Test Summary
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Error = 0.07 % Ave. Sample Time = 0.62 sec Offset = 0.03 % Max speed up not computed Max speed down not computed Lag = 7.32 sec FAIL Cycles/Min = 0.00 Overshoot = 1.00 T86 = 0.90 sec Friction = 0.17 psi Friction% = 1.41 % Friction(Position) not computed Spring Range Low = 8.65 psi FAIL Spring Range High= 20.65 psi Possible Causes of Exceptions Possible bad positioner tuning Possible air supply problem Possible air leak Possible packing damage/loss Possible stem wear Possible process condition change Possible actuator spring/diaphragm problem
Trend
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM
Error - Offset
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Error = 0.07 % Ave. Sample Time = 0.62 sec Offset = 0.03 % Max speed up not computed Max speed down not computed
Lag - Cycles
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Lag = 7.32 sec Cycles/Min = 0.00
Step Response
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Overshoot = 1.00 T86 = 0.90 sec
Friction
Valve: Trial Balikpapan Test: 4/13/2012 8:57:14 AM Friction = 0.17 psi Friction% = 1.41 % Friction(from Position) = 0.00 % Spring Range Low = 8.65 psi Spring Range Low = 20.65 psi