameter C for customer programmable


curve for step 1

DCrv1

0.000 - 60.000

0.001

0.000

Parameter D for customer programmable


curve for step 1

PCrv1

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

CrvSat1

0 - 100

Tuning param for programmable over voltage


TOV curve, step 1

tReset2

0.000 - 60.000

0.001

0.025

Time delay in Definite-Time reset (s), step 2

ResetTypeCrv2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of Time Delay reset curve for step 2

tIReset2

0.000 - 60.000

0.001

0.025

Time delay in Inverse-Time reset (s), step 2

ACrv2

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 2

BCrv2

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 2

CCrv2

0.0 - 1.0

0.1

0.0

Parameter C for customer programmable


curve for step 2

DCrv2

0.000 - 60.000

0.001

0.000

Parameter D for customer programmable


curve for step 2

PCrv2

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

CrvSat2

0 - 100

Tuning param for programmable over voltage


TOV curve, step 2

Table 314:
Name
GlobalBaseSel

Step

Default

Description

ROV2PTOV (59N) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description
Selection of one of the Global Base Value
groups

627

Section 9
Voltage protection
9.3.6

1MRK 502 066-UUS A

Monitored data
Table 315:

ROV2PTOV (59N) Monitored data

Name

Type

VLevel

9.3.7

Values (Range)

REAL

Unit
kV

Description
Magnitude of measured
voltage

Operation principle
Two step residual overvoltage protection ROV2PTOV (59N) is used to detect high singlephase voltage, such as high residual voltage, also called 3V0. The residual voltage can be
measured directly from a voltage transformer in the neutral of a power transformer or from
a three-phase voltage transformer, where the secondary windings are connected in an open
delta. Another possibility is to measure the three-phase voltages and internally in the IED
calculate the corresponding residual voltage and connect this calculated residual voltage
to ROV2PTOV (59N). ROV2PTOV (59N) has two steps with separate time delays. If the
single-phase (residual) voltage remains above the set value for a time period
corresponding to the chosen time delay, the corresponding TRIP signal is issued.
The time delay characteristic is individually chosen for the two steps and can be either,
definite time delay or inverse time delay.
The voltage related settings are made in percent of the base voltage, which is set in kV,
phase-phase.

9.3.7.1

Measurement principle
The residual voltage is measured continuously, and compared with the set values, Pickup1
and Pickup2.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.

9.3.7.2

Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse time
delay (TOV). For the inverse time delay four different modes are available:

inverse curve A
inverse curve B
inverse curve C
customer programmable inverse curve

The type A curve is described as:


628

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

t=

TD
V - Vpickup >

Vpickup >
(Equation 159)

ANSIEQUATION2422 V1 EN

where:
Vn>

Set value for step 1 and step 2

Measured voltage

The type B curve is described as:


t=

TD 480

V - Vpickup >
- 0.5
32
Vpickup >

2.0

- 0.035

(Equation 160)

ANSIEQUATION2423 V1 EN

The type C curve is described as:


t=

TD 480

V - Vpickup >
- 0.5
32
Vpickup >

3.0

+ 0.035

(Equation 161)

ANSIEQUATION2421 V1 EN

The customer programmable curve can be created as:


t=

TD A

V - Vpickup

-C
B
Vpickup

+D

EQUATION1616 V1 EN

(Equation 162)

When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to
compensate for this phenomenon. In the voltage interval Vpickup up to Vpickup (1.0 +
CrvSatn/100) the used voltage will be: Vpickup (1.0 + CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:

CrvSatn
-C > 0
100

EQUATION1440 V1 EN

(Equation 163)

The details of the different inverse time characteristics are shown in section "Inverse
characteristics".

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

629

Section 9
Voltage protection

1MRK 502 066-UUS A

TRIP signal issuing requires that the residual overvoltage condition continues for at least
the user set time delay. This time delay is set by the parameter t1 and t2 for definite time
mode (DT) and by some special voltage level dependent time curves for the inverse time
mode (TOV).
If the PICKUP condition, with respect to the measured voltage ceases during the delay
time, and is not fulfilled again within a user defined reset time (tReset1 and tReset2 for the
definite time and tIReset1 and tIReset2 for the inverse time) the corresponding PICKUP
output is reset, after the defined reset time has elapsed.
Here it should be noted that after leaving the hysteresis area, the PICKUP condition must
be fulfilled again and it is not sufficient for the signal to only return back to the hysteresis
area. Also notice that for the overvoltage function TOV reset time is constant and does not
depend on the voltage fluctuations during the drop-off period. However, there are three
ways to reset the timer, either the timer is reset instantaneously, or the timer value is frozen
during the reset time, or the timer value is linearly decreased during the reset time. See
figure 285 and figure 286.

630

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

tIReset1
tIReset1

Voltage
PICKUP

TRIP

PU_Overvolt1

HystAbs1

Measured
Voltage

Time
PICKUP

TRIP

Time
Integrator
Frozen Timer

Linearly
decreased

Time

Instantaneous

ANSI05000019-3-en.vsd
ANSI05000019 V3 EN

Figure 292:

Voltage profile not causing a reset of the PICKUP signal for step 1, and inverse time delay

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

631

Section 9
Voltage protection

1MRK 502 066-UUS A

tIReset1

Voltage
PICKUP

PICKUP

tIReset1
HystAbs1

TRIP

Pickup1
Measured Voltage

Time
t

PICKUP

TRIP

Time
Integrator

Frozen Timer

Time
Instantaneous

Linearly decreased

ANSI05000020-2-en.vsd

ANSI05000020 V2 EN

Figure 293:

Voltage profile causing a reset of the PICKUP signal for step 1, and inverse time delay

Definite timer delay


When definite time delay is selected, the function will trip as shown in figure 294. Detailed
information about individual stage reset/operation behavior is shown in figure 279 and
figure 280 respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the
definite time delayed stage is ensured.

632

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

PU_ST1

tReset1

a
a>b

Vpickup>

t1
t

TRST1
AND

b
OFF
Delay

ON
Delay

ANSI10000100-2-en.vsd
ANSI10000100 V2 EN

Figure 294:

Detailed logic diagram for step 1, Definite time delay, DT operation

Pickup1

PICKUP

TRIP
tReset1

t1

ANSI10000037-2-en.vsd
ANSI10000037 V2 EN

Figure 295:

Example for Definite Time Delay stage 1 reset

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

633

Section 9
Voltage protection

1MRK 502 066-UUS A

Pickup1

PICKUP

TRIP

tReset1

t1

ANSI10000038-2-en.vsd
ANSI10000038 V2 EN

Figure 296:

9.3.7.3

Example for Definite Time Delay stage 1 operation

Blocking
It is possible to block Two step residual overvoltage protection ROV2PTOV (59N)
partially or completely, by binary input signals where:

9.3.7.4

BLOCK:

blocks all outputs

BLKTR1:

blocks all trip outputs of step 1

BLK1:

blocks all pickup and trip outputs related to step 1

BLKTR2:

blocks all trip outputs of step 2

BLK2:

blocks all pickup and trip inputs related to step 2

Design
The voltage measuring elements continuously measure the residual voltage. Recursive
Fourier filters filter the input voltage signal for the rated frequency. The single input
voltage is compared to the set value, and is also used for the inverse time characteristic
integration. The design of Two step residual overvoltage protection (ROV2PTOV, 59N)
is schematically described in figure 297.

634

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

VN

Comparator
VN >
Pickup 1

Phase 1

PICKUP
Time integrator
tIReset1
ResetTypeCrv1

Comparator
VN >
Pickup2

TRIP

TRST1

Pickup
t1
tReset1
&
Trip
Output
Logic
Step 1

PU_ST2

Phase 1

PICKUP
Time integrator
tIReset2
ResetTypeCrv2

PU_ ST1

TRIP

TRST2

Pickup
t2
tReset2
&
Trip
Output
Logic
Step 2

OR

PICKUP

OR

TRIP

ANSI05000748-2-en.vsd
ANSI05000748 V2 EN

Figure 297:

9.3.8

Schematic design of Two step residual overvoltage protection


ROV2PTOV (59N)

Technical data
Table 316:

ROV2PTOV (59N) technical data

Function

Range or value

Accuracy

Trip voltage, step 1 and


step 2

(1.0-200.0)% of VBase

0.5% of Vn at V < Vn
0.5% of Vn at V > Vn

Absolute hysteresis

(0.050.0)% of VBase

0.5% of Vn at V < Vn
0.5% of Vn at V > Vn

Inverse time
characteristics for low
and high step, see
table 990

See table 990

Definite time delay low


step (step 1) at 0 to 1.2
x Vset

(0.006000.00) s

0.2% or 45 ms whichever is
greater

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

635

Section 9
Voltage protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Definite time delay high


step (step 2) at 0 to 1.2
x Vset

(0.00060.000) s

0.2% or 45 ms whichever is
greater

Minimum trip time

(0.000-60.000) s

0.2% or 45 ms whichever is
greater

Trip time, pickup at 0 to


2 x Vset

Min. = 15 ms
Max. = 30 ms

Reset time, pickup at 2


to 0 x Vset

Min. = 15 ms
Max. = 30 ms

Trip time, pickup at 0 to


1.2 x Vset

Min. = 20 ms
Max. = 35 ms

Reset time, pickup at


1.2 to 0 x Vset

Min. = 5 ms
Max. = 25 ms

Critical impulse time

10 ms typically at 0 to 2 x Vset

Impulse margin time

15 ms typically

9.4

Overexcitation protection OEXPVPH (24)

9.4.1

Identification
Function description
Overexcitation protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
24

OEXPVPH

U/f >
SYMBOL-Q V1 EN

9.4.2

Functionality
When the laminated core of a power transformer or generator is subjected to a magnetic
flux density beyond its design limits, stray flux will flow into non-laminated components
that are not designed to carry flux. This will cause eddy currents to flow. These eddy
currents can cause excessive heating and severe damage to insulation and adjacent parts
in a relatively short time. The function has settable inverse operating curves and
independent alarm stages.

636

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.4.3

Function block
OEXPVPH (24)
I3P*
V3P*
BLOCK
RESET

TRIP
PICKUP
ALARM

ANSI05000329-2-en.vsd
ANSI05000329 V2 EN

Figure 298:

9.4.4

OEXPVPH (24) function block

Signals
Table 317:

OEXPVPH (24) Input signals

Name

Type
GROUP
SIGNAL

Current connection

V3P

GROUP
SIGNAL

Voltage connection

BLOCK

BOOLEAN

Block of function

RESET

BOOLEAN

Reset operation

OEXPVPH (24) Output signals

Name

Table 319:
Name

Description

I3P

Table 318:

9.4.5

Default

Type

Description

TRIP

BOOLEAN

Trip from overexcitation function

PICKUP

BOOLEAN

Overexcitation above set trip pickup (instantaneous)

ALARM

BOOLEAN

Overexcitation above set alarm pickup (delayed)

Settings
OEXPVPH (24) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

Pickup1

100.0 - 180.0

%VB/f

0.1

110.0

Operate level of V/Hz at no load and rated freq


in % of (UBase/frated)

Pickup2

100.0 - 200.0

%VB/f

0.1

140.0

High level of V/Hz above which tMin is used, in


% of (VBase/frated)

XLeakage

0.000 - 200.000

Ohm

0.001

0.000

Winding leakage reactance in primary ohms

t_TripPulse

0.000 - 60.000

0.001

0.100

Length of the pulse for trip signal (in sec)

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

637

Section 9
Voltage protection

Name

1MRK 502 066-UUS A

Values (Range)

Unit

t_MinTripDelay

0.000 - 60.000

0.001

7.000

Minimum trip delay for V/Hz inverse curve, in


sec

t_MaxTripDelay

0.00 - 9000.00

0.01

1800.00

Maximum trip delay for V/Hz inverse curve, in


sec

t_CoolingK

0.10 - 9000.00

0.01

1200.00

Transformer magnetic core cooling time


constant, in sec

CurveType

IEEE
Tailor made

IEEE

Inverse time curve selection, IEEE/Tailor made

TDForIEEECurve

1 - 60

Time multiplier for IEEE inverse type curve

AlarmPickup

50.0 - 120.0

0.1

100.0

Alarm pickup level as % of Step1 trip pickup


level

tAlarm

0.00 - 9000.00

0.01

5.00

Alarm time delay, in sec

Default

Table 320:
Name

Step

Default

Description

OEXPVPH (24) Group settings (advanced)


Values (Range)

Unit

Step

t1_UserCurve

0.00 - 9000.00

0.01

7200.00

Time delay t1 (longest) for tailor made curve, in


sec

t2_UserCurve

0.00 - 9000.00

0.01

3600.00

Time delay t2 for tailor made curve, in sec

t3_UserCurve

0.00 - 9000.00

0.01

1800.00

Time delay t3 for tailor made curve, in sec

t4_UserCurve

0.00 - 9000.00

0.01

900.00

Time delay t4 for tailor made curve, in sec

t5_UserCurve

0.00 - 9000.00

0.01

450.00

Time delay t5 for tailor made curve, in sec

t6_UserCurve

0.00 - 9000.00

0.01

225.00

Time delay t6 (shortest) for tailor made curve,


in sec

Step

Default

Table 321:
Name

Description

OEXPVPH (24) Non group settings (basic)


Values (Range)

Unit

Description

MeasuredV

PosSeq
AB
BC
CA

AB

Selection of measured voltage

MeasuredI

AB
BC
CA
PosSeq

AB

Selection of measured current

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

638

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.4.6

Monitored data
Table 322:

OEXPVPH (24) Monitored data

Name

9.4.7

Type

Values (Range)

Unit

Description

TMTOTRIP

REAL

Calculated time to trip for


overexcitation, in sec

VPERHZ

REAL

V/Hz

Voltage to frequency ratio in


per-unit

THERMSTA

REAL

Overexcitation thermal status


in % of trip pickup

Operation principle
The importance of Overexcitation protection (OEXPVPH, 24) function is growing as the
power transformers as well as other power system elements today operate near their
designated limits most of the time.
Modern design transformers are more sensitive to overexcitation than earlier types. This
is a result of the more efficient designs and designs which rely on the improvement in the
uniformity of the excitation level of modern systems. If an emergency that causes
overexcitation does occur, transformers may be damaged unless corrective action is taken.
Transformer manufacturers recommend an overexcitation protection as a part of the
transformer protection system.
Overexcitation results from excessive applied voltage, possibly in combination with
below-normal frequency. Such conditions may occur when a transformer unit is loaded,
but are more likely to arise when the transformer is unloaded, or when loss of load occurs.
Transformers directly connected to generators are in particular danger to experience
overexcitation conditions. It follows from the fundamental transformer equation, see
equation 164, that the peak flux density Bmax is directly proportional to induced voltage
E, and inversely proportional to frequency f and turns n.
E = 4.44 f n B max A
(Equation 164)

EQUATION898 V2 EN

The relative excitation M is therefore according to equation 165.


M ( p.u.) =

E f

( Vr ) ( fn )

ANSIEQUATION2296 V1 EN

(Equation 165)

Disproportional variations in quantities E and f may give rise to core overfluxing. If the
core flux density Bmax increases to a point above saturation level (typically 1.9 Tesla), the
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

639

Section 9
Voltage protection

1MRK 502 066-UUS A

flux will no longer be contained within the core, but will extend into other (non-laminated)
parts of the power transformer and give rise to eddy current circulations.
Overexcitation will result in:

overheating of the non-laminated metal parts


a large increase in magnetizing currents
an increase in core and winding temperature
an increase in transformer vibration and noise

Protection against overexcitation is based on calculation of the relative volt per hertz (V/
Hz) ratio. Protection initiates a reduction of excitation, and if this fails, or if this is not
possible, the TRIP signal will disconnect the transformer from the source after a delay
ranging from seconds to minutes, typically 5-10 seconds.
Overexcitation protection may be of particular concern on directly connected generator
unit transformers. Directly connected generator-transformers are subjected to a wide
range of frequencies during the acceleration and deceleration of the turbine. In such cases,
OEXPVPH (24) may trip the field breaker during a start-up of a machine, by means of the
overexcitation ALARM signal. If this is not possible, the power transformer can be
disconnected from the source, after a delay, by the TRIP signal.
The IEC 60076 - 1 standard requires that transformers operate continuously at not more
than 10% above rated voltage at no load, and rated frequency. At no load, the ratio of the
actual generator terminal voltage to the actual frequency should not exceed 1.1 times the
ratio of transformer rated voltage to the rated frequency on a sustained basis, see
equation 166.
E
f

1.1

Vn
fn
(Equation 166)

EQUATION1630 V1 EN

or equivalently, with 1.1 Vn = Pickup1 according to equation 167.


E
f

Pickup1
fn
(Equation 167)

ANSIEQUATION2297 V2 EN

where:

Pickup1 is the maximum continuously allowed voltage at no load, and rated frequency.

640

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Pickup1 is a setting parameter. The setting range is 100% to 180%. If the user does not
know exactly what to set, then the default value for Pickup1 = 110 % given by the IEC
60076-1 standard shall be used.
In OEXPVPH (24), the relative excitation M is expressed according to equation 168.
M ( p.u.) =

E f
Vn fn

ANSIEQUATION2299 V1 EN

(Equation 168)

It is clear from the above formula that, for an unloaded power transformer, M = 1 for any
E and f, where the ratio E/f is equal to Vn/fn. A power transformer is not overexcited as
long as the relative excitation is M Pickup1, Pickup1 expressed in % of Vn/fn.
The overexcitation protection algorithm is fed with an input voltage V which is in general
not the induced voltage E from the fundamental transformer equation. For no load
condition, these two voltages are the same, but for a loaded power transformer the
internally induced voltage E may be lower or higher than the voltage V which is measured
and fed to OEXPVPH (24), depending on the direction of the power flow through the
power transformer, the power transformer side where OEXPVPH (24) is applied, and the
power transformer leakage reactance of the winding. It is important to specify in the
application configuration on which side of the power transformer OEXPVPH (24) is
placed.
As an example, at a transformer with a 15% short circuit impedance Xsc, the full load, 0.8
power factor, 105% voltage on the load side, the actual flux level in the transformer core,
will not be significantly different from that at the 110% voltage, no load, rated frequency,
provided that the short circuit impedance X can be equally divided between the primary
and the secondary winding: XLeakage = XLeakage1 = XLeakage2 = Xsc / 2 = 0.075 pu.
OEXPVPH (24) calculates the internal induced voltage E if XLeakage (meaning the
leakage reactance of the winding where OEXPVPH (24) is connected) is known to the
user. The assumption taken for two-winding power transformers that XLeakage = Xsc / 2
is unfortunately most often not true. For a two-winding power transformer the leakage
reactances of the two windings depend on how the windings are located on the core with
respect to each other. In the case of three-winding power transformers the situation is still
more complex. If a user has the knowledge on the leakage reactance, then it should
applied. If a user has no idea about it, XLeakage can be set to Xc/2. OEXPVPH (24)
protection will then take the given measured voltage V, as the induced voltage E.
It is assumed that overexcitation is a symmetrical phenomenon, caused by events such as
loss-of-load, etc. A high phase-to-ground voltage does not mean overexcitation. For
example, in an ungrounded power system, a single phase-to-ground fault means high
voltages of the healthy two phases-to-ground, but no overexcitation on any winding.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

641

Section 9
Voltage protection

1MRK 502 066-UUS A

The phase-to-phase voltages will remain essentially unchanged. The important voltage is
the voltage between the two ends of each winding.

9.4.7.1

Measured voltage
If one phase-to-phase voltage is available from the side where overexcitation protection
is applied, then Overexcitation protection OEXPVPH (24) shall be set to measure this
voltage, MeasuredV. The particular voltage which is used determines the two currents that
must be used. This must be chosen with the setting MeasuredI.
It is extremely important that MeasuredV and MeasuredI are set to same
value.
If, for example, voltage Vab is fed to OEXPVPH(24), then currents Ia, and Ib must be
applied. From these two input currents, current Iab = Ia - Ib is calculated internally by the
OEXPVPH (24) algorithm. The phase-to-phase voltage must be higher than 70% of the
rated value, otherwise the protection algorithm exits without calculating the excitation.
ERROR output is set to 1, and the displayed value of relative excitation V/Hz shows
0.000.
If three phase-to-ground voltages are available from the side where overexcitation is
connected, then OEXPVPH (24) shall be set to measure positive sequence voltage and
current. In this case the positive sequence voltage and the positive sequence current are
used by OEXPVPH (24). A check is made if the positive sequence voltage is higher than
70% of rated phase-to-ground voltage, when below this value, OEXPVPH (24) exits
immediately, and no excitation is calculated. ERROR output is set to 1, and the displayed
value of relative excitation V/Hz shows 0.000.

9.4.7.2

OEXPVPH (24) can be connected to any power transformer side, independent from
the power flow.
The side with a possible load tap changer must not be used.

Operate time of the overexcitation protection


The operate time of OEXPVPH (24) is a function of the relative overexcitation.
Basically there are two different delay laws available to choose between:

642

the so called IEEE law, and


a tailor-made law.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

The so called IEEE law approximates a square law and has been chosen based on analysis
of the various transformers overexcitation capability characteristics. They can match the
transformer core capability well.
The square law is according to equation 169.
top =

0.18 TD

PUV Hz - 1

0.18 TD
overexcitation

(Equation 169)

ANSIEQUATION2298 V2 EN

where:
M

the relative excitation

Pickup1 is maximum continuously allowed voltage at no load, and rated frequency, in pu and
TD

is time multiplier for inverse time functions, see figure 300.


Parameter TD (time delay multiplier setting) selects one delay curve from the family of curves.

The relative excitation M is calculated using equation170

Vmeasured

fmeasured
=

Vmeasured

frated

VBase VBase fmeasured

frated
(Equation 170)

ANSIEQUATION2404 V1 EN

An analog overexcitation relay would have to evaluate the following integral expression,
which means to look for the instant of time t = top according to equation 171.
top

( M ( t ) - Pickup1)

dt 0.18 TD

0
ANSIEQUATION2300 V1 EN

(Equation 171)

A digital, numerical relay will instead look for the lowest j (that is, j = n) where it becomes
true that:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

643

Section 9
Voltage protection

1MRK 502 066-UUS A

Dt

( M( j) - PUV / Hz )

0.18 TD

j=k

(Equation 172)

EQUATION1636 V1 EN

where:
is the time interval between two successive executions of OEXPVPH (24) and

Dt

M(j) - Pickup1 is the relative excitation at (time j) in excess of the normal (rated) excitation which is given as
Vn/fn.

As long as M > Pickup1 (that is, overexcitation condition), the above sum can only be
larger with time, and if the overexcitation persists, the protected transformer will be
tripped at j = n.
Inverse delays as per figure 300, can be modified (limited) by two special definite delay
settings, namely t_MaxTripDelay and t_MinTripDelay, see figure 299.
delay in s
t_MaxTrip
Delay

under excitation

inverse delay law

overexcitation
t_MinTripDelay
0

Mmax Pickup1

M=Pickup1
Pickup1

Mmax
Emax

Overexcitation M-Pickup1
Excitation M

E (only if f = fn = const)
ANSI99001067-2en.vsd

ANSI99001067 V2 EN

Figure 299:

Restrictions imposed on inverse delays by t_MaxTripDelay and


t_MinTripDelay

A definite maximum time, t_MaxTripDelay, can be used to limit the operate time at low
degrees of overexcitation. Inverse delays longer than t_MaxTripDelay will not be
allowed. In case the inverse delay is longer than t_MaxTripDelay, OEXPVPH (24) trips
after t_MaxTripDelay seconds.
A definite minimum time, t_MinTripDelay, can be used to limit the operate time at high
degrees of overexcitation. In case the inverse delay is shorter than t_MinTripDelay,
OEXPVPH (24) function trips after t_MinTripDelay seconds. The inverse delay law is not

644

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

valid for values exceeding Mmax. The delay will be tMin, irrespective of the
overexcitation level, when values exceed Mmax (that is, M>Pickup1).
IEEE OVEREXCITATION CURVES

Time (s)

1000

100
TD = 60

TD = 20

TD = 10
TD = 9
TD = 8
TD = 7
TD = 6
TD = 5

10

TD = 4
TD = 3
TD = 2

TD = 1
1

10

20

OVEREXCITATION IN %

30

40

(M-Emaxcont)*100)
en01000373_ansi.vsd

ANSI01000373 V1 EN

Figure 300:

Delays inversely proportional to the square of the overexcitation

The critical value of excitation M is determined indirectly via OEXPVPH (24) setting
Pickup2. Pickup2 can be thought of as a no-load voltage at rated frequency, where the
inverse law should be replaced by a short definite delay, t_MinTripDelay. If, for example,
Pickup2 = 140 %, then M is according to equation 173.
M=

( Pickup2 f )
Vn/fn

= 1.40

ANSIEQUATION2286 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

(Equation 173)

645

Section 9
Voltage protection

1MRK 502 066-UUS A

The Tailor-Made law allows a user to design an arbitrary delay characteristic. In this case
the interval between M = Pickup1, and M = Mmax is automatically divided into five equal
subintervals, with six delays. (settings t1, t2, t3, t4, t5 and t6) as shown in figure 301. These
times should be set so that t1 => t2 => t3 => t4 => t5 => t6.
delay in s

t_MaxTripDelay

t_MinTripDelay

underexcitation

Overexcitation M-E maxcont


0

M max - E maxcont Excitation M

Emaxcont

M max
99001068_ansi.vsd

ANSI99001068 V1 EN

Figure 301:

An example of a Tailor-Made delay characteristic

Delays between two consecutive points, for example t3 and t4, are obtained by linear
interpolation.
Should it happen that t_MaxTripDelay be lower than, for example, delays t1, and t2, the
actual delay would be t_MaxTripDelay. Above Mmax, the delay can only be
t_MinTripDelay.

9.4.7.3

Cooling
Overexcitation protection OEXPVPH (24) is basically a thermal protection; therefore a
cooling process has been introduced. Exponential cooling process is applied. Parameter
Setting tool is an OEXPVPH (24) setting, with a default time constant t_CoolingK of 20
minutes. This means that if the voltage and frequency return to their previous normal
values (no more overexcitation), the normal temperature is assumed to be reached not
before approximately 5 times t_CoolingK minutes. If an overexcitation condition would
return before that, the time to trip will be shorter than it would be otherwise.

9.4.7.4

Overexcitation protection function measurands


A monitored data value, TMTOTRIP, is available on the local HMI and in PCM600. This
value is an estimation of the remaining time to trip (in seconds), if the overexcitation
remained on the level it had when the estimation was done. This information can be useful
during small or moderate overexcitation situations.

646

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

If the overexcitation is so low that the valid delay is t_MaxTripDelay, then the estimation
of the remaining time to trip is done against t_MaxTripDelay.
The relative excitation M, shown on the local HMI and in PCM600 has a monitored data
value VPERHZ and is calculated from the expression:
M ( p.u.) =

E f
Vn fn

ANSIEQUATION2299 V1 EN

(Equation 174)

If VPERHZ value is less than setting Pickup1 (in %), the power transformer is
underexcited. If VPERHZ is equal to Pickup1 (in %), the excitation is exactly equal to the
power transformer continuous capability. If VPERHZ is higher than Pickup1, the
protected power transformer is overexcited. For example, if VPERHZ = 1.100, while
Pickup1 = 110 %, then the power transformer is exactly on its maximum continuous
excitation limit.
The monitored data value THERMSTA shows the thermal status of the protected power
transformer iron core. THERMSTA gives the thermal status in % of the trip value which
corresponds to 100%. THERMSTA should reach 100% at the same time, as TMTOTRIP
reaches 0 seconds. If the protected power transformer is then for some reason not switched
off, THERMSTA shall go over 100%.
If the delay as per IEEE law, or Tailor-made Law, is limited by t_MaxTripDelay, and/or
t_MinTripDelay, then the Thermal status will generally not reach 100% at the same time,
when tTRIP reaches 0 seconds. For example, if, at low degrees of overexcitation, the very
long delay is limited by t_MaxTripDelay, then the OEXPVPH (24) TRIP output signal
will be set to 1 before the Thermal status reaches 100%.

9.4.7.5

Overexcitation alarm
A separate step, AlarmPickup, is provided for alarming purpose. It is normally set 2%
lower than (Pickup1) and has a definite time delay, tAlarm. This will give the operator an
early warning.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

647

Section 9
Voltage protection
9.4.7.6

1MRK 502 066-UUS A

Logic diagram
BLOCK
AlarmPickup
0-tMax
0

I3P

&

ALARM

&

TRIP

tAlarm

M>Pickup1

V3P

t>tAlarm

Pickup1
Calculation
of internal
induced
voltage Ei

Ei

M=
(Ei / f)
(Vn / fn)

TD

IEEE law

&

0-tMax
M
0
Tailor-made law
t_MaxTripDelay
M>Pickup2
Xleakage

OR

0-tMin
t>tMin
0
Pickup2

t_MinTripDelay

M = relative Pickup as service value


ANSI05000162-3-en.vsd
ANSI05000162 V3 EN

Figure 302:

A simplified logic diagram of the Overexcitation protection OEXPVPH


(24)

Simplification of the diagram is in the way the IEEE and Tailor-made delays are
calculated. The cooling process is not shown. It is not shown that voltage and frequency
are separately checked against their respective limit values.

9.4.8

Technical data
Table 323:

OEXPVPH (24) technical data

Function

Range or value

Accuracy

Trip value, pickup

(100180)% of (VBase/fn)

0.5% of V

Trip value, alarm

(50120)% of pickup level

0.5% of Vn at V Vn
0.5% of V at V > Vn

Trip value, high level

(100200)% of (VBase/fn)

0.5% of V

Curve type

IEEE or customer defined

5.0 % or 45 ms, whichever


is greater

IEEE : t =

(0.18 TD)
( M - 1) 2

EQUATION1645 V1 EN

(Equation 175)

where M = (E/f)/(Vn/fn)
Table continues on next page

648

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Minimum time delay for inverse


function

(0.00060.000) s

1.0% or 45 ms, whichever


is greater

Maximum time delay for inverse


function

(0.009000.00) s

1.0% or 45 ms, whichever


is greater

Alarm time delay

(0.009000.00)

1.0% or 45 ms, whichever


is greater

9.5

Voltage differential protection VDCPTOV (60)

9.5.1

Identification
Function description

IEC 61850
identification

Voltage differential protection

9.5.2

VDCPTOV

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
60

Functionality
A voltage differential monitoring function is available. It compares the voltages from two
three phase sets of voltage transformers and has one sensitive alarm step and one trip step.

9.5.3

Function block
VDCPTOV (60)
V3P1*
V3P2*
BLOCK

TRIP
PICKUP
ALARM
V1LOW
V2LOW
VDIFF_A
VDIFF_B
VDIFF_C
ANSI06000528-2-en.vsd

ANSI06000528 V2 EN

Figure 303:

VDCPTOV (60) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

649

Section 9
Voltage protection
9.5.4

1MRK 502 066-UUS A

Signals
Table 324:

VDCPTOV (60) Input signals

Name

Type

Bus voltage

V3P2

GROUP
SIGNAL

Capacitor voltage

BLOCK

BOOLEAN

Block of function

VDCPTOV (60) Output signals

Name

Table 326:
Name

Description

GROUP
SIGNAL

Table 325:

9.5.5

Default

V3P1

Type

Description

TRIP

BOOLEAN

Voltage differential protection operated

PICKUP

BOOLEAN

Pickup of voltage differential protection

ALARM

BOOLEAN

Voltage differential protection alarm

V1LOW

BOOLEAN

Loss of V1 voltage

V2LOW

BOOLEAN

Loss of V2 voltage

VDIFF_A

REAL

Differential Voltage phase A

VDIFF_B

REAL

Differential Voltage phase B

VDIFF_C

REAL

Differential Voltage phase C

Settings
VDCPTOV (60) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

BlkDiffAtVLow

No
Yes

Yes

Block operation at low voltage

VDTrip

2.0 - 100.0

%VB

0.1

5.0

Operate level, in % of VBase

tTrip

0.000 - 60.000

0.001

1.000

Time delay for voltage differential operate, in


seconds

tReset

0.000 - 60.000

0.001

0.000

Time delay for voltage differential reset, in


seconds

VDAlarm

2.0 - 100.0

%VB

0.1

2.0

Alarm level, in % of VBase

tAlarm

0.000 - 60.000

0.001

2.000

Time delay for voltage differential alarm, in


seconds

V1Low

1.0 - 100.0

%VB

0.1

70.0

Input 1 undervoltage level, in % of VBase

V2Low

1.0 - 100.0

%VB

0.1

70.0

Input 2 undervoltage level, in % of VBase

tBlock

0.000 - 60.000

0.001

0.000

Reset time for undervoltage block

650

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Table 327:

VDCPTOV (60) Group settings (advanced)

Name

Values (Range)

RF_A

0.000 - 3.000

0.001

1.000

Ratio compensation factor phase L1


U2L1*RFL1=U1L1

RF_B

0.000 - 3.000

0.001

1.000

Ratio compensation factor phase L2


U2L2*RFL2=U1L2

RF_C

0.000 - 3.000

0.001

1.000

Ratio compensation factor phase L3


U2L3*RFL3=U1L3

Table 328:
Name
GlobalBaseSel

9.5.6

Step

Default

Description

VDCPTOV (60) Non group settings (basic)


Values (Range)
1 - 12

Unit

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 329:
Name

9.5.7

Unit

VDCPTOV (60) Monitored data


Type

Values (Range)

Unit

Description

VDIFF_A

REAL

kV

Differential Voltage phase A

VDIFF_B

REAL

kV

Differential Voltage phase B

VDIFF_C

REAL

kV

Differential Voltage phase C

Operation principle
The Voltage differential protection function VDCPTOV (60) is based on comparison of
the magnitudes of the two voltages connected in each phase. Possible differences between
the ratios of the two Voltage/Capacitive voltage transformers can be compensated for with
a ratio correction factors RF_X. The voltage difference is evaluated and if it exceeds the
alarm level VDAlarm or trip level VDTrip signals for alarm (ALARM output) or trip
(TRIP output) is given after definite time delay tAlarm respectively tTrip. The two three
phase voltage supplies are also supervised with undervoltage settings V1Low and V2Low.
The outputs for loss of voltage V1LOW resp V2LOW will be activated. The V1 voltage
is supervised for loss of individual phases whereas the V2 voltage is supervised for loss
of all three phases.
Loss of all V1 or all V2 voltages will block the differential measurement. This blocking
can be switched off with setting BlkDiffAtULow = No.
VDCPTOV (60) function can be blocked from an external condition with the binary
BLOCK input. It can, for example, be activated from Fuse failure supervision function
FUFSPVC.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

651

Section 9
Voltage protection

1MRK 502 066-UUS A

To allow easy commissioning the measured differential voltage is available as service


value. This allows simple setting of the ratio correction factor to achieve full balance in
normal service.
The principle logic diagram is shown in figure 304.
VDTrip_A

AND

VDTrip_B

AND

VDTrip_C

O
R

0
0-tReset

0-tTrip
0

AND

AND
AND

VDAlarm_A

TRIP

PICKUP

AND

VDAlarm_B

AND

VDAlarm_C

O
R

0-tAlarm
0

AND

ALARM

AND

V1LOW

AND

V1Low_A
V1Low_B

AND

0-tAlarm
0

V1Low_C

AND
OR

BlkDiffAtULow
V2Low_A
V2Low_B

AND

0-t1
0

AND

V2LOW

V2Low_C
BLOCK

en06000382_2_ansi.vsd
ANSI06000382 V3 EN

Figure 304:

652

Principle logic for Voltage differential function VDCPTOV (60)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.5.8

Technical data
Table 330:

VDCPTOV (60) technical data

Function

Range or value

Accuracy

Voltage difference for alarm and


trip

(2.0100.0) % of VBase

0.5% of Vn

Under voltage level

(1.0100.0) % of VBase

0.5% of Vn

Independent time delay for


voltage differential alarm at 0.8 to
1.2 x VDAlarm

(0.00060.000)s

0.2% or 40 ms whichever is
greater

Independent time delay for


voltage differential trip at 0.8 to
1.2 x VDTrip

(0.00060.000)s

0.2% or 40 ms whichever is
greater

Independent time delay for


voltage differential reset at 1.2 to
0.8 x VDTrip

(0.00060.000)s

0.2% or 40 ms whichever is
greater

9.6

100% Stator ground fault protection, 3rd harmonic


based STEFPHIZ (59THD)

9.6.1

Identification
Function description
100% Stator ground fault protection, 3rd
harmonic based

9.6.2

IEC 61850
identification
STEFPHIZ

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
59THD

Functionality
Stator ground fault is a fault type having relatively high fault rate. The generator systems
normally have high impedance grounding, that is, grounding via a neutral point resistor.
This resistor is normally dimensioned to give an ground fault current in the range 3 15
A at a solid ground-fault directly at the generator high voltage terminal. The relatively
small ground fault currents give much less thermal and mechanical stress on the generator,
compared to the short circuit case, which is between conductors of two phases. Anyhow,
the ground faults in the generator have to be detected and the generator has to be tripped,
even if longer fault time compared to internal short circuits, can be allowed.
In normal non-faulted operation of the generating unit the neutral point voltage is close to
zero, and there is no zero sequence current flow in the generator. When a phase-to-ground
fault occurs the neutral point voltage will increase and there will be a current flow through
the neutral point resistor.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

653

Section 9
Voltage protection

1MRK 502 066-UUS A

To detect a ground fault on the windings of a generating unit one may use a neutral point
overvoltage protection, a neutral point overcurrent protection, a zero sequence
overvoltage protection or a residual differential protection. These protections are simple
and have served well during many years. However, at best these simple schemes protect
only 95% of the stator winding. They leave 5% close to the neutral end unprotected. Under
unfavorable conditions the blind zone may extend up to 20% from the neutral.
The 95% stator ground fault protection measures the fundamental frequency voltage
component in the generator star point and it operates when the fundamental frequency
voltage exceeds the preset value. By applying this principle approximately 95% of the
stator winding can be protected. In order to protect the last 5% of the stator winding close
to the neutral end the 3rd harmonic voltage measurement can be performed. In 100%
Stator E/F 3rd harmonic protection either the 3rd harmonic voltage differential principle,
the neutral point 3rd harmonic undervoltage principle or the terminal side 3rd harmonic
overvoltage principle can be applied. However, differential principle is strongly
recommended. Combination of these two measuring principles provides coverage for
entire stator winding against ground faults.
stator winding
N

x E3

(1- x) E3

RN

uN
Samples of the
neutral voltage
from which the
fundamental and
3rd harmonic
voltages are
filtered out

CB 1 may not exist


T

CB 1

Transformer

Rf

CB 2

1- x
1 or 100 %
Neutral point fundamental frequency
over-voltage protection 5% - 100%

over- voltage protection 10% 100%

uT
Samples of the
terminal voltage
from which the
3rd harmonic
voltage is filtered
out

3rd
harmonic
Differential
differential
0% 30%
0% - 30%

ANSI10000202-1-en.vsd

ANSI10000202 V1 EN

Figure 305:

654

Protection principles for STEFPHIZ (59TD) function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.6.3

Function block
STEFPHIZ (59THD)
NEUTVOLT
TRIP
TERMVOLT
TRIP3H
52A
TRIP_VN
BLOCK
PICKUP
BLOCK3RD
PU_3H
BLOCKVN
PU_VN
VT3
VN3
E3
ANGLE
DV3
BV3
V_N
ANSI11000211-1-en.vsd
ANSI11000211 V1 EN

Figure 306:

9.6.4

STEFPHIZ (59THD) function block

Signals
Table 331:
Name

STEFPHIZ (59THD) Input signals


Type

Default

Description

U3PNEUT

GROUP
SIGNAL

Voltage connection neutral side

U3PTERM

GROUP
SIGNAL

Open-Delta connection on Terminal side

52a

BOOLEAN

TRUE means breaker between gen. & trafo is closed

BLOCK

BOOLEAN

Complete block of the stator ground fault protecion


function

BLOCK3RD

BOOLEAN

Block of the 3rd harmonic-based parts of the protection

BLOCKVN

BOOLEAN

Block of the fund. harmonic-based part of the protection

Table 332:
Name

STEFPHIZ (59THD) Output signals


Type

Description

TRIP

BOOLEAN

Main, common trip command

TRIP3H

BOOLEAN

Trip by one of two 3rd harmonic voltage-based prot.

TRIP_VN

BOOLEAN

Trip by fund. freq. neutral over-voltage protection

PICKUP

BOOLEAN

Main, common pick up signal

PU_3H

BOOLEAN

Pickup by one of two 3rd harmonic voltage-based prot.

PU_VN

BOOLEAN

Pick up signal by fund. freq. neutral over-voltage prot.

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

655

Section 9
Voltage protection

1MRK 502 066-UUS A

Name

9.6.5
Table 333:
Name

Type

Description

VT3

REAL

Mag. of 3rd harm. voltage at generator terminal side,


Volts

VN3

REAL

Mag. of 3rd harm. voltage at generator neutral side,


Volts

E3

REAL

Total induced stator 3rd harmonic voltage, primary Volts

ANGLE

REAL

Angle between 3rd harmonic votage phasors, radians

DV3

REAL

Diff. between 3rd harm. volt. at both sides of gen., Volts

BV3

REAL

Bias voltage, a part of voltN3rdHarmonic, primary Volts

V_N

REAL

Fund. frequency voltage at generator neutral, primary


Volts

Settings
STEFPHIZ (59THD) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

Beta

0.50 - 10.00

0.01

3.00

Portion of voltN3rdHarmonic used as bias

CBexists

No
Yes

No

Defines if generator CB exists (between Gen &


Transformer)

FactorCBopen

1.00 - 10.00

0.01

1.00

Beta is multiplied by this factor when CB is


open

VN3rdHPU

0.5 - 10.0

0.1

2.0

Pickup 3rd Harm V< protection (when


activated) % of VB/1,732

VT3BlkLevel

0.1 - 10.0

0.1

1.0

If VT3 is below limit 3rdH Diff is blocked, in % of


VB/1,732

VNFundPU

1.0 - 50.0

0.1

5.0

Pickup fundamental VN> protection (95%


SEF), % of VB/1,732

t3rdH

0.020 - 60.000

0.001

1.000

Operation delay of 3rd harm-based protection


(100% SEF) in s

tVNFund

0.020 - 60.000

0.001

0.500

Operation delay of fundamental VN>


protection (95% SEF) in s

Table 334:
Name

STEFPHIZ (59THD) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

TVoltType

NoVoltage
ResidualVoltage
AllThreePhases
PhaseA
PhaseB
PhaseC

ResidualVoltage

Used connection type for gen. terminal voltage


transformer

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

656

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

9.6.6

Monitored data
Table 335:
Name

9.6.7

STEFPHIZ (59THD) Monitored data


Type

Values (Range)

Unit

Description

VT3

REAL

kV

Mag. of 3rd harm. voltage at


generator terminal side, Volts

VN3

REAL

kV

Mag. of 3rd harm. voltage at


generator neutral side, Volts

E3

REAL

kV

Total induced stator 3rd


harmonic voltage, primary
Volts

ANGLE

REAL

deg

Angle between 3rd harmonic


votage phasors, radians

DV3

REAL

kV

Diff. between 3rd harm. volt. at


both sides of gen., Volts

BV3

REAL

kV

Bias voltage, a part of


voltN3rdHarmonic, primary
Volts

V_N

REAL

kV

Fund. frequency voltage at


generator neutral, primary
Volts

Operation principle
The protection is a combination of the 95% fundamental frequency ground fault
protection and the 3 rd harmonic based stator earth fault protection, (STEFPHIZ, 59THD).
The 3rd harmonic based 100% stator ground fault protection is using the 3rd harmonic
voltage generated by the generator itself. To assure reliable function of the protection it is
necessary that the 3rd harmonic voltage generation is at least 0.8 V RMS on VT secondary
side.
The 3rd harmonic voltage generated by the generator has the same phase angle in the three
phases. It has the characteristic of a zero sequence component. If the generator is
connected to the power system via a block transformer that cannot transform zero
sequence voltages between the voltage levels, the 3rd harmonic voltage, that is V3N and
V3T in fig 307, in the generator system is not influenced by the external power system. At
normal operation the generator third harmonic voltage characteristic can be described as
in figure 307.
Note that angle between V3N and V3T is typically close to 180.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

657

Section 9
Voltage protection

1MRK 502 066-UUS A

V3

- DV3 +
+
V3T,A
-

V3N

+
V3T,B
-

+
V3T,C
-

V3T

V3N

en06000448_ansi.vsd
ANSI06000448 V1 EN

Figure 307:

Generator 3rd harmonic voltage characteristic at normal operation

The generator is modeled as parts of a winding where a 3rd harmonic voltage is induced
along the winding, represented by the end voltages V3N (voltage drop across resistor) and
V3T in the figure. Via the winding capacitances to ground and the neutral point resistor
there will be a small 3rd harmonic current, giving the voltages V3N and V3T. The 3rd
harmonic voltage in the generator neutral point (V3N) will be close to zero in case of a
stator ground-fault close to the neutral. This fact alone can be used as an indication of
stator ground-fault. To enable better sensitivity and stability also measurement of the
generator's 3rd harmonic voltage V3T is also used. In addition to the decrease of V3N the
generator voltage V3T will increase under the stator ground-fault close to the generator
neutral point. Therefore the 3rd harmonic voltage V3T , (which is a zero sequence voltage)
is used by the protection. In the 3rd harmonic voltage differential protection algorithm
equation 176 is used:

658

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

V3N + V3T Beta V 3N


EQUATION2359-ANSI V1 EN

(Equation 176)

V3N, and V3T are third harmonic phasors with real and imaginary parts. The factor Beta
must be set not to risk operation under non-faulted conditions.
The voltage V3N is measured via a voltage transformer between the generator neutral point
and ground. The voltage V3T can be measured in different ways. The setting TVoltType
defines how the protection function is fed from voltage transformers at the high voltage
side of the generator. If V3T is lower than the set level VT3BlkLevel, STEFPHIZ (59THD)
function is blocked. The choices of TVoltType are:
NoVoltage: There is no voltage measured from the generator terminal side. This can be the
case when there are only phase-to-phase voltage transformers available at the generator
terminal side. In this case the protection will operate as a simple neutral point 3rd harmonic
undervoltage protection, which must be blocked externally during generator start-up and
shut-down.
ResidualVoltage: The function is fed from a broken delta connection of the phase to
ground connected voltage transformers at the generator terminal side,
V3T=(1/3)*V_Broken_Delta.
AllThreePhases: The function is fed from the three phase to ground connected voltage
transformers at the generator terminal side. The 3rd harmonic voltage V3T is calculated in
the IED, V3T=(1/3)*(V3A+V3B+V3C).
PhaseA, PhaseB, or PhaseC: The function is fed from one phase voltage transformer only.
The 3rd harmonic zero sequence voltage is assumed to be equal to any of the phase
voltages, as the third harmonic voltage is of zero sequence type, V3T=V3Lx.
A simplified block diagram describing the stator ground fault protection function shown
in figure 308.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

659

Section 9
Voltage protection

1MRK 502 066-UUS A

Samples:
Generator
terminal
voltage

3rd
harmonic
Fourier
filtering
giving VT3

Samples:
Generator
neutral point
voltage

3rd
harmonic
Fourier
filtering
giving VN3

Complex VT3

Stator
Ground
Fault
detection
3rd
harmonic
based

TRIP
TRIP3H

Pickup

TRIPVN

Pickup
and trip
logic

PU3H
PU_VN

Complex VN3

Fundamental frequency residual


voltage

Stator
Ground
Fault
detection
95 %

Pickup

CB Status
Block

en06000449_ansi.vsd
ANSI06000449 V2 EN

Figure 308:

Simplified logic diagram for stator ground fault protection

STEFPHIZ (59THD) function can be described in a simplified logical diagram as shown


in figure 309. Note that the 3rd harmonic numerical filters are not part of the stator groundfault protection function.
These third harmonic voltages are calculated by the preprocessing blocks connected to the
function.

660

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Beta
V3N

V3N+V3T

ba
PU3H

AND
t
0

VT3BlkLevel
V3T

ab

TRIP3H
PICKUP

OR

TRIP

OR
a

VNFundPU
V_N

PU_VN

ba

TRIPVN

t
0

ANSI07000001-2-en.vsd
ANSI07000001 V2 EN

Figure 309:

Simplified Pickup and Trip logical diagram of the 100% Stator earth fault
protection, 3rd harmonic based STEFPHIZ (59THD) protection

There are two different cases of generator block configuration; with or without generator
circuit breaker. If there is no generator breaker the capacitive coupling to ground is the
same under all operating conditions. When there is a generator breaker, the capacitive
coupling to ground differs between the operating conditions when the generator is running
with the generator breaker open (before synchronization) and with the circuit breaker
closed. This can be shown as in figure 310.
-

UV3

- DV3 +
+
V3T,A
-

V3N

+
V3T,B
-

+
V3T,C
-

Ctr/3

Ctr/3

Ctr/3

en07000002-2_ansi.vsd
ANSI07000002 V2 EN

Figure 310:

Generator block with generator circuit breaker

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

661

Section 9
Voltage protection

1MRK 502 066-UUS A

With the circuit breaker open, the total capacitance will be smaller compared to normal
operating conditions. This means that the neutral point 3rd harmonic voltage will be
reduced compared to the normal operating condition. Therefore, there is a possibility to
reduce the sensitivity of the protection when the generator circuit breaker is open.
With the setting CBexists change of the sensitivity is enabled. If the binary input signal 52a
is activated the set sensitivity is valid. If the generator circuit breaker is opened the binary
input 52a is deactivated and the sensitivity is changed. This is done by changing the factor
Beta which is multiplied with a set constant FactorCBopen.
In addition to the binary outputs also some analog outputs are available from the
protection function in order to enable easier commissioning:
E3: the magnitude of the 3rd harmonic voltage induced in the stator given in primary volts
VN3: the magnitude of the 3rd harmonic voltage measured in the neutral point of the
generator
VT3: the magnitude of the 3rd harmonic voltage measured in the terminal point of the
generator
ANGLE: the angle between the phasors VN3 and VT3 given in radians
DV3: the magnitude of the 3rd harmonic differential voltage
BV3: the magnitude of the 3rd harmonic bias voltage
V_N: the fundamental frequency voltage measured in the neutral point of the generator

9.6.8

Technical data
Table 336:

STEFPHIZ (59THD) technical data

Function

Range or value

Accuracy

Fundamental frequency level VN


(95% Stator EF)

(1.050.0)% of VBase

0.25% of Vn

Third harmonic differential level

(0.510.0)% of VBase

0.25% of Vn

Third harmonic differential block


level

(0.110.0)% of VBase

0.25% of Vn

Table continues on next page

662

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 9
Voltage protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Independent time delay to trip for


fundamental VN > protection at 0
to 1.2 x VNFund>

(0.02060.000) s

0.2% or 40 ms whichever is
greater

Independent time delay to trip for


3rd harm-based protection at 0 to
5 x VN3rdH<

(0.02060.000) s

0.2% or 40 ms whichever is
greater

Filter characteristic:
Fundamental
Third harmonic

Reject third harmonic by 140


Reject fundamental harmonic by
140

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

663

664

Section 10
Frequency protection

1MRK 502 066-UUS A

Section 10

Frequency protection

10.1

Underfrequency protection SAPTUF (81)

10.1.1

Identification
Function description
Underfrequency protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
81

SAPTUF

f<
SYMBOL-P V1 EN

10.1.2

Functionality
Underfrequency occurs as a result of a lack of generation in the network.
Underfrequency protection SAPTUF (81) measures frequency with high accuracy, and is
used for load shedding systems, remedial action schemes, gas turbine startup and so on.
Separate definite time delays are provided for trip and restore.
SAPTUF (81) is provided with undervoltage blocking.
The operation is based on positive sequence voltage measurement and requires two phasephase or three phase-neutral voltages to be connected. For information about how to
connect analog inputs, refer to Application manual/IED application/Analog inputs/
Setting guidelines

10.1.3

Function block
SAPTUF (81)
V3P*
BLOCK
BLKTRIP
BLKREST

TRIP
PICKUP
RESTORE
BLKDMAGN
FREQ
ANSI06000279-2-en.vsd

ANSI06000279 V2 EN

Figure 311:

SAPTUF (81) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

665

Section 10
Frequency protection
10.1.4

1MRK 502 066-UUS A

Signals
Table 337:

SAPTUF (81L) Input signals

Name

Type

Three phase group signal for voltage inputs

BLOCK

BOOLEAN

Block of function

BLKTRIP

BOOLEAN

Blocking operate output

BLKREST

BOOLEAN

Blocking restore output

SAPTUF (81L) Output signals

Name

Table 339:
Name

Description

GROUP
SIGNAL

Table 338:

10.1.5

Default

V3P

Type

Description

TRIP

BOOLEAN

Common trip signal

PICKUP

BOOLEAN

Common pickup signal

RESTORE

BOOLEAN

Restore signal for load restoring purposes

BLKDMAGN

BOOLEAN

Measurement blocked due to low voltage amplitude

FREQ

REAL

Measured frequency

Settings
SAPTUF (81L) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PUFrequency

35.00 - 75.00

Hz

0.01

48.80

Frequency set value

tDelay

0.000 - 60.000

0.001

0.200

Operate time delay

tReset

0.000 - 60.000

0.001

0.000

Time delay for reset

tRestore

0.000 - 60.000

0.001

0.000

Restore time delay

RestoreFreq

45.00 - 65.00

Hz

0.01

50.10

Restore frequency value

TimerMode

Definite timer
Volt based timer

Definite timer

Setting for choosing timer mode

VNom

50.0 - 150.0

%VB

1.0

100.0

Nominal voltage for voltage based timer in % of


UBase

VMin

50.0 - 150.0

%VB

1.0

90.0

Lower operation limit for voltage based timer in


% of VBase

Exponent

0.0 - 5.0

0.1

1.0

For calculation of the curve form for voltage


based timer

t_MaxTripDelay

0.010 - 60.000

0.001

1.000

Maximum time operation limit for voltage


based timer

t_MinTripDelay

0.010 - 60.000

0.001

1.000

Minimum time operation limit for voltage based


timer

666

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

Table 340:
Name
GlobalBaseSel

10.1.6

SAPTUF (81L) Non group settings (basic)


Values (Range)
1 - 12

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 341:
Name

10.1.7

Unit

SAPTUF (81L) Monitored data


Type

Values (Range)

Unit

Description

VLevel

REAL

kV

Level of measured voltage

FREQ

REAL

Hz

Measured frequency

Operation principle
Underfrequency protection SAPTUF (81) is used to detect low power system frequency.
SAPTUF (81) can either have a definite time delay or a voltage magnitude dependent time
delay. If the voltage magnitude dependent time delay is applied, the time delay will be
longer if the voltage is higher, and the delay will be shorter if the voltage is lower. If the
frequency remains below the set value for a time period corresponding to the chosen time
delay, the corresponding trip signal is issued. To avoid an unwanted trip due to uncertain
frequency measurement at low voltage magnitude, a voltage controlled blocking of the
function is available from the preprocessing function, that is, if the voltage is lower than
the set blocking voltage in the preprocessing function, the function is blocked and no
PICKUP or TRIP signal is issued.

10.1.7.1

Measurement principle
The fundamental frequency of the measured input voltage is measured continuously, and
compared with the set value, PUFrequency. The frequency function is dependent on the
voltage magnitude. If the voltage magnitude decreases below the setting
MinValFreqMeas in the SMAI preprocessing function, which is described in the Basic
IED Functions chapter and is set as a percentage of a global base voltage parameter,
SAPTUF (81) gets blocked, and the output BLKDMAGN is issued. All voltage settings
are made in percent of the setting VBase, which should be set as a phase-phase voltage in
kV.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

667

Section 10
Frequency protection
10.1.7.2

1MRK 502 066-UUS A

Time delay
The time delay for underfrequency protection SAPTUF (81) can be either a settable
definite time delay or a voltage magnitude dependent time delay, where the time delay
depends on the voltage level; a high voltage level gives a longer time delay and a low
voltage level causes a short time delay. For the definite time delay, the setting tDelay sets
the time delay.
For the voltage dependent time delay the measured voltage level and the settings VNom,
VMin, Exponent, t_MaxTripDelay and t_MinTripDelay set the time delay according to
figure 312 and equation 177. The setting TimerOperation is used to decide what type of
time delay to apply.
Trip signal issuing requires that the underfrequency condition continues for at least the
user set time delay tDelay. If the PICKUP condition, with respect to the measured
frequency ceases during this user set delay time, and is not fulfilled again within a user
defined reset time, tReset, the PICKUP output is reset, after that the defined reset time has
elapsed. Here it should be noted that after leaving the hysteresis area, the PICKUP
condition must be fulfilled again and it is not sufficient for the signal to only return back
to the hysteresis area.
On the RESTORE output of SAPTUF (81) a 100ms pulse is issued, after a time delay
corresponding to the setting of tRestore, when the measured frequency returns to the level
corresponding to the setting RestoreFreq.

10.1.7.3

Voltage dependent time delay


Since the fundamental frequency in a power system is the same all over the system, except
some deviations during power oscillations, another criterion is needed to decide, where to
take actions, based on low frequency. In many applications the voltage level is very
suitable, and in most cases is load shedding preferable in areas with low voltage.
Therefore, a voltage dependent time delay has been introduced, to make sure that load
shedding, or other actions, take place at the right location. At constant voltage, V, the
voltage dependent time delay is calculated according to equation 177. At non-constant
voltage, the actual time delay is integrated in a similar way as for the inverse time
characteristic for the undervoltage and overvoltage functions.

668

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

V - VMin
t=
VNom - VMin

Exponent

( t _ MaxTripDelay - t _ MinTripDelay ) + t _ MinTripDelay

(Equation 177)

EQUATION1559 V1 EN

where:
t

is the voltage dependent time delay (at constant voltage),

is the measured voltage

Exponent

is a setting,

VMin, VNom

are voltage settings corresponding to

t_MaxTripDelay, t_MinTripDelay are time settings.

The inverse time characteristics are shown in figure 312, for:


VMin

= 90%
= 100%

t_MaxTrip
Delay

= 1.0 s

t_MinTripD
elay

= 0.0 s

Exponent

= 0, 1, 2, 3 and 4

TimeDlyOperate [s]

0
Exponenent

1
2

3
0.5

90

95

100

V [% of VBase]
en05000075_ansi.vsd
ANSI05000075 V1 EN

Figure 312:

Voltage dependent inverse time characteristics for underfrequency


protection SAPTUF (81). The time delay to trip is plotted as a function of
the measured voltage, for the Exponent = 0, 1, 2, 3, 4 respectively.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

669

Section 10
Frequency protection
10.1.7.4

1MRK 502 066-UUS A

Blocking
It is possible to block underfrequency protection SAPTUF (81) partially or completely, by
binary input signals or by parameter settings, where:
BLOCK:

blocks all outputs

BLKTRIP:

blocks the TRIP output

BLKREST:

blocks the RESTORE output

If the measured voltage level decreases below the setting of MinValFreqMeas in the
preprocessing function both the PICKUP and the TRIP outputs are blocked.

10.1.7.5

Design
The frequency measuring element continuously measures the frequency of the positive
sequence voltage and compares it to the setting PUFrequency. The frequency signal is
filtered to avoid transients due to switchings and faults. The time integrator can trip either
due to a definite delay time or to the special voltage dependent delay time. When the
frequency has returned back to the setting of RestoreFreq, the RESTORE output is issued
after the time delay tRestore. The design of underfrequency protection SAPTUF (81) is
schematically described in figure 313.

670

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

Block
OR

BLKDMAGN

BLOCK

Comparator
V < IntBlockLevel

Voltage

Frequency

Time integrator

Comparator
f < PuFrequency

TimerOperation Mode
Selector

PICKUP

TimeDlyOperate

TRIP

Pickup
&
Trip
Output
Logic

PICKUP

TimeDlyReset

TRIP

100 ms
Comparator
f > RestoreFreq

RESTORE

TimeDlyRestore

en05000726_ansi.vsd
ANSI05000726 V1 EN

Figure 313:

Simplified logic diagram for SAPTUF (81)

10.2

Overfrequency protection SAPTOF (81)

10.2.1

Identification
Function description
Overfrequency protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
81

SAPTOF

f>
SYMBOL-O V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

671

Section 10
Frequency protection
10.2.2

1MRK 502 066-UUS A

Functionality
Overfrequency protection function SAPTOF (81) is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.
Overfrequency occurs because of sudden load drops or shunt faults in the power network.
Close to the generating plant, generator governor problems can also cause over frequency.
SAPTOF (81) measures frequency with high accuracy, and is used mainly for generation
shedding and remedial action schemes. It is also used as a frequency stage initiating load
restoring. A definite time delay is provided for trip.
SAPTOF (81) is provided with an undervoltage blocking.
The operation is based on positive sequence voltage measurement and requires two phasephase or three phase-neutral voltages to be connected. For information about how to
connect analog inputs, refer to Application manual/IED application/Analog inputs/
Setting guidelines

10.2.3

Function block
SAPTOF (81)
V3P*
BLOCK
BLKTRIP

TRIP
PICKUP
BLKDMAGN
FREQ
ANSI06000280-2-en.vsd

ANSI06000280 V2 EN

Figure 314:

10.2.4

Signals
Table 342:
Name

672

SAPTOF (81) function block

SAPTOF (81H) Input signals


Type

Default

Description

V3P

GROUP
SIGNAL

Three phase group signal for voltage inputs

BLOCK

BOOLEAN

Block of function

BLKTRIP

BOOLEAN

Blocking operate output

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

Table 343:

SAPTOF (81H) Output signals

Name

10.2.5
Table 344:
Name

Type

Description

TRIP

BOOLEAN

Common trip signal

PICKUP

BOOLEAN

Common pickup signal

BLKDMAGN

BOOLEAN

Measurement blocked due to low amplitude

FREQ

REAL

Measured frequency

Settings
SAPTOF (81H) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PUFrequency

35.00 - 90.00

Hz

0.01

51.20

Frequency set value

tDelay

0.000 - 60.000

0.001

0.000

Operate time delay

tReset

0.000 - 60.000

0.001

0.000

Time delay for reset

Table 345:
Name
GlobalBaseSel

10.2.6

SAPTOF (81H) Non group settings (basic)


Values (Range)
1 - 12

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 346:
Name

10.2.7

Unit

SAPTOF (81H) Monitored data


Type

Values (Range)

Unit

Description

VLevel

REAL

kV

Level of measured voltage

FREQ

REAL

Hz

Measured frequency

Operation principle
Overfrequency protection SAPTOF (81) is used to detect high power system frequency.
SAPTOF (81) has a settable definite time delay. If the frequency remains above the set
value for a time period corresponding to the chosen time delay, the corresponding TRIP
signal is issued. To avoid an unwanted TRIP due to uncertain frequency measurement at
low voltage magnitude, a voltage controlled blocking of the function is available from the
preprocessing function, that is, if the voltage is lower than the set blocking voltage in the
preprocessing function, the function is blocked and no PICKUP or TRIP signal is issued.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

673

Section 10
Frequency protection

10.2.7.1

1MRK 502 066-UUS A

Measurement principle
The fundamental frequency of the positive sequence voltage is measured continuously,
and compared with the set value, PUFrequency. Overfrequency protection SAPTOF (81)
is dependent on the voltage magnitude. If the voltage magnitude decreases below the
setting MinValFreqMeas in the SMAI preprocessing function, which is discussed in the
Basic IED Functions chapter and is set as a percentage of a global base voltage parameter
VBase, SAPTOF (81) is blocked and the output BLKDMAGN is issued. All voltage
settings are made in percent of the VBase, which should be set as a phase-phase voltage in
kV. To avoid oscillations of the output PICKUP signal, a hysteresis has been included.

10.2.7.2

Time delay
The time delay for Overfrequency protection SAPTOF (81) is a settable definite time
delay, specified by the setting tDelay.
TRIP signal issuing requires that the overfrequency condition continues for at least the
user set time delay, tReset. If the PICKUP condition, with respect to the measured
frequency ceases during this user set delay time, and is not fulfilled again within a user
defined reset time, tReset, the PICKUP output is reset, after that the defined reset time has
elapsed. It is to be noted that after leaving the hysteresis area, the PICKUP condition must
be fulfilled again and it is not sufficient for the signal to only return back to the hysteresis
area.
The total time delay consists of the set value for time delay plus minimum
trip time of the pickup function (80 - 90 ms).

10.2.7.3

Blocking
It is possible to block overfrequency protection SAPTOF (81) partially or completely, by
binary input signals or by parameter settings, where:
BLOCK:

blocks all outputs

BLKTRIP:

blocks the TRIP output

If the measured voltage level decreases below the setting of MinValFreqMeas in the
preprocessing function both the PICKUP and the TRIP outputs are blocked.

674

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

10.2.7.4

Design
The frequency measuring element continuously measures the frequency of the positive
sequence voltage and compares it to the setting PUFrequency. The frequency signal is
filtered to avoid transients due to switchings and faults in the power system. The time
integrator operates due to a definite delay time. The design of overfrequency protection
SAPTOF (81) is schematically described in figure 315.

BLOCK
BLKTRIP

BLOCK
Comparator
V < IntBlockLevel

Voltage

Time integrator
Definite Time Delay

Frequency

Comparator
f > PuFrequency

BLKDMAGN

OR

PICKUP

Pickup
&
Trip
Output
Logic

PICKUP

TimeDlyOperate
TRIP
TimeDlyReset
TRIP

en05000735_ansi.vsd

ANSI05000735 V1 EN

Figure 315:

10.2.8

Simplified logic diagram for SAPTOF (81)

Technical data
Table 347:

SAPTOF (81) technical data

Function
Trip value, pickup function at
symmetrical three-phase voltage
Trip time, pickup at fset -0.02 Hz to
fset +0.02 Hz

Range or value

Accuracy

(35.00-90.00) Hz

2.0 mHz

fn = 50Hz

Min. = 80 ms
Max. = 95 ms

fn = 60 Hz

Min. = 65 ms
Max. = 80 ms

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

675

Section 10
Frequency protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Reset time, pickup at fset +0.02 Hz


to fset -0.02 Hz

Min. = 15 ms
Max. = 30 ms

Trip time, definite time function at


fset -0.02 Hz to fset +0.02 Hz

(0.000-60.000)s

0.2% 100 ms
whichever is greater

Reset time, definite time function


at fset +0.02 Hz to fset -0.02 Hz

(0.000-60.000)s

0.2% 120 ms,


whichever is greater

10.3

Rate-of-change frequency protection SAPFRC (81)

10.3.1

Identification
Function description
Rate-of-change frequency protection

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
81

SAPFRC

df/dt >
<
SYMBOL-N V1 EN

10.3.2

Functionality
The rate-of-change frequency protection function SAPFRC (81) gives an early indication
of a main disturbance in the system. SAPFRC (81) measures frequency with high
accuracy, and can be used for generation shedding, load shedding and remedial action
schemes. SAPFRC (81) can discriminate between a positive or negative change of
frequency. A definite time delay is provided for trip.
SAPFRC (81) is provided with an undervoltage blocking. The operation is based on
positive sequence voltage measurement and requires two phase-phase or three phaseneutral voltages to be connected. For information about how to connect analog inputs,
refer to Application manual/IED application/Analog inputs/Setting guidelines.

676

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

10.3.3

Function block
SAPFRC (81)
V3P*
TRIP
BLOCK
PICKUP
BLKTRIP
RESTORE
BLKREST
BLKDMAGN
ANSI06000281-2-en.vsd
ANSI06000281 V2 EN

Figure 316:

10.3.4

SAPFRC (81) function block

Signals
Table 348:

SAPFRC (81R) Input signals

Name

Type
GROUP
SIGNAL

Three phase group signal for voltage inputs

BLOCK

BOOLEAN

Block of function

BLKTRIP

BOOLEAN

Blocking operate output

BLKREST

BOOLEAN

Blocking restore output

SAPFRC (81R) Output signals

Name

Table 350:
Name

Description

V3P

Table 349:

10.3.5

Default

Type

Description

TRIP

BOOLEAN

Operate/trip signal for frequency gradient

PICKUP

BOOLEAN

Start/pick-up signal for frequency gradient

RESTORE

BOOLEAN

Restore signal for load restoring purposes

BLKDMAGN

BOOLEAN

Blocking indication due to low magnitude

Settings
SAPFRC (81R) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PUFreqGrad

-10.00 - 10.00

Hz/s

0.01

0.50

Frequency gradient pick up value, the sign


defines direction

tTrip

0.000 - 60.000

0.001

0.200

Operate time delay in positive / negative


frequency gradient mode

RestoreFreq

45.00 - 65.00

Hz

0.01

49.90

Restore frequency value

tRestore

0.000 - 60.000

0.001

0.000

Restore time delay

tReset

0.000 - 60.000

0.001

0.000

Time delay for reset

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

677

Section 10
Frequency protection
10.3.6

1MRK 502 066-UUS A

Monitored data
Table 351:

SAPFRC (81R) Monitored data

Name

Type

STARTDUR

10.3.7

REAL

Values (Range)
-

Unit
%

Description
Start duration in percents of
the total operation time

Operation principle
Rate-of-change frequency protection SAPFRC (81) is used to detect fast power system
frequency changes at an early stage. SAPFRC (81) has a settable definite time delay. If the
rate-of-change of frequency remains below the set value, for negative rate-of-change, for
a time period equal to the chosen time delay, the TRIP signal is issued. If the rate-ofchange of frequency remains above the set value, for positive rate-of-change, for a time
period equal to the chosen time delay, the TRIP signal is issued. To avoid an unwanted trip
due to uncertain frequency measurement at low voltage magnitude a voltage controlled
blocking of the function is available from the preprocessing function. If the voltage is
lower than the set blocking voltage in the preprocessing function the function is blocked
and no PICKUP or TRIP signal is issued. If the frequency recovers, after a frequency
decrease, a restore signal is issued.

10.3.7.1

Measurement principle
The rate-of-change of the fundamental frequency of the selected voltage is measured
continuously, and compared with the set value, PUFreqGrad. Rate-of-change frequency
protection SAPFRC (81) is also dependent on the voltage magnitude. If the voltage
magnitude decreases below the setting MinValFreqMeas in the preprocessing function,
which is set as a percentage of a global base voltage parameter, SAPFRC (81) is blocked,
and the output BLKDMAGN is issued. The sign of the setting PUFreqGrad, controls if
SAPFRC (81) reacts on a positive or on a negative change in frequency. If SAPFRC (81)
is used for decreasing frequency that is, the setting PUFreqGrad has been given a negative
value, and a trip signal has been issued, then a 100 ms pulse is issued on the RESTORE
output, when the frequency recovers to a value higher than the setting RestoreFreq. A
positive setting of PUFreqGrad, sets SAPFRC (81) to PICKUP and TRIP for frequency
increases.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.

10.3.7.2

Time delay
Rate-of-change frequency protection SAPFRC (81) has a settable definite time delay,
tTrip. .

678

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

Trip signal issuing requires that the rate-of-change of frequency condition continues for
at least the user set time delay, tTrip. If the PICKUP condition, with respect to the
measured frequency ceases during the delay time, and is not fulfilled again within a user
defined reset time, tReset, the PICKUP output is reset, after that the defined reset time has
elapsed. Here it should be noted that after leaving the hysteresis area, the PICKUP
condition must be fulfilled again and it is not sufficient for the signal to only return back
into the hysteresis area.
The RESTORE output of SAPFRC (81) is set, after a time delay equal to the setting of
tRestore, when the measured frequency has returned to the level corresponding to
RestoreFreq, after an issue of the TRIP output signal. If tRestore is set to 0.000 s the
restore functionality is disabled, and no output will be given. The restore functionality is
only active for lowering frequency conditions and the restore sequence is disabled if a new
negative frequency gradient is detected during the restore period, defined by the settings
RestoreFreq and tRestore.

10.3.7.3

Blocking
Rate-of-change frequency protection (SAPFRC, 81) can be partially or totally blocked, by
binary input signals or by parameter settings, where:
BLOCK:

blocks all outputs

BLKTRIP:

blocks the TRIP output

BLKREST:

blocks the RESTORE output

If the measured voltage level decreases below the setting of MinValFreqMeas in the
preprocessing function, both the PICKUP and the TRIP outputs are blocked.

10.3.7.4

Design
Rate-of-change frequency protection (SAPFRC, 81) measuring element continuously
measures the frequency of the selected voltage and compares it to the setting
PUFreqGrad. The frequency signal is filtered to avoid transients due to power system
switchings and faults. The time integrator operates with a definite delay time. When the
frequency has returned back to the setting of RestoreFreq, the RESTORE output is issued
after the time delay tRestore, if the TRIP signal has earlier been issued. The sign of the
setting PUFreqGrad is essential, and controls if the function is used for raising or
lowering frequency conditions. The design of SAPFRC (81) is schematically described in
figure 317.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

679

Section 10
Frequency protection

1MRK 502 066-UUS A

BLOCK
BLKTRIP
BLKRESET

Voltage

Rate-of-Change
of Frequency

OR

BLOCK

BLKDMAGN

Comparator
V < IntBlockLevel

Comparator
If
[PickupFreqGrad<0
PICKUP
AND
df/dt < PickupFreqGrad]
OR
[PickupFreqGrad>0
AND
df/dt > PickupFreqGrad]
Then
PICKUP

Time integrator
Definite Time Delay
TimeDlyOperate

Pickup
&
Trip
Output
Logic

PICKUP

TimeDlyReset
TRIP

100 ms
Frequency

Comparator
f > RestoreFreq

TimeDlyRestore

RESTORE

en05000835_ansi.vsd

ANSI05000835 V1 EN

Figure 317:

10.3.8

Simplified logic diagram for SAPFRC (81)

Technical data
Table 352:

SAPFRC (81) Technical data

Function

680

Range or value

Accuracy

Trip value, pickup function

(-10.00-10.00) Hz/s

10.0 mHz/s

Trip value, restore enable


frequency

(45.00-65.00) Hz

2.0 mHz

Definite restore time delay

(0.000-60.000) s

0.2% or 100 ms whichever is


greater

Definite time delay for frequency


gradient trip

(0.200-60.000) s

0.2% or 120 ms whichever is


greater

Definite reset time delay

(0.000-60.000) s

0.2% or 250 ms whichever is


greater

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

10.4

Frequency time accumulation protection function


FTAQFVR (81A)

10.4.1

Identification
Function description
Frequency time accumulation protection

10.4.2

IEC 61850
identification
FTAQFVR

IEC 60617
identification
f<>

ANSI/
IEEEidentification
81A

Functionality
Frequency time accumulation protection FTAQFVR (81A) is based on measured system
frequency and time counters. FTAQFVR (81A) for generator protection provides the
BFI_3P output for a particular settable frequency limit, when the system frequency falls
in that settable frequency band limit and positive sequence voltage within settable voltage
band limit. The BFI_3P signal triggers the individual event timer, which is the continuous
time spent within the given frequency band, and the accumulation timer, which is the
cumulative time spent within the given frequency band. Once the timers reach their limit,
an alarm or trip signal is activated to protect the turbine against the abnormal frequency
operation. This function is blocked during generator start-up or shut down conditions by
monitoring the circuit breaker position and current threshold value. The function is also
blocked when the system positive sequence voltage magnitude deviates from the given
voltage band limit which can be enabled by EnaVoltCheck setting.
It is possible to create functionality with more than one frequency band limit by using
multiple instances of the function. This can be achieved by a proper configuration based
on the turbine manufacturer specification.

10.4.3

Function block
FTAQFVR (81A)
I3P*
ERROR
V3P*
TRIP
BLOCK
TRIPACC
CBCLOSE
TRIPCONT
CBOPEN
BFI_3P
LOADINIT
ACCALARM
HOLDACC
STRORHLD
RESETACC
FREQOK
VOLTOK
ANSI14000049-1-en.vsd
ANSI14000023 V1 EN

Figure 318:

FTAQFVR (81A) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

681

Section 10
Frequency protection
10.4.4

1MRK 502 066-UUS A

Signals
Table 353:
Name

Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for three phase current

V3P

GROUP
SIGNAL

Group signal for three phase voltage

BLOCK

BOOLEAN

Block of function

CBCLOSE

BOOLEAN

Circuit breaker closed status input

CBOPEN

BOOLEAN

Circuit breaker open status input

LOADINIT

BOOLEAN

Loads the initial accumulation time to the function

HOLDACC

BOOLEAN

Holds the time accumulation when input is activated

RESETACC

BOOLEAN

Resetting the accumulated time of the function block

Table 354:
Name

682

FTAQFVR (81A) Input signals

FTAQFVR (81A) Output signals


Type

Description

ERROR

BOOLEAN

Error output for incorrect settings

TRIP

BOOLEAN

Trip signal of the function

TRIPACC

BOOLEAN

Trip signal when accumulation time is exceeded the set


limit

TRIPCONT

BOOLEAN

Trip signal when continuous time is exceeded the set


limit

BFI_3P

BOOLEAN

Pickup signal of the function

ACCALARM

BOOLEAN

Alarm signal for reaching the frequency time


accumulation value

STRORHLD

BOOLEAN

Activated when function starts or HOLDACC input is


active

FREQOK

BOOLEAN

Indicates the system frequency within the frequency


band limits

VOLTOK

BOOLEAN

Indicates the system voltage within the voltage band


limits

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

10.4.5
Table 355:

Settings
FTAQFVR (81A) Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Disable/Enable operation of the function

tContinuous

0.0 - 6000.0

0.1

20.0

Continuous time limit for frequency band limits

tAccLimit

10.0 - 90000.0

0.1

600.0

Accumulation time limit for frequency band


limits

FreqHighLimit

35.00 - 90.00

Hz

0.01

47.50

Frequency High limit value

FreqLowLimit

30.00 - 85.00

Hz

0.01

47.00

Frequency Low limit value

CBCheck

Disable
Enable

Enable

Enabling the generator start or stop detection


logic

PickupCurrentLevel

5.0 - 100.0

%IB

0.1

10.0

Threshold current value of generator in


percentage of base current

EnaVoltCheck

Disable
Enable

Enable

Enabling the voltage band limit check

VHighLimit

0.0 - 200.0

%VB

1.0

200.0

Voltage high limit for voltage band limit check

VLowLimit

0.0 - 200.0

%VB

1.0

0.0

Voltage low limit for voltage band limit check

Table 356:
Name

FTAQFVR (81A) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

initTimeAcc

0.000 - 90000.000

0.001

0.0

Initial accumulated time when LOADINIT


command is executed

10.4.6

Monitored data
Table 357:
Name

10.4.7

FTAQFVR (81A) Monitored data


Type

Values (Range)

Unit

Description

FREQ

REAL

Hz

Measured frequency value

ACCTIME

REAL

Accumulated time for


frequency band limits

LASTEVTD

REAL

Accumulation time for last


event of frequency within band

Operation principle

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

683

Section 10
Frequency protection

1MRK 502 066-UUS A

Frequency time accumulation protection function FTAQFVR (81A) is used to protect the
turbine against an abnormal frequency operation. During the startup and shutdown of the
turbine-generator set, FTAQFVR (81A) is blocked to avoid unnecessary accumulation of
time or tripping of generator. FTAQFVR (81A) is also blocked when the system positivesequence voltage magnitude deviates from the given voltage band limit, which can be
enabled with the EnaVoltCheck setting. The overall logic of FTAQFVR (81A) is
explained in Figure319.
The frequency of the measured input voltage is monitored continuously and compared to
the set frequency band limits FreqHighLimit and FreqLowLimit. When the measured
system frequency is above the FreqLowLimit setting and below the FreqHighLimit
setting, the FREQOK and PICKUP signals are activated. The BFI_3P signal is controlled
by the measured current and voltage input magnitude and the status of the circuit breaker
position.
FTAQFVR (81A) function will block BFI_3P signal activation and Accumulation of
time under two following conditions even if the system frequency falls within set band
limits.

When the generator is not synchronized as indicated by the CBOPEN signal input:
Generator currents are considered to detect whether the generator is supplying its unit
auxiliary supply transformers or not. FTAQFVR (81A) function will be blocked
when the measured current magnitude drops below the setting PickupCurrentLevel
and CBOPEN input is high. FTAQFVR (81A) remains blocked until the generator
returns to the operation condition. It can be verified by using the CBCLOSE signal.
Generator's start and stop detection logics for the BFI_3P output can be ignored by
disabling the CBCheck setting.
When the positive-sequence voltage of the measured input voltage is outside the band
limit.
The BFI_3P output will be blocked if the EnaVoltCheck setting is enabled and the
system positive sequence voltage is not within the voltage band limits.
Voltage band limit check will be ignored for the BFI_3P output if the EnaVoltCheck
setting is disabled. The voltage band limits are set with the settings VHighLimit and
VLowLimit.
The output VOLTOK is activated only if the system positive-sequence voltage falls
within the voltage band limits and the EnaVoltCheck setting is enabled.

To avoid oscillations of the BFI_3P output signal, a hysteresis has been added with
current input comparison and voltage input comparison. It is also possible to block
FTAQFVR (81A) completely by activating the binary input BLOCK and its function is to
reset all the binary outputs of FTAQFVR (81A) and freeze the accumulation time.

Time counters
FTAQFVR (81A) uses two time counters.
684

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

1.

2.

Individual event time: The individual event time counter registers the time passing if
the system frequency falls within the frequency band limits each time. It resets when
the frequency comes out of the frequency band limits and also when the BLOCK
binary input is activated and start from zero when a new start is activated.
Accumulation time: The accumulation time counter registers the time passing
whenever the BFI_3P output is activated. It holds the registered time value even
when the BFI_3P signal is deactivated and continues from the registered value when
the BFI_3P signal is reactivated.

The registration of accumulation time is frozen at its present value when the input
HOLDACC or BLOCK is activated. The accumulation time can be set to the initTimeAcc
parameter value by activating the LOADINT input with the LHMI and it can be reset to
zero by activating the RESETACC input. The RESETACC input can be activated by a
binary input. The accumulated time ACCTIME is provided as a service output.
The last completed individual event time is updated in the LASTEVTD output. This output
holds the last completed individual event time until the next event to complete.

Trip logic
The individual event and accumulation timer values are compared to the tCont and
tAcclLimit settings respectively. If these counter values exceed their limit values,
TRIPCONT and ACCALARM outputs will be activated. The TRIPACC output is activated
if both the ACCALARM and BFI_3P signals are activated. A common TRIP signal is
generated when either TRIPCONT or TRIPACC is activated.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

685

Section 10
Frequency protection

1MRK 502 066-UUS A

Comparator
If
FreqHighLimit <=
FreqLowLimit
Then
ERROR

ERROR

FREQ

FREQ

V3P

Comparator
If
f <= FreqHighLimit
AND
f > FreqLowLimit
Then
PICKUP

FREQOK

FREQOK

VOLTOK

VOLTOK

BFI_3P

Comparator
V01 <= VHighLimit
AND
V01 >= VLowLimit
I3P

Comparator
I < PickupCurrentLevel

CBOPEN
CBCLOSE
LOADINIT

PICKUP
Signal Routing
Based on
Generator
Start or Stop
Detection Logic
and
Voltage Band Limit
Check Logic

PICKUP

Accumulation time
counter

TRIPACC

Continuous time
counter

TRIPCONT

AND
Pickup & Trip
Output Logic

TRIP

ACCALARM

STRORHLD

RESETACC
ACCTIME
HOLDTIME
LASTEVTD

BLOCK

ANSI12000609-1-en.vsd
ANSI12000609 V1 EN

Figure 319:

Logical diagram

To achieve a proper operation, the set frequency high limit should be more than the set
frequency low limit. To avoid malfunction, a check is performed that FreqHighLimit is
greater than FreqLowLimit. If not, the ERROR signal is activated.
FTAQFVR (81A) can be instantiated with one or more frequency ranges according to the
turbine manufacturer's specification. When the frequency falls in to the common zone
when two frequency ranges overlap it is necessary to block one instance and keep only one
instance of FTAQFVR (81A) active. The STRORHLD output is activated when either the
BFI_3P output is active or when the HOLDACC input signal is on. The STRORHLD output
is connected to the input HOLDACC of the other instance of FTAQFVR (81A).

686

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 10
Frequency protection

1MRK 502 066-UUS A

Table 358:

FTAQFVR (81A) technical data

Function

Range or value

Accuracy

Trip value, frequency high limit


level at symmetrical three phase
voltage

(35.00 90.00) Hz

2.0 mHz

Trip value, frequency low limit


level at symmetrical three phase
voltage

(30.00 85.00) Hz

2.0 mHz

Trip value, voltage high and low


limit for voltage band limit check

(0.0 200.0)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Trip value, current pickup level

(5.0 100.0)% of IBase

1.0% of Ir or 0.01 A at IIn

Independent time delay for the


continuous time limit at fset+0.02
Hz to fset-0.02 Hz

(0.0 6000.0) s

0.2% or 200 ms whichever is


greater

Independent time delay for the


accumulation time limit at fset
+0.02 Hz to fset-0.02 Hz

(10.0 90000.0) s

0.2% or 200 ms whichever is


greater

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

687

688

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Section 11

Multipurpose protection

11.1

General current and voltage protection CVGAPC

11.1.1

Identification
Function description
General current and voltage protection

11.1.2

IEC 61850
identification
CVGAPC

IEC 60617
identification
2(I>/U<)

ANSI/IEEE C37.2
device number
-

Functionality
The protection module is recommended as a general backup protection with many
possible application areas due to its flexible measuring and setting facilities.
The built-in overcurrent protection feature has two settable current pickups. Both of them
can be used either with definite time or inverse time characteristic. The overcurrent
protection steps can be made directional with selectable voltage polarizing quantity.
Additionally they can be voltage and/or current controlled/restrained. 2nd harmonic
restraining facility is available as well. At too low polarizing voltage the overcurrent
feature can be either blocked, made non directional or ordered to use voltage memory in
accordance with a parameter setting.
Additionally two overvoltage and two undervoltage steps, either with definite time or
inverse time characteristic, are available within each function.
The general function suits applications with underimpedance and voltage controlled
overcurrent solutions. The general function can also be utilized for generator transformer
protection applications where positive, negative or zero sequence components of current
and voltage quantities are typically required.
Additionally, generator applications such as loss of field, inadvertent energizing, stator or
rotor overload, circuit breaker head flash-over and open phase detection are just a few of
possible protection arrangements with these functions.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

689

Section 11
Multipurpose protection
11.1.2.1

1MRK 502 066-UUS A

Inadvertent generator energization


When the generator is taken out of service, and stand-still, there is a risk that the generator
circuit breaker flashes over or is closed by mistake.
To prevent damages on the generator or turbine, it is essential that high speed tripping is
provided in case of inadvertent energization of the generator. This tripping should be
almost instantaneous (< 100 ms).
There is a risk that the current into the generator at inadvertent energization will be limited
so that the normal overcurrent or underimpedance protection will not detect the
dangerous situation. The delay of these protection functions might be too long. For big and
important machines, fast protection against inadvertent energizing should, therefore, be
included in the protective scheme.

11.1.3

Function block
CVGAPC
I3P*
V3P*
BLOCK
BLKOC1
BLKOC1TR
ENMLTOC1
BLKOC2
BLKOC2TR
ENMLTOC2
BLKUC1
BLKUC1TR
BLKUC2
BLKUC2TR
BLKOV1
BLKOV1TR
BLKOV2
BLKOV2TR
BLKUV1
BLKUV1TR
BLKUV2
BLKUV2TR

TRIP
TROC1
TROC2
TRUC1
TRUC2
TROV1
TROV2
TRUV1
TRUV2
PICKUP
PU_OC1
PU_OC2
PU_UC1
PU_UC2
PU_OV1
PU_OV2
PU_UV1
PU_UV2
BLK2ND
DIROC1
DIROC2
VDIRLOW
CURRENT
ICOSFI
VOLTAGE
VIANGLE

ANSI05000372-2-en.vsd
ANSI05000372 V2 EN

Figure 320:

690

CVGAPC function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

11.1.4

Signals
Table 359:
Name

CVGAPC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKOC1

BOOLEAN

Block of over current function OC1

BLKOC1TR

BOOLEAN

Block of trip for over current function OC1

ENMLTOC1

BOOLEAN

When activated, the current multiplier is in use for OC1

BLKOC2

BOOLEAN

Block of over current function OC2

BLKOC2TR

BOOLEAN

Block of trip for over current function OC2

ENMLTOC2

BOOLEAN

When activated, the current multiplier is in use for OC2

BLKUC1

BOOLEAN

Block of under current function UC1

BLKUC1TR

BOOLEAN

Block of trip for under current function UC1

BLKUC2

BOOLEAN

Block of under current function UC2

BLKUC2TR

BOOLEAN

Block of trip for under current function UC2

BLKOV1

BOOLEAN

Block of over voltage function OV1

BLKOV1TR

BOOLEAN

Block of trip for over voltage function OV1

BLKOV2

BOOLEAN

Block of over voltage function OV2

BLKOV2TR

BOOLEAN

Block of trip for over voltage function OV2

BLKUV1

BOOLEAN

Block of under voltage function UV1

BLKUV1TR

BOOLEAN

Block of trip for under voltage function UV1

BLKUV2

BOOLEAN

Block of under voltage function UV2

BLKUV2TR

BOOLEAN

Block of trip for under voltage function UV2

Table 360:
Name

CVGAPC Output signals


Type

Description

TRIP

BOOLEAN

Common trip signal

TROC1

BOOLEAN

Trip signal from overcurrent function OC1

TROC2

BOOLEAN

Trip signal from overcurrent function OC2

TRUC1

BOOLEAN

Trip signal from undercurrent function UC1

TRUC2

BOOLEAN

Trip signal from undercurrent function UC2

TROV1

BOOLEAN

Trip signal from overvoltage function OV1

TROV2

BOOLEAN

Trip signal from overvoltage function OV2

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

691

Section 11
Multipurpose protection

Name

692

1MRK 502 066-UUS A

Type

Description

TRUV1

BOOLEAN

Trip signal from undervoltage function UV1

TRUV2

BOOLEAN

Trip signal from undervoltage function UV2

PICKUP

BOOLEAN

Common pickup signal

PU_OC1

BOOLEAN

Pickup signal from overcurrent function OC1

PU_OC2

BOOLEAN

Pickup signal from overcurrent function OC2

PU_UC1

BOOLEAN

Pickup signal from undercurrent function UC1

PU_UC2

BOOLEAN

Pickup signal from undercurrent function UC2

PU_OV1

BOOLEAN

Pickup signal from overvoltage function OV1

PU_OV2

BOOLEAN

Pickup signal from overvoltage function OV2

PU_UV1

BOOLEAN

Pickup signal from undervoltage function UV1

PU_UV2

BOOLEAN

Pickup signal from undervoltage function UV2

BLK2ND

BOOLEAN

Second harmonic block signal

DIROC1

INTEGER

Directional mode of OC1 (nondir, forward,reverse)

DIROC2

INTEGER

Directional mode of OC2 (nondir, forward,reverse)

VDIRLOW

BOOLEAN

Low voltage for directional polarization

CURRENT

REAL

Measured current value

ICOSFI

REAL

Measured current multiplied with cos (Phi)

VOLTAGE

REAL

Measured voltage value

VIANGLE

REAL

Angle between voltage and current

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

11.1.5
Table 361:
Name

Settings
CVGAPC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

CurrentInput

Phase A
Phase B
Phase C
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph

MaxPh

Select current signal which will be measured


inside function

VoltageInput

Phase A
Phase B
Phase C
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph

MaxPh

Select voltage signal which will be measured


inside function

OperHarmRestr

Disabled
Enabled

Disabled

Disable/Enable operation of 2nd harmonic


restrain

l_2nd/l_fund

10.0 - 50.0

1.0

20.0

Ratio of second to fundamental current


harmonic in %

BlkLevel2nd

10 - 5000

%IB

5000

Harm analyse disabled above this current level


in % of fundamental current

EnRestrainCurr

Disabled
Enabled

Disabled

Disable/Enable current restrain function

RestrCurrInput

PosSeq
NegSeq
3*ZeroSeq
Max

PosSeq

Select current signal which will be used for


current restrain

RestrCurrCoeff

0.00 - 5.00

0.01

0.00

Restraining current coefficient

RCADir

-180 - 180

Deg

-75

Relay Characteristic Angle

ROADir

1 - 90

Deg

75

Relay Operate Angle

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

693

Section 11
Multipurpose protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

LowVolt_VM

0.0 - 5.0

%VB

0.1

0.5

Below this level in % of VBase setting


ActLowVolt takes over

Operation_OC1

Disabled
Enabled

Disabled

Disable/Enable Operation of OC1

PickupCurr_OC1

2.0 - 5000.0

%IB

1.0

120.0

Operate current level for OC1 in % of IBase

CurveType_OC1

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for OC1

tDef_OC1

0.00 - 6000.00

0.01

0.50

Definite time delay OC1

TD_OC1

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time delay for


OC1

IMin1

1 - 10000

%IB

100

Minimum operate current for step1 in % of


IBase

tMin_OC1

0.00 - 6000.00

0.01

0.05

Minimum operate time for IEC IDMT curves for


OC1

VCntrlMode_OC1

Voltage control
Disabled

Disabled

Control mode for voltage controlled OC1


function

VDepMode_OC1

Step
Slope

Step

Voltage dependent mode OC1 (step, slope)

VDepFact_OC1

0.02 - 5.00

0.01

1.00

Multiplying factor for current pickup when OC1


is voltage dependent

VLowLimit_OC1

1.0 - 200.0

%VB

0.1

50.0

Voltage low limit setting OC1 in % of UBase

VHighLimit_OC1

1.0 - 200.0

%VB

0.1

100.0

Voltage high limit setting OC1 in % of UBase

HarmRestr_OC1

Disabled
Enabled

Disabled

Enable block of OC1 by 2nd harmonic restrain

DirMode_OC1

Non-directional
Forward
Reverse

Non-directional

Directional mode of OC1 (nondir, forward,


reverse)

DirPrinc_OC1

I&V
IcosPhi&V

I&V

Measuring on IandV or IcosPhiandV for OC1

ActLowVolt1_VM

Non-directional
Block
Memory

Non-directional

Low voltage level action for Dir_OC1 (Nodir,


Blk, Mem)

Table continues on next page

694

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Operation_OC2

Disabled
Enabled

Disabled

Disable/Enable Operation od OC2

PickupCurr_OC2

2.0 - 5000.0

%IB

1.0

120.0

Operate current level for OC2 in % of IBase

CurveType_OC2

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for OC2

tDef_OC2

0.00 - 6000.00

0.01

0.50

Definite time delay OC2

TD_OC2

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time delay for


OC2

IMin2

1 - 10000

%IB

50

Minimum operate current for step2 in % of


IBase

tMin_OC2

0.00 - 6000.00

0.01

0.05

Minimum operate time for IEC IDMT curves for


OC2

VCntrlMode_OC2

Voltage control
Disabled

Disabled

Control mode for voltage controlled OC2


function

VDepMode_OC2

Step
Slope

Step

Voltage dependent mode OC2 (step, slope)

VDepFact_OC2

0.02 - 5.00

0.01

1.00

Multiplying factor for current pickup when OC2


is voltage dependent

VLowLimit_OC2

1.0 - 200.0

%VB

0.1

50.0

Voltage low limit setting OC2 in % of UBase

VHighLimit_OC2

1.0 - 200.0

%VB

0.1

100.0

Voltage high limit setting OC2 in % of UBase

HarmRestr_OC2

Disabled
Enabled

Disabled

Enable block of OC2 by 2nd harmonic restrain

DirMode_OC2

Non-directional
Forward
Reverse

Non-directional

Directional mode of OC2 (nondir, forward,


reverse)

DirPrinc_OC2

I&V
IcosPhi&V

I&V

Measuring on IandV or IcosPhiandV for OC2

ActLowVolt2_VM

Non-directional
Block
Memory

Non-directional

Low voltage level action for Dir_OC2 (Nodir,


Blk, Mem)

Operation_UC1

Disabled
Enabled

Disabled

Disable/Enable operation of UC1

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

695

Section 11
Multipurpose protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

EnBlkLowI_UC1

Disabled
Enabled

Disabled

Enable internal low current level blocking for


UC1

BlkLowCurr_UC1

0 - 150

%IB

20

Internal low current blocking level for UC1 in %


of IBase

PickupCurr_UC1

2.0 - 150.0

%IB

1.0

70.0

Operate undercurrent level for UC1 in % of


IBase

tDef_UC1

0.00 - 6000.00

0.01

0.50

Definite time delay of UC1

tResetDef_UC1

0.00 - 6000.00

0.01

0.00

Reset time delay used in IEC Definite Time


curve UC1

HarmRestr_UC1

Disabled
Enabled

Disabled

Enable block of UC1 by 2nd harmonic restrain

Operation_UC2

Disabled
Enabled

Disabled

Disable/Enable operation of UC2

EnBlkLowI_UC2

Disabled
Enabled

Disabled

Enable internal low current level blocking for


UC2

BlkLowCurr_UC2

0 - 150

%IB

20

Internal low current blocking level for UC2 in %


of IBase

PickupCurr_UC2

2.0 - 150.0

%IB

1.0

70.0

Operate undercurrent level for UC2 in % of


IBase

tDef_UC2

0.00 - 6000.00

0.01

0.50

Definite time delay of UC2

HarmRestr_UC2

Disabled
Enabled

Disabled

Enable block of UC2 by 2nd harmonic restrain

Operation_OV1

Disabled
Enabled

Disabled

Disable/Enable operation of OV1

PickupVolt_OV1

2.0 - 200.0

%VB

0.1

150.0

Operate voltage level for OV1 in % of VBase

CurveType_OV1

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for OV1

tDef_OV1

0.00 - 6000.00

0.01

1.00

Operate time delay in sec for definite time use


of OV1

tMin_OV1

0.00 - 6000.00

0.01

0.05

Minimum operate time for Inverse-Time curves


for OV1

TD_OV1

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time delay for


OV1

Operation_OV2

Disabled
Enabled

Disabled

Disable/Enable operation of OV2

PickupVolt_OV2

2.0 - 200.0

%VB

0.1

150.0

Operate voltage level for OV2 in % of VBase

CurveType_OV2

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for OV2

tDef_OV2

0.00 - 6000.00

0.01

1.00

Operate time delay in sec for definite time use


of OV2

Table continues on next page


696

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

tMin_OV2

0.00 - 6000.00

0.01

0.05

Minimum operate time for Inverse-Time curves


for OV2

TD_OV2

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time delay for


OV2

Operation_UV1

Disabled
Enabled

Disabled

Disable/Enable operation of UV1

PickupVolt_UV1

2.0 - 150.0

%VB

0.1

50.0

Operate undervoltage level for UV1 in % of


VBase

CurveType_UV1

Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve

Definite time

Selection of time delay curve type for UV1

tDef_UV1

0.00 - 6000.00

0.01

1.00

Operate time delay in sec for definite time use


of UV1

tMin_UV1

0.00 - 6000.00

0.01

0.05

Minimum operate time for Inverse-Time curves


for UV1

TD_UV1

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time delay for


UV1

EnBlkLowV_UV1

Disabled
Enabled

Enabled

Enable internal low voltage level blocking for


UV1

BlkLowVolt_UV1

0.0 - 5.0

%VB

0.1

0.5

Internal low voltage blocking level for UV1 in %


of VBase

Operation_UV2

Disabled
Enabled

Disabled

Disable/Enable operation of UV2

PickupVolt_UV2

2.0 - 150.0

%VB

0.1

50.0

Operate undervoltage level for UV2 in % of


VBase

CurveType_UV2

Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve

Definite time

Selection of time delay curve type for UV2

tDef_UV2

0.00 - 6000.00

0.01

1.00

Operate time delay in sec for definite time use


of UV2

tMin_UV2

0.00 - 6000.00

0.01

0.05

Minimum operate time for Inverse-Time curves


for UV2

TD_UV2

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time delay for


UV2

EnBlkLowV_UV2

Disabled
Enabled

Enabled

Enable internal low voltage level blocking for


UV2

BlkLowVolt_UV2

0.0 - 5.0

%VB

0.1

0.5

Internal low voltage blocking level for UV2 in %


of VBase

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description

697

Section 11
Multipurpose protection

Table 362:

1MRK 502 066-UUS A

CVGAPC Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

MultPU_OC1

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting value


for OC1

ResCrvType_OC1

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for OC1

tResetDef_OC1

0.00 - 6000.00

0.01

0.00

Reset time delay used in IEC Definite Time


curve OC1

P_OC1

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for OC1

A_OC1

0.000 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for OC1

B_OC1

0.000 - 99.000

0.001

0.000

Parameter B for customer programmable


curve for OC1

C_OC1

0.000 - 1.000

0.001

1.000

Parameter C for customer programmable


curve for OC1

PR_OC1

0.005 - 3.000

0.001

0.500

Parameter PR for customer programmable


curve for OC1

TR_OC1

0.005 - 600.000

0.001

13.500

Parameter TR for customer programmable


curve for OC1

CR_OC1

0.1 - 10.0

0.1

1.0

Parameter CR for customer programmable


curve for OC1

MultPU_OC2

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting value


for OC2

ResCrvType_OC2

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for OC2

tResetDef_OC2

0.00 - 6000.00

0.01

0.00

Reset time delay used in IEC Definite Time


curve OC2

P_OC2

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for OC2

A_OC2

0.000 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for OC2

B_OC2

0.000 - 99.000

0.001

0.000

Parameter B for customer programmable


curve for OC2

C_OC2

0.000 - 1.000

0.001

1.000

Parameter C for customer programmable


curve for OC2

PR_OC2

0.005 - 3.000

0.001

0.500

Parameter PR for customer programmable


curve for OC2

TR_OC2

0.005 - 600.000

0.001

13.500

Parameter TR for customer programmable


curve for OC2

CR_OC2

0.1 - 10.0

0.1

1.0

Parameter CR for customer programmable


curve for OC2

tResetDef_UC2

0.00 - 6000.00

0.01

0.00

Reset time delay used in IEC Definite Time


curve UC2

Table continues on next page


698

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

ResCrvType_OV1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of reset curve type for OV1

tResetDef_OV1

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for definite time use of


OV1

tResetIDMT_OV1

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for Inverse-Time


curves for OV1

A_OV1

0.005 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for OV1

B_OV1

0.500 - 99.000

0.001

1.000

Parameter B for customer programmable


curve for OV1

C_OV1

0.000 - 1.000

0.001

1.000

Parameter C for customer programmable


curve for OV1

D_OV1

0.000 - 10.000

0.001

0.000

Parameter D for customer programmable


curve for OV1

P_OV1

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for OV1

ResCrvType_OV2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of reset curve type for OV2

tResetDef_OV2

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for definite time use of


OV2

tResetIDMT_OV2

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for Inverse-Time


curves for OV2

A_OV2

0.005 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for OV2

B_OV2

0.500 - 99.000

0.001

1.000

Parameter B for customer programmable


curve for OV2

C_OV2

0.000 - 1.000

0.001

1.000

Parameter C for customer programmable


curve for OV2

D_OV2

0.000 - 10.000

0.001

0.000

Parameter D for customer programmable


curve for OV2

P_OV2

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for OV2

ResCrvType_UV1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of reset curve type for UV1

tResetDef_UV1

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for definite time use of


UV1

tResetIDMT_UV1

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for Inverse-Time


curves for UV1

A_UV1

0.005 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for UV1

B_UV1

0.500 - 99.000

0.001

1.000

Parameter B for customer programmable


curve for UV1

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

699

Section 11
Multipurpose protection

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

C_UV1

0.000 - 1.000

0.001

1.000

Parameter C for customer programmable


curve for UV1

D_UV1

0.000 - 10.000

0.001

0.000

Parameter D for customer programmable


curve for UV1

P_UV1

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for UV1

ResCrvType_UV2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of reset curve type for UV2

tResetDef_UV2

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for definite time use of


UV2

tResetIDMT_UV2

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for Inverse-Time


curves for UV2

A_UV2

0.005 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for UV2

B_UV2

0.500 - 99.000

0.001

1.000

Parameter B for customer programmable


curve for UV2

C_UV2

0.000 - 1.000

0.001

1.000

Parameter C for customer programmable


curve for UV2

D_UV2

0.000 - 10.000

0.001

0.000

Parameter D for customer programmable


curve for UV2

P_UV2

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for UV2

Table 363:
Name
GlobalBaseSel

11.1.6

CVGAPC Non group settings (basic)


Values (Range)
1 - 12

Unit

Step

Default
1

Description
Selection of one of the Global Base Value
groups

Monitored data
Table 364:
Name

CVGAPC Monitored data


Type

Values (Range)

Unit

Description

DIROC1

INTEGER

1=Forward
0=Nondirectional
2=Reverse

Directional mode of OC1


(nondir, forward,reverse)

DIROC2

INTEGER

1=Forward
0=Nondirectional
2=Reverse

Directional mode of OC2


(nondir, forward,reverse)

CURRENT

REAL

Measured current value

Table continues on next page

700

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

ICOSFI

REAL

Measured current multiplied


with cos (Phi)

VOLTAGE

REAL

kV

Measured voltage value

VIANGLE

REAL

deg

Angle between voltage and


current

11.1.7

Operation principle

11.1.7.1

Measured quantities within CVGAPC


General current and voltage protection (CVGAPC) function is always connected to threephase current and three-phase voltage input in the configuration tool, but it will always
measure only one current and one voltage quantity selected by the end user in the setting
tool.
The user can select to measure one of the current quantities shown in table 365.
Table 365:

Current selection for CVGAPC function

Set value for the


parameter

CurrentInput

Comment

PhaseA

CVGAPC function will measure the phase A current phasor

PhaseB

CVGAPC function will measure the phase B current phasor

PhaseC

CVGAPC function will measure the phase C current phasor

PosSeq

CVGAPC function will measure internally calculated positive sequence


current phasor

NegSeq

CVGAPC function will measure internally calculated negative sequence


current phasor

3ZeroSeq

CVGAPC function will measure internally calculated zero sequence current


phasor multiplied by factor 3

MaxPh

CVGAPC function will measure current phasor of the phase with maximum
magnitude

MinPh

CVGAPC function will measure current phasor of the phase with minimum
magnitude

UnbalancePh

CVGAPC function will measure magnitude of unbalance current, which is


internally calculated as the algebraic magnitude difference between the
current phasor of the phase with maximum magnitude and current phasor of
the phase with minimum magnitude. Phase angle will be set to 0 all the time

10

PhaseA-PhaseB

CVGAPC function will measure the current phasor internally calculated as the
vector difference between the phase A current phasor and phase B current
phasor (IA-IB)

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

701

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Set value for the


parameter

CurrentInput

Comment

11

PhaseB-PhaseC

CVGAPC function will measure the current phasor internally calculated as the
vector difference between the phase B current phasor and phase C current
phasor (IB-IC)

12

PhaseC-PhaseA

CVGAPC function will measure the current phasor internally calculated as the
vector difference between the phase C current phasor and phase A current
phasor ( IC-IA)

13

MaxPh-Ph

CVGAPC function will measure ph-ph current phasor with the maximum
magnitude

14

MinPh-Ph

CVGAPC function will measure ph-ph current phasor with the minimum
magnitude

15

UnbalancePh-Ph

CVGAPC function will measure magnitude of unbalance current, which is


internally calculated as the algebraic magnitude difference between the ph-ph
current phasor with maximum magnitude and ph-ph current phasor with
minimum magnitude. Phase angle will be set to 0 all the time

The user can select to measure one of the voltage quantities shown in table 366:
Table 366:

Voltage selection for CVGAPC function

Set value for the


parameter

VoltageInput

Comment

PhaseA

CVGAPC function will measure the phase A voltage phasor

PhaseB

CVGAPC function will measure the phase B voltage phasor

PhaseC

CVGAPC function will measure the phase C voltage phasor

PosSeq

CVGAPC function will measure internally calculated positive sequence


voltage phasor

-NegSeq

CVGAPC function will measure internally calculated negative sequence


voltage phasor. This voltage phasor will be intentionally rotated for 180 in
order to enable easier settings for the directional feature when used.

-3ZeroSeq

CVGAPC function will measure internally calculated zero sequence voltage


phasor multiplied by factor 3. This voltage phasor will be intentionally rotated
for 180 in order to enable easier settings for the directional feature when
used.

MaxPh

CVGAPC function will measure voltage phasor of the phase with maximum
magnitude

MinPh

CVGAPC function will measure voltage phasor of the phase with minimum
magnitude

UnbalancePh

CVGAPC function will measure magnitude of unbalance voltage, which is


internally calculated as the algebraic magnitude difference between the
voltage phasor of the phase with maximum magnitude and voltage phasor of
the phase with minimum magnitude. Phase angle will be set to 0 all the time

10

PhaseA-PhaseB

CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase A voltage phasor and phase B voltage
phasor (VA-VB)

Table continues on next page

702

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Set value for the


parameter

VoltageInput

Comment

11

PhaseB-PhaseC

CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase B voltage phasor and phase C voltage
phasor (VB-VC)

12

PhaseC-PhaseA

CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase C voltage phasor and phase A voltage
phasor ( VC-VA)

13

MaxPh-Ph

CVGAPC function will measure ph-ph voltage phasor with the maximum
magnitude

14

MinPh-Ph

CVGAPC function will measure ph-ph voltage phasor with the minimum
magnitude

15

UnbalancePh-Ph

CVGAPC function will measure magnitude of unbalance voltage, which is


internally calculated as the algebraic magnitude difference between the ph-ph
voltage phasor with maximum magnitude and ph-ph voltage phasor with
minimum magnitude. Phase angle will be set to 0 all the time

It is important to notice that the voltage selection from table 366 is always applicable
regardless the actual external VT connections. The three-phase VT inputs can be
connected to IED as either three phase-to-ground voltages VA, VB & VC or three phaseto-phase voltages VAB, VBC & VCA). This information about actual VT connection is
entered as a setting parameter for the pre-processing block, which will then take automatic
care about it.
The user can select one of the current quantities shown in table 367 for built-in current
restraint feature:
Table 367:

Restraint current selection for CVGAPC function

Set value for the


parameter RestrCurr

11.1.7.2

Comment

PosSeq

CVGAPC function will measure internally calculated positive sequence


current phasor

NegSeq

CVGAPC function will measure internally calculated negative sequence


current phasor

3ZeroSeq

CVGAPC function will measure internally calculated zero sequence current


phasor multiplied by factor 3

MaxPh

CVGAPC function will measure current phasor of the phase with maximum
magnitude

Base quantities for CVGAPC function


The parameter settings for the base quantities, which represent the base (100%) for pickup
levels of all measuring stages, shall be entered as setting parameters for every CVGAPC
function.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

703

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Base current shall be entered as:


1.
2.

rated phase current of the protected object in primary amperes, when the measured
Current Quantity is selected from 1 to 9, as shown in table 365.
rated phase current of the protected object in primary amperes multiplied by 3
(1.732*Iphase), when the measured Current Quantity is selected from 10 to 15, as
shown in table 365.

Base voltage shall be entered as:


1.
2.

11.1.7.3

rated phase-to-ground voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table 366.
rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table 366.

Built-in overcurrent protection steps


Two overcurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overcurrent step simply compares the magnitude of the measured current quantity (see
table 365) with the set pickup level. Non-directional overcurrent step will pickup if the
magnitude of the measured current quantity is bigger than this set level. However
depending on other enabled built-in features this overcurrent pickup might not cause the
overcurrent step pickup signal. Pickup signal will only come if all of the enabled built-in
features in the overcurrent step are fulfilled at the same time.

Second harmonic feature


The overcurrent protection step can be restrained by a second harmonic component in the
measured current quantity (see table 365). However it shall be noted that this feature is not
applicable when one of the following measured currents is selected:

PosSeq (positive sequence current)


NegSeq (negative sequence current)
UnbalancePh (unbalance phase current)
UnbalancePh-Ph (unbalance ph-ph current)

This feature will simple prevent overcurrent step pickup if the second-to-first harmonic
ratio in the measured current exceeds the set level.

Directional feature
The overcurrent protection step operation can be made dependent on the relevant phase
angle between measured current phasor (see table 365) and measured voltage phasor (see
table 366). In protection terminology it means that the General currrent and voltage
704

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

protection (CVGAPC) function can be made directional by enabling this built-in feature.
In that case overcurrent protection step will only trip if the current flow is in accordance
with the set direction (Forward, which means towards the protected object, or Reverse,
which means from the protected object). For this feature it is of the outmost importance to
understand that the measured voltage phasor (see table 366) and measured current phasor
(see table 365) will be used for directional decision. Therefore it is the sole responsibility
of the end user to select the appropriate current and voltage signals in order to get a proper
directional decision. CVGAPC function will NOT do this automatically. It will simply use
the current and voltage phasors selected by the end user to check for the directional
criteria.
Table 368 gives an overview of the typical choices (but not the only possible ones) for
these two quantities from traditional directional relays.
Table 368:
Set value for the
parameter

CurrentInput

Typical current and voltage choices for directional feature


Set value for the
parameter

VoltageInput

Comment

PosSeq

PosSeq

Directional positive sequence overcurrent function is


obtained. Typical setting for RCADir is from -45 to -90
depending on the power system voltage level (X/R ratio)

NegSeq

-NegSeq

Directional negative sequence overcurrent function is


obtained. Typical setting for RCADir is from -45 to -90
depending on the power system voltage level (X/R ratio)

3ZeroSeq

-3ZeroSeq

Directional zero sequence overcurrent function is obtained.


Typical setting for RCADir is from 0 to -90 depending on
the power system grounding (that is, solidly grounding,
grounding via resistor)

Phase1

Phase2-Phase3

Directional overcurrent function for the first phase is


obtained. Typical setting for RCADir is +30 or +45

Phase2

Phase3-Phase1

Directional overcurrent function for the second phase is


obtained. Typical setting for RCADir is +30 or +45

Phase3

Phase1-Phase2

Directional overcurrent function for the third phase is


obtained. Typical setting for RCADir is +30 or +45

Unbalance current or voltage measurement shall not be used when the directional feature
is enabled.
Two types of directional measurement principles are available, I & V and IcosPhi&V. The
first principle, referred to as "I & V" in the parameter setting tool, checks that:

the magnitude of the measured current is bigger than the set pick-up level
the phasor of the measured current is within the operating region (defined by the relay
trip angle, ROADir parameter setting; see figure 321).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

705

Section 11
Multipurpose protection

1MRK 502 066-UUS A

V=-3V0

RCADir
Ipickup

ROADir

I=3Io

Operate region
mta line

en05000252_anis.vsd
IEC05000252-ANIS V1 EN

Figure 321:

I & V directional operating principle for CVGAPC function

where:

RCADir is -75
ROADir is 50

The second principle, referred to as "IcosPhi&V" in the parameter setting tool, checks
that:

706

that the product Icos() is bigger than the set pick-up level, where is angle
between the current phasor and the mta line
that the phasor of the measured current is within the operating region (defined by the
Icos() straight line and the relay trip angle, ROADir parameter setting; see
figure 321).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

V=-3V0

RCADir
Ipickup

ROADir

I=3Io

Operate region
mta line

en05000253_ansi.vsd
ANSI05000253 V1 EN

Figure 322:

CVGAPC, IcosPhi&V directional operating principle

where:

RCADir is -75
ROADir is 50

Note that it is possible to decide by a parameter setting how the directional feature shall
behave when the magnitude of the measured voltage phasor falls below the pre-set value.
User can select one of the following three options:

Non-directional (operation allowed for low magnitude of the reference voltage)


Block (operation prevented for low magnitude of the reference voltage)
Memory (memory voltage shall be used to determine direction of the current)

It shall also be noted that the memory duration is limited in the algorithm to 100 ms. After
that time the current direction will be locked to the one determined during memory time
and it will re-set only if the current fails below set pickup level or voltage goes above set
voltage memory limit.

Voltage restraint/control feature


The overcurrent protection step operation can be made dependent of a measured voltage
quantity (see table 366). Practically then the pickup level of the overcurrent step is not
constant but instead decreases with the decrease in the magnitude of the measured voltage
quantity. Two different types of dependencies are available:

Voltage restraint overcurrent (when setting parameter VDepMode_OC1=Slope)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

707

Section 11
Multipurpose protection

1MRK 502 066-UUS A

OC1 Stage Pickup Level

PickupCurr_OC1

VDepFact_OC1 * PickupCurr_OC1

VLowLimit_OC1

VHighLimit_OC1

Selected Voltage
Magnitude
en05000324_ansi.vsd

ANSI05000324 V1 EN

Figure 323:

Example for OC1 step current pickup level variation as function of


measured voltage magnitude in Slope mode of operation

Voltage controlled overcurrent (when setting parameter VDepMode_OC1=Step)


OC1 Stage Pickup Level

PickupCurr_OC1

VDepFact_OC1 *
PickupCurr_OC1

VHighLimit_OC1

Selected Voltage Magnitude


en05000323_ansi.vsd

ANSI05000323 V1 EN

Figure 324:

Example for OC1 step current pickup level variation as function of


measured voltage magnitude in Step mode of operation

This feature will simply change the set overcurrent pickup level in accordance with
magnitude variations of the measured voltage. It shall be noted that this feature will as well
affect the pickup current value for calculation of trip times for IDMT curves (overcurrent
with IDMT curve will trip faster during low voltage conditions).
708

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Current restraint feature


The overcurrent protection step operation can be made dependent of a restraining current
quantity (see table 367). Practically then the pickup level of the overcurrent step is not
constant but instead increases with the increase in the magnitude of the restraining current.

IMeasured

e
Op

te
ra

ea
ar

IsetHigh

eff
Co
r
t
es
I>R

tr
es
*Ir

ain

IsetLow

atan(RestrCoeff)
Restraint
en05000255.vsd
IEC05000255 V1 EN

Figure 325:

Current pickup variation with restraint current magnitude

This feature will simply prevent overcurrent step to pickup if the magnitude of the
measured current quantity is smaller than the set percentage of the restrain current
magnitude. However this feature will not affect the pickup current value for calculation of
trip times for IDMT curves. This means that the IDMT curve trip time will not be
influenced by the restrain current magnitude.
When set, the pickup signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the pickup signal has value one for longer time
than the set time delay, the overcurrent step will set its trip signal to one. Reset of the
pickup and trip signal can be instantaneous or time delay in accordance with the end user
setting.

11.1.7.4

Built-in undercurrent protection steps


Two undercurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here. Undercurrent step simply compares the
magnitude of the measured current quantity (see table 365) with the set pickup level. The
undercurrent step will pickup and set its pickup signal to one if the magnitude of the
measured current quantity is smaller than this set level. The pickup signal will start
definite time delay with set time delay. If the pickup signal has value one for longer time

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

709

Section 11
Multipurpose protection

1MRK 502 066-UUS A

than the set time delay the undercurrent step will set its trip signal to one. Reset of the
pickup and trip signal can be instantaneous or time delay in accordance with the setting.

11.1.7.5

Built-in overvoltage protection steps


Two overvoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overvoltage step simply compares the magnitude of the measured voltage quantity (see
table 366) with the set pickup level. The overvoltage step will pickup if the magnitude of
the measured voltage quantity is bigger than this set level.
The pickup signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the pickup signal has value one for longer time
than the set time delay, the overvoltage step will set its trip signal to one. Reset of the
pickup and trip signal can be instantaneous or time delay in accordance with the end user
setting.

11.1.7.6

Built-in undervoltage protection steps


Two undervoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Undervoltage step simply compares the magnitude of the measured voltage quantity (see
table 366) with the set pickup level. The undervoltage step will pickup if the magnitude of
the measured voltage quantity is smaller than this set level.
The pickup signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the pickup signal has value one for longer time
than the set time delay, the undervoltage step will set its trip signal to one. Reset of the
pickup and trip signal can be instantaneous or time delay in accordance with the end user
setting.

11.1.7.7

Inadvertent generator energizing


The inadvertent energizing function is realized by means of the general current and
voltage protection function (CAGVPC). CVGAPC is configured as shown in figure 326.

710

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

CVGAPC
3IP
3VP

TROC1

TROV1

TRUV1

BLKOC1

ANSI10000028-1-en.vsd
ANSI10000028 V1 EN

Figure 326:

Configuration of the inadvertent energizing function

The setting of the general current and voltage function (typical values) is done as shown
in table 369.
Table 369:

The setting of the general current and voltage function


Measured Quantity

Pickup in % of generator
rating

Time delay in seconds

UndervoltagePickup

Maximum generator
Phase to Phase voltage

< 70%

10.0 s

Overvoltage Pickup

Maximum generator
Phase to Phase voltage

> 85%

1.0 s

OvercurrentPickup

Maximum generator
Phase current

> 50%

0.05 s

In normal operation the overvoltage trip signal is activated and the undervotage trip signal
is deactivated. This means that the overcurrent function is blocked.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

711

Section 11
Multipurpose protection

1MRK 502 066-UUS A

When the generator is taken out of service the generator voltage gets low. The overvoltage
trip signal will be deactivated and the undervoltage trip signal will be activated after the
set delay. At this moment the block signal to the overcurrent function will be deactivated.
It the generator is energized at stand still conditions, that is, when the voltage is zero, the
overcurrent function will operate after the short set delay if the generator current is larger
than the set value.
When the generator is started the overvoltage trip signal will be activated the set time
delay after the moment when the voltage has reached the set value. At this moment the
blocking of the overcurrent function is activated.
The delay of the undervoltage function will prevent false operation at short circuits in the
external power grid.

11.1.7.8

Logic diagram
The simplified internal logics, for CVGAPC function are shown in the following figures.
IED

Phasors &
samples

Current and voltage selection


settings

Selected current

Selection of which current


and voltage shall be given to
the built-in protection
elements

Selected voltage

Restraint current selection

Selection of restraint current

Selected restraint current

Phasors &
samples

Phasor calculation of
individual currents

CVGAPC function

Phasor calculation of
individual voltages

A/D conversion scaling


with CT ratio

52

A/D conversion
scaling with CT ratio

ADM

ANSI05000169_2_en.vsd
ANSI05000169 V2 EN

Figure 327:

712

Treatment of measured currents and voltages within IED for CVGAPC function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Figure 327 shows how internal treatment of measured currents is done for multipurpose
protection function
The following currents and voltages are inputs to the multipurpose protection function.
They must all be expressed in true power system (primary) Amperes and kilovolts.
1.
2.
3.

Instantaneous values (samples) of currents & voltages from one three-phase current
and one three-phase voltage input.
Fundamental frequency phasors from one three-phase current and one three-phase
voltage input calculated by the pre-processing modules.
Sequence currents & voltages from one three-phase current and one three-phase
voltage input calculated by the pre-processing modules.

The multipurpose protection function:


1.
2.
3.

Selects one current from the three-phase input system (see table 365) for internally
measured current.
Selects one voltage from the three-phase input system (see table 366) for internally
measured voltage.
Selects one current from the three-phase input system (see table 367) for internally
measured restraint current.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

713

Section 11
Multipurpose protection

1MRK 502 066-UUS A

CURRENT

UC1
2
Selected current

TRUC1

nd

Harmonic
restraint

PU_UC2

UC2
nd
2 Harmonic
restraint

TRUC2

PU_OC1

OC1

Selected restraint current

2nd Harmonic
restraint

TROC1

OR

Current restraint

BLK2ND
DIROC1

Directionality
Voltage control /
restraint

PU_OC2
TROC2

OC2
2nd Harmonic
restraint
Current restraint
Directionality

OR

VDIRLOW
DIROC2

Voltage control /
restraint

PU_OV1

OV1

TROV1
PU_OV2

OV2
Selected voltage

TROV2
PU_UV1

UV1

TRUV1
PU_UV2

UV2

TRUV2

VOLTAGE

714

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
en05000170_ansi.vsd
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

ANSI05000170 V1 EN

Figure 328:

CVGAPC function main logic diagram for built-in protection elements

Logic in figure 328 can be summarized as follows:


1.

The selected currents and voltage are given to built-in protection elements. Each
protection element and step makes independent decision about status of its PICKUP
and TRIP output signals.
More detailed internal logic for every protection element is given in the following
four figures
Common PICKUP and TRIP signals from all built-in protection elements & steps
(internal OR logic) are available from multipurpose function as well.

2.
3.

Enable
second
harmonic

Second
harmonic check

DEF time
selected

a
b

AND

TROC1

OR

a>b

OC1=On
BLKOC1

BLKTROC1

0-DEF
0

Selected current

PickupCurr_OC1

NOT

PU_OC1

AND

Inverse
Voltage
control or
restraint
feature

Selected voltage

Selected restrain current

Directionality
check

DIR_OK

Inverse
time
selected

Current
Restraint
Feature
Imeasured > k Irestraint

en05000831_ansi.vsd
ANSI05000831 V1 EN

Figure 329:

Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the same
internal logic)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

715

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Bin input: BLKUC1TR

Selected current

b>a

AND

PickupCurr_UC1

TRUC1

AND

0-DEF
0

Operation_UC1=On

PU_UC1

Bin input: BLKUC1

en05000750_ansi.vsd
ANSI05000750 V1 EN

Figure 330:

Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has the same
internal logic)

DEF time
selected

0
Selected voltage

a
b

PickupVolt_OV1

BLKTROV1

0-DEF

AND

TROV1

OR

a>b

PU_OV1

AND
Inverse

Operation_OV1=On
BLKOV1

Inverse time
selected

en05000751_ansi.vsd
ANSI05000751 V1 EN

Figure 331:

716

Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same internal
logic)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

DEF time
selected

0
Selected voltage

BLKTRUV1

0-DEF

AND

TRUV1

OR

b>a

PU_UV1

AND

PickupVolt_UV1

Inverse
Operation_UV1=On
Inverse time
selected

BLKUV1

en05000752_ansi.vsd
ANSI05000752 V1 EN

Figure 332:

11.1.8

Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the same internal
logic)

Technical data
Table 370:

CVGAPC technical data

Function

Range or value

Accuracy

Measuring current input

Phase A, Phase B, Phase C, PosSeq, NegSeq, -3*ZeroSeq, MaxPh, MinPh,


UnbalancePh, Phase A-Phase B, Phase
B-Phase C, Phase C-Phase A, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph

Measuring voltage input

Phase A, Phase B, Phase C, PosSeq, NegSeq, -3*ZeroSeq, MaxPh, MinPh,


UnbalancePh, Phase A-Phase B, Phase
B-Phase C, Phase C-Phase A, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph

Pickup overcurrent, step 1


-2

(2 - 5000)% of IBase

1.0% of In at I In
1.0% of I at I > In

Pickup undercurrent, step


1-2

(2 - 150)% of IBase

1.0% of In at I In
1.0% of I at I > In

Independent time delay,


overcurrent at 0 to 2 x Iset,
step 1 - 2

(0.00 - 6000.00) s

0.2% or 35 ms whichever is
greater

Independent time delay,


undercurrent at 2 to 0 x
Iset, step 1 - 2

(0.00 - 6000.00) s

0.2% or 35 ms whichever is
greater

Overcurrent (nondirectional):
Table continues on next page
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

717

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Pickup time at 0 to 2 x Iset

Min. = 15 ms
Max. = 30 ms

Reset time at 2 to 0 x Iset

Min. = 15 ms
Max. = 30 ms

Pickup time at 0 to 10 x Iset

Min. = 5 ms
Max. = 20 ms

Reset time at 10 to 0 x Iset

Min. = 20 ms
Max. = 35 ms

Pickup time at 2 to 0 x Iset

Min. = 15 ms
Max. = 30 ms

Reset time at 0 to 2 x Iset

Min. = 15 ms
Max. = 30 ms

16 curve types

See table 977, 978 and table 979

Minimum operate time for


inverse curves, step 1 - 2

(0.00 - 6000.00) s

0.2% or 35 ms whichever is
greater

Voltage level where


voltage memory takes
over

(0.0 - 5.0)% of VBase

0.5% of Vn

Pickup overvoltage, step 1


-2

(2.0 - 200.0)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Pickup undervoltage, step


1-2

(2.0 - 150.0)% of VBase

0.5% of Vn at V Vn
0.5% of V at V > Vn

Independent time delay,


overvoltage at 0.8 to 1.2 x
Vset, step 1 - 2

(0.00 - 6000.00) s

0.2% or 35 ms whichever is
greater

Independent time delay,


undervoltage at 1.2 to 0.8
x Vset, step 1 - 2

(0.00 - 6000.00) s

0.2% or 35 ms whichever is
greater

Pickup time at 0.8 to 1.2 x


Vset

Min. = 15 ms
Max. = 30 ms

Reset time at 1.2 to 0.8 x


Vset

Min. = 15 ms
Max. = 30 ms

Pickup time at 1.2 to 0.8 x


Vset

Min. = 15 ms
Max. = 30 ms

Reset time at 1.2 to 0.8 x


Vset

Min. = 15 ms
Max. = 30 ms

Undercurrent:

Overcurrent:
Inverse time
characteristics, see table
977, 978 and table 979
Overcurrent:

Overvoltage:

Undervoltage:

Overvoltage:
Table continues on next page
718

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 11
Multipurpose protection

1MRK 502 066-UUS A

Function

Range or value

Accuracy

4 curve types

See table 988

Inverse time
characteristics, see table
989

3 curve types

See table 989

High and low voltage limit,


voltage dependent
operation, step 1 - 2

(1.0 - 200.0)% of VBase

1.0% of Vn at V Vn
1.0% of V at V > Vn

Directional function

Settable: NonDir, forward and reverse

Relay characteristic angle

(-180 to +180) degrees

2.0 degrees

Relay trip angle

(1 to 90) degrees

2.0 degrees

Reset ratio, overcurrent

> 95%

Reset ratio, undercurrent

< 105%

Reset ratio, overvoltage

> 95%

Reset ratio, undervoltage

< 105%

Critical impulse time

10 ms typically at 0 to 2 x Iset

Impulse margin time

15 ms typically

Critical impulse time

10 ms typically at 2 to 0 x Iset

Impulse margin time

15 ms typically

Critical impulse time

10 ms typically at 0.8 to 1.2 x Vset

Impulse margin time

15 ms typically

Critical impulse time

10 ms typically at 1.2 to 0.8 x Vset

Impulse margin time

15 ms typically

Inverse time
characteristics, see table
988
Undervoltage:

Overcurrent:

Undercurrent:

Overvoltage:

Undervoltage:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

719

720

Section 12
System protection and control

1MRK 502 066-UUS A

Section 12

System protection and control

12.1

Multipurpose filter SMAIHPAC

12.1.1

Identification

12.1.2

Function description

IEC 61850
identification

Multipurpose filter

SMAIHPAC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The multi-purpose filter function block, SMAIHPAC, is arranged as a three-phase filter.
It has very much the same user interface (e.g. inputs and outputs) as the standard preprocessing function block SMAI. However the main difference is that it can be used to
extract any frequency component from the input signal. Thus it can, for example, be used
to build sub-synchronous resonance protection for synchronous generator.

12.1.3

Function block
SMAIHPAC
BLOCK
G3P*

AI3P
AI1
AI2
AI3
AI4
IEC13000180-1-en.vsd

IEC13000180 V1 EN

12.1.4

Signals
Table 371:
Name

SMAIHPAC Input signals


Type

Default

Description

G3P

GROUP
SIGNAL

Analog input group from SMAI

BLOCK

BOOLEAN

Block of function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

721

Section 12
System protection and control

1MRK 502 066-UUS A

Table 372:

SMAIHPAC Output signals

Name

12.1.5
Table 373:
Name

Type

Description

AI3P

GROUP SIGNAL

Analog input 3-phase group

AI1

GROUP SIGNAL

Analog input 1

AI2

GROUP SIGNAL

Analog input 2

AI3

GROUP SIGNAL

Analog input 3

AI4

GROUP SIGNAL

Analog input 4

Settings
SMAIHPAC Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

ConnectionType

Ph - Ph
Ph - N

Ph - N

Analogue input connection type

SetFrequency

2.0 - 500.0

Hz

0.1

50.0

Desired frequency to be extracted by the filter

FreqBandWidth

0.0 - 60.0

Hz

0.1

0.0

Extra added frequency band around the set


frequency

FilterLength

0.1 s
0.2 s
0.5 s
1.0 s
2.0 s
4.0 s

1.0 s

Approximate length of the filtering window in


seconds

OverLap

0 - 95

20

Filtering window overlap between two


calculations in percent

12.1.6

Operation principle
For all four analogue input signals into this filter (i.e. three phases and the residual
quantity) the input samples from the TRM module which are coming at rate of 20 samples
per fundamental system cycle are first stored. When enough samples are available in the
internal memory, the phasor values at set frequency defined by the setting parameter
SetFrequency are calculated. The following values are internally available for each of the
calculated phasors:

Magnitude
Phase angle
Exact frequency of the extracted signal

Note that the special filtering algorithm is used to extract these phasors. This algorithm is
different from the standard one-cycle Digital Fourier Filter typically used by the

722

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 12
System protection and control

1MRK 502 066-UUS A

numerical IEDs. This filter provides extremely good accuracy of measurement and
excellent noise rejection, but at the same time it has much slower response time. It is
capable to extract phasor (i.e. magnitude, phase angle and actual frequency) of any signal
(e.g. 37,2Hz) present in the waveforms of the connected CTs and/or VTs. The magnitude
and the phase angle of this phasor are calculated with very high precision. For example the
magnitude and phase angle of the phasor can be estimated even if it has magnitude of one
per mille (i.e. 1 ) in comparison to the dominating signal (e.g. the fundamental
frequency component). Several instances of this function block are provided. These
instances are fully synchronized between each-other in respect of phase angle calculation.
Thus if two multi-purpose filters are used for some application, one for current and the
second one for the voltage signals, the power values (i.e. P & Q) at the set frequency can
be calculated from them by the over-/under-power function or CVMMXN measurement
function block.
In addition to these phasors the following quantities are internally calculated as well:

Phasors for the individual phases as well as phase-to-phase phasors


True RMS value of the input signal over all samples available in the memory
Positive sequence phasor
Negative sequence phasor
Zero sequence phasor
etc.

In order to properly calculate phase-to-phase phasors from the individual phase phasors or
vice versa, the setting parameters ConnectionType is provided. It defines what quantities
(i.e. individual phases or phase-to-phase quantities) are physically connected to the IED
analogue inputs by wiring. Then the IED knows which one of them are the measured
quantities and the other one is then internally calculated. This setting is only important for
the VT inputs, because the CTs are typically wye connected all the time.
Thus when this filter is used in conjunction with multi-purpose protection function or
overcurrent function or over-voltage function or over-power function many different
protection applications can be arranged. For example the following protection,
monitoring or measurement features can be realized:

Sub-synchronous resonance protection for turbo generators


Sub-synchronous protection for wind turbines/wind farms
Detection of sub-synchronous oscillation between HVDC links and synchronous
generators
Super-synchronous protection
Detection of presence of the geo-magnetic induced currents
Overcurrent or overvoltage protection at specific frequency harmonic, sub-harmonic,
inter-harmonic etc.
Presence of special railway frequencies (e.g. 16.7Hz or 25Hz) in the three-phase
power system

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

723

Section 12
System protection and control

1MRK 502 066-UUS A

Sensitive reverse power protection


Stator or rotor ground fault protection for special injection frequencies (e.g. 25Hz)
etc.

The filter output can also be connected to the measurement function blocks such as
CVMMXN (Measurements), CMMXU (Phase current measurement), VMMXU (Phasephase voltage measurement), etc.
The filter has as well additional capability to report the exact frequency of the extracted
signal. Thus the user can check the actual frequency of some phenomenon in the power
system (e.g. frequency of the sub-synchronous currents) and compare it with expected
value obtained previously by either calculation or simulation. For the whole three-phase
filter group the frequency of the signal connected to the first input (i.e. phase A) is
reported. This value can be then used either by over-/under-frequency protections or
reported to the built-in HMI or any other external client via the measurement blocks such
is the CVMMXN.
How many samples in the memory are used for the phasor calculation depends on the
setting parameter FilterLength. Table 374 gives overview of the used number of samples
for phasor calculation by the filter. Note that the used number of samples is always a power
of number two.
Table 374:

Length of the filtering window

Value for parameter


FilterLength

Used No of samples for


calculation (fixed,
independent from rated
frequency)

Corresponding length of
the input waveform in
miliseconds for 50Hz
power system

Corresponding length of
the input waveform in
miliseconds for 60Hz
power system

0.1 s

128 = 27

128 ms

107 ms

0.2 s

256 = 28

256 ms

213 ms

0.5 s

512 = 29

512 ms

427 ms

1.0 s

1024 =

210

1024 ms

853 ms

2.0 s

2048 = 211

2048 ms

1707 ms

4.0 s

4096 = 212

4096 ms

3413 ms

Note that the selected value for the parameter FilterLength automatically defines certain
filter properties as described below:
First in order to secure proper filter operation the selected length of the filter shall always
be longer than three complete periods of the signal which shall be extracted. Actually the
best results are obtained if at least five complete periods are available within the filtering
window. Thus, this filter feature will limit which filter lengths can be used to extract low
frequency signals. For example if 16,7 Hz signal shall be extracted the minimum filter
length in milliseconds shall be:
724

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 12
System protection and control

1MRK 502 066-UUS A

1000
16.7

= 180ms
(Equation 178)

EQUATION000028 V1 EN

Thus based on the data from Table 374 the minimum acceptable value for this parameter
would be FilterLength = 0.2 s but more accurate results will be obtained by using
FilterLength = 0.5 s
Second feature which is determined by the selected value for parameter FilterLength is the
capability of the filter to separate the desired signal from the other disturbing signals
which may have similar frequency value. Note that the filter output will be the phasor with
the highest magnitude within certain pass frequency band around the SetFrequency.
Table 375 defines the natural size of this pass frequency band for the filter, depending on
the selected value for parameter FilterLength.
Table 375:

Pass frequency band due to FilterLength

Value for parameter FilterLength

For 50Hz power system

For 60Hz power system

0.1 s

22.5 Hz

27.0 Hz

0.2 s

11.5 Hz

14.0 Hz

0.5 s

6.0 Hz

7.2 Hz

1.0 s

3.0 Hz

3.6 Hz

2.0 s

1.5 Hz

1.8 Hz

4.0 s

0.8 Hz

1.0 Hz

Thus the longer length of the filter the better capability it has to reject the disturbing
signals close to the required frequency component and any other noise present in the input
signal waveform. For example if 46 Hz signal wants to be extracted in 50Hz power
system, then from Table 375 it can be concluded that FilterLength=1,0 s shall be
selected as a minimum value. However if frequency deviation of the fundamental
frequency signal in the power system are taken into account it may be advisable to select
FilterLength=2,0 s for such application.
Note that in case when no clear magnitude peak exist in the set pass frequency band the
filter will return zero values for the phasor magnitude and angle while the signal frequency
will have value minus one. Finally the set value for parameter FilterLength also defines
the response time of the filter after a step change of the measured signal. The filter will
correctly estimate the new signal magnitude once 75% of the filter length has been filed
with the new signal value (i.e. after the change).
If for any reason this natural frequency band shall be extended (e.g. to get accurate but
wider filter) it is possible to increase the pass band by entering the value different from
zero for parameter FreqBandWidth. In such case the total filter pass band can be defined
as:
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

725

Section 12
System protection and control

1MRK 502 066-UUS A

(value given in Table 375 + one-half of the set FreqBandWidth value)


Example if in 60Hz system the selected values are FilterLength =1.0 s and
FreqBandWidth = 5.0 the total filter pass band will be (3.6+5.0/2)= 6.1 Hz.
It shall be noted that the phasor calculation is relatively computation demanding (required
certain amount of the CPU processing time). In order to control the CPU usage for this
filter, the setting parameter OverLap is used. This setting parameter defines how often the
new phasor value is calculated during time period defined by the set value for the
parameter FilterLength (see Table 374). The following list gives some examples how this
parameter influence the calculation rate for the extracted phasor:

12.1.7

when OverLap=0% the new phasor value is calculated only once per FilterLength
when OverLap=50% the new phasor value is calculated two times per FilterLength
when OverLap=75% the new phasor value is calculated four times per FilterLength
when OverLap=90% the new phasor value is calculated ten times per FilterLength

Filter calculation example


In the following Figure an example from an installation of this filter on a large, 50 Hz turbo
generator with a rating in excess of 1000 MVA is presented. In this installation filter is
used to measure the stator sub-synchronous resonance currents. For this particular
installation the following settings were used for the filter:

726

SetFrequency= 31.0 Hz
FilterLength= 1.0 s
OverLap = 75%
FreqBandWidth= 0.0 Hz

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 12
System protection and control

1MRK 502 066-UUS A

IEC13000178-2-en.vsd
IEC13000178 V3 EN

Figure 333:

Example of filter calculation

The data shown in the Figure comes from the comtrade file captured by the IED. The
following traces are presented in this Figure.
a) Waveforms of the stator three-phase currents given in primary kA.
b) RMS value of the sub-synchronous resonance current extracted by the filter in primary
amperes.
c) Frequency of the extracted sub-synchronous resonance current provided by the filter in
Hz.
Note the very narrow scale on the y-axle for b) and c). Such small scale as well indicates
with which precision and consistency the filter calculates the phasor magnitude and
frequency of the extracted stator sub-synchronous current component.
The following can be observed in the Figure:

The stator total RMS current value is around 33 kA primary.


The measured magnitude of the sub-synchronous current is around 173 A primary
(that is, 0.5% of the fundamental 50 Hz component).
The frequency of this sub-synchronous current component is 31.24 Hz.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

727

Section 12
System protection and control

1MRK 502 066-UUS A

With above given settings the sub-synchronous current magnitude and frequency are
calculated approximately four times per second (that is, correct value is four times per
1024 ms).

728

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

Section 13

Secondary system supervision

13.1

Current circuit supervision (87)

13.1.1

Identification
Function description

IEC 61850
identification

Current circuit supervision

13.1.2

CCSSPVC

IEC 60617
identification

ANSI/IEEE C37.2
device number

87

Functionality
Open or short circuited current transformer cores can cause unwanted operation of many
protection functions such as differential, ground-fault current and negative-sequence
current functions.
Current circuit supervision (CCSSPVC, 87) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate input
taken from another set of cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to block
protection functions expected to give inadvertent tripping.

13.1.3

Function block
CCSSPVC (87)
I3P*
IREF*
BLOCK

FAIL
ALARM

ANSI13000304-1-en.vsd
ANSI13000304 V1 EN

Figure 334:

CCSSPVC (87) function block

Signal IREF must be connected in the configuration.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

729

Section 13
Secondary system supervision
13.1.4

1MRK 502 066-UUS A

Signals
Table 376:

CCSSPVC (87) Input signals

Name

Type

Group signal for three phase current input

IREF

GROUP
SIGNAL

Residual reference current input

BLOCK

BOOLEAN

Block of function

CCSSPVC (87) Output signals

Name

Table 378:
Name

Description

GROUP
SIGNAL

Table 377:

13.1.5

Default

I3P

Type

Description

FAIL

BOOLEAN

Detection of current circuit failure

ALARM

BOOLEAN

Alarm for current circuit failure

Settings
CCSSPVC (87) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

IMinOp

10 - 200

%IB

20

Minimum operate current differential pickup in


% of IBase

Table 379:
Name
Pickup_Block

Table 380:
Name
GlobalBaseSel

730

CCSSPVC (87) Group settings (advanced)


Values (Range)
20 - 500

Unit
%IB

Step
1

Default
150

Description
Block of the function at high phase current, in %
of IBase

CCSSPVC (87) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Description
Selection of one of the Global Base Value
groups

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

13.1.6

Operation principle
Current circuit supervision CCSSPVC (87) compares the absolute value of the vectorial
sum of the three phase currents |Iphase| and the numerical value of the residual current
|Iref| from another current transformer set, see figure 335.
The FAIL output will be set to a logical one when the following criteria are fulfilled:

The numerical value of the difference |Iphase| |Iref| is higher than 80% of the
numerical value of the sum |Iphase| + |Iref|.
The numerical value of the current |Iphase| |Iref| is equal to or higher than the set
trip value IMinOp.
No phase current has exceeded Pickup_Block during the last 10 ms.
CCSSPVC (87) is enabled by setting Operation = Enabled.

The FAIL output remains activated 100 ms after the AND-gate resets when being
activated for more than 20 ms. If the FAIL lasts for more than 150 ms an ALARM will be
issued. In this case the FAIL and ALARM will remain activated 1 s after the AND-gate
resets. This prevents unwanted resetting of the blocking function when phase current
supervision element(s) trip, for example, during a fault.
I>Pickup_Block
BLOCK
IA
IB
IC
I ref

IA
IB
IC
I ref

+
+
+

I>IMinOp
+
-

x
0,8

1,5 x Ir
OR

10 ms

OR

AND

FAIL

20 ms 100 ms
150 ms

OPERATION

1s

ALARM

BLOCK
en05000463_ansi.vsd
ANSI05000463 V1 EN

Figure 335:

Simplified logic diagram for Current circuit supervision CCSSPVC (87)

The trip characteristic is percentage restrained, see figure 336.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

731

Section 13
Secondary system supervision

1MRK 502 066-UUS A

| I phase | - | I ref |

Slope = 1

Operation
area

Slope = 0.8
I MinOp

| I phase | + | I ref |
99000068.vsd
IEC99000068 V1 EN

Figure 336:

Trip characteristics

Due to the formulas for the axis compared, |SIphase | - |I ref | and |S I phase
| + | I ref | respectively, the slope can not be above 2.

13.1.7

Technical data
Table 381:

CCSSPVC(87) technical data

Function

13.2

732

Range or value

Trip current

(10-200)% of IBase

Reset ratio, Trip current

>90%

Block current

(20-500)% of IBase

Reset ratio, Block current

>90% at (50-500)% of IBase

Accuracy
10.0% of In at I In
10.0% of I at I > In

5.0% of In at I In
5.0% of I at I > In

Fuse failure supervision FUFSPVC

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

13.2.1

Identification
Function description

IEC 61850
identification

Fuse failure supervision

13.2.2

FUFSPVC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The aim of the fuse failure supervision function FUFSPVC is to block voltage measuring
functions at failures in the secondary circuits between the voltage transformer and the IED
in order to avoid inadvertent operations that otherwise might occur.
The fuse failure supervision function basically has three different detection methods,
negative sequence and zero sequence based detection and an additional delta voltage and
delta current detection.
The negative sequence detection algorithm is recommended for IEDs used in isolated or
high-impedance grounded networks. It is based on the negative-sequence quantities.
The zero sequence detection is recommended for IEDs used in directly or low impedance
grounded networks. It is based on the zero sequence measuring quantities.
The selection of different operation modes is possible by a setting parameter in order to
take into account the particular grounding of the network.
A criterion based on delta current and delta voltage measurements can be added to the fuse
failure supervision function in order to detect a three phase fuse failure, which in practice
is more associated with voltage transformer switching during station operations.

13.2.3

Function block
FUFSPVC
I3P*
V3P*
BLOCK
52A
MCBOP
89B
BLKTRIP

BLKZ
BLKV
3PH
DLD1PH
DLD3PH
PU_DI
PU_DI_A
PU_DI_B
PU_DI_C
PU_DV
PU_DV_A
PU_DV_B
PU_DV_C
ANSI14000065-1-en.vsd

ANSI14000065 V1 EN

Figure 337:

FUFSPVC function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

733

Section 13
Secondary system supervision
13.2.4

Signals
Table 382:
Name

FUFSPVC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Current connection

V3P

GROUP
SIGNAL

Voltage connection

BLOCK

BOOLEAN

Block of function

52a

BOOLEAN

Active when circuit breaker is closed

MCBOP

BOOLEAN

Active when external Miniature Circuit Breaker opens


protected voltage circuit

89b

BOOLEAN

Active when line disconnect switch is open

BLKTRIP

BOOLEAN

Blocks operation of function when active

Table 383:
Name

734

1MRK 502 066-UUS A

FUFSPVC Output signals


Type

Description

BLKZ

BOOLEAN

Start of current and voltage controlled function

BLKV

BOOLEAN

General pickup

3PH

BOOLEAN

Three-phase pickup

DLD1PH

BOOLEAN

Dead line condition in at least one phase

DLD3PH

BOOLEAN

Dead line condition in all three phases

PU_DI

BOOLEAN

Common pickup signal of sudden change in current

PU_DI_A

BOOLEAN

Pickupof sudden change in current, phase A

PU_DI_B

BOOLEAN

Start signal of sudden change in current, phase B

PU_DI_C

BOOLEAN

Start signal of sudden change in current, phase C

PU_DV

BOOLEAN

Common start signal of sudden change in voltage

PU_DV_A

BOOLEAN

Start signal of sudden change in voltage, phase A

PU_DV_B

BOOLEAN

Start signal of sudden change in voltage, phase B

PU_DV_C

BOOLEAN

Start signal of sudden change in voltage, phase C

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

13.2.5
Table 384:
Name

Settings
FUFSPVC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OpModeSel

Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs

V0I0

Operating mode selection

3V0PU

1 - 100

%VB

30

Pickup of residual overvoltage element in % of


VBase

3I0PU

1 - 100

%IB

10

Pickup of residual undercurrent element in % of


IBase

3V2PU

1 - 100

%VB

30

Pickup of negative sequence overvoltage


element in % of VBase

3I2PU

1 - 100

%IB

10

Pickup of negative sequence undercurrent


element in % of IBase

OpDVDI

Disabled
Enabled

Disabled

Operation of change based function Disable/


Enable

DVPU

1 - 100

%VB

60

Pickup of change in phase voltage in % of


VBase

DIPU

1 - 100

%IB

15

Pickup of change in phase current in % of


IBase

VPPU

1 - 100

%VB

70

Pickup of phase voltage in % of VBase

IPPU

1 - 100

%IB

10

Pickup of phase current in % of IBase

SealIn

Disabled
Enabled

Enabled

Seal in functionality Disable/Enable

VSealInPU

1 - 100

%VB

70

Pickup of seal-in phase voltage in % of VBase

IDLDPU

1 - 100

%IB

Pickup for phase current detection in % of


IBase for dead line detection

VDLDPU

1 - 100

%VB

60

Pickup for phase voltage detection in % of


VBase for dead line detection

Table 385:
Name
GlobalBaseSel

FUFSPVC Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Step
1

Default
1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description
Selection of one of the Global Base Value
groups

735

Section 13
Secondary system supervision
13.2.6

1MRK 502 066-UUS A

Monitored data
Table 386:
Name

FUFSPVC Monitored data


Type

Values (Range)

Unit

Description

3I0

REAL

Magnitude of zero sequence


current

3I2

REAL

Magnitude of negative
sequence current

3V0

REAL

kV

Magnitude of zero sequence


voltage

3V2

REAL

kV

Magnitude of negative
sequence voltage

13.2.7

Operation principle

13.2.7.1

Zero and negative sequence detection


The zero and negative sequence function continuously measures the currents and voltages
in all three phases and calculates, see figure 338:

the zero-sequence voltage 3V0


the zero-sequence current 3I0
the negative sequence current 3I2
the negative sequence voltage 3V2

The measured signals are compared with their respective set values 3V0PU and 3I0PU,
3V2PU and 3I2PU.
The function enable the internal signal FuseFailDetZeroSeq if the measured zerosequence voltage is higher than the set value 3V0PU and the measured zero-sequence
current is below the set value 3I0PU.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value 3V2PU and the measured negative sequence
current is below the set value 3I2PU.
A drop out delay of 100 ms for the measured zero-sequence and negative sequence current
will prevent a false fuse failure detection at un-equal breaker opening at the two line ends.

736

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

Sequence Detection
3I0PU
IA

CurrZeroSeq
Zero
sequence
filter

IB

3I0
a
b

a>b

Negative
sequence
filter

IC

3I2
AND

a
b

3I2PU

CurrNegSeq

100 ms
0

a>b

100 ms
0
AND

3V0PU

FuseFailDetZeroSeq

FuseFailDetNegSeq
VoltZeroSeq

VA

Zero
sequence
filter

VB

Negative
sequence
filter

VC

a
b

3V0

a>b
VoltNegSeq

a
b

3V2

a>b

3V2PU

ANSI10000036-2-en.vsd
ANSI10000036 V2 EN

Figure 338:

Simplified logic diagram for sequence detection part

The calculated values 3V0, 3I0, 3I2 and 3V2 are available as service values on local HMI
and monitoring tool in PCM600.

Input and output signals


The output signals 3PH, BLKV and BLKZ as well as the signals DLD1PH and DLD3PH
from dead line detections are blocked if any of the following conditions occur:

The input BLOCK is activated


The input BLKTRIP is activated and the internal signal FuseFailStarted is not present
The operation mode selector OpModeSel is set to Disable
The IED is in TEST status (TEST-ACTIVE is high) and the function has been
blocked from the HMI (BlockFUSE=Yes)

The input BLOCK signal is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to receive
a block command from external devices or can be software connected to other internal
functions of the IED itself in order to receive a block command from internal functions.
Through OR gate it can be connected to both binary inputs and internal function outputs.
The input BLKTRIP is intended to be connected to the trip output from any of the
protection functions included in the IED. When activated for more than 20 ms, the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

737

Section 13
Secondary system supervision

1MRK 502 066-UUS A

operation of the fuse failure is blocked; a fixed drop-out timer prolongs the block for 100
ms. The aim is to increase the security against unwanted operations during the opening of
the breaker, which might cause unbalance conditions for which the fuse failure might
operate.
The output signal BLKZ will also be blocked if the internal dead line detection is
activated. The dead line detection signal has a 200 ms drop-out time delay.
The input signal MCBOP is supposed to be connected via a terminal binary input to the
N.C. auxiliary contact of the miniature circuit breaker protecting the VT secondary circuit.
The MCBOP signal sets the output signals BLKV and BLKZ in order to block all the
voltage related functions when the MCB is open independent of the setting of OpModeSel
selector. The additional drop-out timer of 150 ms prolongs the presence of MCBOP signal
to prevent the unwanted operation of voltage dependent function due to non simultaneous
closing of the main contacts of the miniature circuit breaker.
The input signal 89b is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The 89b signal sets the output signal BLKV in
order to block the voltage related functions when the line disconnector is open. The
impedance protection function is not affected by the position of the line disconnector since
there will be no line currents that can cause malfunction of the distance protection. If
89b=0 it signifies that the line is connected to the system and when the 89b=1 it signifies
that the line is disconnected from the system and the block signal BLKV is generated.
The output BLKV can be used for blocking the voltage related measuring functions
(undervoltage protection, energizing check and so on) except for the impedance
protection.
The function output BLKZ shall be used for blocking the impedance protection function.

13.2.7.2

Delta current and delta voltage detection


A simplified diagram for the functionality is found in figure 339. The calculation of the
changes of currents and voltages is based on a sample analysis algorithm. The calculated
delta quantities are compared with their respective set values DIPU and DVPU. The
algorithm detects a fuse failure if a sufficient change in voltage without a sufficient change
in current is detected in each phase separately. The following quantities are calculated in
all three phases:

The change in voltage DV


The change in current DI

The internal FuseFailDetDVDI signal is activated if the following conditions are fulfilled:

738

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

The magnitude of the phase-ground voltage has been above VPPU for more than 1.5
cycles (i.e. 30 ms in a 50 Hz system)
The magnitude of DV in three phases are higher than the corresponding setting
DVPU
The magnitudes of DI in three phases are below the setting DI<

In addition to the above conditions, at least one of the following conditions shall be
fulfilled in order to activate the internal FuseFailDetDVDI signal:

The magnitude of the phase currents in three phases are higher than the setting IPPU
The circuit breaker is closed (52A = True)

The first criterion means that detection of failure in three phases together with high current
for the three phases will set the output. The measured phase current is used to reduce the
risk of false fuse failure detection. If the current on the protected line is low, a voltage drop
in the system (not caused by fuse failure) may be followed by current change lower than
the setting DIPU, and therefore a false fuse failure might occur.
The second criterion requires that the delta condition shall be fulfilled at the same time as
circuit breaker is closed. If this is an important disadvantage, connect the 52A input to
FALSE , then only the first criterion can enable the delta function.If the DVDI detection
of three phases set the internal signal FuseFailDetDVDI at the level high, then the signal
FuseFailDetDVDI will remain high as long as the voltage of three phases are lower then
the setting VPPU.
In addition to fuse failure detection, two internal signals DeltaV and DeltaI are also
generated by the delta current and delta voltage DVDI detection algorithm. The internal
signals DelatV and DeltaI are activated when a sudden change of voltage, or respectively
current, is detected. The detection of the sudden change is based on a sample analysis
algorithm. In particular DelatV is activated if at least three consecutive voltage samples
are higher then the setting DVPU. In a similar way DelatI is activated if at least three
consecutive current samples are higher then the setting DIPU.When DeltaV or DeltaI are
active, the output signals PU_DV_A, PU_DV_B, PU_DV_C and respectively PU_DI_A,
PU_DI_B, PU_DI_C, based on a sudden change of voltage or current detection, are
activated with a 20 ms time off delay. The common pickup output signals PU_DV or
PU_DI are activated with a 60 ms time off delay, if any sudden change of voltage or
current is detected.
The delta function (except the sudden change of voltage and current
detection) is deactivated by setting the parameter OpDVDI to Disabled.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

739

Section 13
Secondary system supervision

1MRK 502 066-UUS A

DVDI Detection
DVDI detection Phase 1
IA
IB
IC

DI detection based on sample analysis


DeltaIA

DIPU
VA

DV detection based on sample analysis


AND

DVPU
a
b

VPPU

a>b

1.5 cycle
t

20 ms
t

DeltaIB

IA
IB
IC
VB

DVDI detection Phase 2

IA
IB
IC
VC

DVDI detection Phase 3

VA

50P

Same logic as for phase 1

a
b

a<b

a>b

AND

AND

a
b

IB

a
b

a
b

IC

a
b

OR

OR

AND

a<b

a>b

AND

AND
VC

DeltaIC
DeltaVC

52A
VB

DeltaVB

Same logic as for phase 1

IA

DeltaVA

OR

OR

AND

a<b

a>b

AND

AND

OR

OR

AND
AND

FuseFailDetDVDI

ANSI12000166-3-en.vsd
ANSI12000166 V3 EN

Figure 339:

740

Simplified logic diagram for the DV/DI detection part

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

intBlock
AND
DeltaIA
DeltaIB
DeltaIC

0
20 ms

OR

0
20 ms
0
20 ms

AND

PU_DI_A

AND

PU_DI_B

AND

AND
DeltaVA
DeltaVB
DeltaVC

0
20 ms

OR

0
20 ms

PU_DI

AND

AND

0
20 ms
AND

PU_DI_C

PU_DV

PU_DV_A

PU_DV_B

PU_DV_B

ANSI12000165-2-en.vsd
ANSI12000165 V2 EN

Figure 340:

13.2.7.3

Internal signals DeltaV or DeltaI and the corresponding output signals

Dead line detection


A simplified diagram for the functionality is found in figure 341. A dead phase condition
is indicated if both the voltage and the current in one phase is below their respective setting
values VDLDPU and IDLDPU. If at least one phase is considered to be dead the output
DLD1PH and the internal signal DeadLineDet1Ph is activated. If all three phases are
considered to be dead the output DLD3PH is activated

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

741

Section 13
Secondary system supervision

1MRK 502 066-UUS A

Dead Line Detection


IA

a
b

IB

a
b

IC

a
b

a<b

AllCurrLow

AND
a<b
a<b

IDLDPU
VA

DeadLineDet1Ph
a
b

VB

a
b

VC

a
b

a<b
a<b

AND
OR

DLD1PH

AND
AND

a<b

AND

AND

AND

DLD3PH

VDLDPU
intBlock

ANSI0000035-1-en.vsd
ANSI0000035 V1 EN

Figure 341:

13.2.7.4

Simplified logic diagram for Dead Line detection part

Main logic
A simplified diagram for the functionality is found in figure 342. The fuse failure
supervision function (FUFSPVC) can be switched on or off by the setting parameter
Operation to Enabled or Disabled.
For increased flexibility and adaptation to system requirements an operation mode
selector, OpModeSel, has been introduced to make it possible to select different operating
modes for the negative and zero sequence based algorithms. The different operation
modes are:

742

Disabled. The negative and zero sequence function is disabled.


V2I2. Negative sequence is selected.
V0I0. Zero sequence is selected.
V0I0 OR V2I2. Both negative and zero sequence are activated and work in parallel in
an OR-condition.
V0I0 AND V2I2. Both negative and zero sequence are activated and work in series
(AND-condition for operation).
OptimZsNs. Optimum of negative and zero sequence current (the function that has the
highest magnitude of measured negative and zero sequence current will be activated).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1MRK 502 066-UUS A

Section 13
Secondary system supervision

The delta function can be activated by setting the parameter OpDVDI to Enabled. When
selected it operates in parallel with the sequence based algorithms.
As soon as any fuse failure situation is detected, signals FuseFailDetZeroSeq,
FuseFailDetNegSeq or FuseFailDetDVDI, and the specific functionality is released, the
function will activate the output signal BLKV. The output signal BLKZ will be activated
as well if the internal dead phase detection, DeadLineDet1Ph, is not activated at the same
time. The output BLKV can be used for blocking voltage related measuring functions
(under voltage protection, energizing check, and so on). The output BLKZ shall be used
to block the impedance protection functions.
If the fuse failure situation is present for more than 5 seconds and the setting parameter
SealIn is set to Enabled it will be sealed in as long as at least one phase voltage is below
the set value VSealInPU. This will keep the BLKV and BLKZ signals activated as long as
any phase voltage is below the set value VSealInPU. If all three phase voltages drop below
the set value VSealInPU and the setting parameter SealIn is set to Enabled the output
signal 3PH will also be activated. The signals 3PH, BLKV and BLKZ signals will now be
active as long as any phase voltage is below the set value VSealInPU.
If SealIn is set to Enabled the fuse failure condition is stored in the non-volatile memory
in the IED. At start-up of the IED (due to auxiliary power interruption or re-start due to
configuration change) it uses the stored value in its non-volatile memory and reestablishes the conditions that were present before the shut down. All phase voltages must
be greater than VSealInPU before fuse failure is de-activated and resets the signals BLKU,
BLKZ and 3PH.
The output signal BLKV will also be active if all phase voltages have been above the
setting VSealInPU for more than 60 seconds, the zero or negative sequence voltage has
been above the set value 3V0PU and 3V2PU for more than 5 seconds, all phase currents
are below the setting IDLDPU (criteria for open phase detection) and the circuit breaker
is closed (input 52a is activated).
If a MCB is used then the input signal MCBOP is to be connected via a binary input to the
N.C. auxiliary contact of the miniature circuit breaker protecting the VT secondary circuit.
The MCBOP signal sets the output signals BLKV and BLKZ in order to block all the
voltage related functions when the MCB is open independent of the setting of OpModeSel
or OpDVDI. An additional drop-out timer of 150 ms prolongs the presence of MCBOP
signal to prevent the unwanted operation of voltage dependent function due to non
simultaneous closing of the main contacts of the miniature circuit breaker.
The input signal 89b is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The 89b signal sets the output signal BLKV in
order to block the voltage related functions when the line disconnector is open. The
impedance protection function does not have to be affected since there will be no line
currents that can cause malfunction of the distance protection.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

743

Section 13
Secondary system supervision

1MRK 502 066-UUS A

Fuse failure detection


Main logic
TEST
TEST ACTIVE

AND

BlocFuse = Yes
BLOCK

intBlock

OR

BLKTRIP

20 ms
t

AND

100 ms
t
FusefailStarted

All VL < VSealInPU


OR

AND

AND

AND

SealIn = Enabled

3PH

AND

Any VL < VSealInPU


FuseFailDetDUDI

AND

OpDVDI = Enabled

OR

FuseFailDetZeroSeq

5s
t

AND

AND
FuseFailDetNegSeq
AND
V2I2

OR

V0I0

OR

V0I0 OR V2I2

OpModeSel

V0I0 AND V2I2


OptimZsNs

CurrZeroSeq

CurrNegSeq

AND

a>b

OR

AND
200 ms
t

DeadLineDet1Ph

AND
150 ms
t

MCBOP

All VL > VSealInPU

60 s
t

VoltZeroSeq
VoltNegSeq

OR

OR

OR

OR

AND

AND

BLKZ

BLKV

AND
5s
t

AllCurrLow
52a
89b
ANSI10000033-3-en.vsd
ANSI10000033 V3 EN

744

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

Figure 342:

13.2.8

Simplified logic diagram for fuse failure supervision function, Main logic

Technical data
Table 387:

FUFSPVCtechnical data

Function

Range or value

Accuracy

Trip voltage, zero sequence

(1-100)% of VBase

0.5% of Vn

Trip current, zero sequence

(1100)% of IBase

0.5% of In

Trip voltage, negative sequence

(1-100)% of VBase

0.5% of Vn

Trip current, negative sequence

(1100)% of IBase

0.5% of In

Trip voltage change pickup

(1-100)% of VBase

10.0% of Vn

Trip current change pickup

(1100)% of IBase

10.0% of In

Trip phase voltage

(1-100)% of VBase

0.5% of Vn

Trip phase current

(1100)% of IBase

0.5% of In

Trip phase dead line voltage

(1-100)% of VBase

0.5% of Vn

Trip phase dead line current

(1100)% of IBase

0.5% of In

Pickup time, 1 ph, pickup at 1 to 0 x Vn

Min. = 10 ms
Max. = 25 ms

Reset time, 1 ph, pickup at 0 to 1 x Vn

Min. = 15 ms
Max. = 30 ms

13.3

Fuse failure supervision VDSPVC (60)

13.3.1

Identification
Function description
Fuse failure supervision

13.3.2

IEC 61850
identification
VDSPVC

IEC 60617
identification
VTS

ANSI/IEEE C37.2
device number
60

Functionality
Different protection functions within the protection IED operates on the basis of measured
voltage at the relay point. Some example of protection functions are:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

745

Section 13
Secondary system supervision

1MRK 502 066-UUS A

Distance protection function.


Undervoltage function.
Energisation function and voltage check for the weak infeed logic.

These functions can operate unintentionally, if a fault occurs in the secondary circuits
between voltage instrument transformers and the IED. These unintentional operations can
be prevented by VDSPVC.
VDSPVC is designed to detect fuse failures or faults in voltage measurement circuit,
based on phase wise comparison of voltages of main and pilot fused circuits. VDSPVC
blocking output can be configured to block functions that need to be blocked in case of
faults in the voltage circuit.

13.3.3

Function block
VDSPVC (60)
V3P1*
V3P2*
BLOCK

MAINFUF
PILOTFUF
V1AFAIL
V1BFAIL
V1CFAIL
V2AFAIL
V2BFAIL
V2CFAIL
ANSI14000057-1-en.vsd

ANSI12000142 V2 EN

Figure 343:

13.3.4

VDSPVC function block

Signals
Table 388:
Name

VDSPVC (60) Input signals


Type

Default

Description

V3P1

GROUP
SIGNAL

Main fuse voltage

V3P2

GROUP
SIGNAL

Pilot fuse voltage

BLOCK

BOOLEAN

Block of function

Table 389:
Name

VDSPVC (60) Output signals


Type

Description

MAINFUF

BOOLEAN

Block of main fuse failure

PILOTFUF

BOOLEAN

Alarm of pilot fuse failure

V1AFAIL

BOOLEAN

Fuse failure of Main fuse group phase A

Table continues on next page

746

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

Name

13.3.5
Table 390:
Name

Type

Description

V1BFAIL

BOOLEAN

Fuse failure of Main fuse group phase B

V1CFAIL

BOOLEAN

Fuse failure of Main fuse group phase C

V2AFAIL

BOOLEAN

Fuse failure of Pilot fuse group phase A

V2BFAIL

BOOLEAN

Fuse failure of Pilot fuse group phase B

V2CFAIL

BOOLEAN

Fuse failure of Pilot fuse group phase C

Settings
VDSPVC (60) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
On

Disabled

Disable/Enable operation of the function

Vdif Main block

10.0 - 80.0

%VB

0.1

20.0

Blocking picked up voltage level in % of VBase


when main fuse fails

Vdif Pilot alarm

10.0 - 80.0

%VB

0.1

30.0

Alarm picked up voltage level in % of VBase


when pilot fuse fails

SealIn

Disabled
On

On

Seal in functionality Disable/Enable

VSealIn

0.0 - 100.0

%VB

0.1

70.0

Operate level of seal-in voltage in % of VBase

Step

Default

Table 391:
Name
GlobalBaseSel

Table 392:
Name

VDSPVC (60) Non group settings (basic)


Values (Range)
1 - 12

Unit
-

Description
Selection of one of the Global Base Value
groups

VDSPVC (60) Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ConTypeMain

Ph-N
Ph-Ph

Ph-N

Selection of connection type for main fuse


group

ConTypePilot

Ph-N
Ph-Ph

Ph-N

Selection of connection type for pilot fuse


group

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

747

Section 13
Secondary system supervision
13.3.6

Monitored data
Table 393:
Name

13.3.7

1MRK 502 066-UUS A

VDSPVC (60) Monitored data


Type

Values (Range)

Unit

Description

VADIF_A

REAL

kV

Differential voltage phase A


for alarm functionality

VBDIF_A

REAL

kV

Differential voltage phase B


for alarm functionality

VCDIF_A

REAL

kV

Differential voltage phase C


for alarm functionality

VADIF_B

REAL

kV

Differential voltage phase A


for block functionality

VBDIF_B

REAL

kV

Differential voltage phase B


for block functionality

VCDIF_C

REAL

kV

Differential voltage phase C


for block functionality

Operation principle
VDSPVC requires six voltage inputs, which are the three phase voltages on main and pilot
fuse groups. The initial voltage difference between the two groups is theoretical zero in the
healthy condition. Any subsequent voltage difference will be due to a fuse failure.
If the main fuse voltage becomes smaller than the pilot fuse voltage (vMainA < vPilotA
or vMainB < vPilotB or vMainC < vPilotC) and the voltage difference exceeds the
operation level (Vdif Main block), a blocking signal will be initiated to indicate the main
fuse failure and block the voltage-dependent functions. In addition, the function also
indicates the phase in which the voltage reduction has occurred.
If the pilot fuse voltage becomes smaller than the main fuse voltage (vPilotA < vMainA
or vPilotB < vMainB or vPilotC < vMainC) and the voltage difference exceeds the
operation level (Vdif Pilot alarm), an alarm signal will be initiated to indicate the pilot fuse
failure and also the faulty phase where the voltage reduction occurred.
When SealIn is set to Enabled and the fuse failure has last for more than 5 seconds, the
blocked protection functions will remain blocked until normal voltage conditions are
restored above the VSealIn setting. Fuse failure outputs are deactivated when normal
voltage conditions are restored.

748

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 13
Secondary system supervision

1MRK 502 066-UUS A

a
a<b
VSealIn

AND

OR

5s
t
0

SealIn=0

vPilotA

vMainA

V1AFAIL

MAX

OR

a>b

AND

Vdif Main block

OR

0
MIN

ABS

a>b
Vdif Pilot alarm

MAINFUF

AND

V2AFAIL

BLOCK
OR
vPilotB

PILOTFUF

V1BFAIL

vMainB

Phase B, same as Phase A

V2BFAIL

vPilotC
vMainC

Phase C, same as Phase A

V2CFAIL

V1CFAIL

ANSI12000144-3-en.vsd

ANSI12000144 V3 EN

Figure 344:

13.3.8

Simplified logic diagram VDSPVC (60)

Technical data
Table 394:

technical data

Function

Range or value

Accuracy

Operate value, block of main fuse


failure

(10.0-80.0)% of VBase

0.5% of Vn

Reset ratio

<110%

Operate time, block of main fuse


failure at 1 to 0 x Vr

Min. = 5 ms

Reset time, block of main fuse


failure at 0 to 1 x Vr

Min. = 15 ms

Operate value, alarm for pilot


fuse failure

(10.0-80.0)% of VBase

0.5% of Vn

Reset ratio

<110%

Operate time, alarm for pilot fuse


failure at 1 to 0 x Vr

Min. = 5 ms

Reset time, alarm for pilot fuse


failure at 0 to 1 x Vr

Min. = 15 ms

Max. = 15 ms

Max. = 30 ms

Max. = 15 ms

Max. = 30 ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

749

750

Section 14
Control

1MRK 502 066-UUS A

Section 14

Control

14.1

Synchronism check, energizing check, and


synchronizing SESRSYN (25)

14.1.1

Identification
Function description
Synchrocheck, energizing check, and
synchronizing

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
25

SESRSYN

sc/vc
SYMBOL-M V1 EN

14.1.2

Functionality
The Synchronizing function allows closing of asynchronous networks at the correct
moment including the breaker closing time, which improves the network stability.
Synchrocheck, energizing check, and synchronizing SESRSYN (25) function checks that
the voltages on both sides of the circuit breaker are in synchronism, or with at least one
side dead to ensure that closing can be done safely.
SESRSYN (25) function includes a built-in voltage selection scheme for double bus and
breaker-and-a-half or ring busbar arrangements.
Manual closing as well as automatic reclosing can be checked by the function and can
have different settings.
For systems, which are running asynchronous, a synchronizing function is provided. The
main purpose of the synchronizing function is to provide controlled closing of circuit
breakers when two asynchronous systems are going to be connected. The synchronizing
function evaluates voltage difference, phase angle difference, slip frequency and
frequency rate of change before issuing a controlled closing of the circuit breaker. Breaker
closing time is a parameter setting.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

751

Section 14
Control

1MRK 502 066-UUS A

However this function can not be used to automatically synchronize the generator to the
network.

14.1.3

Function block
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
VOKSYN
VB1FF
VDIFFSYN
VB2OK
FRDIFSYN
VB2FF
FRDIFFOK
VL1OK
FRDERIVA
VL1FF
VOKSC
VL2OK
VDIFFSC
VL2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
VDIFFME
MENMODE
FRDIFFME
PHDIFFME
VBUS
VLINE
MODEAEN
MODEMEN
ANSI14000060-1-en.vsd
ANSI10000046 V2 EN

Figure 345:

14.1.4

SESRSYN (25) function block

Signals
Table 395:
Name

SESRSYN (25) Input signals


Type

Default

Description

V3PB1

GROUP
SIGNAL

Group signal for phase to ground voltage input Phase A,


busbar 1

V3PB2

GROUP
SIGNAL

Group signal for phase to ground voltage input Phase A,


busbar 1

V3PL1

GROUP
SIGNAL

Group signal for phase to ground voltage input phase A,


line 1

Table continues on next page

752

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

V3PL2

GROUP
SIGNAL

Group signal for phase to ground voltage input phase A,


line 2

BLOCK

BOOLEAN

General block

BLKSYNCH

BOOLEAN

Block synchronizing

BLKSC

BOOLEAN

Block synchro check

BLKENERG

BOOLEAN

Block energizing check

BUS1_OP

BOOLEAN

Open status for CB or disconnector connected to bus1

BUS1_CL

BOOLEAN

Close status for CB and disconnector connected to bus1

BUS2_OP

BOOLEAN

Open status for CB or disconnector connected to bus2

BUS2_CL

BOOLEAN

Close status for CB and disconnector connected to bus2

LINE1_OP

BOOLEAN

Open status for CB or disconnector connected to line1

LINE1_CL

BOOLEAN

Close status for CB and disconnector connected to line1

LINE2_OP

BOOLEAN

Open status for CB or disconnector connected to line2

LINE2_CL

BOOLEAN

Close status for CB and disconnector connected to line2

VB1OK

BOOLEAN

Bus1 voltage transformer OK

VB1FF

BOOLEAN

Bus1 voltage transformer fuse failure

VB2OK

BOOLEAN

Bus2 voltage transformer OK

VB2FF

BOOLEAN

Bus2 voltage transformer fuse failure

VL1OK

BOOLEAN

Line1 voltage transformer OK

VL1FF

BOOLEAN

Line1 voltage transformer fuse failure

VL2OK

BOOLEAN

Line2 voltage transformer OK

VL2FF

BOOLEAN

Line2 voltage transformer fuse failure

STARTSYN

BOOLEAN

Start synchronizing

TSTSYNCH

BOOLEAN

Set synchronizing in test mode

TSTSC

BOOLEAN

Set synchro check in test mode

TSTENERG

BOOLEAN

Set energizing check in test mode

AENMODE

INTEGER

Input for setting of automatic energizing mode

MENMODE

INTEGER

Input for setting of manual energizing mode

Table 396:
Name

SESRSYN (25) Output signals


Type

Description

SYNOK

BOOLEAN

Synchronizing OK output

AUTOSYOK

BOOLEAN

Auto synchronism-check OK

AUTOENOK

BOOLEAN

Automatic energizing check OK

MANSYOK

BOOLEAN

Manual synchronism-check OK

MANENOK

BOOLEAN

Manual energizing check OK

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

753

Section 14
Control

1MRK 502 066-UUS A

Name

754

Type

Description

TSTSYNOK

BOOLEAN

Synchronizing OK test output

TSTAUTSY

BOOLEAN

Auto synchronism-check OK test output

TSTMANSY

BOOLEAN

Manual synchronism-check OK test output

TSTENOK

BOOLEAN

Energizing check OK test output

VSELFAIL

BOOLEAN

Selected voltage transformer fuse failed

B1SEL

BOOLEAN

Bus1 selected

B2SEL

BOOLEAN

Bus2 selected

L1SEL

BOOLEAN

Line1 selected

L2SEL

BOOLEAN

Line2 selected

SYNPROGR

BOOLEAN

Synchronizing in progress

SYNFAIL

BOOLEAN

Synchronizing failed

VOKSYN

BOOLEAN

Voltage amplitudes for synchronizing above set limits

VDIFFSYN

BOOLEAN

Voltage difference out of limit for synchronizing

FRDIFSYN

BOOLEAN

Frequency difference out of limit for synchronizing

FRDIFFOK

BOOLEAN

Frequency difference in band for synchronizing

FRDERIVA

BOOLEAN

Frequency derivative out of limit for synchronizing

VOKSC

BOOLEAN

Voltage magnitudes above set limits

VDIFFSC

BOOLEAN

Voltage difference out of limit

FRDIFFA

BOOLEAN

Frequency difference out of limit for Auto operation

PHDIFFA

BOOLEAN

Phase angle difference out of limit for Auto operation

FRDIFFM

BOOLEAN

Frequency difference out of limit for Manual operation

PHDIFFM

BOOLEAN

Phase angle difference out of limit for Manual Operation

INADVCLS

BOOLEAN

Inadvertent circuit breaker closing

VDIFFME

REAL

Calculated difference of voltage in p.u of set voltage


base value

FRDIFFME

REAL

Calculated difference of frequency

PHDIFFME

REAL

Calculated difference of phase angle

VBUS

REAL

Bus voltage

VLINE

REAL

Line voltage

MODEAEN

INTEGER

Selected mode for automatic energizing

MODEMEN

INTEGER

Selected mode for manual energizing

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.1.5
Table 397:
Name

Settings
SESRSYN (25) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

OperationSynch

Disabled
Enabled

Disabled

Operation for synchronizing function Off/On

VHighBusSynch

50.0 - 120.0

%UBB

1.0

80.0

Voltage high limit bus for synchronizing in % of


VBaseBus

VHighLineSynch

50.0 - 120.0

%UBL

1.0

80.0

Voltage high limit line for synchrocheck in % of


VBaseLine

VDiffSynch

0.02 - 0.50

pu

0.01

0.10

Voltage difference limit for synchronizing in p.u


of set voltage base value

FreqDiffMin

0.003 - 0.250

Hz

0.001

0.010

Minimum frequency difference limit for


synchronizing

FreqDiffMax

0.050 - 0.500

Hz

0.001

0.200

Maximum frequency difference limit for


synchronizing

FreqRateChange

0.000 - 0.500

Hz/s

0.001

0.300

Maximum allowed frequency rate of change

tBreaker

0.000 - 60.000

0.001

0.080

Closing time of the breaker

tClosePulse

0.050 - 60.000

0.001

0.200

Breaker closing pulse duration

tMaxSynch

0.00 - 6000.00

0.01

600.00

Resets synch if no close has been made before


set time

tMinSynch

0.000 - 60.000

0.001

2.000

Minimum time to accept synchronizing


conditions

OperationSC

Disabled
Enabled

Enabled

Operation for synchronism-check function


Off/On

VHighBusSC

50.0 - 120.0

%UBB

1.0

80.0

Voltage high limit bus for synchrocheck in % of


VBaseBus

VHighLineSC

50.0 - 120.0

%UBL

1.0

80.0

Voltage high limit line for synchrocheck in % of


VBaseLine

VDiffSC

0.02 - 0.50

pu

0.01

0.15

Voltage difference limit for synchrocheck in p.u


of set voltage base value

FreqDiffA

0.003 - 1.000

Hz

0.001

0.010

Frequency difference limit between bus and


line Auto

FreqDiffM

0.003 - 1.000

Hz

0.001

0.010

Frequency difference limit between bus and


line Manual

PhaseDiffA

5.0 - 90.0

Deg

1.0

25.0

Phase angle difference limit between bus and


line Auto

PhaseDiffM

5.0 - 90.0

Deg

1.0

25.0

Phase angle difference limit between bus and


line Manual

tSCA

0.000 - 60.000

0.001

0.100

Time delay output for synchrocheck Auto

tSCM

0.000 - 60.000

0.001

0.100

Time delay output for manual synchrocheck

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

755

Section 14
Control

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

AutoEnerg

Disabled
DLLB
DBLL
Both

DLLB

Automatic energizing check mode

ManEnerg

Disabled
DLLB
DBLL
Both

Both

Manual energizing check mode

ManEnergDBDL

Disabled
Enabled

Disabled

Manual dead bus, dead line energizing

VLiveBusEnerg

50.0 - 120.0

%UBB

1.0

80.0

Voltage high limit bus for energizing check in %


of VBaseBus

VLiveLineEnerg

50.0 - 120.0

%UBL

1.0

80.0

Voltage high limit line for energizing check in %


of VBaseLine

VDeadBusEnerg

10.0 - 80.0

%UBB

1.0

40.0

Voltage low limit bus for energizing check in %


of VBaseBus

VDeadLineEnerg

10.0 - 80.0

%UBL

1.0

40.0

Voltage low limit line for energizing check in %


of VBaseLine

VMaxEnerg

50.0 - 180.0

%VB

1.0

115.0

Maximum voltage for energizing in % of VBase,


Line and/or Bus

tAutoEnerg

0.000 - 60.000

0.001

0.100

Time delay for automatic energizing check

tManEnerg

0.000 - 60.000

0.001

0.100

Time delay for manual energizing check

Table 398:
Name

SESRSYN (25) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

SelPhaseBus1

Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence

Phase A

Select phase for busbar1

GblBaseSelBus

1 - 12

Selection of one of the Global Base Value


groups, Bus

GblBaseSelLine

1 - 12

Selection of one of the Global Base Value


groups, Line

SelPhaseBus2

Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence

Phase A

Select phase for busbar2

Table continues on next page

756

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

SelPhaseLine1

Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence

Phase A

Select phase for line1

SelPhaseLine2

Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence

Phase A

Select phase for line2

CBConfig

No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB

No voltage sel.

Select CB configuration

Table 399:
Name
PhaseShift

14.1.6

SESRSYN (25) Non group settings (advanced)


Values (Range)
-180 - 180

Unit

Step

Deg

Default
0

Description
Additional phase angle for selected line voltage

Monitored data
Table 400:
Name

SESRSYN (25) Monitored data


Type

Values (Range)

Unit

Description

VDIFFME

REAL

Calculated difference of
voltage in p.u of set voltage
base value

FRDIFFME

REAL

Hz

Calculated difference of
frequency

PHDIFFME

REAL

deg

Calculated difference of phase


angle

VBUS

REAL

kV

Bus voltage

VLINE

REAL

kV

Line voltage

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

757

Section 14
Control

1MRK 502 066-UUS A

14.1.7

Operation principle

14.1.7.1

Basic functionality
The synchronism check function measures the conditions across the circuit breaker and
compares them to set limits. The output is only given when all measured quantities are
simultaneously within their set limits.
The energizing check function measures the bus and line voltages and compares them to
both high and low threshold detectors. The output is given only when the actual measured
quantities match the set conditions.
The synchronizing function measures the conditions across the circuit breaker, and also
determines the angle change occurring during the closing delay of the circuit breaker,
from the measured slip frequency. The output is given only when all measured conditions
are simultaneously within their set limits. The issue of the output is timed to give closure
at the optimal time including the time for the circuit breaker and the closing circuit.
For double bus single circuit breaker and breaker-and-a-half circuit breaker arrangements,
the SESRSYN (25) function blocks have the capability to make the necessary voltage
selection. For double bus single circuit breaker arrangements, selection of the correct
voltage is made using auxiliary contacts of the bus disconnectors. For breaker-and-a-half
circuit breaker arrangements, correct voltage selection is made using auxiliary contacts of
the bus disconnectors as well as the circuit breakers.
The internal logic for each function block as well as, the input and outputs, and the setting
parameters with default setting and setting ranges is described in this document. For
application related information, please refer to the application manual.

14.1.7.2

Logic diagrams
Logic diagrams
The logic diagrams that follow illustrate the main principles of the SESRSYN function
components such as Synchrocheck, Synchronizing, Energizing check and Voltage
selection, and are intended to simplify the understanding of the function.

Synchronism check
The voltage difference, frequency difference and phase angle difference values are
measured in the IED centrally and are available for the synchronism check function for
evaluation. By setting the phases used for SESRSYN, with the settings SelPhaseBus1,
SelPhaseBus2, SelPhaseLine1 and SelPhaseLine2, a compensation is made automatically
for the voltage amplitude difference and the phase angle difference caused if different
setting values are selected for both sides of the breaker. If needed an additional phase angle
adjustment can be done for selected line voltage with the PhaseShift setting.

758

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

When the function is set to OperationSC = Enabled, the measuring will start.
The function will compare the bus and line voltage values with the set values for
VHighBusSC and VHighLineSC.
If both sides are higher than the set values, the measured values are compared with the set
values for acceptable frequency, phase angle and voltage difference: FreqDiffA,
FreqDiffM, PhaseDiffA, PhaseDiffM and VDiffSC. If additional phase angle adjustment
is done with the PhaseShift setting, the adjustment factor is deducted from the line voltage
before the comparison of the phase angle values.
The frequency on both sides of the circuit breaker is also measured. The frequencies must
not deviate from the rated frequency more than +/-5Hz. The frequency difference between
the bus frequency and the line frequency is measured and may not exceed the set value
FreqDiff.
Two sets of settings for frequency difference and phase angle difference are available and
used for the manual closing and autoreclose functions respectively, as required.
The inputs BLOCK and BLKSC are available for total block of the complete SESRSYN
(25) function and selective block of the Synchronism check function respectively. Input
TSTSC will allow testing of the function where the fulfilled conditions are connected to
a separate test output.
The outputs MANSYOK and AUTOSYOK are activated when the actual measured
conditions match the set conditions for the respective output. The output signal can be
delayed independently for MANSYOK and AUTOSYOK conditions.
A number of outputs are available as information about fulfilled checking conditions.
VOKSC shows that the voltages are high, VDIFFSC, FRDIFFA, FRDIFFM, PHDIFFA,
PHDIFFM shows when the voltage difference, frequency difference and phase angle
difference conditions are out of limits.
Output INADVCLS, inadvertent circuit breaker closing, indicates that the circuit breaker
has been closed at wrong phase angle by mistake. The output is activated, if the voltage
conditions are fulfilled at the same time the phase angle difference between bus and line
is suddenly changed from being larger than 60 degrees to smaller than 5 degrees.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

759

Section 14
Control

1MRK 502 066-UUS A

Note! Similar logic for Manual Synchronism check.


OperationSC = Enabled

AND

AND

TSTAUTSY

TSTSC
BLKSC
BLOCK

AND

OR

AND
tSCA

AND

VDiffSC

AND

VHighBusSC

AUTOSYOK

0-60 ms
0

50 ms
0

VOKSC

AND

VHighLineSC

VDIFFSC

FreqDiffA

PhaseDiffA

FRDIFFA
PHDIFFA
VDIFFME

voltageDifferenceValue

FRDIFFME

frequencyDifferenceValue

PHDIFFME

phaseAngleDifferenceValue

PhDiff > 60

AND

0
32 ms

100 ms

INADVCLS

AND

PhDiff < 5

ANSI07000114-4-en.vsd
ANSI07000114 V4 EN

Figure 346:

Simplified logic diagram for the Auto Synchronism function

Synchronizing
When the function is set to OperationSynch = Enabled the measuring will be performed.
The function will compare the values for the bus and line voltage with the set values for
VHighBusSynch and VHighLineSynch, which is a supervision that the voltages are both
live. Also the voltage difference is checked to be smaller than the set value for
VDiffSynch, which is a p.u value of set voltage base values. If both sides are higher than
the set values and the voltage difference between bus and line is acceptable, the measured
values are compared with the set values for acceptable frequency FreqDiffMax and

760

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

FreqDiffMin, rate of change of frequency FreqRateChange and phase angle, which has to
be smaller than the internally preset value of 15 degrees.
Measured frequencies between the settings for the maximum and minimum frequency
will initiate the measuring and the evaluation of the angle change to allow operation to be
sent in the right moment including the set tBreaker time. There is a phase angle release
internally to block any incorrect closing pulses. At operation the SYNOK output will be
activated with a pulse tClosePulse and the function resets. The function will also reset if
the synchronizing conditions are not fulfilled within the set tMaxSynch time. This
prevents that the function is, by mistake, maintained in operation for a long time, waiting
for conditions to be fulfilled.
The inputs BLOCK and BLKSYNCH are available for total block of the complete
SESRSYN function and block of the Synchronizing function respectively. TSTSYNCH
will allow testing of the function where the fulfilled conditions are connected to a separate
output.
SYN1
OPERATION SYNCH=ON

TEST MODE=ON
STARTSYN
AND

BLKSYNCH
OR

AND

S
R

VDiffSynch
VHighBusSynch

AND

50 ms
t

SYNOK

AND

VHighLineSynch

SYNPROGR

OR

FreqDiffMax

AND

FreqDiffMin

OR

FreqRateChange

AND

TSTSYNOK

tClose
Pulse

fBus&fLine 5Hz
Phase Diff < 15 deg

tMax
Synch
AND

SYNFAIL

PhaseDiff=closing angle
FreqDiff
tBreaker

Close pulse
in advance
ANSI06000636-3-en.vsd

ANSI06000636 V3 EN

Figure 347:

Simplified logic diagram for the synchronizing function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

761

Section 14
Control

1MRK 502 066-UUS A

Energizing check
Voltage values are measured in the IED and are available for evaluation by the
Synchronism check function.
The function measures voltages on the busbar and the line to verify whether they are live
or dead. This is done by comparing with the set values VLiveBusEnerg and
VDeadBusEnerg for bus energizing and VLiveLineEnerg and VDeadLineEnerg for line
energizing.
The frequency on both sides of the circuit breaker is also measured. The frequencies must
not deviate from the rated frequency more than +/-5Hz.
The Energizing direction can be selected individually for the Manual and the Automatic
functions respectively. When the conditions are met the outputs AUTOENOK and
MANENOK respectively will be activated if the fuse supervision conditions are fulfilled.
The output signal can be delayed independently for MANENOK and AUTOENOK
conditions. The Energizing direction can also be selected by an integer input AENMODE
respective MENMODE, which for example, can be connected to a Binary to Integer
function block (B16I). Integers supplied shall be 1=Off, 2=DLLB, 3=DBLL and 4= Both.
Not connected input will mean that the setting is done from Parameter Setting tool. The
active position can be read on outputs MODEAEN resp MODEMEN. The modes are
0=OFF, 1=DLLB, 2=DBLL and 3=Both.
The inputs BLOCK and BLKENERG are available for total block of the complete
SESRSYN (25) function respective block of the Energizing check function. TSTENERG
will allow testing of the function where the fulfilled conditions are connected to a separate
test output.

762

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

manEnergOpenBays

MANENOK

OR

TSTENERG
BLKENERG
OR

BLOCK
selectedFuseOK

VLiveBusEnerg
DLLB

AND

VDeadLineEnerg

OR

AND

OR

0 60 s
tManEnerg
0

AND

BOTH

ManEnerg
DBLL

VDeadBusEnerg

AND

VLiveLineEnerg

AND

ManEnergDBDL

AND

TSTENOK

VMaxEnerg
fBus and fLine 5 Hz
ANSI14000031-1-en.vsd

ANSI14000031 V1 EN

Figure 348:

Manual energizing

TSTENERG
BLKENERG
OR

BLOCK
selectedFuseOK

VLiveBusEnerg
DLLB

AND

OR

VDeadLineEnerg

AND

OR

0 60 s
tAutoEnerg
0

AND

AUTOENOK

BOTH

AutoEnerg

VDeadBusEnerg
DBLL

AND

VLiveLineEnerg
VMaxEnerg

AND

TSTENOK

fBus and fLine 5 Hz

ANSI14000030-1-en.vsd

ANSI14000030 V1 EN

Figure 349:

Automatic energizing

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

763

Section 14
Control

1MRK 502 066-UUS A

BLKENERG
BLOCK

OR

AND

manEnergOpenBays

ManEnerg
1 bus CB

CBConfig

AND

B1QOPEN
LN1QOPEN

AND

OR

B1QCLD
B2QOPEN

AND

LN2QOPEN
1 bus alt. CB
AND

B2QCLD

AND

OR

OR

AND

Tie CB
AND

AND

OR

AND

IEC14000032-1-en.vsd
IEC14000032 V1 EN

Figure 350:

Open bays

Fuse failure supervision


External fuse failure signals or signals from a tripped fuse switch/MCB are connected to
binary inputs that are configured to the inputs of SESRSYN (25) function in the IED.
Alternatively, the internal signals from fuse failure supervision can be used when
available. There are two alternative connection possibilities. Inputs labelled OK must be
connected if the available contact indicates that the voltage circuit is healthy. Inputs
labelled FF must be connected if the available contact indicates that the voltage circuit is
faulty.
The VB1OK/VB2OK and VB1FF/VB2FF inputs are related to the busbar voltage and the
VLNOK and VLNFF inputs are related to the line voltage. Configure them to the binary
input or function outputs that indicate the status of the external fuse failure of the busbar
and line voltages. In the event of a fuse failure, the energizing check function is blocked.
The synchronism check function requires full voltage on both sides, thus no blocking at
fuse failure is needed.

764

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Voltage selection
The voltage selection module including supervision of included voltage transformers for
the different arrangements is a basic part of the SESRSYN (25) function and determines
the voltages fed to the Synchronizing, Synchrocheck and Energizing check functions.
This includes the selection of the appropriate Line and Bus voltages and MCB
supervision.
The voltage selection type to be used is set with the parameter CBConfig.
If No voltage sel. is set the voltages used will be V-Line1 and V-Bus1. This setting is also
used in the case when external voltage selection is provided. Fuse failure supervision for
the used inputs must also be connected.
The voltage selection function, selected voltages, and fuse conditions are used for the
Synchronism check and Energizing check inputs.
For the disconnector positions it is advisable to use (NO) a and (NC) b type contacts to
supply Disconnector Open and Closed positions but, it is also possible to use an inverter
for one of the positions.
If breaker or disconnector positions not are available for deciding if energizing is allowed,
it is considered to be allowed to manually energize. This is only allowed for manual
energizing in breaker-and-a-half and Tie breaker arrangements. Manual energization of a
completely open diameter in 1 1/2 CB switchgear is allowed by internal logic.

Voltage selection for a single circuit breaker with double busbars


The setting CBConfig selected for Double Bus activates the voltage selection for single
CB and double busbars. This function uses the binary input from the disconnectors
auxiliary contacts BUS1_OP-BUS1_CL for Bus 1, and BUS2_OP-BUS2_CL for Bus 2 to
select between bus 1 and bus 2 voltages. If the disconnector connected to bus 1 is closed
and the disconnector connected to bus 2 is opened the bus 1 voltage is used. All other
combinations use the bus 2 voltage. The outputs B1SEL and B2SEL respectively indicate
the selected Bus voltage.
The function checks the fuse-failure signals for bus 1, bus 2 and line voltage transformers.
Inputs VB1OK-VB1FF supervise the MCB for Bus 1 and VB2OK-VB2FF supervises the
MCB for Bus 2. VL1OK and VL1FF supervises the MCB for the Line voltage
transformer. The inputs fail (FF) or healthy (OK) can alternatively be used dependent on
the available signal. If a VT failure is detected in the selected voltage source an output
signal VSELFAIL is set. This output signal is true if the selected bus or line voltages have
a VT failure. This output as well as the function can be blocked with the input signal
BLOCK. The function logic diagram is shown in figure 351.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

765

Section 14
Control

1MRK 502 066-UUS A

BUS1_OP
BUS1_CL
BUS2_OP
BUS2_CL

B1SEL

AND

AND

B2SEL

NOT
AND

invalidSelection
busVoltage

bus1Voltage
bus2Voltage

VB1OK
VB1FF

OR

VB2OK
VB2FF

OR

VL1OK
VL1FF

OR

AND
OR

AND

AND
AND

selectedFuseOK
VSELFAIL

BLOCK

en05000779_2_ansi.vsd
ANSI05000779 V2 EN

Figure 351:

Logic diagram for the voltage selection function of a single circuit breaker with double busbars

Voltage selection for a breaker-and-a-half circuit breaker arrangement


Note that with breaker-and-a-half schemes three Synchronism check functions must be
used for the complete diameter. Below, the scheme for one Bus breaker and the Tie
breaker is described.
With the setting parameter CBConfig the selection of actual CB location in the 1 1/2 circuit
breaker switchgear is done. The settings are: 1 1/2 Bus CB, 1 1/2 alt. Bus CB or Tie CB.
This voltage selection function uses the binary inputs from the disconnectors and circuit
breakers auxiliary contacts to select the right voltage for the SESRSYN function. For the
bus circuit breaker one side of the circuit breaker is connected to the busbar and the other
side is connected either to line 1, line 2 or the other busbar depending on the best selection
of voltage circuit.
Inputs LINE1_OP-LINE1_CL, BUS1_OP-BUS1_CL, BUS2_OP-BUS2_CL,
LINE2_OP-LINE2_CL are inputs for the position of the Line disconnectors respectively
the Bus and Tie breakers. The outputs L1SEL, L2SEL and B2SEL will give indication of
766

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

the selected Line voltage as a reference to the fixed Bus 1 voltage, which indicates
B1SEL.
The fuse supervision is connected to VL1OK-VL1FF, VL2OK-VL2FF and with
alternative Healthy or Failing fuse signals depending on what is available from each fuse
(MCB).
The tie circuit breaker is connected either to bus 1 or line 1 voltage on one side and the
other side is connected either to bus 2 or line 2 voltage. Four different output combinations
are possible, bus to bus, bus to line, line to bus and line to line.

The line 1 voltage is selected if the line 1 disconnector is closed.


The bus 1 voltage is selected if the line 1 disconnector is open and the bus 1 circuit
breaker is closed.
The line 2 voltage is selected if the line 2 disconnector is closed.
The bus 2 voltage is selected if the line 2 disconnector is open and the bus 2 circuit
breaker is closed.

The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2. If a VT
failure is detected in the selected voltage an output signal VSELFAIL is set. This output
signal is true if the selected bus or line voltages have a MCB trip. This output as well as
the function can be blocked with the input signal BLOCK. The function block diagram for
the voltage selection of a bus circuit breaker is shown in figure 352 and for the tie circuit
breaker in figure 353.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

767

Section 14
Control

1MRK 502 066-UUS A

LINE1_OP
LINE1_CL

L1SEL

AND

BUS1_OP
BUS1_CL

L2SEL

AND

AND

LINE2_CL

AND

invalidSelection

AND
AND

BUS2_OP
BUS2_CL

B2SEL

OR

LINE2_OP

AND

lineVoltage

line1Voltage
line2Voltage
bus2Voltage
VB1OK
VB1FF
VB2OK
VB2FF

OR
OR
OR

VL1OK
VL1FF

OR

VL2OK
VL2FF

OR

AND

AND

AND

AND

selectedFuseOK

VSELFAIL

AND

BLOCK

en05000780_2_ansi.vsd
ANSI05000780 V2 EN

Figure 352:

768

Simplified logic diagram for the voltage selection function for a bus circuit breaker in a breaker-and-ahalf arrangement

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

LINE1_OP
LINE1_CL

L1SEL

AND

B1SEL

NOT
BUS1_OP
BUS1_CL

AND

AND

AND

line1Voltage

busVoltage

bus1Voltage
LINE2_OP
LINE2_CL

L2SEL

AND

B2SEL

NOT
BUS2_OP
BUS2_CL

AND

AND

AND

OR

invalidSelection

lineVoltage

line2Voltage
bus2Voltage
VB1OK
VB1FF

OR

VB2OK
VB2FF

OR

AND
OR

VL1OK
VL1FF

OR

VL2OK
VL2FF

OR

AND

AND

AND

AND

selectedFuseOK

VSELFAIL

AND

BLOCK

en05000781_2_ansi.vsd
ANSI05000781 V2 EN

Figure 353:

Simplified logic diagram for the voltage selection function for the tie circuit breaker in breaker-and-ahalf arrangement.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

769

Section 14
Control
14.1.8

1MRK 502 066-UUS A

Technical data
Table 401:

SESRSYN (25) technical data

Function

Range or value

Phase shift, jline - jbus

(-180 to 180) degrees

Voltage high limit for synchronism


check

Accuracy
0.5% of Vn at V Vn
0.5% of V at V > Vn

Reset ratio, synchronism check

> 95%

Frequency difference limit


between bus and line for
synchronism check

(0.003-1.000) Hz

2.5 mHz

Phase angle difference limit


between bus and line for
synchronism check

(5.0-90.0) degrees

2.0 degrees

Voltage difference limit between


bus and line for synchronism check

(0.02-0.5) p.u

0.5% of Vn

Time delay output for synchronism


check

(0.000-60.000) s

0.2% or 35 ms whichever is
greater

Frequency difference minimum


limit for synchronizing

(0.003-0.250) Hz

2.5 mHz

Frequency difference maximum


limit for synchronizing

(0.050-0.500) Hz

2.5 mHz

Maximum allowed frequency rate


of change

(0.000-0.500) Hz/s

10.0 mHz/s

Breaker closing pulse duration

(0.050-60.000) s

0.2% or 15 ms whichever is
greater

tMaxSynch, which resets


synchronizing function if no close
has been made before set time

(0.000-6000.00) s

0.2% or 35 ms whichever is
greater

Minimum time to accept


synchronizing conditions

(0.000-60.000) s

0.2% or 35 ms whichever is
greater

Voltage high limit for energizing


check
Reset ratio, voltage high limit

0.5% of Vn at V Vn
0.5% of V at V > Vn
> 95%

Voltage low limit for energizing


check
Reset ratio, voltage low limit
Maximum voltage for energizing

0.5% of Vn

< 105%

0.5% of Vn at V Vn
0.5% of V at V > Vn

Table continues on next page

770

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Time delay for energizing check


when voltage jumps from 0 to 90%
of Vrated

(0.000-60.000) s

0.2% or 100 ms whichever is


greater

Trip time for synchrocheck function


when angle difference between
bus and line jumps from
PhaseDiff + 2 degrees to
PhaseDiff - 2 degrees

Min. = 15 ms
Max. = 30 ms

Trip time for energizing function


when voltage jumps from 0 to 90%
of Vrated

Min. = 70 ms
Max. = 90 ms

14.2

Interlocking (3)

14.2.1

Functionality
The interlocking functionality blocks the possibility to operate high-voltage switching
devices, for instance when a disconnector is under load, in order to prevent material
damage and/or accidental human injury.
Each control IED has interlocking functions for different switchyard arrangements, each
handling the interlocking of one bay. The interlocking functionality in each IED is not
dependent on any central function. For the station-wide interlocking, the IEDs
communicate via the station bus or by using hard wired binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and status of the system
at any given time.

14.2.2

Operation principle
The interlocking function consists of software modules located in each control IED. The
function is distributed and not dependent on any central function. Communication
between modules in different bays is performed via the station bus.
The reservation function (see section "Functionality") is used to ensure that HV
apparatuses that might affect the interlock are blocked during the time gap, which arises
between position updates. This can be done by means of the communication system,
reserving all HV apparatuses that might influence the interlocking condition of the
intended operation. The reservation is maintained until the operation is performed.
After the selection and reservation of an apparatus, the function has complete data on the
status of all apparatuses in the switchyard that are affected by the selection. Other

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

771

Section 14
Control

1MRK 502 066-UUS A

operators cannot interfere with the reserved apparatus or the status of switching devices
that may affect it.
The open or closed positions of the HV apparatuses are inputs to software modules
distributed in the control IEDs. Each module contains the interlocking logic for a bay. The
interlocking logic in a module is different, depending on the bay function and the
switchyard arrangements, that is, double-breaker or breaker-and-a-half bays have
different modules. Specific interlocking conditions and connections between standard
interlocking modules are performed with an engineering tool. Bay-level interlocking
signals can include the following kind of information:

Positions of HV apparatuses (sometimes per phase)


Valid positions (if evaluated in the control module)
External release (to add special conditions for release)
Line voltage (to block operation of line grounding switch)
Output signals to release the HV apparatus

The interlocking module is connected to the surrounding functions within a bay as shown
in figure 354.
Interlocking
modules in
other bays

Interlocking
module

Apparatus control
modules
SCILO

SCSWI

SXSWI

Apparatus control
modules
SCILO

SCSWI

SXCBR

152

Apparatus control
modules
SCILO

SCSWI

SXSWI

en04000526_ansi.vsd
ANSI04000526 V1 EN

Figure 354:

Interlocking module on bay level

Bays communicate via the station bus and can convey information regarding the
following:

772

Ungrounded busbars
Busbars connected together
Other bays connected to a busbar
Received data from other bays is valid

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Figure 355 illustrates the data exchange principle.


Station bus
Bay 1

Bay n

Disc 189 and 289 closed

WA1 not grounded


WA2 not grounded
WA1 and WA2 interconn

Bus coupler

Disc 189 and 289 closed

...
..

WA1 ungrounded
WA1 ungrounded
WA1 and WA2 interconn

WA1 not grounded


WA2 not grounded
WA1 and WA2 interconn

WA1 and WA2 interconn


in other bay

WA1
WA2
189

289

189

289

289

189

189G

289G

152
152

152
989

989

en05000494_ansi.vsd
ANSI05000494 V1 EN

Figure 355:

Data exchange between interlocking modules

When invalid data such as intermediate position, loss of a control IED, or input board error
are used as conditions for the interlocking condition in a bay, a release for execution of the
function will not be given.
On the local HMI an override function exists, which can be used to bypass the interlocking
function in cases where not all the data required for the condition is valid.
For all interlocking modules these general rules apply:

The interlocking conditions for opening or closing of disconnectors and grounding


switches are always identical.
Grounding switches on the line feeder end, for example, rapid grounding switches,
are normally interlocked only with reference to the conditions in the bay where they
are located, not with reference to switches on the other side of the line. So a line
voltage indication may be included into line interlocking modules. If there is no line
voltage supervision within the bay, then the appropriate inputs must be set to no
voltage, and the operator must consider this when operating.
Grounding switches can only be operated on isolated sections for example, without
load/voltage. Circuit breaker contacts cannot be used to isolate a section, that is, the
status of the circuit breaker is irrelevant as far as the grounding switch operation is
concerned.
Disconnectors cannot break power current or connect different voltage systems.
Disconnectors in series with a circuit breaker can only be operated if the circuit
breaker is open, or if the disconnectors operate in parallel with other closed
connections. Other disconnectors can be operated if one side is completely isolated,

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

773

Section 14
Control

1MRK 502 066-UUS A

or if the disconnectors operate in parallel to other closed connections, or if they are


grounding on both sides.
Circuit breaker closing is only interlocked against running disconnectors in its bay or
additionally in a transformer bay against the disconnectors and grounding switch on
the other side of the transformer, if there is no disconnector between CB and
transformer.
Circuit breaker opening is only interlocked in a bus-coupler bay, if a bus bar transfer
is in progress.

To make the implementation of the interlocking function easier, a number of standardized


and tested software interlocking modules containing logic for the interlocking conditions
are available:

Line for double and transfer busbars, ABC_LINE (3)


Bus for double and transfer busbars, ABC_BC (3)
Transformer bay for double busbars, AB_TRAFO (3)
Bus-section breaker for double busbars, A1A2_BS (3)
Bus-section disconnector for double busbars, A1A2_DC (3)
Busbar grounding switch, BB_ES (3)
Double CB Bay, DB_BUS_A(3), DB_LINE(3), DB_BUS_B(3)
Breaker-and-a-half diameter, BH_LINE_A, BH_CONN, BH_LINE_B (3)

The interlocking conditions can be altered, to meet the customer specific requirements, by
adding configurable logic by means of the graphical configuration tool PCM600. The
inputs Qx_EXy on the interlocking modules are used to add these specific conditions.
The input signals EXDU_xx shall be set to true if there is no transmission error at the
transfer of information from other bays. Required signals with designations ending in TR
are intended for transfer to other bays.

14.2.3

Logical node for interlocking SCILO (3)

14.2.3.1

Identification
Function description
Logical node for interlocking

14.2.3.2

IEC 61850
identification
SCILO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
3

Functionality
The Logical node for interlocking SCILO(3) function is used to enable a switching
operation if the interlocking conditions permit. SCILO (3) function itself does not provide

774

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

any interlocking functionality. The interlocking conditions are generated in separate


function blocks containing the interlocking logic.

14.2.3.3

Function block
SCILO (3)
POSOPEN
EN_OPEN
POSCLOSE
EN_CLOSE
OPEN_EN
CLOSE_EN
ANSI05000359-1-en.vsd
ANSI05000359 V1 EN

Figure 356:

14.2.3.4

SCILO (3) function block

Signals
Table 402:

SCILO (3) Input signals

Name

Type

Description

BOOLEAN

Open position of switch device

POSCLOSE

BOOLEAN

Closed position of switch device

OPEN_EN

BOOLEAN

Open operation from interlocking logic is enabled

CLOSE_EN

BOOLEAN

Close operation from interlocking logic is enabled

Table 403:

SCILO (3) Output signals

Name

14.2.3.5

Default

POSOPEN

Type

Description

EN_OPEN

BOOLEAN

Open operation at closed or intermediate or bad position


is enabled

EN_CLOSE

BOOLEAN

Close operation at open or intermediate or bad position


is enabled

Logic diagram
The function contains logic to enable the open and close commands respectively if the
interlocking conditions are fulfilled. That means also, if the switch has a defined end
position for example, open, then the appropriate enable signal (in this case EN_OPEN) is
false. The enable signals EN_OPEN and EN_CLOSE can be true at the same time only in
the intermediate and bad position state and if they are enabled by the interlocking function.
The position inputs come from the logical nodes Circuit breaker/Circuit switch (SXCBR/
SXSWI) and the enable signals come from the interlocking logic. The outputs are
connected to the logical node Switch controller (SCSWI). One instance per switching
device is needed.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

775

Section 14
Control

1MRK 502 066-UUS A

SCILO

POSOPEN
POSCLOSE

XOR

NOT

EN_OPEN

AND

OR
AND

OPEN_EN
CLOSE_EN

AND

EN_CLOSE
OR

AND
en04000525_ansi.vsd
ANSI04000525 V1 EN

Figure 357:

SCILO (3) function logic diagram

14.2.4

Interlocking for busbar grounding switch BB_ES (3)

14.2.4.1

Identification
Function description
Interlocking for busbar grounding
switch

14.2.4.2

IEC 61850
identification
BB_ES

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
3

Functionality
The interlocking for busbar grounding switch (BB_ES, 3) function is used for one busbar
grounding switch on any busbar parts according to figure 358.

89G

en04000504.vsd
ANSI04000504 V1 EN

Figure 358:

776

Switchyard layout BB_ES (3)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.4.3

Function block
BB_ES (3)
89G_OP
89GREL
89G_CL
89GITL
BB_DC_OP
BBGSOPTR
VP_BB_DC
BBGSCLTR
EXDU_BB
ANSI05000347-2-en.vsd
ANSI05000347 V2 EN

Figure 359:

14.2.4.4

BB_ES (3) function block

Logic diagram
BB_ES
VP_BB_DC
BB_DC_OP
EXDU_BB

AND

NOT

89G_OP
89G_CL

89GREL
89GITL
BBGSOPTR
BBGSCLTR
en04000546_ansi.vsd

ANSI04000546 V1 EN

14.2.4.5

Signals
Table 404:
Name

BB_ES (3) Input signals


Type

Default

Description

89G_OP

BOOLEAN

Busbar grounding switch 89G is in open position

89G_CL

BOOLEAN

Busbar grounding switch 89G is in closed position

BB_DC_OP

BOOLEAN

All disconnectors on this busbar part are open

VP_BB_DC

BOOLEAN

Status for all disconnectors on this busbar part are valid

EXDU_BB

BOOLEAN

No transm error from bays with disc on this busbar part

Table 405:
Name

BB_ES (3) Output signals


Type

Description

89GREL

BOOLEAN

Switching of 89G is allowed

89GITL

BOOLEAN

Switching of 89G is not allowed

BBGSOPTR

BOOLEAN

89G on this busbar part is in open position

BBGSCLTR

BOOLEAN

89G on this busbar part is in closed position

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

777

Section 14
Control

1MRK 502 066-UUS A

14.2.5

Interlocking for bus-section breaker A1A2_BS (3)

14.2.5.1

Identification
Function description

IEC 61850
identification

Interlocking for bus-section breaker

14.2.5.2

A1A2_BS

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
3

Functionality
The interlocking for bus-section breaker (A1A2_BS ,3) function is used for one bussection circuit breaker between section 1 and 2 according to figure 360. The function can
be used for different busbars, which includes a bus-section circuit breaker.
WA1 (A1)

189G

WA2 (A2)

189

289

289G

152

489G

389G

A1A2_BS
en04000516_ansi.vsd
ANSI04000516 V1 EN

Figure 360:

778

Switchyard layout A1A2_BS (3)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.5.3

Function block
A1A2_BS (3)
152_OP
152OPREL
152_CL
152OPITL
189_OP
152CLREL
189_CL
152CLITL
289_OP
189REL
289_CL
189ITL
389G_OP
289REL
389G_CL
289ITL
489G_OP
389GREL
489G_CL
389GITL
S189G_OP
489GREL
S189G_CL
489GITL
S289G_OP
S1S2OPTR
S289G_CL
S1S2CLTR
BBTR_OP
189OPTR
VP_BBTR
189CLTR
EXDU_12
289OPTR
EXDU_89G
289CLTR
152O_EX1
VPS1S2TR
152O_EX2
VP189TR
152O_EX3
VP289TR
189_EX1
189_EX2
289_EX1
289_EX2
ANSI05000348-2-en.vsd
ANSI05000348 V2 EN

Figure 361:

A1A2_BS (3) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

779

Section 14
Control
14.2.5.4

1MRK 502 066-UUS A

Logic diagram
152_OP
152_CL
189_OP
189_CL
289_OP
289_CL
389G_OP
389G_CL
489G_OP
489G_CL
S1189G_OP
S1189G_CL
S2289G_OP
S2289G_CL
VP189
189_OP
152O_EX1
VP289
289_OP
152O_EX2
VP_BBTR
BBTR_OP
EXDU_12
152O_EX3
VP189
VP289
VP152
VP389G
VP489G
VPS1189G
152_OP
389G_OP
489G_OP
S1189G_OP
EXDU_89G
189_EX1
VP389G
VPS1189G
389G_CL
S1189G_CL
EXDU_89G
189_EX2

A1A2_BS
XOR

VP152

XOR

VP189

XOR

VP289

XOR

VP389G

XOR

VP489G

XOR

VPS1189G

XOR

VPS2289G

AND

OR
NOT

152OPREL
152OPITL

AND

AND

AND
AND

NOT

OR
NOT

152CLREL
152CLITL
189REL
189ITL

AND

en04000542_ansi.vsd

ANSI04000542 V1 EN

780

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

VP152
VP389G
VP489G
VPS2289G
152_OP
389G_OP
489G_OP
S2289G_OP
EXDU_89G
289_EX1
VP489G
VPS2289G
489G_CL
S2289G_CL
EXDU_89G
289_EX2
VP189
VP289
189_OP
289_OP

AND

289REL
289ITL

OR
NOT

AND

AND

NOT
NOT

389GREL
389GITL
489GREL
489GITL

189_OP
189_CL
VP189

189OPTR
189CLTR
VP189TR

289_OP
289_CL
VP289

289OPTR
289CLTR
VP289TR

189_OP
289_OP
152_OP
VP189
VP289
VP152

OR

NOT

S1S2OPTR
S1S2CLTR
VPS1S2TR

AND

en04000543_ansi.vsd

ANSI04000543 V1 EN

14.2.5.5

Signals
Table 406:
Name

A1A2_BS (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

189_OP

BOOLEAN

189 is in open position

189_CL

BOOLEAN

189 is in closed position

289_OP

BOOLEAN

289 is in open position

289_CL

BOOLEAN

289 is in closed position

389G_OP

BOOLEAN

389G is in open position

389G_CL

BOOLEAN

389G is in closed position

489G_OP

BOOLEAN

489G is in open position

489G_CL

BOOLEAN

489G is in closed position

S189G_OP

BOOLEAN

S189G on bus section 1 is in open position

S189G_CL

BOOLEAN

S189G on bus section 1 is in closed position

S289G_OP

BOOLEAN

S289G on bus section 2 is in open position

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

781

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

S289G_CL

BOOLEAN

S289G on bus section 2 is in closed position

BBTR_OP

BOOLEAN

No busbar transfer is in progress

VP_BBTR

BOOLEAN

Status are valid for apparatuses involved in the busbar


transfer

EXDU_12

BOOLEAN

No transm error from any bay connected to busbar 1 and


2

EXDU_89G

BOOLEAN

No transm error from bays containing ground sw.


S189G or S289G

152O_EX1

BOOLEAN

External open condition for apparatus 152

152O_EX2

BOOLEAN

External open condition for apparatus 152

152O_EX3

BOOLEAN

External open condition for apparatus 152

189_EX1

BOOLEAN

External condition for apparatus 189

189_EX2

BOOLEAN

External condition for apparatus 189

289_EX1

BOOLEAN

External condition for apparatus 289

289_EX2

BOOLEAN

External condition for apparatus 289

Table 407:
Name

A1A2_BS (3) Output signals


Type

Description

152OPREL

BOOLEAN

Opening of 152 is allowed

152OPITL

BOOLEAN

Opening of 152 is not allowed

152CLREL

BOOLEAN

Closing of 152 is allowed

152CLITL

BOOLEAN

Closing of 152 is not allowed

189REL

BOOLEAN

Switching of 189 is allowed

189ITL

BOOLEAN

Switching of 189 is not allowed

289REL

BOOLEAN

Switching of 289 is allowed

289ITL

BOOLEAN

Switching of 289 is not allowed

389GREL

BOOLEAN

Switching of 389G is allowed

389GITL

BOOLEAN

Switching of 389G is not allowed

489GREL

BOOLEAN

Switching of 489G is allowed

489GITL

BOOLEAN

Switching of 489G is not allowed

S1S2OPTR

BOOLEAN

No bus section connection between bus section 1 and 2

S1S2CLTR

BOOLEAN

Bus coupler connection between bus section 1 and 2


exists

189OPTR

BOOLEAN

189 is in open position

189CLTR

BOOLEAN

189 is in closed position

289OPTR

BOOLEAN

289 is in open position

289CLTR

BOOLEAN

289 is in closed position

Table continues on next page

782

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Description

VPS1S2TR

BOOLEAN

Status of the apparatuses between bus section 1 and 2


are valid

VP189TR

BOOLEAN

Switch status of 189 is valid (open or closed)

VP289TR

BOOLEAN

Switch status of 289 is valid (open or closed)

14.2.6

Interlocking for bus-section disconnector A1A2_DC (3)

14.2.6.1

Identification
Function description

IEC 61850
identification

Interlocking for bus-section


disconnector

14.2.6.2

IEC 60617
identification

A1A2_DC

ANSI/IEEE C37.2
device number
3

Functionality
The interlocking for bus-section disconnector (A1A2_DC, 3) function is used for one bussection disconnector between section 1 and 2 according to figure 362. A1A2_DC (3)
function can be used for different busbars, which includes a bus-section disconnector.
WA1 (A1)

WA2 (A2)

52
289G

189G

A1A2_DC

en04000492_ansi.vsd

ANSI04000492 V1 EN

Figure 362:

Switchyard layout A1A2_DC (3)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

783

Section 14
Control
14.2.6.3

1MRK 502 066-UUS A

Function block
A1A2_DC (3)
089_OP
089OPREL
089_CL
089OPITL
S189G_OP
089CLREL
S189G_CL
089CLITL
S289G_OP
DCOPTR
S289G_CL
DCCLTR
S1DC_OP
VPDCTR
S2DC_OP
VPS1_DC
VPS2_DC
EXDU_89G
EXDU_BB
089C_EX1
089C_EX2
089O_EX1
089O_EX2
089O_EX3
ANSI05000349-2-en.vsd
ANSI05000349 V2 EN

Figure 363:

14.2.6.4

A1A2_DC (3) function block

Logic diagram
A1A2_DC
89_OP
89_CL
S1189G_OP
S1189G_CL
S2289G_OP
S2289G_CL
VPS1189G
VPS2289G
VPS1_DC
S1189G_OP
S2289G_OP
S1DC_OP
EXDU_89G

XOR

VPQB

VPDCTR
DCOPTR
DCCLTR
VPS1189G

XOR

VPS2289G

XOR

AND

OR
NOT

89OPREL
89OPITL

EXDU_BB
QBOP_EX1
VPS1189
VPS2289G
VPS2_DC
S1189G_OP
S2289G_OP
S2DC_OP
EXDU_89G

AND

EXDU_BB
QBOP_EX2
VPS1189G
VPS2289G
S1189G_CL
S2289G_CL
EXDU_89G
QBOP_EX3

AND

en04000544_ansi.vsd

ANSI04000544 V1 EN

784

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

IEC04000545 V1 EN

14.2.6.5

Signals
Table 408:
Name

A1A2_DC (3) Input signals


Type

Default

Description

089_OP

BOOLEAN

089 is in open position

089_CL

BOOLEAN

089 is in closed position

S189G_OP

BOOLEAN

S189G on bus section 1 is in open position

S189G_CL

BOOLEAN

S189G on bus section 1 is in closed position

S289G_OP

BOOLEAN

S289G on bus section 2 is in open position

S289G_CL

BOOLEAN

S289G on bus section 2 is in closed position

S1DC_OP

BOOLEAN

All disconnectors on bus section 1 are in open position

S2DC_OP

BOOLEAN

All disconnectors on bus section 2 are in open position

VPS1_DC

BOOLEAN

Switch status of disconnectors on bus section 1 are valid

VPS2_DC

BOOLEAN

Switch status of disconnectors on bus section 2 are valid

EXDU_89G

BOOLEAN

No transm error from bays containing ground sw.


S189G or S289G

EXDU_BB

BOOLEAN

No transm error from bays with disc conn to section 1


and 2

089C_EX1

BOOLEAN

External close condition for section disconnector 089

089C_EX2

BOOLEAN

External close condition for section disconnector 089

089O_EX1

BOOLEAN

External open condition for section disconnector 089

089O_EX2

BOOLEAN

External open condition for section disconnector 089

089O_EX3

BOOLEAN

External open condition for section disconnector 089

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

785

Section 14
Control

1MRK 502 066-UUS A

Table 409:

A1A2_DC (3) Output signals

Name

Type

Description

089OPREL

BOOLEAN

Opening of 089 is allowed

089OPITL

BOOLEAN

Opening of 089 is not allowed

089CLREL

BOOLEAN

Closing of 089 is allowed

089CLITL

BOOLEAN

Closing of 089 is not allowed

DCOPTR

BOOLEAN

The bus section disconnector is in open position

DCCLTR

BOOLEAN

The bus section disconnector is in closed position

VPDCTR

BOOLEAN

Switch status of 089 is valid (open or closed)

14.2.7

Interlocking for bus-coupler bay ABC_BC (3)

14.2.7.1

Identification
Function description

IEC 61850
identification

Interlocking for bus-coupler bay

14.2.7.2

ABC_BC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
3

Functionality
The interlocking for bus-coupler bay (ABC_BC, 3) function is used for a bus-coupler bay
connected to a double busbar arrangement according to figure 364. The function can also
be used for a single busbar arrangement with transfer busbar or double busbar
arrangement without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
189

289

189G

2089

789

152

289G

en04000514_ansi.vsd
ANSI04000514 V1 EN

Figure 364:
786

Switchyard layout ABC_BC (3)


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.7.3

Function block
ABC_BC (3)
152_OP
152OPREL
152_CL
152OPITL
189_OP
152CLREL
189_CL
152CLITL
289_OP
189REL
289_CL
189ITL
789_OP
289REL
789_CL
289ITL
2089_OP
789REL
2089_CL
789ITL
189G_OP
2089REL
189G_CL
2089ITL
289G_OP
189GREL
289G_CL
189GITL
1189G_OP
289GREL
1189G_CL
289GITL
2189G_OP
189OPTR
2189G_CL
189CLTR
7189G_OP
22089OTR
7189G_CL
22089CTR
BBTR_OP
789OPTR
BC_12_CL
789CLTR
VP_BBTR
1289OPTR
VP_BC_12
1289CLTR
EXDU_89G
BC12OPTR
EXDU_12
BC12CLTR
EXDU_BC
BC17OPTR
152O_EX1
BC17CLTR
152O_EX2
BC27OPTR
152O_EX3
BC27CLTR
189_EX1
VP189TR
189_EX2
V22089TR
189_EX3
VP789TR
289_EX1
VP1289TR
289_EX2
VPBC12TR
289_EX3
VPBC17TR
2089_EX1
VPBC27TR
2089_EX2
789_EX1
789_EX2
ANSI05000350-2-en.vsd
ANSI05000350 V2 EN

Figure 365:

ABC_BC (3) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

787

Section 14
Control
14.2.7.4

1MRK 502 066-UUS A

Logic diagram
152_OP
152_CL
189_OP
189_CL
2089_OP
2089_CL
789_OP
789_CL
289_OP
289_CL
189G_OP
189G_CL
289G_OP
289G_CL
1189G_OP
1189G_CL
2189G_OP
2189G_CL
7189G_OP
7189G_CL
VP189
189_OP
152O_EX1
VP2089
2089_OP
152O_EX2
VP_BBTR
BBTR_OP
EXDU_12

ABC_BC
VP152

XOR
XOR

VP189

XOR

VP2089

XOR

VP789

XOR

VP289

XOR

VP189G

XOR

VP289G

XOR

VP1189G

XOR

VP2189G

XOR

VP7189G

AND

152OPREL
152OPITL

OR

NOT

AND

AND

152O_EX3
VP189
VP289
VP789
VP2089

AND

NOT

152CLREL
152CLITL

en04000533_ansi.vsd

ANSI04000533 V1 EN

VP152
VP289
VP189G
VP289G
VP1189G
152_OP
289_OP
189G_OP
289G_OP
1189G_OP
EXDU_89G
189_EX1
VP289
VP_BC_12
289_CL
BC_12_CL
EXDU_BC
189_EX2
VP189G
VP1189G
189G_CL
1189G_CL
EXDU_89G
189_EX3

AND

OR
NOT

189REL
189ITL

AND

AND

en04000534_ansi.vsd

ANSI04000534 V1 EN

788

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

VP152
VP189
VP189G
VP289G
VP2189G
152_OP
189_OP
189G_OP
289G_OP
2189G_OP
EXDU_89G
289_EX1
VP189
VP_BC_12
189_CL
BC_12_CL
EXDU_BC
289_EX2
VP189G
VP2189G
189G_CL
2189G_CL
EXDU_89G
289_EX3

AND

OR
NOT

289REL
289ITL

AND

AND

en04000535_ansi.vsd

ANSI04000535 V1 EN

VP152
VP2089
VP189G
VP289G
VP7189G
152_OP
2089_OP
189G_OP
289G_OP
7189G_OP
EXDU_89G
789_EX1
VP289G
VP7189G
289G_CL
7189G_CL
EXDU_89G
789_EX2
VP152
VP789
VP189G
VP289G
VP2189G
152_OP
789_OP
189G_OP
289G_OP
2189G_OP
EXDU_89G
2089_EX1
VP289G
VP2189G
289G_CL
2189G_CL
EXDU_89G
2089_EX2

AND

789REL

OR
NOT

789ITL

AND

AND

2089REL

OR
NOT

2089ITL

AND

en04000536_ansi.vsd

ANSI04000536 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

789

Section 14
Control

1MRK 502 066-UUS A

VP189
VP2089
VP789
VP289
189_OP
2089_OP
789_OP
289_OP
189_OP
189_CL
VP189
2089_OP
289_OP
VP2089
VP289
789_OP
789_CL
VP789
189_OP
289_OP
VP189
VP289
152_OP
189_OP
2089_OP
VP152
VP189
VP2089
152_OP
189_OP
789_OP
VP152
VP189
VP789
152_OP
289_OP
789_OP
VP152
VP289
VP789

AND

NOT
NOT

AND

NOT

AND

OR

NOT

AND
OR

NOT

189GREL
189GITL
289GREL
289GITL

189OPTR
189CLTR
VP189TR
22089OTR
22089CTR
V22089TR
789OPTR
789CLTR
VP789TR
1289OPTR
1289CLTR
VP1289TR
BC12OPTR
BC12CLTR
VPBC12TR

AND

OR

NOT

BC17OPTR
BC17CLTR
VPBC17TR

AND

OR

NOT

BC27OPTR
BC27CLTR
VPBC27TR

AND

en04000537_ansi.vsd

ANSI04000537 V1 EN

14.2.7.5

Signals
Table 410:
Name

ABC_BC (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

189_OP

BOOLEAN

189 is in open position

189_CL

BOOLEAN

189 is in closed position

289_OP

BOOLEAN

289 is in open position

289_CL

BOOLEAN

289 is in closed position

789_OP

BOOLEAN

789 is in open position

789_CL

BOOLEAN

789 is in closed position

2089_OP

BOOLEAN

2089 is in open position

2089_CL

BOOLEAN

2089 is in closed position

189G_OP

BOOLEAN

189G is in open position

Table continues on next page

790

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

189G_CL

BOOLEAN

189G is in closed position

289G_OP

BOOLEAN

289G is in open position

289G_CL

BOOLEAN

289G is in closed position

1189G_OP

BOOLEAN

Grounding switch 1189G on busbar 1 is in open position

1189G_CL

BOOLEAN

Grounding switch 1189G on busbar 1 is in closed


position

2189G_OP

BOOLEAN

Grounding switch 2189G on busbar 2 is in open position

2189G_CL

BOOLEAN

Grounding switch 2189G on busbar 2 is in closed


position

7189G_OP

BOOLEAN

Grounding switch 7189G on busbar 7 is in open position

7189G_CL

BOOLEAN

Grounding switch 7189G on busbar 7 is in closed


position

BBTR_OP

BOOLEAN

No busbar transfer is in progress

BC_12_CL

BOOLEAN

A bus coupler connection exists between busbar Bus1


and Bus2

VP_BBTR

BOOLEAN

Status are valid for apparatuses involved in the busbar


transfer

VP_BC_12

BOOLEAN

Status of the bus coupler apparatuses between Bus1


and Bus2 are valid

EXDU_89G

BOOLEAN

No transm error from any bay containing grounding


switches

EXDU_12

BOOLEAN

No transm error from any bay connected to WA1/WA2


busbars

EXDU_BC

BOOLEAN

No transmission error from any other bus coupler bay

152O_EX1

BOOLEAN

External open condition for apparatus 152

152O_EX2

BOOLEAN

External open condition for apparatus 152

152O_EX3

BOOLEAN

External open condition for apparatus 152

189_EX1

BOOLEAN

External condition for apparatus 189

189_EX2

BOOLEAN

External condition for apparatus 189

189_EX3

BOOLEAN

External condition for apparatus 189

289_EX1

BOOLEAN

External condition for apparatus 289

289_EX2

BOOLEAN

External condition for apparatus 289

289_EX3

BOOLEAN

External condition for apparatus 289

2089_EX1

BOOLEAN

External condition for apparatus 2089

2089_EX2

BOOLEAN

External condition for apparatus 2089

789_EX1

BOOLEAN

External condition for apparatus 789

789_EX2

BOOLEAN

External condition for apparatus 789

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

791

Section 14
Control

1MRK 502 066-UUS A

Table 411:
Name

ABC_BC (3) Output signals


Type

Description

152OPREL

BOOLEAN

Opening of 152 is allowed

152OPITL

BOOLEAN

Opening of 152 is not allowed

152CLREL

BOOLEAN

Closing of 152 is allowed

152CLITL

BOOLEAN

Closing of 152 is not allowed

189REL

BOOLEAN

Switching of 189 is allowed

189ITL

BOOLEAN

Switching of 189 is not allowed

289REL

BOOLEAN

Switching of 289 is allowed

289ITL

BOOLEAN

Switching of 289 is not allowed

789REL

BOOLEAN

Switching of 789 is allowed

789ITL

BOOLEAN

Switching of 789 is not allowed

2089REL

BOOLEAN

Switching of 2089 is allowed

2089ITL

BOOLEAN

Switching of 2089 is not allowed

189GREL

BOOLEAN

Switching of 189G is allowed

189GITL

BOOLEAN

Switching of 189G is not allowed

289GREL

BOOLEAN

Switching of 289G is allowed

289GITL

BOOLEAN

Switching of 289G is not allowed

189OPTR

BOOLEAN

189 is in open position

189CLTR

BOOLEAN

189 is in closed position

22089OTR

BOOLEAN

289 and 2089 are in open position

22089CTR

BOOLEAN

289 or 2089 or both are not in open position

789OPTR

BOOLEAN

789 is in open position

789CLTR

BOOLEAN

789 is in closed position

1289OPTR

BOOLEAN

189 or 289 or both are in open position

1289CLTR

BOOLEAN

189 and 289 are not in open position

BC12OPTR

BOOLEAN

No connection via the own bus coupler between Bus1


and Bus2

BC12CLTR

BOOLEAN

Connection exists via the own bus coupler between


Bus1 and Bus2

BC17OPTR

BOOLEAN

No connection via the own bus coupler between Bus1


and Bus 7

BC17CLTR

BOOLEAN

Connection exists via the own bus coupler between


Bus1 and Bus7

BC27OPTR

BOOLEAN

No connection via the own bus coupler between Bus 2


and bus 7

BC27CLTR

BOOLEAN

Connection exists via the own bus coupler between


Bus2 and Bus7

VP189TR

BOOLEAN

Switch status of 189 is valid (open or closed)

Table continues on next page

792

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Description

V22089TR

BOOLEAN

Switch status of 289 and 2089 are valid (open or closed)

VP789TR

BOOLEAN

Switch status of 789 is valid (open or closed)

VP1289TR

BOOLEAN

Switch status of 189 and 289 are valid (open or closed)

VPBC12TR

BOOLEAN

Status of the bus coupler apparatuses between Bus1


and Bus2 are valid

VPBC17TR

BOOLEAN

Status of the bus coupler app. between WA1 and WA7


are valid

VPBC27TR

BOOLEAN

Status of the bus coupler app. between WA2 and WA7


are valid

14.2.8

Interlocking for breaker-and-a-half diameter BH (3)

14.2.8.1

Identification
Function description

14.2.8.2

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Interlocking for breaker-and-a-half


diameter

BH_CONN

Interlocking for breaker-and-a-half


diameter

BH_LINE_A

Interlocking for breaker-and-a-half


diameter

BH_LINE_B

Functionality
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half diameter
according to figure 366.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

793

Section 14
Control

1MRK 502 066-UUS A

WA1 (A)
WA2 (B)
189

289
189G

189G

152

152
289G

289G

689

689
389G

BH_LINE_A

389G

6189

152

BH_LINE_B

6289

989

989
189G

289G

989G

989G

BH_CONN
en04000513_ansi.vsd
ANSI04000513 V1 EN

Figure 366:

Switchyard layout breaker-and-a-half

Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and
BH_LINE_B (3) are the connections from a line to a busbar. BH_CONN (3) is the
connection between the two lines of the diameter in the breaker-and-a-half switchyard
layout.

794

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.8.3

Function blocks
BH_LINE_A (3)
152_OP
152CLREL
152_CL
152CLITL
689_OP
689REL
689_CL
689ITL
189_OP
189REL
189_CL
189ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
389G_OP
389GREL
389G_CL
389GITL
989_OP
989REL
989_CL
989ITL
989G_OP
989GREL
989G_CL
989GITL
C152_OP
189OPTR
C152_CL
189CLTR
C6189_OP
VP189TR
C6189_CL
C189G_OP
C189G_CL
C289G_OP
C289G_CL
1189G_OP
1189G_CL
VOLT_OFF
VOLT_ON
EXDU_89G
689_EX1
689_EX2
189_EX1
189_EX2
989_EX1
989_EX2
989_EX3
989_EX4
989_EX5
989_EX6
989_EX7
ANSI05000352-2-en.vsd
ANSI05000352 V2 EN

Figure 367:

BH_LINE_A (3) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

795

Section 14
Control

1MRK 502 066-UUS A

BH_LINE_B (3)
152_OP
152CLREL
152_CL
152CLITL
689_OP
689REL
689_CL
689ITL
289_OP
289REL
289_CL
289ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
389G_OP
389GREL
389G_CL
389GITL
989_OP
989REL
989_CL
989ITL
989G_OP
989GREL
989G_CL
989GITL
C152_OP
289OPTR
C152_CL
289CLTR
C6289_OP
VP289TR
C6289_CL
C189G_OP
C189G_CL
C289G_OP
C289G_CL
2189G_OP
2189G_CL
VOLT_OFF
VOLT_ON
EXDU_89G
689_EX1
689_EX2
289_EX1
289_EX2
989_EX1
989_EX2
989_EX3
989_EX4
989_EX5
989_EX6
989_EX7
ANSI05000353-2-en.vsd
ANSI05000353 V2 EN

Figure 368:

BH_LINE_B (3) function block

BH_CONN (3)
152_OP
152CLREL
152_CL
152CLITL
6189_OP
6189REL
6189_CL
6189ITL
6289_OP
6289REL
6289_CL
6289ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
1389G_OP
1389G_CL
2389G_OP
2389G_CL
6189_EX1
6189_EX2
6289_EX1
6289_EX2
ANSI05000351-2-en.vsd
ANSI05000351 V2 EN

Figure 369:
796

BH_CONN (3) function block


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.8.4

Logic diagrams
152_OP
152_CL
6189_OP
6189_CL
6289_OP
6289_CL
189G_OP
189G_CL
289G_OP
289G_CL
1389G_OP
1389G_CL
2389G_OP
2389G_CL
VP6189
VP6289
VP152
VP189G
VP289G
VP1389G
152_OP
189G_OP
289G_OP
1389G_OP
6189_EX1
VP189G
VP1389G
189G_CL
1389G_CL
6189_EX2
VP152
VP189G
VP289G
VP2389G
152_OP
189G_OP
289G_OP
2389G_OP
6289_EX1
VP289G
VP2389G
289G_CL
2389G_CL
6289_EX2
VP6189
VP6289
6189_OP
6289_OP

BH_CONN
XOR

VP152

XOR

VP6189

XOR

VP6289

XOR

VP189G

XOR

VP289G

XOR

VP1389G
VP2389G
152CLREL
152CLITL
NOT

XOR
AND
AND

OR
NOT

6189REL
61891ITL

AND

AND

OR
NOT

6289REL
6289ITL

AND

AND

NOT
NOT

189GREL
189GITL
289GREL
289GITL
en04000560_ansi.vsd

ANSI04000560 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

797

Section 14
Control

1MRK 502 066-UUS A

152_OP
152_CL
189_OP
189_CL
689_OP
689_CL
989G_OP
989G_CL
989_OP
989_CL
189G_OP
189G_CL
289G_OP
289G_CL
389G_OP
389G_CL
C152_OP
C152_CL
C189G_OP
C189G_CL
C289G_OP
C289G_CL
C6189_OP
C6189_CL
1189G_OP
1189G_CL
VOLT_OFF
VOLT_ON
VP189
VP689
VP989
VP152
VP189G
VP289G
VP389G
152_OP
189G_OP
289G_OP
389G_OP
689_EX1
VP289G
VP389G
289G_CL
389G_CL
689_EX2

BH_LINE_A
XOR

VP152

XOR

VP189

XOR

VP689

XOR

VP989G

XOR

VP989

XOR

VP189G

XOR

VP289G

XOR

VP389G

XOR

VPC152

XOR

VPC189G

XOR

VPC289G

XOR

VPC6189

XOR

VP1189G

XOR
AND

AND

NOT

OR
NOT

VPVOLT
152CLREL
152CLITL

689REL
689ITL

AND

en04000554_ansi.vsd

ANSI04000554 V1 EN

798

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

VP152
VP189G
VP289G
VP1189G
152_OP
189G_OP
289G_OP
1189G_OP
EXDU_89G
189_EX1
VP189G
VP1189G
189G_CL
1189G_CL
EXDU_89G
189_EX2
VP189
VP689
189_OP
689_OP
VP689
VP989
VPC6189
689_OP
989_OP
C6189_OP
VP152
VP689
VP989G
VP189G
VP289G
VP389G
VPC152
VPC6189
VPC189G
VPC289G
989_EX1
689_OP
989_EX2
152_OP
189G_OP
289G_OP
989_EX3

AND

189REL
189ITL

OR
NOT

AND

AND

189GREL
189GITL
289GREL
289GITL

NOT
NOT

389GREL
389GITL

AND
NOT

AND

OR

NOT

989REL
989ITL

OR
AND

en04000555_ansi.vsd

ANSI04000555 V1 EN

C6189_OP
989_EX4
C152_OP
C189G_OP
C289G_OP
989_EX5
989G_OP
389G_OP
989_EX6
VP989G
VP389G
989G_CL
389G_CL
989_EX7
VP989
VPVOLT
989_OP
VOLT_OFF
189_OP
189_CL
VP189

OR

AND

OR

AND

AND

AND

NOT

989GREL
989GITL
189OPTR
189CLTR
VP189TR
en04000556_ansi.vsd

ANSI04000556 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

799

Section 14
Control

1MRK 502 066-UUS A

152_OP
152_CL
289_OP
289_CL
689_OP
689_CL
989G_OP
989G_CL
989_OP
989_CL
189G_OP
189G_CL
289G_OP
289G_CL
389G_OP
389G_CL
C152_OP
C152_CL
C189G_OP
C189G_CL
C289G_OP
C289G_CL
C6289_OP
C6289_CL
2189G_OP
2189G_CL
VOLT_OFF
VOLT_ON
VP289
VP689
VP989
VP152
VP189G
VP289G
VP389G
152_OP
189G_OP
289G_OP
389G_OP
689_EX1
VP289G
VP389G
289G_CL
389G_CL
689_EX2

BH_LINE_B
XOR

VP152

XOR

VP289

XOR

VP689

XOR

VP989G

XOR

VP989

XOR

VP189G

XOR

VP289G

XOR

VP389G

XOR

VPC152

XOR

VPC189G

XOR

VPC289G

XOR

VPC6289

XOR

VP2189G

XOR

VPVOLT
152CLREL
152CLITL

AND

AND

NOT

OR
NOT

689REL
689ITL

AND

en04000557_ansi.vsd

ANSI04000557 V1 EN

800

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

VP152
VP189G
VP289G
VP2189G
152_OP
189G_OP
289G_OP
2189G_OP
EXDU_89G
289_EX1
VP189G
VP2189G
189G_CL
2189G_CL
EXDU_89G
289_EX2
VP289
VP689
289_OP
689_OP
VP689
VP989
VPC6289
689_OP
989_OP
C6289_OP
VP152
VP689
VP989G
VP189G
VP289G
VP389G
VPC152
VPC6289
VPC189G
VPC289G
989_EX1
689_OP
989_EX2
152_OP
189G_OP
289G_OP
989_EX3

289REL

OR

AND

289ITL

NOT

AND

AND

189GREL
189GITL
289GREL
289GITL

NOT
NOT

389GREL
389GITL

AND
NOT

989REL
AND

OR

NOT

989ITL

OR
AND

en04000558_ansi.vsd

ANSI04000558 V1 EN

C6289_OP
989_EX4
C152_OP
C189G_OP
C289G_OP
989_EX5
989G_OP
389G_OP
989_EX6
VP989G
VP389G
989G_CL
389G_CL
989_EX7
VP989
VPVOLT
989_OP
VOLT_OFF
289_OP
289_CL
VP289

OR

AND

OR

AND

AND

AND

NOT

989GREL
989GITL
289OPTR
289CLTR
VP289TR
en04000559_ansi.vsd

ANSI04000559 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

801

Section 14
Control
14.2.8.5

1MRK 502 066-UUS A

Signals
Table 412:
Name

BH_LINE_A (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

689_OP

BOOLEAN

689 is in open position

689_CL

BOOLEAN

689 is in closed position

189_OP

BOOLEAN

189 is in open position

189_CL

BOOLEAN

189 is in closed position

189G_OP

BOOLEAN

189G is in open position

189G_CL

BOOLEAN

189G is in closed position

289G_OP

BOOLEAN

289G is in open position

289G_CL

BOOLEAN

289G is in closed position

389G_OP

BOOLEAN

389G is in open position

389G_CL

BOOLEAN

389G is in closed position

989_OP

BOOLEAN

989 is in open position

989_CL

BOOLEAN

989 is in closed position

989G_OP

BOOLEAN

989G is in open position

989G_CL

BOOLEAN

989G is in closed position

C152_OP

BOOLEAN

152 in module BH_CONN is in open position

C152_CL

BOOLEAN

152 in module BH_CONN is in closed position

C6189_OP

BOOLEAN

6189 in module BH_CONN is in open position

C6189_CL

BOOLEAN

6189 in module BH_CONN is in closed position

C189G_OP

BOOLEAN

189G in module BH_CONN is in open position

C189G_CL

BOOLEAN

189G in module BH_CONN is in closed position

C289G_OP

BOOLEAN

289G in module BH_CONN is in open position

C289G_CL

BOOLEAN

289G in module BH_CONN is in closed position

1189G_OP

BOOLEAN

Grounding switch 1189G on busbar 1 is in open position

1189G_CL

BOOLEAN

Grounding switch 1189G on busbar 1 is in closed


position

VOLT_OFF

BOOLEAN

There is no voltage on line and not VT (fuse) failure

VOLT_ON

BOOLEAN

There is voltage on the line or there is a VT (fuse) failure

EXDU_89G

BOOLEAN

No transm error from bay containing grounding switch


1189G

689_EX1

BOOLEAN

External condition for disconnector 689

689_EX2

BOOLEAN

External condition for disconnector 689

189_EX1

BOOLEAN

External condition for apparatus 189

Table continues on next page

802

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

189_EX2

BOOLEAN

External condition for apparatus 189

989_EX1

BOOLEAN

External condition for apparatus 989

989_EX2

BOOLEAN

External condition for apparatus 989

989_EX3

BOOLEAN

External condition for apparatus 989

989_EX4

BOOLEAN

External condition for apparatus 989

989_EX5

BOOLEAN

External condition for apparatus 989

989_EX6

BOOLEAN

External condition for apparatus 989

989_EX7

BOOLEAN

External condition for apparatus 989

Table 413:
Name

BH_LINE_A (3) Output signals


Type

Description

152CLREL

BOOLEAN

Closing of 152 is allowed

152CLITL

BOOLEAN

Closing of 152 is not allowed

689REL

BOOLEAN

Switching of 689 is allowed

689ITL

BOOLEAN

Switching of 689 is not allowed

189REL

BOOLEAN

Switching of 189 is allowed

189ITL

BOOLEAN

Switching of 189 is not allowed

189GREL

BOOLEAN

Switching of 189G is allowed

189GITL

BOOLEAN

Switching of 189G is not allowed

289GREL

BOOLEAN

Switching of 289G is allowed

289GITL

BOOLEAN

Switching of 289G is not allowed

389GREL

BOOLEAN

Switching of 389G is allowed

389GITL

BOOLEAN

Switching of 389G is not allowed

989REL

BOOLEAN

Switching of 989 is allowed

989ITL

BOOLEAN

Switching of 989 is not allowed

989GREL

BOOLEAN

Switching of 989G is allowed

989GITL

BOOLEAN

Switching of 989G is not allowed

189OPTR

BOOLEAN

189 is in open position

189CLTR

BOOLEAN

189 is in closed position

VP189TR

BOOLEAN

Switch status of 189 is valid (open or closed)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

803

Section 14
Control

1MRK 502 066-UUS A

Table 414:
Name

BH_LINE_B (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

689_OP

BOOLEAN

689 is in open position

689_CL

BOOLEAN

689 is in closed position

289_OP

BOOLEAN

289 is in open position

289_CL

BOOLEAN

289 is in closed position

189G_OP

BOOLEAN

189G is in open position

189G_CL

BOOLEAN

189G is in closed position

289G_OP

BOOLEAN

289G is in open position

289G_CL

BOOLEAN

289G is in closed position

389G_OP

BOOLEAN

389G is in open position

389G_CL

BOOLEAN

389G is in closed position

989_OP

BOOLEAN

989 is in open position

989_CL

BOOLEAN

989 is in closed position

989G_OP

BOOLEAN

989G is in open position

989G_CL

BOOLEAN

989G is in closed position

C152_OP

BOOLEAN

152 in module BH_CONN is in open position

C152_CL

BOOLEAN

152 in module BH_CONN is in closed position

C6289_OP

BOOLEAN

6289 in module BH_CONN is in open position

C6289_CL

BOOLEAN

6289 in module BH_CONN is in closed position

C189G_OP

BOOLEAN

189G in module BH_CONN is in open position

C189G_CL

BOOLEAN

189G in module BH_CONN is in closed position

C289G_OP

BOOLEAN

289G in module BH_CONN is in open position

C289G_CL

BOOLEAN

289G in module BH_CONN is in closed position

2189G_OP

BOOLEAN

Grounding switch 2189G on busbar 2 is in open position

2189G_CL

BOOLEAN

Grounding switch 2189G on busbar 2 is in closed


position

VOLT_OFF

BOOLEAN

There is no voltage on line and not VT (fuse) failure

VOLT_ON

BOOLEAN

There is voltage on the line or there is a VT (fuse) failure

EXDU_89G

BOOLEAN

No transm error from bay containing grounding switch


2189G

689_EX1

BOOLEAN

External condition for disconnector 689

689_EX2

BOOLEAN

External condition for disconnector 689

289_EX1

BOOLEAN

External condition for apparatus 289

289_EX2

BOOLEAN

External condition for apparatus 289

989_EX1

BOOLEAN

External condition for apparatus 989

Table continues on next page


804

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

989_EX2

BOOLEAN

External condition for apparatus 989

989_EX3

BOOLEAN

External condition for apparatus 989

989_EX4

BOOLEAN

External condition for apparatus 989

989_EX5

BOOLEAN

External condition for apparatus 989

989_EX6

BOOLEAN

External condition for apparatus 989

989_EX7

BOOLEAN

External condition for apparatus 989

Table 415:
Name

BH_LINE_B (3) Output signals


Type

Description

152CLREL

BOOLEAN

Closing of 152 is allowed

152CLITL

BOOLEAN

Closing of 152 is not allowed

689REL

BOOLEAN

Switching of 689 is allowed

689ITL

BOOLEAN

Switching of 689 is not allowed

289REL

BOOLEAN

Switching of 289 is allowed

289ITL

BOOLEAN

Switching of 289 is not allowed

189GREL

BOOLEAN

Switching of 189G is allowed

189GITL

BOOLEAN

Switching of 189G is not allowed

289GREL

BOOLEAN

Switching of 289G is allowed

289GITL

BOOLEAN

Switching of 289G is not allowed

389GREL

BOOLEAN

Switching of 389G is allowed

389GITL

BOOLEAN

Switching of 389G is not allowed

989REL

BOOLEAN

Switching of 989 is allowed

989ITL

BOOLEAN

Switching of 989 is not allowed

989GREL

BOOLEAN

Switching of 989G is allowed

989GITL

BOOLEAN

Switching of 989G is not allowed

289OPTR

BOOLEAN

289 is in open position

289CLTR

BOOLEAN

289 is in closed position

VP289TR

BOOLEAN

Switch status of 289 is valid (open or closed)

Table 416:
Name

BH_CONN (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

6189_OP

BOOLEAN

6189 is in open position

6189_CL

BOOLEAN

6189 is in closed position

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

805

Section 14
Control

1MRK 502 066-UUS A

Name

Description

6289 is in open position

6289_CL

BOOLEAN

6289 is in closed position

189G_OP

BOOLEAN

189G is in open position

189G_CL

BOOLEAN

189G is in closed position

289G_OP

BOOLEAN

289G is in open position

289G_CL

BOOLEAN

289G is in closed position

1389G_OP

BOOLEAN

1389G on line 1 is in open position

1389G_CL

BOOLEAN

1389G on line 1 is in closed position

2389G_OP

BOOLEAN

2389G on line 2 is in open position

2389G_CL

BOOLEAN

2389G on line 2 is in closed position

6189_EX1

BOOLEAN

External condition for apparatus 6189

6189_EX2

BOOLEAN

External condition for apparatus 6189

6289_EX1

BOOLEAN

External condition for apparatus 6289

6289_EX2

BOOLEAN

External condition for apparatus 6289

Name

806

Default

BOOLEAN

Table 417:

14.2.9

Type

6289_OP

BH_CONN (3) Output signals


Type

Description

152CLREL

BOOLEAN

Closing of 152 is allowed

152CLITL

BOOLEAN

Closing of 152 is not allowed

6189REL

BOOLEAN

Switching of 6189 is allowed

6189ITL

BOOLEAN

Switching of 6189 is not allowed

6289REL

BOOLEAN

Switching of 6289 is allowed

6289ITL

BOOLEAN

Switching of 6289 is not allowed

189GREL

BOOLEAN

Switching of 189G is allowed

189GITL

BOOLEAN

Switching of 189G is not allowed

289GREL

BOOLEAN

Switching of 289G is allowed

289GITL

BOOLEAN

Switching of 289G is not allowed

Interlocking for double CB bay DB (3)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.9.1

Identification
Function description

14.2.9.2

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Interlocking for double CB bay

DB_BUS_A

Interlocking for double CB bay

DB_BUS_B

Interlocking for double CB bay

DB_LINE

Functionality
The interlocking for a double busbar double circuit breaker bay including DB_BUS_A
(3), DB_BUS_B (3) and DB_LINE (3) functions are used for a line connected to a double
busbar arrangement according to figure 370.
WA1 (A)
WA2 (B)
189

DB_BUS_A

289

189G

489G

DB_BUS_B

252

152

589G

289G

6189

6289
389G

DB_LINE

989
989G

en04000518_ansi.vsd
ANSI04000518 V1 EN

Figure 370:

Switchyard layout double circuit breaker

Three types of interlocking modules per double circuit breaker bay are defined.
DB_BUS_A (3) handles the circuit breaker QA1 that is connected to busbar WA1 and the
disconnectors and grounding switches of this section. DB_BUS_B (3) handles the circuit
breaker QA2 that is connected to busbar WA2 and the disconnectors and grounding
switches of this section.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

807

Section 14
Control
14.2.9.3

1MRK 502 066-UUS A

Logic diagrams
152_OP
152_CL
6189_OP
6189_CL
189_OP
189_CL
189G_OP
189G_CL
289G_OP
289G_CL
389G_OP
389G_CL
1189G_OP
1189G_CL
VP6189
VP189
VP152
VP189G
VP289G
VP389G
152_OP
189G_OP
289G_OP
389G_OP
6189_EX1
VP289G
VP389G
289G_CL
389G_CL
6189_EX2
VP152
VP189G
VP289G
VP1189G
152_OP
189G_OP
289G_OP
1189G_OP
EXDU_89G
189_EX1
VP189G
VP1189G
189G_CL
1189G_CL
EXDU_89G
189_EX2

DB_BUS_A
VP152

XOR
XOR

VP6189

XOR

VP189

XOR

VP189G

XOR

VP289G

XOR

VP389G

XOR
NOT

VP1189G
152CLREL
152CLITL

NOT

6189REL
6189ITL

AND
AND

OR

AND

AND

OR
NOT

189REL
189ITL

AND

en04000547_ansi.vsd

ANSI04000547 V1 EN

VP6189
VP189
6189_OP
189_OP
189_OP
189_CL
VP189

AND

NOT
NOT

189GREL
189GITL
289GREL
289GITL
189OPTR
189CLTR
VP189TR
en04000548_ansi.vsd

ANSI04000548 V1 EN

808

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

252_OP
252_CL
6289_OP
6289_CL
289_OP
289_CL
489G_OP
489G_CL
589G_OP
589G_CL
389G_OP
389G_CL
2189G_OP
2189G_CL
VP6289
VP289
VP252
VP489G
VP589G
VP389G
252_OP
489G_OP
589G_OP
389G_OP
6289_EX1
VP589G
VP389G
589G_CL
389G_CL
6289_EX2
VP252
VP489G
VP589G
VP2189G
252_OP
489G_OP
589G_OP
2189G_OP
EXDU_89G
289_EX1
VP489G
VP2189G
489G_CL
2189G_CL
EXDU_89G
289_EX2

DB_BUS_B
XOR

VP252

XOR

VP6289

XOR

VP289

XOR

VP489G

XOR

VP589G
VP389G

XOR
XOR
AND
AND

NOT

OR
NOT

VP2189G
252CLREL
252CLITL
6289REL
6289ITL

AND

AND

OR
NOT

289REL
289ITL

AND

en04000552_ansi.vsd

ANSI04000552 V1 EN

VP6289
VP289
6289_OP
289_OP
289_OP
289_CL
VP289

AND

NOT
NOT

489GREL
489GITL
589GREL
589GITL
289OPTR
289CLTR
VP289TR
en04000553_ansi.vsd

ANSI04000553 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

809

Section 14
Control

1MRK 502 066-UUS A

152_OP
152_CL
252_OP
252_CL
6189_OP
6189_CL
189G_OP
189G_CL
289G_OP
289G_CL
6289_OP
6289_CL
489G_OP
489G_CL
589G_OP
589G_CL
989_OP
989_CL
389G_OP
389G_CL
989G_OP
989G_CL
VOLT_OFF
VOLT_ON
VP152
VP252
VP189G
VP289G
VP389G
VP489G
VP589G
VP989G
152_OP
252_OP
189G_OP
289G_OP
389G_OP
489G_OP
589G_OP
989G_OP
989_EX1

DB_LINE
VP152

XOR
XOR

VP252

XOR

VP6189

XOR

VP189G

XOR

VP289G

XOR

VP6289

XOR

VP489G

XOR

VP589G

XOR

VP989

XOR

VP389G

XOR

VP989G
VPVOLT

XOR
AND

OR
NOT

989REL
989ITL

AND
en04000549_ansi.vsd

ANSI04000549 V1 EN

810

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

VP152
VP189G
VP289G
VP389G
VP989G
VP6289
152_OP
189G_OP
289G_OP
389G_OP
989G_OP
6289_OP
989_EX2
VP252
VP6189
VP389G
VP489G
VP589G
VP989G
252_OP
6189_OP
389G_OP
489G_OP
589G_OP
989G_OP
989_EX3
VP389G
VP989G
VP6189
VP6289
389G_OP
989G_OP
6189_OP
6289_OP
989_EX4
VP389G
VP989G
389G_CL
989G_CL
989_EX5

AND

OR

AND

AND

AND

en04000550_ansi.vsd

ANSI04000550 V1 EN

VP6189
VP6289
VP989
6189_OP
6289_OP
989_OP
VP989
VPVOLT
989_OP
VOLT_OFF

NOT

389GREL
389GITL

NOT

989GREL
989GITL

AND

AND

en04000551_ansi.vsd

ANSI04000551 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

811

Section 14
Control
14.2.9.4

1MRK 502 066-UUS A

Function block
DB_BUS_A (3)
152_OP
152CLREL
152_CL
152CLITL
189_OP
6189REL
189_CL
6189ITL
6189_OP
189REL
6189_CL
189ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
389G_OP
189OPTR
389G_CL
189CLTR
1189G_OP
VP189TR
1189G_CL
EXDU_89G
6189_EX1
6189_EX2
189_EX1
189_EX2
ANSI05000354-2-en.vsd
ANSI05000354 V2 EN

Figure 371:

DB_BUS_A (3) function block

DB_LINE (3)
152_OP
152_CL
252_OP
252_CL
6189_OP
6189_CL
189G_OP
189G_CL
289G_OP
289G_CL
6289_OP
6289_CL
489G_OP
489G_CL
589G_OP
589G_CL
989_OP
989_CL
389G_OP
389G_CL
989G_OP
989G_CL
VOLT_OFF
VOLT_ON
989_EX1
989_EX2
989_EX3
989_EX4
989_EX5

989REL
989ITL
389GREL
389GITL
989GREL
989GITL

ANSI05000356-2-en.vsd
ANSI05000356 V2 EN

Figure 372:

812

DB_LINE (3) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

DB_BUS_B (3)
252_OP
252CLREL
252_CL
252CLITL
289_OP
6289REL
289_CL
6289ITL
6289_OP
289REL
6289_CL
289ITL
489G_OP
489GREL
489G_CL
489GITL
589G_OP
589GREL
589G_CL
589GITL
389G_OP
289OPTR
389G_CL
289CLTR
2189G_OP
VP289TR
2189G_CL
EXDU_89G
6289_EX1
6289_EX2
289_EX1
289_EX2
ANSI05000355-2-en.vsd
ANSI05000355 V2 EN

Figure 373:

14.2.9.5

DB_BUS_B (3) function block

Signals
Table 418:
Name

DB_BUS_A (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

189_OP

BOOLEAN

189 is in open position

189_CL

BOOLEAN

189 is in closed position

6189_OP

BOOLEAN

6189 is in open position

6189_CL

BOOLEAN

6189 is in closed position

189G_OP

BOOLEAN

189G is in open position

189G_CL

BOOLEAN

189G is in closed position

289G_OP

BOOLEAN

289G is in open position

289G_CL

BOOLEAN

289G is in closed position

389G_OP

BOOLEAN

389G is in open position

389G_CL

BOOLEAN

389G is in closed position

1189G_OP

BOOLEAN

Grounding switch 1189G on busbar 1 is in open position

1189G_CL

BOOLEAN

Grounding switch 1189G on busbar 1 is in closed


position

EXDU_89G

BOOLEAN

No transm error from bay containing grounding switch


1189G

6189_EX1

BOOLEAN

External condition for apparatus 6189

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

813

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

6189_EX2

BOOLEAN

External condition for apparatus 6189

189_EX1

BOOLEAN

External condition for apparatus 189

189_EX2

BOOLEAN

External condition for apparatus 189

Table 419:
Name

DB_BUS_A (3) Output signals


Type

Description

152CLREL

BOOLEAN

Closing of 152 is allowed

152CLITL

BOOLEAN

Closing of 152 is not allowed

6189REL

BOOLEAN

Switching of 6189 is allowed

6189ITL

BOOLEAN

Switching of 6189 is not allowed

189REL

BOOLEAN

Switching of 189 is allowed

189ITL

BOOLEAN

Switching of 189 is not allowed

189GREL

BOOLEAN

Switching of 189G is allowed

189GITL

BOOLEAN

Switching of 189G is not allowed

289GREL

BOOLEAN

Switching of 289G is allowed

289GITL

BOOLEAN

Switching of 289G is not allowed

189OPTR

BOOLEAN

189 is in open position

189CLTR

BOOLEAN

189 is in closed position

VP189TR

BOOLEAN

Switch status of 189 is valid (open or closed)

Table 420:
Name

DB_BUS_B (3) Input signals


Type

Default

Description

252_OP

BOOLEAN

252 is in open position

252_CL

BOOLEAN

252 is in closed position

289_OP

BOOLEAN

289 is in open position

289_CL

BOOLEAN

289 is in closed position

6289_OP

BOOLEAN

6289 is in open position

6289_CL

BOOLEAN

6289 is in closed position

489G_OP

BOOLEAN

489G is in open position

489G_CL

BOOLEAN

489G is in closed position

589G_OP

BOOLEAN

589G is in open position

589G_CL

BOOLEAN

589G is in closed position

389G_OP

BOOLEAN

389G is in open position

389G_CL

BOOLEAN

389G is in closed position

2189G_OP

BOOLEAN

Grounding switch 2189G on busbar 2 is in open position

Table continues on next page


814

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

2189G_CL

BOOLEAN

Grounding switch 2189G on busbar 2 is in closed


position

EXDU_89G

BOOLEAN

No transm error from bay containing grounding switch


2189G

6289_EX1

BOOLEAN

External condition for apparatus 6289

6289_EX2

BOOLEAN

External condition for apparatus 6289

289_EX1

BOOLEAN

External condition for apparatus 289

289_EX2

BOOLEAN

External condition for apparatus 289

Table 421:
Name

DB_BUS_B (3) Output signals


Type

Description

252CLREL

BOOLEAN

Closing of 252 is allowed

252CLITL

BOOLEAN

Closing of 252 is not allowed

6289REL

BOOLEAN

Switching of 6289 is allowed

6289ITL

BOOLEAN

Switching of 6289 is not allowed

289REL

BOOLEAN

Switching of 289 is allowed

289ITL

BOOLEAN

Switching of 289 is not allowed

489GREL

BOOLEAN

Switching of 489G is allowed

489GITL

BOOLEAN

Switching of 489G is not allowed

589GREL

BOOLEAN

Switching of 589G is allowed

589GITL

BOOLEAN

Switching of 589G is not allowed

289OPTR

BOOLEAN

289 is in open position

289CLTR

BOOLEAN

289 is in closed position

VP289TR

BOOLEAN

Switch status of 289 is valid (open or closed)

Table 422:
Name

DB_LINE (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

252_OP

BOOLEAN

252 is in open position

252_CL

BOOLEAN

252 is in closed position

6189_OP

BOOLEAN

6189 is in open position

6189_CL

BOOLEAN

6189 is in closed position

189G_OP

BOOLEAN

189G is in open position

189G_CL

BOOLEAN

189G is in closed position

289G_OP

BOOLEAN

289G is in open position

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

815

Section 14
Control

1MRK 502 066-UUS A

Name

Description

289G is in closed position

6289_OP

BOOLEAN

6289 is in open position

6289_CL

BOOLEAN

6289 is in closed position

489G_OP

BOOLEAN

489G is in open position

489G_CL

BOOLEAN

489G is in closed position

589G_OP

BOOLEAN

589G is in open position

589G_CL

BOOLEAN

589G is in closed position

989_OP

BOOLEAN

989 is in open position

989_CL

BOOLEAN

989 is in closed position

389G_OP

BOOLEAN

389G is in open position

389G_CL

BOOLEAN

389G is in closed position

989G_OP

BOOLEAN

989G is in open position

989G_CL

BOOLEAN

989G is in closed position

VOLT_OFF

BOOLEAN

There is no voltage on the line and not VT (fuse) failure

VOLT_ON

BOOLEAN

There is voltage on the line or there is a VT (fuse) failure

989_EX1

BOOLEAN

External condition for apparatus 989

989_EX2

BOOLEAN

External condition for apparatus 989

989_EX3

BOOLEAN

External condition for apparatus 989

989_EX4

BOOLEAN

External condition for apparatus 989

989_EX5

BOOLEAN

External condition for apparatus 989

Name

816

Default

BOOLEAN

Table 423:

14.2.10

Type

289G_CL

DB_LINE (3) Output signals


Type

Description

989REL

BOOLEAN

Switching of 989 is allowed

989ITL

BOOLEAN

Switching of 989 is not allowed

389GREL

BOOLEAN

Switching of 389G is allowed

389GITL

BOOLEAN

Switching of 389G is not allowed

989GREL

BOOLEAN

Switching of 989G is allowed

989GITL

BOOLEAN

Switching of 989G is not allowed

Interlocking for line bay ABC_LINE (3)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.10.1

Identification
Function description

IEC 61850
identification

Interlocking for line bay

14.2.10.2

ABC_LINE

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
3

Functionality
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure 374. The function
can also be used for a double busbar arrangement without transfer busbar or a single
busbar arrangement with/without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
189

289

189G

789

152
289G
989

989G

en04000478_ansi.vsd
ANSI04000478 V1 EN

Figure 374:

Switchyard layout ABC_LINE (3)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

817

Section 14
Control
14.2.10.3

1MRK 502 066-UUS A

Function block
ABC_LINE (3)
152_OP
152CLREL
152_CL
152CLITL
989_OP
989REL
989_CL
989ITL
189_OP
189REL
189_CL
189ITL
289_OP
289REL
289_CL
289ITL
789_OP
789REL
789_CL
789ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
989G_OP
989GREL
989G_CL
989GITL
1189G_OP
189OPTR
1189G_CL
189CLTR
2189G_OP
289OPTR
2189G_CL
289CLTR
7189G_OP
789OPTR
7189G_CL
789CLTR
BB7_D_OP
1289OPTR
BC_12_CL
1289CLTR
BC_17_OP
VP189TR
BC_17_CL
VP289TR
BC_27_OP
VP789TR
BC_27_CL
VP1289TR
VOLT_OFF
VOLT_ON
VP_BB7_D
VP_BC_12
VP_BC_17
VP_BC_27
EXDU_89G
EXDU_BPB
EXDU_BC
989_EX1
989_EX2
189_EX1
189_EX2
189_EX3
289_EX1
289_EX2
289_EX3
789_EX1
789_EX2
789_EX3
789_EX4
ANSI05000357-2-en.vsd
ANSI05000357 V2 EN

Figure 375:

818

ABC_LINE (3) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.10.4

Logic diagram
152_OP
152_CL
989_OP
989_CL
189_OP
189_CL
289_OP
289_CL
789_OP
789_CL
189G_OP
189G_CL
289G_OP
289G_CL
989G_OP
989G_CL
1189G_OP
1189G_CL
2189G_OP
2189G_CL
7189G_OP
7189G_CL
VOLT_OFF
VOLT_ON
VP152
VP189G
VP289G
VP989G
152_OP
189G_OP
289G_OP
989G_OP
989_EX1
VP289G
VP989G
289G_CL
989G_CL
989_EX2

ABC_LINE
XOR

VP152

XOR

VP989

XOR

VP189

XOR

VP289

XOR

VP789

XOR

VP189G

XOR

VP289G

XOR

VP989G

XOR

VP1189G

XOR

VP2189G

XOR

VP7189G

XOR

VPVOLT
AND

AND

OR
NOT

NOT

152CLREL
152CLITL

989REL
989ITL

AND

en04000527_ansi.vsd
ANSI04000527 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

819

Section 14
Control

1MRK 502 066-UUS A

VP152
VP289
VP189G
VP289G
VP1189G
152_OP
289_OP
189G_OP
289G_OP
1189G_OP

AND

VP289

AND

189REL

OR
NOT

189ITL

EXDU_89G
189_EX1

VP_BC_12
289_CL
BC_12_CL
EXDU_BC
189_EX2

VP189G
VP1189G
189G_CL
1189G_CL
EXDU_89G

AND

189EX3

en04000528_ansi.vsd
ANSI04000528 V1 EN

820

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

VP152
VP189
VP189G
VP289G
VP2189G
152_OP
189_OP
189G_OP
289G_OP
2189G_OP
EXDU_89G

AND

VP189
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC

AND

289REL

OR
NOT

289ITL

289_EX1

289_EX2

VP189G
VP2189G
189G_CL
2189G_CL
EXDU_89G

AND

289_EX3

en04000529_ansi.vsd
ANSI04000529 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

821

Section 14
Control

1MRK 502 066-UUS A

VP989G
VP7189G

AND

VP_BB7_D

789REL

OR
NOT

VP_BC_17

789ITL

VP_BC_27
989G_OP
7189G_OP
EXDU_89G
BB7_D_OP
EXDU_BPB
BC_17_OP
BC_27_OP
EXDU_BC
789_EX1
VP152
VP189
VP989G
VP989
VP7189G
VP_BB7_D
VP_BC_17
152_CL
189_CL
989G_OP
989_CL
7189G_OP
EXDU_89G

AND

BB7_D_OP
EXDU_BPB
BC_17_CL
EXDU_BC
789_EX2
en04000530_ansi.vsd
ANSI04000530 V1 EN

822

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

VP152
VP289
VP989G
VP989
VP7189G
VP_BB7_D
VP_BC_27
152_CL
289_CL
989G_OP
989_CL
7189G_OP
EXDU_89G

AND

OR

BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
789_EX3
VP989G
VP7189G
989G_CL
7189G_CL
EXDU_89G
789_EX4
VP189
VP289
VP989
189_OP
289_OP
989_OP
VP789
VP989
VPVOLT
789_OP
989_OP
VOLT_OFF

AND

AND

189GREL
189GITL
289GREL
289GITL

NOT
NOT

989GREL
989GITL

AND
NOT

en04000531_ansi.vsd
ANSI04000531 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

823

Section 14
Control

1MRK 502 066-UUS A

189_OP
189_CL
VP189

189OPTR
189CLTR
VP189TR

289_OP
289_CL
VP289

289OPTR
289CLTR
VP289TR

789_OP
789_CL
VP789

789OPTR
789CLTR
VP789TR

189_OP
289_OP
VP189
VP289

OR

NOT

AND

1289OPTR
1289CLTR
VP1289TR

en04000532_ansi.vsd
ANSI04000532 V1 EN

14.2.10.5

Signals
Table 424:
Name

ABC_LINE (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

989_OP

BOOLEAN

989 is in open position

989_CL

BOOLEAN

989 is in closed position

189_OP

BOOLEAN

189 is in open position

189_CL

BOOLEAN

189 is in closed position

289_OP

BOOLEAN

289 is in open position

289_CL

BOOLEAN

289 is in closed position

789_OP

BOOLEAN

789 is in open position

789_CL

BOOLEAN

789 is in closed position

189G_OP

BOOLEAN

189G is in open position

189G_CL

BOOLEAN

189G is in closed position

289G_OP

BOOLEAN

289G is in open position

289G_CL

BOOLEAN

289G is in closed position

989G_OP

BOOLEAN

989G is in open position

989G_CL

BOOLEAN

989G is in closed position

1189G_OP

BOOLEAN

Grounding switch 1189G on busbar 1 is in open position

Table continues on next page


824

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

1189G_CL

BOOLEAN

Grounding switch 1189G on busbar 1 is in closed


position

2189G_OP

BOOLEAN

Grounding switch 2189G on busbar 2 is in open position

2189G_CL

BOOLEAN

Grounding switch 2189G on busbar 2 is in closed


position

7189G_OP

BOOLEAN

Grounding switch 7189G on busbar 7 is in open position

7189G_CL

BOOLEAN

Grounding switch 7189G on busbar 7 is in closed


position

BB7_D_OP

BOOLEAN

Disconnectors on busbar bus7 except in the own bay


are open

BC_12_CL

BOOLEAN

A bus coupler connection exists between busbar Bus1


and Bus2

BC_17_OP

BOOLEAN

No bus coupler connection exists between busbar 1 and


Bus 7

BC_17_CL

BOOLEAN

A bus coupler connection exists between busbar Bus1


and Bus7

BC_27_OP

BOOLEAN

No bus coupler connection exists between busbar 2 and


Bus 7

BC_27_CL

BOOLEAN

A bus coupler connection exists between busbar Bus2


and Bus7

VOLT_OFF

BOOLEAN

There is no voltage on the line and not VT (fuse) failure

VOLT_ON

BOOLEAN

There is voltage on the line or there is a VT (fuse) failure

VP_BB7_D

BOOLEAN

Switch status of the disconnectors on busbar WA7 are


valid

VP_BC_12

BOOLEAN

Status of the bus coupler apparatuses between Bus1


and Bus2 are valid

VP_BC_17

BOOLEAN

Status of the bus coupler app. between WA1 and WA7


are valid

VP_BC_27

BOOLEAN

Status of the bus coupler app. between WA2 and WA7


are valid

EXDU_89G

BOOLEAN

No transm error from any bay containing grounding


switches

EXDU_BPB

BOOLEAN

No transm error from any bay with disconnectors on


WA7

EXDU_BC

BOOLEAN

No transmission error from any bus coupler bay

989_EX1

BOOLEAN

External condition for apparatus 989

989_EX2

BOOLEAN

External condition for apparatus 989

189_EX1

BOOLEAN

External condition for apparatus 189

189_EX2

BOOLEAN

External condition for apparatus 189

189_EX3

BOOLEAN

External condition for apparatus 189

289_EX1

BOOLEAN

External condition for apparatus 289

289_EX2

BOOLEAN

External condition for apparatus 289

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

825

Section 14
Control

1MRK 502 066-UUS A

Name

Default

Description

BOOLEAN

External condition for apparatus 289

789_EX1

BOOLEAN

External condition for apparatus 789

789_EX2

BOOLEAN

External condition for apparatus 789

789_EX3

BOOLEAN

External condition for apparatus 789

789_EX4

BOOLEAN

External condition for apparatus 789

Table 425:
Name

826

Type

289_EX3

ABC_LINE (3) Output signals


Type

Description

152CLREL

BOOLEAN

Closing of 152 is allowed

152CLITL

BOOLEAN

Closing of 152 is not allowed

989REL

BOOLEAN

Switching of 989 is allowed

989ITL

BOOLEAN

Switching of 989 is not allowed

189REL

BOOLEAN

Switching of 189 is allowed

189ITL

BOOLEAN

Switching of 189 is not allowed

289REL

BOOLEAN

Switching of 289 is allowed

289ITL

BOOLEAN

Switching of 289 is not allowed

789REL

BOOLEAN

Switching of 789 is allowed

789ITL

BOOLEAN

Switching of 789 is not allowed

189GREL

BOOLEAN

Switching of 189G is allowed

189GITL

BOOLEAN

Switching of 189G is not allowed

289GREL

BOOLEAN

Switching of 289G is allowed

289GITL

BOOLEAN

Switching of 289G is not allowed

989GREL

BOOLEAN

Switching of 989G is allowed

989GITL

BOOLEAN

Switching of 989G is not allowed

189OPTR

BOOLEAN

189 is in open position

189CLTR

BOOLEAN

189 is in closed position

289OPTR

BOOLEAN

289 is in open position

289CLTR

BOOLEAN

289 is in closed position

789OPTR

BOOLEAN

789 is in open position

789CLTR

BOOLEAN

789 is in closed position

1289OPTR

BOOLEAN

189 or 289 or both are in open position

1289CLTR

BOOLEAN

189 and 289 are not in open position

VP189TR

BOOLEAN

Switch status of 189 is valid (open or closed)

VP289TR

BOOLEAN

Switch status of 289 is valid (open or closed)

VP789TR

BOOLEAN

Switch status of 789 is valid (open or closed)

VP1289TR

BOOLEAN

Switch status of 189 and 289 are valid (open or closed)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.11

Interlocking for transformer bay AB_TRAFO (3)

14.2.11.1

Identification
Function description

IEC 61850
identification

Interlocking for transformer bay

14.2.11.2

AB_TRAFO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
3

Functionality
The interlocking for transformer bay (AB_TRAFO, 3) function is used for a transformer
bay connected to a double busbar arrangement according to figure 376. The function is
used when there is no disconnector between circuit breaker and transformer. Otherwise,
the interlocking for line bay (ABC_LINE, 3) function can be used. This function can also
be used in single busbar arrangements.
WA1 (A)
WA2 (B)
189

289

189G
AB_TRAFO

152
289G

389G
252
489G
389

252 and 489G are not


used in this interlocking

489

en04000515_ansi.vsd
ANSI04000515 V1 EN

Figure 376:

Switchyard layout AB_TRAFO (3)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

827

Section 14
Control
14.2.11.3

1MRK 502 066-UUS A

Function block
AB_TRAFO (3)
152_OP
152CLREL
152_CL
152CLITL
189_OP
189REL
189_CL
189ITL
289_OP
289REL
289_CL
289ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
389_OP
189OPTR
389_CL
189CLTR
489_OP
289OPTR
489_CL
289CLTR
389G_OP
1289OPTR
389G_CL
1289CLTR
1189G_OP
VP189TR
1189G_CL
VP289TR
2189G_OP
VP1289TR
2189G_CL
BC_12_CL
VP_BC_12
EXDU_89G
EXDU_BC
152_EX1
152_EX2
152_EX3
189_EX1
189_EX2
189_EX3
289_EX1
289_EX2
289_EX3
ANSI05000358-2-en.vsd
ANSI05000358 V2 EN

Figure 377:

828

AB_TRAFO (3) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.11.4

Logic diagram
152_OP
152_CL
189_OP
189_CL
289_OP
289_CL
189G_OP
189G_CL
289G_OP
289G_CL
389_OP
389_CL
489_OP
489_CL
389G_OP
389G_CL
1189G_OP
1189G_CL
2189G_OP
2189G_CL
VP189
VP289
VP189G
VP289G
VP389
VP489
VP389G
152_EX2
389G_OP
152_EX3
189G_CL
289G_CL
389G_CL
152_EX1

AB_TRAFO
XOR

VP152

XOR

VP189

XOR

VP289

XOR

VP189G

XOR

VP289G

XOR

VP389

XOR

VP489

XOR

VP389G

XOR

VP1189G

XOR

VP2189G
152CLREL
152CLITL

AND

NOT

OR
AND

en04000538_ansi.vsd

ANSI04000538 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

829

Section 14
Control

1MRK 502 066-UUS A

VP152
VP289
VP189G
VP289G
VP389G
VP1189G
152_OP
289_OP
189G_OP
289G_OP
389G_OP
1189G_OP
EXDU_89G
189_EX1
VP289
VP389G
VP_BC_12
289_CL
389G_OP
BC_12_CL
EXDU_BC
189_EX2
VP189G
VP289G
VP389G
VP1189G
189G_CL
289G_CL
389G_CL
1189G_CL
EXDU_89G
189_EX3

AND

189REL

OR
NOT

189ITL

AND

AND

en04000539_ansi.vsd

ANSI04000539 V1 EN

VP152
VP189
VP189G
VP289G
VP389G
VP2189G
152_OP
189_OP
189G_OP
289G_OP
389G_OP
2189G_OP
EXDU_89G
289_EX1
VP189
VP389G
VP_BC_12
189_CL
389G_OP
BC_12_CL
EXDU_BC
289_EX2
VP189G
VP289G
VP389G
VP2189G
189G_CL
289G_CL
389G_CL
2189G_CL
EXDU_89G
289_EX3

AND

OR
NOT

252REL
252ITL

AND

AND

en04000540_ansi.vsd

ANSI04000540 V1 EN

830

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

VP189
VP289
VP389
VP489
189_OP
289_OP
389_OP
489_OP

AND

NOT
NOT

189GREL
189GITL
289GREL
289GITL

189_OP
189_CL
VP189

189OPTR
189CLTR
VP189TR

289_OP
289_CL
VP289
189_OP
289_OP
VP189
VP289

289OPTR
289CLTR
VP289TR
1289OPTR
1289CLTR
VP1289TR

OR

NOT

AND

en04000541_ansi.vsd

ANSI04000541 V1 EN

14.2.11.5

Signals
Table 426:
Name

AB_TRAFO (3) Input signals


Type

Default

Description

152_OP

BOOLEAN

152 is in open position

152_CL

BOOLEAN

152 is in closed position

189_OP

BOOLEAN

189 is in open position

189_CL

BOOLEAN

189 is in closed position

289_OP

BOOLEAN

289 is in open position

289_CL

BOOLEAN

289 is in closed position

189G_OP

BOOLEAN

189G is in open position

189G_CL

BOOLEAN

189G is in closed position

289G_OP

BOOLEAN

289G is in open position

289G_CL

BOOLEAN

289G is in closed position

389_OP

BOOLEAN

389 is in open position

389_CL

BOOLEAN

389 is in closed position

489_OP

BOOLEAN

489 is in open position

489_CL

BOOLEAN

489 is in closed position

389G_OP

BOOLEAN

389G is in open position

389G_CL

BOOLEAN

389G is in closed position

1189G_OP

BOOLEAN

1189G on busbar WA1 is in open position

1189G_CL

BOOLEAN

1189G on busbar WA1 is in closed position

2189G_OP

BOOLEAN

2189G on busbar WA2 is in open position

2189G_CL

BOOLEAN

2189G on busbar WA2 is in closed position

BC_12_CL

BOOLEAN

A bus coupler connection exists between busbar Bus1


and Bus2

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

831

Section 14
Control

1MRK 502 066-UUS A

Name

Default

Description

BOOLEAN

Status of the bus coupler apparatuses between Bus1


and Bus2 are valid

EXDU_89G

BOOLEAN

No transm error from any bay containing grounding


switches

EXDU_BC

BOOLEAN

No transmission error from any bus coupler bay

152_EX1

BOOLEAN

External condition for breaker 152

152_EX2

BOOLEAN

External condition for breaker 152

152_EX3

BOOLEAN

External condition for breaker 152

189_EX1

BOOLEAN

External condition for apparatus 189

189_EX2

BOOLEAN

External condition for apparatus 189

189_EX3

BOOLEAN

External condition for apparatus 189

289_EX1

BOOLEAN

External condition for apparatus 289

289_EX2

BOOLEAN

External condition for apparatus 289

289_EX3

BOOLEAN

External condition for apparatus 289

Table 427:
Name

832

Type

VP_BC_12

AB_TRAFO (3) Output signals


Type

Description

152CLREL

BOOLEAN

Closing of 152 is allowed

152CLITL

BOOLEAN

Closing of 152 is not allowed

189REL

BOOLEAN

Switching of 189 is allowed

189ITL

BOOLEAN

Switching of 189 is not allowed

289REL

BOOLEAN

Switching of 289 is allowed

289ITL

BOOLEAN

Switching of 289 is not allowed

189GREL

BOOLEAN

Switching of 189G is allowed

189GITL

BOOLEAN

Switching of 189G is not allowed

289GREL

BOOLEAN

Switching of 289G is allowed

289GITL

BOOLEAN

Switching of 289G is not allowed

189OPTR

BOOLEAN

189 is in open position

189CLTR

BOOLEAN

189 is in closed position

289OPTR

BOOLEAN

289 is in open position

289CLTR

BOOLEAN

289 is in closed position

1289OPTR

BOOLEAN

189 or 289 or both are in open position

1289CLTR

BOOLEAN

189 and 289 are not in open position

VP189TR

BOOLEAN

Switch status of 189 is valid (open or closed)

VP289TR

BOOLEAN

Switch status of 289 is valid (open or closed)

VP1289TR

BOOLEAN

Switch status of 189 and 289 are valid (open or closed)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.2.12

Position evaluation POS_EVAL

14.2.12.1

Identification

14.2.12.2

Function description

IEC 61850
identification

Position evaluation

POS_EVAL

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals OPENPOS or
CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.

14.2.12.3

Function block
POSITION

POS_EVAL
OPENPOS
CLOSEPOS
IEC09000079_1_en.vsd

IEC09000079 V1 EN

Figure 378:

14.2.12.4

POS_EVAL function block

Logic diagram
Position including quality

POSITION

POS_EVAL
OPENPOS
CLOSEPOS

Open/close position of
switch device

IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN

Only the value, open/close, and status is used in this function. Time information is not
used.
Input position (Value)

Signal quality

Output OPENPOS

Output CLOSEPOS

0 (Breaker intermediate)

Good

1 (Breaker open)

Good

2 (Breaker closed)

Good

3 (Breaker faulty)

Good

Any

Invalid

Any

Oscillatory

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

833

Section 14
Control
14.2.12.5

1MRK 502 066-UUS A

Signals
Table 428:

POS_EVAL Input signals

Name

Type

POSITION

Table 429:

INTEGER

Default
0

Description
Position status including quality

POS_EVAL Output signals

Name

Type

Description

OPENPOS

BOOLEAN

Open position

CLOSEPOS

BOOLEAN

Close position

14.3

Apparatus control APC

14.3.1

Functionality
The apparatus control functions are used for control and supervision of circuit breakers,
disconnectors and grounding switches within a bay. Permission to trip is given after
evaluation of conditions from other functions such as interlocking, synchronism check,
operator place selection and external or internal blockings.
Apparatus control features:

Select-Execute principle to give high reliability


Selection function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position and quality indications
Overriding of interlocking functions
Overriding of synchrocheck
Operation counter
Suppression of mid position

Two types of command models can be used:

834

Direct with normal security


SBO (Select-Before-Operate) with enhanced security

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Normal security means that only the command is evaluated and the resulting position is
not supervised. Enhanced security means that the command is evaluated with an
additional supervision of the status value of the control object. The command sequence
with enhanced security is always terminated by a CommandTermination service primitive
and an AddCause telling if the command was successful or if something went wrong.
Control operation can be performed from the local HMI with authority control if so
defined.

14.3.2

Operation principle
A bay can handle, for example a power line, a transformer, a reactor, or a capacitor bank.
The different primary apparatuses within the bay can be controlled via the apparatus
control functions directly by the operator or indirectly by automatic sequences.
Because a primary apparatus can be allocated to many functions within a Substation
Automation system, the object-oriented approach with a function block that handles the
interaction and status of each process object ensures consistency in the process
information used by higher-level control functions.
Primary apparatuses such as breakers and disconnectors are controlled and supervised by
one function block (SCSWI) each. Because the number and type of signals used for the
control of a breaker respectively a disconnector are almost the same, the same function
block type is used to handle these two types of apparatuses.
The SCSWI function block is connected either to an SXCBR function block (for circuit
breakers) or to an SXSWI function block (for disconnectors and grounding switches). The
physical process in the switchyard is connected to these two function blocks via binary
inputs and outputs.
Four types of function blocks are available to cover most of the control and supervision
within the bay. These function blocks are interconnected to form a control function
reflecting the switchyard configuration. The total number used depends on the switchyard
configuration. These four types are:

Bay control QCBAY


Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI

The functions Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL),
to handle the local/remote switch, and the functions Bay reserve (QCRSV) and
Reservation input (RESIN), for the reservation function, also belong to the apparatus
control function. The principles of operation, function blocks, input and output signals and
setting parameters for all these functions are described below.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

835

Section 14
Control
14.3.3

1MRK 502 066-UUS A

Error handling
Depending on the error that occurs during the command sequence the error signal will be
set with a value. Table 430 describes the cause values given on local HMI. The translation
to AddCause values specified in IEC 61850-8-1 is shown in Table 431. For IEC 61850-8-1
edition 2 only addcauses defined in the standard are used, for edition 1 also a number of
vendor specific causes are used. The values are available in the command response to
commands from IEC61850-8-1 clients. An output L_CAUSE on the function block for
Switch controller (SCSWI), Circuit breaker (SXCBR) and Circuit switch (SXSWI)
indicates the value of the cause during the latest command.
Table 430:

Values for "cause" signal

Cause
number

Name

Description

Supported

None

Control action successfully executed

Not-supported

Given for Cancel request with Direct Control in Ready state

Blocked-byswitching-hierarchy

Not successful since one of the downstream Loc switches


like in CSWI has the value TRUE

Select-failed

Cancelled due to an unsuccessful selection (select service)

Invalid-position

Control action is aborted due to invalid switch position (Pos


in XCBR or XSWI)

Position-reached

Switch is already in the intended position (Pos in XCBR or


XSWI)

Parameter-changein-execution

Control action is blocked due to running parameter change

Step-limit

Control action is blocked, because tap changer has


reached the limit (EndPosR or EndPosL in YLTC)

Blocked-by-Mode

Control action is blocked, because the LN (CSWI or XCBR/


XSWI)is in a mode (Mod) which doesnt allow any switching

Blocked-by-process

Control action is blocked due to some external event at


process level that prevents a successful operation, for
example blocking indication (EEHealth in XCBR or XSWI)

10

Blocked-byinterlocking

Control action is blocked due to interlocking of switching


devices (in CILO attribute EnaOpn.stVal=FALSE or
EnaCls.stVal=FALSE

11

Blocked-bysynchrocheck

Control action with synchrocheck is aborted due to exceed


of time limit and missing synchronism condition

12

Command-alreadyin-execution

Control, select or cancel service is rejected, because


control action is already running

13

Blocked-by-health

Control action is blocked due to some internal event that


prevents a successful operation (Health)

14

1-of-n-control

Control action is blocked, because another control action in


a domain (for example substation) is already running (in
any XCBR or XSWI of that domain, the
DPC.stSeld=TRUE)

15

Abortion-by-cancel

Control action is aborted due to cancel service

Table continues on next page


836

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Cause
number

Name

Description

Supported

16

Time-limit-over

Control action is terminated due to exceed of some time


limit

17

Abortion-by-trip

Control action is aborted due to a trip (PTRC with


ACT.general=TRUE)

18

Object-not-selected

Control action is rejected, because control object was not


selected

19

Object-alreadyselected

Select action is not executed, because the addressed


object is already selected

20

No-access-authority

Control action is blocked due to lack of access authority

21

Ended-withovershoot

Control action executed but the end position has overshoot

22

Abortion-due-todeviation

Control action is aborted due to deviation between the


command value and the measured value

23

Abortion-bycommunication-loss

Control action is aborted due to the loss of connection with


the client that issued the control

24

Blocked-bycommand

Control action is blocked due to the data attribute


CmdBlk.stVal is TRUE

26

Inconsistentparameters

The parameters between successive control services are


not consistent, for example the ctlNum of Select and
Operate service are different

27

Locked-by-otherclient

Another client has already reserved the object

-22

Wrong_CTL_Model

Command from client uses wrong control model

-24

Blocked_for_Open_C
md

Blocked for Open command

-25

Blocked_For_Close_
Cmd

Blocked for Close Command

-30

longOperationTime

Operation time too long

-31

switchNotStartMovin
g

Switch did not start moving

-32

persistantIntermediat
eState

Switch stopped in intermediate state

-33

switchReturnedToInit
Pos

Switch returned to the initial position

-34

switchInBadState

Switch is in a bad position state

-35

notExpectedFinalPos
ition

Switch did not reach the expected final position

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

837

Section 14
Control

1MRK 502 066-UUS A

Table 431:
Internal Cause
Number

Translation of cause values for IEC61850 edition 2 and edition 1


AddCause in IEC61850-8-1
Ed 2

Name

Ed 1

25

None

Not-supported

Blocked-by-switching-hierarchy

Select-failed

Invalid-position

Position-reached

Parameter-change-in-execution

Step-limit

Blocked-by-Mode

Blocked-by-process

10

10

10

Blocked-by-interlocking

11

11

11

Blocked-by-synchrocheck

12

12

12

Command-already-in-execution

13

13

13

Blocked-by-health

14

14

14

1-of-n-control

15

15

Abortion-by-cancel

16

16

16

Time-limit-over

17

17

17

Abortion-by-trip

18

18

18

Object-not-selected

19

19

Object-already-selected

20

20

No-access-authority

21

21

Ended-with-overshoot

22

22

Abortion-due-to-deviation

23

23

Abortion-by-communication-loss

24

24

-23

Blocked-by-command

26

26

Inconsistent-parameters

27

27

12

Locked-by-other-client

-22

-22

Wrong_CTL_Model

-24

24

-24

Blocked_for_Open_Cmd

-25

24

-25

Blocked_For_Close_Cmd

-30

24

-30

longOperationTime

-31

16

-31

switchNotStartMoving

-32

16

-32

persistantIntermediateState

Table continues on next page

838

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Internal Cause
Number

AddCause in IEC61850-8-1

Name

Ed 2

Ed 1

-33

22

-33

switchReturnedToInitPos

-34

-34

switchInBadState

-35

22

-35

notExpectedFinalPosition

14.3.4

Bay control QCBAY

14.3.4.1

Functionality
The Bay control QCBAY function is used together with Local remote and local remote
control functions to handle the selection of the operator place per bay. QCBAY also
provides blocking functions that can be distributed to different apparatuses within the bay.

14.3.4.2

Function block
QCBAY
LR_OFF

PSTO

LR_LOC

UPD_BLKD

LR_REM

CMD_BLKD

LR_VALID

LOC

BL_UPD

STA

BL_CMD

REM
IEC10000048-2-en.vsd

IEC10000048 V2 EN

Figure 379:

14.3.4.3

QCBAY function block

Signals
Table 432:
Name

QCBAY Input signals


Type

Default

Description

LR_OFF

BOOLEAN

External Local/Remote switch is in Off position

LR_LOC

BOOLEAN

External Local/Remote switch is in Local position

LR_REM

BOOLEAN

External Local/Remote switch is in Remote position

LR_VALID

BOOLEAN

Data representing the L/R switch position is valid

BL_UPD

BOOLEAN

Steady signal to block the position updates

BL_CMD

BOOLEAN

Steady signal to block the command

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

839

Section 14
Control

1MRK 502 066-UUS A

Table 433:

QCBAY Output signals

Name

14.3.4.4
Table 434:
Name

Type

Description

PSTO

INTEGER

Value for the operator place allocation

UPD_BLKD

BOOLEAN

Update of position is blocked

CMD_BLKD

BOOLEAN

Function is blocked for commands

LOC

BOOLEAN

Local operation allowed

STA

BOOLEAN

Station operation allowed

REM

BOOLEAN

Remote operation allowed

Settings
QCBAY Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

AllPSTOValid

Priority
No priority

Priority

Override Priority of originators, commands


from both local, station and remote are allowed

RemoteIncStation

No
Yes

No

Both Station and Remote control are allowed


but not Local when local remote switch is in
remote

14.3.4.5

Operation principle
The function sends information about the Permitted Source To Operate (PSTO) and
blocking conditions to other functions within the bay for example, switch control
functions and voltage control functions. The functionality of the Bay control (QCBAY)
function is mainly described by the LLN0 node in the IEC61850-8-1 edition 2 standard,
applied to one bay. In IEC61850 edition 1 the functionality is not described by the LLN0
node or any other node, therefore the Bay control function is represented as a vendor
specific node in edition 1.

Local panel switch


The local panel switch is a switch that defines the operator place selection. The switch
connected to this function can have three positions (remote/local/off). The positions are
here defined so that remote means that operation is allowed from station and/or remote
level and local means that operation is allowed from the IED level. The local/remote
switch is also on the control/protection IED itself, which means that the position of the
switch and its validity information are connected internally, not via I/O boards. When the
switch is mounted separately from the IED the signals are connected to the function via I/
O boards.
When the local panel switch (or LHMI selection, depending on the set source to select this)
is in Off position, all commands from remote and local level will be ignored. If the position

840

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

for the local/remote switch is not valid the PSTO output will always be set to faulty state
(3), which means no possibility to operate.
To adapt the signals from the local HMI or from an external local/remote switch, the
function blocks LOCREM and LOCREMCTRL are needed and connected to QCBAY.

Permitted Source To Operate (PSTO)


The actual state of the operator place is presented by the value of the Permitted Source To
Operate, PSTO signal. The PSTO value is evaluated from the local/remote switch position
according to Table 435. In addition, there are two parameters that affect the value of the
PSTO signal.
If the parameter AllPSTOValid is set and LR-switch position is in Local or Remote state,
the PSTO value is set to 5 (all), that is, it is permitted to operate from both local and remote
level without any priority. When the external panel switch is in Off position the PSTO
value shows the actual state of the switch that is, 0. In this case it is not possible to control
anything
If the parameter RemoteIncStation is set and the LR-switch position is in Remote state, the
PSTO value is set to 2 (Station or Remote), that is, it is permitted to operate from both
station and remote level without any priority.
Table 435:
Local panel
switch positions

PSTO values for different Local panel switch positions


PSTO
value

AllPSTOValid RemoteInc
Station
(setting
(setting
parameter)
parameter)

LocSta.CtlVal Possible
(command)
locations that
shall be able to
operate

0 = Off

Not possible
to operate

1 = Local

Priority

Local Panel

1 = Local

No priority

Local or
Remote level
without any
priority

2 = Remote

Priority

No

TRUE

Station level

2 = Remote

Priority

No

FALSE

Remote level

2 = Remote

Priority

Yes

Station or
Remote level

2 = Remote

No priority

Local, Station
or Remote
level without
any priority

3 = Faulty

Not possible
to operate

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

841

Section 14
Control

1MRK 502 066-UUS A

Blockings
The blocking states for position indications and commands are intended to provide the
possibility for the user to make common blockings for the functions configured within a
complete bay.
The blocking facilities provided by the bay control function are the following:

Blocking of position indications, BL_UPD. This input will block all inputs related to
apparatus positions for all configured functions within the bay.
Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
Blocking of function, BLOCK. If the BLOCK signal is set, it means that the function
is active, but no outputs are generated, no reporting, control commands are rejected
and functional and configuration data is visible.

The switching of the Local/Remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been defined
in the IED. Otherwise the default authority level, SuperUser, can handle the control
without LogOn. The users and passwords are defined with the IED Users tool in PCM600.

14.3.5

Local/Remote switch LOCREM, LOCREMCTRL


The signals from the local HMI or from an external local/remote switch are connected via
the function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY function
block. The parameter ControlMode in function block LOCREM is set to choose if the
switch signals are coming from the local HMI or from an external hardware switch
connected via binary inputs.

14.3.5.1

Function block
LOCREM
CTRLOFF
LOCCTRL
REMCTRL
LHMICTRL

OFF
LOCAL
REMOTE
VALID
IEC05000360-2-en.vsd

IEC05000360 V2 EN

Figure 380:

842

LOCREM function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

PSTO1
PSTO2
PSTO3
PSTO4
PSTO5
PSTO6
PSTO7
PSTO8
PSTO9
PSTO10
PSTO11
PSTO12

LOCREMCTRL
HMICTR1
HMICTR2
HMICTR3
HMICTR4
HMICTR5
HMICTR6
HMICTR7
HMICTR8
HMICTR9
HMICTR10
HMICTR11
HMICTR12
IEC05000361-2-en.vsd

IEC05000361 V2 EN

Figure 381:

14.3.5.2

LOCREMCTRL function block

Signals
Table 436:
Name

LOCREM Input signals


Type

Default

Description

CTRLOFF

BOOLEAN

Disable control

LOCCTRL

BOOLEAN

Local in control

REMCTRL

BOOLEAN

Remote in control

LHMICTRL

INTEGER

LHMI control

Table 437:
Name

LOCREM Output signals


Type

Description

OFF

BOOLEAN

Control is disabled

LOCAL

BOOLEAN

Local control is activated

REMOTE

BOOLEAN

Remote control is activated

VALID

BOOLEAN

Outputs are valid

Table 438:
Name

LOCREMCTRL Input signals


Type

Default

Description

PSTO1

INTEGER

PSTO input channel 1

PSTO2

INTEGER

PSTO input channel 2

PSTO3

INTEGER

PSTO input channel 3

PSTO4

INTEGER

PSTO input channel 4

PSTO5

INTEGER

PSTO input channel 5

PSTO6

INTEGER

PSTO input channel 6

PSTO7

INTEGER

PSTO input channel 7

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

843

Section 14
Control

1MRK 502 066-UUS A

Name

Type

PSTO input channel 8

PSTO9

INTEGER

PSTO input channel 9

PSTO10

INTEGER

PSTO input channel 10

PSTO11

INTEGER

PSTO input channel 11

PSTO12

INTEGER

PSTO input channel 12

LOCREMCTRL Output signals

Name

Table 440:
Name
ControlMode

14.3.5.4

Description

INTEGER

Table 439:

14.3.5.3

Default

PSTO8

Type

Description

HMICTR1

INTEGER

Bitmask output 1 to local remote LHMI input

HMICTR2

INTEGER

Bitmask output 2 to local remote LHMI input

HMICTR3

INTEGER

Bitmask output 3 to local remote LHMI input

HMICTR4

INTEGER

Bitmask output 4 to local remote LHMI input

HMICTR5

INTEGER

Bitmask output 5 to local remote LHMI input

HMICTR6

INTEGER

Bitmask output 6 to local remote LHMI input

HMICTR7

INTEGER

Bitmask output 7 to local remote LHMI input

HMICTR8

INTEGER

Bitmask output 8 to local remote LHMI input

HMICTR9

INTEGER

Bitmask output 9 to local remote LHMI input

HMICTR10

INTEGER

Bitmask output 10 to local remote LHMI input

HMICTR11

INTEGER

Bitmask output 11 to local remote LHMI input

HMICTR12

INTEGER

Bitmask output 12 to local remote LHMI input

Settings
LOCREM Non group settings (basic)
Values (Range)
Internal LR-switch
External LR-switch

Unit
-

Step
-

Default
Internal LR-switch

Description
Control mode for internal/external LR-switch

Operation principle
The function block Local remote (LOCREM) handles the signals coming from the local/
remote switch. The connections are seen in Figure 382, where the inputs on function block
LOCREM are connected to binary inputs if an external switch is used. When the local
HMI is used, the inputs are not used. The switching between external and local HMI
source is done through the parameter ControlMode. The outputs from the LOCREM

844

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

function block control the output PSTO (Permitted Source To Operate) on Bay control
(QCBAY).
LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID

QCBAY
LR_ OFF
PSTO
LR_ LOC UPD_ BLKD
LR_ REM CMD_ BLKD
LOC
LR_ VALID
STA
BL_ UPD
REM
BL_ CMD

LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID

QCBAY
LR_ OFF
PSTO
LR_ LOC UPD_ BLKD
LR_ REM CMD_ BLKD
LOC
LR_ VALID
STA
BL_ UPD
REM
BL_ CMD

LOCREMCTRL
PSTO1
HMICTR1
PSTO2
HMICTR2
PSTO3
HMICTR3
PSTO4
HMICTR4
PSTO5
HMICTR5
PSTO6
HMICTR6
PSTO7
HMICTR7
PSTO8
HMICTR8
PSTO9
HMICTR9
PSTO 10
HMICTR 10
PSTO 11
HMICTR 11
PSTO 12
HMICTR 12
IEC10000052-1-en.vsd
IEC10000052 V2 EN

Figure 382:

Configuration for the local/remote handling for a local HMI with two bays
and two screen pages

If the IED contains control functions for several bays, the local/remote position can be
different for the included bays. When the local HMI is used the position of the local/
remote switch can be different depending on which single line diagram screen page that
is presented on the local HMI. The function block Local remote control (LOCREMCTRL)
controls the presentation of the LEDs for the local/remote position to applicable bay and
screen page.
The switching of the local/remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been defined
in the IED. Otherwise the default authority level, SuperUser, can handle the control
without LogOn. The users and passwords are defined with the IED Users tool in PCM600.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

845

Section 14
Control

1MRK 502 066-UUS A

14.3.6

Switch controller SCSWI

14.3.6.1

Functionality
The Switch controller (SCSWI) initializes and supervises all functions to properly select
and operate switching primary apparatuses. The Switch controller may handle and operate
on one three-phase device or up to three one-phase devices.

14.3.6.2

Function block
SCSWI
BLOCK
PSTO
L_SEL
L_OPEN
L_CLOSE
AU_OPEN
AU_CLOSE
BL_CMD
RES_GRT
RES_EXT
SY_INPRO
SYNC_OK
EN_OPEN
EN_CLOSE
XPOS1
XPOS2
XPOS3

EXE_OP
EXE_CL
SEL_OP
SEL_CL
SELECTED
RES_RQ
START_SY
CANC_SY
POSITION
OPENPOS
CLOSEPOS
POLEDISC
CMD_BLK
L_CAUSE
POS_INTR
XOUT

IEC05000337-3-en.vsd
IEC05000337 V3 EN

Figure 383:

14.3.6.3

SCSWI function block

Signals
Table 441:
Name

SCSWI Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

L_SEL

BOOLEAN

Select signal from local panel

L_OPEN

BOOLEAN

Open signal from local panel

L_CLOSE

BOOLEAN

Close signal from local panel

AU_OPEN

BOOLEAN

Used for local automation function

AU_CLOSE

BOOLEAN

Used for local automation function

BL_CMD

BOOLEAN

Steady signal for block of the command

RES_GRT

BOOLEAN

Positive acknowledge that all reservations are made

RES_EXT

BOOLEAN

Reservation is made externally

Table continues on next page

846

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

SY_INPRO

BOOLEAN

Synchronizing function in progress

SYNC_OK

BOOLEAN

Closing is permitted by the synchronism-check

EN_OPEN

BOOLEAN

Enables open operation

EN_CLOSE

BOOLEAN

Enables close operation

XPOSL1

GROUP
SIGNAL

Group signal from XCBR/XSWI per phase

XPOSL2

GROUP
SIGNAL

Group signal from XCBR/XSWI per phase

XPOSL3

GROUP
SIGNAL

Group signal from XCBR/XSWI per phase

Table 442:
Name

SCSWI Output signals


Type

Description

EXE_OP

BOOLEAN

Execute Open command

EXE_CL

BOOLEAN

Execute Close command

SEL_OP

BOOLEAN

Selected for open command

SEL_CL

BOOLEAN

Selected for close command

SELECTED

BOOLEAN

Select conditions are fulfilled

RES_RQ

BOOLEAN

Request signal to the reservation function

START_SY

BOOLEAN

Starts the external synchronizing function

CANC_SY

BOOLEAN

Cancels the external synchronizing function, started


through START_SY

POSITION

INTEGER

Position indication

OPENPOS

BOOLEAN

Open position indication

CLOSEPOS

BOOLEAN

Closed position indication

POLEDISC

BOOLEAN

The positions for poles A, B and C are not equal after a


set time

CMD_BLK

BOOLEAN

Commands are blocked

L_CAUSE

INTEGER

Latest value of the error indication during command

POS_INTR

BOOLEAN

Stopped in intermediate position

XOUT

BOOLEAN

Execution information to XCBR/XSWI

AU_OPEN and AU_CLOSE are used to issue automated commands as


e.g. for load shedding for opening respectively closing to the SCSWI
function. They work without regard to how the operator place selector,
PSTO, is set. In order to have effect on the outputs EXE_OP and

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

847

Section 14
Control

1MRK 502 066-UUS A

EXE_CL, the corresponding enable input, EN_OPEN respectively


EN_CLOSE must be set, and that no interlocking is active.

L_SEL, L_OPEN and L_CLOSE are used for local command sequence
connected to binary inputs. In order to have effect, the operator place
selector, PSTO, must be set to local or to remote with no priority. If the
control model used is Select before operate, Also the corresponding
enable input must be set, and no interlocking is active. The L_SEL input
must be set before L_OPEN or L_CLOSE is operated, if the control model
is Select before operate.

14.3.6.4
Table 443:
Name

Settings
SCSWI Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

CtlModel

Dir Norm
SBO Enh

SBO Enh

Specifies control model type

PosDependent

Always permitted
Not perm at 00/11

Always permitted

Permission to operate depending on the


position

tSelect

0.00 - 600.00

0.01

30.00

Maximum time between select and execute


signals

tResResponse

0.000 - 60.000

0.001

5.000

Allowed time from reservation request to


reservation granted

tSynchrocheck

0.00 - 600.00

0.01

10.00

Allowed time for synchronism-check to fulfil


close conditions

tSynchronizing

0.00 - 600.00

0.01

0.00

Supervision time to get the signal


synchronizing in progress

tExecutionFB

0.00 - 600.00

0.01

30.00

Maximum time from command execution to


termination

tPoleDiscord

0.000 - 60.000

0.001

2.000

Allowed time to have discrepancy between the


poles

SuppressMidPos

Disabled
Enabled

Enabled

Mid-position is suppressed during the time


tIntermediate

InterlockChk

Sel & Op phase


Op phase

Sel & Op phase

Selection if interlock check should be done in


select phase

14.3.6.5

Operation principle
The Switch controller (SCSWI) is provided with verification checks for the select execute sequence, that is, checks the conditions prior each step of the operation are

848

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

fulfilled. The involved functions for these condition verifications are interlocking,
reservation, blockings and synchronism-check.

Control handling
.
Two types of control models can be used. The two control models are "direct with normal
security" and "SBO (Select-Before-Operate) with enhanced security". The parameter
CtlModel defines which one of the two control models is used. The control model "direct
with normal security" does not require a select whereas, the "SBO with enhanced security"
command model requires a select before execution. The command sequence for a
command with control mode SBO with enhanced security is shown in figure 384, with
control mode direct with normal security is shown in figure 385.
Client

Reservation
logic

SXCBR /
SXSWI

SCSWI
select

selectAck/AddCause = 0

RES_RQ = TRUE
tSelect

tReservation
Response

RES_GRT = TRUE
SELECTED = TRUE
requestedPosition = 10
opRcvd = TRUE
EXE_CL
opOK = TRUE, tOpOk

operateAck/AddCause = 0
operateAck/AddCause = 0

tExecutionFB

POSITION = 00, timeStamp


POSITION = 00, timeStamp

POSITION = 10, timeStamp


cmdTermination/
AddCause = 0

POSITION = 10, timeStamp


cmdTermination/AddCause = 0

RES_RQ = FALSE
RES_GRT = FALSE
SELECTED = FALSE
IEC15000416-1-EN.vsdx

IEC15000416 V1 EN

Figure 384:

Example of command sequence for a successful close command when


the control model SBO with enhanced security is used

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

849

Section 14
Control

1MRK 502 066-UUS A

Reservation
core

client

SwitchCtrl
core

Switch
core

requestedPosition = 10
opRcvd = TRUE

RES_RQ
tReservation
Response

RES_GRT = TRUE

EXE_CL
opOK = TRUE, tOpOk

operateAck/AddCause = 0

operateAck/AddCause = 0

POSITION = 00, timeStamp

POSITION = 00, timeStamp

POSITION = 10, timeStamp

POSITION = 10, timeStamp


cmdTermination/
AddCause = 0

RES_RQ = FALSE
RES_GRT = FALSE

IEC15000417-1-en.vsdx

IEC15000417 V1 EN

Figure 385:

Example of command sequence for a successful close command when


the control model direct with normal security is used

Normal security means that only the command is evaluated and the resulting position is
not supervised. Enhanced security means that the command sequence is supervised in
three steps, the selection, command evaluation and the supervision of position. Each step
ends up with a pulsed signal to indicate that the respective step in the command sequence
is finished. If an error occurs in one of the steps in the command sequence, the sequence
is terminated. The last error (L_CAUSE) can be read from the function block and used for
example at commissioning.
There is no relation between the command direction and the actual
position. For example, if the switch is in close position it is possible to
execute a close command.
Before an execution command, an evaluation of the position is done. If the parameter
PosDependent is true and the position is in intermediate state or in bad state no execution
command is sent. If the parameter is false the execution command is sent independent of
the position value.

Evaluation of position
The position output from the switches (SXCBR or SXSWI) is connected to the switch
controller SCSWI. The XPOS1, XPOS2 and XPOS3 input signals receive the position,
time stamps and quality attributes of the position which is used for further evaluation.

850

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

In the case when there are three one-phase switches connected to the switch control
function, the switch control will "merge" the position of the three switches to the resulting
three-phase position. In the case when the position differ between the one-phase switches,
following principles will be applied:
All switches in open position:

switch control position = open

All switches in close position:

switch control position = close

One switch =open, two switches= close (or


inversely):

switch control position = intermediate

Any switch in intermediate position:

switch control position = intermediate

Any switch in bad state:

switch control position = bad state

The time stamp of the output three-phase position from switch control will have the time
stamp of the last changed phase when it reaches the end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.
In addition, there is also the possibility that one of the one-phase switches will change
position at any time due to a trip. Such situation is here called pole discrepancy and is
supervised by this function. In case of a pole discrepancy situation, that is, the positions
of the one-phase switches are not equal positions for a time longer than the setting
tPoleDiscord, an error signal POLEDISC will be set.
In the supervision phase, the switch controller function evaluates the "cause" values from
the switch modules Circuit breaker (SXCBR)/ Circuit switch (SXSWI). At error the
"cause" value with highest priority is shown.

Blocking principles
The blocking signals are normally coming from the bay control function (QCBAY) and
via the IEC 61850 communication from the operator place.
The different blocking possibilities are:

Block/deblock of command. It is used to block command for operation of position.


Blocking of function, BLOCK. If the BLOCK signal is set, it means that the function
is active, but no outputs are generated, no reporting, control commands are rejected
and functional and configuration data is visible.
The different block conditions will only affect the operation of this
function, that is, no blocking signals will be "forwarded" to other
functions. The above blocking outputs are stored in a non-volatile
memory.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

851

Section 14
Control

1MRK 502 066-UUS A

Dependence on Operator place


For commands from communication protocol, such as IEC61850-8-1 and DNP, and
through the inputs L_SEL, L_OPEN and L_CLOSE, the operator place is evaluated, and
only commands from enabled operator places are accepted, see Table 435. Commands
through the inputs L_SEL, L_OPEN and L_CLOSE are always from the local operator
place. For commands through the inputs AU_OPEN and AU_CLOSE, the operator place is
not evaluated, thus also accepted when the operator place selector is set to Faulty or Off.

Interaction with synchronism-check and synchronizing functions


The Switch controller (SCSWI) works in conjunction with the synchronism-check and the
synchronizing function (SESRSYN, 25). It is assumed that the synchronism-check
function is continuously in operation and gives the result to SCSWI. The result from the
synchronism-check function is evaluated during the close execution. If the operator
performs an override of the synchronism-check, the evaluation of the synchronism-check
state is omitted. When there is a positive confirmation from the synchronism-check
function, SCSWI will send the close signal EXE_CL to the switch function Circuit
breaker (SXCBR).
When there is no positive confirmation from the synchronism-check function, SCSWI
will send a start signal START_SY to the synchronizing function, which will send the
closing command to SXCBR when the synchronizing conditions are fulfilled, see
Figure 386. If no synchronizing function is included, the timer for supervision of the
"synchronizing in progress signal" is set to 0, which means no start of the synchronizing
function. SCSWI will then set the attribute "blocked-by-synchronism-check" in the
"cause" signal. See also the time diagram in Figure 390.

852

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

SCSWI
EXE_CL

SXCBR
OR

CLOSE

SYNC_OK
START_SY
SY_INPRO
SESRSYN
CLOSECMD
Synchro
check

Synchronizing
function

ANSI09000209-1-en.vsd
ANSI09000209 V1 EN

Figure 386:

Example of interaction between SCSWI, SESRSYN (25) (synchronism


check and synchronizing function) and SXCBR function

Time diagrams
The Switch controller (SCSWI) function has timers for evaluating different time
supervision conditions. These timers are explained here.
The timer tSelect is used for supervising the time between the select and the execute
command signal, that is, the time the operator has to perform the command execution after
the selection of the object to operate.

select
execute command
tSelect
timer

t1

t1>tSelect, then longoperation-time in 'cause'


is set
en05000092.vsd

IEC05000092 V1 EN

Figure 387:

tSelect

The parameter tResResponse is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback reservation
granted from all bays involved in the reservation function.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

853

Section 14
Control

1MRK 502 066-UUS A

select
reservation request RES_RQ
reservation granted RES_GRT
tResResponse
timer

t1>tResResponse, then 1of-n-control in 'cause' is


set

t1

IEC05000093-2-en.vsd
IEC05000093 V2 EN

Figure 388:

tResResponse

The timer tExecutionFB supervises the time between the execute command and the
command termination, see Figure 389.
execute command
phase A open
close
phase B open
close
phase C open
close
command termination
phase A
command termination
phase B
command termination
phase C
command termination

circuit breaker open


close
tExecutionFB
timer

t1

t1>tExecutionFB, then
long-operation-time in
'cause' is set

* The command termination will be delayed one execution sample.


en05000094_ansi.vsd
ANSI05000094 V1 EN

Figure 389:

tExecutionFB

The parameter tSynchrocheck is used to define the maximum allowed time between the
execute command and the input SYNC_OK to become true. If SYNC_OK=true at the
time the execute command signal is received, the timer "tSynchrocheck" will not start.
The start signal for the synchronizing is obtained if the synchronism-check conditions are
not fulfilled.

854

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

The parameter tSynchronizing is used to define the maximum allowed time between the
start signal for synchronizing and the confirmation that synchronizing is in progress.
execute command
SYNC_OK
tSynchrocheck
t1

START_SY
SY_INPRO
tSynchronizing

t2

t2>tSynchronizing, then
blocked-by-synchronism
check in 'cause' is set

en05000095_ansi.vsd
ANSI05000095 V1 EN

Figure 390:

tSynchroCheck and tSynchronizing

14.3.7

Circuit breaker SXCBR

14.3.7.1

Functionality
The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions and
to perform the control operations, that is, pass all the commands to primary apparatuses in
the form of circuit breakers via binary output boards and to supervise the switching
operation and position.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

855

Section 14
Control
14.3.7.2

1MRK 502 066-UUS A

Function block
SXCBR

BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
BL_CLOSE
BL_UPD
POSOPEN
POSCLOSE
CBOPCAP
TR_OPEN
TR_CLOSE
RS_CNT
EEH_WARN
EEH_ALM
XIN*

XPOS
EXE_OP
EXE_CL
OP_BLKD
CL_BLKD
UPD_BLKD
OPENPOS
CLOSEPOS
TR_POS
CNT_VAL
L_CAUSE
EEHEALTH
CBOPCAP

IEC05000338-3-en.vsd

IEC05000338 V4 EN

Figure 391:

14.3.7.3

Signals
Table 444:
Name

856

SXCBR function block

SXCBR Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

LR_SWI

BOOLEAN

Local/Remote switch indication from switchyard

OPEN

BOOLEAN

Pulsed signal used to immediately open the switch

CLOSE

BOOLEAN

Pulsed signal used to immediately close the switch

BL_OPEN

BOOLEAN

Signal to block the open command

BL_CLOSE

BOOLEAN

Signal to block the close command

BL_UPD

BOOLEAN

Steady signal for block of the position updating

POSOPEN

BOOLEAN

Signal for open position of apparatus from I/O

POSCLOSE

BOOLEAN

Signal for close position of apparatus from I/O

CBOPCAP

INTEGER

Breaker operating capability 1 = None, 2 = O, 3 = CO, 4


= OCO, 5 = COCO, 6+ = More

TR_OPEN

BOOLEAN

Signal for open position of truck from I/O

TR_CLOSE

BOOLEAN

Signal for close position of truck from I/O

RS_CNT

BOOLEAN

Resets the operation counter

EEH_WARN

BOOLEAN

Warning from external equipment

EEH_ALM

BOOLEAN

Alarm from external equipment

XIN

BOOLEAN

Execution information from CSWI

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Table 445:

SXCBR Output signals

Name

14.3.7.4
Table 446:
Name

Type

Description

XPOS

GROUP SIGNAL

Group connection to CSWI for CB

EXE_OP

BOOLEAN

Executes the command for open direction

EXE_CL

BOOLEAN

Executes the command for close direction

OP_BLKD

BOOLEAN

Indication that the function is blocked for open


commands

CL_BLKD

BOOLEAN

Indication that the function is blocked for close


commands

UPD_BLKD

BOOLEAN

Update of position indication is blocked

OPENPOS

BOOLEAN

Apparatus open position

CLOSEPOS

BOOLEAN

Apparatus closed position

TR_POS

INTEGER

Truck position indication

CNT_VAL

INTEGER

Operation counter value

L_CAUSE

INTEGER

Latest value of the error indication during command

EEHEALTH

INTEGER

External equipment health. 1=No warning or alarm,


2=Warning, 3=Alarm

CBOPCAP

INTEGER

Breaker operating capability 1 = None, 2 = O, 3 = CO, 4


= OCO, 5 = COCO, 6+ = More

Settings
SXCBR Non group settings (basic)
Values (Range)

Unit

tStartMove

0.000 - 60.000

0.001

0.100

Supervision time for the apparatus to move


after a command

tIntermediate

0.000 - 60.000

0.001

0.150

Allowed time for intermediate position

AdaptivePulse

Not adaptive
Adaptive

Not adaptive

Output resets when a new correct end position


is reached

tOpenPulse

0.000 - 60.000

0.001

0.200

Output pulse length for open command

tClosePulse

0.000 - 60.000

0.001

0.200

Output pulse length for close command

InitialCount

0 - 20000

Initial number of operations (Initial count value)

14.3.7.5

Step

Default

Description

Operation principle
The Circuit breaker function (SXCBR) is used by other functions such as for example,
switch controller, protection functions, autorecloser function or an IEC 61850 client
residing in another IED or the operator place. This switch function executes commands,
evaluates block conditions and evaluates different time supervision conditions. Only if all
conditions indicate a switch operation to be allowed, the function performs the execution

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

857

Section 14
Control

1MRK 502 066-UUS A

command. In case of erroneous conditions, the function indicates an appropriate "cause"


value, see Table 430.
SXCBR has an operation counter for closing and opening commands. The counter value
can be read remotely from the operator place. The value is reset from local HMI, a binary
input or remotely from the operator place by configuring a signal from the Single Point
Generic Control 8 signals (SPC8GAPC) for example. The health of the external
equipment, the switch, can be monitored according to IEC61850-8-1. The operation
counter functionality and the external equipment health supervision are independent subfunctions of the circuit breaker function.

Local/Remote switch
One binary input signal LR_SWI is included in SXCBR to indicate the local/remote
switch position from switchyard provided via the I/O board. If this signal is set to TRUE
it means that change of position is allowed only from switchyard level. If the signal is set
to FALSE it means that command from IED or higher level is permitted. When the signal
is set to TRUE all commands (for change of position) are rejected, even trip commands
from protection functions are rejected. The functionality of the local/remote switch is
described in Figure 392.

UE
TR

From I/O

Local= Operation at
switch yard level

switchLR
FAL

SE

Remote= Operation at
IED or higher level
en05000096.vsd
IEC05000096 V1 EN

Figure 392:

Local/Remote switch

Blocking principles
SXCBR includes several blocking principles. The basic principle for all blocking signals
is that they will affect commands from all other clients for example, switch controller,
protection functions and autoreclosure.
The blocking possibilities are:

858

Block/deblock for open command. It is used to block operation for open command.
Block/deblock for close command. It is used to block operation for close command.
Update block/deblock of positions. It is used to block the updating of position values.
Other signals related to the position will be reset.
Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is
active, but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

The above blocking outputs are stored in a non-volatile memory.

Substitution
The substitution part in SXCBR is used for manual set of the position and quality of the
switch. The typical use of substitution is that an operator enters a manual value because
that the real process value is erroneous for some reason. SXCBR will then use the
manually entered value instead of the value for positions determined by the process.
It is always possible to make a substitution, independently of the position
indication and the status information of the I/O board. When substitution
is enabled, the other signals related to the position follow the substituted
position. The substituted values are stored in a non-volatile memory. If the
function is blocked or blocked for update when the substitution is
released, the position value is kept the same as the last substitution value,
but the quality is changed to "questionable, old data", indicating that the
value is old and not reliable.

When the position of the SXCBR is substituted, its IEC61850-8-1 data


object is marked as substituted", in addition to the substituted quality, but
the position quality of the connected SCSWI is not dependent on the
substitution indication in the quality, so it does not show that it is derived
from a substituted value.

Time diagrams
There are two timers for supervising of the execute phase, tStartMove and tIntermediate.
tStartMove supervises that the primary device starts moving after the execute output pulse
is sent. tIntermediate defines the maximum allowed time for intermediate position.
Figure 393 explains these two timers during the execute phase.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

859

Section 14
Control

1MRK 502 066-UUS A

AdaptivePulse = TRUE

EXE_CL
Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


"switch-not-start-moving"
attribute in 'cause' is set

tStartMove timer
t1
tStartMove

tIntermediate timer
t2

if t2 > tIntermediate then


"persisting-intermediate-state"
attribute in 'cause' is set

tIntermediate
en05000097.vsd

IEC05000097 V1 EN

Figure 393:

The timers tStartMove and tIntermediate

The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be
sent to the primary equipment. Note that the output pulses for open and close command
can have different pulse lengths. The pulses can also be set to be adaptive with the
configuration parameter AdaptivePulse. Figure 394 shows the principle of the execute
output pulse. The AdaptivePulse parameter will have effect on both execute output pulses.
OPENPOS

CLOSEPOS

AdaptivePulse=FALSE

EXE_CL
tClosePulse

AdaptivePulse=TRUE

EXE_CL
tClosePulse

en05000098.vsd
IEC05000098 V1 EN

Figure 394:

860

Execute output pulse

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.
The execute output pulses are reset when:

the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
If the breaker reaches the final position before the execution pulse time
has elapsed, and AdaptivePulse is not true, the function waits for the end
of the execution pulse before telling the activating function that the
command is completed.

There is one exception from the first item above. If the primary device is in open position
and an open command is executed or if the primary device is in closed position and a close
command is executed. In these cases, with the additional condition that the configuration
parameter AdaptivePulse is true, the execute output pulse is always activated and resets
when tStartMove has elapsed. If the configuration parameter AdaptivePulse is set to false
the execution output remains active until the pulse duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and CLOSEPOS
=1) when a command is executed the execute output pulse resets only
when timer tOpenPulse or tClosePulse has elapsed.
An example of when a primary device is open and an open command is executed is shown
in Figure 395 .

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

861

Section 14
Control

1MRK 502 066-UUS A

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE

EXE_OP
tOpenPulse

AdaptivePulse=TRUE

EXE_OP
tOpenPulse
tStartMove timer

en05000099.vsd
IEC05000099 V1 EN

Figure 395:

Open command with open position indication

14.3.8

Circuit switch SXSWI

14.3.8.1

Functionality
The purpose of Circuit switch (SXSWI) function is to provide the actual status of positions
and to perform the control operations, that is, pass all the commands to primary
apparatuses in the form of disconnectors or grounding switches via binary output boards
and to supervise the switching operation and position.

862

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.3.8.2

Function block
SXSWI
BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
BL_CLOSE
BL_UPD
POSOPEN
POSCLOSE
SWOPCAP
RS_CNT
EEH_WARN
EEH_ALM
XIN

XPOS
EXE_OP
EXE_CL
OP_BLKD
CL_BLKD
UPD_BLKD
OPENPOS
CLOSEPOS
CNT_VAL
L_CAUSE
EEHEALTH
SWOPCAP

IEC05000339-3-en.vsd
IEC05000339 V3 EN

Figure 396:

14.3.8.3

SXSWI function block

Signals
Table 447:
Name

SXSWI Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

LR_SWI

BOOLEAN

Local/Remote switch indication from switchyard

OPEN

BOOLEAN

Pulsed signal used to immediately open the switch

CLOSE

BOOLEAN

Pulsed signal used to immediately close the switch

BL_OPEN

BOOLEAN

Signal to block the open command

BL_CLOSE

BOOLEAN

Signal to block the close command

BL_UPD

BOOLEAN

Steady signal for block of the position updating

POSOPEN

BOOLEAN

Signal for open position of apparatus from I/O

POSCLOSE

BOOLEAN

Signal for close position of apparatus from I/O

SWOPCAP

INTEGER

Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O


and C

RS_CNT

BOOLEAN

Resets the operation counter

EEH_WARN

BOOLEAN

Warning from external equipment

EEH_ALM

BOOLEAN

Alarm from external equipment

XIN

BOOLEAN

Execution information from CSWI

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

863

Section 14
Control

1MRK 502 066-UUS A

Table 448:

SXSWI Output signals

Name

14.3.8.4
Table 449:
Name

Type

Description

XPOS

GROUP SIGNAL

Group connection to CSWI for DIS

EXE_OP

BOOLEAN

Executes the command for open direction

EXE_CL

BOOLEAN

Executes the command for close direction

OP_BLKD

BOOLEAN

Indication that the function is blocked for open


commands

CL_BLKD

BOOLEAN

Indication that the function is blocked for close


commands

UPD_BLKD

BOOLEAN

Update of position indication is blocked

OPENPOS

BOOLEAN

Apparatus open position

CLOSEPOS

BOOLEAN

Apparatus closed position

CNT_VAL

INTEGER

Operation counter value

L_CAUSE

INTEGER

Latest value of the error indication during command

EEHEALTH

INTEGER

External equipment health. 1=No warning or alarm,


2=Warning, 3=Alarm

SWOPCAP

INTEGER

Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O


and C

Settings
SXSWI Non group settings (basic)
Values (Range)

Unit

tStartMove

0.000 - 60.000

0.001

3.000

Supervision time for the apparatus to move


after a command

tIntermediate

0.000 - 60.000

0.001

15.000

Allowed time for intermediate position

AdaptivePulse

Not adaptive
Adaptive

Not adaptive

Output resets when a new correct end position


is reached

tOpenPulse

0.000 - 60.000

0.001

0.200

Output pulse length for open command

tClosePulse

0.000 - 60.000

0.001

0.200

Output pulse length for close command

SwitchType

Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch

Disconnector

Load Break, Disconnector, Grounding Switch,


HS Grounding. Switch

InitialCount

0 - 20000

Initial number of operations (Initial count value)

14.3.8.5

Step

Default

Description

Operation principle
The users of the Circuit switch (SXSWI) are other functions such as for example, switch
controller, protection functions, autorecloser function, or a 61850 client residing in

864

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

another IED or the operator place. SXSWI executes commands, evaluates block
conditions and evaluates different time supervision conditions. Only if all conditions
indicate a switch operation to be allowed, SXSWI performs the execution command. In
case of erroneous conditions, the function indicates an appropriate "cause" value, see
Table 430.
SXSWI has an operation counter for closing and opening commands. The counter value
can be read remotely from the operator place. The value is reset from a binary input or
remotely from the operator place by configuring a signal from the Single Point Generic
Control 8 signals (SPC8GAPC), for example.
Also, the health of the external equipment, the switch, can be monitored according to
IEC61850-8-1.

Local/Remote switch
One binary input signal LR_SWI is included in SXSWI to indicate the local/remote switch
position from switchyard provided via the I/O board. If this signal is set to TRUE it means
that change of position is allowed only from switchyard level. If the signal is set to FALSE
it means that command from IED or higher level is permitted. When the signal is set to
TRUE all commands (for change of position) from internal IED clients are rejected, even
trip commands from protection functions are rejected. The functionality of the local/
remote switch is described in Figure 397.

UE
TR

From I/O

Local= Operation at
switch yard level

switchLR
FAL

SE

Remote= Operation at
IED or higher level
en05000096.vsd
IEC05000096 V1 EN

Figure 397:

Local/Remote switch

Blocking principles
SXSWI includes several blocking principles. The basic principle for all blocking signals
is that they will affect commands from all other clients for example, switch controller,
protection functions and autorecloser.
The blocking possibilities are:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

865

Section 14
Control

1MRK 502 066-UUS A

Block/deblock for open command. It is used to block operation for open command.
Block/deblock for close command. It is used to block operation for close command.
Update block/deblock of positions. It is used to block the updating of position values.
Other signals related to the position will be reset.
Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is
active, but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution
The substitution part in SXSWI is used for manual set of the position and quality of the
switch. The typical use of substitution is that an operator enters a manual value because
the real process value is erroneous of some reason. SXSWI will then use the manually
entered value instead of the value for positions determined by the process.
It is always possible to make a substitution, independently of the position
indication and the status information of the I/O board. When substitution
is enabled, the other signals related to the position follow the substituted
position. The substituted values are stored in a non-volatile memory. If the
function is blocked or blocked for update when the substitution is
released, the position value is kept the same as the last substitution value,
but the quality is changed to "questionable, old data", indicating that the
value is old and not reliable.

When the position of the SXSWI is substituted, its IEC61850-8-1 data


object is marked as substituted", in addition to the substituted quality, but
the position quality of the connected SCSWI is not dependent on the
substitution indication in the quality, so it does not show that it is derived
from a substituted value.

Time diagrams
There are two timers for supervising of the execute phase, tStartMove and tIntermediate.
tStartMove supervises that the primary device starts moving after the execute output pulse
is sent. tIntermediate defines the maximum allowed time for intermediate position.
Figure 398 explains these two timers during the execute phase.

866

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

AdaptivePulse = TRUE

EXE_CL
Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


"switch-not-start-moving"
attribute in 'cause' is set

tStartMove timer
t1
tStartMove

tIntermediate timer
t2

if t2 > tIntermediate then


"persisting-intermediate-state"
attribute in 'cause' is set

tIntermediate
en05000097.vsd

IEC05000097 V1 EN

Figure 398:

The timers tStartMove and tIntermediate

The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be
sent to the primary equipment. Note that the output pulses for open and close command
can have different pulse lengths. The pulses can also be set to be adaptive with the
configuration parameter AdaptivePulse. Figure 399 shows the principle of the execute
output pulse. The AdaptivePulse parameter will have effect on both execute output pulses.
OPENPOS

CLOSEPOS

AdaptivePulse=FALSE

EXE_CL
tClosePulse

AdaptivePulse=TRUE

EXE_CL
tClosePulse

en05000098.vsd
IEC05000098 V1 EN

Figure 399:

Execute output pulse

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

867

Section 14
Control

1MRK 502 066-UUS A

If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.
The execute output pulses are reset when:

the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
If the controlled primary device reaches the final position before the
execution pulse time has elapsed, and AdaptivePulse is not true, the
function waits for the end of the execution pulse before telling the
activating function that the command is completed.

There is one exception from the first item above. If the primary device is in open position
and an open command is executed or if the primary device is in close position and a close
command is executed. In these cases, with the additional condition that the configuration
parameter AdaptivePulse is true, the execute output pulse is always activated and resets
when tStartMove has elapsed. If the configuration parameter AdaptivePulse is set to false
the execution output remains active until the pulse duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and CLOSEPOS
=1) when a command is executed the execute output pulse resets only
when timer tOpenPulse or tClosePulse has elapsed.
An example when a primary device is open and an open command is executed is shown
in Figure 400.

868

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE

EXE_OP
tOpenPulse

AdaptivePulse=TRUE

EXE_OP
tOpenPulse
tStartMove timer

en05000099.vsd
IEC05000099 V1 EN

Figure 400:

Open command with open position indication

14.3.9

Bay reserve QCRSV

14.3.9.1

Functionality
The purpose of the reservation function is primarily to transfer interlocking information
between IEDs in a safe way and to prevent double operation in a bay, switchyard part, or
complete substation.

14.3.9.2

Function block
QCRSV
EXCH_IN
RES_RQ1
RES_RQ2
RES_RQ3
RES_RQ4
RES_RQ5
RES_RQ6
RES_RQ7
RES_RQ8
BLK_RES
OVERRIDE
RES_DATA

RES_GRT1
RES_GRT2
RES_GRT3
RES_GRT4
RES_GRT5
RES_GRT6
RES_GRT7
RES_GRT8
RES_BAYS
ACK_TO_B
RESERVED
EXCH_OUT
IEC05000340-2-en.vsd

IEC05000340 V2 EN

Figure 401:

QCRSV function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

869

Section 14
Control
14.3.9.3

1MRK 502 066-UUS A

Signals
Table 450:
Name

Type

Default

Description

EXCH_IN

INTEGER

Used for exchange signals between different BayRes


blocks

RES_RQ1

BOOLEAN

Signal for apparatus 1 that requests to do a reservation

RES_RQ2

BOOLEAN

Signal for apparatus 2 that requests to do a reservation

RES_RQ3

BOOLEAN

Signal for apparatus 3 that requests to do a reservation

RES_RQ4

BOOLEAN

Signal for apparatus 4 that requests to do a reservation

RES_RQ5

BOOLEAN

Signal for apparatus 5 that requests to do a reservation

RES_RQ6

BOOLEAN

Signal for apparatus 6 that requests to do a reservation

RES_RQ7

BOOLEAN

Signal for apparatus 7 that requests to do a reservation

RES_RQ8

BOOLEAN

Signal for apparatus 8 that requests to do a reservation

BLOCK

BOOLEAN

Reservation is not possible and the output signals are


reset

OVERRIDE

BOOLEAN

Signal to override the reservation

RES_DATA

INTEGER

Reservation data coming from function block ResIn

Table 451:
Name

870

QCRSV Input signals

QCRSV Output signals


Type

Description

RES_GRT1

BOOLEAN

Reservation is made and the apparatus 1 is allowed to


operate

RES_GRT2

BOOLEAN

Reservation is made and the apparatus 2 is allowed to


operate

RES_GRT3

BOOLEAN

Reservation is made and the apparatus 3 is allowed to


operate

RES_GRT4

BOOLEAN

Reservation is made and the apparatus 4 is allowed to


operate

RES_GRT5

BOOLEAN

Reservation is made and the apparatus 5 is allowed to


operate

RES_GRT6

BOOLEAN

Reservation is made and the apparatus 6 is allowed to


operate

RES_GRT7

BOOLEAN

Reservation is made and the apparatus 7 is allowed to


operate

RES_GRT8

BOOLEAN

Reservation is made and the apparatus 8 is allowed to


operate

RES_BAYS

BOOLEAN

Request for reservation of other bays

ACK_TO_B

BOOLEAN

Acknowledge to other bays that this bay is reserved

RESERVED

BOOLEAN

Indicates that the bay is reserved

EXCH_OUT

INTEGER

Used for exchange signals between different BayRes


blocks

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.3.9.4
Table 452:
Name

Settings
QCRSV Non group settings (basic)
Values (Range)

Unit

tCancelRes

0.000 - 60.000

0.001

10.000

Supervision time for canceling the reservation

ParamRequest1

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at selection of


apparatus 1

ParamRequest2

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at selection of


apparatus 2

ParamRequest3

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at selection of


apparatus 3

ParamRequest4

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at selection of


apparatus 4

ParamRequest5

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at selection of


apparatus 5

ParamRequest6

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at selection of


apparatus 6

ParamRequest7

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at selection of


apparatus 7

ParamRequest8

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at selection of


apparatus 8

14.3.9.5

Step

Default

Description

Operation principle
The Bay reserve (QCRSV) function handles the reservation. QCRSV function starts to
operate in two ways. It starts when there is a request for reservation of the own bay or if
there is a request for reservation from another bay. It is only possible to reserve the
function if it is not currently reserved. The signal that can reserve the own bay is the input
signal RES_RQx (x=1-8) coming from switch controller (SCWI). The signals for request
from another bay are the outputs RE_RQ_B and V_RE_RQ from function block RESIN.
These signals are included in signal EXCH_OUT from RESIN and are connected to
RES_DATA in QCRSV.
The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay only
(TRUE) or other bays (FALSE). To reserve the own bay only means that no reservation
request RES_BAYS is created.

Reservation request of own bay


If the reservation request comes from the own bay, the function QCRSV has to know
which apparatus the request comes from. This information is available with the input
signal RES_RQx and parameter ParamRequestx (where x=1-8 is the number of the
requesting apparatus). In order to decide if a reservation request of the current bay can be
permitted QCRSV has to know whether the own bay already is reserved by itself or
another bay. This information is available in the output signal RESERVED.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

871

Section 14
Control

1MRK 502 066-UUS A

If the RESERVED output is not set, the selection is made with the output RES_GRTx
(where x=1-8 is the number of the requesting apparatus), which is connected to switch
controller SCSWI. If the bay already is reserved the command sequence will be reset and
the SCSWI will set the attribute "1-of-n-control" in the "cause" signal.

Reservation of other bays


When the function QCRSV receives a request from an apparatus in the own bay that
requires other bays to be reserved as well, it checks if it already is reserved. If not, it will
send a request to the other bays that are predefined (to be reserved) and wait for their
response (acknowledge). The request of reserving other bays is done by activating the
output RES_BAYS.
When it receives acknowledge from the bays via the input RES_DATA, it sets the output
RES_GRTx (where x=1-8 is the number of the requesting apparatus). If not
acknowledgement from all bays is received within a certain time defined in SCSWI
(tResResponse), the SCSWI will reset the reservation and set the attribute "1-of-n-control"
in the "cause" signal.

Reservation request from another bay


When another bay requests for reservation, the input BAY_RES in corresponding
function block RESIN is activated. The signal for reservation request is grouped into the
output signal EXCH_OUT in RESIN, which is connected to input RES_DATA in
QCRSV. If the bay is not reserved, the bay will be reserved and the acknowledgment from
output ACK_T_B is sent back to the requested bay. If the bay already is reserved the
reservation is kept and no acknowledgment is sent.

Blocking and overriding of reservation


If QCRSV function is blocked (input BLK_RES is set to true) the reservation is blocked.
That is, no reservation can be made from the own bay or any other bay. This can be set, for
example, via a binary input from an external device to prevent operations from another
operator place at the same time.
The reservation function can also be overridden in the own bay with the OVERRIDE input
signal, that is, reserving the own bay without waiting for the external acknowledge.

Bay with more than eight apparatuses


If only one instance of QCRSV is used for a bay that is, use of up to eight apparatuses, the
input EXCH_IN must be set to FALSE.
If there are more than eight apparatuses in the bay there has to be one additional QCRSV.
The two QCRSV functions have to communicate and this is done through the input
EXCH_IN and EXCH_OUT according to Figure 402. If more than one QCRSV are used,
the execution order is very important. The execution order must be in the way that the first
QCRSV has a lower number than the next one.

872

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

QCRSV
EXCH_IN
RES_ GRT1
RES_RQ1 RES_ GRT2
RES_RQ2 RES_ GRT3
RES_RQ3 RES_ GRT4
RES_RQ4 RES_ GRT5
RES_RQ5 RES_ GRT6
RES_RQ6 RES_ GRT7
RES_RQ7 RES_ GRT8
RES_RQ8 RES_ BAYS
BLK_ RES
ACK_TO_B
OVERRIDE RESERVED
RES_ DATA EXCH_ OUT

QCRSV
EXCH_IN
RES_ GRT1
RES_RQ1 RES_ GRT2
RES_RQ2 RES_ GRT3
RES_RQ3 RES_ GRT4
RES_RQ4 RES_ GRT5
RES_RQ5 RES_ GRT6
RES_RQ6 RES_ GRT7
RES_RQ7 RES_ GRT8
RES_RQ8 RES_ BAYS
BLK_ RES
ACK_TO_B
OVERRIDE RESERVED
RES_ DATA EXCH_ OUT

OR

OR

OR

RES_ BAYS

ACK_TO_B

RESERVED

ANSI05000088_2_en.vsd
ANSI05000088 V2 EN

Figure 402:

Connection of two QCRSV function blocks

14.3.10

Reservation input RESIN

14.3.10.1

Functionality
The Reservation input (RESIN) function receives the reservation information from other
bays. The number of instances is the same as the number of involved bays (up to 60
instances are available).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

873

Section 14
Control
14.3.10.2

1MRK 502 066-UUS A

Function block
RESIN1
BAY_ACK
BAY_VAL
BAY_RES

ACK_F_B
ANY_ACK
VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC05000341-2-en.vsd

IEC05000341 V2 EN

Figure 403:

RESIN1 function block

RESIN2
EXCH_IN
BAY_ACK
BAY_VAL
BAY_RES

ACK_F_B
ANY_ACK
VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd

IEC09000807 V1 EN

Figure 404:

14.3.10.3

Signals
Table 453:
Name

RESIN1 Input signals


Type

Default

Description

BAY_ACK

BOOLEAN

Another bay has acknowledged the reservation request


from this bay

BAY_VAL

BOOLEAN

The reservervation and acknowledge signals from


another bay are valid

BAY_RES

BOOLEAN

Request from other bay to reserve this bay

Table 454:
Name

874

RESIN2 function block

RESIN1 Output signals


Type

Description

ACK_F_B

BOOLEAN

All other bays have acknowledged the reservation


request from this bay

ANY_ACK

BOOLEAN

Any other bay has acknowledged the reservation


request from this bay

VALID_TX

BOOLEAN

The reservation and acknowledge signals from other


bays are valid

RE_RQ_B

BOOLEAN

Request from other bay to reserve this bay

V_RE_RQ

BOOLEAN

Check if the request of reserving this bay is valid

EXCH_OUT

INTEGER

Used for exchange signals between different ResIn


blocks

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Table 455:

RESIN2 Input signals

Name

Type

Used for exchange signals between different ResIn


blocks

BAY_ACK

BOOLEAN

Another bay has acknowledged the reservation request


from this bay

BAY_VAL

BOOLEAN

The reservervation and acknowledge signals from


another bay are valid

BAY_RES

BOOLEAN

Request from other bay to reserve this bay

RESIN2 Output signals

Name

Table 457:
Name
FutureUse

Table 458:
Name
FutureUse

14.3.10.5

Description

INTEGER

Table 456:

14.3.10.4

Default

EXCH_IN

Type

Description

ACK_F_B

BOOLEAN

All other bays have acknowledged the reservation


request from this bay

ANY_ACK

BOOLEAN

Any other bay has acknowledged the reservation


request from this bay

VALID_TX

BOOLEAN

The reservation and acknowledge signals from other


bays are valid

RE_RQ_B

BOOLEAN

Request from other bay to reserve this bay

V_RE_RQ

BOOLEAN

Check if the request of reserving this bay is valid

EXCH_OUT

INTEGER

Used for exchange signals between different ResIn


blocks

Settings
RESIN1 Non group settings (basic)
Values (Range)
Bay in use
Bay future use

Unit
-

Step
-

Default
Bay in use

Description
The bay for this ResIn block is for future use

RESIN2 Non group settings (basic)


Values (Range)
Bay in use
Bay future use

Unit
-

Step
-

Default
Bay in use

Description
The bay for this ResIn block is for future use

Operation principle
The reservation input (RESIN) function is based purely on Boolean logic conditions. The
logic diagram in Figure 405 shows how the output signals are created. The inputs of the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

875

Section 14
Control

1MRK 502 066-UUS A

function block are connected to a receive function block representing signals transferred
over the station bus from another bay.
EXCH_IN

INT
BIN

ACK_F_B

AND
FutureUse

OR

BAY_ACK

ANY_ACK

OR

VALID_TX

AND
BAY_VAL

OR
RE_RQ_B

OR

BAY_RES

AND
V _RE_RQ

OR

BIN

EXCH_OUT
INT

INT..Integer
BIN..Binary

en05000089_ansi.vsd

ANSI05000089 V1 EN

Figure 405:

Logic diagram for RESIN

Figure 406 describes the principle of the data exchange between all RESIN modules in the
current bay. There is one RESIN function block per "other bay" used in the reservation
mechanism. The output signal EXCH_OUT in the last RESIN functions are connected to
the module bay reserve (QCRSV) that handles the reservation function in the own bay.

876

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

RESIN
BAY_ACK ACK_F_B
BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT

Bay 1

Bay 2

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT

Bay n

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT

QCRSV
RES_DATA

en05000090.vsd
IEC05000090 V2 EN

Figure 406:

Diagram of the chaining principle for RESIN

14.4

Voltage control

14.4.1

Identification
Function description

14.4.2

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Tap changer control and supervision, 6


binary inputs

TCMYLTC

84

Tap changer control and supervision, 32


binary inputs

TCLYLTC

84

Functionality
Tap changer control and supervision, 6 binary inputs TCMYLTC (84) as well as Tap
changer control and supervision, 32 binary inputs TCLYLTC (84) are is used for control
of power transformers with a on-load tap changer. The functions provide automatic

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

877

Section 14
Control

1MRK 502 066-UUS A

regulation of the voltage on the secondary side of transformers or alternatively on a load


point further out in the network.
Control of a single transformer, as well as control of up to eight transformers in parallel is
possible. For parallel control of power transformers, three alternative methods are
available, the master-follower method, the circulating current method and the reverse
reactance method. The first two methods require exchange of information between the
parallel transformers and this is provided for within IEC 61850-8-1.
Voltage control includes many extra features such as possibility of to avoid simultaneous
tapping of parallel transformers, hot stand by regulation of a transformer in a group which
regulates it to a correct tap position even though the LV CB is open, compensation for a
possible capacitor bank on the LV side bay of a transformer, extensive tap changer
monitoring including contact wear and hunting detection, monitoring of the power flow
in the transformer so that for example, the voltage control can be blocked if the power
reverses etc.

14.4.3

Tap changer control and supervision, 6 binary inputs TCMYLTC


(84) and TCLYLTC (84)
The Tap changer control and supervision, 6 binary inputs (TCMYLTC, 84) and 32 binary
inputs TCLYLTC (84) gives the tap commands to the tap changer, and supervises that
commands are carried through correctly. It has built-in extensive possibilities for tap
changer position measurement, as well as supervisory and monitoring features. This is
used in the voltage control and can also give information about tap position to the
transformer differential protection.

14.4.3.1

Operation principle
Reading of tap changer position
The tap changer position can be received to the tap changer control and supervision, 6
binary inputs TCMYLTC (84) or 32 binary inputs TCLYLTC (84) function block in the
following ways:
1.
2.
3.

Via binary input signals, one per tap position (max. 6 or 32 positions).
Via coded binary (Binary), binary coded decimal (BCD) signals, or Gray coded
binary signals.
Via a mA input signal.

Via binary input signals, one per tap position


In this option, each tap position has a separate contact that is hard wired to a binary input
in the IED. Via the Signal Matrix tool in PCM600, the contacts on the binary input card
are then directly connected to the
878

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

inputs B1 B6 on TCMYLTC (84) function


or inputs B1 B32 on TCLYLTC (84) function.

Via coded binary (Binary), binary coded decimal (BCD) signals or Gray coded
binary signals
The Tap changer control and supervision, (TCMYLTC or TCLYLTC ,84) decodes binary
data from up to six binary inputs to an integer value. The input pattern may be decoded
either as BIN, BCD or GRAY format depending on the setting of the parameter
CodeType.
It is also possible to use even parity check of the input binary signal. Whether the parity
check shall be used or not is set with the setting parameter UseParity.
The input BIERR on (TCMYLTC or TCLYLTC , 84) can be used as supervisory input for
indication of any external error ( Binary Input Module) in the system for reading of tap
changer position. Likewise, the input OUTERR can be used as a supervisory of the Binary
Input Module.
The truth table (see table 459) shows the conversion for Binary, Binary Coded Decimal,
and Gray coded signals.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

879

Section 14
Control

1MRK 502 066-UUS A

Table 459:

Binary, BCD and Gray conversion

IEC06000522 V1 EN

The Gray code conversion above is not complete and therefore the conversion from
decimal numbers to Gray code is given below.

880

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Table 460:

Gray code conversion

IEC06000523 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

881

Section 14
Control

1MRK 502 066-UUS A

Via a mA input signal


Any of the six inputs on the mA card (MIM) can be used for the purpose of tap changer
position reading connected to the Tap changer control and supervision, 6 binary inputs
TCMYLTC (84) or 32 binary inputs TCLYLTC (84).
The measurement of the tap changer position via MIM module is based on the principle
that the specified mA input signal range (usually 4-20 mA) is divided into N intervals
corresponding to the number of positions available on the tap changer. All mA values
within one interval are then associated with one tap changer position value.
The number of available tap changer positions N is defined by the setting parameters
LowVoltTap and HighVoltTap, which define the tap position for lowest voltage and
highest voltage respectively.

14.4.4

Function block
TCMYLTC (84)
YLTCIN*
VRAISE
TCINPROG
VLOWER
INERR
HIPOSAL
RESETERR
LOPOSAL
OUTERR
POSERRAL
RS_CLCNT
CMDERRAL
RS_OPCNT
TCERRAL
PARITY
POSOUT
BIERR
CONVERR
B1
NEWPOS
B2
HIDIFPOS
B3
INVALPOS
B4
TCPOS
B5
YLTCOUT
B6
MA
ANSI07000038-2-en.vsd
ANSI07000038 V2 EN

Figure 407:

882

TCMYLTC (84) function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

TCLYLTC (84)
YLTCIN*
VRAISE
TCINPROG
VLOWER
INERR
HIPOSAL
RESETERR
LOPOSAL
OUTERR
POSERRAL
RS_CLCNT
CMDERRAL
RS_OPCNT
TCERRAL
PARITY
POSOUT
BIERR
CONVERR
B1
NEWPOS
B2
HIDIFPOS
B3
INVALPOS
B4
TCPOS
B5
YLTCOUT
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
B16
B17
B18
B19
B20
B21
B22
B23
B24
B25
B26
B27
B28
B29
B30
B31
B32
MA
ANSI07000037-2-en.vsd
ANSI07000037 V2 EN

Figure 408:

14.4.5

TCLYLTC (84) function block

Signals
Table 461:
Name

TCMYLTC (84) Input signals


Type

Default

Description

YLTCIN

GROUP
SIGNAL

Input group connection for YLTC

TCINPROG

BOOLEAN

Indication that tap is moving

INERR

BOOLEAN

Supervision signal of the input board

RESETERR

BOOLEAN

Reset of command and tap error

OUTERR

BOOLEAN

Supervision off the digital output board

RS_CLCNT

BOOLEAN

Reset of the contact life counter

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

883

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

RS_OPCNT

BOOLEAN

Resets the operation counter

PARITY

BOOLEAN

Parity bit from tap changer for the tap position

BIERR

BOOLEAN

Error bit from tap changer for the tap position

B1

BOOLEAN

Bit 1 from tap changer for the tap position

B2

BOOLEAN

Bit 2 from tap changer for the tap position

B3

BOOLEAN

Bit 3 from tap changer for the tap position

B4

BOOLEAN

Bit 4 from tap changer for the tap position

B5

BOOLEAN

Bit 5 from tap changer for the tap position

B6

BOOLEAN

Bit 6 from tap changer for the tap position

MA

REAL

mA from tap changer for the tap position

Table 462:
Name

TCMYLTC (84) Output signals


Type

Description

VRAISE

BOOLEAN

Raise voltage command to tap changer

VLOWER

BOOLEAN

Lower voltage command to tap changer

HIPOSAL

BOOLEAN

Alarm for tap in highest volt position

LOPOSAL

BOOLEAN

Alarm for tap in lowest volt position

POSERRAL

BOOLEAN

Alarm that indicates a problem with the position


indication

CMDERRAL

BOOLEAN

Alarm for a command without an expected position


change

TCERRAL

BOOLEAN

Alarm for none or illegal tap position change

POSOUT

BOOLEAN

Tap position outside min and max position

CONVERR

BOOLEAN

General tap position conversion error

NEWPOS

BOOLEAN

A new tap position is reported, 1 sec pulse

HIDIFPOS

BOOLEAN

Tap position has changed more than one position

INVALPOS

BOOLEAN

Last position change was an invalid change

YLTCOUT

GROUP SIGNAL

Group connection to ATCCIN

Table 463:
Name

TCLYLTC (84) Input signals


Type

Default

Description

YLTCIN

GROUP
SIGNAL

Input group connection for YLTC

TCINPROG

BOOLEAN

Indication that tap is moving

INERR

BOOLEAN

Supervision signal of the input board

RESETERR

BOOLEAN

Reset of command and tap error

Table continues on next page

884

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Type

Default

Description

OUTERR

BOOLEAN

Supervision off the digital output board

RS_CLCNT

BOOLEAN

Reset of the contact life counter

RS_OPCNT

BOOLEAN

Resets the operation counter

PARITY

BOOLEAN

Parity bit from tap changer for the tap position

BIERR

BOOLEAN

Error bit from tap changer for the tap position

B1

BOOLEAN

Bit 1 from tap changer for the tap position

B2

BOOLEAN

Bit 2 from tap changer for the tap position

B3

BOOLEAN

Bit 3 from tap changer for the tap position

B4

BOOLEAN

Bit 4 from tap changer for the tap position

B5

BOOLEAN

Bit 5 from tap changer for the tap position

B6

BOOLEAN

Bit 6 from tap changer for the tap position

B7

BOOLEAN

Bit 7 from tap changer for the tap position

B8

BOOLEAN

Bit 8 from tap changer for the tap position

B9

BOOLEAN

Bit 9 from tap changer for the tap position

B10

BOOLEAN

Bit 10 from tap changer for the tap position

B11

BOOLEAN

Bit 11 from tap changer for the tap position

B12

BOOLEAN

Bit 12 from tap changer for the tap position

B13

BOOLEAN

Bit 13 from tap changer for the tap position

B14

BOOLEAN

Bit 14 from tap changer for the tap position

B15

BOOLEAN

Bit 15 from tap changer for the tap position

B16

BOOLEAN

Bit 16 from tap changer for the tap position

B17

BOOLEAN

Bit 17 from tap changer for the tap position

B18

BOOLEAN

Bit 18 from tap changer for the tap position

B19

BOOLEAN

Bit 19 from tap changer for the tap position

B20

BOOLEAN

Bit 20 from tap changer for the tap position

B21

BOOLEAN

Bit 21 from tap changer for the tap position

B22

BOOLEAN

Bit 22 from tap changer for the tap position

B23

BOOLEAN

Bit 23 from tap changer for the tap position

B24

BOOLEAN

Bit 24 from tap changer for the tap position

B25

BOOLEAN

Bit 25 from tap changer for the tap position

B26

BOOLEAN

Bit 26 from tap changer for the tap position

B27

BOOLEAN

Bit 27 from tap changer for the tap position

B28

BOOLEAN

Bit 28 from tap changer for the tap position

B29

BOOLEAN

Bit 29 from tap changer for the tap position

B30

BOOLEAN

Bit 30 from tap changer for the tap position

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

885

Section 14
Control

1MRK 502 066-UUS A

Name

Default

Description

BOOLEAN

Bit 31 from tap changer for the tap position

B32

BOOLEAN

Bit 32 from tap changer for the tap position

MA

REAL

mA from tap changer for the tap position

Table 464:
Name

TCLYLTC (84) Output signals


Type

Description

VRAISE

BOOLEAN

Raise voltage command to tap changer

VLOWER

BOOLEAN

Lower voltage command to tap changer

HIPOSAL

BOOLEAN

Alarm for tap in highest volt position

LOPOSAL

BOOLEAN

Alarm for tap in lowest volt position

POSERRAL

BOOLEAN

Alarm that indicates a problem with the position


indication

CMDERRAL

BOOLEAN

Alarm for a command without an expected position


change

TCERRAL

BOOLEAN

Alarm for none or illegal tap position change

POSOUT

BOOLEAN

Tap position outside min and max position

CONVERR

BOOLEAN

General tap position conversion error

NEWPOS

BOOLEAN

A new tap position is reported, 1 sec pulse

HIDIFPOS

BOOLEAN

Tap position has changed more than one position

INVALPOS

BOOLEAN

Last position change was an invalid change

CNT_VAL

INTEGER

Number of operations on tap changer

TCPOS

INTEGER

Integer value corresponding to actual tap position

YLTCOUT

GROUP SIGNAL

Group connection to ATCCIN

Table 465:
Name
BLOCK

Table 466:
Name

886

Type

B31

VCTRRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of function

VCTRRCV Output signals


Type

Description

VCTR_REC

GROUP SIGNAL

Received data from horizontal communication

COMVALID

BOOLEAN

Communication is valid

DATVALID

BOOLEAN

Data valid

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.4.6
Table 467:
Name

Settings
TCMYLTC (84) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

tTCTimeout

1 - 120

Tap changer constant time-out

tPulseDur

0.5 - 10.0

0.1

1.5

Raise/lower command output pulse duration

Table 468:
Name

TCMYLTC (84) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

LowVoltTap

1 - 63

Tap position for lowest voltage

HighVoltTap

1 - 63

33

Tap position for highest voltage

mALow

0.000 - 25.000

mA

0.001

4.000

mA for lowest voltage tap position

mAHigh

0.000 - 25.000

mA

0.001

20.000

mA for highest voltage tap position

CodeType

BIN
BCD
Gray
SINGLE
mA

BIN

Type of code conversion

UseParity

Disabled
Enabled

Disabled

Enable parity check

tStable

1 - 60

Time after position change before the value is


accepted

CLFactor

1.0 - 3.0

0.1

2.0

Adjustable factor for contact life function

InitCLCounter

0 - 9999999

250000

CL counter start value

EnabTapCmd

Disabled
Enabled

Enabled

Enable commands to tap changer

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

Table 469:
Name

TCLYLTC (84) Group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

tTCTimeout

1 - 120

Tap changer constant time-out

tPulseDur

0.5 - 10.0

0.1

1.5

Raise/lower command output pulse duration

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

887

Section 14
Control

Table 470:
Name

1MRK 502 066-UUS A

TCLYLTC (84) Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

LowVoltTap

1 - 63

Tap position for lowest voltage

HighVoltTap

1 - 63

33

Tap position for highest voltage

mALow

0.000 - 25.000

mA

0.001

4.000

mA for lowest voltage tap position

mAHigh

0.000 - 25.000

mA

0.001

20.000

mA for highest voltage tap position

CodeType

BIN
BCD
Gray
SINGLE
mA

BIN

Type of code conversion

UseParity

Disabled
Enabled

Disabled

Enable parity check

tStable

1 - 60

Time after position change before the value is


accepted

CLFactor

1.0 - 3.0

0.1

2.0

Adjustable factor for contact life function

InitCLCounter

0 - 9999999

250000

CL counter start value

EnabTapCmd

Disabled
Enabled

Enabled

Enable commands to tap changer

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

14.4.7

Monitored data
Table 471:
Name
TCPOS

Table 472:
Name

Type
INTEGER

Values (Range)
-

Unit
-

Description
Integer value corresponding to
actual tap position

TCMYLTC (84) Monitored data


Type

Values (Range)

Unit

Description

CNT_VAL

INTEGER

Number of operations on tap


changer

CLCNT_VAL

REAL

Remaining number of
operations at rated load

TCPOS

INTEGER

Integer value corresponding to


actual tap position

Table 473:
Name
TCPOS

888

TCMYLTC (84) Monitored data

TCLYLTC (84) Monitored data


Type
INTEGER

Values (Range)
-

Unit
-

Description
Integer value corresponding to
actual tap position

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.4.8

Operation principle

Tap changer control and supervision

TCMYLTC (84), 6 binary inputs


TCLYLTC (84), 32 binary inputs

TCMYLTC (84) and TCLYLTC (84) also serve the purpose of giving information about
tap position to the transformer differential protection T2WPDIF (87T) and T3WPDIF
(87T).

14.4.9

Technical data
Table 474:

TCMYLTC (84) and TLCYLTC (84) technical data

Function

Range or value

Accuracy

Transformer reactance

(0.1200.0), primary

Time delay for lower command


when fast step down mode is
activated

(1.0100.0) s

Voltage control set voltage

(85.0120.0)% of VBase

0.25 % of Vn

Outer voltage deadband

(0.29.0)% of VBase

Inner voltage deadband

(0.19.0)% of VBase

Upper limit of busbar voltage

(80180)% of VBase

0.5% of Vn

Lower limit of busbar voltage

(70120)% of VBase

0.5% of Vn

Undervoltage block level

(50120)% of VBase

0.5% of Vn

Time delay (long) for automatic


control commands

(31000) s

0.2% or 600 ms
whichever is greater

Time delay (short) for automatic


control commands

(11000) s

0.2% or 600 ms
whichever is greater

Minimum operating time in


inverse mode

(3120) s

0.2% or 600 ms
whichever is greater

Line resistance

(0.00150.00), primary

Line reactance

(-150.00150.00), primary

Load voltage adjustment


constants

(-20.020.0)% of VBase

Load voltage auto correction

(-20.020.0)% of VBase

Duration time for the reverse


action block signal

(306000) s

0.2% or 600 ms
whichever is greater

Current limit for reverse action


block

(0100)% of I1Base

Overcurrent block level

(5250)% of I1Base

1.0% of In at IIn
1.0% of I at I>In

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

889

Section 14
Control

1MRK 502 066-UUS A

Function

Range or value

Accuracy

Level for number of counted raise/


lower within one hour

(030) operations/hour

Level for number of counted raise/


lower within 24 hours

(0100) operations/day

Time window for hunting alarm

(1120) minutes

Hunting detection alarm, max


operations/window

(330) operations/window

Alarm level of active power in


forward and reverse direction at
(10-200)% of Sn and (85-120)% of
VBase

(-9999.999999.99) MW

1.0% of Sn

Alarm level of reactive power in


forward and reverse direction at
(10-200)% of Sn and (85-120)% of
VBase

(-9999.999999.99) MVAr

1.0% of Sn

Time delay for alarms from power


supervision

(16000) s

0.2% or 600 ms
whichever is greater

Tap position for lowest and


highest voltage

(163)

mA for lowest and highest voltage


tap position

(0.00025.000) mA

Type of code conversion

BIN, BCD, GRAY, SINGLE, mA

Time after position change before


the value is accepted

(160) s

0.2% or 200 ms
whichever is greater

Tap changer constant time-out

(1120) s

0.2% or 200 ms
whichever is greater

Raise/lower command output


pulse duration

(0.510.0) s

0.2% or 200 ms
whichever is greater

14.5

Logic rotating switch for function selection and LHMI


presentation SLGAPC

14.5.1

Identification
Function description
Logic rotating switch for function
selection and LHMI presentation

890

IEC 61850
identification
SLGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.5.2

Functionality
The logic rotating switch for function selection and LHMI presentation SLGAPC (or the
selector switch function block) is used to get an enhanced selector switch functionality
compared to the one provided by a hardware selector switch. Hardware selector switches
are used extensively by utilities, in order to have different functions operating on pre-set
values. Hardware switches are however sources for maintenance issues, lower system
reliability and an extended purchase portfolio. The selector switch function eliminates all
these problems.

14.5.3

Function block
SLGAPC
BLOCK
PSTO
UP
DOWN

^P01
^P02
^P03
^P04
^P05
^P06
^P07
^P08
^P09
^P10
^P11
^P12
^P13
^P14
^P15
^P16
^P17
^P18
^P19
^P20
^P21
^P22
^P23
^P24
^P25
^P26
^P27
^P28
^P29
^P30
^P31
^P32
SWPOSN
IEC14000005-1-en.vsd

IEC14000005 V1 EN

Figure 409:

SLGAPC function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

891

Section 14
Control
14.5.4

1MRK 502 066-UUS A

Signals
Table 475:
Name

SLGAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

UP

BOOLEAN

Binary "UP" command

DOWN

BOOLEAN

Binary "DOWN" command

Table 476:

SLGAPC Output signals

Name

Type

Description

P01

BOOLEAN

Selector switch position 1

P02

BOOLEAN

Selector switch position 2

P03

BOOLEAN

Selector switch position 3

P04

BOOLEAN

Selector switch position 4

P05

BOOLEAN

Selector switch position 5

P06

BOOLEAN

Selector switch position 6

P07

BOOLEAN

Selector switch position 7

P08

BOOLEAN

Selector switch position 8

P09

BOOLEAN

Selector switch position 9

P10

BOOLEAN

Selector switch position 10

P11

BOOLEAN

Selector switch position 11

P12

BOOLEAN

Selector switch position 12

P13

BOOLEAN

Selector switch position 13

P14

BOOLEAN

Selector switch position 14

P15

BOOLEAN

Selector switch position 15

P16

BOOLEAN

Selector switch position 16

P17

BOOLEAN

Selector switch position 17

P18

BOOLEAN

Selector switch position 18

P19

BOOLEAN

Selector switch position 19

P20

BOOLEAN

Selector switch position 20

P21

BOOLEAN

Selector switch position 21

P22

BOOLEAN

Selector switch position 22

P23

BOOLEAN

Selector switch position 23

P24

BOOLEAN

Selector switch position 24

P25

BOOLEAN

Selector switch position 25

P26

BOOLEAN

Selector switch position 26

Table continues on next page


892

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

14.5.5
Table 477:
Name

Type

Description

P27

BOOLEAN

Selector switch position 27

P28

BOOLEAN

Selector switch position 28

P29

BOOLEAN

Selector switch position 29

P30

BOOLEAN

Selector switch position 30

P31

BOOLEAN

Selector switch position 31

P32

BOOLEAN

Selector switch position 32

SWPOSN

INTEGER

Switch position (integer)

Settings
SLGAPC Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

NrPos

2 - 32

32

Number of positions in the switch

OutType

Pulsed
Steady

Steady

Output type, steady or pulse

tPulse

0.000 - 60.000

0.001

0.200

Operate pulse duration, in [s]

tDelay

0.000 - 60000.000

0.010

0.000

Time delay on the output, in [s]

StopAtExtremes

Disabled
Enabled

Disabled

Stop when min or max position is reached

14.5.6

Monitored data
Table 478:
Name
SWPOSN

14.5.7

SLGAPC Monitored data


Type
INTEGER

Values (Range)
-

Unit
-

Description
Switch position (integer)

Operation principle
The logic rotating switch for function selection and LHMI presentation (SLGAPC)
function has two operating inputs UP and DOWN. When a signal is received on the UP
input, the function will activate the output next to the present activated output, in
ascending order (for example if the present activated output is P03 and one activates the
UP input then the output P04 will be activated). When a signal is received on the DOWN
input, the function will activate the output next to the present activated output, in
descending order (for example if the present activated output is P03 and one activates the
DOWN input then the output P02 will be activated). Depending on the output settings the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

893

Section 14
Control

1MRK 502 066-UUS A

output signals can be steady or pulsed. In case of steady signals, the output will be active
till the time it receives next operation of UP/DOWN inputs. Also, depending on the
settings one can have a time delay between the UP or DOWN activation signal positive
front and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the desired
position directly (without activating the intermediate positions), either locally or
remotely, using a select before execute dialog. One can block the function operation, by
activating the BLOCK input. In this case, the present position will be kept and further
operation will be blocked. The operator place (local or remote) is specified through the
PSTO input. If any operation is allowed the signal INTONE from the Fixed signal
function block can be connected. SLGAPC function block has also an integer value
output, that generates the actual position number. The positions and the block names are
fully settable by the user. These names will appear in the menu, so the user can see the
position names instead of a number.

14.5.7.1

Graphical display
There are two possibilities for SLGAPC

if it is used just for the monitoring, the switches will be listed with their actual position
names, as defined by the user (max. 13 characters).
if it is used for control, the switches will be listed with their actual positions, but only
the first three letters of the name will be used.

In both cases, the switch full name will be shown, but the user has to redefine it when
building the Graphical Display Editor, under the "Caption". If used for the control, the
following sequence of commands will ensure:

894

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Change to the "Switches" page


of the SLD by left-right arrows.
Select switch by up-down
arrows

../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
Damage control
DAL

Control
Single Line Diagram
Commands

Control
Measurements
Events
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language

Open

Close

../Control/SLD/Switch
SMBRREC control
WFM

Select switch. Press the


Open or Close key. A
dialog box appears.

Pilot setup
OFF

P: Disc

The pos will not be modified


(outputs will not be activated) until
you press the E-button for O.K.

OK

N: Disc Fe
Cancel

../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
Damage control
DFW
ANSI06000421-2-en.vsd
ANSI06000421 V2 EN

Figure 410:
Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.

14.6

Selector mini switch VSGAPC

14.6.1

Identification
Function description
Selector mini switch

IEC 61850
identification
VSGAPC

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

895

Section 14
Control
14.6.2

1MRK 502 066-UUS A

Functionality
The Selector mini switch VSGAPC function block is a multipurpose function used for a
variety of applications, as a general purpose switch.
VSGAPC can be controlled from the menu, from a symbol on the single line diagram
(SLD) on the local HMI or from Binary inputs

14.6.3

Function block
VSGAPC
BLOCK
PSTO
IPOS1
IPOS2

BLOCKED
POSITION
POS1
POS2
CMDPOS12
CMDPOS21
IEC14000066-1-en.vsd

IEC14000066 V1 EN

Figure 411:

14.6.4

Signals
Table 479:
Name

VSGAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

IPOS1

BOOLEAN

Position 1 indicating input

IPOS2

BOOLEAN

Position 2 indicating input

Table 480:
Name

896

VSGAPC function block

VSGAPC Output signals


Type

Description

BLOCKED

BOOLEAN

The function is active but the functionality is blocked

POSITION

INTEGER

Position indication, integer

POS1

BOOLEAN

Position 1 indication, logical signal

POS2

BOOLEAN

Position 2 indication, logical signal

CMDPOS12

BOOLEAN

Execute command from position 1 to position 2

CMDPOS21

BOOLEAN

Execute command from position 2 to position 1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.6.5
Table 481:
Name

Settings
VSGAPC Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

CtlModel

Dir Norm
SBO Enh

Dir Norm

Specifies the type for control model according


to IEC 61850

Mode

Steady
Pulsed

Pulsed

Operation mode

tSelect

0.000 - 60.000

0.001

30.000

Max time between select and execute signals

tPulse

0.000 - 60.000

0.001

0.200

Command pulse lenght

14.6.6

Operation principle
Selector mini switch (VSGAPC) function can be used for double purpose, in the same way
as switch controller (SCSWI) functions are used:

for indication on the single line diagram (SLD). Position is received through the
IPOS1 and IPOS2 inputs and distributed in the configuration through the POS1 and
POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and distributed in the
configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command from
the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command from
the local HMI when the SLD is displayed and the object is chosen.
It is important for indication in the SLD that the a symbol is associated
with a controllable object, otherwise the symbol won't be displayed on the
screen. A symbol is created and configured in GDE tool in PCM600.

The PSTO input is connected to the Local remote switch to have a selection of operators
place, operation from local HMI (Local) or through IEC 61850 (Remote). An INTONE
connection from Fixed signal function block (FXDSIGN) will allow operation from local
HMI.
As it can be seen, both indications and commands are done in double-bit representation,
where a combination of signals on both inputs/outputs generate the desired result.
The following table shows the relationship between IPOS1/IPOS2 inputs and the name of
the string that is shown on the SLD. The value of the strings are set in PST.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

897

Section 14
Control

1MRK 502 066-UUS A

IPOS1

IPOS2

Name of displayed string

Default string value

PosUndefined

P00

Position1

P01

Position2

P10

PosBadState

P11

14.7

Generic communication function for Double Point


indication DPGAPC

14.7.1

Identification
Function description
Generic communication function for
Double Point indication

14.7.2

IEC 61850
identification
DPGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
Generic communication function for Double Point indication DPGAPC function block is
used to send double indications to other systems, equipment or functions in the substation
through IEC 61850-8-1 or other communication protocols. It is especially used in the
interlocking station-wide logics.

14.7.3

Function block

IEC13000081 V1 EN

Figure 412:

898

DPGAPC function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.7.4

Signals
Table 482:

DPGAPC Input signals

Name

Type

Description

BOOLEAN

Open indication

CLOSE

BOOLEAN

Close indication

VALID

BOOLEAN

Valid indication

Table 483:

DPGAPC Output signals

Name
POSITION

14.7.5

Default

OPEN

Type
INTEGER

Description
Double point indication

Settings
The function does not have any parameters available in the local HMI or PCM600.

14.7.6

Operation principle
When receiving the input signals, DPGAPC sends the signals over IEC 61850-8-1 to the
systems, equipment or functions that requests and thus subscribes on these signals. To be
able to get the signals into other systems, equipment or functions, one must use other tools,
described in the Engineering manual and define which function block in which systems,
equipment or functions should receive this information.

14.8

Single point generic control 8 signals SPC8GAPC

14.8.1

Identification
Function description
Single point generic control 8 signals

14.8.2

IEC 61850
identification
SPC8GAPC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The Single point generic control 8 signals SPC8GAPC function block is a collection of 8
single point commands that can be used for direct commands for example reset of LED's

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

899

Section 14
Control

1MRK 502 066-UUS A

or putting IED in "ChangeLock" state from remote. In this way, simple commands can be
sent directly to the IED outputs, without confirmation. Confirmation (status) of the result
of the commands is supposed to be achieved by other means, such as binary inputs and
SPGAPC function blocks. The commands can be pulsed or steady with a settable pulse
time.

14.8.3

Function block
SPC8GAPC
BLOCK
PSTO

^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
ANSI07000143-3-en.vsd

ANSI07000143 V1 EN

Figure 413:

14.8.4

Signals
Table 484:
Name

SPC8GAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Blocks the function operation

PSTO

INTEGER

Operator place selection

Table 485:
Name

900

SPC8GAPC function block

SPC8GAPC Output signals


Type

Description

OUT1

BOOLEAN

Command output 1

OUT2

BOOLEAN

Command output 2

OUT3

BOOLEAN

Command output 3

OUT4

BOOLEAN

Command output 4

OUT5

BOOLEAN

Command output 5

OUT6

BOOLEAN

Command output 6

OUT7

BOOLEAN

Command output 7

OUT8

BOOLEAN

Command output 8

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.8.5
Table 486:
Name

Settings
SPC8GAPC Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PulseMode1

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for output 1

tPulse1

0.01 - 6000.00

0.01

0.10

Pulse time output 1

PulseMode2

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for output 2

tPulse2

0.01 - 6000.00

0.01

0.10

Pulse time output 2

PulseMode3

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for output 3

tPulse3

0.01 - 6000.00

0.01

0.10

Pulse time output 3

PulseMode4

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for output 4

tPulse4

0.01 - 6000.00

0.01

0.10

Pulse time output 4

PulseMode5

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for output 5

tPulse5

0.01 - 6000.00

0.01

0.10

Pulse time output 5

PulseMode6

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for output 6

tPulse6

0.01 - 6000.00

0.01

0.10

Pulse time output 6

PulseMode7

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for output 7

tPulse7

0.01 - 6000.00

0.01

0.10

Pulse time output 7

PulseMode8

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for output 8

tPulse8

0.01 - 6000.00

0.01

0.10

Pulse time output 8

14.8.6

Operation principle
The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the eight
outputs is activated based on the command sent from the operator place selected. The
settings Latchedx and tPulsex (where x is the respective output) will determine if the
signal will be pulsed (and how long the pulse is) or latched (steady). BLOCK will block
the operation of the function in case a command is sent, no output will be activated.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

901

Section 14
Control

1MRK 502 066-UUS A

PSTO is the universal operator place selector for all control functions.
Although, PSTO can be configured to use LOCAL or ALL operator
places only, REMOTE operator place is used in SPC8GAPC function.

14.9

AutomationBits, command function for DNP3.0


AUTOBITS

14.9.1

Identification
Function description
AutomationBits, command function for
DNP3

14.9.2

IEC 61850
identification
AUTOBITS

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
AutomationBits function for DNP3 (AUTOBITS) is used within PCM600 to get into the
configuration of the commands coming through the DNP3 protocol. The AUTOBITS
function plays the same role as functions GOOSEBINRCV (for IEC 61850) and
MULTICMDRCV (for LON).

902

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.9.3

Function block
AUTOBITS
BLOCK
PSTO

^CMDBIT1
^CMDBIT2
^CMDBIT3
^CMDBIT4
^CMDBIT5
^CMDBIT6
^CMDBIT7
^CMDBIT8
^CMDBIT9
^CMDBIT10
^CMDBIT11
^CMDBIT12
^CMDBIT13
^CMDBIT14
^CMDBIT15
^CMDBIT16
^CMDBIT17
^CMDBIT18
^CMDBIT19
^CMDBIT20
^CMDBIT21
^CMDBIT22
^CMDBIT23
^CMDBIT24
^CMDBIT25
^CMDBIT26
^CMDBIT27
^CMDBIT28
^CMDBIT29
^CMDBIT30
^CMDBIT31
^CMDBIT32
IEC09000925-1-en.vsd

IEC09000925 V1 EN

Figure 414:

14.9.4

AUTOBITS function block

Signals
Table 487:
Name

AUTOBITS Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

Table 488:
Name

AUTOBITS Output signals


Type

Description

CMDBIT1

BOOLEAN

Command out bit 1

CMDBIT2

BOOLEAN

Command out bit 2

CMDBIT3

BOOLEAN

Command out bit 3

CMDBIT4

BOOLEAN

Command out bit 4

CMDBIT5

BOOLEAN

Command out bit 5

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

903

Section 14
Control

1MRK 502 066-UUS A

Name

14.9.5
Table 489:
Name
Operation

904

Type

Description

CMDBIT6

BOOLEAN

Command out bit 6

CMDBIT7

BOOLEAN

Command out bit 7

CMDBIT8

BOOLEAN

Command out bit 8

CMDBIT9

BOOLEAN

Command out bit 9

CMDBIT10

BOOLEAN

Command out bit 10

CMDBIT11

BOOLEAN

Command out bit 11

CMDBIT12

BOOLEAN

Command out bit 12

CMDBIT13

BOOLEAN

Command out bit 13

CMDBIT14

BOOLEAN

Command out bit 14

CMDBIT15

BOOLEAN

Command out bit 15

CMDBIT16

BOOLEAN

Command out bit 16

CMDBIT17

BOOLEAN

Command out bit 17

CMDBIT18

BOOLEAN

Command out bit 18

CMDBIT19

BOOLEAN

Command out bit 19

CMDBIT20

BOOLEAN

Command out bit 20

CMDBIT21

BOOLEAN

Command out bit 21

CMDBIT22

BOOLEAN

Command out bit 22

CMDBIT23

BOOLEAN

Command out bit 23

CMDBIT24

BOOLEAN

Command out bit 24

CMDBIT25

BOOLEAN

Command out bit 25

CMDBIT26

BOOLEAN

Command out bit 26

CMDBIT27

BOOLEAN

Command out bit 27

CMDBIT28

BOOLEAN

Command out bit 28

CMDBIT29

BOOLEAN

Command out bit 29

CMDBIT30

BOOLEAN

Command out bit 30

CMDBIT31

BOOLEAN

Command out bit 31

CMDBIT32

BOOLEAN

Command out bit 32

Settings
AUTOBITS Non group settings (basic)
Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Table 490:
Name
Operation

Table 491:
Name
BaudRate

Table 492:
Name

DNPGEN Non group settings (basic)


Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

CHSERRS485 Non group settings (basic)


Values (Range)
300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
57600 Bd
115200 Bd

Unit
-

Step
-

Default
9600 Bd

Description
Baud-rate for serial port

CHSERRS485 Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

DLinkConfirm

Never
Sometimes
Always

Never

Data-link confirm

tDLinkTimeout

0.000 - 60.000

0.001

2.000

Data-link confirm timeout in s

DLinkRetries

0 - 255

Data-link maximum retries

tRxToTxMinDel

0.000 - 60.000

0.001

0.000

Rx to Tx minimum delay in s

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment size

StopBits

1-2

Stop bits

Parity

No
Even
Odd

Even

Parity

tRTSWarmUp

0.000 - 60.000

0.001

0.000

RTS warm-up in s

tRTSWarmDown

0.000 - 60.000

0.001

0.000

RTS warm-down in s

tBackOffDelay

0.000 - 60.000

0.001

0.050

RS485 back-off delay in s

tMaxRndDelBkOf

0.000 - 60.000

0.001

0.100

RS485 maximum back-off random delay in s

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

905

Section 14
Control

Table 493:
Name

1MRK 502 066-UUS A

CH1TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
TCP/IP
UDP-Only

Disabled

Operation mode

TCPIPLisPort

1 - 65535

20000

TCP/IP listen port

UDPPortAccData

1 - 65535

20000

UDP port to accept UDP datagrams from


master

UDPPortInitNUL

1 - 65535

20000

UDP portfor initial NULL response

UDPPortCliMast

0 - 65535

UDP port to remote client/master

Table 494:
Name

CH1TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment size

Table 495:
Name

CH2TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
TCP/IP
UDP-Only

Disabled

Operation mode

TCPIPLisPort

1 - 65535

20000

TCP/IP listen port

UDPPortAccData

1 - 65535

20000

UDP port to accept UDP datagrams from


master

UDPPortInitNUL

1 - 65535

20000

UDP port for initial NULL response

UDPPortCliMast

0 - 65535

UDP port to remote client/master

Table 496:
Name

CH2TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment size

906

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Table 497:
Name

CH3TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
TCP/IP
UDP-Only

Disabled

Operation mode

TCPIPLisPort

1 - 65535

20000

TCP/IP listen port

UDPPortAccData

1 - 65535

20000

UDP port to accept UDP datagrams from


master

UDPPortInitNUL

1 - 65535

20000

UDP port for initial NULL response

UDPPortCliMast

0 - 65535

UDP port to remote client/master

Table 498:
Name

CH3TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment size

Table 499:
Name

CH4TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
TCP/IP
UDP-Only

Disabled

Operation mode

TCPIPLisPort

1 - 65535

20000

TCP/IP listen port

UDPPortAccData

1 - 65535

20000

UDP port to accept UDP datagrams from


master

UDPPortInitNUL

1 - 65535

20000

UDP port for initial NULL response

UDPPortCliMast

0 - 65535

UDP port to remote client/master

Table 500:
Name

CH4TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment size

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

907

Section 14
Control

Table 501:
Name

1MRK 502 066-UUS A

MSTSER Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

ChToAssociate

RS485
Optical

RS485

Channel to associate to

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

908

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Table 502:
Name

MSTSER Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ValMasterAddr

No
Yes

Yes

Validate source (master) address

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Disabled

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before off-line


retry mode

tVRRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tVROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

tVREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event buffer


timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tVREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event buffer


timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tVREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event buffer


timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

Yes

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

909

Section 14
Control

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

TSyncReqAfTout

No
Yes

No

Time synchronization request after timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

Step

Default

Table 503:
Name

MST1TCP Non group settings (basic)


Values (Range)

Unit

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

ValMasterAddr

No
Yes

Yes

Validate source (master) address

MasterIP-Addr

0 - 18

IP
Address

0.0.0.0

Master IP-address

MasterIPNetMsk

0 - 18

IP
Address

255.255.255.255

Master IP net mask

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Table continues on next page

910

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

Table 504:
Name

MST1TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Disabled

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before off-line


retry mode

tVRRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tVROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

911

Section 14
Control

Name

1MRK 502 066-UUS A

Unit

Step

Default

tVREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event buffer


timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tVREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event buffer


timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tVREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event buffer


timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

No

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

tBrokenConTout

0 - 3600

Broken connection timeout

tKeepAliveT

0 - 3600

10

Keep-Alive timer

Table 505:
Name

Values (Range)

Description

MST2TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

ValMasterAddr

No
Yes

Yes

Validate source (master) address

MasterIP-Addr

0 - 18

IP
Address

0.0.0.0

Master IP-address

MasterIPNetMsk

0 - 18

IP
Address

255.255.255.255

Master IP net mask

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Table continues on next page

912

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

Table 506:
Name

MST2TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

913

Section 14
Control

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Disabled

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before off-line


retry mode

tVRRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tVROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

tVREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event buffer


timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tVREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event buffer


timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tVREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event buffer


timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

No

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

tBrokenConTout

0 - 3600

Broken connection timeout

tKeepAliveT

0 - 3600

10

Keep-Alive timer

914

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Table 507:
Name

MST3TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

ValMasterAddr

No
Yes

Yes

Validate source (master) address

MasterIP-Addr

0 - 18

IP
Address

0.0.0.0

Master IP-address

MasterIPNetMsk

0 - 18

IP
Address

255.255.255.255

Master IP net mask

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

915

Section 14
Control

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

Table 508:
Name

MST3TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Disabled

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before off-line


retry mode

tVRRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tVROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

Table continues on next page

916

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Unit

Step

Default

tVREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event buffer


timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tVREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event buffer


timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tVREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event buffer


timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

No

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

tBrokenConTout

0 - 3600

Broken connection timeout

tKeepAliveT

0 - 3600

10

Keep-Alive timer

Table 509:
Name

Values (Range)

Description

MST4TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

ValMasterAddr

No
Yes

Yes

Validate source (master) address

MasterIP-Addr

0 - 18

IP
Address

0.0.0.0

Master IP-address

MasterIPNetMsk

0 - 18

IP
Address

255.255.255.255

Master IP net mask

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

917

Section 14
Control

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

Table 510:
Name

MST4TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

Table continues on next page

918

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Disabled

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before off-line


retry mode

tVRRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tVROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

tVREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event buffer


timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tVREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event buffer


timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tVREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event buffer


timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

No

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

tBrokenConTout

0 - 3600

Broken connection timeout

tKeepAliveT

0 - 3600

10

Keep-Alive timer

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

919

Section 14
Control
14.9.6

1MRK 502 066-UUS A

Operation principle
AutomationBits function (AUTOBITS) has 32 individual outputs which each can be
mapped as a Binary Output point in DNP3. The output is operated by a "Object 12" in
DNP3. This object contains parameters for control-code, count, on-time and off-time. To
operate an AUTOBITS output point, send a control-code of latch-On, latch-Off, pulseOn, pulse-Off, Trip or Close. The remaining parameters will be regarded were
appropriate. ex: pulse-On, on-time=100, off-time=300, count=5 would give 5 positive
100 ms pulses, 300 ms apart.
There is a BLOCK input signal, which will disable the operation of the function, in the
same way the setting Operation: Enabled/Disabled does. That means that, upon activation
of the BLOCK input, all 32 CMDBITxx outputs will be set to 0. The BLOCK acts like an
overriding, the function still receives data from the DNP3 master. Upon deactivation of
BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3 master again,
momentarily. For AUTOBITS , the PSTO input determines the operator place. The
command can be written to the block while in Remote. If PSTO is in Local then no
change is applied to the outputs.

14.10

Single command, 16 signals SINGLECMD

14.10.1

Identification
Function description
Single command, 16 signals

14.10.2

IEC 61850
identification
SINGLECMD

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The IEDs can receive commands either from a substation automation system or from the
local HMI. The command function block has outputs that can be used, for example, to
control high voltage apparatuses or for other user defined functionality.

920

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 14
Control

1MRK 502 066-UUS A

14.10.3

Function block
SINGLECMD
BLOCK

^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
IEC05000698-2-en.vsd

IEC05000698 V3 EN

Figure 415:

14.10.4

SINGLECMD function block

Signals
Table 511:
Name
BLOCK

Table 512:
Name

SINGLECMD Input signals


Type
BOOLEAN

Default
0

Description
Block single command function

SINGLECMD Output signals


Type

Description

OUT1

BOOLEAN

Single command output 1

OUT2

BOOLEAN

Single command output 2

OUT3

BOOLEAN

Single command output 3

OUT4

BOOLEAN

Single command output 4

OUT5

BOOLEAN

Single command output 5

OUT6

BOOLEAN

Single command output 6

OUT7

BOOLEAN

Single command output 7

OUT8

BOOLEAN

Single command output 8

OUT9

BOOLEAN

Single command output 9

OUT10

BOOLEAN

Single command output 10

OUT11

BOOLEAN

Single command output 11

OUT12

BOOLEAN

Single command output 12

OUT13

BOOLEAN

Single command output 13

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

921

Section 14
Control

1MRK 502 066-UUS A

Name

14.10.5
Table 513:
Name
Operation

14.10.6

Type

Description

OUT14

BOOLEAN

Single command output 14

OUT15

BOOLEAN

Single command output 15

OUT16

BOOLEAN

Single command output 16

Settings
SINGLECMD Non group settings (basic)
Values (Range)
Disabled
Steady
Pulsed

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Operation principle
Single command, 16 signals (SINGLECMD) function has 16 binary output signals. The
outputs can be individually controlled from a substation automation system or from the
local HMI. Each output signal can be given a name with a maximum of 13 characters in
PCM600.
The output signals can be of the types Disabled, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole function block.
The length of the output pulses are 100 ms. In steady mode, SINGLECMD function has
a memory to remember the output values at power interruption of the IED. Also a BLOCK
input is available used to block the updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in functions
or via the configuration logic circuits to the binary outputs of the IED.

922

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Section 15

Logic

15.1

Tripping logic SMPPTRC (94)

15.1.1

Identification
Function description
Tripping logic

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
94

SMPPTRC

I->O
SYMBOL-K V1 EN

15.1.2

Functionality
A function block for protection tripping is always provided as basic for each circuit
breaker involved in the tripping of the fault. It provides a settable pulse prolongation to
ensure a trip pulse of sufficient length, as well as all functionality necessary for correct cooperation with autoreclosing functions.
The trip function block also includes a settable latch functionality for evolving faults and
breaker lock-out.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

923

Section 15
Logic
15.1.3

1MRK 502 066-UUS A

Function block
SMPPTRC (94)
BLOCK
TRIP
BLKLKOUT
TR_A
TRINP_3P
TR_B
TRINP_A
TR_C
TRINP_B
TR1P
TRINP_C
TR2P
PS_A
TR3P
PS_B
CLLKOUT
PS_C
1PTRZ
1PTRGF
P3PTR
SETLKOUT
RSTLKOUT
ANSI05000707-2-en.vsd
ANSI05000707 V2 EN

Figure 416:

15.1.4

Signals
Table 514:
Name

924

SMPPTRC (94) function block

SMPPTRC (94) Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

BLKLKOUT

BOOLEAN

Blocks circuit breaker lockout output (CLLKOUT)

TRINP_3P

BOOLEAN

Trip all phases

TRINP_A

BOOLEAN

Trip phase A

TRINP_B

BOOLEAN

Trip phase B

TRINP_C

BOOLEAN

Trip phase C

PS_A

BOOLEAN

Input from phase selection, phase A

PS_B

BOOLEAN

Input from phase selection, phase B

PS_C

BOOLEAN

Input from phase selection, phase C

1PTRZ

BOOLEAN

Zone Trip with a separate phase selection

1PTRGF

BOOLEAN

Single phase Directional Ground Fault Overcurrent Trip


with phase selection

P3PTR

BOOLEAN

Prepare all tripping to be three-phase

SETLKOUT

BOOLEAN

Input for setting the circuit breaker lockout function

RSTLKOUT

BOOLEAN

Input for resetting the circuit breaker lockout function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Table 515:

SMPPTRC (94) Output signals

Name

15.1.5
Table 516:
Name

Type

Description

TRIP

BOOLEAN

General trip output signal

TR_A

BOOLEAN

Trip signal from phase A

TR_B

BOOLEAN

Trip signal from phase B

TR_C

BOOLEAN

Trip signal from phase C

TR1P

BOOLEAN

Tripping single-pole

TR2P

BOOLEAN

Tripping two-pole

TR3P

BOOLEAN

Tripping three-pole

CLLKOUT

BOOLEAN

Circuit breaker lockout output (set until reset)

Settings
SMPPTRC (94) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

Program

3 phase
1p/3p
1p/2p/3p

1p/3p

Three pole; single or three pole; single, two or


three pole trip

tTripMin

0.000 - 60.000

0.001

0.150

Minimum duration of trip output signal

tWaitForPHS

0.020 - 0.500

0.001

0.050

Secures 3-pole trip when phase selection


failed

Table 517:
Name

SMPPTRC (94) Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

TripLockout

Disabled
Enabled

Disabled

If TripLockout is set to On, it will activate output


(CLLKOUT) and trip latch. If set to Off it will
activate only CLLKOUT

AutoLock

Disabled
Enabled

Disabled

If AutoLock is set to On i will activate lockout


from input (SETLKOUT) and trip, If set to Off it
will activate only from SETLKOUT

15.1.6

Operation principle
The duration of a trip output signal from tripping logic common 3-phase output
SMPPTRC (94) is settable (tTripMin). The pulse length should be long enough to secure
the breaker opening.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

925

Section 15
Logic

1MRK 502 066-UUS A

For three-pole tripping logic common 3-phase output, SMPPTRC (94) has a single input
(TRINP_3P) through which all trip output signals from the protection functions within the
IED, or from external protection functions via one or more of the IEDs binary inputs, are
routed. It has a single trip output (TRIP) for connection to one or more of the IEDs binary
outputs, as well as to other functions within the IED requiring this signal.

BLOCK
tTripMin

TRIN

AND

OR

TRIP

Operation Mode = Enabled


Program = 3 phase
ANSI10000266-1-en.vsd
ANSI10000266 V1 EN

Figure 417:

Simplified logic diagram for three pole trip

SMPPTRC (94) function for single-pole and two-pole tripping has additional phase
segregated inputs for this, as well as inputs for faulted phase selection. The latter inputs
enable single- pole and two-pole tripping for those functions which do not have their own
phase selection capability, and therefore which have just a single trip output and not phase
segregated trip outputs for routing through the phase segregated trip inputs of the
expanded SMPPTRC (94) function. Examples of such protection functions are the
residual overcurrent protections. The expanded SMPPTRC (94) function has two inputs
for these functions, one for impedance tripping (for example, carrier-aided tripping
commands from the scheme communication logic), and one for ground fault tripping (for
example, tripping output from a residual overcurrent protection).
Additional logic, including a timer tWaitForPHS, secures a three-phase trip command for
these protection functions in the absence of the required phase selection signals.
The expanded SMPPTRC (94) function has three trip outputs TR_A, TR_B, TR_C
(besides the trip output TRIP), one per phase, for connection to one or more of the IEDs
binary outputs, as well as to other functions within the IED requiring these signals. There
are also separate output signals indicating single-pole, two-pole or three-pole trip. These
signals are important for cooperation with the autorecloser SMBRREC (79) function.
The expanded SMPPTRC (94) function is equipped with logic which secures correct
operation for evolving faults as well as for reclosing on to persistent faults. A special input
is also provided which disables single- pole and two-pole tripping, forcing all tripping to
be three-pole.
In multi-breaker arrangements, one SMPPTRC (94) function block is used for each
breaker. This can be the case if single pole tripping and autoreclosing is used.
926

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

The breaker close lockout function can be activated from an external trip signal from
another protection function via input (SETLKOUT) or internally at a three-pole trip, if
desired.
It is possible to lockout seal in the tripping output signals or use blocking of closing only
the choice is by setting TripLockout.

15.1.6.1

Logic diagram
TRINP_A
TRINP_B

OR

TRINP_C

OR

1PTRZ
1PTRGF

OR

TRINP_3P

AND

INTL_ABCTRIP

Program = 3 phase
ANSI05000517-3-en.vsd
ANSI05000517 V3 EN

Figure 418:

Three-phase front logic simplified logic diagram

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

927

Section 15
Logic

1MRK 502 066-UUS A

TRINP_3P
TRINP_A
PS_A

TR_A

OR

AND
TRINP_B

TR_B

PS_B

OR

AND
TRINP_C
PS_C

TR_C

OR

AND
OR

OR

OR
- loop
-loop

OR
AND
1PTRGF

AND
AND

AND

tWaitForPHS

OR

1PTRZ

ANSI10000056-3-en.vsd
ANSI10000056 V3 EN

Figure 419:

928

Phase segregated front logic

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

tTripMin

tEvolvingFault

tTripMin

tEvolvingFault

tTripMin

tEvolvingFault

ANSI05000519-3-en.vsdx

ANSI05000519 V3 EN

Figure 420:

Additional logic for the 1ph/3ph operating mode

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

929

Section 15
Logic

1MRK 502 066-UUS A

BLOCK

tTripMin

tEvolvingFault

tTripMin

tEvolvingFault

tTripMin

tEvolvingFault

ANSI05000520-4-en.vsdx
ANSI05000520 V4 EN

Figure 421:

930

Additional logic for the 1ph/2ph/3ph operating mode

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

ANSI05000521-3.vsd
ANSI05000521 V3 EN

Figure 422:

15.1.7

Final tripping circuits

Technical data
Table 518:

SMPPTRC (94) technical data

Function

Range or value

Accuracy

Trip action

3-ph, 1/3-ph, 1/2/3-ph

Minimum trip pulse length

(0.000-60.000) s

0.2% or 15 ms whichever is
greater

3-pole trip delay

(0.020-0.500) s

0.2% or 15 ms whichever is
greater

Evolving fault delay

(0.000-60.000) s

0.2% or 15 ms whichever is
greater

Table 519:

Number of SMPPTRC instances

Function
SMPPTRC

Quantity with cycle time


3 ms

8 ms

100 ms

12

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

931

Section 15
Logic

1MRK 502 066-UUS A

15.2

Trip matrix logic TMAGAPC

15.2.1

Identification
Function description
Trip matrix logic

15.2.2

IEC 61850
identification
TMAGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The trip matrix logic TMAGAPC function is used to route trip signals and other logical
output signals to different output contacts on the IED.
The trip matrix logic function has 3 output signals and these outputs can be connected to
physical tripping outputs according to the specific application needs for settable pulse or
steady output.

932

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.2.3

Function block
TMAGAPC
BLOCK
BLK1
BLK2
BLK3
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
INPUT17
INPUT18
INPUT19
INPUT20
INPUT21
INPUT22
INPUT23
INPUT24
INPUT25
INPUT26
INPUT27
INPUT28
INPUT29
INPUT30
INPUT31
INPUT32

OUTPUT1
OUTPUT2
OUTPUT3

IEC13000197-1-en.vsd
IEC13000197 V1 EN

Figure 423:

15.2.4

TMAGAPC function block

Signals
Table 520:
Name

TMAGAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

BLK1

BOOLEAN

Block of output 1

BLK2

BOOLEAN

Block of output 2

BLK3

BOOLEAN

Block of output 3

INPUT1

BOOLEAN

Binary input 1

INPUT2

BOOLEAN

Binary input 2

INPUT3

BOOLEAN

Binary input 3

INPUT4

BOOLEAN

Binary input 4

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

933

Section 15
Logic

1MRK 502 066-UUS A

Name

Default

Description

BOOLEAN

Binary input 5

INPUT6

BOOLEAN

Binary input 6

INPUT7

BOOLEAN

Binary input 7

INPUT8

BOOLEAN

Binary input 8

INPUT9

BOOLEAN

Binary input 9

INPUT10

BOOLEAN

Binary input 10

INPUT11

BOOLEAN

Binary input 11

INPUT12

BOOLEAN

Binary input 12

INPUT13

BOOLEAN

Binary input 13

INPUT14

BOOLEAN

Binary input 14

INPUT15

BOOLEAN

Binary input 15

INPUT16

BOOLEAN

Binary input 16

INPUT17

BOOLEAN

Binary input 17

INPUT18

BOOLEAN

Binary input 18

INPUT19

BOOLEAN

Binary input 19

INPUT20

BOOLEAN

Binary input 20

INPUT21

BOOLEAN

Binary input 21

INPUT22

BOOLEAN

Binary input 22

INPUT23

BOOLEAN

Binary input 23

INPUT24

BOOLEAN

Binary input 24

INPUT25

BOOLEAN

Binary input 25

INPUT26

BOOLEAN

Binary input 26

INPUT27

BOOLEAN

Binary input 27

INPUT28

BOOLEAN

Binary input 28

INPUT29

BOOLEAN

Binary input 29

INPUT30

BOOLEAN

Binary input 30

INPUT31

BOOLEAN

Binary input 31

INPUT32

BOOLEAN

Binary input 32

Table 521:
Name

934

Type

INPUT5

TMAGAPC Output signals


Type

Description

OUTPUT1

BOOLEAN

OR function betweeen inputs 1 to 16

OUTPUT2

BOOLEAN

OR function between inputs 17 to 32

OUTPUT3

BOOLEAN

OR function between inputs 1 to 32

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.2.5
Table 522:
Name

Settings
TMAGAPC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PulseTime

0.050 - 60.000

0.001

0.150

Output pulse time

OnDelay

0.000 - 60.000

0.001

0.000

Output on delay time

OffDelay

0.000 - 60.000

0.001

0.000

Output off delay time

ModeOutput1

Steady
Pulsed

Steady

Mode for output ,1 steady or pulsed

ModeOutput2

Steady
Pulsed

Steady

Mode for output 2, steady or pulsed

ModeOutput3

Steady
Pulsed

Steady

Mode for output 3, steady or pulsed

15.2.6

Operation principle
The trip matrix logic (TMAGAPC) block is provided with 32 input signals and 3 output
signals. The function block incorporates internal logic OR gates in order to provide
grouping of connected input signals to the three output signals from the function block.
Internal built-in OR logic is made in accordance with the following three rules:
1.
2.
3.

when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value 1 the
first output signal (OUTPUT1) will get logical value 1.
when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical value
1 the second output signal (OUTPUT2) will get logical value 1.
when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1 the
third output signal (OUTPUT3) will get logical value 1.

By use of the settings ModeOutput1, ModeOutput2, ModeOutput3, PulseTime, OnDelay


and OffDelay the behavior of each output can be customized. The OnDelay is always
active and will delay the input to output transition by the set time. The ModeOutput for
respective output decides whether the output shall be steady with an drop-off delay as set
by OffDelay or if it shall give a pulse with duration set by PulseTime. Note that for pulsed
operation and that the inputs are connected in an OR-function, a new pulse will only be
given on the output if all related inputs are reset and then one is activated again. For steady
operation the OffDelay will pickup when all related inputs have reset. Detailed logical
diagram is shown in figure 424

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

935

Section 15
Logic

1MRK 502 066-UUS A

PulseTime

AND

ModeOutput1

INPUT 1
0-OnDelay
0

OR

INPUT 16

0
0-OffDelay

OR

AND

OUTPUT 1

PulseTime

AND

ModeOutput2

INPUT 17
0-OnDelay
0

OR

INPUT 32

0
0-OffDelay

OR

AND

OUTPUT 2

PulseTime

AND

ModeOutput3

OR

0-OnDelay
0

0
0-OffDelay

OR

AND

OUTPUT 3

ANSI10000055-3-en.vsd
ANSI10000055 V3 EN

Figure 424:

Trip matrix internal logic

Output signals from TMAGAPC are typically connected to other logic blocks or directly
to output contacts in the IED. When used for direct tripping of the circuit breaker(s) the
pulse time shall be set to at least 0.150 seconds in order to obtain satisfactory minimum
duration of the trip pulse to the circuit breaker trip coils.

15.2.7

Technical data
Table 523:
Function
TMAGAPC

936

Number of TMAGAPC instances


3 ms
6

Quantity with cycle time


8 ms
6

100 ms
-

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.3

Logic for group alarm ALMCALH

15.3.1

Identification
Function description

IEC 61850
identification

Logic for group alarm

15.3.2

IEC 60617
identification

ALMCALH

ANSI/IEEE C37.2
device number
-

Functionality
The group alarm logic function ALMCALH is used to route several alarm signals to a
common indication, LED and/or contact, in the IED.

15.3.3

Function block
ALMCALH
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

ALARM

IEC13000181-1-en.vsd
IEC13000181 V1 EN

15.3.4

Signals
Table 524:
Name

ALMCALH Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

BOOLEAN

Binary input 1

INPUT2

BOOLEAN

Binary input 2

INPUT3

BOOLEAN

Binary input 3

INPUT4

BOOLEAN

Binary input 4

INPUT5

BOOLEAN

Binary input 5

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

937

Section 15
Logic

1MRK 502 066-UUS A

Name

Type

Binary input 6

INPUT7

BOOLEAN

Binary input 7

INPUT8

BOOLEAN

Binary input 8

INPUT9

BOOLEAN

Binary input 9

INPUT10

BOOLEAN

Binary input 10

INPUT11

BOOLEAN

Binary input 11

INPUT12

BOOLEAN

Binary input 12

INPUT13

BOOLEAN

Binary input 13

INPUT14

BOOLEAN

Binary input 14

INPUT15

BOOLEAN

Binary input 15

INPUT16

BOOLEAN

Binary input 16

ALMCALH Output signals

Name

Type

ALARM

Table 526:
Name
Operation

15.3.6

Description

BOOLEAN

Table 525:

15.3.5

Default

INPUT6

Description

BOOLEAN

OR function betweeen inputs 1 to 16

Settings
ALMCALH Group settings (basic)
Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Operation principle
The logic for group alarm ALMCALH block is provided with 16 input signals and one
ALARM output signal. The function block incorporates internal logic OR gate in order to
provide grouping of connected input signals to the output ALARM signal from the
function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the ALARM
output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.

938

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Input 1
Input 16

ALARM

200 ms
0

ANSI13000191-1-en.vsd
ANSI13000191 V1 EN

Figure 425:

15.3.7

Group alarm logic

Technical data
Table 527:

Number of ALMCALH instances

Function
ALMCALH

3 ms

Quantity with cycle time


8 ms

15.4

Logic for group warning WRNCALH

15.4.1

Identification
Function description
Logic for group warning

15.4.2

IEC 61850
identification
WRNCALH

100 ms

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The group warning logic function WRNCALH is used to route several warning signals to
a common indication, LED and/or contact, in the IED.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

939

Section 15
Logic
15.4.3

1MRK 502 066-UUS A

Function block
WRNCALH
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

WARNING

IEC13000182-1-en.vsd
IEC13000182 V1 EN

15.4.4

Signals
Table 528:
Name

940

WRNCALH Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

BOOLEAN

Binary input 1

INPUT2

BOOLEAN

Binary input 2

INPUT3

BOOLEAN

Binary input 3

INPUT4

BOOLEAN

Binary input 4

INPUT5

BOOLEAN

Binary input 5

INPUT6

BOOLEAN

Binary input 6

INPUT7

BOOLEAN

Binary input 7

INPUT8

BOOLEAN

Binary input 8

INPUT9

BOOLEAN

Binary input 9

INPUT10

BOOLEAN

Binary input 10

INPUT11

BOOLEAN

Binary input 11

INPUT12

BOOLEAN

Binary input 12

INPUT13

BOOLEAN

Binary input 13

INPUT14

BOOLEAN

Binary input 14

INPUT15

BOOLEAN

Binary input 15

INPUT16

BOOLEAN

Binary input 16

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Table 529:

WRNCALH Output signals

Name

Type

WARNING

15.4.5
Table 530:
Name
Operation

15.4.6

Description

BOOLEAN

OR function betweeen inputs 1 to 16

Settings
WRNCALH Group settings (basic)
Values (Range)
Disabled
Enabled

Unit

Step

Default

Description

Disabled

Operation Disabled/Enabled

Operation principle
The logic for group warning WRNCALH block is provided with 16 input signals and 1
WARNING output signal. The function block incorporates internal logic OR gate in order
to provide grouping of connected input signals to the output WARNING signal from the
function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
WARNING output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.
INPUT1
1

WARNING

200 ms
0

INPUT16

ANSI13000192-1-en.vsd
ANSI13000192 V1 EN

15.4.7

Technical data
Table 531:
Function
WRNCALH

Number of WRNCALH instances


3 ms
-

Quantity with cycle time


8 ms
-

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

100 ms
5

941

Section 15
Logic

1MRK 502 066-UUS A

15.5

Logic for group indication INDCALH

15.5.1

Identification
Function description

IEC 61850
identification

Logic for group indication

15.5.2

IEC 60617
identification

INDCALH

ANSI/IEEE C37.2
device number
-

Functionality
The group indication logic function INDCALH is used to route several indication signals
to a common indication, LED and/or contact, in the IED.

15.5.3

Function block
INDCALH
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IND

IEC13000183-1-en.vsd
IEC13000183 V1 EN

15.5.4

Signals
Table 532:
Name

INDCALH Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

BOOLEAN

Binary input 1

INPUT2

BOOLEAN

Binary input 2

INPUT3

BOOLEAN

Binary input 3

INPUT4

BOOLEAN

Binary input 4

INPUT5

BOOLEAN

Binary input 5

Table continues on next page


942

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Name

Type

Binary input 6

INPUT7

BOOLEAN

Binary input 7

INPUT8

BOOLEAN

Binary input 8

INPUT9

BOOLEAN

Binary input 9

INPUT10

BOOLEAN

Binary input 10

INPUT11

BOOLEAN

Binary input 11

INPUT12

BOOLEAN

Binary input 12

INPUT13

BOOLEAN

Binary input 13

INPUT14

BOOLEAN

Binary input 14

INPUT15

BOOLEAN

Binary input 15

INPUT16

BOOLEAN

Binary input 16

INDCALH Output signals

Name

Type

IND

Table 534:
Name
Operation

15.5.6

Description

BOOLEAN

Table 533:

15.5.5

Default

INPUT6

Description

BOOLEAN

OR function betweeen inputs 1 to 16

Settings
INDCALH Group settings (basic)
Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Operation principle
The logic for group indication INDCALH block is provided with 16 input signals and 1
IND output signal. The function block incorporates internal logic OR gate in order to
provide grouping of connected input signals to the output IND signal from the function
block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the IND
output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

943

Section 15
Logic

1MRK 502 066-UUS A

INPUT1
1

IND

200 ms
0

INPUT16

ANSI13000193-1-en.vsd
ANSI13000193 V1 EN

15.5.7

Technical data
Table 535:
Function
INDCALH

15.6

Number of INDCALH instances


3 ms
-

Quantity with cycle time


8 ms
5

100 ms
-

Basic configurable logic blocks


The basic configurable logic blocks do not propagate the time stamp and quality of signals
(have no suffix QT at the end of their function name). A number of logic blocks and timers
are always available as basic for the user to adapt the configuration to the specific
application needs. The list below shows a summary of the function blocks and their
features.
These logic blocks are also available as part of an extension logic package with the same
number of instances.

944

AND function block. Each block has four inputs and two outputs where one is
inverted.

GATE function block is used for whether or not a signal should be able to pass from
the input to the output.

INVERTER function block that inverts one input signal to the output.

LLD function block. Loop delay used to delay the output signal one execution cycle.

OR function block. Each block has up to six inputs and two outputs where one is
inverted.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.6.1

PULSETIMER function block can be used, for example, for pulse extensions or
limiting of operation of outputs, settable pulse time.

RSMEMORY function block is a flip-flop that can reset or set an output from two
inputs respectively. Each block has two outputs where one is inverted. The memory
setting controls if, after a power interruption, the flip-flop resets or returns to the state
it had before the power interruption. RESET input has priority.

SRMEMORY function block is a flip-flop that can set or reset an output from two
inputs respectively. Each block has two outputs where one is inverted. The memory
setting controls if, after a power interruption, the flip-flop resets or returns to the state
it had before the power interruption. The SET input has priority.

TIMERSET function has pick-up and drop-out delayed outputs related to the input
signal. The timer has a settable time delay.

XOR function block. Each block has two outputs where one is inverted.

AND function block AND


The AND function is used to form general combinatory expressions with boolean
variables. The AND function block has up to four inputs and two outputs. One of the
outputs is inverted.

15.6.1.1

Function block
AND
INPUT1
INPUT2
INPUT3
INPUT4

OUT
NOUT

IEC14000071-1-en.vsd
IEC14000071 V1 EN

Figure 426:

AND function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

945

Section 15
Logic
15.6.1.2

1MRK 502 066-UUS A

Signals
Table 536:

AND Input signals

Name

Type

Input signal 1

INPUT2

BOOLEAN

Input signal 2

INPUT3

BOOLEAN

Input signal 3

INPUT4

BOOLEAN

Input signal 4

AND Output signals

Name

Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

Technical data
Table 538:

Number of AND instances

Logic block

Quantity with cycle time


8 ms

3 ms

AND

15.6.2

Description

BOOLEAN

Table 537:

15.6.1.3

Default

INPUT1

60

60

100 ms
160

Controllable gate function block GATE


The Controllable gate function block (GATE) is used for controlling if a signal should be
able to pass from the input to the output or not depending on a setting.

15.6.2.1

Function block
GATE
INPUT

OUT
IEC04000410-2-en.vsd

IEC04000410 V2 EN

Figure 427:

15.6.2.2

Signals
Table 539:
Name
INPUT

946

GATE function block

GATE Input signals


Type
BOOLEAN

Default
0

Description
Input to gate

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Table 540:

GATE Output signals

Name

Type

OUT

15.6.2.3
Table 541:
Name
Operation

15.6.2.4

Description

BOOLEAN

Output from gate

Settings
GATE Group settings (basic)
Values (Range)

Unit

Disabled
Enabled

Step

Default

Description

Disabled

Operation Disabled/Enabled

Technical data
Table 542:

Number of GATE instances

Logic block

Quantity with cycle time


8 ms

3 ms

GATE

10

10

15.6.3

Inverter function block INV

15.6.3.1

Function block

100 ms
20

INV
INPUT

OUT
IEC04000404_2_en.vsd

IEC04000404 V2 EN

Figure 428:

15.6.3.2

INV function block

Signals
Table 543:
Name
INPUT

Table 544:
Name
OUT

INV Input signals


Type
BOOLEAN

Default
0

Description
Input

INV Output signals


Type
BOOLEAN

Description
Output

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

947

Section 15
Logic
15.6.3.3

1MRK 502 066-UUS A

Technical data
Table 545:

Number of INV instances

Logic block
INV

15.6.4

Quantity with cycle time


8 ms

3 ms
90

90

100 ms
240

Loop delay function block LLD


The Logic loop delay function block (LLD) function is used to delay the output signal one
execution cycle, that is, the cycle time of the function blocks used.

15.6.4.1

Function block
LLD
INPUT

OUT
IEC15000144.vsd

IEC15000144 V1 EN

Figure 429:

15.6.4.2

LLD function block

Signals
Table 546:

LLD Input signals

Name

Type

INPUT

Table 547:

BOOLEAN

Type

OUT

Description
Input signal

BOOLEAN

Description
Output signal delayed one execution cycle

Technical data
Table 548:
Logic block
LLD

948

LLD Output signals

Name

15.6.4.3

Default

Number of LLD instances


3 ms
10

Quantity with cycle time


8 ms
10

100 ms
20

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.6.5

OR function block OR
The OR function is used to form general combinatory expressions with boolean variables.
The OR function block has up to six inputs and two outputs. One of the outputs is inverted.

15.6.5.1

Function block
OR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6

OUT
NOUT

IEC04000405_2_en.vsd
IEC04000405 V2 EN

Figure 430:

15.6.5.2

OR function block

Signals
Table 549:

OR Input signals

Name

Type

Description

BOOLEAN

Input 1 to OR gate

INPUT2

BOOLEAN

Input 2 to OR gate

INPUT3

BOOLEAN

Input 3 to OR gate

INPUT4

BOOLEAN

Input 4 to OR gate

INPUT5

BOOLEAN

Input 5 to OR gate

INPUT6

BOOLEAN

Input 6 to OR gate

Table 550:

OR Output signals

Name

15.6.5.3

Default

INPUT1

Type

Description

OUT

BOOLEAN

Output from OR gate

NOUT

BOOLEAN

Inverted output from OR gate

Technical data
Table 551:
Logic block
OR

Number of OR instances
3 ms
60

Quantity with cycle time


8 ms
60

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

100 ms
160

949

Section 15
Logic
15.6.6

1MRK 502 066-UUS A

Pulse timer function block PULSETIMER


The pulse (PULSETIMER) function can be used, for example, for pulse extensions or
limiting the operation time of outputs. The PULSETIMER has a settable length. When the
input is 1, the output will be 1 for the time set by the time delay parameter t. Then it returns
to 0.

15.6.6.1

Function block
PULSETIMER
INPUT

OUT
IEC04000407-3-en.vsd

IEC04000407 V3 EN

Figure 431:

15.6.6.2

PULSETIMER function block

Signals
Table 552:

PULSETIMER Input signals

Name

Type

INPUT

BOOLEAN

Table 553:

Name
t

15.6.6.4

Input to pulse timer

Description

BOOLEAN

Output from pulse timer

Settings
PULSETIMER Non group settings (basic)
Values (Range)
0.000 - 90000.000

Unit

Step

Default

0.001

Description

0.010

Time delay of function

Technical data
Table 555:

Number of PULSETIMER instances

Logic block

Quantity with cycle time


3 ms
8 ms
100 ms

PULSETIMER

950

Type

OUT

Table 554:

Description

PULSETIMER Output signals

Name

15.6.6.3

Default

10

10

20

Range or Value
(0.00090000.000) s

Accuracy
0.5% 10 ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.6.7

Reset-set with memory function block RSMEMORY


The Reset-set with memory function block (RSMEMORY) is a flip-flop with memory
that can reset or set an output from two inputs respectively. Each RSMEMORY function
block has two outputs, where one is inverted. The memory setting controls if, after a power
interruption, the flip-flop resets or returns to the state it had before the power interruption.
For a Reset-Set flip-flop, RESET input has higher priority over SET input.
Table 556:

Truth table for RSMEMORY function block

RESET

15.6.7.1

SET

OUT

NOUT

Last
value

Inverted last
value

Function block
RSMEMORY
SET
RESET

OUT
NOUT
IEC09000294-1-en.vsd

IEC09000294 V1 EN

Figure 432:

15.6.7.2

RSMEMORY function block

Signals
Table 557:
Name

RSMEMORY Input signals


Type

Default

Description

SET

BOOLEAN

Input signal to set

RESET

BOOLEAN

Input signal to reset

Table 558:
Name

RSMEMORY Output signals


Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

951

Section 15
Logic
15.6.7.3
Table 559:
Name
Memory

15.6.7.4

1MRK 502 066-UUS A

Settings
RSMEMORY Group settings (basic)
Values (Range)

Unit

Disabled
Enabled

Step

Description

Enabled

Operating mode of the memory function

Technical data
Table 560:

Number of RSMEMORY instances

Logic block

Quantity with cycle time


8 ms

3 ms

RSMEMORY

15.6.8

Default

10

10

100 ms
20

Set-reset with memory function block SRMEMORY


The Set-reset with memory function block (SRMEMORY) is a flip-flop with memory that
can set or reset an output from two inputs respectively. Each SRMEMORY function block
has two outputs, where one is inverted. The memory setting controls if, after a power
interruption, the flip-flop resets or returns to the state it had before the power interruption.
The input SET has priority.
Table 561:
SET

15.6.8.1

Truth table for SRMEMORY function block


RESET

OUT

NOUT

Last
value

Inverted
last value

Function block
SRMEMORY
SET
OUT
RESET
NOUT
IEC04000408_2_en.vsd
IEC04000408 V2 EN

Figure 433:

952

SRMEMORY function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.6.8.2

Signals
Table 562:

SRMEMORY Input signals

Name

Type

Input signal to set

RESET

BOOLEAN

Input signal to reset

SRMEMORY Output signals

Name

Table 564:
Name
Memory

15.6.8.4

Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

Settings
SRMEMORY Group settings (basic)
Values (Range)
Disabled
Enabled

Unit

Step

Default

Description

Enabled

Operating mode of the memory function

Technical data
Table 565:
Logic block
SRMEMORY

15.6.9

Description

BOOLEAN

Table 563:

15.6.8.3

Default

SET

Number of SRMEMORY instances


3 ms
10

Quantity with cycle time


8 ms
10

100 ms
20

Settable timer function block TIMERSET


The Settable timer function block (TIMERSET) timer has two outputs for the delay of the
input signal at drop-out and at pick-up. The timer has a settable time delay. It also has an
Operation setting Enabled and Disabled that controls the operation of the timer.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

953

Section 15
Logic

1MRK 502 066-UUS A

Input
tdelay

On
Off

tdelay

t
IEC08000289-2-en.vsd

IEC08000289 V2 EN

Figure 434:

15.6.9.1

TIMERSET status diagram

Function block
TIMERSET
INPUT

ON
OFF
IEC04000411-2-en.vsd

IEC04000411 V2 EN

Figure 435:

15.6.9.2

Signals
Table 566:
Name
INPUT

Table 567:
Name

954

TIMERSET function block

TIMERSET Input signals


Type
BOOLEAN

Default
0

Description
Input to timer

TIMERSET Output signals


Type

Description

ON

BOOLEAN

Output from timer, pickup delay

OFF

BOOLEAN

Output from timer, dropout delay

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.6.9.3
Table 568:
Name

Settings
TIMERSET Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

0.000 - 90000.000

0.001

0.000

Delay for settable timer n

15.6.9.4

Technical data
Table 569:

Number of TIMERSET instances

Logic block

Quantity with cycle time


3 ms
8 ms
100 ms

TIMERSET

15.6.10

15

15

30

Range or Value
(0.00090000.000) s

Accuracy
0.5% 10 ms

Exclusive OR function block XOR


The exclusive OR function (XOR) is used to generate combinatory expressions with
boolean variables. XOR has two inputs and two outputs. One of the outputs is inverted.
The output signal OUT is 1 if the input signals are different and 0 if they are the same.
Table 570:

Truth table for XOR function block

INPUT1

15.6.10.1

INPUT2

OUT

NOUT

Function block
XOR
INPUT1
INPUT2

OUT
NOUT
IEC04000409-2-en.vsd

IEC04000409 V2 EN

Figure 436:

XOR function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

955

Section 15
Logic
15.6.10.2

1MRK 502 066-UUS A

Signals
Table 571:

XOR Input signals

Name

Type

Input 1 to XOR gate

INPUT2

BOOLEAN

Input 2 to XOR gate

XOR Output signals

Name

Type

Description

OUT

BOOLEAN

Output from XOR gate

NOUT

BOOLEAN

Inverted output from XOR gate

Technical data
Table 573:
Logic block
XOR

15.7

Description

BOOLEAN

Table 572:

15.6.10.3

Default

INPUT1

Number of XOR instances


3 ms
10

Quantity with cycle time


8 ms
10

100 ms
20

Configurable logic blocks Q/T


The configurable logic blocks QT propagate the time stamp and the quality of the input
signals (have suffix QT at the end of their function name). The propagation of information
is part of the IEC 61850 capabilities.
The function blocks assist the user to adapt the IEDs' configuration to the specific
application needs. The list below shows a summary of the function blocks and their
features.

956

ANDQT AND function block. The function also propagates the time stamp and the
quality of input signals. Each block has four inputs and two outputs where one is
inverted.

INDCOMBSPQT combines single input signals to group signal. Single position


input is copied to value part of SP_OUT output. TIME input is copied to time part of
SP_OUT output. Quality input bits are copied to the corresponding quality part of
SP_OUT output.

INDEXTSPQT extracts individual signals from a group signal input. The value part
of single position input is copied to SI_OUT output. The time part of single position
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

input is copied to TIME output. The quality bits in the common part and the indication
part of inputs signal are copied to the corresponding quality output.

INVALIDQT function which sets quality invalid of outputs according to a "valid"


input. Inputs are copied to outputs. If input VALID is 0, or if its quality invalid bit is
set, all outputs invalid quality bit will be set to invalid. The time stamp of an output
will be set to the latest time stamp of INPUT and VALID inputs.

INVERTERQT function block that inverts the input signal and propagates the time
stamp and the quality of the input signal.

ORQT OR function block that also propagates the time stamp and the quality of the
input signals. Each block has six inputs and two outputs where one is inverted.

PULSETIMERQT Pulse timer function block can be used, for example, for pulse
extensions or limiting of operation of outputs. The function also propagates the time
stamp and the quality of the input signal.

RSMEMORYQT function block is a flip-flop that can reset or set an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block after a power interruption should return to the
state before the interruption, or be reset. The function also propagates the time stamp
and the quality of the input signal.

SRMEMORYQT function block is a flip-flop that can set or reset an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block after a power interruption should return to the
state before the interruption, or be reset. The function also propagates the time stamp
and the quality of the input signal.

TIMERSETQT function has pick-up and drop-out delayed outputs related to the
input signal. The timer has a settable time delay. The function also propagates the
time stamp and the quality of the input signal.

XORQT XOR function block. The function also propagates the time stamp and the
quality of the input signals. Each block has two outputs where one is inverted.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

957

Section 15
Logic
15.7.1

1MRK 502 066-UUS A

ANDQT function block


The ANDQT function is used to form general combinatory expressions with boolean
variables. The ANDQT function block has four inputs and two outputs. It can propagate
the quality, value and timestamps of the signals via IEC61850.

15.7.1.1

Function block
ANDQT
INPUT1
INPUT2
INPUT3
INPUT4

OUT
NOUT

IEC09000297-1-en.vsd
IEC09000297 V1 EN

Figure 437:

15.7.1.2

ANDQT function block

Signals
Table 574:

ANDQT Input signals

Name

Type
BOOLEAN

Input signal 1

INPUT2

BOOLEAN

Input signal 2

INPUT3

BOOLEAN

Input signal 3

INPUT4

BOOLEAN

Input signal 4

ANDQT Output signals

Name

Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

Technical data
Table 576:
Logic block
ANDQT

958

Description

INPUT1

Table 575:

15.7.1.3

Default

Number of ANDQT instances


3 ms
-

Quantity with cycle time


8 ms
20

100 ms
100

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.7.2

Single point indication related signals combining function block


INDCOMBSPQT
The value of single point input (SP_IN) is copied to the value part of the SP_OUT output.
The TIME input is copied to the time part of the SP_OUT output. State input bits are
copied to the corresponding state part of the SP_OUT output. If the state or value on the
SP_OUT output changes, the Event bit in the state part is toggled.
INDCOMBSPQT can propagate the quality, the value and the time stamps of the signals
via IEC61850.

15.7.2.1

Function block
INDCOMBSPQT
SP_IN*
TIME*
BLOCKED*
SUBST*
INVALID*
TEST*

SP_OUT

IEC15000146.vsd
IEC15000146 V1 EN

Figure 438:

15.7.2.2

INDCOMBSPQT function block

Signals
Table 577:
Name

INDCOMBSPQT Input signals


Type

Default

Description

SP_IN

BOOLEAN

Single point indication

TIME

GROUP
SIGNAL

Timestamp

BLOCKED

BOOLEAN

Blocked for update

SUBST

BOOLEAN

Substituted

INVALID

BOOLEAN

Invalid value

TEST

BOOLEAN

Testmode

Table 578:
Name
SP_OUT

INDCOMBSPQT Output signals


Type
BOOLEAN

Description
Single point indication

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

959

Section 15
Logic
15.7.2.3

1MRK 502 066-UUS A

Technical data
Table 579:

Number of INDCOMBSPQT instances

Logic block
INDCOMBSPQT

15.7.3

Quantity with cycle time


8 ms

3 ms
-

10

100 ms
10

Single point input signal attributes converting function block


INDEXTSPQT
The value part of the single point input signal SI_IN is copied to SI_OUT output. The time
part of single point input is copied to the TIME output. The state bits in the common part
and the indication part of the input signal are copied to the corresponding state output.
INDEXTSPQT can propagate the quality, the value and the time stamps of the signals via
IEC61850.

15.7.3.1

Function block
INDEXTSPQT
SI_IN*

SI_OUT
TIME
BLOCKED
SUBST
INVALID
TEST
IEC14000067-1-en.vsd

IEC14000067 V1 EN

Figure 439:

15.7.3.2

Signals
Table 580:
Name
SI_IN

960

INDEXTSPQT function block

INDEXTSPQT Input signals


Type
BOOLEAN

Default
0

Description
Single indication

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Table 581:

INDEXTSPQT Output signals

Name

15.7.3.3

Description

BOOLEAN

Single indication

TIME

GROUP SIGNAL

Timestamp of input

BLOCKED

BOOLEAN

Blocked for update

SUBST

BOOLEAN

Substituted

INVALID

BOOLEAN

Invalid value

TEST

BOOLEAN

Testmode

Technical data
Table 582:
Logic block
INDEXTSPQT

15.7.4

Type

SI_OUT

Number of INDEXTSPQT instances


3 ms
-

Quantity with cycle time


8 ms
10

100 ms
10

Invalid logic function block INVALIDQT


Component which sets quality invalid of outputs according to a "valid" input.
The values of the input signals INPUTx (where 1<x<16) are copied to the outputs
OUTPUTx (where 1<x<16). If the input VALID is 0 or if its quality bit is set invalid, all
outputs OUTPUTx (where 1<x<16) quality bit will be set to invalid. The time stamp of
any output OUTPUTx (where 1<x<16) will be set to the latest time stamp of any input and
the input VALID.
INVALIDQT can propagate the quality, the value and the time stamps of the signals via
IEC61850.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

961

Section 15
Logic
15.7.4.1

1MRK 502 066-UUS A

Function block
INVALIDQT
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
VALID

OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16

iec08000169.vsd
IEC08000169 V1 EN

Figure 440:

15.7.4.2

Signals
Table 583:
Name

962

INVALIDQT function block

INVALIDQT Input signals


Type

Default

Description

INPUT1

BOOLEAN

Indication input 1

INPUT2

BOOLEAN

Indication input 2

INPUT3

BOOLEAN

Indication input 3

INPUT4

BOOLEAN

Indication input 4

INPUT5

BOOLEAN

Indication input 5

INPUT6

BOOLEAN

Indication input 6

INPUT7

BOOLEAN

Indication input 7

INPUT8

BOOLEAN

Indication input 8

INPUT9

BOOLEAN

Indication input 9

INPUT10

BOOLEAN

Indication input 10

INPUT11

BOOLEAN

Indication input 11

INPUT12

BOOLEAN

Indication input 12

INPUT13

BOOLEAN

Indication input 13

INPUT14

BOOLEAN

Indication input 14

INPUT15

BOOLEAN

Indication input 15

INPUT16

BOOLEAN

Indication input 16

VALID

BOOLEAN

Inputs are valid or invalid

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Table 584:

INVALIDQT Output signals

Name

15.7.4.3

Type
BOOLEAN

Indication output 1

OUTPUT2

BOOLEAN

Indication output 2

OUTPUT3

BOOLEAN

Indication output 3

OUTPUT4

BOOLEAN

Indication output 4

OUTPUT5

BOOLEAN

Indication output 5

OUTPUT6

BOOLEAN

Indication output 6

OUTPUT7

BOOLEAN

Indication output 7

OUTPUT8

BOOLEAN

Indication output 8

OUTPUT9

BOOLEAN

Indication output 9

OUTPUT10

BOOLEAN

Indication output 10

OUTPUT11

BOOLEAN

Indication output 11

OUTPUT12

BOOLEAN

Indication output 12

OUTPUT13

BOOLEAN

Indication output 13

OUTPUT14

BOOLEAN

Indication output 14

OUTPUT15

BOOLEAN

Indication output 15

OUTPUT16

BOOLEAN

Indication output 16

Technical data
Table 585:

Number of INVALIDQT instances

Logic block

3 ms

INVALIDQT

15.7.5

Description

OUTPUT1

Quantity with cycle time


8 ms

100 ms
6

Inverter function block INVERTERQT


The INVERTERQT function block inverts one binary input signal to the output. It can
propagate the quality, value and the time stamps of the signals via IEC61850.

15.7.5.1

Function block
INVERTERQT
INPUT

OUT
IEC09000299-1-en.vsd

IEC09000299 V1 EN

Figure 441:

INVERTERQT function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

963

Section 15
Logic
15.7.5.2

1MRK 502 066-UUS A

Signals
Table 586:

INVERTERQT Input signals

Name

Type

INPUT

BOOLEAN

Table 587:

Type

OUT

BOOLEAN

Description
Input signal

Description
Output signal

Technical data
Table 588:

Number of INVERTERQT instances

Logic block

3 ms

INVERTERQT

15.7.6

INVERTERQT Output signals

Name

15.7.5.3

Default

Quantity with cycle time


8 ms
20

100 ms
100

ORQT function block


The ORQT function block (ORQT) is used to form general combinatory expressions OR
with boolean variables. ORQT function block has up to six inputs and two outputs. One
of the outputs is inverted. It can propagate the quality, value and the timestamps of the
signals via IEC61850.

15.7.6.1

Function block
ORQT
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6

OUT
NOUT

IEC09000298-1-en.vsd
IEC09000298 V1 EN

Figure 442:

15.7.6.2

964

ORQT function block

Signals

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Table 589:

ORQT Input signals

Name

Type

Input signal 1

INPUT2

BOOLEAN

Input signal 2

INPUT3

BOOLEAN

Input signal 3

INPUT4

BOOLEAN

Input signal 4

INPUT5

BOOLEAN

Input signal 5

INPUT6

BOOLEAN

Input signal 6

ORQT Output signals

Name

Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

Technical data
Table 591:
Logic block
ORQT

15.7.7

Description

BOOLEAN

Table 590:

15.7.6.3

Default

INPUT1

Number of ORQT instances


3 ms
-

Quantity with cycle time


8 ms
20

100 ms
100

Pulse timer function block PULSETIMERQT


The pulse timer function block (PULSETIMERQT) can be used, for example, for pulse
extensions or for limiting the operation time of the outputs. PULSETIMERQT has a
settable output pulse length.
When the input goes to 1, the output will be 1 for the time set by the time delay parameter
t. Then it returns to 0.
When the output changes value, the time stamp of the output signal is updated.
The supported quality state bits are propagated from the input to the output at each
execution cycle. A change of these bits will not lead to an updated time stamp on the
output.
PULSETIMERQT can propagate the quality, value and the time stamps of the signals via
IEC61850.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

965

Section 15
Logic
15.7.7.1

1MRK 502 066-UUS A

Function block
PULSETIMERQT
INPUT

OUT
IEC15000145.vsd

IEC15000145 V1 EN

Figure 443:

15.7.7.2

PULSETIMERQT function block

Signals
Table 592:

PULSETIMERQT Input signals

Name

Type

INPUT

Table 593:

Name
t

15.7.7.4

Description

BOOLEAN

Output signal

Settings
PULSETIMERQT Non group settings (basic)
Values (Range)
0.000 - 90000.000

Unit

Step

Default

0.001

Description

0.010

Pulse time length

Technical data
Table 595:

Number of PULSETIMERQT instances

Logic block

Quantity with cycle time


3 ms
8 ms
100 ms

PULSETIMERQT

15.7.8

Input signal

Type

OUT

Table 594:

Description

PULSETIMERQT Output signals

Name

15.7.7.3

Default

BOOLEAN

10

30

Range or Value
(0.00090000.000) s

Accuracy
0.5% 10 ms

Reset/Set function block RSMEMORYQT


The Reset-set function (RSMEMORYQT) is a flip-flop with memory that can reset or set
an output from two inputs respectively. Each RSMEMORYQT function block has two
outputs, where one is inverted. The memory setting controls if, after a power interruption,

966

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

the flip-flop resets or returns to the state it had before the power interruption. For a ResetSet flip-flop, the RESET input has higher priority than the SET input.
RSMEMORYQT can propagate the quality, the value and the time stamps of the signals
via IEC61850.
Table 596:

Truth table for RSMEMORYQT function block

RESET

15.7.8.1

SET

OUT

NOUT

Last
value

Inverted last
value

Function block
RSMEMORYQT
SET
RESET

OUT
NOUT
IEC14000069-1-en.vsd

IEC14000069 V1 EN

Figure 444:

15.7.8.2

RSMEMORYQT function block

Signals
Table 597:
Name

RSMEMORYQT Input signals


Type

Default

Description

SET

BOOLEAN

Input signal to set

RESET

BOOLEAN

Input signal to reset

Table 598:
Name

RSMEMORYQT Output signals


Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

967

Section 15
Logic
15.7.8.3
Table 599:
Name
Memory

15.7.8.4

1MRK 502 066-UUS A

Settings
RSMEMORYQT Group settings (basic)
Values (Range)

Unit

Disabled
Enabled

Step

Description

Enabled

Operating mode of the memory function

Technical data
Table 600:

Number of RSMEMORYQT instances

Logic block

Quantity with cycle time


8 ms

3 ms

RSMEMORYQT

15.7.9

Default

10

100 ms
30

Set/Reset function block SRMEMORYQT


The Set-reset function (SRMEMORYQT) is a flip-flop with memory that can set or reset
an output from two inputs respectively. Each SRMEMORYQT function block has two
outputs, where one is inverted. The memory setting controls if, after a power interruption,
the flip-flop resets or returns to the state it had before the power interruption. The SET
input has priority.
SRMEMORYQT can propagate the quality, the value and the time stamps of the signals
via IEC61850.
Table 601:
SET

Truth table for SRMEMORYQT function block


RESET

OUT

NOUT

Last
value

Inverted
last value

If Memory parameter is Enabled, the output result is stored in semi-retained memory.

968

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.7.9.1

Function block
SRMEMORYQT
SET
RESET

OUT
NOUT
IEC14000070-1-en.vsd

IEC14000070 V1 EN

Figure 445:

15.7.9.2

SRMEMORYQT function block

Signals
Table 602:

SRMEMORYQT Input signals

Name

Type

Input signal to set

RESET

BOOLEAN

Input signal to reset

SRMEMORYQT Output signals

Name

Table 604:
Name
Memory

15.7.9.4

Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

Settings
SRMEMORYQT Group settings (basic)
Values (Range)
Disabled
Enabled

Unit

Step

Default

Description

Enabled

Operating mode of the memory function

Technical data
Table 605:
Logic block
SRMEMORYQT

15.7.10

Description

BOOLEAN

Table 603:

15.7.9.3

Default

SET

Number of SRMEMORYQT instances


3 ms
-

Quantity with cycle time


8 ms
10

100 ms
30

Settable timer function block TIMERSETQT

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

969

Section 15
Logic

1MRK 502 066-UUS A

The Settable timer function block (TIMERSETQT) has two outputs for delay of the input
signal at pick-up and drop-out. The timer has a settable time delay (t). It also has an
Operation setting On/Off that controls the operation of the timer.
When the output changes value, the timestamp of the output signal is updated. The
supported quality state bits are propagated from the input to the output at each execution
cycle. A change of these bits will not lead to an updated timestamp on the output.
TIMERSETQT can propagate the quality, value and the timestamps of the signals via
IEC61850.

15.7.10.1

Function block
TIMERSETQT
INPUT

ON
OFF
IEC14000068-1-en.vsd

IEC14000068 V1 EN

Figure 446:

15.7.10.2

TIMERSETQT function

Signals
Table 606:

TIMERSETQT Input signals

Name

Type

INPUT

BOOLEAN

Table 607:

Table 608:
Name

Description
Input signal

TIMERSETQT Output signals

Name

15.7.10.3

Default

Type

Description

ON

BOOLEAN

Output signal, pick-up delayed

OFF

BOOLEAN

Output signal, drop-out delayed

Settings
TIMERSETQT Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

0.000 - 90000.000

0.001

0.000

Delay for settable timer n

970

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.7.10.4

Technical data
Table 609:

Number of TIMERSETQT instances

Logic block

Quantity with cycle time


3 ms
8 ms
100 ms

TIMERSETQT

15.7.11

10

Range or Value

30

(0.00090000.000) s

Accuracy
0.5% 10 ms

Exclusive OR function block XORQT


The exclusive OR function (XORQT) function is used to generate combinatory
expressions with boolean variables. XORQT function has two inputs and two outputs.
One of the outputs is inverted. The output signal OUT is 1 if the input signals are different
and 0 if they are equal.
Table 610:

Truth table for XORQT function block

INPUT1

INPUT2

OUT

NOUT

XORQT can propagate the quality, value and time stamps of the signals via IEC61850.

15.7.11.1

Function block
XORQT
INPUT1
INPUT2

OUT
NOUT
IEC09000300-1-en.vsd

IEC09000300 V1 EN

Figure 447:

15.7.11.2

XORQT function block

Signals
Table 611:
Name

XORQT Input signals


Type

Default

Description

INPUT1

BOOLEAN

Input signal 1

INPUT2

BOOLEAN

Input signal 2

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

971

Section 15
Logic

1MRK 502 066-UUS A

Table 612:

XORQT Output signals

Name

15.7.11.3

Type
BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

Technical data
Table 613:

Number of XORQT instances

Logic block

3 ms

XORQT

15.8

Description

OUT

Quantity with cycle time


8 ms
10

100 ms
30

Extension logic package


When extra configurable logic blocks are required, an additional package can be ordered.
Table 614:

Number of instances in the extension logic package

Logic block

972

3 ms

Quantity with cycle time


8 ms

100 ms

AND

40

40

100

GATE

49

INV

40

40

100

LLD

49

OR

40

40

100

PULSETIMER

49

SLGAPC

10

10

54

SRMEMORY

110

TIMERSET

49

VSGAPC

10

10

110

XOR

49

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.9

Fixed signals FXDSIGN

15.9.1

Identification
Function description

IEC 61850
identification

Fixed signals

15.9.2

IEC 60617
identification

FXDSIGN

ANSI/IEEE C37.2
device number
-

Functionality
The Fixed signals function FXDSIGN generates nine pre-set (fixed) signals that can be
used in the configuration of an IED, either for forcing the unused inputs in other function
blocks to a certain level/value, or for creating certain logic. Boolean, integer, floating
point, string types of signals are available.
One FXDSIGN function block is included in all IEDs.

15.9.3

Function block
FXDSIGN
OFF
ON
INTZERO
INTONE
INTALONE
REALZERO
STRNULL
ZEROSMPL
GRP_OFF
IEC05000445-3-en.vsd
IEC05000445 V3 EN

Figure 448:

15.9.4

FXDSIGN function block

Signals
Table 615:
Name

FXDSIGN Output signals


Type

Description

OFF

BOOLEAN

Boolean signal fixed off

ON

BOOLEAN

Boolean signal fixed on

INTZERO

INTEGER

Integer signal fixed zero

INTONE

INTEGER

Integer signal fixed one

INTALONE

INTEGER

Integer signal fixed all ones

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

973

Section 15
Logic

1MRK 502 066-UUS A

Name

15.9.5

Type

Description

REALZERO

REAL

Real signal fixed zero

STRNULL

STRING

String signal with no characters

ZEROSMPL

GROUP SIGNAL

Channel id for zero sample

GRP_OFF

GROUP SIGNAL

Group signal fixed off

Settings
The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).

15.9.6

Operation principle
There are nine outputs from FXDSIGN function block:

OFF is a boolean signal, fixed to OFF (boolean 0) value


ON is a boolean signal, fixed to ON (boolean 1) value
INTZERO is an integer number, fixed to integer value 0
INTONE is an integer number, fixed to integer value 1
INTALONE is an integer value FFFF (hex)
REALZERO is a floating point real number, fixed to 0.0 value
STRNULL is a string, fixed to an empty string (null) value
ZEROSMPL is a channel index, fixed to 0 value
GRP_OFF is a group signal, fixed to 0 value

15.10

Boolean 16 to Integer conversion B16I

15.10.1

Identification
Function description
Boolean 16 to integer conversion

IEC 61850
identification
B16I

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary


(logical) signals into an integer.

974

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.10.2

Function block
B16I
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

OUT

IEC07000128-2-en.vsd
IEC07000128 V2 EN

Figure 449:

15.10.3

B16I function block

Signals
Table 616:
Name

B16I Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN1

BOOLEAN

Input 1

IN2

BOOLEAN

Input 2

IN3

BOOLEAN

Input 3

IN4

BOOLEAN

Input 4

IN5

BOOLEAN

Input 5

IN6

BOOLEAN

Input 6

IN7

BOOLEAN

Input 7

IN8

BOOLEAN

Input 8

IN9

BOOLEAN

Input 9

IN10

BOOLEAN

Input 10

IN11

BOOLEAN

Input 11

IN12

BOOLEAN

Input 12

IN13

BOOLEAN

Input 13

IN14

BOOLEAN

Input 14

IN15

BOOLEAN

Input 15

IN16

BOOLEAN

Input 16

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

975

Section 15
Logic

1MRK 502 066-UUS A

Table 617:

B16I Output signals

Name

Type

OUT

15.10.4

Output value

Monitored data
Table 618:

B16I Monitored data

Name

Type

OUT

15.10.5

Description

INTEGER

Values (Range)

INTEGER

Unit

Description

Output value

Settings
The function does not have any parameters available in the local HMI or PCM600.

15.10.6

Operation principle
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to
16 binary inputs INx, where 1x16, to an integer. Each INx represents a value according
to the table below from 0 to 32768. This follows the general formula: INx = 2x-1 where
1x16. The sum of all the values on the activated INx will be available on the output
OUT as a sum of the integer values of all the inputs INx that are activated. OUT is an
integer. When all INx (where 1x16) are activated, that is = Boolean 1, it corresponds to
that integer 65535 is available on the output OUT. The B16I function is designed for
receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze
the output at the last value.
Values of each of the different OUTx from function block B16I for 1x16.
The sum of the value on each INx corresponds to the integer presented on the output OUT
on the function block B16I
Name of input

Type

Default

Description

Value when
activated

Value when
deactivated

IN1

BOOLEAN

Input 1

IN2

BOOLEAN

Input 2

IN3

BOOLEAN

Input 3

IN4

BOOLEAN

Input 4

IN5

BOOLEAN

Input 5

16

IN6

BOOLEAN

Input 6

32

IN7

BOOLEAN

Input 7

64

Table continues on next page

976

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Name of input

Type

Default

Description

Value when
activated

Value when
deactivated

IN8

BOOLEAN

Input 8

128

IN9

BOOLEAN

Input 9

256

IN10

BOOLEAN

Input 10

512

IN11

BOOLEAN

Input 11

1024

IN12

BOOLEAN

Input 12

2048

IN13

BOOLEAN

Input 13

4096

IN14

BOOLEAN

Input 14

8192

IN15

BOOLEAN

Input 15

16384

IN16

BOOLEAN

Input 16

32768

The sum of the numbers in column Value when activated when all INx (where 1x16)
are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to
an integer by the B16I function block.

15.10.7

Technical data
Table 619:

Number of B16I instances

Function
B16I

Quantity with cycle time


8 ms

3 ms
6

100 ms
8

15.11

Boolean 16 to Integer conversion with logic node


representation BTIGAPC

15.11.1

Identification
Function description
Boolean 16 to integer conversion with
logic node representation

IEC 61850
identification
BTIGAPC

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

977

Section 15
Logic
15.11.2

1MRK 502 066-UUS A

Functionality
Boolean 16 to integer conversion with logic node representation function BTIGAPC is
used to transform a set of 16 binary (logical) signals into an integer. The block input will
freeze the output at the last value.
BTIGAPC can receive remote values via IEC 61850 depending on the operator position
input (PSTO).

15.11.3

Function block
BTIGAPC
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

OUT

IEC13000303-1-en.vsd
IEC13000303 V1 EN

Figure 450:

15.11.4

BTIGAPC function block

Signals
Table 620:
Name

BTIGAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN1

BOOLEAN

Input 1

IN2

BOOLEAN

Input 2

IN3

BOOLEAN

Input 3

IN4

BOOLEAN

Input 4

IN5

BOOLEAN

Input 5

IN6

BOOLEAN

Input 6

IN7

BOOLEAN

Input 7

IN8

BOOLEAN

Input 8

IN9

BOOLEAN

Input 9

Table continues on next page

978

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Name

Default

Description

BOOLEAN

Input 10

IN11

BOOLEAN

Input 11

IN12

BOOLEAN

Input 12

IN13

BOOLEAN

Input 13

IN14

BOOLEAN

Input 14

IN15

BOOLEAN

Input 15

IN16

BOOLEAN

Input 16

Table 621:
Name
OUT

15.11.5

Type

IN10

BTIGAPC Output signals


Type

Description

INTEGER

Output value

Settings
The function does not have any parameters available in the local HMI or PCM600.

15.11.6

Monitored data
Table 622:
Name
OUT

15.11.7

BTIGAPC Monitored data


Type
INTEGER

Values (Range)
-

Unit
-

Description
Output value

Operation principle
The Boolean 16 to integer conversion with logic node representation function
(BTIGAPC) will transfer a combination of up to 16 binary inputs INx, where 1x16, to
an integer. Each INx represents a value according to the table below from 0 to 32768. This
follows the general formula: INx = 2x-1 where 1x16. The sum of all the values on the
activated INx will be available on the output OUT as a sum of the integer values of all the
inputs INx that are activated. OUT is an integer. When all INx (where 1x16) are
activated, that is = Boolean 1, it corresponds to that integer 65535 is available on the
output OUT. The BTIGAPC function is designed for receiving the integer input from a
station computer - for example, over IEC 61850. If the BLOCK input is activated, it will
freeze the logical outputs at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1x16.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

979

Section 15
Logic

1MRK 502 066-UUS A

The sum of the value on each INx corresponds to the integer presented on the output OUT
on the function block BTIGAPC.
Name of input

Type

Default

Description

Value when
activated

Value when
deactivated

IN1

BOOLEAN

Input 1

IN2

BOOLEAN

Input 2

IN3

BOOLEAN

Input 3

IN4

BOOLEAN

Input 4

IN5

BOOLEAN

Input 5

16

IN6

BOOLEAN

Input 6

32

IN7

BOOLEAN

Input 7

64

IN8

BOOLEAN

Input 8

128

IN9

BOOLEAN

Input 9

256

IN10

BOOLEAN

Input 10

512

IN11

BOOLEAN

Input 11

1024

IN12

BOOLEAN

Input 12

2048

IN13

BOOLEAN

Input 13

4096

IN14

BOOLEAN

Input 14

8192

IN15

BOOLEAN

Input 15

16384

IN16

BOOLEAN

Input 16

32768

The sum of the numbers in column Value when activated when all INx (where 1x16)
are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to
an integer by the BTIGAPC function block.

15.11.8

Technical data
Table 623:
Function
BTIGAPC

980

Number of BTIGAPC instances


3 ms
4

Quantity with cycle time


8 ms
4

100 ms
8

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.12

Integer to boolean 16 conversion IB16

15.12.1

Identification
Function description

IEC 61850
identification

Integer to boolean 16 conversion

15.12.2

IEC 60617
identification

IB16

ANSI/IEEE C37.2
device number
-

Functionality
Integer to boolean 16 conversion function IB16 is used to transform an integer into a set
of 16 binary (logical) signals.

15.12.3

Function block
IB16
BLOCK
INP

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
ANSI06000501-1-en.vsd

ANSI06000501 V1 EN

Figure 451:

15.12.4

IB16 function block

Signals
Table 624:
Name

IB16 Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INP

INTEGER

Integer Input

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

981

Section 15
Logic

1MRK 502 066-UUS A

Table 625:
Name

15.12.5

IB16 Output signals


Type

Description

OUT1

BOOLEAN

Output 1

OUT2

BOOLEAN

Output 2

OUT3

BOOLEAN

Output 3

OUT4

BOOLEAN

Output 4

OUT5

BOOLEAN

Output 5

OUT6

BOOLEAN

Output 6

OUT7

BOOLEAN

Output 7

OUT8

BOOLEAN

Output 8

OUT9

BOOLEAN

Output 9

OUT10

BOOLEAN

Output 10

OUT11

BOOLEAN

Output 11

OUT12

BOOLEAN

Output 12

OUT13

BOOLEAN

Output 13

OUT14

BOOLEAN

Output 14

OUT15

BOOLEAN

Output 15

OUT16

BOOLEAN

Output 16

Setting parameters
The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)

15.12.6

Operation principle
With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the
remaining OUTx = 0 for (5x16).
OUTx represents a value when activated. The value of each of the OUTx is in accordance
with the table IB16_1. When not activated the OUTx has the value 0.
In the above example when integer 15 is on the input INP the OUT1 has a value =1, OUT2
has a value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum of these OUTx
is equal to 1 + 2 + 4 + 8 = 15.
This follows the general formulae: The sum of the values of all OUTx = 2x-1 where
1x16 will be equal to the integer value on the input INP.

982

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

The Integer to Boolean 16 conversion function (IB16) will transfer an integer with a value
between 0 to 65535 connected to the input INP to a combination of activated outputs
OUTx where 1x16. The sum of the values of all OUTx will then be equal to the integer
on input INP. The values of the different OUTx are according to the table below. When an
OUTx is not activated, its value is 0.
When all OUTx where 1x16 are activated that is = Boolean 1 it corresponds to that
integer 65535 is connected to input INP. The IB16 function is designed for receiving the
integer input locally. If the BLOCK input is activated, it will freeze the logical outputs at
the last value.
Values of each of the different OUTx from function block IB16 for 1x16.
The sum of the value on each INx corresponds to the integer presented on the output OUT
on the function block IB16.
Name of OUTx

Type

Description

Value when
activated

Value when
deactivated

OUT1

BOOLEAN

Output 1

OUT2

BOOLEAN

Output 2

OUT3

BOOLEAN

Output 3

OUT4

BOOLEAN

Output 4

OUT5

BOOLEAN

Output 5

16

OUT6

BOOLEAN

Output 6

32

OUT7

BOOLEAN

Output 7

64

OUT8

BOOLEAN

Output 8

128

OUT9

BOOLEAN

Output 9

256

OUT10

BOOLEAN

Output 10

512

OUT11

BOOLEAN

Output 11

1024

OUT12

BOOLEAN

Output 12

2048

OUT13

BOOLEAN

Output 13

4096

OUT14

BOOLEAN

Output 14

8192

OUT15

BOOLEAN

Output 15

16384

OUT16

BOOLEAN

Output 16

32768

The sum of the numbers in column Value when activated when all OUTx (where x = 1
to 16) are active that is=1; is 65535. 65535 is the highest integer that can be converted by
the IB16 function block.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

983

Section 15
Logic
15.12.7

1MRK 502 066-UUS A

Technical data
Table 626:

Number of IB16 instances

Function

Quantity with cycle time


8 ms

3 ms

IB16

100 ms
8

15.13

Integer to Boolean 16 conversion with logic node


representation ITBGAPC

15.13.1

Identification
Function description
Integer to boolean 16 conversion with
logic node representation

15.13.2

IEC 61850
identification
ITBGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
Integer to boolean conversion with logic node representation function ITBGAPC is used
to transform an integer which is transmitted over IEC 61850 and received by the function
to 16 binary coded (logic) output signals.
ITBGAPC function can only receive remote values over IEC 61850 when the R/L
(Remote/Local) push button on the front HMI, indicates that the control mode for the
operator is in position R (Remote i.e. the LED adjacent to R is lit ), and the corresponding
signal is connected to the input PSTO ITBGAPC function block. The input BLOCK will
freeze the output at the last received value and blocks new integer values to be received
and converted to binary coded outputs.

984

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.13.3

Function block
ITBGAPC
BLOCK
PSTO

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC14000012-1-en.vsd

IEC14000012 V1 EN

Figure 452:

15.13.4

ITBGAPC function block

Signals
Table 627:
Name

ITBGAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

Table 628:
Name

ITBGAPC Output signals


Type

Description

OUT1

BOOLEAN

Output 1

OUT2

BOOLEAN

Output 2

OUT3

BOOLEAN

Output 3

OUT4

BOOLEAN

Output 4

OUT5

BOOLEAN

Output 5

OUT6

BOOLEAN

Output 6

OUT7

BOOLEAN

Output 7

OUT8

BOOLEAN

Output 8

OUT9

BOOLEAN

Output 9

OUT10

BOOLEAN

Output 10

OUT11

BOOLEAN

Output 11

OUT12

BOOLEAN

Output 12

OUT13

BOOLEAN

Output 13

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

985

Section 15
Logic

1MRK 502 066-UUS A

Name

15.13.5

Type

Description

OUT14

BOOLEAN

Output 14

OUT15

BOOLEAN

Output 15

OUT16

BOOLEAN

Output 16

Settings
This function does not have any setting parameters.

15.13.6

Operation principle
An example is used to explain the principle of operation: With integer 15 sent to and
received by the ITBGAPC function on the IEC61850 the OUTx changes from 0 to 1 on
each of the OUT1; OUT2 OUT3 and OUT4. All other OUTx (5x16) remains 0. The
boolean interpretation of this is represented by the assigned values of each of the outputs
OUT1 = 1; and OUT2 = 2; and OUT3= 4; and OUT4 = 8. The sum of these OUTx (1x4)
is equal to the integer 15 received via the IEC61850 network. The remaining OUTx = 0
for (5x16).
OUTx represents a value when activated. The value of each of the OUTx is in accordance
with the Table 629. When not activated the OUTx has the value 0.
The value of each OUTx for 1x16 (1x16) follows the general formulae: OUTx = 2x-1
The sum of the values of all activated OUTx = 2x-1 where 1x16 will be equal to the
integer value received over IEC61850 to the ITBGAPC_1 function block.
The Integer to Boolean 16 conversion with logic node representation function
(ITBGAPC) will transfer an integer with a value between 0 to 65535 communicated via
IEC61850 and connected to the ITBGAPC function block to a combination of activated
outputs OUTx where 1x16. The values represented by the different OUTx are
according to Table 629. When an OUTx is not activated, its value is 0.
The ITBGAPC function is designed for receiving the integer input from a station
computer - for example, over IEC 61850. If the BLOCK input is activated, it will freeze
the logical outputs at the last value.
Table 629:

Outputs and their values when activated

Name of OUTx

Type

Description

Value when
activated

Value when
deactivated

OUT1

BOOLEAN

Output 1

OUT2

BOOLEAN

Output 2

OUT3

BOOLEAN

Output 3

Table continues on next page

986

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Name of OUTx

Type

Description

Value when
activated

Value when
deactivated

OUT4

BOOLEAN

Output 4

OUT5

BOOLEAN

Output 5

16

OUT6

BOOLEAN

Output 6

32

OUT7

BOOLEAN

Output 7

64

OUT8

BOOLEAN

Output 8

128

OUT9

BOOLEAN

Output 9

256

OUT10

BOOLEAN

Output 10

512

OUT11

BOOLEAN

Output 11

1024

OUT12

BOOLEAN

Output 12

2048

OUT13

BOOLEAN

Output 13

4096

OUT14

BOOLEAN

Output 14

8192

OUT15

BOOLEAN

Output 15

16384

OUT16

BOOLEAN

Output 16

32768

The sum of the numbers in column Value when activated when all OUTx (1x16) are
active equals 65535. This is the highest integer that can be converted to boolean by the
ITBGAPC function block.
The operator position input (PSTO) determines the operator place. The integer number
that is communicated to the ITBGAPC can only be written to the block while the PSTO
is in position Remote. If PSTO is in position Off or Local, then no changes are
applied to the outputs.

15.13.7

Technical data
Table 630:
Function
ITBGAPC

15.14

Number of ITBGAPC instances


3 ms
4

Quantity with cycle time


8 ms
4

100 ms
8

Pulse integrator TIGAPC

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

987

Section 15
Logic
15.14.1

1MRK 502 066-UUS A

Identification
Function description

IEC 61850
identification

Pulse integrator

15.14.2

IEC 60617
identification

ANSI/IEEE C37.2
device number

TIGAPC

Functionality
The integrator function TIGAPC integrates input pulses and compares the integrated time
with a settable time delay to operate. Moreover, the time delay to reset the output is
settable in this function.

15.14.3

Function block
TIGAPC
IN

OUT
ANSI14000062-1-en.vsd

ANSI14000062 V1 EN

Figure 453:

15.14.4

TIGAPC function block

Signals
Table 631:

TIGAPC Input signals

Name

Type

IN

BOOLEAN

Table 632:

Type

OUT

Table 633:
Name

Description
Input to integrator

TIGAPC Output signals

Name

15.14.5

Default

Description

BOOLEAN

Output from integrator

Settings
TIGAPC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

tDelay

0.000 - 600.000

0.001

1.000

Time delay to operate

tReset

0.000 - 600.000

0.001

1.000

Time delay to reset

988

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.14.6

Operation principle
In the pulse integrator TIGAPC, the time during which the input is high is integrated. This
means there is no output until the sum of the input pulses equals the set time delay to
operate. The output is deactivated when the input signal is FALSE and the time delay to
reset has elapsed.
1
In
t int

t Reset
0

t Delay
Integration

Out

t
IEC13000175-2-en.vsd

IEC13000175 V2 EN

Figure 454:

IN pulse length sufficient for integration to reach the set tDelay, OUT is set
until the tReset time has elapsed, which resets tDelay and OUT

t Reset

In
t int

t Delay

Integration

Out

IEC13000174=2=en.vsd
IEC13000174 V1 EN

Figure 455:

IN pulse too short for integration to reach the set tDelay

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

989

Section 15
Logic

1MRK 502 066-UUS A

t Reset

In
t int
t Delay
Integration

Out

t Reset

t Reset

t
IEC13000176-2-en.vsd

IEC13000176 V1 EN

Figure 456:

IN pulse too short for integration to reach the set tDelay, and tReset resets
integration before next pulse can be integrated.

t Reset

In

tReset

t int
t Delay
Integration

tReset

Out

t
IEC13000177-2-en.vsd

IEC13000177 V2 EN

Figure 457:

tint

The next IN pulse is received before tReset has elapsed. Sufficient time
during the pulses is accumulated to reach tDelay. When tDelay is reached,
OUT is set until tReset time has elapsed, which resets tDelay and OUT.

integration time

tReset time delay to reset


tDelay

990

time delay to operate

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

Table 634:

TIGAPC technical data

Function

Cycle time (ms)

Time integration
continuous active

Range of value

Accuracy
0.2% or 20 ms whichever is
greater

0-999999.99 s

Time integration
continuous active

0-999999.99 s

0.2% or 50 ms whichever is
greater

Time integration
continuous active

100

0-999999.99 s

0.2% or 250 ms whichever is


greater

Table 635:

Number of TIGAPC instances

Function
TIGAPC

Quantity with cycle time


8 ms

3 ms
-

30

100 ms
-

15.15

Elapsed time integrator with limit transgression and


overflow supervision TEIGAPC

15.15.1

Identification
Function Description
Elapsed time integrator

15.15.2

IEC 61850
identification
TEIGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2 device


number
-

Functionality
Elapsed Time Integrator (TEIGAPC) function is a function that accumulates the elapsed
time when a given binary signal has been high, see also Figure 458.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

991

Section 15
Logic

1MRK 502 066-UUS A

BLOCK
RESET
IN

ACCTIME

Time Integration
with Retain

q-1

999 999 s

a>b

tWarning

a>b

tAlarm

q-1 = unit delay

a>b

AND

AND

AND

OVERFLOW

WARNING

ALARM

IEC13000290-2-en.vsd

IEC13000290 V2 EN

Figure 458:

TEIGAPC logics

The main features of TEIGAPC

15.15.3

Applicable to long time integration up to 999 999.9 seconds


Supervision of overflow
Possibility to define a warning and an alarm with the resolution of 10 milliseconds
Retain the integration value
Possibilities for blocking and reset of the total integrated time
Report of the integrated time

Function block
TEIGAPC
BLOCK
IN
RESET

WARNING
ALARM
OVERFLOW
ACCTIME
IEC14000014-1-en.vsd

IEC14000014 V1 EN

Figure 459:

992

TEIGAPC function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.15.4

Signals
Table 636:

TEIGAPC Input signals

Name

Type

Freeze the integration and block the other outputs

IN

BOOLEAN

The input signal that is used to measure the elapsed


time, when its value is high

RESET

BOOLEAN

Reset the integration time

TEIGAPC Output signals

Name

Table 638:
Name

Description

BOOLEAN

Table 637:

15.15.5

Default

BLOCK

Type

Description

WARNING

BOOLEAN

Indicator of the integrated time has reached the warning


limit

ALARM

BOOLEAN

Indicator of the integrated time has reached the alarm


limit

OVERFLOW

BOOLEAN

Indicator of the integrated time has reached the overflow


limit

ACCTIME

REAL

Integrated elapsed time in seconds

Settings
TEIGAPC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

tWarning

1.00 - 999999.99

0.01

600.00

Time limit for warning supervision

tAlarm

1.00 - 999999.99

0.01

1200.00

Time limit for alarm supervision

15.15.6

Operation principle
The elapsed time integrator (TEIGAPC) provides

time integration, accumulating the elapsed time when a given binary signal has been
high
blocking and reset of the total integrated time
supervision of limit transgression and overflow, the overflow limit is fixed to
999999.9 seconds
retaining of the integrated value

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

993

Section 15
Logic

1MRK 502 066-UUS A

Figure 460 describes the simplified logic of the function where the block Time
Integration covers the logics for the first two items listed above while the block
Transgression Supervision Plus Retain contains the logics for the last two.

Loop Delay

tWarning

OVERFLOW

tAlarm

WARNING

Transgression Supervision
Plus Retain

ALARM

BLOCK
RESET

ACCTIME

Time Integration

IN

Loop Delay

IEC12000195-3-en.vsd

IEC12000195 V3 EN

Figure 460:

TEIGAPC Simplified logic

TEIGAPC main functionalities

integration of the elapsed time when IN has been high

RESET: Reset of the integration value. Consequently all other outputs are also reset

unconditionally on the signal value


BLOCK request overrides RESET request

Monitor and report the conditions of limit transgression

994

unconditionally on the input IN value


reset the value of the nonvolatile memory to zero

BLOCK: Freeze the integration and block/reset the other outputs

applicable to long time integration (999 999.9 seconds)


output ACCTIME presents integrated value in seconds
integrated value is retained in nonvolatile memory
any retained value with a warning/alarm/overflow is used as initiation value for
the integration following by a restart

overflow if output ACCTIME >999999.9 seconds


alarm if ACCTIME > tAlarm
warning if ACCTIME > tWarning

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

The ACCTIME output represents the integrated time in seconds while tOverflow, tAlarm
and tWarning are the time limit parameters in seconds.
tAlarm and tWarning are user settable limits. They are also independent, that is, there is
no check if tAlarm > tWarning.
tAlarm and tWarning are possible to be defined with a resolution of 10 ms, depending on
the level of the defined values for the parameters.
The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs freeze if
an overflow occurs.

15.15.6.1

Operation accuracy
The accuracy of TEIGAPC depends on essentially three factors

function cycle time


the pulse length
the number of pulses, that is, the number of rising and falling flank pairs

In principle, a shorter function cycle time, longer integrated time length or more pulses
may lead to reduced accuracy.

15.15.6.2

Memory storage
The value of the integrated elapsed time is retained in a non-volatile memory.

15.15.7

Technical data
Table 639:

TEIGAPC Technical data

Function

Cycle time (ms)

Elapsed time integration

Table 640:
Function
TEIGAPC

Range or value

Accuracy

0 ~ 999999.9 s

0.2% or 20 ms
whichever is greater

0 ~ 999999.9 s

0.2% or 100 ms
whichever is greater

100

0 ~ 999999.9 s

0.2% or 250 ms
whichever is greater

Number of TEIGAPC instances


3 ms
4

Quantity with cycle time


8 ms
4

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

100 ms
4

995

Section 15
Logic

1MRK 502 066-UUS A

15.16

Comparator for integer inputs INTCOMP

15.16.1

Identification
Function description

IEC 61850
identification

Comparison of integer values

15.16.2

IEC 60617
identification

INTCOMP

ANSI/IEEE C37.2
device number

Int<=>

Functionality
The function gives the possibility to monitor the level of integer values in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be used
for monitoring, supervision, interlocking and other logics.

15.16.3

Function block
INTCOMP
INPUT
REF

INEQUAL
INHIGH
INLOW
IEC15000052-1-en.vsdx

IEC15000052 V1 EN

15.16.4

Signals
Table 641:
Name

Type

Default

Description

INPUT

INTEGER

Input value to be compared with reference value

REF

INTEGER

Reference value to be compared with input value

Table 642:
Name

996

INTCOMP Input signals

INTCOMP Output signals


Type

Description

INEQUAL

BOOLEAN

Input value is equal to the reference value

INHIGH

BOOLEAN

Input value is higher than the reference value

INLOW

BOOLEAN

Input value is lower than the reference value

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.16.5
Table 643:
Name

Settings
INTCOMP Group settings (basic)
Values (Range)

Unit

Step

Default

Description

EnaAbs

Signed
Absolute

Signed

Selection for absolute or signed comparison

RefSource

Set Value
Input REF

Set Value

Selection for reference value either input or


setting

SetValue

-2000000000 2000000000

100

Set value for reference

15.16.6

Operation principle
The comparison can be done in two ways,

Between 2 inputs, INPUT and REF


Between INPUT and the value set by the user SetValue.

The selection of reference value for comparison can be done through setting RefSource. If
RefSource is selected as REF then the reference value for comparison is taken from second
input signal (REF). If RefSource is selected as SetValue then the reference value for
comparison is taken from setting (SetValue).
The comparison can be done either between absolute values or signed values and it
depends on the setting EnaAbs. If EnaAbs is selected as Absolute then both input and
reference value is converted into absolute values and comparison is done. If EnaAbs is
selected as Signed then the comparison is done without any conversion.
The function has three state outputs high, low and equal to condition. It will check the
following condition and give corresponding outputs.

If the input is above the reference value then INHIGH will set
If the input is below the reference value then INLOW will set
If the input is equal to reference value then INEQUAL will set

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

997

Section 15
Logic

1MRK 502 066-UUS A

EnaAbs

INPUT

ABS

b
a

INHIGH

a>b

INEQUAL

a=b

RefSource

REF

SetValue

ABS

INLOW

a<b

IEC15000129-2-en.vsdx
IEC15000129 V2 EN

Figure 461:

15.16.7

Function logic diagram for INTCOMP

Technical data
Table 644:

Number of INTCOMP instances

Function

3 ms

INTCOMP

Quantity with cycle time


8 ms

15.17

Comparator for real inputs - REALCOMP

15.17.1

Identification
Function description
Comparator for real inputs

15.17.2

IEC 61850
identification
REALCOMP

100 ms

IEC 60617
identification

ANSI/IEEE C37.2
device number

Real<=>

Functionality
The function gives the possibility to monitor the level of real value signals in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be used
for monitoring, supervision, interlocking and other logics.

998

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

15.17.3

Function block
REALCOMP
INPUT
REF

INEQUAL
INHIGH
INLOW
IEC15000053-1-en.vsdx

IEC15000053 V1 EN

15.17.4

Signals
Table 645:

REALCOMP Input signals

Name

Type

0.000

Input value to be compared with reference value

REF

REAL

0.000

Reference value to be compared with input value

REALCOMP Output signals

Name

Table 647:
Name

Description

REAL

Table 646:

15.17.5

Default

INPUT

Type

Description

INEQUAL

BOOLEAN

Input value is equal to the reference value

INHIGH

BOOLEAN

Input value is higher than the reference value

INLOW

BOOLEAN

Input value is lower than the reference value

Settings
REALCOMP Group settings (basic)
Values (Range)

Unit

Step

Default

Description

EnaAbs

Signed
Absolute

Signed

Selection for absolute or signed comparison

RefSource

Set Value
Input REF

Set Value

Selection for reference value either input or


setting

SetValue

-999.999 - 999.999

0.001

0.001

Set value for reference

SetValPrefix

milli
unit
kilo
Mega
Giga

unit

Multiplication factor for SetValue

EqualBandHigh

0.10 - 10.00

0.01

0.50

Equal band high limit in % of reference value

EqualBandLow

0.10 - 10.00

0.01

0.50

Equal band low limit in % of reference value

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

999

Section 15
Logic
15.17.6

1MRK 502 066-UUS A

Operation principle
The comparison can be done in two ways,
1.
2.

Between 2 inputs, INPUT and REF


Between INPUT and the value set by the user SetValue

The selection of reference value for comparison can be done through setting RefSource. If
RefSource is selected as REF then the reference value for comparison is taken from second
input signal (REF). If RefSource is selected as SetValue then the reference value for
comparison is taken from setting (SetValue).
Generally the inputs to the function are in SI units, but when the comparison is to be done
with respect to set level, then the user can set a value in any unit out of Milli to Giga range
in setting SetValue. The unit can be separately set with setting RefPrefix. Internally the
function handles the reference value for comparator as SetValue*RefPrefix.
Additionally the comparison can be done either between absolute values or signed values
and it depends on the setting EnaAbs. If EnaAbs is selected as Absolute then both input and
reference value is converted into absolute values and comparison is done. If EnaAbs is
selected as Signed then the comparison is done without any conversion.

EnaAbs
INPUT

ABS

T
F

High
Comparator

EqualBandHigh

RefSource
REF
SetValue

INHIGH

XOR
T
F

ABS

INEQUAL

T
F

Low
comparator

INLOW

RefPrefix
EqualBandLow

IEC15000130-1-en.vsdx
IEC15000130 V1 EN

Figure 462:

Logic diagram for REALCOMP

This function has two settings EqualBandHigh and EqualBandLow to provide margins
from reference value for equal to condition. When the INPUT value is within high and low
band, output INEQUAL will get set.
If the INPUT is above the equal high level margin then output INHIGH will set. Similarly
if the INPUT is below the equal low level margin then output INLOW will set. In order to
1000

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 15
Logic

1MRK 502 066-UUS A

avoid oscillations at boundary conditions of equal band low limit and high limit, hysteresis
has been provided
INEQUAL Reset / INHIGH Set

INEQUAL Set / INHIGH Reset

EqualBandHigh

Equal Band

Internal
Hysteresis for
equal band

REF or SetValue

EqualBandLow

INEQUAL Reset / INLOW Set

INEQUAL Set / INLOW Reset


IEC15000261-1-en.vsdx

IEC15000261 V1 EN

Figure 463:

Operation principle of REALCOMP

When EnaAbs is set as absolute comparison and SetValue is set less than
0.2% of the set unit then INLOW output will never pickups. During the
above mentioned condition, due to marginal value for avoiding
oscillations of function outputs, the INLOW output will never set.

15.17.7

Technical data
REALCOMP function can compare the values from milli value level to giga value level
and the maximum expectable accuracy level from the function is 10 .
Table 648:

REALCOMP Technical data


Function

Accuracy

Operate value,
EqualBandHigh
and EqualBandLow

0.5% of set value

Reset value,
EqualBandHigh

> 0.1% of set RefPrefix

Reset value,
EqualBandLow

< 0.1% of set RefPrefix

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1001

Section 15
Logic

1MRK 502 066-UUS A

Table 649:
Function
REALCOMP

1002

Number of REALCOMP instances


3 ms
4

Quantity with cycle time


8 ms
4

100 ms
4

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Section 16

Monitoring

16.1

Measurements

16.1.1

Identification
Function description
Measurements

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
-

CVMMXN
P, Q, S, I, U, f

SYMBOL-RR V1 EN

Phase current measurement

CMMXU

I
SYMBOL-SS V1 EN

Phase-phase voltage measurement

VMMXU

U
SYMBOL-UU V1 EN

Current sequence component


measurement

CMSQI

Voltage sequence component


measurement

VMSQI

I1, I2, I0
SYMBOL-VV V1 EN

U1, U2, U0

SYMBOL-TT V1 EN

Phase-neutral voltage measurement

VNMMXU

U
SYMBOL-UU V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1003

Section 16
Monitoring
16.1.2

1MRK 502 066-UUS A

Functionality
Measurement functions are used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values of
active power, reactive power, currents, voltages, frequency, power factor etc. is vital for
efficient production, transmission and distribution of electrical energy. It provides to the
system operator fast and easy overview of the present status of the power system.
Additionally, it can be used during testing and commissioning of protection and control
IEDs in order to verify proper operation and connection of instrument transformers (CTs
and VTs). During normal service by periodic comparison of the measured value from the
IED with other independent meters the proper operation of the IED analog measurement
chain can be verified. Finally, it can be used to verify proper direction orientation for
distance or directional overcurrent protection function.
The available measured values of an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.
All measured values can be supervised with four settable limits that is, low-low limit, low
limit, high limit and high-high limit. A zero clamping reduction is also supported, that is,
the measured value below a settable limit is forced to zero which reduces the impact of
noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level when
change in measured value is above set threshold limit or time integral of all changes since
the last time value updating exceeds the threshold limit. Measure value can also be based
on periodic reporting.
Main menu/Measurement/Monitoring/Service values/CVMMXN
The measurement function, CVMMXN, provides the following power system quantities:

P, Q and S: three phase active, reactive and apparent power


PF: power factor
V: phase-to-phase voltage magnitude
I: phase current magnitude
F: power system frequency

,
The measuring functions CMMXU, VMMXU and VNMMXU provide physical
quantities:

1004

I: phase currents (magnitude and angle) (CMMXU)


V: voltages (phase-to-ground and phase-to-phase voltage, magnitude and angle)
(VMMXU, VNMMXU)
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

The CVMMXN function calculates three-phase power quantities by using fundamental


frequency phasors (DFT values) of the measured current respectively voltage signals. The
measured power quantities are available either, as instantaneously calculated quantities
or, averaged values over a period of time (low pass filtered) depending on the selected
settings.
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and magnitude compensation at 5, 30 and
100% of rated current and at 100% of rated voltage.
The power system quantities provided, depends on the actual hardware,
(TRM) and the logic configuration made in PCM600.
The measuring functions CMSQI and VMSQI provide sequence component quantities:

16.1.3

I: sequence currents (positive, zero, negative sequence, magnitude and angle)


V: sequence voltages (positive, zero and negative sequence, magnitude and angle).

Function block
The available function blocks of an IED are depending on the actual hardware (TRM) and
the logic configuration made in PCM600.

CVMMXN
I3P*
V3P*

S
S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
V
V_RANGE
I
I_RANGE
F
F_RANGE
ANSI10000016-1-en.vsd

ANSI10000016 V1 EN

Figure 464:

CVMMXN function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1005

Section 16
Monitoring

1MRK 502 066-UUS A

CMMXU
I3P*

I_A
IA_RANGE
IA_ANGL
I_B
IB_RANGE
IB_ANGL
I_C
IC_RANGE
IC_ANGL
ANSI05000699-2-en.vsd

ANSI05000699 V2 EN

Figure 465:

CMMXU function block

VMMXU
V3P*

V_AB
VAB_RANG
VAB_ANGL
V_BC
VBC_RANG
VBC_ANGL
V_CA
VCA_RANG
VCA_ANGL
ANSI05000701-2-en.vsd

ANSI05000701 V2 EN

Figure 466:

VMMXU function block

CMSQI
I3P*

3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL
IEC05000703-2-en.vsd

IEC05000703 V2 EN

Figure 467:

CMSQI function block

VMSQI
V3P*

3V0
3V0RANG
3V0ANGL
V1
V1RANG
V1ANGL
V2
V2RANG
V2ANGL
ANSI05000704-2-en.vsd

ANSI05000704 V2 EN

Figure 468:

1006

VMSQI function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

VNMMXU
V3P*

V_A
VA_RANGE
VA_ANGL
V_B
VB_RANGE
VB_ANGL
V_C
VC_RANGE
VC_ANGL
ANSI09000850-1-en.vsd

ANSI09000850 V1 EN

Figure 469:

16.1.4

VNMMXU function block

Signals
Table 650:
Name

CVMMXN Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

V3P

GROUP
SIGNAL

Group signal for voltage input

Table 651:
Name

CVMMXN Output signals


Type

Description

REAL

Apparent Power magnitude of deadband value

S_RANGE

INTEGER

Apparent Power range

P_INST

REAL

Active Power

REAL

Active Power magnitude of deadband value

P_RANGE

INTEGER

Active Power range

Q_INST

REAL

Reactive Power

REAL

Reactive Power magnitude of deadband value

Q_RANGE

INTEGER

Reactive Power range

PF

REAL

Power Factor magnitude of deadband value

PF_RANGE

INTEGER

Power Factor range

ILAG

BOOLEAN

Current is lagging voltage

ILEAD

BOOLEAN

Current is leading voltage

REAL

Calculated voltage magnitude of deadband value

V_RANGE

INTEGER

Calculated voltage range

REAL

Calculated current magnitude of deadband value

I_RANGE

INTEGER

Calculated current range

REAL

System frequency magnitude of deadband value

F_RANGE

INTEGER

System frequency range

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1007

Section 16
Monitoring

1MRK 502 066-UUS A

Table 652:
Name
I3P

Table 653:
Name

Type

Default

GROUP
SIGNAL

Description
Group signal for current input

CMMXU Output signals


Type

Description

IA

REAL

Phase A current magnitude of reported value

IA_RANGE

INTEGER

Phase A current magnitude range

IA_ANGL

REAL

Phase A current magnitude angle

IB

REAL

Phase B current magnitude of reported value

IB_RANGE

INTEGER

Phase B current magnitude range

IB_ANGL

REAL

Phase B current magnitude angle

IC

REAL

Phase C current magnitude of reported value

IC_RANGE

INTEGER

Phase C current magnitude range

IC_ANGL

REAL

Phase C current magnitude angle

Table 654:
Name
V3P

Table 655:
Name

1008

CMMXU Input signals

VMMXU Input signals


Type
GROUP
SIGNAL

Default
-

Description
Group connection abstract block 2

VMMXU Output signals


Type

Description

VAB

REAL

VAB Reported magnitude value

VAB_RANG

INTEGER

VAB Magnitude range

VAB_ANGL

REAL

VAB Angle, magnitude of reported value

VBC

REAL

VBC Reported magnitude value

VBC_RANG

INTEGER

VBC Magnitude range

VBC_ANGL

REAL

VBC Angle, magnitude of reported value

VCA

REAL

VCA Reported magnitude value

VCA_RANG

INTEGER

VCA Magnitude range

VCA_ANGL

REAL

VCA Angle, magnitude of reported value

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Table 656:
Name
I3P

Table 657:
Name

CMSQI Input signals


Type
GROUP
SIGNAL

Default
-

Description
Group connection abstract block 3

CMSQI Output signals


Type

Description

3I0

REAL

3I0 magnitude of reported value

3I0RANG

INTEGER

3I0 Magnitude range

3I0ANGL

REAL

3I0 Angle, magnitude of reported value

I1

REAL

I1magnitude of reported value

I1RANG

INTEGER

I1 Magnitude range

I1ANGL

REAL

I1 Angle, magnitude of reported value

I2

REAL

I2 Magnitude of reported value

I2RANG

INTEGER

I2 Magnitude range

I2ANGL

REAL

I2 Angle, magnitude of reported value

Table 658:
Name
V3P

Table 659:
Name

VMSQI Input signals


Type
GROUP
SIGNAL

Default
-

Description
Group connection abstract block 4

VMSQI Output signals


Type

Description

3V0

REAL

3V0 Reported magnitude value

3V0RANG

INTEGER

3V0 Magnitude range

3V0ANGL

REAL

3V0 Magnitude angle

V1

REAL

V1 Reported magnitude value

V1RANG

INTEGER

V1 Magnitude range

V1ANGL

REAL

V1 Magnitude angle

V2

REAL

V2 Reported magnitude value

V2RANG

INTEGER

V2 Magnitude range

V2ANGL

REAL

V2 Magnitude angle

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1009

Section 16
Monitoring

1MRK 502 066-UUS A

Table 660:
Name
V3P

Table 661:
Name

16.1.5

VNMMXU Input signals


Type
GROUP
SIGNAL

Default
-

Description
Group signal for voltage input

VNMMXU Output signals


Type

Description

VA

REAL

VA Amplitude, magnitude of reported value

VA_RANGE

INTEGER

VAAmplitude range

VA_ANGL

REAL

VA Angle, magnitude of reported value

VB

REAL

VB Amplitude, magnitude of reported value

VB_RANGE

INTEGER

VB Amplitude range

VB_ANGL

REAL

VB Angle, magnitude of reported value

VC

REAL

VC Amplitude, magnitude of reported value

VC_RANGE

INTEGER

VC Amplitude range

VC_ANGL

REAL

V_C Angle, magnitude of reported value

Settings
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in PCM600.
These six functions are not handled as a group, so parameter settings are only available in
the first setting group.
The following terms are used in the Unit and Description columns:

1010

VBase: Base voltage in primary kV. This voltage is used as reference for voltage
setting. It can be suitable to set this parameter to the rated primary voltage supervised
object.
IBase: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the supervised
object.
SBase: Base setting for power values in MVA.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Table 662:
Name

CVMMXN Non group settings (basic)


Step

Default

SLowLim

Values (Range)
0.0 - 2000.0

Unit
%SB

0.1

80.0

Description
Low limit in % of SBase

SLowLowLim

0.0 - 2000.0

%SB

0.1

60.0

Low Low limit in % of SBase

SMin

0.0 - 2000.0

%SB

0.1

50.0

Minimum value in % of SBase

SMax

0.0 - 2000.0

%SB

0.1

200.0

Maximum value in % of SBase

SRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

PMin

-2000.0 - 2000.0

%SB

0.1

-200.0

Minimum value in % of SBase

PMax

-2000.0 - 2000.0

%SB

0.1

200.0

Maximum value in % of SBase

PRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

QMin

-2000.0 - 2000.0

%SB

0.1

-200.0

Minimum value in % of SBase

QMax

-2000.0 - 2000.0

%SB

0.1

200.0

Maximum value in % of SBase

QRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

PFMin

-1.000 - 1.000

0.001

-1.000

Minimum value

PFMax

-1.000 - 1.000

0.001

1.000

Maximum value

PFRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

VMin

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

VMax

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

VRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

IMin

0.0 - 500.0

%IB

0.1

5.0

Minimum value in % of IBase

IMax

0.0 - 500.0

%IB

0.1

200.0

Maximum value in % of IBase

IRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

FrMin

0.000 - 100.000

Hz

0.001

0.000

Minimum value

FrMax

0.000 - 100.000

Hz

0.001

70.000

Maximum value

FrRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1011

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

Mode

A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C

A, B, C

Selection of measured current and voltage

PowMagFact

0.000 - 6.000

0.001

1.000

Magnitude factor to scale power calculations

PowAngComp

-180.0 - 180.0

Deg

0.1

0.0

Angle compensation for phase shift between


measured I & V

0.000 - 1.000

0.001

0.000

Low pass filter coefficient for power


measurement, V and I

Table 663:
Name

CVMMXN Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

SDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

SZeroDb

0 - 100000

m%

500

Zero point clamping in 0.001% of range

SHiHiLim

0.0 - 2000.0

%SB

0.1

150.0

High High limit in % of SBase

SHiLim

0.0 - 2000.0

%SB

0.1

120.0

High limit in % of SBase

SLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common for all


limits)

PDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

PZeroDb

0 - 100000

m%

500

Zero point clamping in 0.001% of range

PHiHiLim

-2000.0 - 2000.0

%SB

0.1

150.0

High High limit in % of SBase

PHiLim

-2000.0 - 2000.0

%SB

0.1

120.0

High limit in % of SBase

PLowLim

-2000.0 - 2000.0

%SB

0.1

-120.0

Low limit in % of SBase

PLowLowLim

-2000.0 - 2000.0

%SB

0.1

-150.0

Low Low limit in % of SBase

PLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common for all


limits)

QDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

QZeroDb

0 - 100000

m%

500

Zero point clamping in 0.001% of range

QHiHiLim

-2000.0 - 2000.0

%SB

0.1

150.0

High High limit in % of SBase

QHiLim

-2000.0 - 2000.0

%SB

0.1

120.0

High limit in % of SBase

QLowLim

-2000.0 - 2000.0

%SB

0.1

-120.0

Low limit in % of SBase

QLowLowLim

-2000.0 - 2000.0

%SB

0.1

-150.0

Low Low limit in % of SBase

QLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common for all


limits)

Table continues on next page


1012

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

PFDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

PFZeroDb

0 - 100000

m%

500

Zero point clamping in 0.001% of range

PFHiHiLim

-1.000 - 1.000

0.001

1.000

High High limit (physical value)

PFHiLim

-1.000 - 1.000

0.001

0.800

High limit (physical value)

PFLowLim

-1.000 - 1.000

0.001

-0.800

Low limit (physical value)

PFLowLowLim

-1.000 - 1.000

0.001

-1.000

Low Low limit (physical value)

PFLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common for all


limits)

VDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VZeroDb

0 - 100000

m%

500

Zero point clamping in 0.001% of range

VHiHiLim

0.0 - 200.0

%VB

0.1

150.0

High High limit in % of UBase

VHiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

VLowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

VLowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

VLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common for all


limits)

IDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

IZeroDb

0 - 100000

m%

500

Zero point clamping in 0.001% of range

IHiHiLim

0.0 - 500.0

%IB

0.1

150.0

High High limit in % of IBase

IHiLim

0.0 - 500.0

%IB

0.1

120.0

High limit in % of IBase

ILowLim

0.0 - 500.0

%IB

0.1

80.0

Low limit in % of IBase

ILowLowLim

0.0 - 500.0

%IB

0.1

60.0

Low Low limit in % of IBase

ILimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common for all


limits)

FrDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

FrZeroDb

0 - 100000

m%

500

Zero point clamping in 0.001% of range

FrHiHiLim

0.000 - 100.000

Hz

0.001

65.000

High High limit (physical value)

FrHiLim

0.000 - 100.000

Hz

0.001

63.000

High limit (physical value)

FrLowLim

0.000 - 100.000

Hz

0.001

47.000

Low limit (physical value)

FrLowLowLim

0.000 - 100.000

Hz

0.001

45.000

Low Low limit (physical value)

FrLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common for all


limits)

VGenZeroDb

1 - 100

%VB

Zero point clamping in % of UBase

IGenZeroDb

1 - 100

%IB

Zero point clamping in % of IBase

VMagComp5

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate voltage at 5% of


Vn

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1013

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

VMagComp30

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate voltage at 30% of


Vn

VMagComp100

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate voltage at 100%


of Vn

IMagComp5

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate current at 5% of In

IMagComp30

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate current at 30% of


In

IMagComp100

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate current at 100%


of In

IAngComp5

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 5% of In

IAngComp30

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 30% of In

IAngComp100

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 100% of In

Table 664:
Name

CMMXU Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

IA_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Operation

Disabled
Enabled

Disabled

Disbled/Enabled operation

IA_Max

0.0 - 500.0

%IB

0.1

200.0

Maximum value in % of IBase

IA_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

IA_AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

IB_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

IB_Max

0.0 - 500.0

%IB

0.1

200.0

Maximum value in % of IBase

IB_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

IB_AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

IC_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

IC_Max

0.0 - 500.0

%IB

0.1

200.0

Maximum value in % of IBase

IC_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

IC_AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

1014

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Table 665:
Name

CMMXU Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

IA_ZeroDb

0 - 100000

m%

Zero point clamping

IA_HiHiLim

0.0 - 500.0

%IB

0.1

150.0

High High limit in % of IBase

IA_HiLim

0.0 - 500.0

%IB

0.1

120.0

High limit in % of IBase

IMagComp5

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate current at 5% of In

IMagComp30

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate current at 30% of


In

IA_LowLim

0.0 - 500.0

%IB

0.1

80.0

Low limit in % of IBase

IA_LowLowLim

0.0 - 500.0

%IB

0.1

60.0

Low Low limit in % of IBase

IMagComp100

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate current at 100%


of In

IAngComp5

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 5% of In

IA_Min

0.0 - 500.0

%IB

0.1

50.0

Minimum value in % of IBase

IAngComp30

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 30% of In

IAngComp100

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 100% of In

IA_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

IB_ZeroDb

0 - 100000

m%

Zero point clamping

IB_HiHiLim

0.0 - 500.0

%IB

0.1

150.0

High High limit in % of IBase

IB_HiLim

0.0 - 500.0

%IB

0.1

120.0

High limit in % of IBase

IB_LowLim

0.0 - 500.0

%IB

0.1

80.0

Low limit in % of IBase

IB_LowLowLim

0.0 - 500.0

%IB

0.1

60.0

Low Low limit in % of IBase

IB_Min

0.0 - 500.0

%IB

0.1

50.0

Minimum value in % of IBase

IB_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

IC_ZeroDb

0 - 100000

m%

Zero point clamping

IC_HiHiLim

0.0 - 500.0

%IB

0.1

150.0

High High limit in % of IBase

IC_HiLim

0.0 - 500.0

%IB

0.1

120.0

High limit in % of IBase

IC_LowLim

0.0 - 500.0

%IB

0.1

80.0

Low limit in % of IBase

IC_LowLowLim

0.0 - 500.0

%IB

0.1

60.0

Low Low limit in % of IBase

IC_Min

0.0 - 500.0

%IB

0.1

50.0

Minimum value in % of IBase

IC_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1015

Section 16
Monitoring

Table 666:

1MRK 502 066-UUS A

VMMXU Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

VAB_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Operation

Disabled
Enabled

Disabled

Disbled/Enabled operation

VAB_ZeroDb

0 - 100000

m%

Zero point clamping

VAB_Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

VAB_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

VAB_AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VBC_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VB_ZeroDb

0 - 100000

m%

Zero point clamping

VBC_Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

VBC_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

VBC_AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VCA_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VC_ZeroDb

0 - 100000

m%

Zero point clamping

VCA_Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

VCA_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

VCA_AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Table 667:
Name

VMMXU Non group settings (advanced)


Step

Default

VAB_HiHiLim

Values (Range)
0.0 - 200.0

Unit
%VB

0.1

150.0

Description
High High limit in % of UBase

VAB_HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

VAB_LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

VAB_LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

VMagComp100

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate voltage at 100%


of Vn

Table continues on next page

1016

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Step

Default

VAB_Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in in % of VBase

VAB_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

VBC_HiHiLim

0.0 - 200.0

%VB

0.1

150.0

High High limit in % of UBase

VBC_HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

VBC_LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

VBC_LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

VBC_Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

VBC_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

VCA_HiHiLim

0.0 - 200.0

%VB

0.1

150.0

High High limit in % of UBase

VCA_HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

VCA_LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

VCA_LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

VCA_Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

VCA_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

Table 668:
Name

Values (Range)

Unit

Description

CMSQI Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

3I0DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

3I0ZeroDb

0 - 100000

m%

Zero point clamping

3I0Min

0.0 - 500.0

%IB

0.1

50.0

Minimum value in % of IBase

3I0Max

0.0 - 500.0

%IB

0.1

200.0

Maximum value in % of IBase

3I0RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

3I0LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

3I0AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Operation

Disabled
Enabled

Disabled

Disbled/Enabled operation

3I0AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

3I0AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1017

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

3I0AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

I1DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

I1ZeroDb

0 - 100000

m%

Zero point clamping

I1Min

0.0 - 500.0

%IB

0.1

50.0

Minimum value in % of IBase

I1Max

0.0 - 500.0

%IB

0.1

200.0

Maximum value in % of IBase

I1RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

I1AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

I1AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

I1AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

I2DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

I2ZeroDb

0 - 100000

m%

Zero point clamping

I2Min

0.0 - 500.0

%IB

0.1

50.0

Minimum value in % of IBase

I2Max

0.0 - 500.0

%IB

0.1

200.0

Maximum value in % of IBase

I2RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

I2LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

I2AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

I2AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

I2AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

Table 669:
Name

CMSQI Non group settings (advanced)


Step

Default

3I0HiHiLim

Values (Range)
0.0 - 500.0

Unit
%IB

0.1

150.0

Description
High High limit in % of IBase

3I0HiLim

0.0 - 500.0

%IB

0.1

120.0

High limit in % of IBase

3I0LowLim

0.0 - 500.0

%IB

0.1

80.0

Low limit in % of IBase

3I0LowLowLim

0.0 - 500.0

%IB

0.1

60.0

Low Low limit in % of IBase

3I0AngZeroDb

0 - 100000

m%

Zero point clamping in 0.001% of range

Table continues on next page

1018

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Step

Default

I1HiHiLim

0.0 - 500.0

%IB

0.1

150.0

High High limit in % of IBase

I1HiLim

0.0 - 500.0

%IB

0.1

120.0

High limit in % of IBase

I1LowLim

0.0 - 500.0

%IB

0.1

80.0

Low limit in % of IBase

I1LowLowLim

0.0 - 500.0

%IB

0.1

60.0

Low Low limit in % of IBase

I1LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

I1AngZeroDb

0 - 100000

m%

Zero point clamping in 0.001% of range

I1AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

I2HiHiLim

0.0 - 500.0

%IB

0.1

150.0

High High limit in % of IBase

I2HiLim

0.0 - 500.0

%IB

0.1

120.0

High limit in % of IBase

I2LowLim

0.0 - 500.0

%IB

0.1

80.0

Low limit in % of IBase

I2LowLowLim

0.0 - 500.0

%IB

0.1

60.0

Low Low limit in % of IBase

I2AngZeroDb

0 - 100000

m%

Zero point clamping in 0.001% of range

I2AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

Table 670:
Name

Values (Range)

Unit

Description

VMSQI Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

3V0DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

3V0ZeroDb

0 - 100000

m%

Zero point clamping

3V0Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

3V0Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

3V0RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

3V0LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

3V0AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Operation

Disabled
Enabled

Disabled

Disbled/Enabled operation

3V0AngZeroDb

0 - 100000

m%

Zero point clamping in 0.001% of range

3V0AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

3V0AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

3V0AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1019

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

V1DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

V1ZeroDb

0 - 100000

m%

Zero point clamping

V1Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

V1Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

V1RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

V1LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

V1AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

V2DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

V2ZeroDb

0 - 100000

m%

Zero point clamping

V2Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

V2Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

V2RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

V2LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

V2AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

V2AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

V2AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

V2AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UAmpPreComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to pre-calibrate voltage at 5%


of Vr

UAmpPreComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to pre-calibrate voltage at


30% of Vr

UAmpPreComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to pre-calibrate voltage at


100% of Vr

Table 671:
Name

VMSQI Non group settings (advanced)


Step

Default

3V0HiHiLim

Values (Range)
0.0 - 200.0

Unit
%VB

0.1

150.0

Description
High High limit in % of UBase

3V0HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

3V0LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

Table continues on next page

1020

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Step

Default

3V0LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

V1HiHiLim

0.0 - 200.0

%VB

0.1

150.0

High High limit in % of UBase

V1HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

V1LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

V1LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

V1AngZeroDb

0 - 100000

m%

Zero point clamping in 0.001% of range

V1AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

V1AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

V1AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

V2HiHiLim

0.0 - 200.0

%VB

0.1

150.0

High High limit in % of UBase

V2HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

V2LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

V2LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

V2AngZeroDb

0 - 100000

m%

Zero point clamping in 0.001% of range

Table 672:
Name

Values (Range)

Unit

Description

VNMMXU Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

VA_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Operation

Disabled
Enabled

Disabled

Disbled/Enabled operation

VA_ZeroDb

0 - 100000

m%

Zero point clamping

VA_Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

VA_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

VA_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

VA_AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VB_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VB_ZeroDb

0 - 100000

m%

Zero point clamping

VB_Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1021

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

VB_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

VB_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

VB_AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VC_DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

VC_ZeroDb

0 - 100000

m%

Zero point clamping

VC_Max

0.0 - 200.0

%VB

0.1

200.0

Maximum value in % of VBase

VC_RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

VC_LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is common


for all limits

VC_AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

Table 673:
Name

VNMMXU Non group settings (advanced)


Step

Default

VA_HiHiLim

0.0 - 200.0

%VB

0.1

150.0

High High limit in % of UBase

VA_HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

VA_LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

VA_LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

VMagComp100

-10.000 - 10.000

0.001

0.000

Magnitude factor to calibrate voltage at 100%


of Vn

VA_Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

VB_HiHiLim

0.0 - 200.0

%VB

0.1

150.0

High High limit in % of UBase

VB_HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

VB_LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

VB_LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

VB_Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

VC_HiHiLim

0.0 - 200.0

%VB

0.1

150.0

High High limit in % of UBase

VC_HiLim

0.0 - 200.0

%VB

0.1

120.0

High limit in % of VBase

VC_LowLim

0.0 - 200.0

%VB

0.1

80.0

Low limit in % of VBase

VC_LowLowLim

0.0 - 200.0

%VB

0.1

60.0

Low Low limit in % of VBase

VC_Min

0.0 - 200.0

%VB

0.1

50.0

Minimum value in % of VBase

1022

Values (Range)

Unit

Description

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.1.6

Monitored data
Table 674:
Name

CVMMXN Monitored data


Type

Values (Range)

Unit

Description

REAL

MVA

Apparent Power magnitude of


deadband value

REAL

MW

Active Power magnitude of


deadband value

REAL

MVAr

Reactive Power magnitude of


deadband value

PF

REAL

Power Factor magnitude of


deadband value

REAL

kV

Calculated voltage magnitude


of deadband value

REAL

Calculated current magnitude


of deadband value

REAL

Hz

System frequency magnitude


of deadband value

Table 675:
Name

CMMXU Monitored data


Type

Values (Range)

Unit

Description

IA

REAL

Phase A current magnitude of


reported value

IA_ANGL

REAL

deg

Phase A current magnitude


angle

IB

REAL

Phase B current magnitude of


reported value

IB_ANGL

REAL

deg

Phase B current magnitude


angle

IC

REAL

Phase C current magnitude of


reported value

IC_ANGL

REAL

deg

Phase C current magnitude


angle

Table 676:
Name

VMMXU Monitored data


Type

Values (Range)

Unit

Description

VAB

REAL

kV

VAB Reported magnitude


value

VAB_ANGL

REAL

deg

VAB Angle, magnitude of


reported value

VBC

REAL

kV

VBC Reported magnitude


value

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1023

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

VBC_ANGL

REAL

deg

VBC Angle, magnitude of


reported value

VCA

REAL

kV

VCA Reported magnitude


value

VCA_ANGL

REAL

deg

VCA Angle, magnitude of


reported value

Table 677:
Name

CMSQI Monitored data


Type

Values (Range)

Unit

Description

3I0IMAG

REAL

3I0 Amplitude, magnitude of


instantaneous value

3I0

REAL

3I0 magnitude of reported


value

3I0ANGIM

REAL

3I0 Angle, magnitude of


instantaneous value

3I0ANGL

REAL

deg

3I0 Angle, magnitude of


reported value

I1IMAG

REAL

I1 Amplitude, magnitude of
instantaneous value

I1

REAL

I1magnitude of reported value

I1ANGIM

REAL

I1 Angle, magnitude of
instantaneous value

I1ANGL

REAL

deg

I1 Angle, magnitude of
reported value

I2IMAG

REAL

I2 Amplitude, magnitude of
instantaneous value

I2

REAL

I2 Magnitude of reported value

I2ANGIM

REAL

I2 Angle, magnitude of
instantaneous value

I2ANGL

REAL

deg

I2 Angle, magnitude of
reported value

Table 678:
Name

VMSQI Monitored data


Type

Values (Range)

Unit

Description

3U0IMAG

REAL

3U0 Amplitude, magnitude of


instantaneous value

3V0

REAL

kV

3V0 Reported magnitude


value

3U0ANGIM

REAL

3U0 Angle, magnitude of


instantaneous value

3V0ANGL

REAL

deg

3V0 Magnitude angle

Table continues on next page

1024

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

U1IMAG

REAL

U1 Amplitude, magnitude of
instantaneous value

V1

REAL

kV

V1 Reported magnitude value

U1ANGIM

REAL

U1 Angle, magnitude of
instantaneous value

V1ANGL

REAL

deg

V1 Magnitude angle

U2IMAG

REAL

U2 Amplitude, magnitude of
instantaneous value

V2

REAL

kV

V2 Reported magnitude value

U2ANGIM

REAL

U2 Angle, magnitude of
instantaneous value

V2ANGL

REAL

deg

V2 Magnitude angle

Table 679:
Name

VNMMXU Monitored data


Type

Values (Range)

Unit

Description

VA

REAL

kV

VA Amplitude, magnitude of
reported value

VA_ANGL

REAL

deg

VA Angle, magnitude of
reported value

VB

REAL

kV

VB Amplitude, magnitude of
reported value

VB_ANGL

REAL

deg

VB Angle, magnitude of
reported value

VC

REAL

kV

VC Amplitude, magnitude of
reported value

VC_ANGL

REAL

deg

V_C Angle, magnitude of


reported value

16.1.7

Operation principle

16.1.7.1

Measurement supervision
The protection, control, and monitoring IEDs have functionality to measure and further
process information for currents and voltages obtained from the pre-processing blocks.
The number of processed alternate measuring quantities depends on the type of IED and
built-in options.
The information on measured quantities is available for the user at different locations:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1025

Section 16
Monitoring

1MRK 502 066-UUS A

Locally by means of the local HMI


Remotely using the monitoring tool within PCM600 or over the station bus
Internally by connecting the analog output signals to the Disturbance Report function

Phase angle reference


All phase angles are presented in relation to a defined reference channel. The General
setting parameter PhaseAngleRef defines the reference.

Zero point clamping


Measured value below zero point clamping limit is forced to zero. This allows the noise
in the input signal to be ignored. The zero point clamping limit is a general setting
(XZeroDb where X equals S, P, Q, PF, V, I, F, IA, IB, IC, VA, VB, VC, VAB, VBC,
VCA, I1, I2, 3I0, V1, V2 or 3V0). Observe that this measurement supervision zero point
clamping might be overridden by the zero point clamping used for the measurement
values within CVMMXN.

Continuous monitoring of the measured quantity


Users can continuously monitor the measured quantity available in the function block by
means of four defined operating thresholds, see figure 126. The monitoring has two
different modes of operating:

Overfunction, when the measured current exceeds the High limit (XHiLim) or Highhigh limit (XHiHiLim) pre-set values
Underfunction, when the measured current decreases under the Low limit (XLowLim)
or Low-low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 126.

1026

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Y
X_RANGE = 3
High-high limit

X_RANGE= 1

Hysteresis

High limit
X_RANGE=0

X_RANGE=0
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4

IEC05000657-2-en.vsdx

IEC05000657 V2 EN

Figure 470:

Presentation of operating limits

Each analog output has one corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: Highhigh limit exceeded, 2: below Low limit and 4: below Low-low limit). The output may be
connected to a measurement expander block (XP (RANGE_XP)) to get measurement
supervision as binary signals.
The logical value of the functional output signals changes according to figure 126.
The user can set the hysteresis (XLimHyst), which determines the difference between the
operating and reset value at each operating point, in wide range for each measuring
channel separately. The hysteresis is common for all operating values within one channel.

Actual value of the measured quantity


The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting of the
value to the higher levels depends on the selected reporting mode. The following basic
reporting modes are available:

Cyclic reporting (Cyclic)


Magnitude dead-band supervision (Dead band)
Integral dead-band supervision (Int deadband)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1027

Section 16
Monitoring

1MRK 502 066-UUS A

Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of magnitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.

Value Reported
(1st)

Value Reported

Value Reported

Value Reported

Value Reported

Y3
Y2

Y4

Y1

Y5

(*)Set value for t: XDbRepInt

t (*)

Value 5

Value 4

t (*)

Value 3

t (*)

Value 2

Value 1

t (*)

IEC05000500-2-en.vsdx

IEC05000500 V2 EN

Figure 471:

Periodic reporting

Magnitude dead-band supervision


If a measuring value is changed, compared to the last reported value, and the change is
larger than the Y pre-defined limits that are set by user (UDbRepIn), then the measuring
channel reports the new value to a higher level. This limits the information flow to a
minimum necessary. Figure 128 shows an example with the magnitude dead-band
supervision. The picture is simplified: the process is not continuous but the values are
evaluated with a time interval of one execution cycle from each other.

1028

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Value Reported

Y
Value Reported
(1st)

Value Reported
Y3
Y2

Y1

Value Reported
Y
Y

Y
Y

Y
Y

t
IEC99000529-2-en.vsdx

IEC99000529 V2 EN

Figure 472:

Magnitude dead-band supervision reporting

After the new value is reported, the Y limits for dead-band are automatically set around
it. The new value is reported only if the measured quantity changes more than defined by
the Y set limits.

Integral dead-band reporting


The measured value is reported if the time integral of all changes exceeds the pre-set limit
(XDbRepInt), figure 129, where an example of reporting with integral dead-band
supervision is shown. The picture is simplified: the process is not continuous but the
values are evaluated with a time interval of one execution cycle from each other.
The last value reported, Y1 in figure 129 serves as a basic value for further measurement.
A difference is calculated between the last reported and the newly measured value and is
multiplied by the time increment (discrete integral). The absolute values of these integral
values are added until the pre-set value is exceeded. This occurs with the value Y2 that is
reported and set as a new base for the following measurements (as well as for the values
Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals with
small variations that can last for relatively long periods.
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1029

Section 16
Monitoring

1MRK 502 066-UUS A

A1 >=
pre-set value

Y
A >=
pre-set value

A2 >=
pre-set value
Y3

Y2
Value Reported
(1st)

A1

Value
Reported

A2
Value
Reported

Y1

Y4
Value
Reported

A3 + A4 + A5 + A6 + A7 >=
pre-set value
A4
A3

A5

A6

A7

Y5
Value
Reported
t
IEC99000530-2-en.vsdx

IEC99000530 V2 EN

Figure 473:

16.1.7.2

Reporting with integral dead-band supervision

Measurements CVMMXN
Mode of operation
The measurement function must be connected to three-phase current and three-phase
voltage input in the configuration tool (group signals), but it is capable to measure and
calculate above mentioned quantities in nine different ways depending on the available
VT inputs connected to the IED. The end user can freely select by a parameter setting,
which one of the nine available measuring modes shall be used within the function.
Available options are summarized in the following table:

1030

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Set value for Formula used for complex, threephase power calculation
parameter
Mode
1

A, B, C

Formula used for voltage and


current magnitude calculation

S = VA I A* + VB I B* + VC I C*
EQUATION1561 V1 EN

(
I =( I

V = VA + VB + VC
+ IB + IC

)/
)/3

Comment

Used when three


phase-to-ground
voltages are
available

EQUATION1562 V1 EN

Arone

S = VAB I A - VBC I C
*

(Equation 179)

EQUATION1563 V1 EN

(
I =( I

V = VAB + VBC / 2
A

EQUATION1564 V1 EN

PosSeq

V =

S = 3 VPosSeq I PosSeq
*

(Equation 181)

EQUATION1565 V1 EN

AB

S = VAB I A - I B
*

(Equation 183)

EQUATION1567 V1 EN

I = I PosSeq

BC

S = VBC I B - I C
*

(Equation 185)

EQUATION1569 V1 EN

I = IA + IB / 2

CA

S = VCA I C - I A
EQUATION1571 V1 EN

(Equation 187)

I = I B + IC / 2

S = 3 VA I A
*

I = IC + I A / 2

EQUATION1573 V1 EN

(Equation 189)

V =

Used when only


VCA phase-tophase voltage is
available

(Equation 188)

3 VA

I = IA
EQUATION1574 V1 EN

Used when only


VBC phase-tophase voltage is
available

(Equation 186)

V = VCA

EQUATION1572 V1 EN

Used when only


VAB phase-tophase voltage is
available

(Equation 184)

V = VBC

EQUATION1570 V1 EN

Used when only


symmetrical three
phase power shall
be measured

(Equation 182)

V = VAB

EQUATION1568 V1 EN

(Equation 180)

3 VPosSeq

EQUATION1566 V1 EN

+ IC / 2

Used when three


two phase-tophase voltages
are available

Used when only


VA phase-toground voltage is
available

(Equation 190)

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1031

Section 16
Monitoring

1MRK 502 066-UUS A

Set value for Formula used for complex, threephase power calculation
parameter
Mode
8

S = 3 VB I B
*

EQUATION1575 V1 EN

(Equation 191)

Formula used for voltage and


current magnitude calculation

V =

3 VB

I = IB
EQUATION1576 V1 EN

S = 3 VC I C
*

EQUATION1577 V1 EN

(Equation 193)

V =

Used when only


VB phase-toground voltage is
available

(Equation 192)

3 VC

I = IC
EQUATION1578 V1 EN

Comment

Used when only


VC phase-toground voltage is
available

(Equation 194)

* means complex conjugated value

It shall be noted that only in the first two operating modes that is, 1 & 2 the measurement
function calculates exact three-phase power. In other operating modes that is, from 3 to 9
it calculates the three-phase power under assumption that the power system is fully
symmetrical. Once the complex apparent power is calculated then the P, Q, S, & PF are
calculated in accordance with the following formulas:
P = Re( S )
(Equation 195)

EQUATION1403 V1 EN

Q = Im( S )
(Equation 196)

EQUATION1404 V1 EN

S = S =

P2 + Q2
(Equation 197)

EQUATION1405 V1 EN

PF = cosj = P
S
EQUATION1406 V1 EN

(Equation 198)

Additionally to the power factor value the two binary output signals from the function are
provided which indicates the angular relationship between current and voltage phasors.
Binary output signal ILAG is set to one when current phasor is lagging behind voltage
phasor. Binary output signal ILEAD is set to one when current phasor is leading the
voltage phasor.
1032

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Each analog output has a corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4, see section "Measurement supervision".

Calibration of analog inputs


Measured currents and voltages used in the CVMMXN function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by magnitude and angle compensation at
5, 30 and 100% of rated current and voltage. The compensation below 5% and above
100% is constant and linear in between, see example in figure 474.
% of In

Magnitude
compensation

+10
IMagComp5

Measured
current

IMagComp30
IMagComp100

30

% of In

0-5%:
Constant
5-30-100%: Linear
>100%:
Constant

-10

Degrees

100

Angle
compensation

+10
Measured
current

IAngComp30
IAngComp5
IAngComp100

30

100

% of In

-10

ANSI05000652_3_en.vsd
ANSI05000652 V3 EN

Figure 474:

Calibration curves

The first current and voltage phase in the group signals will be used as reference and the
magnitude and angle compensation will be used for related input signals.

Low pass filtering


In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for P, Q, S, V, I and
power factor. This will make slower measurement response to the step changes in the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1033

Section 16
Monitoring

1MRK 502 066-UUS A

measured quantity. Filtering is performed in accordance with the following recursive


formula:
X = k X Old + (1 - k ) X Calculated
(Equation 199)

EQUATION1407 V1 EN

where:
X

is a new measured value (that is P, Q, S, V, I or PF) to be given out from the function

XOld

is the measured value given from the measurement function in previous execution cycle

XCalculated is the new calculated value in the present execution cycle


k

is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay). When k
is set to value bigger than 0, the filtering is enabled. Appropriate value of k shall be
determined separately for every application. Some typical value for k =0.14.

Zero point clamping


In order to avoid erroneous measurements when either current or voltage signal is not
present, it is possible for the end user to set the magnitudeIGenZeroDb level for current
and voltage measurement VGenZeroDb is forced to zero. When either current or voltage
measurement is forced to zero automatically the measured values for power (P, Q and S)
and power factor are forced to zero as well. Since the measurement supervision
functionality, included in CVMMXN, is using these values the zero clamping will
influence the subsequent supervision (observe the possibility to do zero point clamping
within measurement supervision, see section "Measurement supervision").

Compensation facility
In order to compensate for small magnitude and angular errors in the complete
measurement chain (CT error, VT error, IED input transformer errors and so on.) it is
possible to perform on site calibration of the power measurement. This is achieved by
setting the complex constant which is then internally used within the function to multiply
the calculated complex apparent power S. This constant is set as magnitude (setting
parameter PowMagFact, default value 1.000) and angle (setting parameter
PowAngComp, default value 0.0 degrees). Default values for these two parameters are
done in such way that they do not influence internally calculated value (complex constant
has default value 1). In this way calibration, for specific operating range (for example,
around rated power) can be done at site. However, to perform this calibration it is
necessary to have an external power meter with high accuracy class available.

1034

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Directionality
If CT grounding parameter is set as described in section "Analog inputs", active and
reactive power will be measured always towards the protected object. This is shown in the
following figure 475.

Busbar

52

IED
Q

Protected
Object
ANSI05000373_2_en.vsd
ANSI05000373 V2 EN

Figure 475:

Internal IED directionality convention for P & Q measurements

Practically, it means that active and reactive power will have positive values when they
flow from the busbar towards the protected object and they will have negative values when
they flow from the protected object towards the busbar.
In some application, for example, when power is measured on the secondary side of the
power transformer it might be desirable, from the end client point of view, to have actually
opposite directional convention for active and reactive power measurements. This can be
easily achieved by setting parameter PowAngComp to value of 180.0 degrees. With such
setting the active and reactive power will have positive values when they flow from the
protected object towards the busbar.

Frequency
Frequency is actually not calculated within measurement block. It is simply obtained from
the pre-processing block and then just given out from the measurement block as an output.

16.1.7.3

Phase current measurement CMMXU


The Phase current measurement (CMMXU) function must be connected to three-phase
current input in the configuration tool to be operable. Currents handled in the function can
be calibrated to get better then class 0.5 measuring accuracy for internal use, on the outputs
and IEC 61850. This is achieved by magnitude and angle compensation at 5, 30 and 100%

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1035

Section 16
Monitoring

1MRK 502 066-UUS A

of rated current. The compensation below 5% and above 100% is constant and linear in
between, see figure 474.
Phase currents (magnitude and angle) are available on the outputs and each magnitude
output has a corresponding supervision level output (Ix_RANGE). The supervision
output signal is an integer in the interval 0-4, see section "Measurement supervision".

16.1.7.4

Phase-phase and phase-neutral voltage measurements VMMXU,


VNMMXU
The voltage function must be connected to three-phase voltage input in the configuration
tool to be operable. Voltages are handled in the same way as currents when it comes to
class 0.5 calibrations, see above.
The voltages (phase or phase-phase voltage, magnitude and angle) are available on the
outputs and each magnitude output has a corresponding supervision level output
(Vxy_RANG). The supervision output signal is an integer in the interval 0-4, see section
"Measurement supervision".

16.1.7.5

Voltage and current sequence measurements VMSQI, CMSQI


The measurement functions must be connected to three-phase current (CMSQI) or voltage
(VMSQI) input in the configuration tool to be operable. No outputs, other than X_RANG,
are calculated within the measuring blocks and it is not possible to calibrate the signals.
Input signals are obtained from the pre-processing block and transferred to corresponding
output.
Positive, negative and three times zero sequence quantities are available on the outputs
(voltage and current, magnitude and angle). Each magnitude output has a corresponding
supervision level output (X_RANGE). The output signal is an integer in the interval 0-4,
see section "Measurement supervision".

16.1.8

Technical data
Table 680:

CVMMXN technical data

Function

Range or value

Accuracy

Frequency

(0.95-1.05) x fn

2.0 mHz

Voltage

(10 to 300) V

0.3% of V at V 50 V
0.2% of V at V> 50 V

Current

(0.1-4.0) x In

0.8% of I at 0.1 x In< I < 0.2 x In


0.5% of I at 0.2 x In< I < 0.5 x In
0.2% of I at 0.5 x In< I < 4.0 x In

Table continues on next page

1036

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Function

Range or value

Active power, P

Reactive power, Q

Apparent power, S

Power factor, cos ()

Table 681:

Accuracy

(10 to 300) V
(0.1-4.0) x In

0.5% of Sn at S 0.5 x Sn
0.5% of S at S > 0.5 x Sn

(100 to 220) V
(0.5-2.0) x In
cos < 0.7

0.2% of P

(10 to 300) V
(0.1-4.0) x In

0.5% of Sn at S 0.5 x Sn
0.5% of S at S > 0.5 x Sn

(100 to 220) V
(0.5-2.0) x In
cos > 0.7

0.2% of Q

(10 to 300) V
(0.1-4.0) x In

0.5% of Sn at S 0.5 x Sn
0.5% of S at S >0.5 x Sn

(100 to 220) V
(0.5-2.0) x In

0.2% of S

(10 to 300) V
(0.1-4.0) x In

<0.02

(100 to 220) V
(0.5-2.0) x In

<0.01

CMMXU technical data

Function

Range or value

Accuracy

Current at symmetrical load

(0.1-4.0) In

0.3% of In at I 0.5 In
0.3% of I at I > 0.5 In

Phase angle at symmetrical load

(0.1-4.0) In

1.0 degrees at 0.1 In < I 0.5


In
0.5 degrees at 0.5 In < I 4.0
In

Table 682:

VMMXU technical data

Function

Range or value

Voltage

(10 to 300) V

0.5% of V at V 50 V
0.2% of V at V > 50 V

Phase angle

(10 to 300) V

0.5 at V 50 V
0.2 at V > 50 V

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Accuracy

1037

Section 16
Monitoring

1MRK 502 066-UUS A

Table 683:

CMSQI technical data

Function

Range or value

Accuracy

Current positive sequence, I1


Three phase settings

(0.14.0) In

0.3% of In at I 0.5 In
0.3% of I at I > 0.5 In

Current zero sequence, 3I0


Three phase settings

(0.11.0) In

0.3% of In at I 0.5 In
0.3% of I at I > 0.5 In

Current negative sequence, I2


Three phase settings

(0.11.0) In

0.3% of In at I 0.5 In
0.3% of I at I > 0.5 In

Phase angle

(0.14.0) In

1.0 degrees at 0.1 In < I 0.5


In
0.5 degrees at 0.5 In < I 4.0
In

Table 684:

VMSQItechnical data

Function

Range or value

Accuracy

Voltage positive sequence, V1

(10 to 300) V

0.5% of V at V 50 V
0.2% of V at V > 50 V

Voltage zero sequence, 3V0

(10 to 300) V

0.5% of V at V 50 V
0.2% of V at V > 50 V

Voltage negative sequence, V2

(10 to 300) V

0.5% of V at V 50 V
0.2% of V at V > 50 V

Phase angle

(10 to 300) V

0.5 degrees at V 50 V
0.2 degrees at V > 50 V

Table 685:

VNMMXU technical data

Function

Range or value

Accuracy

Voltage

(5 to 175) V

0.5% of V at V 50 V
0.2% of V at V > 50 V

Phase angle

(5 to 175) V

0.5 at V 50 V
0.2 at V > 50 V

16.2

Gas medium supervision SSIMG (63)

16.2.1

Identification
Function description
Gas medium supervision

1038

IEC 61850
identification
SSIMG

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
63

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.2.2

Functionality
Gas medium supervision SSIMG (63) is used for monitoring the circuit breaker condition.
Binary information based on the gas pressure in the circuit breaker is used as input signals
to the function. In addition, the function generates alarms based on received information.

16.2.3

Function block
SSIMG (63)
BLOCK
PRESSURE
BLK_ALM
PRES_ALM
PRESSURE
PRES_LO
TEMP
TEMP
PRES_ALM
TEMP_ALM
PRES_LO
TEMP_LO
SET_P_LO
SET_T_LO
RESET_LO
ANSI09000129-1-en.vsd
ANSI09000129 V1 EN

Figure 476:

16.2.4

SSIMG (63) function block

Signals
Table 686:
Name

SSIMG (63) Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

BLK_ALM

BOOLEAN

Block all the alarms

PRESSURE

REAL

0.0

Pressure input from CB

TEMP

REAL

0.0

Temperature of the insulation medium from CB

PRES_ALM

BOOLEAN

Pressure alarm signal

PRES_LO

BOOLEAN

Pressure lockout signal

SET_P_LO

BOOLEAN

Set pressure lockout

SET_T_LO

BOOLEAN

Set temperature lockout

RESET_LO

BOOLEAN

Reset pressure and temperature lockout

Table 687:
Name

SSIMG (63) Output signals


Type

Description

PRESSURE

REAL

Pressure service value

PRES_ALM

BOOLEAN

Pressure below alarm level

PRES_LO

BOOLEAN

Pressure below lockout level

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1039

Section 16
Monitoring

1MRK 502 066-UUS A

Name

16.2.5
Table 688:
Name

Type

Description

TEMP

REAL

Temperature of the insulation medium

TEMP_ALM

BOOLEAN

Temperature above alarm level

TEMP_LO

BOOLEAN

Temperature above lockout level

Settings
SSIMG (63) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PressAlmLimit

1.00 - 100.00

0.01

5.00

Alarm setting for pressure

PressLOLimit

1.00 - 100.00

0.01

3.00

Pressure lockout setting

TempAlarmLimit

-40.00 - 200.00

0.01

30.00

Temperature alarm level setting of the medium

TempLOLimit

-40.00 - 200.00

0.01

30.00

Temperature lockout level of the medium

tPressureAlarm

0.000 - 60.000

0.001

0.000

Time delay for pressure alarm

tPressureLO

0.000 - 60.000

0.001

0.000

Time delay for pressure lockout indication

tTempAlarm

0.000 - 60.000

0.001

0.000

Time delay for temperature alarm

tTempLockOut

0.000 - 60.000

0.001

0.000

Time delay for temperture lockout

tResetPressAlm

0.000 - 60.000

0.001

0.000

Reset time delay for pressure alarm

tResetPressLO

0.000 - 60.000

0.001

0.000

Reset time delay for pressure lockout

tResetTempLO

0.000 - 60.000

0.001

0.000

Reset time delay for temperture lockout

tResetTempAlm

0.000 - 60.000

0.001

0.000

Reset time delay for temperture alarm

16.2.6

Operation principle
Gas medium supervision SSIMG (63) is used to monitor the gas pressure in the circuit
breaker. Binary inputs of gas density PRES_ALM, PRES_LO, and gas pressure signal
PRESSURE, are taken into account to initiate the alarms PRES_ALM and PRES_LO.
When PRESSURE is less than PressAlmLimit or binary signal from CB PRES_ALM is
high then the gas pressure alarm, PRES_ALM will be initiated. Similarly, if pressure input
PRESSURE is less than PressLOLimit or binary signal from CB PRES_LO is high or
temperature input TEMP is above lockout level TempLOLimit then the gas pressure
lockout, PRES_LO will be initiated.
There may be sudden change in pressure of the gas for a very small time, for which the
function need not to initiate any alarm. That is why two time delays tPressureAlarm or
tPressureLO have been included. If the pressure goes below the settings for more than
these time delays, then only the corresponding alarm PRES_ALM or lockout PRES_LO

1040

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

will be initiated. The SET_P_LO binary input is used for setting the gas pressure lockout.
The PRES_LO output retains the last value until it is reset by using the binary input
RESET_LO. Hysteresis type comparators have been used with the setting for relative and
absolute hysteresis. The binary input BLK_ALM can be used to block the alarms, and the
BLOCK input can block both alarms and the lockout indication.
Temperature of the medium is available from the input signal of temperature. The signal
is monitored to detect high temperature.
When temperature input TEMP is greater than TempAlarmLimit, then temperature alarm
TEMP_ALM will be initiated. Similarly, if temperature input TEMP is greater than
TempLOLimit, then TEMP_LO will be initiated.
There may be sudden change in temperature of the medium for a very small time, for
which the function need not to initiate any alarm. That is why two time delays tTempAlarm
or tTempLockOut have been included. If the temperature goes above the settings for more
than these time delays, then only the corresponding alarm TEMP_ALM or lockout
TEMP_LO will be initiated. The SET_T_LO binary input is used for setting the
temperature lockout. The TEMP_LO output retains the last value until it is reset by using
the binary input RESET_LO. Hysteresis type comparators have been used with the setting
for relative and absolute hysteresis. The binary input BLK_ALM can be used to block the
alarms, and the BLOCK input can block both alarms and the lockout indication.

16.2.7

Technical data
Table 689:

SSIMG (63) Technical data

Function

Range or value

Accuracy

Pressure alarm level

1.00-100.00

10.0% of set value

Pressure lockout level

1.00-100.00

10.0% of set value

Temperature alarm level

-40.00-200.00

2.5% of set value

Temperature lockout level

-40.00-200.00

2.5% of set value

Time delay for pressure alarm

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Reset time delay for pressure


alarm

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Time delay for pressure lockout

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Time delay for temperature alarm

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Reset time delay for temperature


alarm

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Time delay for temperature


lockout

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1041

Section 16
Monitoring

1MRK 502 066-UUS A

16.3

Liquid medium supervision SSIML (71)

16.3.1

Identification
Function description

IEC 61850
identification

Liquid medium supervision

16.3.2

IEC 60617
identification

SSIML

ANSI/IEEE C37.2
device number
71

Functionality
Liquid medium supervision SSIML (71) is used for monitoring the circuit breaker
condition. Binary information based on the oil level in the circuit breaker is used as input
signals to the function. In addition, the function generates alarms based on received
information.

16.3.3

Function block
SSIML (71)
BLOCK
LEVEL
BLK_ALM
LVL_ALM
LEVEL
LVL_LO
TEMP
TEMP
LVL_ALM
TEMP_ALM
LEVEL_LO
TEMP_LO
SET_L_LO
SET_T_LO
RESET_LO
ANSI09000128-1-en.vsd
ANSI09000128 V1 EN

Figure 477:

16.3.4

SSIML (71) function block

Signals
Table 690:
Name

SSIML (71) Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

BLK_ALM

BOOLEAN

Block all the alarms

LEVEL

REAL

0.0

Level input from CB

TEMP

REAL

0.0

Temperature of the insulation medium from CB

LVL_ALM

BOOLEAN

Level alarm signal

LEVEL_LO

BOOLEAN

Level lockout signal

Table continues on next page

1042

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Type

Set level lockout

SET_T_LO

BOOLEAN

Set temperature lockout

RESET_LO

BOOLEAN

Reset level and temperature lockout

SSIML (71) Output signals

Name

Table 692:
Name

Description

BOOLEAN

Table 691:

16.3.5

Default

SET_L_LO

Type

Description

LEVEL

REAL

Level service value

LVL_ALM

BOOLEAN

Level below alarm level

LVL_LO

BOOLEAN

Level below lockout level

TEMP

REAL

Temperature of the insulation medium

TEMP_ALM

BOOLEAN

Temperature above alarm level

TEMP_LO

BOOLEAN

Temperature above lockout level

Settings
SSIML (71) Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

LevelAlmLimit

1.00 - 100.00

0.01

5.00

Alarm setting for level

LevelLOLimit

1.00 - 100.00

0.01

3.00

Level lockout setting

TempAlarmLimit

-40.00 - 200.00

0.01

30.00

Temperature alarm level setting of the medium

TempLOLimit

-40.00 - 200.00

0.01

30.00

Temperature lockout level of the medium

tLevelAlarm

0.000 - 60.000

0.001

0.000

Time delay for level alarm

tLevelLockOut

0.000 - 60.000

0.001

0.000

Time delay for level lockout indication

tTempAlarm

0.000 - 60.000

0.001

0.000

Time delay for temperature alarm

tTempLockOut

0.000 - 60.000

0.001

0.000

Time delay for temperture lockout

tResetLevelAlm

0.000 - 60.000

0.001

0.000

Reset time delay for level alarm

tResetLevelLO

0.000 - 60.000

0.001

0.000

Reset time delay for level lockout

tResetTempLO

0.000 - 60.000

0.001

0.000

Reset time delay for temperture lockout

tResetTempAlm

0.000 - 60.000

0.001

0.000

Reset time delay for temperture alarm

16.3.6

Operation principle
Liquid medium supervision SSIML (71) is used to monitor the oil level in the circuit
breaker. Binary inputs of oil level LVL_ALM, LEVEL_LO and oil level signal LEVEL

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1043

Section 16
Monitoring

1MRK 502 066-UUS A

are taken into account to initiate the alarms LVL_ALM and LVL_LO. When LEVEL is
less than LevelAlmLimit or binary signal from CB LVL_ALM is high, then the oil level
indication alarm, LVL_ALM will be initiated. Similarly, if oil level input LEVEL is less
than LevelLOLimit or binary signal from CB LVL_LO is high or temperature input TEMP
is above lockout level TempLOLimit, then the oil level indication lockout, LVL_LO will
be initiated.
There may be sudden change in oil level for a very small time, for which the function need
not to initiate any alarm. That is why two time delays tLevelAlarm or tLevelLockOut have
been included. If the oil level goes below the settings for more than these time delays, then
only the corresponding alarm LVL_ALM or lockout LVL_LO will be initiated. The
SET_L_LO binary input is used for setting the gas pressure lockout. The LVL_LO output
retains the last value until it is reset by using the binary input RESET_LO. Hysteresis type
comparators have been used with the setting for relative and absolute hysteresis. The
binary input BLK_ALM can be used for blocking the alarms, and the BLOCK input can
block both alarms and the lockout indication.
Temperature of the medium is available from the input signal of temperature. The signal
is monitored to detect high temperature.
When temperature input TEMP is greater than TempAlarmLimit, then temperature alarm
TEMP_ALM will be initiated. Similarly, if temperature input TEMP is greater than
TempLOLimit, then TEMP_LO will be initiated.
There may be sudden change in temperature of the medium for a very small time, for
which the function need not to initiate any alarm. That is why two time delays tTempAlarm
or tTempLockOuthave been included. If the temperature goes above the settings for more
than these time delays, then only the corresponding alarm TEMP_ALM or lockout
TEMP_LO will be initiated. The SET_T_LO binary input is used for setting the
temperature lockout. The TEMP_LO output retains the last value until it is reset by using
the binary input RESET_LO. Hysteresis type comparators have been used with the setting
for relative and absolute hysteresis. The binary input BLK_ALM can be used for blocking
the alarms, and the BLOCK input can block both alarms and the lockout indication.

16.3.7

Technical data
Table 693:

SSIML(71) Technical data

Function

Range or value

Accuracy

Oil alarm level

1.00-100.00

10.0% of set value

Oil lockout level

1.00-100.00

10.0% of set value

Temperature alarm level

-40.00-200.00

2.5% of set value

Temperature lockout level

-40.00-200.00

2.5% of set value

Time delay for oil alarm

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Table continues on next page


1044

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Function

Range or value
(0.000-60.000) s

0.2% or 250ms whichever is


greater

Time delay for oil lockout

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Time delay for temperature alarm

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Reset time delay for temperature


alarm

(0.000-60.000) s

0.2% or 250ms whichever is


greater

Time delay for temperature


lockout

(0.000-60.000) s

0.2% or 250ms whichever is


greater

16.4

Breaker monitoring SSCBR

16.4.1

Identification
Function description
Breaker monitoring

16.4.2

Accuracy

Reset time delay for oil alarm

IEC 61850
identification
SSCBR

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The breaker monitoring function SSCBR is used to monitor different parameters of the
breaker condition. The breaker requires maintenance when the number of operations
reaches a predefined value. For a proper functioning of the circuit breaker, it is essential
to monitor the circuit breaker operation, spring charge indication or breaker wear, travel
time, number of operation cycles and estimate the accumulated energy during arcing
periods.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1045

Section 16
Monitoring
16.4.3

1MRK 502 066-UUS A

Function block
SSCBR
I3P*
BLOCK
BLKALM
TRIND
POSOPEN
POSCLOSE
PRESALM
PRESLO
SPRCHRST
SPRCHRD
RSTCBWR
RSTTRVT
RSTIPOW
RSTSPCHT

OPENPOS
CLOSEPOS
INVDPOS
TRCMD
TRVTOPAL
TRVTCLAL
OPERALM
OPERLO
CBLIFEAL
MONALM
IPOWALPH
IPOWLOPH
SPCHALM
GPRESALM
GPRESLO

ANSI14000061-1-en.vsd
ANSI14000061 V1 EN

Figure 478:

16.4.4

Signals
Table 694:
Name

1046

SSCBR function block

SSCBR Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

BLOCK

BOOLEAN

Block all the alarm and lockout indication

BLKALM

BOOLEAN

Block all the alarms

TRIND

BOOLEAN

Trip command from trip circuit

POSOPEN

BOOLEAN

Signal for open position of apparatus from I/O

POSCLOSE

BOOLEAN

Signal for close position of apparatus from I/O

PRESALM

BOOLEAN

Pressure alarm indication from CB

PRESLO

BOOLEAN

Pressure lockout indication from CB

SPRCHRST

BOOLEAN

CB spring charging started indication signal

SPRCHRD

BOOLEAN

CB spring charged indication signal

RSTCBWR

BOOLEAN

Reset of CB remaining life and operation counter

RSTTRVT

BOOLEAN

Reset of CB closing and opening travel times

RSTIPOW

BOOLEAN

Reset of accumulated I^CurrExponent

RSTSPCHT

BOOLEAN

Reset of CB spring charging time

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Table 695:

SSCBR Output signals

Name

16.4.5
Table 696:
Name

Type

Description

OPENPOS

BOOLEAN

CB is in open position

CLOSEPOS

BOOLEAN

CB is in closed position

INVDPOS

BOOLEAN

CB is in Invalid Position

TRCMD

BOOLEAN

Open command issued to CB

TRVTOPAL

BOOLEAN

CB open travel time exceeded set value

TRVTCLAL

BOOLEAN

CB close travel time exceeded set value

OPERALM

BOOLEAN

Number of CB operations exceeds alarm limit

OPERLO

BOOLEAN

Number of CB operations exceeds lockout limit

CBLIFEAL

BOOLEAN

Remaining life of CB reduced to Life alarm level

MONALM

BOOLEAN

CB 'not operated for long time' alarm

IPOWALPH

BOOLEAN

Accum I^CurrExponent integr over CB open travel time


exceeds alarm limit

IPOWLOPH

BOOLEAN

Accum I^CurrExponent integr over CB open travel time


exceeds lockout limit

SPCHALM

BOOLEAN

Spring charging time has crossed the set value

GPRESALM

BOOLEAN

Pressure below alarm level

GPRESLO

BOOLEAN

Pressure below lockout level

Settings
SSCBR Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

PhSel

Phase A
Phase B
Phase C

Phase A

Phase selection

RatedOperCurr

100.00 - 5000.00

0.01

1000.00

Rated operating current of the breaker

OperNoRated

1 - 99999

10000

Number of operations possible at rated current

RatedFltCurr

500.00 - 99999.99

0.01

5000.00

Rated fault current of the breaker

OperNoFault

1 - 10000

1000

Number of operations possible at rated fault


current

tTrOpenAlm

0.000 - 0.200

0.001

0.040

Alarm level for open travel time

tTrCloseAlm

0.000 - 0.200

0.001

0.040

Alarm level for close travel time

OperAlmLevel

0 - 9999

200

Alarm level for number of operations

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1047

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

OperLOLevel

0 - 9999

300

Lockout level for number of operations

AccSelCal

Aux Contact
Trip Signal

Trip Signal

Accumulated energy calculation selection

CurrExponent

0.50 - 3.00

0.01

2.00

Current exponent value used for energy


calculation

AccStopCurr

5.00 - 100.00

%IB

0.01

10.00

RMS current level below which energy


accumulation stops

AlmAccCurrPwr

0.00 - 20000.00

0.01

2500.00

Alarm level for accumulated I^CurrExponent


integrated over CB open travel time

LOAccCurrPwr

0.00 - 20000.00

0.01

2500.00

Lockout level for accumulated I^CurrExponent


integrated over CB open travel time

SpChAlmTime

0.00 - 60.00

0.01

1.00

Alarm level for spring charging time

InitCBRemLife

1 - 99999

10000

Initial value for remaining life estimates

InactiveAlDays

0 - 9999

Day

2000

Alarm level for inactive days counter

Table 697:
Name

SSCBR Non group settings (advanced)


Values (Range)

Unit

OpenTimeCorr

-0.100 - 0.100

0.001

0.010

Correction for open travel time

CloseTimeCorr

-0.100 - 0.100

0.001

0.010

Correction for close travel time

DirCoef

-3.00 - -0.50

0.01

-1.50

Directional coefficient for CB life calculation

CBLifeAlmLevel

1 - 99999

5000

Alarm level for CB remaining life

ContTrCorr

-0.010 - 0.010

0.001

0.005

Correction for time difference in auxiliary and


main contacts open time

OperTimeDelay

0.000 - 0.200

0.001

0.020

Time delay between change of status of trip


output and start of main contact separation

tDGasPresAlm

0.00 - 60.00

0.01

0.10

Time delay for gas pressure alarm

tDGasPresLO

0.00 - 60.00

0.01

0.10

Time delay for gas pressure lockout

InitCounterVal

0 - 9999

Initial value for number of operations

InitAccCurrPwr

0.00 - 9999.99

0.01

0.00

Initial value for accum I^CurrExponent integr


over CB open travel time value

InitInactDays

0 - 9999

Day

Initial value for inactive days

InactiveAlHrs

0 - 23

Hour

Alarm time for inactive days counter in hours

1048

Step

Default

Description

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.4.6

Monitored data
Table 698:
Name

16.4.7

SSCBR Monitored data


Type

Values (Range)

Unit

Description

TTRVOP

REAL

ms

Travel time of the CB during


opening operation

TTRVCL

REAL

ms

Travel time of the CB during


closing operation

NOOPER

INTEGER

Number of CB operation cycle

CBLIFEPH

INTEGER

CB Remaining life of
respective phase

INADAYS

INTEGER

The number of days CB has


been inactive

IPOWPH

REAL

Accumulated I^CurrExponent
integrated over CB open travel
time

SPCHT

REAL

The charging time of the CB


spring

Operation principle
The breaker monitoring function includes metering and monitoring subfunctions. The
subfunctions can be enabled and disabled with the Operation setting. The corresponding
parameter values are Enabled and Disabled.
The operation of the subfunctions is described by the module diagram as shown in Figure
479. All the modules in the diagram are explained in subsequent sections.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1049

Section 16
Monitoring

1MRK 502 066-UUS A

I3P-ILRMSPH
POSCLOSE
POSOPEN
BLOCK

TTRVOP

CB Contact Travel
Time

TTRVCL
TRVTOPAL
TRVTCLAL

BLKALM
RSTTRVT

OPENPOS

CB Status

CLOSEPOS
INVDPOS

CBLIFEAL

Remaining Life of CB

CBLIFEPH

RSTCBWR

TRCMD

I3P-IL

Accumulated
energy

TRIND

IPOWALPH
IPOWLOPH
IPOWPH

RSTIPOW

CB Operation
Cycles

OPERALM

CB Operation
Monitoring

MONALM

NOOPER

INADAYS

SPCHALM
SPRCHRST
SPRCHRD

CB Spring Charge
Monitoring

SPCHT

CB Gas Pressure
Indication

GPRESALM

RSTSPCHT

PRESALM
PRESLO

GPRESLO
IEC12000624-3-en.vsd

1050

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

IEC12000624 V3 EN

Figure 479:

16.4.7.1

Functional module diagram of breaker monitoring

Circuit breaker contact travel time


The circuit breaker contact travel time subfunction calculates the breaker contact travel
time for opening and closing operations. The operation of the breaker contact travel time
measurement is described in Figure 480.
POSCLOSE
POSOPEN
RSTTRVT

TTRVOP

Contact travel
time
calculation

TTRVCL

Alarm limit
check

BLOCK

TRVTOPAL
TRVTCLAL

BLKALM
IEC12000615-2-en.vsd

IEC12000615 V2 EN

Figure 480:

Functional module diagram for circuit breaker contact travel time

Contact travel time calculation


The contact travel time of the breaker is calculated from the time between the state of
change of auxiliary contacts. The opening travel time is measured between the opening of
the POSCLOSE and closing of the POSOPEN auxiliary contacts. Similarly, the closing
travel time is measured between the opening of the POSOPEN and closing of the
POSCLOSE auxiliary contacts. A compensation factor has been added to consider the
time difference between auxiliary contact operation and the actual physical opening of the
breaker main contact.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1051

Section 16
Monitoring

1MRK 502 066-UUS A

Main Contact

1
0
POSCLOSE

1
0
POSOPEN

1
0

t1

tOpen

t2

tTravelOpen = tOpen + t1 + t2

t3

tClose

t4

tTravelClose = tClose + t3 + t4
IEC12000616_1_en.vsd

IEC12000616 V1 EN

Figure 481:

Travel time calculation

There is a time difference t1 between the pickup of the main contact opening and the
opening of the POSCLOSE auxiliary contact. Similarly, there is a time difference t2
between the time when the POSOPEN auxiliary contact opens and the main contact is
completely open. Therefore, a correction factor needs to be added to get the actual opening
time. This factor is added with the OpenTimeCorr (t1+t2) setting. The closing time is
calculated by adding the value set with the CloseTimeCorr (t3+t4) setting to the measured
closing time.
The last measured opening travel time (TTRVOP) and the closing travel time (TTRVCL)
are given as service values.
The values can be reset using the Clear menu on the LHMI or by activation the input
RSTCBWR.

Alarm limit check


When the measured opening travel time is longer than the value set in the tTrOpenAlm
setting, the TRVTOPAL output is activated. Similarly, when the measured closing travel
time is longer than the value set in the tTrCloseAlm setting, the TRVTCLAL output is
activated.
It is also possible to block the TRVTCLAL and TRVTOPAL alarm signals by activating the
BLKALM input.

1052

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.4.7.2

Circuit breaker status


The circuit breaker status subfunction monitors the position of the circuit breaker, that is,
whether the breaker is in the open, closed or error position. The operation is described in
Figure 482.

Phase current
check

I3P-ILRMSPH

Contact
position
indicator

POSCLOSE
POSOPEN

OPENPOS
CLOSEPOS
INVDPOS
IEC12000613-3-en.vsd

IEC12000613 V3 EN

Figure 482:

Functional module diagram for monitoring circuit breaker status

Phase current check


The module compares the phase current I3P-ILRMSPH to the AccStopCurr setting. If the
current in the selected phase exceeds the set level, it is reported to the contact position
indicator module as closed circuit breaker.

Contact position indicator


The circuit breaker status is open when the auxiliary input contact POSCLOSE is low, the
POSOPEN input is high and the phase current is less than the setting AccStopCurr value.
The circuit breaker is closed when the POSOPEN input is low and the POSCLOSE input
is high. The breaker is in the error state if both auxiliary contacts have the same value or
if the auxiliary input contact POSCLOSE is low and the POSOPEN input is high but the
current is above the setting AccStopCurr.
The status of the breaker is indicated with the binary outputs OPENPOS, CLOSEPOS and
INVDPOS for open, closed and error position respectively.

16.4.7.3

Remaining life of circuit breaker


The Remaining life of circuit breaker subfunction is used to give an indication on the wear
and tear of the circuit breaker. Every time the breaker operates, the life of the circuit
breaker reduces due to wear. The breaker wear depends on the interrupted current. The
remaining life of the breaker is estimated from the circuit breaker trip curve provided by
the manufacturer. The remaining life is decreased by at least one when the circuit breaker
is opened. The operation of the remaining life of circuit breaker subfunction is described
in Figure 483.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1053

Section 16
Monitoring

1MRK 502 066-UUS A

I3P-ILRMSPH
CB remaining
life estimation

POSCLOSE

CBLIFEPH

RSTCBWR
Alarm limit
Check

BLOCK

CBLIFEAL

BLKALM
IEC12000620-3-en.vsd

IEC12000620 V3 EN

Figure 483:

Functional module diagram for estimating the life of the circuit breaker

Circuit breaker remaining life estimation


If the interrupted current is less than the rated operating current set using the
RatedOperCurr setting, the remaining operations of the breaker are reduced by one
operation. If the interrupted current is more than the rated fault current set using the
RatedFltCurr setting, the remaining operations of the circuit breaker are reduced by the
set OperNoRated divided by the set OperNoFault value. If the tripping current is between
these two values, the remaining life of the circuit breaker is calculated based on the
maintenance curve equation given by the manufacturer. The OperNoRated parameter sets
the number of operations the breaker can perform at the rated current. The OperNoFault
parameter sets the number of operations the breaker can perform at the rated fault current.

Alarm limit check


When the remaining life of a circuit breaker phase drops below the CBLifeAlmLevel
setting, the life alarm CBLIFEAL is activated.
It is possible to deactivate the CBLIFEAL alarm signal by activating the binary input
BLKALM.
The old circuit breaker operation counter value can be used by adding the value to the
InitCBRemLife parameter. The value can be reset using the Clear menu from LHMI or by
activating the input RSTCBWR.

16.4.7.4

Accumulated energy
The Accumulated energy subfunction calculates the accumulated energy (Iyt) based on
current samples, where the setting CurrExponent (y) ranges from 0.5 to 3.0. The operation
is described in Figure 484.
The TRCMD output is enabled when either of the trip indications from the trip coil circuit
TRIND is high or the breaker status is OPENPOS.

1054

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

I3P-IL
TRCMD

I3P-ILRMSPH

Accumulated
energy
calculation

POSCLOSE
TRIND

IPOWPH

LRSTIPOW

Alarm limit
Check

BLOCK

IPOWALPH
IPOWLOPH

BLKALM
IEC12000619-3-en.vsd
IEC12000619 V3 EN

Figure 484:

Functional module diagram for estimating accumulated energy

Accumulated energy calculation


Accumulated energy can be calculated either with TRIND or POSCLOSE by selecting the
AccSelCal parameter value accordingly.
The calculation is initiated with the POSCLOSE or TRIND input events. It ends when the
RMS current is lower than the AccStopCurr setting.
The ContTrCorr setting is used to determine the accumulated energy in relation to the time
the main contact opens. If the setting is positive, the calculation of energy starts after the
auxiliary contact has opened and the delay equal to the value of the ContTrCorr setting has
passed. When the setting is negative, the calculation starts in advance by the correction
time in relation to when the auxiliary contact opened.
Main Contact

Main Contact

close

close
open

POSCLOSE

open

POSCLOSE 1

Energy
Accumulation
starts

Energy
Accumulation
starts

ContTrCorr
(Negative)

ContTrCorr
(Positive)
IEC12000618_1_en.vsd

IEC12000618 V1 EN

Figure 485:

Significance of correction factor setting

Accumulated energy can also be calculated by using the change of state of the trip output.
TRIND is used to get the instance of the trip output and the time delay between the trip
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1055

Section 16
Monitoring

1MRK 502 066-UUS A

initiation and the opening of the main contact is introduced by the setting
OperTimeDelay.
The accumulated energy output IPOWPH is provided as a service value. The value can be
reset by enabling RSTIPOW through LHMI or by activating the input RSTIPOW.

Alarm limit check


The IPOWALPH alarm is activated when the accumulated energy exceeds the set value
AlmAccCurrPwr.
IPOWLOPH is activated when the accumulated energy exceeds the limit of the
LOAccCurrPwr setting.
The IPOWALPH and IPOWLOPH outputs can be blocked by activating the binary input
BLKALM.

16.4.7.5

Circuit breaker operation cycles


The circuit breaker operation cycles subfunction counts the number of closing-opening
sequences of the breaker. The operation counter value is updated after each closingopening sequence. The operation is described in Figure 486.
POSCLOSE
Operation
counter

POSOPEN

NOOPER

RSTCBWR
Alarm limit
Check

BLOCK
BLKALM

OPERALM
OPERLO

IEC12000617 V2 EN

Figure 486:

Functional module diagram for circuit breaker operation cycles

Operation counter
The operation counter counts the number of operations based on the state of change of the
auxiliary contact inputs POSCLOSE and POSOPEN.
The number of operations NOOPER is given as a service value. The old circuit breaker
operation counter value can be used by adding the value to the InitCounterVal parameter
and can be reset by Clear CB wear in the Clear menu on the LHMI or activating the input
RSTCBWR.

1056

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Alarm limit check


OPERALM is generated when the number of operations exceeds the set value of the
OperAlmLevel threshold setting.
If the number of operations increases and exceeds the limit value set with the
OperLOLevel setting, the OPERLO output is activated.
The binary outputs OPERALM and OPERALO are deactivated when the BLKALM input is
activated.

16.4.7.6

Circuit breaker operation monitoring


The circuit breaker operation monitoring subfunction indicates the inactive days of the
circuit breaker and gives an alarm when the number of days exceed the set level. The
operation of the circuit breaker operation monitoring is shown in Figure 487.
POSCLOSE

INADAYS

Inactive timer

POSOPEN
Alarm limit
Check

BLOCK

MONALM

BLKALM
IEC12000614 V2 EN

Figure 487:

Functional module diagram for circuit breaker operation monitoring

Inactive timer
The Inactive timer module calculates the number of days the circuit breaker has remained
in the same open or closed state. The value is calculated by monitoring the states of the
POSOPEN and POSCLOSE auxiliary contacts.
The number of inactive days INADAYS is available as a service value. The initial number
of inactive days is set using the InitInactDays parameter.

Alarm limit check


MONALM is initiated when the number of inactive days and hours exceed the limit value
defined by the InactiveAlDays and InactivAlHrs setting. The alarm signal MONALM can be
blocked by activating the binary input BLKALM.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1057

Section 16
Monitoring
16.4.7.7

1MRK 502 066-UUS A

Circuit breaker spring charge monitoring


The circuit breaker spring charge monitoring subfunction calculates the spring charging
time. The operation is described in Figure 488.
SPRCHRST

Spring charging
time
measurement

SPRCHRD
RSTSPCHT

SPCHT

Alarm limit
Check

BLOCK

SPCHALM

BLKALM
IEC12000621 V2 EN

Figure 488:

Functional module diagram for circuit breaker spring charge indication

Spring charging time measurement


The binary input SPRCHRST indicates the pickup of circuit breaker spring charging time.
SPRCHRD indicates that the circuit breaker spring is charged. The spring charging time is
calculated from the difference of these two signal timings. Spring charging indication is
described in Figure488.
The last measured spring charging time SPCHT is provided as a service value. The spring
charging time SPCHT can be reset on the LHMI or by activating the input RSTSPCHT.

Alarm limit check


If the time taken by the spring to charge is more than the value set with the SpChAlmTime
setting, the subfunction generates the SPCHALM alarm.
It is possible to block the SPCHALM alarm signal by activating the BLKALM binary input.

16.4.7.8

Circuit breaker gas pressure indication


The circuit breaker gas pressure indication subfunction monitors the gas pressure inside
the arc chamber. The operation is described in Figure 489.

1058

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

PRESALM
BLOCK

AND

tDGasPresAlm
0

GPRESALM

BLKALM
PRESLO

AND

tDGasPresLO
0

GPRESLO

ANSI12000622 V1 EN

Figure 489:

Functional module diagram for circuit breaker gas pressure indication

When the PRESALM binary input is activated, the GPRESALM output is activated after a
time delay set with the tDGasPresAlm setting. The GPRESALM alarm can be blocked by
activating the BLKALM input.
If the pressure drops further to a very low level, the PRESLO binary input goes high,
activating the lockout alarm GPRESLO after a time delay set with the tDGasPresLO
setting. The GPRESLO alarm can be blocked by activating the BLKALM input.
The binary input BLOCK can be used to block the function. The activation of the BLOCK
input deactivates all outputs and resets internal timers. The alarm signals from the function
can be blocked by activating the binary input BLKALM.

16.4.8

Technical data
Table 699:

SSCBR Technical data

Function

Range or value

Accuracy

Alarm level for open and close


travel time

(0 200) ms

3 ms

Alarm level for number of


operations

(0 9999)

Independent time delay for spring


charging time alarm

(0.00 60.00) s

0.2% or 30 ms whichever is
greater

Independent time delay for gas


pressure alarm

(0.00 60.00) s

0.2% or 30 ms whichever is
greater

Independent time delay for gas


pressure lockout

(0.00 60.00) s

0.2% or 30 ms whichever is
greater

CB Contact Travel Time, opening


and closing

3 ms

Remaining Life of CB

2 operations

Accumulated Energy

1.0% or 0.5 whichever is


greater

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1059

Section 16
Monitoring

1MRK 502 066-UUS A

16.5

Event function EVENT

16.5.1

Identification
Function description
Event function

IEC 61850
identification

IEC 60617
identification

EVENT

ANSI/IEEE C37.2
device number
-

S00946 V1 EN

16.5.2

Functionality
When using a Substation Automation system with LON or SPA communication, timetagged events can be sent at change or cyclically from the IED to the station level. These
events are created from any available signal in the IED that is connected to the Event
function (EVENT). The event function block is used for remote communication.
Analog and double indication values are also transferred through EVENT function.

16.5.3

Function block
EVENT
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000697-2-en.vsd
IEC05000697 V2 EN

Figure 490:

1060

EVENT function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.5.4

Signals
Table 700:
Name

EVENT Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

GROUP
SIGNAL

Input 1

INPUT2

GROUP
SIGNAL

Input 2

INPUT3

GROUP
SIGNAL

Input 3

INPUT4

GROUP
SIGNAL

Input 4

INPUT5

GROUP
SIGNAL

Input 5

INPUT6

GROUP
SIGNAL

Input 6

INPUT7

GROUP
SIGNAL

Input 7

INPUT8

GROUP
SIGNAL

Input 8

INPUT9

GROUP
SIGNAL

Input 9

INPUT10

GROUP
SIGNAL

Input 10

INPUT11

GROUP
SIGNAL

Input 11

INPUT12

GROUP
SIGNAL

Input 12

INPUT13

GROUP
SIGNAL

Input 13

INPUT14

GROUP
SIGNAL

Input 14

INPUT15

GROUP
SIGNAL

Input 15

INPUT16

GROUP
SIGNAL

Input 16

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1061

Section 16
Monitoring

1MRK 502 066-UUS A

16.5.5
Table 701:

Settings
EVENT Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

SPAChannelMask

Disabled
Channel 1-8
Channel 9-16
Channel 1-16

Disabled

SPA channel mask

LONChannelMask

Disabled
Channel 1-8
Channel 9-16
Channel 1-16

Disabled

LON channel mask

EventMask1

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 1

EventMask2

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 2

EventMask3

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 3

EventMask4

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 4

EventMask5

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 5

EventMask6

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 6

EventMask7

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 7

EventMask8

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 8

Table continues on next page

1062

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

EventMask9

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 9

EventMask10

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 10

EventMask11

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 11

EventMask12

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 12

EventMask13

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 13

EventMask14

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 14

EventMask15

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 15

EventMask16

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 16

MinRepIntVal1

0 - 3600

Minimum reporting interval input 1

MinRepIntVal2

0 - 3600

Minimum reporting interval input 2

MinRepIntVal3

0 - 3600

Minimum reporting interval input 3

MinRepIntVal4

0 - 3600

Minimum reporting interval input 4

MinRepIntVal5

0 - 3600

Minimum reporting interval input 5

MinRepIntVal6

0 - 3600

Minimum reporting interval input 6

MinRepIntVal7

0 - 3600

Minimum reporting interval input 7

MinRepIntVal8

0 - 3600

Minimum reporting interval input 8

MinRepIntVal9

0 - 3600

Minimum reporting interval input 9

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1063

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

MinRepIntVal10

0 - 3600

Minimum reporting interval input 10

MinRepIntVal11

0 - 3600

Minimum reporting interval input 11

MinRepIntVal12

0 - 3600

Minimum reporting interval input 12

MinRepIntVal13

0 - 3600

Minimum reporting interval input 13

MinRepIntVal14

0 - 3600

Minimum reporting interval input 14

MinRepIntVal15

0 - 3600

Minimum reporting interval input 15

MinRepIntVal16

0 - 3600

Minimum reporting interval input 16

16.5.6

Operation principle
The main purpose of the event function (EVENT) is to generate events when the state or
value of any of the connected input signals is in a state, or is undergoing a state transition,
for which event generation is enabled.
Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given a name
from the Application Configuration tool. The inputs are normally used to create single
events, but are also intended for double indication events.
EVENT function also has an input BLOCK to block the generation of events.
The events that are sent from the IED can originate from both internal logical signals and
binary input channels. The internal signals are time-tagged in the main processing
module, while the binary input channels are time-tagged directly on the input module. The
time-tagging of the events that are originated from internal logical signals have a
resolution corresponding to the execution cycle-time of the source application. The timetagging of the events that are originated from binary input signals have a resolution of 1
ms.
The outputs from EVENT function are formed by the reading of status, events and alarms
by the station level on every single input. The user-defined name for each input is intended
to be used by the station level.
All events according to the event mask are stored in a buffer, which contains up to 1000
events. If new events appear before the oldest event in the buffer is read, the oldest event
is overwritten and an overflow alarm appears.
The events are produced according to the set-event masks. The event masks are treated
commonly for both the LON and SPA communication. The EventMask can be set
individually for each input channel. These settings are available:

1064

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

NoEvents
OnSet
OnReset
OnChange
AutoDetect

It is possible to define which part of EVENT function generates the events. This can be
performed individually for the SPAChannelMask and LONChannelMask respectively.
For each communication type these settings are available:

Disabled
Channel 1-8
Channel 9-16
Channel 1-16

For LON communication the events normally are sent to station level at change. It is
possibly also to set a time for cyclic sending of the events individually for each input
channel.
To protect the SA system from signals with a high change rate that can easily saturate the
event system or the communication subsystems behind it, a quota limiter is implemented.
If an input creates events at a rate that completely consume the granted quota then further
events from the channel will be blocked. This block will be removed when the input calms
down and the accumulated quota reach 66% of the maximum burst quota. The maximum
burst quota per input channel is 45 events per second.

16.6

Disturbance report DRPRDRE

16.6.1

Identification
Function description

IEC 61850 identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Disturbance report

DRPRDRE

Disturbance report

A1RADR - A4RADR

Disturbance report

B1RBDR - B8RBDR

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1065

Section 16
Monitoring
16.6.2

1MRK 502 066-UUS A

Functionality
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data of all
selected analog input and binary signals connected to the function block with a, maximum
of 40 analog and 96 binary signals.
The Disturbance report functionality is a common name for several functions:

Sequential of events
Indications
Event recorder
Trip value recorder
Disturbance recorder

The Disturbance report function is characterized by great flexibility regarding


configuration, initiating conditions, recording times, and large storage capacity.
A disturbance is defined as an activation of an input to the AnRADR or BnRBDR function
blocks, which are set to trigger the disturbance recorder. All connected signals from
pickup of pre-fault time to the end of post-fault time will be included in the recording.
Every disturbance report recording is saved in the IED in the standard Comtrade format
as a reader file HDR, a configuration file CFG, and a data file DAT. The same applies to
all events, which are continuously saved in a ring-buffer. The local HMI is used to get
information about the recordings. The disturbance report files may be uploaded to
PCM600 for further analysis using the disturbance handling tool.

16.6.3

Function block
DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC05000406-3-en.vsd
IEC05000406 V3 EN

Figure 491:

1066

DRPRDRE function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

A1RADR
^GRP INPUT1
^GRP INPUT2
^GRP INPUT3
^GRP INPUT4
^GRP INPUT5
^GRP INPUT6
^GRP INPUT7
^GRP INPUT8
^GRP INPUT9
^GRP INPUT10

IEC05000430-4-en.vsdx

IEC05000430 V4 EN

Figure 492:

A1RADR function block example for A1RADR-A3RADR

A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40
IEC05000431-3-en.vsd
IEC05000431 V3 EN

Figure 493:

A4RADR function block, derived analog inputs

B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000432-3-en.vsd
IEC05000432 V3 EN

Figure 494:

B1RBDR function block, binary inputs, example for B1RBDR - B8RBDR

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1067

Section 16
Monitoring
16.6.4

1MRK 502 066-UUS A

Signals
Table 702:
Name

DRPRDRE Output signals


Type

Description

DRPOFF

BOOLEAN

Disturbance report function turned off

RECSTART

BOOLEAN

Disturbance recording started

RECMADE

BOOLEAN

Disturbance recording made

CLEARED

BOOLEAN

All disturbances in the disturbance report cleared

MEMUSED

BOOLEAN

More than 80% of memory used

Table 703:
Name

A1RADR Input signals


Type

Default

Description

GRPINPUT1

GROUP
SIGNAL

Group signal for input 1

GRPINPUT2

GROUP
SIGNAL

Group signal for input 2

GRPINPUT3

GROUP
SIGNAL

Group signal for input 3

GRPINPUT4

GROUP
SIGNAL

Group signal for input 4

GRPINPUT5

GROUP
SIGNAL

Group signal for input 5

GRPINPUT6

GROUP
SIGNAL

Group signal for input 6

GRPINPUT7

GROUP
SIGNAL

Group signal for input 7

GRPINPUT8

GROUP
SIGNAL

Group signal for input 8

GRPINPUT9

GROUP
SIGNAL

Group signal for input 9

GRPINPUT10

GROUP
SIGNAL

Group signal for input 10

A2RADR and A3RADR functions have the same input signal specifications as A1RADR
but with different numbering:

1068

A2RADR: GRPINPUT11 to GRPINPUT20 (group signal for inputs 11 to 20)


A3RADR: GRPINPUT21 to GRPINPUT30 (group signal for inputs 21 to 30)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Table 704:
Name

A4RADR Input signals


Type

Default

Description

INPUT31

REAL

Analog channel 31

INPUT32

REAL

Analog channel 32

INPUT33

REAL

Analog channel 33

INPUT34

REAL

Analog channel 34

INPUT35

REAL

Analog channel 35

INPUT36

REAL

Analog channel 36

INPUT37

REAL

Analog channel 37

INPUT38

REAL

Analog channel 38

INPUT39

REAL

Analog channel 39

INPUT40

REAL

Analog channel 40

Table 705:
Name

B1RBDR Input signals


Type

Default

Description

INPUT1

BOOLEAN

Binary channel 1

INPUT2

BOOLEAN

Binary channel 2

INPUT3

BOOLEAN

Binary channel 3

INPUT4

BOOLEAN

Binary channel 4

INPUT5

BOOLEAN

Binary channel 5

INPUT6

BOOLEAN

Binary channel 6

INPUT7

BOOLEAN

Binary channel 7

INPUT8

BOOLEAN

Binary channel 8

INPUT9

BOOLEAN

Binary channel 9

INPUT10

BOOLEAN

Binary channel 10

INPUT11

BOOLEAN

Binary channel 11

INPUT12

BOOLEAN

Binary channel 12

INPUT13

BOOLEAN

Binary channel 13

INPUT14

BOOLEAN

Binary channel 14

INPUT15

BOOLEAN

Binary channel 15

INPUT16

BOOLEAN

Binary channel 16

B2RBDR to B8RBDR functions have the same input signal specifications as B1RBDR
but with different numbering:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1069

Section 16
Monitoring

1MRK 502 066-UUS A

16.6.5
Table 706:
Name

B2RBDR: INPUT17 to INPUT32 (binary channels 17 to 32)


B3RBDR: INPUT33 to INPUT48 (binary channels 33 to 48)
B4RBDR: INPUT49 to INPUT64 (binary channels 49 to 64)
B5RBDR: INPUT65 to INPUT80 (binary channels 65 to 80)
B6RBDR: INPUT81 to INPUT96 (binary channels 81 to 96)
B7RBDR: INPUT97 to INPUT112 (binary channels 97 to 112)
B8RBDR: INPUT113 to INPUT128 (binary channels 113 to 128)

Settings
DRPRDRE Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PreFaultRecT

0.05 - 9.90

0.01

0.10

Pre-fault recording time

PostFaultRecT

0.1 - 10.0

0.1

0.5

Post-fault recording time

TimeLimit

0.5 - 10.0

0.1

1.0

Fault recording time limit

PostRetrig

Disabled
Enabled

Disabled

Post-fault retrig enabled (On) or not (Off)

MaxNoStoreRec

10 - 100

100

Maximum number of stored disturbances

ZeroAngleRef

1 - 30

Ch

Trip value recorder, phasor reference channel

OpModeTest

Disabled
Enabled

Disabled

Operation mode during test mode

Table 707:
Name

A1RADR Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation01

Disabled
Enabled

Disabled

Operation On/Off

Operation02

Disabled
Enabled

Disabled

Operation On/Off

Operation03

Disabled
Enabled

Disabled

Operation On/Off

Operation04

Disabled
Enabled

Disabled

Operation On/Off

Operation05

Disabled
Enabled

Disabled

Operation On/Off

Operation06

Disabled
Enabled

Disabled

Operation On/Off

Operation07

Disabled
Enabled

Disabled

Operation On/Off

Table continues on next page

1070

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

Operation08

Disabled
Enabled

Disabled

Operation On/Off

Operation09

Disabled
Enabled

Disabled

Operation On/Off

Operation10

Disabled
Enabled

Disabled

Operation On/Off

Table 708:
Name

A1RADR Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

NomValue01

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 1

UnderTrigOp01

Disabled
Enabled

Disabled

Use under level trigger for analog channel 1


(on) or not (off)

UnderTrigLe01

0 - 200

50

Under trigger level for analog channel 1 in % of


signal

OverTrigOp01

Disabled
Enabled

Disabled

Use over level trigger for analog channel 1 (on)


or not (off)

OverTrigLe01

0 - 5000

200

Over trigger level for analog channel 1 in % of


signal

NomValue02

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 2

UnderTrigOp02

Disabled
Enabled

Disabled

Use under level trigger for analog channel 2


(on) or not (off)

UnderTrigLe02

0 - 200

50

Under trigger level for analog channel 2 in % of


signal

OverTrigOp02

Disabled
Enabled

Disabled

Use over level trigger for analog channel 2 (on)


or not (off)

OverTrigLe02

0 - 5000

200

Over trigger level for analog channel 2 in % of


signal

NomValue03

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 3

UnderTrigOp03

Disabled
Enabled

Disabled

Use under level trigger for analog channel 3


(on) or not (off)

UnderTrigLe03

0 - 200

50

Under trigger level for analog channel 3 in % of


signal

OverTrigOp03

Disabled
Enabled

Disabled

Use over level trigger for analog channel 3 (on)


or not (off)

OverTrigLe03

0 - 5000

200

Overtrigger level for analog channel 3 in % of


signal

NomValue04

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 4

UnderTrigOp04

Disabled
Enabled

Disabled

Use under level trigger for analog channel 4


(on) or not (off)

UnderTrigLe04

0 - 200

50

Under trigger level for analog channel 4 in % of


signal

OverTrigOp04

Disabled
Enabled

Disabled

Use over level trigger for analog channel 4 (on)


or not (off)

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1071

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

OverTrigLe04

0 - 5000

200

Over trigger level for analog channel 4 in % of


signal

NomValue05

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 5

UnderTrigOp05

Disabled
Enabled

Disabled

Use under level trigger for analog channel 5


(on) or not (off)

UnderTrigLe05

0 - 200

50

Under trigger level for analog channel 5 in % of


signal

OverTrigOp05

Disabled
Enabled

Disabled

Use over level trigger for analog channel 5 (on)


or not (off)

OverTrigLe05

0 - 5000

200

Over trigger level for analog channel 5 in % of


signal

NomValue06

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 6

UnderTrigOp06

Disabled
Enabled

Disabled

Use under level trigger for analog channel 6


(on) or not (off)

UnderTrigLe06

0 - 200

50

Under trigger level for analog channel 6 in % of


signal

OverTrigOp06

Disabled
Enabled

Disabled

Use over level trigger for analog channel 6 (on)


or not (off)

OverTrigLe06

0 - 5000

200

Over trigger level for analog channel 6 in % of


signal

NomValue07

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 7

UnderTrigOp07

Disabled
Enabled

Disabled

Use under level trigger for analog channel 7


(on) or not (off)

UnderTrigLe07

0 - 200

50

Under trigger level for analog channel 7 in % of


signal

OverTrigOp07

Disabled
Enabled

Disabled

Use over level trigger for analog channel 7 (on)


or not (off)

OverTrigLe07

0 - 5000

200

Over trigger level for analog channel 7 in % of


signal

NomValue08

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 8

UnderTrigOp08

Disabled
Enabled

Disabled

Use under level trigger for analog channel 8


(on) or not (off)

UnderTrigLe08

0 - 200

50

Under trigger level for analog channel 8 in % of


signal

OverTrigOp08

Disabled
Enabled

Disabled

Use over level trigger for analog channel 8 (on)


or not (off)

OverTrigLe08

0 - 5000

200

Over trigger level for analog channel 8 in % of


signal

NomValue09

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 9

UnderTrigOp09

Disabled
Enabled

Disabled

Use under level trigger for analog channel 9


(on) or not (off)

UnderTrigLe09

0 - 200

50

Under trigger level for analog channel 9 in % of


signal

Table continues on next page

1072

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

OverTrigOp09

Disabled
Enabled

Disabled

Use over level trigger for analog channel 9 (on)


or not (off)

OverTrigLe09

0 - 5000

200

Over trigger level for analog channel 9 in % of


signal

NomValue10

0.0 - 999999.9

0.1

0.0

Nominal value for analog channel 10

UnderTrigOp10

Disabled
Enabled

Disabled

Use under level trigger for analog channel 10


(on) or not (off)

UnderTrigLe10

0 - 200

50

Under trigger level for analog channel 10 in %


of signal

OverTrigOp10

Disabled
Enabled

Disabled

Use over level trigger for analog channel 10


(on) or not (off)

OverTrigLe10

0 - 5000

200

Over trigger level for analog channel 10 in % of


signal

A2RADR to A4RADR functions have the same Non group settings (basic) as A1RADR
but with different numbering:

A2RADR: Operation11 to Operation20


A3RADR: Operation21 to Operation30
A4RADR: Operation31 to Operation40

A2RADR to A4RADR functions have the same Non group settings (advanced) as
A1RADR but with different numbering (examples given in brackets):

Table 709:
Name

A2RADR: 11 to 20 (NomValue11, nominal value for analog channel 11)


A3RADR: 21 to 30 (NomValue21, nominal value for analog channel 21)
A4RADR: 31 to 40 (NomValue31, nominal value for analog channel 31)

B1RBDR Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

TrigDR01

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED01

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 1

TrigDR02

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED02

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 2

TrigDR03

Disabled
Enabled

Disabled

Trigger operation On/Off

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1073

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

SetLED03

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 3

TrigDR04

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED04

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 4

TrigDR05

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED05

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 5

TrigDR06

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED06

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 6

TrigDR07

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED07

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 7

TrigDR08

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED08

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 8

TrigDR09

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED09

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 9

TrigDR10

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED10

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 10

TrigDR11

Disabled
Enabled

Disabled

Trigger operation On/Off

Table continues on next page

1074

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

SetLED11

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 11

TrigDR12

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED12

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 12

TrigDR13

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED13

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 13

TrigDR14

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED14

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 14

TrigDR15

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED15

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 15

TrigDR16

Disabled
Enabled

Disabled

Trigger operation On/Off

SetLED16

Disabled
Pickup
Trip
Pickup and Trip

Disabled

Set LED on HMI for binary channel 16

FunType1

0 - 255

Function type for binary channel 1 (IEC


-60870-5-103)

InfNo1

0 - 255

Information number for binary channel 1 (IEC


-60870-5-103)

FunType2

0 - 255

Function type for binary channel 2 (IEC


-60870-5-103)

InfNo2

0 - 255

Information number for binary channel 2 (IEC


-60870-5-103)

FunType3

0 - 255

Function type for binary channel 3 (IEC


-60870-5-103)

InfNo3

0 - 255

Information number for binary channel 3 (IEC


-60870-5-103)

FunType4

0 - 255

Function type for binary channel 4 (IEC


-60870-5-103)

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1075

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

InfNo4

0 - 255

Information number for binary channel 4 (IEC


-60870-5-103)

FunType5

0 - 255

Function type for binary channel 5 (IEC


-60870-5-103)

InfNo5

0 - 255

Information number for binary channel 5 (IEC


-60870-5-103)

FunType6

0 - 255

Function type for binary channel 6 (IEC


-60870-5-103)

InfNo6

0 - 255

Information number for binary channel 6 (IEC


-60870-5-103)

FunType7

0 - 255

Function type for binary channel 7 (IEC


-60870-5-103)

InfNo7

0 - 255

Information number for binary channel 7 (IEC


-60870-5-103)

FunType8

0 - 255

Function type for binary channel 8 (IEC


-60870-5-103)

InfNo8

0 - 255

Information number for binary channel 8 (IEC


-60870-5-103)

FunType9

0 - 255

Function type for binary channel 9 (IEC


-60870-5-103)

InfNo9

0 - 255

Information number for binary channel 9 (IEC


-60870-5-103)

FunType10

0 - 255

Function type for binary channel 10 (IEC


-60870-5-103)

InfNo10

0 - 255

Information number for binary channel 10 (IEC


-60870-5-103)

FunType11

0 - 255

Function type for binary channel 11 (IEC


-60870-5-103)

InfNo11

0 - 255

Information number for binary channel 11 (IEC


-60870-5-103)

FunType12

0 - 255

Function type for binary channel 12 (IEC


-60870-5-103)

InfNo12

0 - 255

Information number for binary channel 12 (IEC


-60870-5-103)

FunType13

0 - 255

Function type for binary channel 13 (IEC


-60870-5-103)

InfNo13

0 - 255

Information number for binary channel 13 (IEC


-60870-5-103)

FunType14

0 - 255

Function type for binary channel 14 (IEC


-60870-5-103)

InfNo14

0 - 255

Information number for binary channel 14 (IEC


-60870-5-103)

FunType15

0 - 255

Function type for binary channel 15 (IEC


-60870-5-103)

Table continues on next page

1076

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

InfNo15

0 - 255

Information number for binary channel 15 (IEC


-60870-5-103)

FunType16

0 - 255

Function type for binary channel 16 (IEC


-60870-5-103)

InfNo16

0 - 255

Information number for binary channel 16 (IEC


-60870-5-103)

Table 710:
Name

B1RBDR Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

TrigLevel01

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 1

IndicationMa01

Hide
Show

Show

Indication mask for binary channel 1

TrigLevel02

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 2

IndicationMa02

Hide
Show

Show

Indication mask for binary channel 2

TrigLevel03

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 3

IndicationMa03

Hide
Show

Show

Indication mask for binary channel 3

TrigLevel04

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 4

IndicationMa04

Hide
Show

Show

Indication mask for binary channel 4

TrigLevel05

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 5

IndicationMa05

Hide
Show

Show

Indication mask for binary channel 5

TrigLevel06

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 6

IndicationMa06

Hide
Show

Show

Indication mask for binary channel 6

TrigLevel07

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 7

IndicationMa07

Hide
Show

Show

Indication mask for binary channel 7

TrigLevel08

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 8

IndicationMa08

Hide
Show

Show

Indication mask for binary channel 8

TrigLevel09

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 9

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1077

Section 16
Monitoring

Name

1MRK 502 066-UUS A

Values (Range)

Unit

Step

Default

Description

IndicationMa09

Hide
Show

Show

Indication mask for binary channel 9

TrigLevel10

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 10

IndicationMa10

Hide
Show

Show

Indication mask for binary channel 10

TrigLevel11

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 11

IndicationMa11

Hide
Show

Show

Indication mask for binary channel 11

TrigLevel12

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 12

IndicationMa12

Hide
Show

Show

Indication mask for binary channel 12

TrigLevel13

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 13

IndicationMa13

Hide
Show

Show

Indication mask for binary channel 13

TrigLevel14

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 14

IndicationMa14

Hide
Show

Show

Indication mask for binary channel 14

TrigLevel15

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 15

IndicationMa15

Hide
Show

Show

Indication mask for binary channel 15

TrigLevel16

Trig on 0
Trig on 1

Trig on 1

Trigger on positive (1) or negative (0) slope for


binary input 16

IndicationMa16

Hide
Show

Show

Indication mask for binary channel 16

B2RBDR to B8RBDR functions have the same Non group settings (basic) as B1RBDR
but with different numbering (examples given in brackets):

B2RBDR: 17 to 32 (SetLED17, set LED on HMI for binary channel 17)


B3RBDR: 33 to 48 (SetLED33, set LED on HMI for binary channel 33)
B4RBDR: 49 to 64 (SetLED49, set LED on HMI for binary channel 49)
B5RBDR: 65 to 80 (SetLED65, set LED on HMI for binary channel 65)
B6RBDR: 81 to 96 (SetLED81, set LED on HMI for binary channel 81)
B7RBDR: 97 to 112 (SetLED97, set LED on HMI for binary channel 97)
B8RBDR: 113 to 128 (SetLED113, set LED on HMI for binary channel 113)

B2RBDR to B8RBDR functions have the same Non group settings (advanced) as
B1RBDR but with different numbering (examples given in brackets):
1078

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.6.6

B2RBDR: 17 to 32 (IndicationMa17, indication mask for binary channel 17)


B3RBDR: 33 to 48 (IndicationMa33, indication mask for binary channel 33)
B4RBDR: 49 to 64 (IndicationMa49, indication mask for binary channel 49)
B5RBDR: 65 to 80 (IndicationMa65, indication mask for binary channel 65)
B6RBDR: 81 to 96 (IndicationMa81, indication mask for binary channel 81)
B7RBDR: 97 to 112 (IndicationMa97, indication mask for binary channel 97)
B8RBDR: 113 to 128 (IndicationMa113, indication mask for binary channel 113)

Monitored data
Table 711:
Name

DRPRDRE Monitored data


Type

Values (Range)

Unit

Description

MemoryUsed

INTEGER

Memory usage (0-100%)

UnTrigStatCh1

BOOLEAN

Under level trig for analog


channel 1 activated

OvTrigStatCh1

BOOLEAN

Over level trig for analog


channel 1 activated

UnTrigStatCh2

BOOLEAN

Under level trig for analog


channel 2 activated

OvTrigStatCh2

BOOLEAN

Over level trig for analog


channel 2 activated

UnTrigStatCh3

BOOLEAN

Under level trig for analog


channel 3 activated

OvTrigStatCh3

BOOLEAN

Over level trig for analog


channel 3 activated

UnTrigStatCh4

BOOLEAN

Under level trig for analog


channel 4 activated

OvTrigStatCh4

BOOLEAN

Over level trig for analog


channel 4 activated

UnTrigStatCh5

BOOLEAN

Under level trig for analog


channel 5 activated

OvTrigStatCh5

BOOLEAN

Over level trig for analog


channel 5 activated

UnTrigStatCh6

BOOLEAN

Under level trig for analog


channel 6 activated

OvTrigStatCh6

BOOLEAN

Over level trig for analog


channel 6 activated

UnTrigStatCh7

BOOLEAN

Under level trig for analog


channel 7 activated

OvTrigStatCh7

BOOLEAN

Over level trig for analog


channel 7 activated

UnTrigStatCh8

BOOLEAN

Under level trig for analog


channel 8 activated

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1079

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

OvTrigStatCh8

BOOLEAN

Over level trig for analog


channel 8 activated

UnTrigStatCh9

BOOLEAN

Under level trig for analog


channel 9 activated

OvTrigStatCh9

BOOLEAN

Over level trig for analog


channel 9 activated

UnTrigStatCh10

BOOLEAN

Under level trig for analog


channel 10 activated

OvTrigStatCh10

BOOLEAN

Over level trig for analog


channel 10 activated

UnTrigStatCh11

BOOLEAN

Under level trig for analog


channel 11 activated

OvTrigStatCh11

BOOLEAN

Over level trig for analog


channel 11 activated

UnTrigStatCh12

BOOLEAN

Under level trig for analog


channel 12 activated

OvTrigStatCh12

BOOLEAN

Over level trig for analog


channel 12 activated

UnTrigStatCh13

BOOLEAN

Under level trig for analog


channel 13 activated

OvTrigStatCh13

BOOLEAN

Over level trig for analog


channel 13 activated

UnTrigStatCh14

BOOLEAN

Under level trig for analog


channel 14 activated

OvTrigStatCh14

BOOLEAN

Over level trig for analog


channel 14 activated

UnTrigStatCh15

BOOLEAN

Under level trig for analog


channel 15 activated

OvTrigStatCh15

BOOLEAN

Over level trig for analog


channel 15 activated

UnTrigStatCh16

BOOLEAN

Under level trig for analog


channel 16 activated

OvTrigStatCh16

BOOLEAN

Over level trig for analog


channel 16 activated

UnTrigStatCh17

BOOLEAN

Under level trig for analog


channel 17 activated

OvTrigStatCh17

BOOLEAN

Over level trig for analog


channel 17 activated

UnTrigStatCh18

BOOLEAN

Under level trig for analog


channel 18 activated

OvTrigStatCh18

BOOLEAN

Over level trig for analog


channel 18 activated

UnTrigStatCh19

BOOLEAN

Under level trig for analog


channel 19 activated

Table continues on next page

1080

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

OvTrigStatCh19

BOOLEAN

Over level trig for analog


channel 19 activated

UnTrigStatCh20

BOOLEAN

Under level trig for analog


channel 20 activated

OvTrigStatCh20

BOOLEAN

Over level trig for analog


channel 20 activated

UnTrigStatCh21

BOOLEAN

Under level trig for analog


channel 21 activated

OvTrigStatCh21

BOOLEAN

Over level trig for analog


channel 21 activated

UnTrigStatCh22

BOOLEAN

Under level trig for analog


channel 22 activated

OvTrigStatCh22

BOOLEAN

Over level trig for analog


channel 22 activated

UnTrigStatCh23

BOOLEAN

Under level trig for analog


channel 23 activated

OvTrigStatCh23

BOOLEAN

Over level trig for analog


channel 23 activated

UnTrigStatCh24

BOOLEAN

Under level trig for analog


channel 24 activated

OvTrigStatCh24

BOOLEAN

Over level trig for analog


channel 24 activated

UnTrigStatCh25

BOOLEAN

Under level trig for analog


channel 25 activated

OvTrigStatCh25

BOOLEAN

Over level trig for analog


channel 25 activated

UnTrigStatCh26

BOOLEAN

Under level trig for analog


channel 26 activated

OvTrigStatCh26

BOOLEAN

Over level trig for analog


channel 26 activated

UnTrigStatCh27

BOOLEAN

Under level trig for analog


channel 27 activated

OvTrigStatCh27

BOOLEAN

Over level trig for analog


channel 27 activated

UnTrigStatCh28

BOOLEAN

Under level trig for analog


channel 28 activated

OvTrigStatCh28

BOOLEAN

Over level trig for analog


channel 28 activated

UnTrigStatCh29

BOOLEAN

Under level trig for analog


channel 29 activated

OvTrigStatCh29

BOOLEAN

Over level trig for analog


channel 29 activated

UnTrigStatCh30

BOOLEAN

Under level trig for analog


channel 30 activated

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1081

Section 16
Monitoring

1MRK 502 066-UUS A

Name

1082

Type

Values (Range)

Unit

Description

OvTrigStatCh30

BOOLEAN

Over level trig for analog


channel 30 activated

UnTrigStatCh31

BOOLEAN

Under level trig for analog


channel 31 activated

OvTrigStatCh31

BOOLEAN

Over level trig for analog


channel 31 activated

UnTrigStatCh32

BOOLEAN

Under level trig for analog


channel 32 activated

OvTrigStatCh32

BOOLEAN

Over level trig for analog


channel 32 activated

UnTrigStatCh33

BOOLEAN

Under level trig for analog


channel 33 activated

OvTrigStatCh33

BOOLEAN

Over level trig for analog


channel 33 activated

UnTrigStatCh34

BOOLEAN

Under level trig for analog


channel 34 activated

OvTrigStatCh34

BOOLEAN

Over level trig for analog


channel 34 activated

UnTrigStatCh35

BOOLEAN

Under level trig for analog


channel 35 activated

OvTrigStatCh35

BOOLEAN

Over level trig for analog


channel 35 activated

UnTrigStatCh36

BOOLEAN

Under level trig for analog


channel 36 activated

OvTrigStatCh36

BOOLEAN

Over level trig for analog


channel 36 activated

UnTrigStatCh37

BOOLEAN

Under level trig for analog


channel 37 activated

OvTrigStatCh37

BOOLEAN

Over level trig for analog


channel 37 activated

UnTrigStatCh38

BOOLEAN

Under level trig for analog


channel 38 activated

OvTrigStatCh38

BOOLEAN

Over level trig for analog


channel 38 activated

UnTrigStatCh39

BOOLEAN

Under level trig for analog


channel 39 activated

OvTrigStatCh39

BOOLEAN

Over level trig for analog


channel 39 activated

UnTrigStatCh40

BOOLEAN

Under level trig for analog


channel 40 activated

OvTrigStatCh40

BOOLEAN

Over level trig for analog


channel 40 activated

FaultNumber

INTEGER

Disturbance fault number

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.6.7

Operation principle
Disturbance report DRPRDRE is a common name for several functions to supply the
operator, analysis engineer, and so on, with sufficient information about events in the
system.
The functions included in the disturbance report are:

Sequential of events (SOE)


Indications (IND)
Event recorder (ER)
Trip value recorder(TVR)
Disturbance recorder (DR)

Figure 495 shows the relations between Disturbance Report, included functions and
function blocks. Sequential of events (SOE), Event recorder (ER) and Indications (IND)
uses information from the binary input function blocks (BxRBDR). Trip value recorder
(TVR) uses analog information from the analog input function blocks (AxRADR).
Disturbance recorder DRPRDRE acquires information from both AxRADR and
BxRBDR.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1083

Section 16
Monitoring

1MRK 502 066-UUS A

AxRADR

Disturbance Report

DRPRDRE
Analog signals

Trip value rec

BxRBDR

Disturbance
recorder

Binary signals

Sequential of
events
Event recorder
Indications

ANSI09000337-2-en.vsd

ANSI09000337 V2 EN

Figure 495:

Disturbance report functions and related function blocks

The whole disturbance report can contain information for a number of recordings, each
with the data coming from all the parts mentioned above. The sequential of events
function is working continuously, independent of disturbance triggering, recording time,
and so on. All information in the disturbance report is stored in non-volatile flash
memories. This implies that no information is lost in case of loss of auxiliary power. Each
report will get an identification number in the interval from 0-999.
Disturbance report

Record no. N

General dist.
information

Indications

Record no. N+1

Trip
values

Record no. N+100

Event
recordings

Disturbance
recording

Event list
(SOE)
en05000161_ansi.vsd

ANSI05000161 V1 EN

Figure 496:
1084

Disturbance report structure


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded when


the memory is full, the oldest disturbance report is overwritten by the new one. The total
recording capacity for the disturbance recorder is depending of sampling frequency,
number of analog and binary channels and recording time. Figure 497 shows the number
of recordings versus the total recording time tested for a typical configuration, that is, in a
60 Hz system it is possible to record 80 where the average recording time is 3.4 seconds.
The memory limit does not affect the rest of the disturbance report (Event list (EL), Event
recorder (ER), Indications (IND) and Trip value recorder (TVR)).

Number of recordings
100

3.4s
20 analog
96 binary

3.4s

80

40 analog
96 binary

60

6.3s

6.3s
50 Hz

6.3s

40

60 Hz

Total recording time


250

300

350

400 s
en05000488_ansi.vsd

ANSI05000488 V1 EN

Figure 497:

Example of number of recordings versus the total recording time

The maximum number of recordings depend on each recordings total


recording time. Long recording time will reduce the number of recordings
to less than 100.

The IED flash disk should NOT be used to store any user files. This might
cause disturbance recordings to be deleted due to lack of disk space.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1085

Section 16
Monitoring

1MRK 502 066-UUS A

Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip values
are available on the local HMI. To acquire a complete disturbance report the user must use
a PC and - either the PCM600 Disturbance handling tool - or a FTP or MMS (over 61850)
client. The PC can be connected to the IED front, rear or remotely via the station bus
(Ethernet ports).

Indications (IND)
Indications is a list of signals that were activated during the total recording time of the
disturbance (not time-tagged).

Event recorder (ER)


The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600.

Sequential of events (SOE)


The sequetial of events may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The oldest
data is overwritten. The logged signals may be presented via local HMI or PCM600.

Trip value recorder (TVR)


The recorded trip values include phasors of selected analog signals before the fault and
during the fault.

Disturbance recorder (DR)


Disturbance recorder records analog and binary signal data before, during and after the
fault.

Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all time
tagging within the disturbance report

Recording times
Disturbance report DRPRDRE records information about a disturbance during a settable
time frame. The recording times are valid for the whole disturbance report. Disturbance
recorder (DR), event recorder (ER) and indication function register disturbance data and
events during tRecording, the total recording time.
The total recording time, tRecording, of a recorded disturbance is:
tRecording =

1086

PreFaultrecT + tFault + PostFaultrecT or PreFaultrecT + TimeLimit, depending on which


criterion stops the current disturbance recording

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Trig point
TimeLimit
PreFaultRecT

PostFaultRecT

3
en05000487.vsd

IEC05000487 V1 EN

Figure 498:

The recording times definition

PreFaultRecT, 1

Pre-fault or pre-trigger recording time. The time before the fault including the trip time of
the trigger. Use the setting PreFaultRecT to set this time.

tFault, 2

Fault time of the recording. The fault time cannot be set. It continues as long as any valid
trigger condition, binary or analog, persists (unless limited by TimeLimit the limit time).

PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all activated
triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit

Limit time. The maximum allowed recording time after the disturbance recording was
triggered. The limit time is used to eliminate the consequences of a trigger that does not
reset within a reasonable time interval. It limits the maximum recording time of a recording
and prevents subsequent overwriting of already stored disturbances. Use the setting
TimeLimit to set this time.

Analog signals
Up to 40 analog signals can be selected for recording by the Disturbance recorder and
triggering of the Disturbance report function. Out of these 40, 30 are reserved for external
analog signals from analog input modules (TRM) and line data communication module
(LDCM) via preprocessing function blocks (SMAI) and summation block (3PHSUM).
The last 10 channels may be connected to internally calculated analog signals available as
function block output signals (mA input signals, phase differential currents, bias currents
and so on).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1087

Section 16
Monitoring

1MRK 502 066-UUS A

A1RADR

SMAI

External analog
signals

Block
^GRP2_A

AI3P
AI1

^GRP2_B
^GRP2_C

AI2
AI3

INPUT2

^GRP2_N
Type

AI4
AIN

INPUT4

A2RADR
INPUT1

A3RADR

INPUT3
INPUT5
INPUT6
...
A4RADR
INPUT31
INPUT32

Internal analog signals

INPUT33
INPUT34
INPUT35
INPUT36
...
INPUT40
ANSI10000029-1-en.vsd

ANSI10000029 V1 EN

Figure 499:

Analog input function blocks

The external input signals will be acquired, filtered and skewed and (after configuration)
available as an input signal on the AxRADR function block via the SMAI function block.
The information is saved at the Disturbance report base sampling rate (1000 or 1200 Hz).
Internally calculated signals are updated according to the cycle time of the specific
function. If a function is running at lower speed than the base sampling rate, Disturbance
recorder will use the latest updated sample until a new updated sample is available.
If the IED is preconfigured the only tool needed for analog configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration). In case
of modification of a preconfigured IED or general internal configuration the Application
Configuration tool within PCM600 is used.
The preprocessor function block (SMAI) calculates the residual quantities in cases where
only the three phases are connected (AI4-input not used). SMAI makes the information
available as a group signal output, phase outputs and calculated residual output (AINoutput). In situations where AI4-input is used as an input signal the corresponding
information is available on the non-calculated output (AI4) on the SMAI function block.
Connect the signals to the AxRADR accordingly.
For each of the analog signals, Operation = Enabled means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and triggers
1088

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

even if operation is set to Disabled. Both undervoltage and overvoltage can be used as
trigger conditions. The same applies for the current signals.
If Operation = Disabled, no waveform (samples) will be recorded and reported in graph.
However, Trip value, pre-fault and fault value will be recorded and reported. The input
channel can still be used to trig the disturbance recorder.
If Operation = Enabled, waveform (samples) will also be recorded and reported in graph.
The analog signals are presented only in the disturbance recording, but they affect the
entire disturbance report when being used as triggers.

Binary signals
Up to 128 binary signals can be selected to be handled by disturbance report. The signals
can be selected from internal logical and binary input signals. A binary signal is selected
to be recorded when:

the corresponding function block is included in the configuration


the signal is connected to the input of the function block

Each of the 128 signals can be selected as a trigger of the disturbance report (Operation =
Operation>TrigDR =Enabled). A binary signal can be selected to activate the red LED
on the local HMI (SetLED = Enabled).
The selected signals are presented in the event recorder, sequential of events and the
disturbance recording. But they affect the whole disturbance report when they are used as
triggers. The indications are also selected from these 128 signals with local HMI
IndicationMask = Show/Hide.

Trigger signals
The trigger conditions affect the entire disturbance report, except the sequential of events,
which runs continuously. As soon as at least one trigger condition is fulfilled, a complete
disturbance report is recorded. On the other hand, if no trigger condition is fulfilled, there
is no disturbance report, no indications, and so on. This implies the importance of
choosing the right signals as trigger conditions.
A trigger can be of type:

Manual trigger
Binary-signal trigger
Analog-signal trigger (over/under function)

Manual trigger
A disturbance report can be manually triggered from the local HMI, PCM600 or via
station bus (IEC 61850). When the trigger is activated, the manual trigger signal is

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1089

Section 16
Monitoring

1MRK 502 066-UUS A

generated. This feature is especially useful for testing. Refer to the operator's manual for
procedure.

Binary-signal trigger
Any binary signal state (logic one or a logic zero) can be selected to generate a trigger
(Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to generate a trigger
from a logic zero, the selected signal will not be listed in the indications list of the
disturbance report.

Analog-signal trigger
All analog signals are available for trigger purposes, no matter if they are recorded in the
disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp, OverTrigLe and
UnderTrigLe.
The check of the trigger condition is based on peak-to-peak values. When this is found, the
absolute average value of these two peak values is calculated. If the average value is above
the threshold level for an overvoltage or overcurrent trigger, this trigger is indicated with
a greater than (>) sign with the user-defined name.
If the average value is below the set threshold level for an undervoltage or undercurrent
trigger, this trigger is indicated with a less than (<) sign with its name. The procedure is
separately performed for each channel.
This method of checking the analog trigger conditions gives a function which is
insensitive to DC offset in the signal. The trip time for this initiation is typically in the
range of one cycle, 16 2/3 ms for a 60 Hz network.
All under/over trig signal information is available on the local HMI and PCM600.

Post Retrigger
Disturbance report function does not automatically respond to any new trig condition
during a recording, after all signals set as trigger signals have been reset. However, under
certain circumstances the fault condition may reoccur during the post-fault recording, for
instance by automatic reclosing to a still faulty power line.
In order to capture the new disturbance it is possible to allow retriggering (PostRetrig =
Enabled) during the post-fault time. In this case a new, complete recording will pickup
and, during a period, run in parallel with the initial recording.
When the retrig parameter is disabled (PostRetrig = Disabled), a new recording will not
pickup until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a new trig
occurs during the post-fault period and lasts longer than the proceeding recording a new
complete recording will be started.
Disturbance report function can handle maximum 3 simultaneous disturbance recordings.

1090

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.6.8

Technical data
Table 712:

DRPRDRE technical data

Function

Range or value

Accuracy

Pre-fault time

(0.059.90) s

Post-fault time

(0.110.0) s

Limit time

(0.510.0) s

Maximum number of recordings

100, first in - first out

Time tagging resolution

1 ms

See table 862

Maximum number of analog inputs

30 + 10 (external + internally
derived)

Maximum number of binary inputs

96

Maximum number of phasors in the Trip


Value recorder per recording

30

Maximum number of indications in a


disturbance report

96

Maximum number of events in the Event


recording per recording

150

Maximum number of events in the


Sequence of events

1000, first in - first out

Maximum total recording time (3.4 s


recording time and maximum number of
channels, typical value)

340 seconds (100 recordings) at


50 Hz, 280 seconds (80
recordings) at 60 Hz

Sampling rate

1 kHz at 50 Hz
1.2 kHz at 60 Hz

Recording bandwidth

(5-300) Hz

16.7

Logical signal status report BINSTATREP

16.7.1

Identification
Function description
Logical signal status report

16.7.2

IEC 61850
identification
BINSTATREP

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The Logical signal status report (BINSTATREP) function makes it possible for a SPA
master to poll signals from various other functions.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1091

Section 16
Monitoring
16.7.3

1MRK 502 066-UUS A

Function block
BINSTATREP
BLOCK
OUTPUT1
^INPUT1
OUTPUT2
^INPUT2
OUTPUT3
^INPUT3
OUTPUT4
^INPUT4
OUTPUT5
^INPUT5
OUTPUT6
^INPUT6
OUTPUT7
^INPUT7
OUTPUT8
^INPUT8
OUTPUT9
^INPUT9
OUTPUT10
^INPUT10
OUTPUT11
^INPUT11
OUTPUT12
^INPUT12
OUTPUT13
^INPUT13
OUTPUT14
^INPUT14
OUTPUT15
^INPUT15
OUTPUT16
^INPUT16
IEC09000730-1-en.vsd
IEC09000730 V1 EN

Figure 500:

16.7.4

Signals
Table 713:
Name

1092

BINSTATREP function block

BINSTATREP Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

BOOLEAN

Single status report input 1

INPUT2

BOOLEAN

Single status report input 2

INPUT3

BOOLEAN

Single status report input 3

INPUT4

BOOLEAN

Single status report input 4

INPUT5

BOOLEAN

Single status report input 5

INPUT6

BOOLEAN

Single status report input 6

INPUT7

BOOLEAN

Single status report input 7

INPUT8

BOOLEAN

Single status report input 8

INPUT9

BOOLEAN

Single status report input 9

INPUT10

BOOLEAN

Single status report input 10

INPUT11

BOOLEAN

Single status report input 11

INPUT12

BOOLEAN

Single status report input 12

INPUT13

BOOLEAN

Single status report input 13

INPUT14

BOOLEAN

Single status report input 14

INPUT15

BOOLEAN

Single status report input 15

INPUT16

BOOLEAN

Single status report input 16

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Table 714:

BINSTATREP Output signals

Name

16.7.5
Table 715:
Name
t

16.7.6

Type

Description

OUTPUT1

BOOLEAN

Logical status report output 1

OUTPUT2

BOOLEAN

Logical status report output 2

OUTPUT3

BOOLEAN

Logical status report output 3

OUTPUT4

BOOLEAN

Logical status report output 4

OUTPUT5

BOOLEAN

Logical status report output 5

OUTPUT6

BOOLEAN

Logical status report output 6

OUTPUT7

BOOLEAN

Logical status report output 7

OUTPUT8

BOOLEAN

Logical status report output 8

OUTPUT9

BOOLEAN

Logical status report output 9

OUTPUT10

BOOLEAN

Logical status report output 10

OUTPUT11

BOOLEAN

Logical status report output 11

OUTPUT12

BOOLEAN

Logical status report output 12

OUTPUT13

BOOLEAN

Logical status report output 13

OUTPUT14

BOOLEAN

Logical status report output 14

OUTPUT15

BOOLEAN

Logical status report output 15

OUTPUT16

BOOLEAN

Logical status report output 16

Settings
BINSTATREP Non group settings (basic)
Values (Range)
0.0 - 60.0

Unit

Step

Default

0.1

10.0

Description
Time delay of function

Operation principle
The Logical signal status report (BINSTATREP) function has 16 inputs and 16 outputs.
The output status follows the inputs and can be read from the local HMI or via SPA
communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1093

Section 16
Monitoring

1MRK 502 066-UUS A

INPUTn
OUTPUTn
t

t
IEC09000732-1-en.vsd

IEC09000732 V1 EN

Figure 501:

BINSTATREP logical diagram

16.8

Measured value expander block RANGE_XP

16.8.1

Identification
Function description
Measured value expander block

16.8.2

IEC 61850
identification
RANGE_XP

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and
VNMMXU), current and voltage sequence measurement functions (CMSQI and VMSQI)
and IEC 61850 generic communication I/O functions (MVGAPC) are provided with
measurement supervision functionality. All measured values can be supervised with four
settable limits: low-low limit, low limit, high limit and high-high limit. The measure value
expander block (RANGE_XP) has been introduced to enable translating the integer
output signal from the measuring functions to 5 binary signals: below low-low limit,
below low limit, normal, above high limit or above high-high limit. The output signals can
be used as conditions in the configurable logic or for alarming purpose.

1094

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.8.3

Function block
RANGE*

RANGE_XP
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC05000346-2-en.vsd

IEC05000346 V2 EN

Figure 502:

16.8.4

RANGE_XP function block

Signals
Table 716:

RANGE_XP Input signals

Name

Type

RANGE

Table 717:

INTEGER

Description
Measured value range

RANGE_XP Output signals

Name

16.8.5

Default

Type

Description

HIGHHIGH

BOOLEAN

Measured value is above high-high limit

HIGH

BOOLEAN

Measured value is between high and high-high limit

NORMAL

BOOLEAN

Measured value is between high and low limit

LOW

BOOLEAN

Measured value is between low and low-low limit

LOWLOW

BOOLEAN

Measured value is below low-low limit

Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC). The
function block converts the input integer value to five binary output signals according to
table 718.
Table 718:

Input integer value converted to binary output signals

Measured supervised
value is:
Output:
LOWLOW
LOW

below low-low between low


limit
low and low
limit

between low
and high limit

between high- above high-high


high and high limit
limit

High
High

NORMAL
HIGH
HIGHHIGH
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

High
High
High
1095

Section 16
Monitoring

1MRK 502 066-UUS A

16.9

Limit counter L4UFCNT

16.9.1

Identification

16.9.1.1

Identification
Function description
Limit counter

16.9.2

IEC 61850
identification

IEC 60617
identification

L4UFCNT

ANSI/IEEE C37.2
device number
-

Functionality
The 12 Up limit counter L4UFCNT provides a settable counter with four independent
limits where the number of positive and/or negative sides on the input signal are counted
against the setting values for limits. The output for each limit is activated when the counted
value reaches that limit.
Overflow indication is included for each up-counter.

16.9.3

Operation principle
Limit counter (L4UFCNT) counts the number of positive and/or negative sides on the
binary input signal depending on the function settings. L4UFCNT also checks if the
accumulated value is equal or greater than any of its four settable limits. The four limit
outputs will be activated relatively on reach of each limit and remain activated until the
reset of the function. Moreover, the content of L4UFCNT is stored in flash memory and
will not be lost at an auxiliary power interruption.

16.9.3.1

Design
Figure 503 illustrates the general logic diagram of the function.

1096

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

BLOCK
INPUT

Operation
Counter

RESET

VALUE
Overflow
Detection

CountType

OVERFLOW

OnMaxValue
LIMIT1 4

Limit
Check

MaxValue

CounterLimit1...4
ERROR

Error
Detection

InitialValue

IEC12000625_1_en.vsd
IEC12000625 V1 EN

Figure 503:

Logic diagram

The counter can be initialized to count from a settable non-zero value after reset of the
function. The function has also a maximum counted value check. The three possibilities
after reaching the maximum counted value are:

Stops counting and activates a steady overflow indication for the next count
Rolls over to zero and activates a steady overflow indication for the next count
Rolls over to zero and activates a pulsed overflow indication for the next count

The pulsed overflow output lasts up to the first count after rolling over to zero, as
illustrated in figure 504.

Overflow indication
Actual value

... Max value -1

Max value

Counted value

... Max value -1

Max value

Max value +1
0

Max value +2
1

Max value +3 ...


2

...

IEC12000626_1_en.vsd
IEC12000626 V1 EN

Figure 504:

Overflow indication when OnMaxValue is set to rollover pulsed

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1097

Section 16
Monitoring

1MRK 502 066-UUS A

The Error output is activated as an indicator of setting the counter limits and/or initial
value setting(s) greater than the maximum value. The counter stops counting the input and
all the outputs except the error output remains at zero state. The error condition remains
until the correct settings for counter limits and/or initial value setting(s) are applied.
The function can be blocked through a block input. During the block time, input is not
counted and outputs remain in their previous states. However, the counter can be
initialized after reset of the function. In this case the outputs remain in their initial states
until the release of the block input.

16.9.3.2

Reporting
The content of the counter can be read on the local HMI.
Reset of the counter can be performed from the local HMI or via a binary input.
Reading of content and resetting of the function can also be performed remotely, for
example from a IEC 61850 client. The value can also be presented as a measurement on
the local HMI graphical display.

16.9.4

Function block
L4UFCNT
BLOCK
INPUT
RESET

ERROR
OVERFLOW
LIMIT1
LIMIT2
LIMIT3
LIMIT4
VALUE
IEC12000029-1-en.vsd

IEC12000029 V1 EN

Figure 505:

16.9.5

Signals
Table 719:
Name

1098

L4UFCNT function block

L4UFCNT Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT

BOOLEAN

Input for counter

RESET

BOOLEAN

Reset of function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

Table 720:

L4UFCNT Output signals

Name

16.9.6
Table 721:
Name

Type

Description

ERROR

BOOLEAN

Error indication on counter limit and/or initial value


settings

OVERFLOW

BOOLEAN

Overflow indication on count of greater than MaxValue

LIMIT1

BOOLEAN

Counted value is larger than or equal to CounterLimit1

LIMIT2

BOOLEAN

Counted value is larger than or equal to CounterLimit2

LIMIT3

BOOLEAN

Counted value is larger than or equal to CounterLimit3

LIMIT4

BOOLEAN

Counted value is larger than or equal to CounterLimit4

VALUE

INTEGER

Counted value

Settings
L4UFCNT Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
On

Disabled

Operation Disabled/Enabled

CountType

Positive edge
Negative edge
Both edges

Positive edge

Select counting on positive and/or negative


sides

CounterLimit1

1 - 65535

100

Value of the first limit

CounterLimit2

1 - 65535

200

Value of the second limit

CounterLimit3

1 - 65535

300

Value of the third limit

CounterLimit4

1 - 65535

400

Value of the fourth limit

MaxValue

1 - 65535

500

Maximum count value

OnMaxValue

Stop
Rollover Steady
Rollover Pulsed

Stop

Select if counter stops or rolls over after


reaching maxValue with steady or pulsed
overflow flag

InitialValue

0 - 65535

Initial count value after reset of the function

16.9.7

Monitored data
Table 722:
Name
VALUE

L4UFCNT Monitored data


Type
INTEGER

Values (Range)
-

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Unit
-

Description
Counted value

1099

Section 16
Monitoring
16.9.8

1MRK 502 066-UUS A

Technical data
Table 723:

L4UFCNTtechnical data

Function

Range or value

Accuracy

Counter value

0-65535

Max. count up speed

30 pulses/s (50% duty cycle)

16.10

Running hour-meter TEILGAPC

16.10.1

Identification

16.10.2

Function Description

IEC 61850
identification

Running hour-meter

TEILGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2 device


number
-

Functionality
The Running hour-meter (TEILGAPC) function is a function that accumulates the elapsed
time when a given binary signal has been high, see also figure 506.
BLOCK
RESET
IN
ADDTIME

ACC_HOUR

Time Accumulation
with Retain

ACC_DAY

tAddToTime

q-1

99 999.9 h

a>b

tWarning

a>b

tAlarm

q-1 = unit delay

a>b

&

&

&

OVERFLOW

WARNING

ALARM

IEC15000321-1-en.vsd

IEC15000321 V1 EN

Figure 506:

TEILGAPC logics

The main features of TEILGAPC are:

1100

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

16.10.3

Applicable to very long time accumulation ( 99999.9 hours)


Supervision of limit transgression conditions and rollover/overflow
Possibility to define a warning and alarm with the resolution of 0.1 hours
Retain any saved accumulation value at a restart
Possibilities for blocking and reset
Possibility for manual addition of accumulated time
Reporting of the accumulated time

Function block

TEILGAPC

BLOCK
IN
ADDTIME
RESET

ALARM
WARNING
OVERFLOW
ACC_HOUR
ACC_DAY
IEC15000323.vsdx

IEC15000323 V1 EN

Figure 507:

16.10.4

TEILGAPC function block

Signals
Table 724:
Name

TEILGAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Freeze the accumulation and block the outputs

IN

BOOLEAN

The input signal that is used to measure the elapsed


time, when its value is high

ADDTIME

BOOLEAN

Add time to the accumulation

RESET

BOOLEAN

Reset accumulated time

Table 725:
Name

TEILGAPC Output signals


Type

Description

ALARM

BOOLEAN

Indicator that accumulated time has reached alarm limit

WARNING

BOOLEAN

Indicator that accumulated time has reached warning


limit

OVERFLOW

BOOLEAN

Indicator that accumulated time has reached overflow


limit

ACC_HOUR

REAL

Accumulated time in hours

ACC_DAY

REAL

Accumulated time in days

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1101

Section 16
Monitoring
16.10.5
Table 726:
Name

1MRK 502 066-UUS A

Settings
TEILGAPC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

tAlarm

1.0 - 99999.9

Hour

0.1

90000.0

Time limit for alarm supervision

tWarning

1.0 - 99999.9

Hour

0.1

50000.0

Time limit for warning supervision

tAddToTime

0.0 - 99999.9

Hour

0.1

0.0

Time to add to the accumulation

16.10.6

Operation principle
Figure 508 describes the simplified logic of the function.

Loop Delay

tWarning

OVERFLOW

tAlarm
Transgression Supervision
Plus Retain

WARNING
ALARM

BLOCK
RESET

ACC_HOUR

Time Accumulation

IN
ACC_DAY

ADDTIME
tAddToTime

Loop Delay

IEC15000322.vsd

IEC15000322 V1 EN

Figure 508:

TEILGAPC Simplified logic

TEILGAPC main functionalities

1102

IN: Accumulation of the elapsed time when input IN is high

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 16
Monitoring

1MRK 502 066-UUS A

RESET: Reset of the accumulated value. Consequently all other outputs are also reset

the amount of time to be added is defined by a setting tAddToTime


time is added through activation of input ADDTIME or from LHMI or with
IEC61850 command

BLOCK: Freeze the accumulation and block/reset the other outputs

independent of the input IN value


reset the value of the nonvolatile memory to zero
reset can be made by activation of input RESET or from LHMI or with
IEC61850 command

ADDTIME: Manually add time to the currently accumulated time

applicable to very long time accumulation (99999.9 hours)


output ACC_HOUR presents accumulated value in hours and ACC_DAY
presents accumulated value in days
accumulated value is retained in a non-volatile memory
any retained value is used as initiation value for the integration following by a
restart

independent of the input IN value


BLOCK request overrides RESET request

Monitor and report the conditions of limit transgression

overflow if output ACC_HOUR > 99 999.9 hours


alarm if output ACC_HOUR > tAlarm
warning if output ACC_HOUR > tWarning

The ACC_HOUR output represents the accumulated time in hours and the ACC_DAY
output represents the accumulated time in days.
tAlarm and tWarning are user settable time limit parameters in hours. They are also
independent of each other, that is, there is no check if tAlarm > tWarning.
tAddToTime is a user settable time parameter in hours.
tAlarm, tWarning and tAddToTime are possible to be defined with a resolution of 0.1 hours
(6 minutes).
The limit for the overflow supervision is fixed at 99999.9 hours. The outputs will reset and
the accumulated time will reset and pickup from zero if an overflow occurs.

16.10.6.1

Operation accuracy
The accuracy of TEILGAPC depends on essentially two factors

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1103

Section 16
Monitoring

1MRK 502 066-UUS A

the pulse length


the number of pulses, that is, the number of rising and falling flank pairs

In principle, more pulses may lead to reduced accuracy.

16.10.6.2

Memory storage
The value of the accumulated time is retained in a non-volatile memory,

at every falling edge of the input IN


at every even 12 hours, after a rising edge of the input IN
after a manual addition of time

Consequently in case of a power failure, there is a risk of losing the difference in time
between actual time and last time stored in the non-volatile memory.

16.10.7

Technical data
Table 727:

TEILGAPC Technical data


Function

1104

Range or value

Accuracy

Time limit for alarm supervision,


tAlarm

(0 - 99999.9) hours

0.1% of set value

Time limit for warning supervision,


tWarning

(0 - 99999.9) hours

0.1% of set value

Time limit for overflow supervision

Fixed to 99999.9 hours

0.1%

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 17
Metering

1MRK 502 066-UUS A

Section 17

Metering

17.1

Pulse-counter logic PCFCNT

17.1.1

Identification
Function description
Pulse-counter logic

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number
-

PCFCNT

S00947 V1 EN

17.1.2

Functionality
Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module and then read by
the PCFCNT function. A scaled service value is available over the station bus. The special
Binary input module with enhanced pulse counting capabilities must be ordered to
achieve this functionality.

17.1.3

Function block
PCFCNT
BLOCK
READ_VAL
BI_PULSE*
RS_CNT

INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL
IEC14000043-1-en.vsd

IEC09000335 V3 EN

Figure 509:

PCFCNT function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1105

Section 17
Metering
17.1.4

1MRK 502 066-UUS A

Signals
Table 728:

PCFCNT Input signals

Name

Type

Block of function

READ_VAL

BOOLEAN

Initiates an additional pulse counter reading

BI_PULSE

BOOLEAN

Connect binary input channel for metering

RS_CNT

BOOLEAN

Resets pulse counter value

PCFCNT Output signals

Name

Table 730:
Name

Description

BOOLEAN

Table 729:

17.1.5

Default

BLOCK

Type

Description

INVALID

BOOLEAN

The pulse counter value is invalid

RESTART

BOOLEAN

The reported value does not comprise a complete


integration cycle

BLOCKED

BOOLEAN

The pulse counter function is blocked

NEW_VAL

BOOLEAN

A new pulse counter value is generated

SCAL_VAL

REAL

Scaled value with time and status information

Settings
PCFCNT Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

EventMask

NoEvents
ReportEvents

NoEvents

Report mask for analog events from pulse


counter

CountCriteria

Disabled
RisingEdge
Falling edge
OnChange

RisingEdge

Pulse counter criteria

Scale

1.000 - 90000.000

0.001

1.000

Scaling value for SCAL_VAL output to unit per


counted value

Quantity

Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy

Count

Measured quantity for SCAL_VAL output

tReporting

0 - 3600

60

Cycle time for reporting of counter value

1106

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 17
Metering

1MRK 502 066-UUS A

17.1.6

Monitored data
Table 731:
Name

17.1.7

PCFCNT Monitored data


Type

Values (Range)

Unit

Description

CNT_VAL

INTEGER

Actual pulse counter value

SCAL_VAL

REAL

Scaled value with time and


status information

Operation principle
The registration of pulses is done for positive transitions (0->1) on one of the 16 binary
input channels located on the Binary Input Module (BIM). Pulse counter values are sent
to the station HMI with predefined cyclicity without reset.
The reporting time period can be set in the range from 1 second to 60 minutes and is
synchronized with absolute system time. Interrogation of additional pulse counter values
can be done with a command (intermediate reading) for a single counter. All active
counters can also be read by the LON General Interrogation command (GI) or IEC 61850.
Pulse-counter logic (PCFCNT) function in the IED supports unidirectional incremental
counters. That means only positive values are possible. The counter uses a 32 bit format,
that is, the reported value is a 32-bit, signed integer with a range 0...+2147483647. The
counter is reset at initialization of the IED.
The reported value to station HMI over the station bus contains Identity, Scaled Value
(pulse count x scale), Time, and Pulse Counter Quality. The Pulse Counter Quality
consists of:

Invalid (board hardware error or configuration error)


Wrapped around
Blocked
Adjusted

The transmission of the counter value by SPA can be done as a service value, that is, the
value frozen in the last integration cycle is read by the station HMI from the database.
PCFCNT updates the value in the database when an integration cycle is finished and
activates the NEW_VAL signal in the function block. This signal can be connected to an
Event function block, be time tagged, and transmitted to the station HMI. This time
corresponds to the time when the value was frozen by the function.
The pulse-counter logic function requires a binary input card, BIMp, that
is specially adapted to the pulse-counter logic function.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1107

Section 17
Metering

1MRK 502 066-UUS A

Figure 510 shows the pulse-counter logic function block with connections of the inputs
and outputs.
SingleCmdFunc
OUTx
SingleCmdFunc
OUTx
I/Omodule

Pulse
INPUT OUT
Pulse length >1s
Reset counter

PulseCounter
BLOCK
INVALID
RESTART
READ_VAL
BLOCKED
NEW_VAL
BI_PULSE
RS_CNT
NAME
SCAL_VAL

SMS settings
1.Operation = Off/On
2.tReporting = 0s...60min
3.Event Mask = No Events/Report Events
4.Scale = 1-90000

EVENT
INPUT1
INPUT2
INPUT3
INPUT4

IEC EVENT

Database
Pulse counter value:
0...2147483647
en05000744_ansi.vsd

ANSI05000744 V1 EN

Figure 510:

Overview of the pulse-counter logic function

The BLOCK and READ_VAL inputs can be connected to Single Command logics, which
are intended to be controlled either from the station HMI or/and the local HMI. As long as
the BLOCK signal is set, the pulse counter is blocked. The signal connected to
READ_VAL performs one additional reading per positive flank. The signal must be a
pulse with a length >1 second.
The BI_PULSE input is connected to the used input of the function block for the Binary
Input Module (BIM).
The RS_CNT input is used for resetting the counter.
Each pulse-counter logic function block has four binary output signals that can be
connected to an Event function block for event recording: INVALID, RESTART,
BLOCKED and NEW_VAL. The SCAL_VAL signal can be connected to the IEC Event
function block.
The INVALID signal is a steady signal and is set if the Binary Input Module, where the
pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED pickup, in the
first message after deblocking, and after the counter has wrapped around during last
integration cycle.

1108

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 17
Metering

1MRK 502 066-UUS A

The BLOCKED signal is a steady signal and is set when the counter is blocked. There are
two reasons why the counter is blocked:

The BLOCK input is set, or


The Binary Input Module, where the counter input is situated, is inoperative.

The NEW_VAL signal is a pulse signal. The signal is set if the counter value was updated
since last report.
Note, the pulse is short, one cycle.

The SCAL_VAL signal consists of scaled value (according to parameter Scale), time and
status information.

17.1.8

Technical data
Table 732:

PCFCNT technical data

Function

Setting range

Accuracy

Input frequency

See Binary Input Module (BIM)

Cycle time for report of counter


value

(13600) s

17.2

Function for energy calculation and demand handling


ETPMMTR

17.2.1

Identification
Function description
Function for energy calculation and
demand handling

17.2.2

IEC 61850
identification
ETPMMTR

IEC 60617
identification
W_Varh

ANSI/IEEE C37.2
device number
-

Functionality
Measurements function block (CVMMXN) can be used to measure active as well as
reactive power values. Function for energy calculation and demand handling
(ETPMMTR) uses measured active and reactive power as input and calculates the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1109

Section 17
Metering

1MRK 502 066-UUS A

accumulated active and reactive energy pulses, in forward and reverse direction. Energy
values can be read or generated as pulses. Maximum demand power values are also
calculated by the function. This function includes zero point clamping to remove noise
from the input signal. As output of this function: periodic energy calculations, integration
of energy values, calculation of energy pulses, alarm signals for limit violation of energy
values and maximum power demand, can be found.
The values of active and reactive energies are calculated from the input power values by
integrating them over a selected time tEnergy. The integration of active and reactive
energy values will happen in both forward and reverse directions. These energy values are
available as output signals and also as pulse outputs. Integration of energy values can be
controlled by inputs (STARTACC and STOPACC) and EnaAcc setting and it can be reset
to initial values with RSTACC input.
The maximum demand for active and reactive powers are calculated for the set time
interval tEnergy and these values are updated every minute through output channels. The
active and reactive maximum power demand values are calculated for both forward and
reverse direction and these values can be reset with RSTDMD input.

17.2.3

Function block
ETPMMTR
P*
ACCINPRG
Q*
EAFPULSE
STARTACC
EARPULSE
STOPACC
ERFPULSE
RSTACC
ERRPULSE
RSTDMD
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
IEC14000019-1-en.vsd
IEC14000019 V1 EN

Figure 511:

1110

ETPMMTR function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 17
Metering

1MRK 502 066-UUS A

17.2.4

Signals
Table 733:
Name

ETPMMTR Input signals


Type

Default

Description

REAL

Measured active power

REAL

Measured reactive power

STARTACC

BOOLEAN

Start to accumulate energy values

STOPACC

BOOLEAN

Stop accumulating energy values

RSTACC

BOOLEAN

Reset of accumulated enery reading

RSTDMD

BOOLEAN

Reset of maximum demand reading

Table 734:
Name

ETPMMTR Output signals


Type

Description

ACCINPRG

BOOLEAN

Accumulation of energy values in progress

EAFPULSE

BOOLEAN

Accumulated forward active energy pulse

EARPULSE

BOOLEAN

Accumulated reverse active energy pulse

ERFPULSE

BOOLEAN

Accumulated forward reactive energy pulse

ERRPULSE

BOOLEAN

Accumulated reverse reactive energy pulse

EAFALM

BOOLEAN

Alarm for active forward energy exceed limit in set


interval

EARALM

BOOLEAN

Alarm for active reverse energy exceed limit in set


interval

ERFALM

BOOLEAN

Alarm for reactive forward energy exceed limit in set


interval

ERRALM

BOOLEAN

Alarm for reactive reverse energy exceed limit in set


interval

EAFACC

REAL

Accumulated forward active energy value in Ws

EARACC

REAL

Accumulated reverse active energy value in Ws

ERFACC

REAL

Accumulated forward reactive energy value in VArS

ERRACC

REAL

Accumulated reverse reactive energy value in VArS

MAXPAFD

REAL

Maximum forward active power demand value for set


interval

MAXPARD

REAL

Maximum reverse active power demand value for set


interval

MAXPRFD

REAL

Maximum forward reactive power demand value for set


interval

MAXPRRD

REAL

Maximum reactive power demand value in reverse


direction

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1111

Section 17
Metering

1MRK 502 066-UUS A

17.2.5
Table 735:
Name

Settings
ETPMMTR Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

EnaAcc

Disabled
Enabled

Disabled

Activate the accumulation of energy values

tEnergy

1 Minute
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes

1 Minute

Time interval for energy calculation

tEnergyOnPls

0.100 - 60.000

0.001

1.000

Energy accumulated pulse ON time in secs

tEnergyOffPls

0.100 - 60.000

0.001

0.500

Energy accumulated pulse OFF time in secs

EAFAccPlsQty

0.001 - 10000.000

MWh

0.001

100.000

Pulse quantity for active forward accumulated


energy value

EARAccPlsQty

0.001 - 10000.000

MWh

0.001

100.000

Pulse quantity for active reverse accumulated


energy value

ERFAccPlsQty

0.001 - 10000.000

MVArh

0.001

100.000

Pulse quantity for reactive forward


accumulated energy value

ERRAccPlsQty

0.001 - 10000.000

MVArh

0.001

100.000

Pulse quantity for reactive reverse


accumulated energy value

Table 736:
Name

ETPMMTR Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

EALim

0.001 10000000000.000

MWh

0.001

1000000.000

Active energy limit

ERLim

0.001 10000000000.000

MVArh

0.001

1000.000

Reactive energy limit

EnZeroClamp

Disabled
Enabled

Enabled

Enable of zero point clamping detection


function

LevZeroClampP

0.001 - 10000.000

MW

0.001

10.000

Zero point clamping level at active Power

LevZeroClampQ

0.001 - 10000.000

MVAr

0.001

10.000

Zero point clamping level at reactive Power

DirEnergyAct

Forward
Reverse

Forward

Direction of active energy flow Forward/


Reverse

DirEnergyReac

Forward
Reverse

Forward

Direction of reactive energy flow Forward/


Reverse

EAFPrestVal

0.000 100000000.000

MWh

0.001

0.000

Preset Initial value for forward active energy

Table continues on next page

1112

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 17
Metering

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

EARPrestVal

0.000 100000000.000

MWh

0.001

0.000

Preset Initial value for reverse active energy

ERFPresetVal

0.000 100000000.000

MVArh

0.001

0.000

Preset Initial value for forward reactive energy

ERRPresetVal

0.000 100000000.000

MVArh

0.001

0.000

Preset Initial value for reverse reactive energy

17.2.6

Monitored data
Table 737:
Name

17.2.7

ETPMMTR Monitored data


Type

Values (Range)

Unit

Description

EAFACC

REAL

MWh

Accumulated forward active


energy value in Ws

EARACC

REAL

MWh

Accumulated reverse active


energy value in Ws

ERFACC

REAL

MVArh

Accumulated forward reactive


energy value in VArS

ERRACC

REAL

MVArh

Accumulated reverse reactive


energy value in VArS

MAXPAFD

REAL

MW

Maximum forward active


power demand value for set
interval

MAXPARD

REAL

MW

Maximum reverse active


power demand value for set
interval

MAXPRFD

REAL

MVAr

Maximum forward reactive


power demand value for set
interval

MAXPRRD

REAL

MVAr

Maximum reactive power


demand value in reverse
direction

Operation principle
The instantaneous output values of active and reactive power from the Measurements
function CVMMXN are used and integrated over a selected time tEnergy to measure the
integrated energy. Figure 512 shows the overall functionality of the energy calculation
and demand handling function ETPMMTR.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1113

Section 17
Metering

1MRK 502 066-UUS A

MAXPAFD

RSTDMD

MAXPARD
MAXPRFD

Zero Clamping
Detection

MAXPRRD

Maximum Power
Demand Calculation

EAFALM
EARALM
ERFALM
ERRALM

ACCINPRG
EAFPULSE
EARPULSE
ERFPULSE

Energy Accumulation
Calculation

STARTACC

ERRPULSE
EAFACC
EARACC

STOPACC

ERFACC
ERRACC

RSTACC

IEC13000185-2-en.vsd
IEC13000185 V2 EN

Figure 512:

ETPMMTR Functional overview logical diagram

The integration of energy values is enabled by the setting EnaAcc and controlled by the
STARTACC and STOPACC inputs. If the integration is in progress, the output ACCINPRG
is high. Otherwise, it is low. Figure 513 shows the logic of the ACCINPRG output.
ACCINPRG is active when the STARTACC input is active and the EnaAcc setting is
enabled. When the RSTACC input is in the active state, the output ACCINPRG is low even
if the integration of energy is enabled. ACCINPRG is deactivated by activating the
STOPACC input.
STOPACC

FALSE
STARTACC

&

EnaAcc

&

ACCINPRG

q-1
RSTACC
q-1 = unit delay

IEC13000186-4-en.vsd

IEC13000186 V4 EN

Figure 513:

ACCINPRG Logic diagram

The accumulated energy values (in MWh and MVArh) are available as service values and
also as pulsed output depending on the ExxAccPlsQty setting, which can be connected to
a pulse counter. Accumulated energy outputs are available for forward as well as reverse
direction. The accumulated energy values can be reset to initial accumulated energy
values (ExxPrestVal) from the local HMI reset menu or with the input signal RSTACC.

1114

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 17
Metering

1MRK 502 066-UUS A

Figure 514 shows the logic for integration of energy in active forward direction. Similarly,
the integration of energy in active reverse, reactive forward and reactive reverse is done.
RSTACC

EAFPrestVal
ACCINPRG

P* (ACTIVE FORWARD)
X

60.0

T
T

EAFACC

&

q-1
T

EALim
-1

a
b

0.0

a>b

q-1 = unit delay

IEC13000187-4-en.vsd

IEC13000187 V4 EN

Figure 514:

Logic for integration of active forward energy

The energy pulses generated by using internally calculated accumulated energy values
and energy per pulse (ExxAccPlsQty) setting. The accumulated energy values are divided
by the energy-per-pulse value to get the number of pulses. The number of pulses can be
reset to zero by activating RSTACC input or by using the local HMI reset menu. The pulse
on and off time duration is set by the settings tEnergyOnPls and tEnergyOffPls. Figure
515 shows the logic for pulse output generation for the integrated energy in the active
forward direction. Similarly, the pulse generation for integrated energy in the active
reverse, reactive forward and reactive reverse is done.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1115

Section 17
Metering

1MRK 502 066-UUS A

tEnergyOffPls
EAFACC
a

EALim

Counter
CU
CV

a>b

q-1

Rst
R

tOff
t

q-1
0

T
a
b

EAFAccPlsQty

a>b

TP

EAFPULSE

0
Counter
CU
CV

RSTACC

Rst

q-1
tEnergyOnPls
q-1 = unit delay

IEC13000188-4-en.vsd

IEC13000188 V4 EN

Figure 515:

Logic for pulse generation of integrated active forward energy

The maximum demand values for active and reactive power are calculated for the set time
interval tEnergy. The maximum values are updated every minute and stored in a register
available over communication and from outputs MAXPAFD, MAXPARD, MAXPRFD and
MAXPRRD for the active and reactive power forward and reverse direction. When the
RSTDMD input is active from the local HMI reset menu, these outputs are reset to zero. The
energy alarm is activated once the periodic energy value crosses the energy limit ExLim.
Figure 516 shows the logic of alarm for active forward energy exceeds limit and
Maximum forward active power demand value. Similarly, the maximum power
calculation and energy alarm outputs in the active reverse, reactive forward and reactive
reverse is implemented.
P (ACTIVE FORWARD)

tEnergy

Average Power
Calculation

EAFALM

a>b

EALim
RSTMAXD

0.0
MAX

q-1 = unit delay

MAXPAFD

q-1
IEC13000189-4-en.vsd

IEC13000189 V4 EN

Figure 516:

1116

Logic for maximum power demand calculation and energy alarm

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 17
Metering

1MRK 502 066-UUS A

17.2.8

Technical data

17.2.8.1

Technical data
Table 738:
Function
Energy metering

Range or value
MWh Export/Import, MVarh
Export/Import

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Accuracy
Input from MMXU. No extra error
at steady load

1117

1118

Section 18
Station communication

1MRK 502 066-UUS A

Section 18

Station communication

18.1

Communication protocols
Each IED is provided with a communication interface, enabling it to connect to one or
many substation level systems or equipment, either on the Substation Automation (SA)
bus or Substation Monitoring (SM) bus.
Available communication protocols are:

IEC 61850-8-1 communication protocol


IEC 61850-9-2LE communication protocol
LON communication protocol
SPA or IEC 60870-5-103 communication protocol
DNP3.0 communication protocol

Several protocols can be combined in the same IED.

18.2

Communication protocol diagnostics


Status of the protocols can be viewed in the LHMI under Main menu/Diagnostics/IED
status/Protocol diagnostics. The diagnostic values are:
Diagnostic value

Description

Off

Protocol is turned off

Error

An error has occured, refer to event list for more


information

Warning

Configuration inconsistency. Unable to locate data


point.

Ready

Protocol is ready

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1119

Section 18
Station communication

1MRK 502 066-UUS A

IEC15000400-1-en.vsd
IEC15000400 V1 EN

Figure 517:

18.3

Protocol diagnostic screen in LHMI

DNP3 protocol
DNP3 (Distributed Network Protocol) is a set of communications protocols used to
communicate data between components in process automation systems. For a detailed
description of the DNP3 protocol, see the DNP3 Communication protocol manual.

1120

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.4

IEC 61850-8-1 communication protocol

18.4.1

Communication interfaces and protocols


Table 739:

Supported station communication interfaces and protocols

Protocol

Ethernet
100BASE-FX (ST
connector)

Serial
Glass fibre (ST connector)

EIA-485

IEC 6185081

DNP3

IEC 60870-5-103

= Supported

When double Ethernet ports are activated, make sure that the two ports are
connected to different subnets. For example: Port 1 has IP-address
138.227.102.10 with subnet mask 255.255.255.0 and port 2 has IPaddress 138.227.103.10 with subnet mask 255.255.255.0

18.4.2
Table 740:

Settings
IEC61850-8-1 Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PortSelGOOSE

Front
LANAB
LANCD

LANAB

Port selection for GOOSE communication

PortSelMMS

Front
LANAB
LANCD
Any

Any

Port selection for MMS communication

ProtocolEdition

Ed 1
Ed 2

Ed 1

Protocol Edition

RemoteModControl

Disabled
Maintenance
All levels

Disabled

Remote Mode Control

AllowGOOSESimulation

No
Yes

No

Allow enabling of GOOSE Simulation

IEC61850BufTimEnable

Disabled
Enabled

Enabled

Enable BRC buf time behavior

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1121

Section 18
Station communication
18.4.3

1MRK 502 066-UUS A

Technical data
Table 741:

Communication protocols

Function

Value

Protocol

IEC 61850-8-1

Communication speed for the IEDs

100BASE-FX

Protocol

IEC 608705103

Communication speed for the IEDs

9600 or 19200 Bd

Protocol

DNP3.0

Communication speed for the IEDs

30019200 Bd

Protocol

TCP/IP, Ethernet

Communication speed for the IEDs

100 Mbit/s

18.4.4

Generic communication function for Single Point indication


SPGAPC, SP16GAPC

18.4.4.1

Functionality
Generic communication function for Single Point indication SPGAPC is used to send one
single logical signal to other systems or equipment in the substation.

18.4.4.2

Function block
SPGAPC
BLOCK
^IN
IEC14000021-1-en.vsd
IEC14000021 V1 EN

Figure 518:

1122

SPGAPC function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

SP16GAPC
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
IEC14000020-1-en.vsd
IEC14000020 V1 EN

Figure 519:

18.4.4.3

SP16GAPC function block

Signals
Table 742:
Name

SPGAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN

BOOLEAN

Input status

Table 743:
Name

SP16GAPC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN1

BOOLEAN

Input 1 status

IN2

BOOLEAN

Input 2 status

IN3

BOOLEAN

Input 3 status

IN4

BOOLEAN

Input 4 status

IN5

BOOLEAN

Input 5 status

IN6

BOOLEAN

Input 6 status

IN7

BOOLEAN

Input 7 status

IN8

BOOLEAN

Input 8 status

IN9

BOOLEAN

Input 9 status

IN10

BOOLEAN

Input 10 status

IN11

BOOLEAN

Input 11 status

IN12

BOOLEAN

Input 12 status

IN13

BOOLEAN

Input 13 status

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1123

Section 18
Station communication

1MRK 502 066-UUS A

Name

18.4.4.4

Type

Default

Description

IN14

BOOLEAN

Input 14 status

IN15

BOOLEAN

Input 15 status

IN16

BOOLEAN

Input 16 status

Settings
The function does not have any parameters available in the local HMI or PCM600.

18.4.4.5

Monitored data
Table 744:
Name
OUT

Table 745:
Name

SPGAPC Monitored data


Type
GROUP
SIGNAL

Values (Range)
-

Unit
-

Description
Output status

SP16GAPC Monitored data


Type

Values (Range)

Unit

Description

OUT1

GROUP
SIGNAL

Output 1 status

OUT2

GROUP
SIGNAL

Output 2 status

OUT3

GROUP
SIGNAL

Output 3 status

OUT4

GROUP
SIGNAL

Output 4 status

OUT5

GROUP
SIGNAL

Output 5 status

OUT6

GROUP
SIGNAL

Output 6 status

OUT7

GROUP
SIGNAL

Output 7 status

OUT8

GROUP
SIGNAL

Output 8 status

OUT9

GROUP
SIGNAL

Output 9 status

OUT10

GROUP
SIGNAL

Output 10 status

OUT11

GROUP
SIGNAL

Output 11 status

OUT12

GROUP
SIGNAL

Output 12 status

Table continues on next page


1124

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

18.4.4.6

Type

Values (Range)

Unit

Description

OUT13

GROUP
SIGNAL

Output 13 status

OUT14

GROUP
SIGNAL

Output 14 status

OUT15

GROUP
SIGNAL

Output 15 status

OUT16

GROUP
SIGNAL

Output 16 status

OUTOR

GROUP
SIGNAL

Output status logic OR gate for


input 1 to 16

Operation principle
Upon receiving a signal at its input, Generic communication function for Single Point
indication (SPGAPC) function sends the signal over IEC 61850-8-1 to the equipment or
system that requests this signal. To get the signal, PCM600 must be used to define which
function block in which equipment or system should receive this information.

18.4.5

Generic communication function for Measured Value MVGAPC

18.4.5.1

Functionality
Generic communication function for Measured Value MVGAPC function is used to send
the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an analog
value and to permit measurement supervision on that value.

18.4.5.2

Function block
MVGAPC
BLOCK
^IN

^VALUE
RANGE
IEC14000022-1-en.vsd

IEC14000022 V1 EN

Figure 520:

MVGAPC function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1125

Section 18
Station communication
18.4.5.3

1MRK 502 066-UUS A

Signals
Table 746:

MVGAPC Input signals

Name

Type

Block of function

IN

REAL

Analog input value

MVGAPC Output signals

Name

Table 748:
Name

Description

BOOLEAN

Table 747:

18.4.5.4

Default

BLOCK

Type

Description

VALUE

REAL

Magnitude of deadband value

RANGE

INTEGER

Range

Settings
MVGAPC Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

BasePrefix

micro
milli
unit
kilo
Mega
Giga
Tera

unit

Base prefix (multiplication factor)

MV db

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of range, Int


Db: In %s

MV zeroDb

0 - 100000

m%

500

Zero point clamping in 0.001% of range

MV hhLim

-5000.00 - 5000.00

xBase

0.01

900.00

High High limit multiplied with the base prefix


(multiplication factor)

MV hLim

-5000.00 - 5000.00

xBase

0.01

800.00

High limit multiplied with the base prefix


(multiplication factor)

MV lLim

-5000.00 - 5000.00

xBase

0.01

-800.00

Low limit multiplied with the base prefix


(multiplication factor)

MV llLim

-5000.00 - 5000.00

xBase

0.01

-900.00

Low Low limit multiplied with the base prefix


(multiplication factor)

MV min

-5000.00 - 5000.00

xBase

0.01

-1000.00

Minimum value multiplied with the base prefix


(multiplication factor)

MV max

-5000.00 - 5000.00

xBase

0.01

1000.00

Maximum value multiplied with the base prefix


(multiplication factor)

MV dbType

Cyclic
Dead band
Int deadband

Dead band

Reporting type

MV limHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common for all


limits)

1126

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.4.5.5

Monitored data
Table 749:

MVGAPC Monitored data

Name

18.4.5.6

Type

Values (Range)

Unit

Description

VALUE

REAL

Magnitude of deadband value

RANGE

INTEGER

1=High
2=Low
3=High-High
4=Low-Low
0=Normal

Range

Operation principle
Upon receiving an analog signal at its input, Generic communication function for
Measured Value (MVGAPC) will give the instantaneous value of the signal and the range,
as output values. In the same time, it will send over IEC 61850-8-1 the value, to other IEC
61850 clients in the substation.

18.4.6

IEC 61850-8-1 redundant station bus communication


Function description

18.4.6.1

LHMI and ACT


identification

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Parallel Redundancy
Protocol Status

PRPSTATUS

RCHLCCH

Duo driver
configuration

PRP

Functionality
Redundant station bus communication according to IEC 62439-3 Edition 1 and IEC
62439-3 Edition 2 parallel redundancy protocol (PRP) are available as options when
ordering IEDs. Redundant station bus communication according to IEC 62439-3 uses
both port AB and port CD on the OEM module.

18.4.6.2

Function block
PRPSTATUS
PRP-A LINK
PRP-A VALID
PRP-B LINK
PRP-B VALID
IEC09000757.vsd
IEC09000757 V2 EN

Figure 521:

PRPSTATUS function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1127

Section 18
Station communication
18.4.6.3

1MRK 502 066-UUS A

Signals
Table 750:

PRPSTATUS Output signals

Name

18.4.6.4
Table 751:
Name

Type

Description

PRP-A LINK

BOOLEAN

PRP-A Link Status

PRP-A VALID

BOOLEAN

PRP-A Link Valid

PRP-B LINK

BOOLEAN

PRP-B Link Status

PRP-B VALID

BOOLEAN

PRP-B Link Valid

Settings
PRP Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation Disabled/Enabled

PRPMode

PRP-0
PRP-1

PRP-1

PRP Mode

IPAddress

0 - 18

IP
Address

192.168.7.10

IP-Address

IPMask

0 - 18

IP
Address

255.255.255.0

IP-Mask

18.4.6.5

Monitored data
Table 752:
Name

1128

PRPSTATUS Monitored data


Type

Values (Range)

Unit

Description

AB Beh

INTEGER

2=Blocked
3=Test
4=Test blocked
5=Off
1=On

AB Link Beh

CD Beh

INTEGER

1=On
2=Blocked
3=Test
4=Test blocked
5=Off

CD Link Beh

PRP Beh

INTEGER

2=Blocked
3=Test
4=Test blocked
5=Off
1=On

PRP Beh

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.4.6.6

Principle of operation
The communication is performed in parallel, that is the same data package is transmitted
on both channels simultaneously. The received package identity from one channel is
compared with data package identity from the other channel, if they are the same, the last
package is discarded. The PRP communication is based on the so called duo driver
concept.
The PRPSTATUS function block supervise the redundant communication on the two
channels. If no data package has been received on one (or both) channels within the last
10 s, the output PRP-A LINK and/or PRP-B LINK is set to 0 which indicates an error.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1129

Section 18
Station communication

1MRK 502 066-UUS A

Station Control System


Redundancy
Supervision
Duo

Data

Data

Switch A

Switch B

1 2

1 2

Data

Data

AB
Configuration

PRP

IED

CD

OEM

PRPSTATUS

=IEC09000758=3=en=Original.vsd
IEC09000758 V3 EN

Figure 522:

1130

Redundant station bus

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.5

LON communication protocol

18.5.1

Functionality
An optical network can be used within the substation automation system. This enables
communication with the IED through the LON bus from the operators workplace, from
the control center and also from other terminals.
LON communication protocol is specified in LonTalkProtocol Specification Version 3
from Echelon Corporation and is designed for communication in control networks. These
networks are characterized by high speed for data transfer, short messages (few bytes),
peer-to-peer communication, multiple communication media, low maintenance,
multivendor equipment, and low support costs. LonTalk supports the needs of
applications that cover a range of requirements. The protocol follows the reference model
for open system interconnection (OSI) designed by the International Standardization
Organization (ISO).
In this document the most common addresses for commands and events are available. For
other addresses, refer to section "".
It is assumed that the reader is familiar with LON communication protocol in general.

18.5.2
Table 753:
Name
Operation

Table 754:
Name

Settings
HORZCOMM Non group settings (basic)
Values (Range)

Unit

Disabled
Enabled

Step
-

Default
Disabled

Description
Operation

ADE Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation

TimerClass

Slow
Normal
Fast

Slow

Timer class

TimeDomain

Local without DST


Local with DST

Local with DST

Time domain

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1131

Section 18
Station communication
18.5.3

1MRK 502 066-UUS A

Operation principle
The speed of the network depends on the medium and transceiver design. With protection
and control devices, fibre optic media is used, which enables the use of the maximum
speed of 1.25 Mbits/s. The protocol is a peer-to-peer protocol where all the devices
connected to the network can communicate with each other. The own subnet and node
number are identifying the nodes (max. 255 subnets, 127 nodes per one subnet).
The LON bus links the different parts of the protection and control system. The measured
values, status information, and event information are spontaneously sent to the higherlevel devices. The higher-level devices can read and write memorized values, setting
values, and other parameter data when required. The LON bus also enables the bay level
devices to communicate with each other to deliver, for example, interlocking information
among the terminals without the need of a bus master.
The LonTalk protocol supports two types of application layer objects: network variables
and explicit messages. Network variables are used to deliver short messages, such as
measuring values, status information, and interlocking/blocking signals. Explicit
messages are used to transfer longer pieces of information, such as events and explicit read
and write messages to access device data.
The benefits achieved from using the LON bus in protection and control systems include
direct communication among all terminals in the system and support for multi-master
implementations. The LON bus also has an open concept, so that the terminals can
communicate with external devices using the same standard of network variables.

Introduction of LON protocol


For more information, refer to LON bus, LonWorks Network in Protection and Control,
Users manual and Technical description.

LON protocol
Configuration of LON
LON network tool (LNT) is a multi-purpose tool for LonWorks network configuration.
All the functions required for setting up and configuring a LonWorks network, is easily
accessible on a single tool program.
Activate LON Communication
Activate LON communication in the Parameter Setting tool under Main Menu/
Configuration/Communication/Station communication/ LON/HORZCOMM:1,
where Operation must be set to ON.
Add LON Device Types LNT
A new device is added to LON Network Tool from the Device menu or by installing the
device from the ABB LON Device Types package for LNT 505 using SLDT package
version 1p2 r04.
1132

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

LON net address


To establish a LON connection, the IED has to be given a unique net address. The net
address consists of a subnet and node number. This is accomplished with the LON
Network Tool by creating one device for each IED.
Vertical communication
Vertical communication describes communication between the monitoring devices and
protection and control IEDs. This communication includes sending of changed process
data to monitoring devices as events and transfer of commands, parameter data and
disturbance recorder files. This communication is implemented using explicit messages.
Events and indications
Events sent to the monitoring devices are using explicit messages (message code 44H)
with unacknowledged transport service of the LonTalk protocol. When a signal is changed
in the IED, one message with the value, quality and time is transmitted from terminal.
Binary events
Binary events are generated in event function blocks EVENT:1 to EVENT:20 in the IEDs.
The event function blocks have predefined LON addresses. Table 755 shows the LON
addresses to the first input on the event function blocks. Addresses to the other inputs on
the event function block are consecutive after the first input. For example, input 15 on
event block EVENT:17 has the address 1280 + 14 (15-1) = 1294.
For double indications, only the first eight inputs 18 must be used. Inputs 916 can be
used for other types of events at the same event block.
Three event function blocks EVENT:1 to EVENT:3 running with a fast loop time (3 ms)
are available as basic in the IEDs.. The remaining event function blocks EVENT:4 to
EVENT:9 run with a loop time of 8 ms and EVENT:10 to EVENT:20 run with a loop time
of 100 ms. The event blocks are used to send binary signals, integers, real time values like
analogue data from measuring functions and mA input modules as well as pulse counter
signals.
16 pulse counter value function blocks PCFCNT:1 to PCFCNT:16, and 24 mA input
service values function blocks SMMI1_In1 to 6 SMMI4_In1 to 6 are available in the
IEDs.
The first LON address in every event function block is found in table 755
Table 755:
Function block

LON adresses for Event functions


First LON address in
function block

EVENT:1

1024

EVENT:2

1040

EVENT:3

1056

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1133

Section 18
Station communication

1MRK 502 066-UUS A

Function block

First LON address in


function block

EVENT:4

1072

EVENT:5

1088

EVENT:6

1104

EVENT:7

1120

EVENT:8

1136

EVENT:9

1152

EVENT:10

1168

EVENT:11

1184

EVENT:12

1200

EVENT:13

1216

EVENT:14

1232

EVENT:15

1248

EVENT:16

1264

EVENT:17

1280

EVENT:18

1296

EVENT:19

1312

EVENT:20

1328

Event masks
The event mask for each input can be set individually from Parameter Setting Tool (PST)
under: Settings/IED settings/ Monitoring / EventFunction or via parameter setting tool
(PST) as follows:

No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria for
integers has no semantic, prefer to be set by the user)

The following type of signals from application functions can be connected to the event
function block.
Single indication
Directly connected binary IO signal via binary input function block (SMBI) is always
reported on change, no changed detection is done in the event function block. Other
Boolean signals, for example a pickup or a trip signal from a protection function is event
masked in the event function block.
Double indications
1134

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Double indications can only be reported via switch-control (SCSWI) functions, the event
reporting is based on information from switch-control, no change detection is done in the
event function block.
Directly connected binary IO signal via binary input function block (SMBI) is not possible
to handle as double indication. Double indications can only be reported for the first 8
inputs on an event function block.

00 generates an intermediate event with the read status 0


01 generates an open event with the read status 1
10 generates a close event with the read status 2
11 generates an undefined event with the read status 3

Analog value
All analog values are reported cyclic. The reporting interval is taken from the connected
function if there is a limit supervised signal, otherwise it is taken from the event function
block.
Command handling
Commands are transferred using transparent SPA-bus messages. The transparent SPAbus message is an explicit LON message, which contains an ASCII character message
following the coding rules of the SPA-bus protocol. The message is sent using explicit
messages with message code 41H and using acknowledged transport service.
Both the SPA-bus command messages (R or W) and the reply messages (D, A or N) are
sent using the same message code. It is mandatory that one device sends out only one SPAbus message at a time to one node and waits for the reply before sending the next message.
For commands from the operator workplace to the IED for apparatus control, That is, the
function blocks type SCSWI 1 to 30, SXCBR 1 to 18 and SXSWI 1 to 24; the SPA
addresses are according to table 756.

Horizontal communication
Network variables are used for communication between 500 and 670 series
IEDs.Network variables are used for communication between 500 and 650 series IEDs
The supported network variable type is SNVT_state (NV type 83). SNVT_state is used to
communicate the state of a set of 1 to 16 Boolean values.
Multiple command send function block (MULTICMDSND) is used to pack the
information to one value. This value is transmitted to the receiving node and presented for
the application by a multiple command receive function block (MULTICMDRCV). With
horizontal communication, the input BOUND on MULTICMDSND must be set to 1.
There are 10 MULTICMDSND and 60 MULTICMDRCV function blocks available.
These function blocks are connected using the LON network tool (LNT). The tool also
defines the service and addressing on LON.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1135

Section 18
Station communication

1MRK 502 066-UUS A

This is an overview for configuring the network variables for the IEDs.
Configuration of LON network variables
Configure the Network variables according to the specific application using the LON
network tool (LNT). The following is an example of how to configure network variables
concerning, for example, interlocking between two IEDs.
LON
BAY E1

BAY E3

MULTICMDSND: 7

MULTICMDSND: 9

BAY E4
MULTICMDSND: 9

en05000718.vsd
IEC05000718 V2 EN

Figure 523:

Examples connections between MULTICMDSND and MULTICMDRCV


function blocks in three IEDs

The network variable connections are done from the NV Connection window. From LNT
window select Connections/ NVConnections/ New.

1136

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

en05000719.vsd
IEC05000719 V1 EN

Figure 524:

The network variables window in LNT

There are two ways of downloading NV connections. Either the users can use the dragand-drop method where they can select all nodes in the device window, drag them to the
Download area in the bottom of the program window and drop them there; or, they can
perform it by selecting the traditional menu, Configuration/ Download.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1137

Section 18
Station communication

1MRK 502 066-UUS A

en05000720.vsd
IEC05000720 V1 EN

Figure 525:

The download configuration window in LNT

Communication ports
The serial communication module (SLM) is a mezzanine module placed on the Main
Processing Module (NUM) and is used for LON, SPA, IEC60870-5-103 and DNP
communication.
There are two types of IO connectors: 1) snap-in for plastic fibre cables, and 2) ST/bayonet
for glass fibre cables. The SLM can be equipped with either type or a combination of both,
which is identified by a tag.
Connect the incoming optical fibre to the RX receiver input, and the outgoing optical fibre
to the TX transmitter output. Pay special attention to the instructions concerning handling
and connection of fibre cables.
Table 756:

SPA addresses for commands from the operator workplace to the IED for apparatus control

Name

Function
block

SPA
address

Description

BL_CMD

SCSWI01

1 I 5115

SPA parameters for block


command

BL_CMD

SCSWI02

1 I 5139

SPA parameters for block


command

BL_CMD

SCSWI02

1 I 5161

SPA parameters for block


command

BL_CMD

SCSWI04

1 I 5186

SPA parameters for block


command

Table continues on next page


1138

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

BL_CMD

SCSWI05

1 I 5210

SPA parameters for block


command

BL_CMD

SCSWI06

1 I 5234

SPA parameters for block


command

BL_CMD

SCSWI07

1 I 5258

SPA parameters for block


command

BL_CMD

SCSWI08

1 I 5283

SPA parameters for block


command

BL_CMD

SCSWI09

1 I 5307

SPA parameters for block


command

BL_CMD

SCSWI10

1 I 5331

SPA parameters for block


command

BL_CMD

SCSWI11

1 I 5355

SPA parameters for block


command

BL_CMD

SCSWI12

1 I 5379

SPA parameters for block


command

BL_CMD

SCSWI13

1 I 5403

SPA parameters for block


command

BL_CMD

SCSWI14

1 I 5427

SPA parameters for block


command

BL_CMD

SCSWI15

1 I 5451

SPA parameters for block


command

BL_CMD

SCSWI16

1 I 5475

SPA parameters for block


command

BL_CMD

SCSWI17

1 I 5499

SPA parameters for block


command

BL_CMD

SCSWI18

1 I 5523

SPA parameters for block


command

BL_CMD

SCSWI19

1 I 5545

SPA parameters for block


command

BL_CMD

SCSWI20

1 I 5571

SPA parameters for block


command

BL_CMD

SCSWI21

1 I 5594

SPA parameters for block


command

BL_CMD

SCSWI22

1 I 5619

SPA parameters for block


command

BL_CMD

SCSWI23

1 I 5643

SPA parameters for block


command

BL_CMD

SCSWI24

1 I 5667

SPA parameters for block


command

BL_CMD

SCSWI25

1 I 5691

SPA parameters for block


command

BL_CMD

SCSWI26

1 I 5715

SPA parameters for block


command

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1139

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

BL_CMD

SCSWI27

1 I 5739

SPA parameters for block


command

BL_CMD

SCSWI28

1 I 5763

SPA parameters for block


command

BL_CMD

SCSWI29

1 I 5787

SPA parameters for block


command

BL_CMD

SCSWI30

1 I 5811

SPA parameters for block


command

BL_CMD

SCSWI31

1 I 5835

SPA parameters for block


command

BL_CMD

SCSWI32

1 I 5859

SPA parameters for block


command

CANCEL

SCSWI01

1 I 5107

SPA parameters for cancel


command

CANCEL

SCSWI02

1 I 5131

SPA parameters for cancel


command

CANCEL

SCSWI03

1 I 5153

SPA parameters for cancel


command

CANCEL

SCSWI04

1 I 5178

SPA parameters for cancel


command

CANCEL

SCSWI05

1 I 5202

SPA parameters for cancel


command

CANCEL

SCSWI06

1 I 5226

SPA parameters for cancel


command

CANCEL

SCSWI07

1 I 5250

SPA parameters for cancel


command

CANCEL

SCSWI08

1 I 5275

SPA parameters for cancel


command

CANCEL

SCSWI09

1 I 5299

SPA parameters for cancel


command

CANCEL

SCSWI10

1 I 5323

SPA parameters for cancel


command

CANCEL

SCSWI11

1 I 5347

SPA parameters for cancel


command

CANCEL

SCSWI12

1 I 5371

SPA parameters for cancel


command

CANCEL

SCSWI13

1 I 5395

SPA parameters for cancel


command

CANCEL

SCSWI14

1 I 5419

SPA parameters for cancel


command

CANCEL

SCSWI15

1 I 5443

SPA parameters for cancel


command

CANCEL

SCSWI16

1 I 5467

SPA parameters for cancel


command

Table continues on next page

1140

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

CANCEL

SCSWI17

1 I 5491

SPA parameters for cancel


command

CANCEL

SCSWI18

1 I 5515

SPA parameters for cancel


command

CANCEL

SCSWI19

1 I 5537

SPA parameters for cancel


command

CANCEL

SCSWI20

1 I 5563

SPA parameters for cancel


command

CANCEL

SCSWI21

1 I 5586

SPA parameters for cancel


command

CANCEL

SCSWI22

1 I 5611

SPA parameters for cancel


command

CANCEL

SCSWI23

1 I 5635

SPA parameters for cancel


command

CANCEL

SCSWI24

1 I 5659

SPA parameters for cancel


command

CANCEL

SCSWI25

1 I 5683

SPA parameters for cancel


command

CANCEL

SCSWI26

1 I 5707

SPA parameters for cancel


command

CANCEL

SCSWI27

1 I 5731

SPA parameters for cancel


command

CANCEL

SCSWI28

1 I 5755

SPA parameters for cancel


command

CANCEL

SCSWI29

1 I 5779

SPA parameters for cancel


command

CANCEL

SCSWI30

1 I 5803

SPA parameters for cancel


command

CANCEL

SCSWI31

1 I 5827

SPA parameters for cancel


command

CANCEL

SCSWI32

1 I 5851

SPA parameters for cancel


command

SELECTOpen=00,
SELECTClose=01,
SELOpen+ILO=10,
SELClose+ILO=11,
SELOpen+SCO=20,
SELClose+SCO=21,
SELOpen+ILO+SCO=30,
SELClose+ILO+SCO=31

SCSWI01

1 I 5105

SPA parameters for select (Open/


Close) command
Note: Send select command before
operate command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI02

1 I 5129

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI03

1 I 5151

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI04

1 I 5176

SPA parameters for select (Open/


Close) command

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1141

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI05

1 I 5200

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI06

1 I 5224

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI07

1 I 5248

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI08

1 I 5273

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI09

1 I 5297

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI10

1 I 5321

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI11

1 I 5345

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI12

1 I 5369

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI13

1 I 5393

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI14

1 I 5417

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI15

1 I 5441

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI16

1 I 5465

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI17

1 I 5489

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI18

1 I 5513

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI19

1 I 5535

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI20

1 I 5561

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI21

1 I 5584

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI22

1 I 5609

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI23

1 I 5633

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI24

1 I 5657

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI25

1 I 5681

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI26

1 I 5705

SPA parameters for select (Open/


Close) command

Table continues on next page

1142

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI27

1 I 5729

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI28

1 I 5753

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI29

1 I 5777

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI30

1 I 5801

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI31

1 I 5825

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI32

1 I 5849

SPA parameters for select (Open/


Close) command

ExcOpen=00,
ExcClose=01,
ExcOpen+ILO=10,
ExcClose+ILO=11,
ExcOpen+SCO=20,
ExcClose+SCO=21,
ExcOpen+ILO+SCO=30,
ExcClose+ILO+SCO=31

SCSWI01

1 I 5106

SPA parameters for operate (Open/


Close) command
Note: Send select command before
operate command

ExcOpen=00,
ExcClose=01, so on.

SCSWI02

1 I 5130

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI02

1 I 5152

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI04

1 I 5177

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI05

1 I 5201

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI06

1 I 5225

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI07

1 I 5249

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI08

1 I 5274

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI09

1 I 5298

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI10

1 I 5322

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI11

1 I 5346

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI12

1 I 5370

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI13

1 I 5394

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI14

1 I 5418

SPA parameters for operate (Open/


Close) command

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1143

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

ExcOpen=00,
ExcClose=01, so on.

SCSWI15

1 I 5442

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI16

1 I 5466

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI17

1 I 5490

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI18

1 I 5514

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI19

1 I 5536

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI20

1 I 5562

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI21

1 I 5585

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI22

1 I 5610

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI23

1 I 5634

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI24

1 I 5658

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI25

1 I 5682

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI26

1 I 5706

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI27

1 I 5730

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI28

1 I 5754

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI29

1 I 5778

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI30

1 I 5802

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI31

1 I 5826

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI32

1 I 5850

SPA parameters for operate (Open/


Close) command

Sub Value

SXCBR01

2 I 7854

SPA parameter for position to be


substituted
Note: Send the value before Enable

Sub Value

SXCBR02

2 I 7866

SPA parameter for position to be


substituted

Sub Value

SXCBR03

2 I 7884

SPA parameter for position to be


substituted

Sub Value

SXCBR04

2 I 7904

SPA parameter for position to be


substituted

Table continues on next page


1144

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

Sub Value

SXCBR05

2 I 7923

SPA parameter for position to be


substituted

Sub Value

SXCBR06

2 I 7942

SPA parameter for position to be


substituted

Sub Value

SXCBR07

2 I 7961

SPA parameter for position to be


substituted

Sub Value

SXCBR08

2 I 7980

SPA parameter for position to be


substituted

Sub Value

SXCBR09

3I7

SPA parameter for position to be


substituted

Sub Value

SXCBR10

3 I 26

SPA parameter for position to be


substituted

Sub Value

SXCBR11

3 I 45

SPA parameter for position to be


substituted

Sub Value

SXCBR12

3 I 56

SPA parameter for position to be


substituted

Sub Value

SXCBR13

3 I 74

SPA parameter for position to be


substituted

Sub Value

SXCBR14

3 I 94

SPA parameter for position to be


substituted

Sub Value

SXCBR15

3 I 120

SPA parameter for position to be


substituted

Sub Value

SXCBR16

3 I 133

SPA parameter for position to be


substituted

Sub Value

SXCBR17

3 I 158

SPA parameter for position to be


substituted

Sub Value

SXCBR18

3 I 179

SPA parameter for position to be


substituted

Sub Value

SXSWI01

3 I 196

SPA parameter for position to be


substituted

Sub Value

SXSWI02

3 I 216

SPA parameter for position to be


substituted

Sub Value

SXSWI03

3 I 235

SPA parameter for position to be


substituted

Sub Value

SXSWI04

3 I 254

SPA parameter for position to be


substituted

Sub Value

SXSWI05

3 I 272

SPA parameter for position to be


substituted

Sub Value

SXSWI06

3 I 292

SPA parameter for position to be


substituted

Sub Value

SXSWI07

3 I 310

SPA parameter for position to be


substituted

Sub Value

SXSWI08

3 I 330

SPA parameter for position to be


substituted

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1145

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

Sub Value

SXSWI09

3 I 348

SPA parameter for position to be


substituted

Sub Value

SXSWI10

3 I 359

SPA parameter for position to be


substituted

Sub Value

SXSWI11

3 I 378

SPA parameter for position to be


substituted

Sub Value

SXSWI12

3 I 397

SPA parameter for position to be


substituted

Sub Value

SXSWI13

3 I 416

SPA parameter for position to be


substituted

Sub Value

SXSWI14

3 I 435

SPA parameter for position to be


substituted

Sub Value

SXSWI15

3 I 454

SPA parameter for position to be


substituted

Sub Value

SXSWI16

3 I 473

SPA parameter for position to be


substituted

Sub Value

SXSWI17

3 I 492

SPA parameter for position to be


substituted

Sub Value

SXSWI18

3 I 511

SPA parameter for position to be


substituted

Sub Value

SXSWI19

3 I 530

SPA parameter for position to be


substituted

Sub Value

SXSWI20

3 I 549

SPA parameter for position to be


substituted

Sub Value

SXSWI21

3 I 568

SPA parameter for position to be


substituted

Sub Value

SXSWI22

3 I 587

SPA parameter for position to be


substituted

Sub Value

SXSWI23

3 I 606

SPA parameter for position to be


substituted

Sub Value

SXSWI24

3 I 625

SPA parameter for position to be


substituted

Sub Value

SXSWI25

3 I 644

SPA parameter for position to be


substituted

Sub Value

SXSWI26

3 I 663

SPA parameter for position to be


substituted

Sub Value

SXSWI27

3 I 682

SPA parameter for position to be


substituted

Sub Value

SXSWI28

3 I 701

SPA parameter for position to be


substituted

Sub Enable

SXCBR01

2 I 7855

SPA parameter for substitute


enable command
Note: Send the Value before
Enable

Table continues on next page

1146

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

Sub Enable

SXCBR02

2 I 7865

SPA parameter for substitute


enable command

Sub Enable

SXCBR03

2 I 7885

SPA parameter for substitute


enable command

Sub Enable

SXCBR04

2 I 7903

SPA parameter for substitute


enable command

Sub Enable

SXCBR05

2 I 7924

SPA parameter for substitute


enable command

Sub Enable

SXCBR06

2 I 7941

SPA parameter for substitute


enable command

Sub Enable

SXCBR07

2 I 7962

SPA parameter for substitute


enable command

Sub Enable

SXCBR08

2 I 7979

SPA parameter for substitute


enable command

Sub Enable

SXCBR09

3I8

SPA parameter for substitute


enable command

Sub Enable

SXCBR10

3 I 25

SPA parameter for substitute


enable command

Sub Enable

SXCBR11

3 I 46

SPA parameter for substitute


enable command

Sub Enable

SXCBR12

3 I 55

SPA parameter for substitute


enable command

Sub Enable

SXCBR13

3 I 75

SPA parameter for substitute


enable command

Sub Enable

SXCBR14

3 I 93

SPA parameter for substitute


enable command

Sub Enable

SXCBR15

3 I 121

SPA parameter for substitute


enable command

Sub Enable

SXCBR16

3 I 132

SPA parameter for substitute


enable command

Sub Enable

SXCBR17

3 I 159

SPA parameter for substitute


enable command

Sub Enable

SXCBR18

3 I 178

SPA parameter for substitute


enable command

Sub Enable

SXSWI01

3 I 197

SPA parameter for substitute


enable command

Sub Enable

SXSWI02

3 I 215

SPA parameter for substitute


enable command

Sub Enable

SXSWI03

3 I 234

SPA parameter for substitute


enable command

Sub Enable

SXSWI04

3 I 252

SPA parameter for substitute


enable command

Sub Enable

SXSWI05

3 I 271

SPA parameter for substitute


enable command

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1147

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

Sub Enable

SXSWI06

3 I 290

SPA parameter for substitute


enable command

Sub Enable

SXSWI07

3 I 309

SPA parameter for substitute


enable command

Sub Enable

SXSWI08

3 I 328

SPA parameter for substitute


enable command

Sub Enable

SXSWI09

3 I 347

SPA parameter for substitute


enable command

Sub Enable

SXSWI10

3 I 360

SPA parameter for substitute


enable command

Sub Enable

SXSWI11

3I 379

SPA parameter for substitute


enable command

Sub Enable

SXSWI12

3 I 398

SPA parameter for substitute


enable command

Sub Enable

SXSWI13

3 I 417

SPA parameter for substitute


enable command

Sub Enable

SXSWI14

3 I 436

SPA parameter for substitute


enable command

Sub Enable

SXSWI15

3 I 455

SPA parameter for substitute


enable command

Sub Enable

SXSWI16

3 I 474

SPA parameter for substitute


enable command

Sub Enable

SXSWI17

3 I 493

SPA parameter for substitute


enable command

Sub Enable

SXSWI18

3 I 512

SPA parameter for substitute


enable command

Sub Enable

SXSWI19

3 I 531

SPA parameter for substitute


enable command

Sub Enable

SXSWI20

3 I 550

SPA parameter for substitute


enable command

Sub Enable

SXSWI21

3 I 569

SPA parameter for substitute


enable command

Sub Enable

SXSWI22

3 I 588

SPA parameter for substitute


enable command

Sub Enable

SXSWI23

3 I 607

SPA parameter for substitute


enable command

Sub Enable

SXSWI24

3 I 626

SPA parameter for substitute


enable command

Sub Enable

SXSWI25

3 I 645

SPA parameter for substitute


enable command

Sub Enable

SXSWI26

3 I 664

SPA parameter for substitute


enable command

Sub Enable

SXSWI27

3 I 683

SPA parameter for substitute


enable command

Table continues on next page

1148

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

Sub Enable

SXSWI28

3 I 702

SPA parameter for substitute


enable command

Update Block

SXCBR01

2 I 7853

SPA parameter for update block


command

Update Block

SXCBR02

2 I 7864

SPA parameter for update block


command

Update Block

SXCBR03

2 I 7883

SPA parameter for update block


command

Update Block

SXCBR04

2 I 7905

SPA parameter for update block


command

Update Block

SXCBR05

2 I 7922

SPA parameter for update block


command

Update Block

SXCBR06

2 I 7943

SPA parameter for update block


command

Update Block

SXCBR07

2 I 7960

SPA parameter for update block


command

Update Block

SXCBR08

2 I 7981

SPA parameter for update block


command

Update Block

SXCBR09

3I6

SPA parameter for update block


command

Update Block

SXCBR10

3 I 27

SPA parameter for update block


command

Update Block

SXCBR11

3 I 44

SPA parameter for update block


command

Update Block

SXCBR12

3 I 57

SPA parameter for update block


command

Update Block

SXCBR13

3 I 73

SPA parameter for update block


command

Update Block

SXCBR14

3 I 92

SPA parameter for update block


command

Update Block

SXCBR15

3 I 122

SPA parameter for update block


command

Update Block

SXCBR16

3 I 131

SPA parameter for update block


command

Update Block

SXCBR17

3 I 160

SPA parameter for update block


command

Update Block

SXCBR18

3 I 177

SPA parameter for update block


command

Update Block

SXSWI01

3 I 198

SPA parameter for update block


command

Update Block

SXSWI02

3 I 214

SPA parameter for update block


command

Update Block

SXSWI03

3 I 236

SPA parameter for update block


command

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1149

Section 18
Station communication

1MRK 502 066-UUS A

Name

Function
block

SPA
address

Description

Update Block

SXSWI04

3 I 253

SPA parameter for update block


command

Update Block

SXSWI05

3 I 273

SPA parameter for update block


command

Update Block

SXSWI06

3 I 291

SPA parameter for update block


command

Update Block

SXSWI07

3 I 311

SPA parameter for update block


command

Update Block

SXSWI08

3 I 329

SPA parameter for update block


command

Update Block

SXSWI09

3 I 349

SPA parameter for update block


command

Update Block

SXSWI10

3 I 358

SPA parameter for update block


command

Update Block

SXSWI11

3 I 377

SPA parameter for update block


command

Update Block

SXSWI12

3 I 396

SPA parameter for update block


command

Update Block

SXSWI13

3 I 415

SPA parameter for update block


command

Update Block

SXSWI14

3 I 434

SPA parameter for update block


command

Update Block

SXSWI15

3 I 453

SPA parameter for update block


command

Update Block

SXSWI16

3 I 472

SPA parameter for update block


command

Update Block

SXSWI17

3 I 491

SPA parameter for update block


command

Update Block

SXSWI18

3 I 510

SPA parameter for update block


command

Update Block

SXSWI19

3 I 529

SPA parameter for update block


command

Update Block

SXSWI20

3 I 548

SPA parameter for update block


command

Update Block

SXSWI21

3 I 567

SPA parameter for update block


command

Update Block

SXSWI22

3 I 586

SPA parameter for update block


command

Update Block

SXSWI23

3 I 605

SPA parameter for update block


command

Update Block

SXSWI24

3 I 624

SPA parameter for update block


command

Update Block

SXSWI25

3 I 643

SPA parameter for update block


command

Table continues on next page

1150

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

18.5.4

Function
block

SPA
address

Description

Update Block

SXSWI26

3 I 662

SPA parameter for update block


command

Update Block

SXSWI27

3 I 681

SPA parameter for update block


command

Update Block

SXSWI28

3 I 700

SPA parameter for update block


command

Technical data
Table 757:

LON communication protocol

Function

Value

Protocol

LON

Communication speed

1.25 Mbit/s

18.6

SPA communication protocol

18.6.1

Functionality
In this section the most common addresses for commands and events are available. For
other addresses, refer to section "".
It is assumed that the reader is familiar with the SPA communication protocol in general.

18.6.2

Design
Using the rear SPA port for either local or remote communication with a PC requires the
following equipment:

Optical fibres
Opto/electrical converter for the PC
PC

The software needed in the PC, either local or remote, is PCM600. (Note! SPA cannot be
used with PCM600 2.6 or later).
When communicating between the local HMI and a PC, the only hardware required is a
front-connection cable. Note! SPA cannot be used from LHMI front, except for using
"FSTACCS", that is, Field Service Tool Access.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1151

Section 18
Station communication
18.6.3
Table 758:
Name

1MRK 502 066-UUS A

Settings
SPA Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

SlaveAddress

1 - 899

30

Slave address

BaudRate

300 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd

9600 Bd

Baudrate on serial line

Table 759:
Name

LONSPA Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Disabled

Operation

SlaveAddress

1 - 899

30

Slave address

18.6.4

Operation principle
The SPA bus uses an asynchronous serial communications protocol (1 start bit, 7 data bits
+ even parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For more information on
recommended baud rate for each type of IED, refer to Technical reference manual.
Messages on the bus consist of ASCII characters.

Introduction of SPA protocol


The basic construction of the protocol assumes that the slave has no self-initiated need to
talk to the master but the master is aware of the data contained in the slaves and,
consequently, can request required data. In addition, the master can send data to the slave.
Requesting by the master can be performed either by sequenced polling (for example, for
event information) or only on demand.
The master requests slave information using request messages and sends information to
the slave in write messages. Furthermore, the master can send all slaves in common a
broadcast message containing time or other data. The inactive state of bus transmit and
receive lines is a logical "1".

SPA protocol
The tables below specify the SPA addresses for reading data from and writing data to an
IED with the SPA communication protocol implemented.

1152

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

The SPA addresses for the mA input service values (MIM3 to MIM16) are found in table
760.
Table 760:

SPA addresses for the MIM function

Function block

SPA address

MIM3-CH1

4-O-6508

MIM3-CH2

4-O-6511

MIM3-CH3

4-O-6512

MIM3-CH4

4-O-6515

MIM3-CH5

4-O-6516

MIM3-CH6

4-O-6519

MIM4-CH1

4-O-6527

MIM4-CH2

4-O-6530

MIM4-CH3

4-O-6531

MIM4-CH4

4-O-6534

MIM4-CH5

4-O-6535

MIM4-CH6

4-O-6538

MIM5-CH1

4-O-6546

MIM5-CH2

4-O-6549

MIM5-CH3

4-O-6550

MIM5-CH4

4-O-6553

MIM5-CH5

4-O-6554

MIM5-CH6

4-O-6557

MIM6-CH1

4-O-6565

MIM6-CH2

4-O-6568

MIM6-CH3

4-O-6569

MIM6-CH4

4-O-6572

MIM6-CH5

4-O-6573

MIM6-CH6

4-O-6576

MIM7-CH1

4-O-6584

MIM7-CH2

4-O-6587

MIM7-CH3

4-O-6588

MIM7-CH4

4-O-6591

MIM7-CH5

4-O-6592

MIM7-CH6

4-O-6595

MIM8-CH1

4-O-6603

MIM8-CH2

4-O-6606

MIM8-CH3

4-O-6607

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1153

Section 18
Station communication

1MRK 502 066-UUS A

Function block

SPA address

MIM8-CH4

4-O-6610

MIM8-CH5

4-O-6611

MIM8-CH6

4-O-6614

MIM9-CH1

4-O-6622

MIM9-CH2

4-O-6625

MIM9-CH3

4-O-6626

MIM9-CH4

4-O-6629

MIM9-CH5

4-O-6630

MIM9-CH6

4-O-6633

MIM10-CH1

4-O-6641

MIM10-CH2

4-O-6644

MIM10-CH3

4-O-6645

MIM10-CH4

4-O-6648

MIM10-CH5

4-O-6649

MIM10-CH6

4-O-6652

MIM11-CH1

4-O-6660

MIM11-CH2

4-O-6663

MIM11-CH3

4-O-6664

MIM11-CH4

4-O-6667

MIM11-CH5

4-O-6668

MIM11-CH6

4-O-6671

MIM12-CH1

4-O-6679

MIM12-CH2

4-O-6682

MIM12-CH3

4-O-6683

MIM12-CH4

4-O-6686

MIM12-CH5

4-O-6687

MIM12-CH6

4-O-6690

MIM13-CH1

4-O-6698

MIM13-CH2

4-O-6701

MIM13-CH3

4-O-6702

MIM13-CH4

4-O-6705

MIM13-CH5

4-O-6706

MIM13-CH6

4-O-6709

MIM14-CH1

4-O-6717

MIM14-CH2

4-O-6720

MIM14-CH3

4-O-6721

Table continues on next page

1154

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Function block

SPA address

MIM14-CH4

4-O-6724

MIM14-CH5

4-O-6725

MIM14-CH6

4-O-6728

MIM15-CH1

4-O-6736

MIM15-CH2

4-O-6739

MIM15-CH3

4-O-6740

MIM15-CH4

4-O-6743

MIM15-CH5

4-O-6744

MIM15-CH6

4-O-6747

MIM16-CH1

4-O-6755

MIM16-CH2

4-O-6758

MIM16-CH3

4-O-6759

MIM16-CH4

4-O-6762

MIM16-CH5

4-O-6763

MIM16-CH6

4-O-6766

The SPA addresses for the pulse counter values PCFCNT:1 to PCFCNT:16 are found in
table 761.
Table 761:
Function block

SPA addresses for the PCFCNT function


SPA address CNT_VAL

SPA address NEW_VAL

PCFCNT:1

6-O-2788

6-O-2787

PCFCNT:2

6-O-2794

6-O-2793

PCFCNT:3

6-O-2800

6-O-2799

PCFCNT:4

6-O-2806

6-O-2805

PCFCNT:5

6-O-2812

6-O-2811

PCFCNT:6

6-O-2818

6-O-2817

PCFCNT:7

6-O-2824

6-O-2823

PCFCNT:8

6-O-2830

6-O-2829

PCFCNT:9

6-O-2836

6-O-2835

PCFCNT:10

6-O-2842

6-O-2841

PCFCNT:11

6-O-2848

6-O-2847

PCFCNT:12

6-O-2854

6-O-2853

PCFCNT:13

6-O-2860

6-O-2859

PCFCNT:14

6-O-2866

6-O-2865

PCFCNT:15

6-O-2872

6-O-2871

PCFCNT:16

6-O-2878

6-O-2877

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1155

Section 18
Station communication

1MRK 502 066-UUS A

I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module function block
are used, that is, the addresses for BI1 BI16. For SPA addresses, refer to section Related
documents in Product Guide.
Single command, 16 signals
The IEDs can be provided with a function to receive signals either from a substation
automation system or from the local HMI. That receiving function block has 16 outputs
that can be used, for example, to control high voltage apparatuses in switchyards. For local
control functions, the local HMI can also be used.
Single command, 16 signals function consists of three function blocks; SINGLECMD:1
to SINGLECMD:3 for 16 binary output signals each.
The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 3 signals function
block, SINGLECMD:1 to SINGLECMD:3, the address is for the first output. The other
outputs follow consecutively after the first one. For example, output 7 on the
SINGLECMD:2 function block has the 5O533 address.
The SPA addresses for Single command, 16 signals functions SINGLECMD:1 to
SINGLECMD:3 are found in table 762.
Table 762:

SPA addresses for SINGLECMD function

Function block

SPA address CMD Input

SPA address CMD output

SINGLECMD1-Cmd1

4-S-4639

5-O-511

SINGLECMD1-Cmd2

4-S-4640

5-O-512

SINGLECMD1-Cmd3

4-S-4641

5-O-513

SINGLECMD1-Cmd4

4-S-4642

5-O-514

SINGLECMD1-Cmd5

4-S-4643

5-O-515

SINGLECMD1-Cmd6

4-S-4644

5-O-516

SINGLECMD1-Cmd7

4-S-4645

5-O-517

SINGLECMD1-Cmd8

4-S-4646

5-O-518

SINGLECMD1-Cmd9

4-S-4647

5-O-519

SINGLECMD1-Cmd10

4-S-4648

5-O-520

SINGLECMD1-Cmd11

4-S-4649

5-O-521

SINGLECMD1-Cmd12

4-S-4650

5-O-522

SINGLECMD1-Cmdt13

4-S-4651

5-O-523

SINGLECMD1-Cmd14

4-S-4652

5-O-524

SINGLECMD1-Cmd15

4-S-4653

5-O-525

SINGLECMD1-Cmd16

4-S-4654

5-O-526

Table continues on next page

1156

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Function block

SPA address CMD Input

SPA address CMD output

SINGLECMD2-Cmd1

4-S-4672

5-O-527

SINGLECMD2-Cmd2

4-S-4673

5-O-528

SINGLECMD2-Cmdt3

4-S-4674

5-O-529

SINGLECMD2-Cmd4

4-S-4675

5-O-530

SINGLECMD2-Cmd5

4-S-4676

5-O-531

SINGLECMD2-Cmd6

4-S-4677

5-O-532

SINGLECMD2-Cmd7

4-S-4678

5-O-533

SINGLECMD2-Cmd8

4-S-4679

5-O-534

SINGLECMD2-Cmd9

4-S-4680

5-O-535

SINGLECMD2-Cmd10

4-S-4681

5-O-536

SINGLECMD2-Cmd11

4-S-4682

5-O-537

SINGLECMD2-Cmd12

4-S-4683

5-O-538

SINGLECMD2-Cmd13

4-S-4684

5-O-539

SINGLECMD2-Cmd14

4-S-4685

5-O-540

SINGLECMD2-Cmd15

4-S-4686

5-O-541

SINGLECMD2-Cmd16

4-S-4687

5-O-542

SINGLECMD3-Cmd1

4-S-4705

5-O-543

SINGLECMD3-Cmd2

4-S-4706

5-O-544

SINGLECMD3-Cmd3

4-S-4707

5-O-545

SINGLECMD3-Cmd4

4-S-4708

5-O-546

SINGLECMD3-Cmd5

4-S-4709

5-O-547

SINGLECMD3-Cmd6

4-S-4710

5-O-548

SINGLECMD3-Cmd7

4-S-4711

5-O-549

SINGLECMD3-Cmd8

4-S-4712

5-O-550

SINGLECMD3-Cmd9

4-S-4713

5-O-551

SINGLECMD3-Cmd10

4-S-4714

5-O-552

SINGLECMD3-Cmd11

4-S-4715

5-O-553

SINGLECMD3-Cmd12

4-S-4716

5-O-554

SINGLECMD3-Cmd13

4-S-4717

5-O-555

SINGLECMD3-Cmd14

4-S-4718

5-O-556

SINGLECMD3-Cmd15

4-S-4719

5-O-557

SINGLECMD3-Cmd16

4-S-4720

5-O-558

Figure 526 shows an application example of how the user can, in a simplified way, connect
the command function via the configuration logic circuit in a protection IED for control
of a circuit breaker.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1157

Section 18
Station communication

1MRK 502 066-UUS A

A pulse via the binary outputs of the IED normally performs this type of command control.
The SPA addresses to control the outputs OUT1 OUT16 in SINGLECMD:1 are shown
in table 762.

#CD01-CMDOUT1
#CD01-CMDOUT2
#CD01-CMDOUT3
#CD01-CMDOUT4
#CD01-CMDOUT5
#CD01-CMDOUT6
#CD01-CMDOUT7
#CD01-CMDOUT8
#CD01-CMDOUT9
#CD01-CMDOUT10
#CD01-CMDOUT11
#CD01-CMDOUT12
#CD01-CMDOUT13
#CD01-CMDOUT14
#CD01-CMDOUT15
#CD01-CMDOUT16

SINGLECMD
BLOCK
^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16

PULSETIMER
INPUT

AND
INPUT1
INPUT2
INPUT3
INPUT4

OUT

To output board, CLOSE

OUT

To output board, OPEN

PULSETIMER
OUT
NOUT

INPUT

IEC05000717-3-en.vsd
SYNCH OK
IEC05000717 V3 EN

Figure 526:

Application example showing a simplified logic diagram for control of a


circuit breaker

The MODE input defines if the output signals from SINGLECMD:1 is off, steady or
setable pulse length signals. This is set in Parameter Setting Tool (PST) under: Main
Menu/Settings / IED Settings / Control / Commands / Single Command or via
Parameter Setting Tool (PST).
Event function
Event function is intended to send time-tagged events to the station level (for example,
operator workplace) over the station bus. The events are there presented in an event list.
The events can be created from both internal logical signals and binary input channels. All
the internal signals are time tagged in the main processing module, while the binary input
channels are time tagged directly on each I/O module. The events are produced according
to the set of event masks. The event masks are treated commonly for both the LON and
SPA channels. All events according to the event mask are stored in a buffer, which
contains up to 1000 events. If new events appear before the oldest event in the buffer is
read, the oldest event is overwritten and an overflow alarm appears.
Two special signals for event registration purposes are available in the IED, Terminal
Restarted (0E50) and Event buffer overflow (0E51).
The input parameters can be set individually from the Parameter Setting Tool (PST)
under: Main Menu/Settings / IED Settings / Monitoring / Event Function or via
parameter Setting Tool (PST) as follows:

1158

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria for
integers has no semantic, prefer to be set by the user)

The Status and event codes for the Event functions are found in table 763.
Table 763:
Event block

Status and event codes


Status

Single indication1)
Set event
Reset
event

Double indication
Intermedi Closed 10 Open 01 Undefined
ate 00
11

EVENT:1
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16

22O1
22O2
22O3
22O4
22O5
22O6
22O7
22O8
22O9
22O10
22O11
22O12
22O13
22O14
22O15
22O16

22E33
22E35
22E37
22E39
22E41
22E43
22E45
22E47
22E49
22E51
22E53
22E55
22E57
22E59
22E61
22E63

22E32
22E34
22E36
22E38
22E40
22E42
22E44
22E46
22E48
22E50
22E52
22E54
22E56
22E58
22E60
22E62

22E0
22E4
22E8
22E12
22E16
22E20
22E24
22E28
-

22E1
22E5
22E9
22E13
22E17
22E21
22E25
22E29
-

22E2
22E6
22E10
22E14
22E18
22E22
22E26
22E30
-

22E3
22E7
22E11
22E15
22E19
22E23
22E27
22E31
-

EVENT:2
EVENT:3
EVENT:20

230..
240..
410..

23E..
24E..
41E..

23E..
24E..
41E..

23E..
24E..
41E..

23E..
23E..
41E..

23E..
24E..
41E..

23E..
24E..
41E..

These values are only applicable if the Event mask is masked OFF.
Connection of signals as events
Signals coming from different protection and control functions and must be sent as events
to the station level over the SPA-bus (or LON-bus) are connected to the Event function
block according to figure 527.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1159

Section 18
Station communication

1MRK 502 066-UUS A

EVENT
Block

ILRANG
PSTO
VABRANG
VBCRANG
VCARANG
3I0RANG
3V0RANG
FALSE

BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

ANSI07000065-1-en.vsd

ANSI07000065 V1 EN

Figure 527:

18.6.4.1

Connection of protection signals for event handling

Communication ports
The serial communication module (SLM) is a mezzanine module placed on the numeric
processing module (NUM) and is used for LON, SPA, IEC60870-5-103, or DNP
communication.
There are two types of IO connectors: 1) snap-in for plastic fibre cables and 2) ST/bayonet
for glass fibre cables. The SLM can be equipped with either type or a combination of both,
which is identified by a tag.
Connect the incoming optical fibre to the RX receiver input, and the outgoing optical fibre
to the TX transmitter output. Pay special attention to the instructions concerning handling
and connection of fibre cables.
For setting the transfer rate (baud rate) and slave number, please refer to the Application
Manual and Commissioning Manual respectively.

1160

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.6.5

Technical data
Table 764:

SPA communication protocol

Function

Value

Protocol

SPA

Communication speed

300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd

Slave number

1 to 899

18.7

IEC 60870-5-103 communication protocol

18.7.1

Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must have
software that can interpret the IEC 60870-5-103 communication messages.

18.7.2

Measurands for IEC 60870-5-103 I103MEAS

18.7.2.1

Functionality
103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The set of connected input will control which ASDUs (Application Service Data Units)
are generated.

9 Will be generated if at least IA is connected. IB, IC, VA, VB, VC, P, Q, F are
optional but there can be no holes.
3.4 Will be generated if IN and VN are present.
3.3 Will be generated if IB, VAB, P and Q present.
3.2 Will be generated if IB, VAB, and P or Q missing.
3.1 Will be generated if IB is present and IA is missing (otherwise I_B in 9).
Description for I103MEAS function block:
9 = IA
3.4 = IN AND VN
3.3 = IB AND VAB AND P AND Q
3.2 = IB AND VAB AND NOT 3.3
3.1 = IB AND NOT (3.2 OR 3.3 OR 9)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1161

Section 18
Station communication
18.7.2.2

1MRK 502 066-UUS A

Identification
Function description

Function block
name

Measurands for IEC 60870-5-103

18.7.2.3

IEC 60617
identification

I103MEAS

ANSI/IEEE C37.2
device number
-

Function block
I103MEAS
BLOCK
I_A
I_B
I_C
IN
V_A
V_B
V_C
V_AB
V_N
P
Q
F
ANSI10000287-1-en.vsd
ANSI10000287 V1 EN

Figure 528:

18.7.2.4

Signals
Table 765:
Name

1162

I103MEAS function block

I103MEAS Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of service value reporting

IA

REAL

0.0

Service value for current phase A

IB

REAL

0.0

Service value for current phase B

IC

REAL

0.0

Service value for current phase C

IN

REAL

0.0

Service value for residual current IN

VA

REAL

0.0

Service value for voltage phase A

VB

REAL

0.0

Service value for voltage phase B

VC

REAL

0.0

Service value for voltage phase C

V_AB

REAL

0.0

Service value for voltage phase-phase AB

V_N

REAL

0.0

Service value for residual voltage VN

REAL

0.0

Service value for active power

REAL

0.0

Service value for reactive power

REAL

0.0

Service value for system frequency

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.7.2.5
Table 766:
Name

Settings
I103MEAS Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

FunctionType

1 - 255

Function type (1-255)

MaxIa

1 - 99999

3000

Maximum current phase A

MaxIb

1 - 99999

3000

Maximum current phase B

MaxIc

1 - 99999

3000

Maximum current phase C

MaxIN

1 - 99999

3000

Maximum residual current IN

MaxVa

0.05 - 2000.00

kV

0.05

230.00

Maximum voltage for phase A

MaxVb

0.05 - 2000.00

kV

0.05

230.00

Maximum voltage for phase B

MaxVc

0.05 - 2000.00

kV

0.05

230.00

Maximum voltage for phase C

MaxVab

0.05 - 2000.00

kV

0.05

400.00

Maximum voltage for phase-phase AB

MaxVn

0.05 - 2000.00

kV

0.05

230.00

Maximum residual voltage VN

MaxP

0.00 - 2000.00

MW

0.05

1200.00

Maximum value for active power

MaxQ

0.00 - 2000.00

MVAr

0.05

1200.00

Maximum value for reactive power

MaxF

45.0 - 66.0

Hz

1.0

51.0

Maximum system frequency

18.7.3

Measurands user defined signals for IEC 60870-5-103


I103MEASUSR

18.7.3.1

Functionality
I103MEASUSR is a function block with user defined input measurands in monitor
direction. These function blocks include the FunctionType parameter for each block in the
private range, and the Information number parameter for each block.

18.7.3.2

Identification
Function description
Measurands user defined signals for
IEC 60870-5-103

Function block
name
I103MEASUSR

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

1163

Section 18
Station communication
18.7.3.3

1MRK 502 066-UUS A

Function block
I103MEASUSR
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
IEC10000288-1-en.vsd
IEC10000288 V1 EN

Figure 529:

18.7.3.4

I103MEASUSR function block

Signals
Table 767:

I103MEASUSR Input signals

Name

18.7.3.5
Table 768:
Name

Type

Default

Description

BLOCK

BOOLEAN

Block of service value reporting

INPUT1

REAL

0.0

Service value for measurement on input 1

INPUT2

REAL

0.0

Service value for measurement on input 2

INPUT3

REAL

0.0

Service value for measurement on input 3

INPUT4

REAL

0.0

Service value for measurement on input 4

INPUT5

REAL

0.0

Service value for measurement on input 5

INPUT6

REAL

0.0

Service value for measurement on input 6

INPUT7

REAL

0.0

Service value for measurement on input 7

INPUT8

REAL

0.0

Service value for measurement on input 8

INPUT9

REAL

0.0

Service value for measurement on input 9

Settings
I103MEASUSR Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

FunctionType

1 - 255

25

Function type (1-255)

InfNo

1 - 255

Information number for measurands (1-255)

MaxMeasur1

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 1

MaxMeasur2

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 2

Table continues on next page

1164

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

MaxMeasur3

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 3

MaxMeasur4

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 4

MaxMeasur5

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 5

MaxMeasur6

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 6

MaxMeasur7

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 7

MaxMeasur8

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 8

MaxMeasur9

0.05 10000000000.00

0.05

1000.00

Maximum value for measurement on input 9

18.7.4

Function status auto-recloser for IEC 60870-5-103 I103AR

18.7.4.1

Functionality
I103AR is a function block with defined functions for autorecloser indications in monitor
direction. This block includes the FunctionType parameter, and the information number
parameter is defined for each output signal.

18.7.4.2

Identification
Function description
Function status auto-recloser for IEC
60870-5-103

18.7.4.3

Function block
name
I103AR

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Function block
I103AR
BLOCK
16_ARACT
128_CBON
130_BLKD
IEC10000289-2-en.vsd
IEC10000289 V2 EN

Figure 530:

I103AR function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1165

Section 18
Station communication
18.7.4.4

1MRK 502 066-UUS A

Signals
Table 769:

I103AR Input signals

Name

18.7.4.5
Table 770:
Name
FunctionType

Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

16_ARACT

BOOLEAN

Information number 16, auto-recloser active

128_CBON

BOOLEAN

Information number 128, circuit breaker on by autorecloser

130_BLKD

BOOLEAN

Information number 130, auto-recloser blocked

Settings
I103AR Non group settings (basic)
Values (Range)

Unit

1 - 255

Step

Default
1

Description
Function type (1-255)

18.7.5

Function status ground-fault for IEC 60870-5-103 I103EF

18.7.5.1

Functionality
I103EF is a function block with defined functions for ground fault indications in monitor
direction. This block includes the FunctionType parameter, and the information number
parameter is defined for each output signal.

18.7.5.2

Identification
Function description
Function status earth-fault for IEC
60870-5-103

18.7.5.3

Function block
name
I103EF

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Function block
I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290-1-en.vsd
IEC10000290 V1 EN

Figure 531:

1166

I103EF function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.7.5.4

Signals
Table 771:

I103EF Input signals

Name

18.7.5.5
Table 772:
Name
FunctionType

Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

51_EFFW

BOOLEAN

Information number 51, ground-fault forward

52_EFREV

BOOLEAN

Information number 52, ground-fault reverse

Settings
I103EF Non group settings (basic)
Values (Range)
1 - 255

Unit
-

Step
1

Default
160

Description
Function type (1-255)

18.7.6

Function status fault protection for IEC 60870-5-103


I103FLTPROT

18.7.6.1

Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to a
correspondent signal present in the configuration. For example: 68_TRGEN represents
the General Trip of the device, and therefore must be connected to the general trip signal
SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.

18.7.6.2

Identification
Function description
Function status fault protection for IEC
60870-5-103

Function block
name
I103FLTPROT

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

1167

Section 18
Station communication
18.7.6.3

1MRK 502 066-UUS A

Function block
I103FLTPROT
BLOCK
64_PU_A
65_PU_B
66_PU_C
67_STIN
68_TRGEN
69_TR_A
70_TR_B
71_TR_C
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
84_STGEN
85_BFP
86_MTR_A
87_MTR_B
88_MTR_C
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
ANSI10000291-1-en.vsd
ANSI10000291 V1 EN

Figure 532:

18.7.6.4

I103FLTPROT function block

Signals
Table 773:
Name

I103FLTPROT Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting.

64_PU_A

BOOLEAN

Information number 64, pickup phase A

65_PU_B

BOOLEAN

Information number 64, pickup phase B

66_PU_C

BOOLEAN

Information number 64, pickup phase C

67_STIN

BOOLEAN

Information number 67, start residual current IN

68_TRGEN

BOOLEAN

Information number 68, trip general

69_TR_A

BOOLEAN

Information number 69, trip phase A

70_TR_B

BOOLEAN

Information number 70, trip phase B

71_TR_C

BOOLEAN

Information number 71, trip phase C

72_TRBKUP

BOOLEAN

Information number 72, back up trip I>>

73_SCL

REAL

Information number 73, fault location in ohm

Table continues on next page


1168

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

18.7.6.5
Table 774:
Name
FunctionType

Type

Default

Description

74_FW

BOOLEAN

Information number 74, forward/line

75_REV

BOOLEAN

Information number 75, reverse/busbar

76_TRANS

BOOLEAN

Information number 76, signal transmitted

77_RECEV

BOOLEAN

Information number 77, signal received

78_ZONE1

BOOLEAN

Information number 78, zone 1

79_ZONE2

BOOLEAN

Information number 79, zone 2

80_ZONE3

BOOLEAN

Information number 80, zone 3

81_ZONE4

BOOLEAN

Information number 81, zone 4

82_ZONE5

BOOLEAN

Information number 82, zone 5

84_STGEN

BOOLEAN

Information number 84, start general

85_BFP

BOOLEAN

Information number 85, breaker failure

86_MTR_A

BOOLEAN

Information number 86, trip measuring system phase A

87_MTR_B

BOOLEAN

Information number 87, trip measuring system phase B

88_MTR_C

BOOLEAN

Information number 88, trip measuring system phase C

89_MTRN

BOOLEAN

Information number 89, trip measuring system neutral N

90_IOC

BOOLEAN

Information number 90, over current trip, stage low

91_IOC

BOOLEAN

Information number 91, over current trip, stage high

92_IEF

BOOLEAN

Information number 92, ground-fault trip, stage low

93_IEF

BOOLEAN

Information number 93, ground-fault trip, stage high

ARINPROG

BOOLEAN

Autorecloser in progress (SMBRREC- INPROGR)

FLTLOC

BOOLEAN

Faultlocator faultlocation valid (LMBRFLOCALCMADE)

Settings
I103FLTPROT Non group settings (basic)
Values (Range)
1 - 255

Unit
-

Step
1

Default
128

Description
Function type (1-255)

18.7.7

IED status for IEC 60870-5-103 I103IED

18.7.7.1

Functionality
I103IED is a function block with defined IED functions in monitor direction. This block
uses parameter as FunctionType, and information number parameter is defined for each
input signal.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1169

Section 18
Station communication
18.7.7.2

1MRK 502 066-UUS A

Identification
Function description

Function block
name

IED status for IEC 60870-5-103

18.7.7.3

IEC 60617
identification

I103IED

ANSI/IEEE C37.2
device number
-

Function block
I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-2-en.vsd
IEC10000292 V2 EN

Figure 533:

18.7.7.4

I103IED function block

Signals
Table 775:

I103IED Input signals

Name

18.7.7.5
Table 776:
Name
FunctionType

1170

Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

19_LEDRS

BOOLEAN

Information number 19, reset LEDs

21_TESTM

BOOLEAN

Information number 21, test mode is active

22_SETCH

BOOLEAN

Information number 22, setting changed

23_GRP1

BOOLEAN

Information number 23, setting group 1 is active

24_GRP2

BOOLEAN

Information number 24, setting group 2 is active

25_GRP3

BOOLEAN

Information number 25, setting group 3 is active

26_GRP4

BOOLEAN

Information number 26, setting group 4 is active

Settings
I103IED Non group settings (basic)
Values (Range)
1 - 255

Unit
-

Step
1

Default
1

Description
Function type (1-255)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.7.8

Supervison status for IEC 60870-5-103 I103SUPERV

18.7.8.1

Functionality
I103SUPERV is a function block with defined functions for supervision indications in
monitor direction. This block includes the FunctionType parameter, and the information
number parameter is defined for each output signal.

18.7.8.2

Identification
Function description

Function block
name

Supervison status for IEC 60870-5-103

18.7.8.3

IEC 60617
identification

I103SUPERV

ANSI/IEEE C37.2
device number
-

Function block
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293-1-en.vsd
IEC10000293 V1 EN

Figure 534:

18.7.8.4

I103SUPERV function block

Signals
Table 777:
Name

I103SUPERV Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

32_MEASI

BOOLEAN

Information number 32, measurand supervision of I

33_MEASU

BOOLEAN

Information number 33, measurand supervision of V

37_IBKUP

BOOLEAN

Information number 37, I high-high back-up protection

38_VTFF

BOOLEAN

Information number 38, fuse failure VT

46_GRWA

BOOLEAN

Information number 46, group warning

47_GRAL

BOOLEAN

Information number 47, group alarm

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1171

Section 18
Station communication
18.7.8.5
Table 778:
Name
FunctionType

1MRK 502 066-UUS A

Settings
I103SUPERV Non group settings (basic)
Values (Range)
1 - 255

Unit

Step

Default

Description
Function type (1-255)

18.7.9

Status for user defined signals for IEC 60870-5-103


I103USRDEF

18.7.9.1

Functionality
I103USRDEF is a function block with user defined input signals in monitor direction.
Each instance is associated with a Function Type (FUN) and each input signal with an
Information Number (INF). Additionally, all input signals may be defined to use relative
time and how to respond to a GI request.
The user is responsible for assigning a proper FUN value and proper INF values to all
connected inputs. See Settings for details.

18.7.9.2

Identification
Function description
Status for user defined signals for IEC
60870-5-103

18.7.9.3

Function block
name
I103USRDEF

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Function block

IEC10000294 V2 EN

Figure 535:

1172

I103USRDEF function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.7.9.4

Signals
Table 779:

I103USRDEF Input signals

Name

Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

INPUT1

BOOLEAN

Binary signal Input 1

INPUT2

BOOLEAN

Binary signal input 2

INPUT3

BOOLEAN

Binary signal input 3

INPUT4

BOOLEAN

Binary signal input 4

INPUT5

BOOLEAN

Binary signal input 5

INPUT6

BOOLEAN

Binary signal input 6

INPUT7

BOOLEAN

Binary signal input 7

INPUT8

BOOLEAN

Binary signal input 8

RT_START

BOOLEAN

Trig to set base of relative time

RT_START registers the positive transition (0->1) of a pulse and sets the time from
which relative time is derived. Relative time is assigned only to inputs where the
corresponding TypNo parameter is set to Relative. The maximum relative time and unit
conform to the IEC60870-5-103 standard.

18.7.9.5
Table 780:
Name

Settings
I103USRDEF Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

FunctionType

1 - 255

Function type (1-255)

InfNo1

1 - 255

Information number for binary input 1 (1-255)

InfNo2

1 - 255

Information number for binary input 2 (1-255)

InfNo3

1 - 255

Information number for binary input 3 (1-255)

InfNo4

1 - 255

Information number for binary input 4 (1-255)

InfNo5

1 - 255

Information number for binary input 5 (1-255)

InfNo6

1 - 255

Information number for binary input 6 (1-255)

InfNo7

1 - 255

Information number for binary input 7 (1-255)

InfNo8

1 - 255

Information number for binary input 8 (1-255)

TypNo1

Absolute
Relative

Absolute

Type identification (TYP)

TypNo2

Absolute
Relative

Absolute

Type identification (TYP)

TypNo3

Absolute
Relative

Absolute

Type identification (TYP)

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1173

Section 18
Station communication

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

TypNo4

Absolute
Relative

Absolute

Type identification (TYP)

TypNo5

Absolute
Relative

Absolute

Type identification (TYP)

TypNo6

Absolute
Relative

Absolute

Type identification (TYP)

TypNo7

Absolute
Relative

Absolute

Type identification (TYP)

TypNo8

Absolute
Relative

Absolute

Type identification (TYP)

GiNo1

Excluded
Included

Included

Response and status change (GI)

GiNo2

Excluded
Included

Included

Response and status change (GI)

GiNo3

Excluded
Included

Included

Response and status change (GI)

GiNo4

Excluded
Included

Included

Response and status change (GI)

GiNo5

Excluded
Included

Included

Response and status change (GI)

GiNo6

Excluded
Included

Included

Response and status change (GI)

GiNo7

Excluded
Included

Included

Response and status change (GI)

GiNo8

Excluded
Included

Included

Response and status change (GI)

The FunctionType parameter associates a particular instance of the function block with
a FUN. Refer to the IEC60870-5-103 standard for details.
The InfNon parameters are used to associate each individual input signal with a
userdefined INF. Refer to the IEC60870-5-103 standard for details.
The TypNon parameters determine if messages use absolute or relative time. This adheres
to the TYPE IDENTIFICATION (TYP) message types 1 (time-tagged message) and 2
(time-tagged message with relative time) of the IEC60870-5-103 standard.
The GiNon parameters determine whether a message is sent as a part of a GI reply or not.
Refer to the IEC60870-5-103 standard for details.

1174

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.7.10

Function commands for IEC 60870-5-103 I103CMD

18.7.10.1

Functionality
I103CMD is a command function block in control direction with pre-defined output
signals. The signals are in steady state, not pulsed, and stored in the IED in case of restart.

18.7.10.2

Identification
Function description

Function block
name

Function commands for IEC


60870-5-103

18.7.10.3

IEC 60617
identification

I103CMD

ANSI/IEEE C37.2
device number
-

Function block
I103CMD
BLOCK

16-AR
17-DIFF
18-PROT
IEC10000282-1-en.vsd

IEC10000282 V1 EN

Figure 536:

18.7.10.4

I103CMD function block

Signals
Table 781:

I103CMD Input signals

Name

Type

BLOCK

Table 782:

Table 783:
Name
FunctionType

Description
Block of commands

I103CMD Output signals

Name

18.7.10.5

Default

BOOLEAN

Type

Description

16-AR

BOOLEAN

Information number 16 disable/enable autorecloser

17-DIFF

BOOLEAN

Information number 17, block of differential protection

18-PROT

BOOLEAN

Information number 18, block of protection

Settings
I103CMD Non group settings (basic)
Values (Range)
1 - 255

Unit
-

Step
1

Default
1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description
Function type (1-255)
1175

Section 18
Station communication

1MRK 502 066-UUS A

18.7.11

IED commands for IEC 60870-5-103 I103IEDCMD

18.7.11.1

Functionality
I103IEDCMD is a command block in control direction with defined IED functions. All
outputs are pulsed and they are NOT stored. Pulse-time is a hidden parameter.

18.7.11.2

Identification
Function description

Function block
name

IED commands for IEC 60870-5-103

18.7.11.3

IEC 60617
identification

I103IEDCMD

ANSI/IEEE C37.2
device number
-

Function block
BLOCK

I103IEDCMD
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283-1-en.vsd

IEC10000283 V1 EN

Figure 537:

18.7.11.4

Signals
Table 784:
Name
BLOCK

Table 785:
Name

1176

I103IEDCMD function block

I103IEDCMD Input signals


Type
BOOLEAN

Default
0

Description
Block of commands

I103IEDCMD Output signals


Type

Description

19-LEDRS

BOOLEAN

Information number 19, reset LEDs

23-GRP1

BOOLEAN

Information number 23, activate setting group 1

24-GRP2

BOOLEAN

Information number 24, activate setting group 2

25-GRP3

BOOLEAN

Information number 25, activate setting group 3

26-GRP4

BOOLEAN

Information number 26, activate setting group 4

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.7.11.5
Table 786:
Name
FunctionType

Settings
I103IEDCMD Non group settings (basic)
Values (Range)

Unit

1 - 255

Step

Default

Description

255

Function type (1-255)

18.7.12

Function commands user defined for IEC 60870-5-103


I103USRCMD

18.7.12.1

Functionality
I103USRCMD is a command block in control direction with user defined output signals.
These function blocks include the FunctionType parameter for each block in the private
range, and the Information number parameter for each output signal.

18.7.12.2

Identification
Function description

Function block
name

Function commands user defined for


IEC 60870-5-103

18.7.12.3

IEC 60617
identification

I103USRCMD

ANSI/IEEE C37.2
device number
-

Function block
BLOCK

I103USRCMD
^OUTPUT1
^OUTPUT2
^OUTPUT3
^OUTPUT4
^OUTPUT5
^OUTPUT6
^OUTPUT7
^OUTPUT8
IEC10000284-1-en.vsd

IEC10000284 V1 EN

Figure 538:

18.7.12.4

I103USRCMD function block

Signals
Table 787:
Name
BLOCK

I103USRCMD Input signals


Type
BOOLEAN

Default
0

Description
Block of commands

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1177

Section 18
Station communication

1MRK 502 066-UUS A

Table 788:

I103USRCMD Output signals

Name

18.7.12.5
Table 789:
Name

Type

Description

OUTPUT1

BOOLEAN

Command output 1

OUTPUT2

BOOLEAN

Command output 2

OUTPUT3

BOOLEAN

Command output 3

OUTPUT4

BOOLEAN

Command output 4

OUTPUT5

BOOLEAN

Command output 5

OUTPUT6

BOOLEAN

Command output 6

OUTPUT7

BOOLEAN

Command output 7

OUTPUT8

BOOLEAN

Command output 8

Settings
I103USRCMD Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

FunctionType

1 - 255

Function type (1-255)

PulseMode

Steady
Pulsed

Pulsed

Pulse mode

PulseLength

0.200 - 60.000

0.001

0.400

Pulse length

InfNo_1

1 - 255

Information number for output 1 (1-255)

InfNo_2

1 - 255

Information number for output 2 (1-255)

InfNo_3

1 - 255

Information number for output 3 (1-255)

InfNo_4

1 - 255

Information number for output 4 (1-255)

InfNo_5

1 - 255

Information number for output 5 (1-255)

InfNo_6

1 - 255

Information number for output 6 (1-255)

InfNo_7

1 - 255

Information number for output 7 (1-255)

InfNo_8

1 - 255

Information number for output 8 (1-255)

18.7.13

Function commands generic for IEC 60870-5-103


I103GENCMD

18.7.13.1

Functionality
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103. The
function has two outputs signals CMD_OFF and CMD_ON that can be used to implement
double-point command schemes.

1178

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2 steady


ON/OFF outputs. The ON output is pulsed with a command with value 2, while the OFF
output is pulsed with a command value 1. If in steady mode is ON asserted and OFF
deasserted with command 2 and vice versa with command 1. Steady mode is selected by
setting PulseLength=0. The I103GENCMD is retained, and a command in steady mode
will be reissued on restart.

18.7.13.2

Identification
Function description

Function block
name

Function commands generic for IEC


60870-5-103

18.7.13.3

IEC 60617
identification

I103GENCMD

ANSI/IEEE C37.2
device number
-

Function block
BLOCK

I103GENCMD
^CMD_OFF
^CMD_ON
IEC10000285-1-en.vsd

IEC10000285 V1 EN

Figure 539:

18.7.13.4

I103GENCMD function block

Signals
Table 790:
Name
BLOCK

Table 791:
Name

I103GENCMD Input signals


Type
BOOLEAN

Default
0

Description
Block of command

I103GENCMD Output signals


Type

Description

CMD_OFF

BOOLEAN

Command output OFF

CMD_ON

BOOLEAN

Command output ON

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1179

Section 18
Station communication
18.7.13.5
Table 792:
Name

1MRK 502 066-UUS A

Settings
I103GENCMD Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

FunctionType

1 - 255

Function type (1-255)

PulseLength

0.000 - 60.000

0.001

0.400

Pulse length

InfNo

1 - 255

Information number for command output


(1-255)

18.7.14

IED commands with position and select for IEC 60870-5-103


I103POSCMD

18.7.14.1

Functionality
The I103POSCMD is a transceiver function that monitors activity on its input signals and
interprets any state transition into commands then sent over an established IEC103 link.
Additionally, it listens for general interrogation (GI) requests, to which it will reply with
a GI response message with the current state of each connected input.
The Position input is a double-indication signal and is GI enabled. This means that any
state transition, i.e. to ON, OFF, intermediate and faulty, will be reported spontaneously.
However, the intermediate and faulty states may be suppressed by setting the "Report
Intermediate Position" to "Off". See the settings for RS485 and optical serial
communication for more information.
The Select input is a single-indication signal and is also GI enabled. State transitions to
ON and OFF are reported spontaneously.
When the Block input is ON, the function will ignore GI requests and cease all monitoring
activity. Consequently, no transitions will be detected.
The I103POSCMD is also equipped with two additional commands; Operate and Cancel.
These are hidden in ACT and respond only to the base INF +2 and +3 respectively. See
table below. The base INF (Information Number) parameter is an IEC 60870-5-103
identifier that associates a function in a 103 Master (such as Scada) with its equivalent in
the IED.

18.7.14.2

Identification
Function description
IED commands with position and select
for IEC 60870-5-103

1180

Function block
name
I103POSCMD

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.7.14.3

Function block
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286-1-en.vsd
IEC10000286 V1 EN

Figure 540:

18.7.14.4

I103POSCMD function block

Signals
Table 793:

I103POSCMD Input signals

Name

18.7.14.5
Table 794:
Name

Type

Default

Description

BLOCK

BOOLEAN

Block of command

POSITION

INTEGER

Position of controllable object

SELECT

BOOLEAN

Select of controllable object

Default

Description

Settings
I103POSCMD Non group settings (basic)
Values (Range)

Unit

Step

FunctionType

1 - 255

Function type

InfNo

160 - 236

160

Information number for command output

18.7.15

Operation principle

18.7.15.1

General
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system, and with a data transfer
rate up to 38400 bit/s. In IEC terminology, a primary station is a master and a secondary
station is a slave. The communication is based on a point-to-point principle. The master
must have software that can interpret IEC 60870-5-103 communication messages.

Introduction to IEC 608705103 protocol


IEC 60870-5-103 protocol functionality consists of the following functions:

Event handling
Report of analog service values (measurements)
Fault location

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1181

Section 18
Station communication

1MRK 502 066-UUS A

Command handling

Autorecloser ON/OFF
Teleprotection ON/OFF
Protection ON/OFF
LED reset
Characteristics 1 - 4 (Setting groups)

File transfer (disturbance files)


Time synchronization

For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard part 5:
Transmission protocols, and to the section 103: Companion standard for the informative
interface of protection equipment.

IEC 60870-5-103 vendor specific implementation


The signal and setting tables specify the information types supported by the IEDs with the
communication protocol IEC 60870-5-103 implemented.
The information types are supported when corresponding functions are included in the
protection and control IED.
Be aware of that different cycle times for function blocks must be
considered to ensure correct time stamping.

Commands in control direction


Commands in control direction, I103IEDCMD
Command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Table 795:

I103IEDCMD supported indications

INF

Description

19

LED Reset

23

Activate setting group 1

24

Activate setting group 2

25

Activate setting group 3

26

Activate setting group 4

Function commands in control direction, pre-defined I103CMD


1182

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Function command block in control direction with defined output signals.


Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Table 796:
INF

Pre-defined I103CMD supported indications


Description

16

Auto-recloser on/off

17

Teleprotection on/off

18

Protection on/off

Function commands in control direction, user-defined, I103USRCMD


Function command blocks in control direction with user-defined output signals.
Number of instances: 4
Function type for each function block instance in private range is selected with parameter
FunctionType.
Information number must be selected for each output signal. Default values are 1 - 8.
Table 797:
INF

I103USRCMD supported indications


Description

11)

Output signal 01

2*

Output signal 02

3*

Output signal 03

4*

Output signal 04

5*

Output signal 05

6*

Output signal 06

7*

Output signal 07

8*

Output signal 08

1) * User defined information number

Status
Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1183

Section 18
Station communication

1MRK 502 066-UUS A

Function type is selected with parameter FunctionType.


Information number is defined for each input signals.
Table 798:

I103IED supported functions

INF

Description

19

LED reset

21

TestMode

22

Local Parameter setting

23

Setting group 1 active

24

Setting group 2 active

25

Setting group 3 active

26

Setting group 4 active

Function status indications in monitor direction, user-defined, I103USRDEF


Function indication block in monitor direction with user-defined input signals.
Number of instances: 20
Function type is selected with parameter FunctionType.
Information number is required for each input signal.
Table 799:
INF

I103USRDEF Information number default values


Description

GI

TYP

COT

11)

Input signal 01

x/-

1/2

1,7,(9)

2*

Input signal 02

x/-

1/2

1,7,(9)

3*

Input signal 03

x/-

1/2

1,7,(9)

4*

Input signal 04

x/-

1/2

1,7,(9)

5*

Input signal 05

x/-

1/2

1,7,(9)

6*

Input signal 06

x/-

1/2

1,7,(9)

7*

Input signal 07

x/-

1/2

1,7,(9)

8*

Input signal 08

x/-

1/2

1,7,(9)

1) * User defined information number

Supervision indications in monitor direction, I103SUPERV


Indication block for supervision in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
1184

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Information number is defined for output signals.


Table 800:
Info. no.

I103SUPERV supported functions


Typ

GI

32

Message
Measurand supervision I

COT
1,7,9

33

Measurand supervision V

1,7,9

37

I>>back-up operation

1,7,9

38

VT fuse failure

1,7,9

46

Group warning

1,7,9

47

Group alarm

1,7,9

Ground fault indications in monitor direction, I103EF


Indication block for ground fault in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 801:
INF

I103EF supported indications


Description

51

Ground fault forward

52

Ground fault reverse

Fault indications in monitor direction, type 1, I103FltDis


Fault indication block for faults in monitor direction with defined functions.
The instance type is suitable for distance protection function.
FUNCTION TYPE parameter for each block.
INFORMATION NUMBER is defined for each input signal.
Number of instances: 1
Info. no.

Message

Supported

64

Pickup A

Yes

65

Pickup B

Yes

66

Pickup C

Yes

67

Pickup IN

Yes

84

General pickup

Yes

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1185

Section 18
Station communication

Info. no.

1MRK 502 066-UUS A

Message

Supported

69

Trip A

Yes

70

Trip B

Yes

71

Trip C

Yes

68

General trip

Yes

74

Fault forward/line

Yes

75

Fault reverse/busbar

Yes

78

Zone 1

Yes

79

Zone 2

Yes

80

Zone 3

Yes

81

Zone 4

Yes

82

Zone 5

Yes

76

Signal transmitted

Yes

77

Signal received

Yes

73

SCL, Fault location in ohm

Yes

Fault indications in monitor direction, type 2, I103FltStd


Fault indication block for faults in monitor direction with defined functions.
The instance type is suitable for line differential, transformer differential, overcurrent and
ground fault protection functions.
FUNCTION TYPE setting for each block.
INFORMATION NUMBER is defined for each input signal.
Number of instances: 1
Info. no.

Message

Supported

64

Pickup A

Yes

65

Pickup B

Yes

66

Pickup C

Yes

67

Pickup IN

Yes

84

General pickup

Yes

69

Trip A

Yes

70

Trip B

Yes

71

Trip C

Yes

68

General trip

Yes

74

Fault forward/line

Yes

75

Fault reverse/busbar

Yes

Table continues on next page


1186

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Info. no.

Message

Supported

85

Breaker failure

Yes

86

Trip measuring system A

Yes

87

Trip measuring system B

Yes

88

Trip measuring system C

Yes

89

Trip measuring system N

Yes

90

Over current trip I>

Yes

91

Over current trip I>>

Yes

92

Ground fault trip IN>

Yes

93

Ground fault trip IN>>

Yes

Autorecloser indications in monitor direction, I103AR


Indication block for autorecloser in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 802:
INF

I103AR supported indications


Description

16

Autorecloser active

128

CB on by Autorecloser

130

Autorecloser blocked

Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement CVMMXN.
Measurands in public range, I103MEAS
Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
The upper limit is the maximum value that can be encoded into the ASDU (Application
Service Data Unit). Any value higher than this value will be tagged as OVERFLOW. The
factors 1.2 and 2.4 are taken from the 103 standard and require that a rated value to use as
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1187

Section 18
Station communication

1MRK 502 066-UUS A

base exists, and then use 1.2 or 2.4 times <rated> as maxVal. You can use 2.4 times rated as
maxVal, but as there is no way to propagate value to client, the use of a scale factor on
<rated> does not make much difference.
You can configure client:client-scaled-max ::= 1.2 * <rated> or
client-scaled-max ::= 1.0 * <maxVal>
If the client has a hard-coded gain of 1.2 * <rated> then client-scaled-max ::=
1.2 times <maxVal>/1.2
Resolution is <maxVal> / 4095 and hence the lowest possible maxVal yields the best
accuracy.
Table 803:
INF

I103MEAS supported indications


Description

148

I_A

144, 145,
146, 148

I_B

148

I_C

147

IN, Neutral current

148

V_A

148

V_B

148

V_C

145, 146

V_A-V_B

147

UN, Neutral voltage

146, 148

P, active power

146, 148

Q, reactive power

148

f, frequency

Measurands in private range, I103MEASUSR


Number of instances: 3
Function type parameter for each block in private range.
Information number must be selected for measurands.

1188

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Table 804:

I103MEASUSR supported indications

INF

FUN

TYP

COT

*1)

*2)

GI
No, polled
with CL2

*3)

2,7

Description
Meas1

No, polled
with CL2

2,7

Meas2

No, polled
with CL2

2,7

Meas3

No, polled
with CL2

2,7

Meas4

No, polled
with CL2

2,7

Meas5

No, polled
with CL2

2,7

Meas6

No, polled
with CL2

2,7

Meas7

No, polled
with CL2

2,7

Meas8

No, polled
with CL2

2,7

Meas9

1) * User defined information value (PARAM.3)


2) * User defined information value (PARAM.2)
3) 9 = Measurands II, Format = Measurand II (7.3.1.8 in IEC 60870-5-103:1997), semantics per IE is defined
by semantics of connected source.

<Number of information elements> is defined by index of first input not connected.


Example: Input1, Input2, and Input4 are connected, Input3 is not connected.
<Number of information elements> will be 3 (Input3 NOT connected) -1 = 2, that is, only
Input1 and Input2 will be transmitted.
Disturbance recordings
The following elements are used in the ASDUs (Application Service Data Units) defined
in the standard.
Analog signals, 40-channels: the channel number for each channel has to be specified.
Channels used in the public range are 1 to 8 and with:

IA connected to channel 1 on disturbance function block A1RADR


IB connected to channel 2 on disturbance function block A1RADR
IC connected to channel 3 on disturbance function block A1RADR
IN connected to channel 4 on disturbance function block A1RADR
VAE connected to channel 5 on disturbance function block A1RADR

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1189

Section 18
Station communication

1MRK 502 066-UUS A

VBE connected to channel 6 on disturbance function block A1RADR


VCE connected to channel 7 on disturbance function block A1RADR
VEN connected to channel 8 on disturbance function block A1RADR

Channel number used for the remaining 32 analog signals are numbers in the private range
64 to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION TYPE
and an INFORMATION NUMBER.
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be reported
to the master. The last eight disturbances that are recorded are available for transfer to the
master. A successfully transferred disturbance (acknowledged by the master) will not be
reported to the master again.
When a new disturbance is recorded by the IED a list of available recorded disturbances
will be sent to the master, an updated list of available disturbances can be sent whenever
something has happened to disturbances in this list. For example, when a disturbance is
deleted (by other client, for example, SPA) or when a new disturbance has been recorded
or when the master has uploaded a disturbance.
Deviations from the standard
Information sent in the disturbance upload is specified by the standard; however, some of
the information are adapted to information available in disturbance recorder in the IED
series.
This section describes all data that is not exactly as specified in the standard.
ASDU23
In list of recorded disturbances (ASDU23) an information element named SOF (status
of fault) exists. This information element consists of 4 bits and indicates whether:

Bit TP: the protection equipment has tripped during the fault
Bit TM: the disturbance data are currently being transmitted
Bit TEST: the disturbance data have been recorded during normal operation or test
mode.
Bit OTEV: the disturbance data recording has been initiated by another event than
pick-up

The only information that is easily available is test-mode status. The other information is
always set (hard coded) to:

1190

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

TP

Recorded fault with trip. [1]

TM

Disturbance data waiting for transmission [0]

OTEV

Disturbance data initiated by other events [1]

Another information element in ASDU23 is the FAN (fault number). According to the
standard this is a number that is incremented when a protection function takes action. FAN
is equal to disturbance number, which is incremented for each disturbance.
ASDU26 / ASDU31
When a disturbance has been selected by the master by sending ASDU24, the protection
equipment answers by sending ASDU26, which contains an information element named
NOF (number of grid faults). This number must indicate fault number in the power
system,that is, a fault in the power system with several trip and auto-reclosing has the same
NOF (while the FAN must be incremented). NOF is just as FAN, equal to disturbance
number.

Interoperability, physical layer


Supported
Electrical Interface
EIA RS-485

No

number of loads

No

Optical interface
glass fibre

Yes

plastic fibre
Transmission speed
9600 bit/s

Yes

19200 bit/s

Yes

Link Layer
DFC-bit used

Yes

Connectors
connector F-SMA

No

connector BFOC/2.5

Yes

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1191

Section 18
Station communication

1MRK 502 066-UUS A

Interoperability, application layer


Supported
Selection of standard ASDUs in monitoring direction
ASDU

Yes

Time-tagged message

Yes

Time-tagged message with rel. time

Yes

Measurands I

Yes

Time-tagged message with rel. time

Yes

Identification

Yes

Time synchronization

Yes

End of general interrogation

Yes

Measurands II

Yes

10

Generic data

No

11

Generic identification

No

23

List of recorded disturbances

Yes

26

Ready for transm. of disturbance data

Yes

27

Ready for transm. of a channel

Yes

28

Ready for transm of tags

Yes

29

Transmission of tags

Yes

30

Transmission fo disturbance data

Yes

31

End of transmission

Yes

Selection of standard ASDUs in control direction


ASDU

Yes

Time synchronization

Yes

General interrogation

Yes

10

Generic data

No

20

General command

Yes

21

Generic command

No

24

Order for disturbance data transmission

Yes

25

Acknowledgement for distance data transmission

Yes

Selection of basic application functions

1192

Test mode

No

Blocking of monitoring direction

Yes

Disturbance data

Yes

Private data

Yes

Generic services

No

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.7.15.2

Communication ports
The serial communication module (SLM) is used for SPA/IEC 60870-5-103/DNP and
LON communication. This module is a mezzanine module, and can be placed on the
Analog/Digital conversion module (ADM). The serial communication module can have
connectors for two plastic fibre cables (snap-in) or two glass fibre cables (ST, bayonet) or
a combination of plastic and glass fibre. Three different types are available depending on
type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing optical
fibre to the TX transmitter output. When the fibre optic cables are laid out, pay special
attention to the instructions concerning the handling and connection of the optical fibres.
The module is identified with a number on the label on the module.

18.7.16

Technical data
Table 805:

IEC 60870-5-103 communication protocol

Function

Value

Protocol

IEC 60870-5-103

Communication speed

9600, 19200 Bd

18.8

Horizontal communication via GOOSE for interlocking


GOOSEINTLKRCV

18.8.1

Functionality
GOOSE communication can be used for exchanging information between IEDs via the
IEC 61850-8-1 station communication bus. This is typically used for sending apparatus
position indications for interlocking or reservation signals for 1-of-n control. GOOSE can
also be used to exchange any boolean, integer, double point and analog measured values
between IEDs.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1193

Section 18
Station communication
18.8.2

1MRK 502 066-UUS A

Function block

GOOSEINTLKRCV
BLOCK

^RESREQ
^RESGRANT
^APP1_OP
^APP1_CL
APP1VAL
^APP2_OP
^APP2_CL
APP2VAL
^APP3_OP
^APP3_CL
APP3VAL
^APP4_OP
^APP4_CL
APP4VAL
^APP5_OP
^APP5_CL
APP5VAL
^APP6_OP
^APP6_CL
APP6VAL
^APP7_OP
^APP7_CL
APP7VAL
^APP8_OP
^APP8_CL
APP8VAL
^APP9_OP
^APP9_CL
APP9VAL
^APP10_OP
^APP10_CL
APP10VAL
^APP11_OP
^APP11_CL
APP11VAL
^APP12_OP
^APP12_CL
APP12VAL
^APP13_OP
^APP13_CL
APP13VAL
^APP14_OP
^APP14_CL
APP14VAL
^APP15_OP
^APP15_CL
APP15VAL
COMMVALID
TEST
IEC07000048.vsd

IEC07000048 V3 EN

Figure 541:

1194

GOOSEINTLKRCV function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.8.3

Signals
Table 806:
Name
BLOCK

Table 807:
Name

GOOSEINTLKRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of output signals

GOOSEINTLKRCV Output signals


Type

Description

RESREQ

BOOLEAN

Reservation request

RESGRANT

BOOLEAN

Reservation granted

APP1_OP

BOOLEAN

Apparatus 1 position is open

APP1_CL

BOOLEAN

Apparatus 1 position is closed

APP1VAL

BOOLEAN

Apparatus 1 position is valid

APP2_OP

BOOLEAN

Apparatus 2 position is open

APP2_CL

BOOLEAN

Apparatus 2 position is closed

APP2VAL

BOOLEAN

Apparatus 2 position is valid

APP3_OP

BOOLEAN

Apparatus 3 position is open

APP3_CL

BOOLEAN

Apparatus 3 position is closed

APP3VAL

BOOLEAN

Apparatus 3 position is valid

APP4_OP

BOOLEAN

Apparatus 4 position is open

APP4_CL

BOOLEAN

Apparatus 4 position is closed

APP4VAL

BOOLEAN

Apparatus 4 position is valid

APP5_OP

BOOLEAN

Apparatus 5 position is open

APP5_CL

BOOLEAN

Apparatus 5 position is closed

APP5VAL

BOOLEAN

Apparatus 5 position is valid

APP6_OP

BOOLEAN

Apparatus 6 position is open

APP6_CL

BOOLEAN

Apparatus 6 position is closed

APP6VAL

BOOLEAN

Apparatus 6 position is valid

APP7_OP

BOOLEAN

Apparatus 7 position is open

APP7_CL

BOOLEAN

Apparatus 7 position is closed

APP7VAL

BOOLEAN

Apparatus 7 position is valid

APP8_OP

BOOLEAN

Apparatus 8 position is open

APP8_CL

BOOLEAN

Apparatus 8 position is closed

APP8VAL

BOOLEAN

Apparatus 8 position is valid

APP9_OP

BOOLEAN

Apparatus 9 position is open

APP9_CL

BOOLEAN

Apparatus 9 position is closed

APP9VAL

BOOLEAN

Apparatus 9 position is valid

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1195

Section 18
Station communication

1MRK 502 066-UUS A

Name

Type
BOOLEAN

Apparatus 10 position is open

APP10_CL

BOOLEAN

Apparatus 10 position is closed

APP10VAL

BOOLEAN

Apparatus 10 position is valid

APP11_OP

BOOLEAN

Apparatus 11 position is open

APP11_CL

BOOLEAN

Apparatus 11 position is closed

APP11VAL

BOOLEAN

Apparatus 11 position is valid

APP12_OP

BOOLEAN

Apparatus 12 position is open

APP12_CL

BOOLEAN

Apparatus 12 position is closed

APP12VAL

BOOLEAN

Apparatus 12 position is valid

APP13_OP

BOOLEAN

Apparatus 13 position is open

APP13_CL

BOOLEAN

Apparatus 13 position is closed

APP13VAL

BOOLEAN

Apparatus 13 position is valid

APP14_OP

BOOLEAN

Apparatus 14 position is open

APP14_CL

BOOLEAN

Apparatus 14 position is closed

APP14VAL

BOOLEAN

Apparatus 14 position is valid

APP15_OP

BOOLEAN

Apparatus 15 position is open

APP15_CL

BOOLEAN

Apparatus 15 position is closed

APP15VAL

BOOLEAN

Apparatus 15 position is valid

COMMVALID

BOOLEAN

Communication Valid

TEST

BOOLEAN

Test Output

18.8.4

Settings

Table 808:

GOOSEINTLKRCV Non group settings (basic)

Name
Operation

1196

Description

APP10_OP

Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.9

Goose binary receive GOOSEBINRCV

18.9.1

Function block
GOOSEBINRCV
BLOCK

^OUT1
DVALID1
^OUT2
DVALID2
^OUT3
DVALID3
^OUT4
DVALID4
^OUT5
DVALID5
^OUT6
DVALID6
^OUT7
DVALID7
^OUT8
DVALID8
^OUT9
DVALID9
^OUT10
DVALID10
^OUT11
DVALID11
^OUT12
DVALID12
^OUT13
DVALID13
^OUT14
DVALID14
^OUT15
DVALID15
^OUT16
DVALID16
COMMVALID
TEST
IEC07000047.vsd

IEC07000047 V3 EN

Figure 542:

18.9.2

GOOSEBINRCV function block

Signals
Table 809:
Name
BLOCK

Table 810:
Name

GOOSEBINRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of output signals

GOOSEBINRCV Output signals


Type

Description

OUT1

BOOLEAN

Binary output 1

DVALID1

BOOLEAN

Valid data on binary output 1

OUT2

BOOLEAN

Binary output 2

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1197

Section 18
Station communication

Name

1198

1MRK 502 066-UUS A

Type

Description

DVALID2

BOOLEAN

Valid data on binary output 2

OUT3

BOOLEAN

Binary output 3

DVALID3

BOOLEAN

Valid data on binary output 3

OUT4

BOOLEAN

Binary output 4

DVALID4

BOOLEAN

Valid data on binary output 4

OUT5

BOOLEAN

Binary output 5

DVALID5

BOOLEAN

Valid data on binary output 5

OUT6

BOOLEAN

Binary output 6

DVALID6

BOOLEAN

Valid data on binary output 6

OUT7

BOOLEAN

Binary output 7

DVALID7

BOOLEAN

Valid data on binary output 7

OUT8

BOOLEAN

Binary output 8

DVALID8

BOOLEAN

Valid data on binary output 8

OUT9

BOOLEAN

Binary output 9

DVALID9

BOOLEAN

Valid data on binary output 9

OUT10

BOOLEAN

Binary output 10

DVALID10

BOOLEAN

Valid data on binary output 10

OUT11

BOOLEAN

Binary output 11

DVALID11

BOOLEAN

Valid data on binary output 11

OUT12

BOOLEAN

Binary output 12

DVALID12

BOOLEAN

Valid data on binary output 12

OUT13

BOOLEAN

Binary output 13

DVALID13

BOOLEAN

Valid data on binary output 13

OUT14

BOOLEAN

Binary output 14

DVALID14

BOOLEAN

Valid data on binary output 14

OUT15

BOOLEAN

Binary output 15

DVALID15

BOOLEAN

Valid data on binary output 15

OUT16

BOOLEAN

Binary output 16

DVALID16

BOOLEAN

Valid data on binary output 16

COMMVALID

BOOLEAN

Communication Valid

TEST

BOOLEAN

Test Output

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.9.3
Table 811:
Name
Operation

Settings
GOOSEBINRCV Non group settings (basic)
Values (Range)

Unit

Disabled
Enabled

Step

Default

Description

Disabled

Operation Disabled/Enabled

18.10

GOOSE function block to receive a double point value


GOOSEDPRCV

18.10.1

Identification
Function description

IEC 61850
identification

GOOSE function block to receive a


double point value

18.10.2

IEC 60617
identification

GOOSEDPRCV

ANSI/IEEE C37.2
device number
-

Functionality
GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.

18.10.3

Function block
GOOSEDPRCV
BLOCK

^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249-1-en.vsd

IEC10000249 V1 EN

Figure 543:

18.10.4

GOOSEDPRCV function block

Signals
Table 812:
Name
BLOCK

GOOSEDPRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1199

Section 18
Station communication

1MRK 502 066-UUS A

Table 813:

GOOSEDPRCV Output signals

Name

18.10.5
Table 814:
Name
Operation

18.10.6

Type

Description

DPOUT

INTEGER

Double point output

DATAVALID

BOOLEAN

Data valid for double point output

COMMVALID

BOOLEAN

Communication valid for double point output

TEST

BOOLEAN

Test output

Settings
GOOSEDPRCV Non group settings (basic)
Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the double point values.

The implementation for IEC61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.

1200

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.11

GOOSE function block to receive an integer value


GOOSEINTRCV

18.11.1

Identification
Function description

IEC 61850
identification

GOOSE function block to receive an


integer value

18.11.2

IEC 60617
identification

GOOSEINTRCV

ANSI/IEEE C37.2
device number
-

Functionality
GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via
GOOSE.

18.11.3

Function block
BLOCK

GOOSEINTRCV
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250-1-en.vsd

IEC10000250 V1 EN

Figure 544:

18.11.4

GOOSEINTRCV function block

Signals
Table 815:
Name
BLOCK

Table 816:
Name

GOOSEINTRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of function

GOOSEINTRCV Output signals


Type

Description

INTOUT

INTEGER

Integer output

DATAVALID

BOOLEAN

Data valid for integer output

COMMVALID

BOOLEAN

Communication valid for integer output

TEST

BOOLEAN

Test output

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1201

Section 18
Station communication
18.11.5
Table 817:
Name
Operation

18.11.6

1MRK 502 066-UUS A

Settings
GOOSEINTRCV Non group settings (basic)
Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the integer values.

The implementation for IEC61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.

18.12

GOOSE function block to receive a measurand value


GOOSEMVRCV

18.12.1

Identification
Function description
GOOSE function block to receive a
measurand value

1202

IEC 61850
identification
GOOSEMVRCV

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.12.2

Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.

18.12.3

Function block
BLOCK

GOOSEMVRCV
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-1-en.vsd

IEC10000251 V1 EN

Figure 545:

18.12.4

GOOSEMVRCV function block

Signals
Table 818:

GOOSEMVRCV Input signals

Name

Type

BLOCK

BOOLEAN

Table 819:

Table 820:
Name
Operation

18.12.6

Description
Block of function

GOOSEMVRCV Output signals

Name

18.12.5

Default

Type

Description

MVOUT

REAL

Measurand value output

DATAVALID

BOOLEAN

Data valid for measurand value output

COMMVALID

BOOLEAN

Communication valid for measurand value output

TEST

BOOLEAN

Test output

Settings
GOOSEMVRCV Non group settings (basic)
Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1203

Section 18
Station communication

1MRK 502 066-UUS A

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the measured value.

The implementation for IEC61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.

18.13

GOOSE function block to receive a single point value


GOOSESPRCV

18.13.1

Identification
Function description
GOOSE function block to receive a
single point value

18.13.2

IEC 61850
identification
GOOSESPRCV

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
GOOSESPRCV is used to receive a single point value using IEC61850 protocol via
GOOSE.

18.13.3

Function block
GOOSESPRCV
BLOCK

^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd

IEC10000248 V1 EN

Figure 546:

1204

GOOSESPRCV function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.13.4

Signals
Table 821:

GOOSESPRCV Input signals

Name

Type

BLOCK

BOOLEAN

Table 822:

Table 823:
Name
Operation

18.13.6

Description
Block of function

GOOSESPRCV Output signals

Name

18.13.5

Default

Type

Description

SPOUT

BOOLEAN

Single point output

DATAVALID

BOOLEAN

Data valid for single point output

COMMVALID

BOOLEAN

Communication valid for single point output

TEST

BOOLEAN

Test output

Settings
GOOSESPRCV Non group settings (basic)
Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Disabled

Description
Operation Disabled/Enabled

Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the binary single point values.

The implementation for IEC61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1205

Section 18
Station communication

18.14

1MRK 502 066-UUS A

MULTICMDRCV and MULTICMDSND


Function description

18.14.1

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Multiple command and receive

MULTICMDRCV

Multiple command and send

MULTICMDSND

Functionality
The IED provides two function blocks enabling several IEDs to send and receive signals
via the interbay bus. The sending function block, MULTICMDSND, takes 16 binary
inputs. LON enables these to be transmitted to the equivalent receiving function block,
MULTICMDRCV, which has 16 binary outputs.

18.14.2

Design

18.14.2.1

General
The common behavior for all 16 outputs of the MULTICMDRCV is set to either of two
modes: Steady or Pulse.

1206

1 = Steady: This mode simply forwards the received signals to the binary outputs.
2 = Pulse: When a received signal transitions from 0 (zero) to 1 (one), a pulse with a
duration of exactly one execution cycle is triggered on the corresponding binary
output. This means that no connected function block may have a cycle time that is
higher than the execution cycle time of the particular MULTICMDRCV instance.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.14.3

Function block
MULTICMDRCV
BLOCK

ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID
IEC06000007-2-en.vsd

IEC06000007 V2 EN

Figure 547:

MULTICMDRCV function block

MULTICMDSND
BLOCK
ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC06000008-2-en.vsd
IEC06000008 V2 EN

Figure 548:

18.14.4

MULTICMDSND function block

Signals
Table 824:
Name
BLOCK

MULTICMDRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of function

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1207

Section 18
Station communication

Table 825:
Name

1MRK 502 066-UUS A

MULTICMDSND Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

BOOLEAN

Input 1

INPUT2

BOOLEAN

Input 2

INPUT3

BOOLEAN

Input 3

INPUT4

BOOLEAN

Input 4

INPUT5

BOOLEAN

Input 5

INPUT6

BOOLEAN

Input 6

INPUT7

BOOLEAN

Input 7

INPUT8

BOOLEAN

Input 8

INPUT9

BOOLEAN

Input 9

INPUT10

BOOLEAN

Input 10

INPUT11

BOOLEAN

Input 11

INPUT12

BOOLEAN

Input 12

INPUT13

BOOLEAN

Input 13

INPUT14

BOOLEAN

Input 14

INPUT15

BOOLEAN

Input 15

INPUT16

BOOLEAN

Input 16

Table 826:
Name

MULTICMDRCV Output signals


Type

Description

ERROR

BOOLEAN

MultiReceive error

NEWDATA

BOOLEAN

New data is received

OUTPUT1

BOOLEAN

Output 1

OUTPUT2

BOOLEAN

Output 2

OUTPUT3

BOOLEAN

Output 3

OUTPUT4

BOOLEAN

Output 4

OUTPUT5

BOOLEAN

Output 5

OUTPUT6

BOOLEAN

Output 6

OUTPUT7

BOOLEAN

Output 7

OUTPUT8

BOOLEAN

Output 8

OUTPUT9

BOOLEAN

Output 9

OUTPUT10

BOOLEAN

Output 10

OUTPUT11

BOOLEAN

Output 11

OUTPUT12

BOOLEAN

Output 12

Table continues on next page

1208

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

Name

Type
BOOLEAN

Output 13

OUTPUT14

BOOLEAN

Output 14

OUTPUT15

BOOLEAN

Output 15

OUTPUT16

BOOLEAN

Output 16

VALID

BOOLEAN

Output data is valid

Table 827:

MULTICMDSND Output signals

Name

Type

ERROR

18.14.5
Table 828:
Name

Description

OUTPUT13

Description

BOOLEAN

MultiSend error

Settings
MULTICMDRCV Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

tMaxCycleTime

0.050 - 200.000

0.001

11.000

Maximum cycle time between receptions of


input data

tMinCycleTime

0.000 - 200.000

0.001

0.000

Minimum cycle time between receptions of


input data

Mode

Steady
Pulsed

Steady

Mode for output signals

tPulseTime

0.000 - 60.000

0.001

0.200

Pulse length for multi command outputs

Table 829:
Name

MULTICMDSND Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

tMaxCycleTime

0.000 - 200.000

0.001

5.000

Maximum time interval between transmission


of output data

tMinCycleTime

0.000 - 200.000

0.001

0.000

Minimum time interval between transmission of


output data

18.14.6

Operation principle
There are 10 instances of the MULTICMDSND function block. The first two are fast (8
ms cycle time) while the others are slow (100 ms cycle time). Each instance has 16 binary
inputs, to which 16 independent signals can be connected. Connected signals are sent
through MULTICMDSND to the receiving equivalent, MULTICMDRCV, located on a
different IED.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1209

Section 18
Station communication

1MRK 502 066-UUS A

The MULTICMDRCV function block has 16 binary outputs, all controlled through the
command block of one or many MULTICMDSND function blocks. There are 60
instances of the MULTICMDRCV where the first 12 are fast (8 ms), and the others are
slow (100 ms). Additionally, the MULTICMDRCV has a supervision function, which
sets the output connector "VALID" to 0 (zero) if its block does not receive any data within
the time defined by tMaxCycleTime.
LON connections are established using LON network tool (LNT).

18.15

Security events on protocols SECALARM

18.15.1

Security alarm SECALARM

18.15.1.1

Signals
Table 830:

SECALARM Output signals

Name

18.15.1.2
Table 831:
Name
Operation

Type

Description

EVENTID

INTEGER

EventId of the generated security event

SEQNUMBER

INTEGER

Sequence number of the generated security event

Settings
SECALARM Non group settings (basic)
Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Enabled

Description
Operation On/Off

18.16

Activity logging parameters ACTIVLOG

18.16.1

Activity logging ACTIVLOG


ACTIVLOG contains all settings for activity logging.
There can be 6 external log servers to send syslog events to. Each server can be configured
with IP address; IP port number and protocol format. The format can be either syslog
(RFC 5424) or Common Event Format (CEF) from ArcSight.

1210

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 18
Station communication

1MRK 502 066-UUS A

18.16.2
Table 832:
Name

Settings
ACTIVLOG Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

ExtLogSrv1Type

Disabled
ExtLogSrv1Type
SYSLOG TCP/IP
CEF TCP/IP

Disabled

External log server 1 type

ExtLogSrv1Port

1 - 65535

514

External log server 1 port number

ExtLogSrv1IP

0 - 18

IP
Address

127.0.0.1

External log server 1 IP-address

ExtLogSrv2Type

Disabled
ExtLogSrv1Type
SYSLOG TCP/IP
CEF TCP/IP

Disabled

External log server 2 type

ExtLogSrv2Port

1 - 65535

514

External log server 2 port number

ExtLogSrv2IP

0 - 18

IP
Address

127.0.0.1

External log server 2 IP-address

ExtLogSrv3Type

Disabled
ExtLogSrv1Type
SYSLOG TCP/IP
CEF TCP/IP

Disabled

External log server 3 type

ExtLogSrv3Port

1 - 65535

514

External log server 3 port number

ExtLogSrv3IP

0 - 18

IP
Address

127.0.0.1

External log server 3 IP-address

ExtLogSrv4Type

Disabled
ExtLogSrv1Type
SYSLOG TCP/IP
CEF TCP/IP

Disabled

External log server 4 type

ExtLogSrv4Port

1 - 65535

514

External log server 4 port number

ExtLogSrv4IP

0 - 18

IP
Address

127.0.0.1

External log server 4 IP-address

ExtLogSrv5Type

Disabled
ExtLogSrv1Type
SYSLOG TCP/IP
CEF TCP/IP

Disabled

External log server 5 type

ExtLogSrv5Port

1 - 65535

514

External log server 5 port number

ExtLogSrv5IP

0 - 18

IP
Address

127.0.0.1

External log server 5 IP-address

ExtLogSrv6Type

Disabled
ExtLogSrv1Type
SYSLOG TCP/IP
CEF TCP/IP

Disabled

External log server 6 type

ExtLogSrv6Port

1 - 65535

514

External log server 6 port number

ExtLogSrv6IP

0 - 18

IP
Address

127.0.0.1

External log server 6 IP-address

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1211

1212

Section 19
Remote communication

1MRK 502 066-UUS A

Section 19

Remote communication

19.1

Binary signal transfer

19.1.1

Identification
Function description

19.1.2

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Binary signal transfer

BinSignReceive

Binary signal transfer

BinSignTransm

Functionality
The remote end data communication is used either for the transmission of current values
with a maximum of 8 binary signals in the line differential protection IED, or for the
transmission of only binary signals (up to 192) in the other IEDs. The binary signals are
freely configurable and can, thus, be used for any purpose, for example, communication
scheme related signals, transfer trip and/or other binary signals between IEDs.
Communication between two IEDs requires that each IED is equipped with a Line Data
Communication Module (LCDM). The LDCMs then act as interfaces to a 64 kbit/s
communication channel for duplex communication between the IEDs.
The IED can be equipped with up to two short range or medium range LDCMs.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1213

Section 19
Remote communication
19.1.3

1MRK 502 066-UUS A

Function block
LDCMRecBinStat1
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
REMCOMF
LOWLEVEL
IEC07000043-2-en.vsd
IEC07000043 V2 EN

LDCMRecBinStat2
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
IEC07000044-2-en.vsd
IEC07000044 V2 EN

Figure 549:

LDCMRecBinStat function blocks

LDCMRecBinStat3
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
IEC05000451-2-en.vsd
IEC05000451 V2 EN

Figure 550:

1214

LDCMRecBinStat function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 19
Remote communication

1MRK 502 066-UUS A

19.1.4

Signals
Table 833:
Name

LDCMRecBinStat1 Output signals


Type

Description

COMFAIL

BOOLEAN

Detected error in the differential communication

YBIT

BOOLEAN

Detected error in remote end with incoming message

NOCARR

BOOLEAN

No carrier is detected in the incoming message

NOMESS

BOOLEAN

No start and stop flags identified for the incoming


message

ADDRERR

BOOLEAN

Incoming message from non-valid address

LNGTHERR

BOOLEAN

Wrong length of the incoming message

CRCERROR

BOOLEAN

Identified error by CRC check in incoming message

REMCOMF

BOOLEAN

Remote terminal indicates problem with received


message

LOWLEVEL

BOOLEAN

Low signal level on the receive link

Table 834:
Name

LDCMRecBinStat2 Output signals


Type

Description

CH1

STRING

Remote communication channel 1

CH2

STRING

Remote communication channel 2

CH3

STRING

Remote communication channel 3

CH4

STRING

Remote communication channel 4

COMFAIL

BOOLEAN

Detected error in the differential communication

YBIT

BOOLEAN

Detected error in remote end with incoming message

NOCARR

BOOLEAN

No carrier is detected in the incoming message

NOMESS

BOOLEAN

No start and stop flags identified for the incoming


message

ADDRERR

BOOLEAN

Incoming message from non-valid address

LNGTHERR

BOOLEAN

Wrong length of the incoming message

CRCERROR

BOOLEAN

Identified error by CRC check in incoming message

TRDELERR

BOOLEAN

Transmission time is longer than permitted

SYNCERR

BOOLEAN

Error in echo synchronization

REMCOMF

BOOLEAN

Remote terminal indicates problem with received


message

REMGPSER

BOOLEAN

Remote terminal indicates problem with GPS


synchronization

SUBSTITU

BOOLEAN

Link error, values are substituted

LOWLEVEL

BOOLEAN

Low signal level on the receive link

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1215

Section 19
Remote communication

1MRK 502 066-UUS A

Table 835:

LDCMRecBinStat3 Output signals

Name

Type
STRING

Remote communication channel 1

CH2

STRING

Remote communication channel 2

CH3

STRING

Remote communication channel 3

CH4

STRING

Remote communication channel 4

COMFAIL

BOOLEAN

Detected error in the differential communication

YBIT

BOOLEAN

Detected error in remote end with incoming message

NOCARR

BOOLEAN

No carrier is detected in the incoming message

NOMESS

BOOLEAN

No start and stop flags identified for the incoming


message

ADDRERR

BOOLEAN

Incoming message from non-valid address

LNGTHERR

BOOLEAN

Wrong length of the incoming message

CRCERROR

BOOLEAN

Identified error by CRC check in incoming message

TRDELERR

BOOLEAN

Transmission time is longer than permitted

SYNCERR

BOOLEAN

Error in echo synchronization

REMCOMF

BOOLEAN

Remote terminal indicates problem with received


message

REMGPSER

BOOLEAN

Remote terminal indicates problem with GPS


synchronization

SUBSTITU

BOOLEAN

Link error, values are substituted

LOWLEVEL

BOOLEAN

Low signal level on the receive link

19.1.5

Settings

Table 836:

LDCMRecBinStat1 Non group settings (basic)

Name

Description

CH1

Values (Range)

Unit

Step

Default

Description

ChannelMode

Blocked
Normal
OutOfService

Normal

Channel mode of LDCM, 0=OFF, 1=ON,


2=OutOfService

TerminalNo

0 - 255

Terminal number used for line differential


communication

RemoteTermNo

0 - 255

Terminal number on remote terminal

CommSync

Slave
Master

Slave

Com Synchronization mode of LDCM,


0=Slave, 1=Master

OptoPower

LowPower
HighPower

LowPower

Transmission power for LDCM, 0=Low, 1=High

Table continues on next page

1216

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 19
Remote communication

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

ComFailAlrmDel

5 - 500

ms

100

Time delay before communication error signal


is activated

ComFailResDel

5 - 500

ms

100

Reset delay before communication error signal


is reset

InvertPolX21

Disabled
Enabled

Disabled

Invert polarization for X21 communication

Table 837:
Name

LDCMRecBinStat2 Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ChannelMode

Blocked
Normal
OutOfService

Normal

Channel mode of LDCM, 0=OFF, 1=ON,


2=OutOfService

TerminalNo

0 - 255

Terminal number used for line differential


communication

RemoteTermNo

0 - 255

Terminal number on remote terminal

DiffSync

Echo
GPS

Echo

Diff Synchronization mode of LDCM, 0=ECHO,


1=GPS

GPSSyncErr

Block
Echo

Block

Operation mode when GPS synchroniation


signal is lost

CommSync

Slave
Master

Slave

Com Synchronization mode of LDCM,


0=Slave, 1=Master

OptoPower

LowPower
HighPower

LowPower

Transmission power for LDCM, 0=Low, 1=High

TransmCurr

CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2

CT-GRP1

Summation mode for transmitted current


values

ComFailAlrmDel

5 - 500

ms

100

Time delay before communication error signal


is activated

ComFailResDel

5 - 500

ms

100

Reset delay before communication error signal


is reset

RedChSwTime

5 - 500

ms

Time delay before switching in redundant


channel

RedChRturnTime

5 - 500

ms

100

Time delay before switching back from


redundant channel

AsymDelay

-20.00 - 20.00

ms

0.01

0.00

Asymmetric delay when communication use


echo synch.

AnalogLatency

2 - 20

Latency between local analogue data and


transmitted

remAinLatency

2 - 20

Analog latency of remote terminal

MaxTransmDelay

0 - 40

ms

20

Max allowed transmission delay

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1217

Section 19
Remote communication

Name

Values (Range)

1MRK 502 066-UUS A

Unit

Step

Default

Description

CompRange

0-10kA
0-25kA
0-50kA
0-150kA

0-25kA

Compression range

MaxtDiffLevel

200 - 2000

us

600

Maximum time diff for ECHO back-up

DeadbandtDiff

200 - 1000

us

300

Deadband for t Diff

InvertPolX21

Disabled
Enabled

Disabled

Invert polarization for X21 communication

Table 838:
Name

LDCMRecBinStat3 Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ChannelMode

Blocked
Normal
OutOfService

Normal

Channel mode of LDCM, 0=OFF, 1=ON,


2=OutOfService

TerminalNo

0 - 255

Terminal number used for line differential


communication

RemoteTermNo

0 - 255

Terminal number on remote terminal

DiffSync

Echo
GPS

Echo

Diff Synchronization mode of LDCM, 0=ECHO,


1=GPS

GPSSyncErr

Block
Echo

Block

Operation mode when GPS synchroniation


signal is lost

CommSync

Slave
Master

Slave

Com Synchronization mode of LDCM,


0=Slave, 1=Master

OptoPower

LowPower
HighPower

LowPower

Transmission power for LDCM, 0=Low, 1=High

TransmCurr

CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
RedundantChannel

CT-GRP1

Summation mode for transmitted current


values

ComFailAlrmDel

5 - 500

ms

100

Time delay before communication error signal


is activated

ComFailResDel

5 - 500

ms

100

Reset delay before communication error signal


is reset

RedChSwTime

5 - 500

ms

Time delay before switching in redundant


channel

RedChRturnTime

5 - 500

ms

100

Time delay before switching back from


redundant channel

AsymDelay

-20.00 - 20.00

ms

0.01

0.00

Asymmetric delay when communication use


echo synch.

AnalogLatency

2 - 20

Latency between local analogue data and


transmitted

remAinLatency

2 - 20

Analog latency of remote terminal

Table continues on next page

1218

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 19
Remote communication

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

Description

MaxTransmDelay

0 - 40

ms

20

Max allowed transmission delay

CompRange

0-10kA
0-25kA
0-50kA
0-150kA

0-25kA

Compression range

MaxtDiffLevel

200 - 2000

us

600

Maximum time diff for ECHO back-up

DeadbandtDiff

200 - 1000

us

300

Deadband for t Diff

InvertPolX21

Disabled
Enabled

Disabled

Invert polarization for X21 communication

19.1.6

Monitored data
Table 839:
Name
CommStatus

Table 840:
Name
CommStatus

LDCMRecBinStat1 Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=SyncErr
2=No RXD
3=LocalGPSErr
4=RemGPSErr
5=LocAndRemG
PSErr
6=LocalADErr
7=RemADErr
8=LocAndRemA
DErr
9=AddressErr
10=FreqConfErr
11=LatencyConf
Err

Unit
-

Description
Status of communication link

LDCMRecBinStat2 Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=SyncErr
2=No RXD
3=LocalGPSErr
4=RemGPSErr
5=LocAndRemG
PSErr
6=LocalADErr
7=RemADErr
8=LocAndRemA
DErr
9=AddressErr
10=FreqConfErr
11=LatencyConf
Err

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Unit
-

Description
Status of communication link

1219

Section 19
Remote communication

Table 841:
Name
CommStatus

19.1.7

1MRK 502 066-UUS A

LDCMRecBinStat3 Monitored data


Type
BOOLEAN

Values (Range)

Unit

0=Ok
1=SyncErr
2=No RXD
3=LocalGPSErr
4=RemGPSErr
5=LocAndRemG
PSErr
6=LocalADErr
7=RemADErr
8=LocAndRemA
DErr
9=AddressErr
10=FreqConfErr
11=LatencyConf
Err

Description
Status of communication link

Operation principle
The communication is made on standard ITU (CCITT) PCM digital 64 kbit/s channels. It
is a two-way communication where telegrams are sent every 5 ms (same in 50 Hz and 60
Hz), exchanging information between two IEDs. The format used is C37.94 and one
telegram consists of start and stop flags, address, data to be transmitted, Cyclic
Redundancy Check (CRC) and Yellow bit (which is associated with C37.94).
Start
flag
8 bits

Information
n x 16 bits

CRC

Stop
flag

16 bits

8 bits

en01000134.vsd
IEC01000134 V1 EN

Figure 551:

Data message structure

The start and stop flags are the 0111 1110 sequence (7E hexadecimal), defined in the
HDLC standard. The CRC is designed according to the standard CRC16 definition. The
optional address field in the HDLC frame is not used instead a separate addressing is
included in the data field.
The address field is used for checking that the received message originates from the
correct equipment. There is always a risk that multiplexers occasionally mix the messages
up. Each terminal in the system is given a number. The terminal is then programmed to
accept messages from a specific terminal number. If the CRC function detects a faulty
message, the message is thrown away and not used in the evaluation.
When the communication is used for line differential purpose, the transmitted data
consists of three currents, clock information, trip-, block- and alarm-signals and eight

1220

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 19
Remote communication

1MRK 502 066-UUS A

binary signals which can be used for any purpose. The three currents are represented as
sampled values.
When the communication is used exclusively for binary signals, the full data capacity of
the communication channel is used for the binary signal purpose which gives the capacity
of 192 signals.

19.2

Transmission of analog data from LDCM


LDCMTransmit

19.2.1

Function block
LDCMTRN
^CT1L1
^CT1L2
^CT1L3
^CT1N
^CT2L1
^CT2L2
^CT2L3
^CT2N
IEC10000017-1-en.vsd
IEC10000017 V1 EN

Figure 552:

LDCMTransmit function block

The function blocks are not represented in the Application Configuration


tool except for the LDCMTRN function block that is visible in ACT. The
signals appear only in the Signal Matrix tool when a LDCM is included in
the configuration with the function selector tool.

19.2.2

Signals
Table 842:
Name

LDCMTRN Input signals


Type

Default

Description

CT1L1

STRING

Input to be used for transmit CT-group1 line L1 to remote


end

CT1L2

STRING

Input to be used for transmit CT-group1 line L2 to remote


end

CT1L3

STRING

Input to be used for transmit CT-group1 line L3 to remote


end

CT1N

STRING

Input to be used for transmit CT-group1 neutral N to


remote end

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1221

Section 19
Remote communication

Name

1222

1MRK 502 066-UUS A

Type

Default

Description

CT2L1

STRING

Input to be used for transmit CT-group2 line L1 to remote


end

CT2L2

STRING

Input to be used for transmit CT-group2 line L2 to remote


end

CT2L3

STRING

Input to be used for transmit CT-group2 line L3 to remote


end

CT2N

STRING

Input to be used for transmit CT-group2 neutral N to


remote end

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Section 20

Basic IED functions

20.1

Authority check ATHCHCK

20.1.1

Identification
Function description
Authority check

20.1.2

IEC 61850
identification
ATHCHCK

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
To safeguard the interests of our customers, both the IED and the tools that are accessing
the IED are protected, by means of authorization handling. The authorization handling of
the IED and the PCM600 is implemented at both access points to the IED:

local, through the local HMI


remote, through the communication ports

The IED users can be created, deleted and edited with PCM600 IED user management
tool.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1223

Section 20
Basic IED functions

1MRK 502 066-UUS A

IEC12000202-2-en.vsd
IEC12000202 V2 EN

Figure 553:

20.1.3

PCM600 user management tool

Operation principle
There are different levels (or types) of users that can access or operate different areas of
the IED and tools functionality. The pre-defined user types are given in Table 843.
Ensure that the user logged on to the IED has the access required when
writing particular data to the IED from PCM600.
The meaning of the legends used in the table:

1224

R= Read
W= Write
- = No access rights

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Table 843:

Pre-defined user types

Access rights

Guest

Super User

SPA Guest

System
Operator

Protection
Engineer

Design
Engineer

User
Administrator

Basic setting possibilities (change


setting group, control settings, limit
supervision)

R/W

R/W

R/W

R/W

Advanced setting possibilities (for


example protection settings)

R/W

R/W

R/W

Basic control possibilities (process


control, no bypass)

R/W

R/W

R/W

R/W

R/W

Advanced control possibilities (process


control including interlock trigg)

R/W

R/W

R/W

R/W

R/W

Basic command handling (for example


clear LEDs, manual trigg)

R/W

R/W

R/W

R/W

Advanced command handling (for


example clear disturbance record)

R/W

R/W

R/W

R/W

Basic configuration possibilities (I/Oconfiguration in SMT)

R/W

R/W

R/W

Advanced configuration possibilities


(application configuration including
SMT, GDE and CMT)

R/W

R/W

R/W

File loading (database loading from


XML-file)

R/W

R/W

R/W

File dumping (database dumping to


XML-file)

R/W

R/W

R/W

File transfer (FTP file transfer)

R/W

R/W

R/W

R/W

R/W

File transfer (limited) (FTP file transfer)

R/W

R/W

R/W

R/W

R/W

File Transfer (SPA File Transfer)

R/W

R/W

Database access for normal user

R/W

R/W

R/W

R/W

R/W

User administration (user management


FTP File Transfer)

R/W

R/W

User administration (user management


SPA File Transfer)

R/W

The IED users can be created, deleted and edited only with the IED User Management
within PCM600. The user can only LogOn or LogOff on the local HMI on the IED, there
are no users, groups or functions that can be defined on local HMI.
If the IED is Central Account Management enabled, users can only be
created, deleted or edited in the Central Account Management server. In
that case, only the user rights can be edited using the PCM600 tool. See
Cyber Security Deployment Guidelines manual.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1225

Section 20
Basic IED functions

1MRK 502 066-UUS A

Only characters A - Z, a - z and 0 - 9 should be used in user names and


passwords.
The maximum of characters in a password is 18.

At least one user must be included in the UserAdministrator group to be


able to write users, created in PCM600, to IED.
At delivery the default user is the SuperUser. No Log on is required to operate the IED
until a user has been created with the IED User Management..
Once a user is created and downloaded to the IED, that user can perform a Log on,
introducing the password assigned in the tool.
If there is no user created, an attempt to log on will display a message box: No user
defined!
If one user leaves the IED without logging off, then after the timeout (set in Main menu/
Settings/General Settings/HMI/Screen/Display Timeout) elapses, the IED returns to
Guest state, when only reading is possible. The display time out is set to 60 minutes at
delivery.
If there are one or more users created with the IED User Management and downloaded
into the IED, then, when a user intentionally attempts a Log on or when the user attempts
to perform an operation that is password protected, the Log on window will appear.
The cursor is focused on the User identity field, so upon pressing the
key, the user can
change the user name, by browsing the list of users, with the up and down arrows.
After choosing the right user name, the user must press the E key again. When it comes
to password, upon pressing the

key, the following character will show up: $. After

all the letters are introduced (passwords are case sensitive) choose OK and press the
key again.
If everything is alright at a voluntary Log on, the local HMI returns to the Authorization
screen. If the Log on is OK, when required to change for example a password protected
setting, the local HMI returns to the actual setting folder. If the Log on has failed, then the
Log on window opens again, until either the user makes it right or presses Cancel.

20.1.3.1

Authorization with Central Account Management enabled IED


The users, their roles and rights are created, deleted and edited only in the Central Account
Management server (SDM600). However, the user rights can be edited in the IED by using
the PCM600 user tool.

1226

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

One user can have one or several user roles. By default, the users in Table 273 are created
in the IED, and when creating new users in the SDM600 server, the predefined roles from
Table 845 can be used.
At delivery, the IED user has full access as SuperUser when using the
LHMI and as Administrator when using FTP or PCM600 until Central
Account Management is activated.
Table 844:

Default users

User name

User rights

SuperUser

Full rights, only presented in LHMI. LHMI is logged on by default until other users are
defined

Guest

Only read rights, only presented in LHMI. LHMI is logged on by default when other users
are defined (same as VIEWER)

Administrator

Full rights. Password: Administrator. This user has to be used when reading out
disturbances with third party FTP-client.

Table 845:

Predefined user roles according to IEC 62351-8

User roles

Role explanation

User rights

VIEWER

Viewer

Can read parameters and browse the menus from LHMI

OPERATOR

Operator

Can read parameters and browse the menus as well as perform


control actions

ENGINEER

Engineer

Can create and load configurations and change settings for the
IED and also run commands and manage disturbances

INSTALLER

Installer

Can load configurations and change settings for the IED

SECADM

Security
administrator

Can change role assignments and security settings. Can


deploy certificates.

SECAUD

Security auditor

Can view audit logs

RBACMNT

RBAC
management

Can change role assignment

ADMINISTRATOR

Administrator
rights

Sum of all rights for SECADM, SECAUD and RBACMNT


This User role is vendor specific and not
defined in IEC 623518

Changes in user management settings do not cause an IED reboot.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1227

Section 20
Basic IED functions

1MRK 502 066-UUS A

The PCM600 tool caches the login credentials after successful login for 15
minutes. During that time no more login will be necessary.
The successfully activation of Central Account Management will disable built-in users or
remove all local created users from PCM600.
Management of user credentials and roles is handled on the central Account Management
server e.g. SDM600 The IED employs two strategies to ensure availability of the
authentication system even if there is a problem with the network or authentication server:

A substation can be equipped with two redundant authentication servers operating in


a hot standby mode.
If configured by the security administrator, the IED itself maintains a local replica in
the database with selected users. This database is periodically updated with data from
the server and used as fallback if none of the servers are reachable.

Note that not all users in the SDM600 server are part of the replica. There might be users
that are not assigned to any replication group. IED only replicates those users which are
part of replication group configured in the IED.
This replication can be disabled using PCM600 by the security administrator, which
means that the IED will forward login requests to the SDM600 for authorization and in
case of problems with the network users will not be able to log in to the IED.
If user replication has been disabled in a CAM-enabled IED and if
communication with SDM600 is lost, access to that IED will be denied
until communication is re-established.
All communication between the central management and the IEDs is protected using
secure communication. Customers using SDM600 are required to generate and distribute
certificates during the engineering process of the substation. These certificates ensure
mutual trust between IED and for example SDM600, FTP, PCM600 and other system.

1228

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Table 846:

Authority-related IED functions

Function

Description

Authority status
ATHSTAT

This function is an indication function block for user logon activity.


User denied attempt to logon and user successful logon are reported.

Authority check
ATHCHCK

To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, by means of authorization handling. The
authorization handling of the IED and the PCM600 is implemented at both access
points to the IED:

local, through the local HMI


remote, through the communication ports

The IED users can be created, deleted and edited only in the CAM server.
This function enables/disables the maintenance menu. It also controls the
maintenance menu logon time out.

Authority
management
AUTHMAN

For more information on the functions Authority Management (AUTHMAN), Authority


Status (ATHSTAT), and Authority Check (ATHCHCK) functions, refer to chapter
Basic IED functions in the Technical Manual.

20.2

Authority management AUTHMAN

20.2.1

Identification
Function description

IEC 61850
identification

Authority management

20.2.2

AUTHMAN

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

AUTHMAN
This function enables/disables the maintenance menu. It also controls the maintenance
menu log on time out.

20.2.3
Table 847:

Settings
AUTHMAN Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

MaintMenuDisAuth

Disable
Enable

Enable

In maintenance menu, disable authority


selection is shown

AuthTimeout

600 - 3600

600

600

Authority blocking timeout

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1229

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.3

FTP access with password FTPACCS

20.3.1

Identification
Function description

IEC 61850
identification

FTP access with SSL

20.3.2

FTPACCS

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

FTP access with TLS, FTPACCS


The FTP Client defaults to the best possible security mode when trying to negotiate with
TLS.
The automatic negotiation mode acts on configured port number 21 and server features,
it tries to negotiate with explicit TLS via AUTH TLS. If the specified port is any other, it
tries to negotiate in a similar way.
Using FTP without TLS encryption gives the FTP client reduced capabilities. This mode
is only for accessing disturbance recorder data from the IED.
If normal FTP is required to read out disturbance recordings, create a
specific account for this purpose with rights only to do File transfer. The
password of this user will be exposed in clear text on the wire.

20.3.3
Table 848:
Name

Settings
FTPACCS Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

PortSelection

None
Front
LANAB
LANCD
Any

Any

Port selection for communication

SSLMode

FTP+FTPS
FTPS

FTPS

Support for AUTH TLS/SSL

TCPPortFTP

1 - 65535

21

TCP port for FTP and FTP with Explicit SSL

1230

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.4

Authority status ATHSTAT

20.4.1

Identification
Function description

IEC 61850
identification

Authority status

20.4.2

IEC 60617
identification

ATHSTAT

ANSI/IEEE C37.2
device number
-

Functionality
Authority status ATHSTAT function is an indication function block for user log-on
activity.
User denied attempt to log-on and user successful log-on are reported.

20.4.3

Function block
ATHSTAT
USRBLKED
LOGGEDON
IEC06000503-2-en.vsd
IEC06000503 V2 EN

Figure 554:

20.4.4

ATHSTAT function block

Signals
Table 849:
Name

ATHSTAT Output signals


Type

Description

USRBLKED

BOOLEAN

At least one user is blocked by invalid password

LOGGEDON

BOOLEAN

At least one user is logged on

The output signal USRBLKED is not valid if the IED is Centralized


Account Management enabled.

20.4.5

Settings
The function does not have any parameters available in Local HMI or in Protection and
Control IED Manager (PCM600)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1231

Section 20
Basic IED functions
20.4.6

1MRK 502 066-UUS A

Operation principle
Authority status (ATHSTAT) function informs about two events related to the IED and
the user authorization:

the fact that at least one user has tried to log on wrongly into the IED and it was
blocked (the output USRBLKED)
the fact that at least one user is logged on (the output LOGGEDON)

Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated. The output can for example, be connected on Event (EVENT)
function block for LON/SPA.The signals are also available on IEC 61850 station bus.

20.5

Self supervision with internal event list INTERRSIG

20.5.1

Functionality
Self supervision with internal event list function listens and reacts to internal system
events, generated by the different built-in self-supervision elements. The internal events
are saved in an internal event list presented on the LHMI and in PCM600 event viewer
tool.

20.5.2

Function block

INTERRSIG
FAIL
WARNING
TSYN CERR
RTCERR
STUPBLK
IEC09000787-2-en.vsdx

IEC09000787 V2 EN

Figure 555:

1232

INTERRSIG function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.5.3

Signals
Table 850:
Name

20.5.4

INTERRSIG Output signals


Type

Description

FAIL

BOOLEAN

Internal fail

WARNING

BOOLEAN

Internal warning

TSYNCERR

BOOLEAN

Time synchronization error

RTCERR

BOOLEAN

Real time clock error

DISABLE

BOOLEAN

Application Disable

Settings
The function does not have any parameters available in the local HMI or PCM600.

20.5.5

Operation principle
The self-supervision operates continuously and includes:

Normal micro-processor watchdog function.


Checking of digitized measuring signals.
Other alarms, for example hardware and time synchronization.

The self-supervision function status can be monitored from the local HMI or from the
Event Viewer in PCM600.
Under the Diagnostics menu in the local HMI, the actual information from the selfsupervision function can be reviewed. The information can be found under Main menu/
Diagnostics/Internal events or Main menu/Diagnostics/IED status/General. The
information from the self-supervision function is also available in the Event Viewer in
PCM600.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1233

Section 20
Basic IED functions

1MRK 502 066-UUS A

IEC15000414-1-en.vsdx
IEC15000414 V1 EN

Figure 556:

IED general status in local HM

The self supervision records internal signal changes in an internal event list. A maximum
of 40 internal events are stored in a first-in, first-out manner.

GUID-B481701F-05B4-4B29-83D4-18F13886FEBE V1 EN

Figure 557:

Self-supervision event list in local HMI

A self-supervision summary can be obtained by means of an output relay with potential


free alarm contact (INTERNAL FAIL) located on the power supply module. This contact
is closed when the IED either does not have auxiliary power, or when one or more error
conditions are present in the IED (for example harware error).
Some output signals are available from the INTERRSIG function block. The signals from
this function block are sent as events via IEC61850 to the station level of the control
system. These signals can also be connected to binary outputs for signalization via output
relays or they can be used as conditions for other functions if required/desired.
Individual error signals from I/O modules can be obtained from respective module in the
Signal Matrix tool. Error signals from time synchronization can be obtained from the
INTERRSIG function block via two outputs TSYNCERR and RTCERR .

1234

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.5.5.1

Internal signals
Self supervision provides several status signals that give information about the internal
status of the IED. For this reason they are also called internal signals. These internal
signals , available on local HMI under Main menu/Diagnostics/IED status/General,
can be divided into two groups.

Standard signals are always presented in the IED, see table 851.
Hardware dependent internal signals are collected depending on the hardware
configuration, see table 852.

Table 851:

Self-supervision's standard internal signals

Name of signal

Description

Displayed on
local HMI as

Reasons for activation

FAIL

Internal
Fail status

Internal fail

This signal will be active if one or more of the


following internal signals are active; LMDERROR,
WATCHDOG, APPERROR, RTEERROR, or any of
the HW dependent signals

WARNING

Internal
Warning
status

Internal
warning

This signal will be active if one or more of the


following internal signals are active; RTCERROR,
IEC61850ERROR, TIMESYNCHERROR

RTCERROR

Real Time
Clock
status

Real time
clock

This signal will be active when there is a hardware


error with the real time clock.

TIMESYNCHERROR

Time
Synchroniz
ation
status

Time synch

This signal will be active when the source of the time


synchronization is lost, or when the time system has
to make a time reset.

RTEERROR

Runtime
Execution
Error
status

Runtime
execution

This signal will be active if the Runtime Engine failed


to do some actions with the application threads. The
actions can be loading of settings or parameters for
components, changing of setting groups, loading or
unloading of application threads.

IEC61850ERROR

IEC 61850
Error
status

IEC61850

This signal will be active if the IEC 61850 stack did


not succeed in some actions like reading IEC 61850
configuration, startup, for example

DNP3

DNP3 error
status

DNP3

This signal will be active when DNP3 detects any


configuration error during startup.

LMDERROR

LON/Mip
Device
Error
status

SLM301

LON network interface, MIP/DPS, is in an


unrecoverable error state.

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1235

Section 20
Basic IED functions

1MRK 502 066-UUS A

Name of signal

Description

APPERROR

Runtime
Application
Error
status

Runtime App
Error

This signal will be active if one or more of the


application threads are not in the state that Runtime
Engine expects. The states can be CREATED,
INITIALIZED, RUNNING, for example

SETCHGD

Settings
changed

Settings
changed

This signal will generate an Internal Event to the


Internal Event list if any settings are changed.

SETGRPCHGD

Setting
groups
changed

Settings
changed

This signal will generate an Internal Event to the


Internal Event list if any setting groups are changed.

Table 852:
Card

Displayed on
local HMI as

Reasons for activation

Self-supervision's hardware dependent internal signals


Name of signal

Description

Displayed on
local HMI as

Reasons for activation

PSM

PSM-Error

Power
Supply
Module
Error
status

PSM1

Activated if the module has a hardware error.

BIM

BIM-Error

Binary In
Module
Error
status

BIMn

Activated if the module has a hardware error.


n = slot number

BOM

BOM-Error

Binary Out
Module
Error
status

BOMn

Activated if the module has a hardware error.


n = slot number

IOM

IOM-Error

In/Out
Module
Error
status

IOMn

Activated if the module has a hardware error.


n = slot number

MIM

MIM-Error

Millampere
Input
Module
Error
status

MIMn

Activated if the module has a hardware error.


n = slot number

SOM

SOM-Error

Static Out
Module
Error
status

SOMn

Activated if the module has a hardware error.


n = slot number

NUM

NUM-Error

Numerical/
CPU
Module
Error
status

NUM30

Activated if the module has a hardware or


software error.

ADM

ADM-Error

A/D
Module
Error
status

ADM31

Activated if the module has a hardware error.

Table continues on next page

1236

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Card

20.5.5.2

Name of signal

Description

Displayed on
local HMI as

Reasons for activation

ADM

ADM-Error

A/D
Module
Error
status

ADM32

Activated if the module has a hardware error.

OEM

OEM-Error

Optical
Ethernet
Module
Error
status

OEM3nn

Activated if the module has a hardware error.


n = slot number

LDCM

LDCM-Error

Line
Differential
Communic
ation
Module
Error
status

LDCM3nn

Activated if the module has a hardware error.


n = slot number

TRM

TRM-Error

Transform
er Module
Error
status

TRM40

TRM

TRM-Error

Transform
er Module
Error
status

TRM41

Supervision of analog inputs


The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification.
When the signal is within measurable limits on both channels, a direct comparison of the
two A/D converter channels can be performed. If the validation fails, the CPU will be
informed and an alarm will be given for A/D converter failure.

20.5.6

Technical data
Table 853:

Self supervision with internal event list

Data

Value

Recording manner

Continuous, event controlled

List size

40 events, first in-first out

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1237

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.6

Time synchronization

20.6.1

Functionality
The time synchronization function is used to select a common source of absolute time for
the synchronization of the IED when it is a part of a protection system. This makes it
possible to compare events and disturbance data between all IEDs within a station
automation system and in between sub-stations.
Micro SCADA OPC server should not be used as a time synchronization
source.

20.6.2

Settings
There are two groups of parameter settings related to time:

System time
Synchronization

The System time group relates to setting the on/off and start/end of the Daylight Saving
Time (DST) for the local time zone in relation to Coordinated Universal Time (UTC). The
Synchronization group relates to selecting the coarse and fine synchronization sources. As
well as defining the synchronization master and accuracy levels specifically for
IEC61850-9-2.
All the settings and parameters related to time are available via Local HMI under Main
menu/Configuration/Time/System time and via PCM600 under IED Configuration/
Time.

1238

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Table 854:
Name

TIMESYNCHGEN Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

CoarseSyncSrc

Disabled
SPA
LON
SNTP
DNP
IEC103

Disabled

Coarse time synchronization source

FineSyncSource

Disabled
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS

Disabled

Fine time synchronization source

SyncMaster

Disabled
SNTP-Server

Disabled

Activate IEDas synchronization master

TimeAdjustRate

Slow
Fast

Fast

Adjust rate for time synchronization

HWSyncSrc

Disabled
GPS
IRIG-B
PPS

Disabled

Hardware time synchronization source

AppSynch

NoSynch
Synch

NoSynch

Time synchronization mode for application

SyncAccLevel

Class T5 (1us)
Class T4 (4us)
Unspecified

Unspecified

Wanted time synchronization accuracy

Table 855:
Name

BININPUT Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ModulePosition

3 - 16

Hardware position of IO module for time


synchronization

BinaryInput

1 - 16

Binary input number for time synchronization

BinDetection

PositiveEdge
NegativeEdge

PositiveEdge

Positive or negative edge detection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1239

Section 20
Basic IED functions

Table 856:
Name

1MRK 502 066-UUS A

SNTP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ServerIP-Add

0 - 255

IP
Address

0.0.0.0

Server IP-address

RedServIP-Add

0 - 255

IP
Address

0.0.0.0

Redundant server IP-address

Table 857:
Name
DST Enable

Table 858:
Name

DSTENABLE Non group settings (basic)


Values (Range)
Disabled
Enabled

Unit
-

Step
-

Default
Enabled

Description
Enables or disables the use of Daylight Saving
Time

DSTBEGIN Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

MonthInYear

January
February
March
April
May
June
July
August
September
October
November
December

March

Month in year when daylight time starts

DayInWeek

Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday

Sunday

Day in week when daylight time starts

WeekInMonth

Last
First
Second
Third
Fourth

Last

Week in month when daylight time starts

UTCTimeOfDay

-24:00
-23:30
...
-00:30
00:00
00:30
...
48:00

1:00

UTC Time of day in hours when daylight time


starts

1240

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Table 859:
Name

DSTEND Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

MonthInYear

January
February
March
April
May
June
July
August
September
October
November
December

October

Month in year when daylight time ends

DayInWeek

Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday

Sunday

Day in week when daylight time ends

WeekInMonth

Last
First
Second
Third
Fourth

Last

Week in month when daylight time ends

UTCTimeOfDay

-24:00
-23:30
...
-00:30
00:00
00:30
...
48:00

1:00

UTC Time of day in hours when daylight time


ends

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1241

Section 20
Basic IED functions

Table 860:
Name
TimeZone

Table 861:
Name

1MRK 502 066-UUS A

TIMEZONE Non group settings (basic)


Values (Range)
-12:00
-11:00
-10:00
-9:30
-9:00
-8:00
-7:00
-6:00
-5:00
-4:30
-4:00
-3:30
-3:00
-2:00
-1:00
0:00
1:00
2:00
3:00
3:30
4:00
4:30
5:00
5:30
5:45
6:00
6:30
7:00
8:00
8:45
9:00
9:30
10:00
10:30
11:00
11:30
12:00
12:45
13:00
14:00

Unit
-

Step
-

Default
1:00

Description
Local time from UTC

IRIG-B Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

SynchType

BNC
Opto

Opto

Type of synchronization

TimeDomain

LocalTime
UTC

LocalTime

Time domain

Encoding

IRIG-B
1344
1344TZ

IRIG-B

Type of encoding

TimeZoneAs1344

MinusTZ
PlusTZ

PlusTZ

Time zone as in 1344 standard

1242

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.6.3

Operation principle

20.6.3.1

General concepts
Time definitions
The error of a clock is the difference between the actual time of the clock, and the time the
clock is intended to have. Clock accuracy indicates the increase in error, that is, the time
gained or lost by the clock. A disciplined clock knows its own faults and tries to
compensate for them.

Design of the time system (clock synchronization)


The time system is based on software and hardware clocks that run independently from
each other. See figure 558
External
Synchronization
sources

Time tagging and general synchronisation

Off
LON
SPA
Min. pulse
GPS
SNTP
DNP

Communication

TimeRegulator
(Setting,
see
technical
reference
manual)

Events

Protection
and control
functions

SW-time
Connected when GPS-time is
used for differential protection

IRIG-B
PPS

Off
GPS
IRIG-B

TimeRegulator
(fast or slow)

PPS

Synchronization for differential protection


(ECHO-mode or GPS)
HW-time

A/D
converter

Diff.communication

Transducers*
*IEC 61850-9-2
IEC08000287-2-en.vsd

IEC08000287 V2 EN

Figure 558:

Design of the time system (clock synchronization)

All time tagging is performed by the software clock. When, for example, a status signal is
changed in the protection system of a function based on the free running hardware clock,
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1243

Section 20
Basic IED functions

1MRK 502 066-UUS A

the event is time tagged by the software clock when it reaches the event recorder. The
hardware clock can thus run independently.
The echo mode of differential protection is based on the hardware clock. Thus, there is no
need to synchronize the hardware clock and the software clock.
The synchronization of the hardware clock to the software clock is necessary only when
GPS or IRIG B 00X with optical fibre, IEEE 1344 is used for differential protection. The
two clock systems are synchronized by a special clock synchronization unit with two
modes, fast and slow. A special feature, an automatic fast clock time regulator is used. The
automatic fast mode makes the synchronization time as short as possible during pickup or
at interruptions/disturbances in the GPS timing. The fast and slow settings are also
available on the local HMI.
The hardware and software clocks are not synchronized if a GPS clock is used.

Fast clock synchronization mode


At start-up and after interruptions in the GPS or IRIG B time signals, the deviation
between the GPS time and the internal differential time system can be substantial. A new
start-up is also required, for example, after maintenance of the auxiliary voltage system.
When the time difference is >16s, the differential function is blocked and the time
regulator for the hardware clock automatically uses a fast mode to synchronize the clock
systems. The time adjustment is made with an exponential function, that is, with big time
adjustment steps in the beginning, and then smaller steps until a time deviation between
the GPS time and the differential time system of <16s has been reached. The differential
function is then enabled and the synchronization remains in fast mode or switches to slow
mode depending on the setting.

Slow clock synchronization mode


During normal service, a setting with slow synchronization mode is used. This prevents
the hardware clock to make too big time steps, >16s, emanating from the differential
protection requirement of correct timing.

Synchronization principle
From a general point of view synchronization can be seen as a hierarchical structure. A
function is synchronized from a higher level and provides synchronization to lower levels.

1244

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Synchronization from
a higher level

Function

Optional synchronization of
modules at a lower level

IEC09000342-1-en.vsd
IEC09000342 V1 EN

Figure 559:

Synchronization principle

A function is said to be synchronized when it periodically receives synchronization


messages from a higher level. As the level decreases, the accuracy of the synchronization
decreases as well. A function can have several potential sources of synchronization, with
different maximum errors. This gives the function the possibility to choose the source with
the best quality, and to adjust its internal clock based on this source. The maximum error
of a clock can be defined as:

20.6.3.2

The maximum error of the last used synchronization message


The time since the last used synchronization message
The rate accuracy of the internal clock in the function.

Real-time clock (RTC) operation


The IED has a built-in real-time clock (RTC) with a resolution of one second. The clock
has a built-in calendar that handles leap years through 2038.

Real-time clock at power off


During power off, the system time in the IED is kept by a capacitor-backed real-time clock
that will provide 35 ppm accuracy for 5 days. This means that if the power is off, the time
in the IED may drift with 3 seconds per day, during 5 days, and after this time the time will
be lost completely.

Real-time clock at startup


Time synchronization startup procedure
The first message that contains the full time (as for instance LON, SNTP and GPS) gives
an accurate time to the IED. After the initial setting of the clock, one of the three following
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1245

Section 20
Basic IED functions

1MRK 502 066-UUS A

conditions happens with each of the coming synchronization messages configured as


FineSynchSource:

If the synchronization message, which is similar to the other messages, has an offset
compared to the internal time in the IED, the message is used directly for
synchronization, which means, for adjusting the internal clock to obtain zero offset at
the next coming time message.
If the synchronization message has a large offset compared to the other messages, a
spike-filter in the IED removes this time-message.
If the synchronization message has a large offset and the following message also has
a large offset, the spike filter does not act and the offset in the synchronization
message is compared to a threshold that defaults to 500 milliseconds. If the offset is
more than the threshold, the clock jumps a whole number of seconds so the remaining
offset is less than 500ms. The remaining offset is then slowly adjusted with 1000 ppm
until the offset is removed. With an adjustment of 1000ppm it takes 500 seconds to
remove an offset of 500 milliseconds.

Synchronization messages configured as coarse are only used for initial setting of the
time. After this has been done, the messages are checked against the internal time and only
an offset of more than 10 seconds resets the time.

Rate accuracy
The Rate accuracy is the accuracy of the internal clock while the external time signal is lost
(e.g. GPS lost). In the IED, the rate accuracy at cold start is 100 ppm but if the IED is
synchronized for a while, the rate accuracy is approximately 1 ppm if the surrounding
temperature is constant. It can take up to one hour after a cold start of the IED to reach to
a stable rate due to the normal warming-up procedure of the IED.

Time-out on synchronization sources


All synchronization interfaces have a time-out, and a configured interface must receive
time synchronization messages regularly in order not to give an error signal
(TSYNCERR) that is reported from the INTERRSIG function block. The time-out is such
that one message can be lost without getting a TSYNCERR, but if more than one message
is lost, a TSYNCERR is given.

20.6.3.3

Synchronization alternatives
Four main alternatives of external synchronization sources are available. The
synchronization message is applied:

1246

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

via any of the communication ports of the IED as a telegram message including date
and time
as a minute pulse connected to a binary input
via GPS
via IRIG-B or PPS

Synchronization via SNTP


SNTP provides a ping-pong method of synchronization. A message is sent from an IED
to an SNTP server, and the SNTP server returns the message after filling in a reception
time and a transmission time. SNTP operates via the normal Ethernet network that
connects IEDs together in an IEC 61850 network. For SNTP to operate properly, there
must be an SNTP server present, preferably in the same station. The SNTP
synchronization provides an accuracy that gives +/- 1 ms accuracy for binary inputs. The
IED itself can be set as an SNTP-time server.
SNTP provides complete time-information and can be used as both fine and coarse time
synch source. However SNTP shall normally be used as fine synch only. The only reason
to use SNTP as coarse synch is in combination with PPS as fine source. The combination
SNTP as both fine and coarse source shall not be used.
SNTP server requirements
The SNTP server to be used is connected to the local network, that is not more than 4-5
switches or routers away from the IED. The SNTP server is dedicated for its task, or at
least equipped with a real-time operating system, that is not a PC with SNTP server
software. The SNTP server should be stable, that is, either synchronized from a stable
source like GPS, or local without synchronization. Using a local SNTP server without
synchronization as primary or secondary server in a redundant configuration is not
recommended.

Synchronization via Serial Communication Module (SLM)


On the serial buses (both LON and SPA) two types of synchronization messages are sent.

Coarse message is sent every minute and comprises complete date and time, that is,
year, month, day, hours, minutes, seconds and milliseconds.
Fine message is sent every second and comprises only seconds and milliseconds.

The SLM module is located on the Numeric processing module (NUM).

Synchronization via Built-in-GPS


The built-in GPS clock modules receive and decode time information from the global
positioning system. The modules are located on the GPS time synchronization Module
(GTM).

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1247

Section 20
Basic IED functions

1MRK 502 066-UUS A

Synchronization via binary input


The IED accepts minute pulses to a binary input. These minute pulses can be generated
from, for example station master clock. If the station master clock is not synchronized
from a world wide source, time will be a relative time valid for the substation. Both
positive and negative edge on the signal can be accepted. This signal is also considered as
a fine time synchronization signal.
The minute pulse is connected to any channel on any Binary Input Module in the IED. The
electrical characteristic is thereby the same as for any other binary input.
If the objective of synchronization is to achieve a relative time within the substation and
if no station master clock with minute pulse output is available, a simple minute pulse
generator can be designed and used for synchronization of the IEDs. The minute pulse
generator can be created using the logical elements and timers available in the IED.
The definition of a minute pulse is that it occurs one minute after the last pulse. As only
the flanks are detected, the flank of the minute pulse shall occur one minute after the last
flank.
Binary minute pulses are checked with reference to frequency.
Pulse data:

Period time (a) should be 60 seconds.


Pulse length (b):

Minimum pulse length should be >50 ms.


Maximum pulse length is optional.

Magnitude (c) - please refer to section "Binary input module (BIM)".

Deviations in the period time (a) larger than 50 ms will cause TSYNCERR.

a
b

c
en05000251.vsd
IEC05000251 V1 EN

Figure 560:

1248

Binary minute pulses

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

The default time-out-time for a minute pulse is two minutes, and if no valid minute pulse
is received within two minutes a SYNCERR will be given.
If contact bounce occurs, only the first pulse will be detected as a minute pulse. The next
minute pulse will be registered first 60 s - 50 ms after the last contact bounce.
If the minute pulses are perfect, for example, it is exactly 60 seconds between the pulses,
contact bounces might occur 49 ms after the actual minute pulse without effecting the
system. If contact bounce occurs more than 50 ms, for example, it is less than 59950 ms
between the two most adjacent positive (or negative) flanks, the minute pulse will not be
accepted.
Binary synchronization example
An IED is configured to use only binary input for time synchronization, and a valid binary
input is applied to a binary input card. The HMI is used to tell the IED the approximate
time, and the minute pulse is then used to synchronize the IED. Minute pulse means that
each pulse occurs one minute after the previous pulse, so the first pulse is not used at all.
The second pulse will probably be rejected due to the spike filter. The third pulse will give
the IED a good time, and will reset the time so that the fourth pulse will occur on a minute
border. After the first three minutes, the time in the IED will be good if the coarse time is
set properly via the HMI or if the RTC backup still keeps the time since last up-time. If the
minute pulse is removed, for example, for an hour, the internal time will drift by maximum
the error rate in the internal clock. If the minute pulse is returned, the first pulse is
automatically rejected. The second pulse will possibly be rejected due to the spike filter.
The third pulse will set the time if the time offset is more than 500 ms or adjust the time
if the time offset is small enough. If the time is set, the application will be brought to a safe
state before the time is set. If the time is adjusted, the time will reach its destination within
one minute.
Synchronization via IRIG-B module
IRIG-B is a protocol used only for time synchronization. A clock can provide local time
of the year in this format. The B in IRIG-B states that 100 bits per second are transmitted
and the message is sent every second. After IRIG-B there are numbers stating if and how
the signal is modulated and the information transmitted.
To receive IRIG-B there are two connectors in the IRIG-B module, one galvanic BNC
connector and one optical ST connector. IRIG-B 12x messages can be supplied via the
galvanic interface, and IRIG-B 00x messages can be supplied via either the galvanic
interface or the optical interface, where x (in 00x or 12x) means a number in the range of
0-7.
00 means that a base band is used, and the information can be fed into the IRIG-B
module via the BNC contact or an optical fiber. 12 means that a 1 kHz modulation is
used. In this case the information must go into the module via the BNC connector.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1249

Section 20
Basic IED functions

1MRK 502 066-UUS A

If the x in 00x or 12x is 4, 5, 6 or 7, the time message from IRIG-B contains information
of the year. If the x is 0, 1, 2 or 3, the information contains only the time within the year,
and year information has to be set via PCM600 or local HMI.
The IRIG-B module also takes care of IEEE1344 messages that are sent by IRIG-B clocks,
as IRIG-B previously did not have any year information. IEEE1344 is compatible with
IRIG-B and contains year information and information of the time-zone.

20.6.4

Technical data
Table 862:

Time synchronization, time tagging

Function

Value

Time tagging resolution, events and sampled measurement values

1 ms

Time tagging error with synchronization once/min (minute pulse


synchronization), events and sampled measurement values

1.0 ms typically

Time tagging error with SNTP synchronization, sampled measurement


values

1.0 ms typically

20.7

Parameter setting groups

20.7.1

Functionality
Use the six different groups of settings to optimize the IED operation for different power
system conditions. Creating and switching between fine-tuned setting sets, either from the
local HMI or configurable binary inputs, results in a highly adaptable IED that can be
applied to a variety of power system scenarios.

20.7.2

Function block
ActiveGroup
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
ACTGRP4
GRP4
ACTGRP5
GRP5
ACTGRP6
GRP6
GRP_CHGD
ANSI05000433-2-en.vsd
ANSI05000433 V2 EN

Figure 561:

1250

ActiveGroup function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.7.3

Signals
Table 863:

ACTVGRP Input signals

Name

Type

Selects setting group 1 as active

ACTGRP2

BOOLEAN

Selects setting group 2 as active

ACTGRP3

BOOLEAN

Selects setting group 3 as active

ACTGRP4

BOOLEAN

Selects setting group 4 as active

ACTGRP5

BOOLEAN

Selects setting group 5 as active

ACTGRP6

BOOLEAN

Selects setting group 6 as active

ACTVGRP Output signals

Name

Table 865:
Name

Description

BOOLEAN

Table 864:

20.7.4

Default

ACTGRP1

Type

Description

GRP1

BOOLEAN

Setting group 1 is active

GRP2

BOOLEAN

Setting group 2 is active

GRP3

BOOLEAN

Setting group 3 is active

GRP4

BOOLEAN

Setting group 4 is active

GRP5

BOOLEAN

Setting group 5 is active

GRP6

BOOLEAN

Setting group 6 is active

GRP_CHGD

BOOLEAN

Pulse when setting changed

REMSETEN

BOOLEAN

Settings over IEC 61850 enabled

Settings
SETGRPS Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

ActiveSetGrp

SettingGroup1
SettingGroup2
SettingGroup3
SettingGroup4
SettingGroup5
SettingGroup6

SettingGroup1

Active setting group

MaxNoSetGrp

1-6

Max number of setting groups 1-6

20.7.5

Operation principle
Parameter setting groups ActiveGroup function has six functional inputs, each
corresponding to one of the setting groups stored in the IED. Activation of any of these

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1251

Section 20
Basic IED functions

1MRK 502 066-UUS A

inputs changes the active setting group. Eight functional output signals are available for
configuration purposes, so that information on the active setting group is always available.
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by activating
the corresponding input to the ActiveGroup function block.
Each input of the function block can be configured to connect to any of the binary inputs
in the IED. To do this PCM600 must be used.
The external control signals are used for activating a suitable setting group when adaptive
functionality is necessary. Input signals that should activate setting groups must be either
permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower order
setting group has priority. This means that if for example both group four and group two
are set to be activated, group two will be the one activated.
Every time a setting is changed, the output signal GRP_CHGD is sending a pulse.
Activating or deactivating test mode is made by changing a parameter, consequently this
will also cause a pulse on the GRP_CHGD output.
The parameter MaxNoSetGrp defines the maximum number of setting groups in use to
switch between.
The output REMSETEN indicates whether setting changes over IEC61850 are enabled or
not. Per default, this is not enabled, which results in REMSETEN being at a logical low
level. If setting changes via IEC61850 are enabled, then REMSETEN will be a logical high.
The setting changes over IEC61850 is enabled with the setting EnableSettings in the
IEC61850-8-1 configuration under Main menu/Configuration/Communication/
Station communication/IEC61850-8-1/IEC61850-8-1. Please refer to documentation
for IEC61850 for further details.
Switching can only be done within that number of groups. The number of setting groups
selected to be used will be filtered so only the setting groups used will be shown on the
Parameter Setting Tool.

1252

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1

+RL2

IOx-Bly1
IOx-Bly2
IOx-Bly3
IOx-Bly4

ActiveGroup
ACTGRP1
GRP1
ACTGRP2

GRP2

ACTGRP3

GRP3

ACTGRP4

GRP4

IOx-Bly5

ACTGRP5

GRP5

IOx-Bly6

ACTGRP6

GRP6
GRP_CHGD

ANSI05000119-2-en.vsd
ANSI05000119 V2 EN

Figure 562:

Connection of the function to external circuits

The above example also includes seven output signals, for confirmation of which group
that is active.

20.8

ChangeLock function CHNGLCK

20.8.1

Functionality
Change lock function CHNGLCK is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to block
inadvertent IED configuration changes beyond a certain point in time.
The change lock function activation is normally connected to a binary input.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1253

Section 20
Basic IED functions
20.8.2

1MRK 502 066-UUS A

Function block

CHNGLCK

LOCK*

ACTIVE
OVERRIDE
IEC09000946.vsd

IEC09000946 V2 EN

Figure 563:

20.8.3

Signals
Table 866:
Name
LOCK

Table 867:
Name

20.8.4

CHNGLCK function block

CHNGLCK Input signals


Type
BOOLEAN

Default
0

Description
Activate change lock

CHNGLCK Output signals


Type

Description

ACTIVE

BOOLEAN

Change lock active

OVERRIDE

BOOLEAN

Change lock override

Operation principle
The Change lock function (CHNGLCK) is configured using ACT.
The function, when activated, will still allow the following changes of the IED state that
does not involve reconfiguring of the IED:

1254

Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Set system time


Enter and exit from test mode
Change of active setting group

The binary input signal LOCK controlling the function is defined in ACT or SMT:
Binary input

Function

Activated

Deactivated

20.9

Test mode functionality TEST

20.9.1

Functionality
When entering IED test mode there is an option to block all functions. Active test mode
is indicated by a flashing yellow Pickup LED on the LHMI. After that, it is possible to
unblock arbitrarily selected functions from the LHMI to perform required tests.
When leaving TESTMODE, all blockings are removed (except for functions that have
their block input active), and the IED resumes normal operation. However, if during
TESTMODE operation, power is removed and later restored, the IED will remain in
TESTMODE with the same protection functions blocked or unblocked as before the
power was removed. All testing will be done with actually set and configured values
within the IED. No settings will be changed, thus mistakes are avoided.
Forcing of binary input and output signals is only possible when the IED is in IED test
mode.

20.9.2

Function block
TESTMODE
IED_TEST

TEST
IED_TEST
BLOCK
NOEVENT
INPUT
SETTING
IEC61850
IEC14000072-1-en.vsd

IEC09000219 V2 EN

Figure 564:

TESTMODE function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1255

Section 20
Basic IED functions
20.9.3

1MRK 502 066-UUS A

Signals
Table 868:

TESTMODE Input signals

Name

Type

IED_TEST

BOOLEAN

Table 869:

Table 870:
Name

Description
Activate IED test mode

TESTMODE Output signals

Name

20.9.4

Default

Type

Description

TEST

BOOLEAN

In test via IED TEST or via LD0 Mode

IED_TEST

BOOLEAN

IED test mode is active

BLOCK

BOOLEAN

Active when LD0 is blocked or test blocked

NOEVENT

BOOLEAN

Event disabled during test mode

INPUT

BOOLEAN

IED TEST input is active

SETTING

BOOLEAN

IED test mode setting is On

IEC61850

BOOLEAN

Active when LD0 Mode is in Blocked, Test or Test


blocked

Settings
TESTMODE Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

IEDTestMode

Disabled
Enabled

Disabled

Activate IED Test mode

EventDisable

Disabled
Enabled

Disabled

Event disable during test mode

BlockAllFunc

Disabled
Enabled

Enabled

Block all functions when entering IED test


mode

CmdTestEd1

Disabled
Enabled

Disabled

Require test bit in command at test mode (only


for IEC61850 Ed1)

20.9.5

Operation principle
Set the IED in test mode by

1256

configuration, activating the input SIGNAL on the function block TESTMODE.


setting TestMode to Enabled in the local HMI, under Main menu/TEST/IED test
mode.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

While the IED is in test mode, the output ACTIVE of the function block TESTMODE is
activated. The other outputs of the function block TESTMODE shows the cause of the
"Test mode: Enabled" state input from configuration (OUTPUT signal is activated) or
setting from local HMI (SETTING signal is activated).
While the IED is in test mode, the yellow Pickup LED will flash and all functions can be
blocked depending on the configuration of the testmode component. Any function can be
unblocked individually regarding functionality and event signalling.
The functions will be blocked next time if the testmode component is configured to block
components upon puting the IED into testmode.
The blocking of a function concerns all output signals from the actual function, so no
outputs will be activated.
If the IED is restarted while set to IED testmode by a binary input all
functions will be temporarily unblocked during startup, which might
cause unwanted operations.
The TESTMODE function block might be used to automatically block functions when a
test handle is inserted in a test switch. A contact in the test switch (RTXP24 contact 29-30)
or an FT switch finger can supply a binary input which in turn is configured to the
TESTMODE function block.
Each of the functions includes the blocking from the TESTMODE function block.
The functions can also be blocked from sending events over IEC 61850 station bus to
prevent filling station and SCADA databases with test events, for example during a
commissioning or maintenance test.

20.10

IED identifiers

20.10.1

Functionality
IED identifiers (TERMINALID) function allows the user to identify the individual IED in
the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1257

Section 20
Basic IED functions
20.10.2
Table 871:
Name

1MRK 502 066-UUS A

Settings
TERMINALID Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

StationName

0 - 18

Station name

Station name

StationNumber

0 - 99999

Station number

ObjectName

0 - 18

Object name

Object name

ObjectNumber

0 - 99999

Object number

UnitName

0 - 18

Unit name

Unit name

UnitNumber

0 - 99999

Unit number

IEDMainFunType

0 - 255

IED main function type for IEC60870-5-103

TechnicalKey

0 - 16

AA0B0Q0A0

Technical key (part 1)

0 - 16

Technical key (part 2)

0 - 16

Technical key (part 3)

0 - 16

Technical key (part 4)

20.11

Product information

20.11.1

Functionality
The Product identifiers function contains constant data (i.e. not possible to change) that
uniquely identifies the IED:

ProductVer
ProductDef
FirmwareVer
SerialNo
OrderingNo
ProductionDate
IEDProdType

The settings are visible on the local HMI , under Main menu/Diagnostics/IED status/
Product identifiersand underMain menu/Diagnostics/IED Status/IED identifiers
This information is very helpful when interacting with ABB product support (e.g. during
repair and maintenance).

1258

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.11.2

Settings
The function does not have any parameters available in the local HMI or PCM600.

20.11.3

Factory defined settings


The factory defined settings are very useful for identifying a specific version and very
helpful in the case of maintenance, repair, interchanging IEDs between different
Substation Automation Systems and upgrading. The factory made settings can not be
changed by the customer. They can only be viewed. The settings are found in the local
HMI under Main menu/Diagnostics/IED status/Product identifiers
The following identifiers are available:

IEDProdType

ProductDef

Describes the product version. Example: 2.1.0


1

is the Major version of the manufactured product this means, new platform of the product

is the Minor version of the manufactured product this means, new functions or new hardware
added to the product

is the Major revision of the manufactured product this means, functions or hardware is either
changed or enhanced in the product

IEDMainFunType

Describes the firmware version.


The firmware version can be checked from Main menu/Diagnostics/IED
status/Product identifiers
Firmware version numbers run independently from the release production
numbers. For every release number there can be one or more firmware versions
depending on the small issues corrected in between releases.

ProductVer

Describes the release number from the production. Example: 2.1.0

FirmwareVer

Describes the type of the IED. Example: REL670

Main function type code according to IEC 60870-5-103. Example: 128


(meaning line protection).

SerialNo
OrderingNo
ProductionDate

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1259

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.12

Signal matrix for binary inputs SMBI

20.12.1

Functionality
The Signal matrix for binary inputs (SMBI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT), see the
application manual to get information about how binary inputs are brought in for one IED
configuration.

20.12.2

Function block
SMBI
^VIN1
^VIN2
^VIN3
^VIN4
^VIN5
^VIN6
^VIN7
^VIN8
^VIN9
^VIN10

^BI1
^BI2
^BI3
^BI4
^BI5
^BI6
^BI7
^BI8
^BI9
^BI10
IEC05000434-2-en.vsd

IEC05000434 V2 EN

Figure 565:

20.12.3

Signals
Table 872:
Name

1260

SMBI function block

SMBI Input signals


Type

Default

Description

BI1

BOOLEAN

SMT Connect input

BI2

BOOLEAN

SMT Connect input

BI3

BOOLEAN

SMT Connect input

BI4

BOOLEAN

SMT Connect input

BI5

BOOLEAN

SMT Connect input

BI6

BOOLEAN

SMT Connect input

BI7

BOOLEAN

SMT Connect input

BI8

BOOLEAN

SMT Connect input

BI9

BOOLEAN

SMT Connect input

BI10

BOOLEAN

SMT Connect input

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Table 873:

SMBI Output signals

Name

20.12.4

Type

Description

BI1

BOOLEAN

Binary input 1

BI2

BOOLEAN

Binary input 2

BI3

BOOLEAN

Binary input 3

BI4

BOOLEAN

Binary input 4

BI5

BOOLEAN

Binary input 5

BI6

BOOLEAN

Binary input 6

BI7

BOOLEAN

Binary input 7

BI8

BOOLEAN

Binary input 8

BI9

BOOLEAN

Binary input 9

BI10

BOOLEAN

Binary input 10

Operation principle
The Signal matrix for binary inputs (SMBI) function , see figure 565, receives its inputs
from the real (hardware) binary inputs via the Signal Matrix Tool (SMT), and makes them
available to the rest of the configuration via its outputs, BI1 to BI10. The inputs and
outputs, as well as the whole block, can be given a user defined name. These names will
be represented in SMT as information which signals shall be connected between physical
IO and SMBI function. The input/output user defined name will also appear on the
respective output/input signal.

20.13

Signal matrix for binary outputs SMBO

20.13.1

Functionality
The Signal matrix for binary outputs (SMBO) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT), see the
application manual to get information about how binary inputs are sent from one IED
configuration.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1261

Section 20
Basic IED functions
20.13.2

1MRK 502 066-UUS A

Function block
SMBO
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10

^BO1
^BO2
^BO3
^BO4
^BO5
^BO6
^BO7
^BO8
^BO9
^BO10
IEC05000439-2-en.vsd

IEC05000439 V2 EN

Figure 566:

20.13.3

Signals
Table 874:
Name

20.13.4

SMBO function block

SMBO Input signals


Type

Default

Description

BO1

BOOLEAN

Signal name for BO1 in Signal Matrix Tool

BO2

BOOLEAN

Signal name for BO2 in Signal Matrix Tool

BO3

BOOLEAN

Signal name for BO3 in Signal Matrix Tool

BO4

BOOLEAN

Signal name for BO4 in Signal Matrix Tool

BO5

BOOLEAN

Signal name for BO5 in Signal Matrix Tool

BO6

BOOLEAN

Signal name for BO6 in Signal Matrix Tool

BO7

BOOLEAN

Signal name for BO7 in Signal Matrix Tool

BO8

BOOLEAN

Signal name for BO8 in Signal Matrix Tool

BO9

BOOLEAN

Signal name for BO9 in Signal Matrix Tool

BO10

BOOLEAN

Signal name for BO10 in Signal Matrix Tool

Operation principle
The Signal matrix for binary outputs (SMBO) function , see figure 566, receives logical
signal from the IED configuration, which is transferring to the real (hardware) outputs, via
the Signal Matrix Tool (SMT). The inputs in SMBO are BO1 to BO10 and they, as well
as the whole function block, can be tag-named. The name tags will appear in SMT as
information which signals shall be connected between physical IO and the SMBO.

20.14

1262

Signal matrix for mA inputs SMMI

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.14.1

Functionality
The Signal matrix for mA inputs (SMMI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT). See the
Application Manual for information about how milliamp (mA) inputs from external
transducers are physically connected to the MIM board inputs used in an IED. Via the
SMMI, the signals are brought into the IED configuration, for example, to the input for
ambient temperature compensation of the thermal overload function when there is a need
for ambient temperature compensation in the thermal function.

20.14.2

Function block
SMMI
^AI1
^AI2
^AI3
^AI4
^AI5
^AI6

^AI1
^AI2
^AI3
^AI4
^AI5
^AI6
IEC05000440.vsd

IEC05000440 V3 EN

Figure 567:

20.14.3

SMMI function block

Signals
Table 875:
Name

SMMI Input signals


Type

Default

Description

AI1

REAL

SMT connected milliampere input

AI2

REAL

SMT connected milliampere input

AI3

REAL

SMT connected milliampere input

AI4

REAL

SMT connected milliampere input

AI5

REAL

SMT connected milliampere input

AI6

REAL

SMT connected milliampere input

Table 876:
Name

SMMI Output signals


Type

Description

AI1

REAL

Analog milliampere input 1

AI2

REAL

Analog milliampere input 2

AI3

REAL

Analog milliampere input 3

AI4

REAL

Analog milliampere input 4

AI5

REAL

Analog milliampere input 5

AI6

REAL

Analog milliampere input 6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1263

Section 20
Basic IED functions
20.14.4

1MRK 502 066-UUS A

Operation principle
The Signal matrix for mA inputs (SMMI) function, see figure 567, receives its inputs from
the real (hardware) mA inputs (the MIM boards) via the Signal Matrix Tool (SMT), and
makes them available to the rest of the configuration via its analog outputs, named AI1 to
AI6. The inputs, outputs, as well as the whole block, can be given user-defined names
which will be represented in SMT and ACT.
The outputs on SMMI can also be connected to the IEC61850 generic communication I/
O functions (MVGAPC) for further use of the mA signals elsewhere in a substation
system.

20.15

Signal matrix for analog inputs SMAI

20.15.1

Functionality
Signal matrix for analog inputs (SMAI), also known as the preprocessor function block,
analyses the connected four analog signals (three phases and neutral) and calculates all
relevant information from them like the phasor magnitude, phase angle, frequency, true
RMS value, harmonics, sequence components and so on. This information is then used by
the respective functions connected to this SMAI block in ACT (for example protection,
measurement or monitoring functions).

20.15.2

Function block
SMAI1
BLOCK
DFTSPFC
REVROT
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N

SPFCOUT
G1AI3P
G1AI1
G1AI2
G1AI3
G1AI4
G1N
ANSI14000027-1-en.vsd

ANSI14000027 V1 EN

Figure 568:

SMAI1 function block

Figure 568 is an example of SMAI1:n in each of the three task time groups 1, 2 or 3 where:

1264

n=112 in task group 1


n=1324 in task group 2
n=2536 in task group 3

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

The task time defines the execution repetition rate, and is 1, 3 or 8 ms respectively for the
three task time groups.
SMAI2
BLOCK
REVROT
^GRP2_A
^GRP2_B
^GRP2_C
^GRP2_N

G2AI3P
G2AI1
G2AI2
G2AI3
G2AI4
G2N
ANSI14000028-1-en.vsd

ANSI14000028 V1 EN

Figure 569:

SMAI2 function block

Figure 569 is an example of SMAI2:n to SMAI12:m in each of the three task time groups
1, 2 or 3 where:

n=2 and m=12 in task group 1


n=14 and m=24 in task group 2
n=26 and m=36 in task group 3

The task time defines the execution repetition rate, and is 3, 8 or 1 ms respectively for the
three task time groups.

20.15.3

Signals
Table 877:
Name

SMAI1 Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block group 1

DFTSPFC

REAL

20.0

Number of samples per fundamental cycle used for DFT


calculation

REVROT

BOOLEAN

Reverse rotation group 1

GRP1_A

STRING

First analog input used for phase A or AB quantity

GRP1_B

STRING

Second analog input used for phase B or BC quantity

GRP1_C

STRING

Third analog input used for phase C or CA quantity

GRP1_N

STRING

Fourth analog input used for residual or neutral quantity

Table 878:
Name

SMAI1 Output signals


Type

Description

SPFCOUT

REAL

Number of samples per fundamental cycle from internal


DFT reference function

G1AI3P

GROUP SIGNAL

Group 1 analog input 3-phase group

G1AI1

GROUP SIGNAL

Group 1 analog input 1

G1AI2

GROUP SIGNAL

Group 1 analog input 2

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1265

Section 20
Basic IED functions

1MRK 502 066-UUS A

Name

Description

GROUP SIGNAL

Group 1 analog input 3

G1AI4

GROUP SIGNAL

Group 1 analog input 4

G1N

GROUP SIGNAL

Group parameter for residual sample

Table 879:
Name

SMAI2 Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block group 2

REVROT

BOOLEAN

Reverse rotation group 2

GRP2_A

STRING

First analog input used for phase A or AB quantity

GRP2_B

STRING

Second analog input used for phase B or BC quantity

GRP2_C

STRING

Third analog input used for phase C or CA quantity

GRP2_N

STRING

Fourth analog input used for residual or neutral quantity

Table 880:
Name

20.15.4

Type

G1AI3

SMAI2 Output signals


Type

Description

G2AI3P

GROUP SIGNAL

Group 2 analog input 3-phase group

G2AI1

GROUP SIGNAL

Group 2 analog input 1

G2AI2

GROUP SIGNAL

Group 2 analog input 2

G2AI3

GROUP SIGNAL

Group 2 analog input 3

G2AI4

GROUP SIGNAL

Group 2 analog input 4

G2N

GROUP SIGNAL

Group parameter for residual sample

Settings
Settings DFTRefExtOut and DFTReference shall be set to default value
InternalDFTRef if no VT inputs are available. Internal nominal frequency
DFT reference is then the reference.

1266

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Table 881:
Name

SMAI1 Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

DFTRefExtOut

InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref

InternalDFTRef

DFT reference for external output

DFTReference

InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref

InternalDFTRef

DFT reference

ConnectionType

Ph-N
Ph-Ph

Ph-N

Input connection type

AnalogInputType

Voltage
Current

Voltage

Analog input signal type

Table 882:
Name

SMAI1 Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

Negation

Disabled
NegateN
Negate3Ph
Negate3Ph+N

Disabled

Negation

MinValFreqMeas

5 - 200

10

Limit for frequency calculation in % of VBase

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1267

Section 20
Basic IED functions

Table 883:
Name

1MRK 502 066-UUS A

SMAI2 Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

DFTReference

InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref

InternalDFTRef

DFT reference

ConnectionType

Ph-N
Ph-Ph

Ph-N

Input connection type

AnalogInputType

Voltage
Current

Voltage

Analog input signal type

Table 884:
Name

SMAI2 Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

Negation

Disabled
NegateN
Negate3Ph
Negate3Ph+N

Disabled

Negation

MinValFreqMeas

5 - 200

10

Limit for frequency calculation in % of VBase

20.15.5

Operation principle
Every Signal matrix for analog inputs function (SMAI) can receive four analog signals
(three phases and one neutral or residual value), either voltage or current, see figure 568
and figure 569. SMAI outputs give information about every aspect of the 3ph analog
signals acquired (phase angle, RMS value, frequency and frequency derivates etc. 244
values in total). The BLOCK input will force all outputs to value zero.
System phase rotation and frequency are defined using the PhaseRotation and Frequency
settings in the primary system values PRIMVAL function. Logic 1 in the REVROT input
to the SMAI function means that the phase rotation is changed relative to the set
PhaseRotation in PRIMVAL.
The output signal AI1 to AI4 are direct output of the, in SMT, connected input to GRPx_A,
GRPxB, GRPxC and GRPx_N, x=1-12. AIN is always calculated residual sum from the

1268

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

first three inputs. A3P is grouped, three-phase information containing all relevant
information about four connected inputs. Note that all other functions, with a few
exceptions, use this output in configuration. Note that the SMAI function will always
calculate the residual sum of current/voltage if the input GRPxN is not connected in SMT.
Applications with a few exceptions shall always be connected to AI3P.

20.15.5.1

Frequency values
The SMAI function includes a functionality based on the level of positive sequence
voltage, MinValFreqMeas, to validate if the frequency measurement is valid or not. If the
positive sequence voltage is lower than MinValFreqMeas, the function freezes the
frequency output value for 500 ms and after that the frequency output is set to the nominal
value. A signal is available for the SMAI function to prevent operation due to non-valid
frequency values. MinValFreqMeas is set as % of VBase/3
If SMAI setting ConnectionType is Ph-Ph, at least two of the inputs GRPx_A, GRPx_B
and GRPx_C, where 1x12, must be connected in order to calculate the positive
sequence voltage. Note that phase to phase inputs shall always be connected as follows:
A-B to GRPxA, B-C to GRPxB, C-A to GRPxC. If SMAI setting ConnectionType is PhN, all three inputs GRPx_A, GRPx_B and GRPx_C must be connected in order to
calculate the positive sequence voltage.
If only one phase-phase voltage is available and SMAI setting ConnectionType is Ph-Ph,
the user is advised to connect two (not three) of the inputs GRPx_A, GRPx_B and
GRPx_C to the same voltage input as shown in figure 570 to make SMAI calculate a
positive sequence voltage.

SMAI1

VAB

TRM_40.CH7(U)

BLOCK
DFTSPFC
REVROT
PHASEA
^GRP1_A
PHASEB
^GRP1_B
PHASEC
^GRP1_C
NEUTRAL
^GRP1_N

SPFCOUT
G1AI3P
G1AI1
G1AI2
G1AI4

SAPTOF
V3P*
BLOCK
BLKTRIP

TRIP
PICK UP
BLKDMAGN
FREQ

SAPTOF(1)_TRIP

G1N

ANSI10000060-1-en.vsdx

ANSI10000060 V1 EN

Figure 570:

Connection example

The above described scenario does not work if SMAI setting


ConnectionType is Ph-N. If only one phase-ground voltage is available,
the same type of connection can be used but the SMAI ConnectionType
setting must still be Ph-Ph and this has to be accounted for when setting
MinValFreqMeas. If SMAI setting ConnectionType is Ph-N and the same
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1269

Section 20
Basic IED functions

1MRK 502 066-UUS A

voltage is connected to all three SMAI inputs, the positive sequence


voltage will be zero and the frequency functions will not work properly.

The outputs from the above configured SMAI block shall only be used for
Overfrequency protection (SAPTOF, 81), Underfrequency protection
(SAPTUF, 81) and Rate-of-change frequency protection (SAPFRC, 81)
due to that all other information except frequency and positive sequence
voltage might be wrongly calculated.
The same phase-phase voltage connection principle shall be used for frequency tracking
master SMAI block in pump-storage power plant applications when swapping of positive
and negative sequence voltages happens during generator/motor mode of operation.

20.16

Summation block 3 phase 3PHSUM

20.16.1

Functionality
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of threephase analog signals (of the same type) for those IED functions that might need it.

20.16.2

Function block

3PHSUM
BLOCK
REVROT
^G1AI3P*
^G2AI3P*

AI3P
AI1
AI2
AI3
AI4
IEC05000441-3-en.vsdx

IEC05000441 V3 EN

Figure 571:

1270

3PHSUM function block

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.16.3

Signals
Table 885:
Name

Type

Default

Description

BLOCK

BOOLEAN

Block

BLKGR1

BOOLEAN

Block input for group 1

BLKGR2

BOOLEAN

Block input for group 2

REVROT

BOOLEAN

Reverse rotation

G1AI3P

GROUP
SIGNAL

Group 1 three phase analog input from first SMAI

G2AI3P

GROUP
SIGNAL

Group 2 three phase analog input from second SMAI

Table 886:
Name

20.16.4

3PHSUM Input signals

3PHSUM Output signals


Type

Description

SPFCOUT

REAL

Number of samples per fundamental cycle from internal


DFT reference function

AI3P

GROUP SIGNAL

Linear combination of two connected three phase inputs

AI1

GROUP SIGNAL

Linear combination of input 1 signals from both SMAI


blocks

AI2

GROUP SIGNAL

Linear combination of input 2 signals from both SMAI


blocks

AI3

GROUP SIGNAL

Linear combination of input 3 signals from both SMAI


blocks

AI4

GROUP SIGNAL

Linear combination of input 4 signals from both SMAI


blocks

Settings
Settings DFTRefExtOut and DFTReference shall be set to default value
InternalDFTRef if no VT inputs are available.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1271

Section 20
Basic IED functions

Table 887:
Name

1MRK 502 066-UUS A

3PHSUM Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

GlobalBaseSel

1 - 12

Selection of one of the Global Base Value


groups

SummationType

Group1+Group2
Group1-Group2
Group2-Group1
-(Group1+Group2)

Group1+Group2

Summation type

DFTReference

InternalDFTRef
DFTRefGrp1
External DFT ref

InternalDFTRef

DFT reference

DFTRefExtOut

InternalDFTRef
DFTRefGrp1
External DFT ref

InternalDFTRef

DFT reference for external output

Table 888:
Name
FreqMeasMinVal

20.16.5

3PHSUM Non group settings (advanced)


Values (Range)
5 - 200

Unit
%

Step
1

Default
10

Description
Amplitude limit for frequency calculation in % of
UBase

Operation principle
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal matrix
for analog inputs function (SMAI). In the same way, the BLOCK input will reset all the
outputs of the function to 0.

20.17

Global base values GBASVAL

20.17.1

Identification

20.17.2

Function description

IEC 61850
identification

Global base values

GBASVAL

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
Global base values function (GBASVAL) is used to provide global values, common for
all applicable functions within the IED. One set of global values consists of values for
current, voltage and apparent power and it is possible to have twelve different sets.

1272

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

This is an advantage since all applicable functions in the IED use a single source of base
values. This facilitates consistency throughout the IED and also facilitates a single point
for updating values when necessary.
Each applicable function in the IED has a parameter, GlobalBaseSel, defining one out of
the twelve sets of GBASVAL functions.

20.17.3
Table 889:
Name

Settings
GBASVAL Non group settings (basic)
Values (Range)

Unit

Step

Default

VBase

0.05 - 2000.00

kV

0.05

400.00

Description
Global base voltage

IBase

1 - 99999

3000

Global base current

SBase

1.00 - 200000.00

MVA

0.05

2000.00

Global base apparent power

20.18

Primary system values PRIMVAL

20.18.1

Identification
Function description

IEC 61850
identification

Primary system values

20.18.2

PRIMVAL

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Functionality
The rated system frequency and phase rotation direction are set under Main menu/
Configuration/ Power system/ Primary Values in the local HMI and PCM600
parameter setting tree.

20.18.3
Table 890:
Name

Settings
PRIMVAL Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Frequency

50.0 - 60.0

Hz

10.0

50.0

Rated system frequency

PhaseRotation

Normal=ABC
Inverse=ACB

Normal=ABC

System phase rotation

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1273

Section 20
Basic IED functions

1MRK 502 066-UUS A

20.19

Denial of service DOS

20.19.1

Functionality
The Denial of service functions (DOSFRNT, DOSLANAB and DOSLANCD) are
designed to limit overload on the IED produced by heavy Ethernet network traffic. The
communication facilities must not be allowed to compromise the primary functionality of
the device. All inbound network traffic will be quota controlled so that too heavy network
loads can be controlled. Heavy network load might for instance be the result of
malfunctioning equipment connected to the network.

20.19.2

Function blocks
DOSFRNT
LINKUP
WARNING
ALARM
IEC09000749-1-en.vsd
IEC09000749 V1 EN

Figure 572:

DOSFRNT function block

DOSLANAB

LINKUP
WARNING
ALARM

IEC13000308-1-en.vsd
IEC13000308 V1 EN

Figure 573:

DOSLANAB function block

DOSLANCD

LINKUP
WARNING
ALARM

IEC13000309-1-en.vsd
IEC13000309 V1 EN

Figure 574:

20.19.3

Signals
Table 891:
Name

1274

DOSLANCD function block

DOSFRNT Output signals


Type

Description

LINKUP

BOOLEAN

Ethernet link status

WARNING

BOOLEAN

Frame rate is higher than normal state

ALARM

BOOLEAN

Frame rate is higher than throttle state

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 20
Basic IED functions

1MRK 502 066-UUS A

Table 892:
Name

Type

Description

LINKUP

BOOLEAN

Ethernet link status

WARNING

BOOLEAN

Frame rate is higher than normal state

ALARM

BOOLEAN

Frame rate is higher than throttle state

Table 893:
Name

20.19.4

DOSLANAB Output signals

DOSLANCD Output signals


Type

Description

LINKUP

BOOLEAN

Ethernet link status

WARNING

BOOLEAN

Frame rate is higher than normal state

ALARM

BOOLEAN

Frame rate is higher than throttle state

Settings
The function does not have any parameters available in the local HMI or PCM600.

20.19.5

Monitored data
Table 894:
Name

DOSFRNT Monitored data


Type

Values (Range)

Unit

Description

State

INTEGER

0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll

Frame rate control state

Quota

INTEGER

Quota level in percent 0-100

Table 895:
Name

DOSLANAB Monitored data


Type

Values (Range)

Unit

Description

DoSStatus

INTEGER

0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll

Frame rate control state

Quota

INTEGER

Quota level in percent 0-100

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1275

Section 20
Basic IED functions

1MRK 502 066-UUS A

Table 896:
Name

20.19.6

DOSLANCD Monitored data


Type

Values (Range)

Unit

Description

DoSStatus

INTEGER

0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll

Frame rate control state

Quota

INTEGER

Quota level in percent 0-100

Operation principle
The Denial of service functions (DOSFRNT, DOSLANAB and DOSLANCD) measures
the IED load from communication and, if necessary, limit it for not jeopardizing the IEDs
control and protection functionality due to high CPU load. The function has the following
outputs:

1276

LINKUP indicates the Ethernet link status


WARNING indicates that communication (frame rate) is higher than normal
ALARM indicates that the IED limits communication

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Section 21

IED hardware

21.1

Overview

21.1.1

Variants of case size with local HMI display

ANSI04000458-2-en.psd
ANSI04000458 V2 EN

Figure 575:

1/2 19 case with local HMI display.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1277

Section 21
IED hardware

1MRK 502 066-UUS A

ANSI05000762-2-en.psd
ANSI05000762 V2 EN

Figure 576:

3/4 19 case with local HMI display.

ANSI04000460 -2-en.psd
ANSI04000460 V2 EN

Figure 577:

1278

1/1 19 case with local HMI display.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.1.2
Table 897:

Case from the rear side


Designations for 1/2 x 19 casing with 1 TRM slot

Module

Rear Positions

PSM

X11

BIM, BOM, SOM, IOM or


MIM

X31 and X32 etc. to X51


and X52

SLM

X301:A, B, C, D

LDCM, IRIG-B or RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM, IRIG-B or GTM

X312, X313

TRM

X401

1MRK002801-AC-2-670-1.2-PG V.3 EN
1MRK002801-AC-2-670-1.2-PG V3 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1279

Section 21
IED hardware

Table 898:

1MRK 502 066-UUS A

Designations for 3/4 x 19 casing with 1 TRM slot

Module

Rear Positions

PSM

X11

BIM, BOM, SOM, IOM or


MIM

X31 and X32 etc. to


X101 and X102

SLM

X301:A, B, C, D

LDCM, IRIG-B or RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM, RS485 or GTM

X312, X313

TRM

X401

1MRK002801-AC-3-670-1.2-PG V.3 EN
1MRK002801-AC-3-670-1.2-PG V3 EN

1280

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Table 899:

Designations for 3/4 x 19 casing with 2 TRM slot

Module

Rear Positions

PSM

X11

BIM, BOM, SOM, IOM or


MIM

X31 and X32 etc. to X71 and


X72

SLM

X301:A, B, C, D

LDCM, IRIG-B or RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM, RS485 or GTM

X312, X313, X322, X323

TRM 1

X401

TRM 2

X411

1MRK002801-AC-4-670-1.2-PG V.3 EN
1MRK002801-AC-4-670-1.2-PG V3 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1281

Section 21
IED hardware

Table 900:

1MRK 502 066-UUS A

Designations for 1/1 x 19 casing with 1 TRM slot

Module

Rear Positions

PSM

X11

BIM, BOM, SOM,


IOM or MIM

X31 and X32 etc. to X161 and


X162

SLM

X301:A, B, C, D

LDCM, IRIG-B or
RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM,RS485 or
GTM

X312, X313

TRM

X401

1MRK002801-AC-5-670-1.2-PG V.3 EN
1MRK002801-AC-5-670-1.2-PG V3 EN

1282

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Table 901:

Designations for 1/1 x 19 casing with 2 TRM slots

Module

Rear Positions

PSM

X11

BIM, BOM, SOM,


IOM or MIM

X31 and X32 etc. to X131 and


X132

SLM

X301:A, B, C, D

LDCM, IRIG-B or
RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM, RS485 or
GTM

X312, X313, X322, X323

TRM 1

X401

TRM 2

X411

1MRK002801-AC-6-670-1.2-PG V.3 EN
1MRK002801-AC-6-670-1.2-PG V3 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1283

Section 21
IED hardware

1MRK 502 066-UUS A

21.2

Hardware modules

21.2.1

Overview
Table 902:

Basic modules

Module

Description

Power supply module (PSM)

Including a regulated DC/DC converter that supplies


auxiliary voltage to all static circuits.

Numerical module (NUM)

Module for overall application control. All information is


processed or passed through this module, such as
configuration, settings and communication.

Local Human machine interface (LHMI)

The module consists of LED:s, an LCD, a push button


keyboard and an ethernet connector used to connect a
PC to the IED.

Transformer input module (TRM)

Transformer module that galvanically separates the


internal circuits from the VT and CT circuits. It has 12
analog inputs.

Analog digital conversion module (ADM)

Slot mounted PCB with A/D conversion.

Table 903:

Application specific modules

Module

1284

An internal fail alarm output is available.

Description

Binary input module (BIM)

Module with 16 optically isolated binary inputs

Binary output module (BOM)

Module with 24 single outputs or 12 double-pole


command outputs including supervision function

Binary I/O module (IOM)

Module with 8 optically isolated binary inputs, 10 outputs


and 2 fast signalling outputs.

Line data communication modules (LDCM), short


range, medium range ,long range,X21

Modules used for digital communication to remote


terminal.

Serial SPA/LON/IEC 60870-5-103


communication modules (SLM)

Used for SPA/LON/IEC 608705103 communication

Optical ethernet module (OEM)

PMC board for IEC 61850 based communication.

mA input module (MIM)

Analog input module with 6 independent, galvanically


separated channels.

GPS time synchronization module (GSM)

Used to provide the IED with GPS time synchronization.

IRIG-B Time synchronization module (IRIG-B)

Module with 2 inputs. One is used for handling both


pulse-width modulated signals and amplitude
modulated signals and one is used for optical input type
ST for PPS time synchronization.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.2

Numeric processing module (NUM)

21.2.2.1

Introduction
The Numeric processing module (NUM), is a CPU-module that handles all protection
functions and logic.
For communication with high speed modules, e.g. analog input modules and high speed
serial interfaces, the NUM is equipped with a Compact PCI bus. The NUM is the compact
PCI system card i.e. it controls bus mastering, clock distribution and receives interrupts.

21.2.2.2

Functionality
The NUM, Numeric processing module is a high performance, compact-PCI CPU
module. It is 6U high and occupies one slot. Contact with the backplane is via two compact
PCI connectors and an euro connector.
The NUM has one PMC slot (32-bit IEEE P1386.1 compliant) and two PC-MIP slots onto
which mezzanine cards such as SLM or LDCM can be mounted.
To reduce bus loading of the compact PCI bus in the backplane the NUM has one internal
PCI bus for internal resources and the PMC/PC-MIP slots and external PCI accesses
through the backplane are buffered in a PCI/PCI bridge.
The application code and configuration data are stored in flash memory using a flash file
system.
The NUM is equipped with a real time clock. It uses a capacitor for power backup of the
real time clock.
No forced cooling is used on this standard module because of the low power dissipation.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1285

Section 21
IED hardware
21.2.2.3

1MRK 502 066-UUS A

Block diagram

Compact
Flash

Logic

PMC
connector

Memory

Ethernet

UBM
connector

PC-MIP

PCI-PCIbridge

Backplane
connector

North
bridge

CPU

en04000473.vsd
IEC04000473 V1 EN

Figure 578:

Numeric processing module block diagram

21.2.3

Power supply module (PSM)

21.2.3.1

Introduction
The power supply module is used to provide the correct internal voltages and full isolation
between the IED and the battery system. An internal fail alarm output is available.

1286

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.3.2

Design
There are two types of the power supply module. They are designed for different DC input
voltage ranges see table 904. The power supply module contains a built-in, self-regulated
DC/DC converter that provides full isolation between the terminal and the external battery
system.

Connection diagram

IEC08000476 V2 EN

Figure 579:

21.2.3.3

PSM Connection diagram.

Technical data
Table 904:

PSM - Power supply module

Quantity

21.2.4

Rated value

Nominal range

Auxiliary dc voltage, EL (input)

EL = (24 - 60) V
EL = (90 - 250) V

EL 20%
EL 20%

Power consumption

50 W typically

Auxiliary DC power in-rush

< 10 A during 0.1 s

Local human-machine interface (Local HMI)


Refer to section "" for information.

21.2.5

Transformer input module (TRM)

21.2.5.1

Introduction
The transformer input module is used to galvanically separate and adapt the secondary
currents and voltages generated by the measuring transformers. The module has twelve
inputs in different combinations of currents and voltage inputs. Either protection class or
metering class CT inputs are available.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1287

Section 21
IED hardware

1MRK 502 066-UUS A

Alternative connectors of Ring lug or Compression type can be ordered.

21.2.5.2

Design
The transformer module has 12 input transformers. There are several versions of the
module, each with a different combination of voltage and current input transformers.
Basic versions:

6 current channels and 6 voltage channels


7 current channels and 5 voltage channels
9 current channels and 3 voltage channels
12 current channels
6 current channels

The rated values and channel type, measurement or protection, of the current inputs are
selected at order.
Transformer input module for measuring should not be used with current
transformers intended for protection purposes, due to limitations in
overload characteristics.
The TRM is connected to the ADM and NUM.
For configuration of the input and output signals, refer to section "Signal matrix for analog
inputs SMAI".

1288

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

IEC08000479 V2 EN

Figure 580:

21.2.5.3

TRM connection diagram

Technical data
Table 905:

TRM - Energizing quantities, rated values and limits for protection transformer modules

Quantity

Rated value

Current

In = 1 or 5 A

Operative range

(0-100) x In

Permissive overload

4 In cont.
100 In for 1 s *)

Burden

< 150 mVA at In = 5 A


< 20 mVA at In = 1 A

Ac voltage

Vn = 120 V

Operative range

(0340) V

Permissive overload

420 V cont.
450 V 10 s

Nominal range
(0.2-40) In

0.5288 V

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1289

Section 21
IED hardware

1MRK 502 066-UUS A

Quantity

Rated value

Burden

< 20 mVA at 110 V

Frequency

fn = 60/50 Hz

*)

Nominal range
5%

max. 350 A for 1 s when COMBITEST test switch is included.

Table 906:

TRM - Energizing quantities, rated values and limits for measuring transformer modules

Quantity

Rated value

Current

In = 1 or 5 A

Permissive overload

1.1 In cont.
1.8 In for 30 min at In = 1 A
1.6 In for 30 min at In = 5 A

Burden

< 350 mVA at In = 5 A


< 200 mVA at In = 1 A

Ac voltage

Vn = 120 V

Operative range

(0340) V

Permissive overload

420 V cont.
450 V 10 s

Burden

< 20 mVA at 110 V

Frequency

fn = 60/50 Hz

Nominal range
(0-1.8) In at In = 1 A
(0-1.6) In at In = 5 A

0.5288 V

5%

21.2.6

Analog digital conversion module, with time synchronization


(ADM)

21.2.6.1

Introduction
The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC slot. The
PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards according to table
907. The OEM card should always be mounted on the ADM board.
Table 907:
PC-MIP cards

PC-MIP cards and PMC cards


PMC cards

LDCM

SLM

LR-LDCM

OEM 1 ch

MR-LDCM

OEM 2 ch

X21-LDCM
IRIG-B
RS485

1290

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.6.2

Design
The Analog digital conversion module input signals are voltage and current from the
transformer module. Shunts are used to adapt the current signals to the electronic voltage
level. To gain dynamic range for the current inputs, two shunts with separate A\D channels
are used for each input current. In this way a 20 bit dynamic range is obtained with a 16
bit A\D converter.
Input signals are sampled with a sampling freqency of 5 kHz at 50 Hz system frequency
and 6 kHz at 60 Hz system frequency.
The A\D converted signals goes through a filter with a cut off frequency of 500 Hz and are
reported to the numerical module (NUM) with 1 kHz at 50 Hz system frequency and 1,2
kHz at 60 Hz system frequency.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1291

Section 21
IED hardware

1MRK 502 066-UUS A

Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel 9
Channel 10
Channel 11
Channel 12

AD1
AD2
1.2v

AD3
AD4

PMC

level shift

PC-MIP
2.5v

PCI to PCI
PC-MIP

en05000474.vsd
IEC05000474 V1 EN

Figure 581:

1292

The ADM layout

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.7

Binary input module (BIM)

21.2.7.1

Introduction
The binary input module has 16 optically isolated inputs and is available in two versions,
one standard and one with enhanced pulse counting capabilities on the inputs to be used
with the pulse counter function. The binary inputs are freely programmable and can be
used for the input of logical signals to any of the functions. They can also be included in
the disturbance recording and event-recording functions. This enables extensive
monitoring and evaluation of operation of the IED and for all associated electrical circuits.

21.2.7.2

Design
The Binary input module contains 16 optical isolated binary inputs. The voltage level of
the binary input is selected at order.
For configuration of the input signals, refer to section "Signal matrix for binary inputs
SMBI".
A signal discriminator detects and blocks oscillating signals. When blocked, a hysteresis
function may be set to release the input at a chosen frequency, making it possible to use
the input for pulse counting. The blocking frequency may also be set.
Well defined input high and input low voltages ensure normal operation at battery supply
ground faults, see figure 582 The figure shows the typical operating characteristics of the
binary inputs of the four voltage levels.
The standard version of binary inputs gives an improved capability to withstand
disturbances and should generally be used when pulse counting is not required. Inputs are
debounced by software.
I/O events are time stamped locally on each module for minimum time deviance and
stored by the event recorder if present.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1293

Section 21
IED hardware

1MRK 502 066-UUS A

[V]
300

176
144
88
72
38
32
19
17
24/30V

48/60V

110/125V

220/250V
xx99000517-2_ansi.vsd

ANSI99000517 V2 EN

Figure 582:

Voltage dependence for the binary inputs


Operation

Operation uncertain

No operation
IEC99000517-ABC V1 EN

This binary input module communicates with the Numerical module (NUM).
The design of all binary inputs enables the burn off of the oxide of the relay contact
connected to the input, despite the low, steady-state power consumption, which is shown
in figure 583 and 584.

1294

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

[mA]
50

55

[ms]
en07000104-3.vsd

IEC07000104 V3 EN

Figure 583:

Approximate binary input inrush current for the standard version of BIM.

[mA]
50

5.5

[ms]
en07000105-1.vsd

IEC07000105 V2 EN

Figure 584:

Approximate binary input inrush current for the BIM version with
enhanced pulse counting capabilities.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1295

Section 21
IED hardware

1MRK 502 066-UUS A

IEC99000503 V3 EN

Figure 585:

21.2.7.3

Connection diagram

Signals
Table 908:
Name

BIM Output signals


Type

Description

STATUS

BOOLEAN

Binary input module status

BI1

BOOLEAN

Binary input 1

BI2

BOOLEAN

Binary input 2

BI3

BOOLEAN

Binary input 3

Table continues on next page

1296

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Name

21.2.7.4
Table 909:
Name

Type

Description

BI4

BOOLEAN

Binary input 4

BI5

BOOLEAN

Binary input 5

BI6

BOOLEAN

Binary input 6

BI7

BOOLEAN

Binary input 7

BI8

BOOLEAN

Binary input 8

BI9

BOOLEAN

Binary input 9

BI10

BOOLEAN

Binary input 10

BI11

BOOLEAN

Binary input 11

BI12

BOOLEAN

Binary input 12

BI13

BOOLEAN

Binary input 13

BI14

BOOLEAN

Binary input 14

BI15

BOOLEAN

Binary input 15

BI16

BOOLEAN

Binary input 16

Settings
BIM Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Enabled

Operation Disabled/Enabled

DebounceTime

0.001 - 0.020

0.001

0.001

Debounce time for binary inputs

OscBlock

1 - 40

Hz

40

Oscillation block limit

OscRelease

1 - 30

Hz

30

Oscillation release limit

21.2.7.5

Monitored data
Table 910:
Name
STATUS

BIM Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=Error

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Unit
-

Description
Binary input module status

1297

Section 21
IED hardware
21.2.7.6

1MRK 502 066-UUS A

Technical data
Table 911:

BIM - Binary input module

Quantity

Rated value

Nominal range

Binary inputs

16

DC voltage, RL

24/30 V
48/60 V
125 V
220/250 V

RL 20%
RL 20%
RL 20%
RL 20%

Power consumption
24/30 V, 50mA
48/60 V, 50mA
125 V, 50mA
220/250 V, 50mA
220/250 V, 110mA

max. 0.05 W/input


max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input

Counter input frequency

10 pulses/s max

Oscillating signal discriminator

Blocking settable 140 Hz


Release settable 130 Hz

Debounce filter

Settable 120ms

Maximum 176 binary input channels may be activated simultaneously


with influencing factors within nominal range.

Table 912:

BIM - Binary input module with enhanced pulse counting capabilities

Quantity

1298

Rated value

Nominal range

Binary inputs

16

DC voltage, RL

24/30 V
48/60 V
125 V
220/250 V

RL 20%
RL 20%
RL 20%
RL 20%

Power consumption
24/30 V
48/60 V
125 V
220/250 V

max. 0.05 W/input


max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input

Counter input frequency

10 pulses/s max

Balanced counter input frequency

40 pulses/s max

Oscillating signal discriminator

Blocking settable 140 Hz


Release settable 130 Hz

Debounce filter

Settable 1-20 ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Maximum 176 binary input channels may be activated simultaneously


with influencing factors within nominal range.

21.2.8

Binary output modules (BOM)

21.2.8.1

Introduction
The binary output module has 24 independent output relays and is used for trip output or
any signaling purpose.

21.2.8.2

Design
The binary output module (BOM) has 24 software supervised output relays. Each pair of
relays have a common power source input to the contacts, see figure 586. This should be
considered when connecting the wiring to the connection terminal on the back of the IED.
The high closing and carrying current capability allows connection directly to breaker trip
and closing coils. If breaking capability is required to manage fail of the breaker auxiliary
contacts normally breaking the trip coil current, a parallel reinforcement is required.
For configuration of the output signals, refer to section "Signal matrix for binary outputs
SMBO".
Output module

3
ANSI_xx00000299.vsd
ANSI00000299 V1 EN

Figure 586:

Relay pair example

1 Output connection from relay 1


2 Output signal power source connection
3 Output connection from relay 2

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1299

Section 21
IED hardware

1MRK 502 066-UUS A

IEC99000505 V3 EN

Figure 587:

21.2.8.3

Connection diagram

Signals
Table 913:
Name

BOM Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block binary outputs

BO1

BOOLEAN

Binary output 1

BO2

BOOLEAN

Binary output 2

BO3

BOOLEAN

Binary output 3

BO4

BOOLEAN

Binary output 4

BO5

BOOLEAN

Binary output 5

BO6

BOOLEAN

Binary output 6

BO7

BOOLEAN

Binary output 7

BO8

BOOLEAN

Binary output 8

BO9

BOOLEAN

Binary output 9

Table continues on next page


1300

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Name

Type

Binary output 10

BO11

BOOLEAN

Binary output 11

BO12

BOOLEAN

Binary output 12

BO13

BOOLEAN

Binary output 13

BO14

BOOLEAN

Binary output 14

BO15

BOOLEAN

Binary output 15

BO16

BOOLEAN

Binary output 16

BO17

BOOLEAN

Binary output 17

BO18

BOOLEAN

Binary output 18

BO19

BOOLEAN

Binary output 19

BO20

BOOLEAN

Binary output 20

BO21

BOOLEAN

Binary output 21

BO22

BOOLEAN

Binary output 22

BO23

BOOLEAN

Binary output 23

BO24

BOOLEAN

Binary output 24

BOM Output signals

Name

Type

STATUS

Table 915:
Name
Operation

21.2.8.5

Description

BOOLEAN

Table 914:

21.2.8.4

Default

BO10

Description

BOOLEAN

Binary output part of IOM module status

Settings
BOM Non group settings (basic)
Values (Range)
Disabled
Enabled

Unit

Step

Default
Enabled

Description
Operation Disabled/Enabled

Monitored data
Table 916:
Name

BOM Monitored data


Type

Values (Range)

Unit

Description

STATUS

BOOLEAN

0=Ok
1=Error

Binary output part of IOM


module status

BO1VALUE

BOOLEAN

1=1
0=0

Binary output 1 value

BO1FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 1 force

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1301

Section 21
IED hardware

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

BO1

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 1 status

BO2VALUE

BOOLEAN

1=1
0=0

Binary output 2 value

BO2FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 2 force

BO2

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 2 status

BO3VALUE

BOOLEAN

1=1
0=0

Binary output 3 value

BO3FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 3 force

BO3

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 3 status

BO4VALUE

BOOLEAN

1=1
0=0

Binary output 4 value

BO4FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 4 force

BO4

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 4 status

BO5VALUE

BOOLEAN

1=1
0=0

Binary output 5 value

BO5FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 5 force

BO5

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 5 status

BO6VALUE

BOOLEAN

1=1
0=0

Binary output 6 value

BO6FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 6 force

BO6

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 6 status

BO7VALUE

BOOLEAN

1=1
0=0

Binary output 7 value

BO7FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 7 force

BO7

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 7 status

BO8VALUE

BOOLEAN

1=1
0=0

Binary output 8 value

Table continues on next page


1302

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

BO8FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 8 force

BO8

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 8 status

BO9VALUE

BOOLEAN

1=1
0=0

Binary output 9 value

BO9FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 9 force

BO9

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 9 status

BO10VALUE

BOOLEAN

1=1
0=0

Binary output 10 value

BO10FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 10 force

BO10

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 10 status

BO11VALUE

BOOLEAN

1=1
0=0

nary output 11 value

BO11FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 11 force

BO11

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 11 status

BO12VALUE

BOOLEAN

1=1
0=0

Binary output 12 value

BO12FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 12 force

BO12

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 12 status

BO13VALUE

BOOLEAN

1=1
0=0

Binary output 13 value

BO13FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 13 force

BO13

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 13 status

BO14VALUE

BOOLEAN

1=1
0=0

Binary output 14 value

BO14FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 14 force

BO14

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 14 status

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1303

Section 21
IED hardware

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

BO15VALUE

BOOLEAN

1=1
0=0

Binary output 15 value

BO15FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 15 force

BO15

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 15 status

BO16VALUE

BOOLEAN

1=1
0=0

Binary output 16 value

BO16FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 16 force

BO16

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 16 status

BO17VALUE

BOOLEAN

1=1
0=0

Binary output 17 value

B017FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 17 force

BO17

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 17 status

BO18VALUE

BOOLEAN

1=1
0=0

Binary output 18 value

BO18FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 18 force

BO18

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 18 status

BO19VALUE

BOOLEAN

1=1
0=0

Binary output 19 value

BO19FORCE

BOOLEAN

1=Forced
0=Normal

Binary output 19 force

BO19

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 19 status

BO20VALUE

BOOLEAN

1=1
0=0

Binary output 20 value

BO20FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 20 force

BO20

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 20 status

BO21VALUE

BOOLEAN

1=1
0=0

Binary output 21 value

BO21FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 21 force

Table continues on next page

1304

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Name

21.2.8.6

Type

Values (Range)

Unit

Description

BO21

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 21 status

BO22VALUE

BOOLEAN

1=1
0=0

Binary output 22 value

BO22FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 22 force

BO22

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 22 status

BO23VALUE

BOOLEAN

1=1
0=0

Binary output 23 value

BO23FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 23 force

BO23

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 23 status

BO24VALUE

BOOLEAN

1=1
0=0

Binary output 24 value

BO24FORCE

BOOLEAN

0=Normal
1=Forced

nary output 24 force

BO24

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 24 status

Technical data
Table 917:

BOM - Binary output module contact data (reference standard: IEC 61810-2)

Function or quantity

Trip and Signal relays

Binary outputs

24

Max system voltage

250 V AC, DC

Test voltage across open contact, 1 min

1000 V rms

Current carrying capacity


Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous

8A
10 A
12 A

Making capacity at inductive load with L/R>10 ms


0.2 s
1.0 s

30 A
10 A

Breaking capacity for AC, cos j>0.4

250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms

48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1305

Section 21
IED hardware

1MRK 502 066-UUS A

Maximum 72 outputs may be activated simultaneously with influencing


factors within nominal range. After 6 ms an additional 24 outputs may be
activated. The activation time for the 96 outputs must not exceed 200 ms.
48 outputs can be activated during 1 s. Continued activation is possible
with respect to current consumption but after 5 minutes the temperature
rise will adversely affect the hardware life. Maximum two relays per
BOM/IOM/SOM should be activated continuously due to power
dissipation.

21.2.9

Static binary output module (SOM)

21.2.9.1

Introduction
The static binary output module has six fast static outputs and six change over output
relays for use in applications with high speed requirements.

21.2.9.2

Design
The Static output module (SOM) have 6 normally open (NO) static outputs and 6
electromechanical relay outputs with change over contacts.
The SOM consists mainly of:

An MCU
A CAN-driver
6 static relays outputs
6 electromechanical relay outputs
A DC/DC converter
Connectors interfacing

CAN-bus to backplane CBM


IO-connectors to binary outputs (2 pcs.)

The following parts are supervised:

1306

Interruption in relay coil


Short circuit of relay coil
Driver failure

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

IEC09000974-1-en.vsd

IEC09000974 V1 EN

Figure 588:

SOM Static output principle

1MRK002802-AB-13-670-1.2-PG-ANSI V1 EN

Figure 589:

21.2.9.3

Connection diagram of the static output module

Signals
Table 918:
Name

SOM Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block binary outputs

BO1

BOOLEAN

Binary output 1

BO2

BOOLEAN

Binary output 2

BO3

BOOLEAN

Binary output 3

BO4

BOOLEAN

Binary output 4

BO5

BOOLEAN

Binary output 5

BO6

BOOLEAN

Binary output 6

BO7

BOOLEAN

Static binary output 7

BO8

BOOLEAN

Static binary output 8

BO9

BOOLEAN

Static binary output 9

BO10

BOOLEAN

Static binary output 10

BO11

BOOLEAN

Static binary output 11

BO12

BOOLEAN

Static binary output 12

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1307

Section 21
IED hardware

1MRK 502 066-UUS A

Table 919:

SOM Output signals

Name

Type

STATUS

21.2.9.4
Table 920:
Name
Operation

21.2.9.5

Description

BOOLEAN

Static binary output module status

Settings
SOM Non group settings (basic)
Values (Range)
Disabled
Enabled

Unit

Step

Default
Enabled

Description
Operation Disabled/Enabled

Monitored data
Table 921:
Name

SOM Monitored data


Type

Values (Range)

Unit

Description

STATUS

BOOLEAN

0=Ok
1=Error

Static binary output module


status

BO1VALUE

BOOLEAN

1=1
0=0

Binary output 1 value

BO1FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 1 force

BO1

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 1 status

BO2VALUE

BOOLEAN

1=1
0=0

Binary output 2 value

BO2FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 2 force

BO2

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 2 status

BO3VALUE

BOOLEAN

1=1
0=0

Binary output 3 value

BO3FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 3 force

BO3

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 3 status

BO4VALUE

BOOLEAN

1=1
0=0

Binary output 4 value

BO4FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 4 force

Table continues on next page

1308

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

BO4

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 4 status

BO5VALUE

BOOLEAN

1=1
0=0

Binary output 5 value

BO5FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 5 force

BO5

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 5 status

BO6VALUE

BOOLEAN

1=1
0=0

Binary output 6 value

BO6FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 6 force

BO6

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 6 status

BO7VALUE

BOOLEAN

1=1
0=0

Binary output 7 value

BO7FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 7 force

BO7

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 7 status

BO8VALUE

BOOLEAN

1=1
0=0

Binary output 8 value

BO8FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 8 force

BO8

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 8 status

BO9VALUE

BOOLEAN

1=1
0=0

Binary output 9 value

BO9FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 9 force

BO9

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 9 status

BO10VALUE

BOOLEAN

1=1
0=0

Binary output 10 value

BO10FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 10 force

BO10

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 10 status

BO11VALUE

BOOLEAN

1=1
0=0

Binary output 11 value

Table continues on next page


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1309

Section 21
IED hardware

1MRK 502 066-UUS A

Name

21.2.9.6

Type

Values (Range)

Unit

Description

BO11FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 11 force

BO11

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 11 status

BO12VALUE

BOOLEAN

1=1
0=0

Binary output 12 value

BO12FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 12 force

BO12

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 12 status

Technical data
Table 922:

SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs

Function of quantity

Static binary output trip

Rated voltage

48 - 60 VDC

110 - 250 VDC

Number of outputs

Impedance open state

~300 k

~810 k

Test voltage across open contact, 1


min

No galvanic separation

No galvanic separation

Continuous

5A

5A

1.0s

10A

10A

0.2s

30A

30A

1.0s

10A

10A

Breaking capacity for DC with L/R


40ms

48V / 1A

110V / 0.4A

60V / 0.75A

125V / 0.35A

Current carrying capacity:

Making capacity at capacitive load


with the maximum capacitance of 0.2
F :

220V / 0.2A
250V / 0.15A
Operating time

1310

<1ms

<1ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Table 923:

SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical
relay outputs

Function of quantity

Trip and signal relays

Max system voltage

250V AC/DC

Number of outputs

Test voltage across open contact, 1 min

1000V rms

Current carrying capacity:


Continuous

8A

1.0s

10A

Making capacity at capacitive load with the maximum


capacitance of 0.2 F:
0.2s

30A

1.0s

10A

Breaking capacity for DC with L/R 40ms

48V / 1A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A

Maximum 72 outputs may be activated simultaneously with influencing


factors within nominal range. After 6 ms an additional 24 outputs may be
activated. The activation time for the 96 outputs must not exceed 200 ms.
48 outputs can be activated during 1 s. Continued activation is possible
with respect to current consumption but after 5 minutes the temperature
rise will adversely affect the hardware life. Maximum two relays per
BOM/IOM/SOM should be activated continuously due to power
dissipation.

21.2.10

Binary input/output module (IOM)

21.2.10.1

Introduction
The binary input/output module is used when only a few input and output channels are
needed. The ten standard output channels are used for trip output or any signaling purpose.
The two high speed signal output channels are used for applications where short operating
time is essential. Eight optically isolated binary inputs cater for required binary input
information.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1311

Section 21
IED hardware
21.2.10.2

1MRK 502 066-UUS A

Design
The binary input/output module is available in two basic versions, one with unprotected
contacts and one with MOV (Metal Oxide Varistor) protected contacts.
Inputs are designed to allow oxide burn-off from connected contacts, and increase the
disturbance immunity during normal protection trip times. This is achieved with a high
peak inrush current while having a low steady-state current, see figure 583. Inputs are
debounced by software.
Well defined input high and input low voltages ensures normal operation at battery supply
ground faults, see figure 582.
The voltage level of the inputs is selected when ordering.
I/O events are time stamped locally on each module for minimum time deviance and
stored by the event recorder if present.
The binary I/O module, IOM, has eight optically isolated inputs and ten output relays. One
of the outputs has a change-over contact. The nine remaining output contacts are
connected in two groups. One group has five contacts with a common and the other group
has four contacts with a common, to be used as single-output channels, see figure 590.
The binary I/O module also has two high speed output channels where a reed relay is
connected in parallel to the standard output relay.
For configuration of the input and output signals, refer to sections "Signal matrix for
binary inputs SMBI" and "Signal matrix for binary outputs SMBO".
The making capacity of the reed relays are limited.

1312

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

IEC1MRK002801-AA11-UTAN-RAM V2 EN

IEC1MRK002802-AA-13 V1 EN

Figure 590:

Binary in/out module (IOM), input contacts named XA corresponds to


rear position X31, X41, and so on, and output contacts named XB to rear
position X32, X42, and so on

The binary input/output module version with MOV protected contacts can for example be
used in applications where breaking high inductive load would cause excessive wear of
the contacts.
The test voltage across open contact is lower for this version of the binary
input/output module.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1313

Section 21
IED hardware

1MRK 502 066-UUS A

xx04000069.vsd
IEC04000069 V1 EN

Figure 591:

21.2.10.3

IOM with MOV protection, relay example

Signals
Table 924:
Name

IOMIN Output signals


Type

Description

STATUS

BOOLEAN

Binary input part of IOM module status

BI1

BOOLEAN

Binary input 1

BI2

BOOLEAN

Binary input 2

BI3

BOOLEAN

Binary input 3

BI4

BOOLEAN

Binary input 4

BI5

BOOLEAN

Binary input 5

BI6

BOOLEAN

Binary input 6

BI7

BOOLEAN

Binary input 7

BI8

BOOLEAN

Binary input 8

Table 925:
Name

IOMOUT Input signals


Type

Default

Description

BLKOUT

BOOLEAN

Block binary outputs

BO1

BOOLEAN

Binary output 1

BO2

BOOLEAN

Binary output 2

BO3

BOOLEAN

Binary output 3

BO4

BOOLEAN

Binary output 4

BO5

BOOLEAN

Binary output 5

BO6

BOOLEAN

Binary output 6

BO7

BOOLEAN

Binary output 7

BO8

BOOLEAN

Binary output 8

BO9

BOOLEAN

Binary output 9

Table continues on next page

1314

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Name

21.2.10.4
Table 926:
Name

Type

Default

Description

BO10

BOOLEAN

Binary output 10

BO11

BOOLEAN

Binary output 11

BO12

BOOLEAN

Binary output 12

Settings
IOMIN Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Enabled

Binary input/output module in operation (On) or


not (Off)

DebounceTime

0.001 - 0.020

0.001

0.001

Debounce time for binary inputs

OscBlock

1 - 40

Hz

40

Oscillation block limit

OscRelease

1 - 30

Hz

30

Oscillation release limit

21.2.10.5

Monitored data
Table 927:
Name
STATUS

Table 928:
Name

IOMIN Monitored data


Type
BOOLEAN

Values (Range)
0=Ok
1=Error

Unit
-

Description
Binary input part of IOM
module status

IOMOUT Monitored data


Type

Values (Range)

Unit

Description

BO1VALUE

BOOLEAN

1=1
0=0

Binary output 1 value

BO1FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 1 force

BO1

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 1 status

BO2VALUE

BOOLEAN

1=1
0=0

Binary output 2 value

BO2FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 2 force

BO2

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 2 status

BO3VALUE

BOOLEAN

1=1
0=0

Binary output 3 value

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1315

Section 21
IED hardware

1MRK 502 066-UUS A

Name

Type

Values (Range)

Unit

Description

BO3FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 3 force

BO3

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 3 status

BO4VALUE

BOOLEAN

1=1
0=0

Binary output 4 value

BO4FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 4 force

BO4

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 4 status

BO5VALUE

BOOLEAN

1=1
0=0

Binary output 5 value

BO5FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 5 force

BO5

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 5 status

BO6VALUE

BOOLEAN

1=1
0=0

Binary output 6 value

BO6FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 6 force

BO6

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 6 status

BO7VALUE

BOOLEAN

1=1
0=0

Binary output 7 value

BO7FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 7 force

BO7

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 7 status

BO8VALUE

BOOLEAN

1=1
0=0

Binary output 8 value

BO8FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 8 force

BO8

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 8 status

BO9VALUE

BOOLEAN

1=1
0=0

Binary output 9 value

BO9FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 9 force

BO9

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 9 status

Table continues on next page


1316

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Name

21.2.10.6

Type

Values (Range)

Unit

Description

BO10VALUE

BOOLEAN

1=1
0=0

Binary output 10 value

BO10FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 10 force

BO10

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 10 status

BO11VALUE

BOOLEAN

1=1
0=0

Binary output 11 value

BO11FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 11 force

BO11

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 11 status

BO12VALUE

BOOLEAN

1=1
0=0

Binary output 12 value

BO12FORCE

BOOLEAN

0=Normal
1=Forced

Binary output 12 force

BO12

BOOLEAN

0=Normal
1=Forced
2=Blocked

Binary output 12 status

Technical data
Table 929:

IOM - Binary input/output module

Quantity

Rated value

Nominal range

Binary inputs

DC voltage, RL

24/30 V
48/60 V
125 V
220/250 V

RL 20%
RL 20%
RL 20%
RL 20%

Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA

max. 0.05 W/input


max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input

Counter input frequency

10 pulses/s max

Oscillating signal discriminator

Blocking settable 1-40 Hz


Release settable 1-30 Hz

Debounce filter

Settable 1-20 ms

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1317

Section 21
IED hardware

1MRK 502 066-UUS A

Maximum 176 binary input channels may be activated simultaneously


with influencing factors within nominal range.

Table 930:

IOM - Binary input/output module contact data (reference standard: IEC 61810-2)

Function or quantity

Trip and signal relays

Fast signal relays (parallel reed


relay)

Binary outputs

10

Max system voltage

250 V AC, DC

250 V DC

Test voltage across open contact, 1 min

1000 V rms

800 V DC

Current carrying capacity


Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous

8A
10 A
12 A

8A
10 A
12 A

30 A
10 A

0.4 A
0.4 A

0.2 s
1.0 s

30 A
10 A

220250 V/0.4 A
110125 V/0.4 A
4860 V/0.2 A
2430 V/0.1 A

Breaking capacity for AC, cos > 0.4

250 V/8.0 A

250 V/8.0 A

Breaking capacity for DC with L/R < 40


ms

48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

Maximum capacitive load

10 nF

Making capacity at inductive load with


L/R>10 ms
0.2 s
1.0 s
Making capacity at resistive load

Maximum 72 outputs may be activated simultaneously with influencing


factors within nominal range. After 6 ms an additional 24 outputs may be
activated. The activation time for the 96 outputs must not exceed 200 ms.
48 outputs can be activated during 1 s. Continued activation is possible
with respect to current consumption but after 5 minutes the temperature
rise will adversely affect the hardware life. Maximum two relays per
BOM/IOM/SOM should be activated continuously due to power
dissipation.

1318

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Table 931:

IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC
61810-2)

Function or quantity

Trip and Signal relays

Fast signal relays (parallel reed


relay)

Binary outputs

IOM: 10

IOM: 2

Max system voltage

250 V AC, DC

250 V DC

Test voltage across open contact,


1 min

250 V rms

250 V rms

8A
10 A
12 A

8A
10 A
12 A

30 A
10 A

0.4 A
0.4 A

0.2 s
1.0 s

30 A
10 A

220250 V/0.4 A
110125 V/0.4 A
4860 V/0.2 A
2430 V/0.1 A

Breaking capacity for AC, cos


j>0.4

250 V/8.0 A

250 V/8.0 A

Breaking capacity for DC with L/R


< 40 ms

48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A

48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A

Maximum capacitive load

10 nF

Current carrying capacity


Per relay, continuous
Per relay, 1 s
Per process connector pin,
continuous
Making capacity at inductive
loadwith L/R>10 ms
0.2 s
1.0 s
Making capacity at resistive load

Maximum 72 outputs may be activated simultaneously with influencing


factors within nominal range. After 6 ms an additional 24 outputs may be
activated. The activation time for the 96 outputs must not exceed 200 ms.
48 outputs can be activated during 1 s. Continued activation is possible
with respect to current consumption but after 5 minutes the temperature
rise will adversely affect the hardware life. Maximum two relays per
BOM/IOM/SOM should be activated continuously due to power
dissipation.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1319

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.11

mA input module (MIM)

21.2.11.1

Introduction
The milli-ampere input module is used to interface transducer signals in the 20 to +20
mA range from for example OLTC position, temperature or pressure transducers. The
module has six independent, galvanically separated channels.

21.2.11.2

Design
The Milliampere Input Module has six independent analog channels with separated
protection, filtering, reference, A/D-conversion and optical isolation for each input
making them galvanically isolated from each other and from the rest of the module.
For configuration of the input signals, refer to section "Signal matrix for mA inputs
SMMI".
The analog inputs measure DC current in the range of +/- 20 mA. The A/D converter has
a digital filter with selectable filter frequency. All inputs are calibrated separately The
filter parameters and the calibration factors are stored in a non-volatile memory on the
module.
The calibration circuitry monitors the module temperature and starts an automatical
calibration procedure if the temperature drift is outside the allowed range.

1320

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

IEC99000504 V2 EN

Figure 592:

MIM connection diagram

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1321

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.11.3

Signals
Table 932:

MIM Output signals

Name

21.2.11.4
Table 933:
Name

Type

Description

STATUS

BOOLEAN

Milliampere input module status

CH1

REAL

Analog input 1

CH2

REAL

Analog input 2

CH3

REAL

Analog input 3

CH4

REAL

Analog input 4

CH5

REAL

Analog input 5

CH6

REAL

Analog input 6

Settings
MIM Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Disabled
Enabled

Enabled

Operation Disabled/Enabled

MaxReportT

0 - 3600

Maximum time between reports

EnDeadBandCh1

Disabled
Enabled

Disabled

Enable amplitude deadband reporting for


channel 1

DeadBandCh1

0.00 - 20.00

mA

0.01

1.00

Deadband amplitude for channel 1

IMinCh1

-25.00 - 25.00

mA

0.01

4.00

Min current of transducer for Channel 1

IMaxCh1

-25.00 - 25.00

mA

0.01

20.00

Max current of transducer for Channel 1

ValueMinCh1

-10000000000.000
- 10000000000.000

0.001

4.000

Min primary value corr. to IMinCh1

ValueMaxCh1

-10000000000.000
- 10000000000.000

0.001

20.000

Max primary value corr. to IMaxCh1

EnDeadBandCh2

Disabled
Enabled

Disabled

Enable amplitude deadband reporting for


channel 2

DeadBandCh2

0.00 - 20.00

mA

0.01

1.00

Deadband amplitude for channel 2

IMinCh2

-25.00 - 25.00

mA

0.01

4.00

Min current of transducer for Channel 2

IMaxCh2

-25.00 - 25.00

mA

0.01

20.00

Max current of transducer for Channel 2

ValueMinCh2

-10000000000.000
- 10000000000.000

0.001

4.000

Min primary value corr. to IMinCh2

ValueMaxCh2

-10000000000.000
- 10000000000.000

0.001

20.000

Max primary value corr. to IMaxCh2

EnDeadBandCh3

Disabled
Enabled

Disabled

Enable amplitude deadband reporting for


channel 3

DeadBandCh3

0.00 - 20.00

mA

0.01

1.00

Deadband amplitude for channel 3

Table continues on next page

1322

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Name

Values (Range)

Unit

Step

Default

IMinCh3

-25.00 - 25.00

mA

0.01

4.00

Min current of transducer for Channel 3

IMaxCh3

-25.00 - 25.00

mA

0.01

20.00

Max current of transducer for Channel 3

ValueMinCh3

-10000000000.000
- 10000000000.000

0.001

4.000

Min primary value corr. to IMinCh3

ValueMaxCh3

-10000000000.000
- 10000000000.000

0.001

20.000

Max primary value corr. to IMaxCh3

EnDeadBandCh4

Disabled
Enabled

Disabled

Enable amplitude deadband reporting for


channel 4

DeadBandCh4

0.00 - 20.00

mA

0.01

1.00

Deadband amplitude for channel 4

IMinCh4

-25.00 - 25.00

mA

0.01

4.00

Min current of transducer for Channel 4

IMaxCh4

-25.00 - 25.00

mA

0.01

20.00

Max current of transducer for Channel 4

ValueMinCh4

-10000000000.000
- 10000000000.000

0.001

4.000

Min primary value corr. to IMinCh4

ValueMaxCh4

-10000000000.000
- 10000000000.000

0.001

20.000

Max primary value corr. to IMaxCh4

EnDeadBandCh5

Disabled
Enabled

Disabled

Enable amplitude deadband reporting for


channel 5

DeadBandCh5

0.00 - 20.00

mA

0.01

1.00

Deadband amplitude for channel 5

IMinCh5

-25.00 - 25.00

mA

0.01

4.00

Min current of transducer for Channel 5

IMaxCh5

-25.00 - 25.00

mA

0.01

20.00

Max current of transducer for Channel 5

ValueMinCh5

-10000000000.000
- 10000000000.000

0.001

4.000

Min primary value corr. to IMinCh5

ValueMaxCh5

-10000000000.000
- 10000000000.000

0.001

20.000

Max primary value corr. to IMaxCh5

EnDeadBandCh6

Disabled
Enabled

Disabled

Enable amplitude deadband reporting for


channel 6

DeadBandCh6

0.00 - 20.00

mA

0.01

1.00

Deadband amplitude for channel 6

IMinCh6

-25.00 - 25.00

mA

0.01

4.00

Min current of transducer for Channel 6

IMaxCh6

-25.00 - 25.00

mA

0.01

20.00

Max current of transducer for Channel 6

ValueMinCh6

-10000000000.000
- 10000000000.000

0.001

4.000

Min primary value corr. to IMinCh6

ValueMaxCh6

-10000000000.000
- 10000000000.000

0.001

20.000

Max primary value corr. to IMaxCh6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Description

1323

Section 21
IED hardware
21.2.11.5

1MRK 502 066-UUS A

Monitored data
Table 934:

MIM Monitored data

Name

21.2.11.6

Type

Values (Range)

Unit

Description

STATUS

BOOLEAN

0=Ok
1=Error

Milliampere input module


status

CH1

REAL

Analog input 1

CH2

REAL

Analog input 2

CH3

REAL

Analog input 3

CH4

REAL

Analog input 4

CH5

REAL

Analog input 5

CH6

REAL

Analog input 6

CH1

REAL

Service value analog input 1

CH2

REAL

Service value analog input 2

CH3

REAL

Service value analog input 3

CH4

REAL

Service value analog input 4

CH5

REAL

Service value analog input 5

CH6

REAL

Service value analog input 6

Technical data
Table 935:

MIM - mA input module

Quantity:

Rated value:

Nominal range:

Input resistance

Rin = 194 Ohm

Input range

5, 10, 20mA
0-5, 0-10, 0-20, 4-20mA

Power consumption
each mA-board
each mA input

2W
0.1 W

21.2.12

Serial and LON communication module (SLM)

21.2.12.1

Introduction
The serial and LON communication module (SLM) is used for SPA, IEC 60870-5-103,
DNP3 and LON communication. The module has two optical communication ports for
plastic/plastic, plastic/glass or glass/glass. One port is used for serial communication
(SPA, IEC 60870-5-103 and DNP3 port) and one port is dedicated for LON
communication.

1324

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.12.2

Design
The SLM is a PMC card and it is factory mounted as a mezzanine card on the NUM
module. Three variants of the SLM are available with different combinations of optical
fiber connectors, see figure 593. The plastic fiber connectors are of snap-in type and the
glass fiber connectors are of ST type.

I
EC0500760=1=en=Or
i
gi
nal
.
psd
IEC05000760 V2 EN

Figure 593:

The SLM variants, component side view

Receiver, LON

Transmitter, LON

Receiver, SPA/IEC 60870-5-103/DNP3

Transmitter, SPA/IEC 60870-5-103/DNP3

Snap in connector for plastic fiber

ST connector for glass fiber

Observe that when the SLM connectors are viewed from the rear side of
the IED, contact 4 above is in the uppermost position and contact 1 in the
lowest position.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1325

Section 21
IED hardware
21.2.12.3

1MRK 502 066-UUS A

Technical data
Table 936:

SLM LON port

Quantity

Range or value

Optical connector

Glass fiber: type ST


Plastic fiber: type HFBR snap-in

Fiber, optical budget

Glass fiber: 11 dB (1000m/3000 ft typically *)


Plastic fiber: 7 dB (10m/35ft typically *)

Fiber diameter

Glass fiber: 62.5/125 mm


Plastic fiber: 1 mm

*) depending on optical budget calculation

Table 937:

SLM SPA/IEC 60870-5-103/DNP3 port

Quantity

Range or value

Optical connector

Glass fiber: type ST


Plastic fiber: type HFBR snap-in

Fiber, optical budget

Glass fiber: 11 dB (1000m/3000ft m typically *)


Plastic fiber: 7 dB (25m/80ft m typically *)

Fiber diameter

Glass fiber: 62.5/125 mm


Plastic fiber: 1 mm

*) depending on optical budget calculation

21.2.13

Galvanic RS485 communication module

21.2.13.1

Introduction
The Galvanic RS485 communication module (RS485) is used for DNP3.0 and IEC
60870-5-103 communication. The module has one RS485 communication port. The
RS485 is a balanced serial communication that can be used either in 2-wire or 4-wire
connections. A 2-wire connection uses the same signal for RX and TX and is a multidrop
communication with no dedicated Master or slave. This variant requires however a control
of the output. The 4-wire connection has separated signals for RX and TX multidrop
communication with a dedicated Master and the rest are slaves. No special control signal
is needed in this case.

21.2.13.2

Design
The RS485 is a PMC card and it is factory mounted as a mezzanine card on the NUM
module.

1326

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

RS485 connector pinouts


The arrangement for the pins in the RS485 connector (figure 594) are presented in table
938:
Table 938:

The arrangement for the pins

Pin

Name 2-wire

Name 4-wire

Description

RS485+

TX+

Receive/transmit high or transmit high

RS485

TX

Receive/transmit

Term

T-Term

Termination resistor for transmitter (and receiver in 2


wir case) (connect to TX+)

N.A.

R-Term

Termination resistor for receiver (connect to RX+)

N.A.

RX

Receive low

N.A.

RX+

Receive high

Angle
bracket

Screw
terminal
X3

Screw
terminal
X1

1
2
1
2
3
4
5
6

RS485
PWB

Backplane

IEC06000517 V1 EN

Figure 594:

RS485 connector

2-wire: Connect pin 1 to pin 6 and pin 2 to pin 5

Termination (2-wire): Connect pin 1 to pin 3

Termination (4-wire): Connect pin 1 to pin 3 and pin 4 to pin 6

Soft ground connector pinouts


A second 2-pole screw connector is used for the connection of IO-ground. It can be used
in two combinations like:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1327

Section 21
IED hardware

21.2.13.3

1MRK 502 066-UUS A

Unconnected: No ground of the IO-part .

Soft grounded: The IO is connected to the GND with an RC net parallel with a MOV

Technical data
Table 939:

Galvanic RS485 communication module

Quantity

Range or value

Communication speed

240019200 bauds

External connectors

RS-485 6-pole connector


Soft ground 2-pole connector

21.2.14

Optical ethernet module (OEM)

21.2.14.1

Introduction
The optical fast-ethernet module is used for fast and interference-free communication of
synchrophasor data over IEEE C37.118 and/or IEEE 1344 protocols. It is also used to
connect an IED to the communication buses (like the station bus) that use the IEC
61850-8-1 protocol (port A, B). The module has one or two optical ports with ST
connectors.

21.2.14.2

Functionality
The Optical Ethernet module (OEM) is used when communication systems according to
IEC6185081 have been implemented.

21.2.14.3

Design
The Optical Ethernet module (OEM) is a PMC card and mounted as a mezzanine card on
the ADM. The OEM is a 100BASE-FXmodule and available as a single channel or double
channel unit.

1328

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

IEC05000472=1=en=Original.vsd
IEC05000472 V3 EN

Figure 595:

21.2.14.4

OEM layout, standard PMC format 2 channels

1: Transmitter
2: Receiver

Technical data
Table 940:

OEM - Optical ethernet module

Quantity

Rated value

Number of channels

1 or 2
1 or 2 (port A, B for IEC 61850-8-1 / IEEE C37.118)

Standard

IEEE 802.3u 100BASE-FX

Type of fiber

62.5/125 mm multimode fibre

Wave length

1300 nm

Optical connector

Type ST

Communication speed

Fast Ethernet 100 Mbit/s

21.2.15

Line data communication module (LDCM)

21.2.15.1

Introduction
The line data communication module (LDCM) is used for communication between the
IEDs situated at distances <68 miles or from the IED to optical to electrical converter with
G.703 interface located on a distances <1.9 miles away. The LDCM module sends and

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1329

Section 21
IED hardware

1MRK 502 066-UUS A

rereceives data, to and from another LDCM module. The IEEE/ANSI standard format is
used.
The line data communication module is used for binary signal transfer. The module has
one optical port with ST connectors see figure 596.

Line data communication module LDCM


Each module has one optical port, one for each remote end to which the IED
communicates.
Alternative cards for Long range (1550 nm single mode), Medium range (1310 nm single
mode) and Short range (850 nm multi mode) are available.
Class 1 laser product. Take adequate measures to protect the eyes. Never
look into the laser beam.

21.2.15.2

Design
The LDCM is a PCMIP type II single width format module. The LDCM can be mounted
on:

the ADM
the NUM

ST

IO-connector

ST

IEC07000087=1=en=Original.vsd
IEC07000087 V2 EN

Figure 596:

1330

The SR-LDCM layout. PCMIP type II single width format with two PCI
connectors and one I/O ST type connector

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

IEC06000393=1=en=Original.vsd
IEC06000393 V2 EN

Figure 597:

21.2.15.3

The MR-LDCM and LR-LDCM layout. PCMIP type II single width format
with two PCI connectors and one I/O FC/PC type connector

Technical data
Table 941:

Line data communication module

Characteristic
Type of LDCM

Range or value
Short range (SR)

Medium range (MR)

Long range (LR)

Graded-index
multimode
62.5/125 m

Singlemode 9/125
m

Singlemode 9/125 m

820 nm
865 nm
792 nm

1310 nm
1330 nm
1290 nm

1550 nm
1580 nm
1520 nm

13 dB (typical
distance about 2
mile *)
9 dB (typical
distance about 1
mile *)

22 dB (typical
distance 50 mile *)

26 dB (typical distance 68 mile *)

Optical connector

Type ST

Type FC/PC

Type FC/PC

Protocol

C37.94

C37.94
implementation **)

C37.94 implementation **)

Data transmission

Synchronous

Synchronous

Synchronous

Type of fiber

Peak Emission Wave


length
Nominal
Maximum
Minimum
Optical budget
Graded-index multimode
62.5/125 mm,
Graded-index multimode
50/125 mm

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1331

Section 21
IED hardware

1MRK 502 066-UUS A

Characteristic
Type of LDCM

Range or value
Short range (SR)

Medium range (MR)

Long range (LR)

Transmission rate / Data


rate

2 Mb/s / 64 kbit/s

2 Mb/s / 64 kbit/s

2 Mb/s / 64 kbit/s

Clock source

Internal or derived
from received
signal

Internal or derived
from received signal

Internal or derived from received


signal

*) depending on optical budget calculation


**) C37.94 originally defined just for multimode; using same header, configuration and data format as C37.94

21.2.16

Galvanic X.21 line data communication (X.21-LDCM)

21.2.16.1

Introduction
The galvanic X.21 line data communication module is used for connection to
telecommunication equipment, for example leased telephone lines. The module supports
64 kbit/s data communication between IEDs.
Examples of applications:

21.2.16.2

Line differential protection


Binary signal transfer

Design
The galvanic X.21 line data communication module uses a ABB specific PC*MIP Type
II format.

1332

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

en07000196.vsd
IEC07000196 V1 EN

Figure 598:

Overview of the X.21 LDCM module

1
1

15

en07000239.wmf

IEC07000239 V1 EN

Figure 599:

1.
2.
3.
4.

The X.21 LDCM module external connectors

Ground selection connector for IO, screw terminals, 2-pole


Ground pin
Soft ground pin, see figure 600
X.21 Micro D-sub 15 pole male connector according to the V11 (X:27) balanced
version

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1333

Section 21
IED hardware

1MRK 502 066-UUS A

I/O

100kW

100nF

Soft ground
en07000242.vsd
IEC07000242 V1 EN

Figure 600:

Schematic view of soft ground

Grounding
At special problems with ground loops, the soft ground connection for the IIO-ground can
be tested.
Three different kinds of grounding principles can be set (used for fault tracing):
1.
2.
3.

Direct ground - The normal grounding is direct ground, connect terminal 2 directly to
the chassis.
No ground - Leave the connector without any connection.
Soft ground - Connect soft ground pin (3), see figure 599

X.21 connector
Table 942:

Pinout for the X.21 communication connector

Pin number

Signal

Shield (ground)

TXD A

Control A

RXD A

Signal timing A

Ground

TXD B

10

Control B

Table continues on next page

1334

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.16.3

11

RXD B

13

Signal timing B

5,7,12,14,15

Not used

Functionality
The data format is HDLC. The speed for the transmission of the messages used is 64 kbit/
s.
A maximum of 100 meter of cable is allowed to ensure the quality of the data (deviation
from X.21 standard cable length).
Synchronization
The X.21 LDCM works like a DTE (Data Terminal Equipment) and is normally expecting
synchronization from the DCE (Data Circuit Equipment). The transmission is normally
synchronized to the Signal Element Timing signal when a device is a DTE. When the
signal is high it will read the data at the receiver and when the signal is low it will write data
to the transmitter. This behaviour can be inverted in the control register.
Normally an external multiplexer is used and it should act like the master.
When two X.21 LDCM is directly communicating with each other one must be set as a
master generating the synchronization for the other (the slave). The DTE Signal Element
Timing is created from the internal 64 kHz clock.
The Byte Timing signal is not used in ABB devices.

21.2.16.4

Technical data
Table 943:

Galvanic X.21 line data communication module (X.21-LDCM)

Quantity

Range or value

Connector, X.21

Micro D-sub, 15-pole male, 1.27 mm (0.050") pitch

Connector, ground selection

2 pole screw terminal

Standard

CCITT X21

Communication speed

64 kbit/s

Insulation

1 kV

Maximum cable length

100 m

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1335

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.17

GPS time synchronization module (GTM)

21.2.17.1

Introduction
This module includes a GPS receiver used for time synchronization. The GPS has one
SMA contact for connection to an antenna. It also includes an optical PPS ST-connector
output.

21.2.17.2

Design
The GTM is a PCMIP-format card and is placed only on one of the ADM slots. The
antenna input connector is shielded and directly attached to a grounded plate to eliminate
the risk of electromagnetic interference.
All communication between the GCM and the NUM is via the PCI-bus. PPS time data is
sent from the GCM to the rest of the time system to provide 1s accuracy at sampling
level. An optical transmitter for PPS output is available for time synchronization of
another relay with an optical PPS input. The PPS output connector is of ST-type for
multimode fibre and could be used up to 1 km.

21.2.17.3

Monitored data
Table 944:

SYNCHGPS Monitored data

Name

Type

NoOfSatellites

21.2.17.4

INTEGER

Values (Range)
-

Description
Number of GPS signals from
satellites

Technical data
Table 945:

GPS time synchronization module (GTM)

Function

1336

Unit

Range or value

Accuracy

Receiver

1s relative UTC

Time to reliable time reference with antenna in new


position or after power loss longer than 1 month

<30 minutes

Time to reliable time reference after a power loss longer


than 48 hours

<15 minutes

Time to reliable time reference after a power loss shorter


than 48 hours

<5 minutes

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.2.18

GPS antenna

21.2.18.1

Introduction
In order to receive GPS signals from the satellites orbiting the earth a GPS antenna with
applicable cable must be used.

21.2.18.2

Design
The antenna with a console for mounting on a horizontal or vertical flat surface or on an
antenna mast. See figure 601

2
3

xx04000155.vsd
IEC04000155 V2 EN

Figure 601:

Antenna with console

where:
1

GPS antenna

TNC connector

Console, (2'6.7"x4'11')

Mounting holes about 1/5"

Tab for securing of antenna cable

Vertical mounting position

Horizontal mounting position

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1337

Section 21
IED hardware

1MRK 502 066-UUS A

Antenna cable
Use a 50 ohm coaxial cable with a male TNC connector in the antenna end and a male
SMA connector in the receiver end to connect the antenna to GTM. Choose cable type and
length so that the total attenuation is max. 26 dB at 1.6 GHz.
Make sure that the antenna cable is not charged when connected to the
antenna or to the receiver. Short-circuit the end of the antenna cable with
some metal device, when first connected to the antenna. When the antenna
is connected to the cable, connect the cable to the receiver. The IED must
be switched off when the antenna cable is connected.

21.2.18.3

Technical data
Table 946:

GPS Antenna and cable

Function

Value

Max antenna cable attenuation

26 db @ 1.6 GHz

Antenna cable impedance

50 ohm

Lightning protection

Must be provided externally

Antenna cable connector

SMA in receiver end


TNC in antenna end

Accuracy

+/-1s

21.2.19

IRIG-B time synchronization module IRIG-B

21.2.19.1

Introduction
The IRIG-B time synchronizing module is used for accurate time synchronizing of the
IED from a station clock.
The Pulse Per Second (PPS) input shall be used for synchronizing when IEC 61850-9-2LE
is used.
Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.

21.2.19.2

Design
The IRIG-B module has two inputs. One input is for the IRIG-B that can handle both a
pulse-width modulated signal (also called unmodulated) and an amplitude modulated
signal (also called sine wave modulated). The other is an optical input type ST for optical
pulse-width modulated signal (IRIG-B 00X).

1338

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

ST

A1

Y2

IEC06000304=1=en=Original.ai
IEC06000304 V2 EN

Figure 602:

21.2.19.3
Table 947:
Name

IRIG-B PC-MIP board with top left ST connector for optical IRIG-B 00X
820 nm multimode fibre optic signal input and lower left BNC connector
for IRIG-B signal input

Settings
IRIG-B Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

SynchType

BNC
Opto

Opto

Type of synchronization

TimeDomain

LocalTime
UTC

LocalTime

Time domain

Encoding

IRIG-B
1344
1344TZ

IRIG-B

Type of encoding

TimeZoneAs1344

MinusTZ
PlusTZ

PlusTZ

Time zone as in 1344 standard

21.2.19.4

Technical data
Table 948:

IRIG-B

Quantity

Rated value

Number of channels IRIG-B

Number of optical channels

Electrical connector:
Electrical connector IRIG-B

BNC

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1339

Section 21
IED hardware

1MRK 502 066-UUS A

Quantity

Rated value

Pulse-width modulated

5 Vpp

Amplitude modulated
low level
high level

1-3 Vpp
3 x low level, max 9 Vpp

Supported formats

IRIG-B 00x, IRIG-B 12x

Accuracy

+/-10s for IRIG-B 00x and +/-100s for IRIG-B 12x

Input impedance

100 k ohm

Optical connector:

1340

Optical connector IRIG-B

Type ST

Type of fibre

62.5/125 m multimode fibre

Supported formats

IRIG-B 00x

Accuracy

+/- 1s

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.3

Dimensions

21.3.1

Case without rear cover

A
D

C
IEC08000164-2-en.vsd

IEC08000164 V2 EN

Figure 603:

Case without rear cover

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1341

Section 21
IED hardware

1MRK 502 066-UUS A

K
F

G
H

J
xx08000166.vsd

IEC08000166 V1 EN

Figure 604:
Case size
(inches)

Case without rear cover with 19 rack mounting kit

6U, 1/2 x 19

10.47

8.81

7.92

9.96

8.10

7.50

8.02

18.31

7.39

19.00

6U, 3/4 x 19

10.47

13.23

7.92

9.96

12.52

7.50

12.44

18.31

7.39

19.00

6U, 1/1 x 19

10.47

17.65

7.92

9.96

16.94

7.50

16.86

18.31

7.39

19.00

The H and K dimensions are defined by the 19 rack mounting kit

1342

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.3.2

Case with rear cover

IEC08000163-2-en.vsd
IEC08000163 V2 EN

Figure 605:

Case with rear cover

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1343

Section 21
IED hardware

1MRK 502 066-UUS A

K
F

G
H

J
xx08000165.vsd

IEC08000165 V1 EN

Figure 606:

Case with rear cover and 19 rack mounting kit

IEC05000503-2-en.vsd
IEC05000503 V2 EN

Figure 607:

1344

Rear cover case with details

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Case size
(inches)

6U, 1/2 x 19

10.47

8.81

9.53

10.07

8.10

7.50

8.02

18.31

9.00

19.00

6U, 3/4 x 19

10.47

13.23

9.53

10.07

12.52

7.50

12.4

18.31

9.00

19.00

6U, 1/1 x 19

10.47

17.65

9.53

10.07

16.86

7.50

16.86

18.31

9.00

19.00

The H and K dimensions are defined by the 19 rack mounting kit.

21.3.3

Flush mounting dimensions

A
B

E
D
IEC08000162-2-en.vsd
IEC08000162 V2 EN

Figure 608:

Flush mounting

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1345

Section 21
IED hardware

1MRK 502 066-UUS A

Case size
Tolerance

Cut-out dimensions (inches)


A
+/0.04

B
+/0.04

6U, 1/2 x 19

8.27

10.01

0.160.39

0.49

6U, 3/4 x 19

12.69

10.01

0.160.39

0.49

6U, 1/1 x 19

17.11

10.01

0.160.39

0.49

E = 7.42 without rear protection cover, 9.03 with rear protection cover

21.3.4

Side-by-side flush mounting dimensions

IEC06000182-2-en.vsd
IEC06000182 V2 EN

Figure 609:

1346

A 1/2 x 19 size IED side-by-side with RHGS6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

C
xx05000505.vsd
IEC05000505 V1 EN

Figure 610:

Case size
(inches)
Tolerance

A
0.04

B
0.04

Panel-cut out dimensions for side-by-side flush mounting

C
0.04

D
0.04

E
0.04

F
0.04

G
0.04

6U, 1/2 x 19

8.42

10.21

9.46

7.50

1.35

0.52

0.25 diam

6U, 3/4 x 19

12.85

10.21

13.89

7.50

1.35

0.52

0.25 diam

6U, 1/1 x 19

17.27

10.21

18.31

7.50

1.35

0.52

0.25 diam

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1347

Section 21
IED hardware
21.3.5

1MRK 502 066-UUS A

Wall mounting dimensions

IEC04000471-2-en.vsd
IEC04000471 V2 EN

Figure 611:

Case size (inches)

Wall mounting

6U, 1/2 x 19

10.50

10.52

10.74

15.36

9.57

6U, 3/4 x 19

15.92

14.94

10.74

15.36

9.57

6U, 1/1 x 19

20.31

19.33

10.74

15.36

9.57

21.3.6

External resistor unit for high impedance differential protection


WARNING! - USE EXTREME CAUTION!Dangerously high
voltages might be present on this equipment, especially on the plate with
resistors. Do any maintenance ONLY if the primary object protected with
this equipment is de-energized. If required by national law/standard
enclose the plate with resistors with a protective cover or in a separate box!

1348

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

[6.97]

[4.02]

[1.48]

1MRK 502 066-UUS A

[18.31]

[0.33]

[0.79]

[7.68]

[18.98]

Dimension
mm [inches]

xx06000232.eps

IEC06000232 V2 EN

Dimension drawing of a one phase impedance resistor unit

[7.50]

[10.47]

[1.50]

Figure 612:

[0.33]

[18.31]

[0.79]

[7.68]

[18.98]

[inches]

en06000234.eps

IEC06000234 V2 EN

Figure 613:

Dimension drawing of a three phase high impedance resistor unit

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1349

Section 21
IED hardware
21.3.7

1MRK 502 066-UUS A

External current transformer unit

57 [2.24]

89 [3.5]

482.6 [19]

Dimension
mm [inches]
xx06000233.vsd

IEC06000233 V1 EN

Figure 614:

Dimension drawing of summation current transformers

21.4

Mounting alternatives

21.4.1

Flush mounting

21.4.1.1

Overview
The flush mounting kit can be used for case sizes:

1/2 x 19
3/4 x 19
1/1 x 19
1/4 x 19 (RHGS6 6U)

Only a single case can be mounted in each cut-out on the cubicle panel, for class IP54
protection.
Flush mounting cannot be used for side-by-side mounted IEDs when IP54
class must be fulfilled. Only IP20 class can be obtained when mounting
two cases side-by-side in one (1) cut-out.

To obtain IP54 class protection, an additional factory mounted sealing


must be ordered when ordering the IED.

1350

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.4.1.2

Mounting procedure for flush mounting


1

5
2

6
3

IEC08000161-2-en.vsd
IEC08000161 V2 EN

Figure 615:

Flush mounting details.

PosNo

Description

Quantity

Type

Sealing strip, used to obtain IP54


class. The sealing strip is factory
mounted between the case and
front plate.

Fastener

Groove

Screw, self tapping

2.9x9.5 mm

Joining point of sealing strip

Panel

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1351

Section 21
IED hardware

1MRK 502 066-UUS A

21.4.2

19 panel rack mounting

21.4.2.1

Overview
All IED sizes can be mounted in a standard 19 cubicle rack by using a suitably sized
mounting kit consisting of two mounting angles and their fastening screws.
The mounting angles are reversible which enables mounting of IED size 1/2 x 19 or 3/4
x 19 either to the left or the right side of the cubicle.
A separately ordered rack mounting kit for side-by-side mounted IEDs or
IEDs together with RHGS cases should be selected so that the total size
equals 19.

When mounting the mounting angles, use screws that follow the
recommended dimensions. Using screws with other dimensions may
damage the PCBs inside the IED.

1352

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.4.2.2

Mounting procedure for 19 panel rack mounting


2
1a

1b

IEC08000160-2-en.vsd
IEC08000160 V2 EN

Figure 616:

19 panel rack mounting details

PosNo

Description

Quantity

Type

1a, 1b

Mounting angles, can be mounted


either to the left or the right side of the
case

Screw

M4x6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1353

Section 21
IED hardware

1MRK 502 066-UUS A

21.4.3

Wall mounting

21.4.3.1

Overview
All case sizes, 1/2 x 19, 3/4 x 19,1/1 x 19, can be wall mounted. It is also possible to
mount the IED on a panel or in a cubicle.
When mounting the side plates, use screws that follow the recommended
dimensions. Using screws with other dimensions may damage the PCBs
inside the IED.

If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for any communication modules
with fiber connection.

1354

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.4.3.2

Mounting procedure for wall mounting

2
3

5
6
IEC130 00266-1-en.vsd

IEC13000266 V1 EN

Figure 617:

21.4.3.3

Wall mounting details.

PosNo

Description

Quantity

Type

Bushing

Screw

M4x10

Screw

M6x12 or
corresponding

Mounting bar

Screw

M5x8

Side plate

How to reach the rear side of the IED


The IED can be equipped with a rear protection cover recommended to be used with this
type of mounting. See figure 618.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1355

Section 21
IED hardware

1MRK 502 066-UUS A

To reach the rear side of the IED, a free space of 3.2 inches is required on the unhinged
side.
View from above
1

3.2"
(80 mm)

ANSI_en06000135.vsd
ANSI06000135 V1 EN

Figure 618:

How to reach the connectors on the rear side of the IED.

PosNo

Description

Type

Screw

M4x10

Screw

M5x8

Rear protection cover

(Ordered separately)

21.4.4

Side-by-side 19 rack mounting

21.4.4.1

Overview
IED case size 1/2 x 19 or 3/4 x 19 and RHGS cases can be mounted side-by-side up to
a maximum size of 19. For side-by-side rack mounting, the side-by-side mounting kit
together with the 19 rack panel mounting kit must be used. The mounting kit has to be
ordered separately.
When mounting the plates and the angles on the IED, use screws that
follow the recommended dimensions. Using screws with other
dimensions may damage the PCBs inside the IED.

1356

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

21.4.4.2

Mounting procedure for side-by-side rack mounting


2
1

IEC04000456-2-en.vsd
IEC04000456 V2 EN

Figure 619:

21.4.4.3

Side-by-side rack mounting details.

PosNo

Description

Quantity

Type

Mounting plate

2, 3

Screw

16

M4x6

Mounting angle

IED mounted with a RHGS6 case


A 1/2 x 19 or 3/4 x 19 size IED can be mounted with a RHGS case (6 or 12 depending
on IED size). The RHGS case can be used for mounting a test switch of type RTXP 24. It
also has enough space for a terminal base of RX 2 type for mounting of, for example, a DCswitch or two trip IEDs.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1357

Section 21
IED hardware

1MRK 502 066-UUS A

IEC06000180-2-en.vsd
IEC06000180 V2 EN

Figure 620:

IED (1/2 x 19) mounted with a RHGS6 case containing a test switch
module equipped with only a test switch and a RX2 terminal base

21.4.5

Side-by-side flush mounting

21.4.5.1

Overview
It is not recommended to flush mount side by side mounted cases if IP54 is required. If
your application demands side-by-side flush mounting, the side-by-side mounting details
kit and the 19 panel rack mounting kit must be used. The mounting kit has to be ordered
separately. The maximum size of the panel cut out is 19.
With side-by-side flush mounting installation, only IP class 20 is
obtained. To reach IP class 54, it is recommended to mount the IEDs
separately. For cut out dimensions of separately mounted IEDs, see
section "Flush mounting".

When mounting the plates and the angles on the IED, be sure to use screws
that follows the recommended dimensions. Using screws with other
dimensions than the original may damage the PCBs inside the IED.

1358

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Please contact factory for special add on plates for mounting FT switches
on the side (for 1/2 19" case) or bottom of the relay.

21.4.5.2

Mounting procedure for side-by-side flush mounting


1

3
4

IEC06000181-2-en.vsd
IEC06000181 V2 EN

Figure 621:

Side-by-side flush mounting details (RHGS6 side-by-side with 1/2 x 19


IED).

PosNo

Description

Quantity

Type

Mounting plate

2, 3

Screw

16

M4x6

Mounting angle

21.5

Technical data

21.5.1

Enclosure
Table 949:
Material

Case
Steel sheet

Front plate

Steel sheet profile with cut-out for HMI

Surface treatment

Aluzink preplated steel

Finish

Light grey (RAL 7035)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1359

Section 21
IED hardware

1MRK 502 066-UUS A

Table 950:

Water and dust protection level according to IEC 60529

Front

IP40 (IP54 with sealing strip)

Sides, top and bottom

IP20

Rear side

IP20 with screw compression type


IP10 with ring lug terminals

Table 951:

Weight

Case size

21.5.2

Weight

6U, 1/2 x 19

6U, 3/4 x 19

33 lb

6U, 1/1 x 19

40 lb

Electrical safety
Table 952:

21.5.3

Electrical safety according to IEC 60255-27

Equipment class

I (protective earthed)

Overvoltage category

III

Pollution degree

2 (normally only non-conductive pollution occurs except that occasionally a


temporary conductivity caused by condensation is to be expected)

Connection system
Table 953:

CT and VT circuit connectors

Connector type

Rated voltage and current


250 V AC, 20 A

4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)

Terminal blocks suitable for ring


lug terminals

250 V AC, 20 A

4 mm2 (AWG12)

Table 954:

Auxiliary power supply and binary I/O connectors

Connector type

1360

Maximum conductor area

Screw compression type

Rated voltage

Maximum conductor area

Screw compression type

250 V AC

2.5 mm2 (AWG14)


2 1 mm2 (2 x AWG18)

Terminal blocks suitable for ring


lug terminals

300 V AC

3 mm2 (AWG14)

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Because of limitations of space, when ring lug terminal is ordered for


Binary I/O connections, one blank slot is necessary between two adjacent
IO cards. Please refer to the ordering particulars for details.

21.5.4

Influencing factors
Table 955:

Temperature and humidity influence

Parameter

Reference value

Nominal range

Influence

Ambient temperature,
operate value

+20C

-10 C to +55C

0.02% / C

Relative humidity
Operative range

10%-90%
0%-95%

10%-90%

Storage temperature

-40 C to +70 C

Table 956:

Auxiliary DC supply voltage influence on functionality during operation

Dependence on

Reference value

Ripple, in DC auxiliary voltage


Operative range

max. 2%
Full wave rectified

Within nominal range Influence


15% of EL

0.01% / %

Auxiliary voltage dependence, operate


value

20% of EL

0.01% / %

Interrupted auxiliary DC voltage

24-60 V DC 20%
90-250 V DC 20%

Interruption
interval
050 ms

Table 957:

No restart

0 s

Correct behaviour
at power down

Restart time

<300 s

Frequency influence (reference standard: IEC 602551)

Dependence on

Within nominal range

Influence

Frequency dependence,
operate value

fn 2.5 Hz for 50 Hz
fn 3.0 Hz for 60 Hz

1.0% / Hz

Frequency dependence for


distance protection operate
value

fn 2.5 Hz for 50 Hz
fn 3.0 Hz for 60 Hz

2.0% / Hz

Harmonic frequency
dependence (20% content)

2nd, 3rd and 5th harmonic of fn

2.0%

Table continues on next page

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1361

Section 21
IED hardware

1MRK 502 066-UUS A

Dependence on

21.5.5

Within nominal range

Influence

Harmonic frequency
dependence for high
impedance differential
protection (10% content)

2nd, 3rd and 5th harmonic of fn

5.0%

Harmonic frequency
dependence for high
impedance differential
protection (10% content)

2nd, 3rd and 5th harmonic of fn

10.0%

Harmonic frequency
dependence for overcurrent
protection

2nd, 3rd and 5th harmonic of fr

3.0% / Hz

Type tests according to standard


Table 958:

Electromagnetic compatibility

Test

Type test values

Reference standards

1 MHz Oscillatory burst


disturbance

2.5 kV

IEC 60255-26

100 kHz slow damped oscillatory


wave immunity test

2.5 kV

IEC 61000-4-18, Class III

Ring wave immunity test, 100 kHz

2-4 kV

IEC 61000-4-12, Class IV

Surge withstand capability test

2.5 kV, oscillatory


4.0 kV, fast transient

IEEE/ANSI C37.90.1

Electrostatic discharge
Direct application
Indirect application

15 kV air discharge
8 kV contact discharge
8 kV contact discharge

IEC 60255-26

Electrostatic discharge
Direct application
Indirect application

15 kV air discharge
8 kV contact discharge
8 kV contact discharge

IEEE/ANSI C37.90.1

Fast transient disturbance

4 kV

IEC 60255-26, Zone A

Surge immunity test

2-4 kV, 1.2/50 ms


high energy

IEC 60255-26, Zone A

Power frequency immunity test

150-300 V

IEC 60255-26, Zone A

Conducted common mode


immunity test

15 Hz-150 kHz

IEC 61000-4-16, Class IV

Power frequency magnetic field


test

1000 A/m, 3 s
100 A/m, cont.

IEC 61000-4-8, Class V

Pulse magnetic field immunity test

1000 A/m

IEC 6100049, Class V

Damped oscillatory magnetic field


test

100 A/m

IEC 61000-4-10, Class V

Radiated electromagnetic field


disturbance

20 V/m, 80-1000 MHz

IEC 60255-26

IEC 61000-4-2, Class IV

1.4-2.7 GHz

Table continues on next page

1362

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 21
IED hardware

1MRK 502 066-UUS A

Test

Type test values

Reference standards

Radiated electromagnetic field


disturbance

20 V/m
80-1000 MHz

IEEE/ANSI C37.90.2

Conducted electromagnetic field


disturbance

10 V, 0.15-80 MHz

IEC 60255-26

Radiated emission

30-5000 MHz

IEC 60255-26

Radiated emission

30-5000 MHz

IEEE/ANSI C63.4, FCC

Conducted emission

0.15-30 MHz

IEC 60255-26

Table 959:

Insulation

Test

Type test values

Reference standard

Dielectric test

2.0 kV AC, 1 min.

Impulse voltage test

5 kV, 1.2/50 ms, 0.5 J

Insulation resistance

>100 MW at 500 VDC

Table 960:

IEC 60255-27
ANSI C37.90

Environmental tests

Test

Type test value

Reference standard

Cold operation test

Test Ad for 16 h at -25C

IEC 60068-2-1

Cold storage test

Test Ab for 16 h at -40C

IEC 60068-2-1

Dry heat operation test

Test Bd for 16 h at +70C

IEC 60068-2-2

Dry heat storage test

Test Bb for 16 h at +85C

IEC 60068-2-2

Change of temperature test

Test Nb for 5 cycles at -25C to


+70C

IEC 60068-2-14

Damp heat test, steady state

Test Ca for 10 days at +40C and


humidity 93%

IEC 60068-2-78

Damp heat test, cyclic

Test Db for 6 cycles at +25 to


+55C and humidity 93 to 95% (1
cycle = 24 hours)

IEC 60068-2-30

Table 961:

CE compliance

Test

According to

Immunity

EN 6025526

Emissivity

EN 6025526

Low voltage directive

EN 6025527

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1363

Section 21
IED hardware

1MRK 502 066-UUS A

Table 962:

Mechanical tests

Test

1364

Type test values

Reference standards

Vibration response test

Class II

IEC 60255-21-1

Vibration endurance test

Class I

IEC 60255-21-1

Shock response test

Class I

IEC 60255-21-2

Shock withstand test

Class I

IEC 60255-21-2

Bump test

Class I

IEC 60255-21-2

Seismic test

Class II

IEC 60255-21-3

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Section 22

Injection equipment hardware

This chapter describes the hardware equipment used for sensitive rotor earth fault
protection and 100% stator earth fault protection by injection. The descriptions includes
diagrams from different elevations indicating the location of connection terminals and
modules as well as dimensions and drilling plan.

22.1

Overview

22.1.1

Front view of injection unit, coupling capacitor and shunt resitor


unit

22.1.1.1

Injection unit REX060


The injection unit REX060 is used to inject voltage and current signals to the generator or
motor stator and rotor circuits. REX060 generates two square wave signals with different
frequencies for injection into the stator and rotor circuits respectively. The response from
the injected voltage and currents are then measured by the REX060 unit and amplified to
a level suitable for the analog voltage inputs of IED.
For local operation, the REX060 unit is provided with a control panel on the front.
Local operation shall only be performed according to the operation
regulations set up by the relevant operation authority of the plant.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1365

Section 22
Injection equipment hardware
22.1.1.2

1MRK 502 066-UUS A

REX060 Front panel controls

IEC11000053-1-en.vsd
IEC11000053 V1 EN

Figure 622:

1366

REX060 front panel

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Table 963:
Key

HMI keys on the front of the injection unit REX060


Function
The Injection switch enables injection at rotor and stator 2 s
after switching on. A LED indicates that the injection switch is
set to enable injection. The injection switch can be padlocked in
off position in order to cut-off both injection signals.

The Key-lock button enables/disables the keypad.


Hold the Key-lock button for a period of 1.2 s to 4 s to lock or
unlock the keys. A key-lock LED indicates when the keypad is
unlocked.

Moves the cursor in the direction of the arrows


When the cursor is in the value change state, pressing
the up button increases the value and pressing the down
button decreases the value.

Pressing the clear button cancels changes that have not been
stored.

Pressing the enter button stores the changed value. If the value
is outside range, the limit value is stored.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1367

Section 22
Injection equipment hardware
22.1.1.3

1MRK 502 066-UUS A

Coupling capacitor unit REX061

X1

X2

IEC11000019-2-en.vsd
IEC11000019 V1 EN

Figure 623:

Coupling capacitor unit REX061


217 [8,54]
155 [6,1]

84 [3,3]

84 [3,3]

223 [8,78]

5,5 [0,22]

38 [1,5]

199 [7,83]

235 [9,25]

255 [10]

2 [0,079]

IEC11000037-2-en.vsd
IEC11000037 V2 EN

Figure 624:

1368

Measure and drilling plan

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

REX061 shall be mounted close to the generator in order to limit the exposure of the field
circuit. Alternatively it can be located in the excitation cubicle.
The surface of REX061 unit may be temporarily very hot due to heat
dissipation, up to about 50 C above the ambient temperature. It must be
installed to get a open air convection and prevent contact with
combustible material to the surface.

22.1.1.4

Shunt resistor unit REX062

X1

IEC11000038-1-en.vsd
IEC11000038 V1 EN

Figure 625:

Shunt resistor unit REX062

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1369

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

217 [8,54]

155 [6,1]

84 [3,3]

84 [3,3]

223 [8,78]

5,5 [0,22]

38 [1,5]

199 [7,83]

235 [9,25]

255 [10]

2 [0,079]

IEC11000039-2-en.vsd

IEC11000039 V2 EN

Figure 626:

REX062 measures and drilling plan

REX062 shall be mounted close to the IED. It is recommended that REX060 and REX062
are mounted in the same cubicle as the IED.
The surface of REX061 unit may be temporarily very hot due to heat
dissipation, up to about 65 C above the ambient temperature. It must be
installed to get a open air convection and prevent contact with
combustible material to the surface.

1370

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

22.1.2

Injection unit REX060 from rear side

22.1.2.1

Injection unit REX060


IED and
Injection
connectors

Power
connector

Top view

Back view

X11

X61

Front view

X81

18

Stator

Power

X62

BackPlane
HMI and Logic

18

X82

Rotor

Power Supply

Stator Injection

Rotor Injection

Front-plate

Injection switch

IEC11000018-1-en.vsd
IEC11000018 V1 EN

Figure 627:

Rear and top view of injection unit REX060

22.2

Injection unit REX060

22.2.1

Introduction
The injection unit REX060 is used to inject voltage and current signals to the generator or
motor stator and rotor circuits. REX060 generates two square wave signals with different
frequencies for injection into the stator and rotor circuits respectively. The response from
the injected voltage and currents are then measured by the REX060 unit and amplified to
a level suitable for the analog voltage inputs of IED.

22.2.2

Design
REX060 consists of a standard enclosure (6U, 1/2 x 19"). In this enclosure, the modules
for stator (SIM) and/or rotor (RIM) earth fault protection are installed. The stator injection
transformer and the power supply are also installed inside the enclosure.
On the front of the enclosure there is a backlit LCD, control buttons and a key switch.
In figure 628 below the content of display is shown for a REX060 with one SIM and one
RIM module. Row 1 contains mains frequency information. Row 2-3 contains stator

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1371

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

information and row 4-5 rotor. Column 1 (empty) gives status, column 2 and 3 are
informative and column 4 contains variables, settable by the keypad.

Column
1
Row
1
2
3
4
5

System

[Hz] :

50

STATOR

[Hz] :

087

[V] :

120

[Hz] :

113

UmaxEF
ROTOR
Gain

4
IEC10000334-1-en.vsd

IEC10000334 V1 EN

Figure 628:

Normal display content

When the injection unit REX060 is energized, the ABB logotype is shown followed by
current REX060 revision status. When the start up sequence is completed, the main menu
(normal display content) is shown. The duration of the start up sequence is a few seconds.
LCD backlight is active during a period of 30 seconds after pressing any button. Backlight
activation by pressing a button will not cause any normal button action.
Column 1 is a status column (empty in the above picture), where the following symbols
are displayed when applicable:

1372

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Table 964:
Status symbol

IEC10000329 V1 EN

IEC10000330 V1 EN

IEC10000332 V1 EN

Status symbols and their description


Description of the status
Over voltage occurred, injection is blocked. This can occur on both
X61/62 and X81/82 (Stator & Rotor) simultaneously or on either of
them. The symbol is displayed in the status column (column 1) in row
2 for X61/62 and in row 4 for X81/82. The injection is blocked until a
manual reset of the blocking occurs.

Priority

Injection blocked by the injection switch. The symbol is displayed in


the status column (column 1) and is always shown in both row 2 and
4.

2
Over voltage
blocked status
overrides
displaying of
this status

Injection blocked by binary input. Blocked injection will be shown in the


status column (column 1) depending on binary in status. This can
occur on both X61/62 then shown in row 2 and X81/82 then shown in
row 4 (Stator & Rotor) simultaneously or on ether of them.

3
Injection switch
and over
voltage blocked
overrides
displaying of
this status

Analog output saturation. This status is set when the analog signal,
current and or voltage, to REG670 IED is too high and may thereby be
incorrect due to saturation in amplifier stage. Saturation status will be
shown in the status column (column 1) in row 3 or 5 depending on the
saturation occurrence

Not applicable

Overvoltage reset
Stator module (SIM) and rotor module (RIM) injection outputs are protected against
voltages exceeding maximum operating range (10% of rated VT/DT for the stator and
75 % of max voltage during gain dependent time for the rotor) by a relay blocking the
injection circuit. This blocking is controlled by measuring the sense voltage, and remains
blocked by stored status in non-volatile memory. Injection block is released by
performing the following sequence:
1.
2.
3.

Power off the REX060


Simultaneous press the C and key buttons
Power on the REX060 and wait until status indication Over-voltage is removed from
display

Stator and rotor overvoltage protection of injection circuit


Both rotor and stator have two levels of protection, injection circuit interruption controlled
by the voltage sense input and a fuse for over-current protection. The voltage controlled
interruption, overvoltage, will normally occur prior to interruption by fuse and the reset
sequence is described above. A blown fuse requires module disassembling to replace the
fuse (F 4 A 250 V for stator and F 160 mA 250 V for rotor). However, if this occurs it is
recommended to identify the reason for the over-current and take necessary actions to
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1373

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

reduce the current before restarting the unit. The problem must be outside the injection
unit since this unit cannot provide enough energy to blow the fuse.
Saturation
When the voltage or current amplifiers in an injection module saturates due to high voltage
level, it is indicated with a warning symbol in the status column in the REX060 display .
Besides this a binary out for the specific module is set active to indicate to the IED that the
signal may not be reliable due to saturation and could cause incorrect measurements.
Binary in
The injection can be blocked by application in the IED. For this purpose, two binary inputs
to the REX060 exist:

BLOCK on X61 terminal 1, 2 or 3: Prohibits injection on the injection unit inserted


in X62
BLOCK on X81 terminal 1, 2 or 3: Prohibits injection on the injection unit inserted
in X82

The used terminal is depending on actual binary voltage, pin 1 for 220 V, 2 for 110 V, 3
for 48 V and 4 for return (common).
Binary out
The following binary outputs exist on the REX060:

INJ_BLOCKED_NC on X61 terminal 5:


Indicates to the IED that the injection on X62 is blocked. The reason for blocking is
indicated in the REX060 LCD.
SAT_NO on X61 pin 6:
Indicates to the IED that there is a risk of saturated amplifier on voltage and/or current
output at X61, indication is also given in the REX060 LCD.
COMMON on X61 terminal 7:
Common return for X61 terminal 5 and 6
INJ_BLOCKED_NC on X81 pin 5:
Indicates to the IED that the injection on X82 is blocked. The reason for blocking is
indicated in the REX060 LCD.
SAT_NO on X81 pin 6:
Indicates to the IED that there is a risk of saturated amplifier on voltage and/or current
output at X81, indication is also given in the REX060 LCD.
COMMON on X81 terminal 7:
Common return for X81 terminal 5 and 6

Power status

1374

X11 terminal 3:
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Fail, power off NC


X11 terminal 1:
Ready, power off NO
X11 terminal 2:
Common

22.3

Coupling capacitor unit REX061

22.3.1

Introduction
REX061 isolates the injection circuit from the rotor exciter voltage.
The REX061 coupling capacitor unit grounding point and grounding brush of the rotor
shaft should be properly interconnected.

22.3.2

Design
Measure points are added to the capacitor box that enables the measuring of rotor voltages
without any connection to a hazardous voltage, by the use of protective impedance. This
enables the usage of standard oscilloscope or handheld DVM.
The measure ports cause an additional rotor impedance of 20 M per
terminal to ground. However, the rotor calibration procedure extracts this
impedance.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1375

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

REX061
Coupling Capacitor unit
Measuring point +
Ground (measuring)
Rotor+

Injection
Ground (injection)

RotorMeasuring pointPE

IEC11000040-3-en.vsd
IEC11000040 V1 EN

Figure 629:

REX062 principle design

22.4

Shunt resistor unit REX062

22.4.1

Introduction
REX062 is typically used when injection is done via a grounding transformer.

22.4.2

Design
REX062 for stator protection is used when either injection via a grounding transformer
(i.e. not via a VT) is used or when maximum voltage posed on injection equipment by the
generator is bigger than 120V.

1376

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

REX062
Shunt Resistor unit
Injection A

External A
Fuse

Injection B

External B
I sense A

PE
I sense B

IEC11000041-2-en.vsd
IEC11000041 V1 EN

Figure 630:

REX062 Principal design

REX062 input protection


REX062 limits overvoltage by a varistor at the injection output to stator. Normally ,
REX060 will interrupt the injection circuit in case of excessive over-current in the
injection chain. Fuse within REX062 is an additional protection in case of failure within
REX062 during over-voltage condition.
A blown REX062 fuse requires a module disassembling to replace the fuse (F 6.3 A 250
V). However, if this occurs it is recommended to identify the reason for the over-current
and do needed actions to reduce the current.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1377

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

REX060
Injection unit

REG670
X11:4
X11:5

Power Supply Module


REX061
Coupling Capacitor unit

Exciter
source

Ready; X11:1
Common; X11:2
Fail; X11:3

X1:1 ; Rotor +

Rotor

X82:1 ; InjA
X82:3 ; InjA

Injection; X1:9

X82:4 ; InjB
X82:5 ; InjB

Ground; X1:10
X1:7 ; Rotor-

X82:2 ; InjShB

PE

X81:16; IA sense
X81:14; IA sense
X81:15; IB sense
X81:12; VA sense
X81:13; VB sense

R
Distribution
Transformer

X1:2 ; Injection A

External A; X1:9

X1:4 ; Injection B

External B; X1:10
I sense A; X1:6
I sense B; X1:8

PE

X62:1 ; InjExtA
X62:3 ; InjA
X62:4 ; InjB
X62:5 ; InjB
X62:2 ; InjExtB

(BI)

BO
RL-

UA Out; X81:8
UB Out; X81:9

Stator Module( SIM)


Block 220V ; X61:1
Block 110V ; X61:2
Block48V ; X61:3
Block Common; X61:4

X61:14 ; IA sense

IA Out; X61:10
IB Out; X61:11

X61:12 ; VA sense

VA Out; X61:8

PE

BI
RL+

IB Out; X81:11

X61:15 ; IB sense

X61:13 ; VB sense

EL

IA Out; X81:10

Blocked; X81:5
Saturation; X81:6
Common; X81:7

REX062
Shunt Resistor unit

Stator

Rotor Module( RIM)


Block 220V ; X81:1
Block 110V ; X81:2
Block48V ; X81:3
Block Common; X81:4

BI
BI
RL+

BO
RL-

AI (V) , current measure

AI (V) , voltage measure

VB Out; X61:9
Blocked; X61:5
Saturation; X61:6
Common; X61:7

BI
BI
RL+

PE

ANSI11000017-1-en.vsd
ANSI11000017 V1 EN

Figure 631:

Example installation when REX062 unit is required

22.5

Technical data

22.5.1

Hardware
Table 965:

REX060 Technical data

Specifications

Values

Case size

6U, 1/2 19; 8.81 x 9.65 x 10.51 inches (W x D x H)

Weight

17.64 lbs

Burden, binary inputs

BI 220 V: burden 0.4 W


BI 110 V: burden 0.2 W
BI 48 V: burden 0.1 W

Burden, RIM injection

< 10 VA at 100 V external disturbance

Burden, SIM injection

< 10 VA at 12 V ground fault voltage


0 VA at > 10% of maximum ground fault voltage

Table continues on next page

1378

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Specifications

Values

Burden, SIM injection with REX062

< 1 VA at 24 V ground fault voltage

Burden, measuring transformer SIM

< 60 mVA at 24 V; 87 Hz

Burden, measuring transformer RIM

< 60 mVA at 50 V; 113 Hz

Installation category

III

Pollution degree

Table 966:

REX060 Power supply Technical data

Quantity

Rated value

Nominal range

Auxiliary dc voltage, EL (input)

EL = (24 60) V
EL = (90 250) V

EL 20%
EL 20%

Power consumption

30 W

Auxiliary DC power in-rush

< 5 A during 0.1 s

Table 967:

REX061 Technical data

Function

Range or values

Accuracy

For machines with:

rated field voltage up to

800 V DC

static exciter with rated


supply voltage up to

1600 V 50/60 Hz

Specifications

Values

Case size

8.58 x 5.91 x 9.57 inches (W x D x H)

Weight

10.58 lbs

Assembling

6 x 0.20 inch screws (3 at bottom and 3 at top)

Rated rotor injection voltage

250 V

Burden, static excitation system X1:1 to X1:7

< 0.5 VA at 100 V external disturbance

Burden, static excitation system X1:1 or X1:7 to 0


V

< 1.0 VA at 100 V external disturbance

Burden, brushless excitation system X1:1 and


X1:7 to 0 V

< 1.5 VA at 100 V external disturbance

Installation category

III

Pollution degree

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1379

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Table 968:

REX062 Technical data

Specifications

Values

Case size

8.58 x 5.91 x 9.57 inches (W x D x H)

Weight

9.92 lbs

Assembling

6 x 0.20 inch screws (3 at bottom and 3 at top)

Rated stator injection voltage

240 V

Rated stator voltage

240 V

Burden, injection X1:2 and X1:4

< 25 VA at 12 V ground fault voltage


< 100 VA at 24 V ground fault voltage

Installation category

III

Pollution degree

Table 969:

Degree of protection

Description

22.5.2

Values

REX060
Front
Panel mounted, front
Rear, sides, top, bottom and connection terminals

IP40
IP54
IP20

REX061 and REX062


Top
Front, rear, sides and bottom

IP41
IP20

Type tests according to standards


Table 970:

Electromagnetic compatibility tests

Test

Type test values

Reference standards

1 MHz Oscillatory burst


disturbance

2.5 kV

IEC 60255-26

100 kHz slow damped oscillatory


wave immunity test

2.5 kV

IEC 61000-4-18, Class III

Surge withstand capability test

2.5 kV, oscillatory


4.0 kV, fast transient

IEEE/ANSI C37.90.1

Electrostatic discharge
Direct application
Indirect application

15 kV air discharge
8 kV contact discharge
8 kV contact discharge

IEC 60255-26

Electrostatic discharge
Direct application
Indirect application

15 kV air discharge
8 kV contact discharge
8 kV contact discharge

IEEE/ANSI C37.90.3

Fast transient disturbance test

4 kV

IEC 60255-26, Zone A

Surge immunity test

1-2 kV, and 2-4 kV, 1.2/50 s


High energy

IEC 60255-26, Zone A

Power frequency immunity test

150-300 V

IEC 60255-26, Zone A

IEC 61000-4-2, Class IV

Table continues on next page


1380

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Test

Type test values

Reference standards

Power frequency magnetic field


test

1000 A/m, 3 s
100 A/m, cont.

IEC 61000-4-8

Radiated electromagnetic field


disturbance test

20 V/m, 80-1000 MHz


1.4-2.7 GHz

IEC 60255-26

Radiated electromagnetic field


disturbance test

20 V/m, 80-1000 MHz

IEEE/ANSI C37.90.2

Conducted electromagnetic field


disturbance test

10 V, 0.15-80 MHz

IEC 60255-26

Voltage dips and short


interruptions

Dips:
40% /200 ms
70% /500 ms
Interruptions:
0-50 ms: No restart
0 s: Correct behaviour at
power down

IEC 60255-26

Radiated emission

30-1000 MHz

IEC 60255-26

Conducted emission

0.15-30 MHz

IEC 60255-26

Table 971:

Insulation tests, REX060, REX062 and REG670

Test

Type test values

Reference standard

Dielectric test

2.0 kV AC, 1 min

IEC 60255-27

Impulse voltage test

5.0 kV, 1.2/50 s, 0.5 J

IEC 60255-27

Insulation resistance

>100 M at 500V DC

IEC 60255-27

Table 972:

Insulation tests, REX061

Test
Dielectric test

Impulse voltage test

Type test values

IEEE 421.3

2.8 kV DC, 1 min

IEC 60255-27

12.0 kV, 1.2/50 s, 0.5 J


(connections to rotor)

IEC 60664-1

5.0 kV, 1.2/50 s, 0.5 J


Insulation resistance

Reference standard

7.48 kV DC, 1min


(connections to rotor)

>100 M at 500V DC

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

IEC 60255-27
IEC 60255-27

1381

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Table 973:

Mechanical tests

Test

Reference standards

Vibration response test

IEC 60255-21-1

Vibration endurance test


REG670 and REX060
REX061 and REX062

IEC 60255-21-1

Shock response test


REG670 and REX060
REX061 and REX062

IEC 60255-21-2

Shock withstand test


REG670 and REX060
REX061 and REX062

IEC 60255-21-2

Bump test
REG670 and REX060
REX061 and REX062

IEC 60255-21-2

Seismic test
REG670 and REX060
REX061 and REX062

IEC 60255-21-3

Table 974:

Type test value

Cold test
operation
storage

16 h at -25C
16 h at -40C

Dry heat test


operation
storage

16 h at +70C
16 h at +85C

Damp heat test


steady state

240 h at +40C
humidity 93%
6 cycles at +25 to +55C
humidity 93-95%

cyclic

Class 1
Class 2
Class 1
Class 2
Class 1
Class 2
Class 1
Class 2
Class 2
Class 2 extended

Reference standard
IEC 60068-2-1

IEC 60068-2-2

IEC 60068-2-78
IEC 60068-2-30

Influencing factors
Table 975:

Auxiliary DC supply voltage influence

Test

1382

Class 2

Environmental tests

Test

22.5.3

Requirements

Type test values

Influence

Auxiliary voltage dependence,


operate value

20% of EL

0.01% /%

Ripple in DC auxiliary voltage,


operate value

15% of EL

0.01% /%

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 22
Injection equipment hardware

1MRK 502 066-UUS A

Table 976:

Temperature influence

Test

Type test values

Influence

Ambient temperature, operate


value

-25 C to +55C

0.02% /C

Storage temperature

-40 C to +85C

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1383

1384

Section 23
Labels

1MRK 502 066-UUS A

Section 23

Labels

23.1

Labels on IED
Front view of IED

1
2
3
4
5
6
6

7
xx06000574.ep
IEC06000574 V1 EN

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1385

Section 23
Labels

1MRK 502 066-UUS A

Product type, description and serial number

Order number, dc supply voltage and rated


frequency

Optional, customer specific information

Manufacturer

Transformer input module, rated currents and


voltages

Transformer designations

Ordering and serial number

IEC06000577-CUSTOMER-SPECIFIC V1 EN

IEC06000576-POS-NO V1 EN

1386

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 23
Labels

1MRK 502 066-UUS A

Rear view of IED

1
2
3

4
en06000573.ep
IEC06000573 V1 EN

Warning label

Caution label

Class 1 laser product label

IEC06000575 V1 EN

Warning label

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1387

Section 23
Labels

23.2

1MRK 502 066-UUS A

Labels on injection equipment


Front view of injection unit REX060

IEC11000226 V1 EN

1a

Product type, description and


serial number

1b

Order number and dc supply


voltage

1c

Stator and rotor input module


designations

1d

Manufacturer

1a
1b

1c

1d
IEC11000233-1-en.vsd
IEC11000233 V1 EN

1388

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 23
Labels

1MRK 502 066-UUS A

2 Ordering and serial number


2
IEC11000234-1-en.vsd
IEC11000234 V1 EN

Rear view of injection unit REX060

IEC11000227 V1 EN

Warning label

Caution label

ESD label

Warning label

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1389

Section 23
Labels

1MRK 502 066-UUS A

Front view of coupling capacitor unit REX061

IEC11000229 V1 EN

Warning label (hot surface)

Ordering number

Rear view of coupling capacitor unit REX061

IEC11000228 V1 EN

1390

Warning label

Caution label

ESD label

Warning label

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 23
Labels

1MRK 502 066-UUS A

Front view of shunt resistor unit REX062

IEC11000231 V1 EN

Warning label (hot surface)

Ordering number

Rear view of shunt resistor unit REX062

IEC11000230 V1 EN

Warning label

Caution label

ESD label

Warning label

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1391

1392

Section 24
Connection diagrams

1MRK 502 066-UUS A

Section 24

Connection diagrams

The connection diagrams are delivered on the IED Connectivity package DVD as part of
the product delivery.
The latest versions of the connection diagrams can be downloaded from
http://www.abb.com/substationautomation.
Connection diagrams for Customized products
Connection diagram, 670 series 2.1 1MRK002802-AF
Connection diagrams for Injection equipment
Connection diagram, Injection unit REX060 1MRK002501-BA
Connection diagram, Generator protection REG670 with injection unit REX060
1MRK002504-BA
Connection diagram, Injection unit REX060 and coupling capacitor unit REX061
1MRK002504-CA
Connection diagram, Injection unit REX060 and optional shunt resistor unit REX062
1MRK002504-DA
Connection diagram, Coupling capacitor unit REX061 1MRK002551-BA
Connection diagram, Shunt resistor unit REX062 1MRK002556-BA

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1393

1394

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Section 25

Inverse time characteristics

25.1

Application
In order to assure time selectivity between different overcurrent protections at different
points in the network different time delays for the different protections are normally used.
The simplest way to do this is to use definite time-lag. In more sophisticated applications
current dependent time characteristics are used. Both alternatives are shown in a simple
application with three overcurrent protections operating in series.

IPickup

IPickup

IPickup

xx05000129_ansi.vsd
ANSI05000129 V1 EN

Figure 632:

Three overcurrent protections operating in series


Stage 3

Time
Stage 2

Stage 2

Stage 1

Stage 1

Stage 1

Fault point
position

en05000130.vsd
IEC05000130 V1 EN

Figure 633:

Definite time overcurrent characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1395

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Time

Fault point
position
en05000131.vsd
IEC05000131 V1 EN

Figure 634:

Inverse time overcurrent characteristics with inst. function

The inverse time characteristic makes it possible to minimize the fault clearance time and
still assure the selectivity between protections.
To assure selectivity between protections there must be a time margin between the
operation time of the protections. This required time margin is dependent of following
factors, in a simple case with two protections in series:

Difference between pickup time of the protections to be co-ordinated


Opening time of the breaker closest to the studied fault
Reset times of the protections
Margin dependent of the time delay inaccuracy of the protections

Assume we have the following network case.

1396

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A1

B1

51

51

Feeder

Time axis

t=0

t=t1

t=t2

t=t3
en05000132_ansi.vsd

ANSI05000132 V1 EN

Figure 635:

Selectivity steps for a fault on feeder B1

where:
t=0

is The fault occurs

t=t1

is Protection B1 trips

t=t2

is Breaker at B1 opens

t=t3

is Protection A1 resets

In the case protection B1 shall trip without any intentional delay (instantaneous). When
the fault occurs the protections pickup to detect the fault current. After the time t1 the
protection B1 send a trip signal to the circuit breaker. The protection A1 starts its delay
timer at the same time, with some deviation in time due to differences between the two
protections. There is a possibility that A1 will pickup before the trip is sent to the B1 circuit
breaker. At the time t2 the circuit breaker B1 has opened its primary contacts and thus the
fault current is interrupted. The breaker time (t2 - t1) can differ between different faults.
The maximum opening time can be given from manuals and test protocols. Still at t2 the
timer of protection A1 is active. At time t3 the protection A1 is reset, that is the timer is
stopped.
In most applications it is required that the times shall reset as fast as possible when the
current fed to the protection drops below the set current level, the reset time shall be
minimized. In some applications it is however beneficial to have some type of delayed
reset time of the overcurrent function. This can be the case in the following applications:

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1397

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

If there is a risk of intermittent faults. If the current IED, close to the faults, picks up
and resets there is a risk of unselective trip from other protections in the system.
Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
Overcurrent protection functions are sometimes used as release criterion for other
protection functions. It can often be valuable to have a reset delay to assure the release
function.

25.2

Principle of operation

25.2.1

Mode of operation
The function can trip in a definite time-lag mode or in a current definite inverse time mode.
For the inverse time characteristic both ANSI and IEC based standard curves are
available. Also programmable curve types are supported via the component inputs: p, A,
B, C pr, tr, and cr.
Different characteristics for reset delay can also be chosen.
If current in any phase exceeds the set pickup current value (here internal signal
pickupValue), a timer, according to the selected operating mode, is started. The
component always uses the maximum of the three phase current values as the current level
used in timing calculations.
In case of definite time-lag mode the timer will run constantly until the time is reached or
until the current drops below the reset value (pickup value minus the hysteresis) and the
reset time has elapsed.
For definite time delay curve ANSI/IEEE Definite time or IEC Definite time are chosen.
The general expression for inverse time curves is according to equation 200.

1398

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A
t [s ] =
P

Pickupn

-C

+ B td

(Equation 200)

EQUATION1640 V1 EN

where:
p, A, B, C

are constants defined for each curve type,

Pickupn

is the set pickup current for step n,

td

is set time multiplier for step n and

is the measured current.

For inverse time characteristics a time will be initiated when the current reaches the set
pickup level. From the general expression of the characteristic the following can be seen:

( top - B td ) Pickupn

-C

= A td
(Equation 201)

EQUATION1642 V1 EN

where:
top

is the operating time of the protection

The time elapsed to the moment of trip is reached when the integral fulfils according to
equation 202, in addition to the constant time delay:
t

Pickupn
0

- C dt A td

EQUATION1643 V1 EN

(Equation 202)

For the numerical protection the sum below must fulfil the equation for trip.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1399

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

i ( j ) P

- C A td

Pickupn

j =1

Dt

(Equation 203)

EQUATION1644 V1 EN

where:
j=1

is the first protection execution cycle when a fault has been detected,
that is, when

i
Pickupn

>1

EQUATION1646 V1 EN

Dt

is the time interval between two consecutive executions of the


protection algorithm,

is the number of the execution of the algorithm when the trip time
equation is fulfilled, that is, when a trip is given and

i (j)

is the fault current at time j

For inverse time operation, the inverse time characteristic is selectable. Both the IEC and
ANSI/IEEE standardized inverse time characteristics are supported.
For the IEC curves there is also a setting of the minimum time-lag of operation, see
figure 636.

1400

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Operate
time

tMin

Current

IMin

IEC05000133-3-en.vsd
IEC05000133 V2 EN

Figure 636:

Minimum time-lag operation for the IEC curves

In order to fully comply with IEC curves definition setting parameter tMin shall be set to
the value which is equal to the operating time of the selected IEC inverse time curve for
measured current of twenty times the set current pickup value. Note that the operating time
value is dependent on the selected setting value for time multiplier k.
In addition to the ANSI and IEC standardized characteristics, there are also two additional
inverse curves available; the RI curve and the RD curve.
The RI inverse time curve emulates the characteristic of the electromechanical ASEA
relay RI. The curve is described by equation 205:

td
t [s ] =
0.339 - 0.235 Pickupn
i

(Equation 205)

EQUATION1647 V1 EN

where:
Pickupn is the set pickup current for step n
td

is set time multiplier for step n

is the measured current

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1401

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

The RD inverse curve gives a logarithmic delay, as used in the Combiflex protection
RXIDG. The curve enables a high degree of selectivity required for sensitive residual
ground-fault current protection, with ability to detect high-resistive ground faults. The
curve is described by equation 206:

td Pickupn

[ ]

t s = 5.8 - 1.35 ln

(Equation 206)

EQUATION1648 V1 EN

where:
Pickupn is the set pickup current for step n,
td

is set time multiplier for step n and

is the measured current

If the curve type programmable is chosen, the user can make a tailor made inverse time
curve according to the general equation 207.

A
t [s ] =
P

Pickupn

-C

+ B td

(Equation 207)

EQUATION1640 V1 EN

Also the reset time of the delayed function can be controlled. There is the possibility to
choose between three different reset time-lags.

Instantaneous Reset
IEC Reset
ANSI Reset.

If instantaneous reset is chosen the timer will be reset directly when the current drops
below the set pickup current level minus the hysteresis.
If IEC reset is chosen the timer will be reset after a set constant time when the current drops
below the set pickup current level minus the hysteresis.
If ANSI reset time is chosen the reset time will be dependent of the current after fault
clearance (when the current drops below the pickup current level minus the hysteresis).
The timer will reset according to equation 208.

1402

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

tr
td
t [s] =
i 2

-1
pickupn

(Equation 208)

ANSIEQUATION1197 V1 EN

where:
The set value tr is the reset time in case of zero current after fault clearance.

The possibility of choice of reset characteristics is to some extent dependent of the choice
of time delay characteristic.
For the definite time delay characteristics the possible reset time settings are instantaneous
and IEC constant time reset.
For ANSI inverse time delay characteristics all three types of reset time characteristics are
available; instantaneous, IEC constant time reset and ANSI current dependent reset time.
For IEC inverse time delay characteristics the possible delay time settings are
instantaneous and IEC set constant time reset).
For the programmable inverse time delay characteristics all three types of reset time
characteristics are available; instantaneous, IEC constant time reset and ANSI current
dependent reset time. If the current dependent type is used settings pr, tr and cr must be
given, see equation 209:

tr
td
t [s] =
i pr

- cr
pickupn

(Equation 209)

ANSIEQUATION1198 V1 EN

For RI and RD inverse time delay characteristics the possible delay time settings are
instantaneous and IEC constant time reset.
When inverse time overcurrent characteristic is selected, the trip time of
the stage will be the sum of the inverse time delay and the set definite time
delay. Thus, if only the inverse time delay is required, it is important to set
the definite time delay for that stage to zero.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1403

Section 25
Inverse time characteristics

25.3

1MRK 502 066-UUS A

Inverse characteristics
Table 977:

ANSI Inverse time characteristics

Function

Range or value

Operating characteristic:

t =

A
P
( I - 1)

0.10 td 3.00
1.5 x Iset I 20 x Iset

Accuracy
ANSI/IEEE C37.112 ,
2.0% or 40 ms
whichever is greater

+ B td

EQUATION1651 V1 EN

Reset characteristic:
t =

(I

tr
2

td

-1

EQUATION1652 V1 EN

I = Imeasured/Iset

1404

ANSI Extremely Inverse

A=28.2, B=0.1217, P=2.0 , tr=29.1

ANSI Very inverse

A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse

A=0.0086, B=0.0185, P=0.02,


tr=0.46

ANSI Moderately Inverse

A=0.0515, B=0.1140, P=0.02,


tr=4.85

ANSI Long Time Extremely Inverse

A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse

A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse

A=0.086, B=0.185, P=0.02, tr=4.6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 978:

IEC Inverse time characteristics

Function

Range or value

Operating characteristic:

t =

A
P
td
( I - 1)

0.10 td 3.00
1.5 x Iset I 20 x Iset

Accuracy
IEC 60255-151, 2.0%
or 40 ms whichever is
greater

EQUATION1653 V1 EN

I = Imeasured/Iset
IEC Normal Inverse

A=0.14, P=0.02

IEC Very inverse

A=13.5, P=1.0

IEC Inverse

A=0.14, P=0.02

IEC Extremely inverse

A=80.0, P=2.0

IEC Short time inverse

A=0.05, P=0.04

IEC Long time inverse

A=120, P=1.0

Programmable characteristic
Trip characteristic:

td = (0.05-999) in steps of 0.01


A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of
0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001

t =

A
P
(I - C )

+ B td

EQUATION1654 V1 EN

Reset characteristic:
t =

(I

TR
PR

- CR

td

EQUATION1655 V1 EN

I = Imeasured/Iset

Table 979:

RI and RD type inverse time characteristics

Function

Range or value

RI type inverse characteristic


1

t =

0.339 -

0.236

0.10 td 3.00
1.5 x Iset I 20 x Iset

Accuracy
IEC 60255-151, 2.0%
or 40 ms whichever is
greater

td

EQUATION1656 V1 EN

I = Imeasured/Iset
RD type logarithmic inverse characteristic

t = 5.8 - 1.35 In

I
td

EQUATION1657 V1 EN

I = Imeasured/Iset
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1405

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 980:

ANSI Inverse time characteristics for Line Differential Protection

Function

Range or value

Operating characteristic:

t =

A
P
( I - 1)

td = (0.05-2.00) in steps of 0.01

Accuracy
ANSI/IEEE C37.112 ,
5.0% or 40 ms
whichever is greater

+ B td

EQUATION1651 V1 EN

Reset characteristic:
t =

(I

tr
2

td

-1

EQUATION1652 V1 EN

I = Imeasured/Iset

1406

ANSI Extremely Inverse

A=28.2, B=0.1217, P=2.0 , tr=29.1

ANSI Very inverse

A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse

A=0.0086, B=0.0185, P=0.02,


tr=0.46

ANSI Moderately Inverse

A=0.0515, B=0.1140, P=0.02,


tr=4.85

ANSI Long Time Extremely Inverse

A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse

A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse

A=0.086, B=0.185, P=0.02, tr=4.6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 981:

IEC Inverse time characteristics for Line Differential protection

Function

Range or value

Operating characteristic:

t =

td = (0.05-2.00) in steps of 0.01

A
P
td
( I - 1)

Accuracy
IEC 60255-151, 5.0%
or 40 ms whichever is
greater

EQUATION1653 V1 EN

I = Imeasured/Iset
IEC Normal Inverse

A=0.14, P=0.02

IEC Very inverse

A=13.5, P=1.0

IEC Inverse

A=0.14, P=0.02

IEC Extremely inverse

A=80.0, P=2.0

IEC Short time inverse

A=0.05, P=0.04

IEC Long time inverse

A=120, P=1.0

Programmable characteristic
Operate characteristic:

td = (0.05-999) in steps of 0.01


A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of
0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001

t =

A
P
(I - C )

+ B td

EQUATION1654 V1 EN

Reset characteristic:
t =

(I

TR
PR

- CR

td

EQUATION1655 V1 EN

I = Imeasured/Iset

The parameter setting Characterist1 and 4/Reserved shall not be used,


since this parameter setting is for future use and not implemented yet.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1407

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 982:

RI and RD type inverse time characteristics for Line Differential protection

Function

Range or value

RI type inverse characteristic


1

t =

0.339 -

0.236

td = (0.05-2.00) in steps of 0.01

Accuracy
IEC 60255-151, 5.0%
or 40 ms whichever is
greater

td

EQUATION1656 V1 EN

I = Imeasured/Iset
RD type logarithmic inverse characteristic

t = 5.8 - 1.35 In

td = (0.05-999) in steps of 0.01

td
I

EQUATION1657 V1 EN

I = Imeasured/Iset

Table 983:

ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power
protection

Function

Range or value

Operating characteristic:

t =

A
P
( I - 1)

0.10 k 2.00
1.5 x Iset I 20 x Iset

Accuracy
ANSI/IEEE C37.112 ,
5.0% or 160 ms
whichever is greater

+ B td

EQUATION1651 V1 EN

Reset characteristic:
t =

(I

tr
2

td

-1

EQUATION1652 V1 EN

I = Imeasured/Iset

1408

ANSI Extremely Inverse

A=28.2, B=0.1217, P=2.0 , tr=29.1

ANSI Very inverse

A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse

A=0.0086, B=0.0185, P=0.02,


tr=0.46

ANSI Moderately Inverse

A=0.0515, B=0.1140, P=0.02,


tr=4.85

ANSI Long Time Extremely Inverse

A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse

A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse

A=0.086, B=0.185, P=0.02, tr=4.6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 984:

IEC Inverse time characteristics for Sensitive directional residual overcurrent and power
protection

Function

Range or value

Operating characteristic:

t =

A
P
td
( I - 1)

0.10 k 2.00
1.5 x Iset I 20 x Iset

Accuracy
IEC 60255-151, 5.0%
or 160 ms whichever is
greater

EQUATION1653 V1 EN

I = Imeasured/Iset
IEC Normal Inverse

A=0.14, P=0.02

IEC Very inverse

A=13.5, P=1.0

IEC Inverse

A=0.14, P=0.02

IEC Extremely inverse

A=80.0, P=2.0

IEC Short time inverse

A=0.05, P=0.04

IEC Long time inverse

A=120, P=1.0

Programmable characteristic
Trip characteristic:

td = (0.05-999) in steps of 0.01


A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of
0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001

t =

A
P
(I - C )

+ B td

EQUATION1654 V1 EN

Reset characteristic:
t =

(I

TR
PR

- CR

td

EQUATION1655 V1 EN

I = Imeasured/Iset

The parameter setting Characterist1 and 4/Reserved shall not be used,


since this parameter setting is for future use and not implemented yet.

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1409

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 985:

RI and RD type inverse time characteristics for Sensitive directional residual overcurrent
and power protection

Function

Range or value

RI type inverse characteristic


1

t =

0.339 -

0.236

0.10 k 2.00
1.5 x Iset I 20 x Iset

Accuracy
IEC 60255-151, 5.0%
or 160 ms whichever is
greater

td

EQUATION1656 V1 EN

I = Imeasured/Iset
RD type logarithmic inverse characteristic

t = 5.8 - 1.35 In

td
I

EQUATION1657 V1 EN

I = Imeasured/Iset

Table 986:

ANSI Inverse time characteristics for Voltage restrained time overcurrent protection

Function

Range or value

Operating characteristic:

t =

A
P
( I - 1)

td = (0.05-2.00) in steps of 0.01

Accuracy
ANSI/IEEE C37.112 ,
5.0% or 40 ms
whichever is greater

+ B td

EQUATION1651 V1 EN

Reset characteristic:
t =

(I

tr
2

td

-1

EQUATION1652 V1 EN

I = Imeasured/Iset

1410

ANSI Extremely Inverse

A=28.2, B=0.1217, P=2.0 , tr=29.1

ANSI Very inverse

A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse

A=0.0086, B=0.0185, P=0.02,


tr=0.46

ANSI Moderately Inverse

A=0.0515, B=0.1140, P=0.02,


tr=4.85

ANSI Long Time Extremely Inverse

A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse

A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse

A=0.086, B=0.185, P=0.02, tr=4.6

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 987:

IEC Inverse time characteristics for Voltage restrained time overcurrent protection

Function
Operating characteristic:

t =

Range or value
td = (0.05-2.00) in steps of 0.01

A
P
td
( I - 1)

Accuracy
IEC 60255-151, 5.0%
or 40 ms whichever is
greater

EQUATION1653 V1 EN

I = Imeasured/Iset
IEC Normal Inverse

A=0.14, P=0.02

IEC Very inverse

A=13.5, P=1.0

IEC Inverse

A=0.14, P=0.02

IEC Extremely inverse

A=80.0, P=2.0

IEC Short time inverse

A=0.05, P=0.04

IEC Long time inverse

A=120, P=1.0

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1411

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 988:

Inverse time characteristics for overvoltage protection

Function

Range or value

Type A curve:
t =

td = (0.05-1.10) in steps of
0.01

Accuracy
5.0% or 45 ms
whichever is greater

td

V - VPickup

VPickup

EQUATION1661 V1 EN

V = Vmeasured
td = (0.05-1.10) in steps of
0.01

Type B curve:
t =

td 480
V VPickup

0.5
32
VPickup

+ 0.035

2.0

EQUATION1662 V2 EN

td = (0.05-1.10) in steps of
0.01

Type C curve:
t =

td 480
V VPickup

0.5
32
VPickup

3.0

+ 0.035

EQUATION1663 V2 EN

Programmable curve:

t =

td A

V - VPickup
B
VPickup

EQUATION1664 V1 EN

1412

-C

+D

td = (0.05-1.10) in steps of
0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in steps
of 0.01
C = (0.0-1.0) in steps of 0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in steps
of 0.001

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 989:

Inverse time characteristics for undervoltage protection

Function

Range or value

Type A curve:

t =

td = (0.05-1.10) in steps of
0.01

Accuracy
5.0% or 45 ms
whichever is greater

td

VPickup - V

VPickup

EQUATION1658 V1 EN

V = Vmeasured
Type B curve:

t =

td = (0.05-1.10) in steps of
0.01

td 480
VPickup - V

32
VPickup

- 0.5

2.0

+ 0.055

EQUATION1659 V1 EN

V = Vmeasured
Programmable curve:

t =

td A

VPickup - V
B
VPickup

EQUATION1660 V1 EN

V = Vmeasured

+D
P

-C

td = (0.05-1.10) in steps of
0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in steps
of 0.01
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in steps
of 0.001

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1413

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

Table 990:

Inverse time characteristics for residual overvoltage protection

Function

Range or value

Type A curve:
t =

td = (0.05-1.10) in steps of
0.01

Accuracy
5.0% or 45 ms
whichever is greater

td

V - VPickup

VPickup

EQUATION1661 V1 EN

V = Vmeasured
td = (0.05-1.10) in steps of
0.01

Type B curve:
t =

td 480
V VPickup

0.5
32
VPickup

+ 0.035

2.0

EQUATION1662 V2 EN

td = (0.05-1.10) in steps of
0.01

Type C curve:
t =

td 480
V VPickup

0.5
32
VPickup

3.0

+ 0.035

EQUATION1663 V2 EN

Programmable curve:

t =

td A

V - VPickup
B
VPickup

EQUATION1664 V1 EN

1414

-C

+D

td = (0.05-1.10) in steps of
0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in steps
of 0.01
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in steps
of 0.001

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070750 V2 EN

Figure 637:

ANSI Extremely inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1415

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070751 V2 EN

Figure 638:

1416

ANSI Very inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070752 V2 EN

Figure 639:

ANSI Normal inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1417

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070753 V2 EN

Figure 640:

1418

ANSI Moderately inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070817 V2 EN

Figure 641:

ANSI Long time extremely inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1419

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070818 V2 EN

Figure 642:

1420

ANSI Long time very inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070819 V2 EN

Figure 643:

ANSI Long time inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1421

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070820 V2 EN

Figure 644:

1422

IEC Normal inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070821 V2 EN

Figure 645:

IEC Very inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1423

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070822 V2 EN

Figure 646:

1424

IEC Inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070823 V2 EN

Figure 647:

IEC Extremely inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1425

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070824 V2 EN

Figure 648:

1426

IEC Short time inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070825 V2 EN

Figure 649:

IEC Long time inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1427

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070826 V2 EN

Figure 650:

1428

RI-type inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

A070827 V2 EN

Figure 651:

RD-type inverse time characteristics

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1429

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN

Figure 652:

1430

Inverse curve A characteristic of overvoltage protection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN

Figure 653:

Inverse curve B characteristic of overvoltage protection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1431

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN

Figure 654:

1432

Inverse curve C characteristic of overvoltage protection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN

Figure 655:

Inverse curve A characteristic of undervoltage protection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1433

Section 25
Inverse time characteristics

1MRK 502 066-UUS A

GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN

Figure 656:

1434

Inverse curve B characteristic of undervoltage protection

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 26
Glossary

1MRK 502 066-UUS A

Section 26

Glossary

26.1

Glossary
AC

Alternating current

ACC

Actual channel

ACT

Application configuration tool within PCM600

A/D converter

Analog-to-digital converter

ADBS

Amplitude deadband supervision

ADM

Analog digital conversion module, with time synchronization

AI

Analog input

ANSI

American National Standards Institute

AR

Autoreclosing

ASCT

Auxiliary summation current transformer

ASD

Adaptive signal detection

ASDU

Application service data unit

AWG

American Wire Gauge standard

BBP

Busbar protection

BFOC/2,5

Bayonet fibre optic connector

BFP

Breaker failure protection

BI

Binary input

BIM

Binary input module

BOM

Binary output module

BOS

Binary outputs status

BR

External bistable relay

BS

British Standards

BSR

Binary signal transfer function, receiver blocks

BST

Binary signal transfer function, transmit blocks

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1435

Section 26
Glossary

1436

1MRK 502 066-UUS A

C37.94

IEEE/ANSI protocol used when sending binary signals between


IEDs

CAN

Controller Area Network. ISO standard (ISO 11898) for serial


communication

CB

Circuit breaker

CBM

Combined backplane module

CCITT

Consultative Committee for International Telegraph and


Telephony. A United Nations-sponsored standards body within
the International Telecommunications Union.

CCM

CAN carrier module

CCVT

Capacitive Coupled Voltage Transformer

Class C

Protection Current Transformer class as per IEEE/ ANSI

CMPPS

Combined megapulses per second

CMT

Communication Management tool in PCM600

CO cycle

Close-open cycle

Codirectional

Way of transmitting G.703 over a balanced line. Involves two


twisted pairs making it possible to transmit information in both
directions

COM

Command

COMTRADE

Standard Common Format for Transient Data Exchange format


for Disturbance recorder according to IEEE/ANSI C37.111,
1999 / IEC60255-24

Contra-directional

Way of transmitting G.703 over a balanced line. Involves four


twisted pairs, two of which are used for transmitting data in both
directions and two for transmitting clock signals

COT

Cause of transmission

CPU

Central processing unit

CR

Carrier receive

CRC

Cyclic redundancy check

CROB

Control relay output block

CS

Carrier send

CT

Current transformer

CU

Communication unit

CVT or CCVT

Capacitive voltage transformer

DAR

Delayed autoreclosing
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 26
Glossary

1MRK 502 066-UUS A

DARPA

Defense Advanced Research Projects Agency (The US


developer of the TCP/IP protocol etc.)

DBDL

Dead bus dead line

DBLL

Dead bus live line

DC

Direct current

DFC

Data flow control

DFT

Discrete Fourier transform

DHCP

Dynamic Host Configuration Protocol

DIP-switch

Small switch mounted on a printed circuit board

DI

Digital input

DLLB

Dead line live bus

DNP

Distributed Network Protocol as per IEEE Std 1815-2012

DR

Disturbance recorder

DRAM

Dynamic random access memory

DRH

Disturbance report handler

DSP

Digital signal processor

DTT

Direct transfer trip scheme

EHV network

Extra high voltage network

EIA

Electronic Industries Association

EMC

Electromagnetic compatibility

EMF

Electromotive force

EMI

Electromagnetic interference

EnFP

End fault protection

EPA

Enhanced performance architecture

ESD

Electrostatic discharge

F-SMA

Type of optical fibre connector

FAN

Fault number

FCB

Flow control bit; Frame count bit

FOX 20

Modular 20 channel telecommunication system for speech, data


and protection signals

FOX 512/515

Access multiplexer

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1437

Section 26
Glossary

1MRK 502 066-UUS A

FOX 6Plus

Compact time-division multiplexer for the transmission of up to


seven duplex channels of digital data over optical fibers

FTP

File Transfer Protocol

FUN

Function type

G.703

Electrical and functional description for digital lines used by


local telephone companies. Can be transported over balanced
and unbalanced lines

GCM

Communication interface module with carrier of GPS receiver


module

GDE

Graphical display editor within PCM600

GI

General interrogation command

GIS

Gas-insulated switchgear

GOOSE

Generic object-oriented substation event

GPS

Global positioning system

GSAL

Generic security application

GSE

Generic substation event

HDLC protocol

High-level data link control, protocol based on the HDLC


standard

HFBR connector type Plastic fiber connector

1438

HMI

Human-machine interface

HSAR

High speed autoreclosing

HV

High-voltage

HVDC

High-voltage direct current

ICT

Installation and Commissioning Tool for injection based


protection in REG670

IDBS

Integrating deadband supervision

IEC

International Electrical Committee

IEC 60044-6

IEC Standard, Instrument transformers Part 6: Requirements


for protective current transformers for transient performance

IEC 60870-5-103

Communication standard for protection equipment. A serial


master/slave protocol for point-to-point communication

IEC 61850

Substation automation communication standard

IEC 6185081

Communication protocol standard

IEEE

Institute of Electrical and Electronics Engineers


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 26
Glossary

1MRK 502 066-UUS A

IEEE 802.12

A network technology standard that provides 100 Mbits/s on


twisted-pair or optical fiber cable

IEEE P1386.1

PCI Mezzanine Card (PMC) standard for local bus modules.


References the CMC (IEEE P1386, also known as Common
Mezzanine Card) standard for the mechanics and the PCI
specifications from the PCI SIG (Special Interest Group) for the
electrical EMF (Electromotive force).

IEEE 1686

Standard for Substation Intelligent Electronic Devices (IEDs)


Cyber Security Capabilities

IED

Intelligent electronic device

I-GIS

Intelligent gas-insulated switchgear

IOM

Binary input/output module

Instance

When several occurrences of the same function are available in


the IED, they are referred to as instances of that function. One
instance of a function is identical to another of the same kind but
has a different number in the IED user interfaces. The word
"instance" is sometimes defined as an item of information that is
representative of a type. In the same way an instance of a
function in the IED is representative of a type of function.

IP

1. Internet protocol. The network layer for the TCP/IP protocol


suite widely used on Ethernet networks. IP is a connectionless,
best-effort packet-switching protocol. It provides packet
routing, fragmentation and reassembly through the data link
layer.
2. Ingression protection, according to IEC 60529

IP 20

Ingression protection, according to IEC 60529, level


IP20- Protected against solid foreign objects of 12.5mm
diameter and greater.

IP 40

Ingression protection, according to IEC 60529, level IP40Protected against solid foreign objects of 1mm diameter and
greater.

IP 54

Ingression protection, according to IEC 60529, level


IP54-Dust-protected, protected against splashing water.

IRF

Internal failure signal

IRIG-B:

InterRange Instrumentation Group Time code format B,


standard 200

ITU

International Telecommunications Union

LAN

Local area network

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1439

Section 26
Glossary

1440

1MRK 502 066-UUS A

LIB 520

High-voltage software module

LCD

Liquid crystal display

LDCM

Line differential communication module

LDD

Local detection device

LED

Light-emitting diode

LNT

LON network tool

LON

Local operating network

MCB

Miniature circuit breaker

MCM

Mezzanine carrier module

MIM

Milli-ampere module

MPM

Main processing module

MVAL

Value of measurement

MVB

Multifunction vehicle bus. Standardized serial bus originally


developed for use in trains.

NCC

National Control Centre

NOF

Number of grid faults

NUM

Numerical module

OCO cycle

Open-close-open cycle

OCP

Overcurrent protection

OEM

Optical Ethernet module

OLTC

On-load tap changer

OTEV

Disturbance data recording initiated by other event than start/


pick-up

OV

Overvoltage

Overreach

A term used to describe how the relay behaves during a fault


condition. For example, a distance relay is overreaching when
the impedance presented to it is smaller than the apparent
impedance to the fault applied to the balance point, that is, the
set reach. The relay sees the fault but perhaps it should not
have seen it.

PCI

Peripheral component interconnect, a local data bus

PCM

Pulse code modulation

PCM600

Protection and control IED manager

PC-MIP

Mezzanine card standard


Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 26
Glossary

1MRK 502 066-UUS A

PMC

PCI Mezzanine card

POR

Permissive overreach

POTT

Permissive overreach transfer trip

Process bus

Bus or LAN used at the process level, that is, in near proximity
to the measured and/or controlled components

PSM

Power supply module

PST

Parameter setting tool within PCM600

PT ratio

Potential transformer or voltage transformer ratio

PUTT

Permissive underreach transfer trip

RASC

Synchrocheck relay, COMBIFLEX

RCA

Relay characteristic angle

RISC

Reduced instruction set computer

RMS value

Root mean square value

RS422

A balanced serial interface for the transmission of digital data in


point-to-point connections

RS485

Serial link according to EIA standard RS485

RTC

Real-time clock

RTU

Remote terminal unit

SA

Substation Automation

SBO

Select-before-operate

SC

Switch or push button to close

SCL

Short circuit location

SCS

Station control system

SCADA

Supervision, control and data acquisition

SCT

System configuration tool according to standard IEC 61850

SDU

Service data unit

SLM

Serial communication module.

SMA connector

Subminiature version A, A threaded connector with constant


impedance.

SMT

Signal matrix tool within PCM600

SMS

Station monitoring system

SNTP

Simple network time protocol is used to synchronize


computer clocks on local area networks. This reduces the

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1441

Section 26
Glossary

1MRK 502 066-UUS A

requirement to have accurate hardware clocks in every


embedded system in a network. Each embedded node can
instead synchronize with a remote clock, providing the required
accuracy.
SOF

Status of fault

SPA

Strmberg Protection Acquisition (SPA), a serial master/slave


protocol for point-to-point and ring communication.

SRY

Switch for CB ready condition

ST

Switch or push button to trip

Starpoint

Neutral/Wye point of transformer or generator

SVC

Static VAr compensation

TC

Trip coil

TCS

Trip circuit supervision

TCP

Transmission control protocol. The most common transport


layer protocol used on Ethernet and the Internet.

TCP/IP

Transmission control protocol over Internet Protocol. The de


facto standard Ethernet protocols incorporated into 4.2BSD
Unix. TCP/IP was developed by DARPA for Internet working
and encompasses both network layer and transport layer
protocols. While TCP and IP specify two protocols at specific
protocol layers, TCP/IP is often used to refer to the entire US
Department of Defense protocol suite based upon these,
including Telnet, FTP, UDP and RDP.

TEF

Time delayed gound-fault protection function

TLS

Transport Layer Security

TM

Transmit (disturbance data)

TNC connector

Threaded Neill-Concelman, a threaded constant impedance


version of a BNC connector

TP

Trip (recorded fault)

TPZ, TPY, TPX, TPS Current transformer class according to IEC

1442

TRM

Transformer Module. This module transforms currents and


voltages taken from the process into levels suitable for further
signal processing.

TYP

Type identification

UMT

User management tool

Underreach

A term used to describe how the relay behaves during a fault


condition. For example, a distance relay is underreaching when
Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

Section 26
Glossary

1MRK 502 066-UUS A

the impedance presented to it is greater than the apparent


impedance to the fault applied to the balance point, that is, the
set reach. The relay does not see the fault but perhaps it should
have seen it. See also Overreach.
UTC

Coordinated Universal Time. A coordinated time scale,


maintained by the Bureau International des Poids et Mesures
(BIPM), which forms the basis of a coordinated dissemination
of standard frequencies and time signals. UTC is derived from
International Atomic Time (TAI) by the addition of a whole
number of "leap seconds" to synchronize it with Universal Time
1 (UT1), thus allowing for the eccentricity of the Earth's orbit,
the rotational axis tilt (23.5 degrees), but still showing the
Earth's irregular rotation, on which UT1 is based. The
Coordinated Universal Time is expressed using a 24-hour
clock, and uses the Gregorian calendar. It is used for aeroplane
and ship navigation, where it is also sometimes known by the
military name, "Zulu time." "Zulu" in the phonetic alphabet
stands for "Z", which stands for longitude zero.

UV

Undervoltage

WEI

Weak end infeed logic

VT

Voltage transformer

X.21

A digital signalling interface primarily used for telecom


equipment

3IO

Three times zero-sequence current.Often referred to as the


residual or the ground-fault current

3VO

Three times the zero sequence voltage. Often referred to as the


residual voltage or the neutral point voltage

Generator protection REG670 2.1 ANSI and Injection equipment REX060, REX061, REX062
Technical manual

1443

1444

1445

For more information please contact:


ABB AB
Substation Automation Products
SE-721 59 Vsters, Sweden
Phone +46 (0) 21 32 50 00
www.abb.com/substationautomation

Note:
We reserve the right to make technical changes or modify the
contents of this document without prior notice. ABB AB does
not accept any responsibility whatsoever for potential errors or
possible lack of information in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained herein. Any reproduction,
disclosure to third parties or utilization of its contents in whole
or in part is forbidden without prior written consent of ABB AB.

Copyright 2016 ABB.


All rights reserved.

Scan this QR code to visit our website

1MRK 502 066-UUS

Contact us

You might also like