www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: Specifier's comments: Page: Project: Sub-Project I Pos. No.

: Date:

PROFIS Anchor 2.1.1


1

-|-

12/19/2010

1. Input data

Anchor type and diameter: Effective embedment depth: Material: Evaluation Service Report:: Issued I Valid: Proof: Stand-off installation: Anchor plate: Profile Base material: Installation: Reinforcement:

HIT-RE 500 + HIT-V-HCR, M20 h ef,opti = 325 mm (hef,limit = 400 mm) HCR -|design method Engineering judgement SOFA BOND - based on ETAG BOND testing e b = 0 mm (no stand-off); t = 20 mm lx x l y x t = 450 x 450 x 20 mm (Recommended plate thickness: not calculated) Advance UKC; (L x W x T x FT) = 308 mm x 305 mm x 15 mm x 15 mm uncracked concrete , C40/50, fcc = 50.00 N/mm; h = 10000 mm, Temp. short/long: 0/0C hammer drilled hole, installation condition: dry no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm) no longitudinal edge reinforcement

Geometry [mm] y z

x 450 t=20 h ef =325 x 450 h = 10000

3 350

2 lx = 450 350

Loading [kN, kNm] Resulting loads Design loads (Load case 1) N Vx Vy Mx My Mz -340.000 0.000 0.000 160.740 0.000 0.000

Eccentricity (structural section) [mm] e x = 0; e y = 0

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.1.1


2

-|-

12/19/2010

2. Load case/Resulting anchor forces


Load case (Design loads): Anchor reactions [kN] Tension force: (+Tension, -Compression) Tension Anchor 1 2 3 4 Tension force 0.000 0.000 129.000 129.000 Shear force 0.000 0.000 0.000 0.000 Shear force x 0.000 0.000 0.000 0.000 Shear force y 0.000 0.000 0.000 0.000 x max. concrete compressive strain []: 0.94 max. concrete compressive stress [N/mm]: 28.29 resulting tension force in (x/y)=(0/175) [kN]: 258.100 resulting compression force in (x/y)=(0/-194) [kN]: 598.100 1 3 y 4

Compression

3. Tension load (EOTA TR 029, Section 5.2.2)


Proof Steel Strength* Combined pullout-concrete cone failure** Concrete Breakout Strength** Splitting failure** 258.074 N/A 270.784 N/A 95 N/A OK N/A Load [kN] 129.037 258.074 Capacity [kN] 130.667 259.773 Utilization bN [%] 99 99 Status OK OK

* anchor having the highest loading **anchor group (anchors in tension) Steel Strength NRk,s [kN] 196.000 g M,s 1.500 NRd,s [kN] 130.667 NSd [kN] 129.037

Combined pullout-concrete cone failure Ap,N [mm ] 517990 yc 1.072 e c1,N [mm] 0 NRk,p [kN] 328.298
0 2

Ap,N [mm ] 320000 t Rk,ucr [N/mm ] 16.08 y ec1,Np 1.000 NRk,p [kN] 545.524
2

t Rk,ucr,25 [N/mm ] 15.00 k 3.200 e c2,N [mm] 0 g M,p 2.100

s cr,Np [mm] 566 y g,Np 1.124 y ec2,Np 1.000 NRd,p [kN] 259.773
0

c cr,Np [mm] 283 y g,Np 1.027 y s,Np 1.000 NSd [kN] 258.074

c [mm] 10000

y re,Np 1.000

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.1.1


3

-|-

12/19/2010

Concrete Breakout Strength Ac,N [mm ] 1291875 e c1,N [mm] 0 NRk,c [kN] 418.438
0 2

Ac,N [mm ] 950625 y ec1,N 1.000 g M,c 2.100

c cr,N [mm] 488 e c2,N [mm] 0 NRd,c [kN] 270.784

s cr,N [mm] 975 y ec2,N 1.000 NSd [kN] 258.074 y s,N 1.000 y re,N 1.000 k1 10.100

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.1.1


4

-|-

12/19/2010

4. Shear load (EOTA TR 029, Section 5.2.3)


Proof Steel Strength (without lever arm)* Steel failure (with lever arm)* Pryout Strength** Concrete edge failure in direction** * anchor having the highest loading **anchor group (relevant anchors) Load [kN] N/A N/A N/A N/A Capacity [kN] N/A N/A N/A N/A Utilization bV [%] N/A N/A N/A N/A Status N/A N/A N/A N/A

5. Displacements
The displacement of the highest loaded anchor should be calculated according to the relevant approval under the effect of the following characteristic loads. NSk VSk = = 95.580 [kN] 0.000 [kN]

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

6. Warnings
The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means. The compliance with current standards (e.g. EC3) is the responsibility of the user An SLS-check is not performed for SOFA and has to be provided by the user! Characteristic bond resistances depend on short- and long-term temperatures. Please contact Hilti to check feasibility of HIT-V rod supply. Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7! The anchor plate is assumed to be sufficiently stiff in order to be not deformed when subjected to the actions! The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger diameters of the clearance hole see Chapter 1.1. of EOTA TR029!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.1.1


5

-|-

12/19/2010

7. Installation data
Anchor plate, steel: Anchor type and diameter: HIT-RE 500 + HIT-V-HCR, M20 Profile: Advance UKC, 308 mm x 305 mm x 15 mm x 15 mm Installation torque: 0.150 kNm Hole diameter in the fixture: df = 22 mm Hole diameter in the base material: 24 mm Plate thickness (input): 20 mm Hole depth in the base material: 325 mm Recommended plate thickness: not calculated Minimum thickness of the base material: 373 mm Cleaning: Premium cleaning of the drilled hole is required Annular gap must be removed by e.g. filling the holes with mortar or welding the anchors to the anchor plate!

4 225.0

50.0

1 50.0 225.0 225.0

2 50.0

Coordinates Anchor [mm] Anchor x y 1 -175 -175 2 175 -175 3 -175 175 4 175 175

c -x -

c +x -

c -y -

c +y -

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

50.0

225.0