You are on page 1of 103

CABLES DE BAJA TENSIN

Pirelli Cables y Sistemas, s. a.


Rambla Pirelli, 2 Apartado 1 08800 Vilanova i la Geltr (Barcelona) Tel. 93 811 60 00 Fax 93 811 60 01 PIRELLI CLUB Tel. 901 25 50 75 e-mail: energia.es@pirelli.com

www.es.pirelli.com

CATLOGO DE CABLES DE BAJA TENSIN

baja tensin INFORMACIN GENERAL

ndice

Radios de curvatura ......................................................................................................................................................................... 4 Tabla de abreviaciones ..................................................................................................................................................................... 5 Normativa sobre el comportamiento de los cables frente al fuego ...................................................................................................... 6

COMENTARIOS GENERALES SOBRE LOS CABLES ELCTRICOS


A) Los cables elctricos en las instalaciones en los edificios ................................................................................................................. Modos de instalacin ....................................................................................................................................................................... Intensidades mximas admisibles en edificios ................................................................................................................................. Factores de correcin ....................................................................................................................................................................... Tipos de cables para instalaciones elctricas en edificios ................................................................................................................. B) Redes subterrneas para distribucin en Baja Tensin ....................................................................................................................... Cables directamente enterrados y/o entubados .................................................................................................................................. Intensidades mximas admisibles .................................................................................................................................................... Factores de correccin ..................................................................................................................................................................... Cables instalados en galeras subterrneas ........................................................................................................................................ Intensidades mximas admisibles .................................................................................................................................................... Factores de correccin ..................................................................................................................................................................... Tipos de cables para redes subterrneas para distribucin en Baja Tensin ...................................................................................... C) Cables a la intemperie para distribucin en Baja Tensin ................................................................................................................... Intensidades mximas admisibles .................................................................................................................................................... Factores de correccin ..................................................................................................................................................................... Tipos de cables para instalaciones a la intemperie para distribucin en Baja Tensin ....................................................................... 7 7 9 9 12 13 13 14 15 16 16 17 19 20 20 21 23

CABLES PARA EDIFICACIN E INDUSTRIA


Pirepol Flexible ................................................................................................................................................................................. Pirepol Rgido .................................................................................................................................................................................... Pirepol Haz ....................................................................................................................................................................................... Pirepol Gas ....................................................................................................................................................................................... Retenax Flex .................................................................................................................................................................................... Retenax Flam ................................................................................................................................................................................... Afumex 750V ................................................................................................................................................................................... Afumex 1000V ................................................................................................................................................................................. Afumex Firs 1000V ............................................................................................................................................................................. 25 27 29 31 35 39 45 47 51

CABLES ESPECIALES PARA LA INDUSTRIA


Solda ............................................................................................................................................................................................... Euroflam N ....................................................................................................................................................................................... Euroflam 0 YCY ................................................................................................................................................................................ Euroflam mltiple ............................................................................................................................................................................. Bupreno H07RN-F / Pireflex ............................................................................................................................................................. Bupreno ........................................................................................................................................................................................... Retenax F y Retenax M ..................................................................................................................................................................... Retenax Varinet ................................................................................................................................................................................ Afumex Paneles flexible .................................................................................................................................................................... Afumex Paneles rgido ...................................................................................................................................................................... Afumex Varinet ................................................................................................................................................................................. 55 57 59 61 63 65 69 77 79 81 83

CABLES PARA ACOMETIDAS SUBTERRNEAS Y LNEAS AREAS


Al Polirret ......................................................................................................................................................................................... 85 Polirret Cobre ................................................................................................................................................................................... 89 Al Voltalene N ................................................................................................................................................................................... 91

ACCESORIOS DE BAJA TENSIN


Cinta de PVC: P1000 ........................................................................................................................................................................ 95 Empalmes y derivaciones CASTFIT ................................................................................................................................................... 97 Accesorios termorretrctiles .............................................................................................................................................................. 99

www.es.pirelli.com

baja tensin

RADIOS DE CURVATURA
Los radios de curvatura indicados en la siguiente tabla, son los radios mnimos que el cable puede adoptar en su posicin definitiva de servicio y son aplicables a todos los cables de la norma UNE 21-123. Estos lmites no se aplican a las curvaturas a que el cable pueda estar sometido durante su tendido, cuyos radios deben tener un valor superior al indicado.

Cables sin armadura Dimetro exterior del cable (mm) Menos de 25 De 25 a 50 Ms de 50 Cables armados

Radio mnimo de curvatura expresado en mltiplos del dimetro del cable 4D 5D 6D 10 D

www.es.pirelli.com

baja tensin

TABLA DE ABREVIACIONES
USO STANDARD DE LAS ABREVIACIONES UTILIZADAS POR LAS ENTIDADES REGULADORAS ASOCIADAS CON LA INDUSTRIA DEL CABLE
REFERENCIA ABREVIACIN

ANSI BASEC BSI (BS) CEBEC CEI CEN CENELEC CMA CSA DEF. STAN. DEMKO DGS DIN DNV ECMC EEMUA ELOT ERA ESI ICEA IEC IEE IEEE IEMMEQU (MQ) ISO KEMA-KEUR LLOYDS MESC MIL NEMKO NP NSAI OCMA OVE SEMKO SETI SEV UNEL UNE UL USE (UTE) VDE NF

American National Standards Institute (USA) British Approvals Service for Electric Cables (UK) British Standards Institution (UK) Comite Electrotechnique Belge (Belgium) Comitato Electrotechnico Italiano or Commission Electrotechnique Internationale (Italy) European Committee for Standardisation (EEC) European Committee for Electrotecnical Standardisation (EEC) Cable Makers Association (UK) Canadian Standard Approval (Canada) Ministry of Defence Specification (UK) Denmarks Elektriske Materielkontrol (Denmark) Director General Ships (UK) Deutsches Institute fr Normung (Germany) Det Norske Veritas (Scadinavia) Electric Cable Makers Confederation (UK) The Engineering Equipment and Materials Users Association (UK) Hellenic Organisation for Standardisation (Grece) Electrical Research Assocciation (UK) Electrical Supply Industry (UK) Insulated Cable Engineers Association (USA) International Electrotechnical Commission (Europe) Institute of Electrical Engineers (UK) Institute of Electrical and Electronic Engineers (UK) Instituto Italiano dell Marchio Di Qualita (Italy) International Standards Organisation (UK) N.V. Tot Keuring Van Electrotechnische Materialen (Netherlands) Lloyds Register of Shipping (UK) Material and Equipment Standars and Code (Shell BV) (Netherlands) United States Military Specification (USA ) Norks Electrisk Materiellkontrol (Norway) IPQ - Instituto Portugues Da Qualidade (Portugal) National Standards Authority of Ireland (Ireland) Oil Companies Materials Association (UK) Usterreichischer Berband Fr Elektrotechnik (Austria) Svenska Electriska Materiel Kontrollanstalten (Sweden) Elektriska Inspektorated (Finland) Schweizerischer Elektrotechnischer Verein (Switzerland) Unificazione Electrechnia (Italy) AEE - Asociacin Electrotcnica y Electrnica Espaola (Espaa) Underwriters Laboratories (USA) Union Technique De Lelectricite (UTE) (France) Verband Deutscher Elektrotechniker (Germany) Norma Francesa (NFC: Electricidad) agrupa las antiguas normas UTE (Union Technique de dElectricit)

www.es.pirelli.com

baja tensin

informacin general

NORMATIVAS SEGN EL COMPORTAMIENTO DE LOS CABLES FRENTE AL FUEGO


Nuevo CENELEC Status Sustituye a: IEC de referencia

EN 50265-11: 1998 Mtodos de ensayo comunes para cables bajo condiciones de fuego. EDITADAS Ensayo de resistencia a la propagacin vertical de la llama para un conductor individual aislado o cable. - Parte 1: Equipo. EN 50265-2-11: 1998 Parte 2: Procedimientos. Seccin 1: Llama premezclada de 1 kW. EN 50265-2-2: 1998 Parte 2: Procedimientos. Seccin 2: Llama de difusin. EN 50266-11: 2001 Ensayo de cables elctricos sometidos al fuego. Ensayo de cables colocados en capas. - Parte 1: Equipo. EN 50266-2-11: 2001 Parte 2: Procedimientos. Seccin 1: Categora A F/R. EN 50266-2-2: 2001 Parte 2: Procedimientos. Seccin 2: Categora A. EN 50266-2-3: 2001 Parte 2: Procedimientos. Seccin 3: Categora B. EN 50266-24: 2001 Parte 2: Procedimientos. Seccin 4: Categora C. EN 50266-2-5: 2001 Parte 2: Procedimientos. Seccin 5: Categora D. EN 50267-1:1998 Mtodos de ensayo comunes a los cables sometidos al fuego. Ensayo de gases desprendidos durante la combustin de materiales procedentes de los cables. - Parte 1: Equipo. EN 50267-2-1:1998 Parte 2: Procedimientos. Seccin 1: Determinacin de la cantidad de gases halgenos cidos. EN 50267-2-2-1998 Parte 2: Procedimientos. Seccin 2: Determinacin de grado de acidez de gases de los materiales por medida del pH y la conductividad. EN 50267-2-3:1998 Parte 2: Procedimientos. Seccin 3: Determinacin del grado de acidez de los gases de los cables a partir de la medida de la media ponderada del pH y de la conductividad. EN 50268-11: 1999 Mtodos de ensayo comunes para cables sometidos al fuego. Medicin de la densidad de humos de cables en combustin bajo condiciones definidas. Parte 1: Equipo de ensayo. EN 50268-2: 1999 Parte 2: Procedimiento de ensayo. EN 50200: 2000 Mtodo de ensayo de la resistencia al fuego de los cables de pequeas dimensiones sin proteccin, para uso en circuitos de emergencia. EN 50362 Mtodo ensayo de la resistencia al fuego de los cables de transmisin de datos y de energa, sin proteccin, para uso en circuitos de emergencia (dimetro superior a 20mm). EDITADAS (EN y UNE-EN) EDITADAS (EN y UNE-EN) EDITADAS (EN y UNE-EN) (EN y UNE-EN)

HD 405.1 HD 405.2

UNE 20432/1 UNE 20432/2

IEC 60332-1 (1993) IEC 60332-2 (1989)

EDITADAS HD 405.3 UNE 20432/3 IEC 60333-2 (1999)

UNE 21147/1

IEC 60754-1 (1994)

(EN y UNE-EN)

HD 602

UNE 21147/2

IEC 60754-2 (1999) + A1(1997

HD 606.1

UNE 21172/1

IEC 61034-1 (1997)

HD 606.2

UNE 21172/2 UNE 20431 (en parte)

IEC 61034-2 (1997) IEC 60331: 1999

PROYECTO EN UNE-EN en traduccin

UNE 20431 (en parte)

IEC 60331: 1999

www.es.pirelli.com

baja tensin

comentarios generales sobre los cables elctricos

A) LOS CABLES ELCTRICOS EN LAS INSTALACIONES DE LOS EDIFICIOS


En el Reglamento Electrotcnico de Baja Tensin de 1973, la Instruccin MIE-BT 017: Instalaciones Interiores o Receptoras en su apartado 2: Prescripciones de Carcter General, punto 2.1.3: Intensidades mximas admisibles, se adverta que los distintos Sistemas de Instalacin descritos en la Instruccin MIE-BT 018, a efectos de la disipacin trmica del calor generado en las canalizaciones por efecto Joule, se clasificaban en dos grandes grupos: al aire o directamente empotradas y bajo tubo o conducto. Por consiguiente, se especificaba la intensidad mxima admisible en servicio permanente en las canalizaciones, haciendo referencia a los dos tipos de instalaciones citados. Basndose en este criterio, en dicha Instruccin MIE-BT 017, se incluyeron dos tablas de carga, una para los cables y conductores aislados con PVC (tabla I) y otra para los aislados con XLPE o EPR (tabla II), en las que se facilitaban las secciones de los conductores correspondientes a las corrientes que haban de transportar, de acuerdo con la temperatura mxima admisible en servicio permanente en los cables citados. El paso del tiempo ha demostrado que dicha simplificacin era excesiva, pues la diversidad de modos de instalaciones elctricas en edificios, que se utilizan en la prctica, haca necesarias unas tablas de cargas ms ajustadas a esta variedad. Esta necesidad ha motivado la publicacin de la norma UNE 20460 - "Instalaciones Elctricas en Edificios", que es una adaptacin, a las circunstancias especficas de nuestro Pas, del Documento de Armonizacin del CENELEC HD-384 que, a su vez, se corresponde con la recomendacin del Comit Electrotcnico Internacional IEC 364. La determinacin de las intensidades admisibles en los cables descritos en esta Publicacin se ajustar a lo prescrito en la citada norma UNE 20460.

MODOS DE INSTALACIN
En el captulo 52 - "Canalizaciones", de la parte 5 - "Seleccin e instalacin de materiales elctricos", de la mencionada norma 20460, en la tabla 52-G se indica que "modos de instalacin" son los adecuados a las distintas situaciones de las canalizaciones previstas en la obra, de acuerdo con el "sistema de instalacin" elegido, mientras que la tabla 52-H, relaciona dichos "modos de instalacin", hacindolos corresponder a unas instalaciones "tipo", cuya capacidad de disipacin del calor generado por las prdidas es similar a aquellos, por lo que se pueden agrupar en una determinada tabla de cargas comn para todos los modos que se adaptan a la misma instalacin tipo.

TABLA 52-G: MODOS DE INSTALACIN


Sistemas de instalacin Situaciones Huecos en la construccin Accesibles No accesibles Sin fijacin 25 21, 25 73, 74 43 52, 53 Fijacin 21, 25 0 43 51 11 Tubos 22 22 73, 74 41, 42 1, 2, 5 3 Canales 31, 32, 35 0 0 31, 32 33, 75 31, 32 71, 72 Bandeja de escalera o soporte 12, 13, 14, 15, 16 0 12, 13, 14, 15, 16 0 12, 13, 14, 15, 16

Canal de obra Empotrados en estructuras En montaje superficial

TABLA 52-H: MODOS DE INSTALACIN E INSTALACIONES TIPO


Ref. 1 2 3 3 A 4 4A 5 5A 11 11 A Modos de instalacin Conductores aislados en tubos empotrados en paredes trmicamente aislantes. Cables multiconductores en tubos empotrados en paredes trmicamente aislantes. Conductores aislados en tubos adosados a una pared de madera Cables multiconductores en tubos adosados a una pared de madera. Conductores aislados en conductos de seccin no circular adosados a una pared de madera. Cables multiconductores en conductos de seccin no circular adosados a una pared de madera. Conductores aislados en tubos empotrados en una pared de obra. Cables multiconductores en tubos empotrados en una pared de obra. Cables multipolares con o sin armadura: fijados sobre pared de madera fijados en el techo de madera C 0,95 C A A2 B B2 B B2 B B2 Tipo

www.es.pirelli.com

baja tensin

comentarios generales sobre los cables elctricos

TABLA 52-H: MODOS DE INSTALACIN E INSTALACIONES TIPO (Continuacin)


Ref. Modos de instalacin Cables multipolares con o sin armadura: 11 B 12 13 14 15 16 17 18 21 22 22 A 23 23 A 24 24 A 25 31 32 31 A 32 A 33 33 A 34 34 A 41 42 43 51 52 53 71 72 72 A 73 74 75 81 separados del techo sobre bandejas no perforadas cables multiconductores sobre bandejas rejilla o perforadas horizontales o verticales cables unipolares (idem) sobre soportes cables multiconductores fijados con collarines, separados de la pared cables unipolares (idem) Cables multiconductores sobre bandejas escalera cables unipolares (idem) cables multiconductores suspendidos de un fiador cables unipolares (idem) conductores aislados sobre aisladores cables uni o multiconductores en huecos de fbrica conductores aislados en tubos dentro de huecos de obra de fbrica cables uni o multiconductores en tubos dentro de huecos en obras de fbrica Conductores aislados en conductos de seccin no circular en huecos de obra de fbrica Cables uni o multiconductores en conductos de seccin no circular en huecos de obra de fbrica Conductores aislados en conductos de seccin no circular embebidos en obra de fbrica Cables uni o multiconductores en conductos de seccin no circular embebidos en obra de fbrica Cables uni o multiconductores en falsos techos o en techos suspendidos Conductores aislados o cables unipolares en canaletas horizontales ventiladas fijadas a la pared Conductores aislados o cables unipolares en canaletas verticales ventiladas fijadas a la pared Cables multiconductores en canaletas ventiladas. Fijadas a la pared en recorrido horizontal Cables multiconductores en canaletas ventiladas. Fijadas a la pared en recorrido vertical Conductores aislados en canaletas empotradas en el suelo Cables multiconductores en canaletas empotradas en el suelo Conductores aislados en canaletas suspendidas Cables multiconductores en canaletas suspendidas Conductores o cables aislados en tubos en canales o atarjeas cerradas, horizontales o verticales Conductores aislados en tubos en canales o atarjeas ventiladas Cables multiconductores en atarjeas ventiladas Cables multiconductores empotrados directamente en paredes trmicamente aislantes Cables directamente empotrados en paredes de obra sin proteccin mecnica complementaria Cables bajo tubo directamente empotrados en paredes de obra Conductores aislados en molduras Conductores aislados o cables unipolares en zcalos acanalados Cables multiconductores dentro de zcalos acanalado Conductores aislados dentro de los marcos de las puertas Conductores aislados dentro de los marcos de las ventanas Conductores o cables en zcalos acanalados enrasados en la pare Cables sumergidos en el agua. Este sistema de instalacin est en estudio, puede considerarse como si se tratara de una instalacin de cables directamente enterrados en terrenos muy hmedos de baja resistividad trmica C C E F E E F E F E F G B2 B2 B B2 B B2 B B B2 B B2 B B2 B B2 B B B2 B2 A C C A B2 B A A B2 Tipo

As, por ejemplo, una canalizacin bajo tubo, en canal de obra, tabla 52-G, permite la utilizacin de un "modo de instalacin" de las ref. 41 y 42 que, segn se trate de canales cerrados o ventilados, se correspondern con una instalacin "tipo" B2 B, respectivamente.

www.es.pirelli.com

baja tensin

comentarios generales sobre los cables elctricos

As pues, solo habr que considerar las tablas de carga de las ocho instalaciones "tipo con las que se identificarn los distintos modos de instalacin mencionados. Estas ocho instalaciones "tipo responden a la siguiente descripcin genrica: Modo A. Conductores aislados en tubos empotrados en paredes trmicamente aislantes. Modo A2. Cables multiconductores en tubos empotrados en paredes trmicamente aislantes. Modo B. Conductores aislados en tubos colocados sobre una pared trmicamente aislante. Modo B2. Cables multiconductores en tubos colocados sobre una pared trmicamente aislante. Modo C. Cables multiconductores posados directamente sobre una pared de madera. Modo E. Cables multiconductores instalados al aire libre sobre una pared, separados de sta una distancia superior a 0,3 veces su dimetro. Modo F. Cables unipolares instalados al aire libre en contacto mtuo, sobre una pared, separados de sta una distancia superior al dimetro del cable. Modo G. Cables unipolares instalados al aire libre, sin contacto mtuo, sobre una pared, separados de sta y entre si una distancia superior al dimetro del cable. Se recuerda que la norma UNE 20460 denomina "conductores aislados" a los conductores aislados sin cubierta como, por ejemplo, los cables PIREPOL 3 AFUMEX 750 V. Se trata de cables termoplsticos que, en el mejor de los casos presentan un nivel de aislamiento de 750 V y siempre sern unipolares, lo que limita su campo de aplicacin a su "instalacin en conductos situados sobre superficies o empotrados, o en sistemas cerrados anlogos", como se especifica en la Gua de utilizacin de la norma UNE 21031. Por otro lado, cuando se alude a los cables, se refiere siempre a conductores aislados con una cubierta adicional como, por ejemplo, los cables RETENAX o AFUMEX 1000 V, tanto unipolares como multipolares. Se trata de cables termoestables, que presentan una tensin nominal de 1000 V. La posibilidad de empleo de uno u otro tipo de cable lo determinar el Reglamento Electrotcnico de Baja Tensin vigente, de acuerdo con las caractersticas de la obra.

INTENSIDADES MXIMAS ADMISIBLES EN EDIFICIOS


Como se puede observar, la tabla 52-C20 - Intensidades admisibles (en A) al aire (40C) de la norma UNE 20460-5-523, que se reproduce a continuacin, presenta once columnas entre las que, segn cual sea el "tipo" de instalacin al que se corresponda el "modo de instalacin" adoptado, el nmero de conductores cargados del circuito y la naturaleza del aislamiento, se tomar la tabla de cargas adecuada al caso de que se trate. Estas tablas se han confeccionado para las condiciones clsicas de instalaciones al aire: un solo circuito a 40C de temperatura ambiente y temperaturas en el conductor de 70C para los aislamientos tipo TP, termoplsticos, (PVC, Z1 o similares) y de 90C para los TE, termoestables, (XLPE, EPR, Z o anlogos). (Ver tabla intensidades mximas admisibles en edificios). Se observa que para instalaciones en el interior de edificios, no se distingue entre cables de tensin nominal 750 1000 V, ya que las resistividades trmicas de ambos son comparables y slo varan de manera notable cuando se compara un "conductor aislado", que slo tiene aislamiento, y un "cable", que dispone de aislamiento y cubierta, extremo que ya se ha tenido en cuenta al definir la instalacin "tipo". Por tanto, para una determinada instalacin "tipo", lo que define la tabla de cargas a considerar ser el nmero de conductores activos, dos en monofsico o tres en trifsico, y la naturaleza del material aislante del conductor, termoplstico (PVC o similar) o termoestable (XLPE, EPR o similar), que determina la temperatura mxima admisible en el conductor en rgimen permanente.

FACTORES DE CORRECCIN
Cuando las condiciones de la instalacin son distintas a las clsicas tomadas como base para la confeccin de la tabla 52-C20: temperatura ambiente de 40C, o hay ms de un circuito en la misma canalizacin, se tomarn los factores de correccin que siguen, que tambin se indican en la citada norma.

www.es.pirelli.com

baja tensin

comentarios generales sobre los cables elctricos

INTENSIDADES MXIMAS ADMISIBLES EN EDIFICIOS


Tipo A A2 B B2 C E F G mm2 Cobre 1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Aluminio 16 25 35 50 70 95 120 150 185 240 300 36 46 38 50 61 73 42 54 67 80 46 61 75 90 116 140 162 187 212 248 285 51 64 78 96 122 148 171 197 225 265 305 56 71 88 106 136 167 193 223 236 300 347 73 92 110 144 177 206 238 274 326 378 65 82 102 124 158 192 223 258 294 348 400 70 88 109 133 170 207 239 277 316 372 429 83 94 117 145 187 230 269 312 359 429 698 126 157 191 247 302 352 406 469 556 664 11 15 20 25 34 45 59 11,5 16 21 27 37 49 64 77 94 13 17,5 23 30 40 54 70 86 103 13,5 18,5 24 32 44 59 77 96 117 149 180 208 236 268 315 360 15 21 27 36 50 66 84 104 125 160 194 225 260 297 350 404 16 22 30 37 52 70 88 110 133 171 207 240 278 317 374 423 96 119 145 188 230 267 310 354 419 484 18 25 34 44 60 80 106 131 159 202 245 284 338 386 455 524 21 29 38 49 68 91 116 144 175 224 271 314 363 415 490 565 24 33 45 57 76 105 123 154 188 244 296 348 404 564 552 640 166 206 250 231 391 455 525 601 711 821 (1) (2) (3) (4) (5) (6) (7) (8) 3xTP 3xTP 3xTP 2xTP 2xTP 3xTE 3xTP 2xTP 3xTP Nmero de conductores y naturaleza del aislamiento 3xTE 2xTE 2xTP 3xTE 2xTP 3xTP 3xTP 3xTP (9) (10) 3xTE 2xTE 3xTE 2xTP 2xTE 3xTE 2xTE 3xTE 3xTE (11) 2xTE 2xTE

www.es.pirelli.com

10

baja tensin

comentarios generales sobre los cables elctricos

FACTORES DE CORRECCIN POR TEMPERATURA


Ya se ha indicado anteriormente que, cuando la temperatura ambiente es distinta a los 40C, las intensidades de la tabla 52-C20 o de la tabla bsica mencionada anteriormente se debern multiplicar por un factor de correccin que tenga en cuenta el distinto salto trmico a utilizar en: I = 3(6e/nRERT). Este factor de correccin por temperatura valdr, en el caso de cables con aislamiento termoplstico (TP): K = 3[(70-ea)/30] y en los de aislamiento termoestable (TE): K = 8[(90-qa)/50]. Sobre la base de estas expresiones se han obtenido los factores de correccin que se indican a continuacin:
Material aislante TP TE Temperatura ambiente (eA) (en C) 10 1,4142 1,2649 15 1,354 1,2247 20 1,2910 1,1832 25 1,2247 1,1402 30 1,1547 1,0954 35 1,0801 1,0488 40 1,0000 1,0000 45 0,9129 0,9487

Material aislante TP TE

Temperatura ambiente (eA) (en C) 50 0,8165 0,8944 55 0,7071 0,8367 60 0,5774 0,7746 65 0,4082 0,7071 70 0,6324 75 0,5477 80 0,4472 85 0,3162

Estos valores se han trasladado a la tabla 52-D1 de la Norma 20460-5-523:


Material aislante TP TE Temperatura ambiente (eA) (en C) 10 1,40 1,26 15 1,34 1,23 20 1,29 1,19 25 1,22 1,14 30 1,15 1,10 35 1,08 1,05 40 1,00 1,00 45 0,91 0,96 50 0,82 0,90 55 0,70 0,83 60 0,57 0,78

Luego, cuando la temperatura ambiente sea inferior a 40C, la mejor refrigeracin de los cables les permitir transportar corrientes superiores. Recprocamente, temperaturas ambiente ms elevadas deben corresponderse con corrientes ms reducidas. Esto es especialmente importante cuando en canalizaciones antiguas se aaden nuevos circuitos a los ya existentes. Si no se tiene en cuenta la mayor temperatura ambiente que suponen estos nuevos cables y se reduce la carga de los circuitos antiguos se pueden producir sobrecalentamientos peligrosos para la instalacin. En estos casos hay que recalcular las intensidades de cada circuito teniendo en cuenta el agrupamiento final resultante.

FACTORES DE CORRECCIN POR AGRUPAMIENTO


El calentamiento mtuo de los cables, cuando varios circuitos coinciden en la misma canalizacin, obliga a considerar un factor de correccin adicional para tener en cuenta la mayor dificultad para disipar el calor generado, ya esta situacin equivale a una mayor temperatura ambiente. Por esta razn, la Norma UNE 20-460-5-523 incluye la tabla 52-E1 en la que se resean los factores de correccin a considerar cuando en una canalizacin se encuentran juntos varios circuitos o varios cables multiconductores. Estos factores deben utilizarse para modificar las intensidades indicadas en la tabla 52-C20 o en la tabla bsica simplificada antes citada.
Nmero de circuitos o cables multiconductores Disposicin de cables 1 En una superficie, empotrados o embutidos Capa nica sobre pared suelo o superficie plena Capa nica en el techo Capa nica en una su-perficie perforada. Capa nica en bandeja rejilla o abrazaderas 1,00 1,00 0,95 1,00 1,00 2 0,80 0,85 0,80 0,90 0,85 3 0,70 0,80 0,70 0,80 0,80 4 0,65 0,75 0,70 0,75 0,80 5 0,60 0,75 0,65 0,75 0,80 6 0,55 0,70 0,65 0,75 0,80 7 0,50 0,70 0,65 0,75 0,80 8 0,50 0,70 0,60 0,70 0,80 9 0,50 0,70 0,60 0,70 0,80 12 0,45 16 0,40 20 0,40

Sin reduccin adicional para ms de nueve circuitos o cables multiconductores.

www.es.pirelli.com

11

baja tensin

comentarios generales sobre los cables elctricos

Cuando los cables vayan dispuestos en varias capas superpuestas, los valores para tales disposiciones pueden ser sensiblemente inferiores y han de determinarse por un mtodo adecuado.

TIPOS DE CABLES PARA INSTALACIONES ELCTRICAS EN EDIFICIOS


A continuacin se relacionan algunos de los tipos de cables adecuados para instalaciones fijas en edificios, tanto de viviendas como comerciales o industriales: PIREPOL (rgido o flexible) PIREPOL HAZ. AFUMEX 750V. RETENAX FLEX. RETENAX FLAM BUPRENO H07RN-F / PIREFLEX AFUMEX 1000V. AFUMEX FIRS 1000V. Con las limitaciones reglamentarias pertinentes, para alimentar equipos mviles se puede utilizar, en viviendas y oficinas el cable tipo: PIREPOL GAS. Para aplicaciones industriales especficas, de acuerdo con las caractersticas de la instalacin, se podrn emplear alguno de los tipos de cables que se relacionan a continuacin: EUROFLAM N. EUROFLAM MULTIPLE. EUROFLAM O YCY. AFUMEX PANELES (rgido o flexible). RETENAX ARMADO (F M). BUPRENO. Las caractersticas particulares de estos tipos de cable, se pueden encontrar en las correspondientes pginas de este Catlogo.

www.es.pirelli.com

12

baja tensin

comentarios generales sobre los cables elctricos

B) REDES SUBTERRNEAS PARA DISTRIBUCIN EN BAJA TENSIN


Este tipo de redes puede adoptar las modalidades de: a) - Directamente enterrados. b) - Enterrados en el interior de tubos. c) - En galeras, visitables o no, en bandejas, soportes, con los cables dispuestos sobre palomillas, o directamente sujetos a la pared.

CABLES DIRECTAMENTE ENTERRADOS Y/O ENTUBADOS


INTRODUCCIN Los cables adecuados para este modo de instalacin podrn ser con conductores de cobre o de aluminio, de tensin nominal 0,6/1 kV, aislados con materiales polimricos termoestables (XLPE, EPR o similar), de acuerdo con lo especificado en la norma UNE 21123. Podrn ser de uno o ms conductores y su seccin ser la adecuada a las intensidades a transportar, de acuerdo con la norma UNE 20435, con las cadas de tensin previstas reglamentariamente. En cualquier caso no sern inferiores a 6 mm2 para conductores de cobre y a 16 mm2 para los de aluminio. El tipo de proteccin, armadura o revestimiento exterior del cable, vendr determinado por las condiciones de instalacin, fundamentalmente por los esfuerzos que deba soportar el cable durante el tendido o en el servicio posterior. Por otro lado, dependiendo del nmero de conductores con que se haga la distribucin, la seccin mnima del neutro deber ser: a) Con dos o tres conductores, igual a la de los conductores de fase b) Con cuatro conductores, la seccin del neutro ser, como mnimo la que se indica en la tabla que sigue
Conductores de fase (en mm2) 6 (Cu) 10 (Cu) 16 (Cu) 16 (Al) 25 35 50 70 Seccin del neutro (en mm2) 6 10 10 16 16 16 25 35 Conductores de fase (en mm2) 95 120 150 185 240 300 400 500 Seccin del neutro (en mm2) 50 70 70 95 120 150 185 240

Nota La seccin reducida del neutro slo es admisible para circuitos bien equilibrados y exentos de armnicos. En caso contrario la seccin del neutro debera ser igual a la de los conductores de fase o incluso superior. En cuanto a la intensidad mxima permanente admisible en los conductores, de acuerdo con lo especificado en la norma UNE 20435, depender de: La profundidad de la instalacin. La resistividad trmica y naturaleza del terreno. Temperatura mxima del terreno a la profundidad de instalacin. La proximidad de otros cables que transporten energa. La longitud de las canalizaciones dentro de tubos: nmero y agrupamiento de stos, separacin entre ellos y material que los constituya. Las tablas de carga que siguen se han previsto para las siguientes condiciones "tipo" de la instalacin: Un cable trifsico, o monofsico, trabajando con corriente alterna, directamente enterrado en todo su longitud en una zanja de 70 cm de profundidad, en un terreno de resistividad media de 100 Kcm/W y temperatura ambiente de 25C o un terno, o un par, de cables unipolares.

www.es.pirelli.com

13

baja tensin

comentarios generales sobre los cables elctricos

INTENSIDADES MXIMAS ADMISIBLES


Intensidad mxima admisible, en amperios, para cables con conductores de aluminio de los tipos AFUMEX 1000V y RETENAX (aislamiento tipo A), BUPRENO (aislamiento tipo B). CONDUCTORES DE ALUMINIO
Seccin nominal mm2 Aluminio 16 25 35 50 70 95 120 150 185 240 300 400 Terna de cables unipolares (1) A 97 125 150 180 220 260 295 330 375 430 485 550 B 94 120 145 175 215 255 290 325 365 420 475 540 1 cable tripolar o tetrapolar A 90 115 140 165 205 240 275 310 350 405 460 520 B 86 110 135 160 200 235 270 305 345 395 445 500 2 cables unipolares 1 cable bipolar

Tipo de aislamiento A 118 153 183 319 269 318 361 404 459 526 594 673 B 115 147 177 214 263 312 355 398 447 514 581 661 A 110 140 171 202 251 294 336 379 428 496 563 637 B 105 134 165 196 245 287 330 373 422 483 545 612

(1) incluye el conductor neutro, si existe. Intensidad mxima admisible, en amperios, para cables con conductores de cobre de los tipos AFUMEX 1000V y RETENAX (aislamiento tipo A), BUPRENO (aislamiento tipo B). CONDUCTORES DE COBRE
Seccin nominal mm2 Cobre 6 10 16 25 35 50 70 95 120 150 185 240 300 400 Terna de cables unipolares (1) A 72 96 125 160 190 230 280 335 380 425 480 550 620 705 B 70 94 120 155 185 225 270 325 375 415 470 540 610 690 1 cable tripolar o tetrapolar A 66 88 115 150 180 215 260 310 355 400 450 520 590 665 B 64 85 110 140 175 205 250 305 350 390 440 505 565 645 2 cables unipolares 1 cable bipolar

Tipo de aislamiento A 88 117 153 196 232 281 343 410 465 520 588 673 759 863 B 85 115 147 189 226 275 330 398 459 508 575 661 747 845 A 90 107 140 183 220 263 318 374 434 490 551 637 722 814 B 78 104 134 171 214 251 306 373 428 477 539 618 692 790

(1) incluye el conductor neutro, si existe. Se advierte que cuando la carga no est equilibrada, con diferencias superiores al 10% entre las fases, o se prevea la presencia de armnicos en la red, fundamentalmente el tercer armnico, puede ser necesario aumentar la seccin del conductor neutro hasta garantizar un calentamiento adecuado de este conductor. En el supuesto de que las condiciones reales de la instalacin sean distintas a las consideradas para la instalacin tipo, los valores de las intensidades indicados en las tablas anteriores debern modificarse para que, en ningn caso, las temperaturas alcanzadas por los conductores excedan las establecidas para estos tipos de cables en servicio permanente (90C).

www.es.pirelli.com

14

baja tensin

comentarios generales sobre los cables elctricos

FACTORES DE CORRECCIN
Si la temperatura del terreno es distinta a 25C, se aplicarn los factores de correccin de la tabla siguiente. FACTOR DE CORRECCIN, F, PARA TEMPERATURAS DEL TERENO DISTINTAS DE 25C.
Temperatura de servicio (eS) (en C) 90 Temperatura del terreno (et) (en C) 10 1,11 15 1,07 20 1,04 25 1 30 0,96 35 0,92 40 0,88 45 0,83 50 0,78

El factor de correccin para otras temperaturas del terreno, distintas de las de la tabla, ser: F = 3[(90-et)/65] Si la conductividad trmica del terreno es distinta a 1 Km/W, se aplicarn los siguientes factores de correccin: FACTOR DE CORRECCIN PARA UNA RESISTIVIDAD TRMICA DEL TERRENO DISTINTA DE 1 Km/W.
Tipo de cable Unipolar Tripolar Resistividad trmica del terreno (en km/W) 0,80 1,09 1,07 0,85 1,06 1,05 0,90 1,04 1,03 1 1 1 1,10 0,96 0,97 1,20 0,93 0,94 1,40 0,87 0,89 1,65 0,81 0,84 2,00 0,75 0,78 2,50 0,68 0,71 2,80 0,66 0,69

Si en una misma zanja coinciden varios circuitos distintos, el calentamiento mtuo modificar las condiciones "tipo", por lo que se debern considerar los factores de correccin que siguen: FACTOR DE CORRECCIN PARA AGRUPACIONES DE CABLES TRIFSICOS O TERNOS DE CABLES UNIPOLARES ENTERRADOS EN LA MISMA ZANJA
Esparacin entre cables o ternos En contacto d = 0,07 m d = 0,10 m d = 0,15 m d = 0,20 m d = 0,25 m Nmero de cables o ternos en la zanja 2 0,80 0,85 0,85 0,87 0,88 0,89 3 0,70 0,75 0,76 0,77 0,79 0,80 4 0,64 0,68 0,69 0,72 0,74 0,76 5 0,60 0,64 0,65 0,68 0,70 0,72 6 0,56 0,60 0,62 0,66 0,68 0,70 8 0,53 0,56 0,58 0,62 0,64 0,66 10 0,50 0,53 0,55 0,59 0,62 0,64 12 0,47 0,50 0,53 0,57 0,60 0,62

FACTORES DE CORRECCIN PARA VARIOS CABLES ENTERRADOS EN LA MISMA ZANJA

Si la profundidad a la que est enterrado el cable es distinta a 70 cm, se considerar el factor de correccin correspondiente: FACTOR DE CORRECCIN PARA DIFERENTES PROFUNDIDADES DE TENDIDO
Profunidad (en metros) Factor de correccin 0,40 1,03 0,50 1,02 0,60 1,01 0,70 1 0,80 0,99 0,90 0,98 1,00 00,97 1,20 0,95

En el caso de cables enterrados en zanja en el interior de tubos o similares, siempre que sea posible se instalar un circuito por tubo, cuyo dimetro interior sea el doble del dimetro exterior del cable. Este modo de instalacin supone un incremento de la resistencia trmica respecto al enterrado directamente, por lo que se aplicarn los factores de correccin que se indican a continuacin:

www.es.pirelli.com

15

baja tensin

comentarios generales sobre los cables elctricos

- Canalizaciones entubadas. a) Canalizaciones bajo tubo de corta longitud Se consideran de corta longitud, aquellas canalizaciones que tienen menos de 15 metros. En este caso, si el tubo se rellena con aglomerados de baja resistencia trmica (bentonita, etc), no ser necesario aplicar ningn factor de correccin. b) Otras canalizaciones entubadas Si se trata de un cable trifsico, o una terna de cables unipolares, o monofsico, o bipolar, o un par de cables unipolares en el interior de un mismo tubo, se aplicar un factor de correccin de 0,8. Si cada cable unipolar va por un tubo distinto, se aplicar un factor de correccin de 0,9. En este caso, los tubos no debern ser de hierro, para evitar prdidas magnticas. La agrupacin de varios tubos se considerar como agrupacin de circuitos.

CABLES INSTALADOS EN GALERAS SUBTERRNEAS


INTRODUCCIN Este modo de instalacin no es exactamente una instalacin subterrnea, pues tanto en las galeras visitables como en las zanjas o canales revisables se deber haber previsto una eficaz renovacin del aire, que permita una buena disipacin del calor generado por las prdidas en el cable, de tal manera, que la temperatura ambiente no supere los 40C. Segn los casos, los cables irn dispuestos en bandejas, soportes, palomillas, o directamente sujetos a la pared mediante abrazaderas u otros dispositivos que proporcionen a la instalacin una adecuada seguridad, en particular para soportar los esfuerzos electrodinmicos producidos en un eventual cortocircuito. Las caractersticas de estos cables se describen en la norma UNE 21123.

INTENSIDADES MXIMAS ADMISIBLES


Las intensidades admisibles y los factores de correccin a considerar, se han tomado de la norma UNE 20435, para el supuesto de instalaciones al aire en las condiciones "tipo" siguientes: Un cable trifsico o monofsico, o un terno o un par de cables unipolares agrupados en contacto, con una colocacin tal que permitan una eficaz renovacin del aire, siendo la temperatura ambiente de 40C. Intensidades mximas admisibles, en servicio permanente, para cables de los tipos AFUMEX 1000V y RETENAX (aislamiento tipo a), BUPRENO (aislamiento tipo B), instalados al aire.
Conductores de aluminio Seccin nominal mm2 3 cables unipolares 1 cable trifsico Conductores de cobre 3 cables unipolares 1 cable trifsico

Tipo de aislamiento A 67 93 115 140 180 220 260 300 350 420 480 560 B 65 90 110 134 175 215 255 290 345 400 465 545 A 64 85 105 130 165 205 235 275 315 370 425 505 B 63 82 100 125 155 195 225 260 300 360 405 475 A 46 64 86 120 145 180 230 285 335 385 450 535 615 720 B 45 62 83 115 140 175 225 280 325 375 440 515 595 700 A 44 61 82 110 135 165 210 260 300 350 400 475 545 645 B 43 60 80 105 130 160 220 250 290 335 385 460 520 610

6 10 16 25 35 50 70 95 120 150 185 240 300 400

En las condiciones tipo indicadas. Para el caso de dos cables unipolares o un cable bipolar, multiplicar por 1,225 la intensidad correspondiente a tres cables unipolares o un cable tripolar.

www.es.pirelli.com

16

baja tensin

comentarios generales sobre los cables elctricos

FACTORES DE CORRECCIN
En el caso de que la temperatura ambiente fuera distinta de 40 C, se aplicara el factor de correccin correspondiente, tomado de la tabla que sigue. FACTOR DE CORRECCIN F PARA TEMPERATURA AMBIENTE DISTINTA DE 40 C
Temperatura de servicio (eS) (en C) 90 Temperatura ambiente (et) (en C) 10 1,27 15 1,22 20 1,18 25 1,14 30 1,10 35 1,05 40 1 45 0,95 50 0,90 55 0,84 60 0,77

El factor de correccin para otras temperaturas del ambiente, distintas de las tabuladas, ser: F = 3 [(90-eA)/50 En las tablas que siguen se dan los factores de correccin a aplicar en los agrupamientos de varios circuitos constituidos por cables unipolares o multipolares, de acuerdo con el tipo de instalacin. FACTOR DE CORRECCIN PARA AGRUPACIONES DE CABLES UNIPOLARES
N de circuitos trifsicos (2) Tipo de instalacin N de bandejas Bandejas perforadas horizontales contiguos (3) Bandejas perforadas verticales contiguos (4) Bandejas escalera soporte, etc. (3) Bandejas perforadas (3) Bandejas perforadas verticales (4) Bandejas escalera, soporte, etc. (3) 1 2 3 1 2 1 2 3 1 2 3 1 2 1 2 3 1 0,95 0,95 0,90 0,95 0,90 1,00 0,95 0,95 1,00 0,95 0,95 1,00 1,00 1,00 0,95 0,95 2 0,90 0,85 0,85 0,85 0,85 0,95 0,90 0,90 1,00 0,95 0,90 0,90 0,90 1,00 0,95 0,95 3 0,85 0,80 0,80 0,95 0,90 0,85 0,95 0,90 0,85 0,90 0,85 1,00 0,95 0,90 Tres cables en capa horizontal Tres cables en capa vertical Tres cables en capa horizontal Tres cables dispuestos en trbol A utilizar para (1)

NOTAS: (1) incluye, adems, el conductor neutro, si existe. (2) Para circuitos con varios cables en paralelo, por fase, a los efectos de aplicacin de esta tabla, cada grupo de tres conductores se considera como un circuito. (3) Los valores estn indicados para una distancia vertical entre bandejas de 300 mm. Para distancias ms pequeas habr que reducir los factores. (4) Los valores estn indicados para una distancia horizontal entre bandejas de 225 mm, estando las bandejas montadas dorso con dorso. Para distancias ms pequeas habr que reducir los factores. FACTOR DE CORRECCIN PARA APLICACIONES DE CABLES TRIFSICOS
Tipo de instalacin Bandejas perforadas, cables contiguos (2) Bandejas perforadas, cables espaciados (2) N de bandejas 1 2 3 1 2 3 1,00 1,00 1,00 1,00 1,00 1,00 0,90 0,85 0,85 1,00 1,00 1,00 Nmero de circuitos trifsicos (nota 2) 0,80 0,80 0,80 1,00 0,95 0,95 0.80 0,75 0,75 0,95 0,90 0,90 0,75 0,75 0,70 0,90 0,85 0,85 0,75 0,70 0,65

www.es.pirelli.com

17

baja tensin

comentarios generales sobre los cables elctricos

FACTOR DE CORRECCIN PARA APLICACIONES DE CABLES TRIFSICOS (Continuacin)


Tipo de instalacin Bandejas verticales perforadas, cables contiguos (3) Bandejas verticales perforadas, cables espaciados (3) Bandejas escalera soporte etc. cables contiuguos (2) Bandejas escalera soporte etc. cables espaciados (2) N de bandejas 1 2 1 2 1 2 3 1 2 3 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 0,90 0,90 0,90 0,90 0,85 0,85 0,85 1,00 1,00 1,00 Nmero de circuitos trifsicos (nota 2) 0,80 0,80 0,90 0,90 0,80 0,80 0,80 1,00 1,00 0,95 0,75 0,75 0,90 0,85 0,80 0,80 0,75 1,00 0,95 0,95 0,75 0,70 0,85 0,85 0,80 0,75 0,75 1,00 0,95 0,75 0,70 0,70 0,80 0,75 0,70

NOTAS: (1) incluye, adems, el conductor neutro, si existiese. (2) Los valores estn indicados para una distancia vertical entre bandejas de 300 mm. Para distancias menores, se reducirn los factores de correccin. (3) Los valores estn indicados para una distancia horizontal entre bandejas de 225 mm, estando las bandejas montadas dorso con dorso. Para distancias ms pequeas se reducirn los factores de correccin. INTENSIDADES DE CORTOCIRCUITO ADMISIBLES EN LOS CONDUCTORES En las tablas que siguen se indican las densidades de corriente de cortocircuito, en A/mm2, admisibles en los conductores de aluminio y de cobre de los cables aislados con materiales termoestables, en funcin de los tiempos de duracin del cortocircuito y algunas intensidades de cortocircuito en A, para algunas secciones usuales.

DENSIDAD DE CORRIENTE DE CORTOCIRCUITO, EN A/mm2, PARA CONDUCTORES DE ALUMINIO


Tipo de aislamiento XLPE y EPR Tcc C 250 Duracin del cortocircuito, en segundos 0,1 294 0,2 203 0,3 170 0,5 132 1,0 93 1,5 76 2,0 66 2,5 59 3,0 54

DENSIDAD DE CORRIENTE DE CORTOCIRCUITO, EN A/mm2, PARA CONDUCTORES DE COBRE


Tipo de aislamiento XLPE y EPR Tcc C 250 Duracin del cortocircuito, en segundos 0,1 449 0,2 318 0,3 259 0,5 201 1,0 142 1,5 116 2,0 100 2,5 90 3,0 82

En base a las densidades de corriente de cortocircuito citadas anteriormente, en A/mm2, a continuacin se indican las intensidades mximas de cortocircuito admisibles, en kA, en funcin de los diferentes tiempos de duracin del cortocircuito para algunas secciones tpicas.

CONDUCTORES DE ALUMINIO
Seccin del conductor (mm2) 16 25 50 95 150 240 Duracin del cortocircuito (en s) 0,1 4,7 7,3 14,7 27,9 44,1 70,6 0,2 3,2 5,0 10,1 19,2 30,4 48,7 0,3 2,7 4,2 8,5 16,1 25,5 40,8 0,5 2,1 3,3 6,6 12,5 19,8 31,7 1,0 1,4 2,3 4,6 8,8 13,9 22,3 1,5 1,2 1,9 3,8 7,2 11,4 18,2 2,0 1,0 1,6 3,3 6,2 9,9 15,8 2,5 0,9 1,4 2,9 5,6 8,8 14,2 3,0 0,8 1,3 2,7 5,1 8,1 13,0

www.es.pirelli.com

18

baja tensin

comentarios generales sobre los cables elctricos

CONDUCTORES DE COBRE
Seccin del conductor (mm2) 16 25 50 95 150 240 Duracin del cortocircuito (en s) 0,1 7,2 11,2 22,4 42,6 67,3 108 0,2 5,0 7,9 15,9 30,2 47,7 76,3 0,3 4,1 6,4 12,9 24,6 38,8 62,1 0,5 3,2 5,0 10,0 19,0 30,1 48,2 1,0 2,2 3,5 7,1 13,4 21,3 34,0 1,5 1,8 2,9 5,8 11,0 17,4 27,8 2,0 1,6 2,5 5,0 9,5 15,0 24,0 2,5 1,4 2,2 4,5 8,5 13,5 21,6 3,0 1,3 2,0 4,1 7,8 12,3 19,6

Para otros tipos de cable o sistemas de instalacin, deber consultarse la norma UNE 20 435, o calcularse el rgimen de cargas de acuerdo con el contenido de la norma UNE 21 144.

TIPOS DE CABLES PARA REDES SUBTERRNEAS PARA DISTRIBUCIN EN BAJA TENSIN


A continuacin se relacionan algunos de los tipos de cables ms adecuados para instalaciones en redes subterrneas para distribucin en Baja Tensin: RETENAX FLEX RETENAX FLAM AFUMEX 1000 V RETENAX ARMADO BUPRENO AL VOLTALENE N Las caractersticas particuares de estos tipos de cables, se pueden encontrar en las correspondientes pginas de este catlogo.

www.es.pirelli.com

19

baja tensin

comentarios generales sobre los cables elctricos

C) CABLES A LA INTEMPERIE PARA LA DISTRIBUCIN EN BAJA TENSIN


INTRODUCCIN Los cables adecuados para estas instalaciones, debern ser de una tensin nominal de 0,6/1 kV, aislados y cubiertos con materiales polimricos termoestables adecuados para soportar la accin de la intemperie, de acuerdo con las especificaciones de la norma UNE 21030 o UNE 21123, con una seccin adecuada a la corriente que deban transportar y capaces de soportar, en el caso de redes tensadas autoportantes, la traccin mecnica de tensado. En el caso de utilizar cables de tensiones nominales inferiores, se les considerar como si se tratara de conductores desnudos y se debern adoptar las precauciones de instalacin y servicio adecuadas a este tipo de material. Estos cables, de tensin nominal 0,6/1 kV, se podrn instalar como: Cables posados directamente sobre los muros mediante abrazaderas slidamente fijadas a los mismos y resistentes a la accin de la intemperie, o sobre cualquier otro soporte que les proporcione anloga robustez. Cables tensados entre piezas especiales colocadas sobre apoyos o sobre muros, con una tensin mecnica adecuada, no considerando al aislamiento o la cubierta del cable, si la tuviera, como un elemento resistente a estos efectos. Cuando los conductores no soporten por si solos la tensin mecnica necesaria, se utilizaran cables fiadores de acero galvanizado, a los que se fijar, mediante abrazaderas u otros dispositivos apropiados, los cables aislados. En los cables tensados, la seccin mnima ser la de 16 mm2 en los cables de aluminio y de 10 mm2 en el cobre. En los conductores de cobre se acepta una seccin mnima de 4 mm2 si el cable va suspendido de un fiador y, por tanto, no debe soportar esfuerzo mecnico alguno.

INTENSIDADES MXIMAS ADMISIBLES


En las tablas que siguen figuran las intensidades mximas admisibles en rgimen permanente para estos tipos de cable, en condiciones normales de instalacin. Se definen como condiciones normales de instalacin las que corresponden a un solo cable, instalado al aire libre y a una temperatura de 40C. Para otras condiciones distintas se aplicarn los factores de correccin definidos en los apartados correspondientes. CABLES AISLADOS CABLEADOS EN HAZ, PARA LNEAS AREAS DE 0,6/1 kV DE TENSIN NOMINAL Segn UNE 21030. (Tipo POLIRRET)
Nmero de conductores por seccin (en mm2) 1 x 25 Al/54,6 Alm 1 x 50 Al/54,6 Alm 3 x 25 Al/54,6 Alm 3 x 50 Al/54,6 Alm 3 x 95 Al/54,6 Alm 3 x 150 Al/54,6 Alm Intensidad mxima (en A) 110 165 100 150 230 305

CABLES SIN NEUTRO FIADOR PARA INSTALACIONES DE CABLES POSADAS, O TENSADAS CON FIADOR DE ACERO (Tipo POLIRRET)
Nmero de conductores por seccin (en mm2) 2 x 16 Al 2 x 25 Al 4 x 16 Al 4 x 25 Al 4 x 50 A l 3 x 95/50 Al 3 x 150/95 Al Intensidad mxima (en A) Posada sobre fachadas 73 101 67 90 133 207 277 Tendida con fiador de acero 81 109 72 97 144 223 301

www.es.pirelli.com

20

baja tensin

comentarios generales sobre los cables elctricos

Nmero de conductores por seccin (en mm2) 2 x 4 Cu 2 x 6 Cu 2 x 10 Cu 4 x 4 Cu 4 x 6 Cu 4 x 10 Cu 4 x 16 Cu

Intensidad mxima (en A) Posada sobre fachadas 45 57 77 37 47 65 86 Tendida con fiador de acero 50 63 85 41 52 72 95

Tambin podrn instalarse a la intemperie, grapados sobre muros, soportados por un fiador de acero mediante abrazaderas u otros dispositivos adecuados o cualquier otro procedimiento que proporcione a la instalacin una adecuada seguridad, los cables descritos en la norma UNE 21123, cuyas intensidades admisibles y factores de correccin correspondientes, para cables tendidos al aire se presentan en la norma UNE 20435, para las condiciones "tipo" antes citadas, siempre que se prevea una eficaz circulacin del aire alrededor del cable, que disipe el calor generado por las prdidas del cable. CABLES DE TRANSPORTE DE ENERGA AISLADOS CON DIELCTRICOS SECOS EXTRUDOS PARA UNA TENSIN NOMINAL DE 0,6/1 kV. Segn UNE 20435 Intensidades mximas admisibles, en servicio permanente, para cables de los tipos AFUMEX 1000V y RETENAX (aislamiento tipo A), BUPRENO (aislamiento tipo B), instalados al aire.
Conductores de aluminio Seccin nominal mm2 3 cables unipolares 1 cable trifsico Conductores de cobre 3 cables unipolares 1 cable trifsico

Tipo de aislamiento A 67 93 115 140 180 220 260 300 350 420 480 560 645 740 B 65 90 110 135 175 215 255 290 345 400 465 545 625 715 A 64 85 105 130 165 205 235 275 315 370 425 505 B 63 82 100 125 155 195 225 260 300 360 405 475 A 46 64 86 120 145 180 230 285 335 385 450 535 615 720 825 950 B 45 62 83 115 140 175 2255 280 325 375 440 515 595 700 800 915 A 44 61 82 110 135 165 210 260 300 350 400 475 545 645 B 43 60 80 105 130 160 220 250 290 335 385 460 520 610

6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

En las condiciones tipo indicadas. Para el caso de dos cables unipolares o un cable bipolar, multiplicar por 1,225 la intensidad correspondiente a tres cables unipolares o un cable tripolar.

FACTORES DE CORRECCIN
En el caso de que la temperatura ambiente fuera distinta de 40C, se aplicara el factor de correccin correspondiente tomado de la tabla que sigue. FACTOR DE CORRECCIN PARA TEMPERATURA AMBIENTE DISTINTA DE 40 C
Temperatura de servicio (eS) (en C) 90 Temperatura ambiente (ea) (en C) 10 1,27 15 1,22 20 1,18 25 1,14 30 1,10 35 1,05 40 1 45 0,95 50 0,90 55 0,84 60 0,77

www.es.pirelli.com

21

baja tensin

comentarios generales sobre los cables elctricos

El factor de correccin para otras temperaturas del ambiente, distintas de las tabuladas, ser: F = 3[(90-eA)/50] En el caso de que los cables estn expuestos directamente al sol, se aplicar un factor 0,9. En las tablas que siguen se dan los factores de correccin a aplicar en los agrupamientos de varios circuitos constituidos por cables unipolares o multipolares, de acuerdo con el tipo de instalacin. Para redes areas tensadas o pasadas con cables del tipo POLIRRET sobrepuestas, se aplicarn los siguientes factores de correccin:
Nmero de cables Factor de correccin 1 1,00 2 0,89 3 0,80 Ms de 3 0,75

Para las redes posadas sobre bandejas con otros tipos de cables (RETENAX, EPROTENAX o AFUMEX X) se aplicarn los siguientes: FACTOR DE CORRECCIN PARA AGRUPACIONES DE CABLES UNIPOLARES INSTALADOS AL AIRE
N de circuitos trifsicos (2) Tipo de instalacin N de bandejas Bandejas perforadas horizontales, cables contiguos (3) Bandejas perforadas verticales, cables contiguos (4) Bandejas escalera soporte, etc. (3) Bandejas perforadas (3) Bandejas perforadas verticales (4) Bandejas escalera, soporte, etc. (3) 1 2 3 1 2 1 2 3 1 2 3 1 2 1 2 3 1 0,95 0,95 0,90 0,95 0,90 1,00 0,95 0,95 1,00 0,95 0,95 1,00 1,00 1,00 0,95 0,95 2 0,90 0,85 0,85 0,85 0,85 0,95 0,90 0,90 1,00 0,95 0,90 0,90 0,90 1,00 0,95 0,95 3 0,85 0,80 0,80 0,95 0,90 0,85 0,95 0,90 0,85 0,90 0,85 1,00 0,95 0,90 Tres cables en capa horizontal Tres cables en capa vertical Tres cables en capa horizontal Tres cables dispuestos en trbol A utilizar para (1)

NOTAS: (1) incluye, adems, el conductor neutro, si existe. (2) Para circuitos con varios cables en paralelo, por fase, a los efectos de aplicacin de esta tabla, cada grupo de tres conductores se considera como un circuito. (3) Los valores estn indicados para una distancia vertical entre bandejas de 300 mm. Para distancias ms pequeas habr que reducir los factores. (4) Los valores estn indicados para una distancia horizontal entre bandejas de 225 mm, estando las bandejas montadas dorso con dorso. Para distancias ms pequeas habr que reducir los factores. FACTOR DE CORRECCIN PARA APLICACIONES DE CABLES TRIFSICOS AL AIRE
Tipo de instalacin Bandejas perforadas, cables contiguos (2) Bandejas perforadas, cables espaciados (2) Nmero de circuitos trifsicos (nota 2) N de bandejas 1 2 3 1 2 3 1 1,00 1,00 1,00 1,00 1,00 1,00 2 0,90 0,85 0,85 1,00 1,00 1,00 3 0,80 0,80 0,80 1,00 0,95 0,95 4 0.80 0,75 0,75 0,95 0,90 0,90 6 0,75 0,75 0,70 0,90 0,85 0,85 9 0,75 0,70 0,65

www.es.pirelli.com

22

baja tensin

comentarios generales sobre los cables elctricos

FACTOR DE CORRECCIN PARA APLICACIONES DE CABLES TRIFSICOS AL AIRE (Continuacin)


Tipo de instalacin Bandejas verticales, perforadas, cables contiguos (3) Bandejas verticales, perforadas, cables espaciados (3) Bandejas escalera soporte etc, cables contiguos (2) Bandejas escalera soporte etc, cables espaciados (2) N de bandejas 1 2 1 2 1 2 3 1 2 3 Nmero de circuitos trifsicos (nota 2) 1 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 2 0,90 0,90 0,90 0,90 0,85 0,85 0,85 1,00 1,00 1,00 3 0,80 0,80 0,90 0,90 0,80 0,80 0,80 1,00 1,00 0,95 4 0,75 0,75 0,90 0,85 0,80 0,80 0,75 1,00 0,95 0,95 6 0,75 0,70 0,85 0,85 0,80 0,75 0,75 1,00 0,95 0,75 9 0,70 0,70 0,80 0,75 0,70

NOTAS: (1) Incluye, adems, el conductor neutro, si existiese. (2) Los valores estn indicados para una distancia vertical entre bandejas de 300 mm. Para distancias menores, se reducirn los factores de correccin. (3) Los valores estn indicados para una distancia horizontal entre bandejas de 225 mm, estando las bandejas montadas dorso con dorso. Para distancias ms pequeas se reducirn los factores de correccin.

TIPOS DE CABLES PARA INSTALACIONES A LA INTEMPERIE PARA DISTRIBUCIN EN BAJA TENSIN


Los tipos de cable a utilizar en estas instalaciones son: Redes tensadas: autoportantes con neutro de ALMELEC: AL POLIRRET. con cable fiador de acero: AL POLIRRET. POLIRRET CU. AL VOLTALENE N. RETENAX FLAM. AFUMEX 1000V. Redes posadas: AL POLIRRET. POLIRRET CU. RETENAX FLAM. AFUMEX 1000V. AL VOLTALENE N. Las caractersticas dimensionales, elctricas y mecnicas de estos cables podrn obtenerse a partir de la pgina de este Catlogo donde se describe el tipo de cable seleccionado.

www.es.pirelli.com

23

www.es.pirelli.com

24

baja tensin

cables para edificacin e industria

PIREPOL FLEXIBLE
Tensin nominal:

500 V 750 V

Norma bsica:

UNE 21031/3

Designacin genrica:

H05V-K H07V-K

CARACTERSTICAS CABLE

Extradeslizante

Resistencia a la absorcin del agua

No propagacin de la llama

No propagacin del incendio

Reducida emsin de halgenos

Cable flexible

Norma constructiva: UNE 21031/3; CENELEC HD 21.3 S2. Temperatura de servicio (instalacin fija):-25C, +70C. Tensin nominal de servicio: hasta 1mm2 -> 500V., desde 1,5mm2 -> 750V. Ensayo de tensin en c.a. durante 5 minutos: 2000V en los cables H05V-K y 2500V en los cables H07V-K. Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1; IEC 60332-1; NFC 32070-C2. No propagacin del incendio: UNE EN 50266-2-4; UNE 20427; IEC 60332-3; IEEE 383; NFC 32070-C1. Reducida emisin de halgenos: UNE EN 50267-2-1; IEC 60754-1 (emisin CLH < 20%).

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 5, segn UNE 21022. Temperatura mxima en el conductor: 70C en servicio permanente, 160 C en cortocircuito.

AISLAMIENTO
Mezcla de PVC del tipo TI1, en los colores: negro, azul, marrn, gris, amarillo-verde y blanco.

APLICACIONES
H05V-K: Montaje fijo protegido, slo en el caso de circuitos de sealizacin o control, timbres, alarmas domsticas o similares. H07V-K: Instalacin en conductos situados sobre superficies o empotrados, o en sistemas cerrados anlogos.

www.es.pirelli.com

25

baja tensin

cables para edificacin e industria

PIREPOL FLEXIBLE
Tensin nominal:

500 V 750 V

Norma bsica:

UNE 21031/3

Designacin genrica:

H05V-K H07V-K

CABLES DISPONIBLES EN STOCK


TABLA DE COLORES SEGN SECCIN
Seccin Colores cable Colores caja

1 x 0,50 1 x 0,75 1x1 1 x 1,5 1 x 2,5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95

AV-BL-RO-MA-AZ-GR-NE-VE AM-AV-BL-RO-MA-AZ-GR-NE-VE AV-BL-MA-AZ-GR-NE AV-RO-MA-AZ-GR-NE-BL AV-RO-MA-AZ-GR-NE AV-RO-MA-AZ-GR-NE AV-RO-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-AZ-NE AV-NE

Naranja Azul Verde Rojo Azul Marrn Gris Naranja Azul claro Marrn -

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor del aislamiento mm Dimetro ext. mx. mm Peso total aprox. Kg/Km Resistencia hmica a 20 C del conductor Ohm/Km

PIREPOL 3 - flexible (tipo H05V-K)


1 x 0,5 1 x 0,75 1x1 0,6 0,6 0,6 2,4 2,6 2,8 9 12 14 39 26,5 19,5

PIREPOL 3 - flexible (tipo H07V-K)


1 x 1,5 1 x 2,5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 0,7 0,8 0,8 0,8 1,0 1,0 1,2 1,2 1,4 1,4 1,6 3,5 4,2 4,8 6,3 7,6 8,8 11,12,5 14,5 17,19,20 32 48 68 135 195 295 400 565 790 1040 13,3 7,98 4,95 3,30 1,91 1,21 0,78 0,554 0,386 0,272 0,206

www.es.pirelli.com

26

baja tensin

cables para edificacin e industria

PIREPOL RGIDO
Tensin nominal:

500 V 750 V

Norma bsica:

UNE 21031/3

Designacin genrica:

H05V-U H07V-U H07V-R

CARACTERSTICAS CABLE

Extradeslizante

Resistencia a la absorcin del agua

No propagacin de la llama

No propagacin del incendio

Reducida emsin de halgenos

Norma constructiva: UNE 21031/3; CENELEC HD 21.3 S2. Temperatura de servicio (instalacin fija): -25C, +70C. Tensin nominal de servicio: hasta 1mm2 -> 500V., desde 1,5mm2 -> 750V. Ensayo de tensin en c.a. durante 5 minutos: 2000V en los cables H05V-U y 2500V en los cables H07V-U y H07V-R. Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1; IEC 60332-1; NFC 32070-C2. No propagacin del incendio: UNE EN 50266-2-4; UNE 20427; IEC 60332-3; IEEE 383; NFC 32070-C1. Reducida emisin de halgenos: UNE EN 50267-2-1; IEC 60754-1 (emisin CLH < 20%).

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 1 hasta 4 mm2, clase 2 desde 6 mm2; segn UNE 21022. Temperatura mxima en el conductor: 70C en servicio permanente, 160C en cortocircuito.

AISLAMIENTO
Mezcla de PVC del tipo TI1, en los colores: negro, azul, marrn, gris, amarillo-verde y blanco.

APLICACIONES
H05V-U: Montaje fijo protegido, slo en el caso de circuitos de sealizacin o control, timbres de alarmas domsticas o similares. H07V-U, H07V-R: Instalacin en conductos situados sobre superficies o empotrados, o en sistemas anlogos.

www.es.pirelli.com

27

baja tensin

cables para edificacin e industria

PIREPOL RGIDO
Tensin nominal:

500 V 750 V

Norma bsica:

UNE 21031/3

Designacin genrica:

H05V-U H07V-U H07V-R

CABLES DISPONIBLES EN STOCK


TABLA DE COLORES SEGN SECCIN
Seccin Colores cable Colores caja

1x1 1 x 1,5 1 x 2,5 1x4 1x6 1 x 10 1 x 16

AV-BL-MA-AZ-GR-NE AV-BL-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-MA-AZ-GR-NE AV-MA-AZ-GR-NE

Verde Rojo Azul Marrn Gris Naranja Azul claro

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor del aislamiento mm Dimetro ext. mx. mm Peso total aprox. Kg/Km Resistencia hmica a 20C del conductor Ohm/Km

PIREPOL 3 - rgido (tipo H05V-U)


1x1 1 x 1,5 1 x 2,5 1x4 0,6 0,7 0,8 0,8 2,4 3,3 3,9 4,4 9 21 32 47 36 12,1 7,41 4,61

PIREPOL 3 - rgido (tipo H07V-U)

PIREPOL 3 - rgido (tipo H07V-R)


1x6 1 x 10 1 x 16 0,8 1 1 5,4 6,8 8 67 125 180 3,08 1,83 1,15

www.es.pirelli.com

28

baja tensin

cables para edificacin e industria

PIREPOL HAZ
Tensin nominal:

750 V

Norma bsica:

UNE 21031/3

Designacin genrica:

H07V-K H07V-R

CARACTERSTICAS CABLE

Extradeslizante

Resistencia a la absorcin del agua

No propagacin de la llama

No propagacin del incendio

Reducida emsin de halgenos

Cable flexible

Norma constructiva: UNE 21031/3; CENELEC HD 21.3 S2. Temperatura de servicio (instalacin fija):-25C, +70C. Tensin nominal de servicio: 750V. Ensayo de tensin en c.a. durante 5 minutos: 2500V. Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1; IEC 60332-1; NFC 32070-C2. No propagacin del incendio: UNE EN 50266-2-4; UNE 20427; IEC 60332-3; IEEE 383; NFC 32070-C1. Reducida emisin de halgenos: UNE EN 50267-2-1; IEC 60754-1; UNE EN 50267-2-1. (emisin CLH <= 20%).

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 5, segn UNE 21022, (IEC 60228). Temperatura mxima en el conductor: 70C en servicio permanente, 160C en cortocircuito.

AISLAMIENTO
Mezcla de PVC del tipo TI1, en los colores: negro, azul, marrn y amarillo, combinados segn formacin del haz: 2 conds.: marrn y azul. 3 conds.: negro, azul y amarillo-verde. 4 conds.: negro, marrn, azul y amarillo-verde. 5 conds.: negro, negro, marrn, azul y amarillo- verde. Conductor rojo de 1,5 para control horario.

APLICACIONES
Cables deslizantes de buena flexibilidad para instalaciones fijas en conductos situados sobre superficie o empotrados, o en sistemas cerrados anlogos, desarrollados a partir del cableado de dos o ms cables del tipo PIREPOL FLEXIBLE. Especialmente indicado para derivaciones individuales en instalaciones de enlace.

www.es.pirelli.com

29

baja tensin

cables para edificacin e industria

PIREPOL HAZ
Tensin nominal:

750 V

Norma bsica:

UNE 21031/3

Designacin genrica:

H07V-K H07V-R

CABLES DISPONIBLES EN STOCK


SECCIONES DISPONIBLES
Flexible

3G6 3 G 10 3 G 16 3 G 25 5G6 5 G 10
Rgido

3 G 6 - 1 x 1,5 3 G 10 - 1 x 1,5 3 G 16 - 1 x 1,5 3 G 25 - 1 x 1,5

DIMENSIONES
Seccin nominal mm2 Longitud carrete m Espesor aislante mm Dimetro alma mm Dimetro haz m) Peso aprox. kg/km Resistencia hmmica (hmio/km) *

3G6 3 G 10 3 G 16 3 G 25 3 G 6 - 1 x 1,5 3 G 10 - 1 x 1,5 3 G 16 - 1 x 1,5 5G6 5 G 10

400 300 200 100 400 400 200 -

0,8 1 1 1,2 0,8 1 1 0,8 1

4,6 6,2 7,2 8,8 4,6 6,2 7,2 4,6 6,2

10 12,6 15,5 19 10 12,6 14,4 12,5 16,5

191 330 490 755 212 350 504 325 550

3,30 1,91 1,21 0,78 3,30 1,91 1,21 3,30 1,91

(*) Para conductor clase 5 segn UNE 21022.

www.es.pirelli.com

30

baja tensin

cables para edificacin e industria

PIREPOL GAS
Tensin nominal:

300 V 500 V

Norma bsica:

UNE 21031/5

Designacin genrica:

H03VV-F A05VV-F H05VV-F

CARACTERSTICAS CABLE

Cable flexible

Resistencia a la absorcin del agua

No propagacin de la llama

Norma constructiva: UNE 21031/5 Temperatura de servicio (instalacin fija):-25C, +70C Tensin nominal de servicio: 500V Ensayo de tensin en c.a. durante 5 minutos: 1500V en los cables de hasta 0,6mm de espesor de aislamiento y de 2000V en los cables de ms de 0,6mm.

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 5, segn UNE 21022. Temperatura mxima en el conductor: 70C en servicio permanente, 160C en cortocircuito.

AISLAMIENTO
Capa de PVC, tipo TI2.

CUBIERTA
PVC de color gris o blanco, tipo TM2.

APLICACIONES
Para su utilizacin en los locales domsticos, cocinas, oficinas; para la alimentacin de aparatos domsticos, inclusive los que estn en locales hmedos; para esfuerzos mecnicos pequeos los cablecillos del tipo H03VV-F (aparatos porttiles ligeros) y para esfuerzos mecnicos medios los del tipo H05VV-F (centrifugadoras, lavadoras, refrigeradores, etc.).

www.es.pirelli.com

31

baja tensin

cables para edificacin e industria

PIREPOL GAS
Tensin nominal:

300 V 500 V

Norma bsica:

UNE 21031/5

Designacin genrica:

H03VV-F A05VV-F H05VV-F

CABLES DISPONIBLES EN STOCK


TABLA DE COLORES SEGN SECCIN
Seccin mm2 Colores de la cubierta Colores de los conductores Colores caja

2x1 2 x 1,5 2 x 2,5 3G1 3 G 1,5 3 G 2,5 4G1 4 G 1,5 4 G 2,5

BL / GR BL / GR BL BL / GR BL / GR BL / GR BL / GR BL BL

AZ-MA AZ-MA AZ-MA AV-AZ-MA AV-AZ-MA AV-AZ-MA AV-AZ-MA-NE AV-AZ-MA-NE AV-AZ-MA-NE

Verde Verde Verde Verde Verde Verde Verde Verde Verde

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde

www.es.pirelli.com

32

baja tensin

cables para edificacin e industria

PIREPOL GAS
Tensin nominal:

300 V 500 V

Norma bsica:

UNE 21031/5

Designacin genrica:

H03VV-F A05VV-F H05VV-F

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor aislamiento especfico mm Espesor aislamiento cubierta mm Dimetro minimo mm Dimetro exterior mximo mm Resistencia aislamiento mnimo 70C MOhm/km

H03VV-F
2 x 0.5 2 x 0.75 3 G 0.5 3 G 0.75 4 G 0.5 4 G 0.75 2 x 0.75 2x1 2 x 1.5 2 x 2.5 2x4 3 G 0.75 3G1 3 G 1.5 3 G 2.5 3G4 4 G 0.75 4G1 4 G 1.5 4G4 5 G 0.75 5G1 5 G 1.5 5 G 2.5 5G4 2x6 3G6 4G6 5G6 0.5 0.5 0.5 0.5 0.5 0.5 0.6 0.6 0.7 0.8 0.8 0.6 0.6 0.7 0.8 0.8 0.6 0.6 0.7 0.8 0.6 0.6 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0.6 0.6 0.6 0.6 0.6 0.6 0.8 0.8 0.8 1 1.1 0.8 0.8 0.9 1.1 1.2 0.8 0.9 1 1.4 0.9 0.9 1.1 1.2 1.4 1.2 1.4 1.4 1.4 4.8 5.2 5 5.4 5.6 6 6 6.4 6.2 6.8 6.8 7.4 7.6 8 9 11 12 8 8.4 9.8 12 13 8.6 9.4 11 14 9.6 10 12 14 15.5 15 16.5 18 19.5 0.012 0.01 0.012 0.01 0.012 0.01 0.011 0.01 0.01 0.009 0.007 0.011 0.01 0.01 0.009 0.007 0.011 0.01 0.01 0.007 0.011 0.01 0.01 0.009 0.007 0.0065 0.0065 0.0065 0.0065

H05VV-F
6 6.4 7.4 8.9 10 6.4 6.8 8 9.6 11 6.8 7.6 9 12 7.4 8.3 10 11.5 13.5 11.5 12.5 13.5 15

NOTA: La G, en lugar del signo x, indica que el cable lleva incorporado el conductor de proteccin Amarillo-Verde.

www.es.pirelli.com

33

www.es.pirelli.com

34

baja tensin

cables para edificacin e industria

RETENAX FLEX
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV-K 0,6/1 kV

CARACTERSTICAS CABLE

Cable flexible

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

Resistencia a los agentes qumicos

Resistencia a las grasas y aceites

No propagacin de la llama

No propagacin del incendio

Norma constructiva: UNE 21123-2 Temperatura de servicio (instalacin fija): -25C, +90C Tensin nominal de servicio: 0,6/1 kV Ensayo de tensin en c.a. durante 5 minutos: 3.500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2 No propagacin del incendio: IEEE 383 Reducida emisin de halgenos: UNE EN 50267-2-1; IEC 60754-1; Emisin ClH < 14%

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico. Flexibilidad: clase 5 segn UNE 21022. Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito; segn la norma UNE 21123-2.

AISLAMIENTO
Aislado con polietileno reticulado (XLPE), tipo DIX3 s/HD 603-1.

CUBIERTA
De PVC tipo DMV-18 s/HD 603-1 de color negro, con franja en color.

APLICACIONES
Para redes de distribucin, acometidas, instalaciones de alumbrado pblico e instalaciones industriales al aire o enterradas, en las que se requiere una mayor facilidad de manipulacin, manteniendo al mismo tiempo unas prestaciones elevadas frente a sobrecargas y cortocircuitos.

www.es.pirelli.com

35

baja tensin

cables para edificacin e industria

RETENAX FLEX
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV-K 0,6/1 kV

CABLES DISPONIBLES EN STOCK


SECCIONES DISPONIBLES EN STOCK
NE AZ-MA MA-AZ-AV AZ (neutro) NE-MA-GR (fases) NE-MA-GR-AV NE-MA-GR AZ-AV

1 x 2,5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300

2 x 1,5 2 x 2,5 2x4 2x6 2 x 10 2 x 16

3 G 1,5 3 G 2,5 3G4 3G6 3 G 10 3 G 16

3,5 x 10 3,5 x 16 3,5 x 25 3,5 x 35 3,5 x 50 3,5 x 70 3,5 x 95 3,5 x 120 3,5 x 150 3,5 x 240

4 G 1,5 4 G 2,5 4G4 4G6 4 G 10 4 G 16

5 G 1,5 5 G 2,5 5G4 5G6 5 G 10 5 G 16 5 G 25 5 G 35

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde

CARACTERSTICAS TCNICAS
CLCULO DE LA CADA DE TENSIN
Secin nominal mm2 Tres cables unipolares cos fi = 1 cos fi = 0,8 cos fi = 1 Un cable unipolar cos fi = 0,8

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

26.50 15.92 9.96 6.74 4,00 2.51 1.59 1.15 0.85 0.59 0.42 0.34 0.27 0.22 0.17 0.14 0.11

21.36 12.88 8.10 5.51 3.31 2.12 1.37 1.01 0.77 0.56 0.43 0.36 0.31 0.26 0.22 0.19 0.17

26.94 16.23 10.16 6.87 4.06 2.56 1.62 1.17 0.86 0.60 0.43 0.34 0.28 0.22 0.17 0.14 0.11

21.27 13.10 8.23 5.59 3.34 2.13 1.38 1.01 0.77 0.56 0.42 0.35 0.30 0.26 0.21 0.18 0.16

Para determinar la cada de tensin, en V, se multiplicar el coeficiente de la tabla por la corriente que recorre el cable, en A, y por la longitud de la lnea en Km. Los valores de la tabla se refieren a c.a. trifsica; para corriente monofsica pueden tomarse los mismos valores resultantes, multiplicados por 1,15.

www.es.pirelli.com

36

baja tensin

cables para edificacin e industria

RETENAX FLEX
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV-K 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica de 20 C del conductor Ohm/Km

1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 2 x 70 2 x 95 2 x 120 2 x 150 2 x 185 2 x 240 2 x 300 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2

5.7 6.2 6.6 7.2 8.3 9.4 11 12.5 14.2 15.8 17.9 19.6 21.7 23.9 26.9 29.5 9.5 10.4 11.3 12.4 14.6 16.9 20.4 23.4 26.8 29.9 34.1 37.7 41.8 46.4 52.3 57.6 9.9 10.9 11.9 13.1 15.5 18 21.4 24.9 28.6 32.1 36.4 40.3

42 54 70 91 135 191 280 389 537 726 958 1243 1537 1866 2465 3063 111 142 182 236 352 503 780 1060 1448 1926 2538 3260 4019 4921 6445 7972 127 166 220 289 441 639 946 1355 1869 2530 3322 4301

13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.0801 0.0641 13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.0801 0.0641 13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272 0.206 0.161

www.es.pirelli.com

37

baja tensin

cables para edificacin e industria

RETENAX FLEX
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV-K 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
DIMENSIONES (Continuacin)
Seccin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica de 20 C del conductor Ohm/Km

3 x 150 3 x 185 3 x 240 3 x 300 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 95/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 300/150 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 5 x 1.5 5 x 2.5 5x4 5x6 5 x 10 5 x 16

1.4 1.6 1.7 1.8 0.9/0.7 0.9/0.7 1.0/0.9 1.1/0.9 1.1/1.0 1.2/1.1 1.4/1.1 1.6/1.1 1.7/1.2 1.8/1.4 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 0.7 0.7 0.7 0.7 0.7 0.7

44.9 49.8 56.1 61.8 22.6 25.7 29.8 34 38.7 43.5 47.4 52.7 59.3 64.7 10.7 11.8 12.9 14.2 16.9 19.7 23.8 27.4 31.7 35.7 40.4 11.5 12.7 14 15.7 18.7 21.5

5332 6521 8576 10633 1091 1485 2078 2879 3809 5028 5980 7490 9705 12145 149 199 266 354 545 796 1233 1711 2386 3240 4261 177 237 320 436 675 976

0.129 0.106 0.0801 0.0641 0.780/1.21 0.554/1.21 0.386/0.780 0.272/0.554 0.206/0.386 0.161/0.272 0.129/0.272 0.106/0.206 0.0801/0.161 0.0641/0.129 13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272 0.206 13.3 7.98 4.95 3.3 1.91 1.21

Tambin disponible en rollos de color blanco 2 x 1,5, - 2 x 2,5 - 3 G 1,5 - 3 G 2,5 - 4 G 1,5 - 4 G 2,5 y rollos de color negro: 1 x 6 - 1 x 10,16 - 1 x 25 - 2 x 1,5 - 2 x 4 - 2 x 6 - 3 G ,5 - 3 G 2,5 - 3 G 4 - 3 G 6 - 3 G 10 - 4 G 1,5 - 4 G 2,5 - 4 G 4 - 4 G 6 - 5 G 1,5 - 5 G 2,5 - 5 G 4. FRANJAS DE COLORES IRISTECH DE LA CUBIERTA
Seccin

FRANJAS LONGITUDINALES
Color

1,5 2,5 4 6 10 16 25 35 > 35

Rojo Azul Marrn Gris Naranja Azul claro Amarillo Verde Amarillo claro

www.es.pirelli.com

38

baja tensin

cables para edificacin e industria

RETENAX FLAM
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV 0,6/1 kV

CARACTERSTICAS CABLE

Resistencia a los golpes

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

Resistencia a los agentes qumicos

Resistencia a las grasas y aceites

No propagacin de la llama

No propagacin del incendio

Norma constructiva: UNE 21123-2 Temperatura de servicio (instalacin fija): -25C, +90C Tensin nominal de servicio: 0,6/1 kV Ensayo de tensin en c.a. durante 5 minutos: 3.500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2 No propagacin del incendio: UNE EN 50266-2-4; IEC 60332-3; IEEE 383 Reducida emisin de halgenos: UNE EN 50267-2-1; IEC 60754-1; Emisin ClH < 14%

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico. Flexibilidad: clase 1 hasta 4 mm2, clase 2 desde 6 mm2; segn UNE 21022. Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito; segn la norma UNE 21123-2.

AISLAMIENTO
Aislado con polietileno reticulado (XLPE), tipo DIX3 s/HD 603-1

CUBIERTA
De PVC tipo DMV-18 s/HD 603-1 de color negro.

APLICACIONES
Para redes de distribucin, acometidas, instalaciones de alumbrado pblico e instalaciones industriales al aire o enterradas, en las que la flexibilidad no es una necesidad imperiosa y, por contra, s es importante que el cable presente unas prestaciones elevadas frente a sobrecargas y cortocircuitos.

www.es.pirelli.com

39

baja tensin

cables para edificacin e industria

RETENAX FLAM
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV 0,6/1 kV

CABLES DISPONIBLES EN STOCK


SECCIONES DISPONIBLES EN STOCK - Colores de los conductores y secciones mm2
NE AZ-MA NE-MA-GR AZ (neutro) NE-MA-GR (fases) AZ (neutro) NE-MA-GR (fases) NE-MA-GR-AZ-AV

1 x 1,5 1 x 2,5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 (*) MA-AZ-AV (**) NE-MA-GR-AV

2 x 1,5 2 x 2,5 2x6 2 x 10 2 x 16

3 x 1,5 3 G1,5(*) 3 x 2,5 3 G2,5(*)

3,5 x 10 3,5 x 16 3,5 x 25

4 x 1,5 4 x 2,5 4 G 2,5(**) 4x4 4x6 4 x 10 4 x 16

5 G 2,5

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde

CARACTERSTICAS TCNICAS
COEFICIENTE PARA EL CLCULO DE LA CADA DE TENSIN
Secin nominal mm2 Cu Tres cables unipolares cos = 1 Al Cu cos = 0,8 Al Cu cos = 1 Al Cu Un cable unipolar cos = 0,8 Al

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

26.5 15.92 9.96 6.74 4 2.51 1.59 1.15 0.85 0.59 0.42 0.34 0.27 0.22 0.17 0.14 0.11

4.15 2.62 1.89 1.39 0.97 0.7 0.55 0.45 0.36 0.27 0.22 0.17

21.36 12.88 8.1 5.51 3.31 2.12 1.37 1.01 0.77 0.56 0.43 0.36 0.31 0.26 0.22 0.19 0.17

3.42 2.19 1.6 1.21 0.86 0.65 0.53 0.45 0.37 0.3 0.26 0.22

26.94 16.23 10.16 6.87 4.06 2.56 1.62 1.17 0.86 0.6 0.43 0.34 0.28 0.22 0.17 0.14 0.11

4.24 2.66 1.93 1.42 0.98 0.71 0.56 0.46 0.37 0.28 0.22 0.18

21.27 13.1 8.23 5.59 3.34 2.13 1.38 1.01 0.77 0.56 0.42 0.35 0.3 0.26 0.21 0.18 0.16

3.48 2.21 1.62 1.22 0.87 0.65 0.53 0.44 0.37 0.3 0.25 0.21

Para determinar la cada de tensin, en V, se multiplicar el coeficiente de la tabla por la corriente que recorre el cable, en A, y por la longitud de la lnea en Km. Los valores de la tabla se refieren a c.a. trifsica; para corriente monofsica pueden tomarse los mismos valores resultantes, multiplicados por 1,15.

www.es.pirelli.com

40

baja tensin

cables para edificacin e industria

RETENAX FLAM
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
CARACTERSTICAS DIMENSIONALES DE LOS CABLES RETENAX FLAM N
Secin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Cu Al Dimetro exterior aproximado mm Cu Al Peso total aproximado Kg/Km Cu Al Resistencia hmica a 20 C del conductor Ohm/km Cu Al

1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 2 x 70 2 x 95 2 x 120 2 x 150 2 x 185 2 x 240 2 x 300 2 x 400

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.-

2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12.13.8 15.4 17.2 19.3 21.8 24.3 27.2 2.8 3.2 3.6 4.4 5.2 6.4 7.7 8.8 10.3 12.13.8 15.6 17.4 19.5 22.24.5 27.4

6.6 8.4 8.9 10.1 11.9 13.8 15.3 17.19.4 22.1 24.3 27.5 6.6 8.4 8.9 10.1 11.9 13.8 15.5 17.2 19.6 22.3 24.5 27.7

6.4 6.8 7.2 8.8.8 9.7 11.3 12.4 13.9 15.6 17.4 19.20.8 22.9 25.4 27.9 31.9.5 10.3 11.2 12.8 14.4 16.2 19.6 21.8 24.8 28.2 32.4 36.2 40.44.4 50.2 55.6 61.8

10.2 12.12.4 13.7 15.5 17.4 19.4 20.6 23.25.7 27.9 31.3 17.2 21.22.24.4 28.32.4 36.39.6 44.6 50.8 55.6 62.4

63 76 94 125 165 225 330 425 555 760 1020 1250 1550 1910 2420 3030 3810 145 180 225 300 410 560 850 1100 1460 1990 2700 3323 4149 5128 6578 8222 10293

140 195 220 265 350 445 530 630 785 980 1180 1480 415 610 700 865 1150 1550 1880 2275 2885 3722 4515 5650

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047

1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1 0.0778 1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1 0.0778

www.es.pirelli.com

41

baja tensin

cables para edificacin e industria

RETENAX FLAM
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
CARACTERSTICAS DIMENSIONALES DE LOS CABLES RETENAX FLAM N (Continuacin)
Secin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Cu Al Dimetro exterior aproximado mm Cu Al Peso total aproximado Kg/Km Cu Al Resistencia hmica a 20 C del conductor Ohm/km Cu Al

3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 3 x 400 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1

2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12.13.8 15.4 17.2 19.3 21.8 24.3 27.2 2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12.13.8

6.6 8.4 8.9 10.1 11.9 13.8 15.3 17.19.4 22.1 24.3 27.5 6.6 8.4 8.9 10.1 11.9 13.8

9.9 10.8 11.8 13.5 15.2 17.1 20.8 23.2 26.4 30.5 34.5 38.2 42.5 47.6 53.4 59.2 65.8 10.6 11.6 12.7 14.6 16.6 18.7 22.8 25.4 29.3 33.8 38.3

18.2 22.3 23.4 26.30.2 34.5 38.42.47.8 54.59.2 66.5 20.1 24.5 25.7 28.8 33.5 38.3

165 205 265 360 495 695 1070 1390 1860 2580 3490 4300 5400 6740 8590 10770 13520 185 240 315 430 605 855 1330 1740 2370 3310 4480

675 780 975 1330 1760 2140 2610 3370 4280 5210 6250 550 790 925 1200 1640 2170

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193

1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1 0.0778 1.91 1.2 0.868 0.641 0.443 0.32

www.es.pirelli.com

42

baja tensin

cables para edificacin e industria

RETENAX FLAM
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RV 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
CARACTERSTICAS DIMENSIONALES DE LOS CABLES RETENAX FLAM N
Seccin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20C del conductor Ohm/Km

Conductor de cobre
3 x 10/6 3 x 16/10 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 95/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 300/150 3 x 400/185 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 95/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 300/150 3 x 400/185 0.7/0.7 0.7/0.7 0.9/0.7 0.9/0.7 1/0.9 1.1/0.9 1.1/1 1.2/1.1 1.4/1.1 1.6/1 1.7/1 1.8/1.4 2/1.6 0.9/0.7 0.9/0.7 1/0.9 1.1/0.9 1.1/1 1.2/1.1 1.4/1.1 1.6/1.1 1.7/1.2 1.8/1.4 2/1.6 5.2/4.4 6.1/5.2 7.7/6.1 8.8/6.1 10.3/7.7 12/8.8 13.8/10.3 15.4/12 17.2/12 19.3/13.8 21.8/15.4 24.3/17.2 27.4/19.5 8.6/6.6 9.1/6.6 10.1/8.4 11.9/8.9 13.8/10.1 15.3/11.9 17/11.9 19.4/13.8 22.1/15.3 24.3/17 27.5/19.4 16.1 18.2 21.9 24 27.6 31.8 36.4 40.5 44.1 49.8 55.7 61.8 69.6 23.9 24.9 27.6 31.7 36.3 40.2 43.7 50.56.3 61.7 69.8 572 811 1230 1550 2110 2920 3970 4990 6040 7660 9720 12200 15385 779 884 1110 1470 1940 2410 2830 3700 4680 5700 7250 1.83/3.08 1.15/1.83 0.727/1.15 0.525/1.15 0.387/0.727 0.268/0.525 0.193/0.387 0.153/0.268 0.124/0.268 0.0991/0.193 0.0754/0.153 0.0601/0.124 0.0470/0.0991 1.2/1.91 0.868/1.91 0.641/1.20 0.443/0.868 0.320/0.641 0.253/0.443 0.206/0.443 0.164/0.320 0.125/0.253 0.1/0.206 0.0778/0.164

Conductor de aluminio

www.es.pirelli.com

43

www.es.pirelli.com

44

baja tensin

cables para edificacin e industria

AFUMEX 750 V QUICK SYSTEM


Tensin nominal:

500 V 750 V

Norma bsica:

UNE 211002

Designacin genrica:

ES05Z1-K ES07Z1-K

CARACTERSTICAS CABLE

Cable flexible

Libre de halgenos

Reducida emisin de gases txicos

Baja emisin de humos opacos

Nula emisin de gases corrosivos

No propagacin de la llama

No propagacin del incendio

Resistencia a la absorcin del agua

Resistencia al fro

Norma constructiva: UNE 211002 Temperatura de servicio (instalacin fija): - 40 + 70C Tensin nominal de servicio: 500V hasta 1 mm2 y 750V desde 1,5 mm2 Ensayo de tensin en c.a. durante 5 minutos: 2000 V en los cables ESO5Z1-K y 2500 V en los ESO7Z1-K Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2 No propagacin del incendio: UNE EN 50266-2-4 ; UNE 20427 ; IEC 60332-3 ; IEEE 383 ; NFC 32070-C1 Libre de halgenos: UNE EN 50267-2-1 ; IEC 60754-1 ; BS 6425-1 Reducida emisin de gases txicos: NES 713 ; NFC 20454 ; It ) 1,5 Baja emisin de humos opacos: UNE EN 50268 ; IEC 61034 - 1,2 Nula emisin de gases corrosivos: UNE EN 50267-2-3 ; IEC 60754-2 ; NFC 20453 ; BS 6425-2 ; pH * 4,3 ; C ) 10 + S/mm.

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 5; segn UNE 21022. Temperatura mxima en el conductor: 70C en servicio continuo, 160C en cortocircuito.

AISLAMIENTO
Aislamiento termoplstico AFUMEX tipo TIZ1 en los colores: negro, azul, marrn, gris, amarillo/verde y rojo.

APLICACIONES
Cable especialmente adecuado para instalaciones en locales de pblica concurrencia: (salas de espectculos, centros comerciales, escuelas, hospitales, edificios de oficinas, pabellones deportivos, etc.), centros informticos, aeropuertos, naves industriales, parkings, tneles ferroviarios y de carreteras, ferrocarriles y metropolitanos, locales de difcil ventilacin y/o evacuacin, etc., y en general en toda instalacin donde el riesgo de incendio no sea despreciable como por ejemplo: instalaciones en montaje superficial, canalizaciones verticales en edificios o sobre bandejas, etc. Tambin deben de emplearse en los proyectos de ecobioconstruccin.

www.es.pirelli.com

45

baja tensin

cables para edificacin e industria

AFUMEX 750V QUICK SYSTEM


Tensin nominal:

500 V 750 V

Norma bsica:

UNE 211002

Designacin genrica:

ES05Z1-K ES07Z1-K

CABLES DISPONIBLES EN STOCK


TABLA DE COLORES SEGN SECCIN
Seccin Colores cable Colores caja

1x1 1 x 1,5 1 x 2,5 1x4 1x6 1 x 10 1 x 16 1 x 25

NE-AZ-GR-AV-MA-RO NE-AZ-GR-AV-MA-RO NE-AZ-GR-AV-MA NE-AZ-GR-AV-MA NE-AZ-GR-AV-MA NE-AZ-GR-AV-MA NE-AZ-GR-AV-MA NE-AZ-GR-AV-MA

Verde Rojo Azul Marrn Gris Naranja Azul claro Marrn

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Secin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Cu Dimetro exterior aproximado mm Cu Peso total aproximado Kg/Km Cu Resistencia hmica a 20 C del conductor Ohm/km Cu

1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2

2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12 13.8 15.4 17.2 19.3 21.8 24.3 27.2

6.4 6.8 7.2 8 8.8 9.7 11.3 12.4 13.9 15.6 17.4 19 20.8 22.9 25.4 27.9 31

63 76 94 125 165 225 330 425 555 760 1020 1250 1550 1910 2420 3030 3810

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047

www.es.pirelli.com

46

baja tensin

cables para edificacin e industria

AFUMEX 1000V
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

RZ1-K 0,6/1 kV

CARACTERSTICAS CABLE

Cable flexible

Libre de halgenos

Reducida emisin de gases txicos

Baja emisin Nula emisin de humos opacos de gases corrosivos

No propagacin de la llama

No propagacin del incendio

Resistencia a Resistencia a los la absorcin del agua rayos ultravioletas

Resistencia al fro

Norma constructiva: UNE 21123-4 Temperatura de servicio (instalacin fija): -40C, +90C Tensin nominal de servicio: 0,6/1 kV Ensayo de tensin en c.a. durante 5 minutos: 3.500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2 No propagacin del incendio: UNE EN 50266-2-4 ; UNE 20427 ; IEC 60332-3 ; IEEE 383 ; NFC 32070-C1 Libre de halgenos: UNE EN 50267-2-1 ; IEC 60754-1 ; BS 6425-1 Reducida emisin de gases txicos: NES 713 ; NFC 20454 ; It ) 1,5 Baja emisin de humos opacos: UNE EN 50268 ; IEC 61034 - 1,2 Nula emisin de gases corrosivos: UNE EN 50267-2-3 ; IEC 60754-2 ; NFC 20453 ; BS 6425-2 ; pH * 4,3 ; C ) 10 + S/mm

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico. Flexibilidad: clase 5, segn UNE 21022. Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito, segn norma UNE 21123.

AISLAMIENTO
Aislados con mezcla especial a base de poliolefinas, tipo DIX3.

CUBIERTA
De mezcla especial termoplstica, cero halgenos, tipo Z1, color negro.

APLICACIONES
Cable especialmente adecuado para instalaciones en locales de pblica concurrencia: ( salas de espectculos, centros comerciales, escuelas, hospitales, edificios de oficinas, pabellones deportivos, etc.), centros informticos, aeropuertos, naves industriales, parkings, tneles ferroviarios y de carreteras,ferrocarriles y metropolitanos, locales de difcil ventilacin y/o evacuacin, etc., y en general en toda instalacin donde el riesgo de incendio no sea despreciable como por ejemplo: instalaciones en montaje superficial, canalizaciones verticales en edificios o sobre bandejas, etc. Tambin deben de emplearse en los proyectos de ecobioconstruccin.

www.es.pirelli.com

47

baja tensin

cables para edificacin e industria

AFUMEX 1000V
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

RZ1-K 0,6/1 kV

CABLES DISPONIBLES EN STOCK


SECCIONES DISPONIBLES EN STOCK
NE AZ-MA MA-AZ-AV AZ (neutro) - NE-MA-GR (fases) NE-MA-GR-AV

1 x 2.5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240

2 x 1.5 2 x 2.5 2x6

3 G 1.5 3 G 2.5 3G4 3G6 3 G 10 3 G 16

3.5 x 25 3.5 x 35 3.5 x 50

4 G 1.5 4 G 2.5 4G4 4G6 4 G 10 4 G 16 NE-MA-GR-AZ-AV 5 G 1.5 5 G 2.5 5G4 5G6 5 G 10 5 G 16 5 G 25

CARACTERSTICAS TCNICAS
CLCULO DE LA CADA DE TENSIN
Secin nominal mm2 Tres cables unipolares cos fi = 1 cos fi = 0,8 cos fi = 1 Un cable unipolar cos fi = 0,8

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

26.5 15.92 9.96 6.74 4 2.51 1.59 1.15 0.85 0.59 0.42 0.34 0.27 0.22 0.17 0.14

21.36 12.88 8.1 5.51 3.31 2.12 1.37 1.01 0.77 0.56 0.43 0.36 0.31 0.26 0.22 0.19

26.94 16.23 10.16 6.87 4.06 2.56 1.62 1.17 0.86 0.6 0.43 0.34 0.28 0.22 0.17 0.14

21.27 13.1 8.23 5.59 3.34 2.13 1.38 1.01 0.77 0.56 0.42 0.35 0.3 0.26 0.21 0.18

Para determinar la cada de tensin, en V, se multiplicar el coeficiente de la tabla por la corriente que recorre el cable, en A, y por la longitud de la lnea en Km. Los valores de la tabla se refieren a c.a. trifsica; para corriente monofsica pueden tomarse los mismos valores resultantes, multiplicados por 1,15.

www.es.pirelli.com

48

baja tensin

cables para edificacin e industria

AFUMEX 1000V
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

RZ1-K 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica de 20 C del conductor Ohm/Km

1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 2 x 70 2 x 95 2 x 120 2 x 150 2 x 185 2 x 240 2 x 300 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1

5.7 6.2 6.6 7.2 8.3 9.4 11 12.5 14.2 15.8 17.9 19.6 21.7 23.9 26.9 29.5 9.5 10.4 11.3 12.4 14.6 16.9 20.4 23.4 26.8 29.9 34.1 37.7 41.8 46.4 52.3 57.6 9.9 10.9 11.9 13.1 15.5 18 21.4 24.9 28.6 32.1

42 54 70 91 135 191 280 389 537 726 958 1243 1537 1866 2465 3063 111 142 182 236 352 503 780 1060 1448 1926 2538 3260 4019 4921 6445 7972 127 166 220 289 441 639 946 1355 1869 2530

13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.0801 0.0641 13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.0801 0.0641 13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272

www.es.pirelli.com

49

baja tensin

cables para edificacin e industria

AFUMEX 1000V
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

RZ1-K 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
DIMENSIONES (Continuacin)
Seccin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica de 20 C del conductor Ohm/Km

3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 95/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 300/150 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 5 x 1.5 5 x 2.5 5x4 5x6 5 x 10 5 x 16

1.1 1.2 1.4 1.6 1.7 1.8 0.9/0.7 0.9/0.7 1.0/0.9 1.1/0.9 1.1/1.0 1.2/1.1 1.4/1.1 1.6/1.1 1.7/1.2 1.8/1.4 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 0.7 0.7 0.7 0.7 0.7 0.7

36.4 40.3 44.9 49.8 56.1 61.8 22.6 25.7 29.8 34 38.7 43.5 47.4 52.7 59.3 64.7 10.7 11.8 12.9 14.2 16.9 19.7 23.8 27.4 31.7 35.7 40.4 11.5 12.7 14 15.7 18.7 21.5

3322 4301 5332 6521 8576 10633 1091 1485 2078 2879 3809 5028 5980 7490 9705 12145 149 199 266 354 545 796 1233 1711 2386 3240 4261 177 237 320 436 675 976

0.206 0.161 0.129 0.106 0.0801 0.0641 0.780/1.21 0.554/1.21 0.386/0.780 0.272/0.554 0.206/0.386 0.161/0.272 0.129/0.272 0.106/0.206 0.0801/0.161 0.0641/0.129 13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272 0.206 13.3 7.98 4.95 3.3 1.91 1.21

www.es.pirelli.com

50

baja tensin

cables para edificacin e industria

AFUMEX FIRS 1000V


Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

SZ1/RZ1

CARACTERSTICAS CABLE

Resistencia al fuego

Libre de halgenos

Reducida emisin de gases txicos

Baja emisin Nula emisin de humos opacos de gases corrosivos

No propagacin de la llama

No propagacin del incendio

Resistencia a Resistencia a los la absorcin del agua rayos ultravioletas

Resistencia al fro

Norma constructiva: UNE 21123-4 Temperatura de servicio (instalacin fija): -40C, +90C Tensin nominal de servicio: 0,6/1 kV Ensayo de tensin en c.a. durante 5 minutos: 3500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1; IEC 60332-1; NFC 32070-C2 No propagacin del incendio: UNE EN50266-2-4; UNE 20427; IEC 60332-3; IEEE 383; NFC 32070-C1 Resistencia al fuego: UNE 20431; IEC 60331 Libre de halgenos: UNE EN 50267-2-1; IEC 60754-1; BS 6425-1 Reducida emisin de gases txicos: NES 713; NFC 20454; It ) 1,5 Baja emisin de humos opacos: UNE EN 50268; IEC 61034-1,2 Nula emisin de gases corrosivos: UNE EN 50267-2-3; IEC 60754-2; NFC 20453; BS 6425-2; pH * 4,3; C ) 10+ S/mm

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico. Flexibilidad: clase 2 o clase 5; segn UNE 21022. Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito; segn norma UNE 21123.

AISLAMIENTO
Compuesto especial reticulado cero halgenos.

CUBIERTA
De mezcla especial termoplstica cero halgenos, tipo Z1. Color azul oscuro.

APLICACIONES
Cable especialmente diseado para poder seguir prestando servicio en condiciones extremas durante un incendio; as, es el cable adecuado para circuitos de alarma, alumbrado de emergencia, alumbrado de sealizacin, bombas de extincin, etc. as como para la alimentacin de extractores de humos en los garages, aparcamientos y cocinas industriales segn la Norma Bsica de Edificacin "NBE-CPI96 Condiciones de proteccin contra incendios en edificios".

www.es.pirelli.com

51

baja tensin

cables para edificacin e industria

AFUMEX FIRS 1000V


Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

SZ1/RZ1

CABLES DISPONIBLES EN STOCK


SECCIONES DISPONIBLES EN STOCK
Secciones

1 x 1.5

1 x 2.5

1x4

1x6

1 x 10

1 x 16

3 G 1,5

3 G 2,5

5 G 2,5

CARACTERSTICAS TCNICAS
CLCULO DE LA CADA DE TENSIN
Secin nominal mm2 Tres cables unipolares cos fi = 1 cos fi = 0,8 cos fi = 1 Un cable unipolar cos fi = 0,8

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

26.5 15.92 9.96 6.74 4 2.51 1.59 1.15 0.85 0.59 0.42 0.34 0.27 0.22 0.17 0.14 0.11

21.36 12.88 8.1 5.51 3.31 2.12 1.37 1.01 0.77 0.56 0.43 0.36 0.31 0.26 0.22 0.19 0.17

26.94 16.23 10.16 6.87 4.06 2.56 1.62 1.17 0.86 0.6 0.43 0.34 0.28 0.22 0.17 0.14 0.11

21.27 13.1 8.23 5.59 3.34 2.13 1.38 1.01 0.77 0.56 0.42 0.35 0.3 0.26 0.21 0.18 0.16

Para determinar la caida de tensin en V, se multiplicar el coeficiente de la tabla por la longitud de la lnea en Km y por la intensidad en A.

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20C del conductor Ohm/Km

1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1

2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12.-

6.4 6.8 7.2 8.8.8 9.7 11.3 12.4 13.9 15.6

63 76 94 125 165 225 330 425 555 760

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268

www.es.pirelli.com

52

baja tensin

cables para edificacin e industria

AFUMEX FIRS 1000V


Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

SZ1/RZ1

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20C del conductor Ohm/Km

1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 2 x 70 2 x 95 2 x 120 2 x 150 2 x 185 2 x 240 2 x 300 2 x 400 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185

1.1 1.2 1.4 1.6 1.7 1.8 2.0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1 1.2 1.4 1.6

13.8 15.4 17.2 19.3 21.8 24.3 27.2 2.8 3.2 3.6 4.4 5.2 6.4 7.7 8.8 10.3 12.13.8 15.6 17.4 19.5 22.24.5 27.4 2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12.13.8 15.4 17.2 19.3

17.4 19.20.8a 22.9 25.4 27.9 31.9.5 10.3 11.2 12.8 14.4 16.2 19.6 21.8 24.8 28.2 32.4 36.2 40.44.4 50.2 55.6 61.8 9.9 10.8 11.8 13.5 15.2 17.1 20.8 23.2 26.4 30.5 34.5 38.2 42.5 47.6

1020 1250 1550 1910 2420 3030 3810 145 180 225 300 410 560 850 1100 1460 1990 2700 3323 4149 5128 6578 8222 10293 165 205 265 360 495 695 1070 1390 1860 2580 3490 4300 5400 6740

0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991

www.es.pirelli.com

53

baja tensin

cables para edificacin e industria

AFUMEX FIRS 1000V


Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

SZ1/RZ1

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20C del conductor Ohm/Km

3 x 240 3 x 300 3 x 400 3 x 10/6 3 x 16/10 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 90/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 300/150 3 x 400/185 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 5 x 1.5 5 x 2.5 5x4 5x6

1.7 1.8 2.0.7/0.7 0.7/0.7 0.9/0.7 0.9/0.7 1/0.9 1.1/0.9 1.1/1 1.2/1.1 1.4/1.1 1.6/1 1.7/1 1.8/1.4 2/1.6 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1 0.7 0.7 0.7 0.7

21.8 24.3 27.2 5.2/4.4 6.1/5.2 7.7/6.1 8.8/6.1 10.3/7.7 12/8.8 13.8/10.3 15.4/12 17.2/12 19.3/13.8 21.8/15.4 24.3/17.2 27.4/19.5 2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12.13.8 2.8 3.2 3.6 4.4

53.4 59.2 65.8 16.1 18.2 21.9 24.27.6 31.8 36.4 40.5 44.1 49.8 55.7 61.8 69.6 10.6 11.6 12.7 14.6 16.6 18.7 22.8 25.4 29.3 33.8 38.3 11.1 12.2 13.3 15.5

8590 10770 13520 572 811 1230 1550 2110 2920 3970 4990 6040 7660 9720 12200 15385 185 240 315 430 605 855 1330 1740 2370 3310 4480 178 240 324 441

0.0754 0.0601 0.047 1.83/3.08 1.15/1.83 0.727/1.15 0.525/1.15 0.387/0.727 0.268/0.525 0.193/0.387 0.153/0.268 0.124/0.268 0.0991/0.193 0.0754/0.153 0.0601/0.124 0.0470/0.0991 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 12.1 7.41 4.61 3.08

www.es.pirelli.com

54

baja tensin

cables especiales para la industria

SOLDA
Tensin nominal:

100/100 V

Norma bsica:

UNE 21027/6

Designacin genrica:

H01N2-D

CARACTERSTICAS CABLE

Resistencia a las grasas y aceites

Resistencia a la abrasin

No propagacin de la llama

Cable flexible

Resistencia al fuego

Normas de diseo: UNE 21027-6, HD 22.6 S2 Tensin nominal: 100/100 V Temperatura de Servicio: -20 C + 90 C Ensayos de fuego: No propagacin de la Llama: UNE EN 50265-2-1, IEC 60332-1

DESCRIPCIN
Conductor cobre desnudo segn tabla 1 UNE 21027-6 Separador de poliester (facultativo). Cubierta termoestable tipo EM5, color negro.

APLICACIONES
Cables de mquina de soldar, con flexibilidad normal, para conexin entre el generador de la mquina industrial de soldar, y el soporte del electrodo y las piezas de soldar.

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin mm2 Espesor alsiamiento mm Dimetro exterior nominal mm Peso aproximado Kg/Km Resistencia conductor Ohm/Km

1x 10 1x 16 1x 25 1x 35 1x 50 1x 70 1x 95 1x 120

2.0 2.0 2.0 2.0 2.2 2.4 2.6 2.8

8.7 9.6 11.1 12.1 14.0 16.4 18.8 20.5

160 225 315 415 575 805 1060 1325

1.910 1.210 0.780 0.554 0.386 0.272 0.206 0.161

www.es.pirelli.com

55

www.es.pirelli.com

56

baja tensin

cables especiales para la industria

EUROFLAM N
Tensin nominal:

500 V

Norma bsica:

UNE 21031/5

Designacin genrica:

H05VV-F ES05VV-F

CARACTERSTICAS CABLE

Cable flexible

Resistencia a la absorcin del agua

No propagacin de la llama

Resistencia a las grasas y aceites

Resistencia a los agentes qumicos

No propagacin del incendio

Reducida emsin de halgenos

Norma constructiva: UNE 21031-5 Temperatura de servicio (instalacin fija): -25C, +70C Tensin nominal de servicio: 500 V Ensayo de tensin en c.a. durante 5 minutos: 2.000 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 No propagacin del incendio: IEEE 383 Reducida emisin de halgenos: UNE EN 50267-2-1; Emisin ClH < 20%

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 5; segn UNE 21022. Temperatura mxima en el conductor: 70C en servicio continuo, 160C en cortocircuito.

AISLAMIENTO
Aislado con PVC, tipo TI2 con los colores: 2 cond.: marrn y azul. 3 cond.: marron, azul y amarillo-verde. 4 cond.: negro, marrn, azul y amarillo-verde. 5 cond.: negro, negro, marrn, azul y amarillo-verde. =>6 cond.: 1 cond. amarillo-verde, el resto negros con numeracin.

CUBIERTA
De PVC de color negro, tipo TM3.

INSCRIPCIN
PIRELLI EUROFLAM N 300/500 V (seccin) (ao fabricacin).

APLICACIONES
En aquellas instalaciones que, aunque sean fija, por su dificultad de recorrido se impone el uso de cables de tipo flexible.

www.es.pirelli.com

57

baja tensin

cables especiales para la industria

EUROFLAM N
Tensin nominal:

500 V

Norma bsica:

UNE 21031/5

Designacin genrica:

H05VV-F ES05VV-F

CABLES DISPONIBLES EN STOCK


SECCIONES DISPONIBLES EN STOCK
Secciones

2x1 3G1

4G1 5G1

6G1 8G1

12 G 1 16 G 1

19 G 1 24 G 1

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Dimetro exterior aproximado mm Peso total aproximado Kg/Km

2x1 3G1 4G1 5G1 6G1 8G1 12 G 1 16 G 1 19 G 1 24 G 1

6.6 7.0 7.8 8.5 9.5 10.6 12.8 14.6 15.3 18.2

68 80 97 127 139 182 252 335 383 490

www.es.pirelli.com

58

baja tensin

cables especiales para la industria

EUROFLAM O YCY
Tensin nominal:

500 V

Norma bsica:

VDE 0250 TEIL 405/10.81

Designacin genrica:

VC4V-K

CARACTERSTICAS CABLE

Cable flexible

Resistencia a la absorcin del agua

No propagacin de la llama

No propagacin del incendio

Reducida emsin de halgenos

Norma constructiva: VDE 0250 teil 405/10.81 (sin cubierta interna) Temperatura de servicio (instalacin fija): -25C, +70C Tensin nominal de servicio: 500 V Ensayo de tensin en c.a. durante 5 minutos: 2.000 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 No propagacin del incendio: IEEE 383 Reducida emisin de halgenos: UNE EN 50267-2-1; Emisin ClH < 20% Radio mnimo de curvatura: 8 D, D = exterior del cable

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 5; segn UNE 21022. Temperatura mxima en el conductor: 70C en servicio continuo, 160C en cortocircuito.

AISLAMIENTO
Aislado con PVC, tipo TI2 con los colores: 2 cond.: marrn y azul. 3 cond.: marron, azul y amarillo-verde. 4 cond.: negro, marrn, azul y amarillo-verde. 5 cond.: negro, negro, marrn, azul y amarillo-verde. =>6 cond.: 1 cond. amarillo-verde, el resto negros con numeracin.

PANTALLA METLICA
Trenza de hilos de cobre desnudo con recubrimiento aproximado 70%.

CUBIERTA
De PVC de color negro, tipo TM2.

INSCRIPCIN
PIRELLI EUROFLAM O YCY 300/500 V (seccin) (ao fabricacin).

APLICACIONES
Cable de gran flexibilidad con buena resistencia a los aceites, grasas e hidrocarburos y agentes qumicos; apantallados con trenza de hilos de cobre para la transmisin de seales de control, instrumentacin y telemando de instalaciones fijas, alarmas, seguridad, robtica, servomecanismos, automatismos, etc.

www.es.pirelli.com

59

baja tensin

cables especiales para la industria

EUROFLAM O YCY
Tensin nominal:

500 V

Norma bsica:

VDE 0250 TEIL 405/10.81

Designacin genrica:

VC4V-K

CABLES DISPONIBLES EN STOCK


Secciones disponibles en stock

2 x 1,5

3 G 1,5

4 G 1,5

6 G 1,5

12 G 1,5

CARACTERSTICAS TCNICAS
Otras caractersticas

Resistencia de aislamiento a 20C (Ki) Capacidad mutua aproximada Inductancia mutua aproximada Resistencia a los aceites

> 20 ( Mohmios x Km ) =< 0,16 ( pF / m ) =< 0,9 ( mH / Km ) ensayo MIL-C-975 E 18 horas a 121C

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica de 20 C del conductor Ohm/Km

2 x 1,5 3 G 1,5 4 G 1,5 6 G 1,5 12 G 1,5

0.6 0.6 0.6 0.6 0.6

8.2 8.6 9.3 11.3 14.7

100 123 148 217 387

13.3 13.3 13.3 13.3 13.3

www.es.pirelli.com

60

baja tensin

cables especiales para la industria

EUROFLAM MLTIPLE
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/1

Designacin genrica:

VV-K 0,6/1 kV

CARACTERSTICAS CABLE

Cable flexible

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia a los agentes qumicos

Resistencia a las grasas y aceites

No propagacin de la llama

No propagacin del incendio

RESISTENCIA A LOS ACEITES, CIDOS Y ALCALIS Norma constructiva: UNE 21123-1 Temperatura de servicio (instalacin fija): -25C, +70C Tensin nominal de servicio: 0,6/1 kV Ensayo de tensin en c.a. durante 5 minutos: 3.500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2 No propagacin del incendio: IEEE 383 Reducida emisin de halgenos: UNE EN 50267-2-1; IEC 60754-1; Emisin ClH < 20%

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico. Flexibilidad: clase 5 segn UNE 21022. Temperatura mxima en el conductor: 70C en servicio continuo, 160C en cortocircuito.

AISLAMIENTO
Aislados con PVC, tipo PVC/A. Colores: un conductor amarillo/verde, el resto negros numerados.

CUBIERTA
PVC de color negro, tipo ST1.

APLICACIONES
Cable adecuado para instalaciones que, an siendo fijas, por su dificultad de recorrido se impone la utilizacin de un cable del tipo flexible. Apto para control y mando, con buenas caractersticas de resistencia a la grasa y aceites.

www.es.pirelli.com

61

baja tensin

cables especiales para la industria

EUROFLAM MLTIPLE
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/1

Designacin genrica:

VV-K 0,6/1 kV

CABLES DISPONIBLES EN STOCK


Secciones disponibles en stock

6 G 1.5 6 G 2.5 7 G 1.5 8 G 1.5 8 G 2.5

10 G 1.5 10 G 2.5 12 G 1.5 14 G 1.5 14 G 2.5

16 G 1.5 19 G 1.5 24 G 1.5 24 G 2.5 30 G 1.5

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica de 20 C del conductor Ohm/Km

6 x 1.5 6 x 2.5 6x4 7 x 1.5 7 x 2.5 7x4 8 x 1.5 8 x 2.5 8x4 10 x 1.5 10 x 2.5 10 x 4 12 x 1.5 12 x 2.5 12 x 4 14 x 1.5 14 x 2.5 14 x 4 16 x 1.5 16 x 2.5 16 x 4 19 x 1.5 19 x 2.5 19 x 4 24 x 1.5 24 x 2.5 24 x 4 27 x 1.5 27 x 2.5 27 x 4 30 x 1.5 30 x 2.5 30 x 4

0.8 0.8 1 0.8 0.8 1 0.8 0.8 1 0.8 0.8 1 0.8 0.8 1 0.8 0.8 1 0.8 0.8 1 0.8 0.8 1 0.8 0.8 1 0.8 0.8 1 0.8 0.8 1

13 14.3 16.9 13 14.3 16.9 14.1 15.7 18.6 16.1 17.9 21.4 16.6 18.5 22 17.4 19.4 23.2 18.3 20.4 24.5 19.3 21.5 25.8 22.4 25.1 30.4 22.9 25.6 31.3 23.7 26.6 32.5

241 319 501 256 341 538 297 400 632 373 498 752 409 538 853 460 624 971 515 734 1097 589 840 1261 728 1001 1586 784 1109 1707 842 1216 1875

13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95 13.3 7.98 4.95

www.es.pirelli.com

62

baja tensin

cables especiales para la industria

BUPRENO H07RN-F / PIREFLEX


Tensin nominal:

750 V

Norma bsica:

UNE 21027/4

Designacin genrica:

H07RN-F A07RN-F

CARACTERSTICAS CABLE

Cable flexible

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

Resistencia a los agentes qumicos

Resistencia a las grasas y aceites

Resistencia a la abrasin

No propagacin de la llama

Norma constructiva: HD 22.4 , IEC 60245, UNE 21027-4 Temperatura de servicio (instalacin fija): - 30 + 85C Tensin nominal de servicio: 450/750 V Ensayo de tensin en c.a. durante 5 minutos: 2.500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1; IEC 60332-1; NFC 32070-C2

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico desnudo. Flexibilidad: clase 5; segn UNE 21022 (IEC 60228). Temperatura mxima en el conductor: 85C en servicio continuo, 250C en cortocircuito.

AISLAMIENTO
Aislamiento de goma EPR (etileno-propileno) colores

RELLENO (si es necesario)


Relleno y capa termoestable tipo EM3 segn HD 22.4 de color negro.

CUBIERTA
Cubierta termoestable tipo EM2 segn HD 22.4 de color negro.

APLICACIONES
Para aquellas instalaciones donde se impone el uso de cables de 750 V de tensin nominal, siendo apto para instalaciones fijas y servicio mvil (mquinas y equipos mviles. Robots, gras, etc.) El cable Bupreno H07RN-F es adecuado para aquellas instalaciones donde se requiera una gran flexibilidad del cable, siendo especialmente indicados en aplicaciones industriales debido a sus caractersticas de: resistencia al calor y al fro, resistencia a los aceites, grasas e hidrocarburos, resistencia a la intemperie y su muy buen comportamiento frente a la humedad y al agua.

www.es.pirelli.com

63

baja tensin

cables especiales para la industria

BUPRENO H07RN-F / PIREFLEX


Tensin nominal:

750 V

Norma bsica:

UNE 21027/4

Designacin genrica:

H07RN-F A07RN-F

CABLES DISPONIBLES EN STOCK


SECCIONES DISPONIBLES EN STOCK
Secciones

2 x 1,5

2 x 2,5

3 G 1,5

3 G 2,5

4 G 1,5

4 G 2,5

5 G 1,5

5 G 2,5

TABLA DE COLORES SEGN SECCIN


A07RN-F H07RN-F

1 cond. Negro 2 conds. Azul, Marrn 3 conds. Negro, Marrn, Azul 4 conds. 2 Negros, Marrn, Azul 5 conds. 3 Negros, Marrn, Azul

1 cond. Negro 2 conds. Azul, Marrn 3 conds. Marrn, Azul, Amarillo/Verde 4 conds. Negro, Marrn, Azul, Amarillo/Verde 5 conds. 2 Negros, Marrn, Azul, Amar./Verde

www.es.pirelli.com

64

baja tensin

cables especiales para la industria

BUPRENO
Tensin nominal:

1000 V

Norma bsica:

IEC 60502/1

Designacin genrica:

DN-K 0,6/1 kV

CARACTERSTICAS CABLE

Cable flexible

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

Resistencia a los agentes qumicos

Resistencia a las grasas y aceites

Resistente a la abrasin

No propagacin de la llama

ALTA RESISTENCIA Norma constructiva: IEC 60502-1 Temperatura de servicio (instalacin fija): -40C, +90C Tensin nominal de servicio: 0,6/1 kV Ensayo de tensin en c.a. durante 5 minutos: 3.500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico. Flexibilidad: clase 5 segn UNE 21022. Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito.

AISLAMIENTO
Aislamiento de goma HEPR (etileno-propileno de alto mdulo) o EPR.

CUBIERTA
Cubierta termoestable tipo SE1 segn IEC 60502-1 de color negro.

APLICACIONES
Al repasar el Reglamento de B.T. se presentan casos que por las caractersticas de la instalacin se impone el uso de cables de 1000V de tensin nominal y en las que debido a lo dificultoso del recorrido, se impone el uso de cable flexible con resistencia a la abrasin, resistencia al calor y al fro, resistencia a los aceites, grasas e hidrocarburos, resistencia a la intemperie y muy buen comportamiento a la humedad y el agua, aun cuando se trate de una instalacin fija.

www.es.pirelli.com

65

baja tensin

cables especiales para la industria

BUPRENO
Tensin nominal:

1000 V

Norma bsica:

IEC 60502/1

Designacin genrica:

DN-K 0,6/1 kV

CABLES DISPONIBLES EN STOCK


SECCIONES DISPONIBLES EN STOCK
Secciones

1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240

2 x 1.5 2 x 2.5 2x4 2x6 2 x 10

3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95

3.5 x 25 3.5 x 35 3.5 x 50 3.5 x 70

4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16

CARACTERSTICAS TCNICAS
CLCULO DE LA CADA DE TENSIN
Secin nominal mm2 Tres cables unipolares cos fi = 1 cos fi = 0,8 cos fi = 1 Un cable unipolar cos fi = 0,8

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

26.50 15.92 9.96 6.74 4.00 2.51 1.59 1.15 0.85 0.59 0.42 0.34 0.27 0.22 0.17 0.14 0.11

21.36 12.88 8.10 5.51 3.31 2.12 1.37 1.01 0.77 0.56 0.43 0.36 0.31 0.26 0.22 0.19 0.17

26.94 16.23 10.16 6.87 4.06 2.56 1.62 1.17 0.86 0.60 0.43 0.34 0.28 0.22 0.17 0.14 0.11

21.27 13.10 8.23 5.59 3.34 2.13 1.38 1.01 0.77 0.56 0.42 0.35 0.30 0.26 0.21 0.18 0.16

Para calcular la cada de tensin, en V, se multiplicarn los coeficientes de la tabla por la corriente que recorre el cable, en A, y por la longitud de la lnea en Km. Los valores de la tabla se refieren a c.a. trifsica; para corriente monofsica pueden tomarse los mismos valores resultantes, multiplicados por 1,15.

www.es.pirelli.com

66

baja tensin

cables especiales para la industria

BUPRENO
Tensin nominal:

1000 V

Norma bsica:

IEC 60502/1

Designacin genrica:

DN-K 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Espesor nominal cubierta mm Dimetro exterior aproximado mm Peso total aproximado Kg/km Resistencia hmica a 20 C del conductor

1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.5 1.7 1.8 0,7 0.7 0.7 0.7 0.7 0.7 0.9 10.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2

5,8 6.3 6.8 7.3 8.4 9.5 11.1 14.3 14.3 16.4 17.8 20.3 22.4 25 27.9 29.4 9.8 10.7 11.6 12.7 14.9 16.9 20.2 10.2 11.2 11.2 12.2 13.4 18.9 21.6 24.8 28.3 32.2 36

56 67 82 106 153 210 308 413 575 827 1052 1345 1660 2023 2622 3210 120 151 193 255 377 552 814 137 179 233 233 314 696 1040 1408 2016 2839 3576

13.3 7.98 4.95 3.3 1.91 1.21 0.78 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.0801 0.0641 13.3 7.98 4.95 3.30 1.91 1.21 0.78 13.3 7.98 4.95 4.95 3.30 1.21 0.78 0.554 0.386 0.272 0.206

www.es.pirelli.com

67

baja tensin

cables especiales para la industria

BUPRENO
Tensin nominal:

1000 V

Norma bsica:

IEC 60502/1

Designacin genrica:

DN-K 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
DIMENSIONES (continuacin)
Seccin nominal mm2 Espesor nominal aislante mm Espesor nominal cubierta mm Dimetro exterior aproximado mm Peso total aproximado Kg/km Resistencia hmica a 20 C del conductor

3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16 3.5 x 25 3.5 x 35 3.5 x 50 3.5 x 70 3.5 x 95 3.5 x 120 35 x 150 3.5 x 185 3.5 x 240 3.5 x 300

1.2 1.4 1.6 1.7 1.8 0.7 0.7 0.7 0.7 0.7 0.7 0.9 / 0.7 0.9 / 0.7 1 / 0.9 1.1 / 0.9 1.1 / 1 1.2 / 1.1 1.4 / 1.1 1.6 / 1.1 1.7 / 1.2 1.8 / 1.4

2.1 2.3 2.4 2.6 2,8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.1 2.2 2.3 2.5 2.7 2.9

40.1 45.1 50.8 57.1 62.7 11 12.1 13.2 14.6 17.3 19.8 22.8 25.7 29.6 34.7 39.0 42.6 46.0 52.9 59.3 65.3

4336 5500 6813 8784 11285 163 214 283 385 583 875 1212 1566 2294 3217 4034 5099 6196 7740 9914 12740

0.161 0.129 0.106 0.0801 0.0641 13.3 7.98 4.95 3.30 1.91 1.21 0.78 / 1.21 0.554 / 1.21 0.386 / 0.78 0.272 / 0.554 0.206 / 0.386 0.161 / 0.272 0.129 7 0.272 0.106 / 0.206 0.0801 / 0.161 0.064 / 0.129

www.es.pirelli.com

68

baja tensin

cables especiales para la industria

RETENAX F
Tensin nominal:

RETENAX M
Norma bsica:

1000 V

UNE 21123/2

Designacin genrica:

RVFV 0,6/1 kV

Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RVMV (RH) 0,6/1 kV

CARACTERSTICAS CABLE

Resistencia a los golpes

Resistencia a los roedores

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

Resistencia a los agentes qumicos

Resistencia a las grasas y aceites

No propagacin de la llama

No propagacin del incendio

Norma constructiva: UNE 21123-2 Temperatura de servicio (instalacin fija): - 25C, +90C Tensin nominal de servicio: 0,6/1 kV Ensayo de tensin en c.a. durante 5 minutos: 3.500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1; IEC 60332-1; NFC 32070-C2 No propagacin del incendio: UNE EN 50226-2-4; IEC 60332-3; IEEE 383 Reducida emisin de halgenos: UNE EN 50267-2-1; IEC 60754-1; Emisin CLH < 14%.

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico o aluminio. Flexibilidad: clase 1 5 hasta 4 mm2, clase 2 desde 6 mm2; segn UNE 21022 Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito segn la norma UNE 21123-2.

AISLAMIENTO
Aislado con polietileno reticulado (XLPE), tipo DIX3 s/HD 603-1.

Retenax F

Retenax M

CUBIERTA INTERIOR
PVC tipo DMV-18 s/HD 603-1.

ARMADURA
Hilos de acero (M) Hilos de aluminio (MA) Fleje de acero (F) Fleje de aluminio (FA).

CUBIERTA EXTERIOR
PVC tipo DMV-18 s/HD 603-1 color negro con caractersticas de resistencia a los hidrocarburos segn UIC 895 OR en el tipo con armadura (M).

APLICACIONES
Para redes de distribucin, acometidas, instalaciones de alumbrado pblico e instalaciones industriales al aire o enterradas, en las que la flexibilidad no es una necesidad imperiosa y, por el contrario, si es importante que el cable presente unas prestaciones elevadas frente a sobrecargas y cortocircuitos. En instalaciones donde sea preciso proteger los cables contra agresiones mecnicas, tales como esfuerzos de traccin, de cizalladura, contra roedores, contra el riesgo de deflagracin en ambientes de atmsfera explosiva o con riesgo de incendio, etc.

www.es.pirelli.com

69

baja tensin

cables especiales para la industria

RETENAX F
Tensin nominal:

RETENAX M
Norma bsica:

1000 V

UNE 21123/2

Designacin genrica:

RVFV 0,6/1 kV

Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RVMV (RH) 0,6/1 kV

CABLES DISPONIBLES EN STOCK


Secciones disponibles en stock

RETENAX FLAM ARMADOS RVMV(RH)


2 x 2.5 2x4 2x6 3 x 1.5 3 G 2.5 3G4 3G6 3 x 10 3 x 16 3.5 G 16 3.5 G 25 3.5 G 35 3.5 G 50 4 x 1.5 4 x 2.5 4x4 4G6 4 G 10 4 G 16

RETENAX FLAM ARMADOS RVFV


1x6 2 x 1.5 2 x 2.5 2x6 2 x 10 3 x 1.5 3 x 2.5 3x6 3 x 10 3 x 16 3.5 x 16 3.5 x 25 3.5 x 35 3.5 x 50 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16

CARACTERSTICAS TCNICAS
COEFICIENTE PARA EL CLCULO DE LA CADA DE TENSIN
Tres cables unipolares Secin nominal mm2 Cu cos fi = 1 Al Cu cos fi = 0,8 Al Cu cos fi = 1 Al Cu Un cable unipolar cos fi = 0,8 Al

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

26.5 15.92 9.96 6.74 4 2.51 1.59 1.15 0.85 0.59 0.42 0.34 0.27 0.22 0.17 0.14 0.11

4.15 2.62 1.89 1.39 0.97 0.7 0.55 0.45 0.36 0.27 0.22 0.17

21.36 12.88 8.1 5.51 3.31 2.12 1.37 1.01 0.77 0.56 0.43 0.36 0.31 0.26 0.22 0.19 0.17

3.42 2.19 1.6 1.21 0.86 0.65 0.53 0.45 0.37 0.3 0.26 0.22

26.94 16.23 10.16 6.87 4.06 2.56 1.62 1.17 0.86 0.6 0.43 0.34 0.28 0.22 0.17 0.14 0.11

4.24 2.66 1.93 1.42 0.98 0.71 0.56 0.46 0.37 0.28 0.22 0.18

21.27 13.1 8.23 5.59 3.34 2.13 1.38 1.01 0.77 0.56 0.42 0.35 0.3 0.26 0.21 0.18 0.16

3.48 2.21 1.62 1.22 0.87 0.65 0.53 0.44 0.37 0.3 0.25 0.21

Para determinar la cada de tensin en V, se multiplicar el coeficiente de la tabla por la longitud de la lnea en Km y por la intensidad en A.

www.es.pirelli.com

70

baja tensin

cables especiales para la industria

RETENAX F
Tensin nominal:

RETENAX M
Norma bsica:

1000 V

UNE 21123/2

Designacin genrica:

RVFV 0,6/1 kV

Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RVMV (RH) 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
CARACTERSTICAS DIMENSIONALES DE LOS CABLES RVMV
Seccin nominal mm2 Espesor aislamiento nominal mm Dimetro s/aislamiento aproximado mm Dimetro exterior mximo mm Peso total aproximado kg/km Resistencia hmica a 20 C Ohm/km

RVMV - (RH)
2 x 1.5 2 x 2.5 2x4 2x6 3 x 1.5 3 x 2.5 3x4 3x6 4 x 1.5 4 x 2.5 4x4 4x6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 2.9 3.4 3.8 4.3 2.9 3.4 3.8 4.3 2.9 3.4 3.8 4.3 8.3 13.3 14.8 15.7 13.4 14.4 15.3 16.3 14.1 15.2 16.3 17.5 326 339 396 474 313 373 442 541 351 421 509 638 13.3 7.98 4.95 3.08 13.3 7.98 4.95 3.08 13.3 7.98 4.95 3.08

CARACTERISTICAS DIMENSIONALES DE LOS CABLES RETENAX FLAM RVFV


Secin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Cu Al Dimetro exterior aproximado mm Cu Al Peso total aproximado Kg/Km Cu Al Resistencia hmica a 20 C del conductor Ohm/km Cu Al

RVFAV
1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 2 x 1.5 2 x 2.5 2x4 2x6 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2 0.7 0.7 0.7 0.7 6.1 7.7 8.8 10.3 12 13.8 15.4 17.2 19.3 21.8 24.3 27.2 2.8 3.2 3.6 4.3 6.6 8.4 8.9 10.1 11.9 13.8 15.3 17.19.4 22.1 24.3 27.5 13.9 15.5 16.6 18.1 19.8 21.6 23.2 25.27.1 29.6 32.3 35.4 15.1 17.1 17.6 18.8 20.6 22.5 24.25.7 28.1 31.33.4 37.6 340 460 560 705 925 1200 1440 1760 2140 2670 3320 4120 210 250 310 375 310 400 435 495 605 730 840 960 1155 1400 1655 2085 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 12.1 7.41 4.61 3.08 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

RVFV
12.4 13.1 14 15.1

www.es.pirelli.com

71

baja tensin

cables especiales para la industria

RETENAX F
Tensin nominal:

RETENAX M
Norma bsica:

1000 V

UNE 21123/2

Designacin genrica:

RVFV 0,6/1 kV

Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RVMV (RH) 0,6/1 kV

CARACTERISTICAS DIMENSIONALES DE LOS CABLES RETENAX FLAM RVFV (Continuacin)


Secin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Cu Al Dimetro exterior aproximado mm Cu Al Peso total aproximado Kg/Km Cu Al Resistencia hmica a 20 C del conductor Ohm/km Cu Al

RVFV
2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 2 x 70 2 x 95 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 3 x 400 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 0.7 0.7 0.9 0.9 1.1.1 1.1 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.1.1 1.1 5.2 6.4 7.7 8.8 10.3 12.13.8 2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12.13.8 15.4 17.2 19.3 21.8 24.3 27.2 2.8 3.2 3.6 4.4 5.2 6.1 7.7 8.8 10.3 12. 6.6 8.4 8.9 10.1 11.9 13.8 15.3 17.19.4 22.1 24.3 27.5 6.6 8.4 8.9 10.1 11.9 13.8 17.2 19.3 22.5 24.7 27.7 31.3 35.5 12.8 13.6 14.6 16.1 18 20.2 23.7 26.1 29.3 33.2 37.8 43.47.7 52.4 58.2 64.4 71. 13.5 14.4 15.5 17.2 19.4 21.8 25.7 28.8 32.6 37.4 23.27.9 29.1 32.2 37.1 43.6 265 320 405 520 730 1030 1580 2050 2720 3730 780 1100 1255 1545 2060 3060 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 1.91 1.20 0.868 0.641 0.443 0.320 25.8 26.7 29.3 33.4 38.3 43.2 47.5 53.59.3 64.8 72.1 230 275 350 440 610 860 1300 1650 2140 2890 3900 5130 6380 7770 9730 12100 14990 680 960 1090 1285 1670 2200 3015 3610 4450 5495 6600 8080 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 510 765 1070 1340 1730 2300 3060 1.83 1.15 0.727 0.524 0.387 0.268 0.193

www.es.pirelli.com

72

baja tensin

cables especiales para la industria

RETENAX F
Tensin nominal:

RETENAX M
Norma bsica:

1000 V

UNE 21123/2

Designacin genrica:

RVFV 0,6/1 kV

Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RVMV (RH) 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
CARACTERISTICAS DIMENS. DE LOS CABLES RETENAX FLAM RVFV (Continuacin)
Seccin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20C del conductor Ohm/Km

RVFV Conductor de cobre


3 x 10/6 3 x 16/10 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 95/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 95/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 300/150 3 x 400/185 0.7/0.7 0.7/0.7 0.9/0.7 0.9/0.7 1/0.9 1.1/0.9 1.1/1 1.2/1.1 1.4/1.1 1.6/1.1 1.7/1.2 0.9/0.7 0.9/0.7 1/0.9 1.1/0.9 1.1/1 1.2/1.1 1.4/1.1 1.6/1.1 1.7/1.2 1.8/1.4 2/1.6 5.2/4.4 6.1/5.2 7.7/6.1 8.8/6.1 10.3/7.7 12/8.8 13.8/10.3 15.4/12 17.2/12 19.3/13.8 21.8/15.4 8.6/6.6 9.1/6.6 10.1/8.4 11.9/8.9 13.8/10.1 15.3/11.9 17/11.9 19.4/13.8 22.1/15.3 24.3/17 27.5/19.4 19.2 21.3 25.3 27.4 30.6 35.6 41.4 45.7 49.8 55.61.2 26.8 27.8 31.35.4 41.3 45.5 49.3 55.2 61.7 67.2 75.770 1035 1510 1855 2390 3345 4800 5920 7115 8795 11030 1055 1170 1435 1885 2770 3345 3900 4840 5995 7135 8795 1.83/3.08 1.15/1.83 0.727/1.15 0.525/1.15 0.387/0.727 0.268/0.525 0.193/0.387 0.153/0.268 0.124/0.268 0.0991/0.193 0.0754/0.153 1.2/1.91 0.868/1.91 0.641/1.2 0.443/0.868 0.320/0.641 0.253/0.443 0.206/0.443 0.164/0.320 0.125/0.253 0.1/0.206 0.0778/0.164

Conductor de aluminio

www.es.pirelli.com

73

baja tensin

cables especiales para la industria

RETENAX F
Tensin nominal:

RETENAX M
Norma bsica:

1000 V

UNE 21123/2

Designacin genrica:

RVFV 0,6/1 kV

Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RVMV (RH) 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
CARACTERISTICAS DIMENSIONALES DE LOS CABLES RETENAX FLAM RVMV
Secin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Cu Al Dimetro exterior aproximado mm Cu Al Peso total aproximado Kg/Km Cu Al Resistencia hmica a 20 C del conductor Ohm/km Cu Al

RVMAV
1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 2 x 70 2 x 95 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 3 x 400 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2 6.1 7.7 8.8 10.3 12 13.8 15.4 17.2 19.3 21.8 24.3 27.2 2.8 3.2 3.6 4.3 5.2 6.4 7.7 8.8 10.3 12 13.8 2.9 3.4 3.8 4.3 5.2 6.1 7.7 8.8 10.3 12 13.8 15.4 17.2 19.3 21.8 24.3 27.2 6.6 8.4 8.9 10.1 11.9 13.8 15.3 17 19.4 22.1 24.3 27.5 6.6 8.4 8.9 10.1 11.9 13.8 15.3 17 19.4 22.1 24.3 27.7 14.5 16.1 17.2 18.7 20.4 22.2 23.8 25.6 27.7 30.4 33.1 37 15.1 17.1 17.6 18.8 20.6 22.5 24 25.7 28.1 31 33.4 37.6 25.0 27.8 28.9 31.7 36.6 41.5 44.9 50.4 55.7 62 67.5 74.8 370 495 605 760 985 1280 1520 1850 2240 2800 3450 4360 292 338 395 473 641 874 1546 1895 2324 3220 4029 313 373 442 541 730 1290 1770 2170 2760 3840 4970 5920 7680 9200 11320 13320 16980 310 400 435 495 605 730 840 960 1155 1400 1655 2085 825 1510 1640 1930 2650 3335 3845 4985 5965 7203 8475 10170 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 12.1 7.41 461 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 13.3 7.98 4.95 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

RVMV
12.1 13.3 14.3 15.2 17 19.8 25.9 28.1 30.7 35.3 39 13.4 14.4 15.3 16.3 18.3 24 25.8 28.2 31.6 36.3 40.9 44.6 50.3 55 60.8 67 73.6

www.es.pirelli.com

74

baja tensin

cables especiales para la industria

RETENAX F
Tensin nominal:

RETENAX M
Norma bsica:

1000 V

UNE 21123/2

Designacin genrica:

RVFV 0,6/1 kV

Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RVMV (RH) 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
CARACTERISTICAS DIMENSIONALES DE LOS CABLES RETENAX FLAM RVMV (continuacin)
Secin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Cu Al Dimetro exterior aproximado mm Cu Al Peso total aproximado Kg/Km Cu Al Resistencia hmica a 20 C del conductor Ohm/km Cu Al

RVMV
4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 2.9 3.4 3.8 4.3 5.2 6.1 7.7 8.8 10.3 12 13.8 6.6 8.4 8.9 10.1 11.9 13.8 14.1 15.2 16.3 17.5 19.6 25.7 27.8 31.2 35.2 40.6 27 30.1 31.6 34.6 43 45.3 351 421 509 638 865 1510 2100 2710 3450 4840 935 1075 1895 2255 3150 3910 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 1.91 1.20 0.868 0.641 0.443 0.320

CARACTERSTICAS DIMENSIONALES
CARACTERISTICAS DIMENS. DE LOS CABLES RETENAX FLAM RVMV (continuacin)
Seccin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20C del conductor Ohm/Km

RVMV Conductor de cobre


3 x 10/6 3 x 16/10 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 95/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 25/16 3 x 35/16 3 x 50/25 3 x 70/35 3 x 95/50 3 x 120/70 3 x 150/70 3 x 185/95 3 x 240/120 3 x 300/150 3 x 400/185 0.7/0.7 0.7/0.7 0.9/0.7 0.9/0.7 1/0.9 1.1/0.9 1.1/1 1.2/1.1 1.4/1.1 1.6/1.1 1.7/1.2 0.9/0.7 0.9/0.7 1/0.9 1.1/0.9 1.1/1 1.2/1.1 1.4/1.1 1.6/1.1 1.7/1.2 1.8/1.4 2/1.6 5.2/4.4 6.1/5.2 7.7/6.1 8.8/6.1 10.3/7.7 12/8.8 13.8/10.3 15.4/12 17.2/12 19.3/13.8 21.8/15.4 8.6/6.6 9.1/6.6 10.3/8.6 12.1/9.1 14/10.3 15.5/12.1 17.2/12.1 19.6/14 22.3/15.5 24.5/17.2 27.7/19.6 19.7 25.1 28.8 40 34.3 38.8 43.1 47.2 52.5 57.7 64.1 29 30 33.4 38.6 43 47 52 57.9 64.6 69.9 79 900 1426 1962 2376 3010 4390 5600 6795 8515 10370 12820 1630 1775 2135 2935 3575 4220 5310 6415 7820 9090 11825 1.83/3.08 1.15/1.83 0.727/1.15 0.525/1.15 0.387/0.727 0.268/0.525 0.193/0.387 0.153/0.268 0.124/0.268 0.0991/0.193 0.0754/0.153 1.20/1.91 0.868/1.91 0.641/1.20 0.443/0.868 0.320/0.641 0.253/0.443 0.206/0.443 0.164/0.320 0.125/0.253 0.100/0206 0.0778/0.164

Conductor de aluminio

www.es.pirelli.com

75

www.es.pirelli.com

76

baja tensin

cables para edificacin e industria

RETENAX VARINET
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

RVKV 0,6/1kV

CARACTERSTICAS CABLE

No propagacin de la llama

No propagacin del incendio

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

Normativa de diseo: UNE 21123-2 Tensin Nominal de Servicio: 0,6/1 kV. Temperatura de Servicio (Inst. fija): -25 + 90 C. Tensin de ensayo en c.a. durante 5 min.: 3500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265, IEC 60332-1 No propagacin del incendio: UNE EN 50266, IEC 60332-3

DESCRIPCIN
CONDUCTOR
Metal: cable electroltico . Flexibilidad: clase 5 segn UNE 21022 Temperatura mxima en el conductor: 90 C en servicio continuo, 250 C en cortocircuito segn norma UNE 21123-2.

AISLAMIENTO
Aislado con polietileno reticulado (XLPE), tipo DIx3 s/HD 603-1.

CUBIERTA INTERIOR
PVC tipo DMV-18 s/HD 603-1.

CONDUCTOR CONCNTRICO
Corona de hilos de cobre colocados helicoidalmente + contraespia de cobre.

CUBIETA EXTERIOR
PVC tipo DMV-18 s/HD 603-1. Color negro.

APLICACIONES
Cables especiales para interconexin entre variadores de frecuencia y motores, de acuerdo con las indicaciones del fabricante de dichos variadores.

www.es.pirelli.com

77

baja tensin

cables para edificacin e industria

RETENAX VARINET
Tensin nominal:

1000 V

Norma bsica:

UNE 21123-2

Designacin genrica:

RVKV 0,6/1kV

CABLES DISPONIBLES
SECCIONES DISPONIBLES
Secciones

3 x 2,5 / 2,5 3 x 95 / 50

3x4/4 3 x 120 / 70

3x6/6 3 x 150 / 70

3 x 10 / 10 3 x 185 / 95

3 x 16 / 16 3 x 240 / 120

3 x 25 / 16 3 x 300 / 150

3 x 35 / 16

3 x 50 / 25

3 x 70 / 35

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin mm2 Espesor nominal aislamiento mm Dimetro s/ aislamiento aproximado mm Dimetro exterior nominal mm Peso aproximado Kg/Km Resistencia conductor a 20 C

3 x 2,5 / 2,5 3x4/4 3x6/6 3 x 10 / 10 3 x 16 / 16 3 x 25 / 16 3 x 35 / 16 3 x 50 / 25 3 x 70 / 35 3 x 95 / 50 3 x 120 / 70 3 x 150 / 70 3 x 185 / 95 3 x 240 / 120 3 x 300 / 150

0.7 0.7 0.7 0.7 0.7 0.9 0.9 7.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8

3,4 3.8 4.4 5.5 6.6 8.2 9.7 10.8 12.9 14.4 15.9 18 20.5 23.3 25.7

14.2 15.2 16.6 19.1 22.1 25.9 29.1 31.7 36.7 40.6 44.3 48.3 56.1 63.1 70.1

290 350 440 650 910 1330 1720 2330 3190 4110 5180 6390 8080 10410 13390

7,980 4,950 3,300 1,910 1,210 0,780 0,554 0,386 0,272 0,206 0,161 0,129 0.106 0,0801 0,0641

www.es.pirelli.com

78

baja tensin

cables para edificacin e industria

AFUMEX PANELES FLEXIBLE


Tensin nominal:

750 V

Norma bsica:

UNE 21027/9

Designacin genrica:

H07Z-K

CARACTERSTICAS CABLE

Cable flexible

Libre de halgenos

Reducida emisin de gases txicos

Baja emisin Nula emisin de humos opacos de gases corrosivos

No propagacin de la llama

No propagacin del incendio

Resistencia a la absorcin del agua

Resistencia al fro

Norma constructiva: UNE 21027-9; HD 22.9 S2; NI 56.10.00 Temperatura de servicio (instalacin fija): - 40, +90 C Tensin nominal de servicio: 750 V Ensayo de tensin en c.a. durante 5 minutos: 2,5 kV Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2 No propagacin del incendio: UNE EN 50266-2-4 ; UNE 20427 ; IEC 60332-3 ; IEEE 383 ; NFC 32070-C1 Libre de halgenos: UNE EN 50267-2-1 ; IEC 60754-1 ; BS 6425-1 Reducida emisin de gases txicos: NES 713 ; NFC 20454 ; It =< 1,5 Baja emisin de humos opacos: UNE EN 50268 ; IEC 61034 - 1,2 Nula emisin de gases corrosivos: UNE EN 50267-2-3 ; IEC 60754-2 ; NFC 20454 ; BS 6425-2 ; pH >= 4,3 ; C =< 10 + S/mm

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 5; segn UNE 21022. Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito segn norma UNE 21123.

AISLAMIENTO
Aislamiento termoestable AFUMEX clase EI5 segn UNE 21027-9, en los colores: gris.

APLICACIONES
Cable especialmente adecuado para el cableado de paneles, armarios de cuadros y bastidores de rels.

www.es.pirelli.com

79

baja tensin

cables especiales para la industria

AFUMEX PANELES FLEXIBLE


Tensin nominal:

750 V

Norma bsica:

UNE 21027/9

Designacin genrica:

H07Z-K

CABLES DISPONIBLES EN STOCK


TABLA DE COLORES SEGN SECCIN
Seccin Colores cable

1 x 0,5 1 x 0,75 1x1 1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16

GR GR GR GR GR GR GR GR GR

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Secin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20 C del conductor Ohm/km

1 x 1.5* 1 x 0.75* 1 x 1* 1 x 1.5 1 x 2.5 1 x 40 1x6 1 x 10 1 x 16 * segn NI 56.10.00

0.7 0.7 0.7 0.7 0.8 0.8 0.8 1 1

2.3 2.5 2.7 3 3.6 4.1 4.6 6.1 7.2

10 12 15 20 31 45 64 108 160

39 26 19.5 13.3 19.7 4.95 3.3 1.91 1.21

www.es.pirelli.com

80

baja tensin

cables especiales para la industria

AFUMEX PANELES RGIDO


Tensin nominal:

750 V

Norma bsica:

UNE 21027/9

Designacin genrica:

H07Z-R

CARACTERSTICAS CABLE

Libre de halgenos

Reducida emisin de gases txicos

Baja emisin de humos opacos

Nula emisin de gases corrosivos

No propagacin de la llama

No propagacin del incendio

Resistencia a la absorcin del agua

Resistencia al fro

Norma constructiva: UNE 21027-9; HD 22.9 S2 Temperatura de servicio (instalacin fija): - 40, +90C Tensin nominal de servicio: 750 V Ensayo de tensin en c.a. durante 5 minutos: 2,5 kV Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2 No propagacin del incendio: UNE EN 50266-2-4 ; UNE 20427 ; IEC 60332-3 ; IEEE 383 ; NFC 32070-C1 Libre de halgenos: UNE EN 50267-2-1 ; IEC 60754-1 ; BS 6425-1 Reducida emisin de gases txicos: NES 713 ; NFC 20454 ; It =< 1,5 Baja emisin de humos opacos: UNE EN 50268 ; IEC 61034 - 1,2 Nula emisin de gases corrosivos: UNE EN 50267-2-3 ; IEC 60754-2 ; NFC 20454 ; BS 6425-2 ; pH >= 4,3 ; C <= 10 + S/mm

DESCRIPCIN
CONDUCTOR
Metal: cobre electroltico recocido. Flexibilidad: clase 2; segn UNE 21 022 Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito segn norma UNE 21123.

AISLAMIENTO
Aislamiento termoestable AFUMEX clase EI5 segn UNE 21027-9, en los colores: negro, azul, marrn, gris, amarillo-verde y rojo.

APLICACIONES
Cable especialmente adecuado para el cableado de paneles, armarios de cuadros, bastidores de rels y centralizacin de contadores.

www.es.pirelli.com

81

baja tensin

cables especiales para la industria

AFUMEX PANELES RGIDO


Tensin nominal:

750 V

Norma bsica:

UNE 21027/9

Designacin genrica:

H07Z-R

CABLES DISPONIBLES EN STOCK


TABLA DE COLORES SEGN SECCIN
Seccin Colores cable

1 x 2.5 1x4 1 x 10

NE-AZ-GR-RO-MA NE-AZ-GR-MA NE-AZ-GR-AV-MA

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Secin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20 C del conductor Ohm/km

1 x 2.5 1x4 1 x 10

0.8 0.8 1

3.7 4.2 6

35 51 111

7.41 4.61 1.83

www.es.pirelli.com

82

baja tensin

cables para edificacin e industria

AFUMEX VARINET K 0,6/1 kV


Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

RZ1KZ1 0,6/1kV

CARACTERSTICAS CABLE

No propagacin de la llama

No propagacin del incendio

Baja emisin de humos

Libre de halgenos

Reducida emisin de gases txicos

Nula emisin de gases corrosivos

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

Normativa de diseo: UNE 21123-4 Tensin Nominal de Servicio: 0,6/1 kV. Temperatura de Servicio (Inst. fija): -40 + 90 C. Tensin de ensayo en c.a. durante 5 min.: 3500 V Ensayos de fuego: No propagacin de la Llama: No propagacin del incendio: Reducida emisin de humos: Libre de halgenos: Indice mx. toxicidad: Corrosividad de los humos: UNE EN 50265-2-1, IEC 60332-1 UNE EN 50266-2-4 , IEC 60332-3, IEEE 383 UNE EN 50268, IEC 61034-1.2 UNE EN 50267-2-1, IEC 60754-1 NES 713, NF C 20454 It ) 1,5 UNE EN 50267-2-3, IEC 60754-2, NF C 20454 ph * 4,3 C ) 10 +S/cm

DESCRIPCIN
CONDUCTOR
Metal: cable electroltico . Flexibilidad: clase 5 segn UNE 21022 Temperatura mxima en el conductor: 90 C en servicio continuo, 250 C en cortocircuito segn norma UNE 21123-4.

AISLAMIENTO
Aislado con polietileno reticulado (XLPE), tipo DIx3 s/HD 603-1.

CUBIERTA INTERIOR
Mezcla especial termoplstica cero halgenos tipo Z1 segn norma UNE 21123-4 anexo 1.

CONDUCTOR CONCNTRICO
Corona de hilos de cobre colocados helicoidalmente + contraespia de cobre.

CUBIETA EXTERIOR
Mezcla especial termplstica cero halgenos tipo Z1 segn norma UNE 21123-4 anexo 1. Color verde.

APLICACIONES
Cables especiales para interconexin entre variadores de frecuencia y motores, de acuerdo con las indicaciones del fabricante de dichos variadores.

www.es.pirelli.com

83

baja tensin

cables para edificacin e industria

AFUMEX VARINET K 0,6/1 kV


Tensin nominal:

1000 V

Norma bsica:

UNE 21123/4

Designacin genrica:

RZ1KZ1 0,6/1kV

CABLES DISPONIBLES
SECCIONES DISPONIBLES
Secciones

3 x 2,5 / 2,5 3 x 95 / 50

3x4/4 3 x 120 / 70

3x6/6 3 x 150 / 70

3 x 10 / 10 3 x 185 / 95

3 x 16 / 16 3 x 240 / 120

3 x 25 / 16 3 x 300 / 150

3 x 35 / 16

3 x 50 / 25

3 x 70 / 35

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin mm2 Espesor nominal aislamiento mm Dimetro s/ aislamiento aproximado mm Dimetro exterior nominal mm Peso aproximado Kg/Km Resistencia conductor a 20 C

3 x 2,5 / 2,5 3x4/4 3x6/6 3 x 10 / 10 3 x 16 / 16 3 x 25 / 16 3 x 35 / 16 3 x 50 / 25 3 x 70 / 35 3 x 95 / 50 3x120 / 70 3x150 / 70 3x185 / 95 3x240 / 120 3x300 / 150

0.7 0.7 0.7 0.7 0.7 0.9 0.9 7.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8

3,4 3.8 4.4 5.5 6.6 8.2 9.7 10.8 12.9 14.4 15.9 18 20.5 23.3 25.7

14.2 15.2 16.6 19.1 22.1 25.9 29.1 31.7 36.7 40.6 44.3 48.3 56.1 63.1 70.1

290 350 440 650 910 1330 1720 2330 3190 4110 5180 6390 8080 10410 13390

7,980 4,950 3,300 1,910 1,210 0,780 0,554 0,386 0,272 0,206 0,161 0,129 0.106 0,0801 0,0641

www.es.pirelli.com

84

baja tensin

cables para acometidas y lneas areas

AL POLIRRET
Tensin nominal:

1000 V

Norma bsica:

UNE 21030

Designacin genrica:

AL RZ 0,6/1 kV

CARACTERSTICAS CABLE

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

RESISTENCIA A LA INTEMPERIE Es evidente que en un cable destinado a prestar servicio al aire libre, en el que adems el aislamiento constituye al propio tiempo la cubierta, los ensayos de resistencia a los efectos de la radiacin ultravioleta, al ozono y a la humedad saturante en una atmsfera agresiva de dixido de azufre, adquieren una destacada importancia. La citada Norma UNE 21030 especifica los ensayos que deben superar estos cables para garantizar una satisfactoria y prolongada vida til de estos materiales.

DESCRIPCIN
CONDUCTOR
Metal: aluminio en los conductores activos. Flexibilidad: clase 2, segn UNE 21022. Neutro fiador: cuando el cable dispone de un conductor neutro, ste estar constituido por una cuerda de alambres de aleacin de aluminio, tipo "Almelec". Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito

AISLAMIENTO
Aislados con XLPE (polietileno reticulado), que a su vez funciona de cubierta de color negra.

REUNIN
Conductores aislados reunidos entre s o en torno al neutro fijador si dispone de l .

APLICACIONES
Especialmente adecuados para instalaciones de lneas areas tensadas autosoportadas en redes secundarias de distribucin en electrificacin rural, alumbrado pblico o acometidas de usuarios, tensados autosoportados sobre apoyos o posados sobre las fachadas de los edificios. No se deben utilizar en instalaciones enterradas ni empotradas.

www.es.pirelli.com

85

baja tensin

cables para acometidas y lneas areas

AL POLIRRET
Tensin nominal:

1000 V

Norma bsica:

UNE 21030

Designacin genrica:

AL RZ 0,6/1 kV

CABLES DISPONIBLES EN STOCK


Secciones disponibles en stock

2 x 16 2 x 16 - 2 x 2.5 2 x 25 3 x 25 + 1 x 29.5 3 x 50 + 1 x 29.5 3 x 50 - 1 x 54.6 3 x 95 - 1 x 54.6 3 x 150 - 1 x 80.6 4 x 16 4 x 16 + 2 x 2,5 4 x 25

CARACTERSTICAS TCNICAS
CLCULO DE LA CADA DE TENSIN
Secin nominal mm2 Coeficientes para c.a. trifsica cos fi = 1 cos fi = 0,8

16 25 50 95 150

4.30 2.70 1.44 0.72 0.47

3.53 2.25 1.24 0.66 0.45

Para determinar la cada de tensin en V, se multiplicar el coeficiente de la tabla por la longitud de la lnea en Km y por la intensidad en A. Los valores obtenidos, como se indica en el prrafo anterior, se refieren a corriente alterna trifsica. Para corriente monofsica pueden tomarse dichos valores multiplicados por 1,15.

www.es.pirelli.com

86

baja tensin

cables para acometidas y lneas areas

AL POLIRRET
Tensin nominal:

1000 V

Norma bsica:

UNE 21030

Designacin genrica:

AL RZ 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Carga de rotura mnima daN Espesor medio aislante mm Dimetro conductor aislado Resistencia hmica de 20 C del conductor Ohm/Km

Clase: Fase o neutro no fiador


16 25 50 95 150 29.5 54.5 80 190 300 600 1140 1800 870 1660 2000 1.2 1.4 1.6 1.8 2.0 7.9 9.6 12.3 16.1 19.3 10.4 13.0 15.8 1.93 1.20 0.641 0.320 0.206 1.15 0.63 0.40

Clase: Neutro fiador ALMELEC


1.4 1.6 1.8

Seccin mominal mm2

Dimetro de referencia

Peso total aproximado Kg/Km

2 x 16 2 x 25 4 x 16 4 x 25 4 x 50 3 x 95 / 50 3 x 150 / 95 1 x 25 Al/54.6 Alm 1 x 50 Al/54.6 Alm 3 x 25 Al/29.5 Alm 3 x 25 Al/54.6 Alm 3 x 50 Al/29.5 Alm 3 x 50 Al/54.6 Alm 3 x 95 Al/54.6 Alm 3 x 150 Al/80 Alm

15.8 19.2 18.0 23.1 29.6 38.0 46.5 22.6 25.3 27.1 31.0 32.1 36.0 44.0 51.0

145 225 285 445 770 1250 1875 310 385 425 535 640 765 1260 1700

Las caractersticas mecnicas del fiador de aleacin de aluminio son: Coeficientes de dilatacin lineal: 23 x 10^-6 K^-1 Mdulo de elasticidad: 62000 N/mm2

www.es.pirelli.com

87

www.es.pirelli.com

88

baja tensin

cables para acometidas y lneas areas

POLIRRET COBRE
Tensin nominal:

1000 V

Norma bsica:

EA-002

Designacin genrica:

RZ 0,6/1 kV

CARACTERSTICAS CABLE

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia al fro

RESISTENCIA A LA INTEMPERIE Es evidente que en un cable destinado a prestar servicio al aire libre, en el que adems el aislamiento constituye al propio tiempo la cubierta, los ensayos de resistencia a los efectos de la radiacin ultravioleta, al ozono y a la humedad saturante en una atmsfera agresiva de dixido de azufre, adquieren una destacada importancia. La citada Norma UNE 21030 especifica los ensayos que deben superar estos cables para garantizar una satisfactoria y prolongada vida til de estos materiales.

DESCRIPCIN
CONDUCTOR
Metal: cobre. Flexibilidad: clase 1 para las secciones de 2.5 y 4 mm2 y clase 2 para las secciones superiores, segn UNE 21022. Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito.

AISLAMIENTO
Aislados con XLPE (polietileno reticulado), que a su vez funciona de cubierta de color negra.

REUNIN
Conductores aislados reunidos entre s.

APLICACIONES
Adecuados para instalaciones de lneas areas en redes secundarias de distribucin en electrificacin rural, alumbrado o acometidas de usuarios, pasadas sobre fachadas de los edificios. No se deben utilizar en instalaciones enterradas ni empotradas.

www.es.pirelli.com

89

baja tensin

cables para acometidas y lneas areas

POLIRRET COBRE
Tensin nominal:

1000 V

Norma bsica:

EA-002

Designacin genrica:

RZ 0,6/1 kV

CABLES DISPONIBLES EN STOCK


Secciones disponibles en stock

2x4 2x6 2 x 10 2 x 16 4 x 2,5 4x4 4x6 4 x 10 4 x 16 4 x 25

CARACTERSTICAS TCNICAS
CLCULO DE LA CADA DE TENSIN
Secin nominal mm2 Coeficientes para c.a. trifsica cos fi = 1 cos fi = 0,8

2.5 4 6 10 16 25

15.92 9.96 6.74 4.00 2.51 1.6

21.36 8.10 5.51 3.39 2.16 1.38

Para determinar la cada de tensin en V, se multiplicar el coeficiente de la tabla por la longitud de la lnea en Km y por la intensidad en A. Los valores obtenidos, como se indica en el prrafo anterior, se refieren a corriente alterna trifsica. Para corriente monofsica pueden tomarse dichos valores multiplicados por 1,15.

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica de 20 C del conductor Ohm/Km

2 x 2.5 2x4 2x6 2 x 10 4 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25

1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.4

9.2 10.6 12.4 10.0 11.1 12.8 15.0 17.2 21.1

95 135 215 130 185 270 425 640 1010

7.41 4.61 3.08 1.83 7.41 4.61 3.08 1.83 1.15 0.727

No se facilita la carga de rotura de este tipo de cables, pues su instalacin deber tener la consideracin de red posada o, en el caso de que sea tensada, deber disponer de un cable fiador adicional de acero.

www.es.pirelli.com

90

baja tensin

cables para acometidas y lneas areas

AL VOLTALENE N
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

AL RV 0,6/1 kV

CARACTERSTICAS CABLE

Resistencia a los golpes

Resistencia al fro

Resistencia a la absorcin del agua

Resistencia a los rayos ultravioletas

Resistencia a los agentes qumicos

Resistencia a las grasas y aceites

No propagacin de la llama

RESISTENTE A LOS ACEITES, CIDOS Y ALCALIS Norma constructiva: UNE 21123-2 Temperatura de servicio (instalacin fija): -25C, +90C Tensin nominal de servicio: 0,6/1 kV Ensayo de tensin en c.a. durante 5 minutos: 3.500 V Ensayos de fuego: No propagacin de la llama: UNE EN 50265-2-1 ; IEC 60332-1 ; NFC 32070-C2 Reducida emisin de halgenos: UNE EN 50267-2-1; IEC 60754-1; Emisin ClH < 14%

DESCRIPCIN
CONDUCTOR
Metal: aluminio. Flexibilidad: clase 2 segn UNE 21 022. Temperatura mxima en el conductor: 90C en servicio continuo, 250C en cortocircuito segn norma UNE 21123.

AISLAMIENTO
Aislado con polietileno reticulado (XLPE) tipo D1x3 = s/HD 603-1.

CUBIERTA
PVC tipo DMV-18 s/HD 603-1 de color negro.

APLICACIONES
Estos cables pueden utilizarse en redes de distribucin, acometidas, instalaciones al aire o enterradas, industriales, de alumbrado pblico y, por sus caractersticas trmicas y elctricas, en aquellas instalaciones donde sean previsibles sobrecargas o cortocircuitos..

www.es.pirelli.com

91

baja tensin

cables para acometidas y lneas areas

AL VOLTALENE N
Tensin nominal:

1000 V

Norma bsica:

UNE 21123/2

Designacin genrica:

AL RV 0,6/1 kV

CABLES DISPONIBLES EN STOCK


Secciones disponibles en stock

1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300

CARACTERSTICAS TCNICAS
CLCULO DE LA CADA DE TENSIN
Secin nominal mm2 Coeficientes para c.a. trifsica cos fi = 1 cos fi = 0,8

1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300

4.15 2.62 1.89 1.39 0.97 0.70 0.55 0.45 0.36 0.27 0.22

3.42 2.19 1.60 1.21 0.86 0.65 0.53 0.45 0.37 0.30 0.26

Para determinar la cada de tensin, en V, se multiplicar el coeficiente de la tabla anterior por la longitud de la lnea, en Km, y por la intensidad en A. La cada de tensin de esta tabla, est referida a la temperatura mxima de servicio en el conductor de 90C.

www.es.pirelli.com

92

baja tensin

cables para acometidas y lneas areas

AL VOLTALENE N
Tensin nominal:

1000 V

Norma bsica:

UNE 21123-2

Designacin genrica:

AL RV 0,6/1 kV

CARACTERSTICAS DIMENSIONALES
DIMENSIONES
Seccin nominal mm2 Espesor nominal aislante mm Dimetro s/aisl. aproximado mm Dimetro exterior aproximado mm Peso total aproximado Kg/Km Resistencia hmica a 20C del conductor Ohm/Km

1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300

0.7 0.9 0.9 1.1.1 1.1 1.2 1.4 1.6 1.7 1.8

6.6 8.4 8.9 10.1 11.9 13.8 15.3 17 19.4 22.1 24.3

10.2 12 12.4 13.7 15.5 17.4 19.4 20.6 23 25.7 27.9

140 195 220 265 350 445 530 630 785 980 1180

1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1

www.es.pirelli.com

93

www.es.pirelli.com

94

baja tensin

accesorios

CINTA DE PVC - P1000


CARACTERSTICAS
Excelentes caractersticas de adherencia y fcil manejabilidad.
Caractersticas Unidad

Espesor Carga de rotura Elongacin rotura Adhesin metal Adhesin dorso Resistencia dielctrica Autoextinguible

mm kg / cm % g / cm g / cm kV / mm

0,15 2,165 157 364 433 58 S

DESCRIPCIN
Cinta P1000. Fabricada en PVC, est disponible en varios colores, y con dimensiones 20 metros x 19 mm de ancho x 0,15 mm.

TABLA DE COLORES DISPONIBLES


Colores cinta

NE-BL-AZ-GR-MA-RO-VE-AM-AV

CDIGO DE COLORES AV - Amarillo-Verde AZ - Azul BL - Blanco GR - Gris MA - Marrn NE - Negro RO - Rojo VE - Verde AM - Amarillo

PRESENTACIN Y EMBALAJE Packs de 10 rollos y cajas de 25 packs.

www.es.pirelli.com

95

www.es.pirelli.com

96

baja tensin

accesorios

EMPALMES Y DERIVACIONES CASTFIT


Los kits estn compuestos por dos medias protecciones acoplables entre s,ajustables sobre el exterior del cable y rellenas de mezcla aislante
exterior cable mm Secciones mximas de los cables (*) mm2 RESINAC Tipo Envase

Empalme

Modelo

26 125

J0

8 a 18

1 x 50

2 x 10

3x6

4x6

E3

Bolsa

35 185

J1

12 a 26

1 x 120

2 x 25

3 x 25 3 x 10 / 10

4 x 16

E3

Bolsa

48 245

J2

14 a 32

1 x 240

3 x 50

4 x 25

E3

Bolsa

52 325

J3

23 a 39

1 x 300

3 x 70 3 x 50 / 35 3 x 120 3 x 70 / 50 3 x 240 3 x 185 / 70

4 x 50

E3

Bolsa

68 375

J4

28 a 50

1 x 400

4 x 95

E3

Bolsa

110

J15
540

38 a 58

1 x 630

4 x 150

P1

Bidn

150

J17
700

62 a 86

4 x 300

3 x 240

P1

Bidn

exterior del cable mm Derivacin


250 65

Secciones mximas de los cables (*) Principal Derivado Tipo

RESINAC Envase

Modelo

Principal

Derivado

D2

12 a 24

12 a 24

2 x 16 4 x 10

2 x 16 4 x 10

E3

Bolsa

370 85

D4

20 a 36

18 a 28

4 x 50

4 x 25

P1

Bidn

300 105

D14

28 a 50

20 a 33

3 x 120 4 x 95

3 x 50 4 x 35

P1

Bidn

420

D16

28 a 60

18 a 45

3 x 185 4 x 150

3 x 95 4 x 70

125

P1

Bidn

(*) Estas secciones son de ejemplo y estn dadas a ttulo indicativo.

www.es.pirelli.com

97

www.es.pirelli.com

98

baja tensin

accesorios termorretrctiles

CAPUCHONES TERMORRETRCTILES PARA PRECINTADO DE PUNTAS DE CABLE


CARACTERSTICAS
Fcil instalacin Altamente resistente a los rayos ultravioleta y agentes agresivos Impermeabilidad, almacenaje ilimitado Elevada resistencia a los agentes atmosfricos Elevada resistencia mecnica La gama SKH comprende los capuchones de medio espesor, adaptados para el sellado de las puntas de los cables no presurizados o de baja presurizacin. Despus de la contraccin, el capuchn resiste hasta la presin de 1200 mb. Con siete tallas se abarca la gama de 48 115 mm . El adhesivo del interior del capuchn se derrite con la aplicacin de calor, garantizando el sellado perfecto de la punta del cable.

W A

CAPUCHONES TIPO SKH


Tipo A mm (*) A mm (*) B mm B mm (*) W mm (*)

SKH 15 SKH 22 SKH 35 SKH 55 SKH 75 SKH 95 SKH 110 -

5 9 15 25 30 40 35

15 22 35 55 75 95 110

5 9 15 25 30 40 35

B
42 70 100 150 160 170 170

42 60 97 135 144 151 135

2,0 2,5 3,0 3,0 5,2 4,5 7,0

El dimetro de las piezas de contraccion deber ser aproximadamente 5 mm mayor que el dimetro del cable.

www.es.pirelli.com

99

baja tensin

accesorios termorretrctiles

TRIFURCACIONES TERMORRETRCTILES
CARACTERSTICAS
Rpida y simple colocacin Excelente resistencia a abrasivos y agentes qumicos Vida ilimitada Contraccin longitudinal inferior al 10% Temperatura de servicio de -50 8 +120 C Se precisan pocas tallas Excelente hidrfugo Recubierto en su interior con adhesivo derretible durante el proceso de contraccin.
A C

RAMIFICACIN TIPO SEH


Tipo A mm A mm (*) B mm B mm (*) C mm C mm (*) W mm (*)

SEH 2
SEH 2 SEH 2 SEH 3 SEH 3 SEH 3 SEH 3 SEH 3 SEH 4 SEH 4 SEH 4 SEH 4 SEH 4 SEH 4 30 - 10 50 - 24 25 - 9 45 - 17 55 - 23 82 - 35 110 -35 28 - 9 35 - 12 47 - 23 60 - 23 78 - 36 95 - 36 30 50 25 45 55 82 110 28 35 48 60 78 95 10 24 9 17 23 35 35 9 12 23 23 35 36 65 85 94 120 15 21 9 13 30 36 40 9,0 15,0 21,5 30,0 38,0 45,0 4,0 7,0 3,0 4,6 9,0 17,5 17,5 1,8 3,0 6,4 6,4 12,5 12,5 1,5 3,0 2,5 3,0 3,0 4,0 4,0 2,7 3,0 4,1 4,1 4,0 4,0

SEH 3
45 85 115 130 145 76 93 180 178 230

SEH 4
50 75 110 125 150 140 78 120 165 202 240 240

www.es.pirelli.com

100

baja tensin

accesorios termorretrctiles

TUBOS TERMORRETRCTILES
CARACTERSTICAS
Simple y rpida instalacin Vida ilimitada Excelente resistencia a abrasivos y agentes qumicos Contracciones longitudinales inferiores al 10% Temperatura de servicio de -50 8 +120 C Dos series de tubos retrctiles de medio y alto espesor, excelentes para la reconstitucin del aislamiento en cables elctricos de aislamiento seco, unin de tuberas, etc., recubiertos en su interior con adhesivo derretible.
A

W A

TUBO DE PARED MEDIANA CON ADHESIVO. CONTRACCIN 3:1.


Tipo Contraccin de A hasta A(*) mm. Espesor W(*) mm. Largo mm.

SRUM SRUM SRUM SRH2 SRH2 SRH2 SRH2 SRH2 SRH2 SRH2 SRH2 SRH2 SRH2 SRH2 SRH2

3-1 6-2 9-3 8-2 12 - 3 22-6 34- 7 40 - 12 56 - 16 63 - 19 75 - 22 95 - 26 120 - 34 140 - 42 160 - 50

3 6 9 8 12 22 34 40 56 63 75 95 120 140 160

1 2 3 2 3 6 7 12 16 19 22 26 34 42 50

1,0 1,2 1,4 1,3 1,4 2,0 2,6 2,6 2,6 2,8 3,0 3,2 3,3 3,5 3,5

1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000

www.es.pirelli.com

101

baja tensin

accesorios termorretrctiles

FUNDAS TERMORRECTRCTILES PARA REPARACIN DE CUBIERTAS


CARACTERSTICAS
Fcil instalacin Excelente resistencia a abrasivos y agentes qumicos Contracciones longitudinales inferiores al 10% Temperatura de servicio de -508 +120 C Excelente hidrfugo Recubiertas en su interior con adhesivo derretible durante el proceso de contraccin

TUBO ABIERTO CON CREMALLERA DE CIERRE


Tipo Contraccin de A hasta A(*) mm. Espesor W(*) mm. Largo mm.

SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV SRMAHV

28-10 / 250 28-10 / 500 28-10 / 750 28-10 / 1000 28-10 / 1500 28-10 / 2000 43-12 / 250 43-12 / 500 43-12 / 750 43-12 / 1000 43-12 / 1500 43-12 / 2000 72-18 / 250 72-18 / 500 72-18 / 750 72-18 / 1000 72-18 / 1500 72-18 / 2000 93-26 / 250 93-26 / 500 93-26 / 750 93-26 / 1000 93-26 / 1500 93-26 / 2000

32 32 32 32 32 32 52 52 52 52 52 52 82 82 82 82 82 82 105 105 105 105 105 105 143 143 143 143 143

10 10 10 10 10 10 12 12 12 12 12 12 18 18 18 18 18 18 26 26 26 26 26 26 32 32 32 32 32

2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3

250 500 750 1.000 1.500 2.000 250 500 750 1.000 1.500 2.000 250 500 750 1.000 1.500 2.000 250 500 750 1.000 1.500 2.000 250 500 750 1.000 1.500

SRMAHV 125-32 / 250 SRMAHV 125-32 / 500 SRMAHV 125-32 / 750 SRMAHV 125-32 / 1000 SRMAHV 125-32 / 1500 A = A(*) = W(*) = Dmetro inicial. Dimetro con traccin libre. Espesor de la pared con adhesivo.

www.es.pirelli.com

102

DELEGACIONES COMERCIALES
BARCELONA Rambla Pirelli, 2. Apartado de Correos, 1 08800 VILANOVA I LA GELTR (Barcelona) Telfono 93 811 60 16 / 902 14 60 00 Fax 93 811 60 17 LA CORUA Novoa Santos, 21. 15006 LA CORUA Telfonos 981 13 87 35 / 981 13 87 36 / 902 14 60 00 Fax 981 13 87 50 PORTUGAL R. Nosa Senhora de Ftima, 424, 1 D. 4050 PORTO PORTUGAL Telfono 00 (351) (2) 609 77 77 Fax 00 (351) (2) 609 78 31 BILBAO Coln de Larretegui, 45, 1 dcha. 48011 BILBAO Telfono 94 424 45 80 / 902 14 60 00 Fax 94 424 45 88 MADRID Conde de Pealver, 38, 5 planta. 28006 MADRID Telfono 91 402 06 68 / 902 14 60 00 Fax 91 402 78 67 SEVILLA Carlos de Cepeda, 2 Planta 2, mdulo 4. 41005 SEVILLA Telfono 95 463 70 18 / 902 14 60 00 Fax 95 463 60 25 CANARIAS frica, 2. 35212 LAS HUESAS TELDE (Gran Canaria) Telfono 928 69 47 54 Fax 928 69 47 66 OVIEDO Campomanes, 26, 4 D. 33008 OVIEDO Telfono 98 520 35 73 / 902 14 60 00 Fax 98 520 28 40 VALENCIA Edificio Trevi. Fontanares, 51, 5 C 46014 VALENCIA Telfono 96 357 12 13 / 902 14 60 00 Fax 96 357 14 12 GRANADA Sederos, 2, 5 A. 18005 GRANADA Telfono 958 52 38 92 / 902 14 60 00 Fax 958 26 54 71

VENTA TELEFONICA Rambla Pirelli, 2 Apartado de Correos, 1 08800 VILANOVA I LA GELTR (Barcelona) Telfono 902 14 60 06 Fax 93 811 60 01

OFICINA COMERCIAL Rambla Pirelli, 2 Apartado de Correos, 1 08800 VILANOVA I LA GELTR (Barcelona) Telfono 93 811 60 00 Fax 93 811 60 01