2x330MW TPP, Mundra SEZ

Attachment-2 to Doc.No.6785-EL-DSN-633-001

SIZING CALCULATION FOR EQUIPMENT EARTHING


S.No Equipment Main Earthing Grid 1 2 3 Buried in ground Embedded in Floor/Concrete Slabs Exposed Conductors Neutral Earthing 4 5 6 7 8 9 HV Neutral of Generator Transformer HV Neutral of Station Transformer NGR of Station Transformer NGR of Unit Auxiliary Transformer LV Neutral of Auxiliary Transformer LV Neutral of Lighting Transformer Enclosure Earthing Generator Transformer Station Transformer Unit Auxiliary Transformer 6.6 kV Switchgear 6.6 kV Motors LT Transformers LT Busducts LT PCC/PMCC LT MCC/DB LT ACB operated Motors Battery Charger /DCDB Local Starters Lighting Mast/Pole Cable Trays Control Panel Junction Boxes Push Button stations 3 Phase Receptacles Structural Steel Columns Steel pipe rack Isolated Phase Bus duct Isolated Phase Bus duct Fence/Gate LT Motors (Rating in kW) Upto 5.5 kW above 5.5kW & Up to 11 kW above 11kW & Up to 30 kW 31.5 31.5 0.2 0.2 50.0 20.0 1 1 1 1 1 1 496.44 496.44 3.152 3.152 788 315.2 16.0 16.0 16.0 16.0 16.0 16.0 50X10 50X10 25X3 25X3 75X12 50X8 32 mm dia. Rod 75 X10 mm Flat 50X10 mm Flat MS MS GS A B C Fuse Rating Earth fault current in kA, (I) Earth fault current Required Steel conductor size withstand duration, sec (t) in sq.mm (15.76 X I X sqrt(t) Required minimum Selected steel conductor conductor size, size Material sq.mm symbol No. of Used leads

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 30

32.0 50.0

31.5 31.5 0.2 0.2 0.2 50.0 50.0 50.0 50.0 50.0 25.0 3.5 5

1 1 1 1 0.2 1 1 1 0.5 0.2 0.5 0.01 0.01

496.44 496.44 3.15 3.15 1.41 788 788 788 557.2 352.4 278.6 5.5 7.9

31.5 31.5

1 1

496.44 496.44

16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0

50X10 50X10 25X3 25X3 25X3 75X12 75X12 75X12 75X8 50X8 50X6 8 swg 8 swg 50x6 25X6 8 swg 8 swg 25X6 50X6 50X6 50X10 Flat 50X10 Flat 25X6

GS GS

A A

2 2

31 32 33

25.0 50.0 100.0

3 5 11

0.01 0.01 0.01

4.7 7.9 17.3

16.0 16.0 16.0

8 swg 8 swg 25X6

PS / GS

2x330MW TPP, Mundra SEZ


Earth fault current in kA, (I) 20 22

Attachment-2 to Doc.No.6785-EL-DSN-633-001
Required minimum Selected steel conductor conductor size, size Material sq.mm 25X6 16.0 50X6 16.0

S.No 34 35

Equipment above 30kW & Up to 90 kW above 90kW & less than 160 kW

Fuse Rating 250.0 315.0

Earth fault current Required Steel conductor size withstand duration, sec (t) in sq.mm (15.76 X I X sqrt(t) 0.01 31.5 0.01 34.7

symbol No. of Used leads

PS / GS