You are on page 1of 10

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS


Three-phase systems characteristics Generation of three-phase voltages Three-phase loads -Y and Y- transformation Instantaneous power Three-phase power: S, P and Q Power measurement. Aron connection Power factor improvement Electrical measurements Exercises

Alternating Current Three-Phase Circuits

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

THREE-PHASE SYSTEMS CHARACTERISTICS

THREE-PHASE SYSTEMS CHARACTERISTICS


Instantaneous electric power has sinusoidal shape with double frequency than voltage or current SINGLE-PHASE AC CIRCUITS: instantaneous electric power is negative twice a period (power flows from load to generator) and positive twice a period, falling to zero in. BALANCED THREE-PHASE AC CIRCUITS: instantaneous electric power is constant. Three-phase power never falls to zero Three-phase electric motors have better performance than single-phase AC motors Three-phase power systems allow two voltage levels (L-L, L-N) When transmitting electric power, three-phase AC systems require 25% less of Cu/Al than single-phase AC systems
3 4

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

GENERATION OF THREE-PHASE VOLTAGES

INTRODUCTION

Three-phase generators contain three sinusoidal voltage sources with voltages of the same frequency but a 120-phase shift with respect to each other This is realized by positioning three coils at 120 electrical angle separations on the same rotor Amplitudes of the three phases are also equal The generator is then balanced
5 6

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

INTRODUCTION
R

INTRODUCTION
R

R N S T
T VTR
120

VRN VTN N VST

VRS VSN S T

VTR
120

VRN VTN N VST

VRS VSN S

Vline = 3.Vline to43 14 N 2


phase

N: neutral point R S T (or A B C) direct sequence or sequence RST VRS, VST, VTR: line voltages or line-to-line voltages VRN, VSN, VTN: line-to-neutral voltages Vline = 3 Vline-to-neutral
7

50 Hz

Usual system 230 volt 400 volt 50 Hz


8

Vphase = Vline-to-neutral Vline


Frequency

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

THREE-PHASE LOADS CLASSIFICATION


WYE (two voltages) Balanced 3-wires 4-wires Unbalanced 3-wires 4-wires DELTA (one voltage) Balanced
S R IRS IS Z

WYE-CONNECTED LOAD
IR R

Z O=N Z S Z

IN N

Z O=N

IS S

IT

IR

IR
R

The wye or star connection is made by connecting one end of each of the three-phase loads together The voltage measured across a single load or phase is known as the phase voltage The voltage measured between the lines is known as the line-to-line voltage or simply as the line voltage In a wye-connected system, the line voltage is higher than the load phase voltage by a factor of the square root of 3 In a wye-connected system, phase current and line current are the same

R
ITR Z

IRS IS ZRS

ITR ZTR

Unbalanced
I ST
S T

I ST
S T

IT

IT

ZST

10

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

DELTA-CONNECTED LOAD
This connection receives its name from the fact that a schematic diagram of this connection resembles the Greek letter delta () In the delta connection, line voltage and phase voltage in the load are the same The line current of a delta connection is higher than the phase current by a factor of the square root of 3

-Y TRANSFORMATION
Z between nodes 1 and 2: : Z 1, 2 =

Z 12 (Z 13 + Z 23 ) Z 12 + ( Z 13 + Z 23 )
R

Y:

Z Y 1, 2 = Z 1 + Z 2
1

Z nodes 1-2: (1)

Z1 + Z 2 =

Z 12 (Z 13 + Z 23 ) Z 12 + ( Z 13 + Z 23 )

Z nodes 1-3: (2) Z 1 + Z 3 =

Z 13 (Z 12 + Z 23 ) Z 12 + ( Z 13 + Z 23 )

Z 13 S Z3

Z1

Z12 Z2

Z 23 (Z 12 + Z 13 ) Z nodes 2-3: (3) Z 2 + Z 3 = Z 12 + ( Z 13 + Z 23 )


T

Z23

From expressions (1), (2) and (3) it results:

Z1 =

Z 12 Z 13 Z 12 + Z 13 + Z 23
(1) + (2) - (3)

Z2 =

Z 12 Z 23 Z 12 + Z 13 + Z 23
(1) - (2) + (3)

Z3 =

Z 13 Z 23 Z 12 + Z 13 + Z 23
12

-(1) + (2) + (3)

11

Balanced loads:

ZY = Z/3

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

BALANCED THREE/FOUR-WIRE, WYE-CONNECTED LOAD


IR R

IR =
IN Z O=N IS Z Z

V RN V SN V TN IS = IT = Z Z Z I N = ( I R + IS + I T ) = 0

BALANCED THREE/FOUR-WIRE, WYE-CONNECTED LOAD Example A three-phase, RST system (400 V, 50 Hz), has a three-wire Y-connected load for which Z = 1030 Obtain the line currents and the complex power consumption R
IR =
Z O=N Z S Z

Stotal = 3.Sfase = 3.V RN .I *R = 3.Vlnia .I lnia


P

IT T

= 3.Vlnia .I lnia .cos + j 3.Vlnia .I lnia .sin 144 2444 4 3 144 244 3 4 4
Q

V RN 400/ 3 40 = = A 10 30 Z 3 30 60 40 V SN 400/ 3 = = A IS = 10 30 Z 3
V TN 400/ 3 = 10 30 Z
210

90

60

The three currents are balanced


Z O=N Z Z

IT =
T

40 3

180

A
90 60

Thus the sum of them is always zero Since the neutral current of a balanced, Yconnected, three-phase load is always zero, the neutral conductor may, for computational purposes, be removed, with no change in the results
13

Stotal = 3Sphase = 3V RN I *R = 3(400/ 3 )(40/ 3 )* = = 1600030 VA = 13856.41 (watt) + j8000 (VAr)


40 = 16000 VA 3 40 Ptotal = 3Vl I l cos = 3400 cos 30 = 13566.41watt 3 40 Q total = 3Vl I l sin = 3400 sin 30 = 8000 VAr 3 Stotal = 3Vl I l = 3400

14

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

UNBALANCED FOUR-WIRE, WYE-CONNECTED LOAD


IR R

UNBALANCED THREE-WIRE, WYE-CONNECTED LOAD


IR R

IN N

ZR O=N

IS S

ZS

ZT

IT T

V RN IR = ZR V SN IS = ZS V TN IT = ZT I N = ( I R + I S + I T ) 0

I R + IS + I T = 0
ZR O=N

IS S

ZS

ZT

V RO V SO V TO + + =0 ZR ZS ZT V RN + V NO V SN + V NO V TN + V NO + + =0 ZR ZS ZT

IT T

Stotal = V RN I *R + VSN I * + V TN I *T S
V ON
15

V RN V SN V TN + + ZR ZS ZT V RN Y R + V SN Y S + V TN Y T = = 1 1 1 Y R + YS + Y T + + ZR ZS ZT 16

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

UNBALANCED THREE-WIRE, WYE-CONNECTED LOAD


IR R

UNBALANCED THREE-WIRE, WYE-CONNECTED LOAD


Example A three-phase, RST system (400 V, 50 Hz), has a three-wire unbalanced Y-connected load for which ZR = 100 , ZS = 100 i ZT = 1030 Obtain the line currents and the total complex power consumption.
IR ZR ZS ZT R IS S IT T

1) V ON =
ZR O=N IS ZS

V RN Y R + V SN Y S + V TN Y T Y R + YS + Y T

ZT

2) I R = IS =

V RO V RN VON = ZR ZR V SO V SN VON = ZS ZS

V RN Y R + V SN Y S + V TN Y T Y R + YS + YT ON 90 0 -30 230 0.1 + 230 0.10 + 230 210 0.1-30 = = 40.93114.89 V 0.10 + 0.10 + 0.130 V ON =

IT T

VRO = VRN VON = 23090 - 40.93114.89 = 193.6484.90 V VSO = VSN VON = 230-30 - 40.93114.89 = 264,54-35.10 V VTO = VTN VON = 230210 - 40.93114.89 = 237,18-140.10 V IR = VRO/ZR = 193.6484.90/100 = 19,3684.90 A IS = VSO/ZS = 264.54-35.10/100 = 26,45-35.10 A IT = VTO/ZT = 237.18-140.10/1030 = 23.72-110.10 A
17

V TO V TN VON = IT = ZT ZT

3) Stotal = V RO I *R + V SO I * + V TO I *T S

Stot = VROIR* + VSOIS* + VTOIT* = 15619.56 W + j2812.72 VAr

18

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

BALANCED DELTA-CONNECTED LOAD


IR R IRS IS Z
R

UNBALANCED DELTA-CONNECTED LOAD


IR R
R

ITR Z

I ST
S T

IT

V RS I RS = Z VST IST = Z V TR I TR = Z

IRS

I R = I RS I TR IS = IST I RS I T = I TR IST

ITR ZTR

I RS = IST

IS

Z RS

V RS Z RS

I R = I RS I TR IS = IST I RS I T = I TR IST

I ST
S T

V ST = ZST V TR ZTR

IT

ZST

I TR =

Stotal = 3Sfase = 3V RS I *RS = 3Vlnia Ilnia


P Q

= 3Vlnia Ilnia cos + j 3Vlnia Ilnia sin 144 2444 4 3 144 244 3 4 4

Stotal = V RS I *RS + VST I * + V TR I *TR ST

19

20

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

UNBALANCED THREE-WIRE, -CONNECTED LOAD


Example A three-phase, RST system (400 V, 50 Hz), has an unbalanced connected load for which ZRS = 100 , ZST = 1030 i ZTR = 10-30 Obtain the R line currents and the complex power consumption

POWER MEASURMENT. Four-wires load


Balanced wye-connected, four-wires load
R W

I RS =

V RS 400120 = = 40120 A 100 Z V ST 4000 = 30 = 4030 A IST = 10 Z V TR 400120 = = 4090 A I TR = 1030 Z


105

VTR
120

VRN VTN N VST

VRS
N

Z O=N Z Z

W = VRNIRcos( VRN - IR) Ptotal = 3W

IR R IRS IS Z RS

VSN S
S

ITR
T

ZTR

Unbalanced wye-connected, four-wires load


R WR

I R = I RS I TR = 77.29 IS = IST I RS = 77.29

A A
S

I ST
T

WR = VRNIRcos( VRN - IR)


Z

45

IT

ZST
N

WS = VSNIScos( VSN - IS) WT = VTNITcos( VTN - IT)


ZT

I T = I TR IST = 40.00 150 A


Stotal = V RS I *RS + VST I * + V TR I *TR = 43712.81(W) + j0 (VAr) = ST = 43712.81VA
21

O=N S WS ZS

Ptotal = WR + WS + WT
WT

22

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

POWER MEASURMENT. ARON CONNECTION


General 3-wires load. Two-wattmeter method (ARON connection) Demonstration done for a balanced 3-wires load

POWER MEASURMENT. BALANCED LOAD


R
Balanced load, general (Y/D, 3/4 wires). Two-wattmeter method (ARON connection)

Ptotal = W1 + W2
BALANCED

LOAD
,

=6 0 =9 0

VTR VRT
120

VRN VTN N VST VST

VRS VSR

LOAD
,

Q total = 3(W1 W2 )

VSN S

= arctg( 3

W1 W2 ) W1 + W2

W1 = VRT IR cos( VRT I R ) = VIcos(30 + ) W2 = VST IS cos( VST IS ) = VIcos(30 + )


= =0 30

Unbalanced wye/delta-connected, three-wires load

UNBALANCED

PTOTAL = W1 + W2 = VI[cos( 30 + ) + cos(30 + )] = 3VIcos Q TOTAL = 3[W1 + W2 ] = 3VI[ 30 + ) cos(30 + )] = 3VIsin cos(
23
,

LOAD

Ptotal = W1 + W2

24

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

POWER MEASURMENT; THE TWO-WATTMETER METHOD Aron Cyclic Permutations


W1 V RT SR TS I R S T V ST TR RS W2 I S T R

INSTANTANEOUS THREE-PHASE POWER Single-phase load:


cosAcosB = 05[cos(A+B) + cos(A-B)]

p(t) = v(t)i(t) = V0cos(wt + V)I0cos(wt + ) p(t) =1/2 V0I0cos(V - I) + 1/2V0I0cos(2wt + V + I) watt


Constant Oscillates twice mains frequency!!!!

Three-phase wye balanced load:


p(t) = vRN(t)iR(t) + vSN(t)iS(t) + vTN(t)iT(t) = = 2Vpcos(wt + V) 2Ipcos(wt + ) + 2Vpcos(wt -120+ V) 2Ipcos(wt -120+ ) + 2Vpcos(wt +120+ V) 2Ipcos(wt +120+ ) =

Q measurement: Cyclic Permutations


W V ST TR RS I R S T

Q TOT = 3W

W = VST I R cos(VST IR ) = Vline I line cos(90- ) = Vline I line sin =

QTOTAL 3

25

VpIpcos(V - I) + VpIpcos(2wt + V + I) + VpIpcos(V - I) + VpIpcos(2wt -240+ V + I) + VpIpcos(V - I) + VpIpcos(2wt +240+ V + I) = 3/2VpIpcos(V - I) = 3/2VpIpcos = constant!!!

26

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

INSTANTANEOUS POWER: SINGLE PHASE LOAD

INSTANTANEOUS THREE-PHASE POWER

v(t)

v(t)

i(t)

i(t)

p(t)
Average power = P

p(t) pTOTAL = pR(t) + pS(t) + pT(t)


27 28

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

POWER LOSSES THREE-PHASE/SINGLE PHASE


Single-phase line
V

Example 1
Three-phase, balanced RST system for which A1 = 1.633 A, A2 = 5.773 A, W1 = 6928.2 W, W2 = 12000 W, U = 6000 V, Zline=4+j3 a) Obtain the complex power in the loads, the ammeter A and the voltmeter U1 readings b) Obtain the value of C to improve the loads PF to 1, supposing U = 6000 V. Q = 3W = 12000VAr
R
U1

I=

Pload V cos
2 2

Plosses = 2R1 I = 2R1

Pload V cos
2

ZL

ZL U ZL A1 A2
W2

Q1 = 12000VAr = 3UI1 sin 1


3 .6 3 =1 000 =6

Three-phase line
V

Pload I= 3V cos

1 = 45
W1

P1 = 3UI1 cos 1 = 12000W


K C C

Plosses = 3R2 I = 3R2

Pload ( 3 ) .V cos
2 2 2

= R2

Pload V cos
2 2

S
Balanced load 1 capacitive Balanced load 2 inductive C

P2 = 3W2 = 36000W = 3UI 2 cos 2

2 = 53.12
Q 2 = 3UI 2 sin 2 = 48000VAr
36.87

Supposing same losses

l l 1 2R 1 = R 2 2 = S3p = S1p S1p S3p 2

S1+ 2 = (P1 + P2 ) + j(Q1 + Q 2 ) = 48000 + j36000 = 60000


6000 3
90

VA

Single-phase line: 2 conductors of length l and section S1p Three-phase line: 3 conductors of length l and section S3p = 1/2S1p As a result:

ITOTAL = I1 + I 2 = 1.63390 +45 + 5.77390 53.12 = 5.77490 36.85 A U1, phase = I.ZL + U phase = 5.77490 36.85 (4 + j 3) +
29

weight3p-cables = 3/4weight1p-cables

= 3492.97 90 V U1 = 3U1,phase = 6050V


30

Q1C , = Q/3 = -36000/3VAr = -

(6000)2 1/(2 .50.C )

C = 1.06F

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

Example 2
Three-phase 50 Hz system, for which V = 400 V, W1 = -8569.24 W, W2 = -5286.36 W, AS = 21.56 A. Obtain a) the value of R b) the reading of AR c) the value of the inductance L W1 W2
R S T W1 W2 AR AS AT V

Example 3
Varley phase-sequence indicator Calculate the voltage in each element and deduce practical consequences Three-phase 400 V/50 Hz system C = 1F XC = 3183 R2bulbs = 2V2/P = 22302/20 = 5290

W1 ' = W1
S
R L R

and W2 ' = W2
T

V RT SR TS

I R S T

V ST TR RS

I S T R

a) Pt otal = W1 '+ W2 ' = 13855.6 W = 2


b) ISR =

VSR 400 60 V 400 +60 I RT = RT = = = 17.32 60 A = 17.32 + 60 A R 23.095 R 23.095 It results : I R = I RT - ISR = 3090 A
VTS 400 400 = 17.32 60 = 8.66 j15 j 90 XL jX L XL
400 2 ) X L = 84.308 = 2 50L XL
31
180

400 R

resulting in :

R = 23.095

V RN Y R + V SN Y S + V TN Y T Y R + YS + Y T 90 -90 230 /3183 + 230-30 /5290 0 + 230 210 /5290 0 = 1 / 318390 + 1 / 5290 0 + 1 / 5290 0 = 171.55171.31 V R V ON =
VRO = VRN VON = 23090 - 171.55171.31 = 265.3450.28 V VSO = VSN VON = 230-30 - 171.55171.31 = 394.78-20.91 V VTO = VTN VON = 230210 171.55171.31 = 144.00-101.86 V
VR0 0 VT0 T V0N VS0 S

c) IS = ISR ITS = 17.32 60

IS = 21.56 A = 8.662 + (15

Conductor R is that where the capacitor is placed, conductor S is that where placed the brighter bulb and the remaining one is T.
32

The result is : L = 0.2684 H

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

Example 4
A 400 V and 50 Hz three-phase line feeds two balanced loads through a line which has an internal impedance ZL=0.5 + j1 The -connected load has phase impedances which values are 45+j30 , whereas the Y-connected load has phase impedances of 15j30 Determine: a) The reading of the ammeter A b) The reading of the voltmeter V c) The readings of watt-meters W1 and W2
R S T ZL ZL ZL W1 W2 A V

Example 5
Three phase 400 V-50 Hz line. When switch K2 is closed WA = 4000 W. When K1 and K3 are closed, WA = 28352.6 and WB = -11647.4 W. Determine: a) R2 b) R1 c) AT
a) K2 closed: WA = VSTIScos(VST - IS) 4000 = 400IScos(0+30) IS = 11.55 A
R S T N WA
AT

WB
AS

R2 = VSN/IS = (400/3)/11.55 = 20
b) K1 and K3 closed:
T

K1 C1
S
0 =2

K2 R1 R1 R2

K3

S
7.125

PTOT = W1 + W2 = -WB + WA = 40000 W = 24002/R1 + 4002/R2 R1 = 10


W1 W2 I R S T V ST TR RS I S T R V RT SR TS

ZTOT = ZL + (Z Y / / ZY ) = Z L + Z// = (0.5 + j1) + (16.731 + j1.154) = 17.365 a) I R = VRN 400 / 3 = = 13.3082.875 A ZTOT 17.3657.125
+90

c) K1 and K3 closed:
I S T R
180 60

W1 V RT SR TS I R S T V ST TR RS

W2

b) V = 3(IZ// ) = 3(13.3016.7706) = 386.33V

IT1 = ITS I RT = IT2 =

c) PLOAD = W1 + W2 = 313.302 16.731 Q LOAD = 3(W1 W2 ) = 313.302 1.154

From the Aron connection it results: W1 = 4616,1 W, W2 = 4262,5 W


33

ITtotal

VTS 400 = = 20 + j0A R2 20 87.18 = IT1 + IT2 = (60 j34.64) + (-20 + j0) = -80 j34.64 = 87.18 A

180

VTS VRT 400 = R1 R1 10

400 10

= 60 j34.64A

34

It results, AT = 87.18 A

Unit 2 AC THREE-PHASE CIRCUITS

Unit 2 AC THREE-PHASE CIRCUITS

ELECTRICAL MEASUREMENTS
INSTRUMENTS FOR INDUSTRIAL MAINTENANCE Multimeters Voltage AC/DC Current AC/DC Resistance Others: capacitance, frequency, temperature, Current probes Voltage AC/DC (depending on models) Current AC/DC Wattmeters Voltage AC Current AC Power: S, P, Q AC PF Frequency Single-phase or three-phase
Single-phase Three-phase

ELECTRICAL MEASUREMENTS
Three phase loads with 3-4 wires Single-phase loads Voltage Current
laboratory

P, Q, S PF
PCE Iberica

Phase angle between voltage and current Energy

35

36

Unit 2 AC THREE-PHASE CIRCUITS

ELECTRICAL MEASUREMENTS
INSTRUMENTS FOR INDUSTRIAL MEASUREMENT AND CONTROL Useful for carrying out low cost energy control checks on electrical consumption Can also be used to carry out an accurate control of the consumption of any other physical unit which has a meter with a digital impulse output Possible measurements: Voltage Current Hz Power (S, P, Q, PF) Energy Single-phase or three-phase

Circutor

37

You might also like