This design test report records the results of laboratory tests made on the Ohio Brass Hi*Lite XL Suspension Insulators. Test performed in accordance with IEC Standard 1109, clause 5 and Annex C. The Hi*Lite XL Suspension Insulators meet all applicable requirements of these standards.
John Sakich
Engineering Manager
M.G. Comber
V.P.-Engineering
Customer Service 210 N. Allen St. Centralia, MO 65240 Phone 573-682-5521 Fax 573-682-8714
NOTE: Because Ohio Brass has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.
Printed in U.S.A.
EU1473-H
Test Report
Testing Services
AT-99/000630
p. 1
Test Report
Testing Services
AT-99/000630
p. 2
Test Report
Testing Services
AT-99/000630
p.
Test Report
Testing Services
AT-99/000630
p. 4
Test Report
Testing Services
AT-99/000630
p. 5
Test Report
Testing Services
AT-99/000630
p. 6
Test Report
Testing Services
AT-99/000630
p. 7
Test Report
Testing Services
AT-99/000630
p. 8
Test Report
Testing Services
AT-99/000630
p. 9
Test Report
Testing Services
AT-99/000630
p. 10
Test Report
Testing Services
AT-99/000630
p. 11
Test Report
Testing Services
AT-99/000630
p. 12
Test Report
Testing Services
AT-99/000630
p. 13
Test Report
Testing Services
AT-99/000630
p. 14
Test Report
Testing Services
AT-99/000630
p. 15
Test Report
Testing Services
AT-99/000630
p. 16
Test Report
Testing Services
AT-99/000630
p. 17
Test Report
Testing Services
AT-99/000630
p. 18
Test Report
Testing Services
AT-99/000630
p. 19
Test Report
Testing Services
AT-99/000630
p. 20
Test Report
Testing Services
AT-99/000630
p. 21
Test Report
Testing Services
AT-99/000630
p. 22
Test Report
Testing Services
AT-99/000630
p. 23
Test Report
Testing Services
AT-99/000630
p. 24