Online Valve Diagnostics

Valve: Trial Balikpapan


Tag: CV255 Descriptor: Message: Mfg ID: Dresser(0x65) Device Type: 0xCA DeviceID: 0xFFAB4011 Comment:

Valve Configuration Information


Air Action: ATO Characterization: Linear Pressure Units: psi Signal Range: 4.00 - 20.00 Spring Range: 3.000 - 15.000

Test: 4/13/2012 8:57:14 AM


Computed Exceptions found

Test Summary
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Error = 0.07 % Ave. Sample Time = 0.62 sec Offset = 0.03 % Max speed up not computed Max speed down not computed Lag = 7.32 sec FAIL Cycles/Min = 0.00 Overshoot = 1.00 T86 = 0.90 sec Friction = 0.17 psi Friction% = 1.41 % Friction(Position) not computed Spring Range Low = 8.65 psi FAIL Spring Range High= 20.65 psi Possible Causes of Exceptions Possible bad positioner tuning Possible air supply problem Possible air leak Possible packing damage/loss Possible stem wear Possible process condition change Possible actuator spring/diaphragm problem

Trend
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM

Error - Offset
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Error = 0.07 % Ave. Sample Time = 0.62 sec Offset = 0.03 % Max speed up not computed Max speed down not computed

Lag - Cycles
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Lag = 7.32 sec Cycles/Min = 0.00

Step Response
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Overshoot = 1.00 T86 = 0.90 sec

Friction
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Friction = 0.17 psi Friction% = 1.41 % Friction(from Position) = 0.00 % Spring Range Low = 8.65 psi Spring Range Low = 20.65 psi