You are on page 1of 92

DF001

This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

Name Name Name


Date Date Date
Name Name Name
Date Date Date
Name Name Name
Date Date Date
Name DINESH Name MHB Name RJR
B UPDATED BASED UPON CUSTOMER'S COMMENTS FA
Date 06/08/2008 Date 06/08/2008 Date 06/08/2008
Name RSD Name MHB Name RJR
A FIRST ISSUE FC
Date 06/12/2006 Date 06/12/2006 Date 13/6/2006

SIGN.
SIGN.

SIGN.
REV. DESCRIPTION DRAWN CHECKED APPROVED STATUS

CLIENT :
ADANI POWER LIMITED
2 x 330MW THERMAL POWER PLANT
MUNDRA SEZ, TUNDA, SIRACHA VILLAGE, KUTCHH DIST. GUJARAT

CONTRACT No.: APL / 130001 / VJ / 967 / 07 DATED 21.11.2007


PROJECT :
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT MUNDRA SEZ

CONSULTANT FICHTNER
CONSULTING ENGINEERS (INDIA) PRIVATE LIMITED,

CHENNAI
TITLE :
400 KV CONTROL & INTERLOCK LOGIC DIAGRAM
File: PG725000-

AREVA T&D India Limited DRAWING NO. REV. SHEET TOTAL SHEET

A-7, SECTOR-65
EMI-7604PG754-4-028 B 001 92
NOIDA - 201301
DF002

REVISION DESCRIPTION REVISION DESCRIPTION


SHEET SHEET
A B C D E F G H I A B C D E F G H I
001 X X FRONT SHEET 042 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN ICT-1

002 X X INDEX 043 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN ICT-1

003 X CONTROL LOGIC FOR LOCAL OPERATION OF ISOLATORS FROM EQP M.BOX 044 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN ICT-1

004 X CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM BCU 045 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN ICT-1

005 X CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM HMI 046 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-3

006 X CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM SCADA 047 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-3 (CONTD.)

007 X CONTROL LOGIC FOR LOCAL OPERATION OF CKT. BKRS FROM EQP M. BOX 048 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-3
CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM BCU/BAY
008 X 049 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-3
CONTROL & PROTECTION PANEL *
008A X PROTECTION TRIP LOGIC FOR LINE PROTECTIONS(TYPICAL) 050 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-3

008B X PROTECTION TRIP LOGIC FOR TIE PROTECTIONS(TYPICAL) 051 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-3

008C X PROTECTION TRIP LOGIC FOR GT PROTECTIONS(TYPICAL) 052 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-3

008D X PROTECTION TRIP LOGIC FOR ICT PROTECTIONS(TYPICAL) 053 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OFEARTH SWITCHES IN TIE-3
CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM BCU/ BAY
009 X X 054 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-3
CONTROL & PROTECTION PANEL *
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

010 X CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM HMI * 055 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-3

011 X X CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM HMI * 056 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-3
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE
012 X 057 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN ICT-2
1
CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM SCADA
013 X X 058 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN ICT-2 (CONTD.)
(LDC) *
CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM SCADA
014 X X 059 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN ICT-2
(LDC) *
015 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-1 060 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN ICT-2

016 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-1 (CONTD) 061 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN ICT-2
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE
017 X X 062 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G ICT-2
1
018 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-1 063 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-4

019 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-1 064 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-4 (CONTD.)

020 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-1 065 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-4

021 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN TIE-1 066 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-4

022 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-1 067 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-4

023 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-1 068 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-4

023A X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-1 (CONTD.) 069 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-4

024 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-1 070 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OFEARTH SWITCHES IN TIE-4

025 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN GT-3 071 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-4

026 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN GT-3 (CONTD.) 072 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-4

027 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN GT-3 073 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-4

CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN
028 X X 074 X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-4
GT-3
029 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-2 075 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN GT-4

030 X X INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-2 (CONTD.) 076 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN GT-4 (CONTD.)
CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE
031 X X 077 X X CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN GT-4
2
032 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-2 078 X X CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN GT-4

033 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-2 079 X X INTERLOCK LOGIC FOR OPERATION OF BUS-1 CVT ISOLATOR & EARTH SWITCH

034 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-2 080 X X INTERLOCK LOGIC FOR OPERATION OF BUS-2 CVT ISOLATOR & EARTH SWITCH

035 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-2 081 X IMPLEMENTATION OF SYNCHROCHECK IN BCU

036 X X CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN TIE-2 082 X IMPLEMENTATION OF SYNCHROCHECK IN BCU

037 X X CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-2 083 X IMPLEMENTATION OF SYNCHROCHECK IN BCU

038 X X INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-2 084 X IMPLEMENTATION OF SYNCHROCHECK IN BCU

039 X X INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-2 085 X IMPLEMENTATION OF AUTORECLOSE FUNCTION IN BCU

040 X X INTERLOCK LOGIC FOR OPERATION OF400kV ISOLATORS IN ICT-1 086 X IMPLEMENTATION OF AUTORECLOSE FUNCTION IN BCU

041 X X INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN ICT-1 (CONTD.)


CLIENT : ADANI POWER LTD.

PROJECT : 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT MUNDRA SEZ
File: PG725000-002.xls

AREVA REV. SHEET NEXT SH.


AREVA T&D India Limited
INDEX
EMI-7604PG754-4-028 B 002 003
DF003

CONTROL LOGIC FOR LOCAL OPERATION OF ISOLATORS FROM EQUIPMENT MARSHALLING BOX*

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
INTLK PERMISSIVE FROM
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
RESPECTIVE BCU **
& TO OPEN CIRCUIT
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

OPEN/CLOSE PUSH BUTTON OPEN


CONTROLS AT EQP
MARSHALLING BOX CLOSE

& TO CLOSING CIRCUIT


INTLK PERMISSIVE FROM
RESPECTIVE BCU **

NOTE :

* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY BCU / HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT EQP MARSHALLING BOX IS IN LOCAL MODE.

** INTERLOCKS REQUIRED FOR CLOSING/OPENING OF ISOLATORS ARE VERIFIED IN THE RESPECTIVE BAY CONTROL UNIT AND A OUTPUT IS GENERATED FROM THE BCU WHEN THE INTERLOCKS ARE SATISIFIED.
THE GENERATED OUTPUT IS HARDWIRED IN THE CONTROL CIRCUIT OF THE ISOLATOR. OPEN/CLOSE COMMANDS TO THE ISOLATOR ARE NOT EXECUTED UNLESS THE INTERLOCKS ARE SATISFIED.
OPERATION OF THE ISOLATORS EITHER FROM LOCAL/REMOTE WILL BE SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. INTERLOCKS CAN BE BYPASSED UNDER EMERGENCY CONDITIONS, BY AUTHORISED PERSONNEL ONLY.

*** FOR DETAILED INTERLOCKS REFER THE INTERLOCKS FOR THE RESPECTIVE DETAILED INTERLOCKS.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR LOCAL OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS
EMI-7604PG754-4-028 A 003 004
DF003

CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM BCU*

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
INTLK PERMISSIVE FROM
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
RESPECTIVE BCU **
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

LOCAL = BCU TO OPEN CIRCUIT


BAY LOCAL/REMOTE &
PUSH BUTTON ON BCU
REMOTE = HMI / SCADA

OPEN/CLOSE OPEN
PUSH BUTTON CONTROL
FROM BCU CLOSE

INTLK PERMISSIVE FROM


RESPECTIVE BCU **

TO CLOSING CIRCUIT
&

NOTE :

* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT BCU IS IN LOCAL MODE.

** INTERLOCKS REQUIRED FOR CLOSING/OPENING OF ISOLATORS ARE VERIFIED IN THE RESPECTIVE BAY CONTROL UNIT AND A OUTPUT IS GENERATED FROM THE BCU WHEN THE INTERLOCKS ARE SATISIFIED.
THE GENERATED OUTPUT IS HARDWIRED IN THE CONTROL CIRCUIT OF THE ISOLATOR. OPEN/CLOSE COMMANDS TO THE ISOLATOR ARE NOT EXECUTED UNLESS THE INTERLOCKS ARE SATISFIED.
OPERATION OF THE ISOLATORS EITHER FROM LOCAL/REMOTE WILL BE SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. INTERLOCKS CAN BE BYPASSED UNDER EMERGENCY CONDITIONS, BY AUTHORISED PERSONNEL ONLY.

*** FOR DETAILED INTERLOCKS REFER THE INTERLOCKS FOR THE RESPECTIVE DETAILED INTERLOCKS.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR REMOTE OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS FROM BCU
EMI-7604PG754-4-028 A 004 005
DF003

CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM HMI*

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
INTLK PERMISSIVE FROM
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
RESPECTIVE BCU **
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

BAY LOCAL/REMOTE LOCAL = BCU TO OPEN CIRCUIT


PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA
&

SUBTATION LOCAL = HMI


LOCAL/REMOTE SELECTION
FROM HMI REMOTE = SCADA

OPEN
OPEN/CLOSE CONTROL
FROM HMI
CLOSE
INTLK PERMISSIVE FROM
RESPECTIVE BCU **

TO CLOSING CIRCUIT
&

NOTE :

* IN THIS MODE, CONTROL FROM HIGHER SCADA LEVEL ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTION AT HMI IS IN LOCAL MODE.

** INTERLOCKS REQUIRED FOR CLOSING/OPENING OF ISOLATORS ARE VERIFIED IN THE RESPECTIVE BAY CONTROL UNIT AND A OUTPUT IS GENERATED FROM THE BCU WHEN THE INTERLOCKS ARE SATISIFIED.
THE GENERATED OUTPUT IS HARDWIRED IN THE CONTROL CIRCUIT OF THE ISOLATOR. OPEN/CLOSE COMMANDS TO THE ISOLATOR ARE NOT EXECUTED UNLESS THE INTERLOCKS ARE SATISFIED.
OPERATION OF THE ISOLATORS EITHER FROM LOCAL/REMOTE WILL BE SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. INTERLOCKS CAN BE BYPASSED UNDER EMERGENCY CONDITIONS, BY AUTHORISED PERSONNEL ONLY.

*** FOR DETAILED INTERLOCKS REFER THE INTERLOCKS FOR THE RESPECTIVE DETAILED INTERLOCKS.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR REMOTE OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS FROM HMI
EMI-7604PG754-4-028 A 005 006
DF003

CONTROL LOGIC FOR REMOTE OPERATION OF ISOLATORS FROM SCADA(LDC)

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
INTLK PERMISSIVE FROM
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
RESPECTIVE BCU **
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

BAY LOCAL/REMOTE LOCAL = BCU TO OPEN CIRCUIT


PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA
&

SUBTATION LOCAL = HMI


LOCAL/REMOTE SELECTION
FROM HMI REMOTE = SCADA

OPEN
OPEN/CLOSE CONTROL
FROM HMI
CLOSE
INTLK PERMISSIVE FROM
RESPECTIVE BCU **

TO CLOSING CIRCUIT
&

** INTERLOCKS REQUIRED FOR CLOSING/OPENING OF ISOLATORS ARE VERIFIED IN THE RESPECTIVE BAY CONTROL UNIT AND A OUTPUT IS GENERATED FROM THE BCU WHEN THE INTERLOCKS ARE SATISIFIED.
THE GENERATED OUTPUT IS HARDWIRED IN THE CONTROL CIRCUIT OF THE ISOLATOR. OPEN/CLOSE COMMANDS TO THE ISOLATOR ARE NOT EXECUTED UNLESS THE INTERLOCKS ARE SATISFIED.
OPERATION OF THE ISOLATORS EITHER FROM LOCAL/REMOTE WILL BE SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. INTERLOCKS CAN BE BYPASSED UNDER EMERGENCY CONDITIONS, BY AUTHORISED PERSONNEL ONLY.

*** FOR DETAILED INTERLOCKS REFER THE INTERLOCKS FOR THE RESPECTIVE DETAILED INTERLOCKS.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR REMOTE OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS FROM SCADA
EMI-7604PG754-4-028 A 006 007
DF003

CONTROL LOGIC FOR LOCAL OPERATION OF CIRCUIT BREAKERS FROM EQUIPMENT MARSHALLING BOX*

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

OPEN/CLOSE PUSH BUTTON OPEN


CONTROLS AT EQP
MARSHALLING BOX CLOSE

& TO CLOSING CIRCUIT


HARDWIRED
INTERLOCKS AT BMK LEVEL **

NOTE :

* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY BCU / HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT EQP MARSHALLING BOX IS IN LOCAL MODE.

** THESE INTERLOCKS ARE HARDWIRED AT BMK LEVEL AND OPERATION FROM EQP. MARSHALLING BOX IS POSSIBLE ONLY WHEN THESE INTERLOCKS ARE SATISFIED.
FOR DETAILS REFER THE RESPECTIVE BREAKER INTERLOCK LOGICS

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR LOCAL OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV CIRCUIT BREAKERS
EMI-7604PG754-4-028 A 007 008
DF003

CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM BCU/BAY CONTROL & PROTECTION PANEL *

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
TO TRIP COIL - 1
OR
&
TO TRIP COIL - 2
BAY LOCAL/REMOTE LOCAL = BCU
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA

&
OPEN/CLOSE OPEN
PUSH BUTTON CONTROL
FROM BCU CLOSE

&

CNTL SWTCH FROM C&R OPEN


PANEL FOR EMERGENCY
CONTROL ** CLOSE

NOTE :

* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT BCU IS IN LOCAL MODE.

** EMERGENCY TRIPPING CAN BE GIVEN THROUGH THE TNC SWITCH PROVIDED ON THE BAY PROTECTION & CONTROL PANEL.
CONTROLS GIVEN THROUGH TNC SWITCH ARE ROUTED INDEPENDENT OF THE BCU AND HENCE ARE INDEPENDENT OF THE LOCAL/REMOTE SELECTION AT BCU/HMI.

*** PERMISSIVE FOR MAINTENANCE CLOSING IS GENERATED FROM BCU, WHEN BOTH THE ISOLATORS ON EITHER SIDES OF THE CB ARE OPEN.
THIS OUTPUT CONTACT FROM BCU IS WIRED INTO THE TNC CLOSING CIRCUIT.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR REMOTE OPENING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS FROM AREVA T&D India Limited
BCU EMI-7604PG754-4-028 A 008 008A
DF003

PROTECTION TRIP LOGIC FOR LINE PROTECTIONS(TYPICAL)


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

PROTECTION TRIP LOGIC FOR


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
LINE PROTECTION
EMI-7604PG754-4-028 B 008A 009
DF003

PROTECTION TRIP LOGIC FOR TIE PROTECTIONS(TYPICAL)


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

PROTECTION TRIP LOGIC FOR


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
TIE PROTECTION
EMI-7604PG754-4-028 B 008B 008C
DF003

PROTECTION TRIP LOGIC FOR GT PROTECTIONS(TYPICAL)


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

NOTE :

* ONLY HV O/C & E/F PROTECTION, LBB & BUSBAR PROTECTION ARE LOCATED IN THE SWITCHYARD RELAY PANEL. ALL THE OTHER PROTECTIONS ARE NOT IN PRESENT SCOPE.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

PROTECTION TRIP LOGIC FOR


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
GT PROTECTION
EMI-7604PG754-4-028 B 008C 008D
DF003

PROTECTION TRIP LOGIC FOR ICT PROTECTIONS(TYPICAL)


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

NOTE :

* 220kV PROTECTIONS ARE NOT IN PRESENT SCOPE.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

PROTECTION TRIP LOGIC FOR


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ICT PROTECTION
EMI-7604PG754-4-028 B 008D 009
DF003

CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM BCU/ BAY CONTROL & PROTECTION PANEL *

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
SELECTED INCOMING SELECTED RUNNING
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
VOLTS VOLTS

&
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

BAY LOCAL/REMOTE LOCAL = BCU


PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA

VALIDATION OF
CHECK-SYNC
OPEN/CLOSE OPEN
& CONDITIONS
PUSH BUTTON CONTROL IN BCU**
FROM BCU CLOSE

OR

TO CLOSING CIRCUIT
INTLKS IMPLEMENTED THROUGH SOFT LOGIC
IN RESPECTIVE BCU ***

CNTL SWTCH FROM C&R OPEN


PANEL FOR EMERGENCY
##
CONTROL CLOSE
PERMISSIVE FOR TNC MAINTENANCE CLOSING FROM BCU
(APPLIES TO ALL BAYS EXCEPT GT & GT TIE BAYS)

INTLKS IMPLEMENTED THROUGH HARDWIRING


&
ISO 89-A OPEN
IN BAY CNTL & PROT PANEL***

##
& PERMISSIVE
PERMISSIVE FOR MAINTENANCE CLOSING

ISO 89-B OPEN

NOTE :

* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT BCU IS IN LOCAL MODE.

** CHECK SYNCHRONISATION CONDITIONS ARE VALIDATED IN THE RESPECTIVE BAY CONTROL UNIT, BASED UPON THE SELECTED INCOMING & RUNNING VOLTAGES.

*** FOR DETAILED INTERLOCKING LOGICS REFER THE INTERLOCKS OF THE RESPECTIVE CIRCUIT BREAKER.

## PERMISSIVE FOR MAINTENANCE CLOSING IS GENERATED FROM BCU, WHEN BOTH THE ISOLATORS ON EITHER SIDES OF THE CB ARE OPEN.
THIS OUTPUT CONTACT FROM BCU IS WIRED INTO THE TNC CLOSING CIRCUIT.

1 CLOSE COMMAND GIVEN BY THE OPERATOR FROM BCU WILL BE EXECUTED ONLY IF THE CHECK-SYNC CONDITIONS ARE SATISFIED.

2 CLOSE COMMAND FROM TNC SWITCH IS MEANT FOR CLOSING WITHOUT ANY SYNCHRONISATION & HENCE TO BE USED FOR MAINTENANCE/TESTING CONDITIONS.

CLIENT
3 INCOMING & RUNNING VOLTS ARE SELECTED BASED UPON THE ISOLATOR & CB POSITIONS IN THE RESPECTIVE DIA. ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
4 FOR GT-3 & GT-4 (BAYS-3, 12) REMOTE OPERATION IS NOT PROVIDED FROM SWITCHYARD. MUNDRA SEZ

5 FOR TIE-1 & TIE-4 (BAYS-2, 11) REMOTE OPERATION IS POSSIBLE FROM BCU/HMI/SCADA ONLY AS LONG AS THE CONTROL LOGIC FOR REMOTE CLOSING OF AREVA REV. SHEET NEXT SH.
TIE/GT SELECTOR SWITCH IS IN TIE MODE. 400kV LINE-TIE-ICT CIRCUIT BREAKERS AREVA T&D India Limited
FROM BCU EMI-7604PG754-4-028 B 009 010
DF003

CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM HMI *

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

BAY LOCAL/REMOTE LOCAL = BCU


PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA
&

&
SUBTATION LOCAL = HMI TO TRIP COIL - 1
LOCAL/REMOTE SELECTION OR
FROM HMI REMOTE = SCADA
TRIP COIL - 2

OPEN
OPEN/CLOSE CONTROL &
FROM HMI
CLOSE

CNTL SWTCH FROM C&R OPEN


PANEL FOR EMERGENCY
CONTROL ** CLOSE

NOTE :

* IN THIS MODE, CONTROL FROM HIGHER LEVELS NAMELY HMI/ SCADA ARE DEFEATED AS LONG AS THE LOCAL/REMOTE SELECTOR SWITCH AT BCU IS IN LOCAL MODE.

** EMERGENCY TRIPPING CAN BE GIVEN THROUGH THE TNC SWITCH PROVIDED ON THE BAY PROTECTION & CONTROL PANEL.
CONTROLS GIVEN THROUGH TNC SWITCH ARE ROUTED INDEPENDENT OF THE BCU.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR REMOTE OPENING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS FROM AREVA T&D India Limited
HMI EMI-7604PG754-4-028 A 010 011
DF003

CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM HMI *

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
SELECTED INCOMING SELECTED RUNNING
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
VOLTS VOLTS

&
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

BAY LOCAL/REMOTE LOCAL = BCU


PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA

VALIDATION OF
CHECK-SYNC
SUBTATION LOCAL = HMI & CONDITIONS
LOCAL/REMOTE SELECTION
FROM HMI REMOTE = SCADA
IN BCU**

OR
OPEN TO CLOSING CIRCUIT
OPEN/CLOSE
CONTROL FROM HMI
CLOSE

INTLKS IMPLEMENTED THROUGH SOFT LOGIC


IN RESPECTIVE BCU ***

INTLKS IMPLEMENTED THROUGH HARDWIRING ##


IN BAY CNTL & PROT PANEL*** PERMISSIVE FOR TNC MAINTENANCE CLOSING FROM BCU
(APPLIES TO ALL BAYS EXCEPT GT & GT TIE BAYS)
CNTL SWTCH FROM C&R OPEN
&
PANEL FOR EMERGENCY ISO 89-A OPEN
CONTROL CLOSE
##
& PERMISSIVE
PERMISSIVE FOR MAINTENANCE CLOSING

ISO 89-B OPEN

NOTE :

* IN THIS MODE, CONTROL FROM SCADA ARE DEFEATED AS LONG AS THE SUBSTATION LOCAL/REMOTE SELECTION IS IN LOCAL MODE.

** CHECK SYNCHRONISATION CONDITIONS ARE VALIDATED IN THE RESPECTIVE BAY CONTROL UNIT, BASED UPON THE SELECTED INCOMING & RUNNING VOLTAGES.

*** FOR DETAILED INTERLOCKING LOGICS REFER THE INTERLOCKS OF THE RESPECTIVE CIRCUIT BREAKER.

## PERMISSIVE FOR MAINTENANCE CLOSING IS GENERATED FROM BCU, WHEN BOTH THE ISOLATORS ON EITHER SIDES OF THE CB ARE OPEN.
THIS OUTPUT CONTACT FROM BCU IS WIRED INTO THE TNC CLOSING CIRCUIT.

1 CLOSE COMMAND GIVEN BY THE OPERATOR FROM HMI WILL BE EXECUTED ONLY IF THE CHECK-SYNC CONDITIONS ARE SATISFIED.

2 CLOSE COMMAND FROM TNC SWITCH IS MEANT FOR CLOSING WITHOUT ANY SYNCHRONISATION & HENCE TO BE USED FOR MAINTENANCE/TESTING CONDITIONS.
CLIENT
ADANI POWER LTD.
:
3 INCOMING & RUNNING VOLTS ARE SELECTED BASED UPON THE ISOLATOR & CB POSITIONS IN THE RESPECTIVE DIA. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR REMOTE CLOSING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS AREVA T&D India Limited
FROM HMI EMI-7604PG754-4-028 B 011 012
DF003

CONTROL LOGIC FOR REMOTE OPENING OF CIRCUIT BREAKERS FROM SCADA (LDC) *

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

BAY LOCAL/REMOTE LOCAL = BCU


PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA &

&
SUBTATION LOCAL = HMI TO TRIP COIL - 1
LOCAL/REMOTE SELECTION
FROM HMI REMOTE = SCADA OR

TRIP COIL - 2

OPEN
&
OPEN/CLOSE CONTROL
FROM SCADA
CLOSE

CNTL SWTCH FROM C&R OPEN


PANEL FOR EMERGENCY
CONTROL ** CLOSE

NOTE :

** EMERGENCY TRIPPING CAN BE GIVEN THROUGH THE TNC SWITCH PROVIDED ON THE BAY PROTECTION & CONTROL PANEL.
CONTROLS GIVEN THROUGH TNC SWITCH ARE ROUTED INDEPENDENT OF THE BCU.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR REMOTE OPENING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS FROM AREVA T&D India Limited
SCADA EMI-7604PG754-4-028 A 012 013
DF003

CONTROL LOGIC FOR REMOTE CLOSING OF CIRCUIT BREAKERS FROM SCADA (LDC) *

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
SELECTED INCOMING SELECTED RUNNING
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
VOLTS VOLTS

&
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

BAY LOCAL/REMOTE LOCAL = BCU


PUSH BUTTON ON
BAY CONTROL UNIT REMOTE = HMI / SCADA

VALIDATION OF
CHECK-SYNC
SUBTATION LOCAL = HMI & CONDITIONS
LOCAL/REMOTE SELECTION
FROM HMI REMOTE = SCADA
IN BCU**
TO CLOSING CIRCUIT

OR
OPEN
OPEN/CLOSE
CONTROL FROM HMI
CLOSE

INTLKS IMPLEMENTED THROUGH SOFT LOGIC


IN RESPECTIVE BCU ***

##
INTLKS IMPLEMENTED THROUGH HARDWIRING PERMISSIVE FOR TNC MAINTENANCE CLOSING FROM BCU
IN BAY CNTL & PROT PANEL*** (APPLIES TO ALL BAYS EXCEPT GT & GT TIE BAYS)

& ISO 89-A OPEN


CNTL SWTCH FROM C&R OPEN
PANEL FOR EMERGENCY
CONTROL CLOSE & PERMISSIVE
##
PERMISSIVE FOR MAINTENANCE CLOSING ISO 89-B OPEN

NOTE :

** CHECK SYNCHRONISATION CONDITIONS ARE VALIDATED IN THE RESPECTIVE BAY CONTROL UNIT, BASED UPON THE SELECTED INCOMING & RUNNING VOLTAGES.

*** FOR DETAILS INTERLOCKING LOGICS REFER THE INTERLOCKS OF THE RESPECTIVE CIRCUIT BREAKER.

## PERMISSIVE FOR MAINTENANCE CLOSING IS GENERATED FROM BCU, WHEN BOTH THE ISOLATORS ON EITHER SIDES OF THE CB ARE OPEN.
THIS OUTPUT CONTACT FROM BCU IS WIRED INTO THE TNC CLOSING CIRCUIT.

1 CLOSE COMMAND GIVEN BY THE OPERATOR FROM SCADA WILL BE EXECUTED ONLY IF THE CHECK-SYNC CONDITIONS ARE SATISFIED.

2 CLOSE COMMAND FROM TNC SWITCH IS MEANT FOR CLOSING WITHOUT ANY SYNCHRONISATION & HENCE TO BE USED FOR MAINTENANCE/TESTING CONDITIONS.
CLIENT
ADANI POWER LTD.
:
3 INCOMING & RUNNING VOLTS ARE SELECTED BASED UPON THE ISOLATOR & CB POSITIONS IN THE RESPECTIVE DIA. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL LOGIC FOR REMOTE CLOSING OF AREVA REV. SHEET NEXT SH.
400kV LINE-TIE- ICT CIRCUIT BREAKERS AREVA T&D India Limited
FROM SCADA EMI-7604PG754-4-028 A 013 014
DF003

INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-1

A) ISOLATOR 1-89A

BUS-2 CVT ISO CLOSED

BUS-2 CVT ES OPEN


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

& ISO 1-89A INTLK


PERMISSIVE*
1-89AE OPEN

1-52CB OPEN***
ISO 1-89A CLOSE ORDER
&

ISO 1-89A CLOSE


REQUEST**

& ISO 1-89A OPEN ORDER


ISO 1-89A OPEN REQUEST**

B) ISOLATOR 1-89B

1-89BE OPEN

& ISO 1-89B INTLK


PERMISSIVE*
1-52CB OPEN***

ISO 1-89B CLOSE ORDER


ISO 1-89B CLOSE
&
REQUEST**

& ISO 1-89B OPEN ORDER


ISO 1-89B OPEN REQUEST**

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN O/G LINE-1
EMI-7604PG754-4-028 B 014 015
DF003

INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-1 (CONTD)

C) ISOLATOR 1-89C

1-89LE OPEN

ISO 1-89L INTLK


1-52CB OPEN***
& PERMISSIVE *

2-52CB OPEN***
ISO 1-89L CLOSE ORDER
ISO 1-89L CLOSE REQUEST
&
**

& ISO 1-89L OPEN ORDER


ISO 1-89L OPEN REQUEST **
This drawing and design is the property of AREVA T&D and must not be copied or lent with

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS IN O/G LINE-1 (CONTD)
EMI-7604PG754-4-028 B 015 016
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-1

A) EARTH SWITCH 1-89AE*

ISO 1-89A OPEN


ES 1-89AE INTLK
& PERMISSIVE **
ISO 1-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TO CLOSING CIRCUIT
&

B) EARTH SWITCH 1-89BE*

ISO 1-89A OPEN


ES 1-89BE INTLK
& PERMISSIVE **
ISO 1-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

C) EARTH SWITCH 1-89LE*

ISO 1-89L OPEN


ES 1-89LE INTLK
& PERMISSIVE **
DEAD LINE O/G LINE-1
(UNDER VOLTAGE
OPERATED) ***
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

*** LINE U/V PERMISSIVE IS TAKEN THROUGH SOFT FROM LINE DISTANCE PROTECTION RELAY.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR OPERATION


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
OF 400kV EARTH SWITCHES IN O/G LINE-1
EMI-7604PG754-4-028 B 016 017
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-1

A) RUNNING VOLTS *

BUS - 2 CVT RUNNING VOLTS

B) INCOMING VOLTS **

CASE - I

LINE - 1 CVT (1 - CVTB)


ISO 1-89L CLOSE
SELECTED

CASE - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CB 3-52 CLOSE

CB 2-52 CLOSE

& BUS-1 CVT SELECTED


ISO 3-89G OPEN

CB 1-89L OPEN

NOTE:

* FOR LINE FEEDERS, BUS-2 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.

** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.

THE SYNCHRONISATION OF LINE WITH GT IS NOT CONSIDERED IN THE CVT SELECTION & THE CB CLOSING SCHEME.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN O/G LINE-1 (BAY-1) EMI-7604PG754-4-028 B 017 018
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-1

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 1-89 AE CLOSE
CB 1-52 LOCAL CLOSING
& CIRCUIT *
ES 1-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

86-A TRIP RELAY RESET

86-B TRIP RELAY RESET


CB 1-52 CLOSING CIRCUIT
& **
A/R LK-OUT TRIP RELAY
(86-LO) RESET

BBP RELAY
RESET

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***

86-A TRIP RELAY RESET


RUNNING (BUS-2 CVT)
VOLTS
86-B TRIP RELAY RESET

A/R LK-OUT TRIP RELAY


(86-LO) RESET
VALIDATION OF
BBP RELAY
RESET
CHECK-SYNC
CB 1-52 CLOSE ORDER
CONDITIONS
ISO 1-89A CLOSE & IN BCU**

ISO 1-89B CLOSE


SELECTED INCOMING
L/R SS AT CB 1-52 M.BOX IN VOLTS (REFER SH: 017)
REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

TRIP CIRCUIT - 1 & 2 HEALTHY

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
CLIENT : ADANI POWER LTD.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. MUNDRA SEZ

*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOS INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-1
EMI-7604PG754-4-028 B 018 019
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-1

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR OPENING FROM REMOTE **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP
MARSHALLING BOX
&
REMOTE = BCU/HMI/SCADA
TO TRIP COIL - 2

CB OPEN REQUEST *

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-1
EMI-7604PG754-4-028 B 019 020
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-1

A) ISOLATOR 2-89A

2-89AE OPEN

& ISO 2-89A INTLK


2-52CB OPEN***
PERMISSIVE *

ISO 2-89A CLOSE


& ISO 2-89A CLOSE ORDER
REQUEST**

ISO 2-89A OPEN ORDER


ISO 2-89A OPEN REQUEST**
&

A) ISOLATOR 2-89B

ISO 2-89B INTLK


2-89BE OPEN
PERMISSIVE *

&
2-52CB OPEN***

ISO 2-89B CLOSE ORDER


&
ISO 2-89B CLOSE
REQUEST**

ISO 2-89B OPEN ORDER


ISO 2-89B OPEN REQUEST** &

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS FOR TIE-1
EMI-7604PG754-4-028 B 020 021
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN TIE-1

A) EARTH SWITCH 2-89AE*

ISO 2-89A OPEN


ES 2-89AE INTLK
& PERMISSIVE **
ISO 2-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

B) EARTH SWITCH 2-89BE*

ISO 2-89A OPEN


ES 2-89BE INTLK
& PERMISSIVE **
ISO 2-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR AREVA REV. SHEET NEXT SH.
OPERATION OF 400kV EARTH SWITCHES IN TIE- AREVA T&D India Limited
1 (BAY-2) EMI-7604PG754-4-028 B 021 022
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-1

A) RUNNING VOLTS *

CASE-1 (TIE/GT SELECTOR SWITCH IN TIE MODE. SYNCHRONISATION IS DONE FROM SWITCHYARD BCU)

BUS - 1 CVT RUNNING VOLTS TO BCU

CASE-2 (TIE/GT SELECTOR SWITCH IN GT MODE. SYNCHRONISATION IS DONE FROM GCP)

GT - 3 CVT RUNNING VOLTS

B) INCOMING VOLTS *
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CASE - I (APPLICABLE TO BOTH TIE & GCP MODE.)

ISO 1-89L CLOSE


LINE - 1 CVT (1 - CVTB)
SELECTED **
TIE/GCP SELECTOR TIE = FEEDER &
SWITCH AT SWYD BAY OR
CONTROL & PROT PANEL GCP = GT

CASE - 2 (APPLICABLE TO BOTH TIE & GCP MODE.)

CB 1-52 CLOSE

BUS-2 CVT SELECTED **


CB 1-89L OPEN
&
TIE/GCP SELECTOR TIE = FEEDER
SWITCH AT SWYD BAY OR
CONTROL & PROT PANEL GCP = GT

CASE - 3 (APPLICABLE FOR GT SYNCHRONISATION ONLY .TIE/GT SELECTOR SWITCH IN GT MODE. SYNCHRONISATION IS DONE FROM GCP)

CB 3-52 OPEN
##
GT-3 CVT SELECTED **
CB 3-89G CLOSED
&
TIE/GCP SELECTOR TIE = FEEDER
SWITCH AT SWYD BAY
CONTROL & PROT PANEL GCP = GT

NOTE:

* SINCE THE SYNCHRONISATION OF GT IS DONE FROM GCP, GT CVT IS NOT CONSIDERED IN THE CVT SELECTION LOGIC FOR BCU.
FOR BCU IN THE SWITCHYARD RUNNING VOLTS BY DEFAULT IS TAKEN AS BUS-1 VOLTS

** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.

## GT-3 CVT WILL BE SELECTED ONLY FOR SYNCHRONISATION OF GT THROUGH THE TIE.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN TIE-1 (BAY-2) EMI-7604PG754-4-028 B 022 023
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-1


(REMOTE CLOSING POSSIBLE FROM SWITCHYARD ONLY AS LONG AS ISOLATOR 3-89G IS OPEN)

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 2-89 AE CLOSE
CB 2-52 LOCAL CLOSING
& CIRCUIT *
ES 2-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

O/G LINE-1
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET

GT-3
86 TRIP RELAY RESET
CB 2-52 CLOSING
A/R LK-OUT TRIP RELAY CIRCUIT**
(86-LO) RESET &
TIE/GCP SELECTOR SWITCH TIE = FEEDER
AT SWYD BAY CONTROL & OR
PROT PANEL GCP = GT

GT3
INTLKS FROM GCP

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-1
EMI-7604PG754-4-028 B 023 023A
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-1 (CONTD.)

(REMOTE CLOSING POSSIBLE FROM SWITCHYARD ONLY AS LONG AS TIE/GCP SELECTOR SWITCH IS IN TIE MODE)

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TIE-1 A/R LK-OUT TRIP RELAY


(86-LO) RESET

RUNNING (BUS-1 CVT)


O/G LINE-1
VOLTS
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET

GT-3
86 TRIP RELAY RESET
VALIDATION OF
ISO 2-89A CLOSE
CHECK-SYNC
CONDITIONS CB 2-52 CLOSE ORDER

ISO 2-89B CLOSE IN BCU**


&
ISO 3-89G OPEN
SELECTED INCOMING
VOLTS (REFER SH: 022)
TRIP CIRCUIT - 1 & 2 HEALTHY

L/R SS AT CB 2-52 M.BOX IN


REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

TIE/GCP SELECTOR SWITCH TIE = FEEDER


AT SWYD BAY CONTROL &
PROT PANEL GCP = GT

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-1(CONTD.)
EMI-7604PG754-4-028 B 023A 024
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-1


(REMOTE OPENING POSSIBLE FROM SWITCHYARD ONLY IF TIE/GCP SELECTOR SWITCH IS IN TIE MODE)

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

SELECTOR SWITCH AT EQP


MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR REMOTE OPENING **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
TO TRIP COIL - 2
&
CB OPEN REQUEST

3-89G OPEN

TIE/GCP SELECTOR SWITCH TIE = FEEDER


AT SWYD BAY CONTROL &
PROT PANEL GCP = GT

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.

*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-1
EMI-7604PG754-4-028 B 024 025
DF003

INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN GT-3

A) ISOLATOR 3-89B

BUS-1 CVT ISO CLOSED

BUS-1 CVT ES OPEN


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

ISO 3-89B INTLK


& PERMISSIVE *
3-89BE OPEN

3-52CB OPEN***
ISO 3-89B CLOSE ORDER
&

ISO 3-89B CLOSE


REQUEST**

& ISO 3-89B OPEN ORDER


ISO 3-89B OPEN REQUEST**

B) ISOLATOR 3-89A

3-89AE OPEN
ISO 3-89A INTLK
& PERMISSIVE *

3-52CB OPEN***

ISO 3-89A CLOSE ORDER


ISO 3-89A CLOSE
&
REQUEST**

& ISO 3-89A OPEN ORDER


ISO 3-89A OPEN REQUEST**

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIEDCLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN GT-3 (BAY-3)
EMI-7604PG754-4-028 B 025 026
DF003

INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN GT-3 (CONTD.)

C) ISOLATOR 3-89G

3-89GE OPEN

ISO 3-89G INTLK


3-52CB OPEN*** & PERMISSIVE*

2-52CB OPEN***
ISO 3-89G CLOSE ORDER
ISO 3-89G CLOSE REQUEST
&
**

& ISO 3-89G OPEN ORDER


ISO 3-89G OPEN REQUEST **
This drawing and design is the property of AREVA T&D and must not be copied or lent with

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS IN GT-3 (BAY-3)
EMI-7604PG754-4-028 B 026 027
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN GT-3

A) EARTH SWITCH 3-89AE*

ISO 3-89A OPEN


ES 3-89AE INTLK
& PERMISSIVE **
ISO 3-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TO CLOSING CIRCUIT
&

B) EARTH SWITCH 3-89BE*

ISO 3-89A OPEN


ES 3-89BE INTLK
& PERMISSIVE **
ISO 3-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

C) EARTH SWITCH 3-89GE*

ES 3-89GE INTLK
ISO 3-89G OPEN
PERMISSIVE **
&
GENERATOR
EXCITATION OFF TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR OPERATION


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
OF 400kV EARTH SWITCHES IN GT-3
EMI-7604PG754-4-028 B 027 028
DF003

CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN GT-3

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL FOR CLOSE OPERATION*

ES 3-89 AE CLOSE

ES 3-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


CB 3-52 LOCAL CLOSING
SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = GCP
& CIRCUIT *

OPEN/CLOSE PUSH BUTTON OPEN


CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR CLOSING FROM REMOTE (GCP)

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = GCP
CB 3-52 REMOTE CLOSING
CIRCUIT *
GT3
INTLKS FROM GCP &
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
C) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE **

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN
OPEN/CLOSE PUSH BUTTON
CONTROLS AT GCP
CLOSE

D) INTERLOCKS FOR OPENING FROM REMOTE (GCP)

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = GCP
TO TRIP COIL - 1
GT3
INTLKS FROM GCP & TO TRIP COIL - 2

OPEN
OPEN/CLOSE PUSH BUTTON
NOTE: CONTROLS AT GCP
CLOSE
CLIENT : ADANI POWER LTD.
* THESE INTERLOCKS APPLY TO OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
OPERATION OF THE CIRCUIT BREAKERS IN GT BAYS IS NOT ALLOWED FROM THE BAY CONTROL & PROTECTION PANEL, BCU/HMI/SCADA. MUNDRA SEZ

** CLOSE POSITION OF THE CIRCUIT BREAKER IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN. CONTROL & INTERLOCK LOGIC FOR 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN GT-3 (BAY-3)
EMI-7604PG754-4-028 B 028 029
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-2

A) ISOLATOR 4-89A

BUS-2 CVT ISO CLOSED

BUS-2 CVT ES OPEN


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

& ISO 4-89A INTLK


PERMISSIVE *
4-89AE OPEN

4-52CB OPEN***
ISO 4-89A CLOSE ORDER
&

ISO 4-89A CLOSE


REQUEST**

& ISO 4-89A OPEN ORDER


ISO 4-89A OPEN REQUEST**

B) ISOLATOR 4-89B

4-89BE OPEN

& ISO 4-89B INTLK


PERMISSIVE *
4-52CB OPEN***

ISO 4-89B CLOSE ORDER


ISO 4-89B CLOSE
&
REQUEST**

& ISO 4-89B OPEN ORDER


ISO 4-89B OPEN REQUEST**

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN O/G LINE-2
EMI-7604PG754-4-028 B 029 030
DF003

INTERLOCK LOGIC FOR OPERATION OF ISOLATORS IN O/G LINE-2 (CONTD.)

C) ISOLATOR 4-89L

4-89LE OPEN

ISO 4-89L INTLK


4-52CB OPEN*** & PERMISSIVE *

5-52CB OPEN***
ISO 4-89L CLOSE ORDER
ISO 4-89L CLOSE REQUEST
&
**

ISO 4-89L OPEN ORDER


ISO 4-89L OPEN REQUEST **
&
This drawing and design is the property of AREVA T&D and must not be copied or lent witho

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS IN O/G LINE-2(CONTD.)
EMI-7604PG754-4-028 B 030 031
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-2

A) EARTH SWITCH 4-89AE*

ISO 4-89A OPEN


ES 4-89AE INTLK
& PERMISSIVE **
ISO 4-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TO CLOSING CIRCUIT
&

B) EARTH SWITCH 4-89BE*

ISO 4-89A OPEN


ES 4-89BE INTLK
& PERMISSIVE **
ISO 4-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

C) EARTH SWITCH 4-89LE*

ISO 4-89L OPEN


ES 4-89LE INTLK
& PERMISSIVE **
DEAD LINE O/G LINE-2
(UNDER VOLTAGE
OPERATED) ***
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

*** LINE U/V PERMISSIVE IS TAKEN THROUGH SOFT FROM LINE DISTANCE PROTECTION RELAY.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR OPERATION


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
OF 400kV EARTH SWITCHES IN O/G LINE-2
EMI-7604PG754-4-028 B 031 032
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-2

A) RUNNING VOLTS *

BUS - 2 CVT RUNNING VOLTS

B) INCOMING VOLTS **

CASE - I

LINE - 2 CVT (4 - CVTB)


ISO 4-89L CLOSE
SELECTED

CASE - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CB 5-52 CLOSE

CB 6-52 CLOSE

& BUS-1 CVT SELECTED


ISO 6-89G OPEN

ISO 4-89L OPEN

CASE - 3

CB 5-52 CLOSE
ICT-1 CVT (6-CVT)
SELECTED
ISO 6-89G CLOSE &

ISO 4-89L OPEN

NOTE:

* FOR LINE FEEDERS, BUS-2 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.

** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN O/G LINE-2 (BAY-4) EMI-7604PG754-4-028 B 032 033
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-2

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 4-89 AE CLOSE
CB 4-52 LOCAL CLOSING
& CIRCUIT *
ES 4-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

86-A TRIP RELAY RESET

86-B TRIP RELAY RESET


CB 4-52 CLOSING
& CIRCUIT **
A/R LK-OUT TRIP RELAY
(86-LO) RESET

BBP RELAY
RESET

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***

86-A TRIP RELAY RESET


RUNNING (BUS-2 CVT)
VOLTS
86-B TRIP RELAY RESET

A/R LK-OUT TRIP RELAY


(86-LO) RESET
VALIDATION OF
BBP RELAY
RESET
CHECK-SYNC
CB 4-52 CLOSE ORDER
CONDITIONS
ISO 4-89A CLOSE & IN BCU**

ISO 4-89B CLOSE


SELECTED INCOMING
L/R SS AT CB 4-52 M.BOX IN VOLTS (REFER SH: 032)
REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

TRIP CIRCUIT - 1 & 2 HEALTHY

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. MUNDRA SEZ

INTERLOCK LOGIC FOR CLOSING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-2
EMI-7604PG754-4-028 B 033 034
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-2

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

SELECTOR SWITCH AT EQP


MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR OPENING FROM REMOTE **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP &
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
TO TRIP COIL - 2

CB OPEN REQUEST *

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.

*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-2
EMI-7604PG754-4-028 B 034 035
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-2

A) ISOLATOR 5-89A

5-89AE OPEN
ISO 5-89A INTLK
& PERMISSIVE*
5-52CB OPEN***

ISO 5-89A CLOSE & ISO 5-89A CLOSE ORDER


REQUEST**

ISO 5-89A OPEN ORDER


ISO 5-89A OPEN REQUEST**
&

A) ISOLATOR 5-89B

ISO 5-89B INTLK


5-89BE OPEN
PERMISSIVE*

&
5-52CB OPEN***

ISO 5-89B CLOSE ORDER


&
ISO 5-89B CLOSE
REQUEST**

ISO 5-89B OPEN ORDER


ISO 5-89B OPEN REQUEST** &

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN TIE-2
EMI-7604PG754-4-028 B 035 036
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN TIE-2

A) EARTH SWITCH 5-89AE*

ISO 5-89A OPEN


ES 5-89AE INTLK
& PERMISSIVE **

ISO 5-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

B) EARTH SWITCH 5-89BE*

ISO 5-89A OPEN


ES 5-89BE INTLK
& PERMISSIVE **

ISO 5-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR AREVA REV. SHEET NEXT SH.
OPERATION OF 400kV EARTH SWITCHES AREVA T&D India Limited
IN TIE-2 (BAY-5) EMI-7604PG754-4-028 B 036 037
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-2

A) RUNNING VOLTS *

CASE - I

ICT CVT (6 - CVT)


ISO 6-89G CLOSE
SELECTED

CASE - 2

CB 6-52 CLOSE

&
BUS-1 CVT SELECTED
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CB 6-89G OPEN

B) INCOMING VOLTS *

CASE - I

LINE - 2 CVT (4 - CVTB)


ISO 4-89L CLOSE
SELECTED

CASE - 2

CB 4-52 CLOSE
BUS-2 CVT SELECTED
&
CB 4-89L OPEN

NOTE:

* AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING /RUNNING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING/RUNNING VOLTS TO BCU.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN TIE-2 (BAY-5) EMI-7604PG754-4-028 B 037 038
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-2

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 5-89 AE CLOSE
CB 5-52 LOCAL CLOSING
& CIRCUIT *
ES 5-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

O/G LINE-2
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET

ICT-1 CB 5-52 CLOSING


86-A TRIP RELAY RESET & CIRCUIT**
86-B TRIP RELAY RESET

TIE-2 A/R LK-OUT TRIP RELAY


(86-LO) RESET

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***

TIE-2 A/R LK-OUT TRIP RELAY


(86-LO) RESET

SELECTED RUNNING
O/G LINE-2
VOLTS (REFER SH:037)
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET

ICT-1
86-A TRIP RELAY RESET VALIDATION OF
86-B TRIP RELAY RESET
CHECK-SYNC
CONDITIONS CB 5-52 CLOSE ORDER
&
ISO 5-89A CLOSE IN BCU**

ISO 5-89B CLOSE


SELECTED INCOMING
VOLTS (REFER SH: 037)
TRIP CIRCUIT - 1 & 2 HEALTHY

L/R SS AT CB 5-52 M.BOX IN


REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
CLIENT : ADANI POWER LTD.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. MUNDRA SEZ

*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOS INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-2
EMI-7604PG754-4-028 B 038 039
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-2

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

SELECTOR SWITCH AT EQP


MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR REMOTE OPENING **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP &
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
TO TRIP COIL - 2

CB OPEN REQUEST

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.

*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-2
EMI-7604PG754-4-028 B 039 040
DF003

INTERLOCK LOGIC FOR OPERATION OF400kV ISOLATORS IN ICT-1

A) ISOLATOR 6-89B

BUS-1 CVT ISO CLOSED

BUS-1 CVT ES OPEN


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

ISO 6-89B INTLK


6-89BE OPEN & PERMISSIVE *

6-52CB OPEN***
ISO 6-89B CLOSE ORDER
&

ISO 6-89B CLOSE


REQUEST**

& ISO 6-89B OPEN ORDER


ISO 6-89B OPEN REQUEST**

B) ISOLATOR 6-89A

ISO 6-89A INTLK


6-89AE OPEN
PERMISSIVE *

&
6-52CB OPEN***

& ISO 6-89A CLOSE ORDER


ISO 6-89A CLOSE
REQUEST**

ISO 6-89A OPEN ORDER


ISO 6-89A OPEN REQUEST** &

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN ICT-1
EMI-7604PG754-4-028 B 040 041
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN ICT-1 (CONTD.)

C) ISOLATOR 6-89G

6-89GE OPEN

ISO 6-89G INTLK


6-52CB OPEN*** & PERMISSIVE *

5-52CB OPEN***

ISO 6-89G CLOSE


& ISO 6-89G CLOSE ORDER
REQUEST**

ISO 6-89G OPEN ORDER


ISO 6-89G OPEN REQUEST**
&
This drawing and design is the property of AREVA T&D and must not be copied or lent witho

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS IN ICT-1 (CONTD.)
EMI-7604PG754-4-028 B 041 042
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN ICT-1

A) EARTH SWITCH 6-89AE*

ISO 6-89A OPEN


ES 6-89AE INTLK
& PERMISSIVE **
ISO 6-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TO CLOSING CIRCUIT
&

B) EARTH SWITCH 6-89BE*

ISO 6-89A OPEN


ES 6-89BE INTLK
& PERMISSIVE **
ISO 6-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

C) EARTH SWITCH 6-89GE*

ES 6-89GE INTLK
ISO 6-89G OPEN
PERMISSIVE **
&
ICT LV CB OPEN
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR OPERATION


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
OF 400kV EARTH SWITCHES IN ICT-1
EMI-7604PG754-4-028 B 042 043
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN ICT-1

A) RUNNING VOLTS *

BUS - 1 CVT RUNNING VOLTS

B) INCOMING VOLTS **

CASE - I

ISO 4-89L CLOSE

LINE - 2 CVT (4 - CVTB)


CB 4-52 OPEN & SELECTED
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CB 5-52 CLOSE

CASE - 2

ICT -1 CVT (6 - CVT)


ISO 6-89G CLOSE
SELECTED

CASE - 3

CB 4-52 CLOSE

CB 5-52 CLOSE & BUS-2 CVT SELECTED

ISO 6-89G OPEN

NOTE:

* FOR ICT BAYS, BUS-1 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.

** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN ICT-1 (BAY-6) EMI-7604PG754-4-028 B 043 044
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN ICT-1

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 6-89 AE CLOSE
CB 6-52 LOCAL CLOSING
& CIRCUIT *
ES 6-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

86-A TRIP RELAY RESET

CB 6-52 CLOSING
86-B TRIP RELAY RESET & CIRCUIT **

BBP RELAY
RESET

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***

86-A TRIP RELAY RESET


RUNNING (BUS-1 CVT)
VOLTS
86-B TRIP RELAY RESET

VALIDATION OF
BBP RELAY
RESET
CHECK-SYNC
CB 6-52 CLOSE ORDER
CONDITIONS
ISO 6-89A CLOSE & IN BCU**

ISO 6-89B CLOSE


SELECTED INCOMING
L/R SS AT CB 6-52 M.BOX IN VOLTS (REFER SH: 043)
REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

TRIP CIRCUIT - 1 & 2 HEALTHY

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN ICT-1
EMI-7604PG754-4-028 B 044 045
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN ICT-1

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

SELECTOR SWITCH AT EQP


MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR OPENING FROM REMOTE **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA &

TO TRIP COIL - 2

CB OPEN REQUEST *

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN ICT-1
EMI-7604PG754-4-028 B 045 046
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-3

A) ISOLATOR 7-89A

BUS-2 CVT ISO CLOSED

BUS-2 CVT ES OPEN


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

& ISO 7-89A INTLK


PERMISSIVE *
7-89AE OPEN

7-52CB OPEN***
ISO 7-89A CLOSE ORDER
&

ISO 7-89A CLOSE


REQUEST**

& ISO 7-89A OPEN ORDER


ISO 7-89A OPEN REQUEST**

B) ISOLATOR 7-89B

7-89BE OPEN

& ISO 7-89B INTLK


PERMISSIVE *
7-52CB OPEN***

ISO 7-89B CLOSE ORDER


ISO 7-89B CLOSE
&
REQUEST**

& ISO 7-89B OPEN ORDER


ISO 7-89B OPEN REQUEST**

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN O/G LINE-3
EMI-7604PG754-4-028 B 046 047
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-3 (CONTD.)

C) ISOLATOR 7-89L

7-89LE OPEN

ISO 7-89L INTLK


7-52CB OPEN*** & PERMISSIVE*

8-52CB OPEN***
ISO 7-89L CLOSE ORDER
ISO 7-89L CLOSE REQUEST
&
**

ISO 7-89L OPEN ORDER


ISO 7-89L OPEN REQUEST **
&
This drawing and design is the property of AREVA T&D and must not be copied or lent without p

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS IN O/G LINE-3 (CONTD.)
EMI-7604PG754-4-028 B 047 048
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-3

A) EARTH SWITCH 7-89AE*

ISO 7-89A OPEN


ES 7-89AE INTLK
& PERMISSIVE **
ISO 7-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TO CLOSING CIRCUIT
&

B) EARTH SWITCH 7-89BE*

ISO 7-89A OPEN


ES 7-89BE INTLK
& PERMISSIVE **
ISO 7-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

C) EARTH SWITCH 7-89LE*

ISO 7-89L OPEN


ES 7-89LE INTLK
& PERMISSIVE **
DEAD LINE O/G LINE-3
(UNDER VOLTAGE
OPERATED) ***
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

*** LINE U/V PERMISSIVE IS TAKEN THROUGH SOFT FROM LINE DISTANCE PROTECTION RELAY.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR OPERATION


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
OF 400kV EARTH SWITCHES IN O/G LINE-3
EMI-7604PG754-4-028 B 048 049
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-3

A) RUNNING VOLTS *

BUS - 2 CVT RUNNING VOLTS

B) INCOMING VOLTS **

CASE - I

LINE - 3 CVT (7 - CVTB)


ISO 7-89L CLOSE
SELECTED

CASE - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CB 8-52 CLOSE

CB 9-52 CLOSE

& BUS-1 CVT SELECTED


ISO 9-89G OPEN

ISO 7-89L OPEN

CASE - 3

CB 8-52 CLOSE

ICT-2 CVT (9-CVT)


ISO 7-89L OPEN & SELECTED

ISO 9-89G CLOSE

NOTE:

* FOR LINE FEEDERS, BUS-2 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.

** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN O/G LINE-3 (BAY-7) EMI-7604PG754-4-028 B 049 050
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-3

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 7-89 AE CLOSE
CB 7-52 LOCAL CLOSING
& CIRCUIT *
ES 7-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

86-A TRIP RELAY RESET

86-B TRIP RELAY RESET


CB 7-52 CLOSING
& CIRCUIT **
A/R LK-OUT TRIP RELAY
(86-LO) RESET

BBP RELAY
RESET

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***

86-A TRIP RELAY RESET


RUNNING (BUS-2 CVT)
VOLTS
86-B TRIP RELAY RESET

A/R LK-OUT TRIP RELAY


(86-LO) RESET
VALIDATION OF
BBP RELAY
RESET
CHECK-SYNC
CB 7-52 CLOSE ORDER
CONDITIONS
ISO 7-89A CLOSE & IN BCU**

ISO 7-89B CLOSE


SELECTED INCOMING
L/R SS AT CB 7-52 M.BOX IN VOLTS (REFER SH: 049)
REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

TRIP CIRCUIT - 1 & 2 HEALTHY

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.
CLIENT : ADANI POWER LTD.
** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. MUNDRA SEZ

*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOS INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-3
EMI-7604PG754-4-028 B 050 051
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-3

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR REMOTE OPENING **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA &

TO TRIP COIL - 2

CB OPEN REQUEST *

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED. 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-3
EMI-7604PG754-4-028 B 051 052
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-3

A) ISOLATOR 8-89A

8-89AE OPEN

&
ISO 8-89A INTLK
8-52CB OPEN***
PERMISSIVE *

ISO 8-89A CLOSE & ISO 8-89A CLOSE ORDER


REQUEST**

ISO 8-89A OPEN ORDER


ISO 8-89A OPEN REQUEST**
&

A) ISOLATOR 8-89B

ISO 8-89B INTLK


8-89BE OPEN
PERMISSIVE *

&
8-52CB OPEN***

ISO 8-89B CLOSE ORDER


&
ISO 8-89B CLOSE
REQUEST**

ISO 8-89B OPEN ORDER


ISO 8-89B OPEN REQUEST** &

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN TIE-3
EMI-7604PG754-4-028 B 052 053
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OFEARTH SWITCHES IN TIE-3

A) EARTH SWITCH 8-89AE*

ISO 8-89A OPEN


ES 8-89AE INTLK
& PERMISSIVE **
ISO 8-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

B) EARTH SWITCH 8-89BE*

ISO 8-89A OPEN


ES 8-89BE INTLK
& PERMISSIVE **
ISO 8-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR AREVA REV. SHEET NEXT SH.
OPERATION OF 400kV EARTH SWITCHES AREVA T&D India Limited
IN TIE-3 (BAY-8) EMI-7604PG754-4-028 B 053 054
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-3

A) RUNNING VOLTS *

CASE - I

ICT -2 CVT (9 - CVT)


ISO 9-89G CLOSE
SELECTED

CASE - 2

CB 9-52 CLOSE

& BUS-1 CVT SELECTED


CB 9-89G OPEN
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INCOMING VOLTS *

CASE - I

LINE - 3 CVT (7 - CVTB)


ISO 7-89L CLOSE
SELECTED

CASE - 2

CB 7-52 CLOSE
BUS-2 CVT SELECTED
&
CB 7-89L OPEN

NOTE:

* AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING/RUNNING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING/RUNNING VOLTS TO BCU.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN TIE-3 (BAY-8) EMI-7604PG754-4-028 B 054 055
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-3

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 8-89 AE CLOSE
CB 8-52 LOCAL CLOSING
& CIRCUIT *
ES 8-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

O/G LINE-3
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET

ICT-2 CB 8-52 CLOSING


86-A TRIP RELAY RESET & CIRCUIT**
86-B TRIP RELAY RESET

TIE-3 A/R LK-OUT TRIP RELAY


(86-LO) RESET

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***

TIE-3 A/R LK-OUT TRIP RELAY


(86-LO) RESET

SELECTED RUNNING
O/G LINE-3
VOLTS (REFER SH:054)
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET

ICT-2
86-A TRIP RELAY RESET VALIDATION OF
86-B TRIP RELAY RESET
CHECK-SYNC
CONDITIONS CB 8-52 CLOSE ORDER
&
ISO 8-89A CLOSE IN BCU**

ISO 8-89B CLOSE


SELECTED INCOMING
VOLTS (REFER SH: 054)
TRIP CIRCUIT - 1 & 2 HEALTHY

L/R SS AT CB 8-52 M.BOX IN


REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-3
EMI-7604PG754-4-028 B 055 056
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-3

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR REMOTE OPENING **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA &

TO TRIP COIL - 2

CB OPEN REQUEST

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.

*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-3
EMI-7604PG754-4-028 B 056 057
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN ICT-2

A) ISOLATOR 9-89B

BUS-1 CVT ISO CLOSED

BUS-1 CVT ES OPEN


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

ISO 9-89B INTLK


9-89BE OPEN & PERMISSIVE *

9-52CB OPEN***
ISO 9-89B CLOSE ORDER
&

ISO 9-89B CLOSE


REQUEST**

& ISO 9-89B OPEN ORDER


ISO 9-89B OPEN REQUEST**

B) ISOLATOR 9-89A

ISO 9-89A INTLK


9-89AE OPEN
PERMISSIVE *

&
9-52CB OPEN***

& ISO 9-89A CLOSE ORDER


ISO 9-89A CLOSE
REQUEST**

& ISO 9-89A OPEN ORDER


ISO 9-89A OPEN REQUEST**

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN ICT-2
EMI-7604PG754-4-028 B 057 058
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN ICT-2 (CONTD.)

C) ISOLATOR 9-89G

9-89GE OPEN

ISO 9-89G INTLK


8-52CB OPEN*** & PERMISSIVE *

9-52CB OPEN***
ISO 9-89G CLOSE ORDER
ISO 9-89G CLOSE
&
REQUEST**

ISO 9-89G OPEN ORDER


ISO 9-89G OPEN REQUEST**
&
This drawing and design is the property of AREVA T&D and must not be copied or lent wi

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS IN ICT-2 (CONTD.)
EMI-7604PG754-4-028 B 058 059
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN ICT-2

A) EARTH SWITCH 9-89AE*

ISO 9-89A OPEN


ES 9-89AE INTLK
& PERMISSIVE **
ISO 9-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TO CLOSING CIRCUIT
&

B) EARTH SWITCH 9-89BE*

ISO 9-89A OPEN


ES 9-89BE INTLK
& PERMISSIVE **
ISO 9-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

C) EARTH SWITCH 9-89GE*

ES 9-89GE INTLK
ISO 9-89G OPEN
PERMISSIVE **

TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR OPERATION


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
OF 400kV EARTH SWITCHES IN ICT-2
EMI-7604PG754-4-028 B 059 060
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN ICT-2

A) RUNNING VOLTS *

BUS - 1 CVT RUNNING VOLTS

B) INCOMING VOLTS **

CASE - I

ISO 7-89L CLOSE

LINE - 3 CVT (7 - CVTB)


CB 7-52 OPEN & SELECTED
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CB 8-52 CLOSE

CASE - 2

ICT-2 CVT (9 - CVT)


ISO 9-89G CLOSE
SELECTED

CASE - 3

CB 7-52 CLOSE

CB 8-52 CLOSE & BUS-2 CVT SELECTED

ISO 9-89G OPEN

NOTE:

* FOR ICT BAYS, BUS-1 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.

** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING/ RUNNING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING/ RUNNING VOLTS TO BCU.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN ICT-2 (BAY-9) EMI-7604PG754-4-028 B 060 061
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN ICT-2

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 9-89 AE CLOSE
CB 9-52 LOCAL CLOSING
& CIRCUIT *
ES 9-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

86-A TRIP RELAY RESET

CB 9-52 CLOSING
86-B TRIP RELAY RESET & CIRCUIT **

BBP RELAY
RESET

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***

86-A TRIP RELAY RESET


RUNNING (BUS-1 CVT)
VOLTS
86-B TRIP RELAY RESET

VALIDATION OF
BBP RELAY
RESET
CHECK-SYNC
CB 9-52 CLOSE ORDER
CONDITIONS
ISO 9-89A CLOSE & IN BCU**

ISO 9-89B CLOSE


SELECTED INCOMING
L/R SS AT CB 9-52 M.BOX IN VOLTS (REFER SH: 060)
REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

TRIP CIRCUIT - 1 & 2 HEALTHY

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN ICT-2
EMI-7604PG754-4-028 B 061 062
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G ICT-2

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

SELECTOR SWITCH AT EQP


MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR REMOTE OPENING **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA &

TO TRIP COIL - 2

CB OPEN REQUEST *

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.

*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN ICT-2
EMI-7604PG754-4-028 B 062 063
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-4

A) ISOLATOR 10-89A

BUS-2 CVT ISO CLOSED

BUS-2 CVT ES OPEN


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

& ISO 10-89A INTLK


PERMISSIVE *
10-89AE OPEN

10-52CB OPEN***
ISO 10-89A CLOSE ORDER
&

ISO 10-89A CLOSE


REQUEST**

ISO 10-89A OPEN & ISO 10-89A OPEN ORDER


REQUEST**

B) ISOLATOR 10-89B

10-89BE OPEN

& ISO 10-89B INTLK


PERMISSIVE *
10-52CB OPEN***

ISO 10-89B CLOSE ORDER


ISO 10-89B CLOSE
&
REQUEST**

& ISO 10-89B OPEN ORDER


ISO 10-89B OPEN
REQUEST**

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIEDCLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN O/G LINE-4
EMI-7604PG754-4-028 B 063 064
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN O/G LINE-4 (CONTD.)

C) ISOLATOR 10-89L

10-89LE OPEN

ISO 10-89L INTLK


10-52CB OPEN*** & PERMISSIVE *

11-52CB OPEN***
ISO 10-89L CLOSE ORDER
ISO 10-89L CLOSE REQUEST
&
**

& ISO 10-89L OPEN ORDER


ISO 10-89L OPEN REQUEST
**
This drawing and design is the property of AREVA T&D and must not be copied or lent with

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS IN O/G LINE-4 (CONTD.)
EMI-7604PG754-4-028 B 064 065
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN O/G LINE-4

A) EARTH SWITCH 10-89AE*

ISO 10-89A OPEN


ES 10-89AE INTLK
& PERMISSIVE **
ISO 10-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TO CLOSING CIRCUIT
&

B) EARTH SWITCH 10-89BE*

ISO 10-89A OPEN


ES 10-89BE INTLK
& PERMISSIVE **
ISO 10-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

C) EARTH SWITCH 10-89LE*

ISO 10-89L OPEN


ES 10-89LE INTLK
& PERMISSIVE **
DEAD LINE O/G LINE-4
(UNDER VOLTAGE
OPERATED) ***
TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

*** LINE U/V PERMISSIVE IS TAKEN THROUGH SOFT FROM LINE DISTANCE PROTECTION RELAY.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR OPERATION


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
OF 400kV EARTH SWITCHES IN O/G LINE-4
EMI-7604PG754-4-028 B 065 066
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN O/G LINE-4

A) RUNNING VOLTS *

BUS - 2 CVT RUNNING VOLTS

B) INCOMING VOLTS **

CASE - I

LINE - 4 CVT (10 - CVTB)


ISO 10-89L CLOSE
SELECTED

CASE - 2
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CB 10-52 CLOSE

CB 11-52 CLOSE

& BUS-1 CVT SELECTED


ISO 12-89G OPEN

ISO 10-89L OPEN

NOTE:

* FOR LINE FEEDERS, BUS-2 CVT WILL BE SELECTED AS RUNNING VOLTS AND EXTENDED TO BCU TERMINALS FOR CHECK-SYNC.

** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.

THE SYNCHRONISATION OF LINE WITH GT IS NOT CONSIDERED IN THE CVT SELECTION & THE CB CLOSING SCHEME.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN O/G LINE-4 (BAY-10) EMI-7604PG754-4-028 B 066 067
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN O/G LINE-4

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 10-89 AE CLOSE
CB 10-52 LOCAL CLOSING
& CIRCUIT *
ES 10-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

86-A TRIP RELAY RESET

86-B TRIP RELAY RESET


CB 10-52 CLOSING
& CIRCUIT **
A/R LK-OUT TRIP RELAY
(86-LO) RESET

BBP RELAY
RESET

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***

86-A TRIP RELAY RESET


RUNNING (BUS-2 CVT)
VOLTS
86-B TRIP RELAY RESET

A/R LK-OUT TRIP RELAY


(86-LO) RESET
VALIDATION OF
BBP RELAY
RESET
CHECK-SYNC
CB 10-52 CLOSE ORDER
CONDITIONS
ISO 10-89A CLOSE & IN BCU**

ISO 10-89B CLOSE


SELECTED INCOMING
L/R SS AT CB 10-52 M.BOX IN VOLTS (REFER SH: 066)
REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

TRIP CIRCUIT - 1 & 2 HEALTHY

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU.
CLIENT : ADANI POWER LTD.
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE 400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH. MUNDRA SEZ

INTERLOCK LOGIC FOR CLOSING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-4
EMI-7604PG754-4-028 B 067 068
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN O/G LINE-4

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR REMOTE OPENING **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA &

TO TRIP COIL - 2

CB OPEN REQUEST *

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.

*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN O/G LINE-4
EMI-7604PG754-4-028 B 068 069
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN TIE-4

A) ISOLATOR 11-89A

11-89AE OPEN

&
ISO 11-89A INTLK
11-52CB OPEN***
PERMISSIVE *

ISO 11-89A CLOSE & ISO 11-89A CLOSE ORDER


REQUEST**

ISO 11-89A OPEN ORDER


ISO 11-89A OPEN &
REQUEST**

A) ISOLATOR 11-89B

ISO 11-89B INTLK


11-89BE OPEN
PERMISSIVE *
&
11-52CB OPEN***

ISO 11-89B CLOSE ORDER


&
ISO 11-89B CLOSE
REQUEST**

ISO 11-89B OPEN


& ISO 11-89B OPEN ORDER
REQUEST**

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN TIE-4
EMI-7604PG754-4-028 B 069 070
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OFEARTH SWITCHES IN TIE-4

A) EARTH SWITCH 11-89AE*

ISO 11-89A OPEN


ES 11-89AE INTLK
& PERMISSIVE **
ISO 11-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

B) EARTH SWITCH 11-89BE*

ISO 11-89A OPEN


ES 11-89BE INTLK
& PERMISSIVE **
ISO 11-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR AREVA REV. SHEET NEXT SH.
OPERATION OF 400kV EARTH SWITCHES IN AREVA T&D India Limited
TIE-4 (BAY-11) EMI-7604PG754-4-028 B 070 071
DF003

CVT SELECTION LOGIC FOR CHECK SYNC OF CIRCUIT BREAKER IN TIE-4

A) RUNNING VOLTS *

CASE-1 (TIE/GT SELECTOR SWITCH IN TIE MODE. SYNCHRONISATION IS DONE FROM SWITCHYARD BCU)

BUS - 1 CVT RUNNING VOLTS TO BCU

CASE-2 (TIE/GT SELECTOR SWITCH IN GT MODE. SYNCHRONISATION IS DONE FROM GCP)

GT - 4 CVT RUNNING VOLTS

B) INCOMING VOLTS *
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CASE - I (APPLICABLE TO BOTH TIE & GCP MODE.)

ISO 10-89L CLOSE


LINE - 4 CVT (10 - CVTB)
SELECTED **
TIE/GCP SELECTOR TIE = FEEDER &
SWITCH AT SWYD BAY OR
CONTROL & PROT PANEL GCP = GT

CASE - 2 (APPLICABLE TO BOTH TIE & GCP MODE.)

CB 10-52 CLOSE

BUS-2 CVT SELECTED **


CB 10-89L OPEN
&
TIE/GCP SELECTOR TIE = FEEDER
SWITCH AT SWYD BAY OR
CONTROL & PROT PANEL GCP = GT

CASE - 3 (APPLICABLE FOR GT SYNCHRONISATION ONLY .TIE/GT SELECTOR SWITCH IN GT MODE. SYNCHRONISATION IS DONE FROM GCP)

CB 12-52 OPEN
##
GT-4 CVT SELECTED **
CB 12-89G CLOSED
&
TIE/GCP SELECTOR TIE = FEEDER
SWITCH AT SWYD BAY
CONTROL & PROT PANEL GCP = GT

NOTE:

* SINCE THE SYNCHRONISATION OF GT IS DONE FROM GCP, GT CVT IS NOT CONSIDERED IN THE CVT SELECTION LOGIC FOR BCU.
FOR BCU IN THE SWITCHYARD RUNNING VOLTS BY DEFAULT IS TAKEN AS BUS-1 VOLTS

** AT ANY TIME ONLY ONE OF THE CASES WILL BE SUCCESFUL FOR INCOMING VOLTS. BASED ON THE ISOLATOR & CB POSITIONS, THE LOGICS ARE VALIDATED AND
OUTPUTS ARE GENERATED FROM THE BCU WHICH ARE WIRED INTO THE PT SELECTION CIRCUIT FOR EXTENSION OF THE APPROPRIATE INCOMING VOLTS TO BCU.

## GT-3 CVT WILL BE SELECTED ONLY FOR SYNCHRONISATION OF GT THROUGH THE TIE.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

CVT SELECTION LOGIC FOR AREVA REV. SHEET NEXT SH.


CHECK-SYNC OF CB AREVA T&D India Limited
IN TIE-4 (BAY-11) EMI-7604PG754-4-028 B 071 072
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-4


(REMOTE CLOSING POSSIBLE FROM SWITCHYARD ONLY AS LONG AS TIE/GCP SELECTOR SWITCH IS IN TIE MODE)

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL *

ES 11-89 AE CLOSE
CB 11-52 LOCAL CLOSING
& CIRCUIT *
ES 11-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

B) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BAY CONTROL & PROTECTION PANEL **

O/G LINE-4
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET

GT-4
86 TRIP RELAY RESET
CB 11-52 CLOSING
A/R LK-OUT TRIP RELAY CIRCUIT**
(86-LO) RESET &
TIE/GCP SELECTOR SWITCH TIE = FEEDER
AT SWYD BAY CONTROL & OR
PROT PANEL GCP = GT

GT4
INTLKS FROM GCP

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-4
EMI-7604PG754-4-028 B 072 072A
DF003

INTERLOCK LOGIC FOR CLOSING OF CIRCUIT BREAKER IN TIE-4

(REMOTE CLOSING POSSIBLE FROM SWITCHYARD ONLY AS LONG AS TIE/GCP SELECTOR SWITCH IS IN TIE MODE)

C) INTERLOCKS IMPLEMENTED IN SOFT LOGIC IN BCU ***


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

TIE-4 A/R LK-OUT TRIP RELAY


(86-LO) RESET

RUNNING (BUS-1 CVT)


O/G LINE-4
VOLTS
86-A TRIP RELAY RESET
86-B TRIP RELAY RESET

GT-4
86 TRIP RELAY RESET
VALIDATION OF
ISO 11-89A CLOSE
CHECK-SYNC
CONDITIONS CB 11-52 CLOSE ORDER

ISO 11-89B CLOSE IN BCU**


&
ISO 12-89G OPEN
SELECTED INCOMING
VOLTS (REFER SH: 070)
TRIP CIRCUIT - 1 & 2 HEALTHY

L/R SS AT CB 11-52 M.BOX IN


REMOTE MODE

CLOSE REQUEST FROM


BCU/SCADA/HMI

TIE/GCP SELECTOR SWITCH TIE = FEEDER


AT SWYD BAY CONTROL &
PROT PANEL GCP = GT

NOTE:

* THESE INTERLOCKS APPLY TO CLOSE OPERATION OF CIRCUIT BREAKER FROM THE EQUIPMENT MARSHALLING BOX.

** THESE HARDWIRED INTERLOCKS APPLY TO THE CONTROL USING TNC SWITCH ON THE BAY CONTROL & PROTECTION PANEL.
IN CASE OF CLOSING FROM BCU/HMI/SCADA, THESE HARDWIRED INTERLOCKS MUST BE SATISFIED IN ADDITION TO THE SOFT LOGICS BUILT IN THE BCU. CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
*** THESE LOGICS APPLY FOR THE CLOSE OPERATION FROM BCU/HMI/SCADA. THESE LOGICS APPLY FOR AUTO RECLOSE MUNDRA SEZ
CLOSE COMMAND ISSUED BY THE BCU. A/R CLOSING WILL SUCCESFUL ONLY IF THE INTERLOCKS ARE THROUGH.
INTERLOCK LOGIC FOR CLOSING OF 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-4
EMI-7604PG754-4-028 B 072A 073
DF003

INTERLOCK LOGIC FOR OPENING OF CIRCUIT BREAKER IN TIE-4


(REMOTE OPENING POSSIBLE FROM SWITCHYARD ONLY IF TIE/GCP SELECTOR SWITCH IS IN TIE MODE)

A) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

SELECTOR SWITCH AT EQP


MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR REMOTE OPENING **

CB CLOSE ***

EQP LOCAL/REMOTE LOCAL = EQP M.BOX TO TRIP COIL - 1


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA
TO TRIP COIL - 2
&
CB OPEN REQUEST

12-89G OPEN

TIE/GCP SELECTOR SWITCH TIE = FEEDER


AT SWYD BAY CONTROL &
PROT PANEL GCP = GT

NOTE:

* THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM EQP. MARSHALLING BOX.

** THESE INTERLOCKS ARE APPLICABLE FOR OPERATION FROM BCU/HMI/SCADA. THESE LOGICS ARE BUILT IN THE BCU.

*** CB CLOSE POSITION IS CONFIRMED ONLY WHEN ALL THE THREE POLES ARE CLOSED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPENING OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN TIE-4
EMI-7604PG754-4-028 B 073 074
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN GT-4

A) ISOLATOR 12-89B

BUS-1 CVT ISO CLOSED

BUS-1 CVT ES OPEN


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

ISO 12-89B INTLK


& PERMISSIVE *
12-89BE OPEN

12-52CB OPEN***
ISO 12-89B CLOSE ORDER
&

ISO 12-89B CLOSE


REQUEST**

ISO 12-89B OPEN & ISO 12-89B OPEN ORDER


REQUEST**

B) ISOLATOR 12-89A

12-89AE OPEN
ISO 12-89A INTLK
PERMISSIVE *
&
12-52CB OPEN***

ISO 12-89A CLOSE ORDER


ISO 12-89A CLOSE
&
REQUEST**

& ISO 12-89A OPEN ORDER


ISO 12-89A OPEN
REQUEST**

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF 400kV


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
ISOLATORS IN GT-4
EMI-7604PG754-4-028 A 074 075
DF003

INTERLOCK LOGIC FOR OPERATION OF 400kV ISOLATORS IN GT-4 (CONTD.)

C) ISOLATOR 12-89G

12-89GE OPEN

ISO 12-89G INTLK


12-52CB OPEN*** & PERMISSIVE*

11-52CB OPEN***
ISO 12-89G CLOSE ORDER
ISO 12-89G CLOSE
&
REQUEST**

ISO 12-89G OPEN ORDER


ISO 12-89G OPEN &
REQUEST**
This drawing and design is the property of AREVA T&D and must not be copied or lent wi

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

*** OPEN POSITION FOR CB IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR OPERATION OF


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
400kV ISOLATORS IN GT-4 (CONTD.)
EMI-7604PG754-4-028 A 075 076
DF003

CONTROL & INTERLOCK LOGIC FOR OPERATION OF EARTH SWITCHES IN GT-4

A) EARTH SWITCH 12-89AE*

ISO 12-89A OPEN


ES 12-89AE INTLK
& PERMISSIVE **
ISO 12-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

EQP MARSHALLING BOX CLOSE


TO CLOSING CIRCUIT
&

B) EARTH SWITCH 12-89BE*

ISO 12-89A OPEN


ES 12-89BE INTLK
& PERMISSIVE **
ISO 12-89B OPEN

& TO OPEN CIRCUIT


OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE
TO CLOSING CIRCUIT
&

C) EARTH SWITCH 12-89GE*

ES 12-89GE INTLK
PERMISSIVE **
ISO 12-89G OPEN
&
GENERATOR
TO OPEN CIRCUIT
EXCITATION OFF
&
OPEN/CLOSE PUSH OPEN
BUTTON CONTROLS AT
EQP MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&
NOTE:

* FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

** THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

CONTROL & INTERLOCK LOGIC FOR OPERATION


AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
OF 400kV EARTH SWITCHES IN GT-4
EMI-7604PG754-4-028 B 076 077
DF003

CONTROL & INTERLOCK LOGIC FOR OPENING & CLOSING OF CIRCUIT BREAKER IN GT-4

A) INTERLOCKS IMPLEMENTED AS HARDWIRED AT BMK LEVEL FOR CLOSE OPERATION*

ES 12-89 AE CLOSE

ES 12-89 BE CLOSE
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


CB 12-52 LOCAL CLOSING
SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = GCP & CIRCUIT *

OPEN/CLOSE PUSH BUTTON OPEN


CONTROLS AT EQP
MARSHALLING BOX CLOSE

B) INTERLOCKS FOR CLOSING FROM REMOTE (GCP)

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = GCP
CB 12-52 REMOTE
CLOSING CIRCUIT *
GT4
INTLKS FROM GCP &
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE

C) INTERLOCKS FOR OPENING FROM BMK LEVEL *

CB CLOSE **

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = BCU/HMI/SCADA & TO TRIP COIL - 1

TO TRIP COIL - 2
OPEN
OPEN/CLOSE PUSH BUTTON
CONTROLS AT GCP
CLOSE

D) INTERLOCKS FOR OPENING FROM REMOTE (GCP)

EQP LOCAL/REMOTE LOCAL = EQP M.BOX


SELECTOR SWITCH AT EQP
MARSHALLING BOX REMOTE = GCP
TO TRIP COIL - 1
GT4
INTLKS FROM GCP
& TO TRIP COIL - 2

OPEN
OPEN/CLOSE PUSH BUTTON
CONTROLS AT GCP
CLOSE

NOTE: CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
* OPERATION OF THE CIRCUIT BREAKERS IN GT BAYS IS NOT ALLOWED FROM THE BAY CONTROL & PROTECTION PANEL, BCU/HMI/SCADA. MUNDRA SEZ

** CLOSE POSITION OF THE CIRCUIT BREAKER IS CONFIRMED ONLY IF ALL THE THREE POLES ARE OPEN. CONTROL & INTERLOCK LOGIC FOR 400kV
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
CIRCUIT BREAKER IN GT-4 (BAY-12)
EMI-7604PG754-4-028 B 077 078
DF003
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writin

BLANK SHEET

CLIENT : ADANI POWER LTD.


400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

AREVA REV. SHEET NEXT SH.


BLANK SHEET AREVA T&D India Limited
EMI-7604PG754-4-028 A 078 079
DF003

INTERLOCK LOGIC FOR OPERATION OF BUS-1 CVT ISOLATOR & EARTH SWITCH
(MANAGED BY TIE-1 BCU)

A) BUS - 1 CVT ISOLATOR

BUS-1 CVT BUS-1 CVT ISO INTLK


EARTH SWITCH OPEN PERMISSIVE *

BUS-1 CVT ISO CLOSE


BUS-1 CVT ISO CLOSE & ORDER
REQUEST **

BUS-1 CVT ISO OPEN


BUS-1 CVT ISO OPEN & ORDER
REQUEST **

#
B) BUS-1 CVT EARTH SWITCH

##
BUS-1 CVT E/S
BUS-1 CVT ISO OPEN
INTLK PERMISSIVE
This drawing and design is the property of AREVA T&D and must not be

TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

# FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

## THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR REMOTE OPERATION AREVA REV. SHEET NEXT SH.
OF 400kV BUS-1 CVT ISOLATOR & EARTH AREVA T&D India Limited
SWITCH EMI-7604PG754-4-028 A 079 080
DF003

INTERLOCK LOGIC FOR OPERATION OF BUS-2 CVT ISOLATOR & EARTH SWITCH
(MANAGED BY TIE-1 BCU)

A) BUS - 2 CVT ISOLATOR

BUS-2 CVT BUS-2 CVT ISO INTLK


EARTH SWITCH OPEN PERMISSIVE *

BUS-2 CVT ISO CLOSE


BUS-2 CVT ISO CLOSE & ORDER
REQUEST **

BUS-2 CVT ISO OPEN


BUS-2 CVT ISO OPEN & ORDER
REQUEST **

#
B) BUS-2 CVT EARTH SWITCH

##
BUS-2 CVT E/S
BUS-2 CVT ISO OPEN
INTLK PERMISSIVE
This drawing and design is the property of AREVA T&D and must not be

TO OPEN CIRCUIT
&
OPEN/CLOSE PUSH BUTTON OPEN
CONTROLS AT EQP
MARSHALLING BOX CLOSE TO CLOSING CIRCUIT
&

NOTE:

* AS INDICATED IN SHEETS: 003, 004, 005, 006 FOR CONTROL LOGIC OF ISOLATORS, THE INTERLOCK PERMISSIVE WILL BE WIRED IN THE CONTROL CIRCUIT OF ISOLATORS
TO ENSURE THAT COMMAND WILL BE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.

** CLOSING & OPENING REQUEST OF ISOLATORS CAN BE GIVEN FROM ANY CONTROL LEVELS DEFINED IN SHEETS 003-006, PROVIDED THE ABOVE INTERLOCKS ARE SATISFIED.

# FOR EARTH SWITCHES THERE IS NO REMOTE CONTROL FROM BCU/HMI/SCADA. CONTROL IS POSSIBLE ONLY FROM EQUIPMENT MARSHALLING BOX.
ALL THE INTERLOCKS FOR EARTH SWITCH OPERATION ARE VERIFIED IN BCU & AN OUTPUT IS GENERATED FROM BCU WHEN THE INTERLOCKS ARE SATISFIED.

## THIS INTERLOCK PERMISSIVE IS GENERATED BY THE BCU AND IS HARD WIRED IN THE CONTROL CIRCUIT OF THE EARTH SWITCH.
COMMANDS GIVEN FROM THE EQUIPMENT MARSHALLING BOX ARE EXECUTED ONLY WHEN THE INTERLOCKS ARE SATISFIED.
CLIENT : ADANI POWER LTD.
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
File: PG725000-003.xls

PROJECT :
MUNDRA SEZ

INTERLOCK LOGIC FOR REMOTE OPERATION AREVA REV. SHEET NEXT SH.
OF 400kV BUS-2 CVT ISOLATOR & EARTH AREVA T&D India Limited
SWITCH EMI-7604PG754-4-028 A 080 081
DF003

IMPLEMENATION OF SYNCHROCHECK FUNCTION IN BCU (TYPICAL FOR ALL BAYS EXCEPT GT BAYS)

CASE -1 DEAD INCOMING VOLTS - DEAD RUNNING VOLTS


IMPLEMENTED IN BCU

SELECTED RUNNING VOLTS < SELECTED


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

RUNNING VOLTS * DEAD VOLTS THRESHOLD

YES
DEAD INCOMING VOLTS TIMER FOR
& DEAD RUNNING VOLTS CONFIRMATION
CONDITIONS SATISFIED? (SETTABLE) ***

SELECTED INCOMING VOLTS < SELECTED


INCOMING VOLTS * DEAD VOLTS THRESHOLD

TO CLOSING
& CIRCUIT
SOFTWARE INTERLOCKS
CLOSE REQUEST FROM
BUILT IN RESPECTIVE BCU
BCU/HMI/SCADA
VERIFIED SUCCESFULLY **

INTLKS IMPLEMENTED THROUGH HARDWIRING


IN BAY CNTL & PROT PANEL

NOTE :

* VOLTAGE SELECTION FOR INCOMING AND RUNNING VOLTS SHALL BE AS PER THE SELECTION LOGIC INDICATED IN THE RESPECTIVE BAY INTERLOCK LOGICS.

** SOFTWARE INTERLOCKS BUILT IN THE BCU ARE VERIFIED BEFORE CHECKING THE SYNCHRONISATION CONDITIONS. FOR DETAILED INTERLOCKS REFER THE RESPECTIVE BAY INTERLOCK LOGIC DIAGRAMS

*** WHEN BOTH VOLTAGES ARE BELOW THE SET THRESHOLD FOR DEAD VOLTS, A TIMER IS STARTED BEFORE GIVING THE CLOSE SIGNAL TO THE CB. THIS TIMER IS CONFIGURABLE IN THE RANGE 0.2 TO 10 Sec.

1 COMMAND TO THE BREAKER WILL BE SUCCESFUL ONLY IF EXTERNAL HARDWIRED INTERLOCKS IN THE CB CLOSING CIRCUIT ARE SATISFIED.

CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

IMPLEMENTATION OF SYNCHROCHECK IN
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
BCU
EMI-7604PG754-4-028 B 081 082
DF003

IMPLEMENATION OF SYNCHROCHECK FUNCTION IN BCU (TYPICAL FOR ALL BAYS EXCEPT GT BAYS)

CASE -2 DEAD INCOMING VOLTS - LIVE RUNNING VOLTS


IMPLEMENTED IN BCU

SELECTED RUNNING VOLTS > SELECTED


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

RUNNING VOLTS * LIVE VOLTS THRESHOLD

YES
DEAD INCOMING VOLTS TIMER FOR
& LIVE RUNNING VOLTS CONFIRMATION
CONDITIONS SATISFIED? (SETTABLE) ***

SELECTED INCOMING VOLTS < SELECTED


INCOMING VOLTS * DEAD VOLTS THRESHOLD

TO CLOSING
& CIRCUIT
SOFTWARE INTERLOCKS
CLOSE REQUEST FROM
BUILT IN RESPECTIVE BCU
BCU/HMI/SCADA
VERIFIED SUCCESFULLY **

INTLKS IMPLEMENTED THROUGH HARDWIRING


IN BAY CNTL & PROT PANEL

NOTE :

* VOLTAGE SELECTION FOR INCOMING AND RUNNING VOLTS SHALL BE AS PER THE SELECTION LOGIC INDICATED IN THE RESPECTIVE BAY INTERLOCK LOGICS.

** SOFTWARE INTERLOCKS BUILT IN THE BCU ARE VERIFIED BEFORE CHECKING THE SYNCHRONISATION CONDITIONS. FOR DETAILED INTERLOCKS REFER THE RESPECTIVE BAY INTERLOCK LOGIC DIAGRAMS

*** WHEN BOTH VOLTAGES ARE BELOW THE SET THRESHOLD FOR DEAD & LIVE VOLTS, A TIMER IS STARTED BEFORE GIVING THE CLOSE SIGNAL TO THE CB. THIS TIMER IS CONFIGURABLE IN THE RANGE 0.2 TO 10 Sec.

1 COMMAND TO THE BREAKER WILL BE SUCCESFUL ONLY IF EXTERNAL HARDWIRED INTERLOCKS IN THE CB CLOSING CIRCUIT ARE SATISFIED.

CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

IMPLEMENTATION OF SYNCHROCHECK IN
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
BCU
EMI-7604PG754-4-028 B 082 083
DF003

IMPLEMENATION OF SYNCHROCHECK FUNCTION IN BCU (TYPICAL FOR ALL BAYS EXCEPT GT BAYS)

CASE -3 LIVE INCOMING VOLTS - DEAD RUNNING VOLTS


IMPLEMENTED IN BCU

SELECTED RUNNING VOLTS < SELECTED


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

RUNNING VOLTS * DEAD VOLTS THRESHOLD

YES
LIVE INCOMING VOLTS & TIMER FOR
DEAD RUNNING VOLTS CONFIRMATION
CONDITIONS SATISFIED? (SETTABLE) ***

SELECTED INCOMING VOLTS > SELECTED


INCOMING VOLTS * LIVE VOLTS THRESHOLD

TO CLOSING
& CIRCUIT
SOFTWARE INTERLOCKS
CLOSE REQUEST FROM
BUILT IN RESPECTIVE BCU
BCU/HMI/SCADA
VERIFIED SUCCESFULLY **

INTLKS IMPLEMENTED THROUGH HARDWIRING


IN BAY CNTL & PROT PANEL

NOTE :

* VOLTAGE SELECTION FOR INCOMING AND RUNNING VOLTS SHALL BE AS PER THE SELECTION LOGIC INDICATED IN THE RESPECTIVE BAY INTERLOCK LOGICS.

** SOFTWARE INTERLOCKS BUILT IN THE BCU ARE VERIFIED BEFORE CHECKING THE SYNCHRONISATION CONDITIONS. FOR DETAILED INTERLOCKS REFER THE RESPECTIVE BAY INTERLOCK LOGIC DIAGRAMS

*** WHEN BOTH VOLTAGES ARE BELOW THE SET THRESHOLD FOR DEAD & LIVE VOLTS, A TIMER IS STARTED BEFORE GIVING THE CLOSE SIGNAL TO THE CB. THIS TIMER IS CONFIGURABLE IN THE RANGE 0.2 TO 10 Sec.

1 COMMAND TO THE BREAKER WILL BE SUCCESFUL ONLY IF EXTERNAL HARDWIRED INTERLOCKS IN THE CB CLOSING CIRCUIT ARE SATISFIED.

CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

IMPLEMENTATION OF SYNCHROCHECK IN
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
BCU
EMI-7604PG754-4-028 B 083 084
DF003

IMPLEMENATION OF SYNCHROCHECK FUNCTION IN BCU (TYPICAL FOR ALL BAYS EXCEPT GT BAYS)

CASE -4 LIVE INCOMING VOLTS - LIVE RUNNING VOLTS


IMPLEMENTED IN BCU

SELECTED RUNNING VOLTS > SELECTED


This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

RUNNING VOLTS * LIVE VOLTS THRESHOLD

YES
LIVE INCOMING VOLTS & TIMER FOR
LIVE RUNNING VOLTS CONFIRMATION
CONDITIONS SATISFIED? (SETTABLE) ***

SELECTED INCOMING VOLTS > SELECTED


INCOMING VOLTS * LIVE VOLTS THRESHOLD

TO CLOSING
& CIRCUIT
SOFTWARE INTERLOCKS
CLOSE REQUEST FROM
BUILT IN RESPECTIVE BCU
BCU/HMI/SCADA
VERIFIED SUCCESFULLY **

INTLKS IMPLEMENTED THROUGH HARDWIRING


IN BAY CNTL & PROT PANEL

NOTE :

* VOLTAGE SELECTION FOR INCOMING AND RUNNING VOLTS SHALL BE AS PER THE SELECTION LOGIC INDICATED IN THE RESPECTIVE BAY INTERLOCK LOGICS.

** SOFTWARE INTERLOCKS BUILT IN THE BCU ARE VERIFIED BEFORE CHECKING THE SYNCHRONISATION CONDITIONS. FOR DETAILED INTERLOCKS REFER THE RESPECTIVE BAY INTERLOCK LOGIC DIAGRAMS

*** WHEN BOTH VOLTAGES ARE BELOW THE SET THRESHOLD FOR DEAD & LIVE VOLTS, A TIMER IS STARTED BEFORE GIVING THE CLOSE SIGNAL TO THE CB. THIS TIMER IS CONFIGURABLE IN THE RANGE 0.2 TO 10 Sec.

1 COMMAND TO THE BREAKER WILL BE SUCCESFUL ONLY IF EXTERNAL HARDWIRED INTERLOCKS IN THE CB CLOSING CIRCUIT ARE SATISFIED.

2 FOR LIVE CONDITIONS OF BOTH THE INCOMING & RUNNING VOLTS, THE FOLLOWING CONDITIONS(CONFIGURED THROUGH SOFTWARE) ARE CHECKED:

A. DIFFERENCE IN VOLTAGE MAGNITUDES


B. DIFFERENCE IN PHASE ANGLES
C. DIFFERENCE IN FREQUENCIES

CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

IMPLEMENTATION OF SYNCHROCHECK IN
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
BCU
EMI-7604PG754-4-028 B 084 085
DF003

IMPLEMENATION OF AUTO RECLOSE FUNCTION IN BCU (TYPICAL FOR ALL LINE BAYS)
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

IMPLEMENTATION OF
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
AUTORECLOSE FUNCTION IN BCU
EMI-7604PG754-4-028 B 085 086
DF003

IMPLEMENATION OF AUTO RECLOSE FUNCTION IN BCU (TYPICAL FOR ALL TIE BAYS)
This drawing and design is the property of AREVA T&D and must not be copied or lent without prior permission in writing

CLIENT
ADANI POWER LTD.
:
400kV SWITCHYARD FOR 2x330MW THERMAL POWER PLANT
PROJECT :
MUNDRA SEZ

IMPLEMENTATION OF
AREVA REV. SHEET NEXT SH.
AREVA T&D India Limited
AUTORECLOSE FUNCTION IN BCU
EMI-7604PG754-4-028 B 086 /