PFISTERER

solutions for your network

History
1978: Introduction of MV-Connex, 24 kV - 36 kV - 52 kV 1988: HV-CONNEX Size 4, 72,5 kV 1994: HV-CONNEX Size 5S, 145 kV 1999: HV-CONNEX Size 6, 170 kV 2002: HV-CONNEX Size 6S, 245 kV 2006: Plug-In Outdoor Bushing Size 6, 170 kV 2007: Surge Arrester for HV CONNEX Size 4

HV-CONNEX Cable Termination Systems for high voltage networks

Motivation: Dry Type


GIS / Transfomer compartment completely enclosed at manufacturing site Connection without expensive gas or oil works on-site Quick Assembly Works at the transformer and assembly of the cable termination are completely independent

GIS or transformer compartment

Size Classification Size 4 Size 5-S Size 6 Size 6-S

Um IN
Cross Section *
Max. Diameter over conductor / insulation

72,5kV 2500A
1600 mm 50,4 mm / 75 mm

145kV 2500A
1600 mm 50,4 mm / 76 mm

170kV 2500A
2500 mm 64,9 mm / 110,5mm

245kV 2500A
2500 mm 64,9 mm / 110,5mm

*valid only, if values comply to max. diameter over insulation / max. diameter over conductor

Socket- The heart of the system

Transformer
Testing: IEC 60137 Dimensions: EN 50299

Cable Termination
Testing: IEC 60840 bzw. IEC 62076

GIS
Routine Test: IEC 62271-203 Type Test: IEC 60840 Iec 62076 Dimensions: IEC 62271-209

Examples of Usage Transformer

Further Transformer applications

HK Macau Siemens

Oberhasli Switzerland EBG

Irkutsk Russia

Examples of Usage GIS

HV - Cable Termination System Application switchgear

Pfisterer Connex Terminales enchufables hasta 245 kV


Aplicacines de GIS

Terminal convencional

Terminal enchufable Connex en seco

Routine Tests
Routine Test according to (EN50089 / DIN

EN 60137 / DIN EN 62271-203 / DIN EN 50089)


Visual Examination Meausurements Material Test Temperature Test (-40C 110C) Rated Power Frequency Voltage (460kV) Partial Discharge (< 5pC at 2*U0) Gas Tightness (Helium; < 4*10-7 bar cm/s) Pressure Test (2*design pressure 1min) X-Ray Test

Features of the Separable Connecting System


An interface for oil and gas insulated components A complete connection system for cables, overhead lines and surge arresters Prefabricated and routine tested components Quick and reliable assembly Rapid and simple disconnection in the event of faults Connection without expensive gas or oil works on-site Works at the transformer and assembly of the cable termination are independent of each other Worldwide References several thousand HV accessories in use worldwide tens of thousands for medium voltage

HV Connex Off Shore


Off Shore Version Optional available

Low Temperature Test


Accessories for temperatures down to -50C System Size 5-S Connector / Socket / dummy plug / bushing System Size 6 (test performed with limited values) Connector / Socket / dummy plug Accessories for temperature down to -25C Bushing Size 6