You are on page 1of 7

Blue Star Telepac Air conditioners

SNAP SHOTS OF BSL TELEPAC


RETURN AIR

CONDENSING
UNIT
SUPPLY AIR

EV APORATOR
UNIT
Features
Specially Designed for all ambient conditions
24 x 7 operation
High sensible application
High fluctuating load
High EER
Redundancy at failure
Higher CFM
Specifications
TP1-422
Model TP1- 302 YE TP1-362 YE TP3-362 RE TP3-482 SE TP3-482 RE
YE

2.5 TR 3.0 TR 3.0 TR 3.5 TR 4.0 TR 4.0 TR


Capacity
(1.25 x 2) (1.5 TR x 2) (1.5 x 2) (1.75 x 2) (2 x 2) (2 x 2)

Airflow (CMH/Circuit) 1270 1525 1525 1780 2030 2030

Power Supply 230V/ 1 PH 230V/ 1 PH 415V/ 3 PH 230V/ 1 PH 415V/ 3 PH 415V/ 3 PH

Compressor Rotary Rotary Reciprocatory Rotary Scroll Reciprocatory

Control Micro Computer control

Sensible Cooling / 4725 5400


3375 Kcal/Hr 4050 Kcal/Hr 4050 Kcal/Hr 5400 Kcal/Hr
Circuit Kcal/Hr Kcal/Hr
5250
Total cooling / Circuit 3750 Kcal/Hr 4500 Kcal/Hr 4500 Kcal/Hr 6000 kcal/Hr 6000 kcal/Hr
Kcal/Hr

Note:

Compressor- Y Rotary/ R- Recip / S-Scroll

E-Economy/TP1-Single Phase/ TP3-Three phase


Unit Dimensions

  Indoor Unit Outdoor Unit Total Unit

Width (mm) 665 665 665

Dept (mm) 743 611 743

Height (mm) 939 1064 2111


Micro Controller Features
• Fully programmable
• Complete protection for AC from unhealthy conditions
• All set points programmable from keypad
• Password protection for controller
• Simple 4 key keypad for onsite programming
• 16 Character 2 line back lit LCD display on controller front panel
• Separate alarm contacts for AC 1/ AC2 fail alarm,powerfail
• Automatic display of AC parameters one by one in Run mode
• Status & healthy indication by LEDs on front panel
• Alarm indication by LEDs on front panel
• Room temperature sensing by precise sensor
• Separate outputs for each fan and compressor
• Direct display of line voltage and actual current drawn by compressor
• Direct display of actual room temperature
• Sequencing of compressors for equal run hours, site selectable
• Fault log history( last 5 faults)
• Smoke fire & D.G.sensing
• Automatic timer mode operation if room sensor fails
Thank you