You are on page 1of 14

1 / 12

Communication
Instruction Manual
(for DC1000 series)

2 / 12

SPECIFICATION
1.INTERFACE
2. Connection
method
3.Coommunication
distance
4.Communication
speed
5.Synchronous
6. Maximum
connection
7. Communication
Code

EIA standard based on RS-232C


EIA standard based on RS-485
3 wire system, Half-duplex Single-drop connection(RS232)
2 wire system, Half-duplex multi-drop connection(RS485)
RS232C : 15meters(max.)
RS485 : 1.2kilo-meters(max.)
110, 300, 1200, 2400, 4800, 9600 bps
It is indicated in BAUD of the controller. Defalut=2400

Start / Stop bit


RS232C : 1 point
RS485 : 30 sets including a host computer
ASCII

Communication DATA
1.DATA FRAME
1 Start bitData Bits 8ODD Parity1 Stop bit
0

B0

B1

B2

B3

B4

(Data bits = 8

B5

B6

B7

)
Parity bit
(odd parity)

1 Start bit

1 Stop bit

2.DATA FORMAT
You must send HEX code as below
NAME

DESCRIPTION

LENGTH

CMD

Command

1 BYTE

XIDNO

The ID No. of controller

1 BYTE

CHNO

Reservationdont care

1 BYTE

XADDR

Address

1 BYTE

XDATA1

HIGH BYTE of DATA

1 BYTE

XDATA2

LOW BYTE of DATA

1 BYTE

CHKSUM

Checksum

1 BYTE

CMD

R (to READ from DC controller)


M(to MODIFY the data into controller temporarily)
After controller restarted, the modified data will be disappeared

3 / 12

W(to WRITE the data to controller)


The HEX CODE of R, M, W are same as followings

R:52H,
XIDNO

M:4DH,

W:57H

Range1(01 H)~100(63 H)
It is indicated as IDNO of the controller

CHNO

Range(00 H ~ FF H)

XADDR

See Appendix(XADDR)

XDATA 1

HIGH BYTE of DATA

XDATA 2

LOW BYTE of DATA

CHKSUM

CHECK SUM CMDXIDNOCHNOXADDR


XDATA 1XDATA 2
Example) 4DH + 01H + 00H +00H +03H +E8H = 01 4AH
CHECK SUM 4AH

When WRITE(or Modify) to controllerthe Data Length is 7 BYTE


CMD XIDNO CHNO XADDR XDATA 1 XDATA 2 CHKSUM
When READ from controllerthe Data Length is 8 BYTE
(Including Header07H)
07H CMD XIDNO CHNO XADDR XDATA 1 XDATA 2 CHKSUM

4 / 12

COMMUNICATION EXAMPLES
Modify SP to 123.4 (The ID of controller is 20)
CMD

MODIFY(M)4D H

XIDNO

20 (decimal) 14H(Hex)

CHNO
XADDR

00 H (Dont care)
00 H (The XADDR of SP)

XDATA1XDATA2

1234(decimal) = 04D2H(hex)

CHKSUM 4DH + 14H + 00H +00H +04H +D2H = 0137H


The DATA are be send to the controller as HEX CODE 4D14 0000 04D2 37
Write SP to 123.4 (The ID of controller is 20)
CMD

WRITE(W)57 H

XIDNO

20 (decimal) 14H(Hex)

CHNO
XADDR

00 H (Dont care)
00 H (The XADDR of SP)

XDATA1XDATA2

1234(decimal) = 04D2H(hex)

CHKSUM 57H + 14H + 00H +00H +04H +D2H = 0141H


The DATA are be send to the controller as HEX CODE 5714 0000 04D2 41
Read PV from controller (The ID of controller is 1)
CMD

READ(R)52 H

XIDNO

1 (decimal) 01H(hex)

CHNO
00H (Dont care)
XADDR
80 H (The XADDR of PV)
XDATA1 & XDATA2 = 0000H
CHKSUM 52H + 01H + 00H +80H +00H +00H = 00D3H
The DATA are be sent to the controller as HEX CODE 5201 0080 0000 D3
Wait about min. 100ms

5 / 12

Controller reply07 4D 00 00 00 xxyy zz

PV

CHECK SUM=4DH + 00H + 00H + 00H


+ xxH +yyH(Not Include header 07H)

6 / 12

APPENDIX A (XADDR)
1) LEVEL1(for details, refer to OP-Manual)
OPTION XADDR Remark OPTION XAADR Remark OPTION XADDR Remark
80H PV
PV
Program Model
Manual
A3H
06H PTN=
21H
OUT%
PTN
SV_12
SV
OUTL
AT
AL1
AL2
AL3

00H
01H
02H
03H
04H
05H

output
SP
Output
Autotune
Alarm 1
Alarm 2
Alarm 3

SEG
TIMR
SV_1
TM_1
OUT1
SV_2
TM_2
OUT2
SV_3
TM_3
OUT3
SV_4
TM_4
OUT4
SV_5
TM_5
OUT5
SV_6
TM_6
OUT6
SV_7
TM_7
OUT7
SV_8
TM_8
OUT8

07H
08H
09H
0AH
0BH
0CH
0DH
0EH
0FH
10H
11H
12H
13H
14H
15H
16H
17H
18H
19H
1AH
1BH
1CH
1DH
1EH
1FH
20H

1,2,0
8(max.)
0~99.59

TM_12
OUT12
SV_22
PTN=1
TM_22
OUT22
Set
SV_32
(1)SP
(2)Time TM_32
(3)Output OUT32
SV_42
TM_42
OUT42
SV_52
TM_52
OUT52
SV_62
TM_62
OUT62
SV_72
TM_72
OUT72
SV_82
TM_82
OUT82

22H
23H
24H
25H
26H
27H
28H
29H
2AH
2BH
2CH
2DH
2EH
2FH
30H
31H
32H
33H
34H
35H
36H
37H
38H

PTN=2
set
(1)SP
(2)Time
(3)Output

2) LEVEL 2(for details, refer to OP-Manual)


OPTION XADDR Remark OPTION XAADR Remark OPTION XADDR Remark
39H Output 1 CYT1
3EH
43H
P1
CYT2
3AH
3FH
44H
I1
HYS1
HYS2
3BH
40H Output2 GAP1
45H
D1
P2
3CH
41H
46H
DB1
I2
GAP2
3DH
42H
47H Lock
ATVL
D2
LCK

7 / 12

3) LEVEL3(for details, refer to OP-Manual)


OPTION XADDR Remark OPTION XAADR
48H INPUT1 ALD3
54H
INP1
49H Analog
55H
ANL1
ALT3
4AH INP1
56H
ANH1
HYSA
4BH
57H
DP
CLO1
4CH Limit low CHO1
58H
LSPL
4DH Limit high CLO2
59H
USPL
4EH Analog
5AH
ANL2
CHO2
4FH INP2
5BH
ANH2
CLO3
50H
5CH
ALD1
CHO3
Alarm 1
51H
5DH
ALT1
RUCY
52H
5EH
ALD2
WAIT
Alarm 2
53H
5FH
ALT2
SETA

Remark OPTION XADDR Remark


60H Communi
IDNO
Alarm 3
61H cation
BAUD
Hysterisis SVOS
62H
63H
PVOS
Analog
OUT1
64H
UNIT
65H
SOFT
Analog
OUT2
66H
CASC
67H
Calibrate OUD
TRS
68H Control
OPAD
69H Set 50/60
HZ

4) LEVEL4(for details, refer to OP-Manual)


OPTION XADDR Remark OPTION XAADR Remark OPTION XADDR Remark
6AH
6EH
72H
SET1
SET5
SET9
6BH
6FH
73H
SET2
SET6
SET0
6CH
70H
74H
SET3
SET7
INP2
6DH
71H
75H
SET4
SET8
OUTY

8 / 12

APPENDIX B (INPUT1 SELECTION)


TYPE

CODE

RANGE
0.0~200.0C/0.0~392.0F
0.0~400.0C/0.0~752.0F

0.0~600.0C/0.0~1112.0F
0.0~800.0C/0.0~1472.0F
0.0~1000.0C/0.0~1832.0F
0.0~1200.0C/0.0~2192.0F
0.0~200.0C/0.0~392.0F
0.0~400.0C/0.0~752.0F

0.0~600.0C/0.0~1112.0F
0.0~800.0C/0.0~1472.0F
0.0~1000.0C/0.0~1832.0F
0.0~1200.0C/0.0~2192.0F

R
S
B
E
N

0.0~1600.0C/0.0~2912.0F
0.0~1769.0C/0.0~3216.0F
0.0~1600.0C/0.0~2912.0F
0.0~1769.0C/0.0~3216.0F
0.0~1820.0C/0.0~3308.0F
0.0~800.0C/0.0~1472.0F
0.0~1000.0C/0.0~1832.0F
0.0~1200.0C/0.0~2192.0F
0.0~1300.0C/0.0~2372.0F
-199.9~400.0C/-199.9~752.0F

-199.9~200.0C/-199.9~392.0F
0.0~350.0C/0.0~662.0F

W
PLII

0.0~2000.0C/0.0~3632.0F
0.0~2320.0C/0.0~2372.0F
0.0~1300.0C/0.0~2372.0F
0.0~1390.0C/0.0~2534.0F
-199.9~600.0C/-199.9~999.9F

-199.9~200.0C/-199.9~392.0F
0.0~400.0C/0.0~752.0F

0.0~400.0C/0.0~752.0F
0.0~800.0C/0.0~1472.0F

* The initial set in factory mode is K2 without any certain requirement.

HEX
00H
01H
02H
03H
04H
05H
06H
07H
08H
09H
0AH
0BH
0CH
0DH
0EH
0FH
10H
11H
12H
13H
14H
15H
16H
17H
18H
19H
1AH
1BH
1CH
1DH
1EH
1FH
20H

9 / 12

TYPE

CODE

RANGE
-199.9~600.0C/-199.9~999.9F
-199.9~400.0C/-199.9~752.0F

JIS
Pt100

-199.9~200.0C/-199.9~392.0F
0.0~200.0C/0.0~392.0F
0.0~400.0C/0.0~752.0F
0.0~600.0C/0.0~1112.0F
-199.9~600.0C/-199.9~999.9F
-199.9~400.0C/-199.9~752.0F

DIN
Pt100

-199.9~200.0C/-199.9~392.0F
0.0~200.0C/0.0~392.0F
0.0~400.0C/0.0~752.0F
0.0~600.0C/0.0~1112.0F
-199.9~600.0C/-199.9~999.9F
-199.9~400.0C/-199.9~752.0F

JIS
Pt50

-199.9~200.0C/-199.9~392.0F
0.0~200.0C/0.0~392.0F
0.0~400.0C/0.0~752.0F
0.0~600.0C/0.0~1112.0F

AN1
AN2
AN3
AN4
AN5

-10~10mV/-1999~9999
0~10mV/-1999~9999
0~20mV/-1999~9999
0~50mV/-1999~9999
10~50mV/-1999~9999

HEX
21H
22H
23H
24H
25H
26H
27H
28H
29H
2AH
2BH
2CH
2DH
2EH
2FH
30H
31H
32H
33H
34H
35H
36H
37H

11 / 12

APPENDIX C. Wiring Diagram


1. RS232C
(1) 9PIN(DTE)
Pin3(T)

RD
SD

Pin2(R)
Pin5(G)

SG

Shield wire

(2) 25PIN(DTE)
Pin2(T)

RD
SD

Pin3(R)
Pin7(G)

SG

Shield wire

2. RS485
(1) 9PIN(DTE)
Converter
Pin3(T)
Pin2(R)
Pin5(G)
Shield wire

1
2
3
4

Controller

T+
TRR+

DD+
Twisted pair wire
(with shield)

(2) 25PIN(DTE)
Converter

Controller

Pin2(T)
Pin3(R)
Pin7(G)
Shield wire

1 T+
2 T3 R4 R+

DD+
Twisted pair wire
(with shield)

12 / 12

3. Connection Example

Host Computer

; RS232C

CONVERTER

RS485

IDNO=1

IDNO=2

IDNO=30

bAUd=2400

bAUd=2400

bAUd=2400

4. Terminal No.
TYPE

RS232

RS485

RD

SD

SG

DX-

DX+

DC1010

11

12

13

11

12

DC1030

15

16

17

15

16

DC1020

14

15

16

14

15

DC1040

14

15

16

14

15

DC1040-XXX-XFX

31

32

33

31

32

Availability

OUT1=1,2,3,7,A,B,C,D
OUT1=all kinds of out1
If the 2nd input is selected.
OUT1=1,2,3,7,A,B,C,D

13 / 12

5. Converter Setting

25pin
T+
TRR+
Recommend SPEC : IC-485SN(ATEN)

Connector 9 to 25 pin Convert

3 5

to PC

3 2

to Converter

14 / 12

6. Procedures for commnunication

Goto Level 4
(In Level 2, set LCK=1111)
SET5.4=1 in Level 4
(To activate the steps of Communications)

Enter to display Menu


Press SET and

key for 5 sec

IDnO=1
bAUd=2400

Return to Level1
Goto Level 3
(In Level 2, set LCK=0000)
Press

Press

key, SET IdnO=1

key, SET BAUd=2400


END

Enter to display Menu


Press SET and

key for 5 sec

Set the ID No=1(default)~30

Set the baud rate= 2400(default)


*Option : 2400, 4800, 9600