You are on page 1of 228

UNISAB II 2.

03

Compressor type: Shop no:

Refrigerant:

Password:

Software version:

03.09
0178_425_en.fm

Instruction Manual
UNISAB II Control
Computerized Control System
for refrigerating compressors

Version 2.03

0178-445 - ENG 1/222


Rev. 03.09
UNISAB II 2.03

Preface
This instruction manual covers reciprocating as This document is produced by:
well as screw compressors, unless otherwise stat- YORK Refrigeration
ed. This manual offers a detailed description of Chr. X’s Vej 201
the UNISAB II control system including function, DK-8270 Hoejbjerg
application, service and trouble shooting. Denmark
Copyright © 2003 YORK Refrigeration

In the space below you can enter the name and address of your local YORK representative:

This document must not be copied without the Be aware of the version number of this manual.
written permission of YORK Refrigeration and the The version number is printed at the bottom of the
contents must not be imparted to a third party nor preceeding page. It is important that this number
be used for any unauthorised purpose. Contra- is identical to the UNISAB II version number ap-
vention will be prosecuted. pearing for a few seconds in the second line of the
This manual is intended for operating and service display when turning on power. It is, however,
personnel. possible to use a manual with higher version
number than UNISAB II. In such cases use the
Please read this manual carefully so that you fully section List of Versions to view the differences.
understand the UNISAB II control system and Never use a manual with lower version number
know how to operate it correctly. Damage occur- than UNISAB II.
ring as a result of incorrect operation is not cov-
ered by YORK Refrigeration‘s guarantee.

2/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

WWarning!
If it is necessary to service UNISAB II control system, the power supply to the compressor motor must
be switched off at the main switch to prevent the compressor from starting up accidentally.
The UNISAB II box contains live parts, which makes it absolutely necessary to comply with the safety
regulations on site.
Failure to do so may cause damage to equipment and affect personal safety. Even though the power
supply to UNISAB II is switched off, some of the terminals may still be live.
Only authorized personnel is permitted to service UNISAB II. If UNISAB II is connected on a network,
always be aware that the compressor can be started from REMOTE. This cannot be avoided solely
by making choices on the UNISAB II display.

Emergency stop
Activate the emergency stop by a light pressure and deactivate it by turning it clockwise. The emer-
gency stop cuts right into the power circuit of the compressor motor guard. Activation of the emergency
0178_425_en.fm

stop during operation will lead to immediate unloading of the motor guard while there is still power on
UNISAB II. In this way it will always be possible to read the state of the compressor.
Whenever the emergency stop is activated during operation, the alarm text COMPR. MOTOR ERROR
will be read on the display. Before compressor restart is possible, deactivate the alarm by means of
the R key and release the emergency stop. PLEASE OBSERVE: If UNISAB II is set on REMOTE or
AUTO, the compressor will restart automatically.

Technical Data

Power supply: Nominal VAC Tolerance Hz

24 +10/-15% 45 - 65

115 +10/-15% 45 - 65

230 +10/-15% 45 - 65

Consumption: 50 VA
Ambient temperature: 0-55° C (during operation)
Humidity: 20-90% relative humidity (not condensing)
Tightness:
IP 54

0178-445 - ENG 3/222


Rev. 03.09
UNISAB II 2.03

4/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

Table of Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Emergency stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Description of UNISAB II control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11


Operating UNISAB II control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Selecting a picture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Display in Bar or °C/R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
The user's own picture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Changing of set values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Application of password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Changing of password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Resetting of password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Procedure for changing of set values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
0178-445TOC.fm

Changing a value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Changing a function, example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Changing a function, example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Contrast (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
SETUP I CONFIG I CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I OIL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I ECONOMIZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I MOTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I MULTISAB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I COP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I MEASURING UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I UNIT/PLANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I FACTORY RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Alarms and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47


Analog alarms and warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Suction gas superheat, alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Auxiliary input signal (4-20 mA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Other alarms and warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Oil system error (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

0178-445 - ENG 5/222


Rev. 03.09
UNISAB II 2.03

Capacity error (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55


PMS error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
No starting permission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Compressor motor error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Compressor motor overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Discharge pressure, overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
High motor temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Oil pump error (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Oil pump error (SAB 80) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Full flow pump error (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Cooling fan error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Oil rectifier error (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Wrong starting number in sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Error in diagnosis - EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting suction pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting discharge pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting brine temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting hot water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting discharge temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
No communication to Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Chiller, alarm from Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Watch the oil pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Vi position error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Evolution, alarm from PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Evolution, warning from PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Evolution, no communication to PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Low lubricating pressure monitoring (screw compressor) . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
1. TIMERS - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
2.TIMER SETUP - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
3. SERVICE COUNTER - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4. DATE - TIME - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5. OIL CHARGING - I (screw compressor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
6. MOTOR FAN I (Frequency controlled screw compressor) . . . . . . . . . . . . . . . . . . . . . . 62
Timer description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Screw compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
7. P BAND FACTOR - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Stop delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Special timers in connection with MULTISAB
Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
8.TRANSFER - I Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
9.TAKE-OVER - I Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
MULTISAB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
1. MULTISAB STATE - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
2. ALL COMPRESSORS - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
3. PARALLEL CONTR. - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

6/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

Compressor regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Control mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Screw compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
PID controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
PID regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Table 9A - Settings - Regulating parameters, Reciprocating compressors . . . . . . . . . . . . 86
Table 9B - Settings - Regulating parameters, Screw compressors . . . . . . . . . . . . . . . . . . 88
Set points on regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Universal regulator (Ext. input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Set point control with current input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Suction pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Brine temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Disch. pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Hotwater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Capacity control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Climatic Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Adjusting slide speed (screw compressors with hydraulic slides) . . . . . . . . . . . . . . . . . . . 97
Capacity slide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Volume ratio slide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Variable Zero position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
0178-445TOC.fm

Corrected capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Automatic setting of new zero point (SAB 202) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Manual setting of new zero point (all types of screw compressors) . . . . . . . . . . . . . . . . . . 99
Built-in spacer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
The alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Zero pos. picture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Electrical slide control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Part load and full load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Calculated Vi position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Change to full load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Change to part load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Position indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Slide brake control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Capacity alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Limiting functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105


Standard limiters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Special limiters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Display indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

Compressor control and surveillance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111


SAB 202, SAB 163H/128H MK3 with oil pump & VMY Mk3 with full flow pump . . . . . . . . 111
SAB 128HR and 163HR with oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
SAB 283, SAB 330 and SAB 355 with oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
SAB 80 with fitted (mechanical) oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
GSV/RWF with oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

0178-445 - ENG 7/222


Rev. 03.09
UNISAB II 2.03

SV 24/26 with oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114


FV 24/26 with oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
FV 19 with oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
VMY Mk 3
without full flow pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
VMY Mk 2 and 2.5 with built-in oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
SAB 110/128/163 Mk 2
without oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
SAB 128/163 Mk 2 Booster with oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
SAB 163 Mk 1 with oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
External starting permission - immediate stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
External starting permission -
normal stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Oil charging, manual (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Motor current measuring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Motor power measuring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
COP set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Thermistor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Aux. output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Capacity down blocked . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Power management system (PMS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Cold store function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Note on screw compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
HP on TWO-STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Oil return (reciprocating compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Oil heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Definition of refrigerant R000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Pressure transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Brine temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Calibration of capacity slide signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Calibration of Vi slide signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Calibration of motor frequency signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Motor current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Hydraulic slide systems
(certain screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Adjusting capacity measuring system for turning transmitter . . . . . . . . . . . . . . . . . . . . . . . . 128
Adjusting Long-Stroke Capacity Rod for SAB 283. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Adjusting Short-Stroke Capacity Rod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Electrical slide systems (certain screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136

Trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137


Diagnosis pictures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
1) Diagnosis I Insp. old alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
2) Diagnosis I Misc. functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
3) Diagnosis I Software version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

8/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

4) Diagnosis I Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140


5) Diagnosis I Digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
6) Diagnosis I Analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
7) Diagnosis I Analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
8) Diagnosis I No of alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
9) Diagnosis I Superuser keyword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
10) Diagnosis I Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
11) Diagnosis I Examine memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
12) Diagnosis J New password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
13) Diagnosis I Power on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
14) Diagnosis I Zero capacity pos. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
15) Diagnosis I COP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Table 11 - Numbering of digital inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Table 12 - Numbering of analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Printed circuit board, light diodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146

Trouble shooting diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149

Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Replacement of door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Replacement of CPU print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Replacement of CPU print and EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
0178-445TOC.fm

Replacement of relay print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160


Replacement of EPROM (program) UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Replacement of serial EEPROM (diagnosis) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Replacement of battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Please note that at the next power failure, the problem will be the same. . . . . . . . . . . . . . 163
Installation of data communication cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
The cable must have the following data: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166

MULTISAB regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
System setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Regulation Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169

Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173

Start and system numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177


- pref. master = COMPR#. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Start and system numbers - pref. master = START# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Example of regulation - screw compressors only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Regulating parameters (for BRINE regulator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Loading sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Unloading sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Operating sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183

0178-445 - ENG 9/222


Rev. 03.09
UNISAB II 2.03

Regulating parameters (for SUCTION PRESSURE regulator) . . . . . . . . . . . . . . . . . . . . . . 184


Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Loading sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Unloading sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Example of regulation - combination of screw and reciprocating compressors . . . . . . . . . . 186
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Regulating parameters (for SUCTION PRESSURE regulator) . . . . . . . . . . . . . . . . . . . . . . 186
Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Loading sequence - sequence A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
State of transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
State of take-over . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Unloading sequence - sequence A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Loading sequence - sequence B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Unloading sequence - sequence B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Practical example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Practical example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Trouble shooting
The plant cannot start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
The plant does not run in sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194

List of Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197

Spare parts for UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209

Supplementary Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213

10/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

1. Description of UNISAB II control


The purpose of the UNISAB II control system is to Other possibilities:
monitor, protect, control and regulate reciprocat- • UNISAB II can be configured to run as a
ing and screw compressors. Both the control box chiller controller.
and the electrical components have been con-
nected from the factory. Thus, only a few connec- • By inserting an optional communication
tions are necessary to link the components to the print, UNISAB II can be configured to com-
electrical installations on site. municate with

UNISAB II is programmed according to the type of a PLC, the configuration by the name EVO-
compressor it is going to controls. See section LUTION
Configuration. one or more Quantum compressor control-
UNISAB II contains different ways of control- lers also manufactured by
ling/regulating compressor capacity according to YORK Refrigeration.
pressure levels or temperatures. Compressor ca- The above points are described in separate man-
pacity can be regulated both manually and auto- uals, only the configuration is included in this man-
matically. ual.
0178_426_en_2.02.fm

Furthermore, a number of limiting functions have UNISAB II is operated by means of a front panel
been incorporated. In periods of overloading as shown in the following drawing. The front panel
these limiting functions will intervene and limit is well-arranged with only a few keys and a distinct
compressor capacity until the situation has re- display.
turned to normal. Consequently, the number of The subsequent description refers to the numbers
undesirable operational stops will be reduced as in the drawing. On delivery UNISAB II is preset
well as the need for supervision. with a number of factory values and is thus ready
Compressors fitted with UNISAB II CONTROL for operation. Therefore, only a few adjustments
can be linked via the built-in communication sys- are necessary to adapt the UNISAB II system to
tem, MULTISAB. In this way compressors can its actual use. For this purpose, use the enclosed
work in a common refrigerating system, thus opti- leaflet Quick Reference.
mizing the operation of the entire compressor UNISAB II is constructed not to lose its preset or
plant. changed values in case of a temporary power fail-
The communication system makes it possible ure. UNISAB II is fitted with a battery, which is
also to connect UNISAB II with a PLC or PC cen- used by the built-in timer so that time and date are
tral monitoring, control and data logging system. always correct even though current has been dis-
UNISAB II can be linked to and communicate with connected. The hour counter and any stored
old SABROE control units such as PROSAB II alarm values will thus maintain the correct time.
and UNISAB S/R/RT/RTH.

0178-445 - ENG 11/222


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

Fig. 1.1 UNISAB II front panel

10 9 8 7 3 4 2 5 6 1 11 13 12 14 15

Suct.temp. -25°C
Disch.temp. 38°C
Oil press. 4.3 bar
Ready 0%

Operating UNISAB II control Fig. 1.2 Drawing of plugs and their positions

Start-up
On delivery all electrical components in the com-
UNISAB II
pressor are connected to UNISAB II. On site it is
only necessary to add the correct supply voltage
from the local installations. The electric wiring
must be carried out according to the wiring dia-
grams for UNISAB II at the end of this manual.

Note in particular
a. that no outside voltage must be applied to the
digital inputs of UNISAB II.

b. that the code plug for the supply voltage must 230 VAC 115 VAC
be correct compared to the local supply volt-
Also check that the 3 Amp fuse is in good working
age. (see Fig. 1.2)
condition.

12/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

Fig. 1.3 Drawing of fuses and their positions points is carried out via the display. The display
contains a number of different pictures.
The control panel is usually closed and locked
with a screw at each end of the panel.
1 2 3 By turning the screws half a turn the control panel
3 Amp is loosened and can be lifted to an open position,
Here, it is fastened to the cabinet (see Fig. 1.4).
UNISAB II
Fig. 1.4 Opening the cabinet

UNISAB II

Before any voltage is applied to UNISAB II, the


emergency stop switch will be activated.
0178_426_en_2.02.fm

UNISAB II

When voltage is applied to UNISAB II, the follow-


ing Main picture will appear in the display, and
UNISAB II will be ready for operation.
SUCT.PRESS 0,0 BAR

DISCH.PRES 0,0 BAR In this way it is still easy to operate the control
MOTOR CURR 0A panel. At the same time easy access to the cabi-
STOPPED 0% net interior is obtained.
When UNISAB II is open, it is still fully opera-
UNISAB II has been programmed with values for tional.
warning limits, alarm limits, set points, etc. This
makes it possible to start up the compressor im-
Display
mediately.
Pos. 1 Has a constant background illumina-
However, some of the values must always be tion and displays 4 lines each with 20
adapted to the actual operating situation. For this characters. The contrast has been
purpose use the enclosed leaflet Quick Refer- factory set, but can be adjusted if re-
ence. It is also recommended to read this manual quired. See subsection Contrast
carefully to acquire a thorough knowledge of how (display) in section Languages.
to operate UNISAB II. Pressure levels, temperatures, set
points as well as warning and alarm
UNISAB II is operated exclusively by means of the
limits can be read in the display.
front panel keys. Reading of operating conditions
as well as changing of limiting values and set

0178-445 - ENG 13/222


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

Front panel is not possible to change to automat-


ic. See section Control Mode.
The UNISAB II front panel is divided into two sec-
tions: Pos. 8 D Key used to acknowledge alarms.
The control section, pos. 2 to 10, by means of Pos. 9 E Loading of capacity during manual
which the compressor is controlled. operation. On screw compressors
The recording section, pos. 11 to 15, by means the slide moves towards higher ca-
of which menu pictures are selected and values pacity as long as the key is held
changed. down. On reciprocating compressors
Control section: a new capacity stage is loaded every
time the key is pressed.
Pos. 2 Green lamp indicating whether the
compressor is running. At start-up Pos. 10 F Unloading of capacity during man-
ual operation. On screw compres-
this lamp will flash until UNISAB II
sors the slide moves towards lower
has received feedback from the mo- capacity as long as the key is held
tor starter. At the same time the text down. On reciprocating compressors
"STARTING" (lamp flashes) and one capacity stage is unloaded every
"OPERATING" (lamp light steady) time the key is pressed.
can be seen in the bottom line of an
operating picture. Recording section

Pos. 3 Yellow lamp indicating whether the Pos. 11 The G key has several functions.
state of operation is automatic or When pressing the G key, a change
manual. Yellow light = manual op- will be made between Bar (PSI) and
eration. °C/R (°F/R) for saturated vapours
Pos. 4 Red lamp indicating warning or when the display shows a suction or
alarm. discharge pressure.
Slow flashes = warning; Changing the set values can only be
Quick flashes = alarm. carried out by using the password
Pos. 5 A Compressor start at manual shown on page 1 in the instruction
operation by pressing the key once. manual for the UNISAB II in ques-
Works only if yellow lamp pos. 3 is lit. tion.
Pos. 6 B Compressor stop at manual oper- As to the encoding of a password,
ation by pressing the key once. see section Changing Set Values.
Works only if yellow lamp pos. 3 is lit. Pos. 12 H Used for moving left in the menu
Pos. 7 C A change between manual system. Used for selecting pictures
(yellow lamp on) and automatic or a digit when changing a value.
(yellow lamp off) takes place by Pos. 13 I Used for moving right in the menu
pressing the key once. system. Used for selecting pictures
Please note that if manual was se- or a digit when changing a value.
lected from the CONTROL menu, it

14/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

Pos. 14 J Used for moving upwards in a pic- Menu structure


ture in order to point at a certain val-
UNISAB II includes a number of different pictures
ue, or when changing to a higher val-
ue. on compressor operation, set values, configu-
ration, etc. These pictures are built up in a menu
Pos. 15 K Used for moving downwards in a system in which a certain picture can be selected
picture in order to point at a certain by means of the arrow keys.
value, or when changing to a lower Fig. 5.1-3 show the structure and the number of
value. pictures in the menu systems for:
- Screw compressors
- One-stage reciprocating compressors
- Two-stage reciprocating compressors.
0178_426_en_2.02.fm

0178-445 - ENG 15/222


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

Fig. 1.5
UNISAB II - Ver. 2.02/2.03 I PARAMETER SETTING
Menu Tree HIGH ALARM
HIGH WARN.
°C/R
°C/R
Screw Compressor Suction LOW WARN. °C/R
SUCT.PRES. °C/R LOW ALARM °C/R
SUCT.TEMP. °C ACTUAL SP. °C/R
SUCT.SUPERH. °C SETPOINT 1 °C/R
RUNNING 100% SETPOINT 2 °C/R
NEUTRALZONE °C/R
PROP.BAND °C/R
T.INT. SEC
T.DIFF. SEC
Discharge P.PART %
I.PART %
DISCH.PRES. °C/R D.PART %
DISCH.TEMP.DI °C REG.OUTPUT %
SCH.SUPERH. °C
RUNNING 100%

Oil
Multisab state
OIL PRES. BAR
DIFF.PRES. BAR START NO.
OIL TEMP. °C SYSTEM NO.
RUNNING 100% SYS.CONTROLLER
RUNS BY ITSELF
Motor
MOTOR CURR 0A All compressors
MOTOR POWER 0 kW
MOTOR FREQ 0 RPM COMPR. # 01 MANUAL
Main picture Main menu READY 0% SYSTEM # 01
START # 01 J
RUNNING 100%
SUCT.PRES. °C/R SUCTION BRINE
DISCH.PRES. °C/R DISCHARGE ALARM Brine
MOTOR CURR A OIL WARNING Timers
RUNNING MOTOR SETUP BRINE TEMP. °C
100% SUCT.BRINE °C/R START START SEC
EXT.INPUT STOP START SEC
RUNNING 100% START DELAY SEC
STOP DELAY SEC
Alarms Control
NO ALARMS Service-timers
COMPRESSOR CTRL.
ON TIME HOUR
SINCE START
MANUAL

Warnings Multisab Date-time


NO WARNINGS MULTISAB HOUR
MIN
K
MULTISAB STATE SEC
ALL COMPRESSORS DAY
PARALLEL CONTR.
Dig. input
Setup Timers D.INPUT
D.INPUT
CONTROL CALIBRATE TIMERS D.INPUT
MULTISAB CAPACITY TIMERS D.INPUT
TIMERS CONFIG TIMER SETUP
DIAGNOSIS LANGUAGE SERVICE TIMERS Dig. output
D.OUTPUT
D.OUTPUT
Capacity Diagnosis D.OUTPUT
CAPACITY 0% DIAGNOSIS D.OUTPUT
CAP POS 0% INSPECT OLD ALARMS Analog. input
VI POSITION 0% MISC.FUNCTIONS
READY 0% PRES. INP 1
SOFTWARE VERSION
PT 100 INP 1
Calibrate EXT.
CALIBRATE
PRESS TRANSDUCER 4-20 MA input
BRINE TEMP. 4 MA
CAPACITY 20 MA

CAPACITY SETPOINT
Config.
CONFIG Auxiliary output
CONTROL
COMPRESSOR AUXILIARY OUTPUT
OIL SYSTEM ACTIVE WHEN
AT MAX.CAP

Language
CONTRAST
LANGUSGE GB
H

16/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

Fig. 1.6
I PARAMETER SETTING
Suction HIGH ALARM °C/R
HIGH WARN. °C/R
SUCT.PRES. °C/R LOW WARN. °C/R
SUCT. TEMP. °C LOW ALARM °C/R
SUCT.SUPERH. °C ACTUAL SP. °C/R
RUNNING 100%
UNISAB II - Ver. 2.02/2.03 SETPOINT 1
SETPOINT 2
°C/R
°C/R
NEUTRALZONE °C/R
Menu Tree PROP.BANDD °C/R
One-stage Discharge
Reciprocating Compressor DISCH.PRES. °C/R
°C
DISCH. TEMP.
DISC.SUPERH. °C
RUNNING 100% Multisab state
START NO.
SYSTEM NO.
Oil SYS. CONTROLLER
NOT MY TURN
SUCT.PRES. BAR
OIL PRES. BAR
OIL TEMP. °C All compressors
RUNNING 100%
COMPR. # 01 MANUAL
Motor SYSTEM # 01
MOTOR CURR 0A START # 01
MOTOR POWER 0 kW RUNNING 100%
MOTOR FREQ 0 RPM

Main picture Main menu


READY 0%
Timers J
SUCT.PRES. °C/R SUCTION BRINE START START SEC
DISCH.PRES. °C/R DISCHARGE ALARM STOP START SEC
Brine START DELAY SEC
MOTOR CURR A OIL WARNING
RUNNING 100% MOTOR SETUP STOP DELAY SEC
BRINE TEMP. °C
SUCT.PRES. °C/R
EXT.INPUT
0178_426_en_2.02.fm

RUNNING 100%
Service timers
ON TIME HOUR
SINCE START
Alarms Control
COMPRESSOR CTRL.
NO ALARMS
Datetime
HOUR
MANUAL MIN
SEC
DAY
Warnings Multisab K
MULTISAB
NO WARNINGS
Dig. input
MULTISAB STATE
ALL COMPRESSORS D. INPUT
PARALLEL CONTR. D. INPUT
D. INPUT
D. INPUT
Setup Timers
CONTROL CALIBRATE TIMERS Dig. output
MULTISAB CAPACITY TIMERS
TIMER SETUP D. OUTPUT
TIMERS CONFIG D. OUTPUT
DIAGNOSIS LANGUAGE SERVICE TIMERS
D. OUTPUT
D. OUTPUT
Capacity Analog input
Diagnosis
CAPACITY 0%
NOT USED 0% DIAGNOSIS PRES. INP 1
NOT USED 0% PT 100 INP 1
INSPECT OLD ALARMS
READY 0% MISC. FUNCTIONS EXT.
SOFTWARE VERSION
4-20 MA input
Calibrate 4 MA
CALIBRATE 20 MA
PRESS TRANSDUCER CAPACITY SETPOINT
BRINE TEMP.
CAPACITY
Auxiliary output
Config. AUXILIARY OUTPUT
ACTIVATE WHEN
CONFIG. AT MAX.CAP
CONTROL
COMPRESSOR
OIL SYSTEM

Language
CONTRAST
H LANGUAGE GB

0178-445 - ENG 17/222


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

Fig. 1.7
I PARAMETER SETTING

Suction
-
UNISAB II Ver. 2.02/2.03 SUCT.PRES.
SUCT.TEMP.
°C/R
°C
HIGH ALARM
HIGH WARN.
°C/R
°C/R
LOW WARN. °C/R
Menu Tree SUCT.SUPERH. °C LOW ALARM °C/R
RUNNING 100% ACTUAL SP.
Two-stage reciprocating com- SETPOINT 1
°C/R
°C/R
pressor SETPOINT 2
NEUTRALZONE
°C/R
°C/R
Discharge PROP.BAND °C/R
DISCH.PRES. °C/R
DISCH.TEMP. °C
DISCH.SUPERH. °C
RUNNING 100%

Multisab state
Oil
START NO.
SUCT.PRES. BAR SYSTEM NO.
OIL PRES. BAR SYS. CONTROLLER
OIL TEMP. °C
RUNNING 100%
J
Motor All compressors
MOTOR CURR 0A COMPR. # 01 MANUAL
MOTOR POWER 0 kW SYSTEM # 01
MOTOR FREQ 0 RPM START # 01
READY 0% RUNNING 100%
Main picture Main menu
SUCH.PRES. °C/R SUCTION INTERMED Timers
DISCH.PRES. °C/R DISCHARGE ALARM Intermed.
MOTOR CURR A OIL WARNING START START SEC
RUNNING 100% MOTOR SETUP INTERM.PRES. °C/R STOP START SEC
INTERM.TEMP. °C/R START DELAY SEC
EXT.INPUT STOP DELAY SEC
RUNNING 100%
Service timers
Alarms Control ON TIME HOUR
NO ALARMS
COMPR.CTRL MODE
SINCE START
K
MANUAL Date-time
HOUR
MIN
Warnings Multisab SEC
DAY
NO WARNINGS MULTISAB
ALL COMPRESSORS
PARALLEL CONTRS Dig. input
D.INPUT
D.INPUT
Setup Timers D.INPUT
D.INPUT
CONTROL CALIBRATE TIMERS
MULTISAB CAPACITY TIMERS
TIMERS CONFIG. TIMER SETUP Dig. output
DIAGNOSIS LANGUAGE SERVICE TIMERS
D.OUTPUT
D.OUTPUT
D.OUTPUT
Capacity Diagnosis D.OUTPUT
DIAGNOSIS
CAPACITY 0% 4-20 MA input
NOT USED 0% INSPECT OLD ARLAMS
NOT USED 0% MISC. FUNCTIONS PRES. INP 1
READY 0% SOFTWARE VERSION PT 100 INR 1

EXT.
Calibrate
CALIBRATE 4-20 MA input
PRES. TRANSDUCER 4 MA
BRINE TEMP. 20 MA
CAPACITY
SUCT. PRES.
Config. Auxiliary output
TYPE AUXILIARY OUTPUT
REFRIGERAN ACTIVATE WHWN
CONTROL ON AT MAX. CAP
VOLUME RATIO.

Language
CONTRAST
H LANGUAGE GB

18/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

In the menu tree the selection of pictures is carried


out by means of the arrow keys in the recording HIGH ALARM XX
panel. HIGH WARNING XX
LOW WARNING XX
The H and I keys make it possible to move to the
LOW ALARM XX
left or the right in the menu tree by pressing the
keys .
The J and K keys make it possible to move up ACTUAL SP XX
and down in the menu picture by moving the dark SETPOINT 1 XX

cursor from line to line. SETPOINT 2 XX


NEUTRAL ZONE XX
PROP. BAND XX
Selecting a picture T.INT. XX

On delivery UNISAB II will display the following T.DIFF. XX


P.PART XX
Main picture when voltage is applied.
I.PART XX
SUCT.PRESS 0.0 BAR D.PART XX
DISCH.PRES 0.0 BAR
REG. OUTPUT XX
MOTOR CURR 0A
0178_426_en_2.02.fm

BLOCKED 0%

It is always possible to return to this picture by Note: The items from NEUTRAL ZONE and
pressing the H key. downwards are only shown when the suction
pressure unit of measure is °C/R. See below for in-
To see Set point 1 for suction pressure regula-
formation on how to change the unit.
tor, do as follows:
Press K until the cursor is at the desired line, SET
With the Main picture in the display, press I
POINT 1, which is read.
Press H until the Main picture appears.
SUCTION BRINE
DISCHARGE ALARM To see the set value for the timer START-DELAY,
OIL WARNING do as follows:
MOTOR SETUP
With the main picture in the display, press I

Press I
SUCTION BRINE
DISCHARGE ALARM
SUCT.PRESS XX
OIL WARNING
SUCT.TEMP XX
MOTOR SETUP
SUCH.SUPERH. XX
BLOCKED X
Press K until the cursor is at SETUP.

Press I Press I

0178-445 - ENG 19/222


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

POS.NO

CONTROL CALIBRATE 19 DISCH. OVERL. XX

MULTISAB CAPACITY 20 CURR OVERLD. XX

TIMERS CONFIG 21 MOTOR START XX

DIAGNOSES LANGUAGE 22 PMS FEEDBACK XX


23 FULL FLW M. XX
Press K until the cursor is at TIMERS. 24 OIL PUMP M. XX
25 RECT. START XX
Press I
26 RECT DELAY XX
27 RECT DISABLl XX

TIMERS 28 START HP XX

TIMERS 29 NO CHILLER XX

TIMERS SETUP 30 CAP. NEGATIVE XX

SERVICE TIMERS 31 START UNLOAD XX

DATE-TIME 32 LOW SUCT. PRESS. XX

OIL CHARGING 33 LUBR.PRESS. XX

MOTOR FAN 34 Vi-PAUSE XX

PBAND FACTOR
TRANSFER
TAKE-OVER This example applies to screw compressors.
Press K until the cursor is at the desired timer
Press K until the cursor is at START-DELAY.
TIMERS SETUP.
Press H until the Main picture appears.
Press I

Display in Bar or °C/R


POS.NO
Refrigerant pressure levels as eg suction pres-
1 START START XX
sure, discharge pressure or intermediate pressure
2 STOP START XX
can be displayed in either Bar or°C/R. It is possible
3 START DELAY XX
to switch between these two units when the cursor
4 STOP DELAY XX
5 SUCTION RAMP XX
is at the relevant value by briefly pressing the G
6 SLIDE MAX. XX key.
7 PRELUB XX To see suction pressure in °C/R, first select the
8 OIL FLOW XX
picture with SUCT. PRESS. With the cursor on
9 FLOW DELAY XX
SUCT. PRESS, briefly press G and the unit dis-
10 NO OIL FLOW XX
played will change from Bar to °C/R or vice versa.
11 LUBRIC.TIME XX
12 DIF.PRES. OK XX Pressure levels displayed in °C/R are dew point
13 OIL PRES LO XX values.
14 OIL PRES HI XX
15 OIL TEMP. LOW XX
16 OIL TTEMP. HIGH XX
The user's own picture
17 SUPERH. LOW XX As it appears from the menu tree, there is a whole
18 SUPERH. HIGH XX range of operating pictures in UNISAB II. Howev-

20/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

er, if no suitable combination of measuring values


can be found in the same picture, a new picture DISC. PRESS XX
can be constructed. MOTOR CURR XX
OIL TEMP XX
Thus, it is possible to compose a standard picture
READY X
appearing in the display.
If the Main picture is required to include eg OIL
PRESS instead of SUCT. PRESS, proceed as fol- Before changing the main picture, it is recom-
lows: mended to plan how to compose the picture and
Press H until the Main picture appears. in which sequence the values should appear.
Please note that the new value is entered into line
3 and that the value in line 1 disappears.
SUCT.PRESS 0,0 BAR
DISCH.PRES 0,0 BAR If SUCT. PRESS is to appear again in the main
MOTOR CURR 0A picture, proceed as follows:
BLOCKED 0%
Press H until the Main picture appears.

Press I and next K until the cursor reach OIL. DISC. PRESS XX
0178_426_en_2.02.fm

MOTOR CURR XX
OIL TEMP XX
SUCTION BRINE READY X
DISCHARGE ALARM
OIL WARNING
MOTOR SETUP
Press I and again I until

Press I SUCT.PRESS XX
SUCT.TEMP XX
SUCT.SUPERH XX
OIL PRESS XX BLOCKED X
DIFF.PRESS XX
OIL TEMP XX
READY X
By a quick pressure on G it is possible to switch
between Bar and °C/R.

Press and keep G until the cursor covers the Press G , until the cursor covers the entire line.
whole line. OIL PRESS and value are moved to SUCT. PRESS and value are moved to line 3 in
line 3 in the main picture and SUCT. PRESS, line the main picture and DISCH.PRES in line 1 has
1, has disappeared from the main picture. disappeared from the picture:

Press H until the Main picture appears.

0178-445 - ENG 21/222


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

MOTOR CURR XX Using the H I and K J keys, enter the correct


OIL PRESS XX password.
SUCT.PRESS XX
Press G and the password will be open for 60
READY X
minutes for changing of values.

Changing of set values Changing of password


The set values in UNISAB II can be changed by
On delivery the UNISAB II password is set for a
means of the keys G H I K J
standard four-figure password. All
YORK Refrigeration companies and agents are
Password able to inform of this standard password.
To safeguard against unwanted changes of the It is possible to change this standard password to
set values, a password must be used before the a personal password.
change can take place.
Please note that not more than one password can
When a password has been entered, the system be used at a time.
will be open for 60 minutes. During this period it is
Change the password in menu:
possible to change the system values before it
SETUP I DIAGNOSIS I NEW
closes again.
PASSWORD
If the system is required to close earlier, press H
until the main picture appears. By pressing H
once more the system will close.
NEW PASSWORD
Passwords are required for changing CONFIG,
TIMERS, ALARMS, WARNINGS as well as REG- RESET PASSWORD
ULATING PARAMETERS.

Application of password
With the cursor on NEW PASSWORD, press the
When the set value to be changed appears in the
G key and enter the current password, cf section
display and has been marked by the cursor, press
Application of password.
G for approx 2 seconds till the following picture
appears: It is now possible to enter a personal password by
changing the current (shown) password to the one
chosen. The password can be set anywhere be-
tween 0001 and 9999.
PASWORD
1 2 3 4
NEW PASSWORD
SET TO ACCEPT / QUIT
+09999
RESET PASSWORD

22/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

Important! • Changing of functions


It is essential to remember the changed password (compressor type, regulators, etc.)
as any changes of the set values will require the
application of the personal password. The stand- Changing a value
ard password, of which it is possible to be in-
To change the alarm value for
formed by contacting YORK Refrigeration, is no
LOW SUCTION PRESSURE, do as follows:
longer applicable.
• From the main picture, press I until this pic-
ture appears:
Resetting of password
In case the password has been changed to a per-
sonal password and this is no longer known, it is SUCT.PRESS XX
SUCT.TEMP XX
possible to get a special password by contacting
SUCT.SUPERH XX
YORK Refrigeration. This password must be used
READY X
to reset the personal password to
YORK Refrigeration's standard password. • Select Bar or °C/R by a quick pressure on
The password is reset to the standard password in G.
the menu: SETUP I DIAGNOSIS I NEW PASS- • Press I until the following picture appear:
0178_426_en_2.02.fm

WORD

HIGH ALARM XX
HIGH WARNING XX
NEW PASSWORD LOW WARNING XX
LOW ALARM X
RESET PASSWORD
NO ACTUAL SP XX
ETC

• With the K key move the cursor to LOW


With the cursor on RESET PASSWORD, press
ALARM.
the G key, then enter the special password. See
section Application of password. • Press G . Enter password if not already
open (see section Application of password)
It is now possible to reset the personal password-
to the standard password by changing NO into • The cursor is now moved to the first digit,
YES by pressing the G key followed by the H eg 0 as shown in the picture.The signs "+" or
key. "-" may be seen in front of the digit.

Procedure for changing of set values HIGH ALARM XX


HIGH WARNING XX
There are two types of changes:
LOW WARNING XX
• Changing of values LOW ALARM -0,3 BAR
(alarms, set points, etc.)

0178-445 - ENG 23/222


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

• Using the arrow keys H I K J, enter the •


new value, eg - 0.5 BAR. COMPRESSOR CONTROL
AUTO
• Press G - the cursor moves to LOW
ALARM, and enter the new value.
• Using the K J keys, change between
HIGH ALARM XX STOPPED-MANUAL-AUTO-REMOTE.
HIGH WARNING XX
• Press G to confirm.
LOW WARNING XX
LOW ALARM -0,5 BAR
Changing a function, example 2
• It is now possible to change other values If required to change the regulating function to
during the 60 minutes the password is open. BRINE regulation, do as follows:
• From the Main picture, press I once.
Changing a function, example 1
• With K, move the cursor to SETUP.
To change the state of operation from AUTO to
REMOTE, proceed as follows: • Press I once more
CONTROL
• From the Main picture, press I once.
• With the K key, move the cursor to CONFIG
SETUP.
• With K, move the cursor to CONFIG.

SUCTION
• Press I once more
CONFIG
CONTROL
SETUP COMPRESSOR
OIL SYSTEM
• Press I once.
CONTROL • Press I once more.
CONTROL ON SUCTION
AUTO START YES
AUTO STOP YES
COLD STORE NO
• Press I once.
COMPRESSOR CONTROL • Press G for approx 2 seconds and enter
AUTO the password, if necessary. The cursor
moves to the text at the right side of the line.

• Press G and the cursor moves to the next


line.
CONTROL ON SUCTION

24/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

• With the J K keys, it is now possible to Select G to confirm.


change between: Press H and FACTORY RESET is carried out.
SUCTION - BRINE - DISCHARGE - HOT
UNISAB II is now restored to its Factory setting.
WATER - EXT. COOL - EXT. HEAT.
• Press G to confirm. In the same way other
Languages
functions may be changed by using the cur-
sor to point them out. When selecting the menu LANGUAGE, the fol-
lowing picture will appear:

Factory settings
CONTRAST 50
On delivery UNISAB II is programmed with facto-
LANGUAGE GB
ry settings for all values such as: Alarms, Warn-
ings, Timers, Set points. These values are stated
in tables for reciprocating and screw compressors Contrast (display)
respectively. The contrast setting of the display takes place au-
tomatically, but it is still possible to make a manual
See tables 1, 2, 3, 4 and 5 in section Alarms and
adjustment.
warnings, tables 7 and 8 in section Timers and ta-
0178_426_en_2.02.fm

bles 9A, 9B and 9C in section Compressor regu- The contrast of the display is adjusted in the main
lation. menu or any other menu in the following way:
Press the alarm button and K = darker contrast
Although other values may have been entered af-
(lower contrast value) or the alarm button and J =
ter delivery, it is always possible to return to the
lighter contrast (higher contrast).
factory settings in the following way:
The value is changed just like any other parame-
For safety reasons, first make sure the compres-
ter and has an adjusting area from 20-80.
sor is stopped.
The value 20 gives a dark display.
From the main picture, press I once.
The value 80 gives a light display.
With K, move the cursor to SETUP.
Press I once to the picture CONTROL. Changes can be made during compressor opera-
Press I once more to COMPRESSOR CON- tion. The contrast setting for the best display lies
TROL. usually between 30 and 50.
Press G to move the cursor to the second line. The contrast can be adjusted from any menu pic-
Press J until STOPPED appears. ture by using the keys D and J or K.
Press G to confirm.
Important!
Carry out factory reset: A setting within the minimum (20) or maximum
Press H to CONTROL and K to CONFIG. and I (80) area may cause a dimming of the display text.
to CONTROL. With K move the cursor to FACTO- However, it is usually still possible to read the text
RY RESET. Press I to Factory Reset menu. by means of a heavy illumination and by viewing
from an angle of approx 20 degrees. Should this
Press G and the cursor moves to the right. Enter
not be possible - ie the display is impossible to
password if not open. Select YES by means of J .
read - carry out a "blind operation" as follows:

0178-445 - ENG 25/222


Rev. 03.09
UNISAB II 2.03
1. Description of UNISAB II control

1.Make sure you are in the Main picture, if neces- F = French


sary by switching the UNISAB II off/on. E = Spanish
DK = Danish
2. Press the following keys, one time each, and in
D = German
the following order: I, J, I J and I (see
CZ = Czech
Fig. 1.5),
S = Swedish
3.Keep G pressed for 5 seconds.
RUS = Russian
4.Press J and/or K. The contrast of the display PL = Polish
should now change gradually, possibly to the oth- P = Portuguese
er extreme. However, it should be possible to se- NL = Dutch
lect a reasonable value (40 or the like). See also I = Italian
section Procedure for changing of set values. N = Norwegian
H = Hungarian
Languages GR = Greek
Like any other function setting (see section Proce- TR = Turkish
dure for changing set values), the language can
be changed to any of the following, even when the
compressor is running: When UNISAB II is switched on for the first time or
GB = English when a program RESET has been performed, the
FIN = Finnish set language will be English (GB).

26/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

2. Configuration
adjusted. This is quite normal. RELEASE the
UNISAB II can be configured to a number of differ- emergency stop.
ent functions depending on compressor type, re- Changes in the points that will lead to the above
frigerant, etc. Some of the settings have already situation are marked with ** in the following con-
been made by the factory, but it will always be figuration table.
necessary to make some final settings before The configuration points are common for 1) recip-
start-up. rocating and 2) screw compressors and their use
The immediate configuration can always be is marked in the list.
checked during operation, BUT if one or more The configuration points have been divided into
configuration points have to be changed, always sub-menus available from the menu SETUP I
STOP the compressor and activate the emergen- CONFIG.
cy stop while making the changes.
After changing the configuration, the first pressure
CONFIG
on H will in some cases display the following pic- CONTROL
ture: COMPRESSOR
OIL SYSTEM
0178_427_en_2.02.fm

ECONOMIZER
MOTOR
CONFIGURATION MULTISAB
CHANGED COP
RESTARTING COMMUNICATIONS
- PLEASE WAIT MEASURING UNIT
UNIT/PLANT
FACTORY RESET
Wait a few seconds - the main picture will appear
and UNISAB II will be reconfigured. At this stage In case of a screw compressor, the sub-menus
the picture may be dark as the contrast is being are composed as follows:

0178-445 - ENG 27/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

SETUP I CONFIG I CONTROL SETUP I CONFIG I MULTISAB


3 CONTROL ON SUCTION 11 PREF. MASTER COMPR#
5 AUTO START YES 15 COMMON EVAP/COND N/N
6 AUTO STOP YES 16 HP ON TWO STAGE NO
21 COLD STORE NO 31 TAKE OVER NO
22 CLIMA COMP NO

SETUP I CONFIG I COP


SETUP I CONFIG I COMPRESSOR 30 COP ACTIVE NO
1 TYPE SMC106E 36 FLOW FACTOR .20 l/pls
20 SWEPT VOLUM 400m3/h 37 LIQ. SUBCOOL 3.0 C
9 BOOSTER NO
4 VOLUME RATIO MAN
12 ECONOMIZER NO
SETUP I CONFIG I
27 MECH. ZERO NO
28 MANUAL ZERO 0.0%
COMMUNICATIONS
34 VI MODE 70.0% 38 DANBUSS YES

23 ADD. UNLOAD NO 10 COMPR. NO 1


24 BAUD RATE 19200
29 PORT1 EVOL. FX2N
SETUP I CONFIG I OIL SYSTEM 39 NODE NO 0
7 PRELUBRICATION NO 40 BAUD RATE 9600
8 FULL FLOW PUMP NO 41 PORT 2 QUANTUM
18 OIL COOLING NONE 42 NODE NO 77
17 WATER COOLED NO 43 BAUD RATE 1200
25 OIL RECTIFIER NO 50 PROFIBUS YES
51 NODE NO 3

SETUP I CONFIG I ECONOMIZER 52 BAUD RATE 12M

13 ECO. LO. CAP 0.0%


14 ECO. HI. SUCT. TEMP 0.0 C/R SETUP I CONFIG I MEASURING
UNIT
26 PRESS/TEMP BAR/C
45 PRESS -1/9-1/25

SETUP I CONFIG I MOTOR 44 MOTOR SIGNAL kW


53 MOTOR INPUT 4-20 mA
19 RANGE MOTOR CUR. 1200 A
54 CAP/FREQ CAP.POS
47 RANGE MOTOR kW 1000 kW
35 MOTOR SIZE 500 kW
46 ROTATUNE YES SETUP I CONFIG I UNIT/PLANT
48 MIN FREQ 1000 RPM 2 REFRIGERANT R22
49 MAX FREQ 6000 RPM 32 CHILLER NO

28/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

SETUP I CONFIG I FACTORY RESET • Use the H I and J K keys to enter the
33 FACTORY RESET NO new configuration.
• Press G to confirm.
• With J or K move the cursor to the next
value to be changed.
Carry out configuration as follows:
• When finished changing the values, use H
• Select the picture SETUP, move the cursor to quit the sub-menu and thereby to activate
to CONFIG. and press I once. the possible changes, which will make
• Move the cursor with K and J to the rele- UNISAB II restart.
vant sub-menu and press I . The following table (cf next page) gives a descrip-
• Move the cursor with K to the function that tion of each configuration point as well as possible
is going to be changed. choices with reference to the position numbers in
the previous pictures.
• Press G and enter password if not already
open.

CONFIGURATION
0178_427_en_2.02.fm

No Function for Possible choices

*1* TYPE 1) Reciprocating and 2) Screw

*2* REFRIGERANT 1)2) R717; R22; R502; R23; R404a;


R134A; R507; R410A; R407C; R744; R1270,
R290, R000

3 CONTROL ON 1)2) Suction; Brine; Discharge;


Hot water; Ext.cool; Ext.heat.

4 VOLUME RATIO 2) Man; Auto

5 AUTO START 1)2) Yes; No

6 AUTO STOP 1)2) Yes; No

7 PRELUB. 2) Yes; No

8 FULL FLOW PUMP 2) Yes; No

9 BOOSTER 2) Yes; No

*10* COMPR.NO. 1)2) 1 to 14

11 PREF. MASTER 1)2) Compressor; Start

12 ECONOMIZER 2) Yes; No

13 ECO LO CAP 2) 0% to 100%

14 ECO HI SUCT 2) -100°C/Rto 100 °C/R

15 COMM. EVAP/CONDENS 1)2) N/N; N/Y; Y/N; Y/Y

0178-445 - ENG 29/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

CONFIGURATION

No Function for Possible choices

16 HP ON TWO STAGE 1)2) Yes; No

17 WATER COOLED 1) Yes; No

18 OIL COOLING 1)2) No; Normal; HLI/BLI; Thermo pump;


3-way valve; AKV

19 RANGE M.CURR 1)2) 0 Amp to 2500 Amp

20 SWEPT VOLUME 1)2) 0 m3/h to 12000 m3/h

21 COLD STORE 1)2) Yes; No

22 CLIMA CONTROL 1) Yes; No

23 ADD. UNLOAD 1) Yes; No

*24* BAUD RATE 1)2) 1200 Baud to 19200 Baud

25 OIL RECTIFIER 2) Yes; No

*26* PRESS/TEMP 1)2) BAR / ° C;PSI / ° F; KPA /°C

27 MECHANICAL ZERO 2) Yes; No

28 MANUAL ZERO 2) 0% til 40%

*29* PORT 1 1) 2) NONE; EVOLUTION A1S; EVOLUTION FX2N

30 COP ACTIVE 1) 2) Yes; No

31 TAKE OVER 1) Yes; No

32 CHILLER 1) 2) Yes; No

*33* FACTORY RESET 1)2) Yes; No

34 VI MODE 2) 70% to 97%

35 MOTOR SIZE 1)2) 0 to 2500 kW

36 FLOW FACTOR 1)2) 0.01 to 10 litres per pulse

37 LIQ. SUBCOOL 1)2) 0° C to 99.9° C

38 DANBUSS 1)2) Yes (not changeable)

39 NODE NO (Port 1) 1)2) 0 (not changeable)

40 BAUD RATE (Port 1) 1)2) 1200 baud to 38400 baud

41 PORT 2 1)2) NONE or QUANTUM

42 NODE NO (Port 2) 1)2) 1 to 99

43 BAUD RATE (Port 2) 1)2) 1200 (not changeable)

44 MOTOR SIGNAL 1)2) kW or Amp

30/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

CONFIGURATION

No Function for Possible choices

45 PRESSURE 1)2) -1/9 - -1/25; -1/25 - -1/59

46 ROTATUNE 1)2) Yes; No

47 RANGE MOTOR (kW) POWER 0-2500 kW

48 MINIMUM FREQUENCY 700 to 2000 revolutions

49 MAXIMUM FREQUENCY 1100 to 12000 revolutions

50 PROFIBUS Yes; No

51 NODE NO 1 to 254

52 BAUD RATE 12 mbit (not changeable)

53 MOTOR INPUT 0-1 amp / 4-20 mA

54 CAP/FREQ Cap. pos./Freq.


0178_427_en_2.02.fm

0178-445 - ENG 31/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

Pos. 1: TYPE VMY 447 M


NOT-DEF SAB 202 S
SMC 104 S/L SAB 202 L
SMC 104 E SAB 128H MK3
SMC 106 S/L SAB 163H MK3
SMC 106 E SAB 330S
SMC 186 SAB 330 L
SMC 108 S/L SAB 330E
SMC 108 E SAB 80
SMC 188 FV 17/19
SMC 112 S/L *SV 17/19
SMC 112 E FV 24/26
SMC 116 S/L SV 24/26
SMC 116 E S 50
CMO 24 S 70
CMO 26 S 93
CMO 28 SAB 128 HR
TSMC 108 S/L SAB 163 HR
TSMC 108 E GST 13 - 16 - 20
TSMC 188 GST 25 - 31 - 41
TSMC 116 S/L GSV 50 L
TSMC 116 E GSV 64 L
TCMO 28 GSV 84 L
TCMO 28NEW GSV 111 L
HPC 104 S GSV 147 L
HPC 106 S GSV 185 L
HPC 108 S GSV 224 L
HPO 24 RWF 270 L
HPO 26 GSV 263 L
HPO 28 GSV 331 L
SAB 110 S GSV 339 L
SAB 110 L RWF 480 L
SAB 128HMK1 GSV 412 L → 0153 L
SAB 128HMK2 GSV 412 L → 0154 L
SAB 163HMK1 GSV 562 L → 0222 K
SAB 163BMK1 GSV 562 L 0222 K →
SAB 163HMK2 GSV 715 L → 0109 XL
VMY MK2 GSV 715 L 0110 XL →
VMY 347 H GSV 900 L
VMY 347 M GSV 50 H
VMY 447 H GSV 64 H

32/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

GSV 84 H R407C
GSV 111 H R744
GSV 147 H R 1270
GSV 185 H R 290
GSV 224 H R000
RWF 270 H For R407C (and all other refrigerants) the convert-
GSV 263 H ed pressure is always shown as dew point values.
GSV 331 H
GSV 339 H Before the user-defined refrigerant R000 is cho-
RWF 480 H sen, the refrigerant curve must be entered in pic-
GSV 412 H → 0153 L ture SETUP I CALIBRATION I DEF. REFRIG-
GSV 412 H → 0154 L ERANT R000. See also section Compressor con-
GSV 562 H → 0222 K trol and surveillance, Define refrigerant R000.
GSV 562 H 0222 K → Pos. 3: CONTROL ON:
GSV 715 H → 0109 XL SUCTION
GSV 715 H 0110 XL → BRINE
GSV 900 H DISCHARGE
GSB 84 - GSB 465 HOT WATER
0178_427_en_2.02.fm

SAB 283 L EXT. COOL


SAB 283 E EXT. HEAT
SAB 355 L
SUCTION: Pressure is measured by the built-in
SAB 110 SR/LR
pressure transducer on the compres-
Note: Please note that the screw compressors sor suction side.
SV 17/19 and GSB 84 - GSB 465 are not yet sup- Set point is set in the picture
ported. SUCT.PRESS I PARAMETER.
Note: Choose GVS/RWF L for compressors with BRINE: Temperature is measured by an ex-
“low volume range” (1.7 - 3.0) and GSV/RWF H tra Pt 100 sensor in the water output
for compressors with “high volume range” (2.2 - of the evaporator.
5.0). See compressor name plate for indication af Set point is set in the picture BRINE
volume range. TEMP. I PARAMETER.
Pos. 2: REFRIGERANT DISCHARGE:
NOT-DEF. Pressure is measured by the built-in
R717 pressure transducer on the compres-
R22 sor discharge side.
R502 Set point is set in the picture
R23 DISCH.PRES I PARAMETER.
R404A HOT WATER:
R134A Temperature is measured by an ex-
R507 tra Pt 100 sensor in the water output
R410A of the condenser. Set point is set in

0178-445 - ENG 33/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

the picture BRINE I BRINE TEMP. If YES is selected, compressor will start by itself in
I PARAMETERS. AUTO/REMOTE depending on what is required.
EXT.COOL: At this stage it is possible to connect Regulation is now automatic.
an external 4-20 mA transducer as If NO is selected, start compressor manually
cooling function, ie at a rising signal even though in AUTO/REMOTE. Howver, dur-
the compressor will load capacity. ing operation compressor regulates automatically.
Furthermore, select EXTERNAL IN-
Pos. 6 :AUTO STOP
PUT SIGNAL in picture SETUP I
NO
CALIB I 4-20 mA input. The points
YES
4 mA as well as 20 mA must be set
as the max (20 mA) and min (4 mA) If YES is selected, compressor will stop automati-
values of the sensor. cally at minimum capacity by decreasing demand.

Select BRINE I EXT. INPUT I PA- If NO is selected, compressor must be stopped


RAMETER and enter regulator set manually even if AUTO or REMOTE has been se-
point, neutral zone and prop.band. lected in COMPRESSOR CTRL. MODE.

See also section Regulators Pos. 7: PRELUBRICATION (screw compr.)


NO
EXT.HEAT: At this stage it is possible to connect
YES
an external 4-20 mA transducer as
heating function, ie at a falling signal a. Select YES for SAB Mk1, SAB Mk3,
the compressor will load capacity. SAB 202, SAB 250, SAB 330, VMY Mk3,
VMY Mk2, FV 19, SV 24/26 and FV 24/26.
Select EXTERNAL INPUT SIGNAL
Prelubrication time is set in picure TIMERS I
in picture SETUP I CALIB I 4-20
TIMER SETUP.
mA input. The points 4 mA as well as
20 mA must be set as the max (20 b. Select NO for all other screw compressors.
mA) and min (4 mA) values of the When compressor has received starting signal,
sensor. prelubrication will start. When prelubrication is
Select BRINE I EXT. INPUT I PA- completed, compressor will start. See also section
RAMETER and enter regulator set Timer Setup, which includes time settings.
point, neutral zone and prop.band. Pos. 8: FULL FLOW PUMP (screw compr.)
See also section Regulators NO
Pos. 4: VOLUME RATIO (screw compr.) YES
MANUAL/AUTO Select YES for VMY Mk3 compressor provided it
If AUTO is selected, compressor must be fitted is fitted with FULL FLOW PUMP.
with solenoid valves, etc for automatic regulation Select NO for all other compressor types.
of Vi slide.
Use pump for prelubrication before start-up and to
Pos. 5: AUTO START maintain minimum oil pressure during operation.
NO
At the same time remember to set set points 1 and
YES
2, which determine at which pressure levels the

34/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

pump is going to start and stop. Select picture OIL START#: If START# is selected, the compressor
PRESS I PARAMETER. which has the lowest starting number and which is
in REMOTE (MULTISAB) will be the regulator.

XX Pos. 12: ECONOMIZER (screw compr.)


LOW WARNING XX NO
SET POINT 1 XX YES
SET POINT 1 XX
If the compressor is connected to an economizer,
SET POINT 1 is the pressure at which the pump this function must be selected. Thus the econo-
will start; SELECT 5.5 Bar. mizer is connected/disconnected according to the
SET POINT 2 is the pressure at which the pump compressor operation. The connection is impor-
will stop; SELECT 7.0 Bar. tant as regards the regulation of the compressor
For more details, see Compressor control and volume ratio.
surveillance. Pos. 13: ECO LO CAP (screw compr.)
Pos. 9: BOOSTER (screw compr.) 0 to 100%
NO If the immediate slide position is higher than the
YES set value, connect the economizer. If the slide po-
0178_427_en_2.02.fm

YES means that the oil pump will run continuously sition is 20% below this value, disconnect the
during compressor operation. The capacity slide economizer again.
can thus be moved at low pressure conditions. Pos. 14: ECO HI SUCT (screw compr.)
Note that both SAB Mk3, SAB 202, VMY Mk3, -100 to +100°C/R
SV/FV and GSV/SGC compressors are fitted with
With ECO operation it is possible to enter a suc-
differential pressure controlled oil pumps (see ta- tion pressure value in °C/R. If the suction pressure
ble 1) and consequently do not use this configura-
of the economizer is above this value, the sole-
tion point.
noid valves connected in the economizer system
Pos.10: COMPR. NO. 1 to 14 will be closed. Hysteresis of 2°C/R.
This no must be entered into UNISAB II. The com- By a combined ECO and HLI operation the set
pressor has now been "named". value must not be above -20°C/R.
Two compressors must under no circum-
Pos. 15: COMMON EVAP/COND
stances have the same number.
N/N
Pos. 11: PREF. MASTER N/Y
START# Y/N
COMPR# Y/Y
COMPR#: If COMPR# is selected, the compres- This point can be configured to the following four
sor with the lowest no (pos 10) will always be the values:
regulator in a MULTISAB system, independent of
N/N - separate evaporator and condenser for
the starting sequence.
each compressor.
N/Y - separate evaporator for each compressor,

0178-445 - ENG 35/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

but common condenser. Water cooling output is activated by a rising dis-


Y/N - common evaporator, but separate condens- charge pipe temperature. The set point for this
er for each compressor. value is set in picture DISCH. TEMP I PARAM-
Y/Y - common evaporator and condenser for each ETER, SET POINT 1. The set point has fixed hys-
plant (ie compressors with a MULTISAB system teresis of 5K.
no). Ex.: Sp 1 = 100°C:
On plants with a common evaporator the suction Cooling starts at 100°C and stops at (100-5) =
pressure limiter cannot start the next compressor 95°C.
in the sequence. This is only possible if a separate Water cooling output is closed at compressor stop
evaporator has been configured. according to adjustable time delay. In picture TIM-
On plants with a common condenser the dis- ERS I TIMER SETUP adjust time delay OIL
charge limiter cannot start the next compressor in COOL ON.
the sequence. This is only possible on plants with
Intermediate pressure liquid injection (two-
separate condensers. stage reciprocating compressors)
Pos. 16: HP ON TWO STAGE The intermediate pressure liquid injection for
NO TSMC/TCMO compressors is active whenever
YES the compressor is configured to TCMO or TSMC.
Usually NO is chosen The solenoid valve for intermediate pressure liq-
uid injection is activated when the compressor has
In special cases on a two-stage plant YES can be
started and the discharge pipe temperature gets
selected for HP compressors. The compressors
too high.
can thus be forced to start by means of the input
"External starting permission". The set point for this value is entered in picture:
DISCH.TEMP I PARAMETER, SET POINT 2.
Please note that the compressor does not stop
The set point has fixed hysterisis of 5°K.
before the starting permission has been removed
even though there is no cooling requirement. See Ex.: Sp2 = 90°C. Cooling starts at 90°C and stops
detailed description in section Compressor control at (90-5) = 85°C.
and surveillance, HP on TWO-STAGE Adjusting range: -20°C-+150°C.
Pos. 17: WATER COOLED (recip.compr.) Factory value: 100°C.
NO The regulator controls the solenoid valve through
YES the liquid injection digital output.

36/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

Pos. 18: Oil cooling - setting


No. Type of regulator Minimum Maximum Factory Unit
setting

RECIPROCATING COMPRESSORS

2 Set point 1/oil temp. +35 +75 +55 °C


Difference 5(fixed) °C
Oil cooling

Set point 2/oil temp. 0 +75 +35 °C


Difference 5(fixed) °C
Oil heating

Set point 1/disch.pipe -20 +150 +100 °C


temp. Difference 5(fixed) °C
Water cooling

Set point 2/disch.pipe -20 +150 +100 °C


temp. Difference 5(fixed)
Interm.pressure
liquid injection

SCREW COMPRESSORS
0178_427_en_2.02.fm

2 Set point 1/oiltemp. +35 +75 +50 °C


Difference 5(fixed) °C
Oil cooling,
normal

3 Set point 1/disch. pipe -20 +150 +40 °C


temp. Difference 2(fixed) °C
HLI/BLI cooling

5 Set point 1/oil temp. +35 +75 +50 °C


Neutral zone 0 100 4 °C
Prop.band 0 100 5 °C
Oil cooling
Three-way valve

6 Set point 1/pressure pipe -20 +150 40 °C


temp.
Neutral zone 0 10 0 °C
Prop. Band 1 100 10 °C
AKV (HLI) oil cooling

0178-445 - ENG 37/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

Pos. 18: OIL COOLING for oil cooling, which is regulated according
1) NONE to oil temperature. The set point for this
value is set in picture OIL TEMP I PARAM-
2) NORMAL (Screw and recip. compr.)
ETER. SET POINT, NEUTRAL ZONE and
3) HLI/BLI (Screw compressors) PROPORTIONAL BAND can now be set.
4) TH.PUMP (Thermo pump, reciprocating This regulator is usually not used. However,
compr.) it can be used provided that a valve with mo-
tor drive is fitted.
5) THREE-WAY (Screw compressor)
6) AKV
6) AKV
Direct regulation of HLI cooling by pulse
1) NONE width modulated AKV valve. During a period
Oil cooling disconnected. of 6 seconds, the AKV valve is kept open
2) NORMAL from 0 to 6 seconds depending on the regu-
Oil cooling output is activated by rising oil lator output signal.
temperature. The HLI-AKV cooling outlet is activated by rising
The set point for this value is set in picture discharge pipe temperature.
OIL TEMP I PARAMETER I SETPOINT
The set point for discharge pipe temperature is
1. The set point has fixed hysteresis of 5K.
adjusted in the parameter picture DISCH.TEMP
Ex.: Set point 1 = 40°C: I PARAMETER, SET POINT 1.
Cooling starts at 40°C and stops at (40-5) = 35°C.
In the same picture NEUTRAL ZONE and PRO-
Oil cooling output is closed at compressor stop ac- PORTIONAL BAND can be adjusted.
cording to adjustable time delay. In picture TIM-
Example:
ERS I TIMER SETUP adjust time delay OIL
Set point 1= 60°C
COOL ON.
Neutral Zone= 4°C
3) HLI/BLI Proportional Band= 5°C
Oil cooling output is activated by rising dis-
The regulator keeps the discharge pipe tempera-
charge temperature.
ture between 58°C and 62°C.
The set point for this value is set in picture
DISCH.TEMP I PARAMETER, SET Pos.19: RANGE M. CURR 0 to 2500A
POINT 1. The set point has a fixed hystere- This value can be read on the current transformer
sis of 2K. at the compressor motor guard (not on the com-
Ex.: Set point 1 = 40°C: pressor motor) so that the 0-1 Amp. signal is read
Cooling starts at 40°C and stops at (40-2) = 38°C. correctly on UNISAB II as the current absorbed by
the motor.
4) TH.PUMP
Output for activating thermo pump takes Enter current in picture MOTOR I MOTOR
place at compressor start-up. No regulation CURR I PARAMETER. Any indication errors can
is connected to this function. be eliminated from the reading on the display by
multiplying the measuring range with a correcting
5) THREE-WAY
Used for controlling three-way motor valve

38/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

factor: Pos. 23: ADD. UNLOAD (reciprocating compr.)


NO
Measured current
Correction = YES
Display reading
Select YES for SMC compressors fitted with addi-
before entering the current in the UNISAB II dis- tional solenoid valve for add. unload.
play. Select NO for all other reciprocating compressors
Pos. 20: SWEPT VOLUME and always for CMO, TCMO and TSMC.
0 to 12000 m3/h When the compressor is started, it will still activate
The compressor swept volume must be entered in the first capacity stage, but during operation
MAN/AUTO/REMOTE it will be able to unload
plants which only consist of:
down to 0% capacity. To avoid a high oil temper-
• Screw compressors ature at this stage of operation, a fixed time limit of
• Screw and reciprocating compressors in the 300 seconds which will stop the compressor on
same system. expiry has been corporated.
On plants consisting solely of reciprocating com- Pos. 24: BAUD RATE
pressors the above is not relevant. 1200
0178_427_en_2.02.fm

Read the swept volume on the compressor name 2400


plate. 4800
9600
Pos. 21: COLD STORE
19200
NO
YES In this position the speed at which several
UNISAB II units communicate with each other can
If this function is chosen, it will affect the way the be set.
MULTISAB system starts and regulates the com-
pressors in a common system. See detailed de- The new UNISAB II allows a communication
scription under the function Cold store. speed of up to 19,200 baud.
This only applies to UNISAB II versions manufac-
Pos. 22: CLIMATE CONTROL
tured from May 1998 supplied with revision G re-
NO
lay prints (relay no 7 will in such cases be mount-
YES
ed in the socket).
If the compressor is used for water/brine cooling
For older UNISAB II units, the maximum is 9600
or for heating water, the flow temperature can be
baud.
raised or lowered, depending on the outside tem-
perature. Usually always select the highest baud rate that
all units on the network can use.
An extra 4 - 20 mA temperature transducer must
be connected. If UNISAB II is connected with UNISAB I and/or
PROSAB II, adjust speed to 1200 baud.
For detailed description see section Climatic con-
trol.

0178-445 - ENG 39/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

Pos. 25: OIL RECTIFIER The value [0-40%] to be entered in MANUAL


NO ZERO must be of the following size:
YES
Lenght of spacer block 4 x 100
Manual zero [%]
The oil rectifying function is used on brine plants Max movement of capacity slide 2

in marine execution. In case this function is select-


ed, check also the timers Oil Rectifying Start, Oil See the following table.
Rectifying Delay and Oil Rectifying Blocked.
For SAB 202, which has automatic zero point set-
Pos. 26: PRESS/TEMP ting, the value 0% must be kept in FACT. setting.
BAR/°C
See also pos. 27 MECHANICAL ZERO.
PSI/°F
KPA/°C Pos. 29: PORT 1
Pressure levels and temperatures can be dis- Note that the use of PORT 1 requires UNISAB II
played in either SI units: Bar, kPa and °C or US to be fitted with the add-on printed circuit board
units: PSI and °F. UNICOM IF.
NONE
Pos. 27: MECHANICAL ZERO
EVOLUTION A1S
NO
EVOLUTION FX2N
YES
Select EVOLUTION A1S or EVOLUTION FX2N if
Only in case the compressor has a built-in spacer
UNISAB II is to be used as an EVOLUTION con-
block as well as automatic Vi regulation, ME-
trol, ie an extended (PLCY) control in which
CHANICAL ZERO must be set for YES. In this
UNISAB II is integrated with a PLC control.
way the travel of the capacity slide is automatically
reduced by the percentage (0-40%) entered in Select NONE if UNISAB II is to be used as an EV-
MANUAL ZERO. Thus corrected capacity is cal- OLUTION control.
culated and shown correctly - see the following ta- Pos. 30: COP ACTIVE
ble. Note that the use of COP ACTIVE requires
Pos. 28: MANUAL ZERO UNISAB II to be fitted with the add-on printed cir-
0 to 40% cuit board UNICOM IF.

For screw compressors without automatic zero NO


point setting, it is possible manually to set a "zero YES
point" below which the compressor capacity slide Select YES if UNISAB II is fitted with a function for
is not allowed to fall while the compressor is oper- COP measuring (Coefficient Of Performance, ie
ating. cooling efficiency of compressor). COP measur-
In case the compressor has a built-in spacer ing requires an extra card for flow measuring as
block as well as automatic Vi regulation, MAN- well as a motor efficency measuring device, cf
UAL ZERO is used for reducing the travel of the UNISAB II COP Manual.
capacity slide by the entered percentage. Thus Select NO if UNISAB II is not used for COP meas-
corrected capacity is calculated and shown cor- uring.
rectly.

40/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

Pos. 31: TAKE OVER (reciprocating This selection is identical to MOTOR SIZE found
compressors) in menu CALIBRATE I CALIBRATE COP. See
NO section COP setting.
YES
Pos. 36: FLOW FACTOR
Select YES if UNISAB II is configured as a recip- 0.01 to 10 l/pls
rocating compressor, operates in a combined
This selection is identical to FLOW FACTOR
plant of reciprocating and screw compressors and
found in menu CALIBRATE I CALIBRATE COP.
the function MULTISAB TAKE OVER/TRANS-
See section COP setting.
FER is required.
Pos. 37: LIQ. SUBCOOL
Pos. 32: CHILLER
0 to 99.9 °C
NO
YES1) Chiller This selection is identical to LIQ. SUBCOOL found
2) Evolution in menu CALIBRATE I CALIBRATE COP. See
section COP setting.
Select YES if UNISAB II is used as part of a chiller
unit control, ie UNISAB II and a UNISAB II chiller Pos. 38: DANBUSS
control are connected via a communication cable. YES (not changeable)
0178_427_en_2.02.fm

See UNISAB II-Chiller Manual. Functions as header of the menu Communication.


Shows that the succeeding COMPR. NO and
Always select NO if UNISAB II is not connected to
BAUD RATE refer to the main communication
a UNISAB II chiller
port, which always runs the Danbuss protocol.
Pos. 33: FACTORY SETTING
Pos. 39: NODE NO ( Port 1)
NO
0 (not changeable)
YES
When the optional communication port 1 is not
With this function it is possible to restore the orig-
used or used for EVOLUTION (see Pos. 29), the
inal values as determined ex factory.
NODE NO is fixed and cannot therefore be
See section Factory settings. changed.
Current configuration as well as calibration values Pos. 40: BAUD RATE ( Port 1)
for pressure transducers and brine temperatures
1200 to 38400 baud
will remain unchanged.
Selection of communication speed for the optional
Pos. 34: VI MODE communication port 1 (see Pos. 29).
70 to 97%
Pos. 41: PORT 2
This point is only relevant for screw compressors
Note that the use of PORT 2 requires UNISAB II
with electrical slide control. See section Electrical
to be fitted with the add-on printed circuit board
slide control.
UNICOM IF.
Pos. 35: MOTOR SIZE NONE or QUANTUM
0 to 2500 kW or Amp
Select QUANTUM if UNISAB II is to work together
with one or more Quantum compressor control-

0178-445 - ENG 41/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

lers (also manufactured by YORK Refrigeration) Pos. 46: ROTATUNE


and/or with one or more Grammatic 2502 com- NO
pressor controllers. See also QUANTUM manual
YES
S90-010-M and S90-010-O.
Select YES if UNISAB II is fitted on a compressor
Select NONE, if Port 2 is not used.
with frequency converter and if this compressor is
Pos. 42: NODE NO (Port 2) to run in sequence with one or more conventional
1 to 99 screw or reciprocating compressors.
If UNISAB II is to communicate with QUANTUM Select NO if this compressor is to run in seqence
(Pos. 41), select a node number which is not iden- with another Rotatune compressor.
tical to any of the Quantum node numbers. Note: This function will be active from EPROM
Pos. 43: BAUD RATE (Port 2) version 2.01 ROTA and later versions.
1200 (not changeable) For further information, please see ROTA Appen-
Selection of communication speed for the optional dix to UNISAB II manual. This appendix describes
communication port 2 (see Pos. 41). As Quantum the use of frequency converters together with
reguires 1200 baud fixed, the speed cannot be UNISAB II.
changed. Pos. 47: RANGE MOTOR (kW) 0-2500 kW
Pos. 44: MOTOR SIGNAL POWER
kW or Amp Enter the value corresponding to 20mA input. For
use of Vacon converter, this value is read on the
When not using UNICOM IF print, the measured
frequency converter name plate and multiplied by
signal can be either an ampere or a kW signal.
two so that the 4-20 mA signal is read correctly in
In case of Amp signal input, use terminals 35-36 UNISAB II as the motor power. Enter the motor
for 0 - 1 Amp AC. nominal power in the picture MOTOR I MOTOR
In case of kW signal input, use terminals 35-40 for SIZE I PARAMETER.
4-20 mA DC. Pos. 48: MINIMUM FREQUENCY
However, it is also possible to use the 4-20 mA 700 to 2000 revolutions
terminals 35-40 for reading Ampere. In this case The minimum number of revolutions which can be
choose 4-20 mA in configuration point pos. 53. shown on the UNISAB II display when the analog
Pos. 45: PRESS output signal is 4 mA from the UNICOM IF add-on
- 1/9 - 1/25 printed circuit board to the frequency converter.
-1/25-1/59 The frequency converter must of course be con-
figured correctly, ie in minimum permissible fre-
Shows the pressure range for pressure transmit-
quency. See converter instruction manual and list
ters mounted on compressor. Usually -1/9 -1/25 is
of settings for details. See moreover ROTA Ap-
selected for ordinary compressor operation (de-
pendix to UNISAB II manual. This appendix de-
fault) and - 1/25 -1/59 for heat pump operation or
scribes the use of frequency converters together
operation with R744 (CO2).
with UNISAB II.

42/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

Pos. 49: MAXIMUM FREQUENCY If UNISAB II is to communicate with Mitsubishi


1100 to 12000 revolutions PLC (Pos. 50), select node number which is differ-
ent from the node numbers of the PLC control.
The maximum number of revolutions which can
be shown on the UNISAB II display when the an- Pos. 52: BAUD RATE
alog output signal is 20 mA from the UNICOM IF 12 mbit (cannot be changed)
add-on printed circuit board to the frequency con-
Pos. 53: MOTOR INPUT
verter. The frequency converter must of course be
0 - 1 amp / 4 - 20 mA
configured correctly, ie in maximum permissible
frequency. See converter instruction manual and Select 0-1 amp when the measured motor current
list of settings for details. See moreover ROTA is supplied from a current transformer with am-
Appendix to UNISAB II manual. This appendix de- pere ratio xxx/1 amp connected to the terminals
scribes the use of frequency converters together 35-36.
with UNISAB II. Select 4-20 mA when the measured motor current
Pos. 50: PROFIBUS is supplied from a 4-20 mA transmitter, for in-
NO stance a frequency converter or other equipment.
The terminals 35 and 40 are used here.
YES
Pos. 54: CAPACITY/FREQUENCY
0178_427_en_2.02.fm

Only for internal use within YORK Marine


Cap.Pos.
Group.
Frequency
Select YES if UNISAB II is fitted with UNICOM IF
Select Cap.Pos. if the terminal input for capacity
add-on printed circuit board and is to communi-
(terminal row 29-30-31) is connected to a capacity
cate with Mitsubishi PLC via PROFIBUS commu-
slide transmitter.
nication.
Select Frequency if the terminal input for capacity
Select NO if the above is not the case.
(terminal row 29-30-31) is connected to a frequen-
Pos. 51: NODE NO cy converter so that changes in the motor frequen-
1 to 254 cy are shown as changes in the capacity.

0178-445 - ENG 43/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

Table 2.1
Screw compressor Max movement Evaporating Length of Mechanical Manual
type of capacity slide temp.R717/R22 spacer block zero zero
1 2 3 4 5 6
mm mm (pos 27) (pos 28)
SAB 110SM
84.5 < -20°C 22 NO 0%
SAB 110SF
SAB 110 LM
96 > -20°C NONE NO FACT 0%
SAB 110 LF
SAB 128 HM Mk2
< -20°C 31.5 NO 0%
SAB 128 HF Mk2
126
SAB 128 HM Mk3
> -20°C NONE NO FACT 0%
SAB 128 HF Mk3
SAB 163 M Mk1, Man Vi
SAB 163 F Mk1, Man Vi < -20°C 38.5 NO 0%
SAB 163 HM Mk2, Man Vi
160
SAB 163 HF Mk2, Man Vi
SAB 163 HM Mk3, Man Vi > -20°C NONE NO FACT0%
SAB 163 HF Mk3, Man Vi
SAB 163 HM Mk2, Aut Vi
< -20°C 38.5 YES 24 %
SAB 163 HF Mk2, Aut Vi
160
SAB 163 HM Mk3, Aut Vi
> -20°C NONE NO FACT 0%
SAB 163 HF Mk3, Aut Vi
SAB 202 SM, Man Vi
SAB 202 SF, Man Vi ** *
245 ALL NONE
SAB 202 SM, Aut Vi NO FACT 0%
SAB 202 SF, Aut Vi
SAB 202 LM, Man Vi
SAB 202 LF, Man Vi ** *
317 ALL NONE
SAB 202 LM, Aut Vi NO FACT 0%
SAB 202 LF, Aut Vi
SAB 283 L 314
Not Not Not Not
SAB 283 E 391
relevant relevant relevant relevant
SAB 355 L 350
SAB 330 S 262
Not Not Not Not
SAB 330 L 371
relevant relevant relevant relevant
SAB 330 E 480

* If another value than the factory set value of 0% is inserted, the automatic zero setting is eliminated.
Therefore, only insert a value different from 0% after having contacted YORK Refrigeration.

44/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
2. Configuration

** If another value than NO is inserted, the automatic zero setting is eliminated.


Therefore, only insert a value different from No after having contacted YORK Refrigeration.
0178_427_en_2.02.fm

0178-445 - ENG 45/222


Rev. 03.09
UNISAB II 2.03
2. Configuration

46/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

3. Alarms and Warnings

Analog alarms and warnings In case an alarm limit is exceeded, the compres-
ALARM and WARNING limits can be set sepa- sor will stop immediately. The red light diode
rately as described in section Changing the set above the D key will start to flash quickly. In the
values. picture ALARM the reason for the alarm can be
read, and at the same time the alarm relay will
UNISAB II does not check whether ALARM and change its position.
WARNING limits have been interchanged by a
mistake (eg if warning limit for high discharge The alarm relay works by connecting the
pressure is set higher than the alarm limit). Con- alarm/common switch during alarm and by dis-
sequently, during adjustments check that the connecting it once the alarm is reset.
settings are correct. The picture ALARM also shows the exact time of
If a warning limit is exceeded, the red light diode the alarm. See also under Diagnosis.
above the D key will begin to flash slowly, and The alarm is reset by pressing the D key, and the
the warning relay will be activated. The reason for warning and alarm relays will return to their nor-
the warning can be seen in the picture WARNING, mal position. However, if the alarm value is still
which also shows whether there are several si- outside the limit, the red light diode will continue to
0178_428_en.fm

multaneous warnings. flash. When the situation has returned to normal,


Note that in case of warning, a limiter might be ac- the D key must be pressed once more,
tive as described in section Limiting functions. The set values for high and low alarms as well as
When the warning disappears, it is automatically the factory values are stated in the following ta-
removed from the picture WARNING and the re- bles 1-5. These are followed by explanatory
lay returns to its normal position. notes.

0178-445 - ENG 47/222


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Table 1
Screw compressors
Measured and calculated pressure levels
Measuring Min Max Factory Note

Suction pressure High alarm - - -


(bar) High warning 1.5 9.0 5.0 3+4+5
Low warning -1.0 6.0 1.5 3+4+5
Low alarm -1.0 6.0 1.0 3+4+5

Discharge pressure High alarm 4.0 24.0 16.0 1+6


(bar) High warning 3.0 22.0 15.0 1+6
Low warning - - -
Low alarm -1.0 -1.0 -1.0 1+5

Oil pressure (bar) Low warning 1.5 6.0 4.0 2+7


Calculated value Low alarm 1.0 5.0 2.5 2+7
SAB Mk 1 compressors

Oil pressure (bar) Low warning 0.0 6.0 0.0 2+9


Calculated value Low alarm 0.0 5.0 0.0 2+9
SAB Mk 2 compressors

Oil pressure (bar) Low warning 1.0 6.0 1.5 2+9


Calculated value Low alarm 0.5 5.0 1.2 2+9
SAB Mk 3, Mk 4 compres-
sors Set point 1 0.0 10.0 2.5 21
SAB 202, 283, 330, 355 Set point 2 0.0 10.0 4.0 21
FV 19, SV 24/26, FV 24/26

Oil pressure (bar) Low warning 1.5 6.0 2.0 2+9+17


Calculated value Low alarm 1.0 5.0 1.5 2+9+17
VMY Mk 2-2.5 compressor

Oil pressure(bar) Low warning 1.5 6.0 4.0 2+9


Calculated value Low alarm 1.0 5.0 3.0 2+9
VMY Mk 3 compressors Set point 1 0.0 10.0 5.5 22
Set point 2 0.0 10.0 7.0 22

Oil pressure (bar) Low warning 1.5 6.0 2.0 2+9


Calculated value Low alarm 1.0 5.0 1.5 2+9
SAB 80 Set point 1 0.0 10.0 0.5 20
Set point 2 0.0 20.0 16.0 20

Diff. pressure High alarm 0.0 1.5 1.0 2+11


across oil filter (bar) Low warning 0.0 1.3 0.7 2+11
Calculated value
All types but SAB 80

Diff. pressure High alarm 0.0 2.5 1.6 2+11+19


across oil filter (bar) High warning 0.0 2.2 1.4 2+11+19
Calculated value
SAB80

48/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Table 2
Screw compressors
Measured and calculated temperatures

Measuring Min Max Factory Note

Discharge temp. High alarm 60.0 130.0 100.0 1+6


(°C) High warning 50.0 120,0 90.0 1+6
Low warning -65.0 -65.0 -65.0
Low alarm - - -

Oil temperature High alarm 40.0 80.0 60.0 2+7


(°C) High warning 30.0 70.0 55.0 2+7
Low warning 10.0 50.0 25.0 2+7
Low alarm 0.0 40.0 20.0 2+7

Brine temperature High alarm -60.0 100,0 60.0 1+6


(°C) High warning -60.0 100.0 50.0 1+6
Low warning -100.0 100.0 4.0 1+6
Low alarm -100.0 100.0 2.0 1+6

Suction gas superheat High alarm 6.0 120.0 110.0 2+7+12


(°C) High warning 5.0 120.0 100.0 2+7+12
0178_428_en.fm

Low warning 0.0 40.0 2.0 2+7+10


Calculated value Low alarm 0.0 40.0 0.0 2+7+10

Disch. gas superheat Low warning 5.0 40.0 10.0 2+7+10


(°C) Low alarm 0.0 40.0 0.0 2+7+10
Calculated value

4-20 m Auxiliary input signal


Measuring Min Max Factory Note

Auxiliary input High alarm -999.9 999.9 0.0 3+18


(4-20 mA) High warning -999.9 999.9 0.0 3+18
Low warning -999.9 999.9 0.0 3+18
Low alarm -999.9 999.9 0.0 3+18

0178-445 - ENG 49/222


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Table 3
Reciprocating compressors
Measured and calculated pressure levels
Measuring Min Max Factory Note

Suction pressure High alarm - - -


(bar) High warning 1.5 9.0 5.0 3+4+5
Low warning -1.0 6.0 2.5 3+4+5
Low alarm -1.0 6.0 1.5 3+4+5

Discharge pressure High alarm 4.0 24.0 16.0 1+6


(bar) High warning 3.0 22.0 15.0 1+6
Low warning - - -
Low alarm -1.0 -1.0 -1.0 1+5

Intermediatepressure High alarm 4.0 24.0 7.0 1+6


(bar) High warning 3.0 22.0 6.0 1+6
For two-stage Low warning -1.0 10.0 -1.0 1+6+16
compressors only Low alarm -1.0 10.0 -1.0 1+6+16

Oil pressure (bar) High alarm 5.0 7.0 6.0 2+5+16


High warning 5.0 7.0 5.5 2+5
Low warning 0.5 5.0 4.0 2+5+14
Calculated value Low alarm 0.5 5.0 3.5 2+5+14

Table 4
Reciprocating compressors
Measured and calculated temperatures
Measuring Min Max Factory Note
Discharge temp. High alarm 60.0 155.0 125.0 1+6
(°C) High warning 50.0 155.0 120.0 1+6
Low warning -65.0 -65.0 -65.0
Low alarm - - -
Oil temperature High alarm 40.0 105.0 80.0 2
(°C) High warning 30.0 105.0 75.0 2
Low warning 0.0 50.0 30.0 2+7
Low alarm 0.0 40.0 25.0 2+7
Brine temperature High alarm -60.0 100.0 60.0 1+6
(°C) High warning -60.0 100.0 50.0 1+6
Low warning -100.0 100.0 4.0 1+6
Low alarm -100.0 100.0 2.0 1+6
Intermediate gas High alarm 50.0 155.0 100.0 2+7
temperature (°C) High warning 50.0 120.0 95.0 2+7
For two-stage Low warning -20.0 50.0 4.0 2+7
compressors only Low alarm -20.0 50.0 2.0 2+7

50/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Measuring Min Max Factory Note


Suction gas superheat High alarm 6.0 120.0 110.0 2+7
(°C) High warning 5.0 120.0 100.0 2+7
Low warning 0.0 40.0 4.0 2+7+13
Calculated value Low alarm 0.0 40.0 2.0 2+7+13
Disch. gas superheat Low warning 5.0 40.0 10.0 2+7+10
(°C) Low alarm 0.0 40.0 0.0 2+7+10
Calculated value

4-20 m Auxiliary input signal


Measuring Min Max Factory Note

Auxiliary input High alarm -999.9 999.9 0.0 3+18


(4-20 mA) High warning -999.9 999.9 0.0 3+18
Low warning -999.9 999.9 0.0 3+18
Low alarm -999.9 999.9 0.0 3+18

Table 5
Reciprocating compressors HPO/HPC
Measured and calculated pressure levels and
temperatures
Measuring Min Max Factory Note
0178_428_en.fm

Suction pressure High alarm - - -


(bar) High warning 1.5 25.0 10.0 3+4+5
Low warning -1.0 25.0 3.5 3+4+5
Low alarm -1.0 25.0 2.5 3+4+5

Discharge pressure High alarm 4.0 40.0 35.0 1+6


(bar) High warning 3.0 40.0 33.0 1+6
Low warning - - -
Low alarm -1.0 -1.0 -1.0 1+5

Oil pressure High alarm 5.0 7.0 6.0 2+7


(bar) High warning 5.0 7.0 5.5 2+7
Low warning 0.5 5.0 4.0
Calculated value Low alarm 0.5 5.0 3.5

High diff. pressure- High alarm - - 26.0 1+15


Pc - Pe (bar) High warning - - 25.2
Calculated value

Discharge temperature High alarm 60.0 170.0 160.0 1+6


(°C) High warning 50.0 170.0 155.0 1+6
Low warning -65.0 -65.0 -65.0
Low alarm - - -

Oil temperature High alarm 40.0 105.0 95.0 2


(°C) High warning 30.0 105.0 90.0 2
Low warning 0.0 70.0 55.0 2+7
Low alarm 0.0 70.0 50.0 2+7

0178-445 - ENG 51/222


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Measuring Min Max Factory Note

Water temperature High alarm -20 100.0 75.0 1+6


(°C) High warning -20 100.0 70.0 1+6
Low warning -20 100.0 4.0 1+6
Low alarm -20 100.0 2.0 1+6

Suction gas superheat High alarm 6.0 120.0 110.0 2+7


(°C) High warning 5.0 120.0 100.0 2+7
Low warning 0.0 40.0 4.0 2+10+13
Calculated value Low alarm 0.0 40.0 2.0 2+10+13

Disch. gas superheat Low warning 5.0 40.0 10.0 2+7+10


(°C) Low alarm 0.0 40.0 0.0 2+7+10
Calculated value

4-20 m Auxiliary input signal


Measuring Min Max Factory Note

Auxiliary input High alarm -999.9 999.9 0.0 3+18


(4-20 mA) High warning -999.9 999.9 0.0 3+18
Low warning -999.9 999.9 0.0 3+18
Low alarm -999.9 999.9 0.0 3+18

Notes: Note 9 Alarm monitoring 45 sec delayed af-


Note 1 The alarm cannot be switched off un- ter compressor start.
til the problem has been solved. Note 10 A setting of 0.0 impedes monitoring.
Note 2 The alarm can be switched off imme- Note 11 Delay of 300 sec, regardless of when
diately (RESET key). limits are exceeded.
Note 3 The alarm is switched off automati- Note 12 The compressor must have been
cally. above 5% capacity. Below 5% ca-
Note 4 The safety limits can be entered in pacity monitoring is impeded.
bar or °C/R. Note 13 Alarm monitoring 15 sec delayed af-
Note 5 Alarm monitoring active when digital ter compressor start.
output "compressor starting signal" Note 14 Delay of 60 sec, regardless of when
has been selected. limits are exceeded.
Note 6 Alarm monitoring always active - ex- Note 15 Only applies to HPO and HPC com-
cept when "BLOCKED" has been se- pressors.
lected in picture COMPRESSOR
Note 16 Alarm monitoring 20 sec delayed af-
CTRL MODE.
ter compressor start.
Note 7 Alarm monitoring 300 sec delayed
Note 17 For VMY Mk 2-2.5, calculate the fol-
after compressor start.
lowing (see Fig. 3.1): Oil pressure =
Note 8 Alarm monitoring 180 sec delayed Oil pressure 3 (after oil filter) - Dis-
after compressor start. charge pressure 2. For all other

52/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

compressor types (except for SAB be set between 1.1 and 1.7 bar or
80, see Note 20), calculate the fol- lower.
lowing: Oil pressure = Oil pressure 3 Note 20: Set points 1 and 2 are used for alarm
(after oil filter) - Suction pressure 1 . monitoring of the mechanical oil
Note 18 The limits are not active until AUX. pump, cf description of the alarm un-
INPUT SIGNAL has been selected in der "Oil pump error" in section Other
the menu CALIBRATION 4-20 mA. Alarms. For SAB 80, the oil pressure
Note 19 For SAB 80 the differential pressure is calculated as follows (see
across the oil filter is calculated as Fig. 3.1): Oil pressure = Oil pressure
follows (see Fig. 3.1): Oil filter diff. 3 (after pump) - Suction pressure 1.
pressure = Discharge pressure 2 - Note 21: The set points are used for control-
Oil pressure 4 (after oil filter). ling the oil pump. When the pressure
The shown oil filter pressure will thus falls below set point 1, the oil pump
be 0.1 to 0.7 bar higher than the ac- will start. When the pressure ex-
tual pressure loss across the filter ceeds set point 2 for 60 seconds, the
due to the pressure loss across the oil pump will stop.
oil separator and the oil cooler. Note 22: The set points are used for control-
ling the full flow pump. When the
0178_428_en.fm

The maximum allowed pressure


drop across the oil filter is 1.2 bar. pressure falls below set point 1, the
Consequently, the warning limit full flow pump will start. When the
should be set between 0.8 and 1.4 pressure exceeds set point 2 for 60
bar or lower. The alarm limit should seconds, the full flow pump will stop.

0178-445 - ENG 53/222


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Fig. 3.1

SAB 80

Oil
Oil filter separator

Oil pump Compressor

Oil cooler

Others

Oil
Oil filter separator

Oil pump
Compressor

Oil cooler

Suction pressure Discharge pressure

Oil pressure Oil pressure 2


(before compressor) (between pump and filter)

Suction gas superheat, alarm If the superheat falls below the set value, the com-
The superheat alarm is an alarm which in many pressor will stop on the relay. However, on R717
cases will protect the compressor against liquid pump circulation plants with a short distance be-
strokes. However, there are many aspects which tween liquid separator and compressor, the suc-
may affect superheating for which reason this tion gas superheat may drop below 0 K during
alarm must not be considered as full protection normal operation.
against liquid strokes.

54/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

In such cases adjust LOW ALARM to 0, thus alarm will be issued. The compressor will
making it inactive. stop.
3) If the compressor is REMOTE CONTROL-
Auxiliary input signal (4-20 mA) LED by a PC/PLC-system, a warning will
The alarm and warning limits are activated when be issued as well. The monitoring is possi-
AUX. INPUT SIGNAL has been selected under ble by means of a 4-20 mA signal in the aux.
CALIBRATION 4-20 mA. input or via communication.
The reason for the difference between situ-
Other alarms and warnings ation 1) and 2) is: If the system runs in se-
quence - REMOTE (MULTISAB), the com-
Oil system error (screw compressors) pressor must be stopped to start any subse-
quent compressors in the sequence.
The reason for the alarm is that the oil float switch
is not activated within the time set in the timer OIL When a compressor is remote controlled (3)
FLOW during prelubrication; or that there is a it is not a part of the sequence - REMOTE
drop-out on the oil float switch for a longer period (MULTISAB) system - thus stopping this
than the one set in the timer NO OIL during oper- compressor will not start up subsequent
ation. compressors.
0178_428_en.fm

Capacity error (screw compressors) PMS error


The reason for the alarm is that the capacity slide If the control is to start the compressor and conse-
is not below 5% within the time set in the timer quently adjusts the output START REQUEST
SLIDE MAX at compressor stop; or that the slide (PMS) to ON, the input START REQUEST OK
- during operation - has not moved within 30 mins, must be set on ON within the time set in the timer
although the regulator is to regulate up or down PMS FEEDBACK - or the alarm will be activated.
and the output signal from the regulator is above
20%; or that the slide - in connection with auto- No starting permission
matic setting of variable zero point - cannot reach The reason for the warning is that the regulator in
the position corresponding to calculated or adjust- REMOTE/MULTISAB cannot start this compres-
ed zero point (ie positive read capacity) before the sor, even though the regulator demands more ca-
expiry of the timer "cap.negative". pacity and this compressor is the next in line to
1) If the compressor is set on "MAN" or "AU- start. The reason is that AUTO START has not
TO" and in operation, and the slide does not been configured to YES, or the input EXTERNAL
react to the regulating signal within 30 mins, STARTING PERMISSION-NORMAL STOP is not
a warning will be issued. The compressor ON.
does not stop.
2) If the compressor is set on "REMOTE" and Compressor motor error
in operation, and the slide does not react to The reason for the warning is that feedback from
the regulating signal within 30 mins, an the motor is not set/does not disappear within the
time set in the timer MOTOR START when the

0178-445 - ENG 55/222


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

compressor motor is started/stopped (ie the out- Oil pump error (SAB 80)
put compressor start is activated/deactivated), or The reason for the alarm is that the differential
that feedback from the motor disappears even pressure across the mechanical oil pump is too
briefly during operation. low, ie lower than 0.5 Bar. This value can be set
The alarm may also occur at compressor start if as set point 1 for the oil pressure.
the emergency stop or an optional high pressure The alarm is delayed 45 seconds after compres-
control has been activated. sor start (same timer as for "low oil pressure").
The alarm is only activated when the discharge
Compressor motor overload pressure is lower than 16 Bar. This value can be
The reason for the alarm is that, within the time set set as set point 2 for the oil pressure.
in the timer CURR OVERL, a motor current has
At a discharge pressure level of approx 16 Bar,
been measured continually. This current exceeds
the pump cannot be expected to generate a posi-
the highest of the set point values that have been
tive relative pressure because of the shunt valve.
set in SET POINT 1 and SET POINT 2 for MO-
There is therefore no alarm surveillance of the dif-
TOR CURR.
ferential pressure across the oil pump.

Discharge pressure, overload


Full flow pump error (screw
The reason for the alarm is that, within the time set compressors)
in the timer DISCH.PRES, OVERLOAD, a dis-
The reason for the alarm is that feedback of the
charge pressure level has been measured contin-
full flow pump motor is not set/does not disappear
ually. This pressure level exceeds the warning
within the time set in the timer FULL FLOW M,
limit for high discharge pressure.
when the motor starts/stops (ie the output full flow
pumps start is activated/deactivated), or that
High motor temperature feedback from the motor disappears even briefly
The reason for the alarm is that the input THER- during operation.
MISTOR is open, ie the load on the input is above The alarm functions as a warning during opera-
3990 Ω. tion, ie after the prelubrication sequence has been
completed.
Oil pump error (screw compressors)
The reason for the alarm is that feedback from the Cooling fan error
oil pump motor is not set/does not disappear with- The alarm will be activated when feedback from
in the time set in the timer OIL PUMP M. when the the electrical cooling fan motor is not set/disap-
compressor starts/stops (ie the output oil pump pears within the time limit set in the timer FULL
start is activated/deactivated), or that feedback FLOW M. when the motor is started/stopped (ie
from the motor disappears even briefly during op- the cooling fan is activated/deactivated), or when
eration. feedback from the motor disappears even briefly
The alarm functions as a warning during opera- during operation.
tion, ie after the prelubrication sequence has been
completed.

56/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Oil rectifier error (screw compressors) Limiting discharge temperature


The reason for the alarm is that suction gas super- The warning indicates that the discharge pipe
heat has not exceeded the value set in SET temperature limiter is active. See section Limiting
POINT 1 before the timer RECT. DISABL has ex- functions, High discharge pipe temperature.
pired, although the OIL RECTIFIER has been set
and the compressor is running. No communication to Chiller
The alarm/warning will only be activated if
Wrong starting number in sequence UNISAB II is configured as part of a Chiller con-
The reason for the warning is that two or more trol, ie as SETUP I CONFIG I CHILLER = YES.
compressors have got the same starting number The alarm will only be activated if the communica-
and the same system number. tion between UNISAB II and the connected Chiller
disappears for a longer period than the one set in
Error in diagnosis - EEPROM the timer NO CHILLER.
The reason for the alarm is that it has become im-
possible to read and write in the serial EPROM Chiller, alarm from Chiller
(EEPROM) fitted on the CPU card, ie the serial The alarm will only be activated if UNISAB II is
EPROM is either missing or defective. configured as part of a Chiller control, ie as
0178_428_en.fm

SETUP I CONFIG I CHILLER = YES.


Limiting suction pressure The alarm will be activated if the alarm of the con-
The warning indicates that the suction pressure nected Chiller goes off.
limiter is active, ie the suction pressure is within
the limiter neutral zone or below the warning limit.
Watch the oil pressure
The warning will appear if the oil pump for oil
Limiting discharge pressure charging is started by means of the picture
The warning indicates that the discharge pressure TIMERS I OIL CHARGING
limiter is active, ie the discharge pressure is within and the compressor is in operation at the same
the limiter neutral zone or above the warning limit. time.

Limiting brine temperature Vi position error


The warning indicates that the brine temperature The alarm will only be activated if UNISAB II is
limiter is active, ie the brine temperatureis within configured for automatic Vi regulation, ie
the limiter neutral zone or below the warning limit. SETUP I CONFIG I VOLUME RATIO = AUTO
The alarm indicates that the display of capacity in
Limiting hot water connection with automatic Vi regulation is incor-
The warning indicates that the hot water tempera- rect. The real capacity of the compressor is lower
ture limiter is active, ie the hot water temperature than the one shown in the display.
is within the limiter neutral zone or above the
warning limit.

0178-445 - ENG 57/222


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Evolution, alarm from PLC The alarm will only be activated if there is no com-
munication between UNISAB II and the connect-
Evolution, warning from PLC ed PLC.

The alarm/warning will only appear if UNISAB II is


configured as part of an Evolution control, ie as Low lubricating pressure monitoring
SETUP I CONFIG. I COMMUNICATIONS I (screw compressor)
PORT 1 = EVOLUTION XXX The reason for this alarm is that the differential
The alarm will be activated if the alarm of the con- pressure across the compressor and thus the ef-
nected PLC goes off. fective lubricating pressure is too low. The differ-
ential pressure is calculated in the following way:
measured oil pressure - 1.1 x suction pressure.
Evolution, no communication to PLC
The differential pressure must be higher that the
The alarm will only appear if UNISAB II is config- set alarm limit for low oil pressure, see the draw-
ured as part of an Evolution control, ie as SETUP ing below. A warning will be issued after 25 sec-
I CONFIG. I COMMUNICATIONS I PORT 1 = onds and an alarm after 145 seconds.
EVOLUTION XXX
Fig. 3.2

LOW LUBRICATING PRESSURE


Pomeasured - 1.1 x
A P suc < lim A
t1 > 25 sec
yes
WARNING
yes

Pomeasured = Measured oil


pressure
No lim A = Alarm for low oil pres-
sure
LOW LUBRICATING
PRESSURE

No t1 > 145 sec ALARM


Yes
RESET
t1 = 0

No
t1 = 145 sec fixed

58/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Table 6
Identification numbers for alarms / warnings
This is a list of alarms and warnings with identification numbers for both screw and reciprocating compres-
sors.
Designation Screw compr. Recipr. compr. Id

Low suction pressure Warn + alrm Warn + alrm 31

High suction pressure Warn only Warn only 32

Low suction gas superheat Warn + alrm Warn + alrm 33

High suction gas superheat Warn + alrm Warn + alrm 34

Low discharge pressure Alrm only Alrm only 35

High discharge pressure Warn + alrm Warn + alrm 36

High discharge temperature Warn + alrm Warn + alrm 37

Low oil pressure (differential pressure) Warn + alrm Warn + alrm 38

Low brine / intermed. gas temperature Warn + alrm Warn + alrm 39

Low discharge temperature Warn only Warn only 40


0178_428_en.fm

Low oil temperature Warn + alrm Warn + alrm 41

High oil temperature Warn + alrm Warn + alrm 42

High oil filter differential pressure Warn + alrm 43

Oil system error ( oil flow switch ) Alrm only 44

Capacity error Warn + alrm 1) 45

Compressor motor overload Alrm only Alrm only 46

Compressor motor error/emergency stop/HP Alrm only Alrm only 47

Oil pump error Warn + alrm 2) 4) 48

High motor temperature (thermistor) Alrm only Alrm only 49

PMS error Alrm only Alrm only 55

No starting permission Warn only Warn only 56

High differential pressure (Pc - Pe) Warn + alrm 3) 57

High brine / intermed. gas temperature Warn + alrm Warn + alrm 58

High oil pressure Warn + alrm 59

High intermed. pressure Warn + alrm 60

Low intermed. pressure Warn + alrm 61

Full flow pump error Warn + alrm 2) 62

0178-445 - ENG 59/222


Rev. 03.09
UNISAB II 2.03
3. Alarms and Warnings

Designation Screw compr. Recipr. compr. Id

63

Oil rectifier error Warn only 64

Wrong starting number in sequence Warn only Warn only 65

Error in diagnosis - EEPROM Alrm only Alrm only 66

Low auxiliary input signal (univ. reg.) Warn + alrm Warn + alrm 67

High auxiliary input signal (univ. reg) Warn + alrm Warn + alrm 68

Low discharge gas superheat Warn + alrm Warn + alrm 69

Discharge gas overload Alrm only Alrm only 70

Evolution, alarm from PLC Alrm only Alrm only 71

Evolution, no communication to PLC Alrm only Alrm only 72

Limiter, suction pressure Warn only Warn only 73

Limiter, discharge pressure Warn only Warn only 74

Limiter, brine temperature Warn only Warn only 75

Limiter, hot water Warn only Warn only 76

Evolution, warning from PLC Warn only Warn only 77

Limiter, discharge temperature Warn only Warn only 78

Watch the oil pressure Warn only 79

Common alarm from Chiller Alrm only Alrm only 80

Chiller, no communication to Chiller Warn + alrm Warn + alrm 81

Cooling fan error Alrm only 82

Vi position error Alrm only 83

Lube press Warn + alarm 84


1) May occur as Warning in MAN and AUTO.
2) Alarm at prelubrication. Warning during operation.
3) Applies only to HPO/HPC.
4) The alarm LOW OIL PUMP PRESSURE DURING OPERATION applies to the SAB 80. The alarm is only activated at a discharge pres-
sure level below 16 Bar.

60/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

4. Timers
UNISAB II includes a number of timer functions reached at that particular moment. In this way it is
under the menu SETUP I TIMERS I . possible to know for how long the compressor has
been running since the last operating period.
When the compressor is restarted, the counter be-
TIMERS
1 TIMERS
gins from 0.
2 TIMER SETUP
3 SERVICE TIMERS 4. DATE - TIME - I
4 DATE-TIMER
This picture shows:
5 OIL CHARGING
6 MOTOR FAN TIME The time in hours
7 P BAND FACTOR MIN The time in minutes
8 TRANSFER SEC The time in seconds
9 TAKE - OVER DAY Date
MONTH Month
1. TIMERS - I YEAR Year
This picture includes all the timers and shows Must be set correctly in order for the alarms to be
which timers are activated (they are counting stored with the correct time. This function is pro-
0178_429_en.fm

down). vided with a battery back-up.

2.TIMER SETUP - I 5. OIL CHARGING - I (screw


In this picture the set values of the timers can be compressor)
changed. The timers and their functions appear Provided that the compressor is fitted with a pump
from the following tables for screw compressors for oil charging, this can be started in the picture
and reciprocating compressors respectively. OIL CHARGING. This picture shows:
Some of these timers can be changed using the
keyboard whereas others are fixed. The tables START OIL PUMP NO
also include the factory set values. TIMER 0 sec

3. SERVICE COUNTER - I To start the pump, proceed as follows:


Place the cursor on TIMER with K and use G for
ON TIME 00 HOUR
parameter changing. Set the time that the pump is
SINCE START 0 sec
to run and place the cursor on START OIL PUMP
On time J which is changed to YES with G and J . Con-
Indicates the total operating time of the compres- firm by pressing G.
sor. The pump will now start and run for the set period.
Since start In case the pump is to stop before time expiry,
Shows how long time the compressor has been select NO in the top line. The pump will now stop
running since it was last started. When stopping and the time drop to 0.
the compressor, the counter will stay on the value

0178-445 - ENG 61/222


Rev. 03.09
UNISAB II 2.03
4. Timers

6. MOTOR FAN I (Frequency To start the cooling fan manually, carry out the fol-
controlled screw compressor) lowing:
If the compressor is fitted with an electrical cooling Place the cursor on TIMER SP with K and press
fan for cooling the compressor motor, this can be G to change the parameter. Set the fan running
started manually in the picture COOLING FAN. time and place the cursor on START COOLING
The function is only available on frequency con- FAN. Select YES with G,and J . Enter setting
trolled compressors. with G .
The picture shows the following: The cooling fan will now start and operate for the
set running time.
START COOLING FAN NO To stop the cooling fan before the end of the
TIMER SP 10 sec running time, select NO in the upper line. The fan
TIMER 0 sec will now stop and the time be reset to 0.

62/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

Table 7 - Screw compressors


No Value Factory Low High Unit Adjust-
able

1 Start-start delay 1200 600 3600 Sec Yes

2 Stop-start delay 300 60 3600 Sec Yes

3 Start delay 300 0 3600 Sec Yes

4 Stop delay 300 60 3600 Sec Yes

5 Suction ramp 0 0 1200 Sec Yes

6 Slide max 300 60 600 Sec Yes

7 Prelub1)/2)/3)/4)/5)/6) 10/60/0/6/50 0 120 Sec Yes

8 Oil flow1)/2)/3)/4)/5) 600/90/60/120/600 -- -- Sec No

9 Oil flow delay 1)/2)/3) 50/0/20 -- -- Sec No

10 No oil/flow 1)/2) 10/2/60 - - Sec No

11 Lubrication time/flow 1)/2) 60/300 - - Sec No

12 Diff press OK 60 - - Sec No


0178_429_en.fm

13 Oil press low 1)/2) 45/300 - - Sec No

14 Filter diff high 300 - - Sec No

15 Oil temp low 300 - - Sec No

16 Oil temp high 300 - - Sec No

17 Superheating low 300 - - Sec No

18 Superheating high 300 - - Sec No

19 Disch press overload 300 - - Sec No

20 Current overload 300 - - Sec No

21 Motor start 15 5 120 Sec Yes

22 PMS feedback 60 10 300 Sec Yes

23 F.F. Pump start 10 5 30 Sec Yes

24 Oil pump start 10 5 30 Sec Yes

25 Oil rectifier start 900 0 3600 Sec Yes

26 Oil rectifier delay 300 0 3600 Sec Yes

27 Oil rectifier disable 3600 0 7200 Sec Yes

28 Start high pressure 30 0 120 Sec Yes

29 No Chiller 10 - - Sec No

0178-445 - ENG 63/222


Rev. 03.09
UNISAB II 2.03
4. Timers

No Value Factory Low High Unit Adjust-


able

30 Cap. negative 10000 60 20000 Sec Yes

31 Start unload 15 0 60 Sec Yes

32 Low suction pressure 0 0 60 Sec Yes

33 Lubricating pressure 145 - - Sec No

34 Vi-pause 60 - - Sec No

64/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

Table 8 - Reciprocating compressors


No Value Factory Low High Unit Adjust-
able

1 Start-start delay 1200 600 3600 Sec Yes

2 Stop-start delay 300 60 3600 Sec Yes

3 Start delay 300 0 3600 Sec Yes

4 Stop delay 300 5 3600 Sec Yes

5 Suction ramp 0 0 1200 Sec Yes

6 Delay up 60 5 1200 Sec Yes

7 Delay down 60 5 1200 Sec Yes

8 Take-over max 0 0 3600 Sec Yes

9 Take-over delay 300 300 300 Sec No

10 Intermediate pressure low 20 - - Sec No

11 Filter diff. high 300 -- -- Sec No

12 Not used -- -- -- -- --
0178_429_en.fm

13 Oil pressure low 60 - - Sec No

14 Oil pressure high 20 - - Sec No

15 Oil temp low 300 - - Sec No

16 Oil temp high 0 - - Sec No

17 Superheating low 15 - - Sec No

18 Superheating high 300 - - Sec No

19 Disch pressure overload 300 - - Sec No

20 Current overload 300 - - Sec No

21 Motor start 15 5 120 Sec Yes

22 PMS feedback 60 10 300 Sec Yes

23 Oil cool on 60 60 1500 Sec Yes

24 Oil return 0 0 1200 Sec Yes

25 Oil rectifier start 900 0 3600 Sec Yes

26 Oil rectifier delay 300 0 3600 Sec Yes

27 Oil rectifier disable 3600 0 7200 Sec Yes

28 Start high pressure 30 0 120 Sec Yes

29 No Chiller 10 - - Sec No

0178-445 - ENG 65/222


Rev. 03.09
UNISAB II 2.03
4. Timers

No Value Factory Low High Unit Adjust-


able

30 Not used - - - - -

31 Not used - - - - -

32 Low suction pressure 0 0 60 Sec Yes

33 Not used - - - - -

34 Not used

Timer description Used only in case of suction pressure regulation.


If the value is set at 0, this function is disconnect-
Screw compressors ed.
1. Start-start delay 6. Slide max
States the number of seconds that must pass from At compressor stop the capacity slide will move
one compressor start to the next. If the compres- towards minimum position. In case it fails to get
sor stops before the timer has counted down to 0, below 5% within the set time, an error message
the timer will block restart. will be issued.
2. Stop-start delay If UNISAB II tries to move the slide during opera-
States the number of seconds that must pass be- tion, and the slide refuses to move within the set
fore the compressor can be restarted after stop. time, an error message will appear.
This function is not used in MANUAL mode.
7. Prelubrication
3. Start delay When starting compressors with prelubrication
When UNISAB II is in AUTOMATIC or REMOTE, pumps, the prelubrication time is calculated from
the compressor start will be delayed for the stated the time when the oil float issues a signal.
number of seconds.
1) For SAB 202, SAB Mk3 and VMY Mk3.
4. Stop delay 2) For SAB 163 Mk1.
When UNISAB II is in AUTOMATIC or REMOTE
3) For SV 10/20, FV 10/20, SAB 110 SR/LR,
and the compressor is below 5% slide stop posi-
SAB 128 HR and SAB 163 HR.
tion, the timer will start counting down and stop
the compressor at 0. 4) For SAB 283, SAB 355, GSV, RWF and
SAB 330 B
5. Suction ramp
This timer indicates how fast the compressor is al- 5) For SAB 330 HP (B is short for Booster,
lowed to lower its suction pressure 1°C. The func- which can be selected in the CONFIG
tion is active as long as the compressor is working menu. HP means Booster = NO).
itself down to its normal working point. When this 6) For Rotatune compressors the time must be
has been reached, the compressor will be regulat- changed from 10 sec. to 0 sec.
ed according to the set regulating values.

66/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

8. Oil flow after the desired differential pressure has been


When prelubrication is initiated, a signal must be reached.
issued from the float switch before the timer ex- 13. Oil pressure low
pires; otherwise an error message appears.
During start the alarm for low oil pressure is de-
1) For SAB 202, SAB Mk3 and VMY Mk3. layed for the stated time. No delay during nor-
2) For SAB 163 Mk1. mal operation.

3) For SV 10/20 and FV 10/20 1. For SAB 202, SAB Mk2, SAB Mk3, VMY,
SAB 80, SV 10/20 and FV 10/20.
4) For SAB 283, SAB 355, GSV, RWF and
SAB 330 B 2. For SAB 163 Mk 1

5) For SAB 330 HP (B is short for Booster, 14. Filter diff. high
which can be selected in the CONFIG During start and operation the alarm for high filter
menu. HP means Booster = NO). differential pressure is delayed for the stated time.

9. Oil flow switch delay, start 15. Oil temp. low


When starting a compressor, a time delay ensures During start the alarm for low oil temperature is
that the oil float has time to lift. delayed for the stated time. No delay during nor-
mal operation.
1. For SAB Mk 2 110/128/163 and SAB 80.
0178_429_en.fm

16. Oil temp. high


2. For compressors with prelubrication delay =
0 sec. During start the alarm for high oil temperature is
delayed for the stated time. No delay during nor-
3. For SV 10/20 and FV 10/20 mal operation.
10. No oil/flow 17. Superheating low
During operation the oil float is allowed to be dis- During start the alarm for low superheating is de-
connected only for the period stated. layed for the stated time. No delay during nor-
1. For SAB and VMY compressors. mal operation.
2. For SV 10/20 and FV 10/20 18. Superheating high
3. For GSV/RWF During start the alarm for high superheating is de-
layed for the stated time. No delay during nor-
11. Lubrication time/flow
mal operation.
After start-up of compressors with prelubrication
pump, the pump will run for the time stated after 19. Disch. pressure, overload
compressor start. If the discharge pressure is higher than the warn-
ing limit in the time stated, the compressor will
1. For SAB 202, SAB Mk3 and VMY Mk3, SV
stop and an error message will appear.
10/20 and FV 10/20
See also Limiters.
2. For SAB 163 Mk1.
20. Current overload
12. Diff. pressure OK
If the motor current is higher than the set point in
For VMY Mk3, SAB Mk3, SAB 202, SV 10/20 and
the time stated, the compressor will stop and an
FV 10/20 the oil pump will run for the stated time
error message will appear.

0178-445 - ENG 67/222


Rev. 03.09
UNISAB II 2.03
4. Timers

See also Limiters. 28. Start high pressure


21. Motor start On two-stage plants the HP compressors can be
started by force by activating the input
When the compressor starts, the motor guard
External starting permission, normal stop.
must issue a feedback before the timer expires; if
not, an error message will appear. The start will be delayed for the set number of sec-
onds.
The green light diode above the starting key A will
flash until feedback has been received whereup- With the compressors in sequence, number 1 in
on the light will be steady. the sequence will start and the system will now
operate normally.
22. PMS (Starting request) feedback
After the control has issued a starting request, it 29. No Chiller
must receive a feedback within the stated time; if When UNISAB II is configured as part of a Chiller
not, an error message will appear. control, the timer will ensure that communication
between UNISAB II and the connected Chiller
23. F. F. Pump start
does not disappear for a period longer period than
In case the motor guard of the full flow pump has
the set time. If this happens, both UNISAB II and
failed to issue a feedback within the stated time af-
UNISAB II-Chiller will be stopped by the alarm.
ter the starting signal, an error message will ap-
pear. 30. Cap. negative
When the compressor is started, the slide must
24. Oil pump start
move to the position corresponding to the set zero
In case the motor guard of the oil pump has failed
point (ie positive read capacity) as quickly as pos-
to issue a feedback within the stated time after the
sible before the expiry of the cap. negative timer.
starting signal, an error message will appear.
Otherwise an error message will be issued. The
25. Oil rectifier start cap. negative timer counts down each second by
Whenever the compressor starts, this timer will be the value: (corrected capacity)2/5, where corrected
activated and start counting down. When 0 has capacity may be negative values between -0 and
been reached, the solenoid valve to the oil rectifier -30%, ie the timer will count down each second by
will be activated. a factor between 1 and 180.
26. Oil rectifier delay Each time the slide moves above 0% capacity, the
If suction gas superheating drops below set point timer will stop.
1 for superheating, the solenoid valve will close. The timer is reset and restarted, as soon as the
Once the superheating rises above this limit slide moves below -2% corrected capacity.
again, the timer must expire before the solenoid
valve opens. 31. Unloaded start
The timer is used in connection with the compres-
27. Oil rectifier disable sors FV 17/19. When the compressor motor is
If suction gas superheating drops below set point started, a by-pass solenoid valve for oil discharge
1 for superheating, the timer will start counting will open for the time set.
down. Provided the superheating still remains be-
The timer is used in connection with the compres-
low the limit once the timer has reached 0, a warn-
sors FV 24/26. When the compressor motor is
ing will be issued to a superior computer.

68/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

started and stopped, the slide capacity down sole- the timer will start counting down and stop the
noid valve will open for the time set. compressor at 0.
32. Low suction pressure 5. Suction ramp
During start-up and operation the alarm for low This timer indicates how fast the compressor is al-
suction pressure is delayed for the indicated peri- lowed to lower its suction pressure1°C/R. If the
od of time. value is set for 0, this function will be disconnect-
ed.
33. Lubricating pressure
During start-up and operation the alarm for low 6. Delay up
suction pressure is delayed for the indicated peri- Indicates the time that passes between the load-
od of time. A warning is issued after 25 seconds. ing of stages at increasing capacity in AUTOMAT-
IC or REMOTE mode.
34. Vi-pause
The timer is used in connection with GST com- 7. Delay down
pressors, which have a three-stage automatic Indicates the time that passes between the un-
regulation of the volume ratio, 2.2-3.5-5.0. Before loading of stages at decreasing capacity in AUTO-
switching from one Vi-step to another, the actual MATIC or REMOTE mode.
Vi ratio for the compressor must have been
8. Take-over max
present for at least the indicated time other wise
Only used in connection with MULTISAB. See this
0178_429_en.fm

the change of the Vi step will be cancelled.


instruction manual.
9. Take-over delay
Reciprocating compressors
Only used in connection with MULTISAB. See this
1. Start-start delay instruction manual.
States the number of seconds that must pass from
one compressor starts to the next. If the compres- 10. Intermediate pressure low
sor stops before the timer has reached 0, the timer During start the alarm for low intermediate pres-
will block restart. sure is delayed for the stated time. No delay dur-
ing normal operation.
2. Stop-start delay
States the number of seconds that must pass be- 11. Filter diff. high
fore the compressor can be restarted after stop. 1. SMC Mk4; during start-up and operation,
This function is not used in MANUAL mode. the warning for high oil filter differential pres-
sure is delayed for the indicated period of
3. Start delay time.
When UNISAB II is in AUTOMATIC or REMOTE,
2. For SMC Mk3 and earlier versions, this tim-
the compressor start will be delayed for the stated
er is not used.
number of seconds.
12. Not used
4. Stop delay
When UNISAB II is in AUTOMATIC or REMOTE, 13. Oil pressure low
and the compressor is at its lowest capacity stage, During start and operation the alarm for low oil
pressure is delayed for the stated time.

0178-445 - ENG 69/222


Rev. 03.09
UNISAB II 2.03
4. Timers

14. Oil pressure high 23. Oil cool on


During start the alarm for high oil pressure is de- At compressor stop the outlet for water cooling or
layed for the stated time. No delay during nor- oil cooling will not close until after the set time has
mal operation. run out.
15. Oil temperature low 24. Oil return
During start the alarm for low oil temperature is At compressor start the outlets for oil return are
delayed for the stated time. No delay during nor- not opened until after the set time has run out.
mal operation.
25. Oil rectifier start
16. Oil temp high Whenever the compressor starts, the timer will be
During start the alarm for high oil temperature is activated and start counting down. When 0 has
delayed for the stated time. No delay during nor- been reached, the solenoid valve to the oil rectifier
mal operation. will be activated.
17. Superheating low 26. Oil rectifier delay
During start the alarm for low superheating is de- If the suction gas superheating drops below set
layed for the stated time. No delay during nor- point 1 for superheating, the solenoid valve will
mal operation. close. Once the superheating rises above this limit
again, the timer must expire before the solenoid
18. Superheating high
valve opens.
During start the alarm for high superheating is de-
layed for the stated time. No delay during nor- 27. Oil rectifier disable
mal operation. If suction gas superheating drops below set point
1 for superheating, the timer will start counting
19. Disch. pressure, overload
down. Provided the superheating still remains be-
In case the discharge pressure is higher than the
low the limit once the timer has reached 0, a war-
warning limit within the stated time, the compres-
ning will be issued to a superior computer.
sor will stop.
28. Start high pressure
20. Current overload
On two-stage plants the HP compressors can be
In case the motor current is higher than the set
started by force by activating the input External
point within the stated time, the compressor will
starting permission, normal stop. The start will
stop.
be delayed for the set number of seconds.
21. Motor start
With the compressors in sequence, number 1 in
When the compressor starts, the motor guard
the sequence will start and the system will now
must issue a feedback before the timer expires; if
operate normally.
not, an error message will appear.
29. No Chiller
22. PMS (Starting request) feedback
When UNISAB II is configured as part of a Chiller
After the control has issued a starting request, it
control, this timer will ensure that the communica-
must receive a feedback within the stated time; if
tion between UNISAB II and the connected Chiller
not, an error message will appear.
does not disappear for a period longer than the set

70/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

time. If this occurs, both UNISAB II and Stop delay


UNISAB II-Chiller will be stopped by the alarm. If the value 0 is selected, the timer will start to
30. Not used count when the measured value of the regulator is
in the neutral zone.
31. Not used
If the value 1 is selected, the timer will not start to
32. Low suction pressure
count until the measured value of the regulator is
During start-up and operation the alarm for low
1% inside the proportional band below the neutral
suction pressure is delayed for the indicated peri-
zone.
od of time.
If the value 100 is selected, the timer will not start
33. Not used
to count until the measured value of the regulator
34. Not used. is 100% inside the proportional band below the
neutral zone.
7. P BAND FACTOR - I Sp = Set point
In case of a screw compressor, the following Nz = Neutral zone
picture will appear: Pb = Proportional band
Example 1:
START DELAY 1 UNISAB II has been set for suction pressure reg-
0178_429_en.fm

STOP DELAY 0 ulation,


Sp = -10 °C,
Start delay Nz = 2 K, Pb = 10 K,
Start delay can be changed in the range from 1 to START DELAY = 90 sec and FACTOR = 50.
100. Stop delay can be changed in the range from
STOP DELAY = 60 sec and FACTOR = 30.
0 to 100. The function of these zones must be
seen in connection with the applied regulator (suc- In the neutral zone and up to -4°C the compressor
tion pressure, brine, etc). will not be in operation. If the measured suction
pressure is a little higher than -4°C, the START
If the value 1 is selected, the timer will not start to
DELAY timer will start counting and the compres-
count until the measured value of the regulator is
sor will start after 90 seconds. If necessary, a
1% inside the proportional band above the neutral
compressor start can thus be delayed or blocked.
zone.
In the neutral zone and up to -14°C the compres-
If the value 100 is selected, the timer will not start
sor will be in operation. If the measured suction
to count until the measured value of the regulator
pressure is a little lower than -14°C and the capac-
is 100% inside the proportional band above the
ity slide is below 5%, the STOP DELAY timer will
neutral zone.
start counting and the compressor will stop after
Whether 1% or 100% is selected, the timer - when 60 seconds.
it is started - will count in seconds without exten-
Example 2:
sion (this is not the case with reciprocating com-
UNISAB II has been set for suction pressure
pressors, see next section).
change,
Sp = -20 °C,

0178-445 - ENG 71/222


Rev. 03.09
UNISAB II 2.03
4. Timers

Nz = 4K, Pb = 10 K, Each of these factors can be selected in the range


START DELAY = 90 sec and FACTOR = 10. 1-10.
STOP DELAY = 60 sec and FACTOR = 0. In AUTO and REMOTE mode, the various
In the neutral zone and up to -17°C the compres- P BAND FACTORs are influencing the decision of
sor will not be in operation. If the measured suc- when to start or stop the compressor or, for recip-
tion pressure is a little higher than -17°C, the rocating compressors, when to engage or disen-
START DELAY timer will start to count and the gage another capacity stage.
compressor will start after 90 seconds. If neces- Basically, starting and stopping as well as engag-
sary, a compressor start can thus be delayed or ing and disengaging are delayed by the timers
blocked. START DELAY, STOP DELAY, DELAY UP and
As long as the measured suction pressure is in the DELAY DOWN. See section Timer description.
upper proportional band, the compressor will be in The relevant timers start as soon as the regulated
operation. If the measured suction pressure is a input (eg suction pressure) is just outside the neu-
little lower than -18°C and the capacity slide is be- tral zone.
low 5%, the STOP DELAY timer will start to count There is one P BAND FACTOR for each of these
and the compressor will stop after 60 seconds. timers.
In case of a reciprocating compressor, the fol- If the P BAND FACTOR is 1, the time delay will be
lowing picture will appear: the same no matter if the regulated input is just
outside the neutral zone or far outside the neutral
zone.
DELAY UP 1
DELAY DOWN 1 By selecting a P BAND FACTOR higher than 1
START DELAY 1 (up to 10), it is possible to have the timer run slow-
STOP DELAY 1 er when the regulated input is close to the neutral
zone as illustrated in the drawing.
Fig. 4.1

Timer step [sec]


PBF = P.Band Factor
Diff = Measuring value - Setpoint

PBF

1
Diff
-NZ 0 NZ PB
-PB

When the regulated input is outside the P band just outside the neutral zone (NZ), each count-
(PB), the timer will run at normal speed, as it is down will last one PBF second.
counting in seconds. When the regulated input is

72/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

In this way, a compressor start can be delayed or When the measured discharge pressure exceeds
blocked if there is no particular cooling require- 31°C/R, the timer DELAY DOWN will begin to
ment. However, if the deviation is large, the timer count with an interval of 3 sec (P BAND FACTOR)
will count down fast and start the compressor. each time the value in the display counts one
down. If the pressure steadies, the timer will run
Example 1:
for 3 x 30 = 90 seconds.
Suction pressure regulation has been selected.
The measured suction pressure equals the set Should the measuring value reach 33.5°C/R, the
point. The compressor is stopped and ready to counting interval will be 2 sec.
start. If the pressure is still moving upwards and ex-
Set point Sp = -10°C/R ceeds 36°C/R (the Pb limit), the timer will count in
Nz = 2°C/R seconds.
Pb = 5°C/R
The resulting total delay will range between 30
START DELAY = 60 sec
and 90 seconds, after which the compressor will
P BAND FACTOR START DELAY = 5.
disengage one capacity stage.
When the measured suction pressure exceeds
-9°C/R, the START DELAY timer will begin to
Special timers in connection with
count with an interval of 5 sec (P BAND FACTOR)
MULTISAB
each time the value in the display counts one
0178_429_en.fm

Reciprocating compressors
down. If the pressure steadies, the timer will run
for 5 x 60 = 300 seconds. In the MULTISAB system which regulates and op-
timizes more than one compressor, there are a
Should the measuring value reach -6.5°C/R, the
number of factors attached to a TRANS-
counting interval will be 3 sec.
FER/TAKE-OVER function between reciprocating
If the pressure is still moving upwards and ex- and screw compressors. These factors are de-
ceeds -4°C/R (the Pb limit), the timer will count in scribed in detail in section MULTISAB regulation.
seconds.
The factors are found in the pictures:
The resulting total delay will range between 60
and 300 seconds, after which the compressor will 8.TRANSFER - I Reciprocating
start. compressors
Example 2:
Discharge pressure regulation has been selected FACTOR DOWN 1
on a reciprocating compressor. The measured ZONE 15%
discharge pressure equals the set point. The com-
pressor is running at 100% capacity.
Set point Sp = 30°C/R 9.TAKE-OVER - I Reciprocating
Nz = 2°C/R compressors
Pb = 5°C/R
DELAY DOWN = 30 sec FACTOR UP 1
P BAND FACTOR DELAY DOWN = 3. FACTOR START 1
ZONE 15%

0178-445 - ENG 73/222


Rev. 03.09
UNISAB II 2.03
4. Timers

MULTISAB If MULTISAB is to function optimally, it is of vital


MULTISAB is a distributed compressor control importance that certain key parameters are se-
system, which is very useful when more compres- lected correctly by the user as explained in section
sors are working together (eg connection to the MULTISAB regulation. To understand the con-
same suction line). With MULTISAB it is possible tents of the MULTISAB pictures, the following key
to start, stop and capacity regulate compressors parameters are described here: COMPR. NO,
according to the varying cooling requirements. SYSTEM NO, PREF. MASTER, START NO and
MULTISAB is a standard function in UNISAB II. CONTROL MODE.
MULTISAB is described in detail in section MUL- Always make sure that all UNISAB II units on a
TISAB regulation. network have different COMPR. NOs, ie two units
MULTISAB is only able to work if all UNISAB II are not allowed to have the same COMPR. NO.
units which are to participate in the distributed See section Configuration.
control are physically connected via the Danbuss SYSTEM NO informs MULTISAB which com-
communication network. The section Installation pressors are to work together. The drawing below
of data communication cable describes how to shows two examples.
connect the units.
Fig. 4.2

SYSTEM NO
= 1 or 2
Compr. 1 Compr. 1

Suction line, subplant 1 SYSTEM NO


= 1 or 2
SYSTEM NO = 1
Compr. 2 Compr. 2

Common Multisab
Multisab network Suction main line 1
network
SYSTEM NO SYSTEM NO = 1
= 1 or 2
Suction main line 2
SYSTEM NO = 2
Compr. 3
Compr. 3

Suction line, subplant 2


SYSTEM NO
SYSTEM NO = 2 = 1 or 2
Compr. 4 Compr. 4

Separated compressor plants Common compressor plant

In the example to the left, two separate compres- • UNISAB No 3 has the same SYSTEM NO
sor plants are connected on a common Danbuss as UNISAB No 4
network. Here it is of vital importance that • SYSTEM NO of UNISAB 1 and 2 differs
• UNISAB No 1 has the same SYSTEMNO as from SYSTEM NO of UNISAB 3 and 4.
UNISAB No 2

74/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

In the example to the right, each of the four com- alarm condition may be due to a sensor error, re-
pressors can be connected independently to any sulting in a change of SYS CONTROLLER and
of the two suction main lines. In this example is is thus of sensor.
also important that SYSTEM NO is correct. How- In order for a compressor to become part of a
ever, it is particularly important that when chang- MULTISAB system, the above key parameters
ing the valve settings, the SYSTEM NO in the must be set up. CONTROL MODE must be set for
UNISAB II units in question is changed according- REMOTE. In other words, by changing the CON-
ly as this does not take place automatically. TROL MODE, the user is able to include and ex-
START NO defines the priority of the compres- clude the compressor from the MULTISAB sys-
sors with common SYSTEM NO. The unit with the tem. See section Compressor regulation.
lowest START NO will be the first to start. The MULTISAB functions are found in the menu
PREF. MASTER must be indentical for all units SETUP I MULTISAB I
with the same SYSTEM NO. See section Config-
uration. PREF. MASTER specifies whether it is
MULTISAB
COMPR. NO or START NO which is to define
MULTISAB STATE
which UNISAB II is to be SYS CONTROLLER.
ALL COMPRESSORS
SYS CONTROLLER is responsible for the co-or- PARALLEL CONTR.
dination of the involved units. It is the sensor of the
0178_429_en.fm

SYS CONTROLLER (eg suction pressure input)


which is used for the regulation. 1. MULTISAB STATE - I
If PREF. MASTER = #COMPR, the unit with the
lowest COMPR. NO will be SYS CONTROLLER START NO 1
except if the UNISAB II unit in question is shut off SYSTEM NO 1
or otherwise unable to communicate. In such cas- SYS. CONTROLLER 1
es the unit with the next COMPR. NO will take MAY START
over as SYS CONTROLLER.
Here START NO and SYSTEM NO can be adjust-
If PREF. MASTER = #START, the unit with the
ed in the range 1-14. Furthermore, SYS CON-
lowest START NO will be SYS CONTROLLER,
TROLLER shows which unit is the master as ex-
but only as long as it is available. If it is not avail-
plained above.
able, the unit with the next START NO will take
over as SYS CONTROLLER. A unit is not availa- In the fourth line of the picture, the MULTISAB
ble if it is shut off, not communicating, not in RE- status of the UNISAB II in question is shown. The
MOTE mode or in shutdown alarm condition. An status can be one of the following:

State Explanation

BLOCKED The compressor cannot (and is not going to) start MULTISAB now.

NOT MY TURN Another compressor must start before this one / there is no cooling requirement.

MAY START Starts when START DELAY expires as there is now a cooling requirement.

0178-445 - ENG 75/222


Rev. 03.09
UNISAB II 2.03
4. Timers

State Explanation

RUNS AT MAX CAP Must run at 100% capacity.

LEAD COMPR. Runs in parallel operation as master.

LAG COMPR. Runs in parallel operation as slave.

MAY STOP Is below 5% capacity, stops when STOP DELAY expires.

RUNS BY ITSELF Is the only compressor in the system that is in operation.

STOP RAMP UP Stops parallel operation, as master - only screw compr.

STOP RAMP DOWN Stops parallel operation, as slave - only screw compr.

2. ALL COMPRESSORS - I Control mode


Operating mode of compressor no 01. In this ex-
ample compressor no. 01 is in MANUAL mode.
COMPR. # 01 MANUAL
Control mode be one of the following: STOPPED,
SYSTEM # 01
MANUAL, AUTO or REMOTE.
START # 02
READY 0% SYSTEM #
SYSTEM NO of compressor no 01.
This picture makes it possible - from a UNISAB II
START #
unit - to see MULTISAB information about the oth-
START NO of compressor no 01.
er compressors in the communication network.
Status
COMPR. #
Compressor operating status of compressor no.
The number of the observed UNISAB II unit. In
01. Operating status can be one of the following:
this example it is compressor no 01.

State Explanation
READY UNISAB II is ready to start.
RUNNING Compressor in operation.
STARTING Compressor motor start-up.
SHUTDOWN In a state of alarm.
PAUSE Waiting for a timer to expire.
PRELUB Working on the prelubrication sequence.
CAP SLIDE DOWN Runs the slide down after stop.
RUNS AT OVERL. Motor current too high.
DISCHARGE LIM. Discharge pressure too high.
SUCTION LIM. Suction pressure too low.
STOPPED Compressor cannot start.

Capacity Capacity of compressor no 1.

76/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
4. Timers

The picture can of course be used for getting an NEXT


overall view of the MULTISAB operation of the The number of the compressor which is next in the
plant. starting sequence - (higher START NO)
It may also be used for testing whether the com- FOLLOWING
munication between the UNISAB II units on the The number of the compressor which follows the
network is working. In case there is no communi- next compressor in the starting sequence (an
cation to one of the UNISAB II units, the status even higher START NO).
field in line 4 will be replaced by a "?".
PARALLEL CAP
The percentage at which MULTISAB is going to
3. PARALLEL CONTR. - I stop this compressor, when this compressor is
one of the two screw compressors that run in par-
PRECEDING 2 allel.
NEXT 3
OFFSET
FOLLOWING 0
PARALLEL CAP 45.0 % Can be set between 0.0% and -20.0%. The OFF-
OFFSET -10.0 % SET value is added to the calculation of PARAL-
LEL CAP. After entering an OFFSET value (not
This picture shows the numbers of the compres- 0), the PARALLEL CAP value will be reduced ac-
0178_429_en.fm

sors which come before and after this compressor cordingly. This means that the point at which the
in the starting sequence and which can start. The lag (screw) compressor is stopped is reduced by
last two lines only apply to screw compressors. the OFFSET value. This may be useful when wa-
PRECEDING ter chillers are running in parallel as these units
The number of the compressor that comes before may have a relatively better COP at part load
this compressor in the starting sequence - (lower (heat transfer being better at part load). Note that
START NO). the OFFSET value is not changed by a FACTORY
RESET.

0178-445 - ENG 77/222


Rev. 03.09
UNISAB II 2.03
4. Timers

78/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

5. Compressor regulation

Control mode MOTE, one (and only one) of these regulators is


The compressor can be adjusted for different responsible for adjusting the capacity according to
modes of operation. These are found in SETUP I the cooling (or heating) requirements. Which reg-
CONTROL I . ulator to use is specified in Pos. 3: CONTROL ON
in the menu CONFIG. See section Configuration.
CONTROL ON can be set to one of the following:
COMPRESSOR CONTROL
STOPPED
• SUCTION
• BRINE
When this picture is selected, the cursor will be • DISCHARGE
positioned in the top line. Press G and the cursor • HOT WATER
moves to the second line. • EXT.COOL
• EXT.HEAT
Select the desired mode of operation with J K.
There are the following possibilities: Each regulator has its own set of parameters. This
means that when changing the CONTROL ON
• STOPPED
setting from one regulator to another and back
• MANUAL
0178_430_en.fm

again, the original parameters are kept.


• AUTO
• REMOTE The common regulator parameter set includes:
Set point (SP), Neutral zone (Nz) and Propor-
STOPPED means that the compressor is blocked
tional band (Pb or P Band). On screw compres-
and thus cannot start.
sors PID parameters are also used. See section
MANUAL means that the compressor only oper- PID controller below.
ates manually, ie it is not possible to change to an-
Set point is the pressure or the temperature de-
other mode by means of C .
sired in the plant.
The compressor can, however, be started with A
Neutral zone indicates how much the pressure or
and stopped with B. Capacity is increased/de-
the temperature is allowed to fluctuate in relation
creased with E F.
to the Sp without the compressor changing its ca-
AUTO means that the compressor runs in local pacity. The set value of Nz is positioned symmet-
automatic operation according to the form of reg- rically around the set point (Sp +/- 1/2 Nz).
ulation chosen (suction pressure, brine, etc). It is
Proportional band indicates how powerful the
possible to change to MANUAL with C.
regulating signal to the compressor capacity reg-
REMOTE means that the compressor works to- ulation is going to be, depending on the difference
gether with one or more compressors in a com- between the desired value (Sp) and the actual val-
mon MULTISAB control system. ue.
In case the measured value is just outside the Nz,
Regulators the regulating impulses will be very short, where-
UNISAB II includes a number of compressor ca- as the regulating impules will be very long if the
pacity regulators. In the modes AUTO and RE-
0178-445 - ENG 79/222
Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

measured value is outside the P Band. The P


Band is positioned symmetrically around Sp out-
side the Nz.
Fig. 5.1

rapidly up

Very slowly up

SP
P.Band P.Band

Error signal
NZ

Very slowly down

rapidly down

Screw compressors pendent of any other outside influence on the ca-


Screw compressors are capacity regulated (hy- pacity slide.
draulically or electrically) by moving the capacity When active, the outer loop will adjust the capac-
slide. This takes place via two digital outputs ity set point according to the selected control set
which are controlled by UNISAB II, so that the point and measured value, eg the suction pres-
slide moves towards max or min capacity accord- sure set point and measurement. In MANUAL
ing to demand. The setting is stageless from 0 to mode, the outer loop is not active. In AUTO, the
100%. UNISAB II will usually pulse the digital out- outer loop is active according to the CONTROL
puts with a pulse/delay ratio. Consequently, a ON setting. See section Regulators.
constant up or down signal will rarely be given. The inner loop set point can also be controlled via
The capacity control must be seen as two PID the external input (see section Set point control
control loops. with current input) or via the communication net-
The inner loop adjusts the slide position continu- work.
ously according to the manually or automatically Inner loop parameters are set in picture SETUP I
selected capacity set point. As long as this set CAPACITY I CAPACITY. The picture includes
point is constant, the inner loop will ensure that the standard PID parameters and the points de-
the capacity slide remains in this position, inde- scribed in section PID controller below. Addition-
ally the following parameters can be selected:
80/222 0178-445 - ENG
Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

• MIN PULSE is the shortest pulse that Outer loop parameters are set in the relevant pic-
UNISAB II will give on the relay output, eg it ture, eg SUCTION I SUCT. PRESS. The picture
takes time for a hydraulicvalve to open and includes the standard PID parameters and the
close, and for the hydraulic oil to move, so a points described in section PID controller below.
pulse shorter than about half a second The automatic Vi slide control works in the same
would have no effect and would only short- way as the inner loop. The parameters are availa-
en the service life of the valve and the relay. ble in picture CAPACITY I VI POSITION.
A longer MIN PULSE increases the service
life of the hardware, but it also makes the
PID controller
regulation less accurate.
On screw compressors a PID controller is used for
• RUN TIME is the approximate time it takes
capacity control and possible Vi control. The the-
for the capacity slide to move from minimum
ory of PID controllers is described in numerous
position to maximum position and vice versa
books on automatic control. Methods of optimiz-
at constant signal. Please note that RUN
ing the parameters are also included in these
TIME for the capacity slide may be reduced
books. The available parameters are described
by variable slide end stop etc where this is
briefly in the following.
relevant.
In the relevant picture, eg SUCTION I SUCT.
0178_430_en.fm

PRESS., the following data are included:

Name Description

ACTUAL SP. The set point which the PID controller works with at the moment.

SET POINT 1 User selected set point 1

SET POINT 2 User selected set point 2

NEUTRAL ZONE The neutral zone is a symmetrical area around ACTUAL SP. When the controlled val-
ue is inside the area, the controller will be passive. The purpose is to increase service
life of the output hardware (relays, valves, spindle motor, etc). However, with the PID
controller this is handled by MIN PULSE, so that the NEUTRAL ZONE should be set
for 0. A larger NEUTRAL ZONE makes the regulation less accurate.

PROP. BAND This parameter decides the total gain in the control loop, as the gain K=n / (PROP.
BAND) where n is a constant that depends on RUN TIME. Thus changing PROP.
BAND does not only affect the proportional term, but also the integral and differential
terms. Increasing PROP. BAND will give a slower response.

T. INT. Integral Time decides the gain of the integral term. A smaller T. INT means a larger
gain, ie the controller will try to reach the set point faster.

T. DIFF. Differential Time decides the gain of the differential term. A larger T. DIFF means a
larger gain. Normally select T. DIFF = 0 as it is then working as a PI controller.

P. PART This field shows the actual Proportional term calculated by the PID controller.

I. PART This field shows the actual Integral term calculated by the PID controller.

0178-445 - ENG 81/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Name Description

D. PART This field shows the actual Differential term calculated by the PID controller

REG. OUTPUT The actual Regulator Output is the sum of P. PART, I. PART and D. PART.

PID regulator If the slide speed for some reason cannot be ad-
With version 2.01, the PID regulator was intro- justed for 60 seconds, the RUN TIME parameter
duced to replace the previous “three-point I regu- must be changed so that run time corresponds to
lator”. It is very important that the parameters ap- the actual operating conditions. If this is not done,
pearing by a factory reset be used. it will appear as if the PID regulator is out of con-
trol, ie it will increase capacity when it should de-
There are both an inner and an outer loop. As re- crease capacity as well as go far beyond its set-
gards the outer loop, it is not recommended to ad- point.
just the P band further down than 10°C and T.INT.
further down than 20 seconds. Higher values may If it is necessary to set the RUN TIME value higher
very well occur. T.DIFF. is usually always 0. The than 60 seconds, YORK Refrigeration recom-
neutral zone can be set for 0.4°C or higher if it is mends increasing the integral-time (T.INT) corre-
not required that the suction pressure is kept as spondingly. Do not, however, use a T.INT. higher
narrow as possible around the set point. If the than 120 seconds as this may prevent the capa-
neutral zone is too high, the regulator may fluctu- city slide from reaching 100%. A T.INT increase
ate too much. informs the system that slide function is slower
than expected.
As regards the inner loop it is recommended only
to use the default values for neutral zone (0.0), P Example 1
band (200%), T.INT. (30 seconds) and T.DIFF. (0 Screw compressor with a combination of slide
seconds)..The parameter MIN PULSE determines regulation and frequency regulation.
the pulse duration up or down every time the sole- Slide velocity is 60 seconds from 0-100% slide
noid valve is activated. If the value is high, a cor- movement. This may be shown as 0-42% capacity
respondingly large capacity change is required on the UNISAB II display. When the slide has
before the regulator reacts with an up or down sig- reached 100%, the frequency converter will start
nal. This is a kind of neutral zone. Default value is to increase the frequency to the max frequency
0.5 seconds and should not be higher than 2 sec- set. This will take 60 seconds and be shown as
onds. 42-100% in the UNISAB II display. Thus the RUN
The parameter RUN TIME defines how long it will TIME parameter must be set for 60+60=120 sec-
take to run the slide from 0-100% at constant up onds for correct regulation.
signal or from 100-0% at constant down signal. When switching between manual and automatic
Usually slide speed is always adjusted on the oil control, another difference between the PID regu-
needle valves positioned on the capacity regulat- lator and the previous regulator can be seen. A
ing block so that the slide speed is approx 60 sec- suction pressure level which is much higher than
onds when the oil is warm from operation. This ad- the set point will produce a very high output signal
justment is usually carried out by the service engi- from the regulator.
neer who starts up the compressor unit.

82/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

If switching from manual to auto and back again of the compressor becomes unsteady again. Now
rather quickly, the regulator will have produced a raise the P band to the last applicable value. If the
very large output signal when regulating in auto. suction pressure still does not reach its setpoint
This signal may make the regulator unstable in (depending on the setting of Nz) a reduction in the
case the setting of the oil valves mentioned above integral-time can be necessary to fine-tune the
is incorrect. If the regulator becomes unstable, regulator.
keep control mode in manual until the regulator If the regulator during a long period of time seems
has stabilized (without activating the capacity up to hunt, increase the T. INT. to eg. 100-200 sec. If
and down keys). the hunting stops, reduce the T. INT. until the sys-
Example 2 tem starts hunting again. Now increase the T. INT.
Nz = 0.0 to the last applicable value.
P band = 10.0 Usually it will never be necessary to change the T.
T. I NT. = 60.0 DIFF. to another value than 0 sec. However, in
T. DI FF. = 0.0 special cases where the compressor is part of a
In case the compressor is running very unsteadily process plant, eg. in petrochemical plants, it may
during regulation or two compressors cannot find be necessary to use another value than 0 sec.
one another in parallel operation, raise the P band This will only be necessary if the process requires
to eg. 50°C. a very fast regulation upwards or downwards to
0178_430_en.fm

avoid that the suction pressure removes itself too


If the running of the compressor has steadied, but far from the set point.
the regulator seems slow to reach its set point, re-
duce the P band a little at a time until the running

0178-445 - ENG 83/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Input signal

0 5 10 15 Time

Output signal
P-part B
A: Proportional band=10°C A
B: Proportional band=5°C

0 5 10 15 Time

Output signal
I-part C
D
C: Integral time=30 sec
D: Integral time=60 sec

0 5 10 15 Time

84/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Output signal
D-part
F
E: Differential time=10 sec E
F: Differential time=20 sec

0 5 10 15 Time

Output signal
0178_430_en.fm

PID-part

0 5 10 15 Time

Reciprocating compressors If the P Band is above 0, the delay times can be


Reciprocating compressors are capacity regulat- prolonged as long as the value is within the P
ed in stages by connection/disconnection of cylin- Band.
ders, typically in pairs, through solenoid valves The P Band is only relevant if the P Band factors
controlled by UNISAB II. DELAY UP and/or DELAY DOWN are set in the
How fast the compressor loads/unloads stages is picture P BAND FACTOR at a value above 1. See
determined by the timers DELAY UP and DELAY section P BAND FACTOR.
DOWN, which will start counting as soon as the If the value is just outside the neutral zone and the
value is outside the neutral zone. P Band factor DELAY UP is eg 10, counting will be
The regulator is allowed to have a P Band of 0, slow: "1 sec." becomes 10 sec.
which means that the stages are loaded in sec- If the value is just outside the P Band, counting will
onds as set. be speeded up, "1 sec" becomes 1 sec.

0178-445 - ENG 85/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Table 9A - Settings - Regulating parameters, Reciprocating compressors

Regulator type Minimum Maximum Factory Unit


setting

Suct. pressure Sp 1 -1 +9 +1 BAR


(-90) (+ 24.8)1* (-19.4) °C/R717

Sp 2 -1 +9 +1 BAR
(-90) (+ 24.8)1* (-19.4) °C/R717

Nz 0 100 4 °C

Pb 0 100 10 °C

Brine temperature Sp 1 - 60 + 100 20 °C

Sp 2 - 60 + 100 20 °C

Nz 0 100 4 °C

Pb 0 100 5 °C

Disch. side Sp 1 -1 + 24 +8 BAR


(-90) (+ 58)2* (+ 21.4) °C/R717

Sp 2 -1 + 24 +8 BAR
(-90) (+ 58)2* (+ 21.4) °C/R717

Nz 0 100 4 °C

Pb 0 100 10 °C

Hot water Sp 1 - 60 + 100 20 °C

Sp 2 - 60 + 100 20 °C

Nz 0 100 4 °C

Pb 0 100 5 °C

Ext. cool Universal regulator Sp 1 - 999 + 999 0 -

Sp 2 - 999 + 999 0 -

Nz 0 + 999 0 -

Pb 0 + 999 0 -

Ext. heat Universal regulator Sp 1 - 999 + 999 0 -

Sp 2 - 999 + 999 0 -

Nz 0 + 999 0 -

Pb 0 + 999 0 -

86/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Regulator type Minimum Maximum Factory Unit


setting

Motor current limiter Sp 1 0 2500 2500 Amp

Sp 2 0 2500 2500 Amp

NOTE: 1* HPO/HPC +25 bar (+60°/R717) 2* HPO/HPC +40 bar (+79.4°/R717)


0178_430_en.fm

0178-445 - ENG 87/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Table 9B - Settings - Regulating parameters, Screw compressors


Regulator type Minimum Maximum Factory setting Unit

Capacity control Nz 0.0 10.0 0.0 %

Pb 0.1 999.9 200.0 %

T.Int. 0.5 999.9 30.0 sec

T.Diff. 0.0 99.9 0.0 sec

Min Pulse 1.0 50.0 1.0 sec

Run Time 1.0 999.0 See note 1 sec

Vi slide control, Nz 0.0 10.0 4.0 %


Compressors with
automatic Vi regu- Pb 0.1 999.9 200.0 %
lation
T.Int. 0.5 999.9 30.0 sec

T.Diff. 0.0 99.9 0.0 sec

Min Pulse 1.0 10.0 1.0 sec

Run Time 1.0 999.0 See note 1 sec

Suct. pressure Sp 1 -1 +9 +1 BAR


(-90) (+24.8) (-19.4) °C/R717

Sp 2 -1 +9 +1 BAR
(-90) (+24.8) (-19.4) °C/R717

Nz 0.0 200.0 0.0 °C/R717

Pb 0.1 999.9 10.0 °C/R717

T.Int. 0.5 999.9 60.0 sec

T.Diff. 0.0 99.9 0.0 sec

Brine temperature Sp 1 -60 100 20 °C

Sp 2 -60 100 20 °C

Nz 0.0 100 0 °C

Pb 0.1 999.9 50 °C

T.Int. 0.5 999.9 30.0 sec

T.Diff. 0.0 99.9 0 sec

88/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Regulator type Minimum Maximum Factory setting Unit

Discharge Sp 1 -1 +24 +8 BAR


(90) (+58) (+21.4) °C/R717

Sp 2 -1 +24 +8 BAR
(90) (+58) (+21.4) °C/R717

Nz 0.0 200 0.0 °C/R717

Pb 0.1 999.9 10 °C/R717

T.Int. 0.5 999.9 60.0 sec

T.Diff. 0.0 99.9 0 sec

Hot water Sp 1 -60 100 20 °C

Sp 2 -60 100 20 °C

Nz 0.0 100 0 °C

Pb 0.1 999.9 50 °C

T.Int. 0.5 999.9 30.0 sec

T.Diff 0.0 99.9 0.0 sec


0178_430_en.fm

Ext. cool Sp 1 -999 +999 0


Universal
regulator Sp 2 -999 +999 0

Nz 0 999.9 0

Pb 0 999.9 100

T.Int. 0.5 999.9 30 sec

T.Diff 0.0 99.9 0 sec

Ext. heat Sp 1 -999 +999 0


Universal
regulator Sp 2 -999 +999 0

Nz 0 999.9 0

Pb 0 999.9 100

T.Int. 0.5 999.9 30 sec

T.Diff 0.0 99.9 0 sec

Motor current Sp 1 0 2500 2500 Amp

Limiter Sp 2 0 2500 2500 Amp

Note 1. Run Time factory settings are as follows:

0178-445 - ENG 89/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

SAB 330 S SAB 330 L SAB 330 E Others

Cap. Run Time 41 56 74 60

Vi Run Time 19 24 31 60

Table 9C - Settings - Regulating parameters, SAB 330


Regulator type Factory setting SAB 330
Hydraulic Mechanical
Capacity control Nz 0 2
Pb 200 200
T.Int. 30 30
T.Diff. 0 0
Min Pulse 1 2
Run time See note 1 See note 1
Vi slide control, Nz 4 10
Compressors with Pb 200 200
automatic Vi T.Int. 30 30
regulation T.Diff. 0 0
Min Pulse 1 1
Run time See note 1 See note 1

Set points on regulators P Band can only be selected when the pressure is
All regulators for capacity regulation (suction shown in °C/R.
pressure, brine temp, etc) can have two 2 set CONTROL ON = BRINE
points which are selected by opening/closing a The brine temperature is measured by a Pt 100
digital input named REGULATOR SET POINT 1 sensor on the spot where the temperature is to be
OR 2 (see wiring diagrams). regulated. The sensor is not built into the com-
Note that also the Motor Current Limiter has two pressor.
set points, which are selected with another digital The regulator is set by selecting BRINE I BRINE
input named MOTOR CURRENT SET POINT 1 TEMP I PARAMETERS followed by repeated
OR 2. pressures on K until reaching the bottom of the
CONTROL ON = SUCTION picture.
The pressure is measured by the built-in pressure CONTROL ON = DISCHARGE
transducer on the compressor suction side. The pressure is measured by the built-in pressure
The regulator is set by selecting SUCTION I transducer on the compressor discharge side.
SUCT.PRESS I PARAMETERS followed by re- The regulator is set by selecting DISCH. SIDE I
peated pressures on K until reaching the bottom DISCH.PRESS I PARAMETERS followed by re-
of the picture. Note that the Neutral zone and the peated pressures on K until reaching the bottom

90/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

of the picture. Note that the Neutral zone and the The cursor is positioned on 4 mA. Press G and
P Band can only be selected when the pressure is the cursor moves to the right. Change the value to
shown in °C/R. -30 and press G .
CONTROL ON = HOT WATER Move the cursor down to 20 mA, press G and
The hot water temperature is measured by a Pt the cursor moves right once more. Change the
100 sensor connected to the brine temperature in- value to +20 and press G .
put (see wiring diagrams). Position the sensor on Move the cursor down to USED FOR, press G
the spot where the temperature is to be regulated. and the cursor moves to the right. Select EXTER-
The sensor is not built into the compressor. NAL INPUT SIGNAL by means of J or K.
The regulator is set by selecting BRINE I BRINE The picture will now look like this:
TEMP I PARAMETERS followed by repeated
pressures on K until reaching the bottom of the
4 mA -30
picture.
20 mA 20
Note that the BRINE REGULATOR at this stage EXTERNAL INPUT SIGNAL
functions as a HOT WATER REGULATOR. The
difference is that the compressor will load capacity Each measuring signal can be scaled in accord-
at decreasing temperature. ance with the transducer measuring range.
0178_430_en.fm

In the menu CONFIG, select in line CONTROL


Universal regulator (Ext. input) ON one of the following:
Besides the above-mentioned regulators it is also Ext. cool
possible to use the universal regulator. If selecting this function, the compressor will reg-
To do so, connect a 4-20 mA sensor (pressure, ulate the capacity upwards in case of increasing
temperature or other) to the UNISAB II input measuring value.
named POSSIBLE REMOTE COMPRESSOR Ext. heat
OPERATION. If selecting this function, the compressor will reg-
When selecting 4-20 mA input in the menu CALI- ulate the capacity upwards in case of decreasing
BRATE, the following picture will appear: measuring value.
Now select menu BRINE I EXT. INPUT I PA-
4 mA 0 RAMETERS. Press to the bottom of the picture
20 mA 0 with K where the set values of the regulator are
NOT USED positioned. These can be set by pressing G fol-
lowed by J or K.
The signal must be scaled to fit the sensor meas-
uring range.
Set point control with current input
Ex.: A temperature sensor of -30°C to +20°C is
The set points of SUCTION PRESSURE, BRINE
used.
TEMPERATURE, DISCH.PRESSURE, HOT WA-
TER and CAPACITY can all be changed through
a 4-20 mA signal.

0178-445 - ENG 91/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Connect these to the terminals as shown in the Brine temperature


wiring diagrams. In the menu CONFIG BRINE must be selected in
the line CONTROL ON. Select 4-20 mA INPUT I
Suction pressure in the menu CALIB, and the following picture will
In the menu CONFIG SUCTION SIDE must be se- appear:
lected in the line CONTROL ON. Select 4-20 mA
INPUT I in the menu CALIB, and the following 4 mA 0
picture will appear: 20 mA 0
NOT USED

4 mA 0
Ex.: The set point is to vary from -10 to +20°C cor-
20 mA 0
responding to a change of the current signal from
NOT USED
4 - 20 mA.
Ex.: The set point is to vary from -50 to -10°C/R The cursor is positioned on 4 mA. Press G until
corresponding to a change of the current signal the cursor moves to the right. Change the value to
from 4 - 20 mA. -10 with K, then press G again.
The cursor is positioned on 4 mA. Press G until Move the cursor down to 20 mA. Press G until
the cursor moves to the right, and change the val- the cursor moves to the right. Change the value to
ue to -50 with K, then press G again. +20, and press G.
Move the cursor to 20 mA, Press G until the cur- Move the cursor down to CONTROL ON. Press
sor moves to the left, and change the value -10, G until the cursor moves to the right, and select
press G again. BRINE TEMP SET POINT with J or K . Finish by
Move the cursor to third line, press G until the pressing G .
cursor moves to the right, and select The picture will now look like this:
SUCT.PRESSURE SETPOINT with J or K. Fin-
ish by pressing G .
4 mA -10
The picture will now look like this: 20 mA 20
BRINE TEMP. SETPOINT

4 mA -50
The set point of the brine regulator is now going to
20 mA -10
change from -10 to +20°C corresponding to a
SUCTION PRESS. SETPOINT
change of the current from 4-20 mA.
The set point of the suction pressure regulator is It is possible to follow the set point value by select-
to vary from -50 to -10°C/R corresponding to a ing BRINE I BRINE TEMP I PARAMETERS
change in the current from 4-20 mA. and press downwards to ACTUAL SP with K.
It is possible to follow the set point value by select-
ing SUCTION SIDE I SUCTION PRESSURE I Disch. pressure
PARAMETERS and press downwards to ACTU- In the menu CONFIG DISCH.SIDE must be se-
AL SP with K. lected in the line CONTROL ON. Select 4-20 mA

92/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

INPUT I in the menu CALIB, and the following INPUT I in the menu CALIB, and the following
picture will appear: picture will appear:

4 mA 0 4 mA 0
20 mA 0 20 mA 0
NOT USED NOT USED

Ex.: The setpoint is to vary from +10 til +35°C/R Ex.: The set point is to vary from +30 to +65°C cor-
corresponding to a change of the current signal responding to a change in the current signal from
from 4-20 mA. 4-20 mA.
The cursor is positioned on 4 mA. Press G until The cursor is positioned on 4 mA. Press G until
the cursor moves to the right. Change the value to the cursor moves to the right, and change the val-
+10 with J, then press G again. ue to +30 with K, then press G again.
Move the cursor down to 20 mA. Press G until Move the cursor down to 20 mA. Press G until
the cursor moves to the right. Change the value to the cursor moves to the right. Change the value to
+35, and press G. +65, and press G.
Move the cursor down to third line. Press G until Move the cursor down to USED FOR, press G
the cursor moves to the right, and select DISCH. until the cursor moves to the right, and select
0178_430_en.fm

PRESSURE SET POINT with J or K. Finish by HOTWATER SET POINT with J eller K. Finish
pressing G . by pressing G.
The picture will now look like this: The picture will now like this:

4 mA 10 4 mA +30
20 mA 35 20 mA +65
DISCH. PRESS. SETPOINT HOT WATER SETPOINT

The set point of the discharge pressure regulator The setpoint in the hotwater regulator now chang-
is now going to change from +10 to +35°C/R cor- es from +30 to +65°C, corresponding to a change
responding to a change of the current from 4-20 in the current from 4-20 mA.
mA. It is possible to follow the setpoint value by select-
It is possible to follow the set point value by select- ing BRINE I BRINE TEMP I PARAMETERS
ing DISCH.SIDE I DISCH.PRESS I PARAME- and press downwards to ACTUAL SP with K .
TERS and press downwards to ACTUAL SP with
K. Capacity control
UNISAB II must be set in REMOTE mode in the
Hotwater picture CONTROL.
In the menu CONFIG, HOTWATER must be se- In the menu CALIB, select 4-20 mA INPUT I, and
lected in the line CONTROL ON. Select 4-20 mA the following picture will appear:

0178-445 - ENG 93/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

takes place with an external 4-20 mA signal (ap-


4 mA 0 plies to version 1.08 and later versions). This
20 mA 0 means that for an SMC 108 without total unload-
NOT USED ing the following changes apply:
0% ≤ Signal < 25% = 0% capacity,
25% ≤ Signal < 50% = 25% capacity,
50% ≤ Signal < 75% = 50% capacity,
Ex.: The set point of the capacity slide on a screw 75% ≤ Signal < 100% = 75% capacity,
compressor is to vary from 0 to 100% correspond- 100% ≤ Signal = 100% capacity.
ing to a change in the current signal from 4-20 mA.
This works as follows:
The cursor is positioned on 4 mA. Press G until
Start
the cursor moves to the right, and change the val-
When the signal is above 5% (4.8 mA) and AUTO
ue to 0 (skip this if the value is 0) with J or K, and
START = YES has been configured, the timer
press G again.
START DELAY will begin to count down (in case
Move the cursor down to 20 mA. Press G until of screw compressors).
the cursor moves to the right, and change the val-
For reciprocating compressors, the timer START
ue to 100, and press G.
DELAY will start once the signal is above the low-
Move the cursor down to USED FOR. Press G est capacity stage. When the timer START DE-
until the cursor moves to the right, and select CA- LAY has counted down, the compressor will start
PACITY SET POINT with J or K. Finish by press- and follow the signal up/down. Note, however,
ing G. that various limiters may reduce the compressor
The picture will now look like this: capacity.
Stop
When the signal is below 5% (4.8 mA) and AUTO
4 mA 0
20 mA 100
STOP = YES has been configured, the timer
CAPACITY SETPOINT STOP DELAY will stop counting down (in case of
screw compressors). For reciprocating compres-
The capacity slide will now move from 0% to sors, the timer STOP DELAY will start once the
100% corresponding to a change in the current signal is below the lowest capacity stage. For re-
from 4 - 20 mA. ciprocating compressors with total unloading, the
In the same way it is possible to control the capac- timer STOP DELAY will be activated when the sig-
ity on a reciprocating compressor. nal is below 0%. When the STOP DELAY timer
has finished counting down, the compressor will
The reciprocating compressor changes one ca-
stop.
pacity stage up or down depending on whether
the signal is above or below the percentage corre- In case the current signal drops to -10% (2.4 mA),
sponding to the capacity stage in question. The there will be a change to the chosen form of regu-
timers DELAY UP and DELAY DOWN, which are lation (eg suction pressure regulation, brine regu-
used during the loading/unloading of capacity lation, etc). If the signal exceeds -10% once more,
stages, are now active when capacity regulation there will be a change to capacity remote control.

94/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

When UNISAB II is configured to "capacity set continuity and below the bottom point of disconti-
point", the starting number is changed to 0. The nuity.
"old" starting number is stored and reinserted in The factor by which the outside temperature will
case UNISAB II is configured differently from "ca- influence the inlet temperature positively or nega-
pacity set point". tively must be set in the BRINE, HOTWATER or
UNIVERSAL regulator. In the picture CONFIG,
Climatic Control select CONTROL ON = BRINE or HOTWATER,
This function can be used for both reciprocating or (UNIVERSAL regulator) EXT.COL/EXT. HEAT
and screw compressors without automatic Vi reg- as well as CLIMA CONTROL = YES in the menu
ulation. The function is included in the menu CON- CONFIG.
FIG and is further described in section Configura- Example 1:
tion.
On a water cooling unit, the inlet temperature is to
The set point of the inlet temperature on the water be corrected by the outside temperature.
side of plants that are regulated on brine temper-
1) If the outside temperature is +30 °C or more,
ature or hot water temperature can be dislocated
the inlet temperature should be +4°C.
by the outside temperature. This requires a 4 - 20
mA temperature transducer, which is connected 2) If the outside temperature is+0°C or less,
to the current inlet in UNISAB II as shown in the the inlet temperature should be +12°C.
0178_430_en.fm

wiring diagrams positioned at the end of this man- In the menu CONFIG, set CONTROL ON on
ual. BRINE and CLIMA CONTROL on YES. Select an
Use a standard temperature transducer with a outside sensor with a range of 0 - +30 °C.
suitabe temperature range, eg -30 - +25°C as Fig. 5.3
shown in Fig. 5.2. Note that the points of disconti-
T inlet
nuity in the diagram will be determined by the
transducer measuring range as seen in the follow-
14
ing examples 1 and 2.
Fig. 5.2 12 Sp 1

T inlet
10

Sp 1 (+65 5
°C) 8

Sp 2 6
(+25 °C) T out
5 Sp 2 4

4 mA 20 mA
(+25 °C)
2
(30 °C)
T out
-10 10 20 30 40
No further compensation will be made once the
outside temperature is above the top point of dis-

0178-445 - ENG 95/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

In the drawing the settings are SP1 = 12°C at To Example 2:


= 0°C and SP2 = 4°C at To = 30°C. On a heat pump unit the inlet temperature is to be
Note that SP1 belongs to the lowest and SP2 to corrected by the outside temperature.
highest outside temperature.
1) If the outside temperature is +30°C, the inlet
The straight line in Fig. 5.3 shows how the inlet temperature must be +40 °C.
temperature is going to vary under the influence of
the outside temperature. 2) If the outside temperature is-10°C, the inlet
temperature must be +65 °C.
Select the menu BRINE I BRINE TEMP I PA-
RAMETERS and go down to SET POINT 1 and In the menu CONFIG, adjust CONTROL ON to
SET POINT 2 with K. HOTWATER and CLIMA CONTROL to YES.

Give SET POINT 1 the value SP1 = 12°C from Select an outside sensor in the range -10 - +30 °C.
Fig. 5.3 by pressing G. Fig. 5.4
Give SET POINT 2 the value SP2 = 4°C from T Inlet
Fig. 5.3 by pressing G.
At the same time set NEUTRAL ZONE = 3°C and 80

PROP.BAND = 5°C as starting points. 70


SP1
60
The system is now adjusted to the desired func- 50
tion. SP2 40
30
The picture will now look like this:
20
10
T out
SET POINT 1 12 °C
-20 -10 10 20 30 40
SET POINT 2 0 °C
NEUTRAL ZONE 3 °C
In the drawing the settings are SP1 = 65°C at To
PROP. BAND 5 °C
= -10°C and SP2 = 40°C at To = 30°C.
The ACTUAL SP shows the value according to Note that SP1 belongs to the lowest and SP2 to
which the inlet temperature is regulated at that the highest outside temperature.
particular moment. If the outside temperature is The straight line indicates how the inlet tempera-
30°C, this value must be 4°C. ture is going to vary under the influence of the out-
If the outside temperature is 0°C, the value must side temperature.
be 12°C. Select menu BRINE I BRINE TEMP I PARAM-
The outside temperature can be seen in % of the ETERS and go down to SET POINT 1 and SET
measuring range in the picture MOTOR: POINT 2.
Give SET POINT 1 the value SP1 = 65°C from the
MOTOR CURR XXX A figure by pressing G.
EXT. INPUT XX Give SET POINT 2 the value SP2 = 40°C from the
OUTSIDE TEMP. XX %
figure by pressing G.

96/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

At the same time set NEUTRAL ZONE = 3°C and Adjusting slide speed (screw
PROP.BAND = 5°C as starting points. compressors with hydraulic slides)
The system is now adjusted to the desired func-
tion. Capacity slide
The capacity slide is moved by adding or remov-
SET POINT 1 65 °C ing oil from the slide piston cylinder. The move-
SET POINT 2 40 °C ment is controlled by UNISAB II, which activates
NEUTRAL ZONE 3 °C the solenoid valves in the oil lines, thus moving
PROP. BAND 5 °C the slide in the desired direction. If this movement
takes place too fast, the system will become very
The ACTUAL SP shows the value according to unstable and give rise to unnecessary wear and
which the inlet temperature is regulated at that tear of the slide.
particular moment. If the outside temperature is
To prevent the above, adjustable throttle valves
30°C, this value must be 40°C.
have been built into the oil lines and by changing
If the outside temperature is -10°C, the value must the opening degree of the throttle valves, the slide
be 65°C. movement can be adjusted to a suitable speed.
The outside temperature can be seen in % of the The slide speed is checked with the compressor in
measuring range in the picture CAPACITY:
0178_430_en.fm

MANUAL mode, at normal oil temperature and by


activating E F used for capacity regulation.
MOTOR CURR XXX A With the slide in minimum position (< 5%) and with
EXT. INPUT XX
a constant pressure on E (capacity up), it takes
CLIMA COMP. XX %
about 60 sec for the slide to move to 100%, and
Examples 1) and 2) precondition that the flow with a constant pressure on F (capacity down)
temperature is measured with the normal Pt 100 approx 60 sec to move down to 0%.
input, but if a temperature transducer of 4-20 mA Is this not the case, adjust the throttle valves.
is installed in a common reservoir, the outdoor
compensation will also be able to work here. Volume ratio slide
See section Universal regulator in which the pro- The volume ratio slide is moved by adding or re-
cedure will be exactly the same as described in moving oil for the slide piston cylinder. The move-
above examples as this regulator can also be ment is controlled by UNISAB II, which activates
used for both COOLING and HEATING functions. the solenoid valves in the oil lines, thus moving
In both examples the inlet temperature will rise at the slide in the desired direction. If this movement
falling outside temperatures. takes place too fast, the system will become very
unstable and give rise to unnecessary wear and
If the opposite effect is required, ie rising inlet tem-
tear of the slide.
perature at rising outside temperature, SP1 and
SP2 must be switched. To prevent the above, adjustable throttle valves
have been built into the oil lines and by changing
the opening degree of the throttle valves, the slide
movement can be adjusted to a suitable speed.

0178-445 - ENG 97/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

The speed is checked with the compressor in Based on discharge pressure, suction pressure,
MANUAL mode and at a normal oil temperature. compressor type and capacity, UNISAB II calcu-
Bring the capacity slide to 20-30% position. lates a "zero point" below which the compressor
capacity slide is not permittted to drop while the
Select picture CAPACITY I VI POSITION I SET compressor is operating.
POINT 1.
When the compressor starts, the new "zero point"
will be calculated, and the capacity slide moves as
SETPOINT 1 0.0% quickly as possible from a physical zero point (me-
chanical impact) to the calculated zero. As long as
and change the value to -10% by pressing G and
the slide position is below the calculated zero
K. This will make the slide move to minimum po-
point, the capacity is shown as a negative value in
sition.
the display.
Return to VI POSITION to check the slide move-
In case the calculated zero point cannot be set
ment.
within a certain time limit, which is dependent on
When the slide has reached minimum, change the calculated movement, an alarm will be issued.
SET POINT 1 to 110%. The slide will now move to
When the compressor stops, the slide will drop to
maximum position. Check the speed of the move-
the calculated zero point. The motor will stop, and
ment from 0% to 100% in the picture with VI PO-
hereafter the slide will be pushed down to the
SITION.
physical zero position by the built-in spring.
The movement from 0% to 100% must be adjust-
Once the differential pressure across the com-
ed on the throttle valves to last approx 120 sec.
pressor has been equalized (Π=1), the calculated
This also applies to the movement from 100% to
zero point and the physical zero position will be
0%.
the same.
Use SET POINT 1 with either - 10% or 110% to
If the pressure conditions are changed during op-
move the slide back and forth until the speed is
eration so that the calculated "zero point" of the
correct.
slide is moved (whereby the corrected capacity is
changed), the capacity may be a negative value
Variable Zero position for a certain period.
In general For all other screw compressor types than SAB
The flow of screw compressors at low slide posi- 202 a "zero point" can be set manually, if required.
tions seen in relation to the fully loaded "flow", is This manually set zero point has the same func-
strongly dependent on the operating conditions. tion as described above in the sections for com-
Thus, it has turned out to be expedient to enter a pressor start and stop.
"floating zero point", which ensures that the com-
pressor operates with a correct slide position.
Corrected capacity
The program in UNISAB II ensures that the SAB
UNISAB II will automatically correct the capacity
202 compressor always adapts to the variable op-
reading in relation to both the new calculated zero
erating conditions.
point and to the Vi slide position when automatic
Vi regulation is included.

98/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

With manual Vi regulation the capacity reading is Remember that whenever the Vi slide is moved
automatically corrected in relation to the new cal- manually, the position transmitter of the capacity
culated zero point. slide must be recalibrated at 100%.
The corrected capacity is calculated according to
the following principle:
Fig. 5.5

0% 100%
Corrected capacity
Pressure cond.
1.5 12 25 Volume cond.: 4.5 3 2

Cap. slide
Measured slide pos.
0% 100%

0% Zero% pos. 100% 0%


“Zero slide” “Vi slide”

The capacity slide signal from the position trans- Manual setting of new zero point (all
mitter is scaled in such a way that 0% is read types of screw compressors)
0178_430_en.fm

when the slide position corresponds to the calcu- For all screw compressor types without automat-
lated/set zero point, and 100% is read when the ic zero point setting, it is possible to set a "zero
capacity slide meets the Vi slide, regardless of point" manually, below which the compressor ca-
whether the setting is carried out automatically or pacity slide is not allowed to drop while the com-
manually. pressor is operating.
For SAB 202S and SAB 202L, which have auto-
Automatic setting of new zero point matic settings of the zero point, manual setting is
(SAB 202) usually not allowed.
The zero point for the various types of SAB 202 is
The manual setting of the zero point is carried out
calculated according to a programmed algorithm.
in the picture SETUP I CONFIG. in the configu-
The current calculated value of the zero point is ration point:
displayed in picture:
MANUAL ZERO 0.0%
SETUP I DIAGNOSIS I ZERO CAPACITY
The setting ranges between 0-40% of max capac-
POS.
ity slide travel (at Vi ratio = 2).
With manual Vi regulation the zero point is correct-
With manual Vi regulation the zero point is cor-
ed and set automatically, corresponding to an op-
rected automatically by a factor that depends on
timum setting of the Vi slide. Consequently, it is of
an optimum (calculated) setting of the Vi-slide.
great importance that the setting of the Vi slide
Consequently, it is very important that the set-
is correct.
ting of the Vi slide is correct.

0178-445 - ENG 99/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

The setting will be stored when the compressor will be stopped. The timer is reset (set to the reset
stops and/or UNISAB II is switched off. value) and is restarted once the slide moves be-
low -2% capacity.
Built-in spacer block The timer is set in the picture SETUP I TIMERS
If the compressor has a built-in spacer block and I TIMER RESET in the timer
Vi regulation is automatic, the MECHANICAL CAP.NEG.
ZERO must be set on YES. Thus, the travel of the
The reset value can be set in the interval of
capacity slide will be reduced by the % value
60-20000. The factory value is 10000.
[0-40%] which is entered in MANUAL ZERO so
that the corrected capacity may be calculated and It is very important that the timer has been set cor-
shown correctly. rectly. Too low a value will result in the alarm Ca-
pacity error. Too high a value will make the com-
The value [0-40%] that must be entered in MAN-
pressor run for too long a period with a negative
UAL ZERO must have the following size:
capacity.
Fig. 5.6
Configuration
length of spacer block
manual zero = 100% To obtain a correct calculation of the zero point, it
length of total capacity travel
is important that the compressor type and swept
Setting of MECHANICAL ZERO is carried out in volume have been entered correctly.
the picture SETUP I CONFIG. in the configura- The swept volume of the compressor is deter-
tion point: mined on the basis of:
MECHANICAL ZERO [NO/YES] Compressor type
MANUAL ZERO 0.0% RPM (50/60 Hz)
The position transmitter is calibrated with the Male/female rotor
spacer block mounted and the Vi-slide in minimum In case of SAB 202, UNISAB II will automatically
(0%). enter a swept volume value corresponding to the
S type with Male rotor and a 2-pole 50 Hz motor,
The alarm ie 1229 m3/h. The correct swept volume must be
based on the number of revolutions of the com-
In case the slide cannot reach the position corre-
pressor, ie 50/60 Hz supply, and on whether the
sponding to a calculated or set zero point (ie a
compressor has male or female rotor drive:
positive read capacity) before the expiry of the
timer Tcap.neg., the compressor will be stopped with SAB 202 SM/ 50 Hz, swept volume = 1229 m3/h
the following alarm: SAB 202 SM/ 60 Hz, swept volume = 1475 m3/h
SAB 202 SF/ 50 Hz, swept volume = 1843 m3/h
CAPACITY ERROR
SAB 202 SF/ 60 Hz, swept volume = 2212 m3/h
Each second the timer Tcap.neg. is counting down by SAB 202 LM/ 50 Hz, swept volume = 1590 m3/h
a factor somewhere between 1 and 180 depend- SAB 202 LM/ 60 Hz, swept volume = 1908 m3/h
ing upon the read negative capacity. Each time SAB 202 LF/ 50 Hz, swept volume = 2385 m3/h
the slide moves above 0% read capacity, the timer SAB 202 LF/ 60 Hz, swept volume = 2862 m3/h

100/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

The nominal swept volume at 50 Hz can be read Manual setting of the zero point is carried out by
on the compressor name plate. entering a zero point between 0-40% of max ca-
As mentioned earlier, two new configuration pacity slide travel in MANUAL ZERO 0.0%
points have been introduced in the picture SETUP See section Manual setting of new zero point.
I CONFIG.:
MECHANICAL ZERO NO [/YES] Zero pos. picture
MANUAL ZERO 0.0% Reading of the current calculated zero point value
Only if the compressor has a built-in spacer block as well as any manual set zero point value takes
as well as automatic Vi regulation, the MECAN- place in the diagnosis picture:
ICAL ZERO must be set on YES. In all other cas- SET UP I DIAGNOSIS I ZERO
es MECHANICAL ZERO is set on NO. See sec- CAPACITY POS.
tion Built-in Spacer Block.

CALCULATED ZERO 22.0% (current reading 0-40%)


MANUAL ZERO 0.0% (manual adjustment 0-40%)
CAP. POSITION 66.5% (current slide position corresponds to 4-20 mA
CAPACITY 100.0% (corrected capacity - as read)
0178_430_en.fm

Electrical slide control Part load and full load


(Screw compressors SAB 250 and SAB 330) As regards capacity control and Vi adjustment,
These screw compressors are fitted with a capac- there are two operating modes: Part load and full
ity slide (master slide) driven by an AC motor load.
through magnetic transmission, gearbox and At full load, the capacity is by definition 100%. By
spindle, as well as a hydraulical Vi slide (baby activating the solenoid valve, the Vi slide is forced
slide) which is controlled by a solenoid valve. The in mesh with the capacity slide. The Vi is then ad-
digital output for the valve is always controlled au- justed by changing the capacity slide position,
tomatically by UNISAB II. Only the capacity slide which consequently moves the Vi slide. Note that
is fitted with a position transmitter. in the survey pictures, full load is indicated in the
Note that the minimum pulse when moving the ca- fourth line by a solenoid valve symbol:
pacity slide is 1 second. For a SAB 330L this cor-
responds to a minimum capacity position change At part load, the Vi slide is reset to minimum po-
of 1.8%. It is very useful to have this in mind when sition by deactivating the solenoid valve. The ca-
adjusting the PID regulators. Further, there is a pacity slide is moved according to the capacity re-
pause of at least 1 second when changing the ro- quirement.
tation direction of the motor. UNISAB II changes from part load to full load
mode when the capacity exceeds the selected
limit, VI MODE included in the picture SETUP I

0178-445 - ENG 101/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

CONFIG I COMPRESSOR. The default limit is moved as quickly as possible down into the area
VI MODE = 97%, but it can be adjusted in the where UNISAB II calculates that the power con-
range 70 to 97%. sumption will be reasonable. After this, UNISAB II
UNISAB II returns to part load when the capacity will move on to points 2 and 3.
requirement decreases.
The changes described are performed automati-
Change to part load
cally in any of the modes MANUAL, AUTO and When changing from full load to part load,
REMOTE. UNISAB II will run through the following steps:
1. If necessary, move capacity slide (and thus
Calculated Vi position Vi slide) as close as possible to the limit VI
When changing to or running in full load mode, MODE to avoid undesirable capacity jumps.
UNISAB II determines an optimal calculated Vi However, stop movement if/when reaching
the limit for reasonable power consumption.
position xVi [%] according to suction pressure/dis-
charge pressure ratio, compressor type, refriger- 2. Deactivate solenoid valve of Vi slide to re-
ant and whether there is an economizer. Further- lease Vi slide and move it to minimum posi-
more, the corresponding capacity slide position is tion.
calculated: 3. If still necessary, move capacity slide to the
xcap [%] xVi =100 [%] -xVi [%] * limit VI MODE.
(Vi-slide [mm] /Cap-slide [mm]) 4. Change to normal capacity control.
While in full load mode, the xcap[%] xVi is the set
point of the capacity slide position regulator. Position indications
In the picture MOTOR, CAPACITY and VI POSI-
Change to full load TION are indicated.
When changing from part load to full load, At full load, CAPACITY indication will show 100%,
UNISAB II will run through the following steps: while VI POSITION is calculated from the actual
1. Move capacity slide if necessary (see be- capacity slide position.
low). At part load, CAPACITY indication will show the
2. Activate solenoid valve of Vi slide to force Vi actual capacity slide position, while VI POSITION
slide into mesh with capacity slide. is 0%.

3. Move capacity slide (and thus Vi slide) to op-


timal position xcap [%] xVi. Slide brake control
The slide brake is released for a short time -
As regards point 1, UNISAB II compares the
BRAKE DLY - before the slide motor is activated.
above defined xcap [%] xVi with the actual capacity
The brake is also released for the period of time
slide position. If the actual position is much higher
BRAKE DLY after deactivating the slide motor.
than xcap [%] xVi , the result would be an undesirable
Brake DLY can be selected in the range 0 to 0.5
power consumption if the Vi slide valve is activat-
seconds in the picture DIAGNOSES I MISC.
ed immediately. Therefore, the capacity slide is FUNCTIONS.

102/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

Capacity alarm a move is expected, the timer will count down. If


If the slide does not move as expected, a capacity the timer reaches 0, the alarm will be issued. The
alarm will be issued. This means that each time timer can be inspected in the picture DIAG-
the slide moves at least 0.5% in the chosen direc- NOSES I MISC. FUNCTIONS.
tion, a CAPACITY timer is reset to 100 seconds. If
0178_430_en.fm

0178-445 - ENG 103/222


Rev. 03.09
UNISAB II 2.03
5. Compressor regulation

104/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
6. Limiting functions

6. Limiting functions
UNISAB II includes a number of limiting functions There is a standard limiter for each of the follow-
(in the following called limiters). ing:
The purpose of a limiter is to prevent shutdowns • Low suction pressure
by limiting or even changing the compressor ca- • High discharge pressure
pacity when the measured value exceeds the se-
lected limits. In most cases, "changing the capac- • High motor current
ity" means decreasing it. However, this is not the • Low brine temperature
case with all limiters. • High water temperature
In general, a limiter can be watching, passive or • High differential pressure
active. While all limiters are watching, the com- Pdiff =Pdisch - Psuct (HPO and
pressor start/stop and the capacity regulation will HPC reciprocating compressors)
work normally.
Furthermore, the following special limiters exist:
While a limiter is passive or active, the compres-
sor cannot be started. If the compressor is in op- • High suction pressure
eration, the capacity regulation will be partly disa- • Suction ramp
bled. Further, if a limiter is active, the capacity will • High discharge temperature
0178_431_en.fm

be changed actively.
All relevant limiters are permanently in operation. Standard limiters
If necessary, they will intervene in any of the oper-
The standard limiting function is based on the user
ating modes MANUAL, AUTO and REMOTE.
selected high/low alarm limit, high/low warning
In case the compressor is in MANUAL mode and limit and the limiting zone Lz. In the special case
a limiter is active, the capacity slide will automat- of the high motor current limiter, the value of Lz is
ically be returned to its original value as soon as 2% for screw compressors and 5% for reciprocat-
the limiter is watching. ing compressors. In all other cases, Lz is calculat-
When a limiter is passive or active, the red lamp ed as half the difference between the alarm limit
will flash slowly, and the warning relay will be ac- and the warning limit.
tivated. Further, the display will show whether the Fig. 6.1illustrates how a standard limiter works
limiter is passive or active. with the high discharge pressure limiter as exam-
ple.

0178-445 - ENG 105/222


Rev. 03.09
UNISAB II 2.03
6. Limiting functions

Fig. 6.1
SCREW COMPRESSORS (ALL LIMITERS) and RECIPROCATING COMPRESSORS
RECIPR. COMPRESSORS (MOTOR CURRENT (ALL LIMITERS EXCEPT MOTOR CURRENT
LIMITER) LIMITER)

ALARM

WARNING
Limiting zone

Time Time

1 Limiter is watching. Normal control, capacity can increase or decrease. If compressor is not in operation, it can be started.
2 Limiter changes from watching to passive.

Limiter is passive. Capacity cannot be increased. Capacity is not reduced by Limiter,


3 but possibly by egulator. If compressor is not running, it cannot be started.

4 Limiter becomes active. Capacity is reduced at once, and timer begins to count.

5 Limiter is active. At each timeout, capacity is reduced and timer restarted, until compressor stops at low capacity. If compres-
sor is not running, it cannot be started.

6 Limiter changes from active to passive.

7 Limiter changes from passive to watching.

8 Compressor is stopped (shutdown) immediately.

In the example, the alarm (= shutdown) limit for Motor current limiter
high discharge pressure has been set for 16 bar, Even the high motor current limiter is special for
while the warning limit is 14 bar. As indicated, the reciprocating compressors. When one stage is
size of the limiting zone (Lz) is then (16 -14) / 2 = disengaged due to the limiter, the resulting motor
1 bar. The limit of the limiting zone is thus warning current drop will be measured. It is assumed that
limit - Lz = 14 -1 = 13 bar. if the stage is re-engaged, the motor current will
As shown in Fig. 6.1, most reciprocating compres- increase by the size of the drop. To avoid disen-
sor limiters differ from the corresponding limiters gaging and re-engaging in turn, the limiter will en-
for screw compressor in the way that when the sure that the stage will not be re-engaged until the
measured value is within the limiting zone, the sta- resulting current will be below 95% of the limit for
tus of the limiter will depend on whether the limiter the limiter zone.
has been watching or active. If the limiter has Note that the warning limit for motor current is
been watching, it will remain watching in the limit- SET POINT 1 selected in the picture MOTOR I
ing zone. If the limiter has been active, it will be- MOTOR POWER. If SETPOINT 1 = 1000 kW,
come passive for as long as it is in the limiting the limit for the limiting zone will be 1000 - 2%
zone. = 980 kW for screw compressors, and 1000 -
5% = 950 kW for reciprocating compressors.

106/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
6. Limiting functions

High difference pressure limiter High discharge pipe temperature (one-stage re-
Note in particular that this limiter only applies to ciprocating compressors)
HPO and HPC compressors and that it has a fixed From version 1.10 and onwards a capacity limiting
warning limit of 25.2 bar and a fixed alarm limit of function has been entered for all one-stage recip-
26 bar. The limiter is released at 25 bar and it is rocating compressors using refrigerant R717.
passive between 25-25.2 bar. This function is activated at certain operating con-
ditions, especially at excessive differential pres-
Special limiters sure, corresponding to the operating diagram
High suction pressure limitation zone 2 (zone 4, however, for CMO, SMC 100 S/L
and SMC 180).
It is possible to have a high suction pressure lim-
iting function. The effect of this high suction pres- At such operating conditions compressors of the
sure limiting function is that the compressor ca- CMO/HPO and SMC/HPC type must as minimum
pacity is limited to an adjustable max value when- load 50% of their capacity when starting up and
ever the suction pressure is above the suction during operation.
pressure warning limit. At present the limit curve (which is a straight line)
Max capacity at "high suction pressure limitation" is fixed on the basis of a max permissible dis-
is set in picture: charge pipe/oil temperature(T2max) of 150°C as
SETUP I CALIBRATE I CAP. LIMIT as: LIMIT well as suction superheating of 10°C.
0178_431_en.fm

HIGH xxx.x%. Whenever the limiting function is active, the fol-


High limit can be set between 0% and 100% lowing will occur at start-up:
where a setting of 100% disables the function.
– Capacity stages corresponding to a min-
In the WARNING picture the text "SUCT. PRESS imum of 50% will be loaded.
HIGH LIM" will appear.
When the limiting function is active during opera-
Suction ramp tion, with 50% capacity or more, the following will
With the timer SUCTION RAMP it is possible to in- occur:
dicate the speed at which the compressor is al-
– It is impossible, both in MANUAL, AUTO
lowed to lower its suction pressure 1°C. The func-
or REMOTE, to unload capacity stages
tion, which is used for as long as the compressor
so that the capacity drops below 50%, ie
is working down towards its normal operating
50/66% are the lowest capacity stages -
point, is a combination of low suction pressure lim-
also when "total unloading" has been se-
iting function and a ramp function.
lected.
If the suction pressure ramp limiting function pre-
– In AUTO and REMOTE the timer STOP
vents the compressor from increasing its capacity
DELAY will be started at 50/66% if the
above 5%, the timer STOP DELAY will not be ac-
regulator sends out a down regulating
tivated and the compressor will continue operat-
signal. If one of the limiting functions is
ing.
to unload capacity, the timer DELAY
The suction pressure limitation without the ramp DOWN will be started at 50/66%.
function can stop the compressor if capacity
comes below 5% for a longer period.

0178-445 - ENG 107/222


Rev. 03.09
UNISAB II 2.03
6. Limiting functions

If the compressor is operating at a capacity below In the WARNING picture the text LIMITING DIS-
50% when the limiting function is active, the limit- CHARGE TEMP. will appear if the compressor is
ing function will not actively begin to load stages. to be stopped on the "total unloading timer" due to
However, the following will take place: insufficient capacity or if the limiting function pre-
– In MANUAL the compressor will be vents the capacity from being reduced in MANU-
stopped on the "total unloading timer" AL, AUTO or REMOTE.
provided that the capacity stays below The limit curve (limiting zones 2/4) corresponds as
50% for more than approx 4 mins. standard to suction superheating of 10°C (factory
– In AUTO and REMOTE the compressor value).
will be stopped on the "total unloading Since the limit curve is directly dependent on the
timer" provided the regulator is neutral suction superheating of the plant, the actual su-
and capacity remains below 50% for perheating of the plant must be entered as set
more than approx 4 mins. point 2 in picture: SUCTION SIDE I SUCTION
– If the regulator sends out a regulating SUPERHEAT. I SETPOINT 2 if it differs from the
down signal, the timer STOP DELAY will above factory value.
be started. Adjusting range: -10 - +30°C
– If one of the other limiting functions is to By adjusting SET POINT 2 parameter for suction
unload capacity, the timer DELAY superheating upwards or downwards, the limit
DOWN will stop at 50/66%. curve will be dislocated accordingly.
– If the regulator sends out a regulating up If SET POINT 2 is set for -10°C, the limit curve will
signal and the compressor is loading be dislocated so much upward - 20°C compared
stages so that capacity rises to 50% or to normal - that the limiting fuction will be discon-
more, the situation will be the same as nected.
the one described in the previous sec-
tion.

108/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
6. Limiting functions

Display indications
The following tables show the texts appearing in
the display in connection with the various limiters.

Screw compressors Overview picture indication

Compressor Compressor WARNING picture, WARNING picture,


Limiter stopped running Passive indication Active indication

Standard Limiters:

Low suction pressure READY SUCTION LIM. LIMITING SUCT. PRESS SUCT. PRESS LOW LIM

High discharge pressure READY DISCHARGE LIM. LIMITING DISCH. PRESS DISCH. PRES HIGH LIM

High motor current Irrelevant RUNN. OVERLOAD None None

Low brine temperature READY SUCTION LIM. LIMITING BRINE TEMP and BRINE TEMP LOW LIM and
LIMITING SUCT. PRESS LIMITING BRINE TEMP

High water temperature READY DISCHARGE LIM. LIMITING HOT WATER and BRINE TEMP HIGH LIM and
LIMITING DISCH. PRESS LIMITING HOT WATER

High differential pressure Irrelevant Irrelevant Irrelevant Irrelevant

Special Limiters:

High suction pressure READY SUCTION LIM. 1) None2) 3) SUCT. PRESS HIGH LIM3)
0178_431_en.fm

Suction ramp Irrelevant SUCTION LIM. LIMITING SUCT. PRESS Irrelevant

High discharge temp. Irrelevant Irrelevant Irrelevant Irrelevant

Recipr. compressor Overview picturei ndication

Compressor stopped or running WARNING picture, WARNING picture,


Limiter Passive indication Active indication

Standard Limiters:

Low suction pressure SUCTION LIM. None SUCT. PRESS LOW LIM

High discharge pressure DISCHARGE LIM. None DISCH. PRES HIGH LIM

High motor current RUNN. OVERLOAD None None

Low brine temperature SUCTION LIM. LIMITING BRINE TEMP BRINE TEMP LOW LIM and
LIMITING BRINE TEMP

High water temperature DISCHARGE LIM. LIMITING HOT WATER BRINE TEMP HIGH LIM and
LIMITING HOT WATER

High differential pressure DISCHARGE LIM. None HIGH DIFFERENTIAL PRES-


SURE

Special Limiters:

High suction pressure SUCTION LIM. 1) None2) 3) SUCT. PRESS HIGH LIM3)

Suction ramp SUCTION LIM. None None

High discharge temperature None None LIMITING DISCH. TEMP

0178-445 - ENG 109/222


Rev. 03.09
UNISAB II 2.03
6. Limiting functions

Notes: pressure comes below the warning limit less


1. Only shown while capacity is limited. 2°C/R.

2. If limiter is active (at suction pressure > 3. Limiter is not active or passive like standard
warning limit), it will remain active until the limiters. It actively limits capacity so that it is
less than or equal to the selected LIMIT
HIGH.

110/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

7. Compressor control and surveillance


The various types of reciprocating and screw Starting sequence
compressors start in differents ways. Some types When the compressor has received starting per-
have prelubrication whereas others start directly. mission, the oil full flow pump will start. Make sure
Under all circumstances certain alarms are sup- that the capacity slide is in minimum position. On
pressed at this stage as described in sections SAB 202 this is generally always the case as the
Alarms and warnings and Timers. slide is pushed down by a spring.
The oil is pumped into the compressor lubrication
SAB 202, SAB 163H/128H MK3 with oil system, and when the oil flow switch is activated,
pump & VMY Mk3 with full flow pump the prelubrication period will start.
The pump is used for prelubrication and for main- When the time has expired the compressor is
taining of a minimum oil pressure level during op- started and the pump will now run for min 60 sec.
eration. The pump is started and stopped in ac- The pump will stop when the differential pressure
cordance with the compressor differential pres- is above SET POINT 2 as described above.
sure during operation.
Alarm surveillance
The difference is set in the picture OIL I OIL During start the following alarms are delayed:
PRESSURE I PARAMETER whereupon SET
Low oil pressature 45 sec
0178_432_en.fm

POINT 1 and SET POINT 2 appear.


SET POINT 1 is the pressure at which the pump High filter diff. pressure 300 sec
is to start, and SET POINT 2 is the pressure at Low superheat 300 sec
which the pump is to stop. Consequently, adjust High superheat 300 sec
SET POINT 1 to the lowest pressure level.
Low/high oil temperature 300 sec
Normal setting for SAB 202:
SET POINT 1 = 2.5 Bar
SAB 128HR and 163HR with oil pump
SET POINT 2 = 4 Bar
The compressors SAB 128 and SAB 163 HR are
Move the cursor to SET POINT 1 and press G
frequency regulated screw compressors, ie the
until the cursor moves to the right in the picture.
capacity slide is fixed in maximum position and
With K and J set the value. When the value has cannot be moved.
been set, press G once more.
The electric oil pump is used for prelubrication and
In the same way adjust SET POINT 2.
for maintenance of a minimum oil pressure during
If the compressor differential pressure (discharge operation.
pressure - suction pressure) is below SET POINT
The pump is started and stopped in accordance
1 during operation, the pump will start immediate-
with the compressor differential pressure during
ly. operation.
When the compressor differential pressure has The difference is set in the picture OIL I OIL
been higher than SET POINT 2 for 60 sec, the
PRESSURE I PARAMETER whereupon SET
pump will stop.
POINT 1 and SET POINT 2 will appear.

0178-445 - ENG 111/222


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

Normal setting for SAB 128/163 HR: ance with the compressor differential pressure
SET POINT 1 = 2.5 Bar during operation.
SET POINT 2 =4.0 Bar The difference is set in the picture OIL I OIL
Set points are adjusted as described in the previ- PRESSURE I PARAMETER whereupon SET
ous section. POINT 1 and SET POINT 2 will appear.
SET POINT 1 is the pressure at which the pump
Starting sequence
is to start, and SET POINT 2 is the pressure at
Once the compressor has received permission to
which the pump is to stop. Consequently, adjust
start, the oil pump will start and oil will be pumped
SET POINT 1 to the lowest pressure level.
into the compressor lubrication system.
Normal setting for SAB 250/330:
The oil flow switch must be activated within 600
seconds to avoid disconnection. SET POINT 1 = 2.5 Bar
SET POINT 2 = 4.0 Bar
When the oil flow switch is activated, the solenoid
valve (capacity slide down) will be open for 15 Move the cursor to SET POINT 1 and press G
seconds and the electric fan will start. The fre- until the cursor moves to the right of the picture.
quency converter will receive a signal to start. With K and J set the value. When the value has
been set, press G once more.
The speed is increased to 1000 rpm in 10 sec-
onds. In the same way adjust SET POINT 2.

The pump will operate for a minimum of 60 sec- If the compressor differential pressure (discharge
onds and stop if the differential pressure is higher pressure - suction pressure) is below SET POINT
than SET POINT 2 as described above. 1 during operation, the pump will start immediate-
ly.
Alarm surveillance
During start the following alarms are delayed: When the compressor differential pressure has
been higher than SET POINT 2 for 60 sec, the
See also section Timers.
pump will stop.
Starting sequence
Low oil pressure 45 sec When SAB 250/330 compressor stops, UNISAB II
High filter diff. pressure 300 sec will attempt to move the capacity slide below 5%
capacity. If this does not succeed, a CAPACITY
Low superheat 300 sec
ERROR alarm will be issued and the compressor
High superheat 300 sec will not start.
Low/high oil temperature 300 sec When the compressor has recieved starting per-
mission, the oil full flow pump will start.
SAB 283, SAB 330 and SAB 355 with oil The oil is pumped into the compressor lubrication
pump system, and when the oil flow switch is activated,
The pump is used for prelubrication and for main- the prelubrication period will start.
taining a minimum oil pressure level during oper- When the time has expired, the compressor will
ation. The pump is started and stopped in accord- start and the pump will now run for min 60 sec.

112/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

The pump will stop when the differential pressure GSV/RWF with oil pump
is above SET POINT 2 as described above. The pump is used for prelubrication and for main-
Alarm surveillance taining a minimum oil pressure level during oper-
During start the following alarms are delayed: ation. The pump is started and stopped in accord-
ance with the compressor differential pressure
during operation.
Low oil pressure 45 sec
The difference is set in the picture OIL I OIL
High filter diff. pressure 300 sec PRESSURE I PARAMETER whereupon SET
Low superheat 300 sec POINT 1 and SET POINT 2 will appear.
High superheat 300 sec SET POINT 1 is the pressure at which the pump
is to start whereas SET POINT 2 is the pressure
Low/high oil temperature 300 sec
at which the pump is to stop. Consequently, set
The delayed alarms are described in section Tim- SET POINT 1 for the lowest pressure level.
ers. Normal setting for GSV/RWF:
SET POINT 1 = 2.5 bar.
SAB 80 with fitted (mechanical) oil SET POINT 2 = 4.0 bar.
pump Move the cursor to SET POINT 1 and press G
0178_432_en.fm

Starting sequence until the cursor has moved to the right side of the
When the compressor has received starting per- picture. Set the value by means of K and J .
mission, it must be checked if the capacity slide is When the value has been set, press G once
in minimum position. Before starting the compres- more.
sor, the oil level switch in the oil separator must be SET POINT 2 is set in the same way.
activated.
If the compressor differential pressure (discharge
Start the compressor. pressure - suction pressure) is below SET POINT
After a delay of 60 seconds from compressor 1 during operation, the pump will start immediate-
start, no signal from the level switch for more than ly.
10 seconds will result in disconnection. When the compressor differential pressure has
Alarm surveillance been higher than SET POINT 2 for 60 seconds,
During start the following alarms are delayed: the pump will stop.

Low oil pressure 45 sec Starting sequence


When the compressor has received starting per-
High filter diff. pressure 300 sec
mission, check whether the capacity slide is still in
Low superheat 300 sec minimum position. In case of compressor stop,
High superheat 300 sec make sure that the capacity slide and the volume
slide (if fitted with automatic Vi) are in minimum
Low/high oil temperature 300 sec
position.
See also section Timers

0178-445 - ENG 113/222


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

Before start-up the oil level switch in the oil sepa- Normal setting for SV24/26:
rator must be active. If this is not the case, an SET POINT 1 = 2.5 Bar
alarm for oil system error will be issued. SET POINT 2 = 4.0 Bar
No signal from the oil level switch will result in dis- Set points are adjusted as described in the previ-
connection after a delay of 60 seconds from com- ous section.
pressor start or during operation.
Starting sequence
If the oil level switch is active, the prelubrication
Once the compressor has received starting per-
period will begin and the oil will be pumped into
mission, check that the capacity slide is in mini-
the compressor lubrication system. When the time
mum position. The oil pump is started and oil will
period has expired, the compressor will start and
now be pumped into the compressor lubrication
the pump will run for min 60 seconds. The pump
system. To avoid disconnection, the oil flow switch
will stop if the differential pressure is higher than
must be activated within 45 seconds.
SET POINT 1.
When the oil flow switch is activated, the compres-
Alarm surveillance
sor will start.
During start the following alarms are delayed:
The pump will operate for a minimum of 60 sec-
onds and stop if the differential pressure is higher
Low oil pressure 45 sec than SET POINT 2 as described above.
High filter diff. pressure 300 sec Alarm surveillance
Low superheat 300 sec During start the following alarms are delayed:
High superheat 300 sec Low oil pressure 45 sec
Low/high oil temperature 300 sec High filter diff. pressure 300 sec

Low superheat 300 sec


The delayed alarms are described in section Tim-
ers. High superheat 300 sec

Low/high oil temperature 300 sec


SV 24/26 with oil pump
The compressors SV 24 and SV 26 are small slide FV 24/26 with oil pump
regulated screw compressors.
The compressors FV 24 and FV 26 are small fre-
The electrical oil pump is used for prelubrication quency regulated screw compressors, ie the
and maintenance of a minimum oil pressure dur- mounted slide is only used during start and stop.
ing operation.
The electrical oil pump is used for prelubrication
The pump is started and stopped in accordance and for maintenance of a minimum oil pressure
with the compressor differential pressure during during operation.
operation.
The pump is started and stopped in accordance
The difference is set in the picture OIL I OIL with the compressor differential pressure during
PRESSURE I PARAMETER whereupon SET operation.
POINT 1 and SET POINT 2 will appear.

114/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

The difference is set in the picture OIL I OIL FV 19 with oil pump
PRESSURE I PARAMETER whereupon SET The compressor FV 19 is a small frequency regu-
POINT 1 and SET POINT 2 will appear. lated screw compressor without the stage regulat-
Normal setting for FV 24/26: ed capacity control as featured in the SV 19.
SET POINT 1 = 2.5 Bar The electrical oil pump is used for prelubrication
SET POINT 2 = 4.0 Bar and for maintenance of a minimum oil pressure
Set points are adjusted as described in the previ- during operation.
ous section. The pump is started and stopped in accordance
with the compressor differential pressure during
Starting sequence
operation.
Once the compressor has received permission to
start, the oil pump will start and oil is pumped into The difference is set in the picture OIL I OIL
the compressor lubrication system. PRESSURE I PARAMETER whereupon SET
POINT 1 and SET POINT 2 will appear.
The oil flow switch must be activated within 45
seconds to avoid disconnection. Normal setting for FV 19:

When the oil flow switch is activated, the solenoid SET POINT 1 = 2.5 Bar
valve (capacity slide down) will be open for 15 SET POINT 2 = 4.0 Bar
seconds and the electrical fan will start. The fre-
0178_432_en.fm

Set points are adjusted as described in the previ-


quency converter will then receive a signal to ous chapter.
start.
Starting sequence
The speed is increased to 1000 rpm in 10 sec- Once the compressor has received starting per-
onds. mission, the oil pump will start and oil will be
The pump will operate for a minimum of 60 sec- pumped into the compressor lubrication system.
onds and will stop if the differential pressure is The oil flow switch must be activated within 45
higher than SET POINT 2 as described above. seconds to avoid disconnection.
Alarm surveillance When the oil flow switch is activated, an oil
During start the following alarms are delayed: by-pass solenoid valve for unloading will open for
Low oil pressure 45 sec 15 seconds and the electrical fan will start.

High filter diff. pressure 300 sec Starting signal is transmitted to the frequency con-
verter.
Low superheat 300 sec
The speed is increased to 1200 rpm in 10 sec-
High superheat 300 sec
onds.
Low/high oil temperature 300 sec
The pump will operate for a minimum of 60 sec-
See also section Timers onds and stop if the differential pressure is higher
than SET POINT 2 as described above.

0178-445 - ENG 115/222


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

Alarm surveillance The pump will run for 60 sec and stop.
During start the following alarms are delayed: Alarm surveillance
Low oil pressure 45 sec During start the following alarms are delayed:
High filter diff. pressure 300 sec Low oil pressure 45 sec
Low superheat 300 sec High filter diff. pressure 300 sec
High superheat 300 sec Low superheat 300 sec
High/low oil temperature 300 sec High superheat 300 sec

Low/high oil temperature 300 sec


See also section Timers.
See also section Timers.
VMY Mk 3
without full flow pump SAB 110/128/163 Mk 2
Once the compressor has received starting per- without oil pump
mission, the oil pump will start. Check that the ca-
Once the compressor has received starting per-
pacity slide is in minimum position.
mission, make sure that the capacity slide is in
The oil is pumped into the compressor lubrication minimum position.
system. As soon as the oil flow switch has been
Start the compressor and wait for a signal from the
activated, the prelubrication period will start.
oil flow switch for max 50+10 sec.
When the time period has expired, the compres-
If there is no signal from the oil flow switch for 10
sor will start and the pump will run for 60 sec.
sec during operation, the compressor will stop.
Alarm surveillance
Alarm surveillance
During start the following alarms are delayed:
During start the following alarms are delayed:
Low oil pressure 45 sec
Low oil pressure 45 sec
High filter diff. pressure 300 sec
High filter diff. pressure 300 sec
Low superheat 300 sec
Low superheat 300 sec
High superheat 300 sec
High superheat 300 sec
Low/high oil temperature 300 sec
Low/high oil temperature 300 sec

See also section Timers.


See also section Timers.

VMY Mk 2 and 2.5 with built-in oil pump SAB 128/163 Mk 2 Booster with oil
Once the compressor has received starting per- pump
mission, the pump will start. Make sure that the
Once the compressor has received starting per-
capacity slide is in minimum position.
mission, the pump will start. The built-in spring en-
The compressor will start working. sures that the capacity slide is in minimum posi-
tion.

116/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

Start the compressor and wait for a signal from the Low superheat 300 sec
oil flow switch for max 50+10 sec.
High superheat 300 sec
If there is no signal from the oil flow switch for 10
Low/high oil temperature 300 sec
sec during operation, the compressor will stop.
The oil pump runs continually during operation to See also section Timers.
ensure sufficient pressure to move the capacity
slide. Reciprocating compressors
Alarm surveillance No particular starting up sequence exists for recip-
During start the following alarms are delayed: rocating compressors. However, some alarms are
delayed at this stage.
Low oil pressure 45 sec
Alarm surveillance
High filter diff. pressure 300 sec
During start the following alarms are delayed:
Low superheat 300 sec
Low oil pressure 60 sec
High superheat 300 sec
High oil pressure 20 sec
Low/high oil temperature 300 sec
Low suct.gas superheat 15 sec
See also section Timers. High suct.gas superheat 300 sec
0178_432_en.fm

Low/high oil temperature 300 sec


SAB 163 Mk 1 with oil pump
Low disch. gas superheat 300 sec
Once the compressor has received starting per-
Low/high intermediate discharge 300 sec
mission, the pump will start. The built-in spring en- temperature
sures that the capacity slide is in minimum posi-
tion. See also section Timers.
The oil is pumped into the compressor lubrication The following descriptions of the various functions
system and when the oil flow switch is activated, must be compared with the wiring diagrams in
the prelubrication period will begin. which the activating connections are included.
When this period has expired, the compressor will
start, and the pump will work for 300 sec and then External starting permission -
stop. immediate stop
In case of a booster compressor, the pump will The input must be connected in order for the com-
run continually during operation to ensure suffi- pressor to run in MANUAL, AUTO or REMOTE. If
cient pressure to move the capacity slide. this input is opened during operation, the com-
See also section Timers. pressor will stop immediately.
When the input is open, STOPPED will appear in
Alarm surveillance
the bottom line of the display.
During start the following alarms are delayed:
Low oil pressure 300 sec

High filter diff. pressure 300 sec

0178-445 - ENG 117/222


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

External starting permission - sued while the oil pump is in manual operation for
normal stop oil charging.
This input and IMMEDIATE STOP must be con- If the pump is to stop before time expiry, select NO
nected before the compressor is going to start in under START OIL PUMP.
AUTO or REMOTE. If the input has not been con- Note: As from 2001 SAB 128/163 Mk3 and SAB
nected, the display will read STOPPED in the bot- 202 are no longer as standard fitted with a valve
tom line. for external connection to the oil pump suction
If the input is opened during operation, the com- side. Thus it is not possible to charge oil with the
pressor capacity will move to its minimum posi- unit oil pump.
tion, and the compressor will stop on its delay be-
fore the actual time to stop. Motor current measuring
In case the input CAPACITY DOWN BLOCKED is UNISAB II can be supplied with a signal 0-1 Amp
connected, the compressor will not reduce capac- AC directly from a current transformer in the com-
ity once the input EXTERNAL STARTING PER- pressor motor starter.
MISSION NORMAL STOP is opened.
The value for the voltage ratio of the current trans-
former must be entered in the menu CONFIG I
Oil charging, manual (screw RANGE M. CURR to get a correct reading of the
compressors) current.
Oil charging cannot take place with UNISAB II in Next, select menu MOTOR I MOTOR CUR-
"STOPPED". If the compressor is fitted with an oil RENT and the following picture will appear:
pump for oil charging, it can be started in the fol-
lowing way:
ACTUAL SP XX A
Select menu TIMERS I OIL CHARGING and the SET POINT 1 XX A
following picture will appear: SET POINT 2 XX A

In SET POINT 1 enter the motor full load current


START OIL PUMP NO
of the motor as read on the name plate. In SET
TIMER 0 sec
POINT 2 a lower value may be entered if the ab-
Place the cursor on TIMER and press G until the sorbed current is to be limited in certain periods.
cursor moves to the right. Set the number of sec- Set points are set by placing the cursor on SET
onds the pump is to run. Press G and move the POINT 1 or SET POINT 2 respectively. Press G
cursor back to START OIL PUMP. Press G until until the cursor moves to the right. The correct
the cursor moves to the right, then select YES with number can now be set by using J or K .
J or K .
It is possible to change between two set points by
The pump will now start and run for the time set. opening or closing a digital input. See wiring dia-
For SAB 202, SAB Mk3 and VMY Mk3 compres- grams.
sors a warning "Watch the oil pressure" will be is- Open input = SET POINT 1.
See also Current limiters.

118/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

Motor power measuring The measuring of these values are set in the pic-
UNISAB II can be supplied with a 4-20 mA signal ture CONFIG I COP.
from a power transmitter of 0-xxxx KW.
Enter the power ratio of the power transmitter in COP ACTIVE NO
FLOW FACTOR 0.20 l/pls
the menu CONFIG I RANGE M. CURR to get a
LIQ. SUBCOOL 3.0
correct reading of the power output.
In the menu CALIB I CALIBRATE COP, select The COP function is connected and disconnected
MOTOR SIGNAL for kW. in the menu SETTING I CONFIG I COP AC-
Then select the menu MOTOR I MOTOR POW- TIVE, cf section Configuration.
ER, and the following picture will appear: The calculated COP values are shown in the pic-
ture SETTING I DIAGNOSIS I COP.

ACTUAL SP xxxx KW A more comprehensive description of the COP


SET POINT 1 xxxx KW funtion and its setting is included in the manual
SET POINT 2 xxxx KW UNISAB II-COP.

In SET POINT 1 enter the motor top load power


read on the name plate. In SET POINT 2 a lower
Thermistor connection
If the motor is fitted with thermistors for protection
0178_432_en.fm

value can be entered for periods when less power


is required. of the motor temperature, these can be connected
directly to a digital input. See wiring diagrams.
Switch between the two set points by opening or
closing a digital input, cf wiring diagrams. Should the motor temperature rise excessively,
the compressor will stop.
Open input = SET POINT 1.
See also Current limiter
Aux. output
In the menu CALIB I AUX. OUTPUT the follow-
COP set-up
ing picture will appear:
UNISAB II can be set for measuring compressor
COP (Coefficient Of Performance), mechanical
AUX. OUTPUT
efficiency as well as Carnot efficiency.
ACTIVATED WHEN
Together with suction and discharge pressure and NOT USED
temperature, the following values form basis of
the calculations: The cursor is on AUX. OUTPUT. Press G and
the cursor moves to NOT USED.
• Temperature of chilled liquid before evapo-
rator. With J or K choose between:

• Volume flow of cooling gas on pressure side • READY


(m3/h). • AT MIN CAP.
• Motor power consumption in kW. • AT MAX CAP.
• Motor efficiency. • RUNNING

0178-445 - ENG 119/222


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

• READY-EXT. in this state by closing a digital input. See wiring


This function is connected to a digital output. See diagrams. The input overrules EXTERNAL
wiring diagrams. STARTING PERMISSION, NORMAL STOP.

1) READY: If selecting this function, the output In case the compressor runs in limited operation,
will be activated when the compressor is it will, however, reduce its capacity. When the
ready for operation in REMOTE. This state of operation is back to normal, the compres-
means that AUTO START has been config- sor will return to full load. See also Limitations.
ured (and AUTO STOP), EXTERNAL If the input is connected while the compressor is
START NORMAL STOP has been set. READY to start in AUTO or REMOTE, the com-
There are no alarms - and the compressor pressor will be started by force.
can start.
2) AT MIN CAP: If selecting this function, the Power management system (PMS)
output will be activated when the compres- This function works in MANUAL, AUTO or RE-
sor is below LOW LIMIT, which is set in the MOTE operation. It is a kind of "an agreement to
menu CALIB I CAP. LIMIT. The hysterisis start" system, consisting of one digital output
is 1%. "Compressor ready to start", which is set when the
3) AT MAX CAP: Select this function and the compressor is to start, as well as a digital input
output is activated when the compressor is "Permission to start OK". This input must be set
above HIGH LIMIT, which is set in the menu before the timer "PMS confirmation" expires in or-
CALIB I CAP. LIMIT. The hysterisis is 1%. der for the compressor to start.

Please note that the line CAP.LIMITER is not in- The alarm "Power management system error" is
cluded in the CALIBRATION menu until the auxil- activated if the input "Permission to start OK" has
iary output has been selected as either AT MIN. not been set before the timer "PMS confirmation"
CAP. or AT MAX. CAP. expires.

4) RUNNING: If selecting this function, the out- The signal can be removed during operation with-
put will be activated whenever the compres- out stopping the compressor.
sor is operating, ie when the start signal to
the compressor has been set. Cold store function
5) READY-EXT.: This function corresponds to This function is connected to the regulators for ca-
the above READY function, but here it is not pacity regulation of the compressor.
required that EXTERNAL START NORMAL Usually, the compressor is going to start in AUTO
STOP must be set for the output to be acti- or REMOTE/MULITSAB if the measured value is
vated. The function works both in REMOTE outside the neutral zone and a capacity require-
and AUTO. ment exists.
If COLD STORE FUNCTION has been selcected
Capacity down blocked in the menu CONFIG, the compressor will not
When the compressor is in max capacity in AUTO start until the measured value is outside the P
or REMOTE, it is possible to lock the compressor

120/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

Band. After this, it will regulate normally in accord- pressor is now going to start within the period of
ance with the set point. time set in the timer START HPRESS.
Fig. 7.1 After this, the compressors will regulate normally
Example of cold store function
on the capacity regulator.
Please note that the last compressor in operation
UNISAB II is set for suction
pressure regulation with in a MULTISAB system (usually the no 1 com-
Set point (Sp) = -40°C pressor in the starting sequence) will not stop on
Neutral zone (Nz) = 4 K
Proportional band (Pb) = 5 K
the timer STOP DELAY. It can only be stopped by
NORMAL opening the input EXT START, NORMAL STOP,
Suct.press (°C/R) which makes the compressor stop for a moment.
-33
1 Pb = 5 K
-38 Oil return (reciprocating compressors)
-40 Nz = 4 K
Pb = 5 K The solenoid valve for oil return from the oil sepa-
rator/oil reservoir to the compressor will be open
1 Compressor start when the compressor starts and an ON signal is
(Just outside Nz)
issued from one digital input (or in the case of
COLD STORE FUNCTION
two-stage compressors two digital input).
Suct.press (°C/R)
0178_432_en.fm

1 In case of a one-stage compressor, only the digital


-33
Pb = 5 K input for high-pressure oil separator is used. Here,
-38
-40 Nz = 4 K the input must be ON before the digital output oil
Pb = 5 K return is set.
In case of two-stage compressors where both the
1 Compressor start IP and HP part may have their own oil separator,
(Just outside Pb)
the digital inputs INTERMEDIATE PRESSURE
OIL RETURN and HIGH PRESSURE OIL RE-
Note on screw compressors TURN are used. Here, both inputs must be ON
before setting the digital output for oil return.
It is not recommended to use the cold store
function on screw compressors! From version 1.10 the opening of the solenoid
valve(s) for oil return can be combined with an ad-
justable time delay.
HP on TWO-STAGE
This function is used on two-stage plants to start At compressor start the output(s) for oil return
HP compressors by force. is/are not opened until the time set in the timer OIL
RETURN has expired.
HP on TWO-STAGE must have been selected in
the menu CONFIG. The function only works in The time delay function will be disconnected if the
REMOTE/MULTISAB. timer OIL RETURN is set for 0 sec or when the
digital inputs for intermediate and high pressure
A compressor is started by force by closing the in-
oil return are OFF.
put EXT START, NORMAL STOP. The first com-

0178-445 - ENG 121/222


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

The time delay OIL RETURN is set in the timer


picture TIMER I TIMER SETUP.
DEF. REFRIGERANT R000

Oil heating TEMP: PRESS (ABS):

Oil heating is NOT a configuration point, but it has


-90 °C/R 00.00 BAR
various functions depending on whether the com-
pressor in question is configured as a reciprocat- -85 °C/R 00.00 BAR
ing or a screw compressor.
-80 °C/R 00.00 BAR
Screw compressors
-75 °C/R 00.00 BAR
A heating element will be connected while the
compressor is not in operation and there is no -70 °C/R 00.00 BAR
temperature regulation.
-65 °C/R 00.00 BAR
Reciprocating compressors
The heating element outlet is activated by de- -60 °C/R 00.00 BAR

creasing oil temperature. This function is active


-55 °C/R 00.00 BAR
both at compressor stand-still and when the com-
pressor is in operation. -50 °C/R 00.00 BAR

The set point of this value is set in picture OIL -45 °C/R 00.00 BAR
TEMP I PARAMETER, SET POINT 2. The set
point has a fixed hysteresis of 5K. -40 °C/R 00.00 BAR

Ex: Set point 2 = 35°C: -35 °C/R 00.00 BAR


Heating starts at 35°C and stops at (35+5) = 40°C.
-30 °C/R 00.00 BAR

Definition of refrigerant R000 -25 °C/R 00.00 BAR

If the refrigerant used cannot be found in the list of -20 °C/R 00.00 BAR
refrigerants - see section Configuration - it is pos-
sible to select a user defined refrigerant designat- -15 °C/R 00.00 BAR

ed R000 (the R000 designation does not refer to


-10 °C/R 00.00 BAR
any known refrigerant).
-5 °C/R 00.00 BAR
Before selecting R000 in SETUP I CONFIG en-
ter the data for the substances (the refrigerant 00 °C/R 00.00 BAR
curve) contained in the refrigerant used.
05 °C/R 00.00 BAR
In the menu SETUP I CALIB I DEF. REFRIG-
ERANT R000, the following picture will appear: 10 °C/R 00.00 BAR

15 °C/R 00.00 BAR

20 °C/R 00.00 BAR

122/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

25 °C/R 00.00 BAR 70 °C/R 00.00 BAR

30 °C/R 00.00 BAR 75 °C/R 00.00 BAR

35 °C/R 00.00 BAR 80 °C/R 00.00 BAR

40 °C/R 00.00 BAR


For BAR/°C, enter the pressure as absolute pres-
45 °C/R 00.00 BAR sure in 1/100 BAR. For temperatures enter values
between -90°C and +80°C with intervals of 5°C.
50 °C/R 00.00 BAR
Each pressure value in the table must be given a
55 °C/R 00.00 BAR
certain value.
The pressure can be entered in the range of 00.00
60 °C/R 00.00 BAR
and 99.99 BAR. The table has been initialized to
65 °C/R 00.00 BAR 00.00 BAR.
0178_432_en.fm

0178-445 - ENG 123/222


Rev. 03.09
UNISAB II 2.03
7. Compressor control and surveillance

124/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
8. Calibration

8. Calibration
Before initial compressor start-up and after Insufficient or incorrect setting of pressure
service1), adjustments of transducers and position transducers may lead to compressor
transmitters must be carried out. Their values breakdown or personal injury.
have usually been preset by the factory, but a re- The temperature sensors must be calibrated as
check must be made before start-up. This is very they are connected electrically with four conduc-
important as failure to adjust may lead to malfunc- tors, which automatically makes up for line resist-
tion during operation. ance.
1) Eg in connection with replacement of CPU
prints, relay prints, pressure transducers or batter- Pressure transducers
ies. See also section Service. Calibrate the pressure transducers at atmos-
pheric pressure in the compressor.
Use the following pressure transducers:
Table 10
Unit = BAR COMPRESSOR TYPE
Max.
MEAS.POINT SAB/VMY SMC TSMC/ HPC/HPO MAX.
0178_433_en_2.02.fm

permissible
TCMO PRESS. deviation at
ATM.PRESS

SUCT.PRESS. 33 +/- 0.2


-1-+9 -1-+9 -1-+9 -1-+25
55 +/- 0.5

DISCH.PRESS 55 +/- 0.5


-1-+25 -1-+25 -1-+25 -1-+59
200 +/- 1.2

OIL PRESS -1-+25 -1-+25 -1-+25 -1-+25 55 +/- 0.5

DIFF PRESS -1-+25 55 +/- 0.5

INTERM.PRESS -1-+25 55 +/- 0.5

0178-445 - ENG 125/222


Rev. 03.09
UNISAB II 2.03
8. Calibration

Select the menu CALIBRATE, and the following As it appears from the above example, the meas-
picture will be displayed: ured pressure levels are not 0.0 Bar. Consequent-
ly calibration must be carried out.

CALIBRATE Place the cursor on SUCT. ADJUST and use the


PRESS.TRANSDUCER G key to change the value.
BRINE TEMP
Now change the value to the value SUCT. AD-
CAPACITY
JUST is showin, ie 0.2 Bar with opposite sign.
MOTOR FREQ
Vi POSITION
Note that the adjusting value is in 1/100.
4 - 20 mA INPUT Change SUCT. ADJUST to the value -.20.
AUX. OUTPUT
Adjust the other pressure levels in the same way.
CAP. LIMITS
DEF. REFRIGERANT R000
However, note that DIFF. PRESS is relevant only
for screw compressors and IMED. PRESS only for
Note that some of the entries in the CALIBRATE two-stage reciprocating compressors.
menu are described in other chapters of this man- The following picture should now appear:
ual.
With the cursor on PRESS.TRANSDUCER, press
SUCT. PRESS .00 BAR
I and the following picture will appear: SUCT. ADJUST -.20 BAR
DISC. PRESS 0.0 BAR
DISC. ADJUST .30 BAR
SUCT. PRESS .20 BAR
OIL PRESS 0.0 BAR
SUCT. ADJUST .00 BAR
OIL ADJUST -.10 BAR
DISC. PRESS -0.3 BAR
DIFF. PRESS 0.0 BAR
DISC. ADJUST .00 BAR
DIFF. ADJUST ..10 BAR
OIL PRESS 0.1 BAR
IMED. PRESS 0.0 BAR
OIL ADJUST .00 BAR
IMED. ADJUST -.10 BAR
DIFF. PRESS -0.1 BAR
DIFF. ADJUST .00 BAR
The pressure transducer calibration has now
IMED. PRESS 0.1 BAR
IMED. ADJUST .00 BAR
been carried out correctly.

Note: The pressure values shown are examples Brine temperature


only. At atmospheric pressure the value of the
Place the cursor on BRINE TEMP and press the
pressure transducer must be within the limits for
I key once. The following picture will appear:
"Max. permissible deviation at atm.pressure" as
indicated in the above table. Is this not the case,
the value will be outside its tolerance and must be BRINE TEMP 18.9°C

replaced. BRINE ADJUST 0.0°C

The pressure levels are measured in BAR (rela- The BRINE TEMP value is the immediate value
tive pressure) and at atmospheric pressure the measured by the sensor. If a test measuring with
reading must show 0.0 Bar to be correct. a precision thermometer shows eg 18.7°C at the
sensor, adjustment can be made.

126/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
8. Calibration

Place the cursor on BRINE ADJUST and change can be adjusted by software as described in sec-
the value to -0.2°C. BRINE TEMP will now be tion Software adjustment.
18.7°C (18.9-0.2), and adjustment has taken
Software adjustment
place.
When the capacity position transmitter has been
Note that it is only possible to adjust BRINE TEMP adjusted mechanically (see section Transmitter
- not the other temperature sensors. adjustment), it can be fine adjusted by selecting
SETUP I CALIBRATE I CAPACITY.
Calibration of capacity slide signal
Software calibration of the capacity slide position CAPACITY XXX.X %
signal can be used if it is not possible to calibrate CAP. ZERO AD XX.X %
the transmitter itself. See below for information on CAP. 100 ADJ XX.X %

software calibration.
Follow the same procedure as described for ca-
pacity slide calibration in section Transmitter ad-
Calibration of Vi slide signal justment.
Software calibration of the Vi slide position signal
0 % calibration is carried out with the capacity
can be used if it is not possible to calibrate the slide in minimum position. If CAPACITY is not
0178_433_en_2.02.fm

transmitter itself. See below for information on showing 0.0 %, but eg 1.5 %, position the cursor
software calibration. on CAP. ZERO AD and change the calibration val-
ue to -1.5 % with the G key.
Calibration of motor frequency signal 100 % calibration is carried out with the capacity
When compressor capacity is regulated wholly or slide in maximum position.
partly by changes in the motor speed, the motor If CAPACITY is not showing 100.0 %, but eg 95.8
frequency signal from the frequency converter %, position the cursor on
can be calibrated in this menu field. CAP. 100 ADJ and change the calibration value to
4.2 % with the G key.
Motor current Transmitter adjustment
The reading of motor current can be calibrated as To ensure a safe and stable movement of the
described in section Configuration, pos. 19. slides, the built-in position transmitter must be ad-
justed correctly in the mechanical minimum and
Hydraulic slide systems maximum of the slide. Furthermore, the slide ve-
(certain screw compressors) locity must be adjusted so that hunting is avoided.
The built-in capacity slide position transmitter as See also Adjusting slide velocity in section Com-
well as the Vi slide position transmitter must be pressor regulation.
adjusted correctly to ensure safe and stable slide Position transmitter
control. This adjustment must always be carried For measuring of slide position, the compressor is
out mechanically as described in section Trans- fitted with a position transmitter, which yields 4 -
mitter adjustment. Additionally, the capacity signal 20 mA to UNISAB II. There will always be fitted a
transmitter at the capacity slide whereas there

0178-445 - ENG 127/222


Rev. 03.09
UNISAB II 2.03
8. Calibration

may be fitted a transmitter at the volume ratio slide


in case the compressor is made for automatic Vi Short-Stroke Transmitter for SAB 283, SAB 355
regulation. Vi, from Gram Refrigeration to GSV, RWF capac-
There are four types of position transmitter. ity and Vi) and capacity for GST.
Turning Transmitter(for capacity and Vi) for SAB Fig. 8.4
110, SAB 128, SAB 163 and SAB 202.
Fig. 8.1

4.5 4.
3.5
3. 2
100%
2.5 3
SPAN + ZERO 1

No. 3
2.
0%

Long-Stroke Capacity Rod Transmitter for SAB


110, SAB 128, SAB 163, SAB 202, SAB 81, SAB
83, SAB 85, SAB 87, SAB 89 and SAB 330.
Fig. 8.2 Adjusting capacity measuring system
for turning transmitter
ALU-Tube The turning transmitter has two ways of adjust-
2
3
1 ment. The cover must be removed before adjust-
ment.
In the following drawing(see Fig. 8.5) the zero and
Long-Stroke Capacity Rod Transmitter for SAB
span adjusting screws of the position transmitter
283.
are shown.
Fig. 8.3

ALU-Tube
3
2 1

128/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
8. Calibration

Fig. 8.5

Slide position
4.5 4.
Volume ratio 3.5
1 = 4 - 20 mA
3. 2
2 = + 24 VDC
Approx min pos 100%
3 = GND
0% 2.5 3
SPAN + ZERO 1

No. 3
2.
0%

T0177063_0

With the cap/Vi slide in minimum position, adjust The following picture will appear:
zero until the display shows 0%. With the cap/Vi KAPACITY XX
slide at maximum positon, adjust span until the CAP. POS XX

display shows 100%. VI POSITION XX


RUNNING XX
Capacity slide adjustment
0178_433_en_2.02.fm

Start the compressor in MANUAL and make sure


that the capacity slide is in minimum. Adjust the Select the Vi POSITION and press I to the follow-
zero screw of the transmitter until the display ing picture:
shows 0%.
Now bring the slide to its maximum position (eg
when the current consumption is no longer rising), SETPOINT 1 0.0%
and adjust the span until the display shows 100%.
Return the slide to minimum and check. 0.0% in this picture indicates that UNISAB II will
Capacity slide adjustment, manual Vi adjust the Vi slide automatically.
Follow the same procedure as above, but note Change SETPOINT 1 to -10% which will change
that adjustment must be made each time the Vi the Vi adjustment to manual and place the Vi slide
position is changed. in minimum position.
Capacity slide adjustment, auto V i Adjust the capacity slide position as above under
To adjust the movement of the capacity slide the Capacity slide adjustment.
Vi slide must be in minimum position. The Vi slide
Capacity slide adjustment, auto zero point
is brought to minimum the following way: Start the
For SAB 202 compressors with automatic zero
compressor in MANUAL, select SETUP I and
point setting, there are two applicable methods to
then CAPACITY I.
ensure that the automatic zero point setting does
not influence the adjusting of the transmitter zero.
1) Do not set the zero until the compressor has
stopped and the slide is in mechanical zero.

0178-445 - ENG 129/222


Rev. 03.09
UNISAB II 2.03
8. Calibration

2) Disconnect the automatic zero point setting adjust the span screw of the transmitter until the
while setting the transmitter zero. This can be display shows 100%.
done by setting MANUAL ZERO = 0.1 in the pic- Change SET POINT 1 to -10% and check mini-
ture SETUP I CONFIG I COMPRESSOR. mum.
Remember to set MANUAL ZERO = 0.0 as soon Change SET POINT 1 to 0.0% for automatic Vi
as the capacity slide adjustment is accomplished.
control. Besides, UNISAB II will change to auto-
It is important that the compressor only runs for a
matic Vi control itself after the compressor has
brief period of time when the automatic zero point
been stopped.
setting is disconnected.
See also Adjusting slide velocity in the Compres-
Volume ratio slide adjustment, auto Vi
sor regulation section.
It is assumed that the capacity slide has been set
Adjusting capacity measuring system for
correctly.
Long-Stroke Capacity Rod for SAB 110, SAB
Start the compressor in MANUAL and take the 128, SAB 163, SAB 202, SAB 81, SAB 83, SAB
slide up to 20-30%. 85, SAB 87, SAB 89 and SAB 330
Select CAPACITY I VI POSITION I and the fol- As shown below, the capacity transmitter is fitted
lowing picture will appear: with a single calibration button surrounded by a
green and red LED.
Fig. 8.6
SETPOINT 1 0.0%
Calibration push botton
LED-Supply
LED-Digital output
In this picture 0.0% will always mean that the Vi
slide will be adjusted automatically by UNISAB II. Plug Connection

Change SETPOINT 1 to -10%, which changes the


Vi adjustment to manual and places the Vi slide in
minimum position.
Return with H to the picture: Out 4-20mA
Supply +24V DC
Common-
GND
CAPACITY XX
CAP. POS XX
VI POSITION XX During normal operation the red LED is flashing
RUNNING XX
rather slowly. The green LED is switched on con-
stantly when the transmitter is in 100% position
and adjust the zero screw of the Vi position trans-
whereas it flashes quickly when the transmitter is
mitter until the reading out for the Vi-position is 0%
in 0% position.
in the display.
Calibration is carried out as follows:
Change SET POINT 1 to 110% and return to the
above picture where the Vi position is now going Note: Make sure that UNISAB II is not in alarm.
to rise. Wait until it does not rise any further and

130/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
8. Calibration

1) Apply supply voltage for a minimum of five 6) Reset “CAP 100 ADJ” at what it was before
minutes before calibration. the calibration or until the capacity shows
2) Press the calibration button for five seconds 100%.
to get the transmitter in calibration mode. 7) The calibration will be remembered even in
The red LED will change from normal flash case of a power failure.
to OFF. To return to “Factory Set Point”, press the CAL.
3) With stopped compressor, press the calibra- Switch for twenty seconds. The green and red
tion button once. The red LED will switch LED will give a short flash (one after the other).
ON immediately. After ten seconds the red The 4-20 mA signal from the transmitter is perma-
LED will turn OFF again, indicating that it is nently available. However, during calibration the
ready for 100% calibration. signal is based on the default calibration values,
4) Start the compressor and increase capacity so it will not show 0% at minimum capacity nor
to its maximum, and press the calibration 100% at maximum capacity!
button twice. The red LED will start flashing Note that it is possible to return to the default cal-
quickly. After ten seconds the red LED will ibration values by keeping the CAL Switch
change to normal flash rate, indicating that pressed for twenty seconds. However, it is the
the calibration has been completed. transmitter manufacturer's default values, which
0178_433_en_2.02.fm

To make sure that the slide is in maximum are reset. These values may differ very much from
physical position, (UNISAB II does not allow the correct values for the compressor in question.
the capacity button to be activated after Reset is indicated by the red and green LED flash-
100% indication in the display has been ing briefly a couple of times.
reached) it is recommended to set “CAP
100 ADJ” at -10% after 100% calibration of Adjusting Long-Stroke Capacity Rod
the transmitter has been completed and the for SAB 283.
slide remains in maximum position. See the
For type part no. 1373-038
Software Calibration section earlier in this
section. The slide indication in the display Note: For long-stroke transmitters with part no.
must now be 90%. If capacity can be in- 1373-057 calibration and terminal connection are
creased further either automatically by UN- similar to that of SAB 110, SAB 128 etc. Please
ISAB II or by pressing the “UP” capacity but- see section on preceeding page.
ton, the slide has not yet been calibrated As shown below, the capacity transmitter is fitted
correctly. with a single calibration button surrounded by a
5) If capacity could be increased to more than green and red LED. During normal operation the
90%, cf. above, calibrate the slide again red LED is flashing rather slowly. The green LED
from point 1 but keep -10% in “CAP 100 is switched on constantly when the transmitter is
ADJ”. in 100% position whereas it flashes quickly when
the transmitter is in 0% position.

0178-445 - ENG 131/222


Rev. 03.09
UNISAB II 2.03
8. Calibration

Fig. 8.7

Long-Stroke SAB 283


Calibration‘s push button

PLUG CONNECTION: 1 = SUPPLY, +11 to 32V DC


LED-supply/operation
2 = COMMON -, 0V DC
3 = OUT, 4-20mA LED-digital
3
output (option)
= GND
2 1

DIA.
7mm
3

2 1

60mm

74mm

Calibration is carried out as follows: slide remains in maximum position. See the
Note: Make sure that UNISAB II is not in alarm. Software Calibration section earlier in this
section. The slide indication in the display
1. Apply supply voltage for a minimum of five must now be 90%. If capacity can be in-
minutes before calibration. creased further either automatically by UN-
2. With stopped compressor, press the calibra- ISAB II or by pressing the “UP” capacity but-
tion button once. The red LED will switch ton, the slide has not yet been calibrated
ON. After ten seconds the red LED will turn correctly.
OFF to indicate readiness for 100% calibra- 5) If capacity could be increased to more than
tion. 90%, cf. above, calibrate the slide again
3. Start the compressor and move the pis- from point 1 but keep -10% in “CAP 100
ton/alu tube to 100% position and press the ADJ”.
calibration button again. The red LED will 6) Reset “CAP 100 ADJ” at what it was before
start flashing quickly. After ten seconds the the calibration or until the capacity shows
calibration will be completed and the red 100%.
LED will flash normally.
4) To make sure that the slide is in maximum Adjusting Short-Stroke Capacity Rod
physical position, (UNISAB II does not allow
For part no. 1373-037
the capacity button to be activated after
100% indication in the display has been Note: For short-stroke transmitters with part no.
reached) it is recommended to set “CAP 1373-061 calibration and terminal connection are
100 ADJ” at -10% after 100% calibration of similar to that of SAB 100, SAB 128 etc. Please
the transmitter has been completed and the see preceeding section.

132/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
8. Calibration

for GST, GSV and RWF from Gram Refrigeration calibration button again. The red LED will
and short-stroke volumen rod for GSV, RWF and start flashing quickly. After ten seconds the
SAB 283 and SAB 355. calibration will be completed and the red
Fig. 8.8 LED will flash normally.
Capacity slide adjustment, auto Vi
The capacity slide movement must be adjusted
Short-Stroke with the Vi slide in minimum position.
The Vi slide is taken to minimum position in the fol-
LED-Supply
Calibration push botton lowing way:
Start the compressor in MANUAL and select CA-
LED-Digital output
PACITY I . The following picture will appear:
Plug Connection

CAPACITY XX
CAP. POS XX
VI POSITION XX
RUNNING XX
1 = Supply, 24V DC
0178_433_en_2.02.fm

2 = Common -, 0V DC
3 = Out, 4-20mA Select VI POSITION and press I to the following
= GND
picture:

As shown below, the capacity transmitter is fitted


with a single calibration button surrounded by a SETPOINT 1 0.0%

green and red LED. During normal operation the


red LED is flashing rather slowly. The green LED
In this picture 0.0% will always mean that the Vi
is switched on constantly when the transmitter is
slide will be adjusted automatically by UNISAB II.
in 100% position whereas it flashes quickly when
the transmitter is in 0% position. Change SETPOINT 1 to -10%, which changes the
Vi adjustment to manual and places the Vi slide in
Capacity calibration is carried out as follows:
minimum position.
Note: Make sure that UNISAB II is not in alarm.
Adjust the capacity slide position as described
1. Apply supply voltage for a minimum five above under Capacity slide adjustment.
minutes before calibration.
Capacity slide adjustment, auto zero point
2. With stopped compressor, press the calibra- For SAB 202 compressors with automatic zero
tion button once. The red LED will switch point setting, two methods can be used to ensure
ON. After ten seconds the red LED will turn that the automatic zero point setting does not af-
OFF to indicate readiness for 100% calibra- fect the adjustment of the transmitter zero.
tion.
1. Do not set the zero until the compressor has
3. Start the compressor and move the pis- stopped and the slide is in mechanical zero.
ton/alu tube to 100% position and press the

0178-445 - ENG 133/222


Rev. 03.09
UNISAB II 2.03
8. Calibration

2. Disconnect the automatic zero point setting Change SET POINT 1 to 110% and return to the
while setting the transmitter zero. This is above picture where the Vi position will increase.
done by setting MANUAL ZERO = 0.1 in the Wait until it does not increase any further and
picture SETUP I CONFIG. push the calibration button once again. The red
Remember to set MANUAL ZERO = 0.0 LED will flash quickly and after 10 sec. the calibra-
once the capacity slide adjustment has tion is completed and the red LED will flash nor-
been completed. The compressor is only mally.
allowed to run for a brief period of time
Change SET POINT 1 to -10% and check mini-
with the automatic zero point setting dis-
mum.
connected.
Change SET POINT 1 to 0.0% for automatic Vi
Volume ratio slide adjustment, auto Vi
control. UNISAB II will change to automatic Vi
It is assumed that the capacity slide has been set control after the compressor has been stopped.
correctly.
See also Adjusting slide velocity in section Com-
Start the compressor in MANUAL and take the pressor regulation.
slide up to 20-30%.
Select CAPACITY I VI POSITION and the fol- Electrical slide systems (certain screw
lowing picture will appear: compressors)
The built-in capacity slide position transmitter
must be adjusted correctly to ensure safe and sta-
SETPOINT 1 0.0%
ble slide control. This adjustment must always be
carried out as described in section Transmitter ad-
In this picture 0.0% will always mean that the Vi justment.
slide will be adjusted automatically by UNISAB II. Afterwards, the capacity signal must be
adjusted by software as described in section
Change SETPOINT 1 to -10%, which changes the
Software adjustment.
Vi adjustment to manual and places the Vi slide in
minimum position. Manual slide positioning
In contrary to hydraulic slides, the electrical ca-
Return with H to the picture:
pacity slide can be positioned manually for test.
This is useful both when performing transmitter
CAPACITY XX adjustment and software adjustment.
CAP. POS XX
Select SETUP I CONTROL I COMPRESSOR-
VI POSITION XX
CONTROL = STOPPED and then SETUP I
RUNNING XX
CALIBRATE I CAPACITY. The picture shown in
Wait until Vi does not decrease any further and section Software adjustment will appear. While
push the calibration button once. The red LED is this picture is open (and still STOPPED mode), it
now constantly ON. After 10 sec. the red LED will is possible to move the capacity slide by means of
turn OFF to indicate that it is ready for 100% cali- the E and F buttons.
bration.

134/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
8. Calibration

Note that when reaching the end stop, the alarm Transmitter adjustment
CAPACITY ERROR will be displayed after two The capacity transmitter is fitted with a single cal-
seconds. Release the button at once and reset the ibration button surrounded by a green and a red
alarm. LED as shown in the drawing.
Fig. 8.9

Calibration
push button LED-Working
LED-Position (red)
(green)

Normally
not visible.
For calibration
remove cover
0178_433_en_2.02.fm

During normal operation the red LED is flashing tion transmitter is ready for 100% calibra-
rather slowly. The green LED is switched on con- tion.
stantly when the transmitter is in 100% position 4. Increase capacity to its maximum and press
whereas it flashes quickly when the transmitter is the calibration button twice. The red LED
in 0% position. will start flashing quickly. After ten seconds
Calibration is carried out as follows: the red LED will change to normal flash rate,
1. Apply supply voltage for a minimum of five indicating that calibration has been complet-
minutes before calibration. ed.

2. Press the calibration button for five seconds It is possible to ignore points 3 or 4 or both. Press-
to get the transmitter in calibration mode. ing the calibration button for five seconds in cali-
The red LED will change from normal flash bration mode will bring the transmitter back to nor-
to OFF. mal operation mode.

3. Decrease capacity to its minimum and press The 4-20 mA signal from the transmitter is perma-
the calibration button once. The red LED nently available. However, during calibration the
will turn ON. After ten seconds the red LED signal is based on the default calibration values,
will turn OFF again, indicating that the posi-

0178-445 - ENG 135/222


Rev. 03.09
UNISAB II 2.03
8. Calibration

so it will not show 0% at minimum capacity nor %), select


100% at maximum capacity! CAP 100ADJ = 1.7 %.
Note that it is possible to return to the default cal-
ibration values by keeping the CAL Switch Factory setting
pressed for twenty seconds. However, it is the During configuration it is possible to bring
transmitter manufacturer's default values, which UNISAB II back to its factory settings.
are reset. These values may differ very much from
If a factory reset is carried out, the following
the correct values for the compressor in question.
points will be affected:
Reset is indicated by the red and green LED flash-
ing briefly a couple of times. - Alarm and warning limits

Software adjustment - Timer setup


When the capacity position transmitter has been - Regulator settings
adjusted (see section Transmitter adjustment), - State of control
the capacity must be further adjusted. It is recom-
mended to introduce a calculation offset of 2% to The factory settings appear from the tables in sec-
ensure that the slide does not collide with the end tions Alarms and Warnings, Timers as well as
stops. Collisions will reduce slide motor service Compressor regulation.
life, etc. Before carring out factory reset, STOP the com-
Select SETUP I CALIBRATE I CAPACITY pressor.
Select CONFIG I FACTORY RESET and
change from NO to YES.
CAPACITY XXX.X %
CAP. ZERO AD XX.X % Now press H and UNISAB II will display the fol-
CAP 100 ADJ XX.X % lowing:

Decrease capacity to its minimum. Change CAP.


ZERO AD so that a value of -2.0% is displayed for CONFIGURATION CHANGED
RESTARTS!
CAPACITY.
PLEASE WAIT
If capacity is eg 0.3 %
(when CAP. ZERO AD = 0.0%), Within a few seconds the operation will be com-
select CAP. ZERO AD = - 2.3%. pleted and UNISAB II can be adjusted to the actu-
Increase capacity to its maximum. Change CAP al operating conditions.
100 ADJ so that a value of 102.0 % is displayed REMEMBER to fill in the forms for actual settings.
for CAPACITY.
These forms are included in the Starting-up Man-
If capacity is eg 100.3% (when CAP 100ADJ = 0.0
ual.

136/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

9. Trouble shooting
3 SOFTWARE VERSION
4 DIGITAL INPUTS
If irregularities occur in connection with the run-
5 DIGITAL OUTPUTS
ning of the compressor, it is possible to inspect
6 ANALOG INPUTS
UNISAB II to determine the cause of these irregu-
7 ANALOG OUTPUTS
larities. 8 NO OF ALARMS

Please note that even though the voltage to 9 SUPERUSER PASSWORD

UNISAB II is disconnected, there may still be live 10 SERIAL NUMBER


11 EXAMINE MEMORY
wires containing unknown voltage.
12 NEW PASSWORD
Before beginning the trouble-shooting, disconnect 13 POWER ON
the main supply to the compressor motor to pre- 14 ZERO CAPACITY POS.
vent it from starting inadvertently. 15 COP
16 PROFICOM
There are light diodes on the printed circuit board.
17 ROTATUNE PISTON
These diodes make it possible to state the condi-
tion of the in- and outputs. It is also possible to en-
ter different menu pictures and have various
1) Diagnosis I Insp. old alarms
0178_434_en_2.02.fm

states displayed. With the cursor in this field and a pressure on I a


picture with the most recent alarm will appear.
Finally, UNISAB II includes a function, which in
case of an alarm will store the operating situation Example:
including time and date. This makes it possible
subsequently to inspect this information on the ALARM 940715-0740
display, which is particularly useful when search- HIGH DISCHARGE PRESSURE
ing for the cause of a compressor shutdown.
The picture shows that on 15 July 1994 at 07:40
In this way UNISAB II can store up to 30 alarm sit-
hrs an alarm was activated due to high discharge
uations where the most recent alarm will replace
pressure.
the oldest one.
To inspect old alarms, press K and the previous
An interruption of the voltage to UNISAB II will not
alarm will appear.
cause any loss of information. Thus, the informa-
tion can be displayed again once the supply volt- When the alarm of interest is displayed, press I
age has been restored. and the following picture will appear:

Diagnosis pictures 1 CTRL STATE


2 MEASURE VALUES
If the menu DIAGNOSIS is selected, the following
3 IMPUT STATE
picture will appear:
4 OUTPUT STATE

DIAGNOSIS Under this menu every piece of operating informa-


1 INSPECT OLD ALARMS tion which existed at the moment of the alarm is
2 MISC. FUNCTIONS stored.

0178-445 - ENG 137/222


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

In the alarm situation HIGH DISCHARGE PRES- EXT.INPUT 0.0 %


SURE, do as follows to inspect the situations 1-4. MOTOR CURR 113A

With the cursor on CTRL STATE and I the fol- This picture shows all the measuring values con-
lowing picture will appear: nected to the above alarm. Note that not all values
are relevant for all compressor types.
CONTROL MANUAL If a different alarm situation is selected, a similar
DISCHARGE LIM set of measuring values will appear.
START NO 1
Use H to get back to the menu, select INPUT
SYSTEM NO 1
STATE and press I , and the following picture will
The compressor has been in MANUAL mode and appear:
has been limited due to high pressure. Further-
more, it has been programmed to START NO 1 D.INPUT 1 1
and SYSTEM NO 1. D.INPUT 2 1

Use H to go back to the menu, select MEASURE D.INPUT 3 1


D.INPUT 4 1
VALUES and press I ,and the following picture
D.INPUT 5 0
will appear:
D.INPUT 6 0
D.INPUT 7 0
SUCT.TEMP 20.3°C D.INPUT 8 0
SUCT.PRESS -10.4°C/R D.INPUT 9 1
SUCT. SUPERH 30.7°C D.INPUT 10 0
DISCH.TEMP 68.7°C D.INPUT 11 0
DISCH.PRESS 44.7°C/R
DISCH.SUPERH 24.0°C Here the state of all digital inputs connected to the
BRINE TEMP 22.1°C selected alarm can be read.
OIL TEMP 39.1°C
0 = The input has been open
OIL PRESS 3.9 BAR
1 = The input has been closed.
DIFF.PRESS 0.0 BAR
INTERM.TEMP 22.1°C Use H to go back to the menu, select OUTPUT
INTERM.PRESS 0.0 BAR STATE and press I , and the following picture will
VI POSITION 62.0 % appear:
CAP POSITION 29.8 %

138/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

14 ZERO CAPACITY POS.

D.OUTPUT 1 0 15 COP

D.OUTPUT 2 0 16 PROFICOM

D.OUTPUT 3 0 17 ROTATUNE PISTON

D.OUTPUT 4 0
D.OUTPUT 5 0 2) Diagnosis I Misc. functions
D.OUTPUT 6 0
This picture includes four items:
D.OUTPUT 7 0
D.OUTPUT 8 0
D.OUTPUT 9 0 SUCT. RAMP L X.X°C/R
D.OUTPUT 10 0 SUCT. SUPERH XX.X°C
D.OUTPUT 11 0 CAPACITY XXX.X SEC
D.OUTPUT 12 1 BRAKE DLY X.X SEC
D.OUTPUT 13 1
D.OUTPUT 14 0 The first item SUCT. RAMP L. shows the state of
D.OUTPUT 15 1 the suction ramp function. See section Limiting
D.OUTPUT 16 1
functions, Suction ramp.
D.OUTPUT 17 0
D.OUTPUT 18 0 The value shows the actual suction pressure limit,
0178_434_en_2.02.fm

which will be equal to the suction pressure set


Here the state of all digital outputs connected to point if the suction ramp is not active. When the
the selected alarm can be read. suction ramp is active, the value will decrease by
0 = The output has been open 1°C every N seconds, where N is the selected val-
1 = The output has been activated. ue of the SUCT. RAMP timer.

Tables 11 and 12 below show the numbering of The second item SUCT. SUPERH is the same as
in-/outputs on screw and reciprocating compres- the suction superheat set point 2, which is used by
sors respectively. the High Discharge Pipe Temperature Limiter.
See section Limiting functions, Special limiters.
Return to the previous menu by pressing H :
The third and the fourth items are explained in
section Compressor regulation, Electrical slide
DIAGNOSIS
control.
1 INSPECT OLD ALARMS
2 MISC. FUNCTIONS
3 SOFTWARE VERSION 3) Diagnosis I Software version
4 DIGITAL INPUTS Here it can be checked which program version is
5 DIGITAL OUTPUTS running in UNISAB II:
6 ANALOG INPUTS
7 ANALOG OUTPUTS Example:
8 NO OF ALARMS
9 SUPERUSER PASSWORD
UNISAB II
10 SERIAL NUMBER
2.00
11 EXAMINE MEMORY
YORK Refrigeration
12 NEW PASSWORD
000119 13 : 46
13 POWER ON

0178-445 - ENG 139/222


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

4) Diagnosis I Digital inputs 6) Diagnosis I Analog inputs


In this picture it is always possible to check the ac- (Pressures, Temperatures, Current)
tual state of the digital inputs both at compressor In this picture it is always possible to check the ac-
standstill and during operation. tual state of the analog inputs both at compressor
The inputs are numbered from 1 to 11 and their standstill and during operation.
particular status is displayed. The picture looks as follows:
0 = Input open
1 = Input closed PRESS INP 1 XXXX
PRESS INP 2 XXXX
Table 11 below shows the numbering of the in-
PRESS INP 3 XXXX
puts. PRESS INP 4 XXXX
PT 100 INP 1 XXXX
5) Diagnosis I Digital outputs PT 100 INP 2 XXXX
PT 100 INP 3 XXXX
In this picture it is always possible to check the ac-
PT 100 INP 4 XXXX
tual state of the digital outputs both at compressor
CURR. XXXX
standstill and during operation. EXT. XXXX

0 = Output open CAP. XXXX


VI. XXXX
1 = Output closed
Table 11 below shows the numbering of the out- It is 12 bit A/D-converted raw values of the input
puts. signal which are displayed.
The displayed raw values are interpreted in the
following way (see tables below):
Pressure
Reading 7 752 7310 8191
Input from pres.transmit. (VDC) 0 0.5 4.5 5.0

Pt100
Reading -2000 -700 +1850 +2000
Temperature (°C) -200 -70 +185 +200

Ext, Cap, Vi
Reading 7 1606 4818 8030
Input (mA) 0 4 12 20

Curr.
Reading 7 5910
Input (Amp AC) 0 1.0

Table 12 shows the numbering of the analog in- puts.

140/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

7) Diagnosis I Analog outputs 9) Diagnosis I Superuser keyword


In this picture any application of the superuser
ANALOG OUTPUTS 0.0% password including date and hour is registered.
TEST MODE NO Use K and J to inspect the list.
TEST VALUE 0.0%

10) Diagnosis I Serial number


In this menu picture it is possible to see which an-
alog output value (in percentage) UNISAB II is In this picture it is possible to read some of the in-
transmitting to the equipment to which it is con- formation related to the EEPROM
nected. The signal is a 4-20 mA signal and is usu-
ally used for regulating the speed of a frequency SERIAL NO 123456
converter. When using analog regulation of the COMMISIONED 950101
frequency converter, it is possible at the same ERASE EEPROM NO
time to regulate the capacity and Vi slides digitally.
This requires that UNISAB II be fitted with an add- The compressor serial no can be read.
on printed circuit board (UNICOM IF) between re- The date of compressor start-up (date of initial
lay print and CPU print. The add-on board is addi- start-up) can be read.
0178_434_en_2.02.fm

tional equipment. See section Configuration for By using a special password it is possible to erase
detailed information on the use of this board. the EEPROM.
As long as the above menu picture is shown in the
display, it is possible to select test mode = YES 11) Diagnosis I Examine memory
and enter a test value between 0 and 100%.
This picture is used for software debugging. A
UNISAB II will thus transmit an mA signal corre-
section of 8 bytes from the RAM store is shown on
sponding to the test value.
the display. The starting address of this section,
Note: Do not let the compressor motor run when which is the figure shown at the top to the left, can
using test mode as the motor revolutions will fol- be changed by means of H I and K J .
low the changes in the signal. However, test mode
can be used to check whether the frequency con-
0000 00 00 70 3A
verter receives the signal correctly by reading the
0004 00 00 00 00
analog input signal in the menu system of the con-
verter.
12) Diagnosis J New password
8) Diagnosis I No of alarms In this picture it is possible to change the pass-
The total number of alarms in the working life of word. See section Operating the UNISAB II con-
the control system is shown here. trol.

Use K and J to inspect the list.

0178-445 - ENG 141/222


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

13) Diagnosis I Power on


In this picture it can be checked how many times COP XX.X
COP CARNOT X.XX
the power supply for UNISAB II has be reconnect-
COP MECH. X.XX
ed. This menu is used for trouble shooting.
COOLING OUTPUT XXXX KW
MASS FLOW XXXX kg/h

POWER ON SHAFT POWER XXXX KW


ABSORBED POWER XXXX KW
020606 22:53:31
MOT. EFFICIENCY XX.X %
+00000011 VOL. FLOW XXXX m3/h
OVH.SPC.VOL XXXX l/kg
SAT.SPC.VOL XXXX l/kg
14) Diagnosis I Zero capacity pos.
ENTALPI H1 XXXX kj/kg
The current calculated value of the zero point as ENTALPI H4 XXXX kj/kg
well as any manual setting value of the zero point ENTALPI H2 XXXX kj/kg
can be read in this picture: LIQUID TEMP XX.X °C

A more comprehensive description of the COP


CALCULATED ZERO 22% function and the setting of this can be found in the
MANUAL ZERO 0.0% manual UNISAB II-COP.
CAP.POSITION 66.5%
16) Diagnosis I PROFICOM
CAPACITY 100.0%
Only for internal use within YORK Refrigera-
(current reading 0-40%) tion, Marine Group.
(manual adjustment 0-40%)
In this menu picture it can be checked how
(immediate slide position, 4-20 mA)
UNISAB II communicates with other equipment
(corrected capacity - as read)
using PROFIBUS communication. The use of
PROFIBUS communication in UNISAB II has not
15) Diagnosis I COP yet been completed. At the moment PROFIBUS
UNISAB II can be set to measure the compressor can therefore only be used for communication
COP values (Coefficient Of Performance) as well with Mitsubishi PLCs of the type FX2N.
as the mechanical efficiency and the Carnot effi-
ciency.
INIT MESS 0
The calculated COP values and a number of inter- I/0 LENGTH ERR 0
mediate calculations are shown in this picture: MODE 0
NEXT 0

17) Diagnosis I Rotatune piston


Only for internal use.

142/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

Table 11 - Numbering of digital inputs 12. Alarm


and outputs 13. Warning
Screw compressors 14. Aux. output (Compressor ready to start at
INPUTS: remote control, limit switch for capacity).
1. Compressor motor starter feedback 15. Starting request (PMS)
2. External starting permission - normal stop- 16. Compressor motor starting signal
ping procedure
17. Prelubrication pump starting signal
3. External starting permission - stop immedi-
18. Full flow pump (cooling fan) starting signal
ately
Reciprocating compressors
4. Starting request OK (PMS)
INPUTS:
5. Regulator set point no 1 /set point no 2
1. Compressor motor starter feedback
6. Motor current limit value no 1/limit value no
2 2. External starting permission - normal stop-
ping procedure
7. Oil pump motor starter feedback
3. External starting permission - stop immedi-
8. Full flow pump (cooling fan) motor starter
0178_434_en_2.02.fm

ately
feedback
4. Starting request OK(PMS)
9. Oil float switch
5. Regulator set point no 1 /set point no 2
10. Capacity down blocked
6. Motor current limit value no 1/limit value no
11. Thermistors in motor windings 2
OUTPUTS: 7. Thermostat for oil return control. Intermedi-
1. Capacity down ate pressure oil separator.
2. Capacity up 8. Thermostat for oil return control. High pres-
3. Volume down sure oil separator

4. Volume up 9. Not used

5. Economizer - suction line 10. Capacity down blocked

6. Economizer - liquid line 11. Thermistors in motor windings

7. Oil cooling system (HLI/BLI cooling) OUTPUTS:

8. Oil cooling system (not used in HLI/BLI cool- 1. Capacity stage no 1


ing) 2. Capacity stage no 2
9. Oil distribution pipe 3. Capacity stage no 3
10. Oil rectifier (Only MKD configuration; other- 4. Capacity stage no 4
wise not used) 5. Capacity stage no 5
11 Heating element 6. Capacity stage no 6

0178-445 - ENG 143/222


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

7. Capacity stage no 7 / intermediate pressure 13. Warning


injection 14. Aux. output, (Compressor ready to start at
8. Oil cooling / thermo pump / thermo pump remote control, limit switch for capacity).
solenoid valve for ventilation 15. Starting request (PMS)
9. Oil return 16. Compressor motor starting signal
10. Water cooling 17. Oil rectifier
11. Heating element 18. Not used
12. Alarm

144/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

Table 12 - Numbering of analog inputs 4. Interm.press.Not used


Screw compressors TSMC,TCMO
Pressures: 1. Suct.press.-1/+9 bar r
1. Suction pressure-1/+9 bar r 2. Disch.press. -1/+25 bar r
2. Discharge pressure-1/+25 bar r 3. Oil press. -1/+25 bar r
3. Oil pressure-1/+25 bar r 4. Interm.press.-1/+25 bar r
4. Oil pressure before filter-1/+25 bar r HPC, HPO
Temperatures: 1. Suct.press.-1/+25 bar r
1. Suction temperature 2. Disch.press. -1/+59 bar r
2. Discharge temperature 3. Oil press. -1/+25 bar r
3. Oil temperature 4. Interm.press.Not used
4. Brine or water temperature
Current inputs: Temperatures:
0178_434_en_2.02.fm

1. Capacity slide position4-20 mA 1. Suction temperature

2. Volume slide position/ 2. Discharge temperature


outside temp.4-20 mA 3. Oil temperature
3. Motor current0-1 A AC 4. Brine or water temperature (Intermedi-
4. External set point / ate temp. on TSMC, TCMO)
ext. measuring signal4-20 mA
Reciprocating compressors Current inputs:
Pressures: 1. Not used
SMC, CMO 2. Outside temperature4-20 mA
1. Suct.press.-/+9 bar r 3. Motor current0-1 A AC
2. Disch.press. -1/+25 bar r 4. External set point /
3. Oil press. -1/+25 bar r ext. measuring signal4-20mA

0178-445 - ENG 145/222


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

Printed circuit board, light diodes Light in diode = output activated.


When opening the UNISAB II door, a number of COMMUNICATION DL12 (red), DL14 (yellow),
light diodes can be inspected on the printed circuit DL13 (green)
boards. In case UNISAB II communicates with other units,
The following signals have light diodes: the flashing of the diodes must be irregular.
DIGITAL INPUTS (Green,12 pcs) The red diode indicates that UNISAB II is trans-
DIGITAL OUTPUTS (Red, 18 pcs) mitting information whereas the green diode indi-
cates that information is being received.
COMMUNICATION (one red, one yellow, one
green) SUPPLY, RST1 (red)

SUPPLY (One red) This diode will flash briefly while voltage is con-
nected to UNISAB II. During normal operation the
CPU PRINT (One green, one red) light is off.
Positioning and identification of these light diodes In case the diode flashes repeatedly when voltage
can be seen from the following drawing. is connected, there may be an error in the voltage
DIGITAL INPUTS, DI1 to DI12 (Green) supply.
The light diodes are marked from DI1 to DI12 and CPU PRINT, ACT1 (green), RST1 (red)
the attached functions appear from the list of in- The green light diode must flash irregularly when-
puts. ever UNISAB II is electrified. A constant light or no
Light in diode = input activated. light is a sign of malfunction.
DIGITAL OUPUTS, DLR1 to DLR18 (Red) The red light diode must usually be off. It is only
The light diodes are marked from DLR1 to DLR18 on for brief moments in case the CPU tries to re-
and the attached functions appear from the list of start the program. This may only happen while
outputs. UNISAB II is switched on.

146/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

Fig. 9.1 Printed circuit board with light diodes

TERMINALS RED Communication

Transmitter EPROM
YELLOW
GREEN
Receiver

DIGITAL
OUTPUTS CPU PRINT

1) Capacity slide down


RE1 2) Capacity stage
1) Capacity slide up
RE2
2) Capacity stage 2

RE3 1) Volume slide down GREEN RED


2) Capacity stage 3
ACT1 RST1
RE4 1) Volume slide up
2) Capacity stage 4
1) Economizer suction line
RE5
2) Capacity stage 5
1) Economizer liquid line
RE6
0178_434_en_2.02.fm

2) Capacity stage 6

Battery
1) HLI/BLI cooling
RE1
RE7
2) Capacity stage 7/intermed. press. injection
1) Oil cooling
RE8
2) Oil cooling/thermo pump
DIGITAL
RE9 1) Oil distribution pipe
2) Oil return INPUTS
1) Oil rectifier DI1 Compressor operation
RE10
2) Water cooling
DI2 EXT. start, normal stop
RE11 1) Heating element
2) Heating element DI3 EXT. start, immediate stop
DI4 Starting request (PMS)
RE12 Alarm
DI5 Regulator Sp1/Sp2
RE13 Warning DI6 Motor currentSp1/Sp2
1) Oil pump operation
RE14 DI7
AUX. output 2) Oil return interm.press
DI8 1) Full flow pump operation
RE15 2) Oil return high pressure
Starting request DI9 1) Oil flow switch
2) Not used
DI10
RE16 Compressor start Capacity down blocked
DI11 Thermistor (no light function)
RE17 1) Oil pump start
2) Oil rectifier DI12 Not used

RE18 1) Full flow pump

230 VAC 115 VAC 24 VAC


RED
1) Screw compressor
K22 RST1
2) Reciprocating compressor

0178-445 - ENG 147/222


Rev. 03.09
UNISAB II 2.03
9. Trouble shooting

148/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

10. Trouble shooting diagrams


Fig. 10.1 Error diagram no 1

Start of reciprocating/screw compressor in MANUAL operating mode

MANUAL
operation

Is there light No Select picture COMPRESSOR CTRL-


in yellow C MODE and adjust to MANUAL
on front?

Yes

Check that input EXT. START IMMED. STOP termi-


0178_435_en.fm

nals 45-46 is closed. Light in green diode no. 3 on


Display No print. Can also be cheked in picture DIAGNOSIS I
=
DIGITAL INPUT no 3=1.
READY

Yes

Display
Yes =
READY

No
Recipr./screw Screw
Prelubrication
No Yes
Contact
YORK Ref.

1 2

0178-445 - ENG 149/222


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

Fig. 10.2 Error diagram no 2

Start of reciprocating/screw compressor in MANUAL mode, continued


1

Press A to start compressor.


3 Green light diode on front
flashes

Does Check emerg. stop and TÜV pres-


OK Yes No sure control, if any. There must be
compres-
sor start? connection between terminals
125-126 and 127-128.

Check that input STARTING REQUEST PMS


FEEDBACK terminals 47-48 is closed. Light Yes error mes-
in green diode no 4 on print. Can also be sage re-
checked in picture DIAGNOSIS I ceived
DIGITAL INPUT no 4 = 1.
No

Input Yes Is relay no 16


closed? Try again activated on No Contact
print when try- YORK Ref.
ing to start (red
light diode)?
No

Yes
Apply jumper, or check connec-
tions from terminals 116-117 to Check connection from terminals 118-
power management system. 119 to motor starter

Yes No Correct wiring


Connection connect.
OK?

Is there feed-
back on termi-
nals 41-42 from No Correct wiring
motor guard? connection
Green light di-
ode no 1 on
print.

Yes

Check pre-fuses and control volt-


age of motor guard.

150/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

Fig. 10.3 Error diagram no 3

Start of screw compressor/prelubrication in MANUAL mode, continued

Press A to start compressor.


Green light diode flashes on front.

Yes Oil pump


starts?

No
Error mes- No
sage in oil 3 Check that input STARTING REQUEST
system? FEEDBACK terminals 47-48 are closed.
PMS Light in green diode no. 4 on print. Can
error mes- Yes also be checked in picture DIAGNOSIS
Yes sage re- I DIGITAL INPUT no. 4=1.
ceived?
Check wiring connec-
tion to oil float. When No
0178_435_en.fm

float has been activat-


ed, green light diode no No Input Yes Try again
9 will flash on print. closed?

Apply jumper, or check con-


nections from terminals 116-
No 117 to power management
Connection Correct wiring
system.
OK? connect.

Relay no 17
Yes is activated No Check that CONFIG I
PRELUBRIFICATION = YES.
on print. Red
Check float
light diode
function

Yes

Check connection from terminals 120-


121 to pump motor starter

Connection No Correct wiring


OK? connection

Yes
Check if feedback is recieved on termi-
nals 53-54 (green light diode no 7 on
print) from pump motor guard

Check pre-fuses and control voltage of Yes No Correct wiring


Connection
pump motor guard. connect.
OK?

0178-445 - ENG 151/222


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

Fig. 10.4 Error diagram no 4

Start of reciprocating/screw compressor in AUTO mode

Prepare for AUTOMATIC opera-


tion

Select regulating form in picture


CONFIG I CONTROL ON

Set Set point, neutral zone and


P. Band for chosen regulator

Select picture CTRL MODE and


set to AUTO

With C it is possible to change


between MANUAL and AUTO by
one single pressure. Adjust to
MANUAL (= light in yellow diode)

In CONFIG check that


AUTO START = YES and
AUTO STOP = YES

Check setting of START DELAY


in picture TIMER SETUP

Check that input EXT. START IMMED. STOP


No terminals 45-46 is closed. Light in green diode
Display
no 3 on print. Can also be checked in picture
READY?
DIAGNOSIS I DIGITAL INPUT no 3=1.

Yes

Yes
Display
READY?

No

4 5

152/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

Fig. 10.5 Error diagram no 5

Start of reciprocating/screw compressor in AUTO mode, continued

4 5

Check that input EXT. START,


NORM. STOP terminals 43-44 is
closed. Light in green diode no 2
print. Can also be checked in pic-
ture DIAGNOSIS I DIGITAL IN-
PUT no 2=1.

Yes Display =
0178_435_en.fm

READY?

Press C so that light in No


diode goes out = AUTO
Contact
YORK Ref.

Compressor can now begin start-up


phase depending on setting of regu-
lator. REMEMBER that start is de-
layed by timer START DELAY.

Is cool-
ing/heat- No Change set point or wait for cool-
ing re- ing/heating requirement.
quired?

Yes

Recipr./screw Screw
Prelubrication
No Yes

7 6

0178-445 - ENG 153/222


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

Fig. 10.6 Error diagram no 6

Start of reciprocating/screw compressor in AUTO mode, continued

At compressor start-up
green light diode on front
will flash.

Check emerg. stop and TÜV pres-


sure control, if any. There must be
connection between terminals 125-
Does com- 126 and 127-128.
Yes No
OK pressor
start?

PMS
Yes error
message
received?
Check that input STARTING RE-
QUEST FEEDBACK terminals 47-48
is closed. Light in green diode no. 4 No
on print. Can also be checked in pic-
ture DIAGNOSIS I DIGITAL INPUT
no 4=1. Is relay no 16
activated on No
Contact
print when try-
YORK Ref.
ing to start (red
No Input Yes light diode)
closed? Try again

Yes
Apply jumper, or check con-
nections from terminals
116-117 to power manage- Check connection from terminals
ment system. 118-119 to motor starter

Yes No Correct wiring con-


Connection
OK? nection

Is there feedback
on terminals 41-42 No Correct wiring con-
from motor guard? nection
Green light diode
no 1 on print.

Yes

Check pre-fuses and control


fuses of motor guard.

154/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

Fig. 10.7 Error diagram no 7

Start of screw compressor/prelubrication in AUTO mode, continued

At compressor start green light


diode on front will flash.

Check that input STARTING REQUEST


FEEDBACK terminals 47-48 are closed.
Oil pump Light in green diode no. 4 on print. Can
Yes also be checked in picture DIAGNOSIS
starts?
I DIGITAL INPUT no. 4=1.

Error mes- No
No
sage in oil
system? No Input Yes
PMS Try again
Yes closed
7 error mes-
Yes sage
0178_435_en.fm

received?
Apply jumper, or check connec-
tions from terminal 116-117 to
Check wiring connec- power management system.
tion to oil float. When No
float has been activat-
ed, green light diode
no 9 will flash on print. Relay no
17 is acti- No Check that CONFIG I
vated on PRELUBRICATION = YES
print. Red
light diode.

Yes
Connec- No Correct
tion OK? wiring connect. Check connection from terminals 120-121 to
the pump motor starter.

Yes

Check float function No Correct wiring


Connection
connection
OK?

Yes

Check if feedback is received on terminals 53-54 on


green light diode no 7 on print from motor guard.

Check pre-fuses and control fuses of Yes Connection No Correct wiring


motor guard. connection
OK?

0178-445 - ENG 155/222


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

Fig. 10.8 Error diagram no 8

General trouble shooting, UNISAB II

No light/text in display

Is diode on
No Is there light in Yes
CPU print
ACT1 flashing
any diodes on 8
relay card
green

Yes No

Check connection to Check supply on termi-


display. If necessary, nals L and N
pull out white plug and
refit.

Is
voltage No
correct?
9
Contact No Display
YORK Ref. Yes
OK?
Check that white code
Yes plug has been fitted.

Problem
solved

= 230 VAC

= 115 VAC
Display reads COPY
EEROM after power =24 VAC
cut

Probably defective bat- Is


tery Yes
plug
correct?
10

No

Replace battery. See Fit correct plug


section, Service, Bat-
tery

156/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

Fig. 10.9 Error diagram no 9

CPU print may have to be re-


8 placed

Check voltage supply of any


9 loose connections, burnt fuses
or the like

Check voltage on terminals 141-


10 142 = 24 VAC

Transformer thermally
Is this
activated. May have to
OK
be replaced.

Check fuse in black re-


tainer.
0178_435_en.fm

Is this Replace fuse.


OK? Max 3 Amp.

Are terminals
29-32-37 short- Correct error
circuited to
frame?

Are terminals
29-30-33 or 37- Correct error
38 short-
circuited?

Are there any er-


rors in external Correct error or replace
components to component
term. 29-30; 32-
33; 37-38

Contact
YORK Ref.

0178-445 - ENG 157/222


Rev. 03.09
UNISAB II 2.03
10. Trouble shooting diagrams

158/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
11. Service

11. Service
In case some of the main parts of UNISAB II are a. Door in which display and keyboard are fit-
defective, it is possible to replace them. ted.
It is recommended to contact b. Relay print with wiring connections.
YORK Refrigeration before changing any of these c. CPU print fitted on relay print.
parts.
d. Transformer.
The main parts comprise:
The parts are shown below (see Fig. 11.1).
Fig. 11.1

Keyboard connection Display connection


EEPROM

PAL Battery
U17 EPROM U17 Cooling
plate Trans-
U18 EPROM U18 former
CPU print Fuse
Digital inputs
0178_436_en_2.02.fm

Empty socket!
NEVER use this
socket together
with sockets pos.
Digital outputs
U17and U18

Terminals

All replacements must be carried out with Replacement of CPU print


UNISAB II in a state of no voltage. Remember that Dismantle the door completely to provide free ac-
outside control voltage may be connected. cess to the printed circuit board.
Disconnect the main supply to the motor to avoid Remove the screws with which the print is se-
risk of indadvertent start-up. cured. Get hold of the bottom of the print and pull
it out carefully. It may be fixed rather firmly as it is
Replacement of door positioned in two plugs with connection to the re-
Remove the blue and white plugs leading to the lay print. It is important to pull at the side of the
relay print (the two securing lugs must be bent a print in which the plugs are positioned to avoid
little backwards). Remove the two fuse straps as pulling it out askew, thus damaging the print.
well as the earth connections. Move both EPROMS and EEPROM from the old
Mount the new door in reverse order as opposed CPU print to the new one.
to the dismounting process. Important!
Connect supply voltage. See also Replacement of EPROMS.

0178-445 - ENG 159/222


Rev. 03.09
UNISAB II 2.03
11. Service

Mount a new CPU print and door in reverse order


as opposed to the dismounting process. SERIAL NO 0

When the above has been completed and the


control is switched on, the following picture will ap-
Enter the compressor serial no and press the H
pear shortly in the display:
key. All three light diodes on the front will flash
shortly, and the display will show the picture CON-
COPY EEPROM YES FIG.
It is also necessary to enter the original setup, all
Press the H key. UNISAB II will now be reconfig- alarm and warning limits as well as set points,
ured and the contents of the EEPROM, corre- which must be different from the factory setting.
sponding to the compressor setup, will now be Remember also to calibrate the pressure trans-
copied into the CPU storeage. ducers.

Important! It is possible to answer NO by means These values are included in the Starting-up Man-
of the password. In this case the contents of the ual. Remember to set time and date. The lan-
EEPROM and RAM store will be deleted, and guage is now English. Select another language if
UNISAB II must be reconfigured. See description this is required.
under Replacement of CPU print and EEPROM.
The setting is now the same as before the CPU
Replacement of relay print
print was changed except for the calibration of Dismantle the door completely to provide free ac-
the pressure transducers, possibly the brine tem- cess to the printed circuit board.
perature as well as the hour counter, which is now All connected wires on the relay print must be dis-
zero. The language is now English. Select anoth- mounted, but first they must be marked so that
er language if this is required. Enter the values correct remounting is possible.
from the table in the Starting-up Manual, which is
Remove the screws that hold the print and tilt the
supplied with the compressor. Remember to set
print out of the plastic holders at the terminal row
time and date.
on the long side of the print.
Pull the print off the guide opposite the terminal
Replacement of CPU print and
row and out of the cabinet.
EEPROM
If - as an exception - it proves necessary to insert Move the CPU print with the EPROM and Serial
a new EEPROM in connection with the replace- EPROM onto the new relay print.
ment of a CPU print, the following procedure must Mount the new relay print in reverse order as op-
be observed. posed to the dismounting procedure and connect
Important! the marked wires in the correct order.
See also Replacement of EPROM. When the above has been completed and the
Mount the new parts and switch on the control. control is switched on, the following picture will ap-
The following picture will appears in the display: pear shortly in the display:

160/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
11. Service

labels. If replacement is necessary, always re-


COPY EEPROM YES place both EPROMs as they belong together.

EPROM and electronics in general can be


Press the H key. UNISAB II will now be reconfig-
damaged by static electricity. Therefore, make
ured and the contents of the EEPROM, corre-
sure that static electricity is discharged without
sponding to the compressor setup, will now be
current passing through the electronics, ie
copied into the CPU storeage.
touch the part on which the EPROM is posi-
Important! It is possible to answer NO by means tioned both before and while picking up the
of the password. In this case the contents of the EPROM. Touch also the box of the device in
EEPROM and RAM store will be deleted, and which EPROM is to be positioned both before
UNISAB II must be reconfigured. See description and while fitting the EPROM. It is of course
under Replacement of CPU print and EEPROM. necessary to use the same hand that holds (or
The settting is now the same as before the CPU is going to hold) the EPROM.
print was changed except for the calibration of
the pressure transducers, possibly the brine tem-
When replacing the EPROM or moving it from one
perature as well as the hour counter, which is now
UNISAB II unit to another, do as follows:
0178_436_en_2.02.fm

zero. The language is now English. Select anoth-


er language if this is required. Enter the values • Note the value of the hour counter as well as
from the table in the Starting-up Manual, which is the calibration values for pressure transduc-
supplied with the compressor. Remember to set ers and brine temperature.
time and date. • Switch off the power supply to UNISAB II.
• Switch off the compressor motor starter and
Replacement of EPROM (program) observe all safety measures in accordance
UNISAB II with the instruction manual, local rules and
The EPROMs are programmable modules, regulations.
mounted in sockets in the microelectronic part of • Place the door in service position as de-
UNISAB II. Please note that there are two scribed in Operating UNISAB II
EPROMs, numbered 0 and 1, identified by white
• The EPROM modules are positioned in the
center of the printed circuit board (see
Fig. 11.1).
• Each EPROM module is loosened from its
socket by an authorized EPROM puller.
Take care not to damage the pins on the
EPROM module.

0178-445 - ENG 161/222


Rev. 03.09
UNISAB II 2.03
11. Service

Fig. 11.2 ues from the table in the Starting-up Manual,


which is supplied with the compressor. Remem-
ber to set time and date.
Notch When changing the EPROM in connection with an
upgrade to an updated program version, it is rec-
ommended to carry out a FACTORY RESET.
EPROM
Before a FACTORY RESET is carried out, write
Mount the EPROMs manually while paying atten-
down all the UNISAB II settings in the table
tion to the following:
UNISAB II settings, especially the parameters
• Make sure to position the EPROM labeled 0 which are changed back to factory setting by a
in the upper socket, and the EPROM la- factory reset. This applies to the following param-
beled 1 in the lower socket. eters:
• Position the EPROM so that the notch in the – Alarm and warning limits, set points,
module is turning right (see Fig. 11.2). PID parameters
• Take care that all pins are fitted in the socket – Timers, P band factors
and carry out the mounting with great care.
– Capacity limits
• Refit the door.
See the table UNISAB II settings for a complete
When the above has been completed and the review.
control is switched on, the following picture will ap-
See section Operating UNISAB II control, Factory
pear shortly in the display:
settings for information on factory reset.
Once FACTORY RESET has been completed,
COPY EEPROM YES
enter all the settings which are included in the ta-
ble UNISAB II settings, and which differ from the
UNISAB II factory values.
Press the H key. UNISAB II will now be reconfig-
ured and the contents of the EEPROM, corre-
sponding to the compressor setup, will now be Replacement of serial EEPROM
copied into the CPU storeage. (diagnosis)
Important! It is possible to answer NO by means This EEPROM includes information on:
of the password. In this case the contents of the e. Compressor serial no.
EEPROM and RAM store will be deleted, and
f. Date of initial start-up.
UNISAB II must be reconfigured. See description
under Replacement of CPU print and EEPROM. g. Compressor configuration.

The settting is now the same as before the h. Total number of alarm and warning limits and
EPROM was changed except for the calibration all other setting values.
of the pressure transducers, possibly the brine i. Status of up to 30 old alarms.
temperature as well as the hour counter, which is
j. Total number of alarms.
now zero. The language is now English. Select
another language if this is required. Enter the val-

162/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
11. Service

The EEPROM (positioned in a socket) can be re- If the following picture appears in the display after
moved from UNISAB II in compliance with the a power failure, the battery should be replaced:
same precautions as described under Replace-
ment of EPROM.
COPY EEPROM YES
The EEPROM must usually remain in the control
as the control cannot function without the EEP-
ROM. However, in case the contents of the EEP- If a new battery is available, switch off the control
ROM is to be examined by YORK Refrigeration, and change the battery. Dispose of the old battery
Denmark, it can be removed for inspection. When in conformity with the environmental rules and
removing the EEPROM, switch off the control and regulations in force.
have an empty EEPROM ready for insertion. Mount a new battery and switch on the control,
Once the new EEPROM has been fitted, switch on and the above picture will appear once more. An-
the control again. All information will now be cop- swer YES and press the H key.
ied into the new EEPROM. The compressor setup is now the same as before
The control is now ready for operation with the the power failure except for the calibration values
same setup as before the EEPROM was re- for the pressure transducers and the brine tem-
moved. perature as well as the hour counter, which is now
0178_436_en_2.02.fm

zero. These values are included in the compres-


sor Starting-up Manual.
Replacement of battery
Remember to set time and date as well as lan-
The battery is used primarily to ensure that the in-
guage. The compressor is now operational.
ternal clock runs accurately after a power failure.
Moreover, the so-called RAM store is supplied In case no new battery is available, answer YES
during power failures. to the above picture and follow the procedure for
replacement of the EEPROM.
The battery has an expected service life of 10
years and is of the Lithium type. It is not reloaded
by the UNISAB II electronic circuit. Please note that at the next power
failure, the problem will be the same.

0178-445 - ENG 163/222


Rev. 03.09
UNISAB II 2.03
11. Service

Installation of data communication These instructions only apply to the installation of


cable UNISAB II. For information on connection of
To obtain a correct function of the data communi- PROSAB II/ UNISAB II, see instr.no 0171-745 un-
cation between several YORK Refrigeration com- der Supplementary material.
puters, the communication cable must be con-
nected according to the following instructions.
Fig. 11.3

UNISAB II/UNISAB II

IN CASE OF COMMUNICATION CONNECTIONS BETWEEN UNISAB II,


RESISTANCE JUMPERS MUST BE CONNECTED IN EACH MODULE

UNISAB II UNISAB II UNISAB II


- TX DL12 - TX DL12 - TX DL12
- RX DL13 - RX DL13 - RX DL13
63 64 65 66 63 64 65 66 63 64 65 66

termination block termination block

LED COLOURS
TX DL12 = RED
RX DL13 = GREEN

UNISAB II/PROSAB II

IN CASE OF CONNECTION BETWEEN MORE THAN TWO COMMUNICATION


MODULES, JUMPER(S) MUST BE CONNECTED IN BOTH END MODULES

PROSAB II PROSAB II
UNISAB II UNISAB-S/R/RT/RTH UNISAB-S/R/RT/RTH
- TX DL12 S1 S1 S1
COMMUNICATION COMMUNICATION
- RX DL13 MODULE MODULE
S2 S2 S2
63 64 65 66 + - + - + - + -

termination block

LED COLOURS
TX DL12 = RED
RX DL13 = GREEN

164/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
11. Service

Important! Fig. 11.4


The screen of the communication cable MUST be
connected correctly in the supplied screwed joints
(see Fig. 11.4). 1.
The cable is connected in the terminals shown in
Fig. 11.3. The cable must be pulled in parallel 2.
from control to control. This applies both to the two
conductors and the screen.
In the first and last control the cable must be fin-
ished correctly. The resistance of 120 ohm must 3.
be fitted as indicated (mounted on delivery). On all
other controls the resistance is removed and the
UNISAB II
terminals are used for passing on the communica-
tion cable. 4.
The total length of the cable between the controls
must not exceed 1,000 m. Cables of this type are
available from YORK Refrigeration.
0178_436_en_2.02.fm

UNISAB II

The cable must have the following 5.


data:
2-conductor data cable with screening
Pair capacity 85 pF/m
Fig. 11.4 shows the connection of the cable
screen in screwed joint.

0178-445 - ENG 165/222


Rev. 03.09
UNISAB II 2.03
11. Service

Grounding cause a large current surge through the cable


UNISAB II must always be grounded to the com- screen. The screen may melt, causing the voltage
pressor frame. See drawing no. 2347-002 page equalisation to be broken and the communication
AC038_13 under Supplementary material. to be hampered by noise.

In case of a shut down, there can be large electri- To avoid this situation, it is strongly recommended
cal potential on the compressor motor and thereby to provide an extra equalising wire in parallel with
on UNISAB II. the communication cable between all the units on
the network, as indicated in the drawing no.
The data communication cable screen provides a 2347-002 page AC040_10 under Supplementary
voltage equalisation between the UNISAB II units. material.
The above mentioned electrical potential may

166/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
12. MULTISAB regulation

12. MULTISAB regulation

Introduction MULTISAB is a distributed software module in-


MULTISAB is a distributed compressor control cluded in all UNISAB II, PROSAB II and
system, which can capacity regulate reciprocating UNISAB II units on delivery.
and/or screw compressors according to rules, MULTISAB connects up to 14 compressors in one
which are set up in detail as described in the fol- and the same communication system.
lowing, and in a sequence set by the user.
Fig. 12.1

1 2 3 14

UNISAB II UNISAB II UNISAB II UNISAB II

The MULTISAB system is based on some basic the optimization of the compressors, it may be
rules: necessary to regulate the compressors externally.
The plant itself may also make special demands
0178_437_en.fm

1. The system is controlled and optimized ac-


cording to suction pressure, brine tempera- as to regulating speed and accuracy, which
ture, discharge pressure or external 4-20 makes a central external regulation necessary.
mA signal, depending on the chosen type of Such an alternative regulation can be carried out
regulation. in several ways:
2. The programmed starting sequence is al- • controlling the digital input External start
ways followed. permission, normal stop
3. Screw compressors in operation are run to • using the digital output Auxiliary output
as high a capacity as possible. • using the 4-20 mA input Auxiliary input
4. It is acceptable that reciprocating compres- • changing capacity set points from PC/PLC
sors operate at part load. via COMSAB II/PCCOMSAB II.
MULTISAB is a regulating system for general ap-
plication. Should special demands be made as to

0178-445 - ENG 167/222


Rev. 03.09
UNISAB II 2.03
12. MULTISAB regulation

Fig. 12.2

PC/PLC

possible modem

COMSAB II/PCCOMSAB II

1 2 3 14

UNISAB II UNISAB II UNISAB II UNISAB II

In case compressor capacity is controlled through See section Installation of data communication
COMSAB II or PCCOMSAB II from a central com- cable as well as Connecting diagrams to
puter, be aware of the time delay through the com- find information on the physical linking of
munication system. UNISAB II units.
It is possible to make an approximate calculation B: All units must be configured for intercommu-
of this time delay. See COMSAB II instruction no nication. See also section Configuration.
0171-400. In SETUP I CONFIG a compressor number,
If UNISAB II is to be connected to controls of the COMPR. NO, beginning with no 1 and up-
UNISAB S/R or PROSAB II type, see the following wards, corresponding to the number of com-
instructions if the control units are part of the plant pressors must be entered in each unit.
in question: It is recommended to mark the compressors with
1) 0171-761 / UNISAB S-Control this number.
2) 0171-772 / UNISAB R-Control Important!
3) 0178-175 / UNISAB RT-Control If two compressors have the same com-
pressor number entered in UNISAB II, there
4) 0178-181 / UNISAB RTH-Control will be no communication between the units.
5) 0171-729 / PROSAB II In SETUP I CONFIG the communication speed,
6) 0171-743 / the MULTISAB system for BAUD RATE, must be entered. In case the
PROSAB/UNISAB II system only consists of UNISAB II units,
usually choose the highest baud rate. In
System setup case the system consists of both UNISAB II
and PROSAB II or UNISAB II units, choose
To be able to use MULTISAB, a number of points
1200 baud. Note that it must be checked
must be completed. Please find the checklist for
that all units on the network are able to run
MULTISAB setup (see the following pages). The
at the selected rate.
points on the checklist can be explained as fol-
lows: C: All units, especially screw compressors,
must have a swept volume value entered.
A: All units that are to be included in the system
must be connected physically.

168/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
12. MULTISAB regulation

In SETUP I CONFIG enter SWEPT VOLUME, er or disconnected from the network, the
which can be read on the compressor name UNISAB II unit with the next START.NO will
plate. See section Configuration. be SYS. REGULATOR.
D: An entry must be made in all units whether The SYS.REGULATOR is master of the co-ordi-
the system contains a common evaporator nated capacity control, which also means
and a common condenser. that the controlled input sensor (point H be-
In SETUP I CONFIG enter the current combina- low) on this particular UNISAB II unit in use.
tion of common evaporator and common If only one compressor is required, it will
condenser in COMMON EVAP/COND. See usually be the compressor of the SYS.REG-
section Configuration. ULATOR which is in operation. However, if
COMPR# is selected, it may very well be
E: All units must be have a system no and a another compressor.
starting no.
Guidelines for selecting COMPR# or START#:
In SETUP I MULTISAB I MULTISAB STATE
enter START NO and a SYSTEM NO. See • COMPR# is easier and more safe if the con-
section MULTISAB. trolled input is not available to all UNISAB II
units.
F: All units in the same system must agree on
the way a regulating master (sys. regulator) • COMPR# must be selected if there are any
0178_437_en.fm

is chosen. PROSAB II or UNISAB I units on the sys-


tem.
In SETUP I CONFIG select the same PREF.
MASTER in all UNISAB II units, COMPR# • START# is easier and more safe if equaliz-
or START#. See section Configuration. ing running hours is important, especially if
all (or all but one) compressors must always
If selecting COMPR#, the UNISAB II with the low- be available.
est COMPR. NO (point B above) will always
be SYS.REGULATOR. The only exceptions • Always make sure that COMPR.NO is a
are if the UNISAB II is off power or discon- fixed value, ie never change it to equalize
nected from the network. In such case, the running hours! However, START.NO is
UNISAB II with the next COMPR.NO will be meant to be changed from time to time.
SYS.REGULATOR. Note that a defective G: All units must be adjusted to remote control.
controlled input sensor does not lead to an In SETUP I CONTROL COMPRESSOR.CTRL
automatic change of SYS.REGULATOR in MODE is on REMOTE. See section Com-
this case. pressor regulation.
If selecting START#, the UNISAB II with the low-
est START.NO (point F above) will be Regulation Setup
SYS.REGULATOR for as long as the com-
H: All units must be configured to the desired
pressor belonging to this UNISAB II unit is
regulating method.
running and ready. If the compressor is not
available, UNISAB II is not in REMOTE In SETUP I CONFIG adjust CONTROL ON to
mode, the controlled input sensor (point H the desired regulating method. See section
below) is defective, or UNISAB II is off pow- Configuration.

0178-445 - ENG 169/222


Rev. 03.09
UNISAB II 2.03
12. MULTISAB regulation

The following four regulators are available. The 2) Regulator neutral zone, NZ
last two have both a cooling and a warming 3) Regulator proportional band, PB
function:
See section Compressor regulation.
– Suction side
(regulation of suction pressure) Regulation of the entire system will usually take
place on the basis of the regulator in the cur-
– Discharge side rent regulating master (sys. regulator), ie
(regulation of discharge pressure) the compressor with the lowest compressor
– Brine / hotwater or starting number.
(regulation of brine/water temperatures) Therefore it is particularly important that the pa-
– Ext. cooling / Ext. heating rameters of the configured regulator has
(regulation of a user defined measuring been set correctly.
value: temp./pressure/level). Always set the same set point on all other units in
– Note that all units that can become mas- the same system (ie with the same SYS-
ter must measure the same value to be TEM NO).
used for the capacity control. If eg Brine K: All units must have their timers adjusted.
/ Hotwater temperature control is select-
ed, a separate temperature sensor must In SETUP I TIMERS I TIMER SETUP the fol-
be available to all the relevant UNISAB II lowing timers are set:
units. Note that point F above describes 1) START DELAY, time delay before start.
how to select the master. 2) STOP DELAY, time delay before stop.
I: All units must (usually) be configured to both See section Timers, Timer setup.
automatic start and automatic stop. If this is
Both timers can be made to work proportionally (ie
not the case, the compressor will not start
depending on the size of Pb).
up automatically in case cooling is required
or stop automatically when cooling is not re- In SETUP I TIMERS I P BAND
quired and the temperature becomes too FACTOR a proportional factor can be set for
low. each of the timers.
In SETUP I CONFIG, choose: This means that if only a small difference exists
between the desired temperature (Sp) and
AUTO START= YES
the current one, the timer in the time delays
AUTO STOP= YES will count very slowly (up to
See section Configuration. 10 times slower than the time set, depend-
J: The chosen regulator must be set in all ing on the factor set).
units. If the difference between the desired temperature
In the picture for the parameter to be regulated, and the current one is considerable (outside
set the following: the P Band), the timer in the time delay will
count in seconds.
1) Regulator set point, SP1 and possibly SP2
See sectionTimers, P Band factor.

170/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
12. MULTISAB regulation

In case of reciprocating compressors, another two Transfer and the Take-over situations are
timers must be set. included.
3) DELAY UP, time delay during loading of As described below, several parameters are
stages. available to adjust the Transfer and the
4) DELAY DOWN, time delay during unloading Take-over function.
of stages. In SETUP ITIMERS I TRANSFER a pro-
Both of these timers can also be made to work portional factor FACTOR DOWN (1-10, de-
proportionally (ie depending on the size of fault 1) can be set for timer DELAY DOWN.
Pb). It is used when MULTISAB wants to let a re-
ciprocating compressor decrease its capac-
In SETUP I TIMERS I P BAND FACTOR a pro- ity in favour of a screw compressor at low
portional factor can be set for each of the capacity. A larger FACTOR DOWN makes
timers. MULTISAB wait longer before reducing the
L: In plants with a combination of screw and reciprocating compressor capacity another
reciprocating compressors a number of fac- stage.
tors may be set to optimize compressor op- In SETUP I TIMERS I TRANSFER the
eration so that the two types of compressors size of a transfer zone ZONE can be set, ie
are used in the best way possible. These the part of the proportional band (0-100%,
0178_437_en.fm

factors can only be set on reciprocating default 15%) where transfer may take place.
compressors and will be effective only in
case all reciprocating compressors have In SETUP I TIMERS I TAKE-OVER a
lower starting numbers than the screw com- proportional factor FACTOR UP (1-10, de-
pressors in the same system, and only if fault 1) can be set for timer DELAY UP. It is
TAKE OVER is set to YES in SETUP I used when MULTISAB wants to increase
CONFIG, See section Configuration. the capacity of the reciprocating compres-
sor to force the screw compressor down be-
The optimization is carried out by the Trans- low 5% capacity, making it stop. A larger
fer function and the Take-over function. FACTOR UP makes MULTISAB wait longer
It is not economical to run a screw compres- before increasing the reciprocating com-
sor at low capacity. The Transfer function pressor capacity another stage.
attempts to avoid this by reducing the ca-
pacity of the reciprocating compressor(s), ie In SETUP I TIMERS I TAKE-OVER a
by transferring load to the screw compres- proportional factor FACTOR START (1-10,
sor. The Take-over function increases the default 1) can be set for the START DELAY
capacity of the reciprocating compressor(s) timer. It is used when MULTISAB wants to
to make the screw compressor stop, ie by start a reciprocating compressor to take
taking over load from the screw compres- over the operation from a screw compressor
sor. which is running at low capacity.

In the section Example of regulation - a In SETUP I TIMERS I TAKE-OVER the


combination of screw and reciprocating size of a take-over zone ZONE can be set,
compressors illustrative examples of the ie the part of the proportional band (0-100%,

0178-445 - ENG 171/222


Rev. 03.09
UNISAB II 2.03
12. MULTISAB regulation

default 15%) where take-over may take tivated once TAKE-OVER DELAY
place. expires.
In SETUP I TIMERS I TIMER SETUP the 2) TAKE-OVER MAX, max duration of a
following timers are found. take-over attempt. When TAKE-OVER DE-
1) TAKE-OVER DELAY, time delay at LAY expires, the time delay TAKE-OVER
take-over, fixed at 300 seconds. When a re- MAX will also be activated to ensure that a
ciprocating compressor has calculated that reciprocating compressor will not use more
it is possible to take over a subsequent than the TAKE-OVER MAX time during a
screw compressor, it will pass into a take-over attempt. If the screw compressor
take-over mode and start TAKE-OVER DE- has not stopped before the TAKE-OVER
LAY. If the reciprocating compressor during MAX expires, the reciprocating compressor
the entire count down of take-over delay can will give up and stop. This delay function
continue to take over, thus staying in the can be cancelled by setting the delay for 0
take-over mode, START DELAY will be ac- (default).

172/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
13. Checklist

13. Checklist
Compressor No
Checklist for MULTISAB setup
No Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14
A Cabling All co-operating UNISAB
units must be wired to-
gether on common net-
work.
B.1 CONFIG→ Unique ID for each com-
COMPR NO pressor on network
B.2 CONFIG → Identical for all units on
BAUD RATE network
C CONFIG → Must be entered correctly
SWEPT for each compressor, at
VOLUME least for screws
D CONFIG→ Identical for all compres-
COMMON sors within system
EVAP/COND
E.1 MULTISAB Unique priority within sys-
STATE → tem (SYSTEM NO)
START NO
0178_438_en.fm

E.2 MULTISAB System ID, identical for all


STATE → compressors on same
SYSTEM NO controlled input
CONFIG → Identical for all compres-
REFRIGERANT sors within system
F CONFIG → Identical for all compres-
PREF. MASTER sors within system
G CONTROL → Must be REMOTE unless
COMPR. the compressor is exclud-
CONTROL ed (temporarily) from
MULTISAB
H.1 CONFIG → Identical for all compres-
CONTROL ON sors within system - see
also item C
H.2 Controlled input The measurement must
sencor be available to all com-
pressors in the system
which can become mas-
ter
I.1 CONFIG → Should usually be YES. If
AUTO START not, the compressor must
be started manually
I.2 CONFIG → Should usually be YES. If
AUTO STOP not, the compressor must
be stopped manually

0178-445 - ENG 173/222


Rev. 03.09
UNISAB II 2.03
13. Checklist

Compressor No
Checklist for MULTISAB setup
No Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14
J.1 Set point Identical for all compres-
sors within system
J.2 Neutral zone Matching values for all
and compressors within sys-
tem
P Band
K.1 TIMER SETUP Matching values for all
→ START DE- compressors within sys-
LAY tem
K.1 P BAND FAC- Matching values for all
a TOR → compressors within sys-
START DELAY tem
K.2 TIMER SETUP Matching values for all
→ STOP DE- compressors within sys-
LAY tem
K.2 P BAND FAC- Matching values for all
a TOR → compressors within sys-
STOP DELAY tem
K.3 TIMER SETUP Matching values for all re-
→ DELAY UP ciprocating compressors
within system
K.3 P BAND FAC- Matching values for all re-
a TOR → ciprocating compressors
DELAY UP within system
K.4 TIMER SETUP Matching values for all re-
→ DELAY ciprocating compressors
DOWN within system
K.4 P BAND FAC- Matching values for all re-
a TOR → ciprocating compressors
DELAY DOWN within system
L.1 CONFIG → Only recipr. compr. Set
TAKE OVER for YES if compr. is to
take over from screw
L.2 TIMER SETUP Matching values for all re-
→ TK OVER ciprocating compressors
MAX within system (TK = Take)
L.3 TRANSFER → Matching values for all re-
FACTOR ciprocating compressors
DOWN within system
L.4 TRANSFER → Matching values for all re-
ZONE ciprocating compressors
within system
L.5 TAKE-OVER → Matching values for all re-
FACTOR UP ciprocating compressors
within system

174/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
13. Checklist

Compressor No
Checklist for MULTISAB setup
No Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14
L.6 TAKE-OVER → Matching values for all re-
FACTOR ciprocating compressors
START within system
L.7 TAKE-OVER → Matching values for all re-
ZONE ciprocating compressors
within system
0178_438_en.fm

0178-445 - ENG 175/222


Rev. 03.09
UNISAB II 2.03
13. Checklist

176/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

14. Start and system numbers

- pref. master = COMPR#.


Example A - plants with one temperature system and five compressors where pref. master = COMPR#.

System no 1 1 1 1 1

Starting no 1 2 3 4 5

Compressor no K1 K2 K3 K4 K5

Example B - plants with one temperature system and five compressors where pref. master = COMPR#.

System no 1 1 1 1 1

Starting no 5 4 3 2 1

Compressor no K1 K2 K3 K4 K5

In examples A and B, K1 will be the regulator (system regulator) of the entire system.

Example C - plants with two temperature systems and five compressors (eg two-stage plants) where
pref. master = COMPR#.
0178_439_en.fm

System no 1 1 2 2 2

Starting no 2 1 3 1 2

Compressor no K1 K2 K3 K4 K5

In example C, K1 will be system regulator of system no 1, and K3 will be system regulator of system no 2.

SETUP I MULTISAB I MULTISAB STATE A compressor will not be part of the MULTISAB
shows which unit has been chosen as SYS. REG- system if it is in either MANUAL, AUTO,
ULATOR. STOPPED or SHUTDOWN, or if the digital inputs
In case of two regulating systems or more, it is the EXTERNAL START-NORMAL STOP and EX-
compressor with the lowest number in the individ- TERNAL START-IMMEDIATE STOP have not
ual system that works as system regulator. been connected.

The regulating compressor (SYS. REGULATOR) Moreover, the compressor will not be part of the
will regulate the other compressors in the system MULTISAB system if it is in REMOTE/capacity re-
even if the compressor is in MANUAL, AUTO, mote control with either a 4-20 mA external signal
STOPPED or SHUTDOWN. or communication signal.

Only if the voltage supply or the communication is The way the system operates can be varied de-
disconnected, the system will automatically select pending on whether a reciprocating or a screw
a new system regulator, which will be the unit with compressor comes first in the sequence. Like-
the second lowest number. wise, the way the system operates can be varied
with screw compressors of different sizes, de-

0178-445 - ENG 177/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

pending on whether a small or large compressor In case of mixed systems, it is recommended that
comes first. all reciprocating compressors in a system is
If compressors of different sizes are mixed, unfor- placed one after the other, followed by the screw
tunate part load conditions may occur, depending compressors, or vice versa. The take-over and
on the sequence. transfer functions will only be effective in case all
of the reciprocating compressors have lower start-
Be aware that if a screw compressor has the low- ing numbers than the screw compressors in the
est starting number, it may go down on low capac- same system.
ity even at small loads.

Start and system numbers - pref. master = START#


Example A - plant with one temperature system and five compressors where pref. master = START#.

System no 1 1 1 1 1

Starting no 1 2 3 4 5

Compressor no K1 K2 K3 K4 K5

In example A, K1 will be the regulator (system regulator) of the entire system, but only if it is operating or
able to start.
If K1 is stopped because of an alarm or if one of the digital inputs EXTERNAL START - NORMAL STOP
or EXTERNAL START- IMMEDIATE STOP is disconnected - and a cooling requirement still exists, the
next compressor in the starting sequence will be the regulator of the entire system provided that it is op-
erating or able to start - and that it does start. In the above example K2 will become the regulator.
Example B - plant with one temperature system and five compressors where pref. master = START#.

System no 1 1 1 1 1

Starting no 5 4 3 2 1

Compressor no K1 K2 K3 K4 K5

In example B, K5 will be the regulator (system regulator) of the entire system, but only if it is operating or
able to start.
If K5 is stopped - and a cooling requirement still exists, the next compressor in the starting sequence will
become the regulator of the entire system provided that it is operating or able to start - and that it does
start. In the above example K4 will become the regulator.
Example C - plant with two temperature systems and five compressors (eg two-stage plants)

System no 1 1 2 2 2

178/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

Example C - plant with two temperature systems and five compressors (eg two-stage plants)

Start no 2 1 3 1 2

Compressor no K1 K2 K3 K4 K5

In example C, K2 will be the system regulator of system no 1, and K4 will be the system regulator of sys-
tem no 2 provided that K2 and K4 are operating or able to start.
SETUP I MULTISAB I MULTISAB STATE If compressors of different sizes are mixed, unfor-
shows which unit has been chosen as SYS. REG- tunate part load conditions may occur, depending
ULATOR. on the sequence.
In case of two regulating systems or more, it is the Be aware that if a screw compressor has the low-
compressor with the lowest number in the individ- est starting number, it may go down on low capac-
ual system that works as system regulator. ity even at small loads.
The regulating compressor (SYS. REGULATOR) In case of mixed systems it is recommended that
will regulate the other compressors in the system, all reciprocating compressors in a system be
but only if the compressor is in REMOTE/MULTI- placed one after the other, followed by the screw
SAB and at the same time operating or ready to compressors, or vice versa. The take-over and
start. transfer functions will only be effective in case all
0178_439_en.fm

A compressor will not be part of the MULTISAB of the reciprocating compressors have lower start-
system if it is in either MANUAL, AUTO, ing numbers than the screw compressors in the
STOPPED or SHUTDOWN, or if the digital inputs same system.
EXTERNAL START-NORMAL STOP and EX- Note:
TERNAL START-IMMEDIATE STOP have not The described example of possible configuration
been connected. where the pref.master = START# can only be
Moreover, the compressor will not be part of the used for plants (systems) which are fitted solely
MULTISAB system if it is in REMOTE/capacity re- with UNISAB II units. The function cannot be used
mote control with either a 4-20 mA external signal together with a PROSAB II, UNISAB S or UNISAB
or communication signal. R / RT/ RTH. In such cases set pref.master =
COMPR# on UNISAB II.
The way the system operates can be varied de-
pending on whether a reciprocating or a screw
compressor is comes first in the sequence. Like-
Example of regulation - screw
wise, the way the system operates can be varied
compressors only
with screw compressors of different sizes, de- The working of MULTISAB will be described on
pending on whether a small or large compressor the basis of the below example and with the indi-
comes first. cated compressors.

Compressor K1. SAB163 Mk.2 K2. SAB163 Mk.2 K3. SAB202S K4. SAB202S

System no 1 1 1 1

Starting no 1 2 3 4

0178-445 - ENG 179/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

The following settings have been made in all units: sors. By increasing Nz the temperature can vary
The digital inputs EXTERNAL START - NORMAL within a larger area before a temperature regula-
STOP and EXTERNAL START - IMMEDIATE tion becomes necessary.
STOP have been connected. If Pb is reduced, the plant will react faster to
changes in temperature to return to its set point.
Configuration This usually leads to temperature variations close
CONTROL ON = BRINE to the set point, but with frequent loading/unload-
ing of compressor capacity.
AUTO START = YES
If Pb is increasedl the plant reaction will be slower,
AUTO STOP = YES
and this can prevent frequent oscillations around
COMPR.NO = xx the set point.
(the compressors are numbered from 1-4)
START DELAY is meant to prevent inadvertent
PREF. MASTER = COMPR# start of a subsequent compressor. In case the
(ie K1 is the system regulator) compressor runs above 95% capacity and the
COMMON EVAP/COND =Y/Y ( temperature is above the set point, START DE-
(common evaporator and common condenser) LAY will be started on the next compressor in the
sequence. Should the temperature reach the set
SWEPT VOLUME = xxxx
point, ie be within the neutral zone before START
(corresponding to compressor name plate)
DELAY expires, the following compressor will not
BAUD RATE = 9600/19200/38400 start.
(all compressors are fitted with UNISAB II)
Should the temperature rise excessively before
start of the next compressor, START DELAY must
Regulating parameters (for BRINE be reduced.
regulator)
In case of too frequent compressor starts/stops,
SP = -2°C
START DELAY must be increased.
(chosen according to the operating conditions of
the plant) STOP DELAY determines the time the compres-
sor runs at minimum capacity before stop. If quick
NZ = 1°C
stop is required, reduce STOP DELAY. If the com-
PB = 5°C pressor is to run for a longer period, increase
STOP DELAY.
Timers The above is a general description of the various
START DELAY = 60 sec. setting potentials. The final settings will depend
STOP DELAY = 45 sec. completely on the plant in question.

During the running-in time, adjustment of the val-


ues will be required. Loading sequence
If Nz is reduced, the plant will react to minor tem- Compressor K1 is assumed to be in operation at
perature variations in relation to the set point. This eg 70 % {Runs by itself}, K2 {Not my turn}, K3 and
will result in a frequent regulation of the compres- K4 {Not my turn} are stopped.

180/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

The MULTISAB status, shown in picture SETUP pr.}. When the compressors meet, ie when their
I MULTISAB I MULTISAB STATE, is marked slide position is the same, they will continue to
with {--}. regulate in parallel (see Fig. 14.1).
At increasing cooling requirements and conse- How much screw compressor K1 decreases in ca-
quent capacity loading, compressor K1 will in- pacity and how fast in order to meet K2 depends
crease capacity until 100% capacity is reached. completely on the strength of the "UP" regulating
The loading speed depends on how far the imme- signal.
diate temperature is above the set point that has With screw compressors K1 and K2 at 100% and
been entered into the regulator. with a persistent cooling requirement, START DE-
If a cooling requirement still exists, ie the immedi- LAY will be started on screw compressor K3. After
ate temperature is above the set point and the ca- a count-down to zero, K3 will start up. K1 will be
pacity of K1 is above 95%, the time delay (START kept at 100% {Runs at max. capacity} and K2 and
DELAY) will start up in UNISAB II on compressor K3 will regulate in parallel.
K2. The timer will count down from its set point to With a persistent cooling requirement and with K1,
zero, and compressor K2 will start. (Should the K2 and K3 at 100%, START DELAY will be started
temperature reach the set point, ie be within Nz on screw compressor K4. The timer will count
before START DELAY expires, K2 will not start). down to zero, and K4 will start up. K1 and K2 will
be kept at 100% {Runs at max. capacity} and K3
0178_439_en.fm

When the above has taken place, screw compres-


sor K1 {Lead compr.} will run slowly down from and K4 will regulate in parallel.
100% while K2 will increase its capacity {Lag com-

0178-445 - ENG 181/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

Fig. 14.1

% Lead

100
Lead=lag
75

Increasing capacity 50
Lag

25
Start
5
0 5 10 15 20 25 min.

%
100

Lead
75

Decreasing capacity 50
Lag

25
Stop
5
0 5 10 15 20 25 min.

When two screw compressors regulate in parallel, At decreasing cooling requirement and a conse-
it means that they follow each other up and down quent capacity unloading, compressors K2 and
in capacity and that both units will try to keep the K3 will decrease their capacity until both are be-
same capacity +/- approx 2%. low the value called parallel capacity. The parallel
If the two compressors that regulate in parallel capacity is automatically calculated by MULTI-
have equal capacities, the capacity change at any SAB. It depends on the size and types of the in-
given relocation of the capacity slide will be dou- volved compressors and the operating conditions.
bled compared to the regulation of a single com- The parallel capacity is the limit at which K2 is
pressor. able to take over for certain. If the two compres-
sors are of equal size, the parallel capacity will
MULTISAB compensates for this by reducing (by usually be about 55%.
half) the up and down regulating speed.
The percentage of PARALLEL CAPACITY can be
read in SETUP I MULTISAB I PARALLEL
Unloading sequence CONTROL.
Three of the four plant compressors are assumed
K3 will now ramp down towards 0% {Stop Ramp
to be in operation, K1 at 100% {Runs at max ca-
Down} with a speed of approx 12%/min. When K3
pacity}, K2 {Lead compr.} and K3 {Lag compr.}
is below 5% {May stop} the STOP DELAY timer
both in parallel operation at eg 90%.
will start up. When STOP DELAY expires, K3 will
stop {Blocked}. K2 will, until K3 stops, ensure reg-

182/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

ulation all alone {Stop Ramp Up}, as K1 remains When K1 and K3 are above 95% the time delay
at 100% {Runs at max capacity}. (START DELAY) will start in UNISAB II
Screw compressor K1 {Lead compr.} and K2 {Lag on compressor K4. The timer will count down from
compr.} will join each other in parallel operation. its set point to zero, and compressor K4 will start
up.
If a cooling requirements still does not exist, K1
and K2 will decrease their capacity until both are K4 will regulate upwards and the plant will have
below parallel capacity. K2 will ramp down and the following operating mode: K1 at 100 % {Runs
stop as soon as the STOP DELAY timer expires. at max capacity}, K3 {Lead compr.} and K4 {Lag
compr.} both in parallel operation at approx 65%
K1 will now ensure regulation all alone {Runs by (the parallel operation percentage is lower now
itself}. than during the output state as K4 is larger than
K2).
Operating sequence The alarm on K2 is confirmed (after the oil filter
Three of the four plant compressors are assumed has been replaced), and although K2 enters the
to be in operation, K1 at 100% {Runs at max. ca- READY status {Not my turn}, it will not start until a
pacity}, K2 {Lead compr.} and K3 {Lag compr.} requirement exists, as MULTISAB does not stop
both in parallel operation at eg 80%. K4 to make K2 resume its position in the se-
The cooling requirement is constant. quence.
0178_439_en.fm

Due to an alarm caused by high oil filter differen- Example of regulation -


tial pressure, K2 stops {Blocked}. This makes K1 reciprocating compressors only
{Lead compr.} and K3 {Lag compr.} change to par- The working of MULTISAB will be described on
allel operation, and K3 will increase its capacity to the basis of the below example and with the indi-
100%. cated compressors.

Compressor K1. SMC108L K2. SMC108L K3. SMC106S K4. SMC106S

System no 1 1 1 1

Starting no 1 2 3 4

The following settings have been made in all units: COMPR.NO = xx


The digital inputs EXTERNAL START - NORMAL (The compressorers are numbered from 1-4)
STOP and EXTERNAL START - IMMEDIATE PREF. MASTER = COMPR#
STOP have been connected. (ie K1 is the system regulator)
COMMON EVAP/COND = Y/Y
Configuration (common evaporator and common condenser)
CONTROL ON = SUCTION
SWEPT VOLUME = xxxx
AUTO START = YES (corresponding to the compressor name plate)
AUTO STOP = YES BAUD RATE = 9600/19200/38400
(all compressors are fitted with UNISAB II)

0178-445 - ENG 183/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

Regulating parameters (for SUCTION quence. Should the temperature reach the set
PRESSURE regulator) point, ie be within the neutral zone before START
SP = -10°C/R DELAY expires, the next compressor will not start.
(chosen according to the operating conditions of Should the temperature rise excessively before
the plant) start of the next compressor, START DELAY must
NZ = 3°C be reduced.

PB = 5°C In case of too frequent compressor starts/stops,


START DELAY must be increased.

Timers STOP DELAY determines the time the compres-


sor runs at minimum capacity before stop. If a
START DELAY = 60 sec
quick stop is required, reduce STOP DELAY. If
STOP DELAY = 45 sec the compressor is to run for a longer period, in-
DELAY UP = 30 sec crease STOP DELAY.

DELAY DOWN = 20 sec If DELAY UP is increased, the reciprocating com-


pressor will load capacity stages at a lower speed;
During the running-in time, adjustment of the val-
vice versa a lower value of DELAY UP will result
ues will be required.
in faster loading.
If Nz is reduced, the plant will react to minor suc-
If DELAY DOWN is increased, the reciprocating
tion pressure variations in relation to the set point.
compressor will unload capacity stages at a lower
This will result in frequent regulation of the com-
speed; vice versa a lower value of DELAY DOWN
pressors. By increasing Nz the suction pressure
will result in faster unloading.
can vary within a larger area before a regulation of
the compressors becomes necessary. In many cases it is advantageous if DELAY UP is
higher than DELAY DOWN.
If Pb is reduced, the plant will react faster to
changes in the suction pressure to return to its set The above is a general description of the various
point. This usually leads to temperature variations setting. The final settings will depend completely
close to the set point, but frequent loading/unload- on the plant in question.
ing of compressor capacity.
If Pb is increased, the plant reaction will be slower, Loading sequence
and this can prevent frequent oscillations around Compressor K1 is assumed to be in operation at
the set point. eg 75 % {Runs by itself}, K2 {Not my turn}, K3 and
START DELAY is meant to prevent inadvertent K4 {Not my turn} have been stopped.
start of a subsequent compressor. In case the The MULTISAB status, as shown in picture SET-
compressor runs at 100% capacity and the tem- UP I MULTISAB I MULTISAB STATE, is
perature is above the set point, START DELAY marked with {--}.
will be started on the next compressor in the se-

184/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

Fig. 14.2
Capacity for
1 compressor
% Increasing requirement for capacity

Compressor 1 Compressors 1+2


100
Compressor 2
75

50

25

Time
Capacity for
1 compressor
%
Decreasing requirement for capacity

Compressors 1+2
100
Compressor 2 Compressors 1
75
50

25
0178_439_en.fm

Time

At increasing cooling requirement and conse- With compressor K2 at 100% and still capacity re-
quent capacity loading, reciprocating compressor quirement, the timer START DELAY starts on
K1 will load stages at the DELAY UP time lag until compressor K3. It will count down before K3 starts
100% capacity has been reached. up.
It is possible to make the loading speed depend When K3 is at 100% and a cooling requirement
on how far the actual suction pressure is above still exists, the timer START DELAY will start on
the set point by setting the proportional factor DE- K4. When timer has expired, K4 will start.
LAY UP above 1 in the picture SETUP I TIMERS
I P BAND FACTOR. See section Regulating set- Unloading sequence
up.
In an operating situation where the entire plant
If a cooling requirement still exists, ie the immedi- runs at 100% and with a decreasing cooling re-
ate suction pressure is higher that the set point, quirement, unloading will start on compressor K4
the timer START DELAY is started on compressor first.
K2. The timer will count down from its set point to
K4 will decrease its capacity by unloading stages
zero, and K2 will start. (In case the suction pres-
with the time delay DELAY DOWN between each
sure reaches the neutral zone before START DE-
change of stage until it reaches minimum capaci-
LAY expires, K2 will not start).
ty, ie 33% (SMC 106S). One stage will now be un-

0178-445 - ENG 185/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

loaded on compressor K3, which will run at 67%, The system will continue its unloading in stages
and the timer STOP DELAY will start on K4, (dur- until K1 is stopped.
ing unloading the reciprocating compressors will It is also possible that the plant stabilizes at part
overlap, Fig. 14.2). load, and if the cooling requirement increases, the
When time delay STOP DELAY expires on K4, K4 situation will be the same as described under
will stop. Loading sequence.
K3 will now decrease its capacity to minimum, and
after K2 has unloaded one stage, K3 will stop on Example of regulation - combination of
the timer STOP DELAY. screw and reciprocating compressors
Reciprocating compressor K2 will now start un- The working of MULTISAB will be described on
loading stages with time delay DELAY DOWN, the basis of the below examples A and B and with
until it reaches minimum capacity, ie 25%. One the indicated compressors.
stage will be unloaded on compressor K1, and the
timer STOP DELAY will start on K2.
A:
Compressor K1. Recip. K2. Recip. K3. Screw K4. Screw K5. Screw

System no 1 1 1 1 1

Starting no 1 2 3 4 5

B:
Compressor K1. Screw K2. Screw K3. Screw K4. Recip. K5.Recip.

System no 1 1 1 1 1

Starting no 1 2 3 4 5

The following settings have been made in all units: COMMON EVAP/COND = Y/Y
The digital inputs EXTERNAL START - NORMAL (common evaporator and common condenser)
STOP and EXTERNAL START - IMMEDIATE SWEPT VOLUME = xxxx
STOP have been connected. (corresponding to the compressor name plate)
BAUD RATE = 9600/19200/38400
Configuration (all compressors are fitted with UNISAB II)
CONTROL ON = SUCTION
AUTO START = YES Regulating parameters (for SUCTION
AUTO STOP = YES PRESSURE regulator)
COMPR.NO = xx SP = -20°C/R
(The compressorers are numbered from 1-5) (chosen according to the operating conditions of
the plant)
PREF. MASTER = COMPR#
(ie K1 is the system regulator) NZ = 1°C

186/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

PB = 5°C In case of too frequent compressor starts/stops,


START DELAY must be increased.
Timers STOP DELAY determines the time the compres-
START DELAY = 60 sec sor runs at minimum capacity before stop. If a
quick stop is required, reduce STOP DELAY. If
STOP DELAY = 45 sec
the compressor is to run for a longer period, in-
DELAY UP = 30 sec crease STOP DELAY.
(only reciprocating compressors)
If DELAY UP is increased, the reciprocating com-
DELAY DOWN = 20 sec pressor will load capacity stages at a lower speed;
(only reciprocating compressors) vice versa a lower value of DELAY UP will result
During the running-in time, adjustment of the val- in faster loading.
ues will be required. If DELAY DOWN is increased, the reciprocating
If Nz is reduced, the plant will react to minor suc- compressor will unload capacity stages at a lower
tion pressure variations in relation to the set point. speed; vice versa a lower value of DELAY DOWN
This will result in frequent regulation of the com- will result in faster unloading.
pressors. By increasing Nz the suction pressure In many cases it is advantageous if DELAY UP is
can vary within a larger area before a regulation of higher than DELAY DOWN.
the compressors becomes necessary.
0178_439_en.fm

It is recommended to place all reciprocating com-


If Pb is reduced, the plant will react faster to pressors in a system one after the other followed
changes in the suction pressure to return to its set by the screw compressors, or vice versa.
point. This usually leads to temperature variations
The take-over and transfer functions described in
close to the set point, but frequent loading/unload-
the following will only be effective if all reciprocat-
ing of compressor capacity.
ing compressors have lower starting numbers
If Pb is increased, the plant reaction will be slower, than the screw compressors.
and this may prevent frequent oscillations around
The above is a general description of the various
the set point.
settings. The final settings will depend completely
The purpose of START DELAY is to try to prevent on the plant in question.
inadvertent start-up of a subsequent compressor.
In case a compressor is at 100% capacity and the
Loading sequence - sequence A
suction pressure is still above the neutral zone,
START DELAY will be started on the next com- Compressor K1 is assumed to be in operation at
pressor in the sequence. Should the suction pres- eg 50 % {Runs by itself}, K2 {Not my turn}, K3, K4
sure reach the neutral zone before START DE- and K5 {Not my turn} have been stopped.
LAY expires, the following compressor will not The MULTISAB status, as shown in picture SET-
start. UP I MULTISAB I MULTISAB STATE, is
Should the temperature rise excessively before marked with {--}.
start of the next compressor, START DELAY must At increasing cooling requirement and conse-
be reduced. quent capacity loading, reciprocating compressor

0178-445 - ENG 187/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

K1 will load stages at the DELAY UP time lag until State of transfer
100% capacity has been reached. In case of a minor cooling requirement, it is as-
It is possible to make the loading speed depend sumed that the plant stabilizes in the following sit-
on how far the actual suction pressure is above uation: reciprocating compressors K1 and K2 both
the set point by setting the proportional factor DE- at 100% and screw compressor K3 in 40% slide
LAY UP above 1 in the picture SETUP I TIMERS position.
I P BAND FACTOR. See section Regulating set- Reciprocating compressor K2 will now pass into
up. the "transfer" state, ie it will start decreasing its ca-
If a cooling requirement still exists, ie the actual pacity to force the screw compressor capacity up-
suction pressure is higher than the set point, the wards.
timer START DELAY will start on compressor K2. However, this will only take place if the actual suc-
The timer will count down from its set point to ze- tion pressure is within the 'transfer zone', consist-
ro, and reciprocating compressor K2 will start. (In ing of the neutral zone (zone 1) plus the transfer
case the suction pressure reaches the neutral zone (zone 3), which is default 15% of the regula-
zone before START DELAY expires, K2 will not tor proportional band, (see Fig. 14.3).
start).
When the reciprocating compressor unloads an-
With compressor K2 at 100% and a persistent ca- other stage, this will happen with a time delay that
pacity requirement, the timer START DELAY will (in sec) is the setting of DELAY DOWN multiplied
start on K3. The timer will count down before K3 by the 'transfer factor' for DELAY DOWN. This
starts up. factor, 1-10, has been entered to avoid hunting in
When K3 is at 100% and a cooling requirement the plant as far as possible as the regulating sys-
still exists, the timer START DELAY will start on tem must have time to react to the rise in the suc-
K4. When the timer has expired, K4 will start. tion pressure when the reciprocating compressor
When the above has taken place, screw compres- is unloading.
sor K3 will go down from 100% while K4 will in- If the suction pressure rises (zone 2), the recipro-
crease its capacity. When they meet, ie when their cating compressor will stop the down regulation
slide positions are the same, they will continue to while the screw compressor regulates upwards to
regulate in parallel (see Fig. 14.1). get the suction pressure in place.
Whether screw compressor K3 decreases its ca- Once the plant has balanced, the reciprocating
pacity and how fast to meet K4 depends com- compressor will continue the unloading of stages
pletely on the strength of the "UP" regulating sig- and the screw compressor will readjust.
nal. Provided that requirements stay the same, this
With screw compressors K3 and K4 at 100% and process will continue until the screw compressor
with a persistent cooling requirement, START DE- is above 85% slide posiiton. Above this fixed limit
LAY will be started on screw compressor K5. After it is assumed that the screw compressor is run-
a countdown to zero, K5 will start up. K3 will now ning fairly economically. Further reduction of the
be kept at 100% {Runs at max capacity}, and K4 reciprocating compressor capacity would result in
{Lead compr.} and K5 {Lag compr.} will regulate in a high risk that the screw compressor is no longer
parallel. able to take over, causing frequent loading and

188/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

unloading of stages or start and stop of the recip- If the cooling requirement increases, screw com-
rocating compressor. pressor K3 will be loaded at 100%, whereupon re-
The result may be that the reciprocating compre- ciprocating compressor K2 will be loaded.
sor K1 runs at 100%, K2 at 25% and screw com-
pressor K3 at 85%.
Fig. 14.3

+ regulator output signal (capacity UP)

6. outside PB

4. 85% PB

2. 15% PB
1. NZ Takeover zone = 1+2
SP
Transfer zone = 1+3
3. 15% PB

5. 85% PB
0178_439_en.fm

7. outside PB

- regulator output signal (capacity DOWN)

State of take-over compensated for by unloading on screw compres-


If the plant stabilizes after a transfer situation with sor K3, until it reaches minimum and stops on
K1 at 100%, K2 stopped, screw compressor K3 at STOP DELAY.
40% capacity, and K2 able to take over this ca- Be aware that during reloading periods it may
pacity, K2 will start. However, this will only take happen that a screw compressor is running at low
place if the actual suction pressure is within the capacity. Furthermore, reloading will take a cer-
'take-over zones', consisting of the neutral zone tain amount of time, which prevents instability in
(zone 1) plus the take-over zone (zone 2) which is the plant.
default 15% of the regulator proportional band, In plants with frequent load changes, it may take
(see Fig. 14.3). longer before the reciprocating compressors take
When K2 starts up to take over the screw com- over/transfer capacity.
pressor capacity, this will take place with the load- If the plant is very unstable, the variations may be
ing time DELAY UP multiplied by the 'take-over' absorbed exclusively by the screw compressor.
factor for DELAY UP. This factor, 1-10, has been Consequently, the screw compressor will in some
entered to avoid hunting. periods run at low capacity. This can be avoided
When reciprocating compressor K2 is loading by removing the starting permission from either
stages, the suction pressure will drop, but this is

0178-445 - ENG 189/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

the screw compressor or the reciprocating com- lay DELAY DOWN until it is down to minimum ca-
pressor. pacity. Next, a stage is unloaded on compressor
Reciprocating compressors will only try to take K1, and the STOP DELAY time will start on K2 (ie
over/transfer capacity from/to screw compressors during unloading the reciprocating compressors
that come later in the sequence. will overlap, (see Fig. 14.2).
The system will continue unloading in stages until
Unloading sequence - sequence A K1 stops.

In an operating situation where the entire plant The plant may also stabilize at part load, and in
runs at 100% and with a decreasing cooling re- case the cooling requirement is increasing, the sit-
quirement, unloading will start on the screw com- uation will be the same as described under Load-
pressors. ing sequence - sequence A.

As illustrated in Fig. 14.1, K4 and K5 will reduce


their capacity in parallel until both are below the Loading sequence - sequence B
value called the parallel capacity. The parallel ca- Compressor K1 is assumed to have stopped {May
pacity is automatically calculated by MULTISAB. start}, K2, K3, K4 and K5 {Not my turn} are
It depends on the size and types of the involved stopped.
compressors and the operating conditions. The The MULTISAB status, as shown in picture SET-
parallel capacity is the limit at which it is certain UP I MULTISAB I MULTISAB STATE, is
that K4 is able to take over. If the two compressors marked with {--}.
are of equal size, the parallel capacity will usually
be approx 55%. In case of a cooling requirement, K1 will start.
When it has reached 100% capacity, START DE-
The percentage of PARALLEL CAPACITY can be LAY will start on screw compressor K2. The timer
read in SETUP I MULTISAB I PARALLEL will count down, and K2 will start up. When this
CONTROL. has happened, screw compressor K1 will go down
K5 will now ramp down towards 0% {Stop Ramp from 100%, while the capacity of K2 will go up.
Down} with a speed of approx 12% /min. When K5 When the compressors meet, ie when their slide
is below 5% {May stop}, the timer STOP DELAY positions are the same, they will regulate in paral-
will start. When STOP DELAY expires, K5 will lel.
stop {Blocked}. K4 will, until K5 stops, ensure reg- When K1 and K2 are in 100%, the time delay
ulation all alone {Stop Ramp Up} as K1, K2 and START DELAY will start on screw compressor K3.
K3 remain at 100% {Runs at max capacity}. When the timer has expired, K3 will start up and
Next, the screw compressors K3 {Lead compr.} K1 will be kept at 100%.
and K4 {Lag compr.} will work together until K4 When this has happened, screw compressor K2
stops. will go down from 100%, while the capacity of K3
K3 will now decrease its capacity to a minimum will go up. When the compressors meet, ie when
and stops on its time, STOP DELAY. their slide positions are the same, they will regu-
When this has happened reciprocating compres- late in parallel.
sor K2 will start unloading stages with the time de-

190/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

Whether K2 reduces its capacity and at which pressor K5 {Lag compr.} will be the first to unload
speed to meet K3 depends completely on the stages with time delay DELAY DOWN until it has
strength of the "UP" regulating signal. reached minimum capacity. Next, one stage is un-
With K2 and K3 at 100% and a persistent cooling loaded on compressor K4, and STOP DELAY will
requirement, ie the actual suction pressure is now start on K5 (ie during unloading the recipro-
higher than the set point, the time delay START cating compressors will overlap, (see Fig. 14.2)).
DELAY will start on reciprocating compressor K4. When STOP DELAY has expired, compressor K5
The timer will count down to zero and reciprocat- will stop, and K4 will now continue the unloading.
ing compressor K4 will start up. Should the actual When K4 has unloaded to minimum capacity, it
suction pressure reach the neutral zone before will start up its STOP DELAY time and when this
START DELAY expires, K4 will not start. has expired, K4 will stop.
K4 will now load and unload stages according to Screw compressors K2 and K3 are now going to
the cooling requirements, while the screw com- decrease their capacity in parallel operation, until
pressors K1, K2, K3 are kept at 100% capacity they are below the parallel capacity (usually 55%
{Runs at max capacity}. if they are of equal size). K3 will be run down to
This will continue until all the compressors are at minimum capacity and stops on its STOP DELAY
100% capacity. time. At the same time K2 will take over.
Screw compressors K1 and K2 will adjust in par-
0178_439_en.fm

Be aware that with the above sequence screw


compressor K1 may start and stabilize at eg 35% allel to the same slide position and start decreas-
capacity corresponding to the actual cooling re- ing their capacity in parallel operation until they
quirement. In this situation a subsequent recipro- are below the parallel capacity. K2 will be run
cating compressor will not try to take over be- down to minimum capacity and stop on its STOP
cause it comes later in the sequence. DELAY time. At the same time K1 will take over.
Depending on the capacity requirement, K1 will
Unloading sequence - sequence B reduce its capacity and possibly stop completely.

With the entire plant running at 100% and a de-


creasing cooling requirement, reciprocating com-

0178-445 - ENG 191/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

Practical example 1
Fig. 14.4

% SMC 8-100 Start # 2


100
80
60
40
20
0
SMC 12-100 Start # 1
100
80
60
40
20
0
VMY 325-3 Start # 5
100
80
60
40
20
0
VMY 325-2 Start # 3
100
80
60
40
20
0
VMY 347-1 Start # 4
100
80
60
40
20
0
-4 -3 -2 -1 Immediate Time

A B C D E F G H I K

0177150_0

Fig. 14.4 shows that the VMY 347 screw com- interval "C". In interval "D" the cooling requirement
pressor has number 1, the two VMY 325 compres- drops, and K2 will unload and stop. The two recip-
sors have numbers 2 and 3. Further, SMC 12-100 rocating compressors K4 and K5 will now cover
has number 4 and SMC 8-100 number 5. The se- the cooling requirements.
quence starting number is seen after "Start #". In interval "E" there is a brief increase in the cool-
The curve, taken from an existing plant, describes ing requirement. This increase is covered by K2.
a regulating course over a period of approx 3 After some time K2 will stop as the cooling re-
hours, divided into intervals from A to K. quirement has dropped again. However, the plant
In interval "A" compressors 1 and 2 run at part does not have time to stabilize.
load, until they are both a little below 50% slide In interval "F" the cooling requirement rises again
position, interval "B". Here, the system decides and K2 will restart and go up to approx 60% slide
that K1 can be unloaded and K2 will take over. position. Here, the plant stabilizes at a constant
K2 will now increase its capacity with a simultane- compressor capacity in interval "G".
ous increase in the cooling requirement, which In the period until interval "H" the reciprocating
means that K4 will start up and adjust its capacity, compressor transfers capacity to the screw com-

192/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

pressor as the screw compressor is below 85% risen to 70%. Until interval "K" K4 will unload fur-
slide position. K5 stops completely, and K4 will ther and K2 will now be at 100% capacity.
start transferring capacity. In interval "I" K2 has

Practical example 2
Fig. 14.5

%
SMC 8-100 Start # 2
100
80
60
40
20
0
SMC 12-100 Start # 1
100
80
60
40
20
0
VMY 325-3 Start # 5
100
80
60
40
20
0
0178_439_en.fm

VMY 325-2 Start # 3


100
80
60
40
20
0
VMY 347-1 Start # 4
100
80
60
40
20
0
-4 -3 -2 -1 Immediate
Time
A B C D E F G H I K
0177150_0

Fig. 14.5 shows that the VMY 347 screw com- Until interval "C" these three compressors are run-
pressor has number 1, the two VMY 325 compres- ning at 100%. A rise in the cooling requirement will
sors have numbers 2 and 3. Furthermore, SMC make K1 start up. At this point K1 and K2 will start
12-100 has number 4 and SMC 8-100 number 5. dividing the capacity. This can be seen in interval
The sequence starting number is seen after "Start "D", where K2 has decreased a little, while K1 is
#". on its way up.
The curve, taken from an existing plant, describes In interval "E" K1 and K2 have the same slide po-
a regulating course over a period of approx. 3 sition (approx 70%) and they regulate in parallel.
hours, divided into intervals from A to K. In interval "F" K5 may transfer capacity and this
In interval "A" compressors K2 and K4 are running may continue with K4 transferring until interval
at 100% until interval "B". Here, there is a rise in "G", where the screw compressors have reached
the cooling requirement, and K5 will start loading. approx 80%.

0178-445 - ENG 193/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

In interval "H" K1 and K2 are above 85% and K4 4) Is the actual suction pressure higher than
will stay passive until interval "I", where K1 and K2 the set point +1/2 neutral zone?
have regulated down due to decreasing cooling 5) Are any of the limiting functions active?
requirement. Once they are below 85%, K4 will
transfer its remaining capacity. The screw com- 6) Have AUTO START and AUTO STOP been
pressors have now taken over the entire load. configured?

Please note that in case the sequence is changed 7) Has the COLD STORE FUNC. been config-
during operation, do not expect any immediate re- ured?
action. If the plant is balanced at this particular
time, it will continue to operate with the "old" se- The plant does not run in sequence
quence, until a movement has taken place in the 1) Do the units communicate? In case of no
regulation and it has adapted to the new se- communication, each UNISAB II will run
quence. The chosen compressor sequence will with its own regulator. It may be useful to en-
depend on the operating mode of the plant as well ter the picture SETUP I MULTISAB I ALL
as the size of the compressors compared to each COMPRESSORS and go through the com-
other. pressor numbers (use J and K ). There will
Thus, it can be difficult to achieve an optimum be a question mark (?) in the lower left cor-
compressor operation in every situation. Howev- ner of the display if there is no communica-
er, it is possible to select compressors by using tion to the UNISAB II with the selected
the signal input external start - normal stop as a number.
supplement to the MULTISAB system facilities as – Check communication cable and
described above. By removing the external start - connection.
normal start signal the compressors can be re-
– Do two or more UNISAB II units have
moved from the sequence. MULTISAB will now
the same compressor number (COMPR.
load compressors with rising sequence numbers -
NO)? Check the numbers in picture
despite the "holes" in the starting sequence.
SETUP I CONFIG I COMMUNICA-
TIONS. They must all be unique.
Trouble shooting
2) Do all units that are supposed to run in se-
The plant cannot start
quence have identical SYSTEM NO, which
1) Are all UNISAB II units set on REMOTE? they must. Check the picture SETUP I
2) Have the signals external start - normal stop MULTISAB I MULTISAB STATE.
and external start - immediate stop been ac- 3) Check whether all units in the same system
tivated? See UNISAB II drawings Digital in- agree upon the same SYS.REGULATOR,
puts. see picture SETUP I MULTISAB I MUL-
3) Do the units communicate? - check this by TISAB STATE. If this is not the case, do all
means of the picture SETUP I MULTISAB units agree on how to decide the mas-
I ALL COMPRESSORS. Check communi- ter/system regulator? See the PREF.MAS-
cation cable. TER field in SETUP I CONFIG.

194/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

4) If PREF. MASTER = START#, has the 5) Is START NO = 0 in one or more UNISAB II


same START NO been entered in two or units? MULTISAB requires that all START
more units? See picture SETUP I MULTI- NO are higher than 0 and that not two are
SAB I MULTISAB STATE. They must all identical. Note that though it is not possible
be unique! to select 0 as START NO., the START NO.
may still become 0 for several reasons.
0178_439_en.fm

0178-445 - ENG 195/222


Rev. 03.09
UNISAB II 2.03
14. Start and system numbers

196/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
15. List of Versions

15. List of Versions


This instruction manual applies to the UNISAB II version stated on page 1.
As an exception, the manual can be used for an earlier version of the UNISAB II program. In such cases
it is necessary to consult the list of versions below to identify the points where the manual cannot be relied
upon.

Version no Description
1.01 On the HPO compressor an incorrect scaling of the discharge pressure has been cor-
rected. 15 languages have been entered.
1.02 No changes in the user's operation.
1.03 The timers Start Delay and Stop Delay will be working, also when capacity is regulated
on the external 4-20 mA analog signal.
The digital output AUX = "ready" is only active when the compressor is able to start, ie
the digital input "external start permission - normal stop" must also be active.
1.04 The hour counter counts in single hours and no longer in intervals of 10 hours.
An error in press./temp. conversion for R23 refrigerant at approx -70°C has been cor-
rected.
An error in the MULTISAB system resulting in blocking of plants with three or more re-
0178_440_en.fm

ciprocating compressors in sequence has been corrected. (The compressor starting


as no 1 remained at 100% capacity at load reduction, preventing no. 2 from unloading
the last stage).
1.05 This version does not exist.
1.06 Refrigerant R508 has changed its name to R410A.
A new refrigerant, R407C, has been entered.
Two new screw compressor types have been introduced: SAB 128H Mk3 and SAB
163H Mk3.
Automatic zero position (capacity slide) setting has been introduced for SAB 202 with
automatic Vi slide as well as manual zero position setting for other screw compressor
types.
1.07 Automatic zero position setting has been introduced for SAB 202 with manual Vi slide.
The regulating speed (max speed) has been increased. The regulation is now faster
(longer pulses - particularly at low oil pressure levels) than in previous versions.
TSMC/TCMO compressors had no setpoint 2 (SP2) for discharge pipe temperature for
regulating the "intermediate press. injection". This has now been introduced.
1.08 General remarks:
During a sequence running with two or more screw compressors, it could happen that
all compressors stayed at low capacity without regulating upwards although a capacity
requirement existed. This error has been corrected in MULTISAB.
If the suction pressure ramp limiting function prevents the compressor from increasing
its capacity to more than 5%, the timer "delay before stop" will not be activated as was
the case previously. The compressor will remain in operation.
The configuration point "COMMON CONDENSER" has been extended to include
"common evaporator" and is now called "COMMON EVAP/COND N/N".

0178-445 - ENG 197/222


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version no Description
Screw compressors:
For screw compressors two warnings have been introduced: "LIMITING SUCTION
PRESSURE"and "LIMITING DISCHARGE PRESSURE". These will occur whenever
the UNISAB II is in position "READY" but unable to start because the suction or dis-
charge pressure is within the neutral zone of the limiter in question.
For VMY compressors, the solenoid valve for "capacity down" opens whenever the
compressor is prelubricated.
A limiting function has been introduced for "high suction pressure limitation". The com-
pressor capacity is limited, during operation, to an adjustable max. value when the suc-
tion pressure is above the high warning limit for the suction pressure.
Reciprocating compressors:
A function controlling the by-pass valve ("cap.stage 1") has now been entered for the
TCMO 28 compressor.
The timers "DELAY UP" and "DELAY DOWN" that operate in connection with the load-
ing and unloading of capacity stages are now active both during capacity regulation
with external "4-20 mA input" signals or if capacity regulation takes place via data com-
munication.
1.09 General remarks:
In the TIMERS menu picture the TIMER SETUP picture has been displaced so that the
picture obtains a position on the part of the timer menu that is immediately visible when
you select the menu.
In the CALIB/AUX.OUTPUTpicture the AUX output can now be activated by: RUN-
NING and READY-EXT.
At auto alarm reset, e.g. at a low suction pressure, the alarm relay will also be auto
reset.
1.09 (cont.) Special warnings: Limiter suction pressure, Limiter discharge pressure, Limiter brine
and Limiter hot water can now be read via the Danbuss communication.
Motor currents SP1 and SP2 can now be changed right up to 2500 Amp.
Due to an error in the A/D converter software, we have received reports of a false
alarm for "Low brine temp" at "Power up" in some plants. This has now been corrected.
Via the communication it is now possible to read whether UII is in REMOTE/capacity
regulating mode. To be read as "Cap.mode".
An HP compressor started up by means of the "HP at two-stages" function + the "Ext.
start normal stop" signal, is now not going to stop on the "Stop delay" timer anymore,
even though capacity is below 5%.
Screw compressors:
A Multisab error has been rectified which could occur as follows:
At suction pressure limitation, both compressors regulated down to 0% and the Lead
compressor stopped. Before the Lag compressor stopped, however, the capacity re-
quirements change. The Lag compressor then continued to run at 0% without regulat-
ing upwards, although capacity was needed. This situation coul be altered by changing
the Lead compressor from Remote to Manual after which the regulation worked cor-
rectly when switching back again to Remote.

198/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version no Description
The position regulator parameters (SP, NZ and PB) are now accessible in a new pa-
rameter picture for MOTOR/CAPACITY. It is also possible to change NZ and PB via
the communication.
Further, the neutral zone (+/-1%) at capacity regulation has been removed.
A false alarmfor "capacity error" that might occur (in some special cases), often at
100% capacity and with regulation in the neutral zone, has now been removed.
If a VMY compressor happened to fall out at "Capacity error" during operation, while
the slide was above 5%, the slide was not run down when the alarm was confirmed,
because the oil pump did not start. This has now been corrected.
The VMY compressor would stop the slide run down (the oil pump was stopped) when-
ever the capacity was below 5%. An extended hysterisis has now been introduced so
that the oil pump does not stop until 10 sec. have passed and capacity is below 4.5%.
1.09 (cont.) Reciprocating compressors:
The MULTISAB transfer- and take-over mode for linking of reciprocating and screw
compressors has now been implemented with the same functionality as that of Unis-
ab-RT.
The texts in the TIMERS, TRANSFER and TAKE-OVER pictures have been changed.
The new E-type for SMC/TSMC compressors has been introduced in CONFIG.
HPO/HPC. The setpoint for the suction pressure regulator can now be set to 25 Bar -
the discharge pressure regulator right up to 40 Bar. The warning limit for High Differ-
0178_440_en.fm

ential Pressure is 25 Bar.


1.10 Please note that this program version no. 1.10 is tied up with instruction
manual version 1.10A.
General remarks:
All SMC and TSMC compressors are going to be configured as either type S/L or E.
An HP compressor started with the "HP at two-stage" function + "Ext. start normal" sig-
nal, is not going to stop on the "Stop delay" timer if the comperessor has been selected
for REMOTE/Multisab and no other compressors are operating in this system. Can
only be stopped by opening the input:"Ext. start normal".
The AUX output READY-EXT is now also applicable in AUTO
It is now possible to use a user-configurable refrigerantR000.
It is now possible to use a user-defined password.
UNISAB II can now be reconfigurered to UNISAB / Evolution.
Screw compressors:
The secondary oil pump on VMY compressors was able to make a brief start on "power
up". This has been corrected.
Prosab II and UNISAB II did not regulate correctly in LEAD-LAG.
This has been corrected.
The minimum limits for low oil pressure has been raised for Mk3 compressors.
The heating rod was not connected at compressor stop if the compressor:
1) stopped on alarm within 60 sec after start or
2) the alarm "capacity error" appeared at a stop.
This has now been rectified.
Reciprocating compressors:

0178-445 - ENG 199/222


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version no Description
An adjustable time delay has been built in on the oil return.
The time delay for low oil pressure is now also active during operation.
It is now possible to set up a delayed closing of the solenoid valves for oil cooling or
water cooling at compressor stop.
A limiting function has beeen introduced for high discharge temperatures.
The limiting function for "high suction pressure limitation" has now also been intro-
duced for reciprocating compressors.
The capacity of the reciprocating compressor is stored in DIAGNOSIS I OLD
ALARMS in case the alarm should fall out.
1.11 This version does not exist.
1.12 General remarks:
COP calculation and display on the UNISAB II is now possible. Select the function in
configuration. The calculated COP, the cooling output and the efficiencyare shown in
the picture COP.
The position transmitter signal for the capacity slide can be calibrated at 0 % and 100
%.
A test version containing the SAB 330 screw compressor is installed. The programme
can only be used for internal YORK test.
It is now possible to select the unit kPa in the UNISAB II.
A larger EEPROM type with a capacity of 4 kByte has been introduced. Up to now the
capacity has only been 2 kByte.
Screw compressors:
Screw compressor type SV 80 is now supported.
The UNISAB Evolution II data are now automatically updated in the Evolution menu
structure.
An error whereby the heating element was not activated after switching the power
on/off has been rectified.
Aconversion error in the display of oil filter difference pressure has now been rectified.
The error only occured during PSI conversion.
Reciprocating compressors:
It is now possible to disconnect the MULTISAB "transfer/take-over" function.
A MULTISAB error which occurred in a certain combination of plants with both screw
compressors and reciprocating compressors has now been rectified.
1.13 General remarks:
EEPROM, calibration settings and hour counter are saved.
Screw compressors
In version 1.12 the VMY compressors started the prelubrication pumps shortly after
power up. This has now been rectified.
Reciprocating compressors:
When the UNISAB II has been configured so that it is regulated using the brine tem-
perature, and this is in the lower P-Band, and a limiting function at the same time is
active, the UNISAB II will - when the lowest step has been reached - count down in
"delay down" instead of "stop timer". This has now been rectified.

200/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version no Description
1.13 Version 1.13 - which is marked with the date 990831 - differs from the original 1.13
(990831) mainly on the following points:
It is found in three varieties: 1.13-A, 1.13-B and 1.13-C. The three varieties contain the
same program but in three different sets of languages:
-1.13-A: English, Danish, Finnish, Italian, Norwegian and Swedish.
-1.13-B: English, German, French, Hungarian, Dutch and Russian.
-1.13-C: English, Czech, Spanish, Greek, Portuguese and Polish.
When UNISAB II is switched on for the first time or when a program
RESET is performed, the set language is English.
Low oil pressure alarm is delayed extra 10 seconds at compressor start to avoid unin-
tended alarm.
A number of alarms and warnings has been added.
The alarm #83 "Vi position" appears if the shown capacity is 100% while the measured
capacity position is < 20%.
1.13 A number of errors have been corrected compared to earlier versions.
(000224) Additionally,
it is now possible in the MULTISAB→ PARALLEL CONTR picture to type in an OFF-
SET to the parallel capacity;
changes regarding "Evolution" have been carried out.
0178_440_en.fm

2.00 General remarks:


The following compressor types have been added:
-SAB 128 HR
-SAB 163 HR
-SAB 250 S/L/E
-SAB 330 S/L/E
The following refrigerant type has been added: R744 (CO2).
Communication with Quantum compressor controller now possible.
The AUX OUTPUT can now additionally be configured to "READY AND ME ONLY"
which can be used to ensure water circulation at the PT100 sensor even if no com-
pressor is running.
The manual has been thoroughly updated.

0178-445 - ENG 201/222


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version no Description
Screw compressors:
The capacity control is now being carried out by standard PID controllers.
Minimum capacity increase/decreace pulse 0.3 sec.
At compressor stop, capacity down signal until capacity < 5%.
Reciprocating compressors:
A low pass filter has been attached to the suction superheat to avoid low superheat
alarm when unloading stages. The timer "Low superheat" is now adjustable 15 - 600
sec.
2.01 Further remarks:
Compressor types SAB 283 L/E, SAB 355 L as well as the GSV/RWF series (see con-
figuration).
Two new refrigerants: R1270 (Propylene), R 290 (Propane).
One new timer has been introduced for screw compressors:
Timer 33 Lubricating pressure.
One new timer for reciprocating and screw compressors have been introduced:
Timer 32 Low suction pressure.
Turkish has been added.
Timer for oil filter differential pressure has been raised to 300 seconds.
Screw compressor, type SAB 80. Max values for oil filter differential pressure have
been changed to: Alarm = 2.5 bar and warning = 2.2 bar.
Contrast can now be adjusted from any menu picture by means of the RESET button
and the arrow up/down keys.
Low alarm and low warning for brine temperature have been changed from -60°C to
100°C.
Screw compressor: Start delay and stop delay factors affecting the countdown of the
timer have been changed to start and stop delay “zones” in [%] of the P-band. When
regulated value is outside a “zone”, the timer will start. Set value 0-100 [%]. Setting of
0 [%] results in the “zone” passing over to the other side of Nz, ie. a stop delay zone =
0 % means that the stop delay timer will start when regulated value is inside or below
Nz.

2.01 (020221) EEPROM. When switching to the use of two EPROMS at the same time (from version
2.0x) a timing problem occurred which had the effect that writing to and reading from
the EEPROM was not always carried out correctly. This has now been rectified.

202/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version no Description
2.01 ROTA This version has never been officially released but has primarily been used for rotatune
units and as spare part for correction of errors.
General remarks
If the compressor capacity was controlled by a 4-20 mA signal, the compressor would
not start even though the signal exceeded 4.8 mA (5% capacity). This has now been
rectified.
At the initial start-up of UNISAB II, the start number and system number were set at a
fixed value of “0”. This had the effect that the compressor could not start and operate
in auto and remote control. This has now been rectified.
Multisab sequence was not optimized to support correct operation between frequency
controlled and conventional compressors. This has now been rectified.
The menu lines CAPACITY and VOLUME have been moved from the MOTOR picture
in the main menu to a new picture called CAPACITY. This picture is found below the
SET UP menu. See menu tree in the beginning of your manual.
There is a new menu line below the MOTOR picture which is called MOTOR FRE-
QUENCY. It indicates motor revolutions per minute when the compressor capacity is
regulated by a frequency converter.
The COP picture has been moved from the CALIBRATION menu to the CONFIGURA-
TION menu.
0178_440_en.fm

Configuration. In the measuring unit picture, there is a new menu line, MOTOR INPUT.
See the configuration section in your manual for installation.
Screw compressors
When operating in 100% capacity for a longer period of time, sometimes the compres-
sor would simply stop for no reason with the alarm for capacity error on. This has now
been rectified.
The following compressor type has been added: Gram GST screw compressor with
stepless capacity slide control and control of the volume slide in three steps by means
of two solenoid valves. Volume ratios: 2.2-3.5-5.
The volume transmitter can now be calibrated by means of software calibration. See
the calibration section in your manual.
The “feedback” signal from a frequency converter can now be calibrated by means of
software calibration. See the calibration section in your manual.
Configuration. In the measuring unit picture, there is a new menu line, CAP/FREQ.
See the configuration section in your manual for installation.
A new timer has been introduced in connection with GST compressors: Timer 34 Vi-
pause.
Reciprocating compressors
HPO/HPC. High warning is increased from 25.0 bar to 25.2 bar. Thus, the limiter zone
is now 25.0-25.2 bar.

0178-445 - ENG 203/222


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version no Description
2.02.1 This version replaces all prior versions.
General remarks
4-20 mA initialization error during UNISAB II restart. The display was flashing during
reconnection of power supply to UNISAB II. The error first occurred in version 2.01. It
has now been rectified.
The ROTA concept has now been extended to include reciprocating compressors with
frequency converters and screw compressors controlled by a combination of frequen-
cy, capacity slide and volume slide.
The multisab system now handles both frequency controlled screw and reciprocating
compressors which operate in sequence with either reciprocating and/or screw com-
pressors.
The “copy EEPROM” function, when changing parts in UNISAB II or at low battery volt-
age and a simultaneous reconnection of power supply, has now been changed. Thus
it is no longer necessary to enter password to reply YES, simply press “arrow left” to
restart. See service section in the manual for further details.
UNISAB evolution plant. When simultaneously using the function EVOLUTION and
CHILLER = YES in the configuration, the following error might occur: During operation,
the green diode on the front cover would start to flash for about one minute and then,
for no apparent reason, the compressor would stop. This has now been rectified.
UNISAB evolution plant. When simoltaneously using the function EVOLUTION and
CHILLER = YES in the configuration, the following error might occur: In case of a
pause before compressor start-up, the compressor would not start. The start delay tim-
er kept counting in negative seconds instead of stopping at 0 and starting the compres-
sor. This has now been rectified.
Configuration. There are two new menu lines in the picture MOTOR below the CON-
FIG menu, namely, MINIMUM frequency and MAXIMUM frequency. See the configu-
ration section.
Multisab error in connection with direct capacity control: When disrupting the 4-20 mA
remote control signal for several UNISAB II compressors at the same time, not all of
the compressors will start when the signal returns. This has now been rectified. The
error might also occur in EPROM version 1.13 and earlier.
In the Instruction Manual of version 2.02 and in later manuals, there are charts of “UN-
ISAB II Settings” and “UNISAB II diagnosis” in the back of this book. These used to be
in the Starting-up Manual.
All new menus and parameters of this version are primarily shown in English only,
even if a language other than English has been chosen. However, the following five
languages are fully translated: Danish, Swedish, Dutch, French and Italian. The re-
maining languages will be updated in later versions as they are being translated.
Screw compressors
When regulating the discharge pressure, the regulator would be out of order and thus
capacity could either be 0% or 100% but could not settle at medium capacity. This has
now been rectified.
Timer values concerning the prelubrication function for screw compressors was not in-
itialized correctly after factory reset - only if followed by a power reset. This has now
been rectified.

204/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version Description

There was an error in the regulator, which would only occur when a limiter was in passive
mode and when, at the same time, more capacity was required. This error caused the ca-
pacity to decrease very slowly as long as the limiter was in passive mode. This has now
been rectified.
The following compressor type has been added: SAB110SR/LR.
The PID-regulator function has been thoroughly explained in this version of the manual and
it contains practical examples of general usage of this function.
Known errors of this version:
General remarks
Multisab. Sequential control of several rotatune compressors in the same system as con-
ventional compressors (rotatune master/slave operation) has not yet been implemented. It
is expected to be implemented in version 2.02.2.
The following concerns compressors which control frequency on the frequency converter
by means of a 4-20 mA output signal from the UNISAB II and only in MANUAL OPERA-
TION MODE:
In MANUAL MODE, the compressor capacity will be regulated back to the capacity it had
before the limiter went into active MODE, as soon as the limiter is no longer in function.
Therefore, if capacity is manually regulated up to e.g. 80% and the limiter is activated and
0178_440_en.fm

forces capacity down to e.g. 30%, capacity will then automatically be regulated back to 80%
as soon as the limiter is no longer in function. This regulation takes place without activating
the capacity keys.
UNISAB II Evolution: When changing baudrate for port 1 (when using Evolution PLC), a
factory reset must be carried out or UNISAB II must be turned off and on. If this is not car-
ried out, the new communication speed will not be initialized and communication to the PLC
cannot be effected.
Screw compressors
SAB110SR/LR. During operation for a long period of time in remote or auto control, it might
be quite some time before capacity is decreased even though the regulator requires less
capacity.
Reciprocating compressors
Motor frequency control in connection with two-stage reciprocating compressors has not
yet been fully implemented.

0178-445 - ENG 205/222


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version Description

2.02.2 General remarks


Multisab sequence with several rotatune compressors running in the same system is now
implemented but has not yet been tested. It is expected to be released in the next version.
UNISAB II evolution; when changing communication speed on port 1 for use with Evolution
PLC, the new speed is now initialised automatically.
Superuser password has been changed.
Textual errors have been corrected in the Swedish instruction manual.
When installing eprom version 2.02.2 instead of an earlier version and at the same time
maintaining battery voltage on UNISAB II, the contrast now initialises at a value between
20 and 80 when pressing the “R” key. Afterwards, the contrast can be adjusted by simulta-
neously activating the “Reset” key and the “arrow up” or “arrow down” key.
Screw compressors
Screw compressor SAB110SR/LR. When operating at 100% capacity for a long period of
time in either remote or auto control, the length of period until capacity was reduced was
disproportionately long even though the regulator had required less capacity. This has now
been rectified.
Due to an error in the outer PID-regulator, a screw compressor about to stop would keep
running at minimum capacity because the “delay before stop” timer was reset and started
recounting before the compressor stopped. The problem only appeared when e.g. the suc-
tion pressure value passed the limit between NZ and the lower P-band. This problem ap-
plies to all regulating modes. Furthermore, the compressor would run up capacity a little
every time this limit was passed. This has now been rectified.
Known errors
When using the “copy eeprom” function, all timer values are reset at default values.

206/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version Description

2.03.1 General remarks


Mode of operation has been changed for timer no. 32 "Low suction pressure". Now the
alarm for low suction pressure can be suppressed for up to 60 seconds during both start-
up and operation.
Rotatune multisab function; the taking over function has been corrected. Now a master
compressor includes subsequent stopped rotatune compressors (slaves) in the taking over
calculation when attempting to take over a subsequent screw compressor. Earlier, it only
included its own 60% free capacity in the taking over calculation. See Rota appendix.
A false warning for low suction pressure when the compressor is in stopped control mode
has been corrected. Before, the warning disappeared when control mode was changed
from stopped but it generated false warnings which communicated with the UNISAB net-
work either via the Sabcom II driver or the Comsab II module. The warning typically ap-
peared when the suction pressure lay between the low alarm default value and the low
warning default value.
Rotatune multisab. An error regarding several systems in the same network has been cor-
rected. When a rotatune compressor was operating with several systems in the network
(e.g. low and high pressure systems) the multisab system would fail. A slave which was
starting up would immediately stop after only a few seconds.
Rotatune multisab. When a master compressor was stopped due to an alarm, the slave did
not automatically adopt the role of master regulator. This has now been rectified.
0178_440_en.fm

Screw compressors
Timer no. 7 "Prelubrication" has been changed for screw compressors of the SABxxxHR
type. Prelubrication has been changed from a default value of 10 seconds to 0 seconds.
The compressor will still be prelubricated but the compressor motor must start up immedi-
ately when the signal of the oil flow switch is present.
An error has been corrected in rotatune multisab between two rota screw compressors.
When two rotatune compressors were running in parallel, the master ran with a fixed ca-
pacity of e.g. 60% and the slave hunted up and down with a variation of 5-10% around the
the master’s 60%=50-70% when it should be running with the same capacity as the master.
To compensate for this, the default values for the internal regulator on the UNISAB II on the
slave compressor must be changed. P-band should be changed from 200 to 400%, T.int.
from 30 to 90 seconds and minimum pulse should be changed to 0.3 seconds.
Reciprocating compressors
Reciprocating compressor Mk4. A new timer no. 11 is introduced, "Filter diff. High". On Mk4
reciprocating compressors, the oil filter differential pressure is monitored by an electrical
switch. Digital input 9 is usually open. If the differential pressure exceeds the set value, the
switch gives an input signal. If this signal is active for more than 300 seconds, the warning
"high oil differential pressure" is given. There is no operating limiting function in this warn-
ing. See wiring diagrams for installation of this switch.
The auxiliary output function has been corrected. When using the auxiliary output function
for maximum and minimum capacity respectively, this did not function correctly for rotatune
machines in earlier eprom versions.
Rotatune reciprocating compressors. An error has been corrected in the outer regulator.
The neutral zone value was doubled so that it applied both above and below the set point.
Now, the neutral zone is divided in equal parts above and below the set point. See also the
section about regulation in this manual.

0178-445 - ENG 207/222


Rev. 03.09
UNISAB II 2.03
15. List of Versions

Version Description

Known errors
When using the "copy eeprom" function, all timer values are reset at default values.
When using the 4-20 mA analog output function from UNISAB II to a frequency
converter to control the speed of the compressor motor the following problem is
found:
When running in auto or remote control mode, it is still possible to change the
speed of the compressor motor with the operating keys capacity up or capacity
down. This should only be possible in manual control mode.

208/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
16. Spare parts for UNISAB II

16. Spare parts for UNISAB II


Item Part number

Normal spare parts set 3084-394

Set of accessories - UNISAB II 1572-018

EPROM tongs 1613-002

EEPROM tongs 1613-003

EEPROM (2kB-serial) - To be used in version Eprom 1.10 and earlier versions. 1571-015

EEPROM (4kB-serial) - To be used in version Eprom 1.12 and later versions. 1571-018

Certificate set 3084-383

Normal spare parts set 3084-394

Front cover with sheet and display, YORK Refrigeration logo 1573-008

Front cover with sheet and display, Sabroe logo 1573-007

CPU print (rev. C) 1572-026

Relay print (rev. G) 1574-016


0178_441_en.fm

Pressure transducer dia.10 AKS32R-1-9 bar 1) 1373-249

Pressure transducer dia.10 AKS2050-1-25 bar 1373-271

Pressure transducer dia.10 AKS32R-1-59 bar 2) 1373-251

Pt100 sensor 4-conductor (1/2" thread) 3) 1373-245

Pt100 sensor 4-conductor (1/4" thread) 4) 1373-252

Pt100 sensor 4-conductor (1/4" thread) 5) 1373-264

Position transmitter 6) 3448-004

Position transmitter 7) 3448-___

Position transmitter 8) 3448-___

Position transmitter 9) 3448-___

Notes: SAB 163B, SAB 163H (not HR) and SAB


1) Not used for HPO/HPC compressors 202 compressors.
2) Only used forHPO/HPC compressors 7) Only for SAB 250 and SAB 330 compres-
3) Units supplied before November 1995 sors.
4) Units supplied after 1 November 1995 8) Only for SAB 80 compressors.
5) Units supplied after 1 January 1997 9) Only for SV 10/20 compressors (not Ro-
6) Only for SAB 110, SAB 128H (not HR), tatune)

0178-445 - ENG 209/222


Rev. 03.09
UNISAB II 2.03
16. Spare parts for UNISAB II

210/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03
17. Supplementary Material

17. Supplementary Material


"Quick Reference"Leaflet Data sheet for Pt100 sensor - Temp./resistance
Installing a data communications cable0171-745 table0178-411
Data sheet for AKS 32R -(-1/+9 bar)0178-410 Capacity and Vi pos. transmitters0178-412
Data sheet for AKS 2050 - (-1/+25 bar)0178-414
Electrical Wiring Diagrams for:
• Mounting of ground log and emergency stop • Screw compressors(page 1-4, 10-14,
(page AC038_13) 16-22, 25-32, 35-36, 39-40)
2347-002 3448-235
• Voltage equalization (page AC040_10) • Reciprocating compressors (page 1-40)
2347-002 3448-236
0178_442_en.fm

0178-445 - ENG 211/222


Rev. 03.09
UNISAB II 2.03
17. Supplementary Material

212/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

Index

A Additional unload
reciprocating compr. ........................................................................................ 39
Adjusting slide velocity .......................................................................................... 97
Alarm
alarm from Chiller ............................................................................................. 57
auxiliary input signal ......................................................................................... 55
capacity .......................................................................................................... 103
capacity error
screw compr. .............................................................................................. 55
Cooling fan error .............................................................................................. 56
Error in diagnosis- EEPROM ........................................................................... 57
Evolution
no communication to PLC .......................................................................... 58
full flow pump error
screw compr. .............................................................................................. 56
high motor temperature .................................................................................... 56
identification numbers Alarms-warnings .......................................................... 59
Limiting brine temperature ............................................................................... 57
Limiting discharge pressure ............................................................................. 57
0178-445IX.fm

Limiting discharge temperature ........................................................................ 57


Limiting hot water ............................................................................................. 57
Limiting suction pressure ................................................................................. 57
low lubricating pressure monitoring ................................................................. 58
motor error ....................................................................................................... 55
motor overload ...........................................................................................55, 56
no communication to Chiller ............................................................................. 57
no starting permission ...................................................................................... 55
oil pump error
SAB 80 ....................................................................................................... 56
screw compr. .............................................................................................. 56
oil rectifier error ................................................................................................ 57
oil system error
screw compr. .............................................................................................. 55
overload discharge pressure ............................................................................ 56
suction gas superheat ...................................................................................... 54
Vi-position error ................................................................................................ 57
Wrong starting number in sequence ................................................................ 57
Analog inputs
numbering ...................................................................................................... 145
Auto
Start ................................................................................................................. 34
stop .................................................................................................................. 34

0178-445 - ENG 213/222


Rev. 03.09
UNISAB II 2.03

Automatic setting of a new zero point


(SAB 202) ........................................................................................................99
Aux.
output .............................................................................................................119

B Baud rate
port 1 ................................................................................................................41
port 2 ................................................................................................................42
selecting ...........................................................................................................39
Booster
menu description ..............................................................................................35
Brine
temperature ......................................................................................................33
Brine temperature
Calibration ......................................................................................................126

C Cabinet
open the cabinet ..............................................................................................13
Calculated Vi position ..........................................................................................102
Calibration ...........................................................................................................125
Capacity
corrected capacity ............................................................................................98
Capacity measuring system
Long-Stroke Capacity-Rod
Calibration ................................................................................................130
Turning Transmitter
Calibration ................................................................................................128
Change to full load ...............................................................................................102
Change to part load .............................................................................................102
Checklist ..............................................................................................................173
Chiller
menu description ..............................................................................................41
Circuit board with light diodes ..............................................................................147
Clima control
menu description ..............................................................................................39
Climate control
description ........................................................................................................95
code plug ...............................................................................................................12
Cold store
funktion ..........................................................................................................120
menu description ..............................................................................................39
Compressor
adjusting slide velocity .....................................................................................97
slide data ............................................................................................. 42, 43, 44
Configuration
menus ..............................................................................................................27
Control and surveillance ......................................................................................111

214/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

Aux. output ..................................................................................................... 119


Capacity down blocked .................................................................................. 120
Cold store function ......................................................................................... 120
COP setting .................................................................................................... 119
External start permission- immediate stop ..................................................... 117
External start permission- normal stop .......................................................... 118
FV 19 with oil pump ....................................................................................... 115
FV 24/26 with oil pump .................................................................................. 114
GSV/RWF with oil pump ................................................................................ 113
Motor current measuring ................................................................................ 118
motor power measuring ................................................................................. 119
Power management system .......................................................................... 120
Reciprocating compressors ........................................................................... 117
SAB 110/128/163 Mk 2 without oil pump ....................................................... 116
SAB 128/163 Mk 2 Booster with oil pump ...................................................... 116
SAB 163 Mk 1 with oil pump .......................................................................... 117
SAB 202/ 163 & 128H MK3 with oil pump ..................................................... 111
SAB 283/ 330 and 355 with oil pump ............................................................. 112
SAB 80 with fitted (mechanical) oil pump ...................................................... 113
SAB128/163 HR with oil pump ....................................................................... 111
Thermistor connection ................................................................................... 119
VMY Mk 2 and 2.5 with built-in oil pump ........................................................ 116
0178-445IX.fm

VMY Mk 3 without full flow pump ................................................................... 116


VMY Mk3 with full flow pump ......................................................................... 111
Control mode ......................................................................................................... 79
COP
active ................................................................................................................ 40
Diagnosis ....................................................................................................... 142
setting ............................................................................................................ 119

D Danbuss
menu description .............................................................................................. 41
Data communication cable
installing the data communication cable ........................................................ 164
Define refrigerant R000 ....................................................................................... 122
Diagnosis
Analog inputs ................................................................................................. 140
COP ............................................................................................................... 142
Digital inputs .................................................................................................. 140
Digital outputs ................................................................................................ 140
Examine memory ........................................................................................... 141
Insp. old alarms .............................................................................................. 137
Misc. functions ............................................................................................... 139
New password ............................................................................................... 141
No. of alarms .................................................................................................. 141
pictures .......................................................................................................... 137
serial number ................................................................................................. 141
Software version ............................................................................................ 139

0178-445 - ENG 215/222


Rev. 03.09
UNISAB II 2.03

Zero capacity pos. ..........................................................................................142


Digital inputs
Diagnosis .......................................................................................................140
Digital inputs and outputs
Numbering .....................................................................................................143
Digital outputs
Diagnosis .......................................................................................................140
Discharge pressure
menu description ..............................................................................................33
overload ...........................................................................................................56
Display
contrast ............................................................................................................25
description ........................................................................................................13
in Bar or °C/R ...................................................................................................20
Display indications
various limiters ...............................................................................................109

E Economizer
high suction pressure .......................................................................................35
low capacity .....................................................................................................35
menu description ..............................................................................................35
Electrical slide control
SAB 250 and SAB 330 ...................................................................................101
Evolution
no communication to PLC ................................................................................58
warning from PLC ............................................................................................58
Examine memory
Diagnosis .......................................................................................................141
EXT.COOL
menu description ..............................................................................................34
EXT.HEAT
menu description ..............................................................................................34
External input
universal regulators ..........................................................................................91

F Factory setting
restore setting ..................................................................................................41
Factory settings
return to ... ........................................................................................................25
Flow factor
menu description ..............................................................................................41
Front panel
control/recording section ..................................................................................14
green lamp .......................................................................................................14
Red lamp ..........................................................................................................14
Yellow lamp ......................................................................................................14

216/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

Function
changing a function .......................................................................................... 24

G Green ..................................................................................................................... 14
Grounding ............................................................................................................ 166

H High difference pressure Limiter .......................................................................... 107


HP
on two stage ..................................................................................................... 36
HP on TWO-STAGE ............................................................................................ 121
Hydraulic slide systems
Calibration ...................................................................................................... 127

I Input signal
Auxiliary input signal
screw compressors .................................................................................... 49
auxiliary input signal
HPO-HPC ................................................................................................... 52
recip.compr. ................................................................................................ 51
0178-445IX.fm

L Languages
list of languages ............................................................................................... 26
Limiting functions
Standard limiters ............................................................................................ 105
Liquid subcool
menu description .............................................................................................. 41
List of Versions .................................................................................................... 197
Loading sequence ............................................................................................... 180
Long-Stroke Capacity-Rod
Adjusting ........................................................................................................ 131

M Manual setting of a new zero point ........................................................................ 99


Manual zero ........................................................................................................... 40
Mecanical zero ...................................................................................................... 40
Menu Tree
One-stage Reciprocating Compressor ............................................................. 17
Screw Compressor .......................................................................................... 16
Two-stage reciprocating compressor ............................................................... 18
Motor
alarm for cooling fan error ................................................................................ 56
alarm for high motor temperature .................................................................... 56
alarm motor overload ....................................................................................... 55
current
calibration ................................................................................................. 127

0178-445 - ENG 217/222


Rev. 03.09
UNISAB II 2.03

limiter ........................................................................................................106
measuring .................................................................................................118
range ..........................................................................................................38
motor error alarm .............................................................................................55
motor overload alarm .......................................................................................56
power measuring ...........................................................................................119
signal ................................................................................................................42
size ...................................................................................................................41
Multisab
compressor. no. 1 to 14 ...................................................................................35
description ........................................................................................................74
parallel control ..................................................................................................77
preferred master ..............................................................................................35
regulating Setup .............................................................................................169
regulation .......................................................................................................167
special timers
recip.compr. ................................................................................................73
state .................................................................................................................75
system setup ..................................................................................................168
take over ..........................................................................................................41

N New password
Diagnosis .......................................................................................................141
No. of alarms
Diagnosis .......................................................................................................141
Node no
port 1 ................................................................................................................41
port 2 ................................................................................................................42

O Oil cooling
selecting ...........................................................................................................38
setting ..............................................................................................................37
Oil heating ...........................................................................................................122
Oil pump
full flow
screw compr. ..............................................................................................34
Oil rectifier
selecting ...........................................................................................................40
Oil return
reciprocating compressors .............................................................................121
Operating sequence ............................................................................................183

P Part load and Full load .........................................................................................101


Password
Applying the password .....................................................................................22
Changing the password ...................................................................................22

218/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

description ........................................................................................................ 22
Resetting the password ................................................................................... 23
P-band
factor ................................................................................................................ 71
start delay ........................................................................................................ 71
stop delay ......................................................................................................... 71
PBF ........................................................................................................................ 72
PID
controller .......................................................................................................... 81
Port 1
menu description .............................................................................................. 40
Port 2
menu description .............................................................................................. 41
Position indications .............................................................................................. 102
Pref. master = START
Starting- and system numbers ....................................................................... 178
Prelubrication
menu description .............................................................................................. 34
Press
menu description .............................................................................................. 42
Pressure
measured/calculated pressure levels
0178-445IX.fm

recip.compressors ...................................................................................... 50
screw compr. .............................................................................................. 48
measured/calculated pressures/temperatures
HPO-HPC ................................................................................................... 51
Pressure transducers
Calibration ...................................................................................................... 125
Printed circuit board, light diodes ........................................................................ 146

R Regulators ............................................................................................................. 79
Replacing
CPU print and EEPROM ................................................................................ 160
the battery ...................................................................................................... 163
the CPU print ................................................................................................. 159
the door .......................................................................................................... 159
the EPROM (program) UNISAB II .................................................................. 161
the relay print ................................................................................................. 160
the serial EEPROM (diagnosis) ..................................................................... 162
Rotatune
menu description ........................................................................................42, 43

S Sequence
The plant does not run in sequence ............................................................... 194
Serial number
Diagnosis ....................................................................................................... 141
Service ................................................................................................................. 159

0178-445 - ENG 219/222


Rev. 03.09
UNISAB II 2.03

Set points
control with current input ..................................................................................91
on regulators ....................................................................................................90
Settings
regulating parameters
reciprocating compressors .........................................................................86
SAB 330 .....................................................................................................90
screw compressors .....................................................................................88
Short-Stroke Capacity-Rod
Adjusting ........................................................................................................132
Slide brake control ...............................................................................................102
Spacer block
built-in space block ........................................................................................100
Spare parts for UNISAB II ...................................................................................209
Special Limiters ...................................................................................................107
State of take-over ................................................................................................189
State of transfer ...................................................................................................188
Suction Pressure
menu description ..............................................................................................33
Superuser keyword
Diagnosis .......................................................................................................141
Swept volumen
menu description ..............................................................................................39
System numbers ..................................................................................................177

T Temperature
Measured and calculated temperatures
screw compressors .....................................................................................50
measured and calculated temperatures
screw compressors .....................................................................................49
measured/calculated pressures/temperatures
HPO-HPC ...................................................................................................51
Timer description
reciprocating compressors ...............................................................................69
screw compressors ..........................................................................................66
Timers
menu ................................................................................................................61
reciprocating compressor values .....................................................................65
screw compressor values ................................................................................63
Trouble shooting ..................................................................................................137
Trouble-shooting
The plant cannot start ....................................................................................194
Trouble-shooting diagrams
General trouble-shooting, UNISAB II .............................................................156
Start compressor
in AUTO, continued ..........................................................................153, 154
in MANUAL, continued .............................................................................150
Start of compressor

220/222 0178-445 - ENG


Rev. 03.09
UNISAB II 2.03

in AUTO mode .......................................................................................... 152


in MANUAL mode ..................................................................................... 149
Start Screw comp,
Prelub. in MANUAL, continued ................................................................. 151
Start Screw comp.
Prelub. in AUTO mode, continued ............................................................ 155

U Universal regulator
ext.input ........................................................................................................... 91
Unloading sequence ....................................................................................182, 185

V Value
changing a value .............................................................................................. 23
Variable Zero position ............................................................................................ 98
Vi
mode ................................................................................................................ 41
Volume ratio
auto .................................................................................................................. 34
Volume ratio slide .................................................................................................. 97
0178-445IX.fm

W Warning
Evolution
warning from PLC ....................................................................................... 58
identification numbers alarms / warnings ......................................................... 59
watch the oil pressure ...................................................................................... 57
Water
cooling
recip. compr. ............................................................................................... 36
menu description .............................................................................................. 33

Y Yellow .................................................................................................................... 14

Z Zero capacity pos.


Diagnosis ....................................................................................................... 142
Zero point
automatic setting .............................................................................................. 99
configuration .................................................................................................. 100
manual setting of a new zero point .................................................................. 99
Zero pos.
menu .............................................................................................................. 101

0178-445 - ENG 221/222


Rev. 03.09
UNISAB II 2.03

222/222 0178-445 - ENG


Rev. 03.09
2.02-020911 IVH
Date: ____________ Init: ______

Settings for UNISAB II 2.03

Customer: ROC No.:

Enduser: Order No.:

Plant Type:

Compressor Shop No.: Compressor Type:

Local Compr. No. : Software version/date

0179-005-EN 1
2.02-020911 IVH

Settings for UNISAB II 2.03

Setup>Configuration
>Control >Economizer >COP >Measuring unit
No Function Setting No Function Setting No Function Setting No Function Setting
01 Control On 01 Eco Low Cap. 01 COP Active 01 Press./Temp.
02 Auto Start 02 Eco High Suction 02 Flow Factor 02 Press
03 Auto Stop 03 Liq. Sub-cooling 03 Motor Signal
04 Cold Store >Motor 04 Motor Input
05 Climate Control No Function Setting >Communication 05 Cap/Freq
01 Range Motor Current No Function Setting >Unit Plant
>Compressor 02 Range Motor Power 01 Danbuss No Function Setting
No Function Setting 03 Motor size kW 02 Compressor No. 01 Refrigerant
01 Compressor Type 04 Rotatune 03 Baud Rate 02 Chiller
02 Swept Volume 05 min freq 04 Port 1 >Factory reset
03 Booster 06 max freq 05 Node No 01 Factory Reset
04 Volume Ratio >Multisab 06 Baud Rate
05 Economizer No Function Setting 07 Port 2
06 Mech. Zero 01 Pref. Master 08 Node No
07 Manual Zero 02 Common Evap/Cond 09 Baud Rate
08 Vi Mode % 03 HP on Two Stage 10 Profibus
09 Add. Unload 04 Take Over 11 Node No
>Oil system 12 Baud Rate
No Function Setting
01 Pre-lubrication
02 Full Flow Pump
03 Oil Cooling
04 Water Cooled
05 Oil Rectifier

0179-005-EN 2
2.02-020911 IVH

Settings for UNISAB II 2.03

Alarm-/Warning Limits & Regulator High High Low Low Set pt. Set pt. NZ PB T. T. MIN RUN
Settings (1) Alarm Warning Warning Alarm No. 1 No. 2 INTE DIFF PULS TIME

Suction>Suction pressure [ºC/R]


Suction>Suction superheat

Discharge>Disch. superheat
Oil>Oil pressure
Oil>Diff. pressure (*S)

Oil>Oil temperature
Motor>Motor current
Motor>Motor Power
Setup>Capacity>Capacity (*S)

Setup>Capacity>Vi Position (*S)

Intermediate>Interm. temperature (*R)

All the empty/not used squares must always be filled out. ///////////

The availability of the areas framed is dependent upon the configuration of the UNISAB II.

Setup>Control (1+2) Setup>Multisab>Multisab state (2) Setup>Diagnose> Setup>Language (2) >Setup>Diagnose


Compressor Control Start No. System No. Sys. Controller Software version / date Contrast Language >Misc. functions
Brake Delay

0179-005-EN 3
2.02-020911 IVH

Settings for UNISAB II 2.03


Setup>Calibrate> Setup>Calibrate> Setup>Calibrate> Setup>Calibrate>
Press Transducer Brine Temp. (2) Cap. Pos Motor Freq
Suction Adjust Brine Adjust Cap. Pos Motor Freq
Discharge Adjust Cap. Zero Ad Frq. Zero Adj
Oil Adjust Cap. 100 Adj Freq. 100 Adj
Diff. Adjust
Imed. Adjust

Setup>Calibrate> Setup>Calibrate> Setup>Calibrate> Setup>Calibrate>


Vi position 4-20mA Input Aux. Output Cap. Limits (1)

Vi Position 4mA Activate When Signal Low


Vi. Zero Adj 20mA Signal High
Vi. 100 Adj Used at Limit High

Setup>Timers>Timers Setup (1)

No Function Setting No Function Setting No Function Setting


Prelubrication (*S)
01 Start-Start Delay 07 25 Oil Rect. Start
Delay Down (*R)
02 Stop-Start Delay 08 Transfer max 26 Oil Rect. Delay
03 Start Delay 09-20 NOT ADJUSTABLE 27 Oil Rect. Disable
04 Stop Delay 21 Motor Start 28 Start HP
05 Suction Ramp 22 PMS Feedback 29 NOT ADJUSTABLE
Slide Max (*S) F.F. Pump Start (*S) 30 Cap. Negative (*S)
06 23
Delay Up (*R) Oil Cool On (*R) 31 Start Unload (*S)
Oil Pump Start (*S) 32 Low suct. press
24
Oil Return (*R) 33 NOT ADJUSTABLE

0179-005-EN 4
2.02-020911 IVH

Settings for UNISAB II 2.03

Setup>Timers> Setup>Timers> Setup>Timers> Setup>Timers>


Service (2) P Band Factor (1) Transfer (1) Take Over (1)

On Time Delay Up (*R) Factor Down (*R) Factor Up (*R)

(Service Hours) Delay Down (*R) Zone (*R) Factor Start (*R)

Start Delay Zone (*R)

Stop Delay

Notes:

*(S) = Screw, *(R) = Reciprocating


(1) The value(s) will be changed to factory settings by a “Factor Reset”.
(2) The value(s) are not stored in the EEPROM and will therefore be changed to ‘initial settings’ after a “Copy EEPROM” messages on the display.
The hour counter “Setup>Timers>Service>On Time” will be reset to zero.

0179-005-EN 5
Date: Init.:

96.09

Diagnosis for UNISAB II

Customer: Ordre no.:

Compressor shop no.: Compr. type:

Diagnosis > Inspect old alarms


Alarm text (type of alarm)
Date and time of alarm

Diagnosis > Inspect old alarms > Ctrl state Current operating conditions Unit
Compressor Control Text
Compressor State Text
Start no 0-14
System no 1-14
Multisab state Text
On time Hour
Since start Sec/Hour
Rev. 0

Diagnosis > Inspect old alarms > Current Unit Diagnosis > Inspect old Diagnosis>
Measure values operating alarms >
1661-215-EN

conditions
No Input Output Digital Digital
Input Output
Suction temp. °C 1
Suction press. °C/R 2
Suction superheat °C 3
Disch. temp °C 4
Disch. press. °C/R 5
Disch. superheat °C 6
Brine temp. °C 7
Oil temp. °C 8
Oil press. BAR 9
Diff. press. (S) BAR 10
Intermediate press. (R) °C/R 11
ÉÉÉÉ ÉÉÉÉ
Intermediate temp. (R) °C 12
ÉÉÉÉ ÉÉÉÉ
Vi position (S) % 13
ÉÉÉÉ ÉÉÉÉ
Capacity position % 14
ÉÉÉÉ ÉÉÉÉ
Ext. input 15
ÉÉÉÉ ÉÉÉÉ
Motor current Amp 16
ÉÉÉÉ ÉÉÉÉ
17
ÉÉÉÉ ÉÉÉÉ
Notes:
18
ÉÉÉÉ ÉÉÉÉ
* (S) = Screw, (R) = Reciprocating

1661-215-EN Rev. 0 1

You might also like