This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
SIGN.
SIGN.
SIGN.
REV. DESCRIPTION DRAWN CHECKED APPROVED STATUS
CLIENT :
ADANI POWER LIMITED
2 x 330MW THERMAL POWER PLANT
MUNDRA SEZ, TUNDA, SIRACHA VILLAGE, KUTCHH DIST. GUJARAT
CONSULTANT FICHTNER
CONSULTING ENGINEERS (INDIA) PRIVATE LIMITED,
CHENNAI
TITLE :
400 KV CONTROL & INTERLOCK LOGIC DIAGRAM
File: PG725000-
AREVA T&D India Limited DRAWING NO. REV. SHEET TOTAL SHEET
A-7, SECTOR-65
EMI-7604PG754-4-028 B 001 92
NOIDA - 201301
DF002
002 X X INDEX 043 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN ICT-1
003 X CONTROL LOGIC FOR LOCAL OPERATION OF ISOLATORS FROM EQP M.BOX 044 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN ICT-1
004 X CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM BCU 045 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN ICT-1
005 X CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM HMI 046 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-3
006 X CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM SCADA 047 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-3 (CONTD.)
007 X CONTROL LOGIC FOR LOCAL OPERATION OF CKT. BKRS FROM EQP M. BOX 048 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-3
CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM BCU/BAY
008 X 049 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-3
CONTROL & PROTECTION PANEL *
008A X PROTECTION TRIP LOGIC FOR LINE PROTECTIONS(TYPICAL) 050 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-3
008B X PROTECTION TRIP LOGIC FOR TIE PROTECTIONS(TYPICAL) 051 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-3
008C X PROTECTION TRIP LOGIC FOR GT PROTECTIONS(TYPICAL) 052 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-3
008D X PROTECTION TRIP LOGIC FOR ICT PROTECTIONS(TYPICAL) 053 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OFEARTH SWITCHES IN TIE-3
CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM BCU/ BAY
009 X X 054 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-3
CONTROL & PROTECTION PANEL *
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
010 X CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM HMI * 055 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-3
011 X X CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM HMI * 056 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-3
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE
012 X 057 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN ICT-2
1
CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM SCADA
013 X X 058 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN ICT-2 (CONTD.)
(LDC) *
CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM SCADA
014 X X 059 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN ICT-2
(LDC) *
015 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-1 060 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN ICT-2
016 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-1 (CONTD) 061 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN ICT-2
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE
017 X X 062 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G ICT-2
1
018 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-1 063 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-4
019 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-1 064 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-4 (CONTD.)
020 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-1 065 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-4
021 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN TIE-1 066 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-4
022 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-1 067 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-4
023 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-1 068 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-4
023A X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-1 (CONTD.) 069 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-4
024 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-1 070 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OFEARTH SWITCHES IN TIE-4
025 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN GT-3 071 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-4
026 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN GT-3 (CONTD.) 072 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-4
027 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN GT-3 073 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-4
CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN
028 X X 074 X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-4
GT-3
029 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-2 075 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN GT-4
030 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-2 (CONTD.) 076 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN GT-4 (CONTD.)
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE
031 X X 077 X X CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN GT-4
2
032 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-2 078 X X CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN GT-4
033 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-2 079 X X INTERLOCK LOGIC FOR OPERATION OF BUS-1 CVT ISOLATOR & EARTH SWITCH
034 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-2 080 X X INTERLOCK LOGIC FOR OPERATION OF BUS-2 CVT ISOLATOR & EARTH SWITCH
035 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-2 081 X IMPLEMENTATION OF SYNCHROCHECK IN BCU
036 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN TIE-2 082 X IMPLEMENTATION OF SYNCHROCHECK IN BCU
037 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-2 083 X IMPLEMENTATION OF SYNCHROCHECK IN BCU
038 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-2 084 X IMPLEMENTATION OF SYNCHROCHECK IN BCU
039 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-2 085 X IMPLEMENTATION OF AUTORECLOSE FUNCTION IN BCU
040 X X INTERLOCK LOGIC FOR OPERATION OF400kV ISOLATORS IN ICT-1 086 X IMPLEMENTATION OF AUTORECLOSE FUNCTION IN BCU
PROJECT : 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT MUNDRA SEZ
File: PG725000-002.xls
CONTROL LOGIC FOR LOCAL OPERATION OF ISOLATORS FROM EQUIPMENT MARSHALLING BOX*
NOTE :
* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY BCU / HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT EQP MARSHALLING BOX IS IN LOCAL MODE.
** INTERLOCKS REQUIRED FOR CLOSING/OPENING OF ISOLATORS ARE VERIFIED IN THE RESPECTIVE BAY CONTROL UNIT AND A OUTPUT IS GENERATED FROM THE BCU WHEN THE INTERLOCKS ARE SATISIFIED.
THE GENERATED OUTPUT IS HARDWIRED IN THE CONTROL CIRCUIT OF THE ISOLATOR. OPEN/CLOSE COMMANDS TO THE ISOLATOR ARE NOT EXECUTED UNLESS THE INTERLOCKS ARE SATISFIED.
OPERATION OF THE ISOLATORS EITHER FROM LOCAL/REMOTE WILL BE SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. INTERLOCKS CAN BE BYPASSED UNDER EMERGENCY CONDITIONS, BY AUTHORISED PERSONNEL ONLY.
*** FOR DETAILED INTERLOCKS REFER THE INTERLOCKS FOR THE RESPECTIVE DETAILED INTERLOCKS.
PROJECT :
MUNDRA SEZ
OPEN/CLOSE OPEN
PUSH BUTTON CONTROL
FROM BCU CLOSE
TO CLOSING CIRCUIT
&
NOTE :
* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT BCU IS IN LOCAL MODE.
** INTERLOCKS REQUIRED FOR CLOSING/OPENING OF ISOLATORS ARE VERIFIED IN THE RESPECTIVE BAY CONTROL UNIT AND A OUTPUT IS GENERATED FROM THE BCU WHEN THE INTERLOCKS ARE SATISIFIED.
THE GENERATED OUTPUT IS HARDWIRED IN THE CONTROL CIRCUIT OF THE ISOLATOR. OPEN/CLOSE COMMANDS TO THE ISOLATOR ARE NOT EXECUTED UNLESS THE INTERLOCKS ARE SATISFIED.
OPERATION OF THE ISOLATORS EITHER FROM LOCAL/REMOTE WILL BE SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. INTERLOCKS CAN BE BYPASSED UNDER EMERGENCY CONDITIONS, BY AUTHORISED PERSONNEL ONLY.
*** FOR DETAILED INTERLOCKS REFER THE INTERLOCKS FOR THE RESPECTIVE DETAILED INTERLOCKS.
PROJECT :
MUNDRA SEZ
OPEN
OPEN/CLOSE CONTROL
FROM HMI
CLOSE
INTLK PERMISSIVE FROM
RESPECTIVE BCU **
TO CLOSING CIRCUIT
&
NOTE :
* IN THIS MODE, CONTROL FROM HIGHER SCADA LEVEL ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTION AT HMI IS IN LOCAL MODE.
** INTERLOCKS REQUIRED FOR CLOSING/OPENING OF ISOLATORS ARE VERIFIED IN THE RESPECTIVE BAY CONTROL UNIT AND A OUTPUT IS GENERATED FROM THE BCU WHEN THE INTERLOCKS ARE SATISIFIED.
THE GENERATED OUTPUT IS HARDWIRED IN THE CONTROL CIRCUIT OF THE ISOLATOR. OPEN/CLOSE COMMANDS TO THE ISOLATOR ARE NOT EXECUTED UNLESS THE INTERLOCKS ARE SATISFIED.
OPERATION OF THE ISOLATORS EITHER FROM LOCAL/REMOTE WILL BE SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. INTERLOCKS CAN BE BYPASSED UNDER EMERGENCY CONDITIONS, BY AUTHORISED PERSONNEL ONLY.
*** FOR DETAILED INTERLOCKS REFER THE INTERLOCKS FOR THE RESPECTIVE DETAILED INTERLOCKS.
PROJECT :
MUNDRA SEZ
OPEN
OPEN/CLOSE CONTROL
FROM HMI
CLOSE
INTLK PERMISSIVE FROM
RESPECTIVE BCU **
TO CLOSING CIRCUIT
&
** INTERLOCKS REQUIRED FOR CLOSING/OPENING OF ISOLATORS ARE VERIFIED IN THE RESPECTIVE BAY CONTROL UNIT AND A OUTPUT IS GENERATED FROM THE BCU WHEN THE INTERLOCKS ARE SATISIFIED.
THE GENERATED OUTPUT IS HARDWIRED IN THE CONTROL CIRCUIT OF THE ISOLATOR. OPEN/CLOSE COMMANDS TO THE ISOLATOR ARE NOT EXECUTED UNLESS THE INTERLOCKS ARE SATISFIED.
OPERATION OF THE ISOLATORS EITHER FROM LOCAL/REMOTE WILL BE SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. INTERLOCKS CAN BE BYPASSED UNDER EMERGENCY CONDITIONS, BY AUTHORISED PERSONNEL ONLY.
*** FOR DETAILED INTERLOCKS REFER THE INTERLOCKS FOR THE RESPECTIVE DETAILED INTERLOCKS.
PROJECT :
MUNDRA SEZ
CONTROL LOGIC FOR LOCAL OPERATION OF CIRCUIT BREAKERS FROM EQUIPMENT MARSHALLING BOX*
TO TRIP COIL - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
NOTE :
* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY BCU / HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT EQP MARSHALLING BOX IS IN LOCAL MODE.
** THESE INTERLOCKS ARE HARDWIRED AT BMK LEVEL AND OPERATION FROM EQP. MARSHALLING BOX IS POSSIBLE ONLY WHEN THESE INTERLOCKS ARE SATISFIED.
FOR DETAILS REFER THE RESPECTIVE BREAKER INTERLOCK LOGICS
PROJECT :
MUNDRA SEZ
CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM BCU/BAY CONTROL & PROTECTION PANEL *
PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA
&
OPEN/CLOSE OPEN
PUSH BUTTON CONTROL
FROM BCU CLOSE
&
NOTE :
* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT BCU IS IN LOCAL MODE.
** EMERGENCY TRIPPING CAN BE GIVEN THROUGH THE TNC SWITCH PROVIDED ON THE BAY PROTECTION & CONTROL PANEL.
CONTROLS GIVEN THROUGH TNC SWITCH ARE ROUTED INDEPENDENT OF THE BCU AND HENCE ARE INDEPENDENT OF THE LOCAL/REMOTE SELECTION AT BCU/HMI.
*** PERMISSIVE FOR MAINTENANCE CLOSING IS GENERATED FROM BCU, WHEN BOTH THE ISOLATORS ON EITHER SIDES OF THE CB ARE OPEN.
THIS OUTPUT CONTACT FROM BCU IS WIRED INTO THE TNC CLOSING CIRCUIT.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
CONTROL LOGIC FOR REMOTE OPENING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS FROM AREVA T&D India Limited
BCU EMI-7604PG754-4-028 A 008 008A
DF003
NOTE :
* ONLY HV O/C & E/F PROTECTION, LBB & BUSBAR PROTECTION ARE LOCATED IN THE SWITCHYARD RELAY PANEL. ALL THE OTHER PROTECTIONS ARE NOT IN PRESENT SCOPE.
NOTE :
CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM BCU/ BAY CONTROL & PROTECTION PANEL *
&
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
VALIDATION OF
CHECK-SYNC
OPEN/CLOSE OPEN
& CONDITIONS
PUSH BUTTON CONTROL IN BCU**
FROM BCU CLOSE
OR
TO CLOSING CIRCUIT
INTLKS IMPLEMENTED THROUGH SOFT LOGIC
IN RESPECTIVE BCU ***
##
& PERMISSIVE
PERMISSIVE FOR MAINTENANCE CLOSING
NOTE :
* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT BCU IS IN LOCAL MODE.
** CHECK SYNCHRONISATION CONDITIONS ARE VALIDATED IN THE RESPECTIVE BAY CONTROL UNIT, BASED UPON THE SELECTED INCOMING & RUNNING VOLTAGES.
*** FOR DETAILED INTERLOCKING LOGICS REFER THE INTERLOCKS OF THE RESPECTIVE CIRCUIT BREAKER.
## PERMISSIVE FOR MAINTENANCE CLOSING IS GENERATED FROM BCU, WHEN BOTH THE ISOLATORS ON EITHER SIDES OF THE CB ARE OPEN.
THIS OUTPUT CONTACT FROM BCU IS WIRED INTO THE TNC CLOSING CIRCUIT.
1 CLOSE COMMAND GIVEN BY THE OPERATOR FROM BCU WILL BE EXECUTED ONLY IF THE CHECK-SYNC CONDITIONS ARE SATISFIED.
2 CLOSE COMMAND FROM TNC SWITCH IS MEANT FOR CLOSING WITHOUT ANY SYNCHRONISATION & HENCE TO BE USED FOR MAINTENANCE/TESTING CONDITIONS.
CLIENT
3 INCOMING & RUNNING VOLTS ARE SELECTED BASED UPON THE ISOLATOR & CB POSITIONS IN THE RESPECTIVE DIA. ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
4 FOR GT-3 & GT-4 (BAYS-3, 12) REMOTE OPERATION IS NOT PROVIDED FROM SWITCHYARD. MUNDRA SEZ
5 FOR TIE-1 & TIE-4 (BAYS-2, 11) REMOTE OPERATION IS POSSIBLE FROM BCU/HMI/SCADA ONLY AS LONG AS THE CONTROL LOGIC FOR REMOTE CLOSING OF AREVA REV. SHEET NEXT SH.
TIE/GT SELECTOR SWITCH IS IN TIE MODE. 400kV LINE-TIE-ICT CIRCUIT BREAKERS AREVA T&D India Limited
FROM BCU EMI-7604PG754-4-028 B 009 010
DF003
&
SUBTATION LOCAL = HMI TO TRIP COIL - 1
LOCAL/REMOTE SELECTION OR
FROM HMI REMOTE = SCADA
TRIP COIL - 2
OPEN
OPEN/CLOSE CONTROL &
FROM HMI
CLOSE
NOTE :
* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT BCU IS IN LOCAL MODE.
** EMERGENCY TRIPPING CAN BE GIVEN THROUGH THE TNC SWITCH PROVIDED ON THE BAY PROTECTION & CONTROL PANEL.
CONTROLS GIVEN THROUGH TNC SWITCH ARE ROUTED INDEPENDENT OF THE BCU.
CONTROL LOGIC FOR REMOTE OPENING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS FROM AREVA T&D India Limited
HMI EMI-7604PG754-4-028 A 010 011
DF003
&
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
VALIDATION OF
CHECK-SYNC
SUBTATION LOCAL = HMI & CONDITIONS
LOCAL/REMOTE SELECTION
FROM HMI REMOTE = SCADA
IN BCU**
OR
OPEN TO CLOSING CIRCUIT
OPEN/CLOSE
CONTROL FROM HMI
CLOSE
NOTE :
* IN THIS MODE, CONTROL FROM SCADA ARE DEFEATED AS LONG AS THE SUBSTATION LOCAL/REMOTE SELECTION IS IN LOCAL MODE.
** CHECK SYNCHRONISATION CONDITIONS ARE VALIDATED IN THE RESPECTIVE BAY CONTROL UNIT, BASED UPON THE SELECTED INCOMING & RUNNING VOLTAGES.
*** FOR DETAILED INTERLOCKING LOGICS REFER THE INTERLOCKS OF THE RESPECTIVE CIRCUIT BREAKER.
## PERMISSIVE FOR MAINTENANCE CLOSING IS GENERATED FROM BCU, WHEN BOTH THE ISOLATORS ON EITHER SIDES OF THE CB ARE OPEN.
THIS OUTPUT CONTACT FROM BCU IS WIRED INTO THE TNC CLOSING CIRCUIT.
1 CLOSE COMMAND GIVEN BY THE OPERATOR FROM HMI WILL BE EXECUTED ONLY IF THE CHECK-SYNC CONDITIONS ARE SATISFIED.
2 CLOSE COMMAND FROM TNC SWITCH IS MEANT FOR CLOSING WITHOUT ANY SYNCHRONISATION & HENCE TO BE USED FOR MAINTENANCE/TESTING CONDITIONS.
CLIENT
ADANI POWER LTD.
:
3 INCOMING & RUNNING VOLTS ARE SELECTED BASED UPON THE ISOLATOR & CB POSITIONS IN THE RESPECTIVE DIA. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
CONTROL LOGIC FOR REMOTE CLOSING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS AREVA T&D India Limited
FROM HMI EMI-7604PG754-4-028 B 011 012
DF003
CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM SCADA (LDC) *
&
SUBTATION LOCAL = HMI TO TRIP COIL - 1
LOCAL/REMOTE SELECTION
FROM HMI REMOTE = SCADA OR
TRIP COIL - 2
OPEN
&
OPEN/CLOSE CONTROL
FROM SCADA
CLOSE
NOTE :
** EMERGENCY TRIPPING CAN BE GIVEN THROUGH THE TNC SWITCH PROVIDED ON THE BAY PROTECTION & CONTROL PANEL.
CONTROLS GIVEN THROUGH TNC SWITCH ARE ROUTED INDEPENDENT OF THE BCU.
CONTROL LOGIC FOR REMOTE OPENING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS FROM AREVA T&D India Limited
SCADA EMI-7604PG754-4-028 A 012 013
DF003
CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM SCADA (LDC) *
&
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
VALIDATION OF
CHECK-SYNC
SUBTATION LOCAL = HMI & CONDITIONS
LOCAL/REMOTE SELECTION
FROM HMI REMOTE = SCADA
IN BCU**
TO CLOSING CIRCUIT
OR
OPEN
OPEN/CLOSE
CONTROL FROM HMI
CLOSE
##
INTLKS IMPLEMENTED THROUGH HARDWIRING PERMISSIVE FOR TNC MAINTENANCE CLOSING FROM BCU
IN BAY CNTL & PROT PANEL*** (APPLIES TO ALL BAYS EXCEPT GT & GT TIE BAYS)
NOTE :
** CHECK SYNCHRONISATION CONDITIONS ARE VALIDATED IN THE RESPECTIVE BAY CONTROL UNIT, BASED UPON THE SELECTED INCOMING & RUNNING VOLTAGES.
*** FOR DETAILS INTERLOCKING LOGICS REFER THE INTERLOCKS OF THE RESPECTIVE CIRCUIT BREAKER.
## PERMISSIVE FOR MAINTENANCE CLOSING IS GENERATED FROM BCU, WHEN BOTH THE ISOLATORS ON EITHER SIDES OF THE CB ARE OPEN.
THIS OUTPUT CONTACT FROM BCU IS WIRED INTO THE TNC CLOSING CIRCUIT.
1 CLOSE COMMAND GIVEN BY THE OPERATOR FROM SCADA WILL BE EXECUTED ONLY IF THE CHECK-SYNC CONDITIONS ARE SATISFIED.
2 CLOSE COMMAND FROM TNC SWITCH IS MEANT FOR CLOSING WITHOUT ANY SYNCHRONISATION & HENCE TO BE USED FOR MAINTENANCE/TESTING CONDITIONS.
CLIENT
ADANI POWER LTD.
:
3 INCOMING & RUNNING VOLTS ARE SELECTED BASED UPON THE ISOLATOR & CB POSITIONS IN THE RESPECTIVE DIA. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
CONTROL LOGIC FOR REMOTE CLOSING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS AREVA T&D India Limited
FROM SCADA EMI-7604PG754-4-028 A 013 014
DF003
A) ISOLATOR 1-89A
1-52CB OPEN***
ISO 1-89A CLOSE ORDER
&
B) ISOLATOR 1-89B
1-89BE OPEN
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
C) ISOLATOR 1-89C
1-89LE OPEN
2-52CB OPEN***
ISO 1-89L CLOSE ORDER
ISO 1-89L CLOSE REQUEST
&
**
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-1
TO CLOSING CIRCUIT
&
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
*** LINE U/V PERMISSIVE IS TAKEN THROUGH SOFT FROM LINE DISTANCE PROTECTION RELAY.
CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-1
A) RUNNING VOLTS *
B) INCOMING VOLTS **
CASE - I
CASE - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 3-52 CLOSE
CB 2-52 CLOSE
CB 1-89L OPEN
NOTE:
* FOR LINE FEEDERS, BUS-2 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.
** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.
THE SYNCHRONISATION OF LINE WITH GT IS NOT CONSIDERED IN THE CVT SELECTION & THE CB CLOSING SCHEME.
ES 1-89 AE CLOSE
CB 1-52 LOCAL CLOSING
& CIRCUIT *
ES 1-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
BBP RELAY
RESET
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
CLIENT : ADANI POWER LTD.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. MUNDRA SEZ
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOS INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-1
EMI-7604PG754-4-028 B 018 019
DF003
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
CB OPEN REQUEST *
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
A) ISOLATOR 2-89A
2-89AE OPEN
A) ISOLATOR 2-89B
&
2-52CB OPEN***
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
NOTE:
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
PROJECT :
MUNDRA SEZ
CONTROL & INTERLOCK LOGIC FOR AREVA REV. SHEET NEXT SH.
OPERATION OF 400kV EARTH SWITCHES IN TIE- AREVA T&D India Limited
1 (BAY-2) EMI-7604PG754-4-028 B 021 022
DF003
A) RUNNING VOLTS *
CASE-1 (TIE/GT SELECTOR SWITCH IN TIE MODE. SYNCHRONISATION IS DONE FROM SWITCHYARD BCU)
B) INCOMING VOLTS *
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 1-52 CLOSE
CASE - 3 (APPLICABLE FOR GT SYNCHRONISATION ONLY .TIE/GT SELECTOR SWITCH IN GT MODE. SYNCHRONISATION IS DONE FROM GCP)
CB 3-52 OPEN
##
GT-3 CVT SELECTED **
CB 3-89G CLOSED
&
TIE/GCP SELECTOR TIE = FEEDER
SWITCH AT SWYD BAY
CONTROL & PROT PANEL GCP = GT
NOTE:
* SINCE THE SYNCHRONISATION OF GT IS DONE FROM GCP, GT CVT IS NOT CONSIDERED IN THE CVT SELECTION LOGIC FOR BCU.
FOR BCU IN THE SWITCHYARD RUNNING VOLTS BY DEFAULT IS TAKEN AS BUS-1 VOLTS
** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.
## GT-3 CVT WILL BE SELECTED ONLY FOR SYNCHRONISATION OF GT THROUGH THE TIE.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
ES 2-89 AE CLOSE
CB 2-52 LOCAL CLOSING
& CIRCUIT *
ES 2-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
O/G LINE-1
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET
GT-3
86 TRIP RELAY RESET
CB 2-52 CLOSING
A/R LK-OUT TRIP RELAY CIRCUIT**
(86-LO) RESET &
TIE/GCP SELECTOR SWITCH TIE = FEEDER
AT SWYD BAY CONTROL & OR
PROT PANEL GCP = GT
GT3
INTLKS FROM GCP
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-1
EMI-7604PG754-4-028 B 023 023A
DF003
(REMOTE CLOSING POSSIBLE FROM SWITCHYARD ONLY AS LONG AS TIE/GCP SELECTOR SWITCH IS IN TIE MODE)
GT-3
86 TRIP RELAY RESET
VALIDATION OF
ISO 2-89A CLOSE
CHECK-SYNC
CONDITIONS CB 2-52 CLOSE ORDER
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-1(CONTD.)
EMI-7604PG754-4-028 B 023A 024
DF003
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
3-89G OPEN
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.
PROJECT :
MUNDRA SEZ
A) ISOLATOR 3-89B
3-52CB OPEN***
ISO 3-89B CLOSE ORDER
&
B) ISOLATOR 3-89A
3-89AE OPEN
ISO 3-89A INTLK
& PERMISSIVE *
3-52CB OPEN***
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIEDCLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN MUNDRA SEZ
C) ISOLATOR 3-89G
3-89GE OPEN
2-52CB OPEN***
ISO 3-89G CLOSE ORDER
ISO 3-89G CLOSE REQUEST
&
**
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
TO CLOSING CIRCUIT
&
ES 3-89GE INTLK
ISO 3-89G OPEN
PERMISSIVE **
&
GENERATOR
EXCITATION OFF TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN GT-3
ES 3-89 AE CLOSE
ES 3-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB CLOSE **
TO TRIP COIL - 2
OPEN
OPEN/CLOSE PUSH BUTTON
CONTROLS AT GCP
CLOSE
OPEN
OPEN/CLOSE PUSH BUTTON
NOTE: CONTROLS AT GCP
CLOSE
CLIENT : ADANI POWER LTD.
* THESE INTERLOCKS APPLY TO OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
OPERATION OF THE CIRCUIT BREAKERS IN GT BAYS IS NOT ALLOWED FROM THE BAY CONTROL & PROTECTION PANEL, BCU/HMI/SCADA. MUNDRA SEZ
** CLOSE POSITION OF THE CIRCUIT BREAKER IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN. CONTROL & INTERLOCK LOGIC FOR 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN GT-3 (BAY-3)
EMI-7604PG754-4-028 B 028 029
DF003
A) ISOLATOR 4-89A
4-52CB OPEN***
ISO 4-89A CLOSE ORDER
&
B) ISOLATOR 4-89B
4-89BE OPEN
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
C) ISOLATOR 4-89L
4-89LE OPEN
5-52CB OPEN***
ISO 4-89L CLOSE ORDER
ISO 4-89L CLOSE REQUEST
&
**
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-2
TO CLOSING CIRCUIT
&
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
*** LINE U/V PERMISSIVE IS TAKEN THROUGH SOFT FROM LINE DISTANCE PROTECTION RELAY.
CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-2
A) RUNNING VOLTS *
B) INCOMING VOLTS **
CASE - I
CASE - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 5-52 CLOSE
CB 6-52 CLOSE
CASE - 3
CB 5-52 CLOSE
ICT-1 CVT (6-CVT)
SELECTED
ISO 6-89G CLOSE &
NOTE:
* FOR LINE FEEDERS, BUS-2 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.
** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.
ES 4-89 AE CLOSE
CB 4-52 LOCAL CLOSING
& CIRCUIT *
ES 4-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
BBP RELAY
RESET
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. MUNDRA SEZ
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
CB OPEN REQUEST *
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.
PROJECT :
MUNDRA SEZ
A) ISOLATOR 5-89A
5-89AE OPEN
ISO 5-89A INTLK
& PERMISSIVE*
5-52CB OPEN***
A) ISOLATOR 5-89B
&
5-52CB OPEN***
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
PROJECT :
MUNDRA SEZ
NOTE:
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
PROJECT :
MUNDRA SEZ
CONTROL & INTERLOCK LOGIC FOR AREVA REV. SHEET NEXT SH.
OPERATION OF 400kV EARTH SWITCHES AREVA T&D India Limited
IN TIE-2 (BAY-5) EMI-7604PG754-4-028 B 036 037
DF003
A) RUNNING VOLTS *
CASE - I
CASE - 2
CB 6-52 CLOSE
&
BUS-1 CVT SELECTED
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 6-89G OPEN
B) INCOMING VOLTS *
CASE - I
CASE - 2
CB 4-52 CLOSE
BUS-2 CVT SELECTED
&
CB 4-89L OPEN
NOTE:
* AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING /RUNNING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING/RUNNING VOLTS TO BCU.
ES 5-89 AE CLOSE
CB 5-52 LOCAL CLOSING
& CIRCUIT *
ES 5-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
O/G LINE-2
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET
SELECTED RUNNING
O/G LINE-2
VOLTS (REFER SH:037)
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET
ICT-1
86-A TRIP RELAY RESET VALIDATION OF
86-B TRIP RELAY RESET
CHECK-SYNC
CONDITIONS CB 5-52 CLOSE ORDER
&
ISO 5-89A CLOSE IN BCU**
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
CLIENT : ADANI POWER LTD.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. MUNDRA SEZ
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOS INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-2
EMI-7604PG754-4-028 B 038 039
DF003
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
CB OPEN REQUEST
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.
PROJECT :
MUNDRA SEZ
A) ISOLATOR 6-89B
6-52CB OPEN***
ISO 6-89B CLOSE ORDER
&
B) ISOLATOR 6-89A
&
6-52CB OPEN***
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
C) ISOLATOR 6-89G
6-89GE OPEN
5-52CB OPEN***
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
PROJECT :
MUNDRA SEZ
TO CLOSING CIRCUIT
&
ES 6-89GE INTLK
ISO 6-89G OPEN
PERMISSIVE **
&
ICT LV CB OPEN
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
A) RUNNING VOLTS *
B) INCOMING VOLTS **
CASE - I
CB 5-52 CLOSE
CASE - 2
CASE - 3
CB 4-52 CLOSE
NOTE:
* FOR ICT BAYS, BUS-1 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.
** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.
ES 6-89 AE CLOSE
CB 6-52 LOCAL CLOSING
& CIRCUIT *
ES 6-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 6-52 CLOSING
86-B TRIP RELAY RESET & CIRCUIT **
BBP RELAY
RESET
VALIDATION OF
BBP RELAY
RESET
CHECK-SYNC
CB 6-52 CLOSE ORDER
CONDITIONS
ISO 6-89A CLOSE & IN BCU**
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN ICT-1
EMI-7604PG754-4-028 B 044 045
DF003
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
TO TRIP COIL - 2
CB OPEN REQUEST *
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
A) ISOLATOR 7-89A
7-52CB OPEN***
ISO 7-89A CLOSE ORDER
&
B) ISOLATOR 7-89B
7-89BE OPEN
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
C) ISOLATOR 7-89L
7-89LE OPEN
8-52CB OPEN***
ISO 7-89L CLOSE ORDER
ISO 7-89L CLOSE REQUEST
&
**
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-3
TO CLOSING CIRCUIT
&
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
*** LINE U/V PERMISSIVE IS TAKEN THROUGH SOFT FROM LINE DISTANCE PROTECTION RELAY.
CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-3
A) RUNNING VOLTS *
B) INCOMING VOLTS **
CASE - I
CASE - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 8-52 CLOSE
CB 9-52 CLOSE
CASE - 3
CB 8-52 CLOSE
NOTE:
* FOR LINE FEEDERS, BUS-2 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.
** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.
ES 7-89 AE CLOSE
CB 7-52 LOCAL CLOSING
& CIRCUIT *
ES 7-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
BBP RELAY
RESET
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
CLIENT : ADANI POWER LTD.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. MUNDRA SEZ
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOS INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-3
EMI-7604PG754-4-028 B 050 051
DF003
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
TO TRIP COIL - 2
CB OPEN REQUEST *
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
A) ISOLATOR 8-89A
8-89AE OPEN
&
ISO 8-89A INTLK
8-52CB OPEN***
PERMISSIVE *
A) ISOLATOR 8-89B
&
8-52CB OPEN***
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
PROJECT :
MUNDRA SEZ
NOTE:
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
PROJECT :
MUNDRA SEZ
CONTROL & INTERLOCK LOGIC FOR AREVA REV. SHEET NEXT SH.
OPERATION OF 400kV EARTH SWITCHES AREVA T&D India Limited
IN TIE-3 (BAY-8) EMI-7604PG754-4-028 B 053 054
DF003
A) RUNNING VOLTS *
CASE - I
CASE - 2
CB 9-52 CLOSE
B) INCOMING VOLTS *
CASE - I
CASE - 2
CB 7-52 CLOSE
BUS-2 CVT SELECTED
&
CB 7-89L OPEN
NOTE:
* AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING/RUNNING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING/RUNNING VOLTS TO BCU.
ES 8-89 AE CLOSE
CB 8-52 LOCAL CLOSING
& CIRCUIT *
ES 8-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
O/G LINE-3
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET
SELECTED RUNNING
O/G LINE-3
VOLTS (REFER SH:054)
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET
ICT-2
86-A TRIP RELAY RESET VALIDATION OF
86-B TRIP RELAY RESET
CHECK-SYNC
CONDITIONS CB 8-52 CLOSE ORDER
&
ISO 8-89A CLOSE IN BCU**
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-3
EMI-7604PG754-4-028 B 055 056
DF003
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
TO TRIP COIL - 2
CB OPEN REQUEST
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.
PROJECT :
MUNDRA SEZ
A) ISOLATOR 9-89B
9-52CB OPEN***
ISO 9-89B CLOSE ORDER
&
B) ISOLATOR 9-89A
&
9-52CB OPEN***
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
PROJECT :
MUNDRA SEZ
C) ISOLATOR 9-89G
9-89GE OPEN
9-52CB OPEN***
ISO 9-89G CLOSE ORDER
ISO 9-89G CLOSE
&
REQUEST**
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
PROJECT :
MUNDRA SEZ
TO CLOSING CIRCUIT
&
ES 9-89GE INTLK
ISO 9-89G OPEN
PERMISSIVE **
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
A) RUNNING VOLTS *
B) INCOMING VOLTS **
CASE - I
CB 8-52 CLOSE
CASE - 2
CASE - 3
CB 7-52 CLOSE
NOTE:
* FOR ICT BAYS, BUS-1 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.
** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING/ RUNNING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING/ RUNNING VOLTS TO BCU.
ES 9-89 AE CLOSE
CB 9-52 LOCAL CLOSING
& CIRCUIT *
ES 9-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 9-52 CLOSING
86-B TRIP RELAY RESET & CIRCUIT **
BBP RELAY
RESET
VALIDATION OF
BBP RELAY
RESET
CHECK-SYNC
CB 9-52 CLOSE ORDER
CONDITIONS
ISO 9-89A CLOSE & IN BCU**
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN ICT-2
EMI-7604PG754-4-028 B 061 062
DF003
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
TO TRIP COIL - 2
CB OPEN REQUEST *
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.
PROJECT :
MUNDRA SEZ
A) ISOLATOR 10-89A
10-52CB OPEN***
ISO 10-89A CLOSE ORDER
&
B) ISOLATOR 10-89B
10-89BE OPEN
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIEDCLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN MUNDRA SEZ
C) ISOLATOR 10-89L
10-89LE OPEN
11-52CB OPEN***
ISO 10-89L CLOSE ORDER
ISO 10-89L CLOSE REQUEST
&
**
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
PROJECT :
MUNDRA SEZ
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-4
TO CLOSING CIRCUIT
&
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
*** LINE U/V PERMISSIVE IS TAKEN THROUGH SOFT FROM LINE DISTANCE PROTECTION RELAY.
CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-4
A) RUNNING VOLTS *
B) INCOMING VOLTS **
CASE - I
CASE - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 10-52 CLOSE
CB 11-52 CLOSE
NOTE:
* FOR LINE FEEDERS, BUS-2 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.
** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.
THE SYNCHRONISATION OF LINE WITH GT IS NOT CONSIDERED IN THE CVT SELECTION & THE CB CLOSING SCHEME.
PROJECT :
MUNDRA SEZ
ES 10-89 AE CLOSE
CB 10-52 LOCAL CLOSING
& CIRCUIT *
ES 10-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
BBP RELAY
RESET
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. MUNDRA SEZ
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
TO TRIP COIL - 2
CB OPEN REQUEST *
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.
PROJECT :
MUNDRA SEZ
A) ISOLATOR 11-89A
11-89AE OPEN
&
ISO 11-89A INTLK
11-52CB OPEN***
PERMISSIVE *
A) ISOLATOR 11-89B
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
PROJECT :
MUNDRA SEZ
NOTE:
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
PROJECT :
MUNDRA SEZ
CONTROL & INTERLOCK LOGIC FOR AREVA REV. SHEET NEXT SH.
OPERATION OF 400kV EARTH SWITCHES IN AREVA T&D India Limited
TIE-4 (BAY-11) EMI-7604PG754-4-028 B 070 071
DF003
A) RUNNING VOLTS *
CASE-1 (TIE/GT SELECTOR SWITCH IN TIE MODE. SYNCHRONISATION IS DONE FROM SWITCHYARD BCU)
B) INCOMING VOLTS *
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB 10-52 CLOSE
CASE - 3 (APPLICABLE FOR GT SYNCHRONISATION ONLY .TIE/GT SELECTOR SWITCH IN GT MODE. SYNCHRONISATION IS DONE FROM GCP)
CB 12-52 OPEN
##
GT-4 CVT SELECTED **
CB 12-89G CLOSED
&
TIE/GCP SELECTOR TIE = FEEDER
SWITCH AT SWYD BAY
CONTROL & PROT PANEL GCP = GT
NOTE:
* SINCE THE SYNCHRONISATION OF GT IS DONE FROM GCP, GT CVT IS NOT CONSIDERED IN THE CVT SELECTION LOGIC FOR BCU.
FOR BCU IN THE SWITCHYARD RUNNING VOLTS BY DEFAULT IS TAKEN AS BUS-1 VOLTS
** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.
## GT-3 CVT WILL BE SELECTED ONLY FOR SYNCHRONISATION OF GT THROUGH THE TIE.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
ES 11-89 AE CLOSE
CB 11-52 LOCAL CLOSING
& CIRCUIT *
ES 11-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
O/G LINE-4
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET
GT-4
86 TRIP RELAY RESET
CB 11-52 CLOSING
A/R LK-OUT TRIP RELAY CIRCUIT**
(86-LO) RESET &
TIE/GCP SELECTOR SWITCH TIE = FEEDER
AT SWYD BAY CONTROL & OR
PROT PANEL GCP = GT
GT4
INTLKS FROM GCP
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-4
EMI-7604PG754-4-028 B 072 072A
DF003
(REMOTE CLOSING POSSIBLE FROM SWITCHYARD ONLY AS LONG AS TIE/GCP SELECTOR SWITCH IS IN TIE MODE)
GT-4
86 TRIP RELAY RESET
VALIDATION OF
ISO 11-89A CLOSE
CHECK-SYNC
CONDITIONS CB 11-52 CLOSE ORDER
NOTE:
* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-4
EMI-7604PG754-4-028 B 072A 073
DF003
CB CLOSE ***
TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
CB CLOSE ***
12-89G OPEN
NOTE:
* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.
** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.
PROJECT :
MUNDRA SEZ
A) ISOLATOR 12-89B
12-52CB OPEN***
ISO 12-89B CLOSE ORDER
&
B) ISOLATOR 12-89A
12-89AE OPEN
ISO 12-89A INTLK
PERMISSIVE *
&
12-52CB OPEN***
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
C) ISOLATOR 12-89G
12-89GE OPEN
11-52CB OPEN***
ISO 12-89G CLOSE ORDER
ISO 12-89G CLOSE
&
REQUEST**
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
PROJECT :
MUNDRA SEZ
ES 12-89GE INTLK
PERMISSIVE **
ISO 12-89G OPEN
&
GENERATOR
TO OPEN CIRCUIT
EXCITATION OFF
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:
* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
PROJECT :
MUNDRA SEZ
CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN GT-4
ES 12-89 AE CLOSE
ES 12-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CB CLOSE **
TO TRIP COIL - 2
OPEN
OPEN/CLOSE PUSH BUTTON
CONTROLS AT GCP
CLOSE
OPEN
OPEN/CLOSE PUSH BUTTON
CONTROLS AT GCP
CLOSE
PROJECT :
* OPERATION OF THE CIRCUIT BREAKERS IN GT BAYS IS NOT ALLOWED FROM THE BAY CONTROL & PROTECTION PANEL, BCU/HMI/SCADA. MUNDRA SEZ
** CLOSE POSITION OF THE CIRCUIT BREAKER IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN. CONTROL & INTERLOCK LOGIC FOR 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN GT-4 (BAY-12)
EMI-7604PG754-4-028 B 077 078
DF003
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writin
BLANK SHEET
PROJECT :
MUNDRA SEZ
INTERLOCK LOGIC FOR OPERATION OF BUS-1 CVT ISOLATOR & EARTH SWITCH
(MANAGED BY TIE-1 BCU)
#
B) BUS-1 CVT EARTH SWITCH
##
BUS-1 CVT E/S
BUS-1 CVT ISO OPEN
INTLK PERMISSIVE
This drawing and design is the property of AREVA T&D and must not be
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
# FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
## THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
INTERLOCK LOGIC FOR REMOTE OPERATION AREVA REV. SHEET NEXT SH.
OF 400kV BUS-1 CVT ISOLATOR & EARTH AREVA T&D India Limited
SWITCH EMI-7604PG754-4-028 A 079 080
DF003
INTERLOCK LOGIC FOR OPERATION OF BUS-2 CVT ISOLATOR & EARTH SWITCH
(MANAGED BY TIE-1 BCU)
#
B) BUS-2 CVT EARTH SWITCH
##
BUS-2 CVT E/S
BUS-2 CVT ISO OPEN
INTLK PERMISSIVE
This drawing and design is the property of AREVA T&D and must not be
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:
* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.
# FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.
## THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls
PROJECT :
MUNDRA SEZ
INTERLOCK LOGIC FOR REMOTE OPERATION AREVA REV. SHEET NEXT SH.
OF 400kV BUS-2 CVT ISOLATOR & EARTH AREVA T&D India Limited
SWITCH EMI-7604PG754-4-028 A 080 081
DF003
IMPLEMENATION OF SYNCHROCHECK FUNCTION IN BCU (TYPICAL FOR ALL BAYS EXCEPT GT BAYS)
YES
DEAD INCOMING VOLTS TIMER FOR
& DEAD RUNNING VOLTS CONFIRMATION
CONDITIONS SATISFIED? (SETTABLE) ***
TO CLOSING
& CIRCUIT
SOFTWARE INTERLOCKS
CLOSE REQUEST FROM
BUILT IN RESPECTIVE BCU
BCU/HMI/SCADA
VERIFIED SUCCESFULLY **
NOTE :
* VOLTAGE SELECTION FOR INCOMING AND RUNNING VOLTS SHALL BE AS PER THE SELECTION LOGIC INDICATED IN THE RESPECTIVE BAY INTERLOCK LOGICS.
** SOFTWARE INTERLOCKS BUILT IN THE BCU ARE VERIFIED BEFORE CHECKING THE SYNCHRONISATION CONDITIONS. FOR DETAILED INTERLOCKS REFER THE RESPECTIVE BAY INTERLOCK LOGIC DIAGRAMS
*** WHEN BOTH VOLTAGES ARE BELOW THE SET THRESHOLD FOR DEAD VOLTS, A TIMER IS STARTED BEFORE GIVING THE CLOSE SIGNAL TO THE CB. THIS TIMER IS CONFIGURABLE IN THE RANGE 0.2 TO 10 Sec.
1 COMMAND TO THE BREAKER WILL BE SUCCESFUL ONLY IF EXTERNAL HARDWIRED INTERLOCKS IN THE CB CLOSING CIRCUIT ARE SATISFIED.
CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
IMPLEMENTATION OF SYNCHROCHECK IN
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
BCU
EMI-7604PG754-4-028 B 081 082
DF003
IMPLEMENATION OF SYNCHROCHECK FUNCTION IN BCU (TYPICAL FOR ALL BAYS EXCEPT GT BAYS)
YES
DEAD INCOMING VOLTS TIMER FOR
& LIVE RUNNING VOLTS CONFIRMATION
CONDITIONS SATISFIED? (SETTABLE) ***
TO CLOSING
& CIRCUIT
SOFTWARE INTERLOCKS
CLOSE REQUEST FROM
BUILT IN RESPECTIVE BCU
BCU/HMI/SCADA
VERIFIED SUCCESFULLY **
NOTE :
* VOLTAGE SELECTION FOR INCOMING AND RUNNING VOLTS SHALL BE AS PER THE SELECTION LOGIC INDICATED IN THE RESPECTIVE BAY INTERLOCK LOGICS.
** SOFTWARE INTERLOCKS BUILT IN THE BCU ARE VERIFIED BEFORE CHECKING THE SYNCHRONISATION CONDITIONS. FOR DETAILED INTERLOCKS REFER THE RESPECTIVE BAY INTERLOCK LOGIC DIAGRAMS
*** WHEN BOTH VOLTAGES ARE BELOW THE SET THRESHOLD FOR DEAD & LIVE VOLTS, A TIMER IS STARTED BEFORE GIVING THE CLOSE SIGNAL TO THE CB. THIS TIMER IS CONFIGURABLE IN THE RANGE 0.2 TO 10 Sec.
1 COMMAND TO THE BREAKER WILL BE SUCCESFUL ONLY IF EXTERNAL HARDWIRED INTERLOCKS IN THE CB CLOSING CIRCUIT ARE SATISFIED.
CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
IMPLEMENTATION OF SYNCHROCHECK IN
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
BCU
EMI-7604PG754-4-028 B 082 083
DF003
IMPLEMENATION OF SYNCHROCHECK FUNCTION IN BCU (TYPICAL FOR ALL BAYS EXCEPT GT BAYS)
YES
LIVE INCOMING VOLTS & TIMER FOR
DEAD RUNNING VOLTS CONFIRMATION
CONDITIONS SATISFIED? (SETTABLE) ***
TO CLOSING
& CIRCUIT
SOFTWARE INTERLOCKS
CLOSE REQUEST FROM
BUILT IN RESPECTIVE BCU
BCU/HMI/SCADA
VERIFIED SUCCESFULLY **
NOTE :
* VOLTAGE SELECTION FOR INCOMING AND RUNNING VOLTS SHALL BE AS PER THE SELECTION LOGIC INDICATED IN THE RESPECTIVE BAY INTERLOCK LOGICS.
** SOFTWARE INTERLOCKS BUILT IN THE BCU ARE VERIFIED BEFORE CHECKING THE SYNCHRONISATION CONDITIONS. FOR DETAILED INTERLOCKS REFER THE RESPECTIVE BAY INTERLOCK LOGIC DIAGRAMS
*** WHEN BOTH VOLTAGES ARE BELOW THE SET THRESHOLD FOR DEAD & LIVE VOLTS, A TIMER IS STARTED BEFORE GIVING THE CLOSE SIGNAL TO THE CB. THIS TIMER IS CONFIGURABLE IN THE RANGE 0.2 TO 10 Sec.
1 COMMAND TO THE BREAKER WILL BE SUCCESFUL ONLY IF EXTERNAL HARDWIRED INTERLOCKS IN THE CB CLOSING CIRCUIT ARE SATISFIED.
CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
IMPLEMENTATION OF SYNCHROCHECK IN
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
BCU
EMI-7604PG754-4-028 B 083 084
DF003
IMPLEMENATION OF SYNCHROCHECK FUNCTION IN BCU (TYPICAL FOR ALL BAYS EXCEPT GT BAYS)
YES
LIVE INCOMING VOLTS & TIMER FOR
LIVE RUNNING VOLTS CONFIRMATION
CONDITIONS SATISFIED? (SETTABLE) ***
TO CLOSING
& CIRCUIT
SOFTWARE INTERLOCKS
CLOSE REQUEST FROM
BUILT IN RESPECTIVE BCU
BCU/HMI/SCADA
VERIFIED SUCCESFULLY **
NOTE :
* VOLTAGE SELECTION FOR INCOMING AND RUNNING VOLTS SHALL BE AS PER THE SELECTION LOGIC INDICATED IN THE RESPECTIVE BAY INTERLOCK LOGICS.
** SOFTWARE INTERLOCKS BUILT IN THE BCU ARE VERIFIED BEFORE CHECKING THE SYNCHRONISATION CONDITIONS. FOR DETAILED INTERLOCKS REFER THE RESPECTIVE BAY INTERLOCK LOGIC DIAGRAMS
*** WHEN BOTH VOLTAGES ARE BELOW THE SET THRESHOLD FOR DEAD & LIVE VOLTS, A TIMER IS STARTED BEFORE GIVING THE CLOSE SIGNAL TO THE CB. THIS TIMER IS CONFIGURABLE IN THE RANGE 0.2 TO 10 Sec.
1 COMMAND TO THE BREAKER WILL BE SUCCESFUL ONLY IF EXTERNAL HARDWIRED INTERLOCKS IN THE CB CLOSING CIRCUIT ARE SATISFIED.
2 FOR LIVE CONDITIONS OF BOTH THE INCOMING & RUNNING VOLTS, THE FOLLOWING CONDITIONS(CONFIGURED THROUGH SOFTWARE) ARE CHECKED:
CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
IMPLEMENTATION OF SYNCHROCHECK IN
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
BCU
EMI-7604PG754-4-028 B 084 085
DF003
IMPLEMENATION OF AUTO RECLOSE FUNCTION IN BCU (TYPICAL FOR ALL LINE BAYS)
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
IMPLEMENTATION OF
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
AUTORECLOSE FUNCTION IN BCU
EMI-7604PG754-4-028 B 085 086
DF003
IMPLEMENATION OF AUTO RECLOSE FUNCTION IN BCU (TYPICAL FOR ALL TIE BAYS)
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing
CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ
IMPLEMENTATION OF
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
AUTORECLOSE FUNCTION IN BCU
EMI-7604PG754-4-028 B 086 /