1. Total voltage drop shuldnot exceed 10v in 3 ph cct and 5.75v in ph ccts
2. current capacity and constant k should be derated as follows. If more than one cct is drown thrugh a conduit.
No.s of ccts 2 3 4 5 6 8
Deratoing Factor 0.8 0.69 0.62 0.59 0.55 0.51
wn thrugh a conduit.
10 12 14
0.48 0.43 0.41
E CURRENT PROTECTION
SINGLE PHASE & DC
K FUSE IN SWG
79 29
108 29
145 25
250 23
400 22
597 20
781 19
1165 18
1535 17
2140 17
3090 14
4500 14
REW REABLE FUSE WIRE H.P KW CURRENT IN AMP
AMP SWG 230 V--1PH
3 38 1/2 0.37 3.72
5 35 3/4 0.55 4.97
8.5 30 1 0.75 6.3
10 29 1 1/2 1.1 9.19
15 25 2 1.5 12.2
17 24 2 1/2 1.8 15
20 23 3 2.2 17.9
24 22 4 3 23.2
29 21 5 4 28.3
32 20 6 4.4
38 19 7 5.2
45 18 7 1/2 5.5
65 17 8 6
78 15 9 7
102 14 10 7.5
12 1/2 9.3
15 11
20 15
25 18.5
30 22
35 26
40 30
45 33.5
50 37
60 45
70 52
75 55
80 60
90 67
100 75
125 90
150 110
175 132
200 150
URRENT IN AMP
400 V--3PH
1.09
1.5
1.92
2.84
3.74
4.62
5.48
7.12
8.7
10.2
11.7
12.4
13.1
14.5
15.9
19.6
23.1
30.1
37.2
44
50.9
57.7
64.5
71.5
85.3
99
106
112
126
139
171
203
233
265