You are on page 1of 1

Transformer O/C Relay TMS calculation.

Transformer KVA 1000


Transformer % impedance 5.5
CT Ratio 100 5
Transformer Voltage ratio 11000 433

HV Side current 52.4864 Max. HV Fault current 954.298


LV Side Current 1333.37 Max. LV Fault current 24243.1

Grading margin 0.154 msec. 0.4tr + 0.15 tr = 10 msec


Tripping time Tr 0.164 msec.
Fault current ratio 18.1818

TMS 0.67564 Characteristic selected is EI.


12/8/2021 19:42 MPRajan