CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

ABB Contactors:
Capacitor switching Contactors types A, UA and UA-R

A1

A1

A1

A2

A2

A2

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Why the capacitors need ? In factories the load is mainly constituted of motors The resulting characteristic is inductive
Solution = Capacitors

pa p

n re

Po

er w

L I2 Inductive Power

- I2/C
we nt Po re Appa r

Active Power

Active Power

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Comparison

Resistance

Motor

Capacitor

In

In

In

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Single step capacitor

30 times In

In

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Multi steps capacitor bank

> 100 times In

In

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Contactor sizing: Thermal current + peak current

Thermal current Up to 30% for harmonics and voltage fluctuations on mains Up to 15% for tolerances on capacitor power Contactor have to support Ith

Ith = 1.3 x 1.15 x Inc = 1.5 Inc

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
ABB contactor range

Current peak 30 In 100 In > 100 In

Contactor types A9 ... EH 800 UA16 ... UA110 U16-R UA75-R

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

A Contactors
Standard Contactors

kvar: 400V, 50/60 Hz, 40C


11 A12 12.5 A16 19 22 26 38 43 48 60 70 A26 A30 A40 A50 A63 A75 A95 A110 4 4

Max permissible peak current (kA) 0.7 1 1.6 1.9 2.1 2.3 2.5 2.6
( Higher peak needs additional self inductance )
CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Contactors EH
Standard Contactors

kvar :
90

400V, 50/60 Hz, 40C 105 125 140 160 200 280 350 390

EH145 EH175 EH210 EH260 EH300 EH370 EH550 EH700 EH800

Max permissible peak current (kA)


4 5 5 8 8 10 10 12 12
(Higher peak needs additional self inductance )

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor Contactors UA
Max. peak current up to 100 times r.m.s

kvar : 400V, 50/60 Hz, 40C


12.5 20 27,5 33 45 50 60 74 UA16 UA26 UA30 UA50 UA63 UA75 UA95 UA110 Max permissible peak current (kA) (Ue<500V) 1.8 3 3,5 5 5.5 6 9.3
(Higher peak needs additional self inductance )

10.5

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor Contactors UA-R


No prospective current peak limits

kvar : 400V, 50/60 Hz, 40C


12.5 22 30 40 50 60
UA16..-R UA26..-R UA30..-R UA50..-R UA63..-R UA75..-R
Used without additional inductance

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Contactors type UA-R

Making
R

Breaking
R

A1 A2
R

A1 A2
R

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
How to select the contactor ? According to : Capacitor power (Kvar) Current peak and with the help of the ABB tables

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Example of application Three -phase capacitor: 22 kVar (22 000 Var) 400V (50Hz) 40C Ambient temp. around the contactor: How to select the right contactor?

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Standard Contactors type A
Power ( kVar ) 400 V 50/60 Hz 40 C 55 C 70 C
11 12.5 19 22 26 38 43 48 60 70 11 12.5 19 22 26 38 43 48 60 70 9.5 10 15 18.5 20 34 39 41 53 60 Peak current max ( KA ) 0.7 1 1.6 1.9 2.1 2.3 2.5 2.6 4 4

Types
A 12 A 16 A 26 A 30 A 40 A 50 A 63 A 75 A 95 A110

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Standard Contactors type EH
40 C Power kVar 400 V 50/60 Hz 55 C 70 C Peak current max. ( KA ) Types

90 105 125 140 160 200 260 350 390

90 105 125 140 160 200 260 350 370

74 78 99 130 150 185 255 332 332

4 5 5 8 8 10 10 12 12

EH 145 EH 175 EH 210 EH 260 EH 300 EH 370 EH 550 EH 700 EH 800

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
Contactors type UA
Power kVar 400 V 50/60 Hz 40 C 55 C 70 C
20 27.5 33 45 50 60 74 18.5 27.5 33 43 50 60 70 14.5 19 32 37 39 50 65
Peak current max. ( KA )

Types
UA 26 UA 30 UA 50 UA 63 UA 75 UA 95 UA110

3 3.5 5 5.5 6 9.3 10.5

Designed for peak currents up to 100 times In


CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

Capacitor switching
Contactors type UA-R
Power ( kVar ) 400 V 50/60 Hz 40 C
12.5 22 30 40 50 60
Peak current max. ( KA )

Types
UA 16R UA 26R UA 30R UA 50R UA 63R UA 75R

55 C
12.5 20 27.5 40 45 50

70 C
10 15.5 19.5 35 39 41

No Limitation

Designed for peak currents up to no limitation


CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

Capacitor switching
1st Case:
22 kVar ,Three-phase 400V 50Hz, temp. 40C Peak current : 1.7 kA

Selection: A 30 - Standard contactor - This contactor is rated 22 kVar - It can accept up to = 1.9 kA Peak current.

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
2nd Case:
22 kVar ,Three-phase 400V 50Hz, temp. 40C Peak current : 2.5 kA Selection 1: A 63 - This contactor can accept up to 2.5 kA peak current. - It is rated 43 kVar Selection 2: A 30 + addition of inductance's by user - Peak current must be limited to 1.9 kA. - Contactor rating 22 kVar Selection 3: UA 30 - Max. peak current 3.5 kA. - Contactor rating 27.5 kVar

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

Capacitor switching
3rd Case:
22 kVar ,Three-phase 400V 50Hz, temp. 40C Peak current : 4.5 kA Selection 1: EH 175

- This contactor can accept up to 5 kA peak current. - It is rated 105 kVar Selection 2: A 30 + addition of inductance's by user - Max. peak current must be limited to 1.9 kA. - Contactor rating 22 kVar Selection 3: UA 30 + addition of inductance's by user - Max. peak current must be limited to 3.5 kA. - Contactor rating 27.5 kVar Selection 2: UA 26 -R - This contactor is rated 22 kVar. - No limit on accepted prospective peak current

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Three possible cases : - Three-phase capacitor bank with a single step - Three-phase capacitor bank with several steps of identical power - Three-phase capacitor bank with several steps of different power Two possible ways :

- Calculation - Measurement
CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


1) Single step - Calculation

=
k1 : Constant = 1457 (50 Hz) or 1330 (60 Hz) Q : Capacitor Power (kvar) Known Lt : Transformer inductance per phase (H)

k1

Q L +t L

Known Calculation on next picture

L : Sum of Inductance between the transformer and the capacitor (H) w (Circuit-breaker, Contactor, Electrical connection or fuses)
CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Transformer inductance per phase

U Lt = k 3S
: Short-circuit voltage (%) U : Phase to phase operating voltage (V) k2 : 31,4 (If F=50 Hz) or 37,68 (If F=60 Hz) S : Transformer power (kVA)
All of these datas are written on the transformer

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Inductance between the transformer and the capacitor 1) Calculation of am/d
Single phase installation or am = a d = Conductor diameter (mm) Example for a U1000 RO2V cable : am = 1,26 a Three-phase delta installation Three-phase adjacent installation

d a

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Inductance between the transformer and the capacitor

2) Selection of the linear coefficient k4 . see on the curve


k4

3) Le = Cable length * k4 (mm)

Am/d
CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Inductance between the transformer and the capacitor

Circuit-breaker inductance (Lb) = 0,5 H

Fuses inductance (Lf) = 0,4 H

Contactor inductance (Lc) = 0,3 H


Total inductance

L = Le + Lb + Lc or L = Le + Lf + Lc
ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

How to define the current peak ?


2) Several steps of identical power - Calculation

= k1

n-1 n
Known Known

Qn Ln

k1 : Constant = 1457 (50 Hz) or 1330 (60 Hz) n : Number of capacitor steps Known Qn = Q1 = Q2 = Q... : Power of a step (kvar)

Ln = L1 = L2 = L... : Inductance by phase of a step in H


CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


3) Several steps of different power - Calculation

To calculate the current peak in several steps of different power, just take a look on page 9, 18 and 19 of the ABB Application Guide.

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Exercise I: Find the current peak of this installation :
Transformer : 2000 kVA 380 V Short-circuit voltage = 6% 50 Hz

15 meters of delta cables 15 m Conductive cross-sectional area = 10 mm

Capacitor = 20 kvar
CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Transformer : 2000 kVA 380 V 50 Hz

Short-circuit voltage = 6%

6 * 380 Lt = = 31,4 * 2000 k3 S


Transformer inductance :

Lt = 13.8 H
ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

How to define the current peak ?


Looking on the chart :
Conductive cross-sectionnal area = 10 mm (15 meters length)

Am = 1.26 a = 1.26 * 9.2 = 11.592 mm


0.41 H

Am d

11.592 3.9

Lc = 0.41 * 15 6.1 H

L = 0.5 + 0.3 + 6.1 = 6.9 H


Contactor inductance

3
CONTACTORES INDUSTRIALES

Circuit-breaker inductance

ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


So the current peak is :

= k1

Q Lt + L 20 13.8 + 6.9

= 1457

= 1.43 kA
CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Exercise II : Find the current peak of the same installation but with 4 steps :
Transformer : 2000 kVA 380 V Short-circuit voltage = 6% 50 Hz

15 m

1m

1 meter of delta cables between the capacitor and the busbar Conductive cross-sectional area = 10 mm Capacitor = 20 kvar 4 steps

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Looking on the chart :
Conductive cross-sectionnal area = 10 mm (1 meter length)

Am = 1.26 a = 1.26 * 9.2 = 11.592 mm


0.41 H

Am d

11.592 3.9

Lc = 0.41 * 1 = 0.41 H

L = 0.4 + 0.3 +0.41 = 1.11 H

3
CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Current peak for the last closed contactor :

= k1

n-1 n

Qn Ln 20 1.11

4-1 = 1457 * 4

= 4.64 kA
CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


4) Single step / several step - Measurement
The peak measurement must be done on 220 operating cycles to be sure to measure the highest current peak. Required equipment : (Able to measure a I peak of 1 or 2 ms) oscilloscope (10 Mhz Frequency, 12 bytes resolution) Three current sensors (50 kHz frequency, 2000A nominal current, 10 000 A max current peak) ABB rf : ES 2000 - 9725 ES 2000 F ES 2000 S depends on secondary connexion c

The measurement is made before the contactor


CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

How to define the current peak ?


Calculation or measurement
Calculation Measurement

All parameters of the installation must be known

The installation must be made b before. It s only for a checking o or a confirmation of the cccontactor choice

Warning : If the current peak is too difficult to define, the best solution is UA-R contactor
CONTACTORES INDUSTRIALES ING. HUBER MURILLO MANRIQUE

CONTACTORES Y FILTROS NORMALIZADOS

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

HM

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE

CONTACTORES INDUSTRIALES

ING. HUBER MURILLO MANRIQUE