LAB. No.: TR-0212-25168-1 Date: March 9, 2012 CUSTOMER/CLIENT: Holcim Philippines Inc. PROJECT: For Info.

KIND OF MATERIALS: River Sand SAMPLE I.D.: River Sand SOURCE: Viking SAMPLED/SUBMITTED BY: D. J. Alladin TEST REQUIRED: Quality Test

DATE SUBMITTED: February 25, 2012

LABORATORY TEST REPORT ON AGGREGATES RESULTS C. UNIT WEIGHT, ASTM C-29/AASHTO T-19 3 KG/M ASTM C-136 SIEVE SIZE RESULTS SPECS LOOSE, SSD mm (inch) RODDED, SSD 75.00 (3") LOOSE, DRY 63.00 (2 1/2) RODDED, DRY 50.00 (2") D. ABRASION LOSS, % 38.10 (1 1/2) ASTM C-131/AASHTO T-96 25.00 (1") E. MORTAR STRENGTH, % 19.00 (3/4) ASTM C-87/AASHTO T-71 12.50 (1/2) F. SOUNDNESS LOSS, % 9.50 (3/8) 100 100 ASTM C-88/AASHTO T-104 4.75 (#4) 98 95 - 100 G. MOISTURE CONTENT, % 2.36 (#8) 75 ASTM C-566/AASHTO T-225 2.00 (#10) H. SAND EQUIVALENT TEST, % 1.18 (#16) 61 45 - 80 ASTM C-2419 0.600 (#30) 39 I. ORGANIC IMPURITIES FLAKINESS INDEX 0.425 (#40) ASTM C-40 0.30 (#50) 16 5 - 30 J. WASH LOSS ON #200 SIEVE, % 0.15 (#100) 5 0 - 10 ASTM C-117 0.075 (#200) 1 0-3 K. CLAY LUMPS AND FRIABLE B. SPECIFIC GRAVITY, ASTM C-128 PARTICLES,% ASTM C-142 ASTM C-128/C-127;AASHTO T-84/T-85 L. FINENESS MODULUS RESULTS M. FRACTURED FACE BULK DRY 2.301 ASTM D-5821 SSD 2.382 N. SULPHATE CONTENT,% FLAKINESS INDEX APPARENT 2.503 BS - 812 ABSORPTION, % 3.514 O. ELONGATION INDEX BS - 812 REMARKS: This report is the results of test performed on the samples submitted. Advanced copy only. Tested by: A. GRADING ANALYSIS SPECS

1510 1557 1459 1504 98.0 4.61 3.06 40.0 Max. 95.00 Min. 12.00 Max.

T.S. Husmalaga Jr. Lab. Technician