70072-0129-07 02/2007
In This Document
VT Fuse Block Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 VTFB6Diagram....................................................... 2 VTFB6Specifications.................................................. 3 VTFB6Dimensions .................................................... 3 CT Shorting Block Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CTSB10Diagram...................................................... 4 CTSB10Specifications ................................................. 5 CTSB10Dimensions ................................................... 5 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 SinglePhase.......................................................... 7 4WireWye,3ElementDirect........................................... 8 4WireWye,3Element,3VT ............................................ 9 4WireWye,2Element,2VT......................................... 10 3WireSolidGroundedWye,3ElementDirect ........................... 11 3WireDelta,2ElementDirect(ION7500/ION7600) .................... 12 3WireDelta,Direct(ION7300series).................................... 13 3WireDelta,2Element,2VT&3CT .................................. 14 3WireDelta,2Element,2VT&2CT ................................... 15 Additional Information YourmetersInstallationGuide
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 2007 Schneider Electric. All rights reserved. www.powerlogic.com
VTFB-6 Diagram
DIN Rail End Bracket
NOTE
Individual components may not be exactly as shown.
Page 2
VTFB-6 Specifications
VTFB-6 Specifications
Fused Terminal Block
Description
Mounting Fuse Nominal voltage rating Nominal current rating Conductor size Standards compliance
Specification
35 mm DIN rail Midget fuse (10.3 x 38 mm) 600 V 30 A 14 to 8 AWG UL and CSA approved
Terminal Block
Description
Mounting Bridging method Nominal voltage rating Nominal current rating Conductor size Standards compliance
Specification
35 mm DIN rail Bridging via the 3-way Fixed bridge 600 V 30 A 22 to 10 AWG UL and CSA approved
VTFB-6 Dimensions
Thedimensionsindicatedbelowareapproximate.Theactualpartmaymeasure differentlythanindicated,dependingonthemanufacturer.
DEPTH CLEARANCE 85mm
Page 3
CTSB-10 Diagram
DIN Rail End Bracket
End Bracket
NOTE
Individual components may not be exactly as shown.
Page 4
CTSB-10 Specifications
CTSB-10 Specifications
Switchable Terminal Block
Description
Mounting
Specification
35 mm DIN rail Sliding link to open CT secondary circuit for test/maintenance purposes. Shorting mechanism to short CT secondary circuit for test/maintenance purposes. 300 V 45 A 20 to 8 AWG UL and CSA approved
Nominal voltage rating Nominal current rating Conductor size Standards compliance
Terminal Block
Description
Mounting Bridging method Nominal voltage rating Nominal current rating Conductor size Standards compliance
Specification
35 mm DIN rail Bridging via the 4-way Fixed bridge. 600 V 45 A 20 to 8 AWG UL and CSA approved
CTSB-10 Dimensions
Thedimensionsindicatedbelowareapproximate.Theactualpartmaymeasure differentlythanindicated,dependingonthemanufacturer.
Page 5
CTSB-10 Dimensions
Page 6
Wiring Diagrams
Wiring Diagrams
DANGER
Only licensed electricians who have appropriate training and experience with high voltage and current devices should install and wire the terminal block assemblies.
Single-Phase
Page 7
Page 8
Page 9
Page 10
Page 11
Page 12
Page 13
Page 14
Page 15