You are on page 1of 6

April 2001

Product Flier PF34.2:2500

Level-TrolR Pneumatic Liquid Level Controllers and Transmitters

W3120-2/IL

W3121-3/IL

D Proportional, Proportional-plus-Reset, Differential Gap (On/Off) Control Mode or Transmitter Operation D Simple Dial Controls for Set Point, Proportional Band, Reset, Zero, and Span Adjustments D The Displacer Sensor Measures Changes in Liquid Level, Specific Gravity, or Interface Level, and the Controller or Transmitter Sends a Pneumatic Signal that is Proportional to the Changes D The 249 Series Displacer is Contained in a Rugged Cage for Mounting on the Side of a Tank, or the Displacer can be Suspended in a Tank without a Cage D Tank Flanged Connections to 8-Inch Size

D102776X412

Product Flier PF34.2:2500


General Specifications
Proportional pneumatic controller Proportional-plus-reset pneumatic controller Controller and Transmitter Selections (Also Refer to Sensor Tables) Proportional-plus reset pneumatic controller with anti-reset windup Proportional pneumatic transmitter Differential gap (on-off) pneumatic controller with full adjustment Differential gap (on-off) pneumatic controller with limited adjustment Fluid level or fluid interface level Process Sensor Range (Input Signal) Fluid density Proportional band adjustable for full output pressure change over 10 to 100% of displacer length: Type 2500 Proportional band adjustable for full output change over 20 to 200% of displacer length: Type 2502 Proportional band adjustable for full output change over 20 to 200% of displacer length: Type 2502F Span adjustable for full output change over 20 to 100% of displacer length: Type 2500T Differential gap adjustable for full output change over 0 to 100% of displacer length: Type 2500S Differential gap adjustable for full output change over 25 to 40% of displacer length (adjustment will vary based on displacer length, specific gravity and supply pressure): Type 2503 From 0 to 100 percent of displacer lengthstandard lengths for all sensors are 356 mm (14 inches) or 813 mm (32 inches); other lengths available depending on sensor construction From 0 to 100 percent of displacement force change obtained with given displacer volumestandard volumes are 980 cm3 (60 inches3) for Types 249C and 249CP sensors or 1640 cm3 (100 inches3) for most other sensors; other volumes available depending upon sensor construction Type 2503 and 2503R: Specific gravity range, 0.25 to 1.10 All other types: Specific gravity range, 0.20 to 1.10 Type 2503 and 2503R: Minimum change in specific gravity, 0.25 All other types: Minimum change in specific gravity, 0.20 Continuously adjustable to position control point or differential gap of less than 100 percent anywhere within displacer length (fluid or interface level) or displacement force change (density) Continuously adjustable to position span of less than 100 percent anywhere within displacer length (fluid or interface level) or displacement force change (density) Continuously adjustable from 0.005 to over 0.9 minutes per repeat (from 200 to under 1.1 repeats per minute) Continuously adjustable from 0.14 to 0.48 bar or 2 to 7 psi differential to relieve excessive difference between proportional and reset pressures 0.2 to 1.0 or 0.4 to 2.0 bar 0 and 1.4 or 0 and 2.0 bar 0 and full supply pressure Stainless steel heat insulator assembly; assembly Jerguson gauges; Mechanical level indicator 3 to 15 or 6 to 30 psig 0 and 15 or 0 and 30 psig

Allowable Specific Gravity (Standard)

Fluid level or fluid interface level Fluid density

Set Point Adjustment (Controllers only)

Zero Adjustment (Transmitters only) Reset Adjustment (Proportional-Plus-Reset Controllers Only) Anti-Reset Differential Relief (Type 2502F and 2502FR Controllers Only) Output Signal--Direct (Increasing Level Increases O tp t) or Output) Reverse Action Proportional or reset controllers and transmitters Differential gap controllers with full adjustment Differential gap controllers with limited adjustment

Options O

Performance
Independent Linearity (Transmitters Only) Hysteresis Repeatability Deadband (Except Differential Gap Controllers) Typical Frequency Response 1 percent of output pressure change at span of 100 percent 0.6 percent of output pressure change at 100 percent of proportional band, differential gap, or span 0.2 percent of displacer length or displacement force change 0.05 percent of proportional band or span 4 Hz and 90-degree phase shift at 100 percent of proportional band, diferential gap, or span with output pipe to typical instrument bellows using 6.1 meters or 20 feet of 6.3 mm or 1/4-inch tubing

Product Flier PF34.2:2500


Supply Pressure
OUTPUT SIGNAL NORMAL OPERATING SUPPLY PRESSURE Bar 1.4 2.4 Psig 3 to 15 or 0 and 20 for on-off 6 to 30 or 0 and 35 for on-off 20 35 45 45 4.2 7 MAXIMUM (TO PREVENT DAMAGE TO PARTS) AIR CONSUMPTION AT NORMAL OPERATING SUPPLY PRESSURE, Nm3/H Minimum 3.1 3.1 0.11 0.19 SCFH 27 42 Maximum 0.72 1.1

0.2 to 1.0 or 0 and 1.4 for on-off 0.4 to 2.0 or 0 and 2.4 for on-off

Temperatures
Temperature Temperat re Type or Material Standard 2500 Series Ambient High-temperature 2500 Series Cast iron sensor parts Steel sensor parts Stainless steel sensor parts Process N05500 torque tube Graphite/stainless steel gaskets Monel/PTFE gaskets Temperature Capability _C 40 to 71 18 to 104 29 to 232 29 to 427 198 to 427 198 to 371 198 to 427 73 to 204 _F 40 to 160 0 to 219 20 to 450 20 to 801 324 to 801 324 to 700 325 to 800 100 to 400 For process temperatures rocess tem eratures below 29_C or 20_F and 29 C 20 F for guidance on the need for a heat insulator contact insulator, your Fisher sales office office. If the ambient dew point is oint higher than the process tem erature, temperature, ice might form and cause instrument malfunction and reduce insulator effectiveness. Notes

Some combinations of process and ambient temperatures within the above require Combination of ambient and an optional heat insulator to protect the instrument from high or low temperatures. process For example, an ambient temperature of 86_F or 30_C and a process temperature of 200_C or 392_F require a heat insulator.

W0656-1/IL

W0660-1/IL

Typical Controller

Cageless Sensor

W2141-1/IL

Caged Sensor

Product Flier PF34.2:2500


Materials
Part Sensor Type Sensor 249 Cage, head Cage head, and torque tube arm 249CP 249K, 249L, and 249N 249P and 249V Torque tube All except 249CP 249CP All except 249CP and 249L Dis lacer Displacer 249CP 249L Bolting All Cast iron CF8M (316 stainless steel) Steel Cast iron or steel N05500 (K-Monel) S31600 (316 stainless steel) S30400 (304 stainless steel) S31600 A91100F (solid aluminum) B7 steel studs or cap screws and 2H steel nuts Controller or Transmitter Bourdon tube or bellows Relay diaphragms Relay O-ring Gasketing Seal ring O-rings (and reset relief valve O-rings if used) Case Cover Brass, plus stainless steel 3-way valve for Type 2503 or 2503R controller Nitrile (standard) or polyacrylate (high-temperature) Nitrile Neoprene (standard) or rubber (high-temperature) Nitrile (standard) or fluoroelastomer (high-temperature) Aluminum Aluminum with glass gauge windows and nitrile cover gasket --For o tional materials and for parts optional arts not shown, contact y your Fisher sales office. l ffi Standard Material Notes

Sensor Sizes, Connections, and Ratings


Rating Connection Size Caged Displacers Class 125 or 250; cast iron PN 10/16, 25/40, or 63/100; steel PN 10/16 or 25/40; steel Class 600; steel Class 150, 300, or 600; steel Class 1500; steel Class 2500; steel Class 900; steel Class 150, 300, or 600; 316 stainless steel PN10/16, 25/40, or 63 (Ratings to PN 250 also available); steel or stainless steel Class 900 or 1500; steel or stainless steel Class 150 through 2500; steel or stainless steel Class 125 or 250; cast iron Class 150; steel Class 300 through 1500; steel Class 2500; steel Class 150; stainless steel Class 300, 600, or 900; stainless steel 1-1/2 or 2 inches 2 inches DN 40 DN 50 1-1/2 1 1/2 or 2 inches 1-1/2 or 2 inches 2 inches (if a top connection is specified, it will be 1-inch flanged) 1-1/2 or 2 inches 3 inches DN 100 4 inches 6 or 8 inches Side-Mounted Cageless Sensors 4 inches 4 inches 4 inches 4 inches 4 inches 4 inches Flat-face flanged Raised-face flanged or flat-face flanged Raised-face flanged or ring-type joint flanged Ring-type joint flanged Raised-face flanged or flat-face flanged Raised-face flanged or ring-type joint flanged 249V Screwed or flanged Flanged Flanged NPT or socket-welding ends Raised-face flanged or ring-type joint flanged Raised-face flanged or ring-type joint flanged Ring-type joint flanged Raised-face flanged or ring-type joint flanged Raised-face flanged Flanged Raised-face flanged or ring-type joint flanged Raised-face flanged 249P 249K 249L 249N 249CP 249BF 249 Connection Type Sensor Type Number

Top-Mounted Cageless Sensors

Product Flier PF34.2:2500


Displacer Lengths and Volumes
Sensor Type Number Caged Displacers 249 249BF, 249K, 249L, 249N Top-Mounted Cageless Sensors 249CP, 249P Side-Mounted Cageless Sensors 249V 356, 813, 1219, 1524, 1829, 2134, 2438, 2743, 3048 14, 32 48 60 72 84 96 14 32, 48, 60, 72, 84, 96, 108, 108 120 Ty e Type 249 CP: 983 All others: 1639 Ty e Type 249 CP: 60 All others: 100 mm 356 or 813 Displacer Length Inches 14 or 32 cm3 Displacer Volume Inches3

Connection Styles and Positions


TOP CONNECTION ALTERNATE POSITIONS FOR LEFTOR RIGHTHAND MOUNTING

UPPER SIDE CONNECTION

LEFTHAND MOUNTING (INSTRUMENT ON LEFT OF SENSOR WHEN VIEWED AS SHOWN)

TANK

APPROXIMATE DISPLACER LENGTH BOTTOM CONNECTION LOWER SIDE CONNECTION

LEFT

E0669 / IL

A6924/IL

Connection Types: Style 1 Top and bottom

Connection Locations: Example:

S = Screwed F = Flanged SW = Socket Welding Style 2 Style 3 Top and lower side Upper side and lower side

Style 4 Upper side and bottom

F-1 means flanged connections at the top and bottom of the cage.

Product Flier PF34.2:2500


For Further Information, Contact...
AUSTRIA Fisher-Rosemount Industrie - Zentrum No Sud Strae 2a, obj M29 A- 2351 Wr. Neudorf ) +43.2236.607 3 +43.2236.60744 BELGIUM Fisher-Rosemount De Kleetlaan 4 B-1831 Diegem ) +32.2.716.77.11 3 +32.2.725.83.00 GERMANY Fisher-Rosemount RobertBoschStrae 21 D-64625 Bensheim ) +49.6251.107340 3 +49.6251.67.442 GREECE TEVEX 4, Argyrokastrou Street GR-15235 Vrilissia-Athens ) +30.1.80.33.652 3 +30.1.80.33.819 HUNGARY Fisher-Rosemount Ersbet Kirlyn tja 1/c Hu- 1146 Budapest ) +36.1.462.40.00 3 +36.1.343.01.73 ITALY Fisher-Rosemount Via dell Artigianato 8/12 I-20053 Muggi (Mi) ) +39.39.2.278.0590 3 +39.39.2.270.2302 NETHERLANDS Fisher-Rosemount Patrijsweg 140 NL-2289 EZ Rijswijk ) +31.70.413.66.66 3 31.70.390.68.15 NORWAY SAAS SA Postboks 6500 Etterstad Grenseveien 95 N-0606 OSLO ) +47.23.19.30.00 3 +47.23.19.30.96 POLAND Fisher-Rosemount Ul.Konstruktorska 11 PL- 02673 Warszawa ) +48.22.54.85.200 3 +48.22.54.85.231 PORTUGAL Fisher-Rosemount Rua Alfredo da Silva 8 P-2720 Alfragide ) +351.01.471.28.850 3 +351.01.472.88.55 ROMANIA Fisher-Rosemount Romania 155 Calea Victoriei Street BL. D1, Sc.3 Ap.76 Sector 1 RO-71401 Bucharest ) +40.1.230.41.49 3 +40.1.230.05.01 SLOVAK Rep Fisher-Rosemount Hanulova 5/b SR- 84101 Bratislava ) +421.7.643.62.182 3 +421.7.642.87.245 SLOVENIA MIR Strmeckijeva 16 Sl-8270 Krsko ) +386.608.23.14.70 3 +386.608.23.14.71 SPAIN Fisher-Rosemount Ctra Fuencarral-Alcobendas Km 12.2; Edificio Auge 1 E-28049 Madrid ) +34.1.358.91.41 3 +34.1.358.91.45 : frspain@frco.com SWEDEN PEAB Ilanda Grd S - 65350 Karlstad ) +46.54.53.07.50 3 +46.54.53.18.51 SWITZERLAND Fisher-Rosemount Blegistr. 21 CH-6341 Baar ) +41.41.768.61.11 3 +41.41.761.87.40 TURKEY Fisher-Rosemount Kisikli Caddesi Basaran Ap. N_3 Kat2 81130 Altunizade TR- skdarIstanbul ) +90.216.492.40.42-46 3 +90.216.492.40.47 UKRAINE Fisher-Rosemount Tereschenkovskaya St. 13, Rm. 58 252004 Kiev ) +38.44.246.46.56 3 +38.44.246.46.58 UNITED KINGDOM and MIDDLE EAST Fisher-Rosemount Horsfield Way Bredbury Stockport SK6 2SU UK ) +44.161.406.8826 3 +44.161.406.8827 UZBEKISTAN Fisher-Rosemount Eski Juva Square Branch of Shayhantour of NBU, r 208 700 002 Tashkent ) +998.71.249.44.88 3 +998.71.249.44.89

BULGARIA Process Control 17, Mila Rodina Str. BG- 1408 Sofia ) +359.2.958.21.85 3 +359.2.958.21.85 CIS Fisher-Rosemount Malaya Trubetskaya Street 8 - 11th floor CIS-119881 Moscow ) +7.095.232.69.68 3 +7.095.232.69.70 CROATIA Fisher-Rosemount Tratinska 19 10000 Zagreb ) +385.1.309.42.20 3 +385.1.309.44.69 CZECH Rep Fisher-Rosemount Volsinch 75 Cz- 100 97 Praha 10 ) +420.2.810.026 66 3 +420.2.810.026.70 DENMARK Fisher-Rosemount Hejrevang 11 DK-3450 Allerd ) +45.48.17.03.33 3 +45.48.17.02.44 : fisher.rosemount.dk FINLAND Oy Valmet-Rosemount Sinimaentie 10B FIN - 02630 Espoo ) +358.9.523.500 3 +358.9.523.997 FRANCE and FRENCH SPEAKING AFRICA Fisher-Rosemount 2, Place Gustave Eiffel Silic 247 F- 94568 Rungis ) +33.01.49.79.73.00 3 +33.01.49.79.73.99

: WEB site: www.fisher.com

Fisher, Fisher-Rosemount, and Level-Trol are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc. All other marks are the property of their respective owners. E Fisher Controls International, Inc. 1997, 2001; All Rights Reserved

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

Fisher Marshalltown, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461
Printed in U.S.A. 6