Proposed 2-Storey Residential House

Slab Design Analysis..


Mr. Mrs. Felomino Aguilar
DECEMBER 2008 .
Geenland Subd., Pequena, Conception, Naga City.

DESIGN OF 0NE-WAY SLAB


FOR ROOF DECK FLOOR SLAB - 5 , RDS-5
SERVICE LOAD
SLAB LOAD ANALYSIS

SLAB THICKNESS:
PERIMETER/180
NOTE:Consider largest slab perimeter
slab thickness= 53.33333
say: 100 mm

Fc'= 21.00 MPA


Fy= 276.00 MPA

a.) Dead Load


Load (KPa)

Slab Weight……………………… 2.40


Concrete topping…………………… 0.10 NSCP C101-01
Ceiling Load……………………………… 0.24 VOL.1 / FIFFT EDITION 2001
Utilities………………………………… 0.50
Miscelleneus………………………….. 1.58
Floor Finish ……………………….. 1.53
TOTAL DEAD LOAD 6.35
b.) Live Load , Residential
ROOF DECK SLAB ……………. 7.6 NSCP C101-01
VOL.1 / FIFFT EDITION 2001
FACTORED DEAD LOAD 8.89 KPA
FACTORED LIVE LOAD 12.92 KPA

WU=1.4DL+1.7LL(FACTORED LOAD)
WU= 21.81 KPA

RDS- 5 4.00 M

BEAM

RDS- 5 0.80 M

BEAM

CONSIDER 1000MM STRIPS


M=S/L
M= 0.2 < 0.5
THEREFORE: ONE WAY!

Fc'= 21.00 mpa


Fy= 276.00 mpa
COMPUTED H = 100 MM
CONSIDER 1M STRIP:
WU= 12.49 KN/M
MU= 0.9992 KN.M

d
H= 100 mm

EFFECTIVE DEPTH D
Try diam. Of bars = 12 mm
d = 74 mm

FDC Engineers Contractor Surveyor


Page no._____of_______
Structural Analysis...L.R.Abeleda
Proposed 2-Storey Residential House
Slab Design Analysis..
Mr. Mrs. Felomino Aguilar
DECEMBER 2008 .
Geenland Subd., Pequena, Conception, Naga City.
Mu=ǾFc'bd2w(1-0.59w)
by quadratic eqn.:
a= 0.59
b= -1
c= 0.0096544421
w yeild;
w= 0.0097100705
p=wFc'/Fy
p= 0.0007388097
pmin.=1.4/Fy
pmin. = 0.0050724638
pmax.=0.75pb
pb=0.85ßFc'/Fy(600/600+Fy)
pb = 0.0376526206
pmax. = 0.0282394655
note;check pact. Vs.pmin. Vs pmax.
Use p = 0.0007388097
note; 1.if P is less than Pmin.,decrease thickness of slab.
2.if P is greater than Pmin.,increase thickness of slab.
As = Pbd
As = 375.36231884 mm2
Using diameter of bar = 12 MM
As= 113.094 mm2
spacing = 301.29289575 mm
say 250 mm
check spacing:
1.min.spacing=100mm
2.max. spacing = 3h = 300 mm
or
3.max. spacing = 450 450
therefore: ok! s < 300 mm
ok! < 450 mm
ok! < 301.2929 mm
TEMPARATURE REINFORCEMENT:
FOR FY=276MPA
AST = .0020 BH
AST = 200 mm2
USE DIAM. OF BARS= 10 MM
AST = 78.5375 mm2
SPACING = 392.6875
SAY 290 mm
check spacing:
1.min.spacing=100mm
2.max. spacing = 3h = 300 mm
or
3.max. spacing = 450 450
therefore: ok! s < 392.6875 mm
ok! < 300 mm
ok! < 392.6875 mm
COMPARE AST TO MAIN AS:
FROM ACI CODE,
AST < AS
OK! AST = 200 mm2 < As = Pbd
375.3623 mm2

TYPICAL DETAIL SECTION :

74
100 mm

10 mm TB @ 290 mm
1-WAY SLAB SECTION 12 mm RB @ 250 mm

************** END OF DESIGN *************