SIMEAS P Power Meter

POWER QUALITY Catalog SR 10.2.6 1999

SIMEAS P

Contents

Economical alternative to traditional analog meters Fast and simple DINcompatible installation with single panel cutout and minimal wiring requirements Firmware upgradable via infrared port Bright, backlit LCD front panel display shows four measurements at once Security options include password protection Utilizes standard PROFIBUS-DP communications protocol for compatibility and ease of measurement Non-volatile memory contains integrated battery backup systems Provides a large selection of digitally accurate power, energy, and demand measurements in a single package Small, space-saving case size makes the SIMEAS P the ideal choice for OEM switchboards and switchgears

Meets UL, CSA, IEC 1010-1, FCC, and CE standards. Conforms to ISO 9002 Eight separate screens accessible on the front panel display for ease of measurement PT scales, CT scales, demand period and other setup parameters are all easily programmed from the front panel Harmonics analyzers capable of calculating up to the 15th harmonic Non-volatile memory (NVRAM), battery life is rated for 35 years under normal conditions.

Features Communications Display Maintenance Simple installation Simple upgrades Security Dimensions Electrical connections Standards compliance Default measurements Measurements kW and kWh measurements Measurements via Profibus Input ratings Additional specifications Selection and ordering data Catalog index

2 2 2 2 2 2 2 3 3 4 4 4 5 6 6 7 8

Siemens AG 1999 Siemens SR 10.2.6 1999

SR26096.eps

SIMEAS P

Features
Communications The SIMEAS P operating architecture conforms to the Profibus communications protocol, allowing you to access the meter using any third party software that conforms to Profibus. Telecontrol of the SIMEAS P is thus made available. The SIMEAS P provides a Profibus port at its rear panel. Profibus communications is achieved via an internal Profibus expansion communications card. This card allows communication using the Profibus standard at baud rates up to 12 Mbps. Connection to the Profibus network is achieved via a Profibus adapter (not included) and Profibus cables (not included). Profibus communications allows multiple master and slave devices to be connected on the same communications line. Up to 32 devices can be connected on a single Profibus communication line, or up to 126 devices, if repeaters are used. Display The SIMEAS Ps backlit LCD display shows four parameters at a time. Eight different displays are available enabling easy monitoring of important functions. Each display is configurable allowing the user to select one, two or four parameters to be shown. Any of the parameters available in the meter can be selected. The LCD has adjustable contrast, programmable backlighting, and automatic screen scrolling. The automatic screen scrolling function causes the front panel screens to advance automatically. You can specify the amount of time each successive screen is displayed, with a maximum time of 99 seconds. The backlight will automatically shut off after a specified time lapse in order to prolong its life. Maintenance The only regular maintenance required by the SIMEAS P is the replacement of the nonvolatile memory (NVRAM) battery. The battery has a rated life of 35 years under normal circumstances. No cleaning of the device is necessary. Simple installation The SIMEAS P requires only a single panel cutout to mount it on a panel door. It is DIN compatible, so you can reuse existing DIN cutouts in switchgear cabinet doors. It is easily secured by sliding brackets, tightened by thumbscrews. Simple upgrades The SIMEAS P firmware is flash-memory based so it can be upgraded by the factory, using the infrared port. Security The SIMEAS P is protected against unauthorized tampering through the front panel. Users must enter a password before the unit will allow changes to be made to its configuration.

Dimensions

Base unit front view

Base unit side view

Siemens SR 10.2.6 1999

Electrical connections
You can connect the SIMEAS Ps voltage inputs for Wye (star) systems up to 347 / 600 V AC without using voltage transformers (VTs). For higher voltage systems and Delta systems, VTs with 120 V AC secondaries may be used. Voltage and current inputs are available in either barrier strip or pluggable captured-wire connectors for systems up to 277 / 480 V AC.

Standards compliance
UL: CSA: International: Certified to UL 3111 No. 142-M1987 IEC 1010-1 Measuring inputs comply with Installation Category III Power supply inputs comply with Installation Category II Device operable under Pollution Degree II All inputs pass ANSI/IEEE C37.90-1989 surge withstand and fast transient tests Part 15 of FCC Rules for a Class A Digital Device approved

Surge withstand: FCC: CE:

Quality Assurance Certification: ISO 9002 certified by QMI

SHORTING BLOCK or TEST BLOCK

Barrier-type terminals (ring or spade connectors)

Thumbscrew

Chassis ground AWG 14 (2.5 mm) Captured-wire terminals

Fuses 2 Amp

Power supply connections, phase voltage and current connections, and fuse, CT and PT details depend on the configuration of the power system.

Phase voltage and power supply connections: AWG 12 to AWG 14 (2.5 mm to 4.0 mm)

Back panel diagram of SIMEAS P


Siemens SR 10.2.6 1999

SIMEAS P

Default measurements

Measurements (50.0 Hz or 60.0 Hz, 25 C/77 F)

Basic Voltage (L-L/L-N) per phase and average Current per phase and average Power factor (signed) per phase and total Line frequency

Parameter

Accuracy (% rdg + % range)1)

Voltage (L-N) in Wye, Vab, Vbc in Delta Voltage (L-L) in Wye, Vca in Delta

0.25 % + 0.05 % 0.75 % + 0.1% 0.01 % 0.25 % + 0.05 % 0.5 % + 0.1% 1.5 % reading 1.0 % reading 1.5 % reading 1.5 % reading 1.0 % full scale 5.0 % full scale

Power kW per phase and total kVA per phase and total kvar per phase and total Energy
kWh (absolute, net, imported

Frequency Current kVA kvar (>5%) kVAh kVarh Power factor Total harmonic distortion (THD) K factor

and exported)
kVAh (absolute) kvarh (absolute, net, imported

and exported) Demand


Total kW demand (sliding window,

thermal and predicted


Total kvar demand (thermal) Total kVA demand (thermal)

Percent unbalanced
Voltage Current

1) Percent-range is defined as a percentage of nominal full scale voltage and current (e.g. 120 V AC / 10 A for a 7300 ION -120). 2) Resolutions given are from the front panel display. Higher resolution can be obtained via communications.

Total harmonic distortion


Voltage per phase Current per phase

kW and kWh measurements


Accuracy3)

Minimums and maximums


Average voltage (L-L/L-N) Sliding window total kW demand Power factor total Frequency Total kW sliding window demand Total kVA sliding window demand Total power factor Line frequency Average current Thermal total kW demand (max. only) Thermal total kvar demand (max. only) Thermal total kVA demand (max. only)

Rated current (Ir) and power factor (PF)

PF between 0.8 and 1.0 2 % Ir 100 % PF between 0.8 and 1.0 1 % Ir 2 % PF between 0.8 and 0.5 lead or lag 20 % Ir 100 % PF between 0.8 and 0.5 lead or lag 2% Ir 20 %

1.0 % reading 1.5 % reading 1.0 % reading 1.5 % reading

3) All accuracy specifications in this table comply with IEC 1036 Class 1 specification and ANSI C12.16 Class 10 at 25 C (77 F) 4) Resolutions given are from the front panel display. Higher resolution can be obtained via communications.

Siemens SR 10.2.6 1999

Measurements available via Profibus DP protocol

Display resolution (% range)2) 0.1 % 0.1 % 0.1 0.1 % 0.1 % 0.1 % 0.1 % of reading 0.1 % of reading 0.01 0.1 % 0.1 %

Range

Module

0 to 1x106 0 to 2x106 40 Hz to 70 Hz 0 to 1x106 0 to 3.3x10


7

Volts line to neutral A Volts line to neutral B Volts line to neutral C Volts line to neutral average VL-N avg. MAX VL-N avg. MIN Module

l
1

Module
Power factor A

0 to 3.3x107 0 to 1038 0 to 1038 -0.01 to -100.00, 100.00 to 0.01 0.01 to 100.00 0 to 1x106

Volts line to line AB Volts line to line BC Volts line to line CA Volts line to line average VL-L avg. MAX VL-L avg. MIN Module Current A Current B Current C Current average Current average MAX Current average MIN Module

l
2

Power factor B Power factor C Power factor total Power factor total MAX Power factor total MIN Module Volts unbalanced Current unbalanced Line frequency Line frequency MAX Line frequency MIN Not used Module kWh total kvarh total kVAh Not used Not used Not used Module kWh Import kWh Export kWh Net kvarh Import kvarh Export kvarh Net Module

l
7

l
8

l
3

l
9

kW A kW B (kWb) kW C (kWc) kW Total (kW total) kW Total thermal demand kW Total thermal demand MAX Module
Display resolution4) kW (% range) kWh (% reading) 0.1 % 0.1 % 0.1 % 0.1 % 0.1 % 0.1 % 0.1 % 0.1 % Range kW 0 to 3.3 x 10
7

l
4

l
10

kWh 0 to 1038 0 to 1038 0 to 1038 0 to 1038

kvar A kvar B kvar C kvar Total kvar Total thermal demand kvar Total thermal demand MAX Module

l
5

0 to 3.3 x 107 0 to 3.3 x 107 0 to 3.3 x 107

kVA A kVA B kVA C kVA Total kVA Total thermal demand kVA Total thermal demand MAX

l
6

kW Sliding demand kW Predicted demand kW Sliding demand MAX kW Sliding demand MIN Not used Not used Module

l
11

Va Total harmonic distortion Vb Total harmonic distortion Vc Total harmonic distortion Ia Total harmonic distortion Ib Total harmonic distortion Ic Total harmonic distortion

l
12

Siemens SR 10.2.6 1999

SIMEAS P

Input ratings

Input Voltage inputs

Options
120 option: 277 option: 347 option: CWC option:

Specifications 120 V AC nominal input, 25 % overrange Barrier strip connector rated to 600 V line to line 277 V AC nominal input, 25 % overrange Barrier strip connector rated to 600 V line to line 347 V AC nominal input, 25 % overrange Barrier strip connector rated to 600 V line to line (available with 120 and 277 options only) Captured-wire connectors rated to 500 V line to line Overload withstand for all options: 1500V AC continuous, 2500 V AC for 1 sec non-recurring Input impedance for all options: 2 MW 5 A nominal/10 A full scale, 25 % overrange Overload withstand for all options: 15 A continuous, 300 A for 1 sec non-recurring Input impedance: 2 MW Worst case burden (10 A): 0.0625 VA 85-240 V AC (20-440 Hz) or 85-240 V DC ( 10%), 0.5 A worst case loading (20 W) 100 V AC 25 C 20-60 V DC ( 10%), 1A worst case loading (10 W) Power supply fuse current rating, type and rupturing speed: 2 A slow-blow

Current inputs

Power supply

Standard P24 option

Additional specifications

Operating temperature Storage temperature Humidity

0 C to +50 C (+32 F to +122 F) ambient air. -30 C to +70 C (-22 F to +158 F) 5 % to 95 % non-condensing

Siemens SR 10.2.6 1999

Selection and ordering data

Designation

Order No.

7KG7800-8A


Line frequency 50 Hz 60 Hz

A B 0 1 0 1 2 A B

Control power supply

20 to 60 V DC 85 to 240 VAC/DC

Voltage connection

120 V AC 277 V AC 347 V AC

Communications

No communications PROFIBUS-DP

For more information, please contact:

Siemens Power, Transmission & Distribution,LLC Distribution Automation Division PO 29503 Raleigh, North Carolina 27626 Ph 919/365-2245 Fx 919/365-2552

Siemens SR 10.2.6 1999

Catalog Index

Catalog Index of the Power Transmission and Distribution Group (Protection and Substation Control System Division)
Title Numerical Protective Relaying Numerical Protection Devices Operation and Evaluation Software for Numerical Protection Devices Relay Selection Guide SIPROTEC 7SJ600 Overcurrent, Motor and Overload Protection SIPROTEC 7SJ601 Overcurrent Protection 7SJ41 Definite-Time Overcurrent Protection Relay 7SJ511 Numerical Overcurrent-Time Protection (Version V3) 7SJ512 Numerical Overcurrent-Time Protection (Version V3) 7SJ512 Numerical Feeder Protection SIPROTEC 7SJ531 Numerical Line and Motor Protection with Control Function 7SJ551 Multi-Function Protection Relay SIPROTEC 4 7SJ61/62/63 6MD63 Multifunction Protection Ralay and Bay Controller SIPROTEC 7SA510 Distance Protection Relay (Version V3) SIPROTEC 7SA511 Distance Protection Relay (Version V3) 7SA513 Line Protection Relay (Version V3) 7SA518/519 Overhead Control-Line Protection Relay (Version V3) 3VU13 Miniature Circuit-Breaker 7SD502 Line Differential Protection with Two Pilot Wires 7SD503 Line Differential Protection with Three Pilot Wires 7SD511/512 Current Comparison Protection Relay (Version V3) for Overhead Lines and Cables 7UT512/513 Differential Protection Relay (Version V3) for Transformers, Generators and Motors SIPROTEC 7RW600 Numerical Voltage, Frequency and Overexcitation Relay 7SS5 Station Protection SIPROTEC 7SS52 Distributed Numerical Busbar and Circuit-Breaker Failure Protection Relay Auxiliary Current Transformers 4AM50, 4AM51, 4AM52 and Isolating Transformers 7XR95 Introduction to Earth-Fault Detection 7SN71 Transient Earth-Fault Relay 7XR96 Toroidal Current Transformer 7VC1637 Earth-Leakage Monitor 7SK52 Motor Protection Introduction to Generator Protection 7UM511 Generator Protection Relay (Version V3) 7UM512 Generator Protection Relay (Version V3) 7UM515 Generator Protection Relay (Version V3) 7UM516 Generator Protection Relay (Version V3) 7UW50 Tripping Matrix 7VE51 Synchronizing Unit 7VP151 Three-Phase Portable Test Set (Omicron CMC56) 7XV72 Test Switch 7SV50 Numerical Circuit-Breaker Failure Protection Relay 7SV512 Numerical Circuit-Breaker Failure Protection Relay 7VK512 Numerical Auto-Reclose/Check-Synchronism Relay 7SM70 Analog Output Unit 7SM71 Analog Output Unit 7SV7220 Power Supply Unit Communication for Protection Devices Centralized and Remote Control of Siemens Protection Relays (Overview) Operating and Analysis Software DIGSI V3 Analog Protective Relaying Static Analog Network Protection Relays Static Analog Machine Protection Relays Static Analog Ancillary Protection Equipment Energy Automation Substation SICAM RTU System PS20A-6EP8090 Power Supply Module DI32-6MD1021 Digital Input Functional Module AI32-6MD1031 Analog Input Functional Module AI16-6MD1032 Analog Input Functional Module CO32-6MD1022 Command Output Functional Module CR-6MD1023 Command Release Functional Module Power Quality Fault and Digital Recorder SIMEAS R Central Fault Data Unit DAKON OSCOP P The Program for Quality Recorders Power System Quality Analysis OSCILLOSTORE SIMEAS P Power Meter Active Filter and Power Conditioner for Distributed Networks SIPCON P/S Low Voltage Capacitors and Power Factor Correction Units SIPCON T Designation LSA 2.0.1 LSA 2.0.2 LSA 2.0.3 LSA 2.1.15 LSA 2.1.16 LSA 2.1.10 LSA 2.1.3 LSA 2.1.4 LSA 2.1.30 LSA 2.1.9 LSA 2.4.2 SIPROTEC 3.1 LSA 2.1.17 LSA 2.1.11 LSA 2.1.12 LSA 2.1.14 LSA 2.1.8 LSA 2.2.1 LSA 2.2.2 LSA 2.2.3 LSA 2.2.4 LSA 2.7.10 LSA 2.2.5 LSA 2.2.7 LSA 2.2.6 LSA 2.3.1 LSA 2.3.2 LSA 2.3.3 LSA 2.3.4 LSA 2.4.1 LSA 2.5.1 LSA 2.5.2 LSA 2.5.3 LSA 2.5.4 LSA 2.5.5 LSA 2.5.6 LSA 2.5.7 LSA 2.6.1 LSA 2.6.2 LSA 2.7.1 LSA 2.7.2 LSA 2.7.3 LSA 2.7.5 LSA 2.7.6 LSA 2.7.9 SIPROTEC 8.1 LSA 2.8.2 Order No. E50001-K5702-A011-A1-7600 E50001-K5702-A121-A1-7600 E50001-K5702-A031-A2-7600 E50001-K5712-A251-A2-7600 E50001-K5712-A261-A1-7600 E50001-K5712-A201-A2-7600 E50001-K5712-A131-A3-7600 E50001-K5712-A141-A3-7600 E50001-K5712-A411-A1-7600 E50001-K5712-A191-A4-7600 E50001-K5742-A121-A3-7600 E50001-K4403-A111-A1-7600 E50001-K5712-A271-A1-7600 E50001-K5712-A211-A2-7600 E50001-K5712-A221-A1-7600 E50001-K5712-A241-A2-7600 E50001-K5712-A181-A2-7600 E50001-K5722-A111-A2-7600 E50001-K5722-A121-A2-7600 E50001-K5722-A131-A2-7600 E50001-K5722-A141-A2-7600 E50001-K5772-A201-A1-7600 E50001-K5722-A151-A2-7600 E50001-K5722-A171-A1-7600 E50001-K5722-A161-A1-7600 E50001-K5732-A111-A2-7600 E50001-K5732-A121-A1-7600 E50001-K5732-A131-A1-7600 E50001-K5732-A141-A1-7600 E50001-K5742-A111-A1-7600 E50001-K5752-A111-A1-7600 E50001-K5752-A121-A2-7600 E50001-K5752-A131-A2-7600 E50001-K5752-A141-A2-7600 E50001-K5752-A151-A1-7600 E50001-K5752-A161-A1-7600 E50001-K5752-A171-A1-7600 E50001-K5762-A111-A2-7600 E50001-K5762-A121-A1-7600 E50001-K5772-A111-A1-7600 E50001-K5772-A121-A1-7600 E50001-K5772-A131-A1-7600 E50001-K5772-A151-A1-7600 E50001-K5772-A161-A1-7600 E50001-K5772-A191-A1-7600 E50001-K4408-A111-A1-7600 E50001-K5782-A121-A1-7600

R 1.1 R 1.2 R 1.3

E50001-K4501-A111-A1-7600 E50001-K4501-A121-A1-7600 E50001-K4501-A131-A1-7600

SICAM 2.1.1 SICAM 5.1.1 SICAM 5.2.1 SICAM 5.2.2 SICAM 5.2.3 SICAM 5.3.1 SICAM 5.3.2

E50001-K5602-A111-A1-7600 E50001-K5605-A111-A1-7600 E50001-K5605-A211-A1-7600 E50001-K5605-A221-A1-7600 E50001-K5605-A231-A1-7600 E50001-K5605-A311-A1-7600 E50001-K5605-A321-A1-7600

SR 10.1.1 SR 10.1.2 SR 10.1.3 SR 10.2 SR 10.2.6 SR 10.5 SR 10.6

E50001-K4011-A101-A1-7600 see Intranet E50001-K4013-A101-A1-7600 E50001-K4020-A101-A1-7600 E50001-K4026-A101-A1-7600 E50001-K4050-A201-A1-7600 E50001-K4050-A101-A1-7600

Siemens SR 10.2.6 1999

Conditions of Sale and Delivery

Conditions of Sale and Delivery


Subject to the General Conditions of Supply and Delivery for Products and Services of the Electrical and Electronic Industry and to any other conditions agreed upon with the recipients of catalogs. s The technical data, dimensions and weights are subject to change unless otherwise stated on the individual pages of this catalog. The illustrations are for reference only. We reserve the right to adjust the prices and shall charge the price applying on the date of delivery.

Export Regulations
In accordance with the present provisions of the German Export List and the US Commercial Control List, export licences are not required for the products listed in this catalog. An export licence may however be required due to countryspecific application and final destination of the products. Relevant are the export criteria stated in the delivery note and the invoice regarding a possible export and reexport licence. Subject to change without notice.

Trademarks
All product designations used are trademarks or product names of Siemens AG or of other suppliers.

Dimensions
All dimensions in this catalog are given in mm.

Responsible for Technical contents: Ralf Mhlensiepen Siemens AG, EV S PQ2, Nuremberg General editing: Claudia Khn-Sutiono Siemens AG, EV BK T, Erlangen
Order No.: E50001-K4026-A101-A1-7600 Printed in Germany KGK 0199 5.0 8 En 100622 6101/U779

Bereich Energiebertragung und -verteilung Geschftsgebiet Sekundrsysteme Postfach 4806 D-90026 Nrnberg http://www.ev.siemens.de

Siemens Aktiengesellschaft

Order-No.: E50001-K4026-A101-A1-7600